MV-90 5 - 35 kV Single Conductors
Description Copper or aluminum stranded, thermo set insulated.
Contruction Conductor Copper or aluminum stranded, thermo set insulated. Conductor Shield Cross linked polyethylene semiconductor. Insulation Cross linked polyethylene XLPE. Insulation shield Cross linked polyethylene removable semiconductor Insulation and shields are applied by true triple extrusion process. Metallic shield Copper tape helically and overlapped applied over insulation shield, 2.5 mils (0.0635mm) thickness. Jacket Flame retardant polyvinyl chloride PVC. Options EPR or XLPE-TR (Tree retardant XLPE). Copper wires metallic shield. Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable type jacket. Moisture barrier against longitudinally migration. Armor for Direct Burial
Characteristics Operating Temperature Normal continuous operation 90째C for wet or dry locations (105째C optional). Overload 130째C. Short circuit 250째C. 7
Rated Voltage 5, 8, 15, 25 and 35 kV. Insulation Level 100% (133% and 173% optional).
Applications Distribution of electric energy at Medium Voltage, installed at air, underground ducts, raceways, direct buried or tray cables.
Standards CENTELSA’s 5-35 kV single conductors are manufactured in accordance with the following standards: ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded Copper Conductors. ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded Aluminum 1350 Conductors. UL 1072. Medium Voltage Power Cables MV90. ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV.
Certifications CENTELSA’s 5-35 kV single conductors are certified by: UL 1072. File E167359. ICONTEC (Colombia). NTC 2186 standard CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE. CIDET (Colombia). Cert. 00413. 35 kV Medium Voltage Copper, XLPE. CIDET (Colombia). Cert. 00414. 15 kV Medium Voltage Copper, EPR. CIDET (Colombia). Cert. 00415. 35 kV Medium Voltage Copper, EPR.
8
Note: Configurations and sizes herein not specified are available upon request.
MV-90 5 kV Single Conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
3.40 4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
8.4 13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
8.86 9.75 10.87 12.27 13.05 13.99 15.01 16.20 17.53 18.91 20.18 21.35 22.44 23.48 24.39 26.57 28.98 32.84
1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
13.20 14.88 16.00 17.40 18.18 19.12 20.14 22.35 23.68 25.06 26.33 27.50 28.59 29.63 30.54 33.30 35.71 39.57
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
245 333 428 571 665 785 933 1169 1401 1615 1875 2133 2389 2644 2896 3452 4203 5452
192 249 294 359 398 448 508 632 725 816 916 1014 1111 1206 1298 1534 1806 2255
2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
3.43 2.16 1.36 0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.4010 0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
9
15795 13740 11824 10081 9319 8544 7838 7150 6512 5961 5531 5187 4902 4659 4465 4060 3691 3221
MV-90 5 kV Single Conductors, 90째C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
134 169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90
349 384 428 483 514 551 591 638 690 744 794 841 883 924 960 1046 1141 1293
45 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80
520 586 630 685 716 753 793 880 932 987 1037 1083 1126 1167 1202 1311 1406 1558
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20째C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
164 224 287 384 447 528 627 786 942 1085 1260 1434 1606 1777 1946 2320 2825 3664
129 167 198 241 267 301 341 425 487 548 616 682 746 810 872 1031 1214 1515
0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
1.05 0.658 0.414 0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.6454 0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
10
9815 8538 7347 6264 5791 5309 4870 4443 4046 3704 3437 3223 3046 2895 2774 2523 2293 2002
MV-90 8 kV Single Conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
CROSS SECTION (mm2)
13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION THICKNESS (mm)
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
INSULATION JACKET DIAMETER THICKNESS (mm) (mm)
11.05 12.17 13.57 14.35 15.29 16.31 17.50 18.83 20.21 21.48 22.65 23.74 24.78 25.69 27.87 30.28 34.14
1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
OVERALL DIAMETER (mm)
16.18 17.30 18.70 19.48 20.42 22.46 23.65 24.98 26.36 27.63 28.80 29.89 30.93 32.42 34.60 37.01 40.87
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
368 465 611 707 829 1030 1220 1455 1671 1934 2194 2452 2709 2999 3524 4280 5535
285 332 399 440 492 605 683 778 872 975 1075 1173 1270 1400 1606 1882 2338
1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
2.16 1.36 0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
16338 14169 12171 11291 10388 9562 8752 7997 7341 6827 6414 6071 5778 5543 5052 4601 4027
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Single Conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115
INSULATION JACKET DIAMETER THICKNESS (mm) (mm)
435 479 534 565 602 642 689 741 796 846 892 935 976 1011 1097 1192 1344
60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80 80
OVERALL DIAMETER (mm)
637 681 736 767 804 884 931 984 1038 1088 1134 1177 1218 1276 1362 1457 1609
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
248 313 411 475 557 692 820 978 1123 1300 1474 1648 1820 2015 2368 2876 3720
191 223 268 295 330 406 459 523 586 655 722 788 854 941 1079 1265 1572
0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.658 0.414 0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
11
10152 8804 7563 7016 6455 5942 5438 4969 4562 4242 3985 3773 3590 3444 3139 2859 2502
MV-90 15 kV Single Conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 26.80 27.84 28.75 30.93 33.34 37.20
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79
22.78 23.56 24.50 25.52 26.71 28.04 29.42 30.69 32.44 33.53 34.57 35.48 37.66 40.07 45.50
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
768 869 997 1154 1349 1590 1813 2081 2383 2647 2909 3168 3703 4469 5900
556 601 660 729 813 914 1013 1122 1264 1368 1471 1569 1785 2071 2704
0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
16393 15303 14175 13131 12097 11123 10268 9592 9044 8588 8195 7879 7214 6600 5809
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Single Conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
175 175 175 175 175 175 175 175 175 175 175 175 175 175 175
655 685 722 763 809 862 916 966 1012 1055 1096 1132 1218 1313 1465
80 80 80 80 80 80 80 80 80 80 80 80 80 80 110
897 928 965 1005 1052 1104 1158 1208 1277 1320 1361 1397 1483 1578 1791
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
516 584 670 776 907 1069 1218 1398 1601 1779 1955 2129 2488 3003 3965
373 404 443 490 546 614 681 754 849 919 988 1055 1199 1392 1817
0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
12
10186 9509 8808 8160 7517 6912 6381 5960 5620 5337 5092 4896 4483 4101 3610
MV-90 25 kV Single Conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 27.53 28.80 29.97 31.06 32.10 33.01 35.19 37.60 41.46
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79
27.82 28.76 29.78 30.97 32.88 34.26 35.53 36.70 37.79 38.83 39.74 43.49 45.90 50.62
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1052 1186 1350 1552 1838 2071 2348 2622 2892 3161 3425 4125 4915 6309
785 849 924 1016 1162 1271 1389 1503 1614 1723 1827 2207 2518 3112
0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
19847 18509 17258 16006 14814 13758 12915 12227 11651 11150 10747 9893 9096 8060
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Single Conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
260 260 260 260 260 260 260 260 260 260 260 260 260 260
INSULATION JACKET DIAMETER THICKNESS (mm) (mm)
853 890 930 977 1030 1084 1134 1180 1223 1264 1300 1385 1480 1632
80 80 80 80 80 80 80 80 80 80 80 110 110 110
OVERALL DIAMETER (mm)
1095 1132 1173 1219 1295 1349 1399 1445 1488 1529 1565 1712 1807 1993
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
707 797 907 1043 1235 1391 1578 1762 1944 2125 2302 2772 3303 4240
527 571 621 683 781 854 933 1010 1085 1158 1228 1483 1692 2091
0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
13
12333 11501 10724 9946 9205 8549 8025 7598 7240 6929 6678 6147 5652 5008
MV-90 35 kV Single conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76
26.97 27.99 29.18 30.51 31.89 33.16 34.33 35.42 36.46 37.37 39.55 41.96 45.82
JACKET THICKNESS (mm)
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79
OVERALL DIAMETER (mm)
33.70 34.72 35.91 37.24 38.62 39.89 41.06 42.15 43.19 44.10 48.71 51.12 54.98
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1445 1616 1827 2086 2327 2612 2893 3171 3447 3716 4526 5335 6675
1108 1190 1291 1410 1528 1653 1775 1892 2008 2118 2608 2937 3479
0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
22170 20773 19366 18016 16810 15841 15047 14378 13794 13323 12318 11374 10136
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Single conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
345 345 345 345 345 345 345 345 345 345 345 345 345
INSULATION JACKET DIAMETER THICKNESS (mm) (mm)
1062 1102 1149 1201 1256 1306 1352 1394 1435 1471 1557 1652 1804
80 80 80 80 80 80 80 80 80 80 110 110 110
OVERALL DIAMETER (mm)
1327 1367 1414 1466 1521 1571 1617 1660 1700 1736 1918 2013 2164
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
971 1086 1228 1402 1564 1756 1945 2131 2316 2498 3042 3585 4486
744 800 867 947 1027 1111 1193 1272 1350 1423 1753 1974 2338
0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
14
13776 12908 12034 11195 10446 9844 9350 8934 8572 8279 7654 7068 6298
46 - 69 kV Single Conductors
Description Copper or aluminum stranded, thermo set insulated
Construction Conductor Soft Copper or 1350-H19 aluminum, compact stranded. Conductor Shield Cross linked polyethylene semiconductor. Insulation Cross linked polyethylene XLPE. Insulation shield Cross linked polyethylene removable semiconductor. Insulation and shields are applied by true triple extrusion process. Metallic shield Copper tape helically and overlapped applied over insulation shield, 2.5 mils (0.0635mm) thickness. Jacket Flame retardant polyvinyl chloride PVC. Options EPR or XLPE-TR (Tree retardant XLPE). Copper wires metallic shield. Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable type jacket. Moisture barrier against longitudinally migration. Armor for Direct Burial.
Characteristics Operating Temperature Normal continuous operation 90째C for wet or dry locations (105째C optional) Overload 130째C Short circuit 250째C 15
Rated Voltage 45 and 69 kV Insulation Level 100% (133% and 173% optional only for 46 kV)
Applications Distribution of electric energy at 46 and 69 kV, installed at air, underground ducts, raceways, direct buried or tray cables.
Standards CENTELSA’s 46-69 kV single conductors are manufactured in accordance with the following standards: ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded Copper Conductors. ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded Aluminum 1350 Conductors. AEIC CS6. Specification for Ethylene Propylene Rubber Insulated Shielded Power Cables Rated 5 through 69 kV. AEIC CS7. Specification for Cross Linked Polyethylene Insulated Shielded Power Cables Rated 69 through 138 kV.
Certifications CENTELSA’s 46 kV conductors are certified by CTL Laboratories.
Note: Configurations and sizes herein not specified are available upon request.
16
46 kV Single conductors, 90°C (International Unit System) 100% Insulation Level Standards: AEIC CS8 Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
4/0 250 300 350 400 450 500 600 750 1000
12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
11.30 11.30 11.30 11.30 11.30 11.30 11.30 11.30 11.30 11.30
35.63 37.01 38.28 39.45 40.54 41.58 42.49 44.67 47.08 50.94
JACKET THICKNESS (mm)
2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79
OVERALL DIAMETER (mm)
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
2565 2821 3199 3495 3786 4075 4356 4945 5772 7141
1889 2022 2240 2376 2508 2636 2758 3027 3374 3944
0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
43.93 45.31 47.44 48.61 49.70 50.74 51.65 53.83 56.24 60.10
0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
21236 19901 18822 17932 17180 16522 15988 14845 13764 12335
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
46 kV Single conductors, 90°C 100% Insulation Level Standards: AEIC CS8 Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
4/0 250 300 350 400 450 500 600 750 1000
475 520 570 616 659 700 736 813 908 1060
0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
445 445 445 445 445 445 445 445 445 445
1403 1457 1507 1553 1596 1637 1673 1759 1854 2006
JACKET THICKNESS (mm)
110 110 110 110 110 110 110 110 110 110
OVERALL DIAMETER (mm)
1729 1784 1868 1914 1957 1998 2033 2119 2214 2366
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1724 1896 2150 2349 2544 2738 2927 3323 3879 4799
1269 1359 1505 1597 1685 1772 1853 2034 2268 2651
0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
17
13196 12366 11696 11143 10676 10267 9935 9225 8553 7665
69 kV Single conductors, 90°C (International Unit System) 100% Insulation Level Standards: AEIC CS7 Specification for Cross Linked Polyethylene Insulated Shielded Power Cables Rated 69 through 138 kV, NTC 3599. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
500 600 750 1000
18.69 20.65 23.06 26.92
253.4 304.0 380.0 506.7
16.51 16.51 16.51 16.51
53.15 55.37 57.78 61.64
2.79 2.79 2.79 3.56
62.31 64.53 66.94 72.38
APPROXIMATE TOTAL WEIGHT (kg/km) COPPER
5318 5945 6809 8496
DC RESISTANT AT 20°C1 (ohm/km)
ALUMINUM
COPPER
ALUMINUM
3719 4027 4411 5299
0.0694 0.0578 0.0463 0.0347
0.113 0.0945 0.0756 0.0567
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.2683 0.2604 0.2521 0.2404
20509 19151 17879 16175
Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
69 kV Single conductors, 90°C 100% Insulation Level Standards: AEIC CS7 Specification for Cross Linked Polyethylene Insulated Shielded Power Cables Rated 69 through 138 kV, NTC 3599.
SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
500 600 750 1000
736 813 908 1060
0.393 0.471 0.589 0.785
650 650 650 650
2093 2180 2275 2427
110 110 110 140
2453 2540 2635 2850
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
3574 3995 4576 5709
2500 2706 2965 3561
0.0212 0.0176 0.0141 0.0106
0.0346 0.0288 0.0230 0.0173
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.4318 0.4191 0.4057 0.3869
Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
18
12744 11900 11110 10051
6 - 30 kV Single Conductors
Description Copper or aluminum stranded, thermo set insulated
Construction Conductor Soft Copper or 1350-H19 aluminum, compact stranded. Conductor Shield Cross linked polyethylene semiconductor. Insulation Cross linked polyethylene XLPE. Insulation shield Cross linked polyethylene removable semiconductor. Insulation and shields are applied by true triple extrusion process. Metallic shield Copper tape helically and overlapped applied over insulation shield, 2.5 mils (0.0635mm) thickness. Jacket Flame retardant polyvinyl chloride PVC. Options EPR or XLPE-TR (Tree retardant XLPE) Copper wires metallic shield. Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable type jacket. Moisture barrier against longitudinally migration. Armor for Direct Burial.
Characteristics Operating Temperature Normal continuous operation 90째C for wet or dry locations (105째C optional) Overload 130째C Short circuit 250째C 19
Rated Operating Voltage 6, 10, 15, 20 & 30 kV
Applications Distribution of electric energy at Medium Voltage, installed at air, underground ducts, raceways, direct buried or tray cables.
Standards CENTELSA’s 6-30 kV single conductors are manufactured in accordance with the following standards: IEC 60228 Conductors for insulated cables. IEC 60502-2. Power Cables with extruded insulation for voltages form 6 to 30 kV.
Note: Configurations and sizes herein not specified are available upon request.
