1 minute read

Conclusion

Next Article
Test Assembly

Test Assembly

FC-891 Concrete Reinforcing Steel Institute July 14, 2017 Page 13 of 30

The following conclusion is based on the results of the fire test presented in this report.

Advertisement

The voided concrete slab assembly constructed of the materials and in the manner described in this report achieved a 2 hr. unrestrained assembly rating when exposed to fire in accordance with Test Method ASTM E119-16a.

The above classification is based on the “Conditions of Acceptance – Unrestrained Assembly Classification” for tests of floors and roofs in ASTM E119 – 16a Standard Test Methods for Fire Tests of Building Construction and Materials.

This article is from: