HOME INSPECTION REPORT 1234 Main St. Bolton Ontario L7E0N4 Buyer Name
02/09/2022 9:00AM
Inspector
Panos Loucaides
Certified Master Inspector 416-997-3644
panos@inspectionservicesgroup.com
Inspection Services Group Inc
Agent
Agent Name
555-555-5555 agent@spectora.com
Page 1 of 38
1234 Main St.
Buyer Name
TABLE OF CONTENTS 1: Inspection Details
4
2: General Notes
5
3: Insurance Company Information
7
4: Exterior Components
8
5: Garage
11
6: Roof
13
7: Cooling System
15
8: Heating System
17
9: Plumbing System
20
10: Electrical System
23
11: Structural Components
25
12: Basement, Crawlspaces
27
13: Kitchen(s)
28
14: Interior Components
29
15: Laundry Area
30
16: Bathroom(s)
32
17: Smoke and CO Alarms
33
18: Attic
34
19: Indoor Air Quality and Home Environment
36
20: Conclusion
38
Inspection Services Group Inc
Page 2 of 38
1234 Main St.
Buyer Name
SUMMARY
121
5
5
ITEMS INSPECTED
MAINTENANCE ITEM
RECOMMENDATION
4.4.1 Exterior Components - Exhaust Vents: Mesh screen is detached 4.12.1 Exterior Components - Soffits and Fascia: Minor damage noted on the soffits 5.5.1 Garage - Service Doors: Door doesn't latch 6.6.1 Roof - Downspouts, Gutters and Extensions: Downspouts Discharging to close to house 6.6.2 Roof - Downspouts, Gutters and Extensions: Extend Downspouts Shedding from Upper Roof 8.5.1 Heating System - Filter: Air filter is dirty 10.3.1 Electrical System - Breakers & Branch Circuit Wiring: Double Tapped Breaker(s) 11.1.1 Structural Components - Foundation: Settlement crack noted at an interior wall 11.5.1 Structural Components - Floor / Slab: Normal shrinkage cracks noted on the concrete slab 16.3.1 Bathroom(s) - Bathtubs and Showers: The hot & cold water supplies are reversed
Inspection Services Group Inc
Page 3 of 38
1234 Main St.
Buyer Name
1: INSPECTION DETAILS section-OGUwYmMxMjItMjJlMy00ZWFhLWIyMTgtYmVhNzdhNDA5YTI5
Information Age of Home
Attendance
Exposure
Garage
Inspection Start Time
Inspection End Time
Occupancy
Residence Type/Style
Utilities
Water and Sewers
Weather Conditions
Soil Conditions
Less than 5 Years Attached Garage Occupied - Furnished: Moderate to heavy personal and household items observed. Access to some items such as: electrical outlets/receptacles; windows; wall/floor surfaces; and cabinet interiors may be restricted by furniture or personal belongings. Any such items are excluded from this inspection report. City water and sewers., AS PER:, Home Owner
Client and Buyer Agent present 1:00 PM
Single Family Home / Townhouse
Cloudy
North West 3:30 PM
The utilities where on at the time of inspection.
Snow Covered, Frozen
Temperature at time of inspection Temperature in C: 2
Inspection Services Group Inc
Page 4 of 38
1234 Main St.
Buyer Name
2: GENERAL NOTES section-NjAyMDczODItZjBlZC00ZTEyLTgwNTAtYmU0MzU2YmJhNmUw
Information Inspection Standards and General Guidelines This inspection has been performed according to the CSA A 770 Canadian National Standards of Practice. In some cases; we may go above the Standards as a courtesy to the client. This is a functionality inspection and does not include references to cosmetic items. Houses are built with the rules and regulations of their construction year. Updating to current standards (code requirements) is not mandatory. This is not a code compliance inspection. Houses are expected to have some wear and tear a few years after construction. Some of the noted items on the report may be relevant to normal wear and tear.
Life Expectancy of Components Please click on the link below to find more information about the Life Expectancy of the different components of your home: https://inspectionservicesgroup.com/life-expectancy-of-components/
New Construction Home under Tarion Warranty This is a new construction home that has not been lived in yet. Some items may be covered under the different stages of the Tarion Warranty program. Plumbing fixtures and other components have been tested briefly. These tests do not in any way simulate actual living conditions inside the home. The condition of these components may change when used under normal living conditions.