20
3.6/6 (7.2) kV¹ Single conductors, 90°C
Standards: IEC 60502-2. Power Cables with extruded insulation for voltages from 6 to 30 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
10 16 25 35 50 70 95 120 150 185 240 300 400 500
3.72 4.70 5.88 6.96 8.26 9.77 11.39 12.88 14.40 15.99 18.29 20.45 23.62 26.41
Notes:
CROSS SECTION (mm2)
10.0 16.0 25.0 35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0 300.0 400.0 500.0
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
2.50 2.50 2.50 2.50 2.50 2.50 2.50 2.50 2.50 2.50 2.60 2.60 2.60 2.60
9.55 10.53 11.71 12.79 14.09 15.60 17.22 18.93 20.45 22.04 24.55 27.35 30.94 34.15
1.40 1.40 1.50 1.50 1.60 1.60 1.70 1.70 1.80 1.80 1.90 2.00 2.20 2.30
OVERALL DIAMETER (mm)
14.43 15.41 16.80 17.88 19.39 20.90 22.73 24.44 26.16 27.75 30.47 34.06 38.02 41.44
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
292 367 482 596 767 982 1255 1525 1844 2199 2777 3462 4512 5545
229 266 324 375 452 540 656 768 898 1032 1263 1569 1988 2391
1.76 1.10 0.703 0.502 0.352 0.251 0.185 0.147 0.117 0.0951 0.0733 0.0586 0.0440 0.0352
2.87 1.80 1.15 0.821 0.575 0.411 0.302 0.239 0.192 0.155 0.120 0.0958 0.0718 0.0575
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.3943 0.3766 0.3597 0.3470 0.3309 0.3182 0.3066 0.2964 0.2880 0.2801 0.2699 0.2611 0.2503 0.2418
16087 13941 12029 10697 9444 8318 7377 6592 6023 5525 5113 4909 4626 4458
1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage. 2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 19 cm separated. 4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
6/10 (12) kV¹ Single conductors, 90°C Standards: IEC 60502-2. Power Cables with extruded insulation for voltages from 6 to 30 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
16 25 35 50 70 95 120 150 185 240 300 400 500
4.70 5.88 6.96 8.26 9.77 11.39 12.88 14.40 15.99 18.29 20.45 23.62 26.41
16.0 25.0 35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0 300.0 400.0 500.0
3.50 3.50 3.50 3.50 3.50 3.50 3.50 3.50 3.50 3.50 3.50 3.50 3.50
INSULATION JACKET DIAMETER THICKNESS (mm) (mm)
12.59 13.77 14.85 16.15 17.66 19.28 20.99 22.51 24.10 26.40 28.80 31.97 34.76
1.50 1.60 1.60 1.60 1.70 1.70 1.80 1.90 1.90 2.00 2.10 2.20 2.30
OVERALL DIAMETER (mm)
17.68 19.07 20.15 21.45 23.17 24.79 26.70 28.43 30.02 33.11 35.68 39.05 42.05
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
434 554 672 839 1069 1337 1624 1950 2310 2924 3557 4576 5586
333 396 451 523 627 738 867 1003 1143 1410 1665 2052 2432
1.10 0.703 0.502 0.352 0.251 0.185 0.147 0.117 0.0951 0.0733 0.0586 0.0440 0.0352
1.80 1.15 0.821 0.575 0.411 0.302 0.239 0.192 0.155 0.120 0.0958 0.0718 0.0575
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.3766 0.3597 0.3470 0.3309 0.3182 0.3066 0.2964 0.2880 0.2801 0.2699 0.2611 0.2503 0.2418
Notes: 1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage. 2. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 7.5" separated. 4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
21
17650 15393 13797 12277 10892 9723 8736 8015 7380 6622 5982 5305 4826
8.7/15 (17.5) kV¹ Single conductors, 90°C
Standards: IEC 60502-2. Power Cables with extruded insulation for voltages from 6 to 30 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
25 35 50 70 95 120 150 185 240 300 400 500
5.88 6.96 8.26 9.77 11.39 12.88 14.40 15.99 18.29 20.45 23.62 26.41
25.0 35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0 300.0 400.0 500.0
4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50
15.74 16.82 18.12 19.63 21.25 22.96 24.48 26.07 28.37 30.77 33.94 36.73
1.60 1.70 1.70 1.80 1.80 1.90 1.90 2.00 2.10 2.20 2.30 2.40
21.04 22.33 23.63 25.34 26.96 28.88 30.40 32.78 35.25 37.85 41.23 44.22
Notes:
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
621 753 924 1160 1434 1727 2045 2462 3046 3692 4722 5742
464 532 609 719 834 970 1098 1295 1532 1799 2198 2588
0.703 0.502 0.352 0.251 0.185 0.147 0.117 0.0951 0.0733 0.0586 0.0440 0.0352
1.15 0.821 0.575 0.411 0.302 0.239 0.192 0.155 0.120 0.0958 0.0718 0.0575
INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm-km)
0.3597 0.3470 0.3309 0.3182 0.3066 0.2964 0.2880 0.2801 0.2699 0.2611 0.2503 0.2418
18169 16383 14666 13088 11742 10598 9757 9011 8116 7355 6547 5970
1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage. 2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 19 cm separated. 4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
12/20 (24) kV¹ Single conductors, 90°C Standards: IEC 60502-2. Power Cables with extruded insulation for voltages from 6 to 30 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
35 50 70 95 120 150 185 240 300 400 500
6.96 8.26 9.77 11.39 12.88 14.40 15.99 18.29 20.45 23.62 26.41
35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0 300.0 400.0 500.0
5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50
18.86 20.16 21.67 23.29 25.00 26.52 28.11 30.41 32.81 35.98 38.77
1.70 1.80 1.80 1.90 1.90 2.00 2.10 2.20 2.20 2.30 2.50
24.37 25.87 27.38 29.21 30.92 33.23 34.99 37.49 39.89 43.27 47.33
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
833 1020 1249 1541 1827 2202 2587 3183 3819 4860 5989
612 704 808 942 1070 1256 1420 1669 1927 2336 2835
0.502 0.352 0.251 0.185 0.147 0.117 0.0951 0.0733 0.0586 0.0440 0.0352
0.821 0.575 0.411 0.302 0.239 0.192 0.155 0.120 0.0958 0.0718 0.0575
0.3470 0.3309 0.3182 0.3066 0.2964 0.2880 0.2801 0.2699 0.2611 0.2503 0.2418
18759 16881 15140 13645 12365 11419 10575 9557 8688 7758 7092
Notes: 1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage. 2. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 7.5" separated. 4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
22
18/30 (36) kV¹ Single conductors, 90°C
Standards: IEC 60502-2. Power Cables with extruded insulation for voltages from 6 to 30 kV. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm2)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
50 70 95 120 150 185 240 300 400 500
8.26 9.77 11.39 12.88 14.40 15.99 18.29 20.45 23.62 26.41
50.0 70.0 95.0 120.0 150.0 185.0 240.0 300.0 400.0 500.0
8.00 8.00 8.00 8.00 8.00 8.00 8.00 8.00 8.00 8.00
25.10 26.61 28.23 29.94 31.46 33.05 35.35 37.75 40.92 43.71
1.90 2.00 2.10 2.10 2.20 2.20 2.30 2.40 2.60 2.60
31.02 33.32 35.11 36.82 38.54 40.13 42.64 45.24 49.69 52.48
Notes:
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C1 INDUCTIVE CAPACITIVE REACTANCE2 REACTANCE2 (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1264 1558 1864 2166 2519 2904 3520 4196 5369 6405
949 1116 1265 1409 1573 1737 2006 2303 2845 3251
0.352 0.251 0.185 0.147 0.117 0.0951 0.0733 0.0586 0.0440 0.0352
0.575 0.411 0.302 0.239 0.192 0.155 0.120 0.0958 0.0718 0.0575
0.3309 0.3182 0.3066 0.2964 0.2880 0.2801 0.2699 0.2611 0.2503 0.2418
1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage. 2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 19 cm separated. 4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
23
21431 19403 17638 16109 14965 13936 12682 11599 10429 9582
MV-90 5 - 35 kV Three Conductors
Description Three phases copper or aluminum stranded, thermo set insulated, stranded and with common PVC jacket.
Contruction Conductor Soft Copper or 1350-H19 aluminum, compact stranded. Conductor Shield Cross linked polyethylene semiconductor. Insulation Cross linked polyethylene XLPE. Insulation shield Cross linked polyethylene removable semiconductor. Insulation and shields are applied by true triple extrusion process. Metallic shield Copper tape helically and overlapped applied over insulation shield, 2.5 mils (0.0635mm) thickness. Filler Flame retardant polyvinyl chloride PVC, applied over the three stranded phases. Jacket Flame retardant polyvinyl chloride PVC. Options EPR or XLPE-TR (Tree retardant XLPE) Copper wires metallic shield. Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable type jacket. Moisture barrier against longitudinally migration. Ground conductors laid on interstices. Armor for Direct Burial. 24
Characteristics Operating Temperature Normal continuous operation 90°C for wet or dry locations (105°C optional) Overload 130°C Short circuit 250°C Rated Voltage 5, 8, 15, 25 and 35 kV. Insulation Level 100% (133% and 173% optional).
Applications Distribution of electric energy at Medium Voltage, installed at air, underground ducts, raceways, direct buried or tray cables.
Standards CENTELSA’s 5-35 kV three conductors are manufactured in accordance with the following standards: ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded Copper Conductors. ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded Aluminum 1350 Conductors. UL 1072. Medium Voltage Power Cables MV90. ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV.
25
Certifications CENTELSA’s 5-35 kV single conductors are certified by: UL 1072. File E167359. ICONTEC (Colombia). NTC 2186 standard CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE
Note: Configurations and sizes herein not specified are available upon request.
MV-90 5 kV Three conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (mm²) (mm) (mm)
3.40 4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
8.4 13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
8.86 9.75 10.87 12.27 13.05 13.99 15.01 16.20 17.53 18.91 20.18 21.35 22.44 23.48 24.39 26.57 28.98 32.84 Notes:
26
DIAMETER FILLER OVER THICKNESS TRANDED (mm) PHASE (mm)
23.34 25.26 27.67 30.69 32.37 34.39 36.59 39.16 42.02 45.00 47.73 50.26 52.60 54.85 56.81 62.75 67.95 76.27
0.50 0.50 0.50 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
JACKET THICKNESS (mm)
2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 3.56
OVERALL DIAMETER (mm)
28.52 30.44 32.85 36.87 38.55 40.58 44.34 46.90 49.77 52.74 55.48 58.00 60.35 62.59 64.55 72.09 77.28 85.60
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1101 1339 1688 2297 2638 3072 3755 4423 5245 6023 6938 7842 8737 9628 10498 12786 -
941 1084 1284 1654 1828 2050 2466 2797 3196 3601 4032 4452 4863 5269 5655 6975 8145 10113
2.12 1.34 0.840 0.528 0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 -
3.47 2.18 1.37 0.863 0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
0.1638 0.1522 0.1416 0.1320 0.1246 0.1204 0.1165 0.1128 0.1093 0.1067 0.1042 0.1022 0.1006 0.0992 0.0981 0.0977 0.0954 0.0924
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
15795 13740 11824 10081 9319 8544 7838 7150 6512 5961 5531 5187 4902 4659 4465 4060 3691 3221
MV-90 5 kV Three conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm²)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
134 169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
Notes:
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90
349 384 428 483 514 551 591 638 690 744 794 841 883 924 960 1046 1141 1293
DIAMETER OVER TRANDED PHASE (mm)
919 994 1089 1208 1274 1354 1441 1542 1654 1772 1879 1979 2071 2159 2236 2471 2675 3003
FILLER JACKET THICKNESS THICKNESS (mm) (mm)
20 20 20 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39
80 80 80 80 80 80 110 110 110 110 110 110 110 110 110 140 140 140
OVERALL DIAMETER (mm)
1123 1198 1293 1452 1518 1598 1746 1847 1959 2077 2184 2284 2376 2464 2542 2838 3043 3370
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
740 900 1134 1544 1773 2065 2524 2972 3525 4048 4663 5270 5872 6470 7055 8593 -
632 729 863 1112 1228 1378 1657 1880 2148 2420 2710 2992 3268 3541 3800 4687 5474 6796
0.647 0.407 0.256 0.161 0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 -
1.06 0.665 0.418 0.263 0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
27
0.2635 0.2449 0.2278 0.2125 0.2005 0.1937 0.1876 0.1815 0.1759 0.1717 0.1677 0.1645 0.1619 0.1597 0.1579 0.1572 0.1535 0.1487
9815 8538 7347 6264 5791 5309 4870 4443 4046 3704 3437 3223 3046 2895 2774 2523 2293 2002
MV-90 8 kV Three conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm²)
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
11.05 12.17 13.57 14.35 15.29 16.31 17.50 18.83 20.21 21.48 22.65 23.74 24.78 25.69 27.87 30.28 34.14 Notes:
DIAMETER OVER TRANDED PHASE (mm)
28.06 30.47 33.49 35.17 37.20 39.39 41.96 44.83 47.80 50.54 53.06 55.41 57.65 60.86 65.56 70.75 79.07
FILLER JACKET THICKNESS THICKNESS (mm) (mm)
0.50 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 3.56
OVERALL DIAMETER (mm)
33.24 36.65 39.67 41.35 44.94 47.14 49.71 52.57 55.55 58.28 60.80 63.15 65.39 68.61 74.89 80.08 88.40
APPROXIMATE TOTAL WEIGHT (kg/km) COPPER
ALUMINUM
1519 1972 2513 2863 3464 4011 4692 5529 6322 7251 8168 9075 9978 11042 13188 -
1265 1567 1870 2052 2442 2722 3067 3480 3901 4346 4778 5201 5619 6199 7377 8574 10584
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km) COPPER ALUMINUM
1.34 0.840 0.528 0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 -
2.18 1.37 0.863 0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
0.1601 0.1488 0.1386 0.1309 0.1263 0.1221 0.1180 0.1142 0.1112 0.1085 0.1063 0.1045 0.1030 0.1033 0.1010 0.0984 0.0951
16338 14169 12171 11291 10388 9562 8752 7997 7341 6827 6414 6071 5778 5543 5052 4601 4027
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Three conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115
435 479 534 565 602 642 689 741 796 846 892 935 976 1011 1097 1192 1344 Notes:
28
DIAMETER OVER TRANDED PHASE (mm)
1105 1200 1318 1385 1464 1551 1652 1765 1882 1990 2089 2181 2270 2396 2581 2785 3113
FILLER JACKET THICKNESS THICKNESS (mm) (mm)
20 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39
80 80 80 80 110 110 110 110 110 110 110 110 110 110 140 140 140
OVERALL DIAMETER (mm)
1309 1443 1562 1628 1769 1856 1957 2070 2187 2295 2394 2486 2575 2701 2948 3153 3480
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1021 1325 1689 1924 2328 2696 3153 3716 4249 4873 5489 6099 6705 7421 8863 -
850 1053 1257 1379 1641 1830 2061 2339 2621 2920 3211 3495 3776 4166 4958 5762 7113
0.407 0.256 0.161 0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 -
0.665 0.418 0.263 0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
0.2577 0.2395 0.2231 0.2106 0.2032 0.1965 0.1899 0.1838 0.1790 0.1746 0.1711 0.1682 0.1657 0.1662 0.1625 0.1584 0.1531
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
10152 8804 7563 7016 6455 5942 5438 4969 4562 4242 3985 3773 3590 3444 3139 2859 2502
MV-90 15 kV Three conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 26.80 27.84 28.75 30.93 33.34 37.20
DIAMETER OVER TRANDED PHASE (mm)
40.08 41.76 43.79 45.99 48.55 51.42 54.39 57.13 60.90 63.25 65.49 67.45 72.15 77.34 85.66
FILLER JACKET THICKNESS THICKNESS (mm) (mm)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 3.56 3.56 3.56 3.56
OVERALL DIAMETER (mm)
47.83 49.51 51.54 53.74 56.30 59.17 62.14 64.88 68.65 72.58 74.83 76.79 81.48 86.68 95.00
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
3245 3621 4097 4671 5383 6255 7084 8046 9178 10378 11321 12238 14191 -
2602 2810 3075 3382 3758 4205 4662 5140 5788 6504 6963 7395 8380 9640 11751
0.528 0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 -
0.863 0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
0.1522 0.1438 0.1386 0.1338 0.1290 0.1245 0.1210 0.1178 0.1167 0.1145 0.1126 0.1110 0.1082 0.1051 0.1012
16393 15303 14175 13131 12097 11123 10268 9592 9044 8588 8195 7879 7214 6600 5809
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Three conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
175 175 175 175 175 175 175 175 175 175 175 175 175 175 175
655 685 722 763 809 862 916 966 1012 1055 1096 1132 1218 1313 1465
DIAMETER OVER TRANDED PHASE (mm)
1578 1644 1724 1811 1912 2024 2141 2249 2398 2490 2578 2656 2841 3045 3373
FILLER JACKET THICKNESS THICKNESS (mm) (mm)
39 39 39 39 39 39 39 39 39 39 39 39 39 39 39
110 110 110 110 110 110 110 110 110 140 140 140 140 140 140
OVERALL DIAMETER (mm)
1883 1949 2029 2116 2217 2329 2446 2554 2703 2858 2946 3023 3208 3413 3740
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
2181 2433 2753 3139 3618 4204 4761 5407 6168 6974 7608 8224 9537 -
1749 1889 2066 2273 2525 2826 3133 3455 3890 4371 4679 4970 5631 6478 7897
0.161 0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 -
0.263 0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
29
0.2449 0.2315 0.2231 0.2153 0.2076 0.2004 0.1947 0.1895 0.1878 0.1843 0.1812 0.1787 0.1741 0.1692 0.1628
10186 9509 8808 8160 7517 6912 6381 5960 5620 5337 5092 4896 4483 4101 3610
MV-90 25 kV Three conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 27.53 28.80 29.97 31.06 32.10 33.01 35.19 37.60 41.46 Notes:
DIAMETER OVER TRANDED PHASE (mm)
50.95 52.97 55.17 57.73 61.85 64.82 67.56 70.08 72.43 74.67 76.63 81.33 86.52 96.70
FILLER THICKNESS (mm)
JACKET OVERALL THICKNESS DIAMETER (mm) (mm)
APPROXIMATE TOTAL WEIGHT (kg/km) COPPER
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2.79 2.79 2.79 2.79 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56
58.69 60.72 62.92 65.48 69.60 72.57 76.89 79.42 81.76 84.01 85.97 90.66 95.86 106.03
4601 5111 5723 6478 7585 8472 9761 10767 11757 12738 13688 -
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
ALUMINUM COPPER
3791 4089 4434 4852 5535 6050 6855 7377 7883 8379 8845 9909 11256 13926
0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 -
ALUMINUM
0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
