Page 1

Uniclass L74731:L68114

EPIC K7321:F813

CI/SfB (63.29)

Fire Protection for Electrical Installations Downlight Fire and Sound Protection Covers

Fluorescent Module Fire Protection Covers

Conduit, Trunking & Cable Tray Fire Protection Sleeves Ventilation Duct Fire Protection Sleeves

Gaskets & Pillows Fire Protection for Accessories

Vapour and Thermal Seal for Downlights

X

(K2)


Firecap Fire Protection Products What do the Regulations say?

How we can help you to comply

Building Regulations in the whole of the UK - Document B,

The New Firecap Range

England & Wales; Technical Handbook No:2, Scotland; and

Mindful of electrical contractors' increased responsibilities,

Technical Booklet E, Northern Ireland - demand that if a fire

we have extended the range of high performance Firecap

resistant element e.g a ceiling protecting an upper floor, is

intumescent Fire Protection Products. These now include Fire

broken into to install services, such as recessed downlights,

Protection Sleeves for electrical trunking, conduit, SWA,

the fire resistance must be made good. The recent Approved

cable tray and ventilation ducting. Furthermore, in response

Document P makes specific reference to the electrician's

to demands from the NHBC and other insurers, we have

responsibility to ensure that the fire resistance of any floor,

launched Loftcap, a vapour seal to cover downlights that

ceiling or wall that any services he has installed pass

penetrate a loft void.

through, are properly re-instated, with possible legal All these technically advanced products are easy to install

consequences for non-compliance.

and have been designed to ensure minimum additional This is further reinforced by the IEE Wiring Regulations 16th Edition

costs. Rigorous testing by independent laboratories and

BS 7671:2001, section 527-02-01, applying to all buildings:

consistently high standards throughout the UK based

“Where a wiring system passes through elements of a building

manufacturing process provide contractors with total

construction...the openings remaining...shall be sealed

peace of mind that their installations have been carried out

according to the degree of fire resistance required of the

with proper materials that satisfy the demands of Building

element concerned...�

Control in all respects.

It doesn't end there. Part E of the Building Regulations in England & Wales, Technical Handbook 5 of the Building (Scotland) Regulations and Technical Booklets G & G1 of the Building Regulations (Northern Ireland) all require that penetrations through walls, floors or ceilings for electrical installations should be made good in order to minimise the transmission of sound.

Approvals Local Authority

LANTAC APPROVED

FIRE TESTED

GLOBALLY ASSESSED

NHBC Type Approved for Building Regulations. Type Approval No. 0001/--/2005

2


Total Protection For Ceilings With Downlights Building Regulations confirm...

Sound Insulation

...that when a hole is cut into a fire rated ceiling to fit a

Building Regulations demand that many walls and ceilings

downlight, the fire stopping ability of the ceiling is

must resist the transmission of sound to adjoining areas.

impaired. In the event of a fire, flames could penetrate

Firecap downlight covers have unique insulation properties

through the light fitting and spread to the floor above with

and have been independently tested by the Building

the subsequent risk to life and property. The downlight itself

Research Establishment (BRE) to meet all Building

can also be a source of fire due to the high temperature

Regulations requirements when correctly installed as part of

of lamps and the promixity to flammable material.

an approved building system. Firecap is also LANTAC, Robust Details and NHBC approved for this application.

To provide total peace of mind and total protection, a Firecap downlight cover should be installed over the light

Permanent Protection

fitting if the ceiling is a fire separating element. Firecap will

Firecap covers maintain the integrity of the ceiling structure

stop the spread of fire for at least 60 minutes. In fact,

whatever downlight fitting is used, changed or even

recent tests by Chiltern International have demonstrated

removed. On the other hand, if fire rated downlights are

that Firecap downlight covers can give added peace of

installed and then subsequently replaced with standard

mind by providing up to 2 hours protection from fire.

downlights, the fire stopping integrity of the ceiling will be compromised. In these circumstances someone may be

When Firecap downlight covers are fitted as part of the

liable or vulnerable in the event of a fire unless Firecap

ceiling structure they become in effect a permanent fixture.

covers are installed.

This means that the fire protection with Firecap remains even when fashion may dictate a change of light fittings.

