Technical Specification Datasheet SCADAPack Smart RTU Compact, versatile controller for telemetry and remote SCADA solutions
01
SCADAPack Smart RTUs that combine the monitoring and communications capabilities of remote terminal units (RTU) with the processing and data-logging power of programmable logic controllers (PLC), providing superior functionality wherever remote processes require automatic supervision and autonomous control. SCADAPack Smart RTUs are the foundation for a range of solutions offering specific software and configuration tools to enhance performance in oil and gas and water/ wastewater applications.
02
Selection Guide
SCADAPack 100, 300, 32 • •
Modbus core database, DNP3 level 2 layer, optional DF1 support Programming and configuration: TelePACE Studio, IEC61131-3, C/C++
314
330
334
350
357
32P
32 P4
32 P4A
32 P4B
100
8: 0-20mA, 4-20mA 0-5V 0-10V
n/a
8: 0-20mA, 4-20mA 0-5V 0-10V
5: 0-10V, 0-20mA 1: 0-32.7VDC
5: 0-10V, 0-20mA 1: 0-32.7VDC 8: 0-20mA, 4-20mA 0-10V 0-5V
n/a
8: 0-20/ 4-20mA or 0-5/1-5V
8: 0-20mA/ 0-10V 1: 0-32.768V
8: 0-20/ 4-20mA 0-5/0-10V
3: 0-20/ 4-20mA 0-5/1-5 VDC 1: 0-32.7 VDC
2 or 4: 0-20mA 4-20mA Optional
n/a
Analog Inputs On-board1
Analog Outputs On-board1
2: 0-20mA 4-20mA Optional
n/a
2: 0-20mA 4-20mA Optional
2: 0-20mA 4-20mA Optional
n/a
16: 12/24V 48V 115/125V 240V
n/a
16: 12/24V 48V 115/125V 240V
8: Dry contact, Shared with output points.
8: Dry contact, shared with output points 32: (12/24V, 48V, 115/125V, 240V)
3: 24VAC/ 30VDC, shared with Counter inputs 1: 30V interrupt
3: 24VAC/ 30VDC, shared with Counter inputs 1: 30V interrupt 16: 12-24/120/ 220V-VAC
3: 24VAC/ 30VDC, shared with Counter inputs 1: 30V interrupt 32: dry contact Shared with outputs
3: 24VAC/ 30VDC Shared with Counter inputs, 1: 30V interrupt input 32: 12/24V, 48V, 115/125V, 240V
6: selectable as input or output
n/a
10: dry contact or solid-state
8: open drain, Shared with input points.
8: open drain, Shared with input points. 16: dry contact
1: Controller Status Output
1: Controller Status Output 12: Dry contact
1: Controller Status Output 32: dry contact Shared with inputs
1: Controller Status Output 16: Dry contact
6: selectable as input or output
Digital Inputs On-board1
Digital Outputs On-board1
10: dry contact or 10: solid-state
Frequency Inputs On-board1
1: 0-10Hz or 0-5kHz (dry contact)
3: 0-5 kHz shared with digital inputs, 1: 0-500Hz, interrupt input
1: 0-6 kHz turbine or dry contact
2: 0-10kHz (turbine or dry contact)
n/a
1
General Turbine Inputs Serial Ports
2: RS232/ RS485
USB Ports
1: Peripheral
1: Host, 1: Peripheral
n/a
1, 10/100BaseT
Ethernet Ports EFM Flow Runs Programming Software Modbus DNP3
2: RS232/RS485 1: RS232
1: RS485, 1: RS232/RS485, 1: RS232
2: RS232 1: RS232/ RS485
2: RS232 1: RS232/ RS485
1: RS232 1: RS232/ RS485
n/a
4
1: 10BaseT
n/a
10
1
TP Studio, IEC61131-3, C++ Master and Slave: Modbus RTU, Modbus ASCII, Modbus/TCP, Modbus UDP Level 2 Slave
Number of on-board I/O may be further expanded for any SCADAPack using Expansion I/O Modules. Refer to individual product data sheets for detailed specifications. 1
3: RS232, 1: RS232/RS485
TP Studio, IEC61131, C
03
Contents
SCADAPack Smart RTU
I/O Expansion Modules*
SCADAPack 314
Analog Input Modules
Specifications .............................................................................................. 4 Model Code ................................................................................................ 5
SCADAPack 330 | 334 Specifications 330 ....................................................................................... 6 Specifications 334 ....................................................................................... 7 Model Code ................................................................................................ 8
5502 - Differential analog input module ..................................................... 5504 - Thermocouple input module .......................................................... 5505 - RTD input module .......................................................................... 5506 - Analog input module ......................................................................
Analog Output Modules 5302 - Analog output module .................................................................... 24 5304 - Analog output module .................................................................... 25
SCADAPack 350 | 357
Digital Input Modules
Specifications 350 ..................................................................................... 10 Specifications 357 ..................................................................................... 11 Model Code .............................................................................................. 12
SCADAPack 32
Specifications P4A .................................................................................... Specifications P4 ....................................................................................... Specifications P4B .................................................................................... Model Code ..............................................................................................
14 15 16 17
SCADAPack 100 Specifications ............................................................................................ 18 Model Code .............................................................................................. 19
20 21 22 23
5403 - High level digital input module ........................................................ 5404 - High level digital input module ........................................................ 5405 - Digital input module ....................................................................... 5410 - High speed counter/accumulator ................................................... 5414 - Compact digital input module ........................................................
26 27 28 29 30
Digital I/O Modules 5401 - Configurable digital I/O module ...................................................... 31 5402 - Configurable digital input or output module .................................... 32
Digital Output Modules
5406A - Dry contact relay out module ....................................................... 33 5407 - Dry contact relay out module ......................................................... 34 5408 - Triac digital output module .............................................................. 35 5409 - FET digital output module .............................................................. 36 5411 - Digital output module ..................................................................... 37 5415 - Compact relay digital output module .............................................. 38
Combination I/O Modules 5606 - Analog/digital I/O module ............................................................... 39 5607 - Analog/digital I/O module ............................................................... 40
I/O Simulator Modules 5421 - Toggle switch digital input module .................................................. 41 5521 - Potentiometer input module ........................................................... 42
UPS Power Supply 5103 - Uninterruptible Power Supply ......................................................... 43
Non-Programmable Controller Modules 5201 - RS-485 communication controller .................................................. 44 5202 - RS-232 communication controller .................................................. 45
Communication Modules Modems, Interface Modules & Gateways
5901 - Dial-up modem .............................................................................. 46 5902 - Bell 202 radio or leased line modem .............................................. 47 5904 - HART interface module ................................................................... 48 5908 - Wireless data transceiver ............................................................... 49. 5908-WO2 - Wireless data transceiver ...................................................... 50. 5910 - Ethernet switch .............................................................................. 51 5915 - SDI-12 interface module ................................................................ 52
* IO Expansion Module Compatibility Notes: The SCADAPack 100 does not support IO Expansion modules.
04
Product Data Sheet SCADAPack 314 Specifications
P314: 5212 controller board and integrated 56O7 I/O board Controller Processors
• CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer • Microcontroller co-processor, 20 MHz clock
Memory
16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM
CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity
465k words
I/O Analog Inputs
• 8 software configurable: 0-20/4-20mA / 0-5/0-10V (15-bit) • 3 internal: measure incoming power supply voltage for solar applications, battery voltage, and controller temperature
Analog Outputs
• Standard: None • 2 with optional 5305 on 5607 I/O board: 0-20/4-20mA (12-bit)
Digital I/O
• 16 digital inputs: 12/24V, 48V, 115/125V, 240V • 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive), DC solid state rating: 3A, 60 VDC
Counter Inputs
• 1 dry contact: 0-10Hz or 0-5kHz • 2 turbine or dry contact: 0-10kHz
Communications Serial Ports COM1, COM2
• RS-232 port, 8-pin modular RJ45 jack, full or half-duplex, or • RS-485 port, 2-wire, half-duplex
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
USB Peripheral Port
USB 2.0 compliant B-type receptacle
Wireless1
Spread spectrum radio at 900MHz2 and 2.4GHz2
General I/O Terminations
5, 6, and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions
5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant, zinc-plated steel with black enamel paint
Environment
5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power 5212 Controller Board
• • • • • •
1 - 30VDC, 30mW at 12V during sleep mode. 1 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, and USB disabled 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, USB disabled Add 190mW when enabling the USB port Add 30 to 90mW when enabling the LEDs 8.5W at 24V maximum, 5V supply fully-loaded
5607 I/O Module
• 11 - 30VDC, 10.3mA plus analog outputs • 235mA (max.) at 5V required from 5212 controller board
Warranty
3 years on parts and labor
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations • UL Std. No. 1604 - Hazardous (Classified) Locations
Hazardous Locations Europe
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations
IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2). Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
05
Product Data Sheet SCADAPack 314 Model Code
TBUP314-1A20-AB00 represents a sample code for a SCADAPack 314, 5607 I/O board and Modbus protocol emulation
Model TBUP314
Code 1
Code A
Select: Controller SCADAPack 314 , 32 Bit controller, 8 Analog Inputs, 16 Digital Inputs, 10 Digital Outputs, 3 Accumulators
Future Option None
Select: Gas Flow Run-Time Option None Flow Computer Runs
G
2 Run Gas Flow
F
4 Run Gas Flow
V
2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
W
4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
Code 2
Code 0 1
Code A
Select: Protocol Option Modbus and DNP 3.0 (Level 2) protocol emulation
Select: Programming Environment Telepace Ladder Logic and C Language firmware loaded - IEC enabled (programming tools sold separately) IEC 61131-3 and C Language firmware loaded - Telepace enabled (programming tools sold separately)
Select: Analog Inputs 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Code
Select: Digital Inputs/Outputs
B
16 DI (12/24V) and 10 dry contact relays
D
16 DI (120V) and 10 dry contact relays
F
16 DI (12/24V) and 10 DC solid-state relays, ATEX and IECEx certification
H
Code
16 DI (120V) and 10 solid state relays
Select: Analog Outputs
0
None
1
2 channel analog output option, 0 - 20mA
Code 0
Select: Integrated Communication Interfaces None FreeWave & MDS Radios (requires one RS232 port)
1
900Mhz FreeWave Spread Spectrum Radio
A
900MHz MDS Spread Spectrum Radio Trio Radios - 900MHz (requires one RS232 port)
B
900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C
900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D
900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E
900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios - 2.4GHz (requires one RS232 port)
J
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
06
Product Data Sheet SCADAPack 330 Specifications
P330: 5210 controller board only Controller Processors
• CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer • Microcontroller co-processor, 20 MHz clock
Memory
16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM
CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity
465k words
I/O Counter Inputs
• 1, 0-10Hz or 0-5kHz (dry contact) • 2, 0-10kHz (turbine or dry contact)
Communications Serial Ports COM1, COM2
• RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or • RS-485 port, 2-wire, half duplex
Serial Port COM3
• RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
Ethernet Port
RJ45, 10/100BaseT
Ethernet Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols
IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port
USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port
USB 2.0 compliant “B”-type receptacle
Wireless1
Spread spectrum radio at 900MHz2 and 2.4GHz2
General I/O Terminations
6-pole removable terminal block, 12 to 22AWG, 15A contacts
Dimensions
5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep
Packaging
Corrosion resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input
• • • • • • •
Warranty
3 years on parts and labor
11 - 30VDC, 15mW at 12V during Sleep 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled Add 800mW when enabling LAN Add 190mW when enabling USB Add 25 to 100mW when enabling the LEDs 8.5W at 24V maximum, 5V supply fully loaded
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. • UL Std. No. 1604 - Hazardous (Classified) Locations.
