Caledonian BS 6346 PVC Insulated, Armored Power and Control Cables

www.caledonian-cables.co.uk www.caledonian-cables.com

Addison


Company Profile Caledonian. established in 1978.offers one of the most complete lines of fiber and copper cabling system solutions with over hundreds of different cabling system products. . Our superior products provide leading edge within every cable series and for every application. Among the national and international standards with which our cables could comply are: BS - British Standard; LPCB Fire Performance Standard. ISO Standard etc. Caledonian Cables offers a comprehensive stock of cables and cabling products through its nationwide network of resellers and distributors. Caledonian Cables has continually expanded its global presence in Europe and Asia. Caledonian & Addison. produces a wide range of cables for communication. power and electronics in its primary plants in UK. Italy and Spain. To stay in front. we continually keep expanding our manufacturing capabilities in more low cost region such as Romania. Taiwan. Malaysia etc. This low-cost manufacturing facilities enable us provide a flexible. scalable global system that delivers superior operational performance and optimal results for our customers. Our extensive global network of manufacturing facilities gives us significant scale and the flexibility to fulfill our customer requirements. This global presence provides design and consultancy solutions that are combined with core cable manufacturing. logistic services. and vertically integrated with our E commerce technologies. to optimize customer operations by lowering costs and reducing time to market. Caledonian & Addison has been respected for its high standards of quality. excellent service level. competitive pricing and a unique and innovative spirit. With our latest technologies. we are both inspired and well-positioned to meet the changing needs of our customers. We have the resources to diversify and to enhance our product lines and services. We understand the need for change and with our accurate planning. we are ready for the future and the promise of new marketing opportunities. Our tradition of growth through excellence is assured. Our Design Centers work closely with customers to constantly improve its standard range of products and technologies and to develop customized. country and industry-specific solutions. Caledonian & Addison has established an extensive network of design. manufacturing. and logistics facilities in the world’s major markets to serve the growing outsourcing needs of both multinational and regional customers.


Our Certificate


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation Cables

Table of Contents BS 6346 PVC Insulated Cables, 600/1000V................................................5 BS 6346 PVC Insulated Cables, 1900/3300V............................................17 Technical Reference..................................................................................21

4

www.addison-tech.com

www.addison-cables.com


Caledonian Cables Power Cables 600/1000V PVC Insulation,

BS5467 BS 6346

BS 6346 PVC Insulated Cables, 600/1000V Application These power and control cables are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...).

Construction Conductor

Filler(optional)

Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228. PVC(Polyvinyl Chloride) type TI1 1 Core : Brown 2 Cores: Brown or Blue 3 Cores: Brown, Black, Grey 4 Cores: Blue, Brown, Black, Grey 5 Cores: Green-yellow, Blue, Brown, Black, Grey Above 5 Cores: White Cores with black numbers PVC or Polypropylene yarn

Binder Tape(optional)

Polyester (Mylar) tape

Insulation Colour Code

Inner Sheath/ Bedding PVC (Polyvinyl Chloride) Armour Single Core: AWA (Aluminum Wire Armour) Multi Core: SWA (Steel Wire or Tape Armour) Outer Sheath PVC(Polyvinyl Chloride), type TM1

Technical Information Voltage rating

600/1000V

Temperature rating

-20°C to +60°C

Bending radius

Single core: 10 x overall diameter

Multicores: 8 x overall diameter

Flame retardant

IEC60332 part 1, BS4066 part 1

www.caledonian-cables.co.uk

www.caledonian-cables.com

5


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 600/1000V

Cable Parameter Single-core 600/1000V cables with circular stranded copper conductor PVC bedding PVC insulation Plain copper conductor Aluminum wire armour PVC jacket Nominal crosssectional area mm²

6

Nominal sheath thickness

Approx. overall diameter

Approx. cable weight

mm

Nominal alum wire armor dia. mm

mm

mm

kg/km

1.4

0.8

1.25

1.5

19.1

820

19/2.14

1.4

0.8

1.25

1.6

21.1

1070

1x95

19/2.52

1.6

0.8

1.25

1.6

23.4

1390

1x120

37/2.03

1.6

1.0

1.6

1.7

26.3

1600

1x150

37/2.25

1.8

1.0

1.6

1.7

28.3

1900

1x185

37/2.52

2.0

1.0

1.6

1.8

30.8

2450

1x240

61/2.25

2.2

1.0

1.6

1.9

34.1

3100

1x300

61/2.52

2.4

1.0

1.6

1.9

37.0

3760

1x400

61/2.85

2.6

1.2

2.0

2.1

42.0

4850

1x500

61/3.20

2.8

1.2

2.0

2.1

45.6

5930

1x630

61/3.65

2.8

1.2

2.0

2.2

49.7

7390

1x800

127/2.85

2.8

1.4

2.5

2.4

55.8

9400

1x1000

127/3.20

3.0

1.4

2.5

2.5

61.0

11430

Number/ wire

Nominal insulation thickness

Nominal bedding thickness

No./mm

mm

1x50

19/1.78

1x70

www.addison-tech.com

www.addison-cables.com


Caledonian Cables BS5467 BS 6346

Power Cables 600/1000V PVC Insulation,

Single-core 600/1000V cables with solid aluminum conductor PVC bedding PVC insulation Aluminum conductor Aluminum wire armour PVC jacket Nominal Nominal Nominal Nominal alum crossbedding insulation wire sectional thickness thickarmor area ness dia. mm² mm mm mm

