2009 circuit protection



Founded in 1897, Wylex introduced the first ‘consumer unit’ to the electrical industry, this original design was the forerunner to the ‘Standard Range’, which is still in wide use today. From its base at Wythenshawe, through a policy of continuous design improvement, Wylex has developed a comprehensive range of Domestic, Commercial and Industrial circuit protection devices based on quality and close attention to the practical requirements of the contractor including the fundamental requirements of electrical safety embodied in the relevant British and International Standards including IEE Wiring Regulations.

N H I N S U L AT E D C O N S U M E R U N I T S

2

N H M E TA L C O N S U M E R U N I T S

6

CONSUMER UNIT MCBs RCBOs & FUSES

9

CONTROL DEVICES

9

NH DISTRIBUTION BOARDS

10

DISTRIBUTION BOARD INCOMERS

13

DISTRIBUTION BOARD MCBs & RCBOs

14

N H 1 2 5 M C C B PA N E L B O A R D S

16

PA N E L B O A R D N H 1 2 5 M C C B s

19

N H 2 0 0 M C C B PA N E L B O A R D S

20

PA N E L B O A R D N H 2 0 0 M C C B s

23

N H F U S E S W I T C H C O M B I N AT I O N U N I T S

24

S TA N D A R D R A N G E

26

LIFELINE RCDs & ENCLOSURES

30

S W I T C H D I S C O N N E C T O R S & I S O L AT O R S

34

T E C H N I C A L D ATA & D I M E N S I O N S

36

NUMERIC INDEX

51

L eft Electrium’s purpose built Commercial Centre in Cannock, Staffordshire

As a leading manufacturer of electrical domestic and industrial circuit protection products, Wylex is committed to the continual improvement of all quality assurance procedures and performance.

This publication has been printed on paper that originates from a forest that is responsibly managed, using vegetable based inks.


THE NH Solution To help installers comply with the requirements of the new 17th Edition wiring regulations Wylex have created the NH Solution 17 Range of consumer units providing 100% 30mA RCD protection (if required)

● ● ● ●

RANGE

Main Switch - Independent circuits Split Load - Half independent circuits High Integrity - Some independent circuits Dual RCD - No independent circuits

EDITION For details on the application to meet the 17th edition wiring regulations please refer to page 40.


MAIN SWITCH CAT REF

MS RATING

* WAYS

40A 63A 100A 100A 100A 100A 100A 100A 100A 100A 100A

2 2 5 8 11 14 19 5 8 8 11

RCD RATING

MCB WAYS

MS RATING

* WAYS

80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA

2 3 4 5 4 3 6 3 4 6 5 7 8 9 12 11 10 6 7 9 8 5

100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

4 3 2 4 5 6 3 9 8 6 7 5 4 3 5 6 7 11 10 8 9 12

3 3 3 6 3

With DIN Accessory Section

SPLIT LOAD NH804

NHRS6604

CAT REF

NHRS2404 NHRS3304 NHRS4204 NHRS5404 NHRS4504 NHRS3604 NHRS6304 NHRS3904 NHRS4804 NHRS6604 NHRS5704 NHRS7504 NHRS8404 NHRS9304 NHRS12504 NHRS11604 NHRS10704 NHRS61104 NHRS71004 NHRS9804 NHRS8904 NHRS51204

FLEXIBLE SPLIT LOAD CONSUMER UNITS CAT REF

NHRS6SL NHRS9SL NHRS12SL NHRS17SL

RCD RATING MCB WAYS MIN MAX

80A 30mA 80A 30mA 80A 30mA 80A 30mA

2 3 3 5

4 6 9 12

MS RATING

100A 100A 100A 100A

* WAYS

2 3 3 5

4 6 9 12

* WAYS TOTAL

6 9 12 17

SPLIT LOAD WITH DIN RAIL ACCESSORY SECTION CAT REF

NHRS12SL

NHRS6504+6 NHRS5604+6 NHRS7704+3 NHRS8604+3 NHRS6804+3

RCD RATING MCB WAYS

MS RATING

* WAYS

NO OF MODULES

6 5 7 8 6

100A 100A 100A 100A 100A

5 6 7 6 8

6 6 3 3 3

30mA MCB WAYS

30mA MCB WAYS

MS RATING

* MS WAYS

TOTAL *

2 4 4 3 7 6 4 5 4 1 to 4 2 to 5 2 to 9

3 4 3 3 6 6 6 5 5 1 to 4 2 to 5 2 to 9

100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

2 2 3 4 2 3 5 5 6 1 to 4 2 to 5 2 to 9

7 10 10 10 15 15 15 15 15 7 10 15

80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA

HIGH INTEGRITY CAT REF

NHRS44204

NHRS23204 NHRS44204 NHRS43304 NHRS33404 NHRS76204 NHRS66304 NHRS46504 NHRS55504 NHRS45604 NHRS7SSLHI NHRS10SSLHI NHRS15SSLHI

* RCBOs or MCBs may be fitted to unprotected ways depending upon the installation requirements (see page 40).

NH Insulated Range

NH204/40 NH204/63 NH504 NH804 NH1104 NH1404 NH1904 NH504+3 NH804+3 NH804+6 NH1104+3

DIN MODULES


INSULATED - DUAL RCD 2x 80A 30mA RCD CAT REF

NHISS3404 NHISS4604 NHISS5504 NHISS8704

4

MS WAYS

RCD 1 MCB WAYS

RCD 2 MCB WAYS

TOTAL No of MCB WAYS

-

3 4 5 7

4 6 5 8

7 10 10 15

NH Insulated Range

INSULATED - FLEXIBLE DUAL RCD 2x 80A 30mA RCD CAT REF

NHISS10SL NHISS15SL

MS WAYS

RCD1 MCB WAYS

RCD2 MCB WAYS

TOTAL No of MCB WAYS

-

4 to 6 Max 6 to 9 Max

4 to 6 Max 6 to 9 Max

10 15

RCD INCOMER

NHISS5504

CAT REF

RCD RATING

NHRS204/40 NHRS204/63 NHRS504 NHRS804 NHRS1104 NHRS1404 NHRS1904 NHRM204/40 NHRM204/63 NHRM504 NHRM804 NHRM1104 NHRM1404 NHRM1904 NHRS504+3 NHRS804+3 NHRS804+6 NHRS1104+3 NHTM504 NHTM804 NHTM1104 NHTM1404 NHTM1904

40A 30mA 63A 30mA 100A 30mA 100A 30mA 100A 30mA 100A 30mA 100A 30mA 40A 100mA 63A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 30mA 100A 30mA 100A 30mA 100A 30mA 100A 100mA TD* 100A 100mA TD* 100A 100mA TD* 100A 100mA TD* 100A 100mA TD*

MCB WAYS

DIN MODULES

2 2 5 8 11 14 19 2 2 5 8 11 14 19 5 8 8 11 5 8 11 14 19

3 3 6 3

With DIN Accessory Section

* Time Delay RCD

TIME DELAY FLEXIBLE SPLIT LOAD CONSUMER UNITS NHRS504

CAT REF

RCD RATING MCB WAYS MIN MAX

NHSTM9SL NHSTM12SL NHSTM17SL

80A 30mA 80A 30mA 80A 30mA

3 3 5

6 9 12

TD RCD

*MCB WAYS MCB WAYS MIN MAX TOTAL*

100A 100mA 100A 100mA 100A 100mA

3 3 5

6 9 12

9 12 17

Flexible consumer units utilise a full DIN rail and accept modular DIN devices such as a Bell Transformer or Timer.

SPLIT LOAD WITH TIME DELAY RCD INCOMER CAT REF

NHSTM4504

NHSTM3604 NHSTM4504 NHSTM5404 NHSTM6304 NHSTM3904 NHSTM4804 NHSTM5704 NHSTM6604 NHSTM7504 NHSTM8404 NHSTM9304 NHSTM12504 NHSTM11604 NHSTM8904 NHSTM9804 NHSTM10704 NHSTM71004 NHSTM61104 NHSTM51204

RCD RATING

80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA

MCB WAYS

3 4 5 6 3 4 5 6 7 8 9 12 11 8 9 10 7 6 5

TD RCD

*MCB WAYS

100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA

6 5 4 3 9 8 7 6 5 4 3 5 6 9 8 7 10 11 12

A range of matching DIN enclosures is also available, see page 33. * RCBOs or MCBs may be fitted to unprotected ways depending upon the installation requirements (see page 40).


DUAL TARIFF 100A MAIN SWITCH AND 100A MAIN SWITCH CAT REF

NHIIX6604

*WAYS

MS RATING

*WAYS

63A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

2 3 5 4 3 4 7 6 5 9 8 11 5

100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

4 3 4 5 9 8 5 6 7 8 9 6 12

DUAL TARIFF 100A MAIN SWITCH AND 100A 30mA RCD MAIN SWITCH CAT REF

NHRSX5704 NHRSX6604 NHRSX7504 NHRSX8904 NHRSX9804

RCD RATING

MCB WAYS

MS RATING

*WAYS

100A 30mA 100A 30mA 100A 30mA 100A 30mA 100A 30mA

5 6 7 8 9

100A 100A 100A 100A 100A

7 6 5 9 8

IP65 CONSUMER UNITS WITH MAIN SWITCH CAT REF

MS RATING

*WAYS✝

NH304IP

63A

3

NH704IP

100A

7

NH1004IP

100A

10

✝ 2 module wide RCBOs only

IP65 CONSUMER UNITS WITH RCD INCOMER NH704IP

CAT REF

RCD RATING

MCB WAYS

NHRS304IP

40A 30mA

3

NHRS704IP

80A 30mA

7

NHRS1004IP

80A 30mA

10

CUSTOM BUILT To meet the ever changing requirements and designs of the modern electrical installation, Wylex offers a service where the standard range of products can be modified to specific customer needs. Our technical services and engineering teams can assess the feasability of a product requirement whilst our modern manufacturing facilities will produce a high quality competitive solution.

CUSTOM BUILT HIGH INTEGRITY

* RCBOs or MCBs may be fitted to unprotected ways depending upon the installation requirements (see page 40).

5 NH Insulated Range

NHIIX2404 NHIIX3304 NHIIX5404 NHIIX4504 NHIIX3904 NHIIX4804 NHIIX7504 NHIIX6604 NHIIX5704 NHIIX9804 NHIIX8904 NHIIX11604 NHIIX51204

MS RATING


MAIN SWITCH CAT REF

NH Metal Cased Range

6

NH806

MS RATING

*WAYS

NH206/40 NH206/63 NH506 NH806 NH1106 NH1406 NH1906

40A 63A 100A 100A 100A 100A 100A

2 2 5 8 11 14 19

NH506+3 NH806+3 NH806+6 NH1106+3

100A 100A 100A 100A

5 8 8 11

3 3 6 3

SPLIT LOAD CAT REF

NHRS4506

+ DIN MODULES

NHRS2406 NHRS3306 NHRS4206 NHRS5406 NHRS4506 NHRS3606 NHRS6306 NHRS3906 NHRS4806 NHRS6606 NHRS5706 NHRS7506 NHRS8406 NHRS9306 NHRS12506 NHRS11606 NHRS10706 NHRS61106 NHRS71006 NHRS9806 NHRS8906 NHRS51206

RCD RATING

MCB WAYS

MS RATING

*WAYS

80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA

2 3 4 5 4 3 6 3 4 6 5 7 8 9 12 11 10 6 7 9 8 5

100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

4 3 2 4 5 6 3 9 8 6 7 5 4 3 5 6 7 11 10 8 9 12

FLEXIBLE SPLIT LOAD CONSUMER UNITS CAT REF

RCD RATING

NHRS6SLM NHRS9SLM NHRS12SLM NHRS17SLM

80A 30mA 80A 30mA 80A 30mA 80A 30mA

MCB WAYS MIN MAX

2 3 3 5

4 6 9 12

MS RATING

100A 100A 100A 100A

* WAYS MIN MAX

2 3 3 5

* WAYS TOTAL

4 6 9 12

6 9 12 17

SPLIT LOAD WITH DIN RAIL ACCESSORY SECTION CAT REF

RCD RATING

NHRS5606+6 80A 30mA NHRS7706+3 80A 30mA

NHRS12SLM

MCB WAYS

MS RATING

* WAYS

No of MODULE WAYS

6 7

100A 100A

5 7

6 3

100mA available to order

HIGH INTEGRITY CAT REF

NHRS10SSLMHI

30mA 30mA RCD WAYS RCD WAYS MCB MCB

NHRS23206 2 NHRS44206 4 NHRS43306 4 NHRS33406 3 NHRS76206 7 NHRS66306 6 NHRS46506 4 NHRS55506 5 NHRS45606 4 NHRS7SSLMHI 1 to 4 NHRS10SSLMHI 2 to 5 NHRS15SSLMHI 2 to 9

3 4 3 3 6 6 6 5 5 1 to 4 2 to 5 2 to 9

MS RATING

MS WAYS * TOTAL

100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

2 2 3 4 2 3 5 5 6 1 to 4 2 to 5 2 to 9

7 10 10 10 15 15 15 15 15 7 10 15

Flush mounting consumer units available to order. Suffix Catalogue Reference with /FLU eg: NHRS6606/FLU * RCBOs or MCBs may be fitted to unprotected ways depending upon the installation requirements (see page 40).


METAL - DUAL RCD 2x 80A 30mA RCD CAT REF

NHISS3406 NHISS4606 NHISS5506 NHISS8706

MS WAYS

RCD 1 MCB WAYS

RCD 2 MCB WAYS

TOTAL No of MCB WAYS

-

3 4 5 7

4 6 5 8

7 10 10 15

7

METAL - FLEXIBLE DUAL RCD 2x 80A 30mA RCD

NHISS10SLM NHISS15SLM

RCD 1 MCB WAYS

RCD 2 MCB WAYS

TOTAL No of MCB WAYS

6 Max 9 Max

6 Max 9 Max

10 15

-

RCD INCOMER NHISS5506

CAT REF

NHRS206/40 NHRS206/63 NHRS506 NHRS806 NHRS1106 NHRM206/40 NHRM206/63 NHRM506 NHRM806 NHRM1106 NHTM506 NHTM806 NHTM1106

RCD RATING

MCB WAYS

40A 30mA 63A 30mA 100A 30mA 100A 30mA 100A 30mA 40A 100mA 63A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA time delay 100A 100mA time delay 100A 100mA time delay

2 2 5 8 11 2 2 5 8 11 5 8 11

SPLIT LOAD WITH TIME DELAY RCD INCOMER CAT REF

NHRS1106

NHSTM3606 NHSTM4506 NHSTM5406 NHSTM6306 NHSTM3906 NHSTM4806 NHSTM6606 NHSTM7506 NHSTM9306 NHSTM8906 NHSTM9806 NHSTM71006 NHSTM61106 NHSTM51206

RCD RATING

MCB WAYS TD RCD RATING

80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA 80A 30mA

3 4 5 6 3 4 6 7 9 8 9 7 6 5

*WAYS

100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA 100A 100mA

6 5 4 3 9 8 6 5 3 9 8 10 11 12

FLEXIBLE SPLIT LOAD CONSUMER UNITS (TIME DELAY) CAT REF

NHSTM9SLM

NHSTM9SLM NHSTM12SLM NHSTM17SLM

RCD RATING

MCB WAYS MIN MAX

80A 30mA 80A 30mA 80A 30mA

3 3 5

6 9 12

* WAYS MIN MAX

TD RCD

100A 100mA 100A 100mA 100A 100mA

3 3 5

* WAYS TOTAL

6 9 12

9 12 17

DUAL TARIFF 100A MAIN SWITCH & 100A MAIN SWITCH CAT REF

NHIIX2406 NHIIX3306 NHIIX4506 NHIIX7506 NHIIX6606 NHIIX5706 NHIIX8906 NHIIX51206 NHIIX11606

MS RATING

*WAYS

MS RATING

*WAYS

63A 100A 100A 100A 100A 100A 100A 100A 100A

2 3 4 7 6 5 8 5 11

100A 100A 100A 100A 100A 100A 100A 100A 100A

4 3 5 5 6 7 9 12 6

DUAL TARIFF 100A MAIN SWITCH & 100A 30mA RCD SWITCH CAT REF

NHIIX4506

NHRSX5706 NHRSX6606 NHRSX7506 NHRSX8906 NHRSX9806

RCD RATING

100A 30mA 100A 30mA 100A 30mA 100A 30mA 100A 30mA

MCB WAYS

5 5 7 8 9

MS RATING

100A 100A 100A 100A 100A

* WAYS

7 6 5 9 8

* RCBOs or MCBs may be fitted to unprotected ways depending upon the installation requirements (see page 40).

