Caledonian BS 6346 PVC Insulated, Armored Power and Control Cables
www.caledonian-cables.co.uk www.caledonian-cables.com
Addison
Company Profile Caledonian. established in 1978.offers one of the most complete lines of fiber and copper cabling system solutions with over hundreds of different cabling system products. . Our superior products provide leading edge within every cable series and for every application. Among the national and international standards with which our cables could comply are: BS - British Standard; LPCB Fire Performance Standard. ISO Standard etc. Caledonian Cables offers a comprehensive stock of cables and cabling products through its nationwide network of resellers and distributors. Caledonian Cables has continually expanded its global presence in Europe and Asia. Caledonian & Addison. produces a wide range of cables for communication. power and electronics in its primary plants in UK. Italy and Spain. To stay in front. we continually keep expanding our manufacturing capabilities in more low cost region such as Romania. Taiwan. Malaysia etc. This low-cost manufacturing facilities enable us provide a flexible. scalable global system that delivers superior operational performance and optimal results for our customers. Our extensive global network of manufacturing facilities gives us significant scale and the flexibility to fulfill our customer requirements. This global presence provides design and consultancy solutions that are combined with core cable manufacturing. logistic services. and vertically integrated with our E commerce technologies. to optimize customer operations by lowering costs and reducing time to market. Caledonian & Addison has been respected for its high standards of quality. excellent service level. competitive pricing and a unique and innovative spirit. With our latest technologies. we are both inspired and well-positioned to meet the changing needs of our customers. We have the resources to diversify and to enhance our product lines and services. We understand the need for change and with our accurate planning. we are ready for the future and the promise of new marketing opportunities. Our tradition of growth through excellence is assured. Our Design Centers work closely with customers to constantly improve its standard range of products and technologies and to develop customized. country and industry-specific solutions. Caledonian & Addison has established an extensive network of design. manufacturing. and logistics facilities in the world’s major markets to serve the growing outsourcing needs of both multinational and regional customers.
Our Certificate
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation Cables
Table of Contents BS 6346 PVC Insulated Cables, 600/1000V................................................5 BS 6346 PVC Insulated Cables, 1900/3300V............................................17 Technical Reference..................................................................................21
4
www.addison-tech.com
www.addison-cables.com
Caledonian Cables Power Cables 600/1000V PVC Insulation,
BS5467 BS 6346
BS 6346 PVC Insulated Cables, 600/1000V Application These power and control cables are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...).
Construction Conductor
Filler(optional)
Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228. PVC(Polyvinyl Chloride) type TI1 1 Core : Brown 2 Cores: Brown or Blue 3 Cores: Brown, Black, Grey 4 Cores: Blue, Brown, Black, Grey 5 Cores: Green-yellow, Blue, Brown, Black, Grey Above 5 Cores: White Cores with black numbers PVC or Polypropylene yarn
Binder Tape(optional)
Polyester (Mylar) tape
Insulation Colour Code
Inner Sheath/ Bedding PVC (Polyvinyl Chloride) Armour Single Core: AWA (Aluminum Wire Armour) Multi Core: SWA (Steel Wire or Tape Armour) Outer Sheath PVC(Polyvinyl Chloride), type TM1