Nominal sheath thickness width

Armour strip thickness mm

mm

mm

Approx. overall diameter wire strip armor armor mm mm

Approx. cable weight kg/km

1x50

1.4

0.8

1.25

0.6

2.4

1.5

17.8

16.5

530

1x70

1.4

0.8

1.25

0.6

2.4

1.6

19.6

18.3

650

1x95

1.6

0.8

1.25

0.6

2.4

1.6

21.7

20.4

810

1x120

1.6

1

1.6

0.6

2.4

1.7

24.3

22.3

960

1x150

1.8

1

1.6

0.6

2.4

1.7

26.1

24.1

1115

1x185

2

1

1.6

1

3.6

1.8

28.3

27.1

1315

1x240

2.2

1

1.6

1

3.6

1.9

31.2

30

1610

1x300

2.4

1

1.6

1

3.6

1.9

33.7

32.5

1890

www.caledonian-cables.co.uk

www.caledonian-cables.com

7


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 600/1000V

Two-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal Nominal Nominal Nominal Nominal crossbedding wire sheath insulation sectional Number/ thickarmor thickwire thickness area ness dia. ness mm² No./mm mm mm mm mm

Approx. overall diameter extruded taped bedding bedding mm mm

kg/mm

2x1.5

7/0.53

0.6

0.8

0.9

1.4

12.3

-

270

2x2.5

7/0.67

0.7

0.8

0.9

1.4

13.6

-

350

2x4

7/0.85

0.8

0.8

0.9

1.4

15.1

-

470

2x6

7/1.04

0.8

0.8

0.9

1.5

16.5

-

580

2x10

7/1.35

1.0

0.8

1.25

1.6

20.1

-

840

2x16

7/1.70

1.0

0.8

1.25

1.6

21.9

21.9

990

2x25

7/2.14

1.2

1.0

1.6

1.7

26.7

26.3

1480

2x25*

7/2.14

1.2

1.0

1.6

1.7

23.0

22.6

1480

2x35

19/1.53

1.2

1.0

1.6

1.8

29.2

28.8

1770

2x35*

19/1.53

1.2

1.0

1.6

1.8

24.8

24.4

1770

2x50*

19/1.78

1.4

1.0

1.6

1.9

27.8

27.4

1900

2x70*

19/2.14

1.4

1.0

1.6

1.9

30.4

30.0

2430

2x95*

19/2.52

1.6

1.2

2.0

2.1

35.5

34.7

2970

2x120*

37/2.03

1.6

1.2

2.0

2.2

38.0

37.2

3970

2x150*

37/2.25

1.8

1.2

2.0

2.3

41.3

40.5

4700

2x185*

37/2.52

2.0

1.4

2.5

2.4

46.4

45.2

5990

2x240*

61/2.25

2.2

1.4

2.5

2.5

51.2

50.0

7420

2x300*

61/2.52

2.4

1.6

2.5

2.7

56.4

54.8

8950

2x400*

61/2.85

2.6

1.6

2.5

2.9

61.9

60.3

11030

*Shaped stranded conductor (class 2)

8

Approx. cable weight

www.addison-tech.com

www.addison-cables.com


mm

1

1.2

1.2

1.2

1.2

1.4

1.4

1.6

mm²

www.caledonian-cables.co.uk

2x16

2x25

2x25*

2x35

2x35*

2x50*

2x70*

2x95*

www.caledonian-cables.com

1.2

1

1

1

1

1

1

0.8

mm

Nominal bedding thickness

 2.0

1.6

1.6

1.6

1.6

1.6

1.6

1.25

mm

Nominal wire armor dia.

1

1

0.6

0.6

0.6

0.6

0.6

0.6

mm

thickness

3.6

3.6

2.4

2.4

2.4

2.4

2.4

2.4

mm

width

Armour strip

2.1

1.9

1.9

1.8

1.8

1.7

1.7

1.6

mm

Nominal sheath thickness

32.4

27.7

25.5

22.9

27.2

21.3

25

20.6

31.6

27.3

25.1

22.5

26.8

20.9

24.6

20.6

wire armor extruded taped bedding bedding mm mm

29.6

26.1

23.1

20.5

24.8

18.9

22.6

19.3

mm

strip armor

Approx. overall diameter

2200

1560

1450

1340

1340

1170

1170

795

kg/km

Approx. cable weight

Power Cables 600/1000V PVC Insulation,

*Solid shaped conductor (class 1)

Nominal insulation thickness

Nominal crosssectional area

PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket

Two-core 600/1000V cables with solid aluminum conductors

Caledonian Cables BS5467 BS 6346

9


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 600/1000V

Three-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal Nominal Nominal Nominal Nominal crossbedding wire sheath insulation sectional Number/ thickarmor thickwire thickness area ness dia. ness mm² No./mm mm mm mm mm

Approx. overall Approx. diameter cable extruded taped weight bedding bedding mm mm kg/mm