NH Metal Cased Range

MS WAYS

CAT REF


METAL - SPLIT LOAD DUPLEX TOP BANK MS RATING *WAYS

CAT REF

NHDIS88 NHDIS1111

100A 100A

8 11

BOTTOM BANK RCD RATING MCB WAYS

80A 30mA 80A 30mA

8 11

METAL- HIGH INTEGRITY DUPLEX 2 xRCDS, 1x 100A MAIN SWITCH

8 Metal Cased Range

CAT REF

80A 30mA RCD WAYS BOTTOM BANK

NHDRS14SSLHI NHDRS20SSLHI NHDRS26SSLHI NHDRS36SSLHI

80A 30mA RCD WAYS BOTTOM BANK

-

8 11 14 19

80A 30mA RCD WAYS TOP BANK

* WAYS

MS

Flexi Flexi Flexi Flexi

Flexi Flexi Flexi Flexi

TOTAL

14 20 26 36

METAL - HIGH INTEGRITY DUPLEX 3xRCDS, 1x 100A MAIN SWITCH CAT REF

80A 30mA RCD WAYS BOTTOM BANK

NHDRS12HI NHDRS18HI NHDRS24HI NHDRS34HI

80A 30mA RCD WAYS BOTTOM BANK

Flexi Flexi Flexi Flexi

Flexi Flexi Flexi Flexi

80A 30mA RCD WAYS TOP BANK

* WAYS

MS

Flexi Flexi Flexi Flexi

Flexi Flexi Flexi Flexi

TOTAL

12 18 24 34

METAL - DUAL RCD DUPLEX 2 xRCDS, 100A MAIN SWITCH

CAT REF

NHDIS1414

BOTTOM BANK 80A 30mA 80A 30mA RCD WAYS RCD WAYS

NHDISS119 NHDISS1214

-

11 14

TOP BANK 80A 30mA MS RCD WAYS WAYS

9 12

TOTAL

-

20 26

METAL - DUAL TARIFF DUPLEX CAT REF

TOP BANK MS RATING *WAYS

NHDIIX88 NHDIIX1111 NHDIIX1414 NHDIIX1919 CAT REF

BOTTOM BANK MS RATING * WAYS

100A 100A 100A 100A

8 11 14 19

100A 100A 100A 100A

8 11 14 19

MS RATING

*WAYS

RCD RATING

MCB WAYS

100A 100A

8 11

80A 30mA 80A 30mA

8 11

NHDISX88 NHDISX1111

MAIN SWITCH CAT REF

80A 30mA RCD WAYS

80A 30mA RCD WAYS

MS RATING

* WAYS

TOTAL

-

-

100A 100A 100A

8 12 17

8 12 17

-

Flexi Flexi

100A 100A

Flexi Flexi

10 15

Flexi Flexi 4 5 6 7

Flexi Flexi 6 5 6 6

100A 100A 100A 100A 100A 100A

Flexi Flexi 5 5 3 2

8 13 15 15 15 15

6 5 7

100A 100A 100A

-

10 10 15

FALNH806 FALNH1206 FALNH1706

SPLIT LOAD FALNHRS10SL FALNHRS15SL

HIGH INTEGRITY FALNHRS8SSL FALNHRS13SSL FALNHRS46506 FALNHRS55506 FALNHRS66306 FALNHRS76206

DUAL SPLIT LOAD RCD FALNHR10SL

FALNHISS4606 FALNHISS5506 FALNHISS8706

4 5 8

RCD INCOMER CAT REF

FALNHRS706 FALNHRS1106

100A 30mA RCD WAYS

TOTAL

7 11

7 11

* RCBOs or MCBs may be fitted to unprotected ways depending upon the installation requirements (see page 40).


MINIATURE CIRCUIT BREAKERS (6KA) C CURVE

RATING

POLES

MODULES

NSB03 NSB06 NSB10 NSB16 NSB20 NSB25 NSB32 NSB40 NSB50

WELC06 WELC10 WELC16 WELC20 WELC32 WELC40 WELC50

3A 6A 10A 16A 20A 25A 32A 40A 50A

1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1

ACCESSORIES NSB06 NSB10 NSB16 NSB20 NSB32 NSB40 NSB50

MCBLDX WPL

MCB Locking device Padlock for MCBLDX

NSBS RCBO ( combined MCB /RCD device)

NSBS6 - B / 1 NSBS16- B / 1 NSBS32- B / 1 NSBS10 - B / 1 NSBS20- B / 1 NSBS40 - B / 1

B CURVE

C CURVE

CURRENT RATING

RCD RATING

POLES

MODULES

NSBS6-B/1 NSBS10-B/1 NSBS16-B/1 NSBS20-B/1 NSBS32-B/1 NSBS40-B/1 NSBS50-B/1

NSBS6/1 NSBS10/1 NSBS16/1 NSBS20/1 NSBS32/1 NSBS40/1 NSBS50/1

6A 10A 16A 20A 32A 40A 50A

30mA 30mA 30mA 30mA 30mA 30mA 30mA

SP SP SP SP SP SP SP

1 1 1 1 1 1 1

-

NSBS6/2 NSBS10/2 NSBS16/2 NSBS20/2 NSBS32/2 NSBS40/2

6A 10A 16A 20A 32A 40A

30mA 30mA 30mA 30mA 30mA 30mA

2P 2P 2P 2P 2P 2P

2 2 2 2 2 2

MODULAR CARTRIDGE FUSE HOLDERS WITH FUSE CAT REF

RATING

POLES

MODULE

SPARE FUSE

5A 10A 15A 20A 30A 35A 40A 45A

1 1 1 1 1 1 1 1

1 1 1 1 1 2 2 2

CFL05 CFL10 CFL15 CFL20 CFL30 CFL35 CFL40 CFL45

NSC05 NSC10 NSC15 NSC20 NSC30 NSC35 NSC40 NSC45

NSC05 NSC10 NSC20 NSC30

NSC45

DIN RAIL MODULAR DEVICES FOR USE IN + UNITS & FLEXIBLE UNITS

MTS12/1 MTS8/1

MESB-40NO

CAT REF

PRODUCT

ME232-230 SMSCD11 TMSCD21 TMTCD22 MESB-20NO MESB-24NO MESB-40NO MESB-63NO MTS8 MTS6/1 MTS8/1 MTS12/1 TRMSCT31 TRMSCT11 SMSCT11

Staircase timer Digital time clock 1 channel 1xNO/NC contact 16A Digital time clock 1 channel 1xNO contact 16A Digital time clock 2 channel 24 hour 7Day prog 20A 2 pole contactor 24A 4 pole contactor 40A 4 pole contactor 63A 4 pole contactor Bell transformer 12V 8VA Bell transformer 6V 8VA Bell transformer 8V 8VA Bell transformer 12V 8VA Disc type time clock 1 channel 1xNC contact 16A Disc type time clock 1 channel 1xNC contact 16A Disc type time clock 1 channel 1xNO contact 16A

MODULE

1 1 2 2 1 2 3 3 2 1 1 1 3 3 1

When fitting in NH Consumer Units contact Wylex technical services department

NH ACCESSORIES

NH00 NH00PP NHB1PP

CAT REF

PRODUCT

NHB1PP NH00PP NH00 NHET25

Blanking plate - Busbar & cover Blanking plate - Twist fit Blanking plate - Push fit 25mm Earth Terminal

MODULE

NH13CBKIT

13 pin comb busbar c/w labels and 5 protection covers

1 1 1 -

9 NH Consumer Unit Outgoing Devices & Control Modules

B CURVE


Standards: Consumer units BS EN 60439 - 3 when fully assembled & designed to BS5486 part 13: 1989 Factory Built Assemblies. Degree of protection IP2X to BS EN60529. Switches BS EN 60947-3 Double pole 240V 50Hz, category of duty AC21. RCBOs BS EN 61009. RCDs BS EN 61008. MCBs B, C, D, switching curve BS EN 60898.


NH DISTRIBUTION BOARDS The Wylex range of NH distribution Boards is designed to cater for a variety of industrial and commercial applications. The wide range of boards is complemented by an extensive choice of incoming Devices including direct connection, switch disconnector and RCD, outgoing devices include a broad selection of MCBs and RCBOs . This comprehensive collection of circuit protection and distribution products allows the contractor to select the most economical and electrically appropriate solutions. ●

All metal enclosures for both A Boards and B Boards

Two frame sizes 125A and 250A B Boards

Choice of incoming devices including Switch Disconnector, RCDs, or Direct Connection

B Boards accept four pole incomers (125A)

Over 250 different boards available from standard catalogue items

Removable pan assembly and gland plates for easy fixing and cable entry

Split neutral bars help make full use of interior space and keep all terminals accessible

Range of 10kA and 6kA MCBs

Single pole 18mm wide RCBOs


TYPE ‘A’ SP & N DISTRIBUTION BOARD

NH Distribution Boards

12

CAT REF

SWITCH RATING

NHSPN0051 NHSPN0081 NHSPN00111 NHSPN00141 NHSPN00161 NHSPN00191

125A 125A 125A 125A 125A 125A

NO. OF SP WAYS

5 8 11 14 16 19

A wide range of custom built variations are also available. Contact Wylex Technical for full details.

NHSPN0081

TP & N TYPE ‘B’ DISTRIBUTION BOARDS (Excluding Incomer) CAT REF

DESCRIPTION

NHTN4 NHTN6 NHTN8 NHTN12 NHTN16 NHTN20 NHTN24

125A Distribution board Excluding incomer 125A Distribution board Excluding incomer 125A Distribution board Excluding incomer 125A Distribution board Excluding incomer 125A Distribution board Excluding incomer 125A Distribution board Excluding incomer 125A Distribution board Excluding incomer

NO. OF TP WAYS

4 6 8 12 16 20 24

Suitable for use with switch disconnector, RCD or direct connection incomer arrangement IP66 TP & N MCB Distribution boards are available up to 16 TP ways

NH 125 METER PACKS An add on assembly fits below a NHTN 125A board comprising of an enclosure with a slotted front plate and hinged door. Digital meter with pulsed output, offering Amps, Volts and Kwh readout. 3x current transformers with associated fuses and wiring.

NHTN4

CAT REF

HEIGHT

NHTN125MP

245mm

TP & N TYPE ‘B’ DISTRIBUTION BOARDS (Excluding Incomer) CAT REF

DESCRIPTION

NHTN2540 NHTN2560 NHTN2580 NHTN25120 NHTN25160 NHTN25200 NHTN25240

250A Distribution board Excluding incomer 250A Distribution board Excluding incomer 250A Distribution board Excluding incomer 250A Distribution board Excluding incomer 250A Distribution board Excluding incomer 250A Distribution board Excluding incomer 250A Distribution board Excluding incomer

NO. OF TP WAYS

4 6 8 12 16 20 24

NH 250 METER PACKS An add on assembly fits below a NHTN 250A board comprising of an enclosure with a slotted front plate and hinged door. Digital meter with pulsed output, offering Amps, Volts and Kwh readout. 3x current transformers with associated fuses and wiring. CAT REF

HEIGHT

NHTN250MP

245mm

NHTN25120 Suitable for switch disconnector, or direct connection incomer arrangement Flush mounting boards also available add suffix /FLU to Catalogue Reference eg: NHTN4/FLU


NH A BOARD INCOMERS DESCRIPTION

RATING

WS602 WS102 WS122 WRS63/2 WRS80/2 WRS100/2 WRM63/2 WRM80/2 WRM100/2 WRL63/2 WRL100/2 WRMT100/2 NHDPDC

2 Pole 2 module switch 2 Pole 2 module switch 2 Pole 2 module switch Double Pole RCD Double Pole RCD Double Pole RCD Double Pole RCD Double Pole RCD Double Pole RCD Double Pole RCD Double Pole RCD Double Pole Time Delay RCD Double Pole direct connection

63A 100A 125A 63A 30mA 80A 30mA 100A 30mA 63A 100mA 80A 100mA 100A 100mA 63A 300mA 100A 300mA 100A 100mA 100A

NH B BOARD INCOMERS

WS123

CAT REF

DESCRIPTION

RATING

WS603 WS103 WS123 WS604 WS104 WS124 WRS63/4 WRS100/4 WRM63/4 WRM100/4 WRL63/4 WRL100/4 WRMT100/4 NH4PINKIT NH200TPSW NH250TPSW NHTPDC NH250DC NHSPAK

3 Pole 3 module switch 3 Pole 3 module switch 3 Pole 3 module switch 4 Pole 4 module switch* 4 Pole 4 module switch* 4 Pole 4 module switch* Four Pole RCD* Four Pole RCD* Four Pole RCD* Four Pole RCD* Four Pole RCD* Four Pole RCD* Four Pole Time Delay RCD* Four Pole Incomer Connection Kit* Three Pole switch disconnector Three Pole switch disconnector Direct connection Direct connection Single phase adaptor kit

63A 100A 125A 63A 100A 125A 63A 30mA 100A 30mA 63A 100mA 100A 100mA 63A 300mA 100A 300mA 100A 100mA 100A 200A 250A 125A 250A 125A

* Four Pole DIN Incomers require Incomer connection Kit. REF, NH4PINKIT

EXTENSION & ACCESSORY BOXES

NHAB2

CAT REF

DESCRIPTION

DIN MODULES

NHEB NHEB/DIN NHAB NHAB2 NHAB3 NHAB4 NHAB5

Cable extension box (plain) DIN accessory box single row (plain) DIN accessory box single row DIN accessory box two row DIN accessory box three row DIN accessory box four row DIN accessory box five row

18 36 54 72 90

18 modules per row

ACCESSORIES

NH4PINKIT

CAT REF

DESCRIPTION

NHEP11 NH00 NHB1PP NH18BB1 PSBL3 PSBL9 MCBLDX WPL NHPBDL PDDPL NHCEKIT NHCEKIT20 NHMSL NHBBTOK

Replacement gland plate Way blank 1 Way busbar & cover blank 9 busbar insulators Way blank (3 module) Way blank (9 modules) Locking device for MCB Padlock for MCBLDX MCB Board lock Doorlock with padlocking device 14 terminal clean earth kit 20 terminal clean earth kit Locking device for incoming switch Bus bar tap off kit

13 NH Distribution Board Incoming Units & Accessories

WS102

CAT REF


SINGLE POLE MCBs RATING

NH Miniature Circuit Breakers

14

PSB06-B

PSB32-B

PSB63-B

6A 6kA 10A 6kA 16A 6kA 20A 6kA 32A 6kA 40A 6kA 50A 6kA 63A 6kA 6A 10kA 10A 10kA 16A 10kA 20A 10kA 25A 10kA 32A 10kA 40A 10kA 50A 10kA 63A 10kA