Inspection Services Group Inc
Page 5 of 38
1234 Main St.
Buyer Name
General Limitations Exterior - Inspection of the exterior may be limited by vegetation, sheds and other personal belongings. We cannot move any of these items and do not have visibility behind these items. We do our best to thoroughly inspect these areas as long as it is safe and we have access. Garages - Inspection of the garage and its components may be limited by items stored in the garage or parked cars. Roof - Due to the unpredictable and latent nature of roof leaks, no assurances or warranty can be provided that your roof and flashings will not develop leaks within the approximate expected life span given by the inspector. We caution the home owner that skylights are prone to leaks. Ice damming problems are beyond our ability to predict. Extreme weather conditions such as heavy snow fall, heavy rainfall, freezing rain and ice built up, may cause leaks to any roof and are beyond our ability to predict. Attic - Some areas in the attic may not be fully accessible or visible, due to low roof line, insulation present, interior skylights, etc. The comments in the report reflect only the visible areas of the attic. Inspection of the attic may be done from the attic hatch, if the inspector deems the area to be unsafe or to prevent potential damages and/or movement of the insulation. Interiors - Inspection of interior spaces may be limited by furniture, carpets, personal belongings and paintings. The inspector is not required to move any of the above items. A representative number of outlets and windows may be inspected. Any such items that are not accessible cannot be inspected. The inspector does not make reference to cosmetic issues. Bathroom - Bathrooms can consist of many features from jacuzzi tubs and showers to toilets and bidets. Because of all the plumbing involved it is an important area of the house to look over. Moisture in the air and leaks can cause mildew, wallpaper and paint to peel, and other problems. The visual access to drain lines and supply pipes underneath the floors and behind walls is restricted. No assurances or warranty can be provided regarding proper drainage conditions or performance. We are unable to predict slow leaks in drains and water lines. Shut Off valves and pipe connections leaks cannot be predicted and may happen at any time. Structural - This report makes reference to the visible parts of the structure, whether inside or outside the home. We do not have visibility under the ground, behind walls, under floors or any other items that restrict visibility. We do not offer any engineeting services or engineering advice. If the report identifies any major structural issues or if the client is planning to do major renovations, the advice of an engineer should be utilized. Basement - Full Inspection of the basement may be limited due to furniture or personal items stored. The comments on this report reflect only the visible areas of the basement. A representative number of outlets are tested. The Inspector does not inspect basement sleeping areas for compliance to local by-laws. Every municipality nay have different by-laws concerning basement apartments. The client is advised to do their due diligence with the local authorities in regards to basement apartment requirements. Electrical - All electrical work should be carried out by a licensed electrical contractor. The Inspector does not conduct an exhaustive electrical inspection and does not have visibility to electrical systems hidden behind walls. Electrical system deficiencies should be addressed, as some may be of great importance and pose a safety hazard. HVAC - We are not HVAC professionals. Feel free to hire one prior to closing. The inspection of the heating system is visual, using the standard operating controls and it is not technically exhaustive. Full Inspection of the Heat exchanger is beyond the scope of this inspection and can only be done by a licensed HVAC technician. If any deficiencies are identified in this report in regards to the operation of the heating equipment it is recommended that an HVAC technician is hired before closing, because a technically exhaustive inspection may reveal other issues that require attention. Main Plumbing System - The visual access to main drain lines underneath the basement floors and behind walls is restricted. No assurances or warranty can be provided regarding proper drainage conditions or performance. Sewer back-up is beyond our ability to detect or predict. The visual access to supply pipes behind walls or under floors is restricted. We are unable to predict slow leaks in drains and water lines. Shut Off valves and pipe connections leaks cannot be predicted and may happen at any time. Air Surveys - Air quality surveys or observations on the home environment are limited to conditions on the day of the inspection and may vary. The survey results may be impacted by use of air fresheners, diffusers or other household fragrances and/or the use of cleaning products. If you would like more accurate testing to determine mold spores present in the home environment we recommend booking a complete Indoor Air Quality Test on the property.
Inspection Services Group Inc
Page 6 of 38
1234 Main St.
Buyer Name
3: INSURANCE COMPANY INFORMATION section-NWZhOGE0MmItMGYzZS00YzcwLWEwZTYtODg5MThiZWY3YTQ2
Information Age of Home
AC Manufacture Year
Furnace Manufacture Year
Electrical Panel Type
Panel Installation Date
Electrical Service AMPS
Electrical Distribution system type
Plumbing system
Water Heater Manufacture Year
Sump Pump
Back Flow Valve
1 - 5 Years
Breaker Panel
Copper Wiring
No Sump pump present
Inspection Services Group Inc
2020 2020
Supply Line is Plastic, Plumbing Pipes Are PEX - SuperPex Brand
2020
100 AMPS 2020
No back flow Valve is visible
Page 7 of 38
1234 Main St.
Buyer Name
4: EXTERIOR COMPONENTS section-MWFmNzY0OWMtNmZmMS00N2MwLWI5YWEtMmM0MTA0Njk1OTEz
NP ACC / MNT UPD REP MON NI 4.1
Vegetation
X
4.2
Driveway and Walkway
X
4.3
Porch, Steps and Railings
X
4.4
Exhaust Vents
4.5
Exterior Windows and Screens
X
4.6
Exterior Entry Doors
X
4.7
Window Wells
X
4.8
Gas Meter and Exterior Gas Installations
X
4.9
Grading / Drainage
X
X
4.10 Exterior Cladding
X
4.11 Decks/Balconies
X
4.12 Soffits and Fascia
X
4.13 Fences and Retaining Walls
X
4.14 Basement Stairways ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Porch, Steps and Railings: No material deficiencies noted
Exterior Entry Doors: No material Decks/Balconies: Not applicable deficiencies noted
Fences and Retaining Walls: No fences present
Basement Stairways: Not applicable
Vegetation: Nothing material to report Proper landscaping of vegetation around home is recommended as ongoing maintenance.
Driveway and Walkway: No major system safety or function concerns noted at time of inspection Sealing and resurfacing of driveways is advised when required. These surfaces can last 15-20 years with proper maintenance.
Exterior Windows and Screens: No material deficiencies noted
It is normal for caulking to deteriorate over time due to natural weather exposure. Recommend monitoring and recaulking around windows and doors when required.
Window Wells: No material deficiencies noted Window wells should be kept clear of debris at all times. Older window wells should be monitored for proper drainage.
Gas Meter and Exterior Gas Installations: No material deficiencies noted No gas odors detected. Please note that the inspector does not conduct specific tests with equipment or soap tests for gas leak detection. If a gas odor is noted it will be reported. The area around the gas meter should be kept clear of bushes, enclosures and trees, for ease of access during an emergency.