Technical Information Voltage rating
600/1000V
Temperature rating
-20°C to +60°C
Bending radius
Single core: 10 x overall diameter
Multicores: 8 x overall diameter
Flame retardant
IEC60332 part 1, BS4066 part 1
www.caledonian-cables.co.uk
www.caledonian-cables.com
5
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 600/1000V
Cable Parameter Single-core 600/1000V cables with circular stranded copper conductor PVC bedding PVC insulation Plain copper conductor Aluminum wire armour PVC jacket Nominal crosssectional area mm²
6
Nominal sheath thickness
Approx. overall diameter
Approx. cable weight
mm
Nominal alum wire armor dia. mm
mm
mm
kg/km
1.4
0.8
1.25
1.5
19.1
820
19/2.14
1.4
0.8
1.25
1.6
21.1
1070
1x95
19/2.52
1.6
0.8
1.25
1.6
23.4
1390
1x120
37/2.03
1.6
1.0
1.6
1.7
26.3
1600
1x150
37/2.25
1.8
1.0
1.6
1.7
28.3
1900
1x185
37/2.52
2.0
1.0
1.6
1.8
30.8
2450
1x240
61/2.25
2.2
1.0
1.6
1.9
34.1
3100
1x300
61/2.52
2.4
1.0
1.6
1.9
37.0
3760
1x400
61/2.85
2.6
1.2
2.0
2.1
42.0
4850
1x500
61/3.20
2.8
1.2
2.0
2.1
45.6
5930
1x630
61/3.65
2.8
1.2
2.0
2.2
49.7
7390
1x800
127/2.85
2.8
1.4
2.5
2.4
55.8
9400
1x1000
127/3.20
3.0
1.4
2.5
2.5
61.0
11430
Number/ wire
Nominal insulation thickness
Nominal bedding thickness
No./mm
mm
1x50
19/1.78
1x70
www.addison-tech.com
www.addison-cables.com
Caledonian Cables BS5467 BS 6346
Power Cables 600/1000V PVC Insulation,
Single-core 600/1000V cables with solid aluminum conductor PVC bedding PVC insulation Aluminum conductor Aluminum wire armour PVC jacket Nominal Nominal Nominal Nominal alum crossbedding insulation wire sectional thickness thickarmor area ness dia. mm² mm mm mm
Nominal sheath thickness width
Armour strip thickness mm
mm
mm
Approx. overall diameter wire strip armor armor mm mm
Approx. cable weight kg/km
1x50
1.4
0.8
1.25
0.6
2.4
1.5
17.8
16.5
530
1x70
1.4
0.8
1.25
0.6
2.4
1.6
19.6
18.3
650
1x95
1.6
0.8
1.25
0.6
2.4
1.6
21.7
20.4
810
1x120
1.6
1
1.6
0.6
2.4
1.7
24.3
22.3
960
1x150
1.8
1
1.6
0.6
2.4
1.7
26.1
24.1
1115
1x185
2
1
1.6
1
3.6
1.8
28.3
27.1
1315
1x240
2.2
1
1.6
1
3.6
1.9
31.2
30
1610
1x300
2.4
1
1.6
1
3.6
1.9
33.7
32.5
1890
www.caledonian-cables.co.uk
www.caledonian-cables.com
7
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 600/1000V
Two-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal Nominal Nominal Nominal Nominal crossbedding wire sheath insulation sectional Number/ thickarmor thickwire thickness area ness dia. ness mm² No./mm mm mm mm mm
Approx. overall diameter extruded taped bedding bedding mm mm
kg/mm
2x1.5
7/0.53
0.6
0.8
0.9
1.4
12.3
-
270
2x2.5
7/0.67
0.7
0.8
0.9
1.4
13.6
-
350
2x4
7/0.85
0.8
0.8
0.9
1.4
15.1
-
470
2x6
7/1.04
0.8
0.8
0.9
1.5
16.5
-
580
2x10
7/1.35
1.0
0.8
1.25
1.6
20.1
-
840
2x16
7/1.70
1.0
0.8
1.25
1.6
21.9
21.9
990
2x25
7/2.14
1.2
1.0
1.6
1.7
26.7
26.3
1480
2x25*
7/2.14
1.2
1.0
1.6
1.7
23.0
22.6
1480
2x35
19/1.53
1.2
1.0
1.6
1.8
29.2
28.8
1770
2x35*
19/1.53
1.2
1.0
1.6
1.8
24.8
24.4
1770
2x50*
19/1.78
1.4
1.0
1.6
1.9
27.8
27.4
1900
2x70*
19/2.14
1.4
1.0
1.6
1.9
30.4
30.0
2430
2x95*
19/2.52
1.6
1.2
2.0
2.1
35.5
34.7
2970
2x120*
37/2.03
1.6
1.2
2.0
2.2
38.0
37.2
3970
2x150*
37/2.25
1.8
1.2
2.0
2.3
41.3
40.5
4700
2x185*
37/2.52
2.0
1.4
2.5
2.4
46.4
45.2
5990
2x240*
61/2.25
2.2
1.4
2.5
2.5
51.2
50.0
7420
2x300*
61/2.52
2.4
1.6
2.5
2.7
56.4
54.8
8950
2x400*
61/2.85
2.6
1.6
2.5
2.9
61.9
60.3
11030
*Shaped stranded conductor (class 2)
8
Approx. cable weight
www.addison-tech.com
www.addison-cables.com
mm
1
1.2
1.2
1.2
1.2
1.4
1.4
1.6
mm²
www.caledonian-cables.co.uk
2x16
2x25
2x25*
2x35
2x35*
2x50*
2x70*
2x95*
www.caledonian-cables.com
1.2
1
1
1
1
1
1
0.8
mm
Nominal bedding thickness
 2.0
1.6
1.6
1.6
1.6
1.6
1.6
1.25
mm
Nominal wire armor dia.
