REGAL™ MODEL 7009/7010

Bulletin 7009/7010

SMARTVALVE

FOR FEEDBACK (CLOSED LOOP) CONTROL SCHEMES

Chlorinators’ new Model 7009 and Model 7010 SMARTVALVEs are highly sophisticated control valves for use wherever chlorine or sulfur dioxide is needed to treat varying water flow rates and/or varying water quality. These SMARTVALVEs: • Can be configured to operate in either of the following control schemes: flow proportional control, residual only control, compound loop control or feed forward dechlorination control. • Include a unique “linearization” program that assures the SMARTVALVE’s digital display reading matches the reading indicated on the gas feed system’s metering tube. • Can automatically compensate for changing system hydraulic “lag time” that occurs as the water flow rate increases and decreases. • Can operate with ORP monitors or residual analyzers. • Include an adjustable “deviation alarm” consisting of an LED and a relay that alerts operators when residual is too low or too high. • Include a residual “deadband” adjustment within which the controller will not make any corrections. This is to enhance the stability of the feedback control scheme. • Can be operated in the field four ways: fully automatic, electric/manual, and two (2) methods of manual. • Digital display and annunciator LEDs indicate: – Flow process variable in actual numbers or as a percent of flow. – Residual process variable in PPM residual or ORP value. – Valve plug position in pounds per day (PPD) of actual gas feed rate.

®

SMARTVALVE

– Mode of operation: automatic or manual. – Setpoint value: • Residual: 0.2 – 20.0 PPM • ORP: 1.0 – 2000 mV – Dosage value: .01 to 4.00.

PATENT PENDING


REGAL MODEL 7009/7010 SMARTVALVE THEORY OF OPERATION Compound Loop Control A water flow meter with a 4-20 mA signal transmitter continually measures the amount of water flowing and transmits instantaneous signals to the primary input of the REGAL Model 7009 or 7010 SMARTVALVE causing the valve to feed the correct amount of chemical to the water based on the immediate dosage setting. At the same time, a residual or ORP analyzer draws a continuous sample of the treated water at the appropriate point downstream of the chemical injection point (after suitable mixing is achieved) and sends a proportional signal to the secondary input of the REGAL Model 7009 or 7010 SMARTVALVE based on the value of the actual residual measured. The controller circuitry in the SMARTVALVE compares the measured residual to the desired residual (operator established set point) and sends a timed correction signal to the SMARTVALVE motor driver circuitry based on the results of the analysis. If the analysis shows an actual residual greater than (or less than) the desired residual, the timed correction signal opens or closes the SMARTVALVE motor driver circuitry as necessary in an attempt to keep these two values the same.

SPECIFICATIONS Maximum Gas Feed Rates

10, 25, 50, 100, 250, 500, 1000 and 2000 PPD (200, 500, 900, 2000, 5000 g/hr and 10, 20, and 40 kg/hr).

Power Requirements

Field selectable 115/230 VAC ±15%, single phase. Operating frequency 50/60 Hz.

Fusing

1/4A @230V, 1/2A @115V (time delay, 250V).

Power Consumption

45 Watts absolute maximum.

Input Signals

0-10 VDC. 4-20 milliamps DC.

Input Impedance

60.4 Ohms for current inputs. 100K Ohms for voltage inputs.

Output Signals

4-20 milliamps DC. 12 Volt compliance (600 Ohms) isolated and powered.

Environmental Limits

32°F to 120°F (0°C to 50°C).

Calibration Accuracy

±0.25% from zero.

Speed of Response

Variable and field selectable.

Operating Range

10:1 in automatic and 20:1 in manual.

Operator Interface

Four button keypad.

Displays

20-character, 2-line Polymer LED (PLED)

Control Mode

Automatic or manual.

Dosage Ratio

0.01 to 4.00.

Serial Communications OPTIONAL. Isolated RS 232/RS 422/ RS 485 (2/4-wire) module. Reliability & Protection

MOV and fuse for power supply. Transorb for digital power supply and analog input.

EEPROM

128 byte.

Memory

8K RAM. 32K ROM.

Gain Setting

1.0 to 9999.

Lag Time Setting

0-9999 seconds.

Decimal Point Setting

0, 0.0, 0.00.

Residual Full Scale Setting

.2-20.0 PPM.

ORP

1.0-2000 mV.

Residual Input Signal Filtering

0.0 to 20.0 seconds.

1044 SE Dixie Cutoff Road, Stuart, FL 34994 USA • Tel: 772-288-4854 Fax: 772-287-3238 • www.regalchlorinators.com • Email: regal@regalchlorinators.com © Copyright 2007, Printed in USA