POLES

B CURVE

C CURVE

D CURVE

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

NSB06-B NSB10-B NSB16-B NSB20-B NSB32-B NSB40-B NSB50-B NSB63-B PSB06-B PSB10-B PSB16-B PSB20-B PSB25-B PSB32-B PSB40-B PSB50-B PSB63-B

NSB06-C NSB10-C NSB16-C NSB20-C NSB32-C NSB40-C NSB50-C NSB63-C PSB06-C PSB10-C PSB16-C PSB20-C PSB25-C PSB32-C PSB40-C PSB50-C PSB63-C

NSB06-D NSB10-D NSB16-D NSB20-D NSB32-D NSB40-D NSB50-D NSB63-D PSB06-D PSB10-D PSB16-D PSB20-D PSB25-D PSB32-D PSB40-D PSB50-D PSB63-D

TWO POLE MCBs RATING

PSB206-B

PSB232-B

POLES

B CURVE

C CURVE

D CURVE

6A 6kA 10A 6kA 16A 6kA 20A 6kA 32A 6kA 40A 6kA 50A 6kA 63A 6kA

2 2 2 2 2 2 2 2

NSB206-B NSB210-B NSB216-B NSB220-B NSB232-B NSB240-B NSB250-B NSB263-B

NSB206-C NSB210-C NSB216-C NSB220-C NSB232-C NSB240-C NSB250-C NSB263-C

NSB206-D NSB210-D NSB216-D NSB220-D NSB232-D NSB240-D NSB250-D NSB263-D

6A 10kA 10A 10kA 16A 10kA 20A 10kA 25A 10kA 32A 10kA 40A 10kA 50A 10kA 63A 10kA

2 2 2 2 2 2 2 2 2

PSB206-B PSB210-B PSB216-B PSB220-B PSB225-B PSB232-B PSB240-B PSB250-B PSB263-B

PSB206-C PSB210-C PSB216-C PSB220-C PSB225-C PSB232-C PSB240-C PSB250-C PSB263-C

PSB206-D PSB210-D PSB216-D PSB220-D PSB225-D PSB232-D PSB240-D PSB250-D PSB263-D

TRIPLE POLE MCBs RATING

PSB306-B

PSB332-B

6A 10A 16A 20A 32A 40A 50A 63A 6A 10A 16A 20A 25A 32A 40A 50A 63A

6kA 6kA 6kA 6kA 6kA 6kA 6kA 6kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA

POLES

B CURVE

C CURVE

D CURVE

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

NSB306-B NSB310-B NSB316-B NSB320-B NSB332-B NSB340-B NSB350-B NSB363-B PSB306-B PSB310-B PSB316-B PSB320-B PSB325-B PSB332-B PSB340-B PSB350-B PSB363-B

NSB306-C NSB310-C NSB316-C NSB320-C NSB332-C NSB340-C NSB350-C NSB363-C PSB306-C PSB310-C PSB316-C PSB320-C PSB325-C PSB332-C PSB340-C PSB350-C PSB363-C

NSB306-D NSB310-D NSB316-D NSB320-D NSB332-D NSB340-D NSB350-D NSB363-D PSB306-D PSB310-D PSB316-D PSB320-D PSB325-D PSB332-D PSB340-D PSB350-D PSB363-D


SINGLE MODULE RCBO FOR USE IN NH TYPE A & B DISTRIBUTION BOARDS RATING

6A 10kA 10A 10kA 16A 10kA 20A 10kA 32A 10kA 40A 10kA 50A 10kA

RCD RATING

C CURVE

1 1 1 1 1 1 1

30mA 30mA 30mA 30mA 30mA 30mA 30mA

PSBS6/1 PSBS10/1 PSBS16/1 PSBS20/1 PSBS32/1 PSBS40/1 PSBS50/1

PSBS32/1 PSBS50/1

ACCESSORIES

MCBLDX WPL

NH00 NH00PP

NHB1PP

CAT REF

DESCRIPTION

NHEP11 NH00 NH00PP NHB1PP NH18BB1 PSBL3 PSBL9 MCBLDX WPL NHPBDL PDDPL NHCEKIT NHCEKIT20 NHMSL NHBBTOK

Replacement gland plate Way blank Twist fit 1 module blank 1 Way busbar & cover blank 9 busbar insulators Way blank (3 module) Way blank (9 modules) Locking device for MCB Padlock for MCBLDX MCB Board lock Doorlock with padlocking device 14 terminal clean earth kit 20 terminal clean earth kit Locking device for incoming switch Bus bar tap off kit

TWO MODULE RCBO NOT FOR USE IN NH TYPE A & B DISTRIBUTION BOARDS

PSBS40/2

RATING

POLES

RCD RATING

C CURVE

6A 6kA 10A 6kA 16A 6kA 20A 6kA 32A 6kA 40A 6kA

2 2 2 2 2 2

30mA 30mA 30mA 30mA 30mA 30mA

NSBS6/2 NSBS10/2 NSBS16/2 NSBS20/2 NSBS32/2 NSBS40/2

6A 10kA 10A 10kA 16A 10kA 20A 10kA 32A 10kA 40A 10kA

2 2 2 2 2 2

30mA 30mA 30mA 30mA 30mA 30mA

PSBS6/2 PSBS10/2 PSBS16/2 PSBS20/2 PSBS32/2 PSBS40/2

For use in DIN Enclosures EG: NH ED Range or + Units

DIN RAIL MODULAR DEVICES

TMSCD21

TMTCD22

MESB-40NO

15 SP & SPSN RCBOs & Modular Devices

PSBS6/1

POLES

CAT REF

PRODUCT

SMSCD11 TMSCD21 TMTCD22 MESB-20NC MESB-20NO MESB-24NC MESB-24NO MESB-40NC MESB-40NO MESB-63NO

Digital Timeclock 1 channel 1xNO/NC Contact 16A Digital Timeclock 1 channel 1xNO Contact 16A Digital Timeclock 2 channel 240V Coil 2 Pole 20A Contact rating 2 x N/C 240V Coil 2 Pole 20A Contact rating 2 x N/O 240V Coil 4 Pole 24A Contact rating 4 x N/C 240V Coil 4 Pole 24A Contact rating 4 x N/O 240V Coil 4 Pole 40A Contact rating 4 x N/C 240V Coil 4 Pole 40A Contact rating 4 x N/O 240V Coil 4 Pole 63A Contact rating 4 x N/O

For use in DIN Enclosures EG: NH ED Range, Flexible CUs or ‘+’ Units

MODULE

1 2 2 1 1 2 2 3 3 3


NH125 MCCB PANELBOARDS NH125 MCCB Panelboards offer 250A or 400A fault rated, fully shrouded busbar systems in a modular enclosure system. The 630mm wide enclosure system combined with MCCBs and a range of accessories, provides a competent flexible main or sub-main distribution board.

NHG125 MCCBs with 25kA fault breaking capacity

25A - 125A ratings G Frame

70mm2 cable clamp terminals or 10mm flat bar

Comprehensive range of accessories including sealable terminal covers

Fully shrouded bus bars

Excellent access to N/E bars for cabling

Full or partial lockable doors

Conforms fully with BSEN 60943-1 form 2


250A SWITCH DISCONNECTOR INCOMER

250A

OUTGOING MODULAR WAYS HEIGHT

HEIGHT (mm)

CAT REF

6 8 12

902 902 1060

NHPB6SW250 NHPB8SW250 NHPB12SW250

17 17 20

NHPB6SW250

200A MCCB INCOMER

200A

OUTGOING MODULAR WAYS HEIGHT

HEIGHT (mm)

CAT REF

6 8 12

902 902 1060

NHPB6CB200 NHPB8CB200 NHPB12CB200

17 17 20

BSEN 60439 250A Busbars ● Busbar fault rated 25kA–1 sec ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● 630mm wide x 165mm deep ● 120 mm2 4 Core Max on Incoming Terminals ● 70 mm2 4 Core Max on Outgoing Terminals ● Fully assembled ● Complete with incomer ● ●

NH 125 PANEL BOARD METER PACKS NHPB6CB200

An add on assembly fits below a NHPB 250A Panelboard comprising of an enclosure with a slotted front plate and hinged door. Digital meter with pulsed output, offering Amps, Volts and Kwh readout. 3x current transformers with associated fuses and wiring. RATING

HEIGHT

CAT REF

0-250A

210mm

NHG250MP

PANELBOARD

MODULAR HEIGHT

CAT REF

6/8 way 12 way Door lock

17 20

DOOR KITS

NHFHDK17 NHFHDK20 NHPBDL

ACCESSORY BOXES

NHG250MP

PANELBOARD

MODULAR HEIGHT

HEIGHT (mm)

Cable Spreader Box DIN Accessory Box A Board 13 way

4

210

CAT REF

NHCSB NHGAB NHG13DB

All NH Panelboard enclosures are 630mm wide x 165mm deep x modular height 1 Module = 52.5mm. Colour finish RAL 7035

17 NH125 Panelboards

BSEN 60439 250A Busbars ● Busbar fault rated 25kA–1 sec ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● 630mm wide x 165mm deep ● 120 mm2 4 Core Max on Incoming Terminals ● 70 mm2 4 Core Max on Outgoing Terminals ● Fully assembled ● Complete with incomer ● Also available excluding incomer for direct connection applications ●


400A SWITCH DISCONNECTOR INCOMER

400A

18

OUTGOING WAYS

MODULAR HEIGHT

HEIGHT (mm)

6 8 12 16

20 20 23 26

1060 1060 1217 1375

CAT REF

NHPB6SW400 NHPB8SW400 NHPB12SW400 NHPB16SW400

BSEN 60439 400A Busbars ● Busbar fault rated 25kA–1 sec ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● 630mm wide x 165mm deep ● 240 mm2 4 Core Max on Incoming Terminals ● 70 mm2 4 Core Max on Outgoing Terminals ● Fully assembled ● Complete with incomer ● Also available excluding incomer for direct connection applications ●

NH125 Panelboards

NHPB6SW400

400A MCCB INCOMER

400A

OUTGOING WAYS

MODULAR HEIGHT

HEIGHT (mm)

6 8 12 16

20 20 23 26

1060 1060 1217 1375

CAT REF

NHPB6CB400 NHPB8CB400 NHPB12CB400 NHPB16CB400

Conforms to BSEN 60439 400A Busbars ● Busbar fault rated 25kA–1 sec ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● 630mm wide x 165mm deep ● 240 mm2 4 Core Max on Incoming Terminals ● 70 mm2 4 Core Max on Outgoing Terminals ● Fully assembled ● Complete with incomer ● ●

NH 125 PANEL BOARD METER PACKS NHPB6CB400

An add on assembly fits below a NHPB 400A Panelboard comprising of an enclosure with a slotted front plate and hinged door. Digital meter with pulsed output, offering Amps, Volts and Kwh readout. 3x current transformers with associated fuses and wiring. RATING

HEIGHT

CAT REF

0-400A

210mm

NHG400MP

PANELBOARD

MODULAR HEIGHT

CAT REF

6/8 way

20

NHFHDK20

12 way

23 (12+11)

NHCBDK12 NHCBDK11

16 way

26 (15+11)

DOOR KITS

} NHCBDK15 NHCBDK11 }

Door lock

NHPBDL

EXTENSION BOXES

NHFHDK20

PANELBOARD

MODULAR HEIGHT

HEIGHT (mm)

Cable Spreader Box DIN Accessory Box A Board 13 way

4

210

CAT REF

NHCSB NHGAB NHG13DB


NH SINGLE POLE MCCBs Conforms to BSEN 60947-2 16kA Icu at 240V ac ● Fixed magnetic ● Fixed thermal ● Double insulated ● Terminal Capacity 70mm2 ● ●

RATING

NHGPCB161 NHGPCB251 NHGPCB321 NHGPCB401 NHGPCB501 NHGPCB631 NHGPCB801 NHGPCB1001 NHGPCB1251

NHGPCB1001

NH THREE POLE MCCBs Conforms to BSEN 60947-2 25kA Icu at 415V ac ● Fixed magnetic ● Fixed thermal ● Double insulated ● Large range of accessories ● Terminal Capacity 70mm2 ● ●

RATING

16A 25A 32A 40A 50A 63A 80A 100A 125A

CAT REF

NHGPCB163 NHGPCB253 NHGPCB323 NHGPCB403 NHGPCB503 NHGPCB633 NHGPCB803 NHGPCB1003 NHGPCB1253

NHGPCB633

NH MCCBs ACCESSORIES DESCRIPTION

CAT REF

70mm Terminal adaptor (2x25 to 1x70mm) Dolly and padlocking facility Padlock to fit

NHPBN25/70 NHPCBLDX NHPCBPL

1P Terminal Shroud 3P Terminal Shroud

NHPCB1TS NHPCB3TS

AUXILIARY EQUIPMENT

Auxiliary Contacts 1 x n.o./n.c. Volt Free 2 x n.o./n.c. Volt Free 9 x Busbar Insulators 9 module Blanking plate

NHCB1TS

NHCB3TS

NHPCBAU1 NHPCBAU2 NH18BB1 PSBL9

19 NH125 Panelboard Circuit Breakers

16A 25A 32A 40A 50A 63A 80A 100A 125A

CAT REF



NH200 MCCB PANELBOARDS NH200 MCCB Panelboards offer 400A, 630A and 800A fault rated, fully shrouded busbar systems in a modular enclosure arrangement. The 630mm wide enclosure system combined with NH J MCCBs and a range of accessories, provides a competent flexible main or sub-main distribution board. ●

NH J MCCBs with 25kA fault breaking capacity ●

25A - 200A ratings J Frame ●

70mm2 cable clamp terminals or 10mm flat bar ●

Comprehensive range of accessories including sealable terminal covers ●

Fully shrouded bus bars ●

Excellent access to N/E bars for cabling ●

Full or partial lockable doors ●

Conforms fully with BSEN 60943-1 form 2


400A J FRAME PANEL BOARDS OUTGOING WAYS

MODULAR HEIGHT

HEIGHT (mm)

3 4 5 6

576 768 960 1152

NSPE-4136 NSPE-4120 NSPE-4137 NSPE-4138

3 4 5 6

576 768 960 1152

NSPE-4182 NSPE-4183 NSPE-4184 NSPE-4185

3 4 5 6

576 768 960 1152

NSPE-4186 NSPE-4187 NSPE-4188 NSPE-4189

CAT REF

Switch Disconnector Incomer 400A

22

4 8 12 16

NH200 Panelboards

32kA MCCB Incomer 400A

4 8 12 16

50kA MCCB Incomer 400A

4 8 12 16

BSEN 60439 400A Busbar ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● Fully assembled ● Complete with incomer ●

NSPE 4120

630A J FRAME PANEL BOARDS OUTGOING WAYS

MODULAR HEIGHT

HEIGHT (mm)

3 4 5 6

576 768 960 1152

NSPE-4190 NSPE-4191 NSPE-4192 NSPE-4193

3 4 5 6

576 768 960 1152

NSPE-4171 NSPE-4172 NSPE-4173 NSPE-4174

3 4 5 6

576 768 960 1152

NSPE-4194 NSPE-4195 NSPE-4196 NSPE-4197

CAT REF

Switch Disconnector Incomer 630A

4 8 12 16

32kA MCCB Incomer 630A

4 8 12 16

50kA MCCB Incomer 630A

NSPE 4172

4 8 12 16

BSEN 60439 630A Busbar ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● Fully assembled ● Complete with incomer ● ●