Inspection Services Group Inc
Page 8 of 38
1234 Main St.
Buyer Name
Grading / Drainage: Grading is Sufficient No material deficiencies noted. The grading around the house should be such that it will allow for rain water to shed away from the foundation into the swale around the home. 1/4 in for 10' is the general recommendation.
Exterior Cladding: No major system safety or function concerns noted at time of inspection Regular yearly maintenance of all siding materials, metal trim or metal lintels, bricks and/or mortar is required, this includes refinishing, caulking at transitions and utility connections, painting or repairs where and when needed. Ensure all exposed areas (holes, cracks, pipe entry points, or at any dissimilar material abutments, etc) are sealed to reduce the risk of water intrusion and subsequent damage.
Limitations Vegetation
SNOW COVERING LIMITS VISIBILITY IN SOME AREAS. Grading / Drainage
DUE TO SNOW COVER
The comments reflect the visible parts of the grading.
Observations 4.4.1 Exhaust Vents
MESH SCREEN IS DETACHED
Maintenance Item
This may allow insects or birds to nest in the vent. It is recommended to install the mesh screen properly.
4.12.1 Soffits and Fascia
MINOR DAMAGE NOTED ON THE SOFFITS
Recommendation
This was probably done during construction. Recommend repair.
Inspection Services Group Inc
Page 9 of 38
1234 Main St.
Inspection Services Group Inc
Buyer Name
Page 10 of 38
1234 Main St.
Buyer Name
5: GARAGE section-N2FmOTQ3ZmEtN2JhYy00ZDM0LWFiOGYtY2JkYWIyZGJkZTlm
NP ACC / MNT UPD REP MON NI 5.1
Garage Walls and Ceilings
X
5.2
Garage Floor
X
5.3
Garage Door
X
5.4
Garage Door Operation
X
5.5
Service Doors
5.6
Garage Windows
5.7
Garage Gas Proofing
5.8
Storage, Shelving or Other Structures
5.9
Stairs and Railings
X X X X X
5.10 Garage Heating ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Garage Walls and Ceilings: No major system safety or function concerns noted at time of inspection
Garage Floor: No material deficiencies noted
Storage, Shelving or Other Structures: Not applicable
Stairs and Railings: No material deficiencies noted
Garage Windows: None Present
Comments reflect visible portions.
Garage Heating: None present
Garage Door: No deficiencies observed
Garage doors and garage door frames, require frequent maintenance. This includes painting, re-caulking, lubricating the rollers and tightening of the bolts on the door.
Garage Door Operation: The door is operational at the time of the inspection Periodic calibration of contact sensitivity is advised. Always ensure stored items are away from light beam sensors to ensure proper operation.
Garage Gas Proofing: Garage gas proofing An attached garage must be gas proofed, so that exhaust fumes from cars parked inside the garage or at the driveway, will not enter the home. To the extend we have visibility, there are no gaps at the walls or ceilings.
Observations 5.5.1 Service Doors
DOOR DOESN'T LATCH
Recommendation
This is due to the self closing hinges not set correctly. This has to be repaired so that the door latches and seals fully on its own.
Inspection Services Group Inc
Page 11 of 38
1234 Main St.
Inspection Services Group Inc
Buyer Name
Page 12 of 38
1234 Main St.
Buyer Name
6: ROOF section-MTY2Y2Y2ZjgtYmE5Ni00NjRmLWI0MTAtMWNkMWU5MjllNzE3
NP ACC / MNT UPD REP MON NI 6.1
Roof Coverings
X
6.2
Flashing
X
6.3
Vents & Roof Penetrations
X
6.4
Chimneys
X
6.5
Skylight
X
6.6
Downspouts, Gutters and Extensions ACC = Acceptable
NP / NI = Not Present / Not Inspected
X MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Age
Material
Method of Inspection
Vents & Roof Penetrations: No material deficiencies noted
Chimneys: Not applicable
Skylight: Not applicable / not present
1 - 5 Years Old. The Roof age is based on estimates. Different material may react in a different a way under different conditions.
Asphalt Shingles
From ground with binoculars and telescoping pole
Ongoing maintenance is required.
Roof Coverings: No material deficiencies were found The life expectancy of asphalt shingles is 15 to 20 years, or more, depending on the quality of shingles installed and installation practices.
Flashing: No material deficiencies noted Regular caulking of roof penetrations, fasteners, vents & flashing and around the perimeter of the roof system as general maintenance is required to prevent leakage.
Limitations
Inspection Services Group Inc
Page 13 of 38
1234 Main St.
Buyer Name
Roof Information
INSPECTION LIMITATIONS
The inspection was done mostly from the ground; therefore some areas of the roof may not be visible., The roof was partly covered with snow therefore the comments reflect only the visible parts of the roof.
Flashing
DUE TO SNOW COVER INSPECTION WAS LIMITED The comments reflect the visible areas of the flashing.
Vents & Roof Penetrations
SNOW COVERING LIMITS INSPECTION
Observations 6.6.1 Downspouts, Gutters and Extensions
DOWNSPOUTS DISCHARGING TO CLOSE TO HOUSE
Maintenance Item
Downspouts are shedding very close to the house. Leaders should be extended at least 4 feet beyond the foundation perimeter to move water away from foundation. 6 feet is preferred where space is available.
6.6.2 Downspouts, Gutters and Extensions
EXTEND DOWNSPOUTS SHEDDING FROM UPPER ROOF
Maintenance Item
It is recommended that the downspout is extended to the lower eaves, to prevent faster deterioration of the shingles in that area.
