FolderSCGCellsGb

Page 1

SCG_Cell_1709002018_gb_SCG_Cell_1709002018_gb 17.01.12 10:08 Seite 1

www.bannerbatteries.com

STAND BY BULL Cell SCG: Type SCG 2-50 ➔ SCG 2-3850 Banner Stand-by Bull Cell GEL batteries are encapsulated, valve controlled lead batteries containing an electrolyte gel. These block batteries are characterised by their robust design, versatility of application and zero-maintenance design. Other advantages include their long service life, high cyclical resistance and large capacity range of up to 3,850 Ah. These batteries are mainly employed in power stations, the telecommunications and medical units.

Features - Single cells, 2 V rated voltage - Corrosion-resistant terminal design - Zero-maintenance for entire service life - Compensation charge voltage of 2.27 V/cell - Recommended temperature range of 20°C (max. –10°C to +50°C) - Long service life even under cyclical loads - Employment independent of position - Designed for a service life of 10 years + in stand by operation mode - "High performance" after EUROBAT - Secure agianst deep discharge in accordance with DIN 43539 T 5

Design - Positive electrode Lead/calcium, high-performance grid with pasted active mass - Negative electrode Lead/calcium, high-performance grid with pasted active mass - Separation Microporous duroplastic cutter with glass fibre coating - Casing material ABS, bonded cover - Electrolyte Extremely pure sulphuric acid bound into a gel - Terminal design Electrolyte-tight safety terminal sealed with epoxy resin - Cell connections Flexible/rigid, fully insulated copper cable connector - Cell plug Safety valve with an overpressure ventilation system for 2 psi (14 Kpa) gas pressure


SCG_Cell_1709002018_gb_SCG_Cell_1709002018_gb 17.01.12 10:08 Seite 2

www.bannerbatteries.com

STAND BY BULL Technical details

SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG SCG

Type 2-50 2-100 2-150 2-200 2-250 2-300 2-375 2-400 2-450 2-500-1 2-500-2 2-575 2-600 2-625 2-750 2-800 2-1000-1 2-1000-2 2-1250 2-1500 2-1875 2-2000 2-2500 2-3000 2-3850

Rated Capacity in Ah Dimensions Charge Type voltage C 10 C5 C 1 Length Width Height Ri Ik Termi-voltage of connin V 1.80 V/Z. 1.75 V/Z. 1.67 V/Z. mm mm mm mOhm in A nal No max. A ection 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

50 100 150 200 250 300 375 400 450 500 500 575 600 625 750 800 1000 1000 1250 1500 1875 2000 2500 3000 3850

43.4 89 133 178 222.5 267 334 355.5 399.5 445 445 505 535 555 670 715 890 890 1115 1330 1665 1780 2225 2670 3425

32 65,2 93,4 125 156 187 234 250 280 356 356 356 374 390 468 500 624 624 781 935 1170 1249 1561 1873 2404

161 171 172 173 173 171 171 211 223 211 241 223 301 241 301 410 410 475 475 401 401 491 491 712 712

50 72 102 111 111 151 151 176 187 176 172 187 175 172 175 175 175 175 175 351 351 351 351 353 353

166 205 205 329 329 330 330 329 351 329 331 351 331 331 331 330 330 328 328 342 342 344 344 341 341

2.1 2 1.5 0.5 0.45 0.4 0.39 0.36 0.33 0.3 0.3 0.29 0.28 0.25 0.22 0.2 0.16 0.16 0.13 0.11 0.1 0.09 0.08 0.08 0.07

509 1.080 1.550 1.600 2.000 2.400 3.000 3.200 3.600 4.000 4.000 4.600 4.800 5.000 6.000 6.400 7.900 7.900 10.050 11.950 15.050 16.100 19.850 24.100 30.800

2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 8 8 8 8 8 8 8 8 8 8

10 20 30 40 50 60 75 80 90 100 100 115 120 125 130 160 200 200 250 300 375 400 500 600 770

Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert Insert

Tota weight kg

3.8 5.6 10 14.2 17 19.7 23.5 27 32 32.3 32.3 36.5 38 39 51 52.5 63 63 78 103 125 132 175 211 261

The given electrical values are valid for loads in a fully charged condition and an ambient temperature of 20°C.

Installation The cells are suitable for position-independent installation on racks or in cabinets. On request, we supply special racks for zones subject to earthquakes, telecommunications applications and UPS systems. The safety regulations according to EN 50272-2 are to be observed, particularly those relating to ventilation. Charging must be adjusted to the voltage limits stipulated in our data sheets. All figures relating to dimensions and weight are subject ton the standard production tolerances. The electrical values are approximate. Our products are subject to ongoing development, therefore we retain the right to make changes without an obligation to inform.

Presented by:

A:

Banner GmbH, A-4021 Linz, Banner StraĂ&#x;e 1, Tel. 0732/3888-0, Fax 0732/3888-21598, e-mail: office@bannerbatterien.com

GB: Banner Batteries (GB) Ltd., Units 5-8 Canal View Business Park, Wheelhouse Road, Rugeley, Staffordshire WS15 1UY, Tel. +44/ (0)1889/ 57 11 00, Telefax +44/ (0)1889/ 57 73 42, e-mail: office.bgb@bannerbatteries.com

1709002018/02-12