Directional Valve With the advanced electrolysis technology to remove the burrs, the inner surface of the valve comes to be very smooth, and it is also a big support for ensuring the life cycles of valves when using the Japanese seals. 64 pcs valve bodies are machined simultaneously by completely computer controlled CNC machines at one time, coils are tested under 20,000 voltage equipment, and armatures are well provided by 3-D CNC machines imported from Japan, all these details make E¡MC to be the top in China.
Notes for Directional Valve
Notes for Energy Saving Low Power Coil energy saving low power coil
Directional Valve
Precaution for Installation and Use
Precaution for Installation and Use
☆Single control solenoid valve ○ It is best to install the coil partly or horizontally
Vibration Direction
√
Vibration Direction
Principle for energy saving : There are 2 stages for valve electrifying: actuation start moment and the stable process. For actuation start moment, it requires high voltage and large current to make sure the valve start normally(High power for the coil is required for this process),after the actuation start moment, it comes to the stable process, for this stage, it only requires low power to maintain stable. The energy saving low power consumption coil is developed according to this feature, it saves 80% energy during the stable stage through the internal energy saving chip, it reduce the coil heat, lower the temperature rising, prolong the life-span of the valve. It can be widely used for the occasions which requires long time coil electrify and low coil temperature rising. The below drawing show the voltage and the energy saving(take N2R251 valve DC24V coil as example).
24V
√
0
t(Time)
Vibration Direction
☆Double control solenoid valve ○It is best to install the coils horizontally
2
P(Power)
2
×
1.
Input voltage
1. Please check whether the product is damaged during transport, and check the technical parameters (such as operating voltage, working pressure, working temperature, etc.) to confirm whether they satisfy the requirements before installation. 2. Please pay attention to the air flow direction during installation, P(1) is air inlet、A(2)/B(4) is working port、R(3)/S(5)is exhaust port, working medium must be filtered through 40um filter(higher filter precision is available). 3. Before installation,the pipeline should be completely cleaned (Propos to use air guns or empty the pipeline directly before connection) to remove pipeline dust, debris and oil, so that to avoid the influence of valve action (such as stuck, no response or response slowly, etc.), avoid noise from damaged spool and the working life reduction. 4. When using fitting with thread to connect the valve and tubing, not allowed the thread dust and sealing tape fragments into the valve body;When using the sealing tape, the thread end should be set aside 1 or 2 thread pitch non-winding sealing tape;When using liquid glue, should avoid excessive liquid glue going into the valve body 5. Try to avoid using the valve in vibration environment ; if slight vibration, please make the vibration direction and spool action direction at right angle to avoid the influence of the spool.
Standard coil
3W
×
Vibration Direction
√
Vibration Direction
Saving 80% energy
6. In order to prevent condensate water, oil ,etc flowing into the coil, it is better to make the coil upwards or adopt lateral installation . Pay attention to condensed water
Energy efficient coil 0.6W 0
Vibration Direction
√ Vibration Direction
× Vibration Direction
√
Vibration Direction
Vibration Direction
Stabilization time
t(Time)
2 . Requirement for input power: range of the fluctuation of voltage-15%~+10%;the electric source output power shall be above 2-3 times than the power in actuation start moment 3. Actuation start moment of energy saving coil:The starting time is different for different specification and voltage of coil. The lower voltage, the longer time for starting time. Here is the standard voltage testing value of our current products:
Pay attention to condensed water
×
The suction start time 80ms
√
7. Try to install the valve as close as possible to the cylinder, to avoid the influence of active time because of the long pipeline and air consumption increase. 8. When manifold assembly used, please note back pressure phenomenon that caused by incompletely exhaust. Please note wrong action caused by the interaction between the valves. Especially when using the 3 positions ,center exhaust valve and single acting cylinder, recommend to inlet and exhaust separately. 9. When using 3 positions center close or 3 positions center pressure valves ,it is difficult to guarantee the cylinder stop exactly at any intermediate position ,because air compressibility and reasonable leakage of valve and cylinder.If require to stay at the stop position for a long time, please take other methods (such as using induction check valve together). 10. When using 3 positions center close valve, please consider the residual pressure release between the valve and cylinder , please set the residual pressure release function in the air circuit . 11. When using internal pilot type, please consider minimum operating pressure ,not allowed to throttle at inlet ,either exhaust emptied directly , to avoid wrong action caused by big air pressure reduction. If blowing environment, please use external pilot type. 12. Pilot valve, piston cavity, breathing hole and pilot valve exhaust port shall not block or restricted, and the filter need to do regular cleaning or replacement if necessary 13. It is recommended to install muffler to the exhaust port to avoid inhaling of impurity into the valve body. 14. such as valves used in vacuum condition, should use direct acting valve or exterior pilot type valve, and measures should be taken to prevent dust from sucking in the suction cup 15. Double electric air control valve has memory function (except three position valve), power up time should be more than 0.1s in time to ensure the valve reversing in place. 16. although the coil calibration is 100%ED, long time continuous electricity will cause overheating, accelerated insulation aging, reduce the performance of the solenoid valve、lifetime and energy, so in the condition of continuous power on,we should consider to use double electronically controlled solenoid valve with memory function or adopt energy saving and low power coil . in order to extended coil life , and save energy. 17. Solenoid valve installed in the control cabinet,We should pay attention to the ventilation of the control cabinet, heat radiation, to ensure that the temperature in the cabinet within the safety use range. 18. Solenoid valve coil should not be connected to the wrong voltage (such as the DC24V coil connect to the AC220V voltage), Otherwise, the coil will be burned, and the working voltage should be in the required voltage range, to make sure the valve works well. 19. Since DC solenoid valve has polarity indicator light, please pay attention to the positive and negative poles when wiring, "1" connect the positive pole, and "2" connect the negative pole, If the positive and negative poles are reversed, The light will not turn on, but the valve can still be actuated. 20. During use energy saving and low power consumption coil solenoid valve, please refer to energy-saving, low-power solenoid valve instructions. 21. The valve on this catalogue shall not be used as an emergency shut-off valve. If the emergency shut-off function is required, other ways of ensuring safety shall be used to control it.
Energy saving coil/Modules specification
Starting time
N1R(Internal 110 series) N2R/N3R/N4R(Internal 210series) ELP(Internal solenoid valve series) NF(External small power energy saving module) NF(External big power energy saving module)
50±1 0ms 80±2 0ms 250±1 00ms 50±1 0ms 100±2 0ms
Note:The rise time shall be less than 5 ms when the voltage start from 0 to rated voltage in the proceed of solenoid valve energization.
4. When the coil is on stable keeping period, it can’t be used in vibration and dust application because it is on energy saving and low power status. Air inlet of solenoid valve shall be fully filtered to avoid the impurity to reach the end face of pilo. 5. Working temperature: -20~80℃,the internal energy saving chip can no work in high temperature medium, like high temperature water/oil/gas and so on. If the working medium is high temperature, external energy saving conversion module is recommended, the important issue is to make sure environment temperature is not higher than 80℃。 6. Normal electric conversion components: mechanical switch; mechanical relay; solid-state relay; MOS tube; Thyistor tube. Please note below issues when using energy saving coil: (1) Current for convert components should be 2-3 times higher than the Max.current when coils start and actuation. (2) Max.leak current for convert components should be ≤40uA. The leak current of Normal convert components with protection is relatively big, like solid-state relay( we suggest choose it carefully). In addition, RC circuit protection can not be used, otherwise, directional valve can not revert normally.
V Series Standard/ N Series Low Power Solenoid Valve (2/2 way) 2.01
V Series Standard/ N Series Low Power Solenoid Valve (2/2 way)
V221 Series
V221 Series
2.02
V221
(G,PT,NPT)
Low Power Solenoid Valve
2
ID Code
Positions
Ways
M: Standard armature +Low power coil
2 positions
2 : 2 ways
Series No.
N
Controls
— Port Size
Connection Mode
Voltage
1: Single control 06:1 / 8" E1:AC110V 08:1 / 4" E2:AC220V E4:DC24V
Cover Color
2
— Thread Type
Blank: DIN connector Blank: G F: Flying leads P: PT T: NPT Blank: Brown translucent J: Colorless and translucent
Engineered plastics (FPM)
Standard Solenoid Valve Series No.