3x1.5

7/0.53

0.6

0.8

0.9

1.4

12.8

-

307

3x2.5

7/0.67

0.7

0.8

0.9

1.4

14.1

-

387

3x4

7/0.85

0.8

0.8

0.9

1.4

15.8

-

493

3x6

7/1.04

0.8

0.8

1.25

1.5

18.0

-

701

3x10

7/1.35

1.0

0.8

1.25

1.6

21.2

-

967

3x16

7/1.70

1.0

0.8

1.25

1.6

23.1

23.1

1219

3x25

7/2.14

1.2

1.0

1.6

1.7

28.2

27.8

1612

3x25*

7/2.14

1.2

1.0

1.6

1.7

25.0

24.6

1612

3x35

19/1.53

1.2

1.0

1.6

1.8

30.8

30.4

1992

3x35*

19/1.53

1.2

1.0

1.6

1.8

27.1

26.7

1992

3x50*

19/1.78

1.4

1.0

1.6

1.9

30.5

30.1

2534

3x70*

19/2.14

1.4

1.2

2.0

2.0

35.0

34.2

3518

3x95*

19/2.52

1.6

1.2

2.0

2.1

39.3

38.5

4510

3x120*

37/2.03

1.6

1.2

2.0

2.2

42.2

41.4

5375

3x150*

37/2.25

1.8

1.4

2.5

2.4

47.5

46.3

6810

3x185*

37/2.52

2.0

1.4

2.5

2.5

51.9

50.7

8190

3x240*

61/2.25

2.2

1.6

2.5

2.6

57.8

56.2

10280

3x300*

61/2.52

2.4

1.6

2.5

2.8

63.2

61.6

12430

3x400*

61/2.85

2.6

1.6

2.5

3.0

69.6

68.0

15400

*Shaped stranded conductor (class 2)

10

www.addison-tech.com

www.addison-cables.com


www.caledonian-cables.co.uk

1

1.2

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2

2.2

2.4

3x16

3x25

3x25*

3x35

3x35*

3x50*

3x70*

3x95*

www.caledonian-cables.com

3x120*

3x150*

3x185*

3x240*

3x300*

1.6

1.6

1.4

1.4

1.2

1.2

1.2

1

1

1

1

1

0.8

mm

Nominal bedding thickness

2.5

2.5

2.5

2.5

2

2

2

1.6

1.6

1.6

1.6

1.6

1.25

mm

Nominal wire armor dia.

1.8

1.8

1.4

1.4

1.4

1.4

1

1

0.6

0.6

0.6

0.6

0.6

mm

thickness

6.4

6.4

4.8

4.8

4.8

4.8

3.6

3.6

2.4

2.4

2.4

2.4

2.4

mm

width

Armour strip

2.8

2.6

2.5

2.4

2.2

2.1

2

1.9

1.8

1.8

1.7

1.7

1.6

mm

Nominal sheath thickness

59.2

54.2

48.7

44.7

39.7

37.1

33

28.9

28.7

26.4

25.8

23.9

21.7

57.6

52.6

47.5

43.5

38.9

36.3

32.2

28.5

28.3

26.0

25.4

23.5

21.7

wire armor extruded taped bedding bedding mm mm

56.2

51.2

45.3

41.3

37.7

35.1

30.2

26.4

27.3

24.1

23.4

21.5

20.4

mm

strip armor

Approx. overall diameter

6850

5820

4730

4020

3145

2745

2220

1610

1345

1345

1150

1150

925

kg/km

Approx. cable weight

Power Cables 600/1000V PVC Insulation,

*Solid shaped conductor (class 1)

mm

mm²

Nominal Nominal crossinsulation sectional thickness area

PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket

Three-core 600/1000V cables with solid aluminum conductors

Caledonian Cables BS5467 BS 6346

11


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 600/1000V

Four-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal Nominal Nominal Nominal Nominal crossbedding wire sheath insulation sectional Number/ thickarmor thickwire thickness area ness dia. ness mm² No./mm mm mm mm mm

Approx. overall diameter extruded taped bedding bedding mm mm

kg/mm

4x1.5

7/0.53

0.6

0.8

0.9

1.4

13.5

-

330

4x2.5

7/0.67

0.7

0.8

0.9

1.4

15.0

-

430

4x4

7/0.85

0.8

0.8

1.25

1.5

17.8

-

640

4x6

7/1.04

0.8

0.8

1.25

1.5

19.2

-

770

4x10

7/1.35

1.0

0.8

1.25

1.6

22.8

-

1070

4x16

7/1.70

1.0

1.0

1.6

1.7

26.3

25.9

1550

4x25

7/2.14

1.2

1.0

1.6

1.8

30.7

30.3

2005

4x25*

7/2.14

1.2

1.0

1.6

1.8

27.8

27.4

2005

4x35

19/1.53

1.2

1.0

1.6

1.9

33.7

33.3

2490

4x35*

19/1.53

1.2

1.0

1.6

1.9

30.3

29.9

2490

4x50*

19/1.78

1.4

1.2

2.0

2.0

35.4

34.6

3475

4x70*

19/2.14

1.4

1.2

2.0

2.1

39.2

38.4

4480

4x95*

19/2.52

1.6

1.2

2.0

2.2

43.3

43.5

5710

4x120*

37/2.03

1.6

1.4

2.5

2.4

49.3

48.1

7350

4x150*

37/2.25

1.8

1.4

2.5

2.5

53.6

52.4

8720

4x185*

37/2.52

2.0

1.6

2.5

2.6

59.0

57.4

10540

4x240*

61/2.25

2.2

1.6

2.5

2.8

65.7

64.1

13290

4x300*

61/2.52

2.4

1.6

2.5

3.0

72.0

70.4

16050

4x400*

61/2.85

2.6

1.8

3.15

3.3

81.3

79.3

20950

*Shaped stranded conductor (class 2)