2 Hour Tested To demonstrate the exceptional fire stopping capabilities of

Fully Intumescent Material

Firecap downlight covers they have been third party fire

Firecap is uniquely manufactured from a fully intumescent

tested for 2 hours in a plasterboard ceiling. At time of printing,

material that swells to more than three times its original

no other intumescent cover has yet matched this level of

thickness when exposed to fire. This means that the void

endurance in a fire test.

above the downlight fills to ensure that flames and heat do not penetrate into the area above.

All Covered Amongst the key benefits of Firecap downlight covers is the

The Local Authority Building Control approval scheme,

broad range of both light fittings and ceiling types and

(LANTAC) and the National House Builders Confederation

constructions that the products have been designed to

(NHBC) have approved Firecap covers for use in this

protect. They include most commonly used ceilings and joist

application.

constructions as well as suspended ceilings, unlike some competitor fire rated downlights and covers that can have limited applications. Peter E Jackman IEng MIFire EFBEng AIWSc, Technical Director of International Fire Consultants Ltd. - widely acknowledged as a leading independent expert in fire engineering - says:

“Building Regulations 2000 Approved Document P allocates full responsibility to the electrician to make good the fire performance of any fire-rated floor/ceiling/wall after carrying out an electrical installation and legal action can be taken for non-compliance. Many, so called fire rated downlight fittings/covers are only tested in a small number of ceiling constructions and consequently this leaves the electrician vulnerable to “legal action” if the solution that he uses is wrong for the installation”

3


Intumescent Fire & Sound Pro Installed in Seconds Protects for Life ● Global assessment accreditation for all

common ceiling types and joist constructions ● Suitable for use with all commonly used lamp

types including “cool beam” dichroic and aluminium reflector lamps ● For use with a wide range of mains and LV

light fittings up to 270mm ø

WITH FIRECAP

● Easy to install from above or below the

ceiling without requiring an accurate hole ● Can be fitted in seconds - no screws, drilling

or additional sealant required ● Self supporting, flexible and lightweight

Installs in Seconds

● Tested and approved for use on both

plasterboard and suspended ceilings ● Fully ventilated to avoid over-heating of the

1

light fitting

Roll into a cylinder with the wiring and insert

● Reinstates acoustic protection of the ceiling -

through the downlight hole.

items tested have satisfied requirements of Building Regulations Document E under test conditions ● When exposed to fire the intumescent fibre

2

swells to over three times its original thickness

Pull down the wire legs and

to provide a highly effective fire-stopping

move into position. (The two

seal

larger sized covers 300 and 350 do not require a wire fixing.)

● Keeps all combustible material away from

the hot light fitting (all makes, styles and sizes) ● Provides a high level of additional heat

insulation to the ceiling void during a fire thus

3

reducing the chances of ignition of

Trim off surplus wire from the legs.

accumulated dust and flammable materials ● Specially formulated high performance outer

coating improves durability and minimises thermal convection ● Conserves energy - reduces heat within the

4

room from escaping through the light fitting

Wire up and insert the downlight.

● Multiple cable entry points on the side and

top for ease of installation ● Fibres used are exonerated from

classification according to HSE guidelines ● Rot, corrosion and vermin

resistant ● Maintenance free ● Light fitting can be

removed without

Swells to over three times its original thickness when exposed to fire to provide a highly effective fire stopping seal

disturbing the Firecap

4


tection Covers for Downlights Downlight Fire Protection Selection Guide Cut Out Size in mm