ID Code
V
Blank: Standard type A: Amisco coil
Positions
Controls
—
2 positions 1 : Single control
Port Size
Ways
06:1 / 8" 08:1 / 4"
2 : 2 ways
Voltage
E1:AC110V E2:AC220V E3:AC380V E4:DC24V E5:DC12V
Connection Mode
Cover Color —
Thread Type
Blank: G Blank: DIN connector P: PT F: Flying leads T: NPT Blank: Brown translucent E6:AC36V J: Colorless and translucent E7:AC24V E8:DC110V E9:DC48V E10:DC36V
Order Example: V series directional valve, 2/2 way, single control, 1/8 port size, Amisco coil, AC110V, DIN connector, G thread, ERP code is: V221-06AE1
NM221 - 06
NM221 - 08
V221 - 06
V221 - 08
V221-06/08 NM221-06/08 0~0.8 1.2 -5~60(No freezing)
(MPa) (MPa)
AC : 1VA
DC : 0 . 9W
class 9.5
9.5
(If with the steel nut, the height is 60.7mm)
V Series Standard/ N Series Low Power Solenoid Valve (3/2 way) 2.03
V Series Standard/ N Series Low Power Solenoid Valve (3/2 way)
V321 Series
V321 Series
V321
2.04
Internal Structure (G,PT,NPT) * With manual installation, easy to debugging
Low Power Solenoid Valve
N
Valve Body ID code
ID Code
Positions
Ways
Voltage
Controls — Port Size
Cover Color — Thread Type — Valves
Connection Mode
3 : 3 ways Blank: DIN connector M5:M5 M: Standard armature Blank: G F: Flying leads 06:1 / 8" +Low power coil P: PT T: NPT Blank: Standard valve body 2:2 positions 1 : Single control E1:AC110V Blank: Brown translucent P: Europeans valve body E2:AC220V J: Colorless and translucent (Only for 3/2 way) E4:DC24V
Note:Only V series solenoid valve has port size M5 and only the 1 valve type ( no mounting accessory)
2
Blank:1Valve (No mounting accessory) 2F:2 Valves 3F:3 Valves …… 20F:20 Valves
Engineered plastics
Standard Solenoid Valve Series No.
V VP
Ways
Positions
Controls
—
3 : 3 ways 2:2 positions 1: Single control
Port Size
ID Code
Voltage
Blank: Standard type V321 A: Amisco coil M5 : M5 06:1 / 8" VP321 E1:AC110V 06:1 / 8" E2:AC220V E3:AC380V E4:DC24V E5:DC12V
Connection Mode
Cover Color — Thread Type — Valves
Blank: G Blank: DIN connector P: PT F: Flying leads T: NPT Blank: Brown translucent E6:AC36V J: Colorless and translucent E7:AC24V E8:DC110V E9:DC48V E10:DC36V
Blank:1Valve (No mounting accessory) 2F:2 Valves 3F:3 Valves …… 20F:20 Valves
V321
Vp321
Note:Only V series solenoid valve has port size M5 and only the 1 valve type ( no mounting accessory)
Order Example: N series solenoid valve, standard pilot+Low power coil, 3/2 way, single control,1/8" port size, standard coil,DC24V, DIN connector, G thread, ERP code is: NM231 - 06E4
NPM231 - 06
V321 - M5
V321 - 06
2- Ø 3.3(Through hole)
2-M 4 Dep 7
VP321 - 06
40
18
2
4 M
25
15
(60)
(65.2)
11
AC:7VA DC:6.5V
class
M 5:12.5 06:10.5 22
141
138
141
138
3-1/8"
5
15 30
29.1 20
AC:5VA DC:4.8V
2- Ø 3.3
9 4
DC : 0 . 9W
M 5:3-M 5X0.8 06:3-1/8"
4- Ø 5.3 (Dep8.5/2 sides)
18
AC : 1VA
(60.7)
0~0.8 1.2 -5~60(No freezing)
3.5
(MPa) (MPa)
9
NM231 - 06
3
NM231 - M5
16.3 8
2
Series No.
13.6 Dep 0.7 12.9 25.3
19.7 34
V / ( ) 2.05
V / ( )
V321
V321
Combination of Schematic Diagram
V 321-05
2.06
Combination of Schematic Diagram
V 321-04
V 321-03
2
2 V 321-06 VP321-P20 Mounting accessory
Mounting accessory order details: V321-06â–¡ The finished valves
V321-03
V321-04
V321-05
V321-06â–¡-â–¡-2F
2
2
2
2
1
V321-06â–¡-â–¡-3F
3
4
2
2
2
…… V321-06□-□-nF
…… n
…… 2(n-1)
…… 2
…… 2
…… n-1
Valve Quantity
V321-06
Note : n indicates valve quantity ,and 2≤n≤20
18
3
3.8
(Through hole)
M4 Dep 7
25
15 (65.2)
(60)
(60.7)
(67.8)
11
15 30
9
9
5
13.6 Dep 0.7
4
10.5 66
3.5
22
20
29.1
18
16.3 8
1/8"
1/8"
12.4
23.8
19.7 72.9
34
RVT Series Standard/ N Series Low Power Solenoid Valve (3/2 way) 2.07
RVT Series Standard/ N Series Low Power Solenoid Valve (3/2 way)
RVT Series
RVT Series
NTR231 - 06
2.08
RVT321 - 06
40
(MPa) (MPa)
0~0.8 1.2 -20~70 DC24V:0.7W AC220V:0.9VA AC110V:1.4VA
Series No.
Valve Body ID code
ID Code
Ways
Positions
Controls
Port Size
Voltage
Connection Mode
Cover Color
Thread Type
DC:3W
2
Valves
0.05s below N
2:2 positions
T :Integrated body
3 : 3 ways
R: Standard armature +Low power coil
06:1/8" 1 : Single control
E1:AC 1 10V E2:AC 220V E4:D C24V
Blank: Brown translucent Blank: G J: Colorless and translucent P: PT B: Black T : N PT (Only black color availale for water proof connector)
Each valve increases 141 weight
2F:2 Valves 3F:3 Valves …… 2 0F:20 Valves
Each valve increases 138 weight
Blank :DIN connector K: Waterproof DIN connector M: M8 connector
Standard Solenoid Valve Series No. Ways
Positions
Controls
Port Size
ID Code
Voltage
Connection Mode
Cover Color
Thread Type
Valves 4-M 4 Depth 6
1 : Single control
2:2 positions
06:1/8" Blank: Standard type A: Amisco coil E1:AC 1 10V E2:AC 220V E3:AC 380V E4:D C 24V E5:D C12V
E6:AC 36V E7:AC 24V E8:D C1 10V E9:D C48V E10:DC 36V
Blank :DIN connector F: Flying leads K: Waterproof DIN connector M: M8 connector
Blank: G P: PT T : N PT
2F:2 Valves 3F:3 Valves …… 2 0F:20 Valves
10
Blank: Brown translucent J: Colorless and translucent B: Black (Only black color availale for water proof connector)
12
12
10
Order Example: RVT series solenoid valve, 3/2 way, A m i s c o coil, single control,1/8" port size,,AC110V,DIN connector, G thread, ERP code is: RVT321 - 06AE1-5F P
P
12.5
24.5
16.5
N-G 1/8
4-
*Direct Acting, Normal Close, Sensitive Response;
4.5
15.5
3 : 3 ways
63.2
R VT
4
2
AC:4VA
class
Low Power Solenoid Valve
4
4 16
23
2-G 1/8
11 30
16
60.2
(n-1)X23+32
*Integrated body , Install easily; *Multiple valtage and Energy-Saving are optional;
Note : n indicates valve quantity ,and 2≤n≤20
*Multiple connection mode are optional. Sign/Valves L M P Sign/Valves L M P
2Valves 55 47 11
3Valves 78 70 34
12Valves 13Valves 285 308 277 300 241 264
4Valves 101 93 57
5Valves 124 116 80
14Valves 331 323 287
15Valves 354 346 310
6Valves 147 139 103
7Valves 170 162 126
8Valves 193 185 149
9Valves 216 208 172
10Valves 239 231 195
16Valves 17Valves 377 400 369 392 333 356
18Valves 423 415 379
19Valves 446 438 402
20Valves 469 461 425
11Valves 262 254 218
RV Series Standard/ Low Power Solenoid Valve (3/2 way) 2.09
RV Series Standard/ Low Power Solenoid Valve (3/2 way)
NRV Series
RV Series
2.10
(Only 1,2,3 series single control)
Standard Solenoid Valve (Only 4 series single control)
Series No. Ways Positions 2:2 positions RV 3:3 ways
How to Order?
Controls
Original Status — Port Size Reset Type
Voltage
Acting Type
Connection Cover Color Mode
N1R231-M5 N1R232-M5
N1R231-06 N1R232-06
N2R251-06 N2R252-06
N2R251-08 N2R252-08
N3R251-08 N3R252-08
N3R251-10 N3R252-10
M5
G1/8
G1/8
G1/4
G1/4
G3/8
5.5(CV=0.31)
12(CV=0.67)
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
N4R251-10 N4R252-10
N4R251-15 N4R252-15
G3/8
Model No.