12

Approx. cable weight

www.addison-tech.com

www.addison-cables.com


www.caledonian-cables.co.uk

1

1.2

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2

2.2

2.4

4x16

4x25

4x25*

4x35

4x35*

4x50*

4x70*

4x95*

www.caledonian-cables.com

4x120*

4x150*

4x185*

4x240*

4x300*

1.6

1.6

1.6

1.4

1.4

1.2

1.2

1.2

1

1

1

1

1

mm

Nominal bedding thickness

2.5

2.5

2.5

2.5

2.5

2

2

2

1.6

1.6

1.6

1.6

1.6

Nominal alum wire armor dia. mm

1.8

1.8

1.8

1.4

1.4

1.4

1

1

0.6

0.6

0.6

0.6

0.6

mm

thickness

6.4

6.4

6.4

4.8

4.8

4.8

3.6

3.6

2.4

2.4

2.4

2.4

2.4

mm

width

Armour strip

3

2.8

2.6

2.5

2.4

2.2

2.1

2

1.9

1.9

1.8

1.8

1.7

mm

Nominal sheath thickness

67

61.2

55.1

50.1

46.1

41.5

36.8

33.3

28.6

31.3

26.3

28.7

24.7

65.4

59.6

53.5

48.9

44.9

40.7

36.0

32..5

28.2

30.9

25.9

28.3

24.3

wire armor extruded taped bedding bedding mm mm

64

58.2

52.1

46.7

42.7

39.5

34

30.5

26.2

28.9

23.9

26.3

22.3

mm

strip armor

Approx. overall diameter

8610

7340

5960

5000

4380

3360

2750

2240

1625

1625

1390

1390

1125

kg/km

Approx. cable weight

Power Cables 600/1000V PVC Insulation,

*Solid shaped conductor (class 1)

mm

mm²

Nominal Nominal crossinsulation sectional thickness area

PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket

Four-core 600/1000V cables with solid aluminum conductors

Caledonian Cables BS5467 BS 6346

13


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 600/1000V

3+1 Core (4 Core with reduced neutral) 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket

mm²

mm²

mm

mm

mm

Nominal wire armor dia. mm

3x10

3x6

1.0

0.8

1.0

1.25

1.8

23.4

1370

3x16

3x10

1.0

1.0

1.0

1.25

1.8

25.0

1620

3x25*

3x16

1.2

1.0

1.0

1.6

1.8

27.8

1900

3x35*

3x16

1.2

1.0

1.0

1.6

1.8

29.5

2300

3x50*

3x25

1.4

1.2

1.0

1.6

1.9

33.1

3050

3x70*

3x35

1.4

1.2

1.2

2.0

2.0

38.0

4130

3x95*

3x50

1.6

1.4

1.2

2.0

2.2

43.7

5370

3x120*

3x70

1.6

1.4

1.4

2.5

2.3

49.0

6840

3x150*

3x70

1.8

1.4

1.4

2.5

2.4

52.0

8040

3x185*

3x95

2.0

1.6

1.4

2.5

2.5

57.2

9760

3x240*

3x120

2.2

1.6

1.6

2.5

2.7

63.7

12210

3x300*

3x150

2.4

1.8

1.6

2.5

2.9

69.8

14840

3x300*

3x185

2.4

2.0

1.6

2.5

2.9

71.8

17730

3x400*

3x185

2.6

2.0

1.8

3.15

3.1

78.6

19090

Nominal crosssectional area Phase Neutral

Nominal insulation thickness Phase Neutral

Nominal bedding thickness

Nominal sheath thickness

Approx. Overall Diameter

Approx. cable weight

mm

mm

kg/mm

*Shaped stranded conductor (class 2)

14

www.addison-tech.com

www.addison-cables.com


Caledonian Cables BS5467 BS 6346

Power Cables 600/1000V PVC Insulation,

Five-core 600/1000V cables with stranded copper conductors PVC bedding Plain copper conductor PVC insulation Steel wire armour PVC jacket