Hazardous Locations - Europe
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations
IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
07
Product Data Sheet SCADAPack 334 Specifications
P334: 5210 controller board and integrated 5607 I/O board Controller Processors
• CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer • Microcontroller co-processor, 20 MHz clock
Memory
16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volalite RAM
CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity
465k words
I/O Analog Inputs
8, 0-20/4-20mA / 0-5/0-10V (15-bit) software configurable
Analog Outputs
• Standard: None • 2, 0-20/4-20mA (12-bit) with optional 5305 on 5607 I/O board
Digital I/O
• 16, 12/24V, 48V, 115/125V, 240V digital inputs • 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive), DC solid state rating: 3A, 60 VDC
Counter Inputs
1, 0-10Hz or 0-5kHz (dry contact); 2, 0-10kHz (turbine or dry contact)
Communications Serial Ports COM1, COM2
• RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or • RS-485 port, 2-wire, half duplex
Serial Port COM3
RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
Ethernet Port
RJ45, 10/100BaseT
Ethernet Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols
IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port
USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port
USB 2.0 compliant “B”-type receptacle
Wireless
Spread spectrum radio at 900MHz2 and 2.4GHz2
1
General I/O Terminations
5, 6 and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions
5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power 5210 Controller Board
• • • • • • •
11 - 30VDC, 15mW at 12 V during Sleep 500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled 300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled Add 800mW when enabling LAN Add 190mW when enabling USB Add 25 to 100mW when enabling the LEDs 8.5W at 24V maximum, 5V supply fully loaded
5607 I/O Module
• 11 - 30VDC, 10.3mA plus analog outputs • 325mA (max.) at 5V required from 5210 controller board
Warranty
3 years on parts and labor
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. • UL Std. No. 1604 - Hazardous (Classified) Locations.
Hazardous Locations - Europe
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations
IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
08
Product Data Sheet SCADAPack 330 | 334 Model Code
TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation
Model
Select: Controller
TBUP330
SCADAPack 330, 32 Bit controller, 3 Accumulators
TBUP334
SCADAPack 334, with Model 5607 I/O board, comes with above I/O plus 8 Analog I/P, 16 Digital I/P and 10 Digital O/P
Code 1
Code A
Future Option None
Select: Gas Flow Run-Time Option None Flow Computer Runs
G
2 Run Gas Flow
F
4 Run Gas Flow
V
2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
W
4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
Code 2
Code
Select: Protocol Option Modbus and DNP 3.0 (Level 2) protocol emulation
Select: Programming Environment
0
Telepace Ladder Logic and C Language firmware loaded - IEC enabled (Programming Tools sold separately)
1
IEC 61131-3 and C Language firmware loaded - Telepace enabled (Programming Tools sold separately)
Code A
Code
Select: Analog Inputs P330: None – P334: 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Select: Digital Inputs/Outputs
A
P330 - None
B
P334 - 16 DI (12/24V) and 10 dry contact relays
D
P334 - 16 DI (120V) and 10 dry conta ct relays
F
P334 - 16 DI (12/24V) and 10 DC solid state relays, ATEX and IECEx certification
H
Code
P334 - 16 DI (120V) and 10 solid state relays
Select: Analog Outputs
0
None
1
P334 only - 2 channel analog output option, 0 - 20mA
Model codes continue on next page
09
Product Data Sheet SCADAPack 330 | 334 Model Code
TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation
Code 0
Select: Integrated Communication Interfaces None FreeWave & MDS Radios (requires one RS232 port)
1
900Mhz FreeWave Spread Spectrum Radio
A
900MHz MDS Spread Spectrum Radio Trio Radios - 900MHz (requires one RS232 port)
B
900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C
900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D
900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E
900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios - 2.4GHz (requires one RS232 port)
J
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
10
Product Data Sheet SCADAPack 350 Specifications
P350: 5209 controller board only Controller Processors
• CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer • Two Microcontroller co-processors, 20 MHz clock
Memory
16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM
CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity
465k words
I/O Analog Inputs
• 5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit) • 1, 0-32.7VDC (15-bit)
Analog Outputs
• Standard: None • 2, 0-20/4-20mA (12-bit) with optional 5305
Digital I/O
8, user selectable as dry contact inputs or open drain outputs
Counter Inputs
• 1, 0-10Hz (dry contact) • 2, 0-10kHz (turbine or dry contact)
Communications Serial Port COM1
RS-485 port, 2-pole removable terminal block, 2-wire, half duplex
Serial Port COM2
• RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or • RS-485 port, 2-wire, half duplex
Serial Port COM3
RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
Ethernet Port
RJ45, 10/100BaseT
Ethernet Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols
IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port
USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port
USB 2.0 compliant “B”-type receptacle
Wireless
Spread spectrum radio at 900MHz2 and 2.4GHz2
1
General I/O Terminations
6 and 12- pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions
8.40 inch (213mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep
Packaging
Corrosion resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input
• • • • • •
Voltage Converter
12VDC to 24VDC
Warranty
3 years on parts and labor
11 - 30VDC, 12mW at 12V during Sleep 510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled. 320mW at 12V during reduced power mode operation. 12MHz., LEDs off, no expansion, LAN and USB disabled 1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled Add 25 to 100mW when enabling the LED 12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. • UL Std. No. 1604 - Hazardous (Classified) Locations.
Hazardous Locations - Europe
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations
IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
11
Product Data Sheet SCADAPack 357 Specifications
P357: 52O9 controller board and integrated 56O6 I/O board Controller Processors
• CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer • Microcontroller co-processor, 20 MHz clock
Memory
16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM
CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity
465k words
I/O Analog Inputs
• 5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit) • 1, 0-32.7VDC (15-bit) ; 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software configurable
Analog Outputs
• Standard: None • 2, 0-20/4-20mA (12-bit) with optional 5305 on 5209 controller board • 2, 0-20/4-20mA (12-bit) with optional 5305 on 5606 I/O board
Digital I/O
• 8, user selectable as dry contact inputs or open drain outputs • 32, 12/24V, 48V, 115/125V, 240V digital inputs; 16, relay outputs - dry contact or DC solid state
Counter Inputs
1, 0-10Hz (dry contact); 2, 0-10kHz (turbine or dry contact)
Communications Serial Port COM1
RS-485 port, 2-pole removable terminal block, 2-wire, half duplex
Serial Port COM2
• RS-232 port, 8-pin modular RJ45 jack, full or half duplex RS-232, or • RS-485 port, 2-wire, half duplex
Serial Port COM3
RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
Ethernet Port
RJ45, 10/100BaseT
Ethernet Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Network Protocols
IP, ARP, TCP, TFTP, UDP and ICMP
USB Host Port
USB 2.0 compliant “A”-type receptacle, provides up to 100mA at 5V
USB Peripheral Port
USB 2.0 compliant “B”-type receptacle
Wireless1
Spread spectrum radio at 900MHz2 and 2.4GHz2
General I/O Terminations
5, 6, 9, 10 and 12-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions
8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant zinc-plated steel with black enamel paint
Environment Power
5% RH to 95%, non-condensing, –40°C (–40°F) to 70°C (158°F)
5209 Controller Board
• • • • • •
5606 I/O Module
• 600mA (max.) at 5V required from 5209 controller board • 11 - 30VDC, 12mA plus analog outputs
Voltage Converter
12VDC to 24VDC
Warranty
3 years on parts and labor
11 - 30VDC, 12mW at 12V during Sleep 510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled 320mW at 12V during normal operation. 12MHz., LEDs off, no expansion, LAN and USB disabled 1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled Add 25 to 100mW when enabling the LEDs 12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. • UL Std. No. 1604 - Hazardous (Classified) Locations.