Blank: Internal pilot WB: External pilot
E4:DC24V E9:DC48V E5:DC12V E10:DC36V
RV3211-M5 RV3212-M5
RV3211-06 RV3212-06
RV3221-06 RV3222-06
RV3221-08 RV3222-08
RV3231-08 RV3232-08
RV3231-10 RV3232-10
RV3241-10 RV3242-10
RV3241-15 RV3242-15
M5
G1/8
G1/8
G1/4
G1/4
G3/8
G3/8
G1/2
Port size
Sectional area(mm) 2 way:5.5(CV=0.31) 2 way:12(CV=0.67) 2 way:14(CV=0.78) 2 way:16(CV=0.89) 2 way:25(CV=1.40) 2 way:30(CV=1.68) 2 way:50(CV=2.79) :50(CV=2.79) Working medium
50(CV=2.79)
Clean air(After 40 μm filteration )
Acting type
Internal pilot type/External pilot type
Reset type
Spring reset/Gas reset
Lubrication
Not required
Working pressure(MPa)
0.15~0.8
Guaranteed pressur(MPa)
1.2
Working temperature(℃)
-20~70(No freezing)
Voltage range
G1/2
Insulation class
50(CV=2.79)
Protective class
Clean air(After 40 μm filteration )
Acting type
-15%~10% DC:2.8W ; AC:3.0VA
DC:3.0W ; AC:4.0VA IP65(DIN40050) 5 Cycles/s
Activate time(S)
<0.05
Internal pilot type/External pilot type
Reset type
Weight(g)
Spring reset/Gas reset
Lubrication
R V 3211: 102 RV3212: 169
R V 3221: 107 RV3222: 303
R V 3231: 260 RV3232: 270
R V 3241: 528 RV3242: 638
Not required
Working pressure(MPa)
0.15~0.8 -5~60(No freezing)
Voltage range
-15%~10% DC24V:0.7W AC220V:0.9VA AC110V:1.4VA
DC24V:0.6W
Insulation class Protective class
IP65(DIN40050)
Max. acting frequency
5 Cycles/s
Activate time(S)
<0.05 N1R231: 102 N1R232: 169
Note: Normal open is same as normal close.
N2R231: 107 N2R232: 303
N3R231: 260 N3R232: 370
N4R231: 443 N4R232: 569
N1R231 - M5、RV3211 - M5
Flow Rate (L/min)
Working Pressure (MPa)
1.2
Working temperature(℃)
Working Pressure (MPa)
Flow Chart
Guaranteed pressur(MPa)
Weight(g)
Thread Valve Color — Type
Blank: DIN connector Blank: Standard type M5:M5 1:1Series 1: Single control F: Flying leads Blank:G 06:1/8" A: Amisco coil K: Waterproof DIN connector 2:2Series 2: Double control 08:1/4" P:PT (Only for 2,3,4 series) 3:3Series 10:3/8" T:NPT 15:1/2" 4:4Series E1:AC110V E6:AC36V Blank: Brown translucent Blank: Spring Blank: Normal close E2:AC220V E7:AC24V J: Colorless and translucent (Only 4 series single control) H: Normal open E3:AC380V E8:DC110V B: Black (Only Waterproof DIN connector)
Max. acting frequency Working medium
Power consumption
Cover Color
2
Power consumption
Sectional area(mm)
Connection Mode
Thread Type
Order Example: RV series low power solenoid valve, 2 series valve body size, 3/2 ways, double control, 1/8" port size, AC220V, DIN connector, G thread, ERP code is :N2R232-06E2
Port size
Voltage
—
Blank: Brown translucent Blank:G E1:AC110V M5:M5 2:positions 1: Single control 1:1Series J: Colorless and translucent P:PT 06:1/8" E2:AC220V 2: Double control B: Black 2:2Series T:NPT 08:1/4" (Only black color availale E4:DC24V 3:3Series 3:3 ways Blank: Normal close 10:3/8" for water proof connector) (for 1series, 4:4Series H: Normal open 15:1/2" Blank: Internal pilot only DC24V available ) WB: External pilot Blank: DIN connector Blank: Spring R: Standard armature K: Waterproof DIN connector (4 series single control only) + Lower power coil (Only 2,3,4 series) Q:Air (1,2,3 series single control)
Model No.
Original Status — Port Size Reset Type ID Code
Q: Air (1,2,3 series single control)
Series Valve body ID code Positions Ways size N
Controls
Order Example: RV series solenoid valve, 2 series valve body size, 3/2 ways, single control, 1/8” port size, air return, standard coil, AC220V, DIN connector, G thread, ERP code is :RV3221-06QE2
Low Power Solenoid Valve
2
Valve Body ID Code
N1R231 - 06、RV3211 - 06
Flow Rate (L/min)
RV Series Standard/ Low Power Solenoid Valve (3/2 way)
RV Series Standard/ Low Power Solenoid Valve (3/2 way)
RV Series
2.11
RV Series
2.12
Flow Chart Single Solenoid Valve N3R231 - 08、RV3231 - 08
M5(Optional)
Flow Rate (L/min)
(mm)
Flow Rate (L/min)
Flow Rate (L/min)
Internal Structure Single Solenoid Valve(Normal close)
Single Solenoid Valve(Normal open)
1
9 10
O-ring
2 3 4 5 6 2
R 3
4
5
6
7
8
P
9 10 11
R 12 13
Double solenoid valve(Normal close)
P
7 8
13
Rear cover Filter Piston
14
Manual button
11 12
14
A
R
P
Part Name
Connector Nut Coil Pilot units Plate Piston Pilot seat Valve body Spool
1
A
Model/Sign
A
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
W
W1*
RV3211-M5 RV3211-06 RV3221-06 RV3221-08 RV3231-08 RV3231-10 RV3241-10 RV3241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
19 19 30 30 35 35 40.5 40.5
13 13 17 17 20 20 27 27
16.5 16.5 16 16 19.1 19.1 24.8 24.8
18 18 22 22 27 27 34 34
0 1.5 0 1.5 0 2 0 2
26 27 31 32 36.6 36.6 45 45
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.2 4.2 4.3 4.3 5.2 5.2
15.5 15.5 18.5 18.5 21.6 21.6 21 21
21 21 25 25 30 30 48 48
6 6 9.3 9.3 9.5 9.5 11.5 11.5
27 27 35 35 40 40 50 50
55.2 55.2 66.7 66.7 69.2 69.2 74.2 74.2
33.9 33.9 40.2 40.2 40.2 40.2 40.2 40.2
18.9 18 20 19.8 24.6 24.6 29.3 29.3
14.2 16 22 22.5 24 24 31.5 31.5
92.1 92.1 112.7 112.7 124.3 124.3 144.7 144.7
132.2 132.2 163.4 163.4 175.4 175.4 199.4 199.4
Note: The dimension of NR series and RV series are same, The dimension of normal open type and normal close type are same, W1*is the dimension of double control solenoid valve.
No.
A
2
N4R231 - 10、RV3241 - 10 N4R231 - 15、RV3241 - 15
Working Pressure (MPa)
Working Pressure (MPa)
Working Pressure (MPa)
N3R231 - 10、RV3231 - 10
Flow Rate (L/min)
Manual button
Manual button
2 N2R231 - 08、RV3221 - 08
External guide air holes
Flying Leads Type
External guide air holes
M5(Optional)
Flow Rate (L/min)
Double Solenoid Valve
DIN Type
Working Pressure (MPa)
Working Pressure (MPa)
N2R231 - 06、RV3221 - 06
Material
Engineered plastics POM Cu+ Thermosetting resin Pure iron + copper + stainless steel Carton steel POM
Engineered plastics Aluminum alloy Aluminum alloy NBR
Engineered plastics Synthetic material
Engineered plastics Engineered plastics
V Series Standard/ N Series Low Power Solenoid Valve (3/2 way) V Series
V Series
V3212
N1M231 - 06、V3211 - 06
N2M231 - 08、V3221 - 08
N3M231 - 10、V3231 - 10
Working Pressure (MPa)
Working Pressure (MPa)
V3211H
400
Flow Rate (L/min)
2
2.14
Flow Chart
V3211
Working Pressure (MPa)
2.13
V Series Standard/ N Series Low Power Solenoid Valve (3/2 way)
800
1200
Flow Rate (L/min)
1600
2000
2400
Flow Rate (L/min)
Standard Solenoid Valve Series No. Ways
Positions Valve Body Controls Size 2:2 positions 1:1Series 2:2Series 3:3Series 4:4Series
V
3:3 ways
Original — Port Size ID Code Status
Blank: NC H:NO 1 : Single control 2:Double control
Order Example:
Voltage
Blank: Standard type A: Amisco coil M5:M5 06:1 / 8" E1:AC110V E2:AC220V E3:AC380V E4:DC24V E5:DC12V
2 Connection Mode
Cover Color Valve Color — Thread Type
Blank: DIN connector F: Flying leads E6:AC36V E7:AC24V E8:DC110V E9:DC48V E10:DC36V
Blank:Black W:White
Blank: G P: PT T: NPT
Blank: Brown translucent J: Colorless and translucent
Internal Structure Single Solenoid Valve
V series solenoid valve, 1 series valve body size, standard pilot+Low power coil, 3/2 way, single control, NC, 1/8" port size, standard coil,DC24V, DIN connector, G thread, ERP code is: V3211-06E4
No.
Model No. Port size
V3211-06 V3212-06
M5
G1/8
V3221-06 V3222-06
V3221-08 V3222-08
V3231-08 V3232-08
V3231-10 V3232-10
V3241-10 V3242-10
V3241-15 V3242-15
G1/8
G1/4
G1/4
G3/8
G3/8
G1/2
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
Working medium
9
O-ring
11
Stainless steel Spring Zinc alloy Rear cover Screw Carbon steel Manual override Engineered plastics
4 5 6
Clean air(After 40μm filteration)
7
Acting type
Pilot type
8
Lubrication
Not required
Working pressure(MPa)
0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing)
13
-15%~10%
14
Voltage range Power consumption
DC:2.8W ; AC:3.0VA
12
DC:4.8W ; AC:5VA
Insulation class
Class F
Protective class
IP65(DIN40050)
Max. acting frequency
5 Cycles/s <0.05
Activate time(S) Weight(g)
V3211: 102 V3212: 169
Note: The technical data of NO type and NC type are same.