800A J FRAME PANEL BOARDS OUTGOING WAYS

MODULAR HEIGHT

HEIGHT (mm)

3 4 5 6

576 768 960 1152

NSPE-4151 NSPE-4152 NSPE-4153 NSPE-4154

3 4 5 6

576 768 960 1152

NSPE-4198 NSPE-4199 NSPE-4200 NSPE-4201

CAT REF

Switch Disconnector Incomer 800A

4 8 12 16

50kA MCCB Incomer 800A

BSEN 60439 800A Busbar ● IP31 (41 with door) Ingress Protection ● Earth and neutral terminals for each SP way ● Fully assembled ● Complete with incomer ● ●

NSPE 4199

4 8 12 16


NH J SINGLE POLE MCCBs Conforms to BSEN 60947-2 50kA Icu at 240V ac ● Fixed magnetic ● Fixed thermal ● Double insulated ● Terminal Capacity 120mm2 (solid) 150mm2 (stranded) ● ●

RATING

CAT REF

NHJPCB161 NHJPCB251 NHJPCB321 NHJPCB401 NHJPCB501 NHJPCB631 NHJPCB801 NHJPCB1001 NHJPCB1251 NHJPCB1601 NHJPCB2001

NHJPCB1601 NH J THREE POLE MCCBs Conforms to BSEN 60947-2 50kA Icu at 240V ac ● Fixed magnetic ● Fixed thermal ● Double insulated ● Terminal Capacity 120mm2 (solid) 150mm2 (stranded) ● ●

RATING

CAT REF

16A 25A 32A 40A 50A 63A 80A 100A 125A 160A 200A

NHJPCB163 NHJPCB253 NHJPCB323 NHJPCB403 NHJPCB503 NHJPCB633 NHJPCB803 NHJPCB1003 NHJPCB1253 NHJPCB1603 NHJPCB2003

SINGLE POLE NH J WAY BLANK NHJPCB2003

MODULES

CAT REF

1

NHJ00

OUTGOING SECTION OPTIONAL DOORS 3 Mod high door (4W OUT) 4 Mod high door (8W OUT) 5 Mod high door (12W OUT) 6 Mod high door (16W OUT)

MODULES

CAT REF

3 4 5 6

NHJD03 NHJD04 NHJD05 NHJD06

CABLEWAYS/SPREADER EXTENSION BOXES

NHJD04

MODULES

CAT REF

3 Mod side cable way ✝ 4 Mod side cable way ✝ 5 Mod side cable way ✝ 6 Mod side cable way ✝

3 4 5 6

NHJCW3 NHJCW4 NHJCW5 NHJCW6

2 Mod cable spreader box ✝✝ 3 Mod cable spreader box ✝✝ 4 Mod cable spreader box ✝✝ 5 Mod cable spreader box ✝✝ 6 Mod cable spreader box ✝✝

2 3 4 5 6

NHJCSB2 NHJCSB3 NHJCSB4 NHJCSB5 NHJCSB6

✝ Fits left or right hand side of Panelboard ✝✝ Fits at bottom of Panelboard

23 NH200 Panelboard Circuit Breakers

16A 25A 32A 40A 50A 63A 80A 100A 125A 160A 200A


NH FUSE-COMBINATION UNITS NH Fuse combination units are designed with features that ensure compliance with EN60947 while also providing an economical and high quality range of industrial switchgear products. With ratings from 20A to 200A and a choice of single pole or three pole configurations, NH fuse combination units have a utilisation category of AC23A, and fused short circuit capacity of 80kA.

Robust steel enclosures with cable glanding plate supplied top and bottom

Removable door opens through 180º for ease of access

Easy access fuse link fixings

Neutral fully rated

Fully shrouded terminals

Handle padlocking facility locks switch & door in off position

Large cable terminal capacity

Ingress protection to IP4X

Positive indication of On and Off


NH FUSE COMBINATION UNIT 20A-32A AMPERAGE

20A 20A 32A 32A

TYPE

SUPPLIED WITH FUSES

4 4 4 4

SP & N TP & N SP & N TP & N

YES YES YES YES

CAT REF

NHSPSF20 NHTPSF20 NHSPSF32 NHTPSF32

Fuse Combination Units Technical Specification EN 60947-3 IEC 947-3 80kA RMS Fused Short Circuit Capacity 415V ac Rated Voltage Full Uninterrupted Duty AC23A Utilisation Category

NH FUSE COMBINATION UNIT 63A-125A AMPERAGE

63A 63A 100A 100A 125A

MODULES

TYPE

SUPPLIED WITH FUSES

5 5 5 5 6

SP & N TP & N SP & N TP & N TP & N

YES YES YES YES YES

CAT REF

NHSPSF63 NHTPSF63 NHSPSF100 NHTPSF100 NHTPSF125

ACCESSORIES 63A 100A & 125A 63A to 100A 125A For fuse types see page 50

DESCRIPTION

CAT REF

Copper Isolator links Copper Isolator links Cable Spreader Box Cable Spreader Box

NHCIL2 NHCIL3 NHCSB2 NHCSB3

NHTPSF63

NH FUSE COMBINATION UNIT 160A-800A AMPERAGE

160A 200A 315A 400A 630A 800A

MODULES

6 6 8 8 12 12

TYPE

TP TP TP TP TP TP

& & & & & &

SUPPLIED WITH FUSES

N N N N N N

NO NO NO NO NO NO

CAT REF

NHTPSF160 NHTPSF200 NHTPSF315 NHTPSF400 NHTPSF630 NHTPSF800

ACCESSORIES

100A 125A 315A 315A 630A 630A

NHTPSF160

to 200A to 200A & 400A & 400A & 800A & 800A

DESCRIPTION

CAT REF

Copper Isolator links Cable Spreader Box Copper Isolator links Cable Spreader Box Copper Isolator links Cable Spreader Box

NHCIL3 NHCSB3 NHCIL4 NHCSB4 NHCIL5 NHCSB5

For fuse types see page 50

BUS BAR CHAMBER AMPERAGE

400A 250A

MODULES

TYPE

16 Each

TP & N Busbar Terminal

CAT REF

NHSFBBC400 NHSFBBTM250

NH ISOLATOR SWITCHES IN STEEL ENCLOSURE AMPERAGE

NHSW63X

20A 32A 40A 63A 63A 100A 125A

BOX SIZE

1 1 1 1 2 2 1

CAT REF

NHSW320 NHSW332 NHSW340 NHSW363 NHSW363X NHSW3100 NHSW3125

Cable spreading room is allowed for at one end only. To fit a 4 core cable at both ends an additional cable spreader box will be required. Above 22mm wide cable lugs terminal interphase barriers are required. 1 Module=52.5mm. Contact Wylex Technical Services department for details.

25 NH Fuse Combination Units & Isolator Switches

NHSPSF32

MODULES



STANDARD RANGE The Wylex Standard range of consumer units remains one of the most widely used ranges in domestic circuit protection applications.

This time saving feature offers installers an economical alternative to full consumer unit replacement.

Originally designed with fuses in mind, standard consumer units can easily be upgraded to current standards by using the plug in range of MCBs.

The range also includes SP&N switch fuses up to 100A allowing for submain circuit installation or system extensions / additions to be easily completed.


INSULATED - SWITCH FUSE CAT REF

CURRENT RATING

NO. OF WAYS

45A 60A 60A

1 1 1

104 108 160C

‘C’ models supplied with cartridge fuse

Standard Range

28

104

INSULATED-MAIN SWITCH ISOLATOR CAT REF

ISOLATOR RATING

NO. OF WAYS

45A 60A 60A 100A 100A

2 3 4 6 8

CAT REF

CURRENT RATING

NO. OF WAYS

106 106RED 108M 160CM* 110M/63* 110M/80* 110M*

45A 45A 60A 60A 63A 80A 100A

1 1 1 1 1 1 1

204 304 404 604 804

204

METAL- SWITCH FUSE

*Supplied complete with cartridge fuse

160CM

110M

METAL-MAIN SWITCH ISOLATOR CAT REF

206 306 406 606

106

206

ISOLATOR RATING

NO. OF WAYS

45A 60A 60A 100A

2 3 4 6


MCBs CAT REF

CURRENT RATING

CONTACT SHIELD COLOUR

6A 10A 16A 20A 32A 40A

WHITE GREY BLUE YELLOW RED ORANGE

B6 B10 B16 B20 B32 B40

B10

B16

B20

B32

B40

CARTRIDGE FUSES (Including contact shield) CAT REF

CURRENT RATING

CONTACT SHIELD COLOUR

5A 15A 20A 30A 35A 40A 45A

WHITE BLUE YELLOW RED ORANGE ORANGE GREEN

C5 C15 C20 C30 C35 C40 C45 CAT REF

CURRENT RATING

L45 L60

C5

C15

C20

C30

C35

C40

45A 60A

}

for use with 108, 145 & 160 type switch fuses

C45

CARTRIDGE FUSE LINKS CAT REF

CURRENT RATING

CONTACT SHIELD COLOUR

5A 10A 15A 20A 30A 35A 40A 45A

WHITE BLUE BLUE YELLOW RED ORANGE ORANGE GREEN

CFL05 CFL10 CFL15 CFL20 CFL30 CFL35 CFL40 CFL45

CARTRIDGE FUSE LINKS CAT REF

CARTRIDGE FUSE LINKS

CURRENT RATING

}

LFL45 LFL60

45A 60A

LFL63 LFL80 LFL100

63A for use with 110M 80A units only 100A

for use with 108 or 108M

}

ACCESSORIES

M10

CAT REF

DESCRIPTION

FWC M10

Fusewire card 1m 5A, 15A, 30A Blank shield for unused ways

Standard Range Outgoing Devices & Accessories

B6

29



LIFELINE RANGE The Lifeline range of residual current devices, rcd’s provides valuable additional protection to almost any type of installation by detecting earth fault current below the level sensed by traditional overcurrent devices such as fuses of miniature circuit breakers.

One of the largest ranges available in the UK today offers other features which include:●

Fully shrouded terminals

Contact position indication on the dolly handle

Both Type AC and Type A (DC sensitive) devices available

A range of enclosures from IP20 upto IP65

Time delay versions available in 2 and 4 pole configurations


2 POLE RCDs – TYPE AC CAT REF

Lifeline Range

32

WRS32/2

WRS80/2

WRS16/2 WRS25/2 WRS32/2 WRS40/2 WRM40/2 WRS63/2 WRM63/2 WRL63/2 WRS80/2 WRM80/2 WRS100/2 WRM100/2 WRL100/2

RATED CURRENT

SENSITIVITY

16A 25A 32A 40A 40A 63A 63A 63A 80A 80A 100A 100A 100A

30mA 30mA 30mA 30mA 100mA 30mA 100mA 300mA 30mA 100mA 30mA 100mA 300mA

2 POLE RCDs DC SENSITIVE – TYPE A CAT REF

WRDVS32/2 WRDS40/2 WRDM40/2 WRDS63/2 WRDS80/2 WRDS100/2 WRDM100/2

WRS100/2

RATED CURRENT

SENSITIVITY

32A 40A 40A 63A 80A 100A 100A

10mA 30mA 100mA 30mA 30mA 30mA 100mA

WRM100/2

4 POLE RCDs – TYPE AC CAT REF

WRS32/4 WRS40/4 WRM40/4 WRS63/4 WRM63/4 WRL63/4 WRS100/4 WRM100/4 WRL100/4

RATED CURRENT

SENSITIVITY

32A 40A 40A 63A 63A 63A 100A 100A 100A

30mA 30mA 100mA 30mA 100mA 300mA 30mA 100mA 300mA

4 POLE RCDs DC SENSITIVE – TYPE A CAT REF

WRS63/4

WRDS40/4 WRDM40/4 WRDS63/4 WRDM63/4 WRDS100/4 WRDM100/4

RATED CURRENT

SENSITIVITY

40A 40A 63A 63A 100A 100A

30mA 100mA 30mA 100mA 30mA 100mA

TIME DELAY UNITS (100ms) TYPE S CAT REF

WRMT100/2 WRMT100/4

WRMT100/4

DESCRIPTION

RATED CURRENT

SENSITIVITY

2P 4P

100A 100A

100mA 100mA


DIN ENCLOSURES IP RATING

CAT REF INSULATED

CAT REF METAL

2 2 2

IP40 IP40 IP54

ESE2 ESE2L* -

ESM6 ESM7

4 4 4 4

IP20 IP40 IP54 IP54

ESE4 ESi4 -

ESM8 ESM11 ESM13**

* Supplied with earth connection link ** Enclosure for larger cables

ESE2

ESE4

ESM6

ESM8

IP65 DIN ENCLOSURES AND ACCESSORIES WBE4/NK installed in WBE4

CAT REF

DESCRIPTION

WBE3 WBE4 WBE3/EK WBE3/NK WBE4/EK WBE4/NK WBE/BS

2/3 module enclosure 4 module enclosure Earth block Neutral block Earth block Neutral block Blanks

NH INSULATED DIN ENCLOSURES CAT REF

DESCRIPTION

NH4ED4 4 modules NH7ED4 7 modules NH10ED4 10 modules NH13ED4 13 modules NH16ED4 16 modules NH21ED4 21 modules Supplied with earth & neutral terminal bars cover and visor

NH10ED4

NH METAL DIN ENCLOSURES CAT REF

DESCRIPTION

NH4ED6 4 modules NH7ED6 7 modules NH10ED6 10 modules NH13ED6 13 modules NH16ED6 16 modules NH21ED6 21 modules Supplied with earth & neutral terminal bars cover and visor

NH13ED6

33 Enclosures Range

DIN MODULES


SWITCH DISCONNECTORS & ISOLATORS Wylex provide a range of isolators designed for applications where local isolation is required. The modular WS range of switches can be independently configured to provide a variety of live and neutral arrangements up to 4 poles. In addition Wylex offer a range of enclosed switch disconnector isolators suitable for commercial and industrial applications up to 125A. Rotary isolators can be locked in the off position and have facility for up to 3 padlocking devices for added safety and security.


TRIPLE POLE & NEUTRAL 415V, 50HZ AC CAT REF

DESCRIPTION

921E

With switched neutral, surface mounting in a metal enclosure With switched neutral, for loose mounting in an enclosure (Non DIN)

921X

CURRENT RATING

32A 32A

35

NH ISOLATOR SWITCHES STEEL ENCLOSURE RATING

20A 32A 40A 63A 63A 100A 125A

BOX SIZE

1 1 1 1 2 2 2

TP&N/SP&N

NHSW320 NHSW332 NHSW340 NHSW363 NHSW363X NHSW3100 NHSW3125

NHSW363X

SUPPLY AUTHORITY ISOLATOR ASSEMBLIES CAT REF

DESCRIPTION

REC2S REC2 REC3 REC4

Slimline & DP Switch Enclosure DP Isolator & 4 Mod Enclosure TP Isolator & 4 Mod Enclosure 4P Isolator & 4 Mod Enclosure

CURRENT RATING

100A 100A 100A 100A

A wide range of custom built variations is also available. Contact Wylex Technical for full details.

