SCADAPack 350E | 357E Smart Remote Terminal Units
The SCADAPack™ 300E Smart RTU is a platform built on a 32-bit processor and fitted with a 12...30 Vdc supply, various communication links and a wide range of analog and digital I/O that adheres to open standards and can operate in the harsh demands of a remote environment. The SCADAPack 300E controller may be configured and programmed locally or remotely and is optionally configurable directly from StruxureWare™ SCADA Expert ClearSCADA™ host software. It can play multiple roles simultaneously: end point, automation point, data concentrator, protocol converter, peer-to-peer device and a telemetry router, and use Secure Authentication.
• Data concentrator for DNP3, Modbus and DF1 devices • Communication with up to 13 active SCADA masters, up to 10 remote/local slave devices and up to 100 remote DNP3 devices in peer-to-peer mode • Remote management suite (amend configuration, modify programs and update firmware remotely, using open standard DNP3) • Up to 76 integrated digital/analog inputs/outputs, and more with I/O expansion modules • 1 Ethernet, 3 Serial, 1 USB configuration port • Tool-less DIN rail mounting system • IP2x terminal blocks • Operation from –40 to +70°C (–40 to +158°F)
The SCADAPack 350E/357E Smart RTU provides the following features:
• Cost-effective, compact form factor
• Open-standard telemetry protocols IEC 60870-5-101/ -104 and DNP3 level 4 with Security Suite (Secure Authentication and/or Data Encryption)
When fed from a solar supply, the SCADAPack 350E controller can power its embedded analog inputs/outputs using its integrated auxiliary supply Vloop and 12 to 24 Vdc booster,
• Open-standard industrial protocols Modbus™ RTU/TCP and DF1 master
thus having the ability to switch off this supply to reduce power consumption and help increase battery back-up autonomy.
• Open-standard IEC 61131-3 programming environment
schneider-electric.com
SCADAPack 350E | 357E Smart Remote Terminal Units
Specifications – General characteristics Controller Processor
• 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer. • Two microcontroller IO co-processors, 20 MHz clock
Memory
• 16 MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM • CMOS SRAM with lithium battery retains contents for 2 years with no power
Event Logging Capacity (events)
20,000 events
Database Capacity
Up to 1,000 points
Data Concentrator Capacity (points)
Up to 500 in DNP3
Data Concentrator Capacity (devices)
Up to 10 in DNP3 and up to 10 in Modbus or DF1
File System Typical Storage
Internal: 6MB
Communications Serial Port : COM1 Serial Port : COM2
• RS-485, 2-pole removable terminal block, 2-wire, half duplex, supports baud rates up to 115,200 bps • RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or RS-485 port, 2-wire, half-duplex, supports baud rates up to 115,200 bps in RS-232 mode
Serial Port : COM3
RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control, supports baud rates up to 115,200 bps
Embedded Wireless
The controller may embed an unlicensed radio module (different options in 900 Mhz or 2.4 Ghz) that uses one of the serial ports
Serial Protocols
DNP3 level 4 slave/master and peer-to-peer, IEC 60870-5-101 slave, Modbus slave/master, DF1 master
Ethernet port
8-pin modular RJ45 jack, 10/100 Mbps UTP (10/100Base-T), transformer-isolated
IP Protocol
• DNP3 level 4 in TCP Master/Slave, UDP Master/Slave and peer-to-peer, IEC 60870-5-104 Slave, Modbus/TCP Server, Modbus/ TCP Client, Modbus RTU in TCP Client • NTP Client/Server, Telnet Server, FTP Server, BOOTP Server
Master – Slave Capability
• Can simultaneously report to up to multiple independent active masters: 3 in DNP3, 2 in IEC 60870-5-101/-104, 5 in Modbus TCP and 3 in Modbus RTU, and connect to up to 100 remote devices in DNP3 peer-to-peer. • As a data concentrator it can manage up to 10 local or remote DNP3 slaves, and up to 10 local slaves communicating with Modbus RTU, Modbus TCP or DF1 serial.
