PROPOSED THREE DOUBLE STOREY TOWNHOUSES AT 2 TARA AVENUE KEW VIC
SHEET NUMBER
SHEET NAME
A000 A001 A002 A100 A200 A202 A203 A204 A205 A300 A301 A302 A303 A304 A305 A306 A307 A308 A400 A401 A500 A501 A502 A600 A601 A602 A603 A700 A701 A702
COVER PAGE PERSPECTIVES PERSPECTIVES GENERAL NOTES SITE PLAN BASEMENT PLAN GROUND FLOOR PLAN FIRST FLOOR PLAN ROOF PLAN INDIVIDULE PERSPECTIVE-U1 INDIVIDULE PLAN-U1 INDIVIDULE PLAN-U1 INDIVIDULE PERSPECTIVE-U2 INDIVIDULE PLAN-U2 INDIVIDULE PLAN-U2 INDIVIDULE PERSPECTIVE-U3 INDIVIDULE PLAN-U3 INDIVIDULE PLAN-U3 ELEVATIONS ELEVATIONS WALL TYPES DETAILS DETAILS DOOR SCHEDULE WINDOW SCHEDULE-U1 WINDOW SCHEDULE-U2 WINDOW SCHEDULE-U3 TYPICAL INTERNAL ELEVATION TYPICAL INTERNAL ELEVATION TYPICAL INTERNAL ELEVATION
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 50 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
COVER PAGE 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A000
PROJECT NO.
20-009
REVISION.
1
SOUTH PERSPECTIVE Scale -
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
@ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
PERSPECTIVES 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR ENDORSEMENT
DRAWING NO.
A001
PROJECT NO.
20-009
REVISION.
1
NORTH PERSPECTIVE Scale -
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
@ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
PERSPECTIVES 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR ENDORSEMENT
DRAWING NO.
A002
PROJECT NO.
20-009
REVISION.
GENERAL NOTES
SPACING BETWEEN ALL BALUSTRADES MUST NOT PERMIT A SPHERE OF 125 MM TO PASS THROUGH IT.
PROTECTION OF OPENINGS
DO NOT SCALE DRAWINGS. ALL WORKMANSHIP TO BUILDING SURVEYORS SATISFACTION & TO COMPLY WITH CURRENT AUSTRALIAN STANDARDS AND THE BUILDING CODE OF AUSTRALIA.
OPENINGS IN EXISTING WALLS AND FLOORS, THROUGH WHICH THERE IS A RISK OF PERSONS FALLING TO A LOWER LEVEL, SHALL BE EITHER PROPERLY GUARDED OR BOARDED OVER AND THE BOARDING SECURED AGAINST UNAUTHORIZED OR ACCIDENTAL REMOVAL.
THESE DRAWINGS ARE TO BE READ IN CONJUNCTION WITH ATTCHED STRUCTURAL & CIVIL ENGINEERS COMPUTATIONS & DRAWINGS.
GLASS
THE CONTRACTOR IS TO VERIFY ALL DIMENSIONS, CONDITIONS & LEVELS ON SITE BEFORE COMMENCING WORK.
PRECAUTIONS SHALL BE TAKEN TO PREVENT GLASS FROM FALLING ONTO PERSONS IN OR OUTSIDE THE BUILDING.
STORMWATER DRAINAGE AS PER CITY ENGINEERS DIRECTIVE.
I) TAKE ALL NECESSARY PRECAUTIONS TO PROTECT THE PUBLIC & ARRANGE ANY PEDESTRIAN DIVERSIONS AS MAY BE REQUIRED BY COUNCIL.
ALL DIMENSIONS ARE TO BE CHECKED ON SITE & CONFIRMED AGAINST TITLE DIMENSIONS.
II)
ALL GLAZING TO COMPLY WITH AS 1288, INSTALLATION OF GLASS IN BUILDINGS.
ERECT ANY BARRIERS DEEMED NECESSARY BY COUNCIL.
SERVICES
ALL WORK IS TO BE CARRIED OUT IN ACCORDANCE WITH THE CURRENT AUSTRALIAN BUILDING CODE AND ALL RELEVANT AUSTRALIAN STANDARDS, AND LOCAL AUTHORITY BY-LAW.
THE CONTRACTOR IS RESPONSIBLE FOR THE DISCONNECTION OF ALL SERVICES TO THE PROPERTY. BUILDER TO VERIFY ALL SERVICES INCLUDING GAS LINES, WATER, SEWER, ELECTRICITY & ALL METRES & CONNECTIONS BEFORE COMMENCEMENT OF ANY WORKS. MAKE GOOD ALL EXISTING SERVICES AS REQUIRED ON COMPLETION.
USE OF/OR CHANGE OF ANY MATERIAL OTHER THAN THAT IS SPECIFIED IS TO BE APPROVED IN WRITING BY THE ARCHITECT. BUILDER NOT TO ENCROACH NEIGHBORING BOUNDARIES NOR UNDERMINE EXISTING NEIGHBORING BUILDING. BUILDER TO ENSURE THAT ALL NECCESSARY PRECAUTIONS & PROTECTION OF THE PUBLIC IS COMPLETED BEFORE COMMENCEMENT OF ANY WORKS. IF BUILDER IN DOUBT CONSULT APPROPRIATE AUTHORITIES.
ASBESTOS REMOVAL TO ASBESTOS DISPOSAL REGULATIONS.
BUILDER TO CONTAIN ALL WORKS WITHIN ENCLOSURE. THE SITE SHALL BE SECURED AT ALL TIMES AGAINST THE UNAUTHORIZED ENTRY OF PERSONS OR VEHICLES. PROVISION SHALL BE MADE FOR READY ACCESS TO THE SITE BY EMERGENCY SERVICES PERSONNEL, IN THE EVENT OF FIRE OR ACCIDENT. BUILDER TO PREPARE ALL PROTECTION TO EXISTING CONCRETE PAVING, INCLUDING GROUND SPREADING TIMBER PROTECTION. ANY NEW CRACKING TO PAVING SLABS WILL BE COMPLETELY REMOVED AND REPLACED BY BUILDER AT OWN EXPENSE.
REMOVAL OF ASBESTOS MATERIALS CONTAINING ASBESTOS FIBRE SHALL BE IN ACCORDANCE WITH THE NOHSC (WIRKSAFE VICTORIA), CODE OF PRACTICE FOR THE SAFE REMOVAL OF ASBESTOS. REMOVAL OF DEMOLISHED MATERIALS DEMOLISHED MATERIAL SHALL BE REMOVED PROGESSIVELY FROM THE SITE AND, AT ANY TIME, SHALL NOT BE ALLOWED TO ACCUMULATE TO THE EXTENT THAT IT PRESENTS A HAZARD TO THE PUBLIC OR TO SITE PERSONNEL.
DEMOLITION
NOTICES AND PERMITS
THE CONTRACTOR SHALL GIVE TWO (2) CLEAR WORKING DAYS NOTICE TO THE SUPERINTENDENTʼS REPRESENTATIVE PRIOR TO COMMENCEMENT OF THE WORKS.
THE CONTRACTOR SHALL COMPLY WITH ALL SUCH ORDINATES, REGULATIONS AND BY LAWS IN RELATION TO THE WORKS, AND SHALL GIVE ALL NOTICES AND OBTAIN ALL PERMITS AND PAY ALL FEES ASSOCIATED THERE-WITH PRIOR TO THE COMMENCEMENT OF THE WORKS.
GENERALLY REMOVE ALL BUILDINGS & OUT BUILDINGS AS INDICATED INCLUDING ALL SUB-SURFACE REDUNDENT MATERIALS & LEAVE SITE IN A CLEAN & LEVEL CONDITION.
THE STRUCTURE TO BE DEMOLISHED AND ALL ITS COMPONENTS SHALL BE MAINTAINED IN A STABLE AND SAFE CONDITION AT ALL STAGES OF THE DEMOLITION WORK. TEMPORARY BRACING, GUYS, SHORING, OR ANY COMBINATION OF THESE, SHALL BE ADDED FOR STABILITY WHEN NECESSARY. CONTROLS NEED TO BE IMPLEMENTED TO EFFECT THE REMOVAL OF THE MASONRY WALL WITHOUT AFFECTING THE STABILITY OF THE REMAINING WALL RETURNS.
ALL CONCRETE FOOTINGS SHALL BE PLACED ON A FOUNDATION HAVING THE REQUIRED ALLOWABLE BEARING PRESSURE, AND BE PREPARED, REINFORCED AND CONSTRUCTED STRICTLY IN ACCORDANCE WITH THE MANDATORY REQUIREMENTS OF THE BUILDING REGULATIONS. REQUIREMENTS OF THE RESIDENTIAL SLABS AND FOOTINGS CODE AS2870.1 MAY BE USED UNLESS OTHERWISE DESIGNED BY ENGINEER. TIMBER FRAMING
LOADING AGAINST WALLS
NOTE: TIMBER WALL & FLOOR CONSTRUCTION/FRAMING SHALL COMPLY WITH AS1684.2-2010
WALLS SHALL NOT BE LATERALLY LOADED BY ACCUMULATED RUBBLE OR DEBRIS, TO THE EXTENT THAT THEY ARE IN DANGER OF COLLAPSE.
90 x 45 MGP10 STUDS AT 450 CTRS. FOR ALL WALL HEIGHTS UP TO 2700 MM HIGH
DISCONNECTION OF SERVICES
90 x 45 MGP10 STUDS AT 450 CTRS FOR ALL WALL HEIGHTS UP TO 3000 MM HIGH
A) THE DEMOLISHER SHALL ARRANGE TO PROPERLY DISCONNECT ALL SERVICES TO RELEVANT LOCAL AUTHORITY STANDARDS.
2/90 x 35 MGP10 STUDS AT 450 CTRS FOR ALL WALL HEIGHTS UP TO 3500 MM HIGH
B) STORM WATER SHALL BE TERMINATED AT PIT SERVICING THE BLOCK. EXISTING PAVING WHICH REQUIRES NEW SERVICES INSTALLED TO BE SAW CUT & EXCAVATED TO REQUIRED LEVELS. ON COMPLETION BACKFILL & MAKE GOON AS REQUIRED.
2/90 x 45 MGP10 STUDS AT 450 CTRS FOR ALL WALL HEIGHTS UP TO 3800 MM HIGH 120 x 45 MGP10 STUDS AT 450 CTRS FOR ALL WALL HEIGHTS UP TO 3900 MM HIGH
PROTECTION & DIVERSION TAKE ALL NECESSARY PRECAUTIONS TO PROTECT THE PUBLIC & ARRANGE ANY PEDESTRIAN DIVERSIONS AS MAY BE REQUIRED BY COUNCIL. II. ERECT ANY BARRIERS DEEMED NECESSARY BY COUNCIL. EXISTING BOUNDARY FENCING AND SHRUBS TO BE REMOVED TO ALLOW FOR NEW FENCE. SITE PREPARATION ANY FILLING UNDER PAVING SLABS TO BE FCR, GRADE 2A MATERIAL OF 50mm. (MAX.) SIZE COMPACTED IN 200mm. THICK ( MAX) LAYERS TO GIVE 100% STANDARD COMPACTION. GRADE UNIFORMLY BETWEEN GIVEN LEVELS. ALL CROSSINGS TO LOCAL COUNCIL REQUIREMENTS. REFER RELEVANT DETAILS FROM COUNCIL. ALL FRC, RCP, EW & SEWER QUALITY PVC PIPES UNDER TRAFFICABLE PAVING TO HAVE 450mm. MIN. COVER. STORMWATER QUALITY PVC PIPES TO HAVE 600mm. MIN COVER. ALL PIPES IN GARDEN AREAS TO HAVE 300mm. COVER. PIPES TO BE 150 mm. PVC. FROM LEGAL POINT OF DISCHARGE TO THE BUILDING EDGE. ALL PIPES UNDER PAVING & BUILDING TO BE 100mm. UPVC. IN ALL OTHER INSTANCES USE 100 mm PVC (90mm Ø PIPE WOULD ALSO BE SUFFICIENT).
ALL STAIR CONSTRUCTION TO BE KDHW STRINGER, BULL NOSE TREADS & RISERS OR ALTERNATIVE PREFABRICATED STAIRLOK TYPE WITH 2 COAT POLYURETHANE FINISH WITH SINGLE STRIP NON SLIP TAPE PER TREAD OR ALTERNATIVE BULL NOSE TREADS & RISERS WITH CARPET FINISH TO MATCH CARPET SPECIFICATION.