1
1
0.6
0.6
0.6
0.6
0.6
0.6
mm
thickness
3.6
3.6
2.4
2.4
2.4
2.4
2.4
2.4
mm
width
Armour strip
2.1
1.9
1.9
1.8
1.8
1.7
1.7
1.6
mm
Nominal sheath thickness
32.4
27.7
25.5
22.9
27.2
21.3
25
20.6
31.6
27.3
25.1
22.5
26.8
20.9
24.6
20.6
wire armor extruded taped bedding bedding mm mm
29.6
26.1
23.1
20.5
24.8
18.9
22.6
19.3
mm
strip armor
Approx. overall diameter
2200
1560
1450
1340
1340
1170
1170
795
kg/km
Approx. cable weight
Power Cables 600/1000V PVC Insulation,
*Solid shaped conductor (class 1)
Nominal insulation thickness
Nominal crosssectional area
PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket
Two-core 600/1000V cables with solid aluminum conductors
Caledonian Cables BS5467 BS 6346
9
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 600/1000V
Three-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal Nominal Nominal Nominal Nominal crossbedding wire sheath insulation sectional Number/ thickarmor thickwire thickness area ness dia. ness mm² No./mm mm mm mm mm
Approx. overall Approx. diameter cable extruded taped weight bedding bedding mm mm kg/mm
3x1.5
7/0.53
0.6
0.8
0.9
1.4
12.8
-
307
3x2.5
7/0.67
0.7
0.8
0.9
1.4
14.1
-
387
3x4
7/0.85
0.8
0.8
0.9
1.4
15.8
-
493
3x6
7/1.04
0.8
0.8
1.25
1.5
18.0
-
701
3x10
7/1.35
1.0
0.8
1.25
1.6
21.2
-
967
3x16
7/1.70
1.0
0.8
1.25
1.6
23.1
23.1
1219
3x25
7/2.14
1.2
1.0
1.6
1.7
28.2
27.8
1612
3x25*
7/2.14
1.2
1.0
1.6
1.7
25.0
24.6
1612
3x35
19/1.53
1.2
1.0
1.6
1.8
30.8
30.4
1992
3x35*
19/1.53
1.2
1.0
1.6
1.8
27.1
26.7
1992
3x50*
19/1.78
1.4
1.0
1.6
1.9
30.5
30.1
2534
3x70*
19/2.14
1.4
1.2
2.0
2.0
35.0
34.2
3518
3x95*
19/2.52
1.6
1.2
2.0
2.1
39.3
38.5
4510
3x120*
37/2.03
1.6
1.2
2.0
2.2
42.2
41.4
5375
3x150*
37/2.25
1.8
1.4
2.5
2.4
47.5
46.3
6810
3x185*
37/2.52
2.0
1.4
2.5
2.5
51.9
50.7
8190
3x240*
61/2.25
2.2
1.6
2.5
2.6
57.8
56.2
10280
3x300*
61/2.52
2.4
1.6
2.5
2.8
63.2
61.6
12430
3x400*
61/2.85
2.6
1.6
2.5
3.0
69.6
68.0
15400
*Shaped stranded conductor (class 2)
10
www.addison-tech.com
www.addison-cables.com
www.caledonian-cables.co.uk
1
1.2
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2
2.2
2.4
3x16
3x25
3x25*
3x35
3x35*
3x50*
3x70*
3x95*
www.caledonian-cables.com
3x120*
3x150*
3x185*
3x240*
3x300*
1.6
1.6
1.4
1.4
1.2
1.2
1.2
1
1
1
1
1
0.8
mm
Nominal bedding thickness
2.5
2.5
2.5
2.5
2
2
2
1.6
1.6
1.6
1.6
1.6
1.25
mm
Nominal wire armor dia.
1.8
1.8
1.4
1.4
1.4
1.4
1
1
0.6
0.6
0.6
0.6
0.6
mm
thickness
6.4
6.4
4.8
4.8
4.8
4.8
3.6
3.6
2.4
2.4
2.4
2.4
2.4
mm
width
Armour strip
2.8
2.6
2.5
2.4
2.2
2.1
2
1.9
1.8
1.8
1.7
1.7
1.6
mm
Nominal sheath thickness
59.2
54.2
48.7
44.7
39.7
37.1
33
28.9
28.7
26.4
25.8
23.9
21.7
57.6
52.6
47.5
43.5
38.9
36.3
32.2
28.5
28.3
26.0
25.4
23.5
21.7
wire armor extruded taped bedding bedding mm mm
56.2
51.2
45.3
41.3
37.7
35.1
30.2
26.4
27.3
24.1
23.4
21.5
20.4
mm
strip armor
Approx. overall diameter
6850
5820
4730
4020
3145
2745
2220
1610
1345
1345
1150
1150
925
kg/km
Approx. cable weight
Power Cables 600/1000V PVC Insulation,
*Solid shaped conductor (class 1)
mm
mm²
Nominal Nominal crossinsulation sectional thickness area
PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket
Three-core 600/1000V cables with solid aluminum conductors
Caledonian Cables BS5467 BS 6346
11
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 600/1000V
Four-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal Nominal Nominal Nominal Nominal crossbedding wire sheath insulation sectional Number/ thickarmor thickwire thickness area ness dia. ness mm² No./mm mm mm mm mm
Approx. overall diameter extruded taped bedding bedding mm mm
kg/mm
4x1.5
7/0.53
0.6
0.8
0.9
1.4
13.5
-
330
4x2.5
7/0.67
0.7
0.8
0.9
1.4
15.0
-
430
4x4
7/0.85
0.8
0.8
1.25
1.5
17.8
-
640
4x6
7/1.04
0.8
0.8
1.25
1.5
19.2
-
770
4x10
7/1.35
1.0
0.8
1.25
1.6
22.8
-
1070
4x16
7/1.70
1.0
1.0
1.6
1.7
26.3
25.9
1550
4x25
7/2.14
1.2
1.0
1.6
1.8
30.7
30.3
2005
4x25*
7/2.14
1.2
1.0
1.6
1.8
27.8
27.4
2005
4x35
19/1.53
1.2
1.0
1.6
1.9
33.7
33.3
2490
4x35*
19/1.53
1.2
1.0
1.6
1.9
30.3
29.9
2490
4x50*
19/1.78
1.4
1.2
2.0
2.0
35.4
34.6
3475
4x70*
19/2.14
1.4
1.2
2.0
2.1
39.2
38.4
4480
4x95*
19/2.52
1.6
1.2
2.0
2.2
43.3
43.5
5710
4x120*
37/2.03
1.6
1.4
2.5
2.4
49.3
48.1
7350
4x150*
37/2.25
1.8
1.4
2.5
2.5
53.6
52.4
8720
4x185*
37/2.52
2.0
1.6
2.5
2.6
59.0
57.4
10540
4x240*
61/2.25
2.2
1.6
2.5
2.8
65.7
64.1
13290
4x300*
61/2.52
2.4
1.6
2.5
3.0
72.0
70.4
16050
4x400*
61/2.85
2.6
1.8
3.15
3.3
81.3
79.3
20950
*Shaped stranded conductor (class 2)
12
Approx. cable weight
www.addison-tech.com
www.addison-cables.com
www.caledonian-cables.co.uk
1
1.2
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2
2.2
2.4
4x16
4x25
4x25*
4x35
4x35*
4x50*
4x70*
4x95*
www.caledonian-cables.com
4x120*
4x150*
4x185*
4x240*
4x300*
1.6
1.6
1.6
1.4
1.4
1.2
1.2
1.2
1
1
1
1
1
mm
Nominal bedding thickness
2.5
2.5
2.5
2.5
2.5
2
2
2
1.6
1.6
1.6
1.6
1.6
Nominal alum wire armor dia. mm
1.8
1.8
1.8
1.4
1.4
1.4
1
1
0.6
0.6
0.6
0.6
0.6
mm
thickness
6.4
6.4
6.4
4.8
4.8
4.8
3.6
3.6
2.4
2.4
2.4
2.4
2.4
mm
width
Armour strip
3
2.8
2.6
2.5
2.4
2.2
2.1
2
1.9
1.9
1.8
1.8
1.7
mm
Nominal sheath thickness
67
61.2
55.1
50.1
46.1
41.5
36.8
33.3
28.6
31.3
26.3
28.7
24.7
65.4
59.6
53.5
48.9
44.9
40.7
36.0
32..5
28.2
30.9
25.9
28.3
24.3
wire armor extruded taped bedding bedding mm mm
64
58.2
52.1
46.7
42.7
39.5
34
30.5
26.2
28.9
23.9
26.3
22.3
mm
strip armor
Approx. overall diameter
8610
7340
5960
5000
4380
3360
2750
2240
1625
1625
1390
1390
1125
kg/km
Approx. cable weight
Power Cables 600/1000V PVC Insulation,
*Solid shaped conductor (class 1)
mm
mm²
Nominal Nominal crossinsulation sectional thickness area
PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket
Four-core 600/1000V cables with solid aluminum conductors
Caledonian Cables BS5467 BS 6346
13
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 600/1000V
3+1 Core (4 Core with reduced neutral) 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket
mm²
mm²
mm
mm
mm
Nominal wire armor dia. mm
3x10
3x6
1.0
0.8
1.0
1.25
1.8
23.4
1370
3x16
3x10
1.0
1.0
1.0
1.25
1.8
25.0
1620
3x25*
3x16
1.2
1.0
1.0
1.6
1.8
27.8
1900
3x35*
3x16
1.2
1.0
1.0
1.6
1.8
29.5
2300
3x50*
3x25
1.4
1.2
1.0
1.6
1.9
33.1
3050
3x70*
3x35
1.4
1.2
1.2
2.0
2.0