V3221: 107 V3222: 303
V3231: 260 V3232: 370
V3241: 443 V3242: 569
Material
10
2 3
Double Solenoid Valve 2 Sectional area(mm ) 5.5(CV=0.31) 12(CV=0.67)
Part Name
Connector Nut Coil Pilot units Plate Piston Screw Valve body Spool
1 V3211-M5 V3212-M5
Engineered plastics POM+Carbon steel
Carbon steel POM Carbon steel Aluminum alloy Aluminum alloy HNBR
V Series Standard/ N Series Low Power Solenoid Valve (3/2 way)
RV Series Air Control Valve (3/2 way)
V Series
2.15
RVA Series
2.16
(1,2,3 series single air control valve)
Single Solenoid Valve
Double Solenoid Valve Flying Leads Type
3-A
M
C G
N
2- K
D F
O
Series No.
L
E
R
L
E
2- K
G D F
Valve Body ID Code
R
H
S
M
C H
2
3-A
S
Manual button
W1
2- J
(4 series single air control valve only)
2- J
W
P Q
W
DIN Type
N
RVA
O
Ways
Positions
3:3 ways 2:2 positions
(mm) Model\Sign
A
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
W
W1*
V3211-M5 V3211-06 V3221-06 V3221-08 V3231-08 V3231-10 V3241-10 V3241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
19 19 30 30 35 35 40.5 40.5
13 13 17 17 20 20 27 27
13.2 13.2 12.7 12.7 15 15 24.8 24.8
18 18 22 22 27 27 34 34
0 1.5 0 1.5 0 2 0 2
22.7 23.7 27.7 28.7 32.5 32.5 45 45
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.3 4.3 4.3 4.3 5.2 5.2
12.2 12.2 15.2 15.2 17.5 17.5 21 21
21 21 25 25 30 30 48 48
7.5 7.5 8.2 8.2 10.5 10.5 13.5 13.5
27 27 35 35 40 40 50 50
54.8 54.8 67.5 67.5 70 70 75 75
32.8 32.8 40.5 40.5 40.5 40.5 40.5 40.5
15.7 14.7 18.5 16.5 21.5 20.5 29.3 29.3
14 16 18.5 22.5 22 24 31.5 31.5
87.5 87.5 109.7 109.7 120.5 120.5 144 144
129.6 129.6 164 164 176 176 198 198
2 Controls
Initial Status
— Port Size
1:1Series 1: Single control 2:2Series 2: Double control 3:3Series Blank: Normal close(N.C) 4:4Series H:Normal open(N.O)
M5:M5 06:1/8" 08:1/4" 10:3/8" 15:1/2"
Reset Type —Thread Type Blank:G P:PT T:NPT
Blank: Spring return (Apply to 4 series single control valve) Q: Air return (Apply to 1,2,3 series single control valve)
Order Example: RVA series air control valve, 3/2 way, 2 series valve body size, single control, NC type, 1/4" port size, air return, PT thread ERP code is: RVA3221-08Q-P
Note: The dimensions of NO type and NC type are same, the dimensions of N series and V series are same.
Model No. Port size Sectional area(mm)
RVA3211-M5 RVA3212-M5
RVA3211-06 RVA3212-06
RVA3221-06 RVA3222-06
RVA3221-08 RVA3222-08
RVA3231-08 RVA3232-08
M5
G1/8
G1/8
G1/4
G1/4
G3/8
5.5(CV=0.31)
12(CV=0.67)
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
Working medium
RVA3241-10 RVA3242-10
G3/8 50(CV=2.79)
RVA3241-15 RVA3242-15
G1/2 50(CV=2.79)
Clean air(After 40 μm filteration )
Acting type
External type
Reset type
Spring reset / Gas reset
Lubrication
Not required
Working pressure(MPa)
0.15~0.8
Guaranteed Pressure(MPa)
1.2
Working temperature(℃)
-20~70(No freezing) 5 Cycles/s
Max. acting frequency Weight(g)
RVA3231-10 RVA3232-10
RVA3211:60 RVA3212:75
RVA3221:116 RVA3222:143
RVA3231:187 RVA3232:220
RVA3241:378 RVA3242:430
RV Series Air Control Valve (3/2 way) 2.17
RV Series Air Control Valve (3/2 way)
RVA Series
RVA Series
Flow Chart
Internal Structure Single Air Control(N.C)
Double Air Control(N.O) RVA3231 - 08
5
4 3
No.
2 1
5/3 Ways Solenoid Valve
2
Part Name
Material
1
Air Control Cover Aluminum Alloy
2
Piston
POM
3
Screw
Carbon Steel
4
Valve Body
Aluminum Alloy
5
Spool
Aluminum Alloy
6
O-ring
7
Piston
8
Rear Cover
Working Pressure(MPa)
6
Working Pressure(MPa)
7
RVA3241 - 10 RVA3241 - 15
RVA3231 - 10
Working Pressure(MPa)
8
2.18
NBR Flow Rate(L/min)
POM
Flow Rate(L/min)
Flow Rate(L/min)
2
Zinc Alloy
Main Dimension Single Air Control
Double Air Control
Flow Chart RVA3211 - 06
Working Pressure(MPa)
Working Pressure(MPa)
RVA3211 - M5
Flow Rate(L/min)
Flow Rate(L/min)
RVA3221 - 08
Working Pressure(MPa)
Working Pressure(MPa)
RVA3221 - 06
Flow Rate(L/min)
Model/Sign
A
C
D
E
F
G
H
J
K
L
M
N
O
P
R
S
W
W1*
RVA3211-M5 RVA3211-06 RVA3221-06 RVA3221-08 RVA3231-08 RVA3231-10 RVA3241-10 RVA3241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
19 19 30 30 35 35 40.5 40.5
13 13 17 17 20 20 27 27
16.5 16.5 16 16 19.1 19.1 24.8 24.8
18 18 22 22 27 27 34 34
0 1.5 0 1.5 0 2 0 2
26 27 31 32 36.6 36.6 45 45
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.2 4.2 4.3 4.3 5.2 5.2
15.5 15.5 18.5 18.5 21.6 21.6 21 21
21 21 25 25 30 30 48 48
6 6 9.3 9.3 9.5 9.5 11.5 11.5
27 27 35 35 40 40 50 50
G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8
18.9 18 20 19.8 24.6 24.6 29.3 29.3
14.2 16 22 22.5 24 24 31.5 31.5
61 61 73 73 84.6 84.6 103 103
70 70 84 84 96 96 116 116
Note: The dimesnion of N.O type and N.C type are same, W1* is the dimesnion of double control type.
Flow Rate(L/min)
V Series Air Control Valve (3/2 way)
V Series Air Control Valve (3/2 way)
VA Series
2.19
RVA Series
2.20
VA3211
Internal Structure VA3211H
Single Air Control
VA3212
No.
5
O-ring
7
Spring Rear cover
3 4
Series No. Ways
2
Positions
2:2 positions
VA 3 : 3 ways
Valve Body Size
Controls
1:1Series 2:2Series 3:3Series 4:4Series
1 : Single control 2:Double control
Original Status —
Valve Type
Port size
Blank: Standard type M: NAMUR type
M5 : M5 06 : 1 / 8" 08 : 1 / 4" 10 : 3 / 8" 15 : 1 / 2"
Blank: NC H: NO
Order Example:
— Thread Type
Valve Color
Blank: G P: PT T: NPT
Blank:Black W:White
Material
6
2
Double Air Control
Part Name
Air control cover Aluminum alloy POM Piston Carbon steel Screw Aluminum alloy Valve body Aluminum alloy Spool
1
8
HNBR Stainless steel Zinc alloy
V series air control valve, 1 series valve body size, NC type, 3/2 way,1/8" port size, standard valve body, white color, PT thread, ERP code is: VA3211-06W-P
Single Air Control Model No. Port size
VA3211-M5 VA3212-M5
VA3211-06 VA3212-06
M5
G1/8
VA3221-06 VA3222-06
VA3221-08 VA3222-08
VA3231-08 VA3232-08
VA3231-10 VA3232-10
VA3241-10 VA3242-10
Double Air Control
VA3241-15 VA3242-15
G1/8
G1/4
G1/4
G3/8
G3/8
G1/2
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
P 2 Sectional area(mm ) 5.5(CV=0.31) 12(CV=0.67)
Working medium
Clean air(After 40μm filteration) External type
Lubrication
Not required
VA3211: 60 VA3212: 75
V A 3221: 116 VA3222: 143
S
W M
5 Cycles/s
L
Max. acting frequency
C
-5~60(No freezing) E
1.2
Working temperature(℃)
2- K
V A 3231: 187 VA3232: 220
V A 3241: 378 VA3242: 430 G
Note: The technical data of NO type and NC type are same.