WITHOUT FIRECAP

Technical Information 1

2

3

4

5

6

7

Manufactured from fully intumescent mineral fibre. Specially formulated high performance outer coating improves durability and minimises thermal convection. Upto 2 hour fire rated. Swells to over 3 times its original thickness preventing flames and minimising heat being transmitted through the downlight when exposed to fire. AFF109/150, 109/200, 109/250, 109/300, 109/350 - the full range of Firecap fire protection downlight covers have been assessed for the following applications: Suspended Ceiling and Timber, Steel or Concrete Beam/Joist protected by plasterboard.Assessment No. CHILT/A02166A/Chiltern Int. Fire, to BS 476:Pt.21:1987, BS 476:Pt.23:1987, BS EN 1365-2:2000. Duration of effective protection: 60 minutes. AFF109/150, 109/200, 109/250 - individual tests: Suspended ceiling (unloaded test): BS 476:Pt.23:1987 Duration of effective protection: 72 minutes without failure. Certificate number: FEI/F99029/Chiltern International Fire. Plasterboard ceiling: BS EN 1365-2:2000 Integrity: 60 minutes without failure. Insulation: 60 minutes without failure. Certificate number: TE94667/BRE. AFF109/300, AFF109/350 - individual tests Suspended ceiling (unloaded test): BS 476:Pt.23:1987 Integrity: 72 minutes without failure. Certificate number: FG8962/208217/BRE. AFF109/150, 109/200, 109/300 - individual tests to BS 476: Pt.20 & 22:1987 plasterboard ceiling under timber joists. Integrity and insulation 120 minutes. Test report number: Chilt/IF03028 Chiltern International Fire. Firecap AFF109/150 fully intumescent downlight covers have been tested at BRE in cooperation with a leading plasterboard manufacturer and have been shown to reinstate original acoustic performance of both 60dB party ceilings and 40dB internal ceilings when correctly fitted. This satisfies requirements of the Building Regulations Approved Document E, Resistance to passage of sound. 8 Fulfils requirements of IEE Wiring Regulations 16th Edition and Building Regulations. Cat No

Height

Weight

AFF109/150 150mm x 150mm

Dia

100gm

AFF109/200 200mm x 200mm

200gm

AFF109/250 250mm x 250mm

300gm

AFF109/300 370mm x 210mm

600gm

AFF109/350 450mm x 255mm

800gm

Maximum height of fitting - mains powered or low voltage AFF109 /150

AFF109 /200

AFF109 /250

AFF109 /300

AFF109 /350

50

83

136

188

170

245

55

78

130

183

170

245

60

73

125

177

170

245

65

68

120

172

170

245

70

63

115

167

170

245

75

57

110

162

170

245

80

104

157

170

245

85

99

151

170

245

90

94

146

170

245

95

89

141

170

245

100

83

136

170

245

105

130

170

245

110

125

170

245

115

120

170

245

120

115

170

245

125

110

170

245

130

104

170

245

135

99

170

245

140

94

170

245

145

170

245

150

170

245

175

170

245

200

170

245

225

170

245

250

170

245

270

245

How to Use this Selection Guide 1. All covers are equally suitable for mains or low voltage fittings using “cool beam� dichroic or aluminium reflector lamps. It is only necessary to know the cut-out size and the height of the fitting. 2. Select the cut-out size of the fitting in the left hand column. 3. Read across to the right hand column that contains the height of the fitting concerned. Always select the exact height, or move up to the next size. For example: a cover for a fitting with a 98mm cut-out and a height of 95mm is required. In the left hand column you will see that the nearest cut-out size is 100mm; reading across the right hand columns, you will note that the AFF109/150 is not suitable, the 83mm size shown for the AFF109/200 is too small and the 136mm shown for the AFF109/250 is too large. You should select the larger size, AFF109/250. PLEASE NOTE: IF YOUR FITTING SIZE IS SHOWN IN THE ORANGE SHADED AREA, THE COVER CAN ONLY BE INSTALLED FROM ABOVE THE CEILING. THE COVER WILL NOT FIT THROUGH THE CUT-OUT HOLE.

5


Fire Protection Covers for Fluorescent Modules Installed in Seconds Protects for Life ● Easy to install - flexible one piece unit that can

be folded and fitted through the diagonal in the ceiling grid ● Can be fitted in seconds - no fixing clips, frame

assembly or additional sealant required ● Self supporting and lightweight - no pre-assembly required ● Pre-made slots for easy location on to ceiling grid ● Designed to fit a wide range of 600 x 600 and

Available in two sizes that cover the majority of popular modular fluorescent luminaires

1200 x 600 modular luminaires ● Tested and approved for use on suspended ceilings ● Provides a high level of additional heat insulation to the

ceiling void during a fire thus reducing the chances of ignition of accumulated dust and flammable materials

AF130/600 for 600 x 600 Module Side: 730mm external base 680mm top End: 670mm external base 620mm top Height: 155mm external Weight: 1.75kg approx

● Specially formulated durable mineral fibre minimises

thermal convection ● Easy to remove and re-install for luminaire maintenance ● Reinstates the acoustic protection of the ceiling ● Reduces heat within the room from escaping

through the light fitting

AF130/1200 for 1200 x 600 Module Side: 1330mm external base 1280mm top End: 700mm external base 650mm top Height: 140mm external Weight: 2.25kg approx

● Cable entry points can be made anywhere on

the sides and top for ease of wiring the luminaire ● Fibres used are exonerated from classification according

to HSE guidelines ● Rot, corrosion and vermin resistant ● Maintenance free ● In excess of 60 minute protection

Technical Information 1

Manufactured from fire resistant mineral fibre.