38.0
4130
3x95*
3x50
1.6
1.4
1.2
2.0
2.2
43.7
5370
3x120*
3x70
1.6
1.4
1.4
2.5
2.3
49.0
6840
3x150*
3x70
1.8
1.4
1.4
2.5
2.4
52.0
8040
3x185*
3x95
2.0
1.6
1.4
2.5
2.5
57.2
9760
3x240*
3x120
2.2
1.6
1.6
2.5
2.7
63.7
12210
3x300*
3x150
2.4
1.8
1.6
2.5
2.9
69.8
14840
3x300*
3x185
2.4
2.0
1.6
2.5
2.9
71.8
17730
3x400*
3x185
2.6
2.0
1.8
3.15
3.1
78.6
19090
Nominal crosssectional area Phase Neutral
Nominal insulation thickness Phase Neutral
Nominal bedding thickness
Nominal sheath thickness
Approx. Overall Diameter
Approx. cable weight
mm
mm
kg/mm
*Shaped stranded conductor (class 2)
14
www.addison-tech.com
www.addison-cables.com
Caledonian Cables BS5467 BS 6346
Power Cables 600/1000V PVC Insulation,
Five-core 600/1000V cables with stranded copper conductors PVC bedding Plain copper conductor PVC insulation Steel wire armour PVC jacket
Number/ wire
Nominal insulation thickness
No./mm
mm
Nominal bedding thickness mm
5x1.5
7/0.53
0.6
0.8
0.9
1.4
14.3
-
430
5x2.5
7/0.67
0.7
0.8
0.9
1.5
16.3
-
545
5x4
7/0.85
0.8
0.8
1.25
1.5
19.0
-
790
5x6
7/1.04
0.8
0.8
1.25
1.6
20.9
-
880
5x10
7/1.35
1.0
1.0
1.6
1.7
25.8
-
1150
5x16
7/1.70
1.0
1.0
1.6
1.7
28.4
28.0
1670
5x25
7/2.14
1.2
1.0
1.6
1.9
33.5
33.1
2250
5x35
19/1.53
1.2
1.0
1.6
1.9
36.6
36.2
2670
5x50
19/1.78
1.4
1.2
2.0
2.1
43.0
42.2
3590
5x70
19/2.14
1.4
1.2
2.0
2.2
48.1
47.3
4610
www.caledonian-cables.co.uk
Nominal Nominal wire sheath armor thickdia. ness mm mm
Approx. overall Approx. diameter cable extruded taped weight bedding bedding mm mm kg/mm
Nominal crosssectional area mm²
www.caledonian-cables.com
15
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 600/1000V
Multi-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket
No. of Cores
16
Nominal Nominal Nominal Nominal crossNumber/ insulation bedding alum wire sectional wire thickthickness armor dia. area ness mm² No./mm mm mm mm
Nominal sheath thickness mm
Approx. overall diameter
Approx. cable weight
mm
kg/mm
7
1.5
7/0.53
0.6
0.8
0.9
1.4
15.2
500
10
1.5
7/0.53
0.6
0.8
1.25
1.5
18.6
780
12
1.5
7/0.53
0.6
0.8
1.25
1.5
19.4
830
19
1.5
7/0.53
0.6
0.8
1.25
1.6
22.2
1090
27
1.5
7/0.53
0.6
1.0
1.6
1.7
26.7
1600
37
1.5
7/0.53
0.6
1.0
1.6
1.8
29.2
1940
48
1.5
7/0.53
0.6
1.0
1.6
1.9
32.9
2360
7
2.5
7/0.67
0.7
0.8
1.25
1.5
18.0
750
10
2.5
7/0.67
0.7
0.8
1.25
1.6
21.8
1000
12
2.5
7/0.67
0.7
0.8
1.25
1.6
22.4
1080
19
2.5
7/0.67
0.7
1.0
1.6
1.7
26.6
1640
27
2.5
7/0.67
0.7
1.0
1.6
1.8
30.7
2110
37
2.5
7/0.67
0.7
1.0
1.6
1.9
34.0
2600
48
2.5
7/0.67
0.7
1.2
2.0
2.1
39.5
3520
7
4
7/0.85
0.8
0.8
1.25
1.6
20.5
970
10
4
7/0.85
0.8
1.0
1.6
1.7
26.1
1500
12
4
7/0.85
0.8
1.0
1.6
1.7
26.8
1630
19
4
7/0.85
0.8
1.0
1.6
1.8
30.5
2170
27
4
7/0.85
0.8
1.2
2.0
2.0
37.1
3170
37
4
7/0.85
0.8
1.2
2.0
2.1
40.8
3910
48
4
7/0.85
0.8
1.2
2.0
2.2
46.0
4790
www.addison-tech.com
www.addison-cables.com
Caledonian Cables Power Cables 1900/3000V PVC Insulation,
BS5467 BS 6346
BS 6346 PVC Insulated Cables,1900/3300V Application These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour, so they are well adapted to underground use in industrial applications, in moist areas.