0.1588 0.1530 0.1475 0.1421 0.1385 0.1342 0.1304 0.1273 0.1247 0.1225 0.1207 0.1172 0.1136 0.1103
19847 18509 17258 16006 14814 13758 12915 12227 11651 11150 10747 9893 9096 8060
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Three conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
260 260 260 260 260 260 260 260 260 260 260 260 260 260
853 890 930 977 1030 1084 1134 1180 1223 1264 1300 1385 1480 1632 Notes:
30
DIAMETER FILLER OVER THICKNESS TRANDED (mm) PHASE (mm)
2006 2085 2172 2273 2435 2552 2660 2759 2852 2940 3017 3202 3406 3807
39 39 39 39 39 39 39 39 39 39 39 39 39 39
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
110 110 110 110 140 140 140 140 140 140 140 140 140 140
2311 2390 2477 2578 2740 2857 3027 3127 3219 3307 3385 3569 3774 4174
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
3092 3435 3846 4353 5097 5693 6560 7236 7901 8561 9199 -
2548 2748 2980 3261 3720 4066 4607 4958 5297 5631 5944 6659 7565 9359
0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 -
0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
0.2556 0.2461 0.2374 0.2286 0.2228 0.2160 0.2099 0.2049 0.2007 0.1971 0.1942 0.1887 0.1828 0.1775
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
12333 11501 10724 9946 9205 8549 8025 7598 7240 6929 6678 6147 5652 5008
MV-90 35 kV Three conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06
53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76
26.97 27.99 29.18 30.51 31.89 33.16 34.33 35.42 36.46 37.37 39.55 41.96
DIAMETER OVER TRANDED PHASE (mm)
63.62 65.81 68.38 71.25 74.22 76.96 79.48 81.83 84.07 86.03 92.58 97.77
FILLER THICKNESS (mm)
JACKET THICKNESS (mm)
OVERALL DIAMETER (mm)
APPROXIMATE TOTAL WEIGHT (kg/km) COPPER
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56 3.56
72.95 75.15 77.71 80.58 83.55 86.29 88.81 91.16 93.40 95.36 101.91 107.11
6761 7424 8239 9227 10176 11249 12298 13329 14349 -
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
ALUMINUM COPPER
5739 6135 6614 7178 7754 8343 8908 9454 9990 10489 12036 13494
0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 -
ALUMINUM
0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764
0.1668 0.1608 0.1548 0.1491 0.1444 0.1402 0.1368 0.1339 0.1314 0.1294 0.1270 0.1228
22170 20773 19366 18016 16810 15841 15047 14378 13794 13323 12318 11374
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Three conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
336 376 423 475 520 570 616 659 700 736 813 908
0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589
345 345 345 345 345 345 345 345 345 345 345 345
1062 1102 1149 1201 1256 1306 1352 1394 1435 1471 1557 1652
DIAMETER FILLER OVER THICKNESS TRANDED (mm) PHASE (mm)
2505 2591 2692 2805 2922 3030 3129 3222 3310 3387 3645 3849
39 39 39 39 39 39 39 39 39 39 39 39
JACKET OVERALL THICKNESS DIAMETER (mm) (mm)
140 140 140 140 140 140 140 140 140 140 140 140
2872 2959 3060 3172 3289 3397 3496 3589 3677 3754 4012 4217
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ INDUCTIVE CAPACITIVE REACTANCE² REACTANCE² (ohm/km) (ohm/km) (ohm-km)
COPPER
ALUMINUM
COPPER
ALUMINUM
4544 4989 5537 6201 6839 7560 8265 8957 9643 -
3857 4123 4445 4824 5211 5607 5987 6354 6714 7049 8089 9068
0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 -
0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
31
0.2684 0.2588 0.2492 0.2400 0.2324 0.2257 0.2201 0.2155 0.2115 0.2082 0.2044 0.1976
13776 12908 12034 11195 10446 9844 9350 8934 8572 8279 7654 7068
MV-90 5 - 35 kV Triplexed Conductors
Description Three phases copper or aluminum stranded, thermo set insulated.
Contruction Conductor Soft Copper or 1350-H19 aluminum, compact stranded. Conductor Shield Cross linked polyethylene semiconductor. Insulation Cross linked polyethylene XLPE. Insulation shield Cross linked polyethylene removable semiconductor. Insulation and shields are applied by true triple extrusion process. Metallic shield Copper tape helically and overlapped applied over insulation shield, 2.5 mils (0.0635mm) thickness. Jacket Flame retardant polyvinyl chloride PVC. Options EPR or XLPE-TR (Tree retardant XLPE) Copper wires metallic shield. Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable type jacket. Moisture barrier against longitudinally migration.
32
Characteristics Operating Temperature Normal continuous operation 90°C for wet or dry locations (105°C optional) Overload 130°C Short circuit 250°C Rated Voltage 5, 8, 15, 25 and 35 kV. Insulation Level 100% (133% and 173% optional).
Applications Distribution of electric energy at Medium Voltage, installed at air, underground ducts, raceways, direct buried or tray cables.
Standards CENTELSA’s 5-35 kV three conductors are manufactured in accordance with the following standards: ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded Copper Conductors. ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded Aluminum 1350 Conductors. UL 1072. Medium Voltage Power Cables MV90. ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV.
33
Certifications CENTELSA’s 5-35 kV Triplex conductors are certified by: UL 1072. File E167359. ICONTEC (Colombia). NTC 2186 standard CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE CIDET (Colombia). Cert. 00413. 35 kV Medium Voltage Copper, XLPE CIDET (Colombia). Cert. 00414. 15 kV Medium Voltage Copper, EPR CIDET (Colombia). Cert. 00415. 35 kV Medium Voltage Copper, EPR
Note: Configurations and sizes herein not specified are available upon request.
MV-90 5 kV Triplexed conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm²)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
3.40 4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
8.4 13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
8.86 9.75 10.87 12.27 13.05 13.99 15.01 16.20 17.53 18.91 20.18 21.35 22.44 23.48 24.39 26.57 28.98 32.84
1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
13.20 14.88 16.00 17.40 18.18 19.12 20.14 22.35 23.68 25.06 26.33 27.50 28.59 29.63 30.54 33.30 35.71 39.57
28.45 32.07 34.48 37.50 39.18 41.21 43.41 48.17 51.04 54.01 56.75 59.27 61.62 63.86 65.82 71.77 76.96 85.28
Notes:
34
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
742 1008 1296 1729 2015 2380 2828 3542 4246 4894 5682 6464 7239 8012 8775 10460 12736 16518
582 754 891 1086 1205 1357 1539 1916 2197 2472 2776 3074 3365 3653 3932 4648 5471 6832
2.12 1.34 0.840 0.528 0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 0.0467 0.0351
3.47 2.18 1.37 0.863 0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.1787 0.1702 0.1582 0.1471 0.1390 0.1340 0.1294 0.1284 0.1240 0.1204 0.1173 0.1147 0.1125 0.1107 0.1092 0.1078 0.1048 0.1008
15795 13740 11824 10081 9319 8544 7838 7150 6512 5961 5531 5187 4902 4659 4465 4060 3691 3221
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 5 kV Triplexed conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (sq inches)
134 169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90
349 384 428 483 514 551 591 638 690 744 794 841 883 924 960 1046 1141 1293
45 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80
520 586 630 685 716 753 793 880 932 987 1037 1083 1126 1167 1202 1311 1406 1558
1120 1263 1358 1476 1543 1622 1709 1896 2009 2126 2234 2333 2426 2514 2591 2825 3030 3357
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
498 677 871 1162 1354 1599 1901 2380 2854 3289 3819 4344 4865 5384 5897 7030 8559 11101
391 506 599 730 810 912 1035 1288 1476 1661 1866 2066 2261 2455 2642 3124 3677 4592
0.647 0.407 0.256 0.161 0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 0.0142 0.0107
1.06 0.665 0.418 0.263 0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
35
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.2876 0.2739 0.2545 0.2368 0.2237 0.2157 0.2083 0.2067 0.1995 0.1938 0.1887 0.1845 0.1811 0.1781 0.1757 0.1735 0.1686 0.1623
9815 8538 7347 6264 5791 5309 4870 4443 4046 3704 3437 3223 3046 2895 2774 2523 2293 2002
MV-90 8 kV Triplexed conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm²)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
11.05 12.17 13.57 14.35 15.29 16.31 17.50 18.83 20.21 21.48 22.65 23.74 24.78 25.69 27.87 30.28 34.14
1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
16.18 17.30 18.70 19.48 20.42 22.46 23.65 24.98 26.36 27.63 28.80 29.89 30.93 32.42 34.60 37.01 40.87
34.87 37.29 40.30 41.98 44.01 48.41 50.97 53.84 56.81 59.55 62.07 64.42 66.66 69.87 74.57 79.76 88.08
Notes:
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1116 1410 1852 2143 2512 3121 3696 4408 5063 5859 6647 7429 8207 9086 10678 12967 16772
862 1006 1209 1332 1490 1832 2070 2359 2642 2953 3257 3555 3849 4243 4866 5703 7086
1.34 0.840 0.528 0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 0.0467 0.0351
2.18 1.37 0.863 0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.1765 0.1641 0.1526 0.1442 0.1390 0.1376 0.1327 0.1280 0.1243 0.1209 0.1182 0.1159 0.1139 0.1137 0.1107 0.1074 0.1033
16338 14169 12171 11291 10388 9562 8752 7997 7341 6827 6414 6071 5778 5543 5052 4601 4027
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Triplexed conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (sq inches)
169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115
435 479 534 565 602 642 689 741 796 846 892 935 976 1011 1097 1192 1344
60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80 80
637 681 736 767 804 884 931 984 1038 1088 1134 1177 1218 1276 1362 1457 1609
1373 1468 1587 1653 1733 1906 2007 2120 2237 2344 2444 2536 2624 2751 2936 3140 3468
Notes:
36
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
750 948 1245 1440 1688 2097 2484 2962 3403 3938 4467 4993 5516 6106 7176 8714 11271
579 676 813 895 1001 1231 1391 1585 1775 1985 2189 2389 2586 2852 3270 3832 4762
0.407 0.256 0.161 0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 0.0142 0.0107
0.665 0.418 0.263 0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.2840 0.2640 0.2455 0.2321 0.2237 0.2215 0.2135 0.2060 0.2000 0.1945 0.1901 0.1865 0.1833 0.1830 0.1781 0.1729 0.1662
10152 8804 7563 7016 6455 5942 5438 4969 4562 4242 3985 3773 3590 3444 3139 2859 2502
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Triplexed conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
CROSS SECTION (mm²)
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 26.80 27.84 28.75 30.93 33.34 37.20
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79
22.78 23.56 24.50 25.52 26.71 28.04 29.42 30.69 32.44 33.53 34.57 35.48 37.66 40.07 45.50
49.10 50.78 52.80 55.00 57.57 60.43 63.41 66.14 69.91 72.26 74.50 76.46 81.16 86.36 98.05
Notes:
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
2326 2633 3022 3497 4088 4818 5492 6305 7219 8019 8815 9598 11219 13541 17878
1683 1822 1999 2208 2463 2769 3071 3399 3829 4145 4456 4755 5407 6276 8192
0.528 0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 0.0467 0.0351
0.863 0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764 0.0573
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.1675 0.1586 0.1527 0.1473 0.1419 0.1367 0.1325 0.1288 0.1271 0.1245 0.1223 0.1205 0.1171 0.1134 0.1113
16393 15303 14175 13131 12097 11123 10268 9592 9044 8588 8195 7879 7214 6600 5809
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.2695 0.2552 0.2458 0.2370 0.2283 0.2200 0.2133 0.2073 0.2046 0.2004 0.1968 0.1939 0.1884 0.1826 0.1792
10186 9509 8808 8160 7517 6912 6381 5960 5620 5337 5092 4896 4483 4101 3610
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Triplexed conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (sq inches)
268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
175 175 175 175 175 175 175 175 175 175 175 175 175 175 175
655 685 722 763 809 862 916 966 1012 1055 1096 1132 1218 1313 1465
80 80 80 80 80 80 80 80 80 80 80 80 80 80 110
897 928 965 1005 1052 1104 1158 1208 1277 1320 1361 1397 1483 1578 1791
1933 1999 2079 2165 2266 2379 2496 2604 2752 2845 2933 3010 3195 3400 3860
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
1563 1769 2031 2350 2747 3238 3691 4237 4852 5389 5924 6450 7539 9100 12015
1131 1225 1344 1484 1655 1861 2064 2284 2573 2786 2995 3196 3634 4218 5505
0.161 0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 0.0142 0.0107
0.263 0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233 0.0175
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
37
MV-90 25 kV Triplexed conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750
7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06
CROSS SECTION (mm²)
42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 27.53 28.80 29.97 31.06 32.10 33.01 35.19 37.60
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79
Notes:
JACKET DIAMETER (mm)
27.82 28.76 29.78 30.97 32.88 34.26 35.53 36.70 37.79 38.83 39.74 43.49 45.90
DIAMETER OVER TRANDED PHASE (mm)
59.96 61.98 64.18 66.75 70.86 73.84 76.57 79.09 81.44 83.68 85.64 93.72 98.91
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
3189 3595 4089 4703 5570 6274 7114 7944 8764 9579 10379 12500 14893
2378 2573 2800 3077 3520 3852 4208 4554 4890 5220 5536 6688 7628
0.419 0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701 0.0584 0.0467
0.684 0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115 0.0955 0.0764
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.1711 0.1648 0.1589 0.1530 0.1487 0.1440 0.1398 0.1364 0.1336 0.1311 0.1290 0.1279 0.1237
19847 18509 17258 16006 14814 13758 12915 12227 11651 11150 10747 9893 9096
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Triplexed conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750
CONDUCTOR CROSS DIAMETER SECTION (mm) (sq inches)
299 336 376 423 475 520 570 616 659 700 736 813 908
0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
JACKET DIAMETER (mm)
DIAMETER OVER TRANDED PHASE (mm)
260 260 260 260 260 260 260 260 260 260 260 260 260
853 890 930 977 1030 1084 1134 1180 1223 1264 1300 1385 1480
80 80 80 80 80 80 80 80 80 80 80 110 110
1095 1132 1173 1219 1295 1349 1399 1445 1488 1529 1565 1712 1807
2361 2440 2527 2628 2790 2907 3015 3114 3206 3295 3372 3690 3894
Notes:
38
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER ALUMINUM
COPPER
ALUMINUM
2143 2416 2748 3160 3743 4216 4781 5338 5890 6437 6975 8401 10009
0.128 0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214 0.0178 0.0142
0.209 0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349 0.0291 0.0233
1598 1729 1882 2068 2366 2589 2828 3060 3286 3508 3721 4495 5127
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.2753 0.2652 0.2557 0.2462 0.2393 0.2318 0.2251 0.2196 0.2149 0.2109 0.2077 0.2059 0.1990
12333 11501 10724 9946 9205 8549 8025 7598 7240 6929 6678 6147 5652
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Triplexed conductors, 90°C (International Unit System) 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
CONDUCTOR DIAMETER (mm)
1/0 2/0 3/0 4/0 250 300 350 400 450 500
8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69
Notes:
CROSS SECTION (mm²)
53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4
INSULATION THICKNESS (mm)
8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76
INSULATION DIAMETER (mm)
26.97 27.99 29.18 30.51 31.89 33.16 34.33 35.42 36.46 37.37
JACKET THICKNESS (mm)
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
JACKET DIAMETER (mm)
33.70 34.72 35.91 37.24 38.62 39.89 41.06 42.15 43.19 44.10
DIAMETER OVER TRANDED PHASE (mm)
72.63 74.83 77.39 80.26 83.23 85.97 88.49 90.84 93.08 95.04
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER
ALUMINUM
COPPER
ALUMINUM
4379 4896 5536 6320 7051 7916 8767 9609 10443 11261
3356 3607 3910 4271 4629 5010 5377 5734 6085 6418
0.332 0.263 0.209 0.166 0.140 0.117 0.100 0.0876 0.0779 0.0701
0.543 0.430 0.341 0.271 0.229 0.191 0.164 0.143 0.127 0.115
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.1767 0.1705 0.1642 0.1581 0.1531 0.1486 0.1449 0.1418 0.1391 0.1369
22170 20773 19366 18016 16810 15841 15047 14378 13794 13323
INDUCTIVE REACTANCE² (ohm/km)
CAPACITIVE REACTANCE² (ohm-km)
0.2844 0.2744 0.2642 0.2544 0.2463 0.2391 0.2332 0.2282 0.2238 0.2203
13776 12908 12034 11195 10446 9844 9350 8934 8572 8279
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm²/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Triplexed conductors, 90°C 100% Insulation Level Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (sq inches)
336 376 423 475 520 570 616 659 700 736
0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393
INSULATION THICKNESS (mm)
INSULATION DIAMETER (mm)
JACKET THICKNESS (mm)
345 345 345 345 345 345 345 345 345 345
1062 1102 1149 1201 1256 1306 1352 1394 1435 1471
80 80 80 80 80 80 80 80 80 80
JACKET DIAMETER (mm)
1327 1367 1414 1466 1521 1571 1617 1660 1700 1736
DIAMETER OVER TRANDED PHASE (mm)
2859 2946 3047 3160 3277 3385 3484 3576 3665 3742
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
COPPER ALUMINUM
COPPER
ALUMINUM
2943 3290 3720 4248 4738 5320 5892 6457 7018 7568
0.101 0.0803 0.0637 0.0505 0.0427 0.0356 0.0305 0.0267 0.0237 0.0214
0.165 0.131 0.104 0.0825 0.0698 0.0582 0.0499 0.0436 0.0388 0.0349
2256 2424 2628 2870 3111 3367 3614 3854 4089 4313
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
39
MV-90 5 - 35 kV Single Conductors URD Type (Underground Residential Distribution)
Description Copper or aluminum stranded, thermo set insulated.
