Zehnder ZIP Radiant Ceiling Panels



The Sun – a masterpiece.

The sun radiates warmth and light. Its thermal radiation is only effective when its rays shine on an object. The air is therefore not warmed directly. Even when the air is very cold it is possible to feel warm in the sun. The decisive factors for our personal 씱2

thermal comfort are the average values of

3씰

the ambient temperature and those of the surrounding surfaces. Zehnder ZIP radiant ceiling panels for heating applies this natural principle. The perceived temperature is about 3° C higher than the air temperature, resulting in comfort at a lower room temperature. Zehnder ZIP radiant ceiling panels reduce costs. Heated by hot water, maintenance is minimal and service life is unlimited, saving energy and money. Zehnder ZIP radiant ceiling panels create healthy warmth. They operate without causing air movement and consequently do not swirl dust about. This in turn assists in the prevention of allergies and illnesses. Range of Application: Rooms from 3 m to 30 m high, such as production and storage facilities, workshops, sports halls, garages, sales rooms, shipyards, maintenance shops, damp locations, etc. Zehnder is Europe’s leading supplier of radiant ceiling panels, with decades of invaluable experience.

Zehnder ZIP radiant ceiling panel.


Excellent Technology.

Zehnder creates an entirely new system: Zehnder ZIP Radiant Ceiling Panels. The many advantages are:

Easy to store. Only one module width –

320 mm – uses storage space effectively. Flexible, straightforward fastening

system. Simplifies installation as well as Optional connection method: threaded

or press fit connections. No welding required. This simplifies installation and facilitates easy system extension when premises are enlarged. Lightweight. Easy to assemble and

install. Installation-compatible. Shorter installa-

tion time means reduced costs. High heat emission (tested in accordan-

ce with EN 14037). The efficient heat

reconfiguration or extension. Attractive slimline appearance, with 15

mm. Diameter tubes. Rapid reaction time. Thanks to low

storage mass and low water content. Corrosion prevention. The Zehnder ZIP

radiant ceiling panels are corrosion inhibited. The relevant test was carried out in accordance with DIN 50017 ”Condensation Water Test Atmospheres“. Special version for damp locations.

transfer design of the Zehnder ZIP radiant

Zehnder ZIP radiant ceiling panels are

ceiling panels ensure the highest possible

suitable for washrooms, HGV washing

heat output, further reducing costs.

bays, butchers’ premises, etc.

n Modular construction: 2,3,4,5 and 6m

lengths. The unique, modular concept of the Zehnder ZIP radiant ceiling panel system offers the right solution for any installation situation. For the very first time, modules can be arranged end to end or side by side, as required.


20

m PL 0 m nt ZI 0 0 2 eme l ce asi

Zehnder ZIP Radiant Ceiling Panels.

B

30

m IP L 0 m ent Z 0 0 3 lem ce asi

B

Overall length

m IP 0 m nt Z 400 leme ce asi

L40

B

IP tZ

L50

en

lem

m

0m

e sic Ba

500

IP

Z ent

L60

m

m

0m

sic Ba

ele

600

le

g

n

si

Overall widths

0

32 le

b

u

o

d 4

70 m

m

씹4

5ě”° tr le ip 88

10

Examples of parallel warrant

m

m

0

32 0 32

64

u q ru

ad le p 14 m

0

72

32

m

0

32

64

32 0

64

0 32 0

32

64

32 0

64

0

32

64


Outstanding Down to the Last Detail. The Material. Zehnder ZIP radiant

Installation Method. Zehnder sup-

ceiling panels are made from 0.5 mm-thick

plies the modules ready-to-install in lengths

sheet steel with Zehnder special clip profi-

of 2, 3, 4, 5 and 6 metres and a width of 320

ling. Each one accommodates four precision

mm. The individual modules can be joined

steel tubes and the top-surface insulation.

together with the Zehnder threaded cou-

Folded side flanges and galvanised box-sec-

plings or alternative Zehnder press fittings,

tion crossbars stiffen the steel sheeting, and

making the job simple and quick.

