CHDD AUSTRALIA TOPPRE MODULAR HOUSE
Installation instructions for LGS house
Practical cases CHDD
Assembly of wall components (Wall components - L126 as sample)
Spray code (TOPPRE265-A) is ID code of company and project number. TOPPRE is company logo, 265 is project number, A is house code in this project.
Spray code (N2/L126) is ID code of studs and components. N2 means the current code of studs, L126 means the code of the whole wall components. studs’ code are for assembly of components, components’ code are for installation of the whole building.
Front view
Back view
Assembly of wall components (Wall components - L126 as sample)
View direction
It is necessary to consider left & right of each component during assembly. For example, component code is on the left for component L126, so must ensure component code on the left when placing this wall component.
Installation drawings for wall component of ground floor, L126 (in red circle) as sample
Assembly of wall components
Expansion bolt M12X100 @900MM
Pad @900mm SBS waterproof tape (100*1.5mm) to isolate light steel & foundation
Foundation
Confirm the positions of wall components according to the drawing
Connection of wall joint (expansion bolt + asphalt tape)
Node diagram for external wall
CCA1-4 18 anti-pull connector (2 pcs on each corner)
50*50mm square pad
CCA1-4 18 anti-pull connector (2 pcs on each corner)
1200mm M12*100 expansion bolt
M12*100 expansion bolt
2.1.1 Connection between corner wall & foundation
2.1.4 Connection between wall & foundation(wind speed<=45m/s
1200mm M12*100 expansion bolt
2.1.5 Connection between wall & foundationďź&#x2C6;wind speed>45m/s)
Node diagram for external wall
Door hole width â&#x2030;Ľ900mm CCA1-4 18 anti-pull connector (2 pcs on each corner)
M12*100 expansion bolt
2.1.2 Connection between wall & foundation
Window hole width â&#x2030;Ľ900mm
CCA1-4 18 anti-pull connector (2 pcs on each corner) M12*100 expansion bolt
2.1.3 Connection between wall & foundation
Node diagram for connection between wall
2.2.1 Connection between wall & wall
2.2.2 Connection between wall & wall
CCA7-1 connector plate =1 pcs (8-M4.8*16 flat-head screws / 1 pcs) 2*M5.5*19 hexagonal screw 2 pcs close to the top, another 2 pcs on the bottom Spacing between top & bottom @600mm
CCA7-1 connector plate =1 pcs (8-M4.8*16 flat-head screws / 1 pcs) 2*M5.5*19 hexagonal screw 2 pcs close to the top, another 2 pcs on the bottom Spacing between top & bottom @600mm
2.3.1 Connection between wall & wall
2.3.1 Connection between wall & wall
CCA7-2 “T” shape connector =1 pcs (8-M4.8*16 flathead screws / 1 pcs)
2*M5.5*19 hexagonal screw 2 pcs close to the top, another 2 pcs on the bottom Spacing between top & bottom @600mm
CCA7-2 “T” shape connector =1 pcs (8-M4.8*16 flathead screws / 1 pcs) 2*M5.5*19 hexagonal screw 2 pcs close to the top, another 2 pcs on the bottom Spacing between top & bottom @600mm
Light steel wall components Installation (Sketch display of ground floor)
Assembly of stair
面板布置
CCA7-1 connector plate =1 pcs (8-M4.8*16 flat-head screws / 1 pcs)
立板布置 Layout plan
Assembly mode
Assembly of floor joist
Layout plan
3D model
Node diagram for floor joist
CCA2-1 wind resistance connector =1 pcs (10-M4.8*16 flat-head screws / 1 pcs)
3.1.2 Connection between joist & exterior wall (Wind speed ≤ 45m/s)
CCA2-1 each pcs wind resistance connector on left & right (10-M4.8*16 flat-head screws / 1 pcs)