Contruction Conductor Soft Copper or 1350-H19 aluminum, compact stranded. Conductor Shield Cross linked polyethylene semiconductor. Insulation Cross linked polyethylene XLPE. Insulation shield Cross linked polyethylene removable semiconductor. Insulation and shields are applied by true triple extrusion process. Metallic shield Copper tape helically and overlapped applied over insulation shield, 2.5 mils (0.0635mm) thickness. Jacket Flame retardant polyvinyl chloride PVC. Options EPR or XLPE-TR (Tree retardant XLPE) Copper wires metallic shield. Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable type jacket. Moisture barrier against longitudinally migration.
Characteristics Operating Temperature Normal continuous operation 90째C for wet or dry locations (105째C optional) 40
Overload 130°C Short circuit 250°C Rated Voltage 5, 8, 15, 25 and 35 kV. Insulation Level 100% (133% and 173% optional).
Applications Distribution of electric energy at Medium Voltage, installed at air, underground ducts, raceways, direct buried or tray cables.
Standards CENTELSA’s 5-35 kV three conductors are manufactured in accordance with the following standards: ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded Copper Conductors. ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded Aluminum 1350 Conductors. UL 1072. Medium Voltage Power Cables MV90. ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 – 46 kV AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV.
Certifications CENTELSA’s 5-35 kV Single conductors are certified by: UL 1072. File E167359. ICONTEC (Colombia). NTC 2186 standard. CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE CIDET (Colombia). Cert. 00413. 35 kV Medium Voltage Copper, XLPE. CIDET (Colombia). Cert. 00414. 15 kV Medium Voltage Copper, EPR CIDET (Colombia). Cert. 00415. 35 kV Medium Voltage Copper, EPR.
41
Note: Configurations and sizes herein not specified are available upon request.
MV-90 5 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (mm²) (mm) (mm)
3.40 4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
8.4 13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
8.86 9.75 10.87 12.27 13.05 13.99 15.01 16.20 17.53 18.91 20.18 21.35 22.44 23.48 24.39 26.57 28.98 32.84 Notes:
42
CONCENTRIC NEUTRAL
JACKET STRANDS STRANDS CROSS DIAMETER THICKNESS No. DIAMETER SECTION No. (mm) (mm) (mm²)
6 6 6 9 11 14 18 22 28 21 25 29 33 37 26 31 25 32
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 1.63 1.63 1.63 2.05 2.05 2.59 2.59
7.9 7.9 7.9 11.8 14.4 18.3 23.6 28.8 36.7 43.8 52.1 60.4 68.8 77.1 86.0 102.5 131.5 168.3
13.22 14.11 15.23 16.63 17.41 18.35 19.37 20.56 21.89 23.95 25.22 26.39 27.48 28.52 30.27 33.03 36.52 40.38
1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
15.74 17.42 18.54 19.94 20.72 21.66 22.68 24.89 26.22 28.28 29.55 30.72 31.81 32.85 34.61 37.37 40.85 44.71
311 402 494 671 788 943 1137 1424 1727 2010 2344 2677 3007 3337 3677 4380 5404 6984
2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.4010 0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
15795 13740 11824 10081 9319 8544 7838 7150 6512 5961 5531 5187 4902 4659 4465 4060 3691 3221
MV-90 5 kV Single Copper conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (sq inches) (mm²) (mm) (mm)
134 169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90
349 384 428 483 514 551 591 638 690 744 794 841 883 924 960 1046 1141 1293
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
6 6 6 9 11 14 18 22 28 21 25 29 33 37 26 31 25 32
51 51 51 51 51 51 51 51 51 64 64 64 64 64 81 81 102 102
0.0122 0.0122 0.0122 0.0183 0.0223 0.0284 0.0365 0.0446 0.0568 0.0678 0.0808 0.0937 0.107 0.120 0.133 0.159 0.204 0.261
521 556 600 655 686 723 763 810 862 943 993 1039 1082 1123 1192 1301 1438 1590
45 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80
620 686 730 785 816 853 893 980 1032 1113 1163 1209 1252 1293 1362 1471 1608 1760
209 270 332 451 530 634 764 957 1160 1351 1575 1799 2021 2243 2471 2944 3632 4693
0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
43
0.6454 0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
9815 8538 7347 6264 5791 5309 4870 4443 4046 3704 3437 3223 3046 2895 2774 2523 2293 2002
MV-90 8 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
11.05 12.17 13.57 14.35 15.29 16.31 17.50 18.83 20.21 21.48 22.65 23.74 24.78 25.69 27.87 30.28 34.14 Notes:
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
6 6 9 11 14 18 22 28 21 25 29 33 37 26 31 25 32
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 1.63 1.63 1.63 2.05 2.05 2.59 2.59
7.9 7.9 11.8 14.4 18.3 23.6 28.8 36.7 43.8 52.1 60.4 68.8 77.1 86.0 102.5 131.5 168.3
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C ¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
15.41 16.53 17.93 18.71 19.65 20.67 21.86 23.19 25.25 26.52 27.69 28.78 29.82 32.15 34.33 37.82 41.68
1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
18.72 19.84 21.24 22.02 22.96 25.00 26.19 27.52 29.58 30.85 32.02 33.11 34.15 36.49 38.67 42.15 46.01
435 530 709 828 984 1237 1473 1778 2063 2400 2735 3068 3399 3776 4450 5478 7065
1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
16338 14169 12171 11291 10388 9562 8752 7997 7341 6827 6414 6071 5778 5543 5052 4601 4027
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Single Copper conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115
435 479 534 565 602 642 689 741 796 846 892 935 976 1011 1097 1192 1344 Notes:
44
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
6 6 9 11 14 18 22 28 21 25 29 33 37 26 31 25 32
51 51 51 51 51 51 51 51 64 64 64 64 64 81 81 102 102
0.0122 0.0122 0.0183 0.0223 0.0284 0.0365 0.0446 0.0568 0.0678 0.0808 0.0937 0.107 0.120 0.133 0.159 0.204 0.261
607 651 706 737 774 814 861 913 994 1044 1090 1133 1174 1266 1352 1489 1641
60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80 80
737 781 836 867 904 984 1031 1084 1165 1215 1261 1304 1344 1436 1522 1659 1811
292 356 477 556 661 831 990 1195 1387 1613 1838 2062 2284 2538 2990 3681 4748
0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
10152 8804 7563 7016 6455 5942 5438 4969 4562 4242 3985 3773 3590 3444 3139 2859 2502
MV-90 15 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 26.80 27.84 28.75 30.93 33.34 37.20
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
9 11 14 18 22 28 21 25 29 33 37 26 31 25 32
1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 1.63 1.63 1.63 2.05 2.05 2.59 2.59
11.8 14.4 18.3 23.6 28.8 36.7 43.8 52.1 60.4 68.8 77.1 86.0 102.5 131.5 168.3
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C ¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
20.99 21.77 22.71 23.73 24.92 26.25 28.31 29.58 31.33 32.42 33.46 35.21 37.39 40.88 44.74
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79
25.32 26.10 27.04 28.06 29.25 30.58 32.64 33.91 35.66 36.75 37.79 39.55 41.73 45.21 50.63
866 990 1152 1356 1597 1907 2199 2542 2917 3256 3593 3940 4622 5661 7443
0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
16393 15303 14175 13131 12097 11123 10268 9592 9044 8588 8195 7879 7214 6600 5809
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Single Copper conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
175 175 175 175 175 175 175 175 175 175 175 175 175 175 175
655 685 722 763 809 862 916 966 1012 1055 1096 1132 1218 1313 1465
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
9 11 14 18 22 28 21 25 29 33 37 26 31 25 32
51 51 51 51 51 51 64 64 64 64 64 81 81 102 102
0.0183 0.0223 0.0284 0.0365 0.0446 0.0568 0.0678 0.0808 0.0937 0.107 0.120 0.133 0.159 0.204 0.261
826 857 894 934 981 1034 1114 1164 1233 1276 1317 1386 1472 1609 1761
80 80 80 80 80 80 80 80 80 80 80 80 80 80 110
997 1028 1065 1105 1152 1204 1285 1335 1404 1447 1488 1557 1643 1780 1993
582 665 774 911 1073 1282 1478 1708 1960 2188 2415 2648 3106 3805 5002
0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
45
0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
10186 9509 8808 8160 7517 6912 6381 5960 5620 5337 5092 4896 4483 4101 3610
MV-90 25 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 27.53 28.80 29.97 31.06 32.10 33.01 35.19 37.60 41.46 Notes:
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
11 14 18 22 28 21 25 29 33 37 26 31 25 32
1.29 1.29 1.29 1.29 1.29 1.63 1.63 1.63 1.63 1.63 2.05 2.05 2.59 2.59
14.4 18.3 23.6 28.8 36.7 43.8 52.1 60.4 68.8 77.1 86.0 102.5 131.5 168.3
26.03 26.97 27.99 29.18 31.09 33.15 34.42 35.59 36.68 37.72 39.47 41.65 45.14 49.86
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79
30.36 31.30 32.32 33.51 35.42 37.48 38.75 39.92 41.01 42.05 43.81 47.55 51.03 55.75
1165 1334 1543 1791 2146 2448 2800 3148 3493 3837 4189 5052 6118 7842
0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
19847 18509 17258 16006 14814 13758 12915 12227 11651 11150 10747 9893 9096 8060
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Single Copper conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
260 260 260 260 260 260 260 260 260 260 260 260 260 260
853 890 930 977 1030 1084 1134 1180 1223 1264 1300 1385 1480 1632 Notes:
46
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
11 14 18 22 28 21 25 29 33 37 26 31 25 32
51 51 51 51 51 64 64 64 64 64 81 81 102 102
0.0223 0.0284 0.0365 0.0446 0.0568 0.0678 0.0808 0.0937 0.107 0.120 0.133 0.159 0.204 0.261
1025 1062 1102 1149 1224 1305 1355 1401 1444 1485 1554 1640 1777 1963
80 80 80 80 80 80 80 80 80 80 80 110 110 110
1195 1232 1273 1319 1395 1476 1526 1572 1615 1656 1725 1872 2009 2195
783 896 1037 1204 1442 1645 1882 2116 2348 2579 2815 3395 4111 5270
0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
12333 11501 10724 9946 9205 8549 8025 7598 7240 6929 6678 6147 5652 5008
MV-90 35 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76
26.97 27.99 29.18 30.51 31.89 33.16 34.33 35.42 36.46 37.37 39.55 41.96 45.82
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
14 18 22 28 21 25 29 33 37 26 31 25 32
1.29 1.29 1.29 1.29 1.63 1.63 1.63 1.63 1.63 2.05 2.05 2.59 2.59
18.3 23.6 28.8 36.7 43.8 52.1 60.4 68.8 77.1 86.0 102.5 131.5 168.3
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
31.91 32.93 34.12 35.45 37.51 38.78 39.95 41.04 42.08 43.83 46.87 50.36 54.22
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79
36.24 37.26 38.45 39.78 41.84 43.11 44.28 45.37 46.41 48.17 52.77 56.25 60.11
1583 1800 2057 2386 2696 3056 3412 3764 4114 4472 5443 6528 8200
0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0771 0.0694 0.0578 0.0463 0.0347
0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
22170 20773 19366 18016 16810 15841 15047 14378 13794 13323 12318 11374 10136
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Single Copper conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
345 345 345 345 345 345 345 345 345 345 345 345 345
1062 1102 1149 1201 1256 1306 1352 1394 1435 1471 1557 1652 1804
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
14 18 22 28 21 25 29 33 37 26 31 25 32
51 51 51 51 64 64 64 64 64 81 81 102 102
0.0284 0.0365 0.0446 0.0568 0.0678 0.0808 0.0937 0.107 0.120 0.133 0.159 0.204 0.261
1256 1297 1343 1396 1477 1527 1573 1616 1657 1726 1845 1983 2134
80 80 80 80 80 80 80 80 80 80 110 110 110
1427 1467 1514 1566 1647 1697 1743 1786 1827 1896 2078 2215 2367
1064 1210 1382 1603 1812 2054 2293 2530 2765 3006 3658 4387 5511
0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0235 0.0212 0.0176 0.0141 0.0106
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
47
0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
13776 12908 12034 11195 10446 9844 9350 8934 8572 8279 7654 7068 6298
MV-90 5 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
3.40 4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
8.4 13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
8.86 9.75 10.87 12.27 13.05 13.99 15.01 16.20 17.53 18.91 20.18 21.35 22.44 23.48 24.39 26.57 28.98 32.84 Notes:
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
6 6 6 6 7 9 11 14 17 20 24 28 32 36 25 30 24 31
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 2.05 2.05
7.9 7.9 7.9 7.9 9.2 11.8 14.4 18.3 22.3 26.2 31.4 36.7 41.9 47.1 52.1 62.5 79.4 102.5
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
13.22 14.11 15.23 16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 26.80 27.84 29.43 32.19 35.44 39.30
1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
15.74 17.42 18.54 19.94 20.72 21.66 22.68 24.89 26.22 27.60 28.87 30.04 31.13 32.17 33.76 36.52 39.78 43.64
258 318 361 423 472 545 627 792 918 1042 1188 1333 1475 1616 1759 2086 2516 3171
3.43 2.16 1.36 0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.4010 0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
15795 13740 11824 10081 9319 8544 7838 7150 6512 5961 5531 5187 4902 4659 4465 4060 3691 3221
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 5 kV Single Aluminum conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
134 169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90
349 384 428 483 514 551 591 638 690 744 794 841 883 924 960 1046 1141 1293 Notes:
48
CONCENTRIC NEUTRAL STRANDS No.
