DC Surge Suppressors Trabtech

Page 1

SURGETRAB (PIPETRAB) Field Mounted Transmitter/Signal Protection Instructions 1669A

November 2002

Features

Description

• Field mounted design - Surge protection device is encapsulated in stainless steel pipe nipple for fast and easy installation at two wire field mounted device.

The PIPETRAB S-PT1-2PE-24DC field mounted surge suppressors are specially designed for protection of field mounted control devices. The PIPETRAB is packaged in a 3/4" 304 stainless steel pipe nipple to provide environmental protection of the suppression electronics.

• Easy wiring - Screw clamp connectors allow easy in and out wiring.

The suppression circuit is a multistage hybrid utilizing fast response surge arresting diodes combined with high energy handling gas discharge tubes.

• 10 kA 8 x 20 µs surge suppression current: normal mode and common mode. Protection from electrical transients induced by lightning, load switching and other common industrial noise sources.

The suppression electronics are removable and feature screw clamp connections. Allowing the user an easy installation. No wire nuts or additional crimp connectors are required.

• Easy earth ground connection. "Grounding

disk" uses conduit as surge path to ground. (Conduit must be grounded for reliable operation.)

Used with the Phoenix Contact DIN-rail mount SURGETRAB UBK-2PE-24HB provides total protection of sensitive control signal circuits.

• Replaceable protection electronics. In case of failure the user can easily replace the surge protection device.

Figure 1. PIPETRAB Application Drawing Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • Fax: (717) 944-1625

1


S-PT1-2PE-24DC

Part # 2818122

Table 1. General Specifications

Figure 2. Circuit Schematic Diagram

Figure 3. Interior Wiring Diagram

Ordering Information S-PT1-2PE-24DC (includes surge protection circuit, 4" long x 3/4" NPT pipe nipple and cap)

28 18 12 2

S-PT1-2PE-24DC/P (replacement surge protection circuit)

28 18 21 6

PT 1X2-24DC-ST (DIN-rail mount analog signal protection - plug)

28 56 03 2

PT 1X2-BE (base)

28 56 11 3

Data Sheet 1669A

The information given herein is based on data believed to be reliable, but Phoenix Contact Inc. makes no warranties expressed or implied as to its accuracy and assumes no liability arising out of its use by others. This publication is not to be taken as a license to operate under, or recommendation to infringe, any patent.

Headquarters, U.S. Phoenix Contact Inc. P.O. Box 4100 Harrisburg, PA 17111-0100 Phone: (717) 944-1300 Fax: (717) 944-1625 Email: info@phoenixcon.com Web Site: www.phoenixcon.com Technical Support or Information Phone: 1-800-322-3225 Documentation Fax: 1-800-944-9901 Headquarters, Canada Phoenix Contact Ltd. 235 Watline Avenue Mississauga, Ontario L4Z 1P3 Phone: (905) 890-2820 Fax: (905) 890-0180