Number/ wire

Nominal insulation thickness

No./mm

mm

Nominal bedding thickness mm

5x1.5

7/0.53

0.6

0.8

0.9

1.4

14.3

-

430

5x2.5

7/0.67

0.7

0.8

0.9

1.5

16.3

-

545

5x4

7/0.85

0.8

0.8

1.25

1.5

19.0

-

790

5x6

7/1.04

0.8

0.8

1.25

1.6

20.9

-

880

5x10

7/1.35

1.0

1.0

1.6

1.7

25.8

-

1150

5x16

7/1.70

1.0

1.0

1.6

1.7

28.4

28.0

1670

5x25

7/2.14

1.2

1.0

1.6

1.9

33.5

33.1

2250

5x35

19/1.53

1.2

1.0

1.6

1.9

36.6

36.2

2670

5x50

19/1.78

1.4

1.2

2.0

2.1

43.0

42.2

3590

5x70

19/2.14

1.4

1.2

2.0

2.2

48.1

47.3

4610

www.caledonian-cables.co.uk

Nominal Nominal wire sheath armor thickdia. ness mm mm

Approx. overall Approx. diameter cable extruded taped weight bedding bedding mm mm kg/mm

Nominal crosssectional area mm²

www.caledonian-cables.com

15


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 600/1000V

Multi-core 600/1000V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket

No. of Cores

16

Nominal Nominal Nominal Nominal crossNumber/ insulation bedding alum wire sectional wire thickthickness armor dia. area ness mm² No./mm mm mm mm

Nominal sheath thickness mm

Approx. overall diameter

Approx. cable weight

mm

kg/mm

7

1.5

7/0.53

0.6

0.8

0.9

1.4

15.2

500

10

1.5

7/0.53

0.6

0.8

1.25

1.5

18.6

780

12

1.5

7/0.53

0.6

0.8

1.25

1.5

19.4

830

19

1.5

7/0.53

0.6

0.8

1.25

1.6

22.2

1090

27

1.5

7/0.53

0.6

1.0

1.6

1.7

26.7

1600

37

1.5

7/0.53

0.6

1.0

1.6

1.8

29.2

1940

48

1.5

7/0.53

0.6

1.0

1.6

1.9

32.9

2360

7

2.5

7/0.67

0.7

0.8

1.25

1.5

18.0

750

10

2.5

7/0.67

0.7

0.8

1.25

1.6

21.8

1000

12

2.5

7/0.67

0.7

0.8

1.25

1.6

22.4

1080

19

2.5

7/0.67

0.7

1.0

1.6

1.7

26.6

1640

27

2.5

7/0.67

0.7

1.0

1.6

1.8

30.7

2110

37

2.5

7/0.67

0.7

1.0

1.6

1.9

34.0

2600

48

2.5

7/0.67

0.7

1.2

2.0

2.1

39.5

3520

7

4

7/0.85

0.8

0.8

1.25

1.6

20.5

970

10

4

7/0.85

0.8

1.0

1.6

1.7

26.1

1500

12

4

7/0.85

0.8

1.0

1.6

1.7

26.8

1630

19

4

7/0.85

0.8

1.0

1.6

1.8

30.5

2170

27

4

7/0.85

0.8

1.2

2.0

2.0

37.1

3170

37

4

7/0.85

0.8

1.2

2.0

2.1

40.8

3910

48

4

7/0.85

0.8

1.2

2.0

2.2

46.0

4790

www.addison-tech.com

www.addison-cables.com


Caledonian Cables Power Cables 1900/3000V PVC Insulation,

BS5467 BS 6346

BS 6346 PVC Insulated Cables,1900/3300V Application These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour, so they are well adapted to underground use in industrial applications, in moist areas.

Construction Conductor

Filler(optional)

Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228. PVC(Polyvinyl Chloride) type TI1 1 Core : Brown 2 Cores: Brown or Blue 3 Cores: Brown, Black, Grey 4 Cores: Blue, Brown, Black, Grey 5 Cores: Green-yellow, Blue, Brown, Black, Grey Above 5 Cores: White Cores with black numbers PVC or Polypropylene yarn

Binder Tape(optional)

Polyester (Mylar) tape

Inner Sheath/ Bedding Armour

PVC (Polyvinyl Chloride) Single Core: AWA (Aluminum Wire Armour) Multi Core: SWA (Steel Wire or Tape Armour) PVC(Polyvinyl Chloride), type TM1

Insulation Colour Code

Outer Sheath

Technical Information Voltage rating

1900/3300V

Temperature rating -20°C to +60°C Bending radius

Single core: 10 x overall diameter

Multicores: 8 x overall diameter

Flame retardant

IEC60332 part 1, BS4066 part 1

www.caledonian-cables.co.uk

www.caledonian-cables.com

17


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 1900/3000V

Cable Parameter Single-core 1900/3300 V cables with circular stranded copper conductor PVC bedding PVC insulation Plain copper conductor Aluminum wire armour PVC jacket Nominal crosssectional area mm²