Construction Conductor
Filler(optional)
Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228. PVC(Polyvinyl Chloride) type TI1 1 Core : Brown 2 Cores: Brown or Blue 3 Cores: Brown, Black, Grey 4 Cores: Blue, Brown, Black, Grey 5 Cores: Green-yellow, Blue, Brown, Black, Grey Above 5 Cores: White Cores with black numbers PVC or Polypropylene yarn
Binder Tape(optional)
Polyester (Mylar) tape
Inner Sheath/ Bedding Armour
PVC (Polyvinyl Chloride) Single Core: AWA (Aluminum Wire Armour) Multi Core: SWA (Steel Wire or Tape Armour) PVC(Polyvinyl Chloride), type TM1
Insulation Colour Code
Outer Sheath
Technical Information Voltage rating
1900/3300V
Temperature rating -20°C to +60°C Bending radius
Single core: 10 x overall diameter
Multicores: 8 x overall diameter
Flame retardant
IEC60332 part 1, BS4066 part 1
www.caledonian-cables.co.uk
www.caledonian-cables.com
17
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 1900/3000V
Cable Parameter Single-core 1900/3300 V cables with circular stranded copper conductor PVC bedding PVC insulation Plain copper conductor Aluminum wire armour PVC jacket Nominal crosssectional area mm²
Nominal sheath thickness
Approx. overall diameter
Approx. cable weight
mm
Nominal alum wire armor dia. mm
mm
mm
kg/mm
2.2
0.8
1.25
1.6
21.0
840
19/2.14
2.2
0.8
1.25
1.6
22.8
1070
1x95
19/2.52
2.2
1.0
1.6
1.7
26.0
1445
1x120
37/2.03
2.2
1.0
1.6
1.7
27.7
1715
1x150
37/2.25
2.2
1.0
1.6
1.8
29.4
2010
1x185
37/2.52
2.2
1.0
1.6
1.8
31.3
2380
1x240
61/2.25
2.2
1.0
1.6
1.9
34.1
2975
1x300
61/2.52
2.4
1.0
1.6
1.9
37.0
3615
1x400
61/2.85
2.6
1.2
2.0
2.1
42.0
4655
1x500
61/3.20
2.8
1.2
2.0
2.1
45.6
5725
1x630
61/3.65
2.8
1.2
2.0
2.2
49.7
7150
1x800
127/2.85
2.8
1.4
2.5
2.4
55.8
9160
1x1000
127/3.20
3.0
1.4
2.5
2.5
61.0
11400
Number/ wire
Nominal insulation thickness
Nominal bedding thickness
No./mm
mm
1x50
19/1.78
1x70
Single-core 1900/3300 V cables with solid aluminum conductor PVC bedding PVC insulation Aluminum conductor Aluminum wire armour PVC jacket
18
www.addison-tech.com
www.addison-cables.com
Caledonian Cables BS5467 BS 6346
Power Cables 1900/3000V PVC Insulation, Nominal crosssectional area mm²
Nominal insulation thickness
Nominal bedding thickness
Nominal alum wire armor dia.
Nominal sheath thickness
Approx. overall diameter
Approx. cable weight
mm
mm
mm
mm
mm
kg/mm
1x50
2.2
0.8
1.25
1.6
19.8
625
1x70
2.2
0.8
1.25
1.6
21.3
735
1x95
2.2
1.0
1.6
1.7
24.3
965
1x120
2.2
1.0
1.6
1.7
25.6
1090
1x150
2.2
1.0
1.6
1.8
27.1
1250
1x185
2.2
1.0
1.6
1.8
28.8
1415
1x240
2.2
1.0
1.6
1.9
31.2
1680
1x300
2.4
1.0
1.6
1.9
33.7
1935
Three-core 1900/3300 V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal crosssectional area mm²
Nominal sheath thickness
Approx. overall diameter
Approx. cable weight
mm
Nominal wire armor dia. mm
mm
mm
kg/mm
2.2
1.0
1.6
1.8
30.3
1700
7/2.14
2.2
1.0
1.6
1.8
33.1
2085
3x35
19/1.53
2.2
1.0
1.6
1.9
35.8
2405
3x35*
19/1.53
2.2
1.0
1.6
1.9
32.1
2405
3x50*
19/1.78
2.2
1.2
2.0
2.0
35.6
3160
3x70*
19/2.14
2.2
1.2
2.0
2.1
38.9
3925
3x95*
19/2.52
2.2
1.2
2.0
2.2
42.3
4860
3x120*
37/2.03
2.2
1.4
2.5
2.3
46.6
6205
3x150*
37/2.25
2.2
1.4
2.5
2.4
49.4
7175
3x185*
37/2.52
2.2
1.4
2.5
2.5
52.8
8320
3x240*
61/2.25
2.2
1.6
2.5
2.6
57.8
10395
3x300*
61/2.52
2.4
1.6
2.5
2.8
63.2
12575
3x400*
61/2.85
2.6
1.6
2.5
3.0
69.6
15325
Number/ wire
Nominal insulation thickness
Nominal bedding thickness
No./mm
mm
3x16
7/1.70
3x25
*Shaped stranded conductor (class 2)
www.caledonian-cables.co.uk
www.caledonian-cables.com
19
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation, 1900/3000V
Three-core 1900/3300 V cables with solid aluminum conductors PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket Nominal crosssectional area mm²
Nominal insulation thickness
Nominal bedding thickness
Nominal Armor dia.