FLOORING STRUCTURE TO COMPLY WITH AS1684. PLUMBER AND DRAINER SANITARY PLUMBER (ALL AREAS) PROVIDE WASH TUBS, PEDESTAL PAN, KITCHEN SINK, WASH BASIN, BATH AND FLOOR GRATE TO SHOWER AREAS ( AS PER PLAN). PROVIDE WASTE TRAPS AND CONNECT TO DRAINAGE IN ACCORDANCE WITH THE REQUIREMENTS OF THE SEWERAGE AUTHORITY CONCERNED. WATER SERVICE WHERE A RETICULATED WATER SUPPLY IS AVAILABLE ALL WORK SHALL BE CARRIED OUT BY A LICENSED WATER PLUMBER. ALL WATER SUPPLY INSTALLATIONS SHALL BE CARRIED OUT IN ACCORDANCE WITH AS 3500: NATIONAL PLUMBING AND DRAINAGE CODE. TERMITE PROTECTION THE PROPERTY IS SUBJECT TO TERMITE INFESTATION AND IS TO BE PROTECTED IN ACCORDANCE WITH AS 3660.1. SUB FLOOR AREA OF ALL TIMBER DECK AREAS ARE TO ACHIEVE A MINIMUM SUB FLOOR CLEARANCE OF 400mm ABOVE NATURAL GROUND LEVEL. WET AREAS ALL WET AREA AREAS ARE TO COMPLY WITH BCA F1.7 OR AS 3740 - 2010. WALL FINISHES SHALL BE IMPERVIOUS TO A HEIGHT OF 1800mm ABOVE FLOOR LEVEL TO ANY SHOWER ENCLOSURES AND 150mm ABOVE BATHS, BASINS, SINKS & TROUGHS IF WITHIN 75mm OF WALLS. ROOFING SPECIFICATION ROOF CLADDING TO BE INSTALLED TO COMPLY WITH BCA 3.5.1 AND THE FOLLOWING STANDARDS.
GUTTERING TO BE INSTALLED IN ACCORDANCE WITH BCA 3.5.3.1g TO FALL NOT LESS THAN 1:500 FOR EAVES GUTTERS UNLESS FIXED TO METAL FASCIAS FALL OF NOT LESS THAN 1:100 FOR BOX GUTTERS. DOWNPIPES TO BE SIZED TO COMPLY WITH BCA TABLE 3.5.2.1 AND TABLES 3.5.3.2a, b & c.
ALL ROOFING MATERIALS AND RAINWATER GOODS TO BE INSTALLED IN ACCORDANCE WITH THE PRINTED INSTRUCTIONS. NEW SKILLION FLAT ROOFS TO BE 0.60mm LYSAGHT KLIP-LOK HI-TEN COLORBOND ROOFING AT 2° PITCH. TO BE INSTALLED AS PER MANUF'S RECOMMENDATIONS. REFER TO STRUCT'L ENGRS DRWGS FOR DETAIL AND CONSTRUCTION OF ROOF FRAME. NEW HIP ROOFS, RIDGE CAPPING AND HIP CAPPING TO BE TERRACATTA OR ALERNATIVE CONCRETE WITH PAINT FINISH TO MATCH EXISTING. NEW FASCIA & GUTTER SYSTEM TO BE COLORBOND NOVALINE FASCIA & GUTTER SYSTEM WITH COLORBOND HI FRONT QUAD GUTTER. TO BE INSTALLED AS PER MANUF'S RECOMMENDATIONS. UNDERSIDE EAVES OVERHANG LINING LOCATED WITHIN 900mm FROM TITLE BOUNDARY TO BE CONSTRUCTED USING 6mm COMPRESSED CEMENT SHEET OR ALTERNATIVE NON COMBUSTABLE MATERIAL.
GLAZING
ALL ROOFING STRUCTURE INCLUDING SIZES & SUPPORT MEMBERS REFER TO STRUCTURAL ENGINEERS DRAWINGS & COMPUTATIONS.
STAIR RISERS MAX 190, MIN 115 STAIR TREADS MAX 335, MIN 240 BALUSTRADES TO HAVE MINIMUM HEIGHT OF 865MM ABOVE NOSING OF TREADS AND 1000MM ABOVE LANDINGS AND FLOORS. ALL RAILS AND BALLUSTRADES TO HAVE A MAXIMUM 125MM CLEARANCE FROM LANDINGS AND OR LINE CONNECTING TREAD NOSINGS.
PROVIDE MASTIC SEAL AROUND DOWNPIPE PENETRATIONS AND PROVIDE STAINLESS STEEL WIRE LEAF GUARDS TO ALL DOWNPIPES.
ANY FILLING UNDER PAVING SLABS TO BE FCR, GRADE 2A MATERIAL OF 50mm. (MAX.) SIZE COMPACTED IN 200mm. THICK ( MAX) LAYERS TO GIVE 100% STANDARD COMPACTION. GRADE UNIFORMLY BETWEEN GIVEN LEVELS. ALL CROSSINGS TO LOCAL COUNCIL REQUIREMENTS. REFER RELEVANT DETAILS FROM COUNCIL. ALL FRC, RCP, EW & SEWER QUALITY PVC PIPES UNDER TRAFFICABLE PAVING TO HAVE 450mm. MIN. COVER. STORMWATER QUALITY PVC PIPES TO HAVE 600mm. MIN COVER. ALL PIPES IN GARDEN AREAS TO HAVE 300mm. COVER. ALL PIPES TO BE 150 mm. PVC. ALL PIPES UNDER PAVING TO BE 100mm. UPVC.
AS 1288 GLASS IN BUILDINGS SELECTIONS AND INSTALLATIONS AS 1562 DESIGN AND INSTALLATION SHEET ROOF AND WALL CLADDING. PART 1 METAL AS 1684.2 NATIONAL TIMBER FRAMING CODE AS 1860 INSTALLATION OF PARTICLE BOARD FLOORING AS 2047 WINDOWS IN BUILDING SELECTIONS AND INSTALLATIONS AS 2049 ROOF TILES AS 2050 INSTALLATION OF ROOFING TILES AS 2870 RESIDENTIAL SLABS AND FOOTING CONSTRUCTION AS 2904 DAMP PROOF COURSES AND FLASHINGS AS 3600 CONCRETE STRUCTURES AS 3660.1 PROTECTION OF BUILDINGS AGAINST SUBTERRANEAN TERMITES PART 1 NEW BUILDINGS AS 3700 OR MASONARY STRUCTURES AS 4773.1 AND AS 4773.2 AS 3740 AND WATERPROOFING OF WET AREAS IN RESIDENTIAL BCA PART 3.8.1, BUILDINGS AS/NZS 4654.1, AS/NZS 4654.2 TERMINATION OF MEMBRANES AS 3786 SMOKE ALARMS AS 4100 STEEL STRUCTURES AS 4256 PLASTIC ROOF AND WALL CLADDING MATERIALS AS 4055 WIND LOADS FOR HOUSING
STORMWATER DRAIN SHALL BE 150mm. DIA. UPVC, I:100 GRADIENT CONNECTED TO LEGAL POINT OF DISCHARGE AS NOMINATED BY COUNCIL AUTHORITIES. PROVIDE INSPECTION OPENINGS @ 9000mm c/c. O DP DOWN PIPE WITHIN THE LEGAL BOUNDARY LINE. ALL DOWNPIPES TO BE CONFIRMED ON SITE & IN ACCORDANCE WITH SHIRES DIRECTIVE. ALL SEWER DRAINAGE REQUIRES CONNECTION TO A RETICULATED SEWERAGE SYSTEM, PACKAGE TREATMENT PLANT OR AN APPROVED SEPTIC SYSTEM, WORKS TO BE IN ACCORDANCE WITH LOCAL AUTHORITY REGULATIONS. LEVELS FLOOR LEVELS & ALL LEVELS TO AHD SEE SURVEYORS CADESTRAL DRAWINGS COORDINATE THE POSITIONS OF ALL TRENCHES FOR SERVICES & IN GROUND WORK WITH PLAN OF TREES TO BE RETAINED. REFER TO ENGINEERS DRAWINGS FOR DEPTHS OF ALL STORMWATER PITS HEIGHT & POSITION OF SEWER ORG TO BE BELOW LOWEST FLOOR WASTE TO LOCAL SEWERAGE AUTHORITY REGULATION ROOT BARRIERS REQUIRED TO TREE DRIPLINE ABUTING BUILDINGS. WOB NOTE CLASS 1A WALL ON BOUNDARY IS TO BE WATER PROOFED IN ACCORDANCE WITH 4.7.4 OF AS.3700 WATERPROOFING TO BASEMENT WALL
SELECTION OF MATERIALS FOR SHEET ROOFING, GUTTERING AND DOWNPIPES TO COMPLY WITH TABLES 3.5.1.1 & 2 TO PREVENT CORROSION FROM CONTACT OF DIFFERENT METALS.
SUPPLY AND INSTALL SAFETY MESH UNDER ALL ROOFING.
STAIR
EXHAUST FANS, RIDGE VENTS TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS.
SITE PREPARATION
FOR LARGE SPAN FLOOR JOISTS & CEILING JOISTS REFER TO STRUCTURAL DRAWINGS.
ALL GLAZING TO COMPLY WITH AS 1288-2006, INSTALLATION OF GLASS IN BUILDINGS & AS 2047-2014 WINDOWS IN BUILDING - SELECTION & INSTALLATION. SHOWER SCREENS AND WINDOWS WITHIN 2000mm. OF SHOWER OR BATH PERIMETERS TO BE GLAZED WITH GRADE A SAFETY GLASS. GLAZING IN DOORS SHALL BE GRADE 'A' SAFETY GLASS.
ALL EXTERNAL DOWNPIPES TO BE 100mm COLORBOND DOWNPIPES TO BE FIXED TO 2mm THICK COLORBOND STEEL DOWN PIPE STAND OFF BRACKET FIXED TO EXTERNAL WALL WITH 2No COATCH BOLTS. TO BE INSTALLED TO COUNCIL REGULATIONS & DISCHARGE INTO STORMWATER PIT.
NOTE: ALL RAIN WATER HEAD & SUMP/DP LOCATED TO HAVE NEW OVERFLOW POP INSTALLED TO AVOID OVERFOW OF STORMWATER.
AS 1562.1 DESIGN AND INSTALLATION OF METAL SHEET ROOFING.
CONCRETE FOOTINGS
STABILITY OF THE STRUCTURE
NOTE: NO GAPS GREATER THAN 125MM. REFER TO BALUSTRADE NOTE.
TIMBER FLOORING
PROTECTION & DIVERSION
CONTRACTORS ARE TO TAKE PARTICULAR CARE NOT TO UNDERMINE FOOTINGS OF ANY EXISTING WALLS.
HANDRAIL TO BE 1000MM HIGH.
BCA AND STANDARDS - GENERAL: ALL WORKS SHALL COMPLY WITH THE BCA/NCC 2019 VOLUMN 2AMENDMENT 1 AND NOT BE LIMITED TO THE FOLLOWING AUSTRALIAN STANDARDS:
ALL MECHANICAL AND OTHER SERVICE PENETRATIONS TO BE FULLY FLASHED IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
COLORBOND SOAKER FLASHING WITH, COMPRESSED SHEET LINING TO WALL FLASHING TO TUCK UNDER SHEET LINING FLASH & SEAL MAKE WATERTIGHT & VERMINPROOF MAKE GOOD ON COMPLETION. COLORBOND VALLEY FLASHING AND BARGE FLASHING AS REQUIRED AS PER MANUFACTURERS INSTALLATION AND DETAILS. MAKE GOOD, WATERPROOF AND VERMINE PROOF AS REQUIRED.
THE RETAINING WALLS TO THE BASEMENT WILL BE CONSTRUCTED OF REINFORCED BLOCKWORK PLACED ABOVE THE SLAB FOOTING. THE BLOCKWORK WALLS WILL FORM PART OF THE BUILDING'S SUBFLOOR CONSTRUCTION. THE WATERPROOFING DESIGN OF THE BASEMENT WILL BE IN ACCORDANCE WITH THE REQUIREMENTS OF BRITISH STANDARD BS8102:2022 - CODE OF PRACTICE FOR PROTECTION OF STRUCTURES AGAINST WATER FROM THE GROUND FOR A GRADE 3 DRY ENVIRONMENT. THE BASEMENT SLAB ON GROUND WILL BE INSTALLED ON A DAMP-PROOF MEMBRANE/VAPOUR BARRIER IN ACCORDANCE WITH AS 2870 RESIDENTIAL SLAB & FOOTINGS CLASSIFICATION. THE BLOCKWORK WALLS WILL BE PROVIDED WITH XYPEX ADMIX ADMIXTURE FOR THE CONCRETE INFILL FOR WATERPROOFING. BLOCKWORK WALLS WILL BE PROVIDED WITH A CONTINUOUS VOLTEX BENTONITE GEOTEXTILE LAYER AND GRIPSET 51 WATERPROOFING MEMBRANE. THE UNDERSLAB POLYTHENE MEMBRANE WILL FORM A CONTINUOUS WRAP OVER THE BLOCKWORK WALLS IN ACCORDANCE WITH AS 3700 - MASONRY STRUCTURES BEHIND THE GEOTEXTILE LAYER. THE WATERPROOFING MEMBRANES WILL BE APPLIED FROM A MINIMUM 150MM ABOVE THE NATURAL GROUND LEVEL DOWN THE EXTERIOR FACE OF THE BLOCKWORK WALL TO OVERLAP A MINIMUM 150MM WITH THE UNDERSLAB POLYTHENE MEMBRANE. A PLIABLE MEMBRANE WILL BE INSTALLED TO THE CAVITY SIDE OF INTERNAL BASEMENT WALLS IN ACCORDANCE WITH AS/NZS 4200.1 & AS/NZS 4200.2. A SPOON DRAIN SYSTEM WILL BE PRESENT AROUND THE PERIMETER OF THE BASEMENT LOCATED AT THE INTERIOR OF THE BLOCKWORK WALLS. THE WALL CAVITY WILL BE PROVIDED WITH APPROPRIATE VENTILATION TO PREVENT DAMPNESS. THE BASEMENT SPOON DRAIN WILL SIT LEVEL WITH THE BASEMENT FINISHED FLOOR LEVEL BEHIND A 150MM CONCRETE HOB. ALL BASEMENT SPOON DRAINS WILL FALL AT A MINIMUM GRADIENT OF 1:100 TO A SERIES OF FLOOR WASTES WHICH WILL CONNECT TO THE STORMWATER SYSTEM OF THE BUILDING.