Hazardous Locations - Europe
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations
IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless version
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
12
Product Data Sheet SCADAPack 350 | 357 Model Code
TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation
Model
Select: Controller
TBUP350
SCADAPack 350 , 32 Bit controller, 5 Analog Inputs, 8 configurable Digital I/O, 3 Accumulators
TBUP357
SCADAPack 357, with Model 5606 I/O board, comes with above I/O plus 8 Analog I/P, 32 Digital I/P and 16 Digital O/P
Code 1
Code A
Future Option None
Select: Gas Flow Run-Time Option None Flow Computer Runs
G
2 Run Gas Flow
F
4 Run Gas Flow
V
2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
W
4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
Code 2
Code
Select: Protocol Option Modbus and DNP 3.0 (Level 2) protocol emulation
Select: Programming Environment
0
Telepace Ladder Logic and C Language firmware loaded - IEC enabled (Programming Tools sold separately)
1
IEC 61131-3 and C Language firmware loaded - Telepace enabled (Programming Tools sold separately)
Code A
Code
Select: Analog Inputs P350: 5 selectable as 0-10V or 0-20mA inputs. P357: adds another 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Select: Digital Inputs/Outputs
A
P350 - 8 configurable Digital I/O, individually selectable as DI (Dry Contact) or DO (Open Drain)
B
P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Dry Contact Relay Outputs on 5606 I/O board
D
P357 - Includes P350 I/O plus 32 DI (120V) and 16 Dry Contact Relay Outputs on 5606 I/O board
F
P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Solid State Relay Outputs on 5606 I/O board, ATEX and IECEx certification
H
P357 - Includes P350 I/O plus 32 DI (120V) and 16 Solid State Relay Outputs on 5606 I/O board
Code
Select: Analog Outputs
0
None
1
P350 or P357 - 2 channel analog output option, 0 - 20mA (P357 - 2 channel A/O option on the 5606)
2
P357 only - 4 channel analog output option, 0 - 20mA (consists of the 2 channel A/O option board on both modules)
Model codes continue on next page
13
Product Data Sheet SCADAPack 350 | 357 Model Code
TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation
Code 0
Select: Integrated Communication Interfaces None FreeWave & MDS Radios (requires one RS232 port)
1
900Mhz FreeWave Spread Spectrum Radio
A
900MHz MDS Spread Spectrum Radio Trio Radios - 900MHz (requires one RS232 port)
B
900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C
900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D
900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)
E
900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios - 2.4GHz (requires one RS232 port)
J
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
14
Product Data Sheet SCADAPack 32 Specifications
P4A, integrated 56O4 I/O board Controller Processor
Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer
Memory
8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM
Non Volatile RAM
CMOS RAM with lithium battery retains contents for 2 years with no power
I/O Analog Inputs
• 8, user selectable 0 - 10V (15 bit) or 0 - 20mA (14 bit) • 1, 0 - 32.678V (10 bit)
Analog Outputs
2 with optional 5305 analog output module, output range 0-20mA
Digital Inputs
4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation
Digital Outputs
1, 30V / 60mA (used as status output)
Digital I/O (5604 I/O board)
32 configurable as input or output (1 Amp DC max output / dry contact input)
Communications Serial Port COM1
Configurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex
Serial Ports COM2, COM4
• RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control • Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Serial Port COM3
Located on 5604 I/O module. Same specifications as COM2 and COM4
Baud Rates COM1, COM2, COM4
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Baud Rate COM3
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1, PPP
Ethernet Port
RJ45, 10BaseT
Network Protocols
IP: ARP, TCP, TFTP, UDP, ICMP
Ethernet Port Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Wireless1
Spread spectrum radio at 900MHz2 and 2.4GHz2
General I/O Terminations
6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions
8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input
11 - 30 VDC, 4.3W typical (10.8W full I/O capacity in use )
Warranty
3 years on parts and labor
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations • UL Std. No. 1604 - Hazardous (Classified) Locations
Safety
CSA (cCSAus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment, Industrial Control Equipment) UL (cULus) listed: UL508 (Industrial Control Equipment)
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
15
Product Data Sheet SCADAPack 32 Specifications
P4, integrated 56O1A I/O board Controller Processor
Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer
Memory
8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM
Non Volatile RAM
CMOS RAM with lithium battery retains contents for 2 years with no power
I/O Analog Inputs
8, user selectable 0 - 5V (15 bit) or 0 - 20mA (14 bit)
Analog Outputs
2 with optional 5303 analog output module, output range 0-20mA
Digital Inputs
• 4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation • 16 on 5601A I/O module - 6.5mA typical at 24V and 3.5mA typical at 115V
Digital Outputs
• •
1 on controller board , 30V, 60mA (used as status output) 12 on 5601A I/O module - Sealed mechanical relay: • 0.4A at 125 Vrms, 2A at 30V resistive loads • 1.0A at 30V, 0.2A at 125Vrms inductive load with pf=0.4, L/R=7ms • 250Vrms, 220V maximum operating voltage
Communications Serial Port COM1
Configurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex
Serial Ports COM2, COM4
RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control. Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Serial Port COM3
Located on 5601A I/O module. Same specifications as COM2 and COM4
Baud Rates COM1, COM2, COM4
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Baud Rate COM3
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1, PPP
Ethernet Port
10BaseT, RJ45
Network Protocols
IP:ARP, TCP, TFTP, UDP, ICMP
Ethernet Port Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Wireless
Spread spectrum radio at 900MHz2 and 2.4 GHz2
1
General I/O Terminations
6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions
8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input:
11 - 30 VDC, 3.5W typical all relays off, 6.5W typical all relays on
Warranty
3 years on parts and labor
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations • UL Std. No. 1604 - Hazardous (Classified) Locations
Safety
CSA (cCSAus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment, Industrial Control Equipment) UL (cULus) listed: UL508 (Industrial Control Equipment)
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
16
Product Data Sheet SCADAPack 32 Specifications
P4B, integrated 56O6 I/O board Controller Processor
Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer
Memory
8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM
Non Volatile RAM
CMOS RAM with lithium battery retains contents for 2 years with no power
I/O Analog Inputs
8, single-ended, software selectable 0-5V / 0-10 V or 0-20mA / 4-20mA (15 bit resolution)
Analog Outputs
2 with optional 5305 analog output module, output range 0-20mA
Digital Inputs
4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation, 32 on 5606 I/O module: • 0.67 mA typical at 24V on the 12/24V range • 0.37 mA typical at 48V on the 48V range • 0.35 mA typical at 120V on the 115/125V range • 0.35 mA typical at 240V on the 240V range
Digital Outputs
1 on controller board, 30V, 60mA (used as status output) 16 relay outputs on 5606 I/O module - dry contact or DC solid state: • Dry contact rating: 3A, 30VDC or 240VAC (Resistive) • DC solid state rating: 3A, 60 VDC
Communications Serial Port COM1
Configurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex
Serial Ports COM2, COM4
RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Baud Rates COM1, COM2, COM4
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1, PPP
Ethernet Port
RJ45, 10BaseT
Network Protocols
IP: ARP, TCP, TFTP, UDP, ICMP
Ethernet Port Protocols
Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP
Wireless
Spread spectrum radio at 900MHz2 and 2.4 GHz2
1
General I/O Terminations
5, 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions
8.40 inch (213mm) wide, 6.48 inch (164mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
Power Input:
11 - 30 VDC, 4.3W typical (10.8W full I/O capacity in use )
Warranty
3 years on parts and labor
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 UL Listed and CSA certified to the following standards: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations • UL Std. No. 1604 - Hazardous (Classified) Locations
Hazardous Locations Europe
Model “5606 SSR, 24DI version only” ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) Does not include Wireless versions.
Hazardous Locations
Model “5606 SSR version only” IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
17
Product Data Sheet SCADAPack 32 Model Code
TBUP4-102-02-0-0 represents a sample code for a P4 with DNP, 0-5V inputs, 12-24V outputs
Model
Select: Controller
TBUP4
SCADAPack 32, 32 Bit controller with Integrated Ethernet Port
Code
Select: Lower I/O Module 5601A lower I/O module, includes 16 Digital Inputs, 12 Digital Outputs and 8 Analog Inputs (see options below)
A
5604 lower I/O module, includes 32 configurable Digital I/O and 8 selectable Analog Inputs (0-10v or 0-20mA)
B
5606 lower I/O module, includes 32 D/I, 16 Dry Contact D/O and 8 software configurable A/I
C
5606-A lower I/O module, includes 32 D/I, 16 Solid State Relay D/O and 8 software configurable A/I
N
No lower I/O module (provides controller module only)
Code 1
Select: Communications Serial Ports TBUP4/P4A/P4N: 3 RS232, 1 RS232/485, 1 Ethernet TBUP4B/P4C: 2 RS232, 1 RS232/485, 1 Ethernet Integrated FreeWave & MDS Radios (requires one RS232 port)
A
900Mhz FreeWave Spread Spectrum Radio Consult CMI for availability in your market area
3
900MHz MDS Spread Spectrum Radio
Consult CMI for availability in your market area
Trio Radios - 900MHz (requires one RS232 port) B
900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C
900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D
900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E
900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios - 2.4GHz (requires one RS232 port)
J
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L
Code 0
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Select: Gas Flow Run-time Option None Flow Computer Runs
G
2 Run Gas Flow
F
4 Run Gas Flow
T
10 Run Gas Flow Flow Computer Runs - Gas Transmission Version (Requires Realflo 6.72+)
V
2 Run Gas Flow
W
4 Run Gas Flow
Code 2 5
Code
Select: Protocol Option/Programming Environment Modbus and DNP 3.0 (Level 2) protocol with Telepace Ladder Logic and C Language firmware loaded - IEC enabled Modbus and DNP 3.0 (Level 2) protocol with IEC 61131-3 and C Language firmware loaded - Telepace enabled
Select: Analog Inputs
01
0-20mA, single ended (On TBUP4 & TBUP4A, Default on TBUP4B which is software configurable to 0-5v or 0-10v)
02
0-5 volt, single ended (TBUP4 Only)
03
0-10 volt, single ended (TBUP4A Only)
Code
Select: Digital Inputs/Outputs
0
24 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: SS Relay D/O TBUP4A: Config I/O TBUP4N: No I/O
1
120 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: Solid State Relay D/O (Not for TBUP4A or TBUP4N)
Code
Select: Analog Outputs
0
None (required for TBUP4N)
1
2 channel Analog Output option, 0-20 mA
18
Product Data Sheet SCADAPack 100 Specifications
SCADAPack 100 Controller Processors
• 16-bit CMOS micro-controller, 14.74MHz clock, integrated watchdog timer • micro-controller co-processor: 14.74MHz clock
Memory
• 256KBytes CMOS RAM (controller ID number A182921 or less) • 1024KBytes CMOS RAM (controller ID number A182922 or greater) • 512kBytes flash ROM, 1kBytes EEPROM
Non-volatile RAM