3.1.3 Connection between joist & exterior wall (Wind speed > 45m/s)
CCA3-2 85 corner brace =1pcs (8-M4.8*16 flathead screws / 1 pcs)
3.1.1 Connection between joist & interior wall
Node diagram for floor joist CCA3-2 85 corner brace =2pcs (8-M4.8*16 flat-head screws / 1 pcs)
CCA3-2 85 corner brace =4pcs (8-M4.8*16 flat-head screws / 1 pcs)
Joist ≤4000mm
CCA3-2 85 corner brace =2pcs (8-M4.8*16 flat-head screws / 1 pcs)
Joist >4000mm
3.3.1 Connection between joist & joist
3.3.2 Connection between joist & joist
3.3.3 Connection between joist & joist
(Wind speed ≤ 45m/s)
(Wind speed > 45m/s, span<=4000mm)
(Wind speed> 45m/s,span>4000mm)
Node diagram for floor joist CCA3-2 85 corner brace =2pcs (8-M4.8*16 flat-head screws / 1 pcs)
CCA3-2 85 corner brace =2pcs (8-M4.8*16 flat-head screws / 1 pcs)
CCA3-2 85 corner brace =4pcs (8-M4.8*16 flat-head screws / 1 pcs)
Joist ≤4000mm Joist >4000mm
3.2.1 Connection between joist & exterior wall (Wind speed ≤ 45m/s)
3.2.2 Connection between joist & exterior wall (Wind speed > 45m/s,span<=4000mm)
3.2.3 Connection between joist & exterior wall (Wind speed > 45m/s,span>4000mm)
Assembly of floor base board 75mm AAC floor base board M5.5X90 hexagonal self-tapping screw
M5.5X90 hexagonal self-tapping screw (@300mm)
M4.2X38 screw with wing
Sound insulation cushion
18mm fiber cement board (bathroom)
M4.2X38 screw with wing
Assembly of wall components for first floor 2*M5.5X50 hexagonal selftapping screw @600mm
2*M5.5X100 hexagonal screw @600mm
Anti-pull steel plate connector @1200mm (M4.8x16 screw) Connection between fiber cement board first floorâ&#x20AC;&#x2122;s wall structure
Connection between AAC board first floorâ&#x20AC;&#x2122;s wall structure Anti-pull steel plate connector @1200mm (M4.8x16 screw)
Node diagram for wall components Remarks: 1- If wind speed ≤45m/s, should add anti-pull plate for exterior corners and holes of doors & windows with over 900mm width. 2- If wind speed >45m/s, should follow point 1, and add 1 pcs anti-pull connector per 1.2m. 3- If wind speed is over than 70m/s, should put special anti-pull connector according to actual calculation data.
M4.8*16mm flat head screw
40mm steel plate
2.4.2 Anti-pull steel plate connector
CCA4-2 fastener
“x” bracing Shear wall components
Assembly of roof truss
Roof truss layout plan
Node diagram for roof truss 4.1.1 Connection between roof truss & exterior wall Wind speed ≤45m/s
4.1.2 Connection between roof truss & exterior wall Wind speed >45m/s
CCA2-1 wind resistance connector =1 pcs (10-M4.8*16 flat-head screws / 1 pcs)
CCA2-1 each pcs wind resistance connector on left & right (10-M4.8*16 flat-head screws / 1 pcs)
4.2.1 Connection between roof truss & wall
Roof truss ≤8000mm
Wind speed ≤45m/s
4.2.2 Connection between roof truss & wall Wind speed >45m/s
Roof truss >8000mm
CCA3-2 85 corner brace =2pcs (8-M4.8*16 flathead screws / 1 pcs)
CCA3-2 85 corner brace =4pcs (8-M4.8*16 flathead screws / 1 pcs)
Node diagram for roof truss CCA3-2 85 corner brace =2pcs (8-M4.8*16 flathead screws / 1 pcs)
4.4.1 Connection between main roof truss & roof truss Wind speed ≤45m/s
Wind speed >45m/s
CCA3-2 85 corner brace =4pcs (8-M4.8*16 flathead screws / 1 pcs)
90°roof truss
135°roof truss
Wind speed ≤45m/s
90°roof truss
4.4.2 Connection between main roof truss & roof truss
4.4.3 Connection between main roof truss & slope roof truss