ALL COLOURBOND CAPPING FLASHING TO ENCAPSULATE BUILDING PROJECTION SUPORTED ON WATERPROOF PLY AND TIMBER FRAMING WITH APROVED INSULATION MAKE WATER PROOF & VERMIN PROOF AS REQUIRED. ALL FLASHINGS AND CAPPINGS SHALL BE 1.0mm COLOURBOND FIXED WITH ZINCALUME COATED STEEL SCREWS & NEOPRENE WASHERS INTO APPROVED MASONRY PLUGS. SILICON SEAL EACH FIXING POINT. HOLES IN CAPPING TO BE SLIGHTLY OVERSIZED TO ALLOW FOR EXPANSION.
HANDRAIL TO BE PROVIDED ALONG ONE SIDE OF STAIRS, FIXED AT A HEIGHT OF 865MM ABOVE NOSINGS. STRINGERS TO BE 245 X 45 F17 MIN.
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 50 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
GENERAL NOTES 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A100
PROJECT NO.
20-009
REVISION.
FOOTPA
I
RTW
STORMWATER PIT
GRATED PIT
51.2
51.4
51.6
50.4
49.8
0
TELSTRA PITS TELSTRA PITS
48.2 RTW
HAB
51. 6
19.10 269°45'
TBM-RIVET IN FOOTPATH AHD R.L 46.71m
2
4
.0
49.4
49.
48
4
9. 2
4
49
:
:
IN V
9.
4
8. 6
48 .
16
47 .
.
04
86
8
4 48 .
5
8. 6
:4
IN V
5 0 .3 1
6
4 9.
4
84
7
9. 6
4
50 . 54 4 9 .9 8
4 9 .9 4
55
49 .
5
IN V :4 9 .7 7
5
IN V
DEVELOPMENT SUMMARY 957.3m² Total Site Area 492.8m²(51.5%) Total Site Coverage Total Permeable Area 249.3m²(26.0%) 99.1 m² Total Driveway Area 437.3m²(45.7%) Total Garden Area TERRACE1 Ground Floor Area 152.2m² First Floor Area 142.5m² Basement Area 181.8m² Total Floor Area 476.5m² Garden Area 214.5m²
9. 2
:4
TERRACE2 124.9m² Ground Floor Area 119.1m² First Floor Area 152.2m² Basement Area 396.2m² Total Floor Area 95.8m² Garden Area TERRACE3 127.2m² Ground Floor Area 116.9m² First Floor Area 147.6m² Basement Area 391.7m² Total Floor Area 112.2m² Garden Area
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
5 1 .1 7
9. 8
76
T.O.G.59.26
49.6
49
.0 8
20
IN V
4
0
0. 2
HAB
50.
8
47 .
49.6
48.
17 TELSTRA PIT 47 .
IN
9
9. 2
2m PALING FENCE
48.0
V: 4
45
5 1 .6 3
TELSTRA PIT IN V :5 0 .3 2
5 0 .8 1
51 . 52
5 1 .2 5 5 1 .0 5
50 . 63
51 . 32 5 1 .7 1
PROP OUTLET I NV : 5 51 0. . 03 5 95 1 .1 3
5 0 .8 8 I N V: 5 0 .7 1
PROPOSED 2.0M PALING FENCE
RTW
0
16
6. 8
47
.0 3
SIGN
46
.9 3
5
0. 0
49.8
48 .
6.
PROP OUTLET
4
48
SIGN
15
4
9
.7 6
4
92
5 0 .3 4
5
Ht-1m
14
6. 6
8. 4 3 8 7 . 43 48.6 63
79
Ht-3m
.
48
48 .
5 1 .1 6
Ht-3m
46
4
5 0 .3 1
SIGN
IN
60
4
7
8. 3
5 1 .7 0
1.5m WELD MESH
13
6
6. 98 48 .
.8 2
PROPOSED NEW CROSSOVER
11
V: 4
12
ELECTRICAL METER BOX
10
12
.4 6
99 RTW
09
46
47 .
49 .
AVENUE
46
4
RTW
359°54' 49.99
.7 5
DN
.5 6
9
8. 7
FW
.
FW
46
U2 MAIL BOX
02
RTW
FFL 48.820
48 .
5
46
TL-01
ENS
PROJECT
08
IN
U1 MAIL BOX
07
6.
.
49
10
FFL 50.388
FFL 46.936
26
03
CT-01
48 .
4
BED 1
WIR
.
21
DP
38
48 .
FFL 48.800
19
FW
0.0
PROPOSED NEW CROSSOVER
FFL 47.495
46
47
51 . 41
TARA
EXISTING CROSSOVER TO BE REMOVED
.
51 .0 51 8 . 05
EXISTING STREET TREE1 TO BE REMOVED& RELOCATED ON PROPERTY OWNER'S COST
ELECTRICAL METER BOX
48
50 . 32
5 0 .3 2 U3 MAIL BOX
0
50 . 30
0 51.
8. 6
5 1 .6 6
EXISTING CROSSOVER TO BE REMOVED
CT-01
FFL 50.420
UP
.9 8
51 . 40
ELECTRICAL METER BOX
BED 1
.
DN
ENTRY
TL-01
46
49
TL-01
7 8 9
P'TRY
ENTRY
50.2
73
UNIT 1
UP
70
.0 4
B KIT
DP
FW
TL-01
FW
4
5 1 .6 8
89°45' 19.20
6 1
46
50 .
5
50
B KIT 1
8. 1
FFL 48.950
WC
ENS
PROPOSED NEW CROSSOVER EXISTING STREET TREE4 TO BE REMOVED& RELOCATED ON PROPERTY OWNER'S COST
.3 6
24
5 0 .3 3
5 1 .4 6
5 1 .0 5
5 0 .2 7 50 . 39
CT-01
06
V: 4
48
TF-01
16 15 14 13 12 11 10 9 8 7 6 5 43
BED 1
RTW
48
.9 9
LIVING & DINING
10 11 12 13 14 15 16
2 51.
.
7
0. 1
.1 3
UP
TL-01
FFL 51.500
48
09
DP
KIT
DN
WC
.4 51
.1 5
50 .
UNIT 2
WC
FFL 51.520
75
49
FW
DP
TL-01
ENTRY
.
48
FFL 50.550 TF-01
18
FW DP
ENS
18
.8 3
50
B KIT
16 15 14 13 12 11 10 9 8 7 6 5 43
TL-01
48
.7 7
49
DN
DP
1
I
49
FFL 51.650 UP
46 .
50 50 .2 . 24
.1 9
TF-01 18
KIT
LIVING & DINING
4
.8 9
UNIT 3
05
FW
KIT
04
NV :
.3 9 DP
DP
LIVING & DINDING
75
DP
FFL 48.820
47 .
DP
FFL 50.420
61
FFL 51.520
PROPOSED 2.0M PALING FENCE
02 03
2
3645
PROPOSED 2.0M PALING FENCE
Ht-12m
6. 1
R. 5 5 .5 8 PROPOSED 2.0M PALING FENCE
01
4
180°01' 49.99
2m PALING FENCE
COD E
3
Dwellings Under UNIT 1 Construction
RTW RTW
NOTE A
6. 2
18 Stevenson Street 4
UNIT 3
OUSE
1.4m BRICK WALL
CARPORT
Ht-7m
SITE PLAN 2 Tara Avenue Kew VIC
17 18
No. of Bed: No. of Carspace:
4 2
Total POS Total SPOS
222.8m² 76.2m²
19
20
21
No. of Bed: No. of Carspace: Total POS Total SPOS
No. of Bed: No. of Carspace: Total POS Total SPOS
4 2 98.9m² 54.8m²
4 2 115.6m² 59.1m²
DRAWING STATUS
FOR CONSTRUCTION
22
23 24
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A200
PROJECT NO.
20-009
REVISION.
51 . 55 51 . 5 1 .4 1 IN V :5 1 . 31
NOTE A
A
O
B
1225
C
9535
D
3650
E
9985
F
3650
G
6700
H
5950
COD E 01
9310
02 03
04
N PARKDISC D450 @ KLAUS GARAGE TURNTABLE
WT-F1
I
PARKDISC D450 @ KLAUS GARAGE TURNTABLE
WT-F1
WT-F1 DP
DP
DP
05
3250
3250
N
DP
I
WT-F1
WT-F
06
FW
L'DRY TL-01
TL-01
WT-B
TL-01
BATH FW
DP
FW
WT-B
L'DRY TL-01
3915
THEATER TF-01
WT-D
WT-D
123 / 1000 RAMP UP
WT-D
3050
5285
CONC. FFL 45.810
WT-E
M
K CAR SPACE
DP WT-E
11 10 11 12 13 14 15 16
WT-B
10
UP
D.23 U1
WT-E
DP
WT-B
T W
3600
WT-B
D.16 U2
CELLAR
TF-01
THEATER
TF-01
D.22 U1
1 -F
DP
DP WT-F
12
L
WT-E
L
WT-E
WT-B
TL-01
TL-01 194 / 1000 RAMP UP
WT-F
3600
THEATER
BATH
D.17 U2
TL-01
09
WT-F1
UNIT 1
FFL 45.950 TF-01
3050
WT-E3
FFL 47.550
D.18 U2
BATH
UP
WT-F1
UP
1
123 / 1000 RAMP UP
DP D.19 U2
1 2 3 4 5 6 7 8 9
2
CELLAR TF-01
DP
D.21 U1
3
249 / 1000 RAMP UP
D.16 U3
TL-01
WT-E
TF-01 WT-B
D.17 U3
123 / 1000 RAMP UP
K
FFL 48.650 WT-E
5285
UP D.18 U3
D.19 U3
1
D.20 U1
CELLAR
D.14 U2
E2
16 15 14 13 12 11 10 9 8 7 6 5 4
2
DP
D.15 U2
DP
3
16 15 14 13 12 11 10 9 8 7 6 5 4
WT-E3
WT-E2
D.14 U3
T-
D.15 U3
DP
W
WT-E2
WT-E
UNIT 2
D.20 U2
J
D.19 U1
2
D.20 U3
D.18 U1
DP
08
E T-
UNIT 3
GYM TF-01
07
87 / 1000 RAMP UP
W
J
CONC.
WT-E
CONC.
WT-B
WT-F1
FFL 47.410
CAR SPACE
WT-E2
FFL 48.510
CAR SPACE
WT-E2
WT-D
3915
DP
14
M
WT-F1
13
15
16 17
O
A
9535
3650
B
9985
3650
C
D
6700
5950
E
F
18
9310
G
H
19
20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1225
PROJECT
BASEMENT PLAN 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A202
PROJECT NO.
20-009
REVISION.