6 6 6 6 7 9 11 14 17 20 24 28 32 36 25 30 24 31
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 51 51 51 51 51 51 51 51 51 51 51 51 64 64 81 81
0.0122 0.0122 0.0122 0.0122 0.0142 0.0183 0.0223 0.0284 0.0345 0.0406 0.0487 0.0568 0.0649 0.0730 0.0808 0.0969 0.123 0.159
521 556 600 655 686 723 763 810 862 916 966 1012 1055 1096 1159 1267 1395 1547
45 60 60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80
620 686 730 785 816 853 893 980 1032 1087 1137 1183 1226 1267 1329 1438 1566 1718
173 213 243 284 317 366 422 532 617 700 799 895 991 1086 1182 1402 1691 2131
1.05 0.658 0.414 0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.6454 0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
9815 8538 7347 6264 5791 5309 4870 4443 4046 3704 3437 3223 3046 2895 2774 2523 2293 2002
MV-90 8 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
11.05 12.17 13.57 14.35 15.29 16.31 17.50 18.83 20.21 21.48 22.65 23.74 24.78 25.69 27.87 30.28 34.14
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
6 6 6 7 9 11 14 17 20 24 28 32 36 25 30 24 31
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 2.05 2.05
7.9 7.9 7.9 9.2 11.8 14.4 18.3 22.3 26.2 31.4 36.7 41.9 47.1 52.1 62.5 79.4 102.5
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
15.41 16.53 17.93 18.71 19.65 20.67 21.86 23.19 24.57 25.84 27.01 28.10 29.14 31.31 33.49 36.74 40.60
1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
18.72 19.84 21.24 22.02 22.96 25.00 26.19 27.52 28.90 30.17 31.34 32.43 33.47 35.64 37.82 41.08 44.94
351 396 461 512 586 727 840 969 1096 1244 1391 1535 1678 1858 2155 2590 3252
2.16 1.36 0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
16338 14169 12171 11291 10388 9562 8752 7997 7341 6827 6414 6071 5778 5543 5052 4601 4027
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Single Aluminum conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
169 213 268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115
435 479 534 565 602 642 689 741 796 846 892 935 976 1011 1097 1192 1344
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
6 6 6 7 9 11 14 17 20 24 28 32 36 25 30 24 31
51 51 51 51 51 51 51 51 51 51 51 51 51 64 64 81 81
0.0122 0.0122 0.0122 0.0142 0.0183 0.0223 0.0284 0.0345 0.0406 0.0487 0.0568 0.0649 0.0730 0.0808 0.0969 0.123 0.159
607 651 706 737 774 814 861 913 967 1017 1063 1106 1147 1233 1318 1447 1599
60 60 60 60 60 80 80 80 80 80 80 80 80 80 80 80 80
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
737 781 836 867 904 984 1031 1084 1138 1188 1234 1277 1318 1403 1489 1617 1769
236 266 310 344 394 489 565 651 736 836 935 1032 1128 1249 1449 1741 2186
0.658 0.414 0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
49
0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
10152 8804 7563 7016 6455 5942 5438 4969 4562 4242 3985 3773 3590 3444 3139 2859 2502
MV-90 15 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 26.80 27.84 28.75 30.93 33.34 37.20 Notes:
CONCENTRIC NEUTRAL
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
6 7 9 11 14 17 20 24 28 32 36 25 30 24 31
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 2.05 2.05
7.9 9.2 11.8 14.4 18.3 22.3 26.2 31.4 36.7 41.9 47.1 52.1 62.5 79.4 102.5
20.99 21.77 22.71 23.73 24.92 26.25 27.63 28.90 30.65 31.74 32.78 34.37 36.55 39.80 43.66
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79
25.32 26.10 27.04 28.06 29.25 30.58 31.96 33.23 34.98 36.07 37.11 38.70 40.88 44.14 49.56
618 674 755 846 964 1098 1232 1386 1573 1723 1872 2021 2328 2774 3626
0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
16393 15303 14175 13131 12097 11123 10268 9592 9044 8588 8195 7879 7214 6600 5809
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Single Aluminum conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
268 299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
175 175 175 175 175 175 175 175 175 175 175 175 175 175 175
655 685 722 763 809 862 916 966 1012 1055 1096 1132 1218 1313 1465 Notes:
50
CONCENTRIC NEUTRAL STRANDS No.
6 7 9 11 14 17 20 24 28 32 36 25 30 24 31
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 51 51 51 51 51 51 51 51 51 64 64 81 81
0.0122 0.0142 0.0183 0.0223 0.0284 0.0345 0.0406 0.0487 0.0568 0.0649 0.0730 0.0808 0.0969 0.123 0.159
826 857 894 934 981 1034 1088 1138 1207 1250 1291 1353 1439 1567 1719
80 80 80 80 80 80 80 80 80 80 80 80 80 80 110
997 1028 1065 1105 1152 1204 1258 1308 1377 1420 1461 1524 1609 1738 1951
415 453 507 568 648 738 828 931 1057 1158 1258 1358 1565 1864 2437
0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
10186 9509 8808 8160 7517 6912 6381 5960 5620 5337 5092 4896 4483 4101 3610
MV-90 25 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
CONCENTRIC NEUTRAL INSULATION INSULATION JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE THICKNESS DIAMETER STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ (mm) (mm) No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 27.53 28.80 29.97 31.06 32.10 33.01 35.19 37.60 41.46
7 9 11 14 17 20 24 28 32 36 25 30 24 31
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 2.05 2.05
9.2 11.8 14.4 18.3 22.3 26.2 31.4 36.7 41.9 47.1 52.1 62.5 79.4 102.5
26.03 26.97 27.99 29.18 31.09 32.47 33.74 34.91 36.00 37.04 38.63 40.81 44.06 48.78
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79
30.36 31.30 32.32 33.51 35.42 36.80 38.07 39.24 40.33 41.37 42.96 46.71 49.96 54.68
849 936 1033 1159 1337 1481 1644 1804 1961 2116 2271 2755 3227 4025
0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
19847 18509 17258 16006 14814 13758 12915 12227 11651 11150 10747 9893 9096 8060
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Single Aluminum conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
299 336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
260 260 260 260 260 260 260 260 260 260 260 260 260 260
853 890 930 977 1030 1084 1134 1180 1223 1264 1300 1385 1480 1632
CONCENTRIC NEUTRAL STRANDS No.
7 9 11 14 17 20 24 28 32 36 25 30 24 31
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 51 51 51 51 51 51 51 51 64 64 81 81
0.0142 0.0183 0.0223 0.0284 0.0345 0.0406 0.0487 0.0568 0.0649 0.0730 0.0808 0.0969 0.123 0.159
1025 1062 1102 1149 1224 1278 1328 1374 1417 1458 1521 1607 1735 1921
80 80 80 80 80 80 80 80 80 80 80 110 110 110
1195 1232 1273 1319 1395 1449 1499 1545 1588 1629 1691 1839 1967 2153
571 629 694 779 899 995 1105 1212 1318 1422 1526 1851 2168 2705
0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
51
0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
12333 11501 10724 9946 9205 8549 8025 7598 7240 6929 6678 6147 5652 5008
MV-90 35 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
8.53 9.55 10.74 12.07 13.21 14.48 15.65 16.74 17.78 18.69 20.65 23.06 26.92
53.5 67.4 85.0 107.2 126.7 152.0 177.3 202.7 228.0 253.4 304.0 380.0 506.7
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76 8.76
26.97 27.99 29.18 30.51 31.89 33.16 34.33 35.42 36.46 37.37 39.55 41.96 45.82 Notes:
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
9 11 14 17 20 24 28 32 36 25 30 24 31
1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.29 1.63 1.63 2.05 2.05
11.8 14.4 18.3 22.3 26.2 31.4 36.7 41.9 47.1 52.1 62.5 79.4 102.5
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
31.91 32.93 34.12 35.45 36.83 38.10 39.27 40.36 41.40 42.99 46.03 49.28 53.14
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79
36.24 37.26 38.45 39.78 41.16 42.43 43.60 44.69 45.73 47.32 51.93 55.18 59.04
1185 1290 1424 1577 1729 1900 2067 2231 2393 2554 3146 3636 4384
0.537 0.426 0.338 0.268 0.227 0.189 0.162 0.142 0.126 0.113 0.0945 0.0756 0.0567
0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817 0.2766 0.2721 0.2683 0.2604 0.2521 0.2404
22170 20773 19366 18016 16810 15841 15047 14378 13794 13323 12318 11374 10136
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Single Aluminum conductor, 90°C 100% Insulation Level, 33% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350 400 450 500 600 750 1000
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
336 376 423 475 520 570 616 659 700 736 813 908 1060
0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.353 0.393 0.471 0.589 0.785
345 345 345 345 345 345 345 345 345 345 345 345 345
1062 1102 1149 1201 1256 1306 1352 1394 1435 1471 1557 1652 1804 Notes:
52
CONCENTRIC NEUTRAL STRANDS No.
9 11 14 17 20 24 28 32 36 25 30 24 31
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 51 51 51 51 51 51 51 64 64 81 81
0.0183 0.0223 0.0284 0.0345 0.0406 0.0487 0.0568 0.0649 0.0730 0.0808 0.0969 0.123 0.159
1256 1297 1343 1396 1450 1500 1546 1589 1630 1692 1812 1940 2092
80 80 80 80 80 80 80 80 80 80 110 110 110
1427 1467 1514 1566 1621 1671 1717 1760 1801 1863 2044 2172 2324
797 867 957 1060 1162 1277 1389 1500 1608 1716 2114 2444 2946
0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494 0.0432 0.0384 0.0346 0.0288 0.0230 0.0173
0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533 0.4452 0.4378 0.4318 0.4191 0.4057 0.3869
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
13776 12908 12034 11195 10446 9844 9350 8934 8572 8279 7654 7068 6298
MV-90 5 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
3.40 4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07
8.4 13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
8.86 9.75 10.87 12.27 13.05 13.99 15.01 16.20 17.53
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
6 10 16 26 20 25 32 25 32
1.29 1.29 1.29 1.29 1.63 1.63 1.63 2.05 2.05
7.9 13.1 20.9 34.0 41.7 52.1 66.7 82.7 105.8
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
13.22 14.11 15.23 16.63 18.09 19.03 20.05 22.08 23.41
1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03
15.74 17.42 18.54 19.94 21.40 22.34 23.36 26.42 27.75
311 450 615 876 1044 1258 1539 1935 2378
2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164
0.4010 0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023
15795 13740 11824 10081 9319 8544 7838 7150 6512
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 5 kV Single Copper conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
134 169 213 268 299 336 376 423 475
0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166
90 90 90 90 90 90 90 90 90
349 384 428 483 514 551 591 638 690
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
6 10 16 26 20 25 32 25 32
51 51 51 51 64 64 64 81 81
0.0122 0.0203 0.0325 0.0528 0.0646 0.0808 0.103 0.128 0.164
521 556 600 655 712 749 789 869 922
45 60 60 60 60 60 60 80 80
620 686 730 785 843 880 920 1040 1092
209 302 413 589 702 846 1034 1300 1598
0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
53
0.6454 0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864
9815 8538 7347 6264 5791 5309 4870 4443 4046
MV-90 8 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
4.29 5.41 6.81 7.59 8.53 9.55 10.74 12.07
13.3 21.2 33.6 42.4 53.5 67.4 85.0 107.2
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
11.05 12.17 13.57 14.35 15.29 16.31 17.50 18.83 Notes:
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
10 16 26 20 25 32 25 32
1.29 1.29 1.29 1.63 1.63 1.63 2.05 2.05
13.1 20.9 34.0 41.7 52.1 66.7 82.7 105.8
15.41 16.53 17.93 19.39 20.33 21.35 23.38 24.71
1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03
18.72 19.84 21.24 22.70 23.64 25.68 27.72 29.05
483 650 914 1084 1300 1640 1983 2429
1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164
0.3835 0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023
16338 14169 12171 11291 10388 9562 8752 7997
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Single Copper conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
6 4 2 1 1/0 2/0 3/0 4/0
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
169 213 268 299 336 376 423 475
0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166
15 15 15 15 15 15 15 15
435 479 534 565 602 642 689 741 Notes:
54
CONCENTRIC NEUTRAL STRANDS No.