Inspection Services Group Inc
Page 14 of 38
1234 Main St.
Buyer Name
7: COOLING SYSTEM section-Y2Q4ZDAwZjctZWIzNC00MTY2LWE2ZWUtMzU0MmVmZTBmOTA4
NP ACC / MNT UPD REP MON NI 7.1
Exterior Unit
X
7.2
Electrical Disconnect and Power Requirements
X
7.3
Refrigerant Lines
X
7.4
AC System Condition & Operation ACC = Acceptable
NP / NI = Not Present / Not Inspected
X MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Brand
Manufacturing Year
AC Size
Refrigerant Type
Exterior Unit: No material deficiencies noted
Electrical Disconnect and Power Requirements: Electrical Disconnect Type
Goodman R-410A
2020
2 Ton
Pullout switch
Electrical Disconnect and Power Requirements: Maximum AMPS 15 AMPS
Electrical Disconnect and Power Requirements: Minimum AMPS 10.3
Electrical Disconnect and Power Requirements: Breaker rating is as per manufacturer specifications
Exterior Unit: Exterior Unit Mounting / Location Suspended
Refrigerant Lines: Refrigerant lines in serviceable condition Replacement of deteriorated insulation is to be expected over time as general maintenance.
Inspection Services Group Inc
Page 15 of 38
1234 Main St.
Buyer Name
Limitations AC System Condition & Operation
NOT OPERATED TO AVOID POSSIBLE COMPRESSOR DAMAGE The unit is not tested when temperatures are below 16.
Inspection Services Group Inc
Page 16 of 38
1234 Main St.
Buyer Name
8: HEATING SYSTEM section-MWE2YzdjMGYtMGNjNS00MjdjLTllZTAtZTVmODg2ZTY3ZDFm
NP ACC / MNT UPD REP MON NI 8.1
Thermostat
X
8.2
Heating system Operation
X
8.3
Furnace Venting and Combustion air
X
8.4
Safety Shut-off
X
8.5
Filter
8.6
Condensate Removal
X
8.7
Humidifier
X
8.8
HRV System
X
8.9
Distribution
X
X
8.10 Auxillary Heating Sources ACC = Acceptable
X
NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Thermostat: Thermostat Type Digital Thermostat, WIFI Type Thermostat
Heating system Operation: Fuel type Natural Gas
Filter: Filter Type
Disposable Filter
Thermostat: Functional at the time of inspection Thermostats are not checked for calibration or timed functions.
Heating system Operation: Manufacturing Year 2020
HRV System: HRV System
Central HRV System present
Heating system Operation: BTU Rating 40000
Furnace Venting and Combustion air: Furnace Venting and Combustion air Outdoor Combustion Air
Distribution: Distribution Material Metal ducts with Air exchange vents
Auxillary Heating Sources: Not present
Inspection Services Group Inc
Page 17 of 38
1234 Main St.
Buyer Name
Heating system Operation: No material deficiencies noted. All components appeared to be in serviceable condition at the time of the inspection. Operated and functional. We advise annual servicing and maintenance. This will ensure your furnace is functioning at maximum capacity at all time and will lengthen the functionality of your unit. With proper maintenance the service life of a gas furnace is up to 20 years. Inspection of heat exchangers is beyond the Standards of Practice and the scope of this inspection, and can only be done by an HVAC technician.
Video
(click here to view on web)
Furnace Venting and Combustion air: No material deficiencies noted
Client should ensure that the vent pipe is always unobstructed and never damaged or altered.
Safety Shut-off: Emergency shut off switch is present The Emergency switch is not to be used for operating the Unit, but only in case of emergencies. Ensure it is clearly labelled at all times.
Condensate Removal: No Material Deficiencies noted
Condensate pipes require frequent cleaning. If a neutralizer is installed, it needs replacement every few years.
Inspection Services Group Inc
Page 18 of 38
1234 Main St.
Buyer Name
Humidifier: No material deficiencies noted MAINTENANCE: The humidifiers filter should be replaced every two years or as often as required. Saddle type water valves (if installed) are known to leak, therefore monitoring or replacement of such valves is recommended.
HRV System: HRV was noted in functional condition Cleaning or replacement of filters are recommended every 3-4 months. Removal and cleaning of the units core is required once a year as general maintenance.
HRV Exhaust
HRV Intake
Distribution: Central Air heating/cooling
At the time of the inspection, all appeared to be functioning and in serviceable condition.
Observations 8.5.1 Filter
AIR FILTER IS DIRTY
Maintenance Item
Disposable filters should be changed every three months and reusable filters cleaned every three months. Consider changing filters more often during the heating season. For improved air quality we recommend higher MERV filters.
Inspection Services Group Inc
Page 19 of 38
1234 Main St.
Buyer Name
9: PLUMBING SYSTEM section-YWZkNTAxNDUtYWY0MS00NGQyLTkxMzAtNjNjYTVjY2IxMWZm
NP ACC / MNT UPD REP MON NI 9.1
Hose Connections & Shutoff Valves
X
9.2
Water Heater
X
9.3
Main Water Shutoff & Service Line
X
9.4
Gas Lines
X
9.5
Water Lines
X
9.6
Drain, Waste & Vent Plumbing
X
9.7
Sump Pump
X
9.8
Backwater Valve
X
9.9
Water Softeners and/or Filtration Systems
X
9.10 Septic or Cisterns ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Water Heater: Water Heater Age Water Heater: Water Heater 2020 Capacity
Water Heater: Water Heater Fuel Type
Main Water Shutoff & Service Line: Service Line Type
Sump Pump: Sump Pump not installed
Tankless
Plastic
Water Lines: Plumbing pipes material Plumbing Pipes Are PEX SuperPex Brand
Natural Gas
The absence of a sump pump, is not a deficiency.