USB Device
USB 2.0 compliant “B”-type receptacle, for local configuration
www.aquatechnologygroup.com 800-513-8993 | +1 513-298-1183 sales@aquatechnologygroup.com
2
schneider-electric.com
SCADAPack 350E | 357E Smart Remote Terminal Units
Specifications – General characteristics General Logic Control
IEC 61131-3 SCADAPack Workbench programming suite (LD, ST, FBD & SFC)
I/O Terminations
SCADAPack 350E: 6, 12-pole connector, 0.0810...3.31mm2 (28...12 AWG), solid or stranded SCADAPack 357E: 5, 6, 7, 9, 10, 12-pole connectors, 0.0810...3.31mm2 (28...12 AWG), solid or stranded
Dimensions
SCADAPack 350E: 211.8mm (8”34) wide, 140.4mm (5.53”) high, 46.5mm (1.83”) deep SCADAPack 357E: 211.8mm (8”34) wide, 181.0mm (7.13”) high, 66.0mm (2.60”) deep
Enclosure
Corrosion resistant zinc-plated steel with black enamel paint
Environment
• Conformally coated • -40°C (-40°F) to 70°C (158°F) operating, -40°C (-40°F) to 85°C (185°F) storage • 5% RH to 95% RH, non-condensing
Shock & Vibration
IEC 60068-2-27 (tested up to 15g), IEC 60068-2-6
Warranty
3 years on parts and labor
Power Rated Voltage
12...30 Vdc. Limit voltage: 11.5...32 Vdc; turn on voltage: 10...11.5 Vdc; turn off voltage: 9...10 Vdc
Maximum Power
12 W at 24 Vdc (internal 5 Vdc supply fully loaded and Vloop on and boosted, fully loaded) • SCADAPack 350E typical power consumption (at 20°C/ 68°F)
Controller LEDs Power Requirements
Use case 1 Use case 2 Use case 3
Vloop fully loaded OFF
OFF
ON ON
12 Vdc
24 Vdc
1.6 W
1.5 W
5.1 W
4.9 W
5.2 W
5.0 W
• SCADAPack 357E typical power consumption: up to 8.9 W (with up to 7 analog input/output loops powered from Vloop supply) Power outputs
Vloop • Maximum 140mA at 12 V (booster turned off) or 24 Vdc (booster turned on); can power up to 7 analog input/output loops
www.aquatechnologygroup.com 800-513-8993 | +1 513-298-1183 sales@aquatechnologygroup.com
3
schneider-electric.com
SCADAPack 350E | 357E Smart Remote Terminal Units
Specifications – Digital and Analog Inputs/Outputs Controller board
Analog Inputs
5, user-selectable 0...10V or 0...20mA plus over range 1, 0...32.7 Vdc (15-bit) for DC supply monitoring • Resolution: 15-bit ADC (15-bit over the measurement range in 10V, 14-bit in 20mA) • Accuracy: ±0.1% of full scale at 25°C (77°F), ±0.2% over temperature range • Input Resistance: 250 Ω or 20 kΩ in 20mA or 10V configurations (60 kΩ for 32.768V) • Normal rejection mode: 27 dB at 60 Hz • Sampling rate: 170 ms
Analog Outputs
2 (optional), 0...20 mA, 4...20 mA, voltage output may be accomplished with external precision resistor • Resolution: 12-bit over 0...20 mA range • Accuracy: ±0.15% at 25°C (77°F), ±0.35% of full scale over temperature range • Response Time: less than 10 μs for 10% to 90% signal change • Power Supply: 12…30 Vdc, external • Power (Current) Requirements: 10 mA plus up to 20 mA per output • Isolation: isolated from RTU logic and chassis • Load Range: 12 Vdc: 0…375Ω, 24 Vdc: 0…925Ω, • Logic End-Of- Scan to Signal Update Latency: typically 18... 27ms • Status & Reporting: output value • Controls: Direct Operate, Select Before Operate
Digital Inputs/Outputs
8, user-selectable as inputs or outputs (open drain) As Digital Inputs • Dry contact • Time stamping: 170ms As Digital Outputs • Sinking MOSFET output, rated 30V, 0.5A, ground return connected to Chassis Ground
Counter Inputs
• 1, 0...10Hz (dry contact) • 2, 0...10kHz (turbine or dry contact)
Internal Power monitor
Power input - analog input and low indication, onboard lithium battery - low indication
Internal Temperature Monitor
Controller temperature range -40°C…+75°C (-40°F...+167°F)
I/O board (357E only) Analog Inputs
8, software-configurable to 0...20, 4...20mA , 0...5 or 0...10V Same features as for the 5 analog inputs located on the controller board (see above) except isolation: • Isolation: 500 Vac from logic and chassis
Analog Outputs
2 (optional), 0...20/4...20mA, voltage output may be accomplished with external precision resistor Same features as for the analog outputs located on the controller board
Digital Inputs
32, 12…24 Vdc • Turn on voltage: 9 Vdc (minimum), Turn off voltage: 4 Vdc (maximum) • Over-voltage tolerance: 150% sustained over-voltage without foreseeable damage • DC input current: 0.67 mA at 24 Vdc • Time stamping : 170ms • Isolation : in group of 8, 1500 Vac from logic supply and chassis