4.4.2 Connection between roof truss & roof truss Wind speed >45m/s
135°roof truss
Node diagram for roof truss
CCA3-2 85 corner brace =1pcs (8-M4.8*16 flathead screws / 1 pcs)
CCA7-1 connector plate (8-M4.8*16 flathead screws / 1 pcs)
4.4.6 Connection between roof truss & roof cover
Node diagram for roof truss
CCA7-1 connector plate =4 pcs (6-M4.8*16 flathead screws / 1 pcs)
4.4.4 Connection between roof truss & roof truss
≤600mm
≤1500m m
CCA7-1 connector plate(minimum 4p) (8-M4.8*16 flathead screws / 1 pcs)
2*M5.5*19 Hexagonal screw 2 pcs close to the top, another 2 pcs on the bottom Spacing between top & bottom @≤600mm
4.4.5 Connection between roof truss & roof truss
Node diagram for roof truss
CCA3-2 85 corner brace =1pcs (8-M4.8*16 flathead screws / 1 pcs)
4.1.3 Connection between roof truss & interior wall
CCA6-1 rotary member (to left) / 1 pcs CCA6-2 rotary member (to right) / 1 pcs (M4.8*16 flat-head screws / 1 pcs)
4.3.1 Connection between slope roof truss & wall
Assembly of roof purlin
900mm
900mm M5.5X19 hexagonal screw
folding Assembly of eave board &gutter1.0mm edge for eave
50mm roof purlin
Downpipe
M4.8X16 screw @400mm 2M4.2X38 screw with wing @400mm Gutter
Side view of node
240*18mm fiber cement eaves board
Isometric view of node
Assembly of roof sheet PPGI roofing
M5.5X60 (AUS standard) PPGI roofing hexagonal screw Gutter (place hole for downpipe on side) 6mm heat insulating & reflective film
Assembly of wall breathe paper extend 100mm width breathe paper on holes of doors & windows
Using tape to connect the joints
Assembly of window
Assembly model
Node diagram of window frame
Assembly of exterior AAC wall
600mm
M5.5X90 hexagonal screw (@300mm)
M5.5X19 hexagonal screw (@600mm)
600mm
600mm
Assembly node diagram for keel of exterior wall
25mm top hat furring
Assembly node diagram for exterior AAC wall board
Assembly eave ceiling 25mm top hat furring
8mm THK cement ceiling board for eave
M5.5X19 hexagonal screw (@900mm) Assembly node diagram for eave ceiling furring
M4.2X38 screw with wing (@300mm)
Assembly node diagram for cement ceiling board for eave
Assembly of electric & plumbing Wire hole cap
Assembly node diagram for wiring
Assembly node diagram for plumbing
Assembly of interior wall
Fill glass wool inside of wall for thermal insulation
M4.2X25 countersunk screw (@300mm)
12mm plasterboard
Assembly of indoor ceiling Fill glass wool upon ceiling board for thermal insulation
M4.2X25 countersunk screw (@300mm)
Assembly of gypsum corner line for the top Gypsum corner line for ceiling
Assembly of bathroom floor Waterproof coating higher than floor @150mm
Non-slip floor tiles 2-layer waterproof coating 30mm slope making cement layer 18mm cement base board
Assembly of bathroom wall Wall tiles Wall tile cement Waterproof coating Fiberglass mesh Cement base board
Assembly of marble floor for stair Stone glue
18mm cement board
Marble step board
Assembly of stair handrail
Wall painting
Assembly node diagram for exterior wall, interior wall & ceiling
Joint crack cover
Brush paint
Painting
Assembly of indoor floor board
Skirting Cement board Waterproof & soundproof cushion Floor board
Fixed by spring leaf
Assembly of wooden door door side trim
door frame door leaf glue
door hinge Assembly model
Node diagram of door frame
Display of finished model
Display of indoor decoration
Photos of practical cases