Water Softeners and/or Filtration Septic or Cisterns: Not applicable Systems: Not applicable / Not / Not present present
Inspection Services Group Inc
Page 20 of 38
1234 Main St.
Buyer Name
Hose Connections & Shutoff Valves: No Material Deficiencies noted Exterior shut off valves need to be shut off before freezing temperatures begin
Hose Connections & Shutoff Valves: Interior Shut-off Location Basement Ceiling
Water Heater: No major system safety or function concerns noted at time of inspection
Water Heaters have a life expectancy of approximately ten years. Regular servicing and inspection of the water heater by a qualified technician will prolong its life.
Inspection Services Group Inc
Page 21 of 38
1234 Main St.
Buyer Name
Main Water Shutoff & Service Line: No deficiencies noted Water pressure appears adequate when running multiple fixtures simultaneously. The main shut off valve is NOT operated during the Home Inspection. Please note that valves may leak over time due to normal wear and tear of interior parts.
Gas Lines: No material deficiencies noted
The inspector does not conduct gas leak checks with gas detectors or soap tests. If there is a distinctive smell of gas, it will be noted on this report.
Water Lines: No material deficiencies noted at the visible parts of the pipes Not all pipes are visible due to the finished areas of the house. The inspector is not required and does not operate any shut off valves at the time of the inspection. Periodic replacement of valves and shutoffs is to be expected.
Drain, Waste & Vent Plumbing: No material defects No leaks observed at the time of the inspection, unless otherwise noted in this report - scoping drain lines is not part of the home inspection. The inspector can not guarantee or warranty the condition of concealed plumbing. Note that drain and vent pipes may be hidden behind walls where access is not possible. These comments reflect the visible parts of the system.
Backwater Valve: Backflow Not Installed Back flow valves are required only by some jurisdictions. Some insurance companies require them in certain areas due to high flooding risk. Inquire with your insurance company about this.
Inspection Services Group Inc
Page 22 of 38
1234 Main St.
Buyer Name
10: ELECTRICAL SYSTEM section-YzkzMTM1NTItMDRhOC00NzE0LWJkOWUtOTgxMmNmYzFjNGNh
NP ACC / MNT UPD REP MON NI 10.1 Electrical Service
X
10.2 Electrical Panel
X
10.3 Breakers & Branch Circuit Wiring
X
10.4 GFCI
X
10.5 AFCI
X
10.6 Grounding and Bonding
X
10.7 Outlets, Wiring and Lighting
X
ACC = Acceptable
NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Electrical Service: No material deficiencies noted
Panel Manufacturer
Wiring type
Breakers & Branch Circuit Wiring: GFCI: GFCI Location All of the circuits appeared GFCI serves exterior outlets ., serviceable GFCI serves bathrooms, GFCI
Copper wiring
Eatons
Service Size 100 AMPS
outlets serve the kitchen
AFCI: AFCI Location
AFCI installed for bedroom and other circuits
Grounding and Bonding: No discrepancies noted Correct bonding was observed.
Electrical Panel : No major system safety or function concerns noted at time of inspection at main panel box The area around the panel should always be accessible for service purposes and emergencies.
GFCI: No material deficiencies noted
Please note that this is only a visual inspection. The inspector does not turn breakers off as this may affect devices plugged in these circuits. Client is advised to test the breakers after they have possession of the property.
AFCI: No material deficiencies noted
Please note that this is only a visual inspection. The inspector does not turn breakers off as this may affect devices plugged in these circuits. Client is advised to test the breakers after they have possession of the property.
Outlets, Wiring and Lighting: No Material deficiencies noted
Some outlets may not be accessible due to furniture and or stored personal items. A Representative number of outlets was tested.
Observations 10.3.1 Breakers & Branch Circuit Wiring
DOUBLE TAPPED BREAKER(S) Inspection Services Group Inc
Maintenance Item
Page 23 of 38
1234 Main St.
Buyer Name
Double Tap observed. Double tapping (i.e. 2 wires on a single pole breaker) can add to the load of the affected circuit causing a possible overload and tripping breakers, or result in loose connections and overheating of the breaker or connections. Some electrical panel manufacturers allow double taps on their breakers, but this is not something we can confirm. Ideally, doubled-up circuits should be independently fused.
Inspection Services Group Inc
Page 24 of 38
1234 Main St.
Buyer Name
11: STRUCTURAL COMPONENTS section-Mjk0MzI1NTItODZkNC00MDQzLWJiNGYtNzhiNmQ3NjdlZGRi
NP ACC / MNT UPD REP MON NI 11.1 Foundation
X
11.2 Joists & Sub Floors
X
11.3 Beams / Bearing Walls
X
11.4 Piers / Posts
X
11.5 Floor / Slab ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Joists & Sub Floors: No material deficiencies noted
Piers / Posts: No deficiencies were observed at the visible Some parts of the structure may portions of the structural not be visible due to finished components of the home areas.
Some parts of the structure may not be visible due to finished areas.
Beams / Bearing Walls: No material deficiencies noted
The comments reflect only the visible parts of the structural components. Visibility may be limited in a finished or partly finished basement.
Observations 11.1.1 Foundation
SETTLEMENT CRACK NOTED AT AN INTERIOR WALL
Recommendation
We recommend monitorin and it becomes wider, the builder should be contacted to seal. This is a 7 year item of your Tarion Warranty.