CMOS RAM with lithium battery retains contents for 2 years with no power
I/O Analog Inputs
• 3 at 5V/20mA: 250W resistance user configurable with jumper link • 1 at 32.768V
Resolution
12 bits over the 5V and 32.768V measurement range
Digital I/O
6 points, each point is an input and an output, dry contact input, 1.0A max output rating
Counter Inputs
1, maximum frequency 5kHz, dry contact input, wetting current typically 5mA with 24V input power
Communications Communication Port COM1
RS-485 serial port, 2 pole removable terminal block, 2 wire half duplex, bias resistors installed
Communication Port COM1
RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex, implemented Td, Rd, +5V
Communication Port COM2
RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex with RTS/CTS control, implemented Td, Rd, CTS, RTS, DCD, DTR, +5V
Baud Rates COM1 & COM2
300, 600, 1200, 2400, 4800, 9600, 19200, 38400
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
Wireless1
Spread spectrum radio at 900MHz2 and 2.4GHz2
General I/O Terminations
5 and 12 pole, removable terminal blocks. 12 to 22 AWG 15A contacts Screw termination 6 lb.-in. (0.68 Nm) torque
Dimensions
5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, –40°C (–40°F) to 70°C (158°F)
DC Power Input:
30V maximum, 10.0 to 11.5V turn on, 9.5V typical turn off, UL508 rated 13.75-28Vdc. Class 2, less than 500mW (at 12V) LEDs off, 2.9W maximum
Output Capacity
5V at 0.425A capacity, 5V at 0.060A required by 5208 controller, 5V at 0.365A available on COM1 and COM2
Warranty
3 years parts and labor
Certifications Hazardous Locations North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 per CSA Std C22.2 No. 213-M1987 / UL1604 UL listed and CSA certified to the following standards: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations • UL Std. No. 1604 - Hazardous (Classified) Locations
Hazardous Locations
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) Does not include Wireless versions
Safety
CSA (cCSAus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment, Industrial Control Equipment) UL (cULus) listed: UL508 (Industrial Control Equipment)
1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
19
Product Data Sheet SCADAPack 100 Model Code
TBUP100-1A20-AA00 represents a sample code for a TBUP100 with DNP, 0-5V inputs
Model
Select: Controller
TBUP100
SCADAPack 100, comes with 3 Analog Inputs, 6 configurable Digital I/O, 1 Accumulator
TBUP110
SCADAPack 100, Gas Flow Controller with 1 Gas Flow Run (I/O as above)
Code 1
Code A
Code 2
Code
Select: Communication Serial Ports 2 Communication Ports (RJ45 Type) : 1 RS-232 and 1 RS232/485
Select: Memory Configuration 1 MB CMOS RAM (512K OS, 512K APP), 512K FLASH ROM
Select: Protocol Option Modbus and DNP 3.0 (Level 2) protocol emulation
Select: Programming Environment
0
Telepace Ladder Logic and C Language firmware loaded - IEC enabled (Programming Tools sold separately)
1
IEC 61131-3 and C Language firmware loaded - Telepace enabled (Programming Tools sold separately)
Code A
Code A
Code 0
Code 0
Select: Analog Inputs 3 Analog Inputs, individually selectable as 0-20mA or 0-5 volts
Select: Digital Inputs/Outputs 6 configurable Digital I/O, individually selectable as Digital Input (Dry Contact) or Digital Output (Open Drain)
Select: Analog Outputs None
Select: Integrated Communication Interfaces None FreeWave & MDS Radios (requires one RS232 port)
1
900Mhz FreeWave Spread Spectrum Radio – consult CMI for availability in your market area
A
900Mhz MDS Spread Spectrum Radio – consult CMI for availability in your market area Trio Radios - 900MHz (requires one RS232 port)
B
900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C
900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D
900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)
E
900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios - 2.4GHz (requires one RS232 port)
J
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
20
Product Data Sheet 5502 – Differential analog input module Specifications
5502 Differential analog input module General Input Points
8: voltage or current inputs, each input is switch selectable as voltage or current
Ranges
Voltage -10V to +10V, Current -20mA to +20mA
Resolution
Voltage 1.22mV, Current 4.88µA
Input Resistance
Voltage > 10MΩ, Current 250Ω
Converter Type
13-bit plus sign successive approximation
Accuracy
• +/- 0.1% of full scale at 25°C (77°F) • +/- 0.2% of full scale over temperature range
Isolation
• 550VAC from any input to the chassis or the system power supplies. • 140VAC/200VDC between inputs
Common Mode Rejection
• >96dB at 50/60Hz, >50dB at 10KHz. with 1KΩ imbalance • >50dB at 1KHz. with 10KΩ imbalance
Normal Mode Rejection
>45dB at 50/60Hz
Transient Protection
• Transient suppressors and fuses on each input • 2.5kV surge withstand capability as per ANSI/IEEE, C37.90.1-1989
Over-Scale Input Capacity
12VDC maximum. Exceeding 12V will cause the fuse to blow.
Input Fuses
1/8 Amp.
Reading Update Time
170ms with 60Hz. rejection selected. 185mS with 50Hz rejection selected.
Power Requirements
5V @ 100mA
Terminations
2: 8 pole, removable terminal blocks, 12 - 22 AWG, 15A contacts
Dimensions
144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
Class 1, Division 2 for use in hazardous locations
Part Number
TBUX297211
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
21
Product Data Sheet 5504 – Thermocouple input module Specifications
5504 Thermocouple input module General Input Points
8 thermocouples or millivolt signals
Thermocouple Types and Ranges
J: K: E: T: mV
Resolution
0.004mV, approximately 0.10°C (0.18°F)
Input Resistance
1MΩ
Accuracy Over -40°C to 60°C Operating Temperature Range
J: K: E: T: mV
Cold Junction Compensation
• ±0.5°C (0.9°F) maximum error from 0°C to 60°C (32°F to 140°F) • ±1°C (1.8°F) maximum error from -40°C to 0°C (-40°F to 32°F)
Converter Type
±20000 count, integrating
Common Mode Voltage Range
±10V can be applied to the inputs, relative to the -24V power supply input
Isolation
500VAC from the logic power
Transient Protection
MOVs on each input
Response Time
0.5 seconds
Power Requirements
• > 5V @40mA • > 20 to 28V @ 45mA
Terminations
10 pole and 8 pole, two fixed terminal blocks, 12 - 22 AWG, 15 amp contacts
Dimensions
144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
Class 1, Division 2 for use in hazardous locations
Part Number
TBUX297166
-200°C to 760°C (-328°F to 1400°F) -270°C to 1370°C (-454°F to 2498°F) -270°C to 1000°C (-454°F to 1832°F) -270°C to 400°C (-454°F to 752°F) ±80mV
±0.20% of full scale ±0.20% of full scale ±0.15% of full scale ±0.50% of full scale ±0.15% of full scale
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
22
Product Data Sheet 5505 – RTD input module Specifications
5505 RTD input module General Input Points
4, RTD
RTD Type
100-ohm platinum, 3 and 4-wire, auto-detection and compensation
Calibration
0.00385Ω/ Ω /°C standard based on ASTM E 1137/E 1137M-04, ITS-90
Ranges
5505: Can be configured to return data in ohms, °C, °F or °K • -200°C to 800°C (-328°F to 1472°F) • 0 to 500Ω 5503 Emulation: Dipswitch selectable • 0°C to 200°C (32°F to 392°F) • -100°C to 100°C (-148°F to 212°F) • -200°C to 0°C (-328°F to 32°F) • 0°C to 800°C (32°F to 1472°F) • 0°C to 400°C (32°F to 752°F) • 0 to 400Ω
Data Format
• 5505: 32-bit floating point and 12 status bits • 5503 Emulation: 16-bit signed integer
Resolution
• 5505: > 17-bit effective • 5505 Emulation: 15-bit
RTD Status
• • • •
Accuracy on RTD Ranges
Percent of full scale over operational temperature range including linearization errors: +0.10%/-0.05%
Accuracy on 0 to 500ohms
Percent of full scale over operational temperature range: ±0.03%
Excitation Current
4mA, 7.2% duty cycle in 4-wire mode, 14.4% in 3-wire mode, 250ms scan interval
Line Resistance
100Ω max., in each line
Converter Type
24-bit delta-sigma
Response Time
380ms typical for 10% to 90% signal change at minimum filter setting
Transient Protection
2.5kV surge-withstand capability as per ANSI/IEEE C37.90.1-1989
Isolation
Isolation from logic supply and chassis, voltage 500Vrms
5V Power Requirements
6mA
11 - 30VDC Power Requirements
12V operation: 4mA • plus 0.6mA per 4-wire RTD • plus 1.2mA per 3-wire RTD 24V operation: 2.2mA • plus 0.3mA per 4-wire RTD • plus 0.6mA per 3-wire RTD
11-30VDC - Connector
Removable. Shared with RTD inputs 0-1
11-30VDC - Isolation
Isolation from logic supply and chassis
Terminations
8 and 10 pole, removable terminal block,12 to 22 AWG, 15A contacts
Dimensions
74mm wide x 124mm high x 45mm deep (2.9in. x 4.9in. x 1.8in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F) operation, -40°C to 85°C (-40°F to 185°F) storage
Safety
• Non-Incendive Electrical Equipment for Use in Class I, Division2 • Groups A, B C and D Hazardous Locations • ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)
Part Number
TBUX297318
RTD is good (not open) RTD in range RTD 3 or 4-wire RTD status not available in 5503 Emulation
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
23
Product Data Sheet 5506 – Analog input module Specifications
5506 Analog input module General Input Points
8
Ranges
• • • •
LED Indicators
8 red LEDs, indicating current input, voltage input and under or over-range signal applied
Input Configuration
Individual inputs configurable with 4mA/1V (20%) offset and for voltage/current operation when configured as a 5506. All inputs dipswitch-selectable with 4mA/1V (20%) offset and for voltage/current operation when configured to emulate a 5501 module.
Input Resistance
250 ohms - Current configuration ; 66k ohms - Voltage configuration
Resolution
15-bits over the 0-5V and 0-20mA measurement range
Type
Single-ended
Accuracy
±0.1% of full scale at 25°C (77°F) ; ±0.2% over temperature range
Transient Protection
2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Normal Mode Rejection At 60 Hz with 60Hz Scanning
• • • •
53dB with 3Hz filter 50dB with 6Hz filter 49dB with 11Hz filter 45dB with 30Hz filter
Normal Mode Rejection At 50 Hz with 50Hz Scanning
• • • •
73dB with 3Hz filter 56dB with 6Hz filter 52dB with 11Hz filter 49dB with 30Hz filter
Response Time for 10% to 90% Signal Change (60Hz Scanning)
• • • •
250ms with 3Hz filter 130ms with 6Hz filter 60ms with 11Hz filter 30ms with 30Hz filter
Response Time for 10% to 90% Signal Change (50Hz Scanning)
• • • •
300ms with 3Hz filter 140ms with 6Hz filter 80ms with 11Hz filter 40ms with 30Hz filter
Over-Scale Input Capacity (without damage)
Continuous: 0.10A/14V on the 20mA inputs ; 0.05A/14V on the 5V inputs
Isolation
500Vac isolation from logic supply and chassis
5V Power Requirements
• 22mA, LEDs off • 45mA, LEDs on
11-30VDC Power Requirements
11mA
11-30VDC - Connector
Removable, 4 positions
11-30VDC - Isolation
Isolation from logic supply and chassis
Terminations
10 pole, removable terminal block,12 to 22 AWG, 15A contacts
Dimensions
2.9 inch (74 mm) wide, 4.9 inch (124 mm) high, 1.8 inch (45 mm) deep
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F) operation, -40°C to 85°C (-40°F to 185°F) storage
Safety
• Non-Incendive Electrical Equipment for Use in Class I, Division2 • Groups A, B C and D Hazardous Locations • ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)
Part Number
TBUX297319
0-20mA 4-20mA 0-5V 1-5V
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
24
Product Data Sheet 5302 – Analog output module Specifications
5302 Analog output module General Output points
4 ( 2 when used with 5201 and 5201 controllers)
Output signal ranges
0-20mA or 4-20mA, switch configurable
Output Type
Single ended regulation on positive side with common negative return
Maximum Load Resistance
1000W with 24VDC loop power, 400W with 12VDC loop power , 250Wwith 9VDC loop power
Isolation
1500VAC field to logic
D/A Resolution
12-bit over the 0-20mA ranges
Absolute Accuracy
+/- 0.05% of full scale at 25ºC (77ºF), +/- 0.2% of full scale over temperature range
Noise and Ripple
0.04% maximum
Transient Protection
2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Response Time
250ms typical for 10% to 90% signal change
Addressing
DIP switch configurable
Power Requirements
5V @ 45mA, 9 - 30V @ 15mA quiescent plus 80mA max.
Terminations
10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297176
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
25
Product Data Sheet 5304 – Analog output module Specifications
5304 Analog output module General Output points
4
Output Modes
• Current mode, jumper link selectable • Voltage mode, 5V full scale, jumper link selectable, • Voltage mode, 10V full scale, jumper link selectable
Output signal ranges
• 0-20mA or 4-20mA, switch configurable • 0-5V or 1-5V, switch configurable, 0-10V or 2-10V, switch configurable
Output Type
Single ended regulation on positive side with common negative return
Maximum Load Resistance
1000Ω with 24VDC loop power, 400Ω with 12VDC loop power, 250Ω with 9VDC loop power
Minimum Load Resistance in Voltage Mode
• 2kΩ for 10V full scale, with min 20VDC power applied • 1kΩ for 5V full scale, with min 15VDC power applied
Isolation
500VAC field to logic
D/A Resolution
12-bit over the 0-20mA / 0-5V/ 0-10V ranges
Absolute Accuracy
+/- 0.05% of full scale at 25ºC (77ºF), +/- 0.2% of full scale over temperature range
Noise and Ripple
0.04% maximum
Transient Protection
• 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989 • Inductive load protection diodes included
Response Time
2ms typical to 90% signal change
Addressing
DIP switch configurable
12-24V Operating Voltage Limits
• 9V or (20mA x load resistance) +4V (whichever is greater) in current mode • (1.5 x Range / load resistance) + Range + 2.5V in voltage mode, 30V maximum
Power Requirements
• 6mA min., 25mA maximum • 15mA quiescent plus 80mA max. in current mode • 15mA quiescent plus 20mA max. in voltage mode
Terminations
10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model
Part Number
Description
5304-20
TBUX297248
4 channel isolated analog output module, 0-20mA
5304-10
TBUX297252
4 channel isolated analog output module, 0-10 volts
5304-5
TBUX297253
4 channel isolated analog output module, 0-5 volts
5304-C
TBUX297254
4 channel isolated analog output module, Custom (specify range of each input)
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
26
Product Data Sheet 5403 – High level digital input module Specifications
5403 High level digital input module General Number of Digital Inputs
8
Input Logic-HI Level
OFF to ON transition threshold is typically 50% of full scale signal range
Over-Voltage Tolerance
150% sustained over-voltage without damage
Input Current
5mA typical
Response Time
• OFF to ON: 7ms typical • ON to OFF: 24ms typical
Isolation
1500VAC in groups of 4 inputs
Addressing
DIP switch configurable
Power Requirements
5V @ 45mA all LEDs ON, 5V @ 25mA with LEDs disabled
Visual Indicators
16: red LEDs controlled for power reduction
Field Terminations
• 1: 10 pole, removable terminal block • 12 to 22 AWG • 15A contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model
Part Number
Signal range
5403-12
TBUX297110
12 volts AC/DC
5403-24
TBUX297109
24 volts AC/DC
5403-48
TBUX297108
48 volts AC/DC
5403-120
TBUX297107
120 volts AC/DC
5403-240
TBUX297106
240 volts AC/DC
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
27
Product Data Sheet 5404 – High level digital input module Specifications
5404 High level digital input module General Number of Digital Inputs
16
Input Logic-HI Level
OFF to ON transition threshold is typically 50% of full scale signal range
Over-Voltage Tolerance
150% sustained over-voltage without damage
Input Current
5mA typical
Response Time
• OFF to ON: 7ms typical • ON to OFF: 24ms typical
Isolation
1500VAC in groups of 4 inputs
Addressing
DIP switch configurable
Power Requirements
5V @ 80mA all LEDs ON, 5V @ 25mA with LEDs disabled
Visual Indicators
16: red LEDs controlled for power reduction
Field Terminations
• 2: 10 pole, removable terminal block • 12 to 22 AWG • 15A contacts
Dimensions
144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model
Part Number
Signal range
5404-12
TBUX297158
12 volts AC/DC
5404-24
TBUX297157
24 volts AC/DC
5404-48
TBUX297156
48 volts AC/DC
5404-120
TBUX297155
120 volts AC/DC
5404-240
TBUX297154
240 volts AC/DC
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
28
Product Data Sheet 5405 – Digital input module Specifications
5405 Digital input module General Input Points
32
Ranges
12-24VDC, 16-24VAC, 120VAC/DC
Over-Voltage Tolerance
150% sustained over-voltage without damage
Input Current
• • • •
DC Input Logic Levels
• OFF to ON transition threshold is typically 7.5VDC on the 24VDC range • OFF to ON transition threshold is typically 55VDC on the 120VDC range
AC Input Levels
• OFF to ON transition threshold is typically 6VAC on the 24VAC range • OFF to ON transition threshold is typically 45VAC on the 120VAC range
Transient Protection
2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Isolation
• Isolated in 4 groups of 8. Inputs 0-15 are on the bottom edge. • Inputs 16-31 are on the top edge. Isolation 500VAC/DC from chassis and logic ground
Power Requirements
5V @ 10mA with all inputs ON
Terminations
4: 9 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts
Dimensions
144mm wide x 127mm high x 45mm deep (5.65in. x 5.00in. x 1.88in.)
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Addressing
Configurable with 4 DIP switches
AC/DC Operation
2: DIP switches determine AC/DC and 50/60Hz operation
Visual Indicators
32: Red LED’s, field powered. Cannot be disabled to conserve power
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model
Part Number
Description
5405-120
TBUX297249
32 point, 120V discrete input module
5405-24
TBUX297247
32 point, 12-24V discrete input module
6.0mA typical @ 24VDC on the 24V range 3.5mA typical @ 24VAC on the 24V range 2.5mA typical @ 120VDC on the 120V range 1.5mA typical @ 120VAC on the 120V range
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
29
Product Data Sheet 5410 – High speed counter/accumulator Specifications
5410 High speed counter/accumulator General Counter Input Points
4
Count Length
32-bit, range is 0 to 4,294,967,295
Over-Voltage Protection
Transient suppressor on each input
Input Voltage Range
Typical operating inputs 5 to 24V, 3V minimum, 28V maximum
Input Current
8mA typical, 13mA maximum
Input Logic Level
OFF to ON threshold is typically 2V
Maximum Input Frequency
10kHz with filters off, 5kHz with quadrature counters, 60Hz with de-bounce filters on
Maximum Pulse High Width
• 50 microseconds (μs), 100μs with quadrature counters • 8.3 milliseconds with de-bounce filters
Minimum Pulse Low Width
• 50 microseconds (μs), 100μs with quadrature counters • 8.3 milliseconds with de-bounce filters
Isolation
500VAC input to input, 500VAC input to logic circuit
Addressing
DIP switch configurable
Terminations
8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Visual Indicators
• 4: red LEDs • LED on time stretched for easy viewing controlled for power reduction
Power Requirements
5V @ 35mA with all LEDs on, 5V @ 15mA with LEDs disabled
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
Class 1, Division 2 for use in hazardous locations
Part Number
TBUX297149
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
30
Product Data Sheet 5414 – Compact digital input module Specifications
5414 Compact digital input module General Number of Digital Inputs
16
Ranges
Factory configurable as: • 12/24V • 48V • 115/125V • 240V
Input Current
• • • •
Over-voltage Tolerance
150% sustained over-voltage without damage
Power Requirements
• 5V@6mA with LEDs off • 5V@40mA with LEDs on
Visual Indicators
Logic powered LEDs. Can be disabled to conserve power
Field Terminations
12 to 22 AWG, 15A contacts
Dimensions
74mm wide x 124mm high x 45mm deep (2.90in. x 4.90in. x 1.80in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
• 5% RH to 95% RH, non-condensing • –40ºC to 70ºC (–40ºF to 158ºF) operation • –40ºC to 85ºC (–40ºF to 185ºF) storage
Safety
• • • •
Model
Part Number
Signal Range
5414-24
TBUX297378
12/24V AC/DC, ATEX and IECEx
5414-48
TBUX297379
48V AC/DC (Not available outside of North America)
5414-120
TBUX297380
115/125V AC/DC (Not available outside of North America)
5414-240
TBUX297381
240V AC/DC (Not available outside of North America)
0.6 – 0.9mA at 24V on the 12/24V range 0.3 – 0.4mA at 48V on the 48V range 0.3 – 0.4mA at 120V on the 115/125V range 0.3 – 0.4mA at 240V on the 240V range
Class I, Division 2, Groups A, B, C and D and CSA certified to UL508 standards ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) (5414-24 only) Maximum permitted voltage in Canada or North America is 240VAC Maximum permitted voltage outside of Canada or North America is 30VAC/42.4PK/60VDC
Note: Module not supported on 16-bit SCADAPack platform (SCADAPack, SCADAPack Light, SCADAPack Plus, SCADAPack 100 and SCADAPack LP) Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
31
Product Data Sheet 5401 – Configurable digital I/O module Specifications
5401 Configurable digital I/O module General Number of Inputs or Outputs
8
Voltage Range
See relay specifications below
Load Current
See relay specifications below
Surge Current
See relay specifications below
Off-State Leakage
See relay specifications below
Transient Protection
Integral to the solid-state relay
Response Time
See relay specifications below
Isolation
1500VAC
Addressing
DIP switch configurable
Input/Output Assignment
DIP switch selection for each I/O point
Power Requirements
5V @ 90mA
Visual Indicators
8: red LEDs, permanently enabled
Field Terminations
2: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
TBUX297121
8-point input or output module (requires solid-state relays)
Model
Part Number
Solid-State Relays for use with Model 5401
IACM-5
TBUX297122
90-140 VAC/VDC input relay
IACM-5A
TBUX297132
180-280 VAC/VDC input relay