R
H
Guaranteed pressure(MPa)
Weight(g)
3-A
2- J
0.15~0.8
Working pressure(MPa)
W1
Acting type
N O
D F
VA3221 - 08
400
Flow Rate (L/min)
Flow Rate (L/min)
(mm)
VA3231 - 10
Working Pressure (MPa)
VA3211 - 06
Working Pressure (MPa)
Working Pressure (MPa)
Flow Chart
800
1200
1600
2000
2400
Flow Rate (L/min)
Model\Sign
A
C
D
E
F
G
H
J
K
L
M
N
O
P
R
S
W
W1*
VA3211-M5 VA3211-06 VA3221-06 VA3221-08 VA3231-08 VA3231-10 VA3241-10 VA3241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
19 19 30 30 35 35 40.5 40.5
13 13 17 17 20 20 27 27
13.2 13.2 12.7 12.7 15 15 24.8 24.8
18 18 22 22 27 27 34 34
0 1.5 0 1.5 0 2 0 2
22.7 23.7 27.7 28.7 32.5 32.5 45 45
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.3 4.3 4.3 4.3 5.2 5.2
12.2 12.2 15.2 15.2 17.5 17.5 21 21
21 21 25 25 30 30 48 48
7.5 7.5 8.2 8.2 10.5 10.5 13.5 13.5
27 27 35 35 40 40 50 50
G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8
15.7 14.7 18.5 16.5 21.5 20.5 29.3 29.3
14 16 18.5 22.5 22 24 31.5 31.5
57.7 57.7 69.7 69.7 80.5 80.5 103 103
70 70 84 84 96 96 116 116
Note: The dimensions of NO type and NC type are same.
2
V Series Manifold (3/2 way) 2.21
RV Series Standard/ Low Power Solenoid Valve ( 5/2,5/3 way) NRV Series
V Series Manifold
RV5211
RV5211Q
32
V V series
N
F
1:1 series valve body 1:1 station Manifold 3/2 way 2:2 series valve body 2:2 stations 3:3 series valve body 3:3 stations 4:4 series valve body 16:16 stations
Thread Type
VBP
Blank:G P:PT T:NPT
Order Example:
2
3/2 way
1:1 series valve body 2:2 series valve body 3:3 series valve body 4:4 series valve body
Manifold Model
stations,
2 series 2 series
NO.
Manifold Model
Valve Model
1
V321-NF(N≤16) V322-NF(N≤16) V323-NF(N≤12) V324-NF(N≤7)
V3211(H)/V3212 V3221(H)/V3222 V3231(H)/V3232 V3241(H)/V3242
2
Note : Blind plate assembly includes: Blinds, gaskets and mounting screws
3 4
Series No. Valve body size
ID Code Positions
Ways Controls
Port Size Reset Voltage Connection Cover Color Acting Type — Thread Type Mode Form
Original — Status
5:5 ways N
Blank: DIN connector C: Center close Blank: Internal pilot K:Waterproof DIN connector Blank : Spring (Only P: Center pressure WB: External pilot 2、3、4 series is opitional) Q:Air E: Center exhaust (Only single control) (Only for 5/3 way) Blank: Brown translucent Blank: G M5 : M5 J: Colorless and translucent P: PT E1:AC110V 1 : Single control 06:1/8" T: NPT 2:Double control E2:AC220V 08:1/4" E4 : DC24V 10:3/8"
2:2 positions 1:1Series 3:3 positions 2:2Series 3:3Series 4:4Series R: Standard armature +Low power coil
RV series solenoid valve, 2 series valve body size, standard pilot+Low power coil, 5/2 way, single control, 1/4" port size, standard coil,DC24V, DIN connector, G thread, ERP code is: N2R251 - 08E4
E MC
Port size
E
Sectional area(mm2)
N1R251-M5 N1R252-M5 N1R352-M5
N1R251-06 N1R252-06 N1R352-06
N2R251-06 N2R252-06 N2R352-06
N2R251-08 N2R252-08 N2R352-08
E
Model\Sign V321-□F V322-□F V323-□F V324-□F
Model\Sign V321-□F V322-□F V323-□F V324-□F
1F
2F
3F
4F
5F
6F
7F
8F
9F
10F
38 46 54 63
57 69 82 98
76 92 110 133
95 115 138 168
114 138 166 203
133 161 194 238
152 184 222 273
171 207 250 308
190 230 278 343
209 253 306 378
A
D
E
31 45 50 62.5
4.5 4.5 4.5 5.5
5.25 6 6 7
F
G
H
J
K
19 18 7.75 19 132.2 23 23 10 23.5 163.4 28 26 28 175.4 12 35 31.5 16 35 199.4
1F
2F
3F
4F
5F
6F
7F
8F
9F
10F
28 34 42 49
47 57 70 84
66 80 98 119
85 103 126 154
104 126 154 189
123 149 182 224
142 172 210 259
161 195 238 294
180 218 266 329
199 241 294 364
N
Q
R
S
92.1 112.7 124.3 144.7
G1/8 G1/4 G3/8 G1/2
17.5 24 29 35.5
25 39 42 51.5
W
X
75.2 20 91.2 24.5 98.2 29 110.2 36
Y 27 35 40 50
G1/8
G1/4(Ex.G1/8)
G1/4
G3/8(Ex.G1/4)
G3/8
G1/2
5/2:14(CV=0.78) 5/3:12(CV=0.67)
5/2:16(CV=0.89) 5/3:12(CV=0.67)
5/2:25(CV=1.40) 5/3:18(CV=1.00)
5/2:30(CV=1.68) 5/3:18(CV=1.00)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
Clean air(After 40μm filteration) Internal pilot type / External pilot type
Reset Type
Spring reset / Gas reset
Lubrication
Not required 0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-20~70(No freezing) -15%~10%
Voltage range
DC:1.0W ; AC:1.0VA
DC:0.7W
Insulation class
Class F
Protective class
IP65(DIN40050) 5/2:5 Cycles/s;5/3:3 Cycles/s <0.05
Activate time(S) Weight(g)
N4R251-15 N4R252-15 N4R352-15
G1/8
Acting type
Power consumption
N4R251-10 N4R252-10 N4R352-10
5/2:12(CV=0.67) 5/3:9(CV=0.50)
Max. acting frequency
P
N3R251-10 N3R252-10 N3R352-10
M5
Working pressure(MPa) L
N3R251-08 N3R252-08 N3R352-08
5/2:5.5(CV=0.31) 5/3:5.5(CV=0.28)
Working medium
(mm)
(1 Serise only DC24V)
15:1/2"
Order Example:
Model No.
Blind plate
RV5312P
Low power solenoid valve
32
E MC
2
1
RV5212
RV5312E
RV5312C
2.22
N1R251: 110 N1R252: 171 N1R352: 181
N2R251: 209 N2R252: 314 N2R352: 357
N3R251: 289 N3R252: 400 N3R352: 450
N4R251: 528 N4R252: 638 N4R352: 727
2
RV Series Standard/ Low Power Solenoid Valve ( 5/2,5/3 way) 2.23
RV Series Standard/ Low Power Solenoid Valve ( 5/2,5/3 way)
RV Series
RV Series
2.24
Flow Chart Standard Solenoid Valve Port Size Reset Form
Voltage
ID Code
Connection Mode
Cover Color
Acting — Thread Type Type
M5:M5 Blank: DIN connector Blank: Standard type Blank: Internal pilot F: Flying leads 06:1/8" A: Amisco coil K:Waterproof DIN connector WB: External pilot 08:1/4" (Only 2、3、4 series is opitional) 10:3/8" E1:AC110V E6:AC36V Blank: Brown translucent 15:1/2" E2:AC220V E7:AC24V J: Colorless and translucent Blank : Spring E3:AC380V E8:DC110V Blank: G Q:Air E4:DC24V E9:DC48V P: PT (Only single control) E5:DC12V E10:DC36V T: NPT Order Example: RV series solenoid valve, 2 series valve body size, 5/2 way, single control, 1/4" port size, standard coil,DC24V, DIN connector, G thread, ERP code is: RV5221-08E4 RV
5:5 ways 1 : Single control 2:Double control 2:2 positions 3:3 positions 1:1Series C: Center close 2:2Series P: Center pressure 3:3Series E: Center exhaust 4:4Series (Only for 5/3 way)
N2R251 - 06、RV5221 - 06
N3R251 - 08、RV5231 - 08
Working Pressure (MPa)
—
Working Pressure (MPa)
Series No. Ways Positions Valve Body Controls Original Size Status
Flow Rate (L/min)
Flow Rate (L/min)
2
Working medium
RV5211-06 RV5212-06 RV5312-06
RV5221-06 RV5222-06 RV5322-06
RV5221-08 RV5222-08 RV5322-08
RV5231-08 RV5232-08 RV5332-08
RV5231-10 RV5232-10 RV5332-10
RV5241-10 RV5242-10 RV5342-10
RV5241-15 RV5242-15 RV5342-15
M5
G1/8
G1/8
G1/4(Ex.G1/8)
G1/4
G3/8(Ex.G1/4)
G3/8
G1/2
5/2:5.5(CV=0.31)
5/2:12(CV=0.67)
5/2:14(CV=0.78)
5/2:16(CV=0.89)
5/2:25(CV=1.40)
5/2:30(CV=1.68)
5/2:50(CV=2.79)
5/2:50(CV=2.79)
5/3:5.5(CV=0.28)
5/3:9(CV=0.50)
5/3:12(CV=0.67)
5/3:12(CV=0.67) 5/3:18(CV=1.00) 5/3:18(CV=1.00) Clean air(After 40μm filteration)
5/3:30(CV=1.67)
5/3:30(CV=1.67)
Acting type
Internal pilot type / External pilot type
Reset Type
Spring reset / Gas reset
Lubrication
Not required
N3R251 - 10、RV5231 - 10
Flow Rate (L/min)
Working pressure(MPa)
0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-20~70(No freezing)
N4R251 - 10、RV5241 - 10 N4R251 - 15、RV5241 - 15
Working Pressure (MPa)
Port size Sectional area(mm2)
RV5211-M5 RV5212-M5 RV5312-M5
N2R251 - 08、RV5221 - 08
Working Pressure (MPa)
Model No.