11.5.1 Floor / Slab
NORMAL SHRINKAGE CRACKS NOTED ON THE CONCRETE SLAB
Recommendation
This is typical in homes and does not affect the structural integrity of the home.If the cracks become more than 4 mm wide they should be sealed.
Inspection Services Group Inc
Page 25 of 38
1234 Main St.
Inspection Services Group Inc
Buyer Name
Page 26 of 38
1234 Main St.
Buyer Name
12: BASEMENT, CRAWLSPACES section-OThjMmNlZjItOTdiZC00ZGQxLWFiZDQtNzQzYmYyYjI0YzRj
NP ACC / MNT UPD REP MON NI 12.1 Stairs and Railings
X
12.2 Doors
X
12.3 Windows
X
12.4 Floors
X
12.5 Surface Drains
X
12.6 Walls and Ceilings
X
12.7 Insulation and Vapour Barrier
X
12.8 Cold Room
X
12.9 Moisture Detection
X
ACC = Acceptable
NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Stairs and Railings: Functional at Doors: No major system safety or Windows: Operated windows are time of inspection function concerns noted at time functional of inspection At time of inspection. A representative number of windows is operated.
Floors: No material deficiencies noted
Surface Drains: Good overall condition
Inspection may be limited by furniture and personal items.
Walls and Ceilings: No material deficiencies noted at the time of the inspection
Insulation and Vapour Barrier: No Material Deficiencies noted at the visible areas of the basement Visibility may be restricted from furniture, personal items or finished areas.
Cold Room: No material deficiencies noted
Avoid storing boxes and other organic material in the cold room, as this is a typically cold and moist area by nature.
Moisture Detection: No moisture penetration was noted at the time of the inspection
Identification of moisture penetration, may not always be possible, due to the weather conditions at the time of the inspection (Dry weather or freezing temperatures).
Inspection Services Group Inc
Page 27 of 38
1234 Main St.
Buyer Name
13: KITCHEN(S) section-NGYxYzlmZjAtOTE1Mi00NmEzLWFmMGYtZWE2NzFlMjNlOTA1
NP ACC / MNT UPD REP MON NI 13.1 Cabinets and Counter tops
X
13.2 Kitchen Plumbing
X
13.3 Cooking appliances
X
13.4 Dishwasher
X
13.5 Refrigerator
X
13.6 Built-in Microwave
X
13.7 Exhaust Hood / Ventilator ACC = Acceptable
X
NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Cabinets and Counter tops: No deficiencies observed
Built-in Microwave: Not applicable
Periodic adjustments of hardware and fasteners is advised.
Exhaust Hood / Ventilator: Exhaust Hood / Ventilator Type Ventilator present- exterior vented
Kitchen Plumbing: No deficiencies observed No leaks were noted at time of inspection. Leaks can occur without warning.
Cooking appliances: Appliance inspection is beyond the scope of a home inspection The cooktop was tested at the time of inspection and it was operational. These components can fail at anytime without warning. No warranty, guarantee, or certification is given as to future operation. The full cooking operation and capabilities of the oven cannot be tested and are beyond the scope of a home inspection.
Dishwasher: Appliance inspection is beyond the scope of a Home Inspection
The dishwasher is put on a short cycle to test for power and water leaks. The dishwasher is not tested for its primary function. The future operation of the dishwasher cannot be guaranteed in any way.
Refrigerator: Appliance inspection Refrigerator and Ice/Water Filtration is beyond the scope of a Home Inspection A basic temperature reading is taken for the refrigerator. The inspection of water purification or ice makers is also beyond the scope of the inspection. A very basic operational test is performed as a courtesy. The future operation of the refrigerator cannot be guaranteed in any way.
Inspection Services Group Inc
Page 28 of 38
1234 Main St.
Buyer Name
14: INTERIOR COMPONENTS section-MDYxOThlOTYtODNlYi00ZWFlLWE2MjctYzVhNTI1ODFhYzY5
NP ACC / MNT UPD REP MON NI 14.1 Interior Stairs and Railings
X
14.2 Ceilings and Walls
X
14.3 Floors
X
14.4 Doors and Patio doors
X
14.5 Window Condition
X
14.6 Central Vacuum ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Interior Stairs and Railings: No material deficiencies noted
Ceilings and Walls: No material deficiencies noted Some areas may not accessible due to personal items and furniture.
Doors and Patio doors: No Window Condition: Operated material deficiencies noted at the windows appeared functional time of the inspection At time of inspection
Inspection Services Group Inc
Floors: No material deficiencies noted Furniture and personal belongings may limit the inspection.
Central Vacuum: Not present Rough in noted terminating in the garage
Page 29 of 38
1234 Main St.
Buyer Name
15: LAUNDRY AREA section-OTRlYmU0MTgtM2QxYi00NWI1LTkyOTMtNTA2YTQ0YjY0OWRl
NP ACC / MNT UPD REP MON NI 15.1 Cabinets & Counters
X
15.2 Floor Drain
X
15.3 Laundry Room Plumbing
X
15.4 Dryer Vent
X
15.5 Laundry Room Ventilation
X
15.6 Laundry Appliances ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Cabinets & Counters: No deficiencies observed
Laundry Room Plumbing: No material deficiencies noted
Periodic tightening of cabinets is required as maintenance.
Laundry Room Ventilation: Laundry Room Ventilation Exhaust Fan
Laundry Room Ventilation: The Laundry Appliances: Laundry exhaust fan was operated and no Appliances issues were found Washer and Dryer present Floor Drain: No visible drain In the absence of a drain, an alarm device can be placed on the floor, that will notify you in the case of a leak.
