www.bannerbatteries.com
STAND BY BULL Bloc FPL: Type FPL 12-100 FPL 12-190 Banner Stand by Bull Bloc FPL is a sealed, valve-regulated pure lead battery of the very latest design. Apart from an extremely high current output, it also offers a service life that is unmatched by any other product in this segment. Moreover, smaller capacities can be employed for the same performance requirement, which secures the advantages of a marked reduction in weight and the battery footprint.
Features - Block batteries, 12 V rated voltage - Front connection - Zero-maintenance for entire service life - Compensation charge voltage of 2.27 V/cell - Recommended temperature range of 20°C (max. –0°C to +40°C) - Non-hazardous article according to FAA and IATA (pursuant to Packaging Regulation 806) - Flame-retardant casing pursuant to UL 94-VO - Corrosion-resistant terminal design - Top voltage level in the high current range - Central degassing - Service life design of 15 years (long life according to EUROBAT)
Design - Positive electrode Pure lead mesh plate, punched and double pasted - Negative electrode Pure lead mesh plate, punched and double pasted - Separation Glass fibre non-woven web - Casing material ABS, bonded cover, hot welded - Electrolyte Extremely pure sulphuric acid bound into a web - Terminal design Electrolyte-tight safety terminal sealed with epoxy resin - Cell connections COS-Interior welding through the casing wall - Cell plug Safety valve with an overpressure ventilation system for 2 psi(14 Kpa) gas pressure
www.bannerbatteries.com
STAND BY BULL Technical details Nenn spann. in Volt 12 12 12
Type FPL 12-100 FPL 12-150 FPL 12-190
C 10 1,80 V/Z. 100 150 190
Capacity in Ah C5 C3 1,75 V/Z. 1,67 V/Z. 87 64,1 132,5 101,2 181 170,1
Dimensions Length Width Height mm mm mm 108 397 287 125 562 260 125 562 320
Charge Ri Termi- voltage mOhm nal No max. A 3 2 40 3,6 2 60 3 2 76
Type Total of conn- weight ection kg M8 31 M8 46,5 M8 60
The given electrical values are valid for loads in a fully charged condition and an ambient temperature of 20°C. Float Current vs Float Time
Charging Charactaristics
2,27V Float Time (h)
25
Charging Charging Volume Current (%) (XCA) 140
20 16
Advised with 0.4 CA to Charge
10
120
0.10
100
0.08
80 60
5
40
0
0.2
0.4
0.6
0.8
1.0
20
Float Current (CA) 80% SOC
90% SOC
0.06 0.04 0.02 0
0
15min Rate
1h Rate
Charging Voltage (V)
Temperature 25°C Charged Volume
2.50 2.33
15.0 14.0
Charged Voltage
13.0
2.16 After 50% Discharge
2.06
After 100% Discharge
1.83 0
4
8
12
16
20
24
28
32
12.0 11.0
Charging Current
0
100% SOC
36
40
Charging Time (hours)
Charging Time vs The Depth of Discharge
Effect of Temperature on Discharging Time 10
0.1CA-2.25V/cell
5h Rate
Constant Voltage 2.40V/Cell, Charging Volume 103% 16.0
Charging time (h)
Discharging Time (h)
18.0
1
0.1
0.1C10A
0.1C10A 0.2C10A 0.3C10A 0.5C10A 1.0C10A
14.0 12.0 10.0
0.2C10A
8.0
0.3C10A
6.0
0.5C10A
4.0
1.0C10A
2.0 0.0 0.01 -40
-30
-20
-10
0
10
20
30
40
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100% 110%
Depth of Discharging (DOD)
Temperature(°C)
Installation The blocks are suitable for position-independent installation on racks or in cabinets. On request, we supply special racks for zones subject to earthquakes, telecommunications applications and UPS systems. The safety regulations according to EN 50272-2 are to be observed, particularly those relating to ventilation. Charging must be adjusted to the voltage limits stipulated in our data sheets. Alle Maß- und Gewichtsangaben unterliegen den üblichen Fertigungstoleranzen. Die elektrischen Werte sind angenähert. Unsere Produkte unterliegen einer ständigen Weiterentwicklung, deshalb behalten wir uns Änderungen ohne Anzeigepflicht vor.
Presented by:
A:
Banner GmbH, A-4021 Linz, Banner Straße 1, Tel. 0732/3888-0, Fax 0732/3888-21598, e-mail: office@bannerbatterien.com
GB: Banner Batteries (GB) Ltd., Units 5-8 Canal View Business Park, Wheelhouse Road, Rugeley, Staffordshire WS15 1UY, Tel. +44/ (0)1889/ 57 11 00, Telefax +44/ (0)1889/ 57 73 42, e-mail: office.bgb@bannerbatteries.com
17709008301/10-14