IACM-5E
TBUX297133
10-32VDC, 15-32VAC, no polarity
IDCM-5
TBUX297124
3-32VDC input relay
OACM-5
TBUX297123
24-140VAC output relay, 3A
OACM-5H
TBUX297134
24-280VAC output relay, 5A
ODCM-5
TBUX297125
3-60VDC output relay, 3A
ODCM-5A
TBUX297135
10-200VDC, 1A
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
32
Product Data Sheet 5402 – Configurable digital input or output module Specifications
5402 Configurable digital input or output module General Number of Inputs or Outputs
16
Voltage Range
See relay specifications below
Load Current
See relay specifications below
Surge Current
See relay specifications below
Off-State Leakage
See relay specifications below
Transient Protection
Integral to the solid-state relay
Response Time
See relay specifications below
Isolation
1500VAC
Addressing
DIP switch configurable
Input/Output Assignment
DIP switch selectable as all inputs or outputs
Power Requirements
5V @ 150mA
Visual Indicators
16: red LEDs, permanently enabled
Field Terminations
4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
Class 1, Division 2 for use in hazardous locations
Part Number
TBUX297153 - 16-point input or output module (requires solid-state relays)
Model
Part Number
Solid-State Relays for use with Model 5402
IACM-5
TBUX297122
90-140 VAC/VDC input relay
IACM-5A
TBUX297132
180-280 VAC/VDC input relay
IACM-5E
TBUX297133
10-32VDC, 15-32VAC, no polarity
IDCM-5
TBUX297124
3-32VDC input relay
OACM-5
TBUX297123
24-140VAC output relay, 3A
OACM-5H
TBUX297134
24-280VAC output relay, 5A
ODCM-5
TBUX297125
3-60VDC output relay, 3A
ODCM-5A
TBUX297135
10 - 200VDC output relay, 1A
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
33
Product Data Sheet 5406A – Dry contact relay out module Specifications
5406A Dry contact relay out module General Number of Relay Outputs
16
Type
Sealed mechanical relay, Form A (normally open) contacts
Contact Ratings
• 6A @ 250VAC resistive loads, 6A @ 30VDC resistive loads • 3.5A at 30VDC/250VAC inductive load (pf=0.4. L/R=7 ms), 1/4 HP 125VAC • 3A maximum in Class 1, Division 2 hazardous locations
Operating Frequency
18,000 operations/hour mechanically, 1,800 electrically at rated load
Service Life
• 1,500,000 operations at 0-250mA loads, 600,000 operations at 1A resistive load • 100,000 operations at 6A resistive load, 300,000 operations at 1A inductive loads (pf=0.4) • 100,000 operations at 3.5A inductive loads (pf=0.4)
Operate Time
10mS maximum, 5mS typical
Release Time
10mS maximum, 2mS typical
Bounce Time
3mS typical
Contact Isolation
1000VAC
Logic Isolation
1500VAC
Addressing
DIP switch configurable
Power Requirements
• 5V Bus Power - 5V @ 600mA with all LEDs and all relays energized • External Power - 5V @ 65mA with all LEDs and all relays energized
Visual Indicators
16: red LEDs, controlled for power reduction
Field Terminations
• 4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts • Additional three pins on connector P3 to support external power
Dimensions
215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297284
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
34
Product Data Sheet 5407 – Dry contact relay out module Specifications
5407 Dry contact relay out module General Number of Relay Outputs
8
Type
Sealed mechanical relay, Form A (normally open) contacts. Can be modified for Form B contacts.
Contact Ratings
• 6A @ 250VAC resistive loads, 6A @ 30VDC resistive loads • 3.5A at 30VDC/250VAC inductive load (pf=0.4. L/R=7 ms), 1/4 HP 125VAC • 3A maximum in Class 1, Division 2 hazardous locations
Operating Frequency
18,000 operations/hour mechanically, 1,800 electrically at rated load
Service Life
• 1,500,000 operations at 0-250mA loads, 600,000 operations at 1A resistive load • 100,000 operations at 6A resistive load, 300,000 operations at 1A inductive loads (pf=0.4) • 100,000 operations at 3.5A inductive loads (pf=0.4)
Operate Time
10mS maximum, 5mS typical
Release Time
10mS maximum, 2mS typical
Bounce Time
3mS typical
Contact Isolation
1000VAC
Logic Isolation
1500VAC
Addressing
DIP switch configurable
Power Requirements
5V @ 300mA all LEDs and all relays energized
Visual Indicators
8: red LEDs, controlled for power reduction
Field Terminations
2: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297126
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
35
Product Data Sheet 5408 – Triac digital output module Specifications
5408 Triac digital ouput module General Number of Triac Outputs
8
Output Voltage Range
24 to 240VAC, 47 to 63Hz
Load Current
0.75A at 60°C (140°F), 1.0A at 25°C (77°F)
Surge Current
55A for 1 cycle @ 60Hz
Triac Rating
600VAC @ 8.0A
Gate Control
Zero crossing turn ON/turn OFF
OFF-State Leakage
• 0.5mA typical, 0.75mA maximum at 115VAC • 1.0mA typical, 1.5mA maximum at 240VAC
Transient Protection
Integral 275V MOV on each output
Snubber
RC snubber on each output allows inductive loads
Response Time
1/2 AC cycle maximum, 8.3 ms @ 60Hz
Isolation
1500VAC
Addressing
DIP switch configurable
Power Requirements
• 5V @ 120mA with all LEDs and outputs turned on • 5V @ 80mA with LEDs disabled and all outputs turned on
Visual Indicators
8: red LEDs controlled for power reduction 1: green field power LED
Field Terminations
10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297103
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
36
Product Data Sheet 5409 – FET digital output module Specifications
5409 FET digital ouput module General Output Points
8
Output Voltage Range
12-24VDC
Load Current
2A continuous per output, 10A total
Surge Current
8A for 2ms
MOSFET Rating
50V, 12A
ON-State Voltage Drop
0.5V maximum at 2A
OFF-State Leakage
<1uA at 24V, 25°C
Transient Protection
Inductive load protection diodes included
Isolation
1500VAC
Addressing
DIP switch configurable
Power Requirements
• 5V @ 70mA with all LEDs and outputs turned on • 5V @ 40mA with LEDs disabled and all outputs turned on • 24V @ 30mA typical, 10V min., 32V max
Terminations
10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Visual Indicators
8: red LEDs, controllable by CPU for power reduction 1: green field power LED
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
Class 1, Division 2 for use in hazardous locations
Part Number
TBUX297117
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
37
Product Data Sheet 5411 – Digital output module Specifications
5411 Digital output module General Output Points
32
Output Rating
• 1.0A maximum • 0.35V maximum drop at 1.0A • 0.05V maximum drop at 0.1A
Transient Protection
• 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989 • Inductive load protection diodes included
Isolation
• Isolated in 2 groups of 16 • Isolation 500VAC/DC from chassis and logic ground
Terminations
• 2: 9 and two 10 pole, removable terminal blocks • 12 to 22 AWG, 15A contacts
Power Requirements
• • • •
Visual Indicators
32: Red LED’s, can be disabled to conserve power
Dimensions
144mm wide x 127mm high x 45mm deep (5.65in. x 5.00in. x 1.80in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 70°C (-40°F to 158°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297246
5V @ 150mA with all LEDs and outputs turned on 5V @ 40mA with all LEDs disabled and all outputs turned on 24V @ 5mA with all outputs ON 8V min. , 30V max
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
38
Product Data Sheet 5415 – Compact relay digital output module Specifications
5415 Compact relay digital output module General Number of Digital Outputs
12
Type
• Form A Contacts (Normally open), Dry Contact or Solid State Relay variants • 4 contacts per common
Contact Rating
• 12A maximum per common • Dry Contact Version: 3A, 30VDC or 250VAC (Resistive) • Solid State Relay Version: 60VDC max., 3A max. at 50°C (122°F), 2A max. at 70°C (158°F)
Switching Capacity (Dry Contact Version)
• 5A, 30VDC (150W Resistive) • 5A X 250VAC (1250VA Resistive)
5V Power Requirements
5mA Quiescent Dry Contact version: 150mA relays on, LEDs on 130mA relays on, LEDs off Peak current during off-to-on transition of any, or all relays 280mA total for 15ms duration Solid State Relay version: Relays on, LEDs on - 144mA Relays on, LEDs off - 120mA
10-30VDC Power Requirements
Dry Contact version: 1.0W maximum with 1.65W peak for 15ms durations Solid State Relay version: 1.0W maximum
Visual Indicators
Logic powered LEDs. Can be disabled to conserve power
Field Terminations
12 to 22 AWG, 15A contacts
Dimensions
74mm wide x 124mm high x 45mm deep (2.90in. x 4.90in. x 1.80in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
• 5% RH to 95% RH, non-condensing • –40ºC to 70ºC (–40ºF to 158ºF) operation • –40ºC to 85ºC (–40ºF to 185ºF) storage
Safety
• • • •
Model
Part Number
Signal Range
5415
TBUX297382
12 Point Compact Mechanical Relay Output Module
5415-A
TBUX297384
12 Point Compact Solid-State Relay Output Module, ATEX and IECEx
Class I, Division 2, Groups A, B, C and D and CSA certified to UL508 standards ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) (5415-A only) Maximum permitted voltage in Canada or North America is 240VAC Maximum permitted voltage outside of Canada or North America is 30VAC/42.4PK/60VDC
Note: Module not supported on 16-bit SCADAPack platform (SCADAPack, SCADAPack Light, SCADAPack Plus, SCADAPack 100 and SCADAPack LP) Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
39
Product Data Sheet 5606 – Analog/digital I/O module Specifications
5606 Analog/digital I/O module General Digital Input Points
• 32 • Factory configurable: 12/24V, 48V, 115/125V, 240V • 150% sustained over-voltage without damage
Digital Output Points
• • • •
16 Form A (Normally open) relay contacts Rating: 3A, 30Vdc or 240Vac (Resistive) 4 contacts per common
Analog Input Points
• • • • •