Inspection Services Group Inc
Page 30 of 38
1234 Main St.
Buyer Name
Dryer Vent: Dryer is properly vented to the exterior The exterior vent cover and the duct need frequent cleaning to prevent built up of lint. A blocked dryer vent may become a fire hazard.
Laundry Appliances: Appliance inspection is beyond the scope of a home inspection
We are not appliance technicians. The Appliances are put on short cycles to test for Power and Leaks only. The future operation of the appliances cannot be guaranteed in any way. If any issues are noted, these will be referenced on the report as a courtesy.
Inspection Services Group Inc
Page 31 of 38
1234 Main St.
Buyer Name
16: BATHROOM(S) section-YzExNThlMDktNDFhNS00N2I4LTgzMWMtNjUxOTY5YTM1NzU2
NP ACC / MNT UPD REP MON NI 16.1 Cabinets & Counters
X
16.2 Plumbing and Sinks
X
16.3 Bathtubs and Showers
X
16.4 Spa Tubs
X
16.5 Toilets and Bidets
X
16.6 Ventilation ACC = Acceptable
X NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Cabinets & Counters: No deficiencies observed Periodic adjustments of hardware is advised.
Toilets and Bidets: 0bserved as functional and in good visual condition
Plumbing and Sinks: No material Spa Tubs: Not applicable Deficiencies noted at the time of the inspection Review may be limited due to personal property stored under the sink.
Ventilation: The bathroom fans were operational Bathroom fans should be cleaned on regular basis to ensure proper suction.
Observations 16.3.1 Bathtubs and Showers
THE HOT & COLD WATER SUPPLIES ARE REVERSED
Recommendation
This is not a functional problem but to someone who is not familiar with this condition unexpected hot water could scald them.
Master Bath
Inspection Services Group Inc
Page 32 of 38
1234 Main St.
Buyer Name
17: SMOKE AND CO ALARMS section-MTAzOTBmYmUtZjk4Yy00M2IyLTk2NzUtYTBiNTBkMGFlZjgy
NP ACC / MNT UPD REP MON NI 17.1 Smoke Alarms
X
17.2 Carbon Monoxide Alarms
X
ACC = Acceptable
NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Carbon Monoxide Alarms: Combination Smoke and CO Alarm is installed Smoke Alarms: Installed as per Current code requirement Current code requires smoke alarms to be installed on every floor and inside the bedrooms. The unit must have audio and visual alarms. Battery operated devices should be installed as a back up and batteries changed every six months. Test the devices on a monthly basis to ensure that they are operational. Smoke Detectors should be replaced every 8 to 10 years or as per Manufacturer's specifications.
Carbon Monoxide Alarms: Installed as per Minimum Law Requirement By law, every house with an attached garage, fireplace and fuel burning appliances is required to have a CO alarm outside the sleeping areas of the home. CO Alarms should be replaced every 6 to 8 Years, or as per Manufacturer's specifications. A general recommendation is having Carbon Monoxide detectors on every floor there is a fuel burning appliance to meet current standards. Carbon Monoxide detectors are now a requirement in all bedrooms. Battery operated devices should be installed as a back up and batteries changed every six months. Carbon Monoxide detectors have a useful life of 7 years. Test the devices on a monthly basis to ensure that they are operational. Recommend reviewing Ontario regulations to enhance safety of occupants. https://www.ontario.ca/laws/regulation/070213
Inspection Services Group Inc
Page 33 of 38
1234 Main St.
Buyer Name
18: ATTIC section-ZGQ2ODFjZGMtZTgwOS00MTE0LTliN2MtMDIwNTg2ZWRhMGE1
NP ACC / MNT UPD REP MON NI 18.1 Hatch & Method of Inspection
X
18.2 Insulation & Vapour Barrier
X
18.3 Framing
X
18.4 Sheathing
X
18.5 Ventilation
X
18.6 Exhaust Vents & Ductwork
X
18.7 Moisture Penetration
X
ACC = Acceptable
NP / NI = Not Present / Not Inspected
MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Hatch & Method of Inspection: Access location
Hatch & Method of Inspection: Inspection method
Insulation & Vapour Barrier: Insulation Depth
Insulation & Vapour Barrier: Insulation Type
Sheathing: No Material Deficiencies noted
Ventilation: The ventilation is adequate
Master Closet
Blown in insulation
From the attic hatch
Insulation averages about 14-16 inches in depth, R 70
Exhaust Vents & Ductwork: No Material Deficiencies noted Not all ventilation ducts may be visible.
Insulation & Vapour Barrier: Insulation is adequate Recommend monitoring, because insulation settles over time or may move. Current standards are R-60.
Inspection Services Group Inc
Page 34 of 38
1234 Main St.
Buyer Name
Framing: No Material Deficiencies noted
Moisture Penetration: No signs of moisture infiltration Ongoing monitoring is advised. Identification of moisture penetration may be limited due to exterior weather conditions.
Limitations Hatch & Method of Inspection
THE INSPECTOR DID NOT ENTER THE ATTIC So as not to disturb the insulation.