Nominal sheath thickness

Approx. overall diameter

Approx. cable weight

mm

Nominal alum wire armor dia. mm

mm

mm

kg/mm

2.2

0.8

1.25

1.6

21.0

840

19/2.14

2.2

0.8

1.25

1.6

22.8

1070

1x95

19/2.52

2.2

1.0

1.6

1.7

26.0

1445

1x120

37/2.03

2.2

1.0

1.6

1.7

27.7

1715

1x150

37/2.25

2.2

1.0

1.6

1.8

29.4

2010

1x185

37/2.52

2.2

1.0

1.6

1.8

31.3

2380

1x240

61/2.25

2.2

1.0

1.6

1.9

34.1

2975

1x300

61/2.52

2.4

1.0

1.6

1.9

37.0

3615

1x400

61/2.85

2.6

1.2

2.0

2.1

42.0

4655

1x500

61/3.20

2.8

1.2

2.0

2.1

45.6

5725

1x630

61/3.65

2.8

1.2

2.0

2.2

49.7

7150

1x800

127/2.85

2.8

1.4

2.5

2.4

55.8

9160

1x1000

127/3.20

3.0

1.4

2.5

2.5

61.0

11400

Number/ wire

Nominal insulation thickness

Nominal bedding thickness

No./mm

mm

1x50

19/1.78

1x70

Single-core 1900/3300 V cables with solid aluminum conductor PVC bedding PVC insulation Aluminum conductor Aluminum wire armour PVC jacket

18

www.addison-tech.com

www.addison-cables.com


Caledonian Cables BS5467 BS 6346

Power Cables 1900/3000V PVC Insulation, Nominal crosssectional area mm²

Nominal insulation thickness

Nominal bedding thickness

Nominal alum wire armor dia.

Nominal sheath thickness

Approx. overall diameter

Approx. cable weight

mm

mm

mm

mm

mm

kg/mm

1x50

2.2

0.8

1.25

1.6

19.8

625

1x70

2.2

0.8

1.25

1.6

21.3

735

1x95

2.2

1.0

1.6

1.7

24.3

965

1x120

2.2

1.0

1.6

1.7

25.6

1090

1x150

2.2

1.0

1.6

1.8

27.1

1250

1x185

2.2

1.0

1.6

1.8

28.8

1415

1x240

2.2

1.0

1.6

1.9

31.2

1680

1x300

2.4

1.0

1.6

1.9

33.7

1935

Three-core 1900/3300 V cables with stranded copper conductors PVC bedding PVC insulation Plain copper conductor Steel wire armour PVC jacket Nominal crosssectional area mm²

Nominal sheath thickness

Approx. overall diameter

Approx. cable weight

mm

Nominal wire armor dia. mm

mm

mm

kg/mm

2.2

1.0

1.6

1.8

30.3

1700

7/2.14

2.2

1.0

1.6

1.8

33.1

2085

3x35

19/1.53

2.2

1.0

1.6

1.9

35.8

2405

3x35*

19/1.53

2.2

1.0

1.6

1.9

32.1

2405

3x50*

19/1.78

2.2

1.2

2.0

2.0

35.6

3160

3x70*

19/2.14

2.2

1.2

2.0

2.1

38.9

3925

3x95*

19/2.52

2.2

1.2

2.0

2.2

42.3

4860

3x120*

37/2.03

2.2

1.4

2.5

2.3

46.6

6205

3x150*

37/2.25

2.2

1.4

2.5

2.4

49.4

7175

3x185*

37/2.52

2.2

1.4

2.5

2.5

52.8

8320

3x240*

61/2.25

2.2

1.6

2.5

2.6

57.8

10395

3x300*

61/2.52

2.4

1.6

2.5

2.8

63.2

12575

3x400*

61/2.85

2.6

1.6

2.5

3.0

69.6

15325

Number/ wire

Nominal insulation thickness

Nominal bedding thickness

No./mm

mm

3x16

7/1.70

3x25

*Shaped stranded conductor (class 2)

www.caledonian-cables.co.uk

www.caledonian-cables.com

19


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation, 1900/3000V

Three-core 1900/3300 V cables with solid aluminum conductors PVC bedding PVC insulation Aluminum conductor Steel wire armour PVC jacket Nominal crosssectional area mm²

Nominal insulation thickness

Nominal bedding thickness

Nominal Armor dia.

Nominal sheath thickness

Approx. overall diameter

Approx. cable weight

mm

mm

mm

mm

mm

kg/mm

3x16

2.2

1.0

1.6

1.8

28.9

1630

3x25

2.2

1.0

1.6

1.8

31.3

1880

3x35

2.2

1.0

1.6

1.9

33.7

2145

3x35*

2.2

1.0

1.6

1.9

30.6

2145

3x50*

2.2

1.2

2.0

2.0

33.9

2880

3x70*

2.2

1.2

2.0

2.1

36.9

3340

3x95*

2.2

1.2

2.0

2.2

40.0

3870

3x120*

2.2

1.4

2.5

2.3

44.0

4980

3x150*

2.2

1.4

2.5

2.4

46.5

5585

3x185*

2.2

1.4

2.5

2.5

49.6

6250

3x240*

2.2

1.6

2.5

2.6

54.2

7315

3x300*

2.4

1.6

2.5

2.8

59.2

8365

*Shaped conductor (class 1)

20

www.addison-tech.com

www.addison-cables.com


Caledonian Cables Power Cables cables PVC Insulation

BS5467 BS 6346

Technical Reference Maximum resistance of conductor and armour for single-core cable having aluminum wire armour Nominal cross sectional area of conductor