Working Pressure (MPa)
2
Flow Rate (L/min)
Flow Rate (L/min)
Internal Structure
-15%~10%
Voltage range Power consumption
DC:2.8W ; AC:3.0VA
DC:3.0W ; AC:4.0VA
Insulation class Protective class
Double Solenoid Valve
IP65(DIN40050)
Max. acting frequency
5/2:5 Cycles/s;5/3:3 Cycles/s
No.
<0.05
1
Activate time(S) R V 5211: 110 RV5212: 171 RV5312: 181
Weight(g)
Single Solenoid Valve
Class F
R V 5221: 209 RV5222: 314 RV5322: 357
R V 5231: 289 RV5232: 400 RV5332: 450
9 10
O-ring
11
Rear cover Engineered plastics Synthetic material Filter POM Piston Stainless steel Spring Manual override Engineered plastics Aluminum alloy Back seat Aluminum alloy Spring seat 65Mn C-type buckle
3 4 5
Flow Chart
6
Working Pressure (MPa)
Working Pressure (MPa)
7 N1R251 - M5、RV5211 - M5
N1R251 - 06、RV5211 - 06
8
5 / 3 Solenoid Valve
12 13 14 15 16 17
Flow Rate (L/min)
Flow Rate (L/min)
18
Material
Engineered plastics
Connector Nut Coil Pilot units Plate Piston Pilot seat Valve body Spool
2
R V 5241: 528 RV5242: 638 RV5342: 727
Part Name
18
POM+Carbon steel Cu
Engineered plastics Carbon steel POM
Engineered plastics Aluminum alloy Aluminum alloy HNBR
RV Series Standard/ Low Power Solenoid Valve ( 5/2,5/3 way) 2.25
V Series Standard/ N Series Low Power Solenoid Valve ( 5/2,5/3 way)
RV Series
V Series
2.26
Single Solenoid Valve DIN Type
Flying Leads Type P Q
2-K 3-A
W
2-B
Standard solenoid valve S
M
I
S
C
2-J
Manual button
M
I
C
Manual button
2-B
W
3-A
Series No. Ways Positions
T L
V
O
2:2 positions 3:3 positions
F
O
Mode\Sign
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
W
RV5211-M5 RV5211-06 RV5221-06 RV5221-08 RV5231-08 RV5231-10 RV5241-10 RV5241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
M5 G1/8 G1/8 G1/8 G1/4 G1/4 G3/8 G1/2
30 30 38 38 50 50 72 72
13 13 17 17 20 20 27 27
16.5 16.5 16 16 19.1 19.1 21 21
18 18 22 22 27 27 34 34
0 3 0 3 0 4 0 4
24.5 23.5 26 24.5 33.1 32.1 39 39
14.1 16 18 21 22 24 36 36
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.3 3.3 4.3 4.3 4.3 4.3 5.5 5.5
24.5 24.5 25 25 32.1 32.1 43 43
14 14 20 20 24 24 28 28
9.5 9.5 10.5 10.5 13.5 13.5 17.5 17.5
27 27 35 35 40 40 50 50
55.2 55.2 66.7 66.7 69.2 69.2 74.2 74.2
33.9 33.9 40.2 40.2 40.2 40.2 40.2 40.2
17.9 17.5 17 17 21.6 21.6 25.5 25.5
27.2 28 36 36 45 45 63 63
31.5 31.5 35 35 44.1 44.1 57 57
103.1 103.1 120.7 120.7 139.3 139.3 168.7 168.7
Note: The dimensions of NR series and RV series are same.
5 / 3 Solenoid Valve
Voltage
ID Code
Connection Mode
Cover Color
Valve Color — Thread Type
V5211-M5 V5212-M5 V5312-M5
Model No.
2
Flying Leads Type
Blank: Standard type Blank: DIN connector A: Amisco coil F: Flying leads
M5:M5 06:1/8" C: Center close 08:1/4" P: Center pressure 10:3/8" E: Center exhaust 15:1/2" (Only for 5/3 way)
E1:AC110V E2:AC220V E3:AC380V E4:DC24V E5:DC12V
V5211-06 V5212-06 V5312-06
V5221-06 V5222-06 V5322-06
V5221-08 V5222-08 V5322-08
V5231-08 V5232-08 V5332-08
Blank: Brown translucent J: Colorless and translucent
V5241-15 V5242-15 V5342-15
G1/8
G1/8
G1/4(Ex.G1/8)
G1/4
G3/8(Ex.G1/4)
G3/8
G1/2
5/2:12(CV=0.67) 5/3:9(CV=0.50)
5/2:14(CV=0.78) 5/3:12(CV=0.67)
5/2:16(CV=0.89) 5/3:12(CV=0.67)
5/2:25(CV=1.40) 5/3:18(CV=1.00)
5/2:30(CV=1.68) 5/3:18(CV=1.00)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
Working medium
Clean air(After 40μm filteration)
Acting type
Pilot type
RV5212-M5 RV5212-06 RV5222-06 RV5222-08 RV5232-08 RV5232-10 RV5242-10 RV5242-15
143.2 143.2 171.4 171.4 190.4 190.4 223.4 223.4
Lubrication
Not required
Mode\Sign
W2
Insulation class
RV5312-M5 RV5312-06 RV5322-06 RV5322-08 RV5332-08 RV5332-10 RV5342-10 RV5342-15
158.2 158.2 190.4 190.4 209.4 209.4 244.4 244.4
Protective class
Working pressure(MPa)
0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing) -15%~10%
Voltage range
DC:4.8W ; AC:5VA
DC:2.8W ; AC:3.0VA Class F
IP65(DIN40050) 5/2:5 Cycles/s;5/3:3 Cycles/s
Max. acting frequency
<0.05
Activate time(S) Weight(g)
V5241-10 V5242-10 V5342-10
M5
W1
Power consumption
V5231-10 V5232-10 V5332-10
5/2:5.5(CV=0.31) 5/3:5.5(CV=0.28)
Mode\Sign
Note: The dimensions of NR series and RV series are same.
E6:AC36V E7:AC24V E8:DC110V E9:DC48V E10:DC36V
Blank: G P: PT T: NPT
Blank:Black W:White
V series solenoid valve, 2 series valve body size, 5/2 way, single control, 1/4" port size, standard coil,DC24V,DIN connector, G thread, ERP code is: V5221-08E4
Sectional area(mm )
W2
DIN Type
W2
W1
W1
Flying Leads Type
Port Size
Order Example:
Port size
DIN Type
—
1 : Single control 2:Double control 1:1Series 2:2Series 3:3Series 4:4Series
(mm)
Double Solenoid Valve
Original Status
5:5 ways
D
N
G
D F
N
Valve Body Controls Size
R
E
H
T G
R
L
H
E
2
2-K
2-J
V5211: 110 V5212: 171 V5312: 181
V5221: 209 V5222: 314 V5322: 357
V5231: 289 V5232: 400 V5332: 450
V5241: 528 V5242: 638 V5342: 727
2
V Series Standard/ N Series Low Power Solenoid Valve ( 5/2,5/3 way) 2.27
V Series Standard/ N Series Low Power Solenoid Valve ( 5/2,5/3 way)
V Series
V Series
2.28
Flow Chart N1M251 - 06、V5211 - 06
Working Pressure (MPa)
Double Solenoid Valve DIN Type
Flow Rate (L/min)
Flow Rate (L/min)
Flow Rate (L/min)
Working Pressure (MPa)
Working Pressure (MPa)
W1
W2
V5212 V5222 V5232 V5242 V5312 V5322 V5332 V5342
140.6 172 191 222 -
155.6 191 210 244
Note: The dimensions of N series and V series are same.
N4M251 - 10、V5241 - 10 N4M251 - 15、V5241 - 15
N3M251 - 10、V5231 - 10
Model\Sign
W2
W2
W1
Working Pressure (MPa)
Working Pressure (MPa)
Flying Leads Type
N3M251 - 08、V5231 - 08
N2M251 - 08、V5221 - 08
Working Pressure (MPa)
DIN Type
Flow Rate (L/min)
N2M251 - 06、V5221 - 06
Single Solenoid Valve Flow Rate (L/min)
Flow Rate (L/min)
Flow Rate (L/min)
DIN Type
Flying Leads Type
5 / 3 Solenoid Valve
Carbon steel
8
Valve body
Aluminum alloy
9
Spool
Aluminum alloy
10
O-ring
HNBR
11
Spring
Stainless steel
12
Rear cover
13 14
Alloy steel Screw Manual override Engineered plastics
Zinc alloy
15
Back seat
Aluminum alloy
16
Spring seat
Aluminum alloy
17
C-type buckle
65Mn
2-B W
3-A
D F
N
G
O
S
C
M
T
POM
Screw
R
Piston
L
6 7
2- K
Manual button
E
Carbon steel
I
Plate
J
Pilot units
5
2- J
H
4
T
Cu
S
POM+Carbon steel
Coil
R
Nut
2- K W
2 3
M
Engineered plastics
L
Material
Connector
I
Part Name
1
H
No.