Inspection Services Group Inc
Page 35 of 38
1234 Main St.
Buyer Name
19: INDOOR AIR QUALITY AND HOME ENVIRONMENT section-ZWVjZDU4NzUtMmUyNS00YjMxLWE0ZTQtOGZhYjg3NDA3MWE5
NP ACC / MNT UPD REP MON NI 19.1 Indoor Air Quality Survey
X
19.2 Mold in a Home
X
19.3 Radon
X
19.4 Pest and Animal Activity ACC = Acceptable
NP / NI = Not Present / Not Inspected
X MNT = Maintenance
UPD = Update
REP = Repair / Replace MON = Monitor
Information Indoor Air Quality Survey: Health Canada Recommendations Health Canada has identified Air contaminants or pollutants that are present in the air and can put your health at risk. People that are more vulnerable to the health effects of air pollution include: 1. Children 2. Pregnant women 3. The elderly 4. Those with heart and lung conditions Please visit https://www.canada.ca/en/health-canada/services/air-quality/indoor-air-contaminants.html for more details on this subject. Our company offers Air quality assessments and Air Quality Testing. Please call your inspector for further information or to book. **General Recommendations and guidelines** 1. Health Canada Recommended Long Term Exposure for HCHO (Formaldehyde): 50mg/m³ on 8 hr average 2. Canadian Ambient Air Quality Standard for PM 2.5: Less than 28mg/m³ in a 24 hr period 3. World Health Organization Guidelines: PM10 not exceed 50mg/m³ in a 24 hr period
Indoor Air Quality Survey: Air Quality Survey not conducted An Air Quality Survey was not conducted as it was not requested by the client.
Mold in a Home: There is no visible mold in the property We will report the presence of visible mold. We do not have visibility behind walls, furniture, bathroom tiles, under floors, etc. We are not responsible if the seller is attempting to hide mold issues by using furniture or other means.
Inspection Services Group Inc
Page 36 of 38
1234 Main St.
Buyer Name
Radon: What is Radon? "Radon is a radioactive gas that comes from the breakdown of uranium in soil and rock. It is invisible, odourless and tasteless. When radon is released from the ground into the outdoor air, it is diluted and is not a concern. However, in enclosed spaces, like homes, it can accumulate to high levels and become a risk to the health of you and your family. " (Source: Health Canada) When radon is released from the ground into the outdoor air, it is diluted and is not a concern. However, in enclosed spaces, like homes, it can accumulate to high levels and become a risk to the health of you and your family.
Radon: Radon Testing not conducted Radon testing was not conducted at this property. A radon test cannot be done during a short inspection appointment. If your property is located in the Green or Brown areas in the map below, we recommend having a Short Term or Long Term Test done after you move into the house. For information about Radon please visit the Health Canada Website at: https://www.canada.ca/content/dam/hc-sc/migration/hc-sc/ewhsemt/alt_formats/pdf/pubs/radiation/radon_canadians-canadiens/radon_canadians-canadien-eng.pdf
Radon: Radon mitigation Radon mitigation is covered under the Tarion Warranty Program for up to 7 years. Https://www.tarion.com/homeowners/your-warranty-coverage/radon-and-your-warranty
Pest and Animal Activity: No pest or animal activity noted The inspector does not perform specific or specialized tests to determine the presence of rodents. If there is evidence of such issues, the inspector will make the client aware as a courtesy. The client is advised that pest control should be done in every home as a preventative measure.
Inspection Services Group Inc
Page 37 of 38
1234 Main St.
Buyer Name
20: CONCLUSION section-ZTY3OTUxYWItYmIxOS00NTg2LWJjMGItMWMxNjMyNzY1YmNh
Information Conclusion GENERAL INFORMATION: We are proud of the service we provide, and trust that you will be happy with the quality of our report. We have made every effort to provide you with an accurate assessment of the condition of the property and its components and to alert you to any significant defects or adverse conditions. However, we may not have tested every outlet, and opened every window and door, or identified every problem. Also, because our inspection is essentially visual, latent defects could exist. We cannot see behind walls. Therefore, you should not regard our inspection as a guarantee or warranty. It is simply a report on the general condition of a property at a given point in time. As a homeowner, you should expect problems to occur. Roofs will leak, basements may have water problems, and systems may fail without warning. We cannot predict future events. For these reasons, you should keep a comprehensive insurance policy current. This report was written exclusively for my client. It is not transferable to other people. The report is only supplemental to a seller's disclosure. Thank you for taking the time to read this report, and call us if you have any questions. We aim always attempting to improve the quality of our service and our report. PRE-CLOSING WALK THROUGH: The walk-through prior to closing is the time for Client to re-inspect the property. Conditions may change between the time of a home inspection and the time of closing. Restrictions that existed during the inspection may have been removed for the walk-through. Defects or problems that were not present during the home inspection may be discovered during the walk-through. Client should be thorough during the walk-through. Any defect or problem discovered during the walk-through should be negotiated with the owner/seller of the property prior to closing. Purchasing the property with a known defect or problem releases the Home Inspection Services Group of all responsibility. Client assumes responsibility for all known defects after settlement. APPLIANCES: Appliances were tested as a courtesy and were in working at the time of the inspection (unless otherwise noted). It cannot be guaranteed that the appliances will be functional at time of possession. It is recommended that the appliances be re-tested prior to possession. Typical Real Estate Contracts provide a 24 HR deficiency reporting clause. NOTE: If you’re reading this report but did not hire us, the Home Inspection Services Group, to perform the original inspection, please note that our liability is LIMITED to our client. Remember that the cost of a home inspection is insignificant compared to the value of the home. Protect your family and your investment, and please call us directly at 647-614-4474 to discuss the report you’re reading for this property so that we can arrange for a re-inspection. A SNAPSHOT IN TIME: This report shows the condition of the house, ON THE DAY OF THE INSPECTION. Please note that it is likely that conditions related to the home have probably changed, even if the report is fairly recent. Minor problems noted may have become worse, recent events may have created new issues, and items may even have been corrected and improved. We do not have control of what happens in a home after the inspection date. Thank you! Sincerely, Inspection Services Group