2

60 minute fire rated. Prevents flames and minimises heat being transmitted through the luminaire when exposed to fire.

3

AF130/1200 - individual tests Suspended ceiling (unloaded test): BS 476:Pt.23:1987 Min 60 minutes integrity. Certificate numbers: FG8962/208217/BRE. FE1/F03076.

4

AF130/600 assessed by Chiltern International Fire to BS 476: Pt.23:1987 unloaded test. Min 60 minutes integrity. Certificate number: Chilt/A05174.

5

Fulfils requirements of IEE Wiring Regulations 16th Edition and Building Regulations.

Easy Installation

6


Vapour and Thermal Seal for Loft Voids Loftcap

● Easy to install - pass cabling through the cover by

piercing with a sharp instrument or pencil, place over the downlight and seal with general purpose mastic. No

Building Regulations Approved Document L calls for a

screws or clips required

solution to allow uninterrupted coverage of thermal

● Rigid construction allows loft insulation to be laid directly

insulation in loft spaces, ensuring minimal heat loss through

over the Loftcap cover, meeting requirements of the

the ceiling.

Building Regulations Approved Document L for continuous loft insulation

Building Regulations Approved Document C, as well as the

● Provides a highly efficient vapour seal meeting the

NHBC and other insurers, call for a vapour seal between the living space and the loft space in order to prevent

requirements of Building Regulations, the NHBC and

condensation forming on roof timbers and causing

other Insurers ● Manufactured from inert mineral fibres and organic

premature rotting.

binders designed to resist the formation of water droplets which could drip on to the lamp and wiring of the fitting

If you are fitting downlights into a ceiling, which penetrates

● Smooth non-porous surfaces, such as steel, are not used

a loft space, you are likely to have a problem in meeting both the Building Regulations Parts C & L and the Insurer's

in Loftcaps as they can promote water droplet

requirements. Fitting Loftcap covers over the downlights

formation ● Maintains sufficient air space around the light fitting in

addresses both problems in one easy step.

order to avoid overheating ● Non combustible - no risk of a fire hazard due to the

Fire or acoustic insulation is not usually required in a loft void;

heat from the light fitting

Loftcaps are therefore designed simply to provide an effective

● Non-electrically conductive - no risk of electric shock or

vapour and thermal seal. Manufactured from inert mineral

fire hazard

fibres, Loftcaps are both non-combustible and non electrically conductive whilst being lightweight and rigid enough to

● Durable construction - rot, corrosion and vermin resistant

support loft insulation. What's more they're simplicity itself to

● Maintenance free

install and will not cause the light

● Lightweight, only 350g, so will not put significant load on

the ceiling

fitting to overheat.

● Fibres used are exonerated from classification according

to HSE guidelines ● Tested and approved by the Lighting Association

Loftcap

7

Cat No

Dimensions (mm)

ALC274

274/224 x 162


Intumescent Fire The Firecap range of Conduit, Trunking, Cable Tray and

Unique Contour Manufacturing Process

Ventilation Duct fire protection sleeves has been

Firecap sleeves are not made by bending flat sheets of

designed to prevent the spread of fire through service

intumescent material into the required shape. Consequently

penetrations made by both electrical and plumbing

they do not require a rigid metallic outer shell in order to

installers. Importantly, they are extremely efficient and

direct the expansion of the intumescent material. Instead,

very easy to fit.

during the manufacturing process, they are formed into shape so that the constituent fibres will follow the contours of the

These unique, high performance, technically advanced

pipe or duct. In the event of fire, when the intumescent

products are all manufactured in the UK. They have been

material expands, it is in exactly the right direction to totally

rigorously tested by independent laboratories to meet all

seal off the penetration very quickly and very efficiently. PVC

the requirements of the UK Building Regulations and IEE

ducts, trunking and conduits are fully crushed by the

Regulations, providing a full 2 hours fire and smoke “stop�

intumescent material in a fire situation, thus sealing all fire and

through all common wall constructions and partitions.