NOTE A
O
A
B
1225
C
9535
D
3650
E
9985
F
3650
G
6700
H
5950
COD E 01
9310
02 03
04
N
TL-02
TL-02
FFL 50.420
FFL 48.820
UP
5285
W.06 U3
DP
D.05 U3
B KIT
1
18
DP
W.06 U2
FW
DN
WT-A
16 15 14 13 12 11 10 9 8 7 6 5 43
DP
TL-01
W.07 U3
K
WT-B
FFL 51.650 WT-B
WC
WT-B
D.05 U2
WT-B
UP
1
TF-01 FFL 48.950 D.08 U1
B KIT
DP W.05 U1
DN
WC
TL-01
WT-A
1
D.09 U1
FW
W.03 U2
WT-B
UNIT 1
UP
P'TRY
D.02 U1
7 8 9
DN
WT-A3
L
WT-A
W.02 U3
W.01 U3
D.02 U3
WT
-A2
WT-A2
ENTRY
D.03 U2 D.02 U2
D.01 U3
WT-A3
FFL 51.520
WT-B
TL-01
WT-A FFL 50.420
3050
UP
W.02 U2
FW
WT -A
2
TL-01
10
ENTRY
TL-01
D.03 U1 19
11 D.01 U1
FFL 48.800
FFL 47.495
K
FFL 46.936
FW
BED 1 CT-01
TL-01
ENS
D.01 U2
W.01 U2
WT-A2
FFL 51.500
WIR
WC
WT-A2
FW
WT-B
ENTRY
WT-B
DP
09
D.04 U1
D.07 U1
W.01 U1
WT-A
WT-B
D.03 U3
WT-A3
ENS
CT-01
ENS
W.08 U2
BED 1 WT-A
CT-01
WT-B
BED 1
WT-A
TL-01
WT-B
WT-A3
3600
W.08 U3
FW
J
W.02 U1
WT-B
10 11 12 13 14 15 16
FW
3915
LIVING & DINING
DP
B KIT
16 15 14 13 12 11 10 9 8 7 6 5 43
W.07 U2
W.03 U3
D.04 U2
UNIT 2
WT-A
TF-01
KIT WT-B
08
5285
D.04 U3
W.03 U1
FW
07
3600
FFL 50.550 TF-01
UNIT 3
W.04 U1
KIT
LIVING & DINING
I
WT-A
W.04 U2
06
L
W.08 U1
D.05 U1
D.06 U1
12 13
FFL 50.388
WT-A2
WT-A
FFL 48.820
W.06 U1
WT-A
W.07 U1
FW
WT-A
FW
3050
WT-A3
LIVING & DINDING
18
W.05 U2
FW
WT-A
DP
WT-A2
DP
W.04 U3
KIT
J
WT-A
WT-A2
W.05 U3
WT-A3
3915
DP
WT-A
DP
WT-B
WT-A
WT-A
WT-A
05
3250
TL-02 FFL 51.520
WT-B
I
1 A701
WT-A2
3250
1 A702
WT-B
N
WT-A2
M
14
M 1 A700
15
16 17
O
A
9535
3650
B
9985
3650
C
D
6700
5950
E
F
18
9310
G
H
19
20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1225
PROJECT
GROUND FLOOR PLAN 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A203
PROJECT NO.
20-009
REVISION.
NOTE A
O
A
B
1225
C
9535
D
3650
E
9985
F
3650
G
6700
H
5950
COD E 01
9310
02 03
04
N 05
3250
3250
N
RH+DP
WT-A2
14 13 12 11 10 9 8 7 6
5
D.06 U2
WT-B
FW
WIR
BED 2
D.07 U2
CT-01
WT-A
W.10 U2
WT-A2
3915 WT-A2
TF-01 FFL 52.500
WIR
09
VOID
10 11
W.10 U1
DN
WT-B
WT-A2
WT-B
RETREAT
J
W.11 U1
WT-B
UNIT 1
10 11 12 13 14 15 16 17 18 19
D.12 U1
W.09 U2
WT-A2
DP
D.13 U1
WT-B
5 6 7 8 9
TL-01
D.08 U2
DP
1.1M BLASTRADE WALL
ENS
D.07 U3
2°
WIR
D.15 U1
08
5285
FW
DP
TL-01
W.11 U3
WT-A
TF-01 FFL 53.900
WT-B
WT-B
WT-A3
WIR
4
W.12 U2
K
WT-B
D.10 U1
D.11 U1
DP
BED 4 CT-01
WT-A3
12
L
W.17 U1
W.11 U2
WT-A3
3050
WT-A2
RETREAT
ENS
WT-A3 W.10 U3
1.1M BLASTRADE WALL
TL-01
WT-A
W.09 U3
WT-B
ENS
D.09 U2
DP
WT-A
WT-A
WT-A3
3600
CT-01
D.08 U3
WT-A
BED 2
D.12 U2
FW
WT-A3
TL-01
DN
17
15
WT-B
ENS
18
16
RH+DP DP
WT-B
K
W.17 U2
W.12 U1
CT-01
WT-B
D.16 U1
WT-B
BED 2
DP
DP
3
WT-B
D.06 U3
FW DP
L
5
WT-B
D.17 U1
D.14 U1
3600
14 13 12 11 10 9 8 7 6
WT-B
D.10 U2
ENS
CT-01
07
W.16 U1
WTA3
WT-A3
W.09 U1
3050
15
4
W.12 U3
CT-01
BED 3
W.15 U1
TL-01
WT-A2
16
2°
RETREAT TF-01 FFL 55.000
3
2°
W.13 U1
FW
WT-A2
1.1M BLASTRADE WALL
17
UNIT 2
DP
WT-B
BED 3
D.11 U2
CT-01
W.14 U1
1.1M BLASTRADE WALL
WT-B
W.13 U2
WT-B
DN
D.09 U3
TL-01
WT-B
D.12 U3
BED 4
W.16 U2
WT-A3
18
WT-B
5285
2°
2°
DP
D.13 U2
WT-B
D.10 U3
DP W.17 U3
FW
I
WT-A2
WT-A
RH+DP
WT-A
UNIT 3
CT-01
WT-A
WT-A
WIR
ENS TL-01
BED 3
D.11 U3
CT-01
WT-B
RH+DP W.13 U3
WT-A3
BED 4
W.16 U3
TL-01
ENS
D.13 U3
WT-B
J
FW
WT-B
WT-A3
3915
RH+DP
TL-01
WT-A FW
WT-A3
FW
ENS
W.15 U2
RH+DP
WT-B
WT-A
W.14 U2
WT-A3
WT-A3
WT-B
I
W.14 U3
WT-A3
W.15 U3
06
M
13
14
M
15
16 17
O
A
9535
3650
B
9985
3650
C
D
6700
5950
E
F
18
9310
G
H
19
20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1225
PROJECT
FIRST FLOOR PLAN 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A204
PROJECT NO.
20-009
REVISION.
NOTE A
O
A
B
1225
C
9535
D
3650
E
9985
F
3650
G
6700
5950
H
COD E 01
9310
02 03
04
N 05
3250
3250
N
I
W.20 U3
W.20 U2
2° FALL
2° FALL W.21 U1
2° FALL
2°
UNIT 3
2°
5285
RH+DP
DP
RH+DP
DP 2°
DP
W.20 U1
09
UNIT 2
2° FALL W.19 U3
J
UNIT 1
2° FALL
W.19 U2
5285
RH+DP
08
2°
2°
J
07
3915
3915
I
06
10
2° FALL
11 DP
3600
2° FALL
W.19 U1
DP
RH+DP
RH+DP
2° FALL
W.18 U3
K DP
3600
K
RH+DP
W.18 U2
12
2° FALL W.18 U1
L
L 3050
3050
DN
M
13
14
M
15
16 17
O
A
9535
3650
B
9985
3650
C
D
6700
5950
E
F
18
9310
G
H
19
20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1225
PROJECT
ROOF PLAN 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A205
PROJECT NO.
20-009
REVISION.
1
2
U1 SOUTHEAST PERSPECTIVE Scale -
U1 NORTH PERSPECTIVE Scale -
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
@ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
INDIVIDULE PERSPECTIVE-U1 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A300
PROJECT NO.
20-009
REVISION.
E
H
F
G
6700 9010
260 925 275
W.04
9310 1185 275
CAR SPACE
KIT, LIVING & DINING 110 1050 110 1305 110 1010 110 2005
2080 B KIT
375 375
2085
110 960 110
BATH
6050
150
9310
275
CAR SPACE 5800
150
9310
14700
CAR SPACE
G
WT-B
BED 1 CT-01
TL-01
ENS
D.00 U#
DOOR TAG
WT-00
WALL TYPE
XX-00
FLOOR MATERIAL
FFL:00.00
FLOOR LEVEL ANNO
WT-A
3250 685 W.03 W.02 D.01
275 685
1185 1700 2180 575 1950
WT-A2 DN
800
W.07 U1
275
WT-A
1985
W.06 U1
1140
275 685
275
FFL 48.820
1800
WT-A 1800
WT-A2
WT-A
L
W.08 U1
D.05 U1
D.06 U1
M
39
H
1185 275
2080
110
3585
110
2455
1185 275
WIR 2080
110
BED1 3585
110
L'DRY 2075
1185
WIR 1660
BED 1 3300
ENS 345 1250
1015
E
2
110
2580
760
8710
110
ENTRY 2960
460
9010
1075
RETREAT 1770
W.07
1350
9010
W.08
F
G
H
U1 GROUND FLOOR PLAN
Scale - 1 : 100
WINDOW TAG
5680
FW
K
W.01
D.07 U1
J
M
U1 BASEMENT PLAN
W.00 U#
FFL 48.800
D.04 U1
W.01 U1
Scale - 1 : 100
DOWNPIPE DOWNPIPE+SUMP DOWNPIPE+RAIN HEAD FLOOR WASTE
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
As indicated @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
F
D.01 U1
2250
19
W.06
E
ENTRY
TL-01
I
1085 500
WT-B
DN
TL-01
D.03 U1
10 11 12 13 14 15 16
WIR
WC
D.02 U1
7 8 9
WT-B
W.02 U1
WT-B
WC 12630
LIFT
P'TRY
BED1
WIR 4445
4445
1
D.09 U1
STAIR
P'TRY B KIT 110 1090 110 1075 110
110 1000 110
1720
W.05 1880
5285
W.05 U1
39 7260
B KIT
UNIT 1
UP
110 980 110
D.08 U1
1655
WT-A
FFL 48.950
L'DRY
LIVING & DINING
4975
KIT 5690
TF-01
DP
110
5800
THEATER
5355
3600 150
275
LIVING & DINING
LIVING & DINING
275 685
275 685
685 3915
2785
M
3250
3250
3250
3250
3250
3250
3250
3250
3600
WT-F1
110
WT-A
KIT
L
3050 WT-F
600150
DP
600150
DP
8710
W.03 U1
1985
WT-E
K
L
WT-E2
TF-01
760
2580 ENTRY
WT-A
DP
WT-F1
THEATER
WT-E 590325
590325
150 150 820
D.23 U1
8095
THEATER
5735
5945 590325
K
10 11 12 13 14 15 16
3600
THEATER 6400
820 4050
UP
CONC. FFL 45.810
3050
J
1
CAR SPACE
M
J
F T-
W
450
W.04 U1
460
DP
I
3600
FW
WC
FFL 48.820
3050
STAIR
TL-01
D.22 U1
I
4480
LIFT
BATH
1 2 3 4 5 6 7 8 9
UP
LIFT
9010
N
WT-F1
UNIT 1
FFL 45.950 TF-01
CAR SPACE
D.21 U1
TL-01
WT-B
L
D.18
WT-E2 D.20 U1
CELLAR
STAIR
460
N
9670
WT-E
WT-E
GYM
275
DP
2015 160 1085 110 1095 110
110 115
110
150 820
150 820 GYM 3380
3295 110 2260
CELLAR 3870
110 1960
BATH
5285
DP
E2
15850
D.18 U1 D.19 U1
T-
K
87 / 1000 RAMP UP
GYM TF-01
410
3250
3250
325 820
325
DP
W
J
WT-F1
WT-F
3915
GYM 3295
WT-F1
14130
I
3250
4070
3250
N 3250
N
11030
110
LIFT
150
ENS
STAIR
235 5800
9010
3985
CELLAR
275
3325
275
8315 1575
9310
7400
WT-A2
275
110 960 110 1100 110
5950
1040
WT-A2
2085
1185
WT-A2
3750
375
9310
WT-A2
375
5950
WT-B
6700
H
1985
G
F
WT-B2
E
PROJECT
INDIVIDULE PLAN-U1 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A301
PROJECT NO.
20-009
REVISION.