REC2S

REC4

WS RANGE OF MODULAR ISOLATORS

WS102

WS104

CAT REF

DESCRIPTION

WS601 WS101 WS121

1 Pole, 1 module 1 Pole, 1 module 1 Pole, 1 module

CURRENT RATING

63A 100A 125A

WS602 WS102 WS122

2 Pole, 2 module 2 Pole, 2 module 2 Pole, 2 module

63A 100A 125A

WS603 WS103 WS123

3 Pole, 3 module 3 Pole, 3 module 3 Pole, 3 module

63A 100A 125A

WS604 WS104 WS124

4 Pole, 4 module 4 Pole, 4 module 4 Pole, 4 module

63A 100A 125A

Isolators & Switch Disconnectors

921E


TECHNICAL DATA & DIMENSIONS

D

A

C E

B Fault

Maximum prospective fault current

A

Healthy circuit current

20ms

20ms

B


MCB INTERNAL VIEW

Box terminal

37

Fixed contact

Trip bar Arc runner

Moving contact

Thermo-element

Box terminal Busbar aperture DIN clip

GENERAL CONSTRUCTION Wylex MCBs are of the thermal-magnetic current limiting type. MCBs have an easy to operate handle with a trip-free toggle mechanism – so even when the handle is held in the ‘on’ position the MCB is free to trip. AMBIENT TEMPERATURE CONSIDERATIONS Wylex MCBs are calibrated to meet the requirements of BS EN 60898, 30°C Ref Calibration Temperature. At other temperatures the following rating factors should be used: At 60°C 0.9

At 20°C 1.0

At 0°C 1.1

Adjacent thermal-magnetic MCBs should not be continuously loaded at or approaching their nominal rated currents when mounted in enclosures. It is good engineering practice to apply generous derating factors or make provision for adequate free air between devices. In these situations, and in common with other manufacturers, we recommend a 66% diversity factor is applied to the MCB nominal rated current where it is intended to load the MCBs continuously (in excess of 1 hour). METHOD OF OPERATION 1 Moderate overload conditions Detection of moderate overload conditions is achieved by the use of a thermo-metal element which deflects in response to the current passing through it. The thermo-metal element moves against the trip bar releasing the trip mechanism.

2 Short circuit conditions When the current flowing through the MCB reaches a predetermined level, the solenoid directly pulls in the plunger which forcibly separates the contacts and simultaneously releases the trip mechanism. 3 Establishment of arc between fixed and moving contacts As the moving contact moves away from the fixed contact, an arc is established. The arc runs along the arc runner to the arc chamber where it is split up between the plates and extinguished. The low inertia and consequent high speed of the moving contact has a limiting effect on the flow of fault current. The rapid development of the arc, together with its accelerated extinction in the arc chamber, BS EN 60898-2 gives a typical operating time of 3.5-5 milliseconds for a type B curve MCB. CURRENT LIMITING ACTION The high speed current limiting action ensures that the MCB operates before the full prospective fault current is allowed to develop. Under fault conditions, damage can be sustained to the installation and associated equipment due to the amount of energy that passes before the current is completely interrupted. The total energy let-through depends on the value of current and the time for which it flows, and is denoted by the symbol I2t. The high speed current limiting action of MCBs ensures that the energy let-through and any subsequent damage is minimised. This reduced energy let-through assists greatly with both back-up and discrimination considerations. CURRENT LIMITING EFFECT Fault

Maximum prospective fault current

Healthy circuit current

20ms

20ms

MCBs - Technical Data

Hammer action solenoid Arc chamber


BACK-UP PROTECTION

CONSUMER UNIT MCBs

Back-up protection is required only if the prospective short circuit current at the point of installation exceeds the breaking capacity of the MCB. When providing back-up protection consideration must be given to discrimination between the MCB and fuse.

Standards Rated voltage (single pole) Tripping characteristics Short circuit rating Reference calibration temperature Terminal capacity – outgoing cable

BS EN 60898-2 : 2006 240V Type B,C 6kA 30°C 0.75 to 25mm2

CAT REF

C CURVE

RATING

NSB03 NSB06 NSB10 NSB16 NSB20 NSB25 NSB32 NSB40 NSB50

WELC06 WELC10 WELC16 WELC20 WELC32 WELC40 WELC50

3A 6A 10A 16A 20A 25A 32A 40A 50A

DISCRIMINATION It is desirable that the protective device nearest the fault should operate first. The low energy let through of modern MCBs provides better discrimination with HRC fuse back-up than is given by earlier types of MCBs. 1.13 1.45 120 60 40 20

6 4

20 10 6 4

sec .01

4 3

125 A

2

104 8

1

6

0.6 0.4

BS88 FUSE 160A

6

2

1

100 A 80 A

6A

63 A 50 A 40 A

2

4 ac

40 A 32 A 25 A 20 A 16 A 10 A

=0

1 40

In=

105 8

HW

2

Let-through I2t (amp2/sec)

Minutes

Tripping time

10

Seconds

3

0.2

35 A

2

0.1 0.06 0.04

32 A

103 4x102

0.02

6

8 103

2

3

4

6

8 104

Prospective short circuit current Ip/A 0.01

1

1.5 2

3 3

4 5 6 8 10 7 5

15 20

30

1

min melting pt (pre-arching) eg In=125A BS 88

2

max let-through I2t of MCB eg 6A

Multiple of rated current

NSB AND PSB DISTRIBUTION BOARD MCBs Standards

BSEN 60898 -2: 2006

Rated Voltage

230/400 Volts

Tripping characteristics

Type B, C and D

Short circuit rating Reference calibration temperature Terminal capacity outgoing cable

6kA and 10kA

2 HRS 1 HR

1,000

30˚C 0.75 to 25mm2 100

NSBS & PSBS RCBO (COMBINED MCB/RCD) Standards

BSEN 61009 -2: 1995 BSEN 61009 -1: 2004

Rated Voltage

230 Volts -1 2004

SP or SP with switched neutral Tripping characteristics NSBS= B,C PSBS= C Short circuit rating Reference calibration temperature Rated residual operating current Single module Two module Terminal capacity outgoing cable

6kA and 10kA

OPERATING TIME IN SECONDS

MCB & RCBO – Technical Data

38

10

1.0

30˚C 30mA Type A Type AC 0.5 to 16mm2

Unique live side busbar combi-terminal allows connection of cable up to 25mm2

0.1

Type B

Type C

Type D

0.01 0.001 1

3

5

10

20

100

Maximum neutral cable size 25mm2 SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT

1,000


IEC PUBLICATION (60479) CURVES WITH WYLEX RCD CHARACTERISTICS SUPERIMPOSED TIME/CURRENT ZONES OF EFFECT OF AC CURRENT (15–100Hz) ON PERSONS a

10,000

b

c1 c2

c3

IEC 60479

Zone Physiological effects 1 Usually no reaction effects (no danger).

5,000

2 Usually no harmful physiological effects (usually no effects). 2000

500 1

2

3

4

200

4 In addition to the effects of zone 3, probability of ventricular fibrillation increased up to 5% (Curve C2), up to 50% (Curve C3) and above 50% beyond Curve C3. Increasing with magnitude and time, pathyphysiological effects such as cardiac arrest, breathing arrest and heavy burns may occur.

Time in milliseconds

100 50

20 10 0.1

0.2 0.3 0.5

1

2

3

5

10

Body current in milliamperes (RMS) 30mA

100mA

20

30 50

100

200 300 500 1,000 2,000 3,000 5,000 10,000 mA

Typical current Limits due to body resistance at 230V

FAULT CURRENT SENSITIVITY As the equipment is fed from the mains electrical supply, in the event of an earth fault the presence of semi-conductors may result in the normal ac waveform being replaced by a non-sinusoidal fault current. In some cases the waveform may be rectified or chopped. These waveforms are said to contain a pulsating dc component which can either partially desensitise or totally disable a standard Type AC RCD. International standards IEC 61008 (RCCBs) and IEC 61009 (RCBOs) divide RCDs into two performance classes: Type AC RCDs for which tripping is ensured for residual sinusoidal alternating currents, whether suddenly applied or slowly arising.

To ensure the correct level of protection, check for the following symbols: TYPE AC normal ac sensitivity

TYPE A pulsating dc sensitivity

Type A RCDs for which tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly arising.

Wylex RCDs are available as both Type AC and Type A devices.

OPERATION

RESIDUAL TRIPPING CURRENTS

The RCD employs the current balance principle which involves the supply conductors to the load (phase and neutral) being wound onto a common transformer core to form the primary windings. Under healthy circuit conditions, the current in the phase conductor is equal to the current in the neutral, and the vector sum of the current is zero. In the event of an earth fault, an amount of current will flow to earth, creating an out of balance situation in the transformer assembly. This out of balance is detected by the secondary winding of the transformer and at a pre-determined level of out of balance will activate the trip mechanism. Single phase and neutral or three phase and neutral units (suitable for 3 or 4 wire systems) are available, the latter being suitable for balanced or unbalanced 3 phase loads. The RCD trip mechanism will operate at a residual current of between 50–100% of its rating tripping current (sensitivity).

10mA Used in special applications where additional protection against contact is essential due to the nature of the installation. 30mA Tripping current designated by the IEE Wiring Regulations to provide additional protection. 100mA Suitable for use where protection is provided to guard against firehazard, etc, rather than to provide additional protection to personnel, and where the earthing requirements need supplementing by RCD protection. 100mA time delay Suitable for use when total RCD protection is required to supplement the system earthing and where local 30mA RCDs are used to give additional protection. The time delay RCD will discriminate with the 30mA RCD.

TRANSIENT EARTH LEAKAGE CURRENTS

If using RCDs in series, discrimination can only be achieved by using Type S devices in series with Types A or AC. See chart below.

All Wylex residual current devices incorporate a high level of immunity to tripping when subjected to transient earth leakage currents. Such transients can occur when there is a significant level of capacitance to earth as can result from cable capacitance (particularly MICC) or RF filter networks. Wylex RCDs are therefore less susceptible to nuisance tripping due to transient earth leakage currents.

300mA For use in large installations where plant and equipment protection are the main considerations and high levels of earth leakage are experienced.

BSEN61008-1:1995 RCBOs BSEN61009-1:1995 l Rated Residual Current (In) RCD to Trip between 50%-100% In

1x In

Tripping times 2x In

5x In

500Amps

Scope

Standard A & AC

Any Value, eg 10, 30, 100mA

300ms

150ms

40ms

40ms

Maximum-Trip

Time Delay (S)

Greater than 30mA, eg 100mA

500ms 130ms

200ms 60ms

150ms 50ms

150ms 40ms

Maximum-Trip Minimum-Non Trip

Type of RCD

Lifeline Range RCDs – Technical Data

3 Usually no organic damage to be expected. Likelihood of muscular contraction and difficulty of breathing, reversible disturbances of formation and conduction of impulses in the heart, and transient cardiac arrest without ventricular fibrillation increases with current magnitude and time.

1000

39


THE 17th EDITION WIRING REGULATIONS Under the latest 17th edition wiring regulations certain installations Extracts from the regulations and examples of these ‘newly’ protected require “additional protection” on many MCB circuits that were not RCD circuits are given in the summary table below. previously protected by the supplementary use of 30mA RCDs. SUMMARY TABLE REGULATIONS

40 RCBOs RCDs - Application Data

411.3.3 *

701.411.3.3 **

522.6.6 *** 522.6.7 522.6.8 and 560.7.1*****

ADDITIONAL PROTECTION

RELATING TO :

EXAMPLES

Sockets up to 20A rating for general use by ordinary persons

Upstairs Sockets Downstairs Sockets Kitchen Sockets Cooker outlet with integral 13A socket Garage Sockets Plus any other sockets up to 20A rated

All Circuits in a room with a fixed bath or shower

Shower circuit Lighting circuit Heating circuit Ventilation circuit Shaver Socket Plus Other circuits

All circuits buried in a wall or partition at less than 50mm and without mechanical protection

Downstairs Lighting Upstairs Lighting Immersion heater Smoke Alarms Burglar Alarm (Safety service) Plus any other circuits

30mA RCD Taking into account 3.14.1 3.14.2 ****

30mA RCDs Taking into account 3.14.1 **** 3.14.2 ****

30mA RCD Taking into account 3.14.1 3.14.2

Note: Each circuit may have more than one reason for additional protection by 30mA RCD eg: firstly because of the equipment ie: a socket outlet and secondly because of the cable installation method. Additional protection is provided as additional protection. It does not obviate the need for circuit protection by circuit breakers or fuses. * Regulation 411.3.3 socket outlets with a rated current not exceeding 20A that are for general use by ordinary persons (exemption may be permitted). ** Regulation 701.411.3.3 Additional protection shall be provided for all circuits of the location by use of one or more 30mA RCD. *** Regulations 522.6.6 522.6.7 522.6.8 cables concealed in a wall or partition at less than 50mm depth and without earthed mechanical protection e.g. conduit. **** Regulation 314.1 Every installation shall be divided into circuits as necessary to avoid danger and inconvenience in the event of a fault, take account of danger that may arise from the failure of a single circuit such as a lighting circuit, reduce the possibility of unwanted tripping of RCDs etc. **** Regulation 314.2 Separate circuits to be provided for parts of the installation that need to be separately controlled in such a way that those circuits are not affected by the failure of other circuits. ***** Regulation 560.7.1 Chapter 56 circuits for safety services shall be independent of other circuits. In addition Chapter 51 requires designers/installers to take account of all relevant British Standards and manufacturers instructions. For example BS5839 Part 6 is the British Standard for fire detection and alarm systems in dwellings. It states that power supplies to Grade D smoke alarms should be an independent circuit at the consumer unit, or a separately electrically protected local lighting circuit. British Standards and IEE regulations are subject to change and amendments. This guide to Wylex conssumer units is not a substitute for the regulations which should always be used for all types of ellectrical installation design and installation work.

