NRC-100HL

Page 1





Meter Relay Specification / Model

NRP-60H

NRP-83H

NRC-100H

NRC-120H

NRP-60HL

NRP-83HL

NRC-100HL

NRC-120HL

60(W)×60(H)

-

-

-

83(W)×83(H)

-

-

-

100(W)×83(H)

-

-

-

120(W)×100(H)

-

-

-

Type

Square

Input

DC Current

Dimension (mm)

(Moving coil)

(*)

500μA

100μA,500μA,1mA,10mA - 5A

1mA 10 - 100mA DC Voltage

(Moving coil)

1V - 300V

Receiver

(Moving coil)

4 - 20mA, 1 - 5V(4kΩ), 1 - 5V(w / 1MΩ,7331)

AC Current

(average)

1 - 20mA 1 - 5A(CT incorporated),

(r.m.s., 1A or more)

Indication

1 - 300mA 10 - 30A(w/7311)

AC Voltage

(average)

Accuracy

Class 1.5

-

Class 2.5

-

-

-

Scale length Scale divisions

10 - 300V

46mm

67mm

20 - 37.5

-

-

-

30 - 50

-

Scale Pointer

Needle type, black

Scale plate color Cover color

88mm

White Black

7.5BG4 / 1.5

-


Output

Optical operation

Output

Hold (relay)

Pointer

Knife shape H(High) : Red, L(Low): Green

Setting range

0 - 100% of scale for H and L

Setting

HL(High / Low) or

minimum setting range (per scale length) Pick up accuracy (per scale length)

H(High)

5% or less 1.5% or less

1.0% or less

Deadband (per scale length)

0.5% or less

Temp. coefficient

0.3% or less

(pick up value at 23degree ±10degree)

Power regulation

0.3% or less

(pick up value at rated voltage ±10%)

Output contact Contact rate (load resistance)

1 transfer for H and L 250V, 2A a.c.

250V, 3A a.c.

220V, 2A d.c.

30V, 3A d.c.

-

100/110,200/220V AC

24V DC

Power on delay

Consumption

1.5VA or less

Operating temperature

0 - 50degree

Operating humidity Weight (1mA d.c. rated)

2.5VA or less

30 - 90%RH (no condensation) approx. 230g

approx. 530g

* The rated input to exceed the specified standard values is associated with an accessory.

approx. 550g

approx. 600g

●:Standard, ○:Option