E
F
G
6700 1185
1040
5950
2400
3645
W.14 3935
110
1185 275 900 110
BED3 1815
ENS 110 1000110 1380 110
2080
110
1980
1135
W.13 3765
110 1580
F
G
110
1890
H
9010 9310 6700
110
6840
WIR
1145
450 845
BED2 1805
110
E
9310
2400
1185 275
1185 275
H
760
8710
2650
5950
1185
8710
10635
9310 1130
9010
ENS
2080
1185 275
ENS 2080
1185
ENS 1600
500
110
2540
110
WIR 2540
110 110 590 110
WIR 3280
1700
W.16
E
110
W.17
BED4 2535
1890 VOID
1850
760
8710
160 300
8710
300 300
9010
G
D.00 U#
DOOR TAG
WT-00
WALL TYPE
XX-00
FLOOR MATERIAL
FFL:00.00
FLOOR LEVEL ANNO
3250 3530 6000
12280
5285
W.11 W.10
K
RH+DP 3600
DP
3200
2175
UNIT 1
K
2° FALL
M
1800
1800
1800
3050
635
M
L
1085
L
635
L
W.18 U1
M 1185
11765
E
H
2
F
9010
G
H
U1 ROOF PLAN
Scale - 1 : 100
WINDOW TAG
DP
W.20 U1
W.19 U1
W.09
F
685
3915
J
VOID 575 2250
K
U1 FIRST FLOOR PLAN
W.00 U#
3250 685
3250
3250 685 W.12
BED2 1700 500 645
J
Scale - 1 : 100
DOWNPIPE DOWNPIPE+SUMP DOWNPIPE+RAIN HEAD FLOOR WASTE
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
As indicated @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
3490 RETREAT 6190
I
2°
2° FALL
M 1185 275
2° FALL W.21 U1
500
110 160 2435
W.09 U1
WT-A3
I
1185
3250
3250 275 685 700110 RETREAT 4630
160 2435
WTA3
160
WT-A3
2435
160
W.17 U1 W.16 U1
I
N
RH+DP
1680
WT-B
CT-01
N
J
W.09
BED 4
N
BED4 1520
DP
BED4 3440
110
WIR
D.11 U1
BED2 3305
ENS 4005 110 RETREAT 4630 STAIR
2760
WT-B
D.10 U1
BED4 3440
WT-B D.12 U1
275 685 2365 110
10 11 12 13 14 15 16 17 18 19
DP
110
W.10 U1
DN
TL-01
VOID
110 1090 110
TF-01 FFL 52.500
WIR
2380
RETREAT
2435
450 160 2435
UNIT 1
5 6 7 8 9
W.11 U1
WT-B
4110
LIFT STAIR
ENS
WT-B
1.1M BLASTRADE WALL
FW FW
D.13 U1
WT-A2
WT-A
TL-01
D.15 U1
110 DP
1530
WT-B
WIR
WT-A2
CT-01
1.1M BLASTRADE WALL
WT-B
ENS
WIR
110 1090 110 1075 110
ENS 1575 110 ENS 1620
5840
D.14 U1
W.12 U1
WT-A2
110 2380 9015
110
5285
ENS
BED 2
DP
3600 3050
2435
450
L
D.16 U1
WT-B
TL-01
WT-A2
CT-01
D.17 U1
K
WT-B
BED3
BED 3
W.15 U1
W.13 U1
FW
WT-B
WT-A
W.14 U1
275 685
3250
3250 285 675
3250 285 675
BED3 4005
W.15 3405
1950
J
WT-A2
WT-A
3915
1315
685
I
3250
3250
N
PROJECT
INDIVIDULE PLAN-U1 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A302
PROJECT NO.
20-009
REVISION.
1
2
U2 SOUTH PERSPECTIVE Scale -
U2 NORTH PERSPECTIVE Scale -
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
@ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
INDIVIDULE PERSPECTIVE-U2 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A303
PROJECT NO.
20-009
REVISION.
C
D
E
9985
C
3650
200
375
CAR SPACE 110 1175 110 1435
375
3650
7400
1245 215 1225
NOTE A
3650
1245 215 1175
13435 6580
E
9985
13785
200
D
W.05 1085
3005
2950
1750
1100
735 275
1010 110
W.04 2775
275
375
B KIT
LIFT
3250 685
275 685
275 685
KIT B KIT 700
6125
W.01 U2
FLOOR MATERIAL
FFL:00.00
FLOOR LEVEL ANNO
04
DOWNPIPE
05
DOWNPIPE+SUMP
06
07
J
08
W.03
09
10 11
3615
L
12
FFL 50.388 3000
UP
W.02 U2
XX-00
3000
WT-A2
WT -A2
3000
WT-A FFL 50.420
D.01 U2
460
WT-A3
WALL TYPE
02 03
FLOOR WASTE
6040
1580
5350
ENTRY D.02 U2
WT-00
K
2535 WT-B D.03 U2
DOOR TAG
110
CT-01
1940
WT-A3
275
WT-B
BED 1
ENTRY
ENS
W.08 U2
W.03 U2
WT-B
1810
WC
TL-01
WT-B
4135
BED1
DP WT-A
TL-01
450390
B KIT
WT-A
STAIR
STAIR 110 1070 110
1
DN
FW
ENS
UP
16 15 14 13 12 11 10 9 8 7 6 5 43
W.07 U2
WC
W.07 110 1300 110 1070 110 W.08 2725 60 275
D.05 U2
DP
WT-B
D.04 U2
LIVING & DINING 110 3800
UNIT 2
3000
L
WT-B
110 1275 110
WT-A3
LIVING & DINING
5350
LIVING & DINING 5350
7105 W.06
2000 2050 3600
450390
1150
800
1350
860
235
L
3840
3050
WT-E
WT-D
FFL 50.550 TF-01
D.00 U#
01
DOWNPIPE+RAIN HEAD
KIT
LIVING & DINING
W.06 U2
I
W.04 U2
LIFT 275
W.05 U2
DP
WT-A
275 685
275 685
DP
3915
685
WT-A
WINDOW TAG
13
DP
M
M 375 375 200
4605 THEATER 4605 THEATER
110 1380 110
1680
110 1240 375
BATH CELLAR L'DRY 110 1380 110 3030 375 9585
BATH
L'DRY
200 200
3650
M
M 1245 215
375
CAR SPACE 3250
375
D.14 3650
200 375
5315
1245 215 1380 110 1245
ENS 1125 665
110 1185 110 4425
1390
BED1 710 1850
W.01
W.02
1545
D
3895
2240
275
3895
1140
ENTRY 1600
275
3895
14 15
16
D.01
D
E
17
E
18
2
U2 BASEMENT PLAN Scale - 1 : 100
U2 GROUND FLOOR PLAN
19
Scale - 1 : 100 20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
As indicated @ A1
DRWN
YH
CHCK
Checker
TITLE
N
C
275
LIFT 110
C
1
3250
3250
3250
3250
3250
3250
3250 150 6340
CAR SPACE 5960 275 LIFT 2495 110 1615 110
110 1085 110 1305 275 WT-E
DP
K
3050
TL-01
K
3000
L'DRY
WT-D
3050
J
L'DRY 9125
WT-B
WT-B
L'DRY 1715
WT-B
TL-01
DP
1615
TL-01
BATH
J
3050
375
WT-B
D.16 U2
CELLAR
TF-01
THEATER
TF-01
110
D.17 U2
375
WT-E
WT-E3
FFL 47.550
D.18 U2
1715
UP D.19 U2
1
123 / 1000 RAMP UP
2
WT-E
STAIR
3
DP
BATH
THEATER 3435 110 1220 160 1115 275
5285
160 1115 275 4765
WT-A
18
DP
E2
3600
T-
375
FFL 50.420
I
D.14 U2
W
D.15 U2
WT-E 3050
I
DP
FW
3050
N
1235
UNIT 2
16 15 14 13 12 11 10 9 8 7 6 5 4
5960
DP
WT-E2
L
WT-E
WT-E
CONC.
375
WT-D
FFL 47.410
CAR SPACE
D.20 U2
K
150
DP
249 / 1000 RAMP UP
5960
CAR SPACE
J
N
TL-02 150
150
150 5960
3915
DP
3250
PARKDISC D450 @ KLAUS GARAGE TURNTABLE
WT-F1
I
3250
3250
3250
N 3250
N
W.00 U#
COD E
PROJECT
INDIVIDULE PLAN-U2 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A304
PROJECT NO.
20-009
REVISION.
D 9985 1210 295510
2410
780
160
1345 260
2435
160
4255
110 1470
2435
160
4255
110 1470 110
2435
160
4255
110 1470 110 980 110 1155 110 1180 215 1345
1245
5045
D.12 U2
WT-B
1.1M BLASTRADE WALL 3
14 13 12 11 10 9 8 7 6
5
D.06 U2
FW
3250 585
J
6040
3550
BED3 4770
2°
DOOR TAG
WT-00
WALL TYPE
XX-00
FLOOR MATERIAL
FFL:00.00
FLOOR LEVEL ANNO
WT-A3
2°
05
DOWNPIPE+SUMP
06
07
J
08
UNIT 2 W.19 U2
2° FALL
09
D.07 U2
L
W.11 U2
L
3000
M 2435
160
2435
160
2435 1190
600
4180
110 1185 110
3895
110
LIFT 4590
RETREAT 110 2240
215 1345
ENS 2425
275
BED2 4590
275
WIR 2290
1345
275
2290
1605
W.09
710
1840 W.10
C
BED2 1150 35
1565
11
L
12 13
M
M
14
215 1345
2430
1390
5080
DN 3050
WT-A2
WT-A3
K
W.18 U2
1045
W.09 U2 W.10 U2
2° FALL
840 60
215 WT-A
WT-A
275
WT-A
K
10
3000
CT-01
K
DP
RH+DP
3600
D.08 U2
WIR 4250
WIR
BED 2
04
DOWNPIPE
DP
TL-01
02 03
DP
WT-B DP
ENS
1245
100
3250
100 685
275585
3915
4
3630
WT-A3
15
460
450390 3000
3050
TF-01 FFL 53.900
16
RH+DP
W.12 U2
0
3050
RETREAT
D.00 U#
01
FLOOR WASTE
2° FALL
J
WINDOW TAG
DOWNPIPE+RAIN HEAD W.20 U2
RH+DP
D.09 U2
3230
DN
17
WT-B
D.10 U2
DP
18
I
W.00 U#
COD E
110
W.17 U2
CT-01
5285
WIR
WT-B
N
I
W.12
UNIT 2
DP
BED 3
D.11 U2
CT-01
I
110
BED 4
1605
W.13 U2
RETREAT 2100
TL-01 ENS
RH+DP
WT-A3
ENS
WT-A3
WT-B W.16 U2
WIR
D.13 U2
WT-A2
M
WT-A
WT-B
FW
TL-01
LIFT
3160
ENS
WT-B
100 160
100
RH+DP
ENS BED4 1580 110 STAIR 110 1430 110 1090 110
WT-A
BED2
4135
ENS 4430
100 160 110
W.15 1580
1210 345 970 1810 1025 790
L
W.14 U2
FW
3600
4740
1810
5285
K
W.16 3160
3915
J
W.17 110 1070 110 1090 110
I
3700
N
3250
3250
3250
3250
3250
3250
N
W.15 U2
6155
215 1345
N
WT-A3
1190
NOTE A
3650
3250
3535
585
4650
E
9985
3650
11270
1190
D
3000
1245
C
E
100
C
15 1245
1125 65
1990
5575
2290
1605
16
W.11
D
C
E
D
E
17 18
2
U2 FIRST FLOOR PLAN Scale - 1 : 100
U2 ROOF PLAN
19
Scale - 1 : 100 20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
As indicated @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
PROJECT
INDIVIDULE PLAN-U2 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A305
PROJECT NO.
20-009
REVISION.
U3 SOUTH PERSPECTIVE Scale -
2
3
U3 WEST PERSPECTIVE Scale -
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
U3 NORTH PERSPECTIVE Scale -
DATE
ISSUE
DATE
02/04/23
SCALE
@ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
PROJECT
INDIVIDULE PERSPECTIVE-U3 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A306
PROJECT NO.
20-009
REVISION.
3650 200
CAR SPACE
1225
585
1225
585215
W.05 12335
585215
LIVING, DINING & KIT 110 1185 110 1555
1225
1780
3650 7400
5525
1570
1000110
LIFT
9010
1225 150
6285 4195
STAIR
THEATER
CAR SPACE 110 1380 110 BATH 9185
1185 110 1430 1680
LIFT 110 1250
CELLAR
A
L'DRY
375
3250
190 375
D.14 3650
200
375
3650
200
200
3650
200
B
W.03 U3
BED 1 CT-01
WT-A
W.02 U3
WT-B
ENTRY
D.02 U3
D.01 U3
FFL 51.520
675
FLOOR MATERIAL
FFL:00.00
FLOOR LEVEL ANNO
04
DOWNPIPE
05
DOWNPIPE+SUMP
06
KIT
07
6060 B KIT
460
WT-A3
XX-00
J
08
10
K
6495
ENS
W.01 U3
WALL TYPE
09
2530
TL-01
WT-00
02 03
11
110
W.08 U3
WT-B
WT-A3
FW
WT-B
DOOR TAG
W.03
WT-A
TL-01
WC
D.00 U#
01
810
DN 16 15 14 13 12 11 10 9 8 7 6 5 43
W.07 U3
BED1
DP
WT-A
DP
D.05 U3
B KIT
1
1810
W.06 U3
LIVING & DINING 110 3810
UP
1590
D.04 U3
WT-B
WT-B
WINDOW TAG
DOWNPIPE+RAIN HEAD
WT-A3
5360
5625
LIVING & DINING
UNIT 3
W.00 U#
COD E
FLOOR WASTE
LIVING & DINDING
STAIR
110 1080 110
I
W.04 U3
KIT
WC ENS 4790
W.06 W.07 110 1300 110
FFL 50.420
WT -A2
L
FFL 51.500
12
3000
13
3000
3050
2500
3050
M
DP
275 675
675
275 675 6540
L
W.08 2675
2050
5285
660 860 1330 800 3600
L
3050
WT-D
123 / 1000 RAMP UP
WT-D
3050
1225 150
3250
3250
3250
3250
3250
675 4425
W.05 U3
WT-A2
1755
3050
3250
3250 19100
LIFT 235 CELLAR
1615 DP
WT-E 3050
DP
460
TL-01
DP
O
WT-A
D.03 U3
900 215
L'DRY
K
1390 60 1100
WT-B
K
110
WT-E
TL-01
1715
WT-F
BATH TL-01
1225 150
J
L'DRY 9125
D.16 U3
194 / 1000 RAMP UP
WT-B
THEATER
375
375
TF-01 WT-B
D.17 U3
DP
110 1075 110 1310 275
D.18 U3
M
M
M
205
14 15
1225
585
1540
1225
215 ENS 585 1335 665
110
4475 BED1 1390 10715 1835 W.01
O
C
2
U3 BASEMENT PLAN
110
2250
275
3850
20 1140
ENTRY 1590
275
3850
W.02
A
16
D.01
B
17
C
18
U3 GROUND FLOOR PLAN
Scale - 1 : 100
19
Scale - 1 : 100 20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
As indicated @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
J
375
FFL 48.650
123 / 1000 RAMP UP
1
WT-E
STAIR
TF-01 BATH
4765
THEATER STORAGE 3435 110 1220 160 1115 275
160 1115 275
14095
5285 3600
UP D.19 U3
DP
CELLAR
1225 325
WT-A
18
2
DP WT-E3
D.14 U3
3
16 15 14 13 12 11 10 9 8 7 6 5 4
FW
L
FFL 51.520
I
FFL 51.650
D.15 U3
275
B KIT
TF-01 WT-E2
2740
N
3915
UNIT 3
CAR SPACE
WT-D
CONC.