CONSUMER UNIT SELECTION GUIDE ALL INDEPENDENT CIRCUITS

HALF INDEPENDENT CIRCUITS

Main Switch

Split Load

SOME INDEPENDENT CIRCUITS

NO INDEPENDENT CIRCUITS

High Integrity

Dual RCD

30mA Earth leakage Protection


INSULATED CONSUMER UNITS

B

DIMENSIONS A=160mm(6.3"),B=117mm(4.6"),C=102mm(4") 4 MODULE

DIMENSIONS A=230mm(9"),B=340mm(13.5"),C=120mm(4.7") 16 MODULE

NH204/40 NH204/63 NHRS204/40 NHRS204/63

NH1404 NHRS1404 NHRM1404 NHSTM3904 NHSTM4804 NHSTM5704 NHSTM6604 NHIIX3904 NHIIX4804 NHSTM7504 NHSTM8404 NHSTM9304 NHRS3904 NHRS4804 NHRS6604 NHRS5704 NHRS7504 NHRS8404 NHRS12SL

NHRM204/40 NHRM204/63 NH4ED4

A DIMENSIONS A=230mm(9"),B=187mm(7.5"),C=120mm(4.7") 7 MODULE

C

NHRM504 NHTM504 NH7ED4

DIMENSIONS A=230mm(9"),B=239mm(9.6"),C=120mm(4.7") 10 MODULE

NH804 NHRS804 NHRM804 NHSTM2404 NHSTM3304 NHSTM4204 NHRS2404 NHIIX2404 NHRS6SL

NHRS3304 NHRS4204 NH504+3 NHRS504+3 NHTM804 NH10ED4 NHIIX3304

DIMENSIONS A=230mm(9"),B=435mm(17.3"),C=120mm(4.7") 21 MODULE

DIMENSIONS A=230mm(9"),B=290mm(11.5"),C=120mm(4.7") 13 MODULE

NH1104 NHRS1104 NHRM1104 NHSTM3604 NHSTM4504 NHSTM5404 NHSTM6304 NHRS5404 NHRS4504

NHRS9SL NHRS3604 NHRS6304 NHIIX5404 NHIIX4504 NH804+3 NHRS804+3 NHTM1104 NH13ED4

41

NHRS23204 NHRS7SSLHI

NH1904 NHRS1904 NHRM1904 NHSTM12504 NHSTM11604 NHSTM8904 NHSTM9804 NHSTM10704 NHSTM71004 NHSTM61104 NHSTM51204 NHRS12504 NHRS11604 NHRS10704 NHRS61104 NHRS17SL NHRS71004

NHRS9804 NHRS8904 NHRS51204 NHIIX9804 NHIIX8904 NHRSX8904 NHRSX9804 NHRS6504+6 NHRS5604+6 NHRS7704+3 NHRS8604+3 NHRS6804+3 NHTM1904 NH21ED4 NHISS8704 NHIIX11604 NHIIX51204

NHISS15SL NHRS15SSLHI NHRS76204 NHRS66304 NHRS46504 NHRS55504 NHRS45604

METAL CONSUMER UNITS

D

230

146

121 90

DIMENSIONS 209(H) 117(W) 90(D) 120(D) 4 MODULE

DIMENSIONS D=353mm(13.5"), E=260mm(10.2") 16 MODULE

NH206/40 NH206/63

NH1406 NHRS1106+3 NHRS4806 NHRS1406 NHRM1106+3 NHRS6606 NHRS10SSLMHI NHRM1406 NH806+6 NHRS7506

DIMENSIONS D=188mm(7.4"), E=107mm(4.2") 7 MODULE

NH506 NHTM506 NH7ED6

E

NHRS206/40 NHRS206/63

NHRS506 NHRM506

DIMENSIONS D=241mm(9.5"), E=160mm(6.3") 10 MODULE

NHRM806 NH10ED6 NHRS2406 NHRS3306 NHRS4206 NHRS6SLM

NH806 NHRS806 NHSTM2406 NHSTM3306 NHTM806

NHRS806+3 NHRS1106 NHRS806+3 NHRS5406 NH13ED6 NHSTM4506 NHRS6306 NHTM1106 NHIIX3306

NHISS10SLM NHRS44206 NHRS43306 NHRS33406

DIMENSIONS D=438mm(17.2"), E=235.7mm(10.1") 21 MODULE

NH1906 NHRS61106 NHRS9806 NHRS17SLM NHSTM9806 NH21ED6 NHSTM8906

DIMENSIONS D=292mm(11.5"), E=210mm(8.3") 13 MODULE

NHRM1106 NHSTM3606 NH1106 NHRS4506 NHSTM5406 NH806+3 NHRS5406 NHRS9SLM NHIIX2406

NHSTM6606 NHRS3906 NHSTM7506 NHRM806+6 NHTM1406 NHRS12SLM NH16ED6 NH1106+3 NHSTM8406 NHISS5506

NHRS23206 NHRS7SSLMHI

NHRS1906 NHRS8906 NHSTM71006 NHSTM9806 NHRS5606+6 NHTM1906 NHIIX51206 NHIIX11606

NHISS8706 NHISS15SLM NHRS76206 NHRS66306 NHRS46506 NHRS55506 NHRS45606 NHRS15SSLMHI

NH Range Dimensions

NH504 NHRS504

NHRS9304 NHIIX7504 NHIIX6604 NHIIX5704 NHRSX5704 NHRSX6604 NHRSX7504 NHTM1404 NH804+6 NH1104+3 NHRS804+6 NHRS1104+3 NH16ED4 NHISS5504 NHISS10SL NHRS10SSLHI NHRS44204 NHRS43304 NHRS33404


DUPLEX METAL

F

127 94

DIMENSIONS F=343mm(13.5"), G=260mm(10.2") 16 MODULE

NHDIS88 NHDIIX88 NHDISX88

NHDIS1414 NHDIIX1414

NHDRS24HI NHDRS26SSLHI

NHDISX1414

NHDISS1214

NHDRS12HI NHDRS14SSLHI

500

DIMENSIONS F=292mm(11.5"), G=210mm(8.3") 13 MODULE

302

NH Range Dimensions

42

DIMENSIONS F=241mm(9.5"), G=160mm(6.3") 10 MODULE

NHDIS1111 NHDIIX1111

NHDRS18HI NHDRS20SSLHI

NHDISX1111

NHDISS119

G

SKELETON DIMENSIONS A=333mm(13.2"), B=165mm(6.5"), C=90mm(3.5”) D=230mm(9”)

A

D

B

FALNHRS8SSL FALNHISS4606 FALNHRS10SL

FALNHISS5506 FALNHISS10SL FALNH806

DIMENSIONS A=444mm(17.5"), B=165mm(6.5"), C=90mm(3.5”) D=230mm(9”)

Standards

C

FALNHRS13SSL FALNHISS15SL FALNHRS55506 FALNHRS76206 FALN1206

FALNHISS8706 FALNHRS46506 FALNHRS66306 FALNHRS15SL FALNH1706

STANDARDS Consumer units Designed to BS5486 Part 13: 1989 Factory Built Assemblies BSEN60439-3 when fully assembled. Degree of protection IP2X to BS EN60529. Switches BS5419. Double pole 240V 50Hz. Category of duty AC21 or BS EN 60947-3. RCDs 30mA BS EN 61008. RCBOs 30mA BS EN 61009. MCBs B,C,D Switching Curve BS EN 60898.

DIMENSIONS F=430mm(17.2"), G=235mm(10.1") 21 MODULE

NHDIS1919 NHDIIX1919 NHDISX1919

NHDRS34HI NHDRS36SSLHI


STANDARD RANGE A

INSULATED-MAIN SWITCH ISOLATOR CAT REF

B FUSES

DIMENSIONS B

C

104

98

121

68

204 304

125

120

70

190

155

95

404 604

190

155

95

272

186

103

804 108/160/160C

323

186

103

143

178

99

METAL-45A AND 60A SWITCHFUSES

METAL - MAIN SWITCH ISOLATOR

A

CAT REF

206 306 406 606

B

43

CAT REF

A

DIMENSIONS B

C

140

131

93

210

153

99

210

153

99

293

210

104

106 108M/160CM

A

DIMENSIONS B

C

112

131

80

172

242

98

METAL-100A DOUBLE POLE SWITCHFUSE CAT REF

C

A

DIMENSIONS B

C

110M 110M/80

178

305

76

178

305

76

110M/63

178

305

76

ENCLOSURES

CAT REF

DIMENSIONS IP RATING A

ESE2 ESE2L WBE3 ESI4 ESM6 ESM7 ESE4 WBE4 ESM11 ESM13 ESM8

B

A

IP40 IP20 IP65 IP40 IP40 IP54 IP20 IP65 IP54 IP54 IP40

60 60 85 100 90 90 77 110 120 137 120

B 153 140 160 150 225 225 140 160 225 318 225

ISOLATORS CAT REF A

B

A

C

DIMENSIONS B C

Terminal Capacity

CAT REF A

DIMENSIONS B C

Terminal Capacity

832A

62

76

30

10

921X

72

45

48

10

860A

57

79

29

25

921E

114

133

61

10

810X

53

94

77

35

REC2S

78

150

65

50

810A

58

170

77

35

REC2

100

150

65

50

810E

76

203

76

35

REC3

100

150

65

50

REC4

100

150

65

50

Standard Range - Dimensions

C

A


TECHNICAL INFORMATION Sheet Steel Enclosure RATING IN AMPS

20A

32A

40A

63A

63A*

100A

125A

800

800

800

800

800

800

800

Dielectric Strength (kV) 50 Hz 1min

3

3

3

3

3

3

3

Shock Resistance Uimp (kV)

8

8

8

8

8

8

8

Rated Insulation Voltage Ui (V)

NH Switch Disconnectors

44

OPERATIONAL CURRENT IE (A) 415 V AC - AC21A / AC21B

20

32

40

63

80

100

125

AC22A / AC22B

20

32

40

63

80

100

125

AC23A / AC23B

20

32

40

63

80

80

80

500 V AC - AC21A / AC21B

20

32

40

63

80

100

125

AC22A / AC22B

20

32

40

63

80

100

125

AC23A / AC23B

20

32

40

40

63

63

63

690 V AC - AC20A / AC20B

20

32

40

63

80

100

125

AC21A / AC21B

20

32

40

63

80

100

125

AC22A / AC22B

20

32

40

63

80

100

100

AC23A / AC23B

20

25

25

25

50

50

50 40

MOTOR POWER (KW) AC 23 415 V AC

7.5

11

11

15

18.5

37

500 V AC

7.5

11

15

18.5

22

37

37

690 V AC

11

11

18.5

18.5

25

30

30

FUSE TYPES TO BS88 OVERLOAD CAPACITY Fuse rating gG

20

32

40

63/40

63

100

125

Short circuit current with fuses (kA Rms)

50

50

50

20/50

50

20

15

Asymmetric short time rating current (kA peak)

6

6

6

9

9

9

9

Admissible short time current 1 s. (kA Rms)

1.26

1.26

1.26

1.5

1.5

1.5

1.5

MAKING & BREAKING CHARACTERISTICS Breaking capacity (A Rms) 415 V AC 23 A Making capacity (A Rms) 415 V AC 23 A

160

256

320

504

504

640

640

200

320

400

630

630

800

800

WITHSTAND Mechanical (number of operations) x 1000 Electrical (number of operations at 415V AC 23A) x 1000

100

100

100

100

30

30

30

3

3

3

3

1.5

1.5

1.5

16

16

16

16

50

50

50

WEIGHT (KG) 3 pole

2.00

2.00

2.00

2.00

2.50

2.50

2.50

4 pole

2.00

2.00

2.00

2.00

2.50

2.50

2.50

CONNECTION Maximum Cu cable section (mm2) Ith using stranded cable (mm2)

DIMENSIONS D

A

B

CAT REF

NHSW320 NHSW332 NHSW340 NHSW363 NHSW363X NHSW3100 NHSW3125

C

BOX SIZE

HEIGHT (A)

WIDTH (B)

DEPTH (C)

TOTAL DEPTH (D)

1

220mm

158mm

136mm

172.5mm

1

220mm

158mm

136mm

172.5mm

1

220mm

158mm

136mm

172.5mm

1

220mm

158mm

136mm

172.5mm

2

325mm

158mm

136mm

172.5mm

2

325mm

158mm

136mm

172.5mm

2

325mm

158mm

136mm

172.5mm


STANDARDS

CONSTRUCTION

Switches

Wylex NH MCB distribution board enclosures are fabricated in heavy gauge steel and are rust protected and highly resistant to both weathering and mechanical damage. Incorporated in the distribution boards are multi-terminal dual earth and neutral bars. They are designed for ease of installation and have ample wiring space.

Multipole: 415V 50Hz BSEN 60947-3 1992 Category of duty AC22A MCBs BSEN 60898: 1991 Type B, C and D Short circuit rating 6 & 10kA Distribution Boards BS EN 60439-3 Degree of For indoor use only Protection. (IP3X)

A

*144mm

Enclosure Top View

107mm

Cover & Door Top View

37mm

125A DISTRIBUTION BOARDS

250A DISTRIBUTION BOARDS

CAT REF

DIMENSION A mm

NHTN4 NHTN6 NHTN8 NHTN12 NHTN16 NHTN20 NHTN24

488.4 569.4 650.4 812.4 893.4 974.4 1136.4

Depth 165mm- all sizes

DIMENSION A mm

NHTN2540 NHTN2560 NHTN2580 NHTN25120 NHTN25160 NHTN25200 NHTN25240

650 815 815 895 975 1085 1190

NHTN METER PACKS CAT REF

* including fixing feet which are 3.5mm high

CAT REF mm A

C

210 210 210 210 210 210

C

188 242 293 343 394 394

105 105 105 105 105 105

245 245

C mm

430 430

144 144

NHAB DIN ACCESSORY BOXES CAT REF

DIN MODULES

DIMENSION A mm

18 18 36 54 72 90

240 240 240 387 544 756 856

NHEB NHEB/DIN NHAB NHAB2 NHAB3 NHAB4 NHAB5

200A-250A PANEL BOARDS

630

MODULAR HEIGHT

HEIGHT (mm)

A(mm)

902 902 1060 902 902 1060

420 420 420 420 420 420

HEIGHT (mm)

A(mm)

CAT REF

1060 1060 1317 1375 1060 1060 1317 1375

577.5 577.5 577.5 577.5 577.5 577.5 577.5 577.5

NHPB6SW400 NHPB8SW400 NHPB12SW400 NHPB16SW400 NHPB6CB400 NHPB8CB400 NHPB12CB400 NHPB16CB400

17 17 20 17 17 20

Height

CAT REF

NHPB6SW250 NHPB8SW250 NHPB12SW250 NHPB6CB200 NHPB8CB200 NHPB12CB200

400A PANEL BOARDS A

164.5

Top View

Depth 165mm - all sizes 630

MODULAR HEIGHT

20 20 23 26 20 20 23 26

NH125 MODULAR MCB/DIN ENCLOSURES MODULAR HEIGHT

Height

HEIGHT (mm)

CAT REF

4

210

TO ORDER

8

420

TO ORDER

NH 125 G FRAME METER PACKS CAT REF 164.5

Top View

NHG250MP NHG400MP

HEIGHT (mm)

WIDTH (mm)

DEPTH (mm)

210 210

630 630

165 165

NHG125 MCCB Panelboards

NHSPN0051 NHSPN0081 NHSPN00111 NHSPN00141 NHSPN00161 NHSPN00191

DIMENSIONS A mm B mm

DIMENSIONS A mm B mm

NHTN125MP NHTN250MP

SINGLE PHASE DISTRIBUTION BOARDS

B

CAT REF

45 NH MCB Distribution Boards

430mm

The WYLEX PSB miniature circuit breakers are rated at 10kA and are of the fault limiting type.

When a short circuit occurs, the current operates a solenoid which trips the mechanism and forces the moving contact away from the fixed contact. The arc generated is forced into an arcing chamber which incorporates splitter plates, to divide and cool it, reducing the total operating time to less than 5ms, This high speed operation substantially reduces the ‘let through’ energy (I2 t) keeping additional damage at the point of the fault to a minimum. Additionally this allows discrimination with HRC fuses at high fault levels.