Copper conductor

mm2 50 70 95 120 150 185 240 300 400 500 630 800 1 000

Ω 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176

Maximum resistance per km of cable at 20 °C Aluminum wire armour Aluminum Cables with stranded Cables with solid conductor copper conductor aluminum conductor 600/1000V 1900/3300 V 600/1000V 1900/3300 V Ω Ω Ω Ω Ω 0.641 1.3 0.75 1.4 0.79 0.443 0.75 0.67 0.84 0.73 0.32 0.67 0.61 0.75 0.67 0.253 0.61 0.42 0.69 0.47 0.206 0.42 0.39 0.47 0.43 0.164 0.38 0.37 0.42 0.4 0.125 0.34 0.34 0.38 0.37 0.1 0.31 0.31 0.35 0.34 — 0.22 0.22 — — — 0.2 0.2 — — — 0.18 0.18 — — — 0.13 0.13 — — — 0.12 0.12 — —

Maximum resistance of conductor and armour for two-, three-, four- and five-core cables having wire armour 1) With stranded copper conductor Nominal cross sectional area of conductor

Copper conductor

mm2 1.5 2.5 4 6 10 16

Ω 12.1 7.41 4.61 3.08 1.83 1.15

Maximum resistance per km of cable at 20 °C Steel wire armour Cables with stranded copper conductors Aluminum TwoFourFiveThree-core conductor core core core 600/ 600/ 1900/ 600/ 600/ 1000V 1000V 3300 V 1000V 1000V Ω Ω Ω Ω Ω Ω — 10.2 9.5 — 8.8 8.2 — 8.8 8.2 — 7.7 6.8 — 7.9 7.5 — 6.8 6.2 — 7 6.7 — 4.3 3.9 — 6 4 — 3.7 3.4 1.91 3.7 3.5 1.9 3.1 2.2

www.caledonian-cables.co.uk

www.caledonian-cables.com

21


Addison Cables BS5467 BS 6346

Nominal cross sectional area of conductor

Copper conductor

mm2 25 35 50 70 95 120 150 185 240 300 400

Ω 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 1 0.075 4 0.060 1 0.047 0

Power Cables PVC Insulation Cables Maximum resistance per km of cable at 20 °C Steel wire armour Cables with stranded copper conductors Aluminum TwoFourFiveThree-core conductor core core core 600/ 600/ 1900/ 600/ 600/ 1000V 1000V 3300 V 1000V 1000V Ω Ω Ω Ω Ω Ω 1.2 3.7 2.5 1.7 2.0 2.3 1.8 0.868 2.6 2.3 1.8 — 1.6 0.641 2.3 2 1.3 1.8 1.1 0.443 2 1.8 1.2 1.2 0.94 0.32 1.4 1.3 1.1 1.1 — 0.253 1.3 1.2 0.76 0.76 — 0.206 1.2 0.78 0.71 0.68 — 0.164 0.82 0.71 0.65 0.61 — 0.125 0.73 0.63 0.59 0.54 — 0.1 0.67 0.58 0.55 0.49 — — 0.59 0.52 0.5 0.35 —

2) With solid aluminum conductor Nominal crosssectional area of conductor mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

22

Copper conductor Ω 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 1 0.075 4 0.060 1 0.047 0

Maximum resistance per km of cable at 20 °C Steel wire armour Cables with solid aluminum conductors Aluminum Two-core Three-core Four-core conductor 600/1000V 600/1000V 1900/3300 V 600/ 1000V Ω — — — — — 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 —

Ω — — — — — 4 4.1 2.9 2.6 2.3 1.6 — — — — — —

www.addison-tech.com

Ω — — — — — 3.8 2.7 2.5 2.2 1.9 1.4 1.2 0.86 0.76 0.68 0.63 —

Ω — — — — — 2 1.9 1.9 1.4 1.3 1.2 0.82 0.76 0.71 0.64 0.59 —

www.addison-cables.com

Ω — — — — — 3.4 2.4 2.2 1.9 1.3 1.2 0.82 0.74 0.67 0.59 0.54 —


Caledonian Cables Power Cables cables PVC Insulation

BS5467 BS 6346

Electrical Properties(600/1000V) 1) Single core with copper conductor Nominal area of conductor mm² 50 70 95 120 150 185 240 300 400 500 630 800 1000

Single Core Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 235 235 222 0.87 0.93 0.87 290 280 285 0.62 0.70 0.62 345 330 346 0.47 0.56 0.47 390 370 402 0.39 0.48 0.39 435 405 463 0.33 0.43 0.33 490 440 529 0.28 0.39 0.28 560 500 625 0.24 0.35 0.24 630 550 720 0.21 0.32 0.21 700 580 815 0.20 0.30 0.20 770 620 918 0.18 0.28 0.18 840 670 1027 0.17 0.26 0.17 888 692 1119 0.17 0.25 0.17 942 735 1214 0.16 0.24 0.16

1) Single core with aluminum conductor Nominal area of conductor mm² 50 70 95 120 150 185 240 300 400 500 630

Single Core Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 175 180 162 1.40 1.60 1.40 220 220 207 0.98 1.00 0.98 260 260 252 0.72 0.79 0.74 295 295 292 0.58 0.66 0.60 330 330 337 0.48 0.57 0.49 375 365 391 0.39 0.49 0.41 435 410 465 0.31 0.42 0.34 490 455 540 0.27 0.38 0.29 540 480 625 0.35 0.38 0.25 580 510 714 0.31 0.35 0.22 630 540 801 0.28 0.32 0.20

www.caledonian-cables.co.uk

www.caledonian-cables.com

23


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation Cables

2) Two cores with copper conductor Nominal area of conductor mm² 16* 25* 35* 50 70