D.20 U3
K
DP
5960
WT-F1
CAR SPACE
CAR SPACE 5960
5960
J
CAR SPACE
275
N
I
150
DP
FFL 48.510
975
TL-02
CAR SPACE 6340
DP
3915
150
150
WT-F1
I
3250
PARKDISC D450 @ KLAUS GARAGE TURNTABLE
150
3250
3250
3250
N 3250
N
1100 W.04
LIFT 275
13035
9535
2465
1225 150
1225
C
ENTRY 3600
13385
B
3050
1225
A
275 675
9535
O
NOTE A
110 1275 110
1225
C
3250
B
1945
A
WT-A
O
PROJECT
INDIVIDULE PLAN-U3 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A307
PROJECT NO.
20-009
REVISION.
A
B
160
4045
W.14 295 110 1480 110
215
1545
160
ENS 4045
ENS BED3 110 1480 110 980 110 1155 110 1180 215
1545
780
W.13 3535
1545
1225
FW
DP
1985
160
1225
1985
160
1225
1985
160
1225
O
585
1400
600
4180
110 1185 110
STAIR 110
LIFT 4600
ENS 1390 10715
1855
W.09
W.10
A
BED2 1140 90
3695 RETREAT 110 2030 1500
275
WIR 2080
215
1545
215
1545
215
1545
100
3250
3915
100
I
2° FALL
DOOR TAG
WT-00
WALL TYPE
XX-00
FLOOR MATERIAL
FFL:00.00
FLOOR LEVEL ANNO
6050 5285
02 03
04
DOWNPIPE
05
DOWNPIPE+SUMP
06
FLOOR WASTE
J
07
J
08
DP
UNIT 3
2°
2° FALL W.19 U3
09
WIR 4250
K
K
RH+DP
DP
2° FALL
815
3600
9280
2430
D.00 U#
01
DOWNPIPE+RAIN HEAD W.20 U3
4770
J
L
3230
L
M 1225
585
3250
3250 585
I
2°
110
100 285 675 ENS WIR 600 815 215
W.11 U3
3000
WT-A2
460
WT-A3 W.10 U3
BED2 3630
D.07 U3
3230
WT-A
WT-A3
W.09 U3
WIR
4430
CT-01
D.08 U3
WT-A
BED 2
WT-A
ENS
TL-01
WT-A3
WT-B
ENS
WT-B
WT-B
M
1
160
3550
WT-B
D.06 U3
I
5070
4 5
W.12 U3
N
3050
16 14 13 12 11 10 9 8 7 6
WT-B
RETREAT TF-01 FFL 55.000
3
RH+DP
1770
N
W.12
WT-B
1.1M BLASTRADE WALL
15
3700
RH+DP RETREAT 2100
DN
D.09 U3
2630
D.12 U3
LIFT
18
17
5955
WINDOW TAG
COD E
110
DP
110 1440 110 1080 110
W.17 U3
3250
3250
WIR
UNIT 3
D.10 U3
1580
CT-01
CT-01
110
D.11 U3
WT-A3
BED 3
DP
275
450440
W.13 U3
3000
3050
ENS
BED 4
WT-A2 3000
TL-01
WT-B
WT-A3 BED4
FW D.13 U3
WT-B
WT-B
4085
4690
TL-01
WT-B
ENS
W.16 U3
3600 450440
L
RH+DP
3160
100 ENS
3250 100 160 W.15 1580 110 W.16 3160
WT-A FW
DP
K
W.14 U3
WT-A3
W.15 U3
STAIR
1810
5285
1035
J
W.17 110 1080 110 1080 110
3250 3915
1810
960
1210 345
3250
N
RH+DP
1400
W.00 U#
WIR
N
I
585
10
K
11
W.18 U3
815
BED4
2410
3650
L
12
3230
1985
510
9535
100
1225
1210
C
3250
1985
4450
575
1225
1400
1225
11225
585
3650
B
890 60
1225
9535
A
3000
1225
O
C
M
13
M
14 15
1225
1770
585
1335 65
2000
5575
2080
1770
16
W.11
B
C
O
2
U3 FIRST FLOOR PLAN Scale - 1 : 100
A
B
17
C
18
U3 ROOF PLAN 19
Scale - 1 : 100
20
21
22
23 24
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
As indicated @ A1
DRWN
YH
CHCK
Checker
TITLE
N
O
NOTE A
PROJECT
INDIVIDULE PLAN-U3 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
PLANS TO BE READ IN CONJUNCTION WITH ALL TOWN PLANNING DOCUMENTS WIND CLASSIFICATION: N1 REFER TO A100 GENERAL NOTES AND ENERGY REPORT FOR ALL ENERGY REQUIREMENTS TO WALLS, CEILINGS, WINDOWS AND LIGHTS. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ARTICULATION JOINTS NEED TO BE MAXIMUM 5M APART. ALL BOX GUTTERS MUST DISCHARGE STRAIGHT INTO A RAIN WATER HEAD WITH NO 90 DEGREE RAIN HEAD OTHERWISE RE-DESIGN WITH AN INTERNAL SUMP, AND BOX GUTTER OVER FLOW PREVENTION IN ACCORDANCE WITH AS3500.3. ALL ROOF TO BE PROVIDED WITH ROOF SARKING. ALL WC, SANITARY COMPARTMENTS, ENSUITES OR BATHROOM DOORS WHICH SWING INWARDS AND ARE WITHIN 1200MM OF A TOILET PAN REQUIRED LIFT OFF DOOR HINGES AND THE TOP OF DOOR TRIMMED 10MM TO ALLOW IT TO BE REMOVABLE. ALL FIRST FLOOR HABITABLE ROOM SITUATED LESS THAN 1700MM ABOVE THE FFL MUST BE RESTRICTED TO OPEN A MAXIMUM 125MM. ALL BOX GUTTER SIZE HAS A MINIMUM SIZE OF 300MM WIDE X 100MM DEEP. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ACCORDANCE WITH AS3786, HARD WIRED WITH BATTERY BACK UP AND INTERCONNECTED TOGETHER IN EACH DWELLING, I.E. IF ONE SMOKE ALARM TURNS ON, ON ANY LEVEL EACH OTHER LEVEL SMOKE ALARM TURNS ON ALSO. ALL STAIRS TO HAVE A NON- SLIP RESISTANT FINISH WITH A RATING OF P3 MINIMUM. GLASS SPLASHBACKS BEHIND GAS COOKTOPS MUST BE IN ACCORDANCE WITH THE PLUMBING AND GAS STANDARDS (MINIMUM 6MM TOUGHENED GLASS) ALL SHOWER TO HAVE IMPERVIOUS WALL LINING UP TO 1800MM, I.E. TILES OR VINYL. WET AREA SINKS TO HAVE IMPERMEABLE SPLASHBACK TO MINIMUM 150MM HIGH, I.E. TILES OR VINYL. TERMITE PROTECTION REQUIRED TO ALL BUILDINGS IN ACCORDANCE WITH AS3660.1. ALL MASONRY MUST BE INSTALLED TO AS4773 AND AS3700. ANY PENETRATIONS IN THIS FIRE RATED CONSTRUCTION MUST BE PROTECTED, I.E. FIRE COLLARS TO ANY SERVICE PIPES, WIRE PENETRATIONS SEALED WITH A FIRE RATED MASTIC SEALANT AND NO DOWN LIGHT ETC. CRUSHED ROCK AND AGI-PIPE FOR THE ON BOUNDARY WALLS AND RETAINING WALLS CANNOT BE INSTALLED OVER THE TITLE ALLOTMENT BOUNDARY ALL BALCONIES ARE TO COMPLY AND BE WATERPROOFED AND DRAINED IN ACCORDANCE WITH AS4654 PARTS 1 AND 2. BALCONY OVER FLOW POPS TO BE INSTALLED TO THE BOTTOM OF THE SOLID BALUSTRADE. THE F.F.L. OF BALCONIES WILL BE MINIMUM OF 50MM LOWER THAN DWELLINGS INTERNAL F.F.L. ENSURE EXTERNAL FINISHED SURFACE SURROUNDING THE SLAB MUST BE DRAINED TO MOVE SURFACE WATER AWAY FROM THE BUILDING AND GRADED TO GIVE A SLOPE OF NOT LESS THAN 50MM OVER THE FIRST 1M FROM THE BUILDING. ALL SHOWERS TO HAVE 50MM SET DOWN ALL EXTERNAL AREA LIGHTING WILL BE CONTROLLED THROUGH MOTION/DAYLIGHT SENSOR.
DRAWING NO.
A308
PROJECT NO.
20-009
REVISION.
M
L
K
J
I
N
UNIT 1
WT-A2 W.11 U1
W.12 U1
WT-A2
U1-GF FCL AHD: 52.050 m
WT-A2
D.01 U1
U1-GF FFL AHD: 48.950 m
350
U1-GF FFL AHD: 48.950 m
U1-GF FCL AHD: 52.050 m
W.03 U1
3100
W.02 U1
3100
W.01 U1
U1-FF FFL AHD: 52.500 m
450
450
U1-FF FFL AHD: 52.500 m
2800
W.10 U1
2800
W.09 U1
WT-A2
U1-RL AHD: 56.000 m U1-FF FCL AHD: 55.300 m
700
WT-A2
700
U1-RL AHD: 56.000 m U1-FF FCL AHD: 55.300 m
3000
U1-BL FCL AHD: 48.600 m
2650
U1-BL FCL AHD: 48.600 m
U1-BL FFL AHD: 45.950 m
1
U1-BL FFL AHD: 45.950 m
EAST ELEVATION Scale - 1 : 100
O
A
B
C
D
E
F
G
H
UNIT 3 UNIT 2 UNIT 1 WT-A2 W.10 U3
W.11 U3
RH+DP
WT-A
RH+DP WT-A3
WT-A3
W.16 U1
RH+DP
WT-A
W.02 U3
2900
W.01 U3
D.01 U3
WT-A2
D.01 U2
WT-A
W.07 U1
W.08 U1
WT-A2
350
U2-BL FCL AHD: 50.200 m 350
2650
U3-BL AHD: 48.650 m
W.06 U1
U2-GF FFL AHD: 50.550 m D.14 U2
U1-RL AHD: 56.000 m U1-FF FCL AHD: 55.300 m
W.09 U1
U2 GF FCL AHD: 53.450 m
WT-A
W.02 U2
W.01 U2
2900
WT-A3
W.17 U1
U2-FF FFL AHD: 53.900 m
D.14 U3
2650
U3-BL FCL AHD: 51.300 m
W.11 U2
WT-A
350
U3-GF FFL AHD: 51.650 m
W.10 U2
2800
WT-A3
WT-A3
450
U3-GF FCL AHD: 54.550 m
W.09 U2
3500
RH+DP
WT-A2
U2-RL AHD: 57.400 m U2-FF FCL AHD: 56.700 m
450
U3-FF FFL AHD: 55.000 m
450
2800
W.09 U3
WT-A3
700
WT-A
U1-FF FFL AHD: 52.500 m U1-GF FCL AHD: 52.050 m
3100
RH+DP
700
U3-RL AHD: 58.500 m U3-FF FCL AHD: 57.800 m
2650
U2-BL FFL AHD: 47.550 m
U1-GF FFL AHD: 48.950 m U1-BL FCL AHD: 48.600 m
U1-BL FFL AHD: 45.950 m
2
SOUTH ELEVATION Scale - 1 : 100
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
ELEVATIONS 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A400
PROJECT NO.
20-009
REVISION.