NHG MCCBs TECHNICAL SPECIFICATION 7

10

NHG MCCB SPECIFICATION • Specification

6

46

10

BSEN60947-2

• Current Range

16 – 125A

• Ue Rated Operation Voltage

240V SP 415V TP

• Ui Rated Insulation Voltage

500V AC

• Rated Frequency

50/60Hz

5

10

4

10 1,000

10,000

100,000

• Release

Thermal Magnetic

• Adjustment

None

• Ambient Range

-20°C to 55°C

• Humidity Range

0 – 90%

• Weight

SP - 0.4kg TP - 0.95kg

• Mechanical Duration

8000 operations

PROSPECTIVE CURRENT

SHORT CIRCUIT BREAKING CAPACITY

AUXILIARY EQUIPMENT

Type Ue

NHG MCCBs Auxiliary Contact Ratings (A) Voltage Resistive Tungsten Load Inductive

220 V 380 V 415 V Ics = 50% Icu

GB Icu SP/TP 30 16 16

GN Icu TP 30 25 25

AC 125 250 DC 30 50 125

INSTANTANEOUS TRIP BANDS 25 – 32A 40 – 80A 100 – 125A Non-adjustable

SP 500A 800A 1250A

TP 400A 600A 600A ±10%

Load (A)

NC (A)

NO (A)

Load (A)

3 3

0.5 0.5

0.5 0.5

3 3

3 1 0.5

3 0.7 0.4

0.5 0.7 0.4

3 1 0.05

TERMINALS Front-connected clamps – 25A to 125A – 70mm2 cable – 10mm strip

MAXIMUM EARTH LOOP IMPEDANCES FOR TRIPLE POLE MCCBS Zs (ohms) for Uo = 240V~ Current Rating (A) 16 /25 32 40 50 63 0.4 Seconds Disconnection Time 0.17Ω 0.17Ω 0.13Ω 0.13Ω 0.13Ω 5.00 Seconds Disconnection Time 0.96Ω 0.75Ω 0.60Ω 0.48Ω 0.38Ω

80

100

125

0.13Ω 0.30Ω

0.13Ω 0.24Ω

0.13Ω 0.19Ω

MAXIMUM EARTH LOOP IMPEDANCES FOR SINGLE POLE MCCBS Zs (ohms) for Uo = 240V~ Current Rating (A) 16 /25 32 40 50 63 0.4 Seconds Disconnection Time 0.43Ω 0.43Ω 0.27Ω 0.27Ω 0.27Ω 5.00 Seconds Disconnection Time 0.96Ω 0.75Ω 0.60Ω 0.48Ω 0.38Ω

80 0.27Ω 0.30Ω

100 0.17Ω 0.24Ω

125 0.17Ω 0.19Ω

Interphase Barriers 78.50

Terminals Suitable for 10mm Strip or 70mm2 Cable

33.50

30.00

26.25 26.25 Phase Ctrs Phase Ctrs 26.00 Use M3 Fasteners

94.00 Fixing Ctrs

120.00

74.00 Fixing Ctrs

I 120.00

NHG Panelboard MCCBs

2

It

T

O R

Use M4 Fasteners 19.50 Fixing Ctrs

26.25 Fixing Ctrs

70.50 77.50 83.50 97.00 max

Operating Lever Positions 'I' Breaker Closed 'O' Breaker Open 'T' Breaker Tripped by Release 'R' Reset Positions from Tripped


NH J FRAME MCCBs TECHNICAL SPECIFICATION 108

NHJ FRAME SPECIFICATION • Specification

BSEN60947-2

• Current Range

16 – 200A

107

• Ue Rated Operation Voltage

240V SP 415V TP

• Ui Rated Insulation Voltage

660V AC

• Rated Frequency

50/60Hz

47

• Release

Thermal Magnetic

• Thermal Adjustment

0.7 - 1.0 x Rated Current

• Instantaneous Adjustment

Non - Adjustable

105

• Short Circuit Breaking Capacity

Icu at 415V = 25kA, Ics =75% Icu

• Ambient Range

-20°C to 55°C

• Humidity Range

0 – 90%

• Weight

SP - 0.7kg TP - 1.8kg TP & Sw N - 2.4kg

104 1000

10000

100000

PROSPECTIVE CURRENT

OPTIONS

SHORT CIRCUIT BREAKING CAPACITY

TERMINALS

• Padlocking

Ue 220 V 380 V 415 V Ics = 75% Icu

Front-connected clamps – 25A to 200A – 120mm2 solid /150mm2 stranded

• Terminal Shrouds

Icu 50kA 32kA 25kA

INSTANTANEOUS TRIP BANDS 25 – 63A 80 – 125A 160 – 200A

400A 800A 1600A

J FRAME DIMENSIONS

400A 768mm

Side Extension Box

G

A

A

A Out Going Height B Incomer Height C Cabling Room D Depth E Depth of Door

4 WAY

8 WAY

12 WAY

16 WAY

576mm 768mm 460mm 265mm 32mm

768mm 768mm 460mm 265mm 32mm

960mm 768mm 460mm 265mm 32mm

1162mm 768mm 460mm 265mm 32mm

4 WAY

8 WAY

12 WAY

16 WAY

576mm 768mm 460mm 265mm 32mm

768mm 768mm 460mm 265mm 32mm

960mm 768mm 460mm 265mm 32mm

1162mm 768mm 460mm 265mm 32mm

630A

A Out Going Height B Incomer Height C Cabling Room D Depth E Depth of Door

Incomer

B

C

800A Bottom Extension Box

H

Top View

D

Cover & Door Top View

A Out Going Height B Incomer Height C Cabling Room D Depth E Depth of Door

4 WAY

8 WAY

12 WAY

16 WAY

576mm 960mm 440mm 265mm 32mm

768mm 960mm 440mm 265mm 32mm

960mm 960mm 440mm 265mm 32mm

1162mm 960mm 440mm 265mm 32mm

576mm 288mm 265mm

768mm 288mm 265mm

960mm 288mm 265mm

1162mm 288mm 265mm

576mm 265mm

576mm 265mm

576mm 265mm

E

SIDE EXTENSION BOXES A Out Going Height G Width D Depth

BOTTOM EXTENSION BOXES H Height (3 Mod) D Depth

576mm 265mm

NH200 Panelboards

106 I2t


J FRAME MCCB s - TYPICAL TIME / CURRENT CHARACTERISTICS

1000

100

100 TIME (seconds)

1000

1

1

0.1

0.1

0.01

0.01 100 1000 CURRENT (Amperes)

10

10000

100 1000 CURRENT (Amperes)

10000

1000

100

100 TIME (seconds)

1000

TIME (seconds)

32A

J 32-200 AMP

160A

63A

25A

J 25-160 AMP

10000

200A

10

10000

125A

10

10

80A

TIME (seconds)

50A

20A

10000

10

10

1

1

0.1

0.1

0.01

0.01 10

100 1000 CURRENT (Amperes)

10

10000

100 1000 CURRENT (Amperes)

WYLEX NH J FRAME MAXIMUM EARTH LOOP IMPEDANCES Zs (ohms) for Uo = 240V~ Current Rating (A) 16/20/25 32 40 50 63 80 0.4 Seconds Disconnection Time 0.500 ⍀ 0.500 ⍀ 0.500 ⍀ 0.500 ⍀ 0.500 ⍀ 0.250 ⍀ 5.00 Seconds Disconnection Time 0.500 ⍀ 0.500 ⍀ 0.500 ⍀ 0.500 ⍀ 0.500 ⍀ 0.250 ⍀

31

100

100 0.250 ⍀ 0.250 ⍀

135

125 0.250 ⍀ 0.250 ⍀

10000

160 0.125 ⍀ 0.125 ⍀

200 0.125 ⍀ 0.125 ⍀

77

35 Position of Terminal Shroud

25

92

154

25

35

178

NH200 Panelboards

48

40A

16A

10000

J 20-125 AMP

100A

J 16-100 AMP

35

105

140

83

29


CONTACTORS TYPE

POWER (W) C(yF)

Incandescent Lamps

Flourescent Lamps uncorrected and Series correction

Flourescent Lamps Parallel correction

Flourescent Lamps with electronic ballast units (EVG)

High- pressure Mercury- vapour Lamps uncorrected

High Pressure Mercury- vapour Lamps Parallel correction

Halogen metal - vapour Lamps uncorrected

Halogen metal - vapour Lamps Parallel correction

High- pressure Sodium - vapour Lamps uncorrected

High- pressure Sodium - vapour Lamps parallel

Low - pressure Sodium - vapour Lamps uncorrected

Low - pressure Sodium - vapour Lamps Parallel correction

4.5 4.5 4.5 7 7 8 10 18 25 45 60 6 12 20 33 35 95 148 20 33 48 106 5 20 20 26 45 40

0.26 0.43 0.87 2.17 4.35 0.37 0.35 0.43 0.67 0.11 0.14 0.22 0.35 0.12 0.15 0.2 0.32 0.09 0.16 0.25 0.17 0.32 0.49 0.61 0.8 1.15 2.15 3.25 5.4 7.5 0.28 0.41 0.65 1.22 1.95 3.45 4.8 0.53 1 1.8 3 3.5 9.5 16.5 0.25 0.45 0.75 1.5 2.5 5.8 11.5 1.8 3 4.7 10.3 0.83 1.5 2.4 6.3 0.35 1.5 1.5 2.4 3.5 3.3 0.35 0.31 0.42 0.63 0.94 1.16

Thermal Rating per Pole MESB- 20NC MESB- 24NC MESB - 40NC -

MESB - 20NO MESB - 24NO MESB - 40NO MESB - 63NO

20 24 40 63

MESB- 20NC MESB- 20NO

2 2 2 2

23 14 7 3 1 22 22 17 14 x 30 x 24 x 17 x 10 7 7 7 4 25 15 14 12 7 7 14 10 7 4 2 1 1 4 4 3 1 1 18 10 5 3 3 1 5 2 1 5 3 2 1 22 7 7 4 3 3 6 1 1 1 -

MESB- 24NC MESB- 24NO

2 2 2 2

29 16 8 3 1 24 24 20 17 x 40 x 31 x 24 x 14 8 8 8 5 35 20 19 17 10 9 18 13 9 5 3 2 1 5 5 4 2 1 22 12 7 4 3 1 6 3 1 1 1 6 4 2 1 1 1 27 9 9 5 4 4 7 1 1 1 -

MESB- 40NC MESB -40NO

MESB -63NC MESB -63NO

65 40 20 8 4 90 90 65 45 2 x 100 2 x 78 2 x 65 2 x 40 48 48 48 31 100 52 50 50 26 25 38 29 20 10 7 4 3 31 27 22 12 9 5 4 43 23 12 7 6 2 1 36 18 11 6 6 2 1 17 10 6 3 11 6 4 2 71 23 23 14 10 10 44 11 11 8 4 5

85 50 25 10 5 140 140 95 70 2 x 150 2 x 118 2 x 95 2 x 60 73 73 73 47 140 75 72 70 38 36 55 42 29 15 10 6 4 47 41 33 18 13 7 5 60 32 18 10 9 3 1 50 25 15 9 8 3 2 22 13 8 3 16 10 6 3 90 30 30 19 13 13 66 16 16 12 7 8

Motor Rating AC3 (kW) 230V 400V 1.3 2.2 4 5.5 11 8.5 15

AC Ratings in accordance with BSEN60947 -5 -1 and BSEN 60947- 4- 1 Deffinitions: AC1 Primarily Resistive Load but may be slightly inductive AC3 Medium-Starting-duty motors, starting and switching off of squirrel-cage motors

49 MESB Contactors

Flourescent Lamps lead- lag circuit

60 100 200 500 1000 18 24 36 58 18 24 36 58 18 24 36 58 1 x 18 1 x 36 1 x 58 2 x 18 2 x 36 2 x 58 50 80 125 250 400 700 1000 50 80 125 250 400 700 1000 35 70 150 250 400 1000 2000 35 70 150 250 400 1000 2000 150 250 400 1000 150 250 400 1000 18 35 55 90 135 180 18 35 55 90 135 180

I(A)


DIMENSION DETAILS

D inc handle W

D Spreader Box

NH Fuse Combination Units

50

W

D

H

H

HOUSED UNIT DIMENSIONS (mm) HOUSED UNIT

H

W

D

D inc. handle

20-32A

220

210

135

200

H

W

D

63-100A

420

262

188

258

SPREADER BOX

105

262

183

125-200A

525

315

240

273

SPREADER BOX

105

315

210

315-400A

735

420

240

305

SPREADER BOX

210

420

240

630-800A

850

620

293

355

SPREADER BOX

210

620

262

Ø20

Ø25

Ø25

Ø20

Ø32

Ø40

SPECIFICATION ●

BSEN947-3

Range of ratings 20A-400A

Pole configurations SP & N, and TP & N

Voltage rating 415V ac

Frequency rating 50/60 Hz

Fuse type BS88

20/32A Gland Plates

All Dimensions in mm

63-100A Gland Plates

TECHNICAL DATA 20–32A

63A

100A

125A

160A

200A

315A

400A

630

800

10,000

10,000

10,000

10,000

10,000

10,000

10,000

10,000

8,000

8,000

80

80

80

80

80

80

80

80

80

80

Ratings

A kW

A kW

A kW

A kW

A kW

A kW

A kW

A kW

A kW

A kW

415V le/pe

32 15

63 30

100 55

125 75

160 90

200 110

315 160

400 220

630 353

800 450

-

NHCIL2

NHCIL3

NHCIL3

NHCIL3

NHCIL3

NHCIL4

NHCIL4

NHCIL5

NHCIL5

Mechanical Endurance Fused s/c Current kA RMS

Isolator links

FUSE COMPARISON DATA CURRENT RATING

BS 88 REFERENCE

LAWSON

GEC

A1

NIT

NIT

NITD

63A

A3, A2

TIS

TIS

BAO

100A

A4

TCP

TCP

CEO

125A

A4

CTFP

TCP

DEO

160A

A4

CTFP

TCP

DEO

200A

A4

CTFP

TCP

DEO

315A

B3

TKF

TKF

ED

20/32A

BUSSMAN

400A

B4, B3, B2,B1

TFM

TFM

ED

630A

C1, C2

TTM, TM

TTM, TM

FF, EF

800A

C1, C2, C3

TLM, TTM, TM

TLM, TTM, TM

GF, FF, EF


Page No 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 35 35 29 29 29 29 29 29 29 29 29 29 29 29 29 9, 29 9, 29 9, 29 9, 29 9, 29 9, 29 9, 29 9, 29 33 33 33 33 33 33 33 33 33 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 29 29 29 29

List No LFL45 LFL60 LFL63 LFL80 M10 MCBLDX ME232-230 MESB-20NC MESB-20NO MESB-24NC MESB-24NO MESB-40NC MESB-40NO MESB-63NO MTS12/1 MTS6/1 MTS8 MTS8/1 NH00 NH00PP NH1004IP NH10ED4 NH10ED6 NH1104 NH1104+3 NH1106 NH1106+3 NH13CBKIT NH13ED4 NH13ED6 NH1404 NH1406 NH16ED4 NH16ED6 NH18BB1 NH1904 NH1906 NH200TPSW NH204/40 NH204/63 NH206/40 NH206/63 NH21ED4 NH21ED6 NH250DC NH250TPSW NH304IP NH4ED4 NH4ED6 NH4PINKIT NH504 NH504+3 NH506 NH506+3 NH704IP NH7ED4 NH7ED6 NH804 NH804+3 NH804+6 NH806 NH806+3 NH806+6 NHAB NHAB2 NHAB3 NHAB4 NHAB5 NHB1PP NHBBTOK NHCBDK11

Page No 29 29 29 29 29 9, 13, 15 9 15 9, 15 15 9, 15 15 9, 15 9, 15 9 9 9 9 9, 13, 15 9, 15 5 33 33 3 3 6 6 9 33 33 3 6 33 33 13, 15, 19 3 6 13 3 3 6 6 33 33 13 13 5 33 33 13 3 3 6 6 5 33 33 3 3 3 6 6 6 13 13 13 13 13 9, 13, 15 13, 15 18

List No NHCBDK12 NHCBDK15 NHCEKIT NHCEKIT20 NHCIL2 NHCIL3 NHCIL4 NHCIL5 NHCSB NHCSB2 NHCSB3 NHCSB4 NHCSB5 NHDIS1919 NHDISS119 NHDISS1214 NHDRS12HI NHDRS18HI NHDRS24HI NHDRS34HI NHDRS14SSLHI NHDRS20SSLHI NHDRS26SSLHI NHDRS36SSLHI NHDIIX1111 NHDIIX1414 NHDIIX1919 NHDIIX88 NHDIS1111 NHDIS1414 NHDIS88 NHDISX1111 NHDISX1414 NHDISX1919 NHDISX88 NHDPDC NHEB NHEB/DIN NHEP11 NHET25 NHFHDK17 NHFHDK20 NHG13DB NHG250MP NHG400MP NHGAB NHGPCB1001 NHGPCB1003 NHGPCB1251 NHGPCB1253 NHGPCB161 NHGPCB163 NHGPCB251 NHGPCB253 NHGPCB321 NHGPCB323 NHGPCB401 NHGPCB403 NHGPCB501 NHGPCB503 NHGPCB631 NHGPCB633 NHGPCB801 NHGPCB803 NHIIX11604 NHIIX11606 NHIIX2404 NHIIX2406 NHIIX3304 NHIIX3306 NHIIX3904