10 16 26 20 25 32 25 32
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 51 64 64 64 81 81
0.0203 0.0325 0.0528 0.0646 0.0808 0.103 0.128 0.164
607 651 706 763 800 840 921 973
60 60 60 60 60 80 80 80
737 781 836 894 931 1011 1091 1144
325 437 614 728 874 1102 1333 1632
0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500
0.6172 0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
10152 8804 7563 7016 6455 5942 5438 4969
MV-90 15 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
6.81 7.59 8.53 9.55 10.74 12.07
33.6 42.4 53.5 67.4 85.0 107.2
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
26 20 25 32 25 32
1.29 1.63 1.63 1.63 2.05 2.05
34.0 41.7 52.1 66.7 82.7 105.8
20.99 22.45 23.39 24.41 26.44 27.77
2.03 2.03 2.03 2.03 2.03 2.03
25.32 26.78 27.72 28.74 30.78 32.11
1071 1247 1470 1759 2107 2558
0.523 0.415 0.329 0.261 0.207 0.164
0.3487 0.3372 0.3284 0.3199 0.3111 0.3023
16393 15303 14175 13131 12097 11123
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Single Copper conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
268 299 336 376 423 475
0.0521 0.0657 0.0829 0.105 0.132 0.166
175 175 175 175 175 175
655 685 722 763 809 862
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
26 20 25 32 25 32
51 64 64 64 81 81
0.0528 0.0646 0.0808 0.103 0.128 0.164
826 884 921 961 1041 1093
80 80 80 80 80 80
997 1054 1091 1131 1212 1264
719 838 988 1182 1416 1719
0.159 0.126 0.100 0.0795 0.0630 0.0500
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
55
0.5611 0.5427 0.5285 0.5148 0.5006 0.4864
10186 9509 8808 8160 7517 6912
MV-90 25 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
7.59 8.53 9.55 10.74 12.07
42.4 53.5 67.4 85.0 107.2
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 Notes:
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
20 25 32 25 32
1.63 1.63 1.63 2.05 2.05
41.7 52.1 66.7 82.7 105.8
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
26.71 27.65 28.67 30.70 32.61
2.03 2.03 2.03 2.03 2.03
31.04 31.98 33.00 35.04 36.95
1423 1651 1946 2302 2797
0.415 0.329 0.261 0.207 0.164
0.3372 0.3284 0.3199 0.3111 0.3023
19847 18509 17258 16006 14814
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Single Copper conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
299 336 376 423 475
0.0657 0.0829 0.105 0.132 0.166
260 260 260 260 260
853 890 930 977 1030 Notes:
56
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
20 25 32 25 32
64 64 64 81 81
0.0646 0.0808 0.103 0.128 0.164
1051 1089 1129 1209 1284
80 80 80 80 80
1222 1259 1299 1379 1455
956 1109 1308 1547 1880
0.126 0.100 0.0795 0.0630 0.0500
0.5427 0.5285 0.5148 0.5006 0.4864
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
12333 11501 10724 9946 9205
MV-90 35 kV Single Copper conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1/0 2/0 3/0 4/0 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
8.53 9.55 10.74 12.07
53.5 67.4 85.0 107.2
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
8.76 8.76 8.76 8.76
26.97 27.99 29.18 30.51
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
25 32 25 32
1.63 1.63 2.05 2.05
52.1 66.7 82.7 105.8
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
32.59 33.61 35.64 36.97
2.03 2.03 2.03 2.03
36.92 37.94 39.98 41.31
1900 2203 2568 3037
0.329 0.261 0.207 0.164
0.3284 0.3199 0.3111 0.3023
22170 20773 19366 18016
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Single Copper conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
336 376 423 475
0.0829 0.105 0.132 0.166
345 345 345 345
1062 1102 1149 1201
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
25 32 25 32
64 64 81 81
0.0808 0.103 0.128 0.164
1283 1323 1403 1456
80 80 80 80
1454 1494 1574 1626
1277 1481 1726 2041
0.100 0.0795 0.0630 0.0500
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
57
0.5285 0.5148 0.5006 0.4864
13776 12908 12034 11195
MV-90 5 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
4 2 1 1/0 2/0 3/0 4/0 250 300 350
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65
21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3
CONCENTRIC NEUTRAL INSULATION INSULATION JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE THICKNESS DIAMETER STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ (mm) (mm) No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29
10.87 12.27 13.05 13.99 15.01 16.20 17.53 18.91 20.18 21.35 Notes:
10 16 20 26 20 25 32 25 29 32
1.29 1.29 1.29 1.29 1.63 1.63 1.63 2.05 2.05 2.05
13.1 20.9 26.2 34.0 41.7 52.1 66.7 82.7 95.9 105.8
15.23 16.63 17.41 18.35 20.05 21.24 22.57 24.79 26.06 27.23
1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03
18.54 19.94 20.72 21.66 23.36 25.57 26.90 29.13 30.40 31.57
409 543 629 750 883 1109 1333 1577 1796 1984
1.36 0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162
0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817
11824 10081 9319 8544 7838 7150 6512 5961 5531 5187
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 5 kV Single Aluminum conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
4 2 1 1/0 2/0 3/0 4/0 250 300 350
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
213 268 299 336 376 423 475 520 570 616
0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275
90 90 90 90 90 90 90 90 90 90
428 483 514 551 591 638 690 744 794 841 Notes:
58
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
10 16 20 26 20 25 32 25 29 32
51 51 51 51 64 64 64 81 81 81
0.0203 0.0325 0.0406 0.0528 0.0646 0.0808 0.103 0.128 0.149 0.164
600 655 686 723 789 836 889 976 1026 1072
60 60 60 60 60 80 80 80 80 80
730 785 816 853 920 1007 1059 1147 1197 1243
275 365 423 504 594 745 896 1060 1207 1333
0.414 0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533
7347 6264 5791 5309 4870 4443 4046 3704 3437 3223
MV-90 8 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
4 2 1 1/0 2/0 3/0 4/0 250 300 350 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
5.41 6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65
21.2 33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92
12.17 13.57 14.35 15.29 16.31 17.50 18.83 20.21 21.48 22.65
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
10 16 20 26 20 25 32 25 29 32
1.29 1.29 1.29 1.29 1.63 1.63 1.63 2.05 2.05 2.05
13.1 20.9 26.2 34.0 41.7 52.1 66.7 82.7 95.9 105.8
16.53 17.93 18.71 19.65 21.35 22.54 23.87 26.09 27.36 28.53
1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03
19.84 21.24 22.02 22.96 25.68 26.87 28.20 30.43 31.70 32.87
445 581 669 791 985 1157 1384 1630 1852 2042
1.36 0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162
0.3660 0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817
14169 12171 11291 10388 9562 8752 7997 7341 6827 6414
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 8 kV Single Aluminum conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
4 2 1 1/0 2/0 3/0 4/0 250 300 350 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
213 268 299 336 376 423 475 520 570 616
0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275
115 115 115 115 115 115 115 115 115 115
479 534 565 602 642 689 741 796 846 892
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
10 16 20 26 20 25 32 25 29 32
51 51 51 51 64 64 64 81 81 81
0.0203 0.0325 0.0406 0.0528 0.0646 0.0808 0.103 0.128 0.149 0.164
651 706 737 774 840 887 940 1027 1077 1123
60 60 60 60 80 80 80 80 80 80
781 836 867 904 1011 1058 1110 1198 1248 1294
299 391 449 532 662 778 930 1096 1245 1372
0.414 0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
59
0.5890 0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533
8804 7563 7016 6455 5942 5438 4969 4562 4242 3985
MV-90 15 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
6.81 7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65
33.6 42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
16.63 17.41 18.35 19.37 20.56 21.89 23.27 24.54 25.71 Notes:
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
16 20 26 20 25 32 25 29 32
1.29 1.29 1.29 1.63 1.63 1.63 2.05 2.05 2.05
20.9 26.2 34.0 41.7 52.1 66.7 82.7 95.9 105.8
20.99 21.77 22.71 24.41 25.60 26.93 29.15 30.42 32.17
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
25.32 26.10 27.04 28.74 29.93 31.26 33.49 34.76 36.51
738 831 960 1103 1281 1514 1766 1994 2224
0.854 0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162
0.3487 0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817
16393 15303 14175 13131 12097 11123 10268 9592 9044
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 15 kV Single Aluminum conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
2 1 1/0 2/0 3/0 4/0 250 300 350
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
268 299 336 376 423 475 520 570 616
0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275
175 175 175 175 175 175 175 175 175
655 685 722 763 809 862 916 966 1012 Notes:
60
CONCENTRIC NEUTRAL STRANDS No.
16 20 26 20 25 32 25 29 32
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 51 64 64 64 81 81 81
0.0325 0.0406 0.0528 0.0646 0.0808 0.103 0.128 0.149 0.164
826 857 894 961 1008 1060 1148 1198 1267
80 80 80 80 80 80 80 80 80
997 1028 1065 1131 1178 1231 1318 1368 1437
496 558 645 742 861 1017 1187 1340 1495
0.260 0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494
0.5611 0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
10186 9509 8808 8160 7517 6912 6381 5960 5620
MV-90 25 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 Notes:
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
7.59 8.53 9.55 10.74 12.07 13.21 14.48 15.65
42.4 53.5 67.4 85.0 107.2 126.7 152.0 177.3
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60
21.67 22.61 23.63 24.82 26.15 27.53 28.80 29.97
CONCENTRIC NEUTRAL STRANDS STRANDS CROSS No. DIAMETER SECTION (mm) (mm²)
20 26 20 25 32 25 29 32
1.29 1.29 1.63 1.63 1.63 2.05 2.05 2.05
26.2 34.0 41.7 52.1 66.7 82.7 95.9 105.8
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (kg/km)
26.03 26.97 28.67 29.86 31.77 33.99 35.26 36.43
2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03
30.36 31.30 33.00 34.19 36.10 38.33 39.60 40.77
1006 1141 1291 1476 1753 2015 2252 2455
0.678 0.537 0.426 0.338 0.268 0.227 0.189 0.162
0.3372 0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817
19847 18509 17258 16006 14814 13758 12915 12227
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 25 kV Single Aluminum conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1 1/0 2/0 3/0 4/0 250 300 350 Notes:
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
299 336 376 423 475 520 570 616
0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275
260 260 260 260 260 260 260 260
853 890 930 977 1030 1084 1134 1180
CONCENTRIC NEUTRAL STRANDS No.
20 26 20 25 32 25 29 32
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 51 64 64 64 81 81 81
0.0406 0.0528 0.0646 0.0808 0.103 0.128 0.149 0.164
1025 1062 1129 1176 1251 1338 1388 1434
80 80 80 80 80 80 80 80
1195 1232 1299 1346 1421 1509 1559 1605
676 767 868 992 1178 1354 1513 1650
0.207 0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
61
0.5427 0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533
12333 11501 10724 9946 9205 8549 8025 7598
MV-90 35 kV Single Aluminum conductor, 90°C (International Unit System) 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350
CONDUCTOR CROSS DIAMETER SECTION (mm) (mm²)
8.53 9.55 10.74 12.07 13.21 14.48 15.65
53.5 67.4 85.0 107.2 126.7 152.0 177.3
INSULATION INSULATION THICKNESS DIAMETER (mm) (mm)
8.76 8.76 8.76 8.76 8.76 8.76 8.76
26.97 27.99 29.18 30.51 31.89 33.16 34.33 Notes:
CONCENTRIC NEUTRAL JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ No. DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (mm²) (kg/km)
26 20 25 32 25 29 32
1.29 1.63 1.63 1.63 2.05 2.05 2.05
34.0 41.7 52.1 66.7 82.7 95.9 105.8
31.91 33.61 34.80 36.13 38.35 39.62 40.79
2.03 2.03 2.03 2.03 2.03 2.03 2.03
36.24 37.94 39.13 40.46 42.69 43.96 45.13
1390 1548 1742 1992 2263 2508 2719
0.537 0.426 0.338 0.268 0.227 0.189 0.162
0.3284 0.3199 0.3111 0.3023 0.2945 0.2875 0.2817
22170 20773 19366 18016 16810 15841 15047
1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
MV-90 35 kV Single Aluminum conductor, 90°C 100% Insulation Level, 100% Concentric Neutral Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5-46 kV. SIZE AWG / kcmil
1/0 2/0 3/0 4/0 250 300 350
CONDUCTOR CROSS INSULATION INSULATION DIAMETER SECTION THICKNESS DIAMETER (mm) (sq inches) (mm) (mm)
336 376 423 475 520 570 616
0.0829 0.105 0.132 0.166 0.196 0.236 0.275
345 345 345 345 345 345 345
1062 1102 1149 1201 1256 1306 1352 Notes:
62
CONCENTRIC NEUTRAL STRANDS No.
26 20 25 32 25 29 32
JACKET OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE STRANDS CROSS DIAMETER THICKNESS DIAMETER TOTAL REACTANCE² REACTANCE² AT 20°C¹ DIAMETER SECTION No. (mm) (mm) WEIGHT (ohm/km) (ohm-km) (ohm/km) (mm) (sq inches) (kg/km)
51 64 64 64 81 81 81
0.0528 0.0646 0.0808 0.103 0.128 0.149 0.164
1256 1323 1370 1422 1510 1560 1606
80 80 80 80 80 80 80
1427 1494 1541 1593 1681 1731 1777
934 1040 1170 1339 1521 1686 1827
0.164 0.130 0.103 0.0817 0.0691 0.0576 0.0494
0.5285 0.5148 0.5006 0.4864 0.4739 0.4627 0.4533
1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum. 2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration. 3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
13776 12908 12034 11195 10446 9844 9350
Covered Cable for Treed Zones 5 - 46 kV
Description ACSR thermo set covered.
Contruction Conductor ACSR cable, compressed. Conductor Shield Cross linked polyethylene semiconductor. Blocking against moisture Conductor filled with blocking compounds against moisture. Conductor shield Cross linked polyethylene semiconductor (for voltages greater than 5 kV). Covering Cross linked polyethylene XLPE tracking resistant. One single layer for 5 kV Cables. Two layers, inner layer natural XLPE, and external layer black XLPE. Options AAC or AAAC conductors.
Characteristics Operating Temperature Normal continuous operation 90째C for wet or dry locations. Overload 130째C. Short circuit 250째C. Rated Voltage 5, 8, 15, 25 and 35 kV.
63
Applications Distribution of electric energy in treed Areas or Industrial Zones. This cable offers more reliability in operation because of outage reduction by accidental contacts between phases, phase and ground. Maintenance and cutting trees cost also are reduced. The external cover is sunlight resistant, corrosive and contaminants agent resistant and tracking resistant.
Standards CENTELSA’s 5-35 kV Covered conductors are manufactured in accordance with the following standards: ASTM B232, NTC-ICONTEC 309. Aluminum Conductor Steel Reinforced. ABNT EB-2173 Overhead cables XLPR covered for use in treed areas, 15 and 25 kV Voltages. CENTELSA’s specifications for covered cables from 5 to 46 kV.
Note: Configurations and sizes herein not specified are available upon request.
64
Covered Cable for treed zones 5 kV 90°C (International Unit System) Standards: ABNT 2173 AND CENTELSA’S Specifications.