N
I
J
K
L
M
UNIT 3
W.16 U3
WT-A2
2800 RH+DP
WT-A3
U3-GF FCL AHD: 54.550 m
450
RH+DP
450
U3-FF FFL AHD: 55.000 m
W.07 U3
350 2650
2900
350
U3-BL FCL AHD: 51.300 m
U3-BL AHD: 48.650 m
1
U3-FF FFL AHD: 55.000 m U3-GF FCL AHD: 54.550 m
W.08 U3
2900
W.06 U3
2650
U3-GF FFL AHD: 51.650 m
U3-RL AHD: 58.500 m U3-FF FCL AHD: 57.800 m
W.17 U3
2800
W.15 U3
RH+DP
700
RH+DP
WT-A3
700
U3-RL AHD: 58.500 m U3-FF FCL AHD: 57.800 m
U3-GF FFL AHD: 51.650 m U3-BL FCL AHD: 51.300 m
U3-BL AHD: 48.650 m
WEST ELEVATION Scale - 1 : 100
H
G
F
E
D
C
B
A
O
UNIT 3 UNIT 2 UNIT 1
2800 450
W.05 U3
W.05 U2
WT-A
U3-GF FCL AHD: 54.550 m
350
W.04 U1
350
U3-BL FCL AHD: 51.300 m
U3-BL AHD: 48.650 m
2650
U2-BL FCL AHD: 50.200 m
U3-GF FFL AHD: 51.650 m
2650
350
U2-GF FFL AHD: 50.550 m
3100
W.04 U3
RH+DP WT-A
U3-FF FFL AHD: 55.000 m
2900
W.04 U2
WT-A
2900
2800
WT-A
WT-A
U2-BL FFL AHD: 47.550 m
2650
U1-BL FCL AHD: 48.600 m
RH+DP
RH+DP
RH+DP
U2 GF FCL AHD: 53.450 m
U1-GF FCL AHD: 52.050 m
U1-GF FFL AHD: 48.950 m
700
W.14 U1
U2-FF FFL AHD: 53.900 m
450
U1-FF FFL AHD: 52.500 m
2800
WT-A W.13 U1
W.14 U3
W.13 U3
W.14 U2
W.13 U2
700
U1-RL AHD: 56.000 m U1-FF FCL AHD: 55.300 m
WT-A3
450
U2-RL AHD: 57.400 m U2-FF FCL AHD: 56.700 m
WT-A3
700
WT-A3
U3-RL AHD: 58.500 m U3-FF FCL AHD: 57.800 m
U1-BL FFL AHD: 45.950 m
2
NORTH ELEVATION Scale - 1 : 100
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 100 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
ELEVATIONS 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A401
PROJECT NO.
20-009
REVISION.
275 205
110
249+X
40
90
10
10 9 35
90
X
159 90
10
10 9 35
5
110 90
10
10
215
90
10
50
5
SELECTED 600x1200 PORCELAIN TILES
9mm FIBRE CEMENT SHEETING. INSTALLED AS PER MANUFACTURE 35mm BATTEN/TOP HAT AS PER MANUFACTURE'S SPECIFICATION
10mm THICK PLASTERBOARD.
10mm THICK PLASTERBOARD.
10mm THICK PLASTERBOARD.
90mm TIMBER STUD WALL.
90mm TIMBER STUD WALL.
90mm TIMBER STUD WALL.
R2.5 BULK INSULATION BETWEEN STUDS
R2.5 BULK INSULATION BETWEEN STUDS
R2.5 BULK INSULATION BETWEEN STUDS
TILE ADHESIVE
TILE ADHESIVE
RENDER
SELECTED 600x1200 PORCELAIN TILES
SELECTED 600x1200 PORCELAIN TILES
ANTIGLARE FOIL WRAP
ANTIGLARE FOIL WRAP
TIMBER LOOKING ALUMINUM BATTEN
110mm BRICKWORK
ANTIGLARE FOIL WRAP
WT-A
BRICK VENEER WALL
WT-A2
WITH TILE FINISH
CEMENT SHEET
WT-A3
WITH TILE FINISH (BOX-UP AREA)
200
2x10mm THICK PLASTERBOARD. 90mm TIMBER STUD WALL.
CEMENT SHEET
REINFORCEMENT AS PER ENG'S DESIGN CONCRETE CORE FILLING CONCRETE MASONRY BLOCK UNIT
TIMBER STUD WALL
WT-B
WITH TILE FINISH
64
10
200
WT-C
INTERNAL WALL
274 100
10
ANTIGLARE FOIL WRAP
374 200
90
9mm FIBRE CEMENT SHEETING. INSTALLED AS PER MANUFACTURE 35mm BATTEN/TOP HAT AS PER MANUFACTURE'S SPECIFICATION 10mm THICK PLASTERBOARD. 90mm TIMBER STUD WALL. 16mm GYPROCK FYRCHEK PLASTERBOARD. R2.5 BULK INSULATION BETWEEN STUDS
9mm FIBRE CEMENT SHEETING. INSTALLED AS PER MANUFACTURE 35mm BATTEN/TOP HAT AS PER MANUFACTURE'S SPECIFICATION
TILE ADHESIVE
59 35 16
TIMBER LOOK ALUMINUM BATTEN WALL EXTERNAL WALL. FRL:60/60/60. CSR2070
245 64
10
200
200 35 10
VERTICAL AND HORIZONTAL REINFORCEMENT AS PER ENG'S DESIGN
VERTICAL AND HORIZONTAL REINFORCEMENT AS PER ENG'S DESIGN
VERTICAL AND HORIZONTAL REINFORCEMENT AS PER ENG'S DESIGN
VERTICAL AND HORIZONTAL REINFORCEMENT AS PER ENG'S DESIGN
64mm STEEL STUD WALL
64mm STEEL STUD WALL
35mm BATTEN
PAINTED FINISH
10mm THICK PLASTERBOARD BULK INSULATION BETWEEN STUD
10mm THICK PLASTERBOARD BULK INSULATION BETWEEN STUD
10mm THICK PLASTERBOARD
100mm GAP FOR SPOON DRAIN
WT-D
CONCRETE CORE FILLED BLOCK WALL
WT-E
--
500 350
AFS WALL
WT-E2
EXTERNAL INSULATED FALSE WALL
174 150
100
AFS WALL
WT-E3
INSULATED
AFS WALL
WT-E4
--
AFS WALL --
500 64
350
150
CAPPING BEAM
CAPPING BEAM
10mm THICK PLASTERBOARD BULK INSULATION BETWEEN STUD 450mm BORED PIER
50 ø4
450mm BORED PIER
ø4
64mm STEEL STUD WALL
50
100mm GAP FOR SPOON DRAIN 150mm SHORTCRETE WALL
WT-F
CONCRETE WALL WITH BORED PIER
150mm SHORTCRETE WALL
WT-F1
150MM. WITH FALSE WALL
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
CONCRETE WALL WITH BORED PIER --
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 5 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
WALL TYPES 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A500
PROJECT NO.
20-009
REVISION.
INTERNAL
EXTERNAL
INTERNAL
EXTERNAL SHORTCRETE WALL WITH 'XPEX' WATERPROOFING TO MANUFACTURES SPECS
SHORTCRETE WALL WITH 'XPEX' WATERPROOFING TO MANUFACTURES SPECS 'NYLEX' STRIP DRAIN REFER TO CIVIL ENGINEER 'VOLTEX' BENTONITE GEOTEXTILE WATERPROOFING+ WATERPROOFING COATING: 2 COATS OF GRIPSET 51 BITUMEN PAIN+ POLYTHENE SHEET WITH PROTECTIVE BOARD OVER
'NYLEX' STRIP DRAIN REFER TO CIVIL ENGINEER
BULK INSULATION BETWEEN STUD
'VOLTEX' BENTONITE GEOTEXTILE WATERPROOFING+ WATERPROOFING COATING: 2 COATS OF GRIPSET 51 BITUMEN PAIN+ POLYTHENE SHEET WITH PROTECTIVE BOARD OVER
64MM STEEL STUD WALL
100MM GAP FOR SPOON DRAIN 10MM THICK PLASTERBOARD
WEEP HOLES SPOON DRAIN
WEEP HOLES SPOON DRAIN
WATERPROOFING MEMBRANE
WATERPROOFING MEMBRANE
1 TYPICAL WATERPROOFING DETAIL1-BORE PIER SHORTCRETE WALL
2 TYPICALWATERPROOFING DETAIL2-BORE PIER SHORTCRETE WALL
Scale - 1 : 10
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
Scale - 1 : 10
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 10 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
DETAILS 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A501
PROJECT NO.
20-009
REVISION.
BLOCKWORK WALL REFER TO STRUCTURE FOR DETAILS
INFILL WITH XPEX ADDITIVE FOR WATER RESISTEANCE BACKFILL WITH FREE DRAINING MATERIAL
REINFORCEMENT REFER TO STRUCTURE FOR DETAILS STEEL STUD WITH INSULATION REFER TO ENERGY RATING REPORT
'VOLTEX' BENTONITE GEOTEXTILE WATERPROOFING +WATERPROOFING COATING: 2 COATS OF GRIPSET 51 BITUMEN PAIN +POLYTHENE SHEET WITH PROTECTIVE BOARD OVER
PLASTERBOARD
150MM HEIGHT CONCRETE HOB KUNISEAL
SPOON DRAIN
AGI DRAIN
WATERPROOFING MEMBRANE
1 TYPICALWATERPROOFING DETAIL3-COREFILLED BLOCKWORK WALL Scale - 1 : 10
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 10 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
DETAILS 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A502
PROJECT NO.
20-009
REVISION.
UNIT
NUMBER
U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1 U1
D.01 D.02 D.03 D.04 D.05 D.06 D.07 D.08 D.09 D.10 D.11 D.12 D.13 D.14 D.15 D.16 D.17 D.18 D.19 D.20 D.21 D.22 D.23
WIDTH 2250 720 720 820 820 720 720 820 820 820 820 720 820 720 820 820 720 4000 920 820 720 720 820
U1 Door Schedule
HEIGHT 3120 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2200 2350 2350 2350 2350 2350
DESCRIPTION
SOLID CORE SWING DOOR WITH 650MM SIDELIGHT SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SLIDING DOOR SEMI-HOLLOW CORE SLIDING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR PERFORATED METAL, ELECTRIC OPERATED PANEL SOLID CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
UNIT
NUMBER
U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2
D.01 D.02 D.03 D.04 D.05 D.06 D.07 D.08 D.09 D.10 D.11 D.12 D.13 D.14 D.15 D.16 D.17 D.18 D.19 D.20
WIDTH 1560 820 720 820 720 820 820 820 820 820 720 820 720 3200 820 720 720 720 820 920
UNIT
NUMBER
WIDTH
U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3
D.01 D.02 D.03 D.04 D.05 D.06 D.07 D.08 D.09 D.10 D.11 D.12 D.13 D.14 D.15 D.16 D.17 D.18 D.19 D.20
1560 820 720 820 720 820 820 820 820 820 720 820 720 3200 820 720 720 720 820 920
DATE
02/04/23
TITLE
SCALE
@ A1
DRWN
YH
CHCK
Checker
PROJECT
U2 Door Schedule
HEIGHT 2900 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2100 2350 2350 2350 2350 2350 2350
DESCRIPTION
SOLID CORE SWING DOOR SEMI-HOLLOW CORE SLIDING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SLIDING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR PERFORATED METAL, ELECTRIC OPERATED PANEL SOLID CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR
U3 Door Schedule
HEIGHT 2900 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2100 2350 2350 2350 2350 2350 2350
DESCRIPTION
SOLID CORE SWING DOOR SEMI-HOLLOW CORE SLIDING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SLIDING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR PERFORATED METAL, ELECTRIC OPERATED PANEL SOLID CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR SEMI-HOLLOW CORE SWING DOOR
DOOR SCHEDULE 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A600
PROJECT NO.
20-009
REVISION.
FIX. CLG.
875 50
AWN. OBS.
1680
W.04 U1
2250
W.05 U1
2180
1700
W.06 U1
2400
W.07 U1
1950
1700
W.09 U1
W.10 U1
1430
W.11 U1
1220
690
W.12 U1
W.13 U1
W.14 U1
50 W.15 U1
2500
1775
AWN. CLG.
FIX. CLG.
300
FIX. OBS.
2500
AWN. CLG.
300 50 625 50
90.00°
AWN. CLG.
300
650
1700
2800
300
300
FFL
650 50 785 50 875 50
340
AWN. CLG.
1810
1100
FIX. CLG.
2500
FIX. CLG.
2800
2500
2800
FIX. CLG.
FIX. CLG.
W.08 U1
1600
TFL FIX. CLG.
FIX. CLG.
W.16 U1
1725
W.03 U1
AWN. CLG.
FIX. CLG.
300 50 625 50
W.02 U1
1770
AWN. CLG.
3100
SLD. CLG.
1250
2175
SLD. CLG.
1150
875 50
1050
3100
FIX. CLG.
SLD. CLG.
1100
3100
1720
FIX. CLG.
W.01 U1
1800
SLD. CLG.
1900
600
FIX. CLG.
FIX. CLG.
1800
3100
FIX. CLG.
1800
900
GFL
FIX. CLG.
3100
3100
3100
3100
FIX. CLG.
50 925 50 1050 50 925 50
FFL
1900
1700
1600
2180
1950
3300
2175
7400
FIX. CLG.