smoke access in and around the penetration. Furthermore, the sleeve material is compressible to 50% of its original thickness, as there is no rigid outer casing it can accept some inaccuracy in the cut penetration, allowing it to be fitted into tight gaps. The specially formulated foil backing on the outside of the sleeves is designed to transmit the heat

Material The Firecap intumescent sleeves are made from a blend of mineral fibres and exfoliated graphite to produce a material structure that combines high grade fire stopping characteristics with excellent acoustic and thermal insulation properties. The foil backing is designed to create a perfect vapour seal between the conduit/duct and helps to reduce any condensation coming into contact with the wall/floor. The sleeves contain no uPVC compounds, only small amounts of organic binders, resulting in minimal smoke emissions in a fire situation. All Firecap materials are exonerated from classification according to HSE Guidelines.

8


Protection Sleeves into the fibres thus accelerating the expansion process in the

No Cutting of Conduit/Ducting Required

event of fire.

Unlike some fire stopping products, Firecap sleeves require no cutting of the conduit/duct, meaning less work and a

Easy to Install

seamless run of conduit/ducting.

No screws, fixings or special skills are required to install any Firecap sleeves. Furthermore they do not require

Acoustics

applications of fire rated mastics to seal the product into

The compressible nature of the material creates a highly

the wall or floor when fitted snugly because in a fire

efficient acoustic barrier between the conduit/ducting and

situation the sleeves expand both outwards to take up

the wall/floor as well as absorbing sound transmission from

small imperfections, as well as inwards to create a perfect

one side of the wall to the other.

fire seal. For optimum acoustic performance any gaps around the sleeves should be filled with non-combustible

Thermal Movement

filler eg mortar or mastic.

PVC ducting can expand many times greater than the metal equivalent; Firecap has been designed to

Fit from One Side of a Wall or Floor

accommodate thermal movement whilst maintaining its full

Ducting and piping often runs along the inaccessible parts

fire stopping integrity.

of a building, in a floor void. Firecap sleeves have been designed to be fitted from either side of a wall or floor

Thermal Insulation

penetration. The sleeves simply wrap around the duct or

Firecap sleeves have the same thermal conductivity as

pipe and slide into place avoiding the need to access the

mineral wool insulation and so create a thermal break

other side of the wall or floor. Time is saved with only one

between the ducting and the wall, preventing condensation.

visit to one side of the wall/floor.

Durable Firecap sleeves are resistant to moisture, humidity, vermin attack, mould and fungus.

Peace of Mind All Firecap sleeves have extensive third party approvals. The sleeves have all been fire tested in both plasterboard and blockwork wall/floor constructions and offer full 2 hours integrity and insulation on non heat conducting products.

Tests Tested and approved by Chiltern International Fire to BS 476:Pt.20 & Pt.22:1987 and the guidelines of EN1366-3 (Fire test assessment No. Chilt/A05153. Duration of effective protection 132 minutes integrity)

9


Electrical Trunking Fire Sleeve A range of intumescent sleeves to prevent the spread of fire through service penetrations made for electrical trunking.

3 2

● Easy to install without special tools or skills ● Cost effective - one sleeve can replace two collars, easily

cut to size

1

● Suitable for use through a wide range of fire partition walls

and floors ● Two hour fire & smoke 'stop' through all common wall

constructions and partitions ● Suitable for a wide range of metal and PVC trunking ● Meets all the requirements of the UK Building Regulations ● In the event of a fire the PVC trunking is crushed by the

Easy to retrofit

intumescent material sealing all air, flame and smoke paths inside and around the trunking ● Can be used for non electrical trunking ● Quickly installed simply by sliding the sleeve over the

trunking and placing in position inside the firewall or partition ● Easily retrofitted, without disturbing the cables or trunking

by slicing and opening the sleeve and fitting it around the trunking and resealing with tape provided ● Easily fitted even when there is access only from one side ● Eliminates the need for metal collars and additional

fittings ● Very easy to cut with a standard padsaw ● Available for 50mm square and 100mm square trunking ● For very wide walls or partitions over 150mm thick,

one fire sleeve may be used on each side of the wall / partition ● Provide a cold smoke seal as well as thermal and

acoustic insulation in their passive state

Cat No Description

To Fit Trunking Size (mm)