8 Single-ended Software configurable, 0-20mA, 4-20mA, 0-10V, 0-5V Resolution: 15-bit over the 0-10V and 0-20mA measurement range Accuracy: ±0.1% of full scale at 25°C (77°F), ±0.2% over temperature range
Analog Outputs
• • • • •
2 (with optional 5305 module) 0-20mA sourcing Resolution: 12-bit Accuracy: (specified from 0.5-20mA.), ±0.15% of full scale at 25°C (77°F) ±0.25% of full scale over temperature range
5V Power Requirements
• Digital Output Relays Continuous - 190mA, Digital Output Relays Peak - 375mA • LED’s - 195mA, Quiescent - 30mA • Total - 415 to 600mA
11-30VDC Power Requirements
• 12mA plus analog outputs • 9-30Vdc operation possible when optional 5305 analog outputs not installed
Addressing
8 modules, DIP switch-selectable
Dimensions
213mm wide x 155mm high x 72mm deep (8.40in. x 6.13in. x 1.80in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, –40°C to 70°C (–40°F to 158°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2), (24VDI/Solid State Relay type only)
Part Number
TBUX297328 TBUX297329 TBUX297330 TBUX297331 TBUX297334 TBUX297335 TBUX297336 TBUX297337 TBUX297498 TBUX297499 TBUX297500 TBUX297501 TBUX297502 TBUX297503 TBUX297504 TBUX297505
(5606-24) (5606-48) (5606-120) (5606-240) (5606-24-AO) (5606-48-AO) (5606-120-AO) (5606-240-AO) (5606-24-A) (5606-48-A) (5606-120-A) (5606-240-A) (5606-24-AO-A) (5606-48-AO-A) (5606-120-AO-A) (5606-240-AO-A)
Note: 5606 module is not supported by the Non-Programmable Controller Modules (Model 5201 & 5202) Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
40
Product Data Sheet 5607 – Analog/digital I/O module Specifications
5607 Analog/digital I/O module General Digital Input Points
• 16 • Factory configurable: 12/24V, 48V, 115/125V, 240V • 150% sustained over-voltage without damage
Digital Output Points
• 10 • Form A Contacts (Normally open) • Dry Contact Relay or DC Solid State Relay • 5 contacts per common Dry Contact Relay Version: • 3A, 30Vdc or 250Vac (Resistive) DC Solid State Relay Version: • 3A continuous maximum at 50ºC (122ºF) ambient TBC • 2A continuous maximum at 70ºC (158ºF) ambient TBC • 9A peak, 100ms
Contact Rataing
Analog Input Points
• • • • •
8 Single-ended Software configurable, 0-20mA, 4-20mA, 0-10V, 0-5V Resolution: 15 bits over the 0-10V measurement range, 14 bits over the 0-5V and 0-20mA measurement range Accuracy: ±0.1% of full scale at 25°C (77°F), ±0.2% over temperature range
Analog Outputs
• • • • •
2 (with optional 5305 module) 0-20mA sourcing Resolution: 12-bit Accuracy: (specified from 0.5-20mA.), ±0.15% of full scale at 25°C (77°F) ±0.25% of full scale over temperature range
5V Power Requirements
Dry Contact Relay version: • Digital Output Relays Continuous - 105mA plus 90mA transients (15ms) when relays switch on. • LEDs - 107mA • Quiescent - 23mA • Total - up to 235mA Solid State Relay version: • Digital Output Relays Continuous - 100mA • LEDs - 110mA • Quiescent - 23mA • Total - up to 233mA
11-30VDC Power Requirements
• 10.3mA plus analog outputs • 9-30Vdc operation possible when optional 5305 analog outputs not installed
Addressing
8 modules, DIP switch-selectable
Dimensions
144mm wide x 165mm high x 72mm deep (5.65in. x 6.50in. x 1.80in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, –40°C to 70°C (–40°F to 158°F)
Safety
• Class I, Division 2 Groups A, B, C and D Hazardous Locations and CSA certified to UL508 standards • ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2), (24VDI/Solid State Relay type only)
Part Number
TBUX297478 TBUX297479 TBUX297480 TBUX297481 TBUX297482 TBUX297483 TBUX297484 TBUX297485 TBUX297490 TBUX297491 TBUX297492 TBUX297493 TBUX297494 TBUX297495 TBUX297496 TBUX297497
(5607-24) (5607-48) (5607-120) (5607-240) (5607-24-AO) (5607-48-AO) (5607-120-AO) (5607-240-AO) (5607-24-A) (5607-48-A) (5607-120-A) (5607-240-A) (5607-24-AO-A) (5607-48-AO-A) (5607-120-AO-A) (5607-240-AO-A)
Note: 5607 module is not supported by the Non-Programmable Controller Modules (Model 5201 & 5202), SCADAPack LP, SCADAPack 100 and SCADAPack ER. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
41
Product Data Sheet 5421 – Toggle switch digital input module Specifications
5421 Toggle switch digital input module General Input Points
8
Signal Range
N/A (toggle switch)
Addressing
DIP switch configurable
Power Requirements
• 5V @ 45mA with all LEDs on • 5V @ 5mA with LEDs disabled
Visual Indicators
8: red LEDs, controlled for power reduction
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297104
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
42
Product Data Sheet 5521 – Potentiometer input module Specifications
5521 Potentiometer input module General Input Points
8
Resolution
12 bits
Repeatability
0.1% over temperature range
Converter Type
Successive approximation
Signal Range
N/A (multi-turn potentiometer)
Power Requirements
5V @ 20mA
Dimensions
4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C/F to 60°C /140°F
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297119
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
43
Product Data Sheet 5103 – Uninterruptible power supply Specifications
5103 Uninterruptible power supply General AC/DC Input
• 16 to 24VAC for 5/24V outputs operational, 24VAC required for battery charging • 14.5+/-0.5V for 5/24V outputs operational, 20VDC required for battery charging
DC/Battery Input
Turn on at 11.5V ± 0.3VDC, Turn off at 10.5V ± 0.5VDC, Maximum input is 36VDC
Input Power
35VA maximum at 24VAC, 1.9A at 13.5VDC
Outputs
5VDC at 2.0 ampere, 24VDC at 0.5 ampere, 17W total available from the two outputs 11 to 14VDC battery charger at 200mA (factory adjusted to 13.5V for gelled electrolyte lead/acid battery)
Mode
Isolated switch-mode, 30KHz switch frequency
Line Regulation
< 1% over operating range
Load Regulation
• 5V output: 5.15V ±1% over operating range • 24V output: ±17%
Output Ripple
o o • 5V output: < 10mV at 20 C (68 F) o o • 24V output: < 50mV at 20 C (68 F)
Visual Indicators
5V and 24V green LEDs show power status
Power Requirements
35VA maximum @ 24VAC, 1.9A @ 13.5VDC
Terminations
10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
• 5% RH to 95% RH, non-condensing • -40°C to 60°C (-40°F to 140°F)
Safety
Non-Incendive Electrical Equipment for Use in Class I, Division 2 Groups A, B, C and D Hazardous Locations. Temperature Code T4 at 60°C ambient. UL Listed to the following standards: • CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. • CSA Std. C22.2 No. 142-M1987 - Process Control Equipment. • UL Std. No. 1604 - Hazardous (Classified) Locations. • UL Std. No. 508 - Industrial Control Equipment.
Part Number
TBUX297102
Accessories Model
Part Number
Description
1206
TBUX294034
12V 6 AH gelled electrolyte battery
ACX-24
TBUX294000
120/24VAC, 40VA transformer
ACX-24E
TBUX294167
220/24VAC, 40VA transformer
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
44
Product Data Sheet 5201 – RS-485 communication controller Specifications
5201 RS-485 communication controller General Processor
M37702 16-bit CMOS microcontroller, 14.754 MHz, clock integrated watchdog timer
Memory
64kBytes total, 32kBytes CMOS RAM, 64kBytes EPROM
Communication Port
RS-485, 2-wire half duplex, 4-wire full/half duplex, optional termination resistors
Baud Rates
9600, 19200, 38400, 115200
Parity
None
Word Length & Stop Bits
8 bits, 1 stop bit
Cable Length
Maximum 1200m (4000ft)
Protocol
TeleBUS (compatible with Modbus RTU and Modbus ASCII)
Protocol Modes
Slave or master
Slave Addresses
Switch configurable from 1 to 255
Physical I/O Capacity
64 digital I/O, 64 analog inputs, 32 analog outputs, maximum 40 I/O modules
Visual Indicators
• RS-485 received data LED , RS-485 transmitted data LED • I/O module LED power status LED, Status LED (shows functional status)
Push-button
I/O Module LED Power toggle
Status Output
Opto coupler open collector transistor, 30VDC, 60mA, opens on fault
Power Requirements
5V @ 130mA
Terminations
8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing; -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297101
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
45
Product Data Sheet 5202 – RS-232 communication controller Specifications
5202 RS-232 communication controller General Processor
M37702 16-bit CMOS microcontroller, 14.7546 MHz clock, integrated watchdog timer
Memory
64kBytes total, 32kBytes CMOS RAM, 64kBytes EPROM
Communication Port
RS-232, Data Terminal Equipment (DTE), DE-9P male connector
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400
Parity
None
Word Length & Stop Bits
8 bits, 1 stop bit
Duplex
Full or half with RTS/CTS control
Cable Length
Maximum 15.2m (50ft)
Protocol
TeleBUS (compatible with Modbus RTU and Modbus ASCII)
Protocol Modes
Slave or master
Slave Addresses
Switch configurable from 1 to 255
Physical I/O Capacity
64 digital inputs, 64 digital outputs, 64 analog inputs, 32 analog outputs, maximum 40 I/O modules
Visual Indicators
• • • •
Push-button
I/O Module LED Power toggle
Status Output
Opto coupler open collector transistor, 30VDC, 60mA, opens on fault
Power Requirements
5V @ 60mA
Terminations
2 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing; -40°C to 60°C (-40°F to 140°F)
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297111
RS-232 received data (RxD) LED, RS-232 transmitted data (TxD) LED RS-232 clear to send (CTS) LED, RS-232 request to send (RTS) LED RS-232 data carrier detect (DCD) LED, I/O module LED power status LED Status LED (shows functional status)
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
46
Product Data Sheet 5901 – High speed modem Specifications
5901 High speed modem General Telco Data Rate
300 to 56k bps
Data Compression and Error Correction
MNP 2-4, MNP 5, V42 bis, MNP 10