W.17 U1
1225
1880
880
1000
600
SKYLIGHT
WINDOW LEGENDS CODE
W.18 U1
W.19 U1
W.20 U1
FIX. AWN. CAS. SLD. OBG. CLG. S.G D.G.
W.21 U1
DESCRIPTION FIXED GLAZING AWNING WINDOW CASEMENT WINDOW SLIDING DOOR OBSCURED GLAZING CLEAR GLAZING SINGLE GLAZING DOUBLE GLAZING
NOTE B CODE 25 26 27 28 29 30 31
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 50 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
WINDOW SCHEDULE-U1 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DESCRIPTION ENSURE GRADE A SAFETY GLASS IN INSTALLED IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF AS1288 ALL UPPER FLOOR WINDOWS WITH A SILL HEIGHT OF LESS THAN 1700MM ABOVE FFL MUST BE RESTRICTED TO OPEN 125MM MAXIMUM. REFER TO A001 GENERAL NOTES FOR ENERGY RATING REQUIREMENT TO WALLS, CEILING, WINDOWS AND LIGHTS. REFER TO PERMIT CONDITION FIXED OBSCURE GLAZING TO 1.7 METERS ABOVE FINISHED FLOOR LEVEL WITH NOT MORE THAN 25% TRANSPARENCY. ALL OBSCURED GLAZING TO BE MANUFACTURED OBSCURED GLASS. OBSCURE FILM BEING APPLIED TO CLEAR GLAZING WILL NOT BE ACCEPTED. ALL GLAZED ELEMENTS (I.E. WITHIN APARTMENTS) REQUIRE DECAL BANDS AS PER AS1288 REQUIREMENTS.
DRAWING NO.
A601
PROJECT NO.
20-009
REVISION.
W.01 U2
SLD. CLG.
2000
FIX. CLG.
800
AWN. OBS.
AWN. OBS.
1000
975
FIX. CLG.
1000
1700
2900 50
FIX. OBS.
AWN. CLG.
860
1900
SLD. CLG.
1900
1900
50
1800
1775 2900
300
FIX. CLG.
1800
W.03 U2
W.04 U2
1850
W.05 U2
1500
W.06 U2
2100
2410
1210
W.07 U2
1210
W.08 U2
1810
1810
W.09 U2
W.10 U2
1550
W.11 U2
799
W.12 U2
W.13 U2
650
1200 W.14 U2
W.15 U2
300
AWN. OBS.
AWN. OBS.
1850
FIX. OBS.
AWN. CLG. FIX. OBS.
650
1850
AWN. OBS.
650 50 925 50 775 50 300
300
300
AWN. OBS.
1300
1100
AWN. CLG.
1700
50 1025 50 975 650 50
FIX. OBS.
2150
AWN. CLG.
650
300 1850
FIX. CLG.
650 50 925 50 775 50
FIX. CLG.
650
FIX. CLG.
50 925 50
2800 50 925 50
2800 50 925 50
2800
1725
AWN. CLG.
1725
AWN. CLG.
1725
AWN. CLG.
50
50
50
50 830 50 830 50
TFL
2800
1900
AWN. CLG.
AWN. CLG.
W.02 U1
1390
FFL
1950
AWN. CLG.
1100
50
GFL
FIX. CLG.
650 50 925 50 875 50
900
2900
2000
FIX. CLG.
1810
650
FFL
50 640 50 1060 50 900 50 1025 50 825 50
1390
7400
1200
1850
W.16 U2
W.17 U2
1390
2240
706
700
SKYLIGHT
WINDOW LEGENDS CODE
W.18 U2
W.19 U2
FIX. AWN. CAS. SLD. OBG. CLG. S.G D.G.
W.20 U2
DESCRIPTION FIXED GLAZING AWNING WINDOW CASEMENT WINDOW SLIDING DOOR OBSCURED GLAZING CLEAR GLAZING SINGLE GLAZING DOUBLE GLAZING
NOTE B CODE 25 26 27 28 29 30 31
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 50 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
WINDOW SCHEDULE-U2 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DESCRIPTION ENSURE GRADE A SAFETY GLASS IN INSTALLED IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF AS1288 ALL UPPER FLOOR WINDOWS WITH A SILL HEIGHT OF LESS THAN 1700MM ABOVE FFL MUST BE RESTRICTED TO OPEN 125MM MAXIMUM. REFER TO A001 GENERAL NOTES FOR ENERGY RATING REQUIREMENT TO WALLS, CEILING, WINDOWS AND LIGHTS. REFER TO PERMIT CONDITION FIXED OBSCURE GLAZING TO 1.7 METERS ABOVE FINISHED FLOOR LEVEL WITH NOT MORE THAN 25% TRANSPARENCY. ALL OBSCURED GLAZING TO BE MANUFACTURED OBSCURED GLASS. OBSCURE FILM BEING APPLIED TO CLEAR GLAZING WILL NOT BE ACCEPTED. ALL GLAZED ELEMENTS (I.E. WITHIN APARTMENTS) REQUIRE DECAL BANDS AS PER AS1288 REQUIREMENTS.
DRAWING NO.
A602
PROJECT NO.
20-009
REVISION.
W.01 U3
SLD. CLG.
2000
FIX. CLG.
800
AWN. OBS.
AWN. OBS.
1000
975
FIX. CLG.
1000
1700
2900 50
FIX. OBS.
AWN. CLG.
860
1900
SLD. CLG.
1900
1900
50
1800
1775 2900
300
FIX. CLG.
1800
W.03 U3
W.04 U3
1850
W.05 U3
1500
W.06 U3
2100
2410
1210
W.07 U3
1210
W.08 U3
1810
1810
W.09 U3
W.10 U3
1530
W.11 U3
790
W.12 U3
W.13 U3
650
1200 W.14 U3
W.15 U3
300
AWN. OBS.
AWN. OBS.
1850
FIX. OBS.
AWN. CLG. FIX. OBS.
650
1850
AWN. OBS.
650 50 925 50 775 50 300
300
300
AWN. OBS.
1300
1100
AWN. CLG.
1700
50 1025 50 975 650 50
FIX. OBS.
2150
AWN. CLG.
650
300 1850
FIX. CLG.
650 50 925 50 775 50
FIX. CLG.
650
FIX. CLG.
50 925 50
2800 50 925 50
2800 50 925 50
2800
1725
AWN. CLG.
1725
AWN. CLG.
1725
AWN. CLG.
50
50
50
50 830 50 830 50
TFL
2800
1900
AWN. CLG.
AWN. CLG.
W.02 U3
1390
FFL
1950
AWN. CLG.
1100
50
GFL
FIX. CLG.
650 50 925 50 875 50
900
2900
2000
FIX. CLG.
1810
650
FFL
50 640 50 1060 50 900 50 1025 50 825 50
1390
7400
1200
1850
W.16 U3
W.17 U3
1380
2230
690
478
SKYLIGHT
WINDOW LEGENDS CODE
W.18 U3
W.19 U3
FIX. AWN. CAS. SLD. OBG. CLG. S.G D.G.
W.20 U3
DESCRIPTION FIXED GLAZING AWNING WINDOW CASEMENT WINDOW SLIDING DOOR OBSCURED GLAZING CLEAR GLAZING SINGLE GLAZING DOUBLE GLAZING
NOTE B CODE 25 26 27 28 29 30 31
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 50 @ A1
DRWN
YH
CHCK
Checker
TITLE
PROJECT
WINDOW SCHEDULE-U3 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DESCRIPTION ENSURE GRADE A SAFETY GLASS IN INSTALLED IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF AS1288 ALL UPPER FLOOR WINDOWS WITH A SILL HEIGHT OF LESS THAN 1700MM ABOVE FFL MUST BE RESTRICTED TO OPEN 125MM MAXIMUM. REFER TO A001 GENERAL NOTES FOR ENERGY RATING REQUIREMENT TO WALLS, CEILING, WINDOWS AND LIGHTS. REFER TO PERMIT CONDITION FIXED OBSCURE GLAZING TO 1.7 METERS ABOVE FINISHED FLOOR LEVEL WITH NOT MORE THAN 25% TRANSPARENCY. ALL OBSCURED GLAZING TO BE MANUFACTURED OBSCURED GLASS. OBSCURE FILM BEING APPLIED TO CLEAR GLAZING WILL NOT BE ACCEPTED. ALL GLAZED ELEMENTS (I.E. WITHIN APARTMENTS) REQUIRE DECAL BANDS AS PER AS1288 REQUIREMENTS.
DRAWING NO.
A603
PROJECT NO.
20-009
REVISION.
3985 2780
2075
1200 600
1165
210
1200
60 TI LE
850
20
40 250 20 1040
1900
1900
3100
3100
930
2250
TI LE
1200
0X
60
0
X
60
800
0
60
0
100
2075 1865
210
2
3
Ensuite - Elevation1 Scale - 1 : 20
Ensuite - Elevation2 Scale - 1 : 20
3985
1200
1200
20
670
670
20
20
670
670
20
2075
20
20
210 450
1425
1
440
210
Ensuite Floor Plan Scale - 1 : 20
1200
4
1425
20
660
660
800
800
2250
930
5
Ensuite - Elevation3 Scale - 1 : 20
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
40
540 250
1060
20
40 250 20
3120
3100
950 210 40 250
20
Ensuite - Elevation4 Scale - 1 : 20
REV.
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 20 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1425
600
1360
5
250
4
1900
A700
530
2
800
3
20 20 20 40 20 20 20 20 20 250 150 350 40 210 250 210 210 210 210 20
360
3985
1200
TILE
600
530
X6
00
200
1865
PROJECT
TYPICAL INTERNAL ELEVATION 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A700
PROJECT NO.
20-009
REVISION.
450 500
1200
80
640
1200
50
400
1880
250 440
640
110
600
4975
640
110
600
600
340
340
600
600
795
1100
600
110
600
600
340
340
600
600
795
1100
700 20 20
20
1810
20
390
20
700 20 120
20 120
170 170 40
20 340 20 120
1285
120
5
780
4
3075
A701
580
585
2
340 20 340 20 360 20 360 20 360 20 360
20 350 20 370 20 700 20
700
1290
800
3100
20
780
1060
905
720
720
25
120
250
1205
600
2
340
Kitchen - Elevation1
580
Scale - 1 : 20
2790
990
20
910 910
3075 20
1165
395
990 395
600
480
20
890
1200
990
700 250
450
Scale - 1 : 20
800
2200
2200
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
40 740
20
120
720 120
840
340 20
5
Kitchen - Elevation3 Scale - 1 : 20
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
40 20 40
700
4
Kitchen Floor Plan
Kitchen - Elevation4 Scale - 1 : 20
DATE
ISSUE
DATE
02/04/23
SCALE
1 : 20 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
120
1375
170 170 40
20 20
1375
120
705
80
720
500
900
125
20
40
650
650
3100
2200
2200
2200
585
585
650
755
700
20
560
20
340
PROJECT
TYPICAL INTERNAL ELEVATION 2 Tara Avenue Kew VIC
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A701
PROJECT NO.
20-009
REVISION.
1300 470
850
1300
235
1380
400 TIL E1 00 x 2300 00 x4 10
0
20
40
LE
540 250
2
WC Floor Plan Scale - 1 : 20
3
WC - Elevation1 Scale - 1 : 20
202 35 Whitehorse Road Deepdene VIC 3000 Australia Tel : +61 3 9817 6788 www.jesseantarchitects.com.au ABN 29 469 352 797
NOTE - ANY ERRORS, DISCREPANCIES OR OMMISSIONS IN THE DRAWINGS, NOTATIONS OR DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO WORKS COMMENCING. - CONTRACTORS SHALL VERIFY JOB DIMENSIONS BEFORE ANY JOB COMMENCES. - ALL SHOP DRAWINGS SHALL BE SUBMITTED TO THE SUPERINTENDENT AND MANUFACTURE - SHALL NOT COMMENCE PRIOR TO THE RETURN OF UNAMENDED SHOP DRAWINGS SIGNED - BY THE CONSULTANT. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED. THIS - DRAWING SHOULD BE READ IN CONJUNCTION WITH ALL RELEVANT CONTRACT, SPECIFICATIONS - AND DRAWINGS COPYRIGHT OF THIS DRAWING IS VESTED IN BEYOND ARCHITECTS
REV.
4
WC - Elevation2 Scale - 1 : 20
DATE
ISSUE
5
WC - Elevation3 Scale - 1 : 20
DATE
02/04/23
SCALE
1 : 20 @ A1
DRWN
YH
CHCK
Checker
TITLE
N
1
250
600
TI
600 250
450
2
540
4
40
A702
20 200
1300
3
FLAT MIRROW
100100
850
5
2900
810
2900
470
2900
100
2050
1380
2900
900 950
TIL E1 00 x
900 950
400
235
450
100
TILE 1 00
810
X 400
1380
PROJECT
TYPICAL INTERNAL ELEVATION 2 Tara Avenue Kew VIC
WC - Elevation4 Scale - 1 : 20
DRAWING STATUS
FOR CONSTRUCTION
DRAWING NO.
A702
PROJECT NO.
20-009
REVISION.