ATR50

Electrical Trunking Fire sleeve

50 x 50

ATR100

Electrical Trunking Fire sleeve

100 x 100

All sleeves are suitable for walls up to 150mm wide

10

1 2 3

Cut with padsaw

Fit over trunking

Reseal with aluminium tape provided and slide into gap


Pipe, Conduit and SWA Fire Sleeve A range of intumescent sleeves to prevent the spread of fire through service penetrations made for pipes and conduits. ● Easy to install without special tools or skills ● Cost effective - one sleeve can replace two collars, easily

cut to size ● Suitable for use through a wide range of fire partition walls

and floors ● Two hour fire & smoke 'stop' through all common wall

constructions and partitions ● Suitable for a wide range of metal and PVC pipes and

conduit ● Meets all the requirements of the UK Building Regulations ● In the event of a fire the PVC conduit is crushed by the

intumescent material sealing all air, flame and smoke paths inside and around the conduit ● Can be used for non electrical pipe ● Quickly installed simply by sliding the sleeve over the

conduit or cables and placing in position inside the firewall or partition ● Easily retrofitted without disturbing the conduit by slicing and

opening the sleeve then fitting around the conduit and resealing ● Easily fitted even when there is access only from one side ● Maintains the thermal insulation of the pipe through the

penetration ● Maintains vapour seal of existing insulation

Cat No

Description

● Eliminates the need for metal collars and additional fittings

APC17/67

Pipe, Conduit & SWA Fire Sleeve

17

● Very easy to cut with a standard padsaw

APC21/71

Pipe, Conduit & SWA Fire Sleeve

21

● A full range of sizes to accommodate conduit or cable sizes

APC27/77

Pipe, Conduit & SWA Fire Sleeve

27

● Allows the thermal movement of the pipe or conduit

from 17mm to 169mm

Nominal OD of Service (mm)

APC34/84

Pipe, Conduit & SWA Fire Sleeve

34

● For very wide walls or partitions over 150mm thick one fire

APC42/92

Pipe, Conduit & SWA Fire Sleeve

42

sleeve may be used on each side of the wall / partition

APC48/98

Pipe, Conduit & SWA Fire Sleeve

48

● Provide a cold smoke seal as well as thermal and acoustic

APC54/104

Pipe, Conduit & SWA Fire Sleeve

54

APC60/110

Pipe, Conduit & SWA Fire Sleeve

60

APC67/117

Pipe, Conduit & SWA Fire Sleeve

67

APC76/126

Pipe, Conduit & SWA Fire Sleeve

76

APC80/130

Pipe, Conduit & SWA Fire Sleeve

80

insulation in their passive state ● Will accept hole irregularities of up to 15mm

APC89/139

Pipe, Conduit & SWA Fire Sleeve

89

APC102/152

Pipe, Conduit & SWA Fire Sleeve

102

APC108/158

Pipe, Conduit & SWA Fire Sleeve

108

APC114/164

Pipe, Conduit & SWA Fire Sleeve

114

APC127/177

Pipe, Conduit & SWA Fire Sleeve

127

APC140/190

Pipe, Conduit & SWA Fire Sleeve

140

APC159/209

Pipe, Conduit & SWA Fire Sleeve

159

APC169/219

Pipe, Conduit & SWA Fire Sleeve

169

All sleeves are suitable for walls up to 150mm wide

11


Cable Tray Fire Sleeve A range of intumescent sleeves to prevent the spread of fire through service penetrations for cable trays. ● Easy to install without special tools or skills.

Simply cut the sleeve to shape and slide on to the end of the tray, reseal and slide into the wall ● Cost effective - easily cut to minimise wastage ● Suitable for use through a wide range

of fire partition walls and floors ● Meets all the requirements of the

UK Building Regulations ● A range of sleeves to fit trays from

150mm to 600mm wide ● In the event of a fire, the

intumescent material quickly expands to seal the opening to prevent a fire spreading ● Easily retrofitted without disturbing

the cables or conduits by slicing and opening the sleeve then fitting it around the tray and resealing ● Easily fitted even when there is access only from one side ● Eliminates the need for metal collars and additional fittings ● Very easy to cut with a standard padsaw ● Additional cables can be easily installed without removing

the sleeve ● For very wide walls or partitions over 150mm thick one fire

sleeve may be used on each side of the wall / partition ● Provide a cold smoke seal as well as thermal and acoustic

insulation in their passive state ● Provides a neat and tidy surface to make good to whilst

surrounding the cable tray where it passes through a fire partition or wall ● For retrofitting, cut and fit as Trunking Fire Sleeve

