
1 minute read
Fig 50- Compton and Edrich Stand Study
Core Analysis: Wankhede
Fig 61- Core Analysis- Wankhede Source- Author (Using AutoCAD)
Advertisement
Inferences:
1. Position of core for West and East Stands doesn’t comply with the codes, and thus doesn’t allow safe travel distance and egress distance. 2. Staircase widths for all cores comply with the minimum requirements as suggested by the codes. However, fire exits are not pressurized, as suggested by the codes.
3. No.of elevators provided per stands would be inefficient in catering to such high occupant load.
4. Frequency of cores and lifts provided in MCA and Garware Pavilion is way too high compared to other stands. Plan Analysis: Wankhede