Two Cores Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 140 115 115 2.9 2.9 2.9 180 145 152 1.9 1.9 1.9 215 175 188 1.3 1.3 1.3 255 210 228 1.0 1.0 1.0 315 260 291 0.7 0.7 0.7

2) Two cores with aluminum conductor Nominal area of conductor mm² 25* 35* 50 70 95

Two Cores Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 135 110 112 3.1 3.1 3.1 165 130 138 2.2 2.2 2.2 195 155 166 1.7 1.7 1.7 240 195 211 1.1 1.1 1.1 288 237 254 0.8 0.8 0.8

3) Three cores with copper conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400

24

Three Cores Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 115 94 99 2.5 2.5 2.5 150 125 131 1.7 1.7 1.7 180 150 162 1.2 1.2 1.2 215 175 197 0.9 0.9 0.9 265 215 251 0.6 0.6 0.6 315 260 304 0.5 0.5 0.5 360 300 353 0.4 0.4 0.4 405 335 406 0.3 0.3 0.3 460 380 463 0.3 0.3 0.3 530 440 546 0.2 0.2 0.2 590 495 628 0.2 0.2 0.2 667 570 728 0.2 0.2 0.2

www.addison-tech.com

www.addison-cables.com


Caledonian Cables Power Cables cables PVC Insulation

BS5467 BS 6346

3) Three cores with aluminum conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400

Three Cores Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 89 72 74 4.2 4.2 4.2 115 94 98 2.7 2.7 2.7 135 110 120 1.9 1.9 1.9 165 135 145 1.4 1.4 1.4 200 165 185 1.0 1.0 1.0 240 200 224 0.7 0.7 0.7 275 230 264 0.6 0.6 0.6 310 255 305 0.5 0.5 0.5 350 295 350 0.4 0.4 0.4 410 340 418 0.3 0.3 0.3 460 385 488 0.3 0.3 0.3 520 443 562 0.2 0.2 0.2

4) Four cores with copper conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Four Cores Stranded Copper Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 115 94 99 2.5 2.5 2.5 150 125 131 1.7 1.7 1.7 180 150 162 1.2 1.2 1.2 215 175 197 0.9 0.9 0.9 265 215 251 0.6 0.6 0.6 315 260 304 0.5 0.5 0.5 360 300 353 0.4 0.4 0.4 405 335 406 0.3 0.3 0.3 460 380 463 0.3 0.3 0.3 530 440 546 0.2 0.2 0.2 590 495 628 0.2 0.2 0.2 667 570 728 0.2 0.2 0.2 720 605 800 0.2 0.2 0.2

www.caledonian-cables.co.uk

www.caledonian-cables.com

25


Addison Cables BS5467 BS 6346

Power Cables PVC Insulation Cables

4) Four cores with aluminum conductor Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Four Cores Aluminum Conductors Approximate voltage drop per ampere Current Ratings per metre Direct in In single Installed in Ground Duct Air ground way ducts air amps amps amps mV mV mV 89 72 74 4.2 4.2 4.2 115 94 98 2.7 2.7 2.7 135 110 120 1.9 1.9 1.9 165 135 145 1.4 1.4 1.4 200 165 185 1.0 1.0 1.0 240 200 224 0.7 0.7 0.7 275 230 264 0.6 0.6 0.6 310 255 305 0.5 0.5 0.5 350 295 350 0.4 0.4 0.4 410 340 418 0.3 0.3 0.3 460 385 488 0.3 0.3 0.3 520 443 562 0.2 0.2 0.2 561 470 618 0.2 0.2 0.2

Electrical Properties(1900/3300 V) Nominal area of conductor mm² 50 70 95 120 150 185 240 300 400 500 630 800 1000

26

Single Core Stranded Copper Conductors Current Ratings In single Installed Direct in way ground in air ducts amps 222 271 324 366 409 460 528 589 651 720 789 831 880

amps 219 264 310 342 376 414 464 506 535 579 624 650 689

amps 228 285 350 407 463 528 623 710 808 915 1030 1119 1214

Nominal area of conductor mm² 16 25 35 50 70 95 120 150 185 240 300 -

www.addison-tech.com

Three Core Stranded Copper Conductors Current Ratings In single Direct in Installed way ground in air ducts amps 114 147 175 207 254 304 345 387 436 502 563 -

amps 96 124 147 174 214 257 293 328 371 428 480 -

www.addison-cables.com

amps 106 142 168 202 255 312 361 410 471 554 634 -


Caledonian Cables Power Cables cables PVC Insulation

www.caledonian-cables.co.uk

www.caledonian-cables.com

BS5467 BS 6346

27


Caledonian Cables Ltd Merchant Ind. Centre Mill-Lane, Laughton, Lewes, Sussex, BN8 6AJ England United Kingdom Tel: 44- 207- 4195087 Fax: 44- 207- 8319489 Email: sales@caledonian-cables.com sales@caledonian-cables.co.uk sales@caledonian-cables.net sales@addison-cables.com