3-A
Double Solenoid Valve
C
Single Solenoid Valve
2- J
Internal Structure
2-B
P Q
E
2
5 / 3 Solenoid Valve Flying Leads Type
W1
Working Pressure (MPa)
N1M251 - M5、V5211 - M5
G N
D F
O
(mm) Model\Sign
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
W
V5211-M5 V5211-06 V5221-06 V5221-08 V5231-08 V5231-10 V5241-10 V5241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
M5 G1/8 G1/8 G1/8 G1/4 G1/4 G3/8 G1/2
30 30 38 38 50 50 72 72
13 13 17 17 20 20 27 27
13.2 13.2 12.7 12.7 15 15 21 21
18 18 22 22 27 27 34 34
0 3 0 3 0 4 0 4
21 20.2 22.7 21.7 28 28 39 39
14.5 16 18 20 24 24 36 36
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.3 4.3 4.3 4.3 5.2 5.2
21.2 21.2 21.7 21.7 28 28 43 43
14 14 20 20 24 24 28 28
9.5 9.5 10.5 10.5 13.5 13.5 17.5 17.5
27 27 35 35 40 40 50 50
54.8 54.8 67.5 67.5 70 70 75 75
32.8 32.8 40.5 40.5 40.5 40.5 40.5 40.5
14.5 14.5 14.2 14.2 17.5 17.5 25.5 25.5
27.5 27.5 36 36 45 45 63 63
28.2 28.2 31.7 31.7 40 40 57 57
98.5 98.5 117.7 117.7 135.5 135.5 168 168
Note: The dimensions of N series and V series are same.
2
RV Series Air Control Valve (5/2, 5/3 way) 2.29
RV Series Air Control Valve (5/2, 5/3 way)
RVA Series
(4 series single air control valve only)
RVA Series
(1,2,3 series single air control valve)
2.30
Internal Structure Single Air Control 8
7
6
5
Double Air Control 4 3
No.
2
1
Air Control Cover
2
5
Piston Screw Valve Body Spool
6
O-ring
7
Piston Rear Cover Back Seat Spring Seat C-type Buckle
3 4 5/3 Ways Solenoid Valve
2
8 Series No. RVA
Ways
Positions
5:5 ways 2:2 positions 3:3 positions
Valve Body ID Code
Controls
Initial Status
— Port Size
9
Reset Type — Thread Type
10
1:1Series 1: Single control 2:2Series 2: Double control 3:3Series C: Center close 4:4Series P: Center pressure E: Center exhaust (only for 5/3 ways)
M5:M5 06:1/8" 08:1/4" 10:3/8" 15:1/2"
11
Bland:G P:PT T:NPT
Blank: Spring return (Apply to 4 series single control valve) Q: Air return (Apply to 1,2,3 series single control valve)
11 10
Order Example:
5/3:5.5(CV=0.28) 5/3:9(CV=0.50)
G1/4(Ex.G1/8)
Working medium
5/3:12(CV=0.67)
5/2:16(CV=0.89) 5/3:12(CV=0.67)
RVA5231-10 RVA5232-10 RVA5332-10
G1/4
G3/8(Ex.G1/4)
5/2:25(CV=1.40) 5/2:30(CV=1.68) 5/3:18(CV=1.00) 5/3:18(CV=1.00)
External type
Reset type
Spring reset / Gas reset
Lubrication
Not required
Working pressure(MPa)
RVA5241-15 RVA5242-15 RVA5342-15
G3/8
G1/2
5/2:50(CV=2.79) 5/3:30(CV=1.67)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
-20~70(No freezing) 5/2:5 Cycles/s;5/3:3 Cycles/s
Max. acting frequency RVA5211:72 RVA5212:87 RVA5312:181
RVA5221:128 RVA5222:153 RVA5322:219
RVA5231:218 RVA5232:260
5 Cycles/s RVA5332:358
Aluminum Alloy Aluminum Alloy
Flow Rate(L/min)
RVA5221 - 08
RVA5221 - 06
1.2
Working temperature(℃)
NBR POM Zinc Alloy
RVA5211 - 06
Flow Rate(L/min)
0.15~0.8
(MPa)
Weight(g)
RVA5241-10 RVA5242-10 RVA5342-10
Clean air(After 40 μm filteration )
Acting type
Aluminum Alloy
Working Pressure(MPa)
G1/8
Sectional area(mm) 5/2:5.5(CV=0.31) 5/2:12(CV=0.67) 5/2:14(CV=0.78)
RVA5231-08 RVA5232-08 RVA5332-08
Aluminum Alloy
RVA5241:437 RVA5242:490 RVA5342:598
Working Pressure(MPa)
G1/8
RVA5221-08 RVA5222-08 RVA5322-08
Working Pressure(MPa)
M5
RVA5221-06 RVA5222-06 RVA5322-06
Working Pressure(MPa)
Port size
RVA5211-06 RVA5212-06 RVA5312-06
POM Carbon Steel
9
RVA5211 - M5
RVA5211-M5 RVA5212-M5 RVA5312-M5
Material Aluminum Alloy
Flow Chart
RV series air control valve, 5/2 way, 2 series valve body size, single control, 1/8" port size, air return, G thread, ERP code is: RVA5221-06Q
Model No.
Part Name
1
Flow Rate(L/min)
Flow Rate(L/min)
65Mn
2
RV Series Air Control Valve (5/2, 5/3 way) 2.31
V Series Air Control Valve (5/2,5/3 way) VA Series
RVA Series
VA5211
Flow Chart RVA5241 - 10 RVA5241 - 15
RVA5231 - 10
Ways
Series No. Flow Rate(L/min)
Flow Rate(L/min)
VA5212
VA5312E
VA5312C
Working Pressure(MPa)
Working Pressure(MPa)
Working Pressure(MPa)
RVA5231 - 08
Positions
Valve body size
Valve type
Original status — Port size
Controls
VA5312P
Valve color — Thread type
Flow Rate(L/min)
2
2:2 positions 1:1Series 1 : Single control 3:3 positions 2:2Series 2:Double control 3:3Series 4:4Series
5:5 ways
VA
C: Center close P: Center pressure E: Center exhaust (Only for 5/3 way)
M5:M5 06:1/8" 08:1/4" 10:3/8" 15:1/2"
Blank: Standard type Blank:Black M: NAMUR type W:White
Blank: G P: PT T: NPT
Order Example:
Main Dimension
V series air control valve, 1 series valve body size, 5/2 way,single control,1/8" port size, standard valve body, white color, PT thread, ERP code is: VA5211-06W-P
Single air control
Double air control
5/3 ways solenoid valve
VA5211-M5 VA5212-M5 VA5312-M5
Model No. Port size 2
Sectional area(mm )
VA5211-06 VA5212-06 VA5312-06
VA5221-06 VA5222-06 VA5322-06
VA5221-08 VA5222-08 VA5322-08
G1/8
G1/4(Ex.G1/8)
G1/4
G3/8(Ex.G1/4)
G3/8
G1/2
5/2:14(CV=0.78) 5/3:12(CV=0.67)
5/2:16(CV=0.89) 5/3:12(CV=0.67)
5/2:25(CV=1.40) 5/3:18(CV=1.00)
5/2:30(CV=1.68) 5/3:18(CV=1.00)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
Clean air(After 40μm filteration)
Acting type
External type
Lubrication
Not required 0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing) 5/2:5 Cycles/s; 5/3:3 Cycles/s
E
F
G
RVA5211-M5 RVA5211-06 RVA5221-06 RVA5221-08 RVA5231-08 RVA5231-10 RVA5241-10 RVA5241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
M5 G1/8 G1/8 G1/8 G1/4 G1/4 G3/8 G1/2
30 30 38 38 50 50 72 72
13 13 17 17 20 20 27 27
16.5 16.5 16 16 19.1 19.1 21 21
18 18 22 22 27 27 34 34
0 3 0 3 0 4 0 4
H
I
24.5 14.1 23.5 16 18 26 24.5 21 33.1 22 32.1 24 36 39 36 39
J
K
L
M
N
O
P
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.3 4.3 4.3 4.3 5.2 5.2
24.5 24.5 25 25 32.1 32.1 43 43
14 14 20 20 24 24 28 28
9.5 9.5 10.5 10.5 13.5 13.5 17.5 17.5
27 27 35 35 40 40 50 50
G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8
R
S
T
W
17.9 27.2 31.5 72 17.5 28 31.5 72 81 35 36 17 81 35 36 17 21.6 45 44.1 99.6 21.6 45 44.1 99.6 57 127 25.5 63 57 127 25.5 63
W1 W2 81 81 92 92 111 111 140 140
96 96 111 111 130 130 161 161
V5211: 72 V5212: 87 V5312: 181
Weight(g)
V5221: 128 V5222: 153 V5322: 219
V5231: 218 V5232: 260 V5332: 358
VA5211-M5
V5241: 437 V5242: 490 V5342: 598
VA5211-06
Working Pressure (MPa)
D
VA5241-15 VA5242-15 VA5342-15
G1/8
Working Pressure (MPa)
C
VA5241-10 VA5242-10 VA5342-10
5/2:12(CV=0.67) 5/3:9(CV=0.50)
Max. acting frequency B
VA5231-10 VA5232-10 VA5332-10
M5
Working pressure(MPa)
A
VA5231-08 VA5232-08 VA5332-08
5/2:5.5(CV=0.31) 5/3:5.5(CV=0.28)
Working medium
Model/Sign
2.32
Flow Rate (L/min)
Flow Rate (L/min)
2
V Series Air Control Valve (5/2,5/3 way) VA Series
VA Series
Single Air Control
Double Air Control
5/3 Air Control
VA5221-08
Working Pressure (MPa)
P 3-A 2- K
2-B
R
L
Flow Rate (L/min)
E
Flow Rate (L/min)
H
T
S
C
M
W
W1
2- J
I
Working Pressure (MPa)
VA5221-06
2.34
W2
2.33
V Series Air Control Valve (5/2,5/3 way)
G
Flow Rate (L/min)
VA5231-10
VA5241-15
Working Pressure (MPa)
Working Pressure (MPa)
VA5231-08
Working Pressure (MPa)
2
8
7
6
Flow Rate (L/min)
Flow Rate (L/min)
Double Air Control 5
4 3 2
1
No.