Nominal sheath thickness
Approx. overall diameter
Approx. cable weight
mm
mm
mm
mm
mm
kg/mm
3x16
2.2
1.0
1.6
1.8
28.9
1630
3x25
2.2
1.0
1.6
1.8
31.3
1880
3x35
2.2
1.0
1.6
1.9
33.7
2145
3x35*
2.2
1.0
1.6
1.9
30.6
2145
3x50*
2.2
1.2
2.0
2.0
33.9
2880
3x70*
2.2
1.2
2.0
2.1
36.9
3340
3x95*
2.2
1.2
2.0
2.2
40.0
3870
3x120*
2.2
1.4
2.5
2.3
44.0
4980
3x150*
2.2
1.4
2.5
2.4
46.5
5585
3x185*
2.2
1.4
2.5
2.5
49.6
6250
3x240*
2.2
1.6
2.5
2.6
54.2
7315
3x300*
2.4
1.6
2.5
2.8
59.2
8365
*Shaped conductor (class 1)
20
www.addison-tech.com
www.addison-cables.com
Caledonian Cables Power Cables cables PVC Insulation
BS5467 BS 6346
Technical Reference Maximum resistance of conductor and armour for single-core cable having aluminum wire armour Nominal cross sectional area of conductor
Copper conductor
mm2 50 70 95 120 150 185 240 300 400 500 630 800 1 000
Ω 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176
Maximum resistance per km of cable at 20 °C Aluminum wire armour Aluminum Cables with stranded Cables with solid conductor copper conductor aluminum conductor 600/1000V 1900/3300 V 600/1000V 1900/3300 V Ω Ω Ω Ω Ω 0.641 1.3 0.75 1.4 0.79 0.443 0.75 0.67 0.84 0.73 0.32 0.67 0.61 0.75 0.67 0.253 0.61 0.42 0.69 0.47 0.206 0.42 0.39 0.47 0.43 0.164 0.38 0.37 0.42 0.4 0.125 0.34 0.34 0.38 0.37 0.1 0.31 0.31 0.35 0.34 — 0.22 0.22 — — — 0.2 0.2 — — — 0.18 0.18 — — — 0.13 0.13 — — — 0.12 0.12 — —
Maximum resistance of conductor and armour for two-, three-, four- and five-core cables having wire armour 1) With stranded copper conductor Nominal cross sectional area of conductor
Copper conductor
mm2 1.5 2.5 4 6 10 16
Ω 12.1 7.41 4.61 3.08 1.83 1.15
Maximum resistance per km of cable at 20 °C Steel wire armour Cables with stranded copper conductors Aluminum TwoFourFiveThree-core conductor core core core 600/ 600/ 1900/ 600/ 600/ 1000V 1000V 3300 V 1000V 1000V Ω Ω Ω Ω Ω Ω — 10.2 9.5 — 8.8 8.2 — 8.8 8.2 — 7.7 6.8 — 7.9 7.5 — 6.8 6.2 — 7 6.7 — 4.3 3.9 — 6 4 — 3.7 3.4 1.91 3.7 3.5 1.9 3.1 2.2
www.caledonian-cables.co.uk
www.caledonian-cables.com
21
Addison Cables BS5467 BS 6346
Nominal cross sectional area of conductor
Copper conductor
mm2 25 35 50 70 95 120 150 185 240 300 400
Ω 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 1 0.075 4 0.060 1 0.047 0
Power Cables PVC Insulation Cables Maximum resistance per km of cable at 20 °C Steel wire armour Cables with stranded copper conductors Aluminum TwoFourFiveThree-core conductor core core core 600/ 600/ 1900/ 600/ 600/ 1000V 1000V 3300 V 1000V 1000V Ω Ω Ω Ω Ω Ω 1.2 3.7 2.5 1.7 2.0 2.3 1.8 0.868 2.6 2.3 1.8 — 1.6 0.641 2.3 2 1.3 1.8 1.1 0.443 2 1.8 1.2 1.2 0.94 0.32 1.4 1.3 1.1 1.1 — 0.253 1.3 1.2 0.76 0.76 — 0.206 1.2 0.78 0.71 0.68 — 0.164 0.82 0.71 0.65 0.61 — 0.125 0.73 0.63 0.59 0.54 — 0.1 0.67 0.58 0.55 0.49 — — 0.59 0.52 0.5 0.35 —
2) With solid aluminum conductor Nominal crosssectional area of conductor mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
22
Copper conductor Ω 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 1 0.075 4 0.060 1 0.047 0
Maximum resistance per km of cable at 20 °C Steel wire armour Cables with solid aluminum conductors Aluminum Two-core Three-core Four-core conductor 600/1000V 600/1000V 1900/3300 V 600/ 1000V Ω — — — — — 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 —
Ω — — — — — 4 4.1 2.9 2.6 2.3 1.6 — — — — — —
www.addison-tech.com
Ω — — — — — 3.8 2.7 2.5 2.2 1.9 1.4 1.2 0.86 0.76 0.68 0.63 —
Ω — — — — — 2 1.9 1.9 1.4 1.3 1.2 0.82 0.76 0.71 0.64 0.59 —
www.addison-cables.com
Ω — — — — — 3.4 2.4 2.2 1.9 1.3 1.2 0.82 0.74 0.67 0.59 0.54 —
Caledonian Cables Power Cables cables PVC Insulation
BS5467 BS 6346
Electrical Properties(600/1000V) 1) Single core with copper conductor Nominal area of conductor mm² 50 70 95 120 150 185 240 300 400 500 630 800 1000
Single Core Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 235 235 222 0.87 0.93 0.87 290 280 285 0.62 0.70 0.62 345 330 346 0.47 0.56 0.47 390 370 402 0.39 0.48 0.39 435 405 463 0.33 0.43 0.33 490 440 529 0.28 0.39 0.28 560 500 625 0.24 0.35 0.24 630 550 720 0.21 0.32 0.21 700 580 815 0.20 0.30 0.20 770 620 918 0.18 0.28 0.18 840 670 1027 0.17 0.26 0.17 888 692 1119 0.17 0.25 0.17 942 735 1214 0.16 0.24 0.16
