Btu measurement system

Page 1

VERSION 2014

Guangdong AKE Technology Co.,Ltd.

Add: 3F, #3 Building, District A, Hantian Technology Park, No. 17 Shenhai Road, Guicheng, Nanhai, Foshan, 528200, Guangdong, P.R.China Marketing Line: +86-757-88386250 Service Line: 400 678 1126 Http://www.ake.com.cn Fax: +86-757-88361166 Email: export@ake.com.cn


Guangdong AKE Technology Co.,Ltd. founded in 1997, is a high-tech enterprise with data acquisition and information processing as its core technology. The main products AKE has are Network Thermostat System, BTU Measurement System, Building Energy Management System, Parking Guidance System and Urban Parking Guidance System.

AKE C03P BTU meter is designed to measure individual energy consumption in the building where chilled water system is installed. Besides, it is also used to measure performance of energy saving system or the loss of efficiency which is directly tied to loss of revenue. Operation mode: Heating , Cooling, Heating&Cooling.

AKE has obtained 6 patents, and passed ISO9001: 2000 Quality Management System in 2005. By the end of 2010, AKE has made over 800 projects all over China and gets high appraisal from local and overseas customers. The culture AKE pursues is Innovation, Pragmaticism, Dedication and Development. Customer-oriented, AKE pursues maximum customer satisfaction by providing efficient service throughout the whole cooperation. We can say that AKE would make a promising and trust-worthy partner in your business. AKE BTU meter consists of the following components: Combination Heating/Cooling Systems

Calculator(Model C03P-06/C03P-11)

st

The 1 generation of AKE BTU Measurement System was developed.

Obtained the 1st national patent of BTU Measurement System in China.

AKE BTU Measurement System was installed and put into practice, which was also the 1st project in China

Obtained the“Innovation and Technology Fund”from Guangdong Province.

Solid state circuitry for accurate and reliable operation with automatic compensation for water density. Receive signal from flowmeter and a couple of temperature sensors, calculate and indicate flow, temperature and energy consumption;

Heating Systems Cooling Systems

Flowmeter

Solar Systems

Electromagnetic, turbine, vortex and ultrasonic flowmeter are compatible, but Electromagnetic flowmeter is strongly recommended to ensure accuracy and minimize maintenance;

Geothermal Systems

Temperature Sensor Pair

Efficiency Measuring/Verification

4-wire PT1000, fast response and high accuracy, longer wiring available for flexible installation without any effect on accuracy. AKE products were chosen as the key new product in Guangdong Province.

Heat Recovery System

Obtained Prize for Progress in Science and Technology of Foshan.

Power Supply: RVV3*1.5mm2 Communication Cable: RVS2*0.75mm2

C03P BTU Meter Flowmeter

Obtained the “Innovation and Technology Fund” from Guangdong again.

Passed ISO9001 Quality Management System.

Cable Connecting Flowmeter and C03P Calculator: RVVP2*0.5mm2 Cable Connecting Temperature Sensor and C03P Calculator: RVVP4*0.5mm2

10D Obtained the authentication of hi-tech enterprises of Guangdong province and named as "Outstanding Enterprise for Self-innovation in Architecture Technology."

Obtained the patent prize of Foshan and obtained the certification of hi-tech enterprise of Guangdong province again.

Temperature Sensor on Outlet

Flow Direction

5D

Named as The Most Influential Enterprise for Building Energy Conservation in China.

Temperature Sensor on Inlet

Partial products obtained CE certification; Chosen as the Chinese Industry Standard(GIS) drafting organization to compile Time-based BTU Measurement System standard.

Flow Direction


FEATURES

FEATURES

Complies with OIML R75 and EN 1434 standards; Shows historic data with bar chart on a daily/monthly/yearly basis; Multi-level password prevents data missing or illegal modification; Adopts optocoupler, good anti-interference performance;

Minimal flow is programmable to be ignored; Secure storage: automatically store data in case of power failure; Remote alarm and clock function, remotely calibrates clock periodically; Data output interface; easy to integrate into Auto Meter Reading system;

SPECIFICATIONS Model

C03P-06

High accuracy; No mechanical movement part, long lifetime and maintenance free; Excellent for high pressure application;

SPECIFICATIONS Model

C03P-11

Picture

Suitable for different kinds of conducting medium, such as pure water, waste water, slurry, paper pulp, etc and the testing result won’t be affected by temperature, pressure, density or conductivity, etc.