(see page 10)

2

Sleeve compresses to accept cables

2

1

Cut and place over tray, reseal & slide into gap

1

Cat No

Description

To Fit Tray Size (mm)

ACT50

Cable Tray Sleeve

50

ACT75

Cable Tray Sleeve

75

ACT100

Cable Tray Sleeve

100

ACT150

Cable Tray Sleeve

150

ACT225

Cable Tray Sleeve

225

ACT300

Cable Tray Sleeve

300

ACT450

Cable Tray Sleeve

450

All sleeves are suitable for walls up to 150mm wide

Easy to retrofit 12


Ventilation Duct Fire Sleeve A range of intumescent sleeves to prevent the spread of fire through service penetrations made for the passage of ventilation ducting. ● Easy to install without special tools or skills ● Cost effective - one sleeve can replace two collars, easily

cut to size ● Suitable for use through a wide range of fire partition walls

and floors ● Suitable for plastic ventilation ducting ● Meets all the requirements of the UK Building Regulations ● In the event of a fire the plastic ducting is crushed by the

intumescent material sealing all air, flame and smoke paths inside and around the ducting ● Quickly installed simply by sliding the sleeve over the

ducting and placing in position inside the firewall or partition ● Easily retrofitted without disturbing the ventilation ducting

by slicing and opening the sleeve then fitting it around the ducting and resealing with tape provided ● Easily fitted even when there is access only from

one side ● Maintains the thermal insulation of the duct

through the penetration ● Maintains vapour seal of existing insulation ● Allows the thermal movement of the duct ● Eliminates the need for metal collars and

additional fittings ● Very easy to cut with a standard padsaw ● Available for a wide variety of sizes ● For very wide walls or partitions over 150mm thick, one

fire sleeve may be used on each side of the wall / partition ● Provide a cold smoke seal as well as thermal and acoustic

insulation in their passive state ● For retrofitting, cut and fit as Trunking Fire Sleeve (see

page 10) Cat No

Description

To Fit Duct Size (mm)

1

1

Slide over duct and into gap

AVD100/54 Ventilation Duct Fire Sleeve

100 x 54

AVD150/70 Ventilation Duct Fire Sleeve

150 x 70

AVD204/60 Ventilation Duct Fire Sleeve

204 x 60

AVD215/25 Ventilation Duct Fire Sleeve

215 x 25

AVD220/55 Ventilation Duct Fire Sleeve

220 x 55

AVD225/25 Ventilation Duct Fire Sleeve

225 x 25

AVD234/29 Ventilation Duct Fire Sleeve

234 x 29

AVD300/25 Ventilation Duct Fire Sleeve

300 x 25

AVD308/29 Ventilation Duct Fire Sleeve

308 x 29

All sleeves are suitable for walls up to 150mm wide

During construction 13


Intumescent Duct Wrap Intumescent Duct Wrap Designed for use with plastic ducting where it passes through brick or blockwork. Intumescent duct wrap has been designed to fit around the outside of the ducting, sealing the gap made between the ducting and the wall. When subjected to heat, the duct wrap expands inwards to crush the ducting, thus sealing it totally and preventing fire spreading via the ducting to adjoining areas.

● For use with small uPVC rectangular ducting in

solid walls ● Easy to install - simply wraps around the duct

and is held in place by a self adhesive strip ● Manufactured from flexible fully intumescent

material encapsulated in a thin polythene sleeve to allow easy handling and installation ● Maintenance free ● Fibres used are exonerated from classification

according to HSE guidelines ● Moisture, humidity and frost resistant ● Smallest dimension less than 54mm use one

wrap, if greater than 54mm use two wraps ● Tested and approved by Chiltern International

Fire to BS 476: Pt.20 & Pt.22. (Fire test assessment No. Chilt/F04007. Duration of effective protection 132 minutes insulation and integrity)