ACSR CODE
SIZE AWG / kcmil
4 2 1 1/0 2/0 3/0 4/0 266.8 336.4 Notes:
SWAN SPARROW ROBIN RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN
STRANDS ALUMINUM
STEEL
6 6 6 6 6 6 6 18 18
1 1 1 1 1 1 1 1 1
CONDUCTOR DIAMETER (mm)
6.16 7.78 8.73 9.81 11.01 12.36 13.88 15.00 16.84
CROSS SECTION ALUMINUM (mm²)
21.2 33.6 42.4 53.5 67.5 85.0 107.2 135.2 170.5
STEEL (mm²)
3.5 5.6 7.1 8.9 11.2 14.2 17.9 7.5 9.5
COVERING THICKNESS (mm)
2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16
OVERALL DIAMETER (mm)
10.60 12.22 13.17 14.25 15.45 16.80 18.32 19.44 21.28
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
151 218 264 321 392 480 589 598 737
1.32 0.829 0.658 0.521 0.414 0.328 0.260 0.211 0.167
APPROXIMATE TOTAL WEIGHT (lb/1000ft)
DC RESISTANT AT 20°C¹ (ohm/1000ft)
102 147 178 216 263 322 396 402 495
0.402 0.253 0.201 0.159 0.126 0.100 0.079 0.064 0.051
1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 5 kV 90°C Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
4 2 1 1/0 2/0 3/0 4/0 266.8 336.4
SWAN SPARROW ROBIN RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN
Notes:
STRANDS ALUMINUM
STEEL
6 6 6 6 6 6 6 18 18
1 1 1 1 1 1 1 1 1
CONDUCTOR DIAMETER (mils)
243 306 344 386 433 487 546 591 663
CROSS SECTION ALUMINUM (sq inches)
0.0328 0.0521 0.0657 0.0830 0.105 0.132 0.210 0.264 0.312
STEEL (sq inches)
0.00547 0.00870 0.0110 0.0138 0.0174 0.0220 0.0116 0.0147 0.0173
COVERING THICKNESS (mils)
85 85 85 85 85 85 85 85 85
OVERALL DIAMETER (mils)
417 481 519 561 608 661 721 765 838
1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
65
Covered Cable for treed zones 15 kV 90°C (International Unit System) Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
4 2 1 1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
SWAN SPARROW ROBIN RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
STRANDS ALUMINUM
STEEL
6 6 6 6 6 6 6 18 18 18 18 18 18
1 1 1 1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR DIAMETER (mm) ALUMINUM STEEL (mm²) (mm²)
6.16 7.78 8.73 9.81 11.01 12.36 13.88 15.00 16.84 18.31 20.05 21.66 23.16 Notes:
21.2 33.6 42.4 53.5 67.5 85.0 107.2 135.2 170.5 201.5 241.7 282.1 322.3
3.5 5.6 7.1 8.9 11.2 14.2 17.9 7.5 9.5 11.2 13.4 15.7 17.9
CONDUCTOR SHIELD THICKNESS (mm)
1st LAYER COVERING THICKNESS (mm)
0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.45 0.45 0.45 0.45 0.57 0.57
1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91
2nd LAYER COVERING THICKNESS (mm)
1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91
OVERALL DIAMETER (mm)
16.06 17.68 18.63 19.71 20.91 22.26 23.78 25.14 26.98 27.25 28.99 30.82 32.32
APPROXIMATE TOTAL WEIGHT (kg/km)
243 318 369 431 506 600 716 750 898 965 1120 1286 1439
DC RESISTANT AT 20°C¹ (ohm/km)
1.32 0.829 0.658 0.521 0.414 0.328 0.260 0.211 0.167 0.141 0.118 0.101 0.088
1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 15 kV 90°C Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
4 2 1 1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
ACSR CODE
SWAN SPARROW ROBIN RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
STRANDS ALUMINUM
STEEL
6 6 6 6 6 6 6 18 18 18 18 18 18
1 1 1 1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR CONDUCTOR SHIELD DIAMETER THICKNESS (mils) ALUMINUM STEEL (mils) (sq inches) (sq inches)
243 306 344 386 433 487 546 591 663 721 790 853 912 Notes:
66
0.0328 0.0521 0.0657 0.0830 0.105 0.132 0.210 0.264 0.312 0.375 0.437 0.166 0.500
0.00547 0.00870 0.0110 0.0138 0.0174 0.0220 0.0116 0.0147 0.0173 0.0208 0.0243 0.0277 0.0278
13 13 13 13 13 13 13 18 18 18 18 22 22
1st LAYER COVERING THICKNESS (mils)
75 75 75 75 75 75 75 75 75 75 75 75 75
2nd LAYER COVERING THICKNESS (mils)
75 75 75 75 75 75 75 75 75 75 75 75 75
OVERALL DIAMETER (mils)
APPROXIMATE TOTAL WEIGHT (lb/1000 ft)
632 696 733 776 823 876 936 990 1062 1073 1142 1214 1272
164 214 248 290 340 403 481 504 603 648 753 864 967
DC RESISTANT AT 20°C¹ (ohm/1000 ft)
0.402 0.253 0.201 0.159 0.126 0.100 0.079 0.064 0.051 0.043 0.036 0.031 0.027
1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 25 kV 90°C (International Unit System) Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
2 1 1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
SPARROW ROBIN RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
Notes:
STRANDS ALUMINUM
6 6 6 6 6 6 18 18 18 18 18 18
STEEL
1 1 1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR DIAMETER (mm) ALUMINUM STEEL (mm²) (mm²)
7.78 8.73 9.81 11.01 12.36 13.88 15.00 16.84 18.31 20.05 21.66 23.16
33.6 42.4 53.5 67.5 85.0 107.2 135.2 170.5 201.5 241.7 282.1 322.3
5.6 7.1 8.9 11.2 14.2 17.9 7.5 9.5 11.2 13.4 15.7 17.9
CONDUCTOR SHIELD THICKNESS (mm)
1st LAYER COVERING THICKNESS (mm)
0.34 0.34 0.34 0.34 0.34 0.34 0.45 0.45 0.45 0.45 0.57 0.57
3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18
2nd LAYER COVERING THICKNESS (mm)
3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18
OVERALL DIAMETER (mm)
APPROXIMATE TOTAL WEIGHT (kg/km)
22.84 23.79 24.87 26.07 27.42 28.94 30.30 32.14 32.41 34.15 35.98 37.48
471 528 598 683 786 914 958 1119 1188 1357 1536 1700
OVERALL DIAMETER (mils)
APPROXIMATE TOTAL WEIGHT (lb/1000 ft)
899 937 979 1026 1079 1139 1193 1266 1276 1345 1417 1476
316 355 402 459 528 614 644 752 799 912 1033 1143
DC RESISTANT AT 20°C¹ (ohm/km)
0.829 0.658 0.521 0.414 0.328 0.260 0.211 0.167 0.141 0.118 0.101 0.088
1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 25 kV 90°C Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
2 1 1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
SPARROW ROBIN RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
Notes:
STRANDS ALUMINUM
6 6 6 6 6 6 18 18 18 18 18 18
STEEL
1 1 1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR CONDUCTOR SHIELD DIAMETER THICKNESS (mils) ALUMINUM STEEL (mils) (sq inches) (sq inches)
306 344 386 433 487 546 591 663 721 790 853 912
0.0521 0.0657 0.0830 0.105 0.132 0.210 0.264 0.312 0.375 0.437 0.166 0.500
0.00870 0.0110 0.0138 0.0174 0.0220 0.0116 0.0147 0.0173 0.0208 0.0243 0.0277 0.0278
13 13 13 13 13 13 18 18 18 18 22 22
1st LAYER COVERING THICKNESS (mils)
125 125 125 125 125 125 125 125 125 125 125 125
2nd LAYER COVERING THICKNESS (mils)
125 125 125 125 125 125 125 125 125 125 125 125
1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
67
DC RESISTANT AT 20°C¹ (ohm/1000 ft)
0.253 0.201 0.159 0.126 0.100 0.079 0.064 0.051 0.043 0.036 0.031 0.027
Covered Cable for treed zones 35 kV 90°C (International Unit System) Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
STRANDS ALUMINUM
6 6 6 6 18 18 18 18 18 18
STEEL
1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR DIAMETER (mm) ALUMINUM STEEL (mm²) (mm²)
9.81 11.01 12.36 13.88 15.00 16.84 18.31 20.05 21.66 23.16 Notes:
53.5 67.5 85.0 107.2 135.2 170.5 201.5 241.7 282.1 322.3
8.9 11.2 14.2 17.9 7.5 9.5 11.2 13.4 15.7 17.9
CONDUCTOR SHIELD THICKNESS (mm)
1st LAYER COVERING THICKNESS (mm)
0.34 0.34 0.34 0.34 0.45 0.45 0.45 0.45 0.57 0.57
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
2nd LAYER COVERING THICKNESS (mm)
3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18
OVERALL DIAMETER (mm)
APPROXIMATE TOTAL WEIGHT (kg/km)
24.87 26.07 27.42 28.94 30.30 32.14 32.41 34.15 35.98 37.48
598 683 786 914 958 1119 1188 1357 1536 1700
DC RESISTANT AT 20°C¹ (ohm/km)
0.521 0.414 0.328 0.260 0.211 0.167 0.141 0.118 0.101 0.088
1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 35 kV 90°C Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
STRANDS ALUMINUM
6 6 6 6 18 18 18 18 18 18
STEEL
CROSS SECTION CONDUCTOR CONDUCTOR SHIELD DIAMETER THICKNESS (mils) ALUMINUM STEEL (mils) (sq inches) (sq inches)
1 1 1 1 1 1 1 1 1 1
386 433 487 546 591 663 721 790 853 912 Notes:
68
0.0830 0.105 0.132 0.210 0.264 0.312 0.375 0.437 0.166 0.500
0.0138 0.0174 0.0220 0.0116 0.0147 0.0173 0.0208 0.0243 0.0277 0.0278
13 13 13 13 18 18 18 18 22 22
1st LAYER COVERING THICKNESS (mils)
175 175 175 175 175 175 175 175 175 175
2nd LAYER COVERING THICKNESS (mils)
125 125 125 125 125 125 125 125 125 125
OVERALL DIAMETER (mils)
APPROXIMATE TOTAL WEIGHT (lb/1000 ft)
979 1026 1079 1139 1193 1266 1276 1345 1417 1476
402 459 528 614 644 752 799 912 1033 1143
DC RESISTANT AT 20°C¹ (ohm/1000 ft)
0.159 0.126 0.100 0.079 0.064 0.051 0.043 0.036 0.031 0.027
1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 46 kV 90°C (International Unit System) Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
ACSR CODE
1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636
RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
Notes:
STRANDS ALUMINUM
STEEL
6 6 6 6 18 18 18 18 18 18
1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR DIAMETER (mm) ALUMINUM STEEL (mm²) (mm²)
9.81 11.01 12.36 13.88 15.00 16.84 18.31 20.05 21.66 23.16
53.5 67.5 85.0 107.2 135.2 170.5 201.5 241.7 282.1 322.3
8.9 11.2 14.2 17.9 7.5 9.5 11.2 13.4 15.7 17.9
CONDUCTOR SHIELD THICKNESS (mm)
1st LAYER COVERING THICKNESS (mm)
2nd LAYER COVERING THICKNESS (mm)
OVERALL DIAMETER (mm)
APPROXIMATE TOTAL WEIGHT (kg/km)
DC RESISTANT AT 20°C¹ (ohm/km)
0.34 0.34 0.34 0.34 0.45 0.45 0.45 0.45 0.57 0.57
5.72 5.72 5.72 5.72 5.72 5.72 5.72 5.72 5.72 5.72
4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45 4.45
29.91 31.11 32.46 33.98 35.34 37.18 37.45 39.19 41.02 42.52
799 892 1006 1144 1198 1374 1444 1626 1819 1994
0.521 0.414 0.328 0.260 0.211 0.167 0.141 0.118 0.101 0.088
1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
Covered Cable for treed zones 46 kV 90°C Standards: ABNT 2173 AND CENTELSA’S Specifications.
SIZE AWG / kcmil
1/0 2/0 3/0 4/0 266.8 336.4 397.5 477 556.5 636 Notes:
ACSR CODE
RAVEN QUAIL PIGEON PENGUIN WAXWING MERLIN CHICADEE PELICAN OSPREY KINGBIRD
STRANDS ALUMINUM
STEEL
6 6 6 6 18 18 18 18 18 18
1 1 1 1 1 1 1 1 1 1
CROSS SECTION CONDUCTOR CONDUCTOR SHIELD DIAMETER THICKNESS (mils) ALUMINUM STEEL (mils) (sq inches) (sq inches)
386 433 487 546 591 663 721 790 853 912
0.0830 0.105 0.132 0.210 0.264 0.312 0.375 0.437 0.166 0.500
0.0138 0.0174 0.0220 0.0116 0.0147 0.0173 0.0208 0.0243 0.0277 0.0278
13 13 13 13 18 18 18 18 22 22
1st LAYER COVERING THICKNESS (mils)
2nd LAYER COVERING THICKNESS (mils)
OVERALL DIAMETER (mils)
APPROXIMATE TOTAL WEIGHT (lb/1000 ft)
DC RESISTANT AT 20°C¹ (ohm/1000 ft)
225 225 225 225 225 225 225 225 225 225
175 175 175 175 175 175 175 175 175 175
1178 1225 1278 1338 1391 1464 1474 1543 1615 1674
537 600 676 769 805 923 971 1093 1222 1340
0.159 0.126 0.100 0.079 0.064 0.051 0.043 0.036 0.031 0.027
1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel. 2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.
69
Medium Voltage Cables Ampacity Ampacity (Amperes) Triplexed conductors Air Installation. 40°C Ambient Temperature. 90°C and 105°C Conductor Temperature. SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Notes:
CROSS SECTION (mm²)
COPPER CONDUCTOR¹ 2001 - 5000 Volts
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ALUMINUM CONDUCTOR²
5001 - 35000 Volts
2001 - 5000 Volts
5001 - 35000 Volts
90° C
105° C
90° C
105° C
90° C
105° C
90° C
105° C
65 90 120 160 185 215 250 290 335 375 465 580 750 880
74 99 130 175 205 240 275 320 375 415 515 645 835 980
100 130 170 195 225 260 300 345 380 470 580 730 850
110 140 195 225 255 295 340 390 430 525 650 820 950
50 70 90 125 145 170 195 225 265 295 365 460 600 715
57 77 100 135 160 185 215 250 290 325 405 510 665 800
75 100 130 150 175 200 230 270 300 370 460 590 700
84 110 150 175 200 230 265 305 335 415 515 660 780
1. NEC Table 310-67. 2. NEC Table 310-68.
Ampacity (Amperes) Single conductors Air Installation. 40°C Ambient Temperature. 90°C and 105°C Conductor Temperature. SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
CROSS SECTION (mm²)
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
COPPER CONDUCTOR¹ 2001 - 5000 Volts
5001 - 15000 Volts
ALUMINUM CONDUCTOR² 5001 - 15000 Volts
15001 - 35000 Volts
90° C
105° C
90° C
105° C
90° C
105° C
90° C
105° C
90° C
105° C
90° C
105° C
83 110 145 190 225 260 300 345 400 445 550 695 900 1075
93 120 160 215 250 290 330 385 445 495 615 775 1000 1200
110 150 195 225 260 300 345 400 445 550 685 885 1060
125 165 215 250 290 335 385 445 495 610 765 990 1185
225 260 300 345 395 440 545 680 870 1040
250 290 330 380 445 490 605 755 970 1160
64 85 115 150 175 200 230 270 310 345 430 545 710 855
71 95 125 165 195 225 260 300 350 385 480 605 790 950
87 115 150 175 200 235 270 310 345 430 535 700 840
97 130 170 195 225 260 300 350 385 480 600 780 940
175 200 230 270 310 345 430 530 685 825
195 225 260 300 345 380 475 590 765 920
Notes:
70
1. NEC Table 310-69. 2. NEC Table 310-70.
15001 - 35000 Volts
2001 - 5000 Volts
Ampacity (Amperes) Three conductors cable Air Installation. 40°C Ambient Temperature. 90°C and 105°C Conductor Temperature. CROSS SECTION (mm²)
SIZE AWG / kcmil
COPPER CONDUCTOR¹ 2001 - 5000 Volts 90° C
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Notes:
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
59 79 105 140 160 185 215 250 285 320 395 485 615 705
ALUMINUM CONDUCTOR²
5001 - 35000 Volts
105° C
90° C
66 88 115 154 180 205 240 280 320 355 440 545 685 790
93 120 165 185 215 245 285 325 360 435 535 670 770
2001 - 5000 Volts
5001 - 35000 Volts
105° C
90° C
105° C
90° C
105° C
105 135 185 210 240 275 315 360 400 490 600 745 860
46 61 81 110 125 145 170 195 225 250 310 385 495 585
51 68 90 120 140 160 185 215 250 280 345 430 550 650
72 95 125 145 170 190 220 255 280 345 425 540 635
80 105 145 165 185 215 245 285 315 385 475 600 705
1. NEC Table 310-71. 2. NEC Table 310-72.
Ampacity (Amperes) Triplexed or three conductors cable Installation in insulated duct at air. 40°C Ambient Temperature. 90°C and 105°C Conductor Temperature. SIZE AWG / kcmil
CROSS SECTION (mm²)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
Notes:
COPPER CONDUCTOR¹ 2001 - 5000 Volts
ALUMINUM CONDUCTOR²
5001 - 35000 Volts
2001 - 5000 Volts
5001 - 35000 Volts
90° C
105° C
90° C
105° C
90° C
105° C
90° C
105° C
55 75 97 130 155 180 205 240 280 315 385 475 600 690
61 84 110 145 175 200 225 270 305 355 430 530 665 770
83 110 150 170 195 225 260 295 330 395 480 585 675
93 120 165 190 215 255 290 330 365 440 535 655 755
43 58 76 100 120 140 160 190 215 250 305 380 490 580
48 65 85 115 135 155 175 210 240 280 340 425 545 645
65 84 115 130 150 175 200 230 255 310 385 485 565
72 94 130 150 170 200 225 260 290 350 430 540 640
1. NEC Table 310-73 2. NEC Table 310-74
71
Ampacity (Amperes) Three conductors cable Installation in insulated duct at air. 40°C Ambient Temperature. 90°C and 105°C Conductor Temperature. SIZE AWG / kcmil
CROSS SECTION (mm²)
COPPER CONDUCTOR¹ 2001 - 5000 Volts 90° C
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Notes:
72
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
52 69 91 125 140 165 190 220 255 280 350 425 525 590
1. NEC Table 310-75. 2. NEC Table 310-76.
105° C
58 77 100 135 155 185 210 245 285 315 390 475 585 660
ALUMINUM CONDUCTOR²
5001 - 35000 Volts 90° C
83 105 145 165 195 220 250 290 315 385 470 570 650
2001 - 5000 Volts
5001 - 35000 Volts
105° C
90° C
105° C
90° C
105° C
92 120 165 185 215 245 280 320 350 430 525 635 725
41 53 71 96 110 130 150 170 200 220 275 340 430 505
46 59 79 105 125 145 165 190 225 245 305 380 480 560
64 84 115 130 150 170 195 225 250 305 380 470 550
71 94 125 145 170 190 220 255 280 340 425 520 615
Ampacity (Amperes) Three single conductors IInstallation in underground electrical ducts (Three conductors by each electrical duct). 20°C Ambient Temperature (Earth). 100% Load Factor. RHO 90. 90°C and 105°C Conductor Temperature. COPPER CONDUCTOR ¹ SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
CROSS SECTION (mm²)
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT - FIGURE 1 2001 - 5000 Volts
THREE CIRCUITS - FIGURE 2
5001 - 35000 Volts
2001 - 5000 Volts
SIX CIRCUITS - FIGURE 3
5001 - 35000 Volts
2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
64 85 110 145 170 195 220 250 290 320 385 470 585 670
69 92 120 155 180 210 235 270 310 345 415 505 630 720
90 115 155 175 200 230 260 295 325 390 465 565 640
97 125 165 185 215 245 275 315 345 415 500 610 690
56 73 95 125 140 160 185 210 235 260 315 375 460 525
60 79 100 130 150 175 195 225 255 280 335 405 495 565
77 99 130 145 165 185 210 240 260 310 370 440 495
83 105 135 155 175 200 225 255 280 330 395 475 535
48 62 80 105 115 135 150 170 195 210 250 300 365 410
52 67 86 110 125 145 160 185 210 225 270 325 395 445
64 82 105 120 135 150 170 190 210 245 290 350 390
68 88 115 125 145 165 185 205 225 265 310 375 415
ALUMINUM CONDUCTOR ² SIZE AWG / kcmil
CROSS SECTION (mm²)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT - FIGURE 1 2001 - 5000 Volts 90°C
Notes:
50 66 86 115 130 150 170 195 225 250 305 370 470 545
105°C
54 71 93 125 140 160 185 210 245 270 325 400 505 590
THREE CIRCUITS - FIGURE 2
5001 - 35000 Volts 90°C
70 91 120 135 155 175 200 230 250 305 370 455 525
105°C
75 98 130 145 165 190 215 245 270 330 400 490 565
2001 - 5000 Volts 90°C
44 57 74 96 110 125 145 160 185 205 245 295 370 425
105°C
47 61 80 105 120 135 155 175 200 220 265 320 395 460
SIX CIRCUITS - FIGURE 3
5001 - 35000 Volts 90°C
60 77 100 110 125 145 165 185 200 245 290 355 405
105°C
65 83 105 120 140 155 175 200 220 260 315 385 440
2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
38 48 62 80 91 105 115 135 150 165 195 240 290 335
41 52 67 86 98 110 125 145 165 180 210 255 315 360
50 64 80 90 105 115 130 150 165 195 230 280 320
54 69 88 99 110 125 145 160 175 210 250 305 345
1. NEC Table 310-77. 2. NEC Table 310-78.
73
Ampacity (Amperes) Three conductors cable Installation in underground electrical ducts (One conductor by each electrical duct). 20°C Ambient Temperature (Earth). 100% Load Factor. RHO 90. 90°C and 105°C Conductor Temperature. COPPER CONDUCTOR ¹ SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
CROSS SECTION (mm²)
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT - FIGURE 1 2001 - 5000 Volts
THREE CIRCUITS - FIGURE 2
5001 - 35000 Volts
2001 - 5000 Volts
SIX CIRCUITS - FIGURE 3
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
59 78 100 135 155 175 200 230 265 290 355 430 530 600
64 84 110 145 165 190 220 250 285 315 380 460 570 645
88 115 150 170 195 220 250 285 310 375 450 545 615
95 125 160 185 210 235 270 305 335 400 485 585 660
53 69 89 115 135 150 170 195 225 245 295 355 430 485
57 74 96 125 145 165 185 210 240 265 315 380 465 520
75 97 125 140 160 185 205 230 255 305 360 430 485
81 105 135 155 175 195 220 250 270 325 385 465 515
2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
46 60 77 98 110 125 145 165 185 200 240 290 350 390
50 65 83 105 120 135 155 175 200 220 270 310 375 420
63 81 105 115 130 150 170 190 205 245 290 340 380
68 87 110 125 145 160 180 200 220 275 305 365 405
ALUMINUM CONDUCTOR ² SIZE AWG / kcmil
CROSS SECTION (mm²)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT - FIGURE 1 2001 - 5000 Volts
THREE CIRCUITS - FIGURE 2
5001 - 35000 Volts
2001 - 5000 Volts
SIX CIRCUITS - FIGURE 3
5001 - 35000 Volts
2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
46 61 80 105 120 140 160 180 205 230 280 340 425 495
50 66 86 110 130 150 170 195 220 245 310 365 460 535
69 89 115 135 150 170 195 220 245 295 355 440 510
74 96 125 145 165 185 210 240 265 315 385 475 545
41 54 70 90 105 120 135 155 175 190 230 280 345 400
44 58 75 97 110 125 145 165 185 205 250 300 375 430
59 75 100 110 125 140 160 180 200 240 285 350 400
64 81 105 120 135 155 175 195 215 255 305 375 430
36 46 60 77 87 99 110 130 145 160 190 230 280 320
39 50 65 83 94 105 120 140 155 170 205 245 305 345
49 63 80 90 105 115 130 150 160 190 230 275 315
53 68 86 98 110 125 140 160 170 205 245 295 335
Notes:
74
1. NEC Table 310-79. 2. NEC Table 310-80.
Ampacity (Amperes) Single conductor Installation in direct buried. 20°C Ambient Temperature (Earth). 100% Load Factor. RHO 90. 90°C and 105°C Conductor Temperature. COPPER CONDUCTOR ¹ SIZE AWG / kcmil
CROSS SECTION (mm2)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT, THREE CONDUCTORS - FIGURE 4 2001 - 5000 Volts
5001 - 35000 Volts
TWO CIRCUITS, SIX CONDUCTORS - FIGURE 5 2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
110 140 180 230 260 295 335 385 435 470 570 690 845 980
115 150 195 250 280 320 365 415 465 510 615 745 910 1055
130 170 210 240 275 310 355 405 440 535 650 805 930
140 180 225 260 295 335 380 435 475 575 700 865 1005
100 130 165 215 240 275 310 355 400 435 520 630 775 890
110 140 180 230 260 295 335 380 430 470 560 680 835 960
120 160 195 225 255 290 330 375 410 495 600 740 855
130 170 210 240 275 315 355 405 440 530 645 795 920
ALUMINUM CONDUCTOR ² SIZE AWG / kcmil
CROSS SECTION (mm2)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Notes:
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT, THREE CONDUCTORS - FIGURE 4 2001 - 5000 Volts 90°C
105°C
85 110 140 180 205 230 265 300 340 370 445 540 665 780
90 115 150 195 220 250 285 320 365 395 480 580 720 840
5001 - 35000 Volts 90°C
100 130 165 185 215 245 275 315 345 415 510 635 740
TWO CIRCUITS, SIX CONDUCTORS - FIGURE 5 2001 - 5000 Volts
5001 - 35000 Volts
105°C
90°C
105°C
90°C
105°C
110 140 175 200 230 260 295 340 370 450 545 680 795
80 100 130 165 190 215 245 275 310 340 410 495 610 710
85 110 140 180 200 230 260 295 335 365 440 530 655 765
95 125 155 175 200 225 255 290 320 385 470 580 680
100 130 165 190 215 245 275 315 345 415 505 625 730
1. NEC Table 310-81. 2. NEC Table 310-82.
75
Ampacity (Amperes) Three conductor cable Installation in direct buried. 20°C Ambient Temperature (Earth). 100% Load Factor. RHO 90. 90°C and 105°C Conductor Temperature. COPPER CONDUCTOR ¹ SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
CROSS SECTION (mm2)
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT - FIGURE 6 2001 - 5000 Volts
TWO CIRCUITS - FIGURE 7
5001 - 35000 Volts
2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
85 105 135 180 200 230 260 295 335 365 440 530 650 730
89 115 150 190 215 245 280 320 360 395 475 570 700 785
115 145 185 210 240 270 305 350 380 460 550 665 750
120 155 200 225 255 290 330 375 410 495 590 720 810
80 100 130 165 185 215 240 275 310 340 410 490 595 665
84 105 140 180 200 230 260 295 335 365 440 525 640 715
105 135 170 195 220 250 280 320 350 420 500 605 675
115 145 185 210 235 270 305 345 375 450 535 650 730
ALUMINUM CONDUCTOR ² SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Notes:
76
CROSS SECTION (mm2)
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT - FIGURE 6 2001 - 5000 Volts
TWO CIRCUITS - FIGURE 7
5001 - 35000 Volts
2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
65 80 105 140 155 180 205 230 260 285 345 420 520 600
70 88 115 150 170 190 220 250 280 310 375 450 560 650
90 115 145 165 185 210 240 270 300 360 435 540 620
95 125 155 175 200 225 260 295 320 390 470 580 665
60 75 100 130 145 165 190 215 245 265 320 385 480 550
66 83 110 140 155 180 205 230 260 285 345 415 515 590
80 105 135 150 170 195 220 250 275 330 395 485 560
95 115 145 165 185 210 240 270 295 355 425 525 600
1. NEC Table 310-83. 2. NEC Table 310-84.
Ampacity (Amperes) Triplexed conductors Installation in direct buried. 20°C Ambient Temperature (Earth). 100% Load Factor. RHO 90. 90°C and 105°C Conductor Temperature. COPPER CONDUCTOR ¹ SIZE AWG / kcmil
CROSS SECTION (mm2)
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT, THREE CONDUCTORS - FIGURE 8 2001 - 5000 Volts
5001 - 35000 Volts
TWO CIRCUITS , SIX CONDUCTORS- FIGURE 9 2001 - 5000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90 120 150 195 225 255 290 330 375 410 490 590 725 825
95 130 165 205 240 270 310 360 405 445 580 635 780 885
115 150 190 215 245 275 315 360 390 470 565 685 770
120 160 205 230 260 295 340 385 410 505 605 740 830
85 110 140 180 205 235 265 300 340 370 445 535 650 740
90 115 150 195 220 250 285 320 365 395 480 575 700 795
5001 - 35000 Volts 90°C
105 140 175 200 225 255 290 325 355 425 510 615 690
105°C
115 150 190 215 240 275 315 350 380 455 545 660 745
ALUMINUM CONDUCTOR ² SIZE AWG / kcmil
8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Notes:
CROSS SECTION (mm2)
8.36 13.3 21.1 33.6 42.2 53.5 67.4 85.0 107 127 177 253 380 507
ONE CIRCUIT, THREE CONDUCTORS - FIGURE 8 2001 - 5000 Volts
5001 - 35000 Volts
TWO CIRCUITS , SIX CONDUCTORS- FIGURE 9 2001 - 5000 Volts
5001 - 35000 Volts
90°C
105°C
90°C
105°C
90°C
105°C
90°C
105°C
70 90 120 155 175 200 225 255 290 320 385 465 580 670
75 100 130 165 190 210 240 275 310 350 420 500 625 725
90 115 145 165 190 215 245 280 305 370 445 550 635
95 125 155 175 205 230 265 305 325 400 480 590 680
65 85 110 140 160 180 205 235 265 290 350 420 520 600
70 95 120 150 170 195 220 250 285 310 375 455 560 645
85 105 135 155 175 200 225 255 280 335 405 485 565
90 115 145 170 190 215 245 275 300 360 435 525 605
1. NEC Table 310-85. 2. NEC Table 310-86.
77
Installations Considered in Ampacities Tables
7.5”
FIGURE 1 Electrical duck bank, one electrical duct
7.5”
7.5”
FIGURE 2 Electrical duck bank (27”x11.5”), three electrical ducts
Electrical duck bank (27”x27”), three electrical ducts
7.5” 7.5” 7.5”
7.5”
7.5”
7.5” FIGURE 3 Electrical duck bank (19”x27”), three electrical ducts
78
Electrical duck bank (27”x19”), three electrical ducts
7.5”
7.5”
FIGURE 4 Buried single-conductor cables, one circuit
7.5”
7.5”
24”
7.5”
7.5”
FIGURE 5 Buried single-conductor cables, two circuits
24” FIGURE 6 Buried Three-conductor cable
FIGURE 7 Buried Three-conductor cables
24” FIGURE 8 Buried Triplexed cables, one circuit
FIGURE 9 Buried Triplexed cables, two circuits
Relleno (tierra u hormigón)
Conducto eléctrico
Tierra
Cable o cables
79
Ampacities at Ambient temperature different from the tables
Ampacities at Ambient temperature different from the Tables can be calculated by:
I2 = I1
TC - TA2 - •TD TC - TA1 - •TD
Where: I1 = Ampacity at Temperature Ambient TA1 (From Tables). I2 = Ampacity at Temperature Ambient TA2 (To be calculated). TC = Conductor temperature (°C). TA1 = Temperature Ambient from Tables. TA2 = Different Temperature Ambient. •TD = Dielectric loss temperature rise.
80
Short Circuit Currents for MV Cables Maximum acceptable short circuit current for MV Cables can be calculated by:
I=Ak
log
(
T2 + T1 + t
)
Where: I = Ampacity at Temperature Ambient TA1 (From Tables). A = Conductor Section in mm². K = 341 for copper, 224 for aluminum. T1 = Maximum Operation Temperature (90°C for conductor and 85°C for jacket). T2 = Maximum Acceptable Short Circuit Temperature (250°C for conductor and 200°C for shield). • = 234 for copper, 228 for aluminum. t = Short circuit duration in seconds.
81
Short Circuit Currents for Copper Conductor
1000 900 800 700 600
1 cycle (1/60 sec)
500 400
2 cycles (1/30 sec)
300
4 cycles (1/15 sec)
200
8 cycles (2/15 sec) 16 cycles (4/15 sec) 30 cycles (1/2 sec)
100 90 80
60 cycles (1 sec)
CURRENT (kA)
70 60
100 cycles (5/3 sec)
50 40 30
20
10 9 8 7 6 5 4 3
2
1 10
20
30
40
50
60
70 80 90
100
150
200
250 300 350 400
CONDUCTOR SECTION (mm2)
82
500 600
800
1000
Short Circuit Currents for Aluminum Conductor
1000 900 800 700 600 500 400
1 cycle (1/60 sec)
300
2 cycles (1/30 sec) 200
4 cycles (1/15 sec) 8 cycles (2/15 sec)
100
16 cycles (4/15 sec)
90
CURRENT (kA)
80 70
30 cycles (1/2 sec)
60 50
60 cycles (1 sec)
40
100 cycles (5/3 sec)
30
20
10 9 8 7 6 5 4 3
2
1 10
20
30
40
50
60
70 80 90
100
150
200
250 300 350 400
500 600
800
1000
CONDUCTOR SECTION (mm2)
83
Short Circuit Currents for Copper Shields
100.0 90 80 70 60 50 40
30
20
10.0 9
CURRENT (kA)
8 7 6 5
1 cycle (1/60 sec)
4
2 cycles (1/30 sec) 3
4 cycles (1/15 sec) 2
8 cycles (2/15 sec) 16 cycles (4/15 sec) 1.0
30 cycles (1/2 sec)
0.9 0.8 0.7
60 cycles (1 sec)
0.6 0.5
100 cycles (5/3 sec)
0.4 0.3
0.2
0.1 1
5
6
7
8 9
10
15
20
25
CONDUCTOR SECTION (mm2)
84
30 35 40
50
60 70 80 90
100
Medium Voltage Cables Designs Single Conductors, Copper Tape Shield.
Soft copper or aluminum 1350 H19 compacted conductor XLPE Conductor shield XLPE Insulation XLPE Insulation shield Metallic Shield. Copper tape Flame retardant polyvinyl chloride PVC Jacket
Single Conductors, Copper Wires Shield.
Soft copper or aluminum 1350 H19 Compacted Conductor XLPE Conductor shield XLPE Insulation XLPE Insulation shield Metallic Shield. Copper Wires Flame retardant polyvinyl chloride PVC Jacket
85
Three Conductors, Copper Tape Shield.
Soft copper or aluminum 1350 - H19 compacted conductor XLPE Conductor shield XLPE Insulation XLPE Insulation shield Metallic Shield. Copper tape Flame retardant polyvinyl chloride PVC Filler Flame retardant polyvinyl chloride PVC Jacket
Triplexed Conductors, Copper Tape Shield.
Soft copper or aluminum 1350 - H19 compacted conductor XLPE Conductor shield XLPE Insulation XLPE Insulation shield Metallic Shield. Copper tape Flame retardant polyvinyl chloride PVC Jacket
86
Single Conductors, 33% Concentric Neutral
Soft copper or aluminum 1350 - H19 compacted conductor XLPE Conductor shield XLPE Insulation XLPE Insulation shield 33% Concentric neutral, copper wires Flame retardant polyvinyl chloride PVC jacket
Single Conductors, 100% Concentric Neutral
Soft copper or aluminum 1350 - H19 compacted conductor XLPE Conductor shield XLPE Insulation XLPE Insulation shield 100% Concentric neutral, copper wires Flame retardant polyvinyl chloride PVC jacket
87
Cables for Treed Areas
Compressed ACSR Blocking Compound against moisture Blocking Tape against moisture XLPE Conductor shield XLPE covering, inner layer XLPE Track resistant covering, outer layer
88