Page No 18 18 13, 15 13, 15 25 25 25 25 17, 18 25 25 25 25 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 13 13 13 13, 15 9 17 17, 18 17, 18 17 18 17, 18 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 5 7 5 7 5 7 5

List No NHIIX4504 NHIIX4506 NHIIX4804 NHIIX51204 NHIIX51206 NHIIX5404 NHIIX5406 NHIIX5704 NHIIX5706 NHIIX6604 NHIIX6606 NHIIX7504 NHIIX7506 NHIIX8904 NHIIX8906 NHIIX9804 NHIIX9806 NHISS3404 NHISS3406 NHISS4604 NHISS4606 NHISS5504 NHISS5506 NHISS8704 NHISS8706 NHISS10SL NHISS15SL NHISS10SLM NHISS15SLM NHJ00 NHJCSB2 NHJCSB3 NHJCSB4 NHJCSB5 NHJCSB6 NHJCW3 NHJCW4 NHJCW5 NHJCW6 NHJD03 NHJD04 NHJD05 NHJD06 NHJPCB1001 NHJPCB1003 NHJPCB1251 NHJPCB1253 NHJPCB1601 NHJPCB1603 NHJPCB161 NHJPCB163 NHJPCB2001 NHJPCB2003 NHJPCB251 NHJPCB253 NHJPCB321 NHJPCB323 NHJPCB401 NHJPCB403 NHJPCB501 NHJPCB503 NHJPCB631 NHJPCB633 NHJPCB801 NHJPCB803 NHMSL NHPB12CB200 NHPB12CB400 NHPB12SW250 NHPB12SW400 NHPB16CB400

Page No 5 7 5 5 7 5 7 5 7 5 7 5 7 5 7 5 7 4 7 4 7 4 7 4 7 4 4 7 7 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 13, 15 17 18 17 18 18

51 Numeric Index

List No 104 106 106RED 108 108M 110M 110M/63 110M/80 160C 160CM 204 206 304 306 404 406 604 606 804 921E 921X B6 B10 B16 B20 B32 B40 C5 C15 C20 C30 C35 C40 C45 CFL05 CFL10 CFL15 CFL20 CFL30 CFL35 CFL40 CFL45 ESE2 ESE2L ESE4 ESI4 ESM11 ESM13 ESM6 ESM7 ESM8 FALNH1206 FALNH1706 FALNH806 FALNHISS4606 FALNHISS5506 FALNHISS8706 FALNHRS10SL FALNHRS1106 FALNHRS13SSL FALNHRS15SL FALNHRS46506 FALNHRS55506 FALNHRS66306 FALNHRS706 FALNHRS76206 FALNHRS8SSL FWC L45 L60 LFL100


Numeric Index

52

List No NHPB16SW400 NHPB6CB200 NHPB6CB400 NHPB6SW250 NHPB6SW400 NHPB8CB200 NHPB8CB400 NHPB8SW250 NHPB8SW400 NHPBDL NHPBN25/70 NHPCB1TS NHPCB3TS NHPCBAU1 NHPCBAU2 NHPCBLDX NHPCBPL NHRM1104 NHRM1104+3 NHRM1106 NHRM1404 NHRM1406 NHRM1904 NHRM204/40 NHRM204/63 NHRM206/40 NHRM206/63 NHRM504 NHRM504+3 NHRM506 NHRM804 NHRM804+3 NHRM804+6 NHRM806 NHRS1004IP NHRS10704 NHRS10706 NHRS10SSLHI NHRS10SSLMHI NHRS1104 NHRS1104+3 NHRS1106 NHRS11604 NHRS11606 NHRS12504 NHRS12506 NHRS12SL NHRS12SLM NHRS1404 NHRS15SSLHI NHRS15SSLMHI NHRS17SL NHRS17SLM NHRS1904 NHRS204/40 NHRS204/63 NHRS206/40 NHRS206/63 NHRS23204 NHRS23206 NHRS2404 NHRS2406 NHRS304IP NHRS3304 NHRS3306 NHRS33404 NHRS33406 NHRS3604 NHRS3606 NHRS3904 NHRS3906

Page No 18 17 18 17 18 17 18 17 18 13, 15, 17, 18 19 19 19 19 19 19 19 4 4 7 4 7 4 4 4 7 7 4 4 7 4 4 4 7 5 3 6 3 6 4 4 7 3 6 3 6 3 6 4 3 6 3 6 4 4 4 7 7 3 6 3 6 5 3 6 3 6 3 6 3 6

List No NHRS4204 NHRS4206 NHRS43304 NHRS43306 NHRS44204 NHRS44206 NHRS4504 NHRS4506 NHRS45604 NHRS45606 NHRS46504 NHRS46506 NHRS4804 NHRS4806 NHRS504 NHRS504+3 NHRS506 NHRS51204 NHRS51206 NHRS5404 NHRS5406 NHRS55504 NHRS55506 NHRS5604+6 NHRS5606+6 NHRS5704 NHRS5706 NHRS61104 NHRS61106 NHRS6304 NHRS6306 NHRS6504+6 NHRS6604 NHRS6606 NHRS66304 NHRS66306 NHRS6804+3 NHRS6SL NHRS6SLM NHRS704IP NHRS71004 NHRS71006 NHRS7504 NHRS7506 NHRS76204 NHRS76206 NHRS7704+3 NHRS7706+3 NHRS7SSLHI NHRS7SSLMHI NHRS804 NHRS804+3 NHRS804+6 NHRS806 NHRS8404 NHRS8406 NHRS8604+3 NHRS8904 NHRS8906 NHRS9304 NHRS9306 NHRS9804 NHRS9806 NHRS9SL NHRS9SLM NHRSX5704 NHRSX5706 NHRSX6604 NHRSX6606 NHRSX7504 NHRSX7506

Page No 3 6 3 6 3 6 3 6 3 6 3 6 3 6 4 4 7 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 3 6 3 6 3 3 6 5 3 6 3 6 3 6 3 6 3 6 4 4 4 7 3 6 3 3 6 3 6 3 6 3 6 5 7 5 7 5 7

List No NHRSX8904 NHRSX8906 NHRSX9804 NHRSX9806 NHSFBBC400 NHSPAK NHSPN00111 NHSPN00141 NHSPN00161 NHSPN00191 NHSPN0051 NHSPN0081 NHSPSF100 NHSPSF20 NHSPSF32 NHSPSF63 NHSTM10704 NHSTM10706 NHSTM11604 NHSTM11606 NHSTM12504 NHSTM12506 NHSTM12SL NHSTM12SLM NHSTM17SL NHSTM17SLM NHSTM3604 NHSTM3606 NHSTM3904 NHSTM3906 NHSTM4504 NHSTM4506 NHSTM4804 NHSTM4806 NHSTM51204 NHSTM51206 NHSTM5404 NHSTM5406 NHSTM5704 NHSTM5706 NHSTM61104 NHSTM61106 NHSTM6304 NHSTM6306 NHSTM6604 NHSTM6606 NHSTM71004 NHSTM71006 NHSTM7504 NHSTM7506 NHSTM8404 NHSTM8406 NHSTM8904 NHSTM8906 NHSTM9304 NHSTM9306 NHSTM9804 NHSTM9806 NHSTM9SL NHSTM9SLM NHSW3100 NHSW3125 NHSW320 NHSW332 NHSW340 NHSW363 NHSW363X NHTM1104 NHTM1106 NHTM1404 NHTM1904

Page No 5 7 5 7 25 13 12 12 12 12 12 12 25 25 25 25 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 4 7 25, 35 25, 35 25, 35 25, 35 25, 35 25, 35 25, 35 4 7 4 4

List No NHTM504 NHTM506 NHTM804 NHTM806 NHTN12 NHTN125MP NHTN16 NHTN20 NHTN24 NHTN250MP NHTN25120 NHTN25160 NHTN25200 NHTN25240 NHTN2540 NHTN2560 NHTN2580 NHTN4 NHTN6 NHTN8 NHTPDC NHTPSF100 NHTPSF125 NHTPSF160 NHTPSF20 NHTPSF200 NHTPSF315 NHTPSF32 NHTPSF400 NHTPSF63 NHTPSF630 NHTPSF800 NSB03 NSB06 NSB06-B NSB06-C NSB06-D NSB10 NSB10-B NSB10-C NSB10-D NSB16 NSB16-B NSB16-C NSB16-D NSB20 NSB20-B NSB20-C NSB20-D NSB206-B NSB206-C NSB206-D NSB210-B NSB210-C NSB210-D NSB216-B NSB216-C NSB216-D NSB220-B NSB220-C NSB220-D NSB232-B NSB232-C NSB232-D NSB240-B NSB240-C NSB240-D NSB25 NSB250-B NSB250-C NSB250-D

Page No 4 7 4 7 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 13 25 25 25 25 25 25 25 25 25 25 25 9 9 14 14 14 9 14 14 14 9 14 14 14 9 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 9 14 14 14


Page No 14 14 14 14 14 14 14 14 14 14 14 14 9 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 9 14 14 14 9 14 14 14 14 14 14 9 9 9, 15 9 9 9, 15 9 9 9, 15 9 9 9, 15 9 9 9, 15 9 9 9 9 9, 15 9 9 9 9 9 9 9 9 22

List No NSPE-4136 NSPE-4137 NSPE-4138 NSPE-4151 NSPE-4152 NSPE-4153 NSPE-4154 NSPE-4171 NSPE-4172 NSPE-4173 NSPE-4174 NSPE-4182 NSPE-4183 NSPE-4184 NSPE-4185 NSPE-4186 NSPE-4187 NSPE-4188 NSPE-4189 NSPE-4190 NSPE-4191 NSPE-4192 NSPE-4193 NSPE-4194 NSPE-4195 NSPE-4196 NSPE-4197 NSPE-4198 NSPE-4199 NSPE-4200 NSPE-4201 PDDPL PSB06-B PSB06-C PSB06-D PSB10-B PSB10-C PSB10-D PSB16-B PSB16-C PSB16-D PSB20-B PSB20-C PSB20-D PSB25-B PSB25-C PSB25-D PSB206-B PSB206-C PSB206-D PSB210-B PSB210-C PSB210-D PSB216-B PSB216-C PSB216-D PSB220-B PSB220-C PSB220-D PSB225-B PSB225-C PSB225-D PSB232-B PSB232-C PSB232-D PSB240-B PSB240-C PSB240-D PSB250-B PSB250-C PSB250-D

Page No 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 13, 15 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14

List No PSB263-B PSB263-C PSB263-D PSB306-B PSB306-C PSB306-D PSB310-B PSB310-C PSB310-D PSB316-B PSB316-C PSB316-D PSB32-B PSB32-C PSB32-D PSB320-B PSB320-C PSB320-D PSB325-B PSB325-C PSB325-D PSB332-B PSB332-C PSB332-D PSB340-B PSB340-C PSB340-D PSB350-B PSB350-C PSB350-D PSB363-B PSB363-C PSB363-D PSB40-B PSB40-C PSB40-D PSB50-B PSB50-C PSB50-D PSB63-B PSB63-C PSB63-D PSBL3 PSBL9 PSBS10/1 PSBS10/2 PSBS16/1 PSBS16/2 PSBS20/1 PSBS20/2 PSBS32/1 PSBS32/2 PSBS40/1 PSBS40/2 PSBS50/1 PSBS6/1 PSBS6/2 REC2 REC2S REC3 REC4 SMSCD11 SMSCT11 TMSCD21 TMTCD22 TRMSCT11 TRMSCT31 WBE/BS WBE3 WBE3/EK WBE3/NK

Page No 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 13, 15 13, 15, 19 15 15 15 15 15 15 15 15 15 15 15 15 15 35 35 35 35 9, 15 9 9, 15 9, 15 9 9 33 33 33 33

List No WBE4 WBE4/EK WBE4/NK WELC06 WELC10 WELC16 WELC20 WELC32 WELC40 WELC50 WPL WRDM100/2 WRDM100/4 WRDM40/2 WRDM40/4 WRDM63/4 WRDS100/2 WRDS100/4 WRDS40/2 WRDS40/4 WRDS63/2 WRDS63/4 WRDS80/2 WRDVS32/2 WRL100/2 WRL100/4 WRL63/2 WRL63/4 WRM100/2 WRM100/4 WRM40/2 WRM40/4 WRM63/2 WRM63/4 WRM80/2 WRMT100/2 WRMT100/4 WRS100/2 WRS100/4 WRS16/2 WRS25/2 WRS32/2 WRS32/4 WRS40/2 WRS40/4 WRS63/2 WRS63/4 WRS80/2 WS101 WS102 WS103 WS104 WS121 WS122 WS123 WS124 WS601 WS602 WS603 WS604

Page No 33 33 33 9 9 9 9 9 9 9 9, 13, 15 32 32 32 32 32 32 32 32 32 32 32 32 32 13, 32 13, 32 13, 32 13, 32 13, 32 13, 32 32 32 13, 32 13, 32 13 13, 32 13, 32 13, 32 13, 32 32 32 32 32 32 32 13, 32 13, 32 13, 32 35 13, 35 13, 35 13, 35 35 13, 35 13, 35 13, 35 35 13, 35 13, 35 13, 35

53 Numeric Index

List No NSB263-B NSB263-C NSB263-D NSB306-B NSB306-C NSB306-D NSB310-B NSB310-C NSB310-D NSB316-B NSB316-C NSB316-D NSB32 NSB32-B NSB32-C NSB32-D NSB320-B NSB320-C NSB320-D NSB332-B NSB332-C NSB332-D NSB340-B NSB340-C NSB340-D NSB350-B NSB350-C NSB350-D NSB363-B NSB363-C NSB363-D NSB40 NSB40-B NSB40-C NSB40-D NSB50 NSB50-B NSB50-C NSB50-D NSB63-B NSB63-C NSB63-D NSBS10-B/1 NSBS10/1 NSBS10/2 NSBS16-B/1 NSBS16/1 NSBS16/2 NSBS20-B/1 NSBS20/1 NSBS20/2 NSBS32-B/1 NSBS32/1 NSBS32/2 NSBS40-B/1 NSBS40/1 NSBS40/2 NSBS50-B/1 NSBS50/1 NSBS6-B/1 NSBS6/1 NSBS6/2 NSC05 NSC10 NSC15 NSC20 NSC30 NSC35 NSC40 NSC45 NSPE-4120


ELECTRIUM SALES LIMITED A SIEMENS COMPANY Commercial Centre, Lakeside Plaza, Walkmill Lane, Bridgtown, Cannock WS11 0XE. eMail: info@electrium.co.uk Web: www.electrium.co.uk UK SALES Telephone: 01543 455020 Facsimile: 01543 455021 eMail: wylex.sales@electrium.co.uk TECHNICAL Telephone: 01543 438320 Facsimile: 01543 438321 eMail: wylex.technical@electrium.co.uk EXPORT SALES Telephone: +44 1543 455049 Facsimile: +44 1543 455048 eMail: export@electrium.co.uk DUBAI OFFICE Telephone: +971 4 3660395 Facsimile: +971 4 3660019

DUBLIN OFFICE Telephone: +353 45899838 Facsimile: +353 45899842

Although every effort has been made to ensure accuracy in the compilation of the technical detail within this publication, speciďŹ cations and performance data are constantly changing. Latest details can be obtained from Wylex.

Publication No.WY2023 Printed in England.