Digital Outputs
16, relays (Form A) • 4 contacts share one common • Isolation : isolated in groups of 4. Isolated from RTU logic, RTU chassis and other groups to 1500 Vac • Maximum Switching Voltage: 30 Vdc or 250 Vac (resistive) • Maximum Switching Load: 150 W or 1250 VA (5 A) • Controls: Direct Operate, Select Before Operate, Trip/Close, Latch, Pulse
Additional I/O Supported modules : • 5606, 5607, 5608 and 5610, and 5304, 5404, 5411, 5414, 5415, 5505 and 5506 I/O Expansion
Maximum number of modules per unit: • SCADAPack 350E: 8 (*) • SCADAPack 357E: 7 (*) (*): to reach this limit, additional power supply modules are required
4
schneider-electric.com
SCADAPack 350E | 357E Smart Remote Terminal Units
Model Code SCADAPack 350E/357E
Model
Select : Controller
TBUP350
SCADAPack350E, Controller 32 bits, 5 Analog Inputs, 8 Digital I/O, 3 High Speed Counter Inputs
TBUP357
SCADAPack357E, Controller 32 bits, comes with the above plus additional I/Os
Code
Select : Platform
E
SCADAPack E Firmware (Configuration Software included), executes two IEC 61131 kernels, Workbench required
Code
Select: SCADA Security
A
None
B
AGA-12 Encryption for DNP3 (Security Administrator application required)
C
DNP3 Secure Authentication SAv2 (Security Administrator application required)
D
DNP3 Secure Authentication with AGA-12 (Security Administrator application required)
Code
Select: Protocol Option
5
DNP3 Serial/IP mstr/slave/peer-to-peer, IEC 60870-5-101/104 Slave, Modbus RTU/TCP mstr/slave, TCP/IP, DF1 mstr
Code
Select: License Option
5
DNP3 Data Concentrator License (limit of 500 points from 10 IEDs), supports multiple DNP3 Masters (up to 3)
7
Adds WITS* protocol (available for SCADA Security Code C and Certification Code S only)
Code
Select : Analog Inputs
A
P350 : 5 selectable as 0...10V or 0...20mA  *P357 : adds 8 selectable as 0...20mA, 4...20mA, 0...5V or 0...10V
Code
Select: Digital Inputs/Outputs
A
P350 only: 8 Digital I/O, individually selectable as digital input (Dry Contact) or digital output (Open Drain)
B
P357 only: adds 32 digital inputs (12-24V), 16 digital outputs (Dry Contact relay for Class I Div 2, Solid State relay for IECEx/ATEX)
* WITS protocol (Water Industry Telemetry Standard)
5
schneider-electric.com
SCADAPack 350E | 357E Smart Remote Terminal Units
Model Code SCADAPack 350E/357E
Code
Select: Analog Outputs
0
None
1
2 channel Analog Output, 0..20 mA, external DC supply
2
P357 only : 4 channel Analog Output, 0..20 mA, external DC supply
Code
Select : Integrated Communications Interfaces
0
None FreeWave™ & MDS™ Radios (requires one RS232 port)
1
900Mhz FreeWave Spread Spectrum Radio
A
900MHz MDS Spread Spectrum Radio Trio™ Radios – 900MHz (requires one RS232 port)
B
900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
C
900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
D
900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
E
900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios – 2.4GHz (requires one RS232 port)
J
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
K
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
L
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Code
Selection: Certifications
S
With FCC, UL508, CE marking and RCM
X
Adds IECEx/ATEX Class I, Zone 2
U
Adds cCSAus Nonincendive Electrical Equipment for use in Class I, Division 2, Groups A, B, C and D
Disclaimer: Not all product features are available in every mode of operation. Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
6
schneider-electric.com
SCADAPack 350E | 357E Smart Remote Terminal Units
www.aquatechnologygroup.com 800-513-8993 | +1 513-298-1183 sales@aquatechnologygroup.com
Telemetry & Remote SCADA Solutions 415 Legget Drive, Suite 101, Kanata, Ontario K2K 3R1 Canada Direct Worldwide: +1 (613) 591-1943 Fax: +1 (613) 591-1022 Toll Free within North America: +1 (888) 267-2232 www.schneider-electric.com
Part Number TBULM08002-92 v27 © 2016 Schneider Electric. All Rights Reserved. Schneider Electric, Life Is On, Struxureware, ClearSCADA, Modbus, SCADAPack and Trio are trademarks and the property of Schneider Electric SE, its subsidiaries and affiliated companies. All other trademarks are the property of their respective owners – February 2016