cmd_II_15.5-362_kV_2012_EN.pdf

Page 1

COSTRUZIONI ELETTROMECCANICHE - SPA

CMD速 II 15.5-362 kV Current monitoring device

Non-contact non-saturating current transformer The versatile solution for a wide variety of three-phase current measurement applications Group


Performance functions ■ Adds current measurement capability to new and existing equipment in substations. ■ Fully protects vulnerable power transformer bushings and arresters. ■ Measures current in distribution lines, subtransmission lines, transmission lines, and EHV transmission lines in real-time. ■ SMART GRID enabling technology via real-time data. ■ Improves reliability by detecting and isolating faults closer to their origin. ■ Assists in NERC (North American Electric Reliability Corporation) reliability standards compliance by providing technological differentiation for use in redundancy of current sensing to complement the already widely used practice of relaying redundancy. ■ Interfaces with RTUs at switched tap points to minimize the number of customers affected by an outage and the duration due to a fault. ■ When furnished with an RTU, provides invaluable real-time information to a customer’s SCADA system/control center to allow timely action in implementing contingency plans to prevent widespread outages.

Rated voltage (kV)

15.5 - 362

Rated lightning impulse withstand voltage (kV)

110 -1300

Rated permanent current (A)

20 - 4000

Rated short-time current (kA)

.020 - 80

Ambient Temperature Range (°C)

-40 to +50 standard (-50 to +50 optional)

Input Voltage

12/24/48/125/250 VDC or 120/240 VAC

Input Power (W)

125 rated

480 maximum

Output (relay input) (A)

1 rated

20 maximum

Output (RTU input) (V)

10 rated

120 maximum

Measurement Error

1-2 % rated

10% maximum

Relay Burden (Ω)

Benefits ■ Measures phase currents in real time. ■ Outputs compatible with digital, microprocessor-based relays. ■ Calibration by customer using standard CT tools & procedures. ■ Electrical cabinet mounted, wired, and shipped on CapSwitcher®, RLSwitcher®. ■ Self powered (no batteries at line potential). ■ EM real-time data transmission. ■ Applications include: - Capacitor Bank Protection. - Reactor Protection. - Transformer Protection. - Overcurrent. - Transmission/Distribution Lines. - SMART GRID information point. - Allows addition of CTs to protection schemes to meet NERC requirements.

COELME Via G. Galilei, 1/2 - 30036 Santa Maria di Sala (VE) - Italia Tel.: +39 041 486022 - Fax: +39 041 486909 E-Mail: contact@coelme-egic.com, www.coelme-egic.com

0.15 maximum

Key advantages ■ Compact, space saving CT solution. ■ Easy retrofit of current measurement to existing equipment. ■ Reduces installation costs substantially. ■ Immune to CT saturation. ■ Interfaces with digital protection relays or RTUs. ■ Mounts on new or existing equipment. ■ No foundations or structures required. ■ Eliminates the need for freestanding current transformers. ■ Enhances reliability through technologically differentiated current sensing. ■ Sensor has no batteries or solar panels. ■ Fault defections and load monitoring.

EGIC 60b, rue L. et R. Desgrand - 69625 Villeurbanne CEDEX - France Tel.: +33 4 72 66 20 70 - Fax: +33 4 72 39 08 65 E-Mail: contact@coelme-egic.com, www.coelme-egic.com

CMD II en - 10/2012 - Due to product and standards evolution, characteristics and dimensions are likely to change.

Technical data


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.