Cell KM P_1709002201_gb_Cell KM P_1709002201_gb 17.01.12 08:37 Seite 1

www.bannerbatteries.com

STAND BY BULL Cell Ni-Cd: Type KM 11 P ➔ KM 520 P Banner Stand by Cell KM-P batteries are nickel cadmium cells for bridging period applications lasting 20-90 min. They are suitable for battery, switching and parallel stand-by operations and due to their robustness, resistance to deep discharge and mechanical loads, are mainly used in power stations, UPS, traffic technology and safety power supply systems. Design

Features - Individual cells: 1.2V rated voltage - Sustained charge voltage: 1.40V per cell - Rapid charge voltage: 1.55-1.65 V per cell - Recommended temperature range of 20°C (max. –35°C to +45°C) - High performance through good voltage position

- Positive electrode - Tubular plates - Negative electrode - Separation Perforated separator - Casing material Translucent polystyrene - Electrolyte Diluted caustic potash solution d = 1.19 kg/l - Terminal design Solid steel, nickel-coated terminal - Terminal screw Hexagonal, nickel-plated metric steel screw - Cell connector Solid copper, nickel-plated connector - Cell plug Folding lid sealing, option: gas drying plug - DIN 40771, DIN EN 60623 and IEC 60623 product standards


Cell KM P_1709002201_gb_Cell KM P_1709002201_gb 17.01.12 08:37 Seite 2

www.bannerbatteries.com

STAND BY BULL Technical data Rated voltage in V

Capacity in 5h

Length mm

Dimensions Width mm

Height* mm

Terminal no.

Version

KM 11 P

1,2

11

46

85

187

2

M 10

0,70

1,00

KM 18 P

1,2

18

46

85

257

2

M 10

1,00

1,50

KM 24 P

1,2

24

46

85

257

2

M 10

1,20

1,59

KM 30 P

1,2

30

46

85

257

2

M 10

1,40

1,70

KM 40 P

1,2

40

85

85

257

2

M 10

1,90

2,80

KM 48 P

1,2

48

85

85

257

2

M 10

2,10

2,80

KM 55 P

1,2

55

85

85

257

2

M 10

2,30

3,00

KM 65 P

1,2

65

53

134

392

2

M 28

3,60

4,90

KM 75 P

1,2

75

53

134

392

2

M 28

3,80

5,00

KM 90 P

1,2

90

69

134

392

2

M 28

4,40

6,20

KM 110 P

1,2

110

69

134

392

2

M 28

4,90

6,50

KM 125 P

1,2

125

70

164

392

2

M 28

5,60

7,70

KM 140 P

1,2 1,2

140 160

70 108

164 164

392 392

2 2

M 28 M 28

6,00 6,90

7,80 10,60

Type

KM 160 P KM 185 P

Connections

Weight in kg Without With electrolyte electrolyte

1,2

185

108

164

392

2

M 28

7,50

10,90

KM 205 P

1,2

205

108

164

392

2

M 28

8,30

11,20

KM 225 P

1,2

225

108

164

392

2

M 28

8,80

11,60

KM 250 P

1,2

250

108

164

392

2

M 28

9,60

12,20

The electrical values given are valid for loads in a fully charged condition and an ambient temperature of 20°C.

Height including connector.

Terminal versions KM 11 - KM 30, KM 65 - KM 250

KM 40 - KM 55

KM 270

KM 310 - KM 520

Installation The cells are suitable for installation on stands or in cabinets. On request, we provide special holders for areas subject to earthquakes. The safety regulations according to EN 50272-2 are to be observed, particularly those relating to ventilation. Charging must be matched to the given voltage limits, the temperature correction factor amounts to -3V/°C at 20°C ambient temperature. All the given dimensions and weights are subject to the standard production tolerances. The electrical values are approximate. Our products are subject to ongoing further development and therefore we retain the right to make alterations without prior notice.

Presented by:

A:

Banner GmbH, A-4021 Linz, Banner Straße 1, Tel. 0732/3888-0, Fax 0732/3888-21598, e-mail: office@bannerbatterien.com

GB: Banner Batteries (GB) Ltd., Units 5-8 Canal View Business Park, Wheelhouse Road, Rugeley, Staffordshire WS15 1UY, Tel. +44/ (0)1889/ 57 11 00, Telefax +44/ (0)1889/ 57 73 42, e-mail: office.bgb@bannerbatteries.com

1709002201/02-08


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.