DTE Data Rate
Auto detect DTE speeds of 300, 600, 1200, 2400, 4800, 7200, 9600, 12000, 14400, 19200, 38400, and 57600 bps
Features
• Compatible with all ITU-T standard modems from 14,400 to 300 bps • Permanently stores modem settings in memory (NVRAM) • Supports the industry-standard AT command set
Ringer Equivalency Number
0.8B
Visual Indicators
TD: RD: DTR: OH:
Power Requirements
• 5901 - 5V @ 200mA • 5901SA - 115 VAC at 10 VA for the 9VDC, 500mA, 2.1mm, center pin positive AC adapter
Terminations
2 pole, removable terminal block, 12 - 22 AWG, 15 amp contacts, RJ11C modular jack
Dimensions
4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep
Mounting
• 5901 - 7.5 x 35 DIN rail • 5901SA - desktop, rubber feet
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C/F to 70°C /158°F
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model
Part Number
5901
TBUX297198
5901SA
TBUX297199
Transmitted data LED Received data LED Data Transmitter Ready LED Off Hook LED
Note: Serial communication cable sold separately Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
47
Product Data Sheet 5902 – Bell 202 modem Specifications
5902 Bell 202 modem General Data Rate
1200 baud
Transmit Carrier
Switched or constant
Duplex
Full or half. Half duplex requires DTE to implement hardware RTS/CTS handshake
Wires
Two or four
Transmit Level
-35dBm to 0dBm into 600Ω, potentiometer adjustable
Receive Sensitivity
-30dBm to +3dBm, potentiometer adjustable to -40dBm
Output and Input Impedance
600Ω balanced, transformer isolated
Anti-Streaming
None, 10Sec, 30Sec, 60Sec
RTS/CTS Delay
• Wire: 25ms, 50ms, 125ms, 250ms • Radio: 67ms, 133ms, 266ms, 1000ms
CTS Hold Time
1ms, 8ms
Carrier Detect Delay
• Wire: 19ms, 30ms, 51ms, 92ms • Radio: 33ms, 67ms, 133ms, 265ms
Carrier Loss Delay
6ms, 10ms, 23ms, 39ms, constant carrier reception half duplex
Carrier Detect Level
-30dBm, adjustable from -20dBm to -40dBm
Radio Transmit Key Output
Optical coupler open collector transistor, 5 to 15VDC, 25mA
Visual Indicators
Transmitted Data LED, Received Data LED, Clear to Send LED, Request to Send LED, Carrier Detect LED, Radio Key Output LED
Power Requirements
• 5902 - 5V @ 60mA • 5902SA - 115VAC at 10VA
Terminations
8 pole, removable terminal block, RJ45
Dimensions
4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95 % RH, non-condensing, -40°C/F to 60°C/140°F
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Model
Part Number
Description
5902
TBUX297120
Bell 202 modem module, 1200 baud, FSK, 2/4 wire, with radio PTT key control & RF carrier detect
5902SA
TBUX297194
Same as 5902 but with a 115VAC AD adapter for connection to other PC’s or RS-232 devices
5902SAF
TBUX297195
Same as 5902SA but with a full duplex to half duplex converter - for devices without RTS/CTS support
Note: Serial communication cable sold separately Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
48
Product Data Sheet 5904 – Hart interface module Specifications
5904 HART interface module General Modulation
• Bell 202 Frequency Shift Key (FSK) • Mark = 1200 Hz • Space = 2200 Hz
Data Rate
1200 baud
Transmit Level
500mVp-p into 250Ω
Receive Sensitivity
• 120mVp-p guaranteed on • 80mVp-p guaranteed off
Output Impedance
• 300Ω • Transformer isolated
Input Impedance
• 4000Ω • Transformer isolated
Load Resistor
250Ω, 1 Watt maximum
Visual Indicators
• TX: Transmitted data LED • RX: Received data LED
Power Requirements
5V @ 20mA
Terminations
4 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts
Dimensions
4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep
Mounting
7.5 x 35 DIN rail
Packaging
Corrosion-resistant zinc-plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing, -40°C/F to 70°C /158°F
Safety
cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
Part Number
TBUX297205
This IO Expansion module is not supported by the SCADAPack E RTU. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
49
Product Data Sheet 5908 – Wireless data transceiver Specifications
5908 Wireless data transceiver General Frequency
902 to 928 MHz, 230 kHz bandwidth
Transmitter Output Power
1 mW to 1 W (+30dBm)
Range
60 miles (Line of sight with unity gain antenna)
Modulation
Spread Spectrum GFSK, 120 kBs - 170 kBs
Spreading Method
Frequency hopping
Receiver Sensitivity
-108dBm for 10-6 BER standard speed, -111dBm for 10-6 BER low speed -110dBm for 10-4 BER standard speed, -113dBm for 10-4 BER low speed
Selectivity
20dB at fc ±115 kHz , 60dB at fc ± 145 kHz
System Gain
140dB
Data Transmission Error Detection
32 Bit CRC, resend on error
Forward Error Correction (low speed)
(24,12) Golay, retransmit on uncorrectable error
Data Encryption
Substitution, dynamic key
Max Link Throughput
115 Kbaud standard speed, 38.4 Kbaud low speed
Data Interface
RS-232/RS-485 1200 baud to 230.4 Kbaud, asynch, full duplex, RJ45 connector
Power Requirements Supply Voltage
7 to 30 VDC (900 MHz model) 10 to 30 UDC (2.46 GHz model) 5908 5908-2.4G mA@12VDC mA@30VDC mA@12VDC mA@30VDC
Transmit
500
200
325
150
Receive
86
43
115
60
Idle
21
12
30
13
Sleep
6
3
5
2
Operating Modes
Point-to-Point , Point-to-Multipoint, Peer-to-Peer, Store and Forward Repeater
Operating Environment
-40°C/F to 75°C/167°F, 0 to 95% humidity non-condensing
Model
Part Number
Description
5908
TBUX297270
Radio Transceiver, FreeWave 900MHz Spread Spectrum, powered by 6-30 Volts DC
5908-2.4G*
TBUX297283
Radio Transceiver, FreeWave 2.4GHz Spread Spectrum, powered by 6-30 Volts DC
Note: Serial communication cable sold separately * Not available in all areas – Consult Schneider Electric for availability in your area Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
50
Product Data Sheet 5908-WO2 – Wireless data transceiver Specifications
5908-WO2 Wireless data transceiver General Frequency
Up to 128 frequencies within 902 - 928 MHz., configurable in 3.2 MHz zones
Transmitter Output Power
1.0 W (+30dBm) maximum (at antenna connector)
Modulation
CPFSK
Spreading Method
Frequency hopping based on network address
Receiver Type
Double conversion super heterodyne
Sensitivity
-108dBm @ 1 X 10-6 BER
Network Addresses
65,000
Data Transmission Error Detection
CRC16; Resend on error
Data Interface
RS-232/RS-485 (user selectable)
Max Link Throughput
Continuous up to 115.2 kbps
Baud Rates
1.2 to 115.2 kbps
Power Requirements Power
7.5W max
Supply Voltage
9 to 30VDC
Transmit Current
510mA @ 13.8VDC
Receive Current
115mA @ 13.8VDC
Sleep Mode Current
8mA @ 13.8VDC
Operating Modes
Point-to-Point, Point-to-Multipoint, Store-and-Forward Repeater
Operating Environment
-40°C/F to 70°C/158°F, 5%RH to 95%RH, non-condensing
Model
Part Number
Description
5908-WO2
TBUX297310
Radio Transceiver, MDS 900MHz Spread Spectrum, powered by 9-30 Volts CD
Note: Serial communication cable sold separately Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
51
Product Data Sheet 5910 – Ethernet switch Specifications
5910 Ethernet switch General Ethernet Switch Type
5 ports, unmanaged, store & forward, 10/100BaseT
Ethernet Terminations
RJ45 ports (shielded)
Protocols
IEEE 802.3, IEEE 802.3u (TBC), IEEE802.3x
Speed and Connection
• Auto-detecting 10/100 Mbps operation, • Auto MDI/MDI-X operation (no need for cross-wired cables)
Memory Bandwidth
1.4 Gbps
Duplex Operation
Full duplex IEEE802.3x and half duplex back pressure flow control
MAC Addressing
Dedicated lookup engine with 1K MAC addresses. Learning, aging and migration
Ethernet Isolation
1500 Vrms
Visual Indicators
Each port has - ACT/LINK and 10/100 (Speed) indicators
Input Power
• • • •
Input Power Terminations
• 4 pole terminal strip and removable terminal block. • 12 to 22 AWG
Dimensions
.25 inch (144 mm) wide, 4.625 inch (118 mm) high, 2.00 inch (51 mm) deep
Mounting
Desktop, rubber feet or 7.5 x 35 DIN rail
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
5% RH to 95% RH, non-condensing –40oC to 70oC –40oF to 158oF
Model
Part Number
Description
5910
TBUX297288
Ethernet Switch, 5 port, 10/100Mb autodetect, 12-24 Vdc power
5910SA
TBUX297289
Same as 5910, with the addition of a 115 Vac adapter
External Power: 11-30Vdc 1.8W at 12Vdc 2.2W at 30Vdc Bus Power: 5V at 375mA
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
52
Product Data Sheet 5915 – SDI-12 interface module Specifications
5915 SDI-12 interface module General SDI-12 bus Terminations
• 12 to 22 AWG • 15A contacts
Dimensions
2.90 inch (74mm) wide, 4.90 inch (124mm) high, 1.80 inch (45mm) deep
Packaging
Corrosion resistant zinc plated steel with black enamel paint
Environment
• 5% RH to 95% RH, non-condensing • –40oC to 70oC (–40oF to 158oF) operation • –40oC to 85oC (–40oF to 185oF) storage
Addressing
None required
Power Requirements 12V
• 6mA Idle • 6.5mA active, with LEDs disabled • 24mA active, continuous transmit, both LEDs on
Communications – Port P1 Port Type
RS-232 compatible serial port
Connector
8 pin modular jack (RJ45)
Pins Used
Transmit, Receive and Ground
Connection
DTE
Protocol
SDI-12 only
Baud
1200bps (as per SDI-12 protocol)
Bits
7 (as per SDI-12 protocol)
Parity
Even (as per SDI-12 protocol)
Hardware Handshaking
None
Protection
15kV ESD protected
Communications – Port P2 Port Type
SDI-12 port
Connector
4-way removable terminal block
Pins Used
12V, Ground, SDI-12 data
Protocol
SDI-12 only
Protection
MOV and current-limit
Indicators Tx
Illuminates when transmitting data from Master Controller to a slave device on the bus
Rx
Illuminates when receiving data from a slave device AND when ever the Master Controller transmits.
Model
Part Number
Description
5915
TBUX297475
SDI-12 Module, serial to SDI-12 converter for SCADAPack 32 and SCADAPack 3xx-Series controllers, c/w config. CD
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.