provide mounting for suspension. Two

Simple, clip-on cover plates then con-

sheet-metal end elements close off the ends

ceal the joints. The headers are fixed to the

of the radiant panels.

modules during installation, with the threa-

The outside surface is polyester coa-

ded couplings. The panels are suspended

ted. The inside surface is coated with a pro-

with chain hanging sets fixed directly to the

tecting lacquer.

integral suspension bars, or if several paral-

The four clip-retained precision steel

lel modules are installed, by using a multiple

tubes are welded and sized in accordance

suspension bar with only two chain hanging

in line with DIN EN 10305-3. The pipe ends

sets per suspension bar.

are chamfered for the use of threaded or compression-type couplings. They thereby ensure maximum and constant heat transfer. The Headers. Round tubing with a diameter of 32 mm. The headers and collectors are fitted with an externally threaded connecting boss, and an oppositely located sleeve as vent/drain. The various header configurations permit customised panel connections.


Zehnder ZIP radiant ceiling panels with the various connecting systems.

Multiple suspension bar

Compression fitting

8-tube header / collector

Precision steel tube

씹6

Clamp ring-type threaded coupling

7ě”°

Suspension bar Cover plate 4-tube header with connection boss

Details of clamp ring-type threading coupling

Details of press fittings


Zehnder ZIP Radiant Ceiling Panels.

Technical Data Designation/Version

Heat Emissions Units

Zehnder ZIP

Tube spacing

mm

80

Tube outside diameter

mm

15

Overall width of RCP

mm

320

No. off

2

Heat output of RCP Heat output tested as per EN 14037 (standard superseding DIN V 4706 parts 1 and 2)

watt/ metre run

208

Cooling capacity ZIP at Δt = 10 K

watt/ metre run

36

Cooling capacity ZIP without thermal insulation at Δt = 10 K

watt/ metre run

42

Cooling capacity collector pair at Δt = 10 K

watt/ collector pair

10

Operating weight of RCP without water content and insulation

kg/m

4.17

Operating weight of RCP with water content and insulation

kg/m

4.70

Water content per lfm ZIP

kg/m

Number of suspensions per bar

0,53

Maximum operating temperature: 95° C.* Maximum operating pressure: 5 bar.* *Higher operating temperatures and pressures available on request.

Δt in K

Zehnder ZIP in W/m

80 78 76 74 72

321 311 302 293 284

92 89 86 83 80

70 68 66 64 62

275 266 257 248 239

77 74 71 68 65

60 58 56

230 222 213

62 60 57

55

208

55

54 52

204 195

54 51

50 48 46 44 42

187 178 170 161 153

49 46 44 41 39

40 38 36 34 32

145 136 128 120 112

36 34 31 29 27

30 28 26 24 22

104 96 88 80 73

24 22 20 18 16

K=2,0871 n=1,1489

K=0,2456 n=1,3524

Collector pair in W

q=K· tn

Performance information in accordance with EN 14037

The Zehnder ZIP radiant ceiling panels offer numerous connection options. Here are only a few examples.


Zehnder ZIP Radiant Ceiling Panels. Water connection options.

rn

tu Re

A w

Flo

rn

tu Re

B Div

ert

er

w

씱8

Flo

9씰

A A rn

tu Re

w

Flo

tur

Re

n

C

w

Div

Flo

ert

tur

er

A

A

Re

A

Div

w

Flo

ert

er Div

ert

er

B A w

Flo

rn

tu Re

n


씹 10

11 ě”°

Zehnder ZIP Radiant Ceiling Panels. Suspension Systems.

7 2

*

1

9

1

8

8

1

9 8

7

7

8

Fastening to multi-suspension bars with spring hooks and knotted-link chain.

Installation Kit KN 53. Fastening to concrete ceiling with steel drive anchors, eye bolts and spring hooks.