Duct is crushed by the intumescent wrap in the event of a fire (Pictures taken during fire testing)

Intumescent Duct Wrap

14

Cat No

Dimensions (mm)

AFDW692

4 x 70 x 692


Intumescent Gaskets and Pillows Intumescent Gaskets

● Easy to remove and re-

Widely used mains wiring accessories such as socket outlets,

install for maintenance

switches, ceiling roses and BESA boxes can all weaken the fire

purposes

stopping integrity of fire separating elements such as walls and

● Installer can

ceilings. Switches and sockets can also be the source of a fire

make suitable

itself, due to arcing or defective wiring. An intumescent gasket

holes in the

can therefore play two vital roles, firstly containing the source of

gasket to

some fires and secondly helping to prevent fire spreading

accommodate

through holes made for wiring in fire stopping elements.

cables ● Non toxic, no special

● Very easy and economical to install

disposal requirements ● Rot proof and

● Insulated with PVC to avoid risk of electrical short circuit

Adding Firecap gaskets in ceiling roses will delay the fire spreading to the floor above When exposed to fire the material swells up to provide a highly effective fire stopping seal

Adding Firecap gaskets to sockets will delay the spread of fire into the adjoining room

maintenance

through the graphite material of the gasket ● Single and twin switch socket pads designed for both

free ● In excess of 60

surface and recessed shallow and deep boxes ● Circular pads for ceiling roses and BESA boxes

minute

● When exposed to fire the material swells up to provide a

protection ● Tested to requirements of

highly effective fire stopping seal

the relevant parts of Cat No

Description

Size (mm)

BS 476: Pt.20 &

ALSG

Single Socket Gasket

68 x 68 x 4

Pt.22

ALDG

Double Socket Gasket

136 x 68 x 4

ALBG

Standard BESA Box Gasket

ø58 x 2.4

ALCG

Ceiling Rose Gasket

ø75 x 2.4

Intumescent Pillows ● Suitable for both indoor and

Intumescent pillows are designed for packing into gaps

outdoor applications up to 1m2

around services and cable entry points where they

● Easy to remove and re-install

penetrate fire separating elements such as walls and floors.

for maintenance purposes

They can be quickly installed in both permanent and temporary applications to provide an effective barrier to the

● Long life

passage of flames, smoke and hot gases in the event of a fire.

● Remains flexible between

-20˚C and +130˚C

They help to maintain the integrity of escape routes, reduce

● Non toxic, no special storage

loss or damage to the building and maintain pressure

or disposal requirements

differentials between compartments and ventilation

● Rot proof and maintenance

channels. The pillows are filled with organic fillers and

free

intumescent additives in a waterproof glass cloth bag.

● Offers a fire barrier of up to ● Flexible and easy to install

4 hours ● Tested to requirements of

● Available in three popular sizes to cover a vast range of

the relevant parts of

applications ● When exposed to fire the material provides a highly

BS 476: Pt.20 & Pt.22

effective fire stopping seal Cat No Description AFP20 Small AFP25 Medium AFP45 Large Quantity required per m2

Dimensions (mm) Weight (gms) 330 x 50 x 20 50 330 x 200 x 25 185 330 x 200 x 45 385 Small 217 in wall / 120 in floor Large 117 in wall / 60 in floor

15

Adding Firecap gaskets to joins in conduit will delay flames from running inside the piping


Fire Protection for Electrical Installations Intumescent Downlight Fire Protection Covers All Ceilings All Fittings All Sizes All Risks All Covered Permanently! We endeavour to collect test data for all floor and ceiling constructions commonly available, however, some specialist constructions may not be included

If you need further information please ask for a free copy of the Firecap Frequently Asked Questions booklet, or our Firecap Presentation CD, or visit our web site.

Stockist

Customer Service Helpline

0870 758 4000 Aico Ltd, Mile End Business Park, Maesbury Road, Oswestry, Shropshire SY10 8NN Tel: 0870 758 4000 • Fax: 0870 758 4010 • Sales - Tel: 0870 758 4001• Fax: 0870 758 4011 e-mail: enquiries@aico.co.uk • www.aico.co.uk E & OE As our policy is one of continuous development, we reserve the right to amend designs and specifications without prior notice. Every care has been taken to ensure that the contents of this document are correct at the time of publication and we shall be under no liability whatsoever in respect of such contents.