EMF-06 Series

EMF-11 Series

Picture

Flowmeter

EMF-06 Series

EMF-11 Series

Design

Flanged Connection

Threaded Connection

Operating Voltage

220V AC±10% ,50±1Hz

DC 24V

Sensor Size

DN25一DN1000

DN20一DN32

Accuracy

Class 2

Class 2

Power Supply

AC 220V ± 10%

DC 24V

Environment Class

Class A

Class A

Output

4一20mA

0一3KHz

Calculation Range

(0一999999.999999)MWh

(0一9999.999)MWh

Accuracy

± 0.5%

± 0.5%

Resolution

0.000001MWh

0.001MWh

Conductivity

≥5uS/cm

≥5uS/cm

Dimension

250×150×60(mm)

120×200×55(mm)

IP

IP65, IP67

IP65

Measurement Range

(0.0一99.9)℃

(2.0一80.0)℃ Pressure Rating

DN25一DN80: PN≤2.5Mpa DN100一DN150: PN≤1.6Mpa DN200一DN1000: PN≤1.0Mpa

1.6Mpa

Straight Pipe

10*pipe diameter up 5*pipe diameter down

10*pipe diameter up 5*pipe diameter down

Measurement Resolution

±0.1℃

±0.1℃

Matched temperature Sensor

4-wires PT1000

2-wires PT1000

Communication Interface

RS485

RS485

Communication Protocol

Modbus

Modbus

Housing

carbon steel, stainless steel

stainless steel, PPS

Communication Rate

9600bps

9600bps

Liner

FEP,Ne,PTFE

PPS

Max. Communication Distance

400m

400m

Electrode

316L,HB,HC,Ta,Ti,Tungsten Carbide

316L

Flow Rate Range

(0一9999.99)m /h

(0一9999.99)m /h

Flanges Type

----

The screw thread

Flow Rate Accuracy

±0.5%

±0.5%

Medium Temp

-40一105℃

Input Signal

Pulse or Current Mode

Pulse Mode

Ne: -40一80℃ PTEF,PTFE:-40一180℃

Ambient Temp

Sinal Range

Current (4一20mA), Pulse (0一200Hz)

Pulse (0一3000Hz)

-25一60℃

5一55℃

3

3


FEATURES Platinum RTD type ensures high accuracy, stability and long-term reliability;

Guangzhou International Finance Centre

Accuray:1 mK;

One of China’s tallest building,with 103 storeys, the 440.2m skyscraper has multi-function, used as office space, a luxury hotel and a top floor sightseeing area.

Wide output signal and high sensitivity: 1 level higher than other thermoelectric thermometer;

BELOW DN50

Installed AKE BTU Measurement System involving over 250 sets of BTU Meters.

Wide testing range with good and stable performance. Able to keep stability below 0.1℃ for a long time under circumstances of small vibration;

Guangzhou Poly International Plaza

4-wire mode, testing results won't be affected if the wire is extended. OVER DN50

Chinese Academy of Engineering

Flowmeter

Flowmeter

Flowmeter

PT1000 PT1000

PT1000 PT1000

PT1000 PT1000

C03P

C03P

AHU

Guangzhou Fortune Plaza

C03P

Shanghai Youyou International Plaza

AHU

AHU

Flowmeter

Flowmeter

Flowmeter

PT1000 PT1000

PT1000 PT1000

PT1000 PT1000

C03P

AHU

C03P

AHU

AHU

RS 485

C03P

RS 485

RS 485

Guangzhou the Lake Front Village

Flowmeter PT1000 PT1000

Master Controller

Building Control Center

C03P

Chilled Water System

Shenzhen Ocean investment Center Maoming People’s Hospital