Quantity of multiple suspension bars per module ZIP L20

2 off

ZIP L30

2 off

ZIP L40

2 off

ZIP L50

3 off

ZIP L60

3 off

Installation Kit KN 54. Fastening to steel section with eye bolts and spring hooks.


1 1 3 4 5 6

Hexagon nut, M8 Steel drive anchor, M 8 Carrier clamp, M 8 Securing clip Flat leaf screw, M 8 Trapezoidally formed suspension element, M 8

7 8 9 10 11

Knotted-link chain, K 22 Spring hook Eye bolt Plain washer Hexagon head screw, M 8 x 40 provided by customer All individual components galvanised.

*

* *

3 6

1

3 11

9

10

5

*

9

9

4

8

8

8

4 1

1

7

7 7

Installation kit KN 56. Fastening to trapezoidally formed sheet steel mounting member with trapezoidally formed suspension element, eye bolts and spring hooks.

Installation kit KN 58. Fastening to horizontal steel girders with carrier clamps, eye bolts and spring hooks.

Installation kit KN 57. Fastening to inclined steel girders with carrier clamps, eye bolts and spring hooks.

Knotted-link chain

Spring hook Spring hook Multi-suspension bar


씱 12

13 씰

Zehnder ZIP Radiant Ceiling Panels. Tendering Text. The 32 mm diameter tubular headers

Zehnder ZIP radiant ceiling panel made of 0.5 mm sheet steel Sendzimir-gal-

are furnished with a 1”externally threaded

vanised on both sides, with Zehnder special

connection boss, blank cover and an oppo-

clip profiling to accommodate four 15 mm

sitely located 1/2“ sleeve as vent/drain. The

precision steel tubes in line with DIN EN

headers/collectors are supplied loose and

10305-3. Outside surface of radiation panel

are installed on site. They are connected to

coated with polyester lacquer similar to RAL

the panel or the panel modules by tightening

9016, opposite side with protecting lacquer.

the threaded couplings.

Suitable for operating temperatures up to The 320 mm-wide modules are sup-

95°C, maximum operating pressure 5 bar.

plied ready-to-install in lengths of 2,3,4,5 or The sheet steel of the panel is rende-

6 metres according to requirements. The

red statically self supporting by folded side

individual modules are joined with threaded

and top flanges. The flanges also accommo-

or press fit connectors. The joins are con-

date and retain the insulation. Two sheet-

cealed with clip fit, lacquer-finished, cover

steel end elements close off the radiant

plates. The Zehnder ZIP radiant ceiling panels

panel.

are protected against corrosion. The releA panel can be attached directly to the

vant test was carried out in accordance with

integral suspension bars in a fixed grid

DIN 50017 ”Condensation Water Test

arrangement or, if several are arranged in

Atmosphere“.

parallel, by using a common multi-suspensi-

There is also a version especially for damp

on bar with only two points for fixing to the

locations. This includes fitted Stryrodur insu-

ceiling.

lation with a galvanised top cover added on site. Manufacturer:

Zehnder

Type:

Zehnder ZIP Radiation Ceiling Panel


Design Temperatures:

Fastening Methods:

Heating medium PWW ......... /.......... 째C

Installation kit KN 53 for fastening to con-

Ambient temperature

..................... 째C

Thermal output

..................... W

Module length

(overall)

(overall)

..................... m

crete ceilings

..................... off

Installation kit KN 54 for fastening to steel section

..................... off

Installation kit KN 56 for fastening to Thermal Insulation:

trapezoidally formed sheet steel

Thermal insulation is fitted on site. ..................... m

..................... off Installation kit KN 57 for fastening to tilted steel girders .....................