1) Single core with aluminum conductor Nominal area of conductor mm² 50 70 95 120 150 185 240 300 400 500 630
Single Core Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 175 180 162 1.40 1.60 1.40 220 220 207 0.98 1.00 0.98 260 260 252 0.72 0.79 0.74 295 295 292 0.58 0.66 0.60 330 330 337 0.48 0.57 0.49 375 365 391 0.39 0.49 0.41 435 410 465 0.31 0.42 0.34 490 455 540 0.27 0.38 0.29 540 480 625 0.35 0.38 0.25 580 510 714 0.31 0.35 0.22 630 540 801 0.28 0.32 0.20
www.caledonian-cables.co.uk
www.caledonian-cables.com
23
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation Cables
2) Two cores with copper conductor Nominal area of conductor mm² 16* 25* 35* 50 70
Two Cores Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 140 115 115 2.9 2.9 2.9 180 145 152 1.9 1.9 1.9 215 175 188 1.3 1.3 1.3 255 210 228 1.0 1.0 1.0 315 260 291 0.7 0.7 0.7
2) Two cores with aluminum conductor Nominal area of conductor mm² 25* 35* 50 70 95
Two Cores Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 135 110 112 3.1 3.1 3.1 165 130 138 2.2 2.2 2.2 195 155 166 1.7 1.7 1.7 240 195 211 1.1 1.1 1.1 288 237 254 0.8 0.8 0.8
3) Three cores with copper conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400
24
Three Cores Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 115 94 99 2.5 2.5 2.5 150 125 131 1.7 1.7 1.7 180 150 162 1.2 1.2 1.2 215 175 197 0.9 0.9 0.9 265 215 251 0.6 0.6 0.6 315 260 304 0.5 0.5 0.5 360 300 353 0.4 0.4 0.4 405 335 406 0.3 0.3 0.3 460 380 463 0.3 0.3 0.3 530 440 546 0.2 0.2 0.2 590 495 628 0.2 0.2 0.2 667 570 728 0.2 0.2 0.2
www.addison-tech.com
www.addison-cables.com
Caledonian Cables Power Cables cables PVC Insulation
BS5467 BS 6346
3) Three cores with aluminum conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400
Three Cores Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 89 72 74 4.2 4.2 4.2 115 94 98 2.7 2.7 2.7 135 110 120 1.9 1.9 1.9 165 135 145 1.4 1.4 1.4 200 165 185 1.0 1.0 1.0 240 200 224 0.7 0.7 0.7 275 230 264 0.6 0.6 0.6 310 255 305 0.5 0.5 0.5 350 295 350 0.4 0.4 0.4 410 340 418 0.3 0.3 0.3 460 385 488 0.3 0.3 0.3 520 443 562 0.2 0.2 0.2
4) Four cores with copper conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400 500
Four Cores Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 115 94 99 2.5 2.5 2.5 150 125 131 1.7 1.7 1.7 180 150 162 1.2 1.2 1.2 215 175 197 0.9 0.9 0.9 265 215 251 0.6 0.6 0.6 315 260 304 0.5 0.5 0.5 360 300 353 0.4 0.4 0.4 405 335 406 0.3 0.3 0.3 460 380 463 0.3 0.3 0.3 530 440 546 0.2 0.2 0.2 590 495 628 0.2 0.2 0.2 667 570 728 0.2 0.2 0.2 720 605 800 0.2 0.2 0.2
www.caledonian-cables.co.uk
www.caledonian-cables.com
25
Addison Cables BS5467 BS 6346
Power Cables PVC Insulation Cables
4) Four cores with aluminum conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400 500
Four Cores Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 89 72 74 4.2 4.2 4.2 115 94 98 2.7 2.7 2.7 135 110 120 1.9 1.9 1.9 165 135 145 1.4 1.4 1.4 200 165 185 1.0 1.0 1.0 240 200 224 0.7 0.7 0.7 275 230 264 0.6 0.6 0.6 310 255 305 0.5 0.5 0.5 350 295 350 0.4 0.4 0.4 410 340 418 0.3 0.3 0.3 460 385 488 0.3 0.3 0.3 520 443 562 0.2 0.2 0.2 561 470 618 0.2 0.2 0.2
Electrical Properties(1900/3300 V) Nominal area of conductor mm² 50 70 95 120 150 185 240 300 400 500 630 800 1000
26
Single Core Stranded Copper Conductors Current Ratings In single Installed Direct in way ground in air ducts amps 222 271 324 366 409 460 528 589 651 720 789 831 880
amps 219 264 310 342 376 414 464 506 535 579 624 650 689
amps 228 285 350 407 463 528 623 710 808 915 1030 1119 1214
Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 -
www.addison-tech.com
Three Core Stranded Copper Conductors Current Ratings In single Direct in Installed way ground in air ducts amps 114 147 175 207 254 304 345 387 436 502 563 -
amps 96 124 147 174 214 257 293 328 371 428 480 -
www.addison-cables.com
amps 106 142 168 202 255 312 361 410 471 554 634 -
Caledonian Cables Power Cables cables PVC Insulation
www.caledonian-cables.co.uk
www.caledonian-cables.com
BS5467 BS 6346
27