Compression Coupling: Galvanised compression fittings, 15 mm

off

Installation kit KN 58 for fastening to horizontal steel girders

.........

off

..................... off Volumetric Flow Controller: Threaded Coupling:

Zehnder combined volumetric flow controller

Galvanised clamp-ring coupling, 15 mm

for flow and return, up to 100째C, differential

..................... off

pressure up to 4,0 bar, DN 25, PN 16 bar, volumetric range 150-1050 litres/h, consi-

Cover Plates:

sting of: Controller for return, complete with

Made of 0.5 mm sheet steel Sendzimir-

shut-off valve, filling valve, drain valve and

galvanised on both sides, polyester-lacque-

threaded connector.

red similar to RAL 9016 on external surface,

Combined flow valve complete with shut-off

for covering the compression or threaded

valve, filling valve, drain valve and threaded

couplings

connector

..................... off

.....................

off

Armoured Flexible Tubing: Zehnder armoured flexible tubing with suitability verification by the Technical Control Board, Germany for use in heating installations, consisting of temperature- and ageingresistant EPDM with woven stainless steel braiding DN 25, PN 10 bar, length 500 mm .....................

off


씹 14

15 ě”°

Zehnder ZIP Radiant Ceiling Panels. Technical Data for Layout Design. Hot-water Flow Rate Less Than

Resistance Loss Calculation. The resistance loss of the Zehnder ZIP Radiant

Minimum Value. If the minimum flow rate

Ceiling Panels is calculated as the sum of

per tube group (4 parallel tubes) cannot be

the tubing-group resistance loss and of the

reached and if it is not possible to connect

resistance loss in the group connections to

several panels in series, a heat emission

the piping system. When Zehnder volume-

reduction of 15% must be allowed for. This

tric flow controllers are installed, the additio-

means that an emission correction factor of

nal resistance loss as per the graph below

about 1.18 must be used when designing

(resistance loss/combined volumetric flow

the panel.

controller) must be used.

Heating Water Flow Rate. The thermal output data apply to fully developed turbulent flow regimes within the tubing of the radiant panel. The minimum flow velocity necessary for this purpose is determined by

obtained from the table shown.

Hot-water Flow Rate Less Than Minimum Value. If the minimum flow rate per tube group (4 parallel tubes) cannot be reached and if it is not possible to connect several panels in series, a heat emission

Resistance Loss through the Connectors

Pressure drop in Pa

the return temperature tR. The minimum heating-water mass flow per tube group is

7000

6000

5000

4000

3000

reduction of 15% must be allowed for. This 2000

means that an emission correction factor of about 1.18 must be used when designing

1000

the panel. 0 500

1000

1500

2000

Total flow rate of heating water kg/h


A

400

B

mass flow in kg/h

Pressure Loss kPa

ll e a ra

350

Volumetric Flow Controller DN 25

l

1 mo dule

20,1

180

21,3

210

22,5

240

23,6

270

24,7

300

25,7

330

26,7

360

27,7

50

390

28,6

0

420

29,5

450

30,4

480

31,2

510

32,0

540

32,7

570

33,4

600

34,1

630

34,8

660

35,4

690

36,0

720

36,6

750

37,2

780

37,7

810

38,3

840

38,8

870

39,3

900

39,7

930

40,2

960

40,6

990

41,1

1020

41,5

1050

41,9

np

150

od

u le

si

300 250

2m

Pressure drop in Pa/m

Resistance Loss through the Tube Groups

200

C 150 100

o 3m

500

1000

s le du

in

1500

l lle ra a p

2000

Total flow rate of heating water kg/h

Flow rate of heating water kg/h

Minimum Mass Flow Rate of Heating Water

900 800 3

700

m

od

ul

es

600 2

500

m

od

u le

si

np

400 300

ara

in

pa

ra

ll e

l

C

ll e l

B 1m

odu

le

A

200 100 0 40

50

60

70

80

Return temperature in 째C


RHC-ZIP-BR1, V0509, English, Subject to change without notice Zehnder GmbH · Systeme für Strahlungsheizung und -kühlung · Europastraße 14 · D-77933 Lahr Tel. +49 (0) 78 21/586-0 · Fax +49 (0) 78 21/586-403 · info@zehnder-online.de · www.zehnder-online.de