5/3 Air Control
11 10
9
O
(mm)
Internal Structure Single Air Control
2
N
D F
Part Name
1
Air control cover
Material Aluminum alloy
2
Piston
3
Screw
4
Valve body
Aluminum alloy Aluminum alloy
POM Carbon steel
5
Spool
6
O-ring
NBR
7
Spring
Stainless steel
8
Rear cover
Zinc alloy
9
Back seat
Aluminum alloy
10
Spring seat
Aluminum alloy
11
C-type buckle
65Mn
Model\Sign
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
R
S
T
W
W1
W2
VA5211-M5 VA5211-06 VA5221-06 VA5221-08 VA5231-08 VA5231-10 VA5241-10 VA5241-15
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
M5 G1/8 G1/8 G1/8 G1/4 G1/4 G3/8 G1/2
30 30 38 38 50 50 72 72
13 13 17 17 20 20 27 27
13.2 13.2 12.7 12.7 15 15 21 21
18 18 22 22 27 27 34 34
0 3 0 3 0 4 0 4
21 20.2 22.7 21.7 28 28 39 39
14.5 16 18 20 24 24 36 36
3.3 3.3 3.3 3.3 4.3 4.3 4.3 4.3
3.1 3.1 4.3 4.3 4.3 4.3 5.2 5.2
21.2 21.2 21.7 21.7 28 28 43 43
14 14 20 20 24 24 28 28
9.5 9.5 10.5 10.5 13.5 13.5 17.5 17.5
27 27 35 35 40 40 50 50
G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8
14.5 14.5 14.2 14.2 17.5 17.5 25.5 25.5
27.5 27.5 35 35 45 45 63 63
28.2 28.2 31.7 31.7 40 40 57 57
68.7 68.7 77.7 77.7 95.5 95.5 127 127
81 81 92 92 111 111 140 140
96 96 111 111 130 130 162 162
V Series Manifold (5/2 way) 2.35
V Series Manifold (5/2 way)
V Series Manifold
V Series Manifold
2
2.36
2 V
52
N
1 1:1 series valve body 2:2 series valve body 3:3 series valve body 4:4 series valve body
F
station stations stations
Thread Type Blank:G P:PT T:NPT Blind plate
stations
Order Example: * V series manifold for 5/2, 2 series valve body, 5 stations, Model: V522-5F
VBP
52
2
Model/Sign V521-□F V522-□F V523-□F V524-□F
1:1 series valve body 2:2 series valve body 3:3 series valve body 4:4 series valve body
Order Example: * Blind plate for 5/2 valve, 2 series valve body, Model: VBP-522
Model/Sign V521-□F V522-□F V523-□F V524-□F
Note : 1 . The dimensions of 5 / 3 way is same as 5 / 2 way series . 2 . Blind plate assembly include: plate, gasket and screws .
58 59 75 98
43 50 64 94
20 21 26 32
D 4.5 4.5 4.5 5.5
5 6 6 7
19 23 28 35
19 23 27 31.5
9.5 9.1 12 15.9
14 14.5 17.5 21.5
23 23.5 28 35
Model/Sign V521-□F V522-□F V523-□F V524-□F
V521-NF(N≤16)
V522-NF(N≤16)
V523-NF(N≤12)
V524-NF(N≤7) Model/Sign V521-□F V522-□F V523-□F V524-□F
K 143.2 171.4 190.4 223.4
M 158.2 190.4 209.4 244.4
N 103.1 120.7 139.3 168.7
Q G1/4 G1/4 G3/8 G1/2
R 40 43 53 70.5
S 49 50 67 86.8
W 79.2 91.2 98.2 110.2
X 24 24.5 29 36
Y 27 35 40 50
RV Series NAMUR Solenoid Valve(3/2 way) 2.37
RV Series NAMUR Solenoid Valve(3/2 way)
RV Series
RV Series
2.38
(1,2,3 series single control valve)
Standard Solenoid Valve (4 series single control valve only) Ways
Series No.
Positions
Valve body ID code
2:2 positions 3 : 3 ways RV(Solenoid valve) RVA(Air control valve )
1:1Series 2:2Series 3:3Series 4:4Series
Valve body Series No. ID code ID Code
Positions
Ways
Controls
Initial Status
Port Size
Reset Type
Valve Body Type M : NAMUR
N
1: Single control 2:2 positions M5:M5 06:1/8" 1:1Series 2: Double control 08:1/4" 10:3/8" 2:2Series 15:1/2" 3:3Series R: Standard armature 3 : 3 ways +Low power coil 4:4Series Blank: Normal close Blank: Spring return H: Normal open (4 series single solenoid control only) Q: Air return (1,2,3 series single solenoid control)
Connection Mode
Voltage
Cover Color
Thread Type
Blank: DIN connector type Blank: G E1:AC110V K: Water proof connector type (only for 2,3,4 series) P: PT E2:AC220V T: NPT E4:DC24V (for 1series, Blank: Brown translucent only DC24V available)
Port Size Reset Type
Valve body Type
ID Code
Blank: Normal close H: Normal open
Air control valve: 1 series 3 series M5:M5 08:1/4" 06:1/8" 10:3/8" 2 series 4 series 06:1/8" 10:3/8" 08:1/4" 15:1/2"
Blank: Spring return (Only apply to 4 series single control valve) Q: Air return (Only apply to 1,2,3 series single control valve)
Connection Mode
Voltage
M : NAMUR type
1: Single control 2: Double control Solenoid valve: M5:M5 06:1/8" 08:1/4" 10:3/8" 15:1/2"
L ow Power Solenoid Valve
2
Controls Initial Status
Cover Color
Blank: DIN connector type F:Flying leads K: Water proof connector type (only for 2,3,4 series)
Blank: Standard type A: Amisco coil E1:AC110V E2:AC220V E3:AC380V E4:DC24V E5:DC12V
E6:AC36V E7:AC24V E8:DC110V E9:DC48V E10:DC36V
Thread Type
Blank: G P: PT T: NPT
Blank: Brown translucent J: Colorless and translucent B: black(only black color available for water proof connector)
2 Order Example: RV series solenoid valve , 3 / 2 ways , 1 series valve body size , double control , 1/8 " port size , NUMAR type , standard coil, DC24V, Fly leads connector, G thread , ERP code is RV3212 - 06ME2F
J: Colorless and translucent B: Black(only black color available for water proof connector)
Order Example: RV series low power solenoid valve , 3 / 2 ways , 1 series valve body size , double control , 1/8 " port size , NUMAR type , DC24V, DIN connector, G thread , ERP code isN1R232 - 06ME4
Model Port Size Sectional area(mm) Model Port Size
N1R231-M5M N1R231-06M N1R232-M5M N1R232-06M
M5
Sectional area(mm) 5.5(CV=0.31)
N2R231-06M N2R231-08M N2R232-06M N2R232-08M
N3R231-08M N3R231-10M N3R232-08M N3R232-10M
G1/8
G1/8
G1/4
G1/4
12(CV=0.67)
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
Working medium
Internal pilot
Reset type
Spring reset / Gas reset
Lubrication
Not required
Working pressure(MPa)
G3/8
G1/2
50(CV=2.79)
50(CV=2.79)
1.2
DC24V:0.6W
Insulation Class
IP65(DIN40050) 5 Cycles/s <0.05
Activate time(S) N1R231-M:114 N1R232-M:171
N2R231-M:203 N2R232-M:310
G1/4
G1/4
G3/8
G3/8
G1/2
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
Clean air(After 40 μm filteration )
Acting type
Internal pilot
Reset type
Spring reset / Gas reset
Lubrication
Not required
Working pressure(MPa)
0.15~0.8
Guaranteed Pressure(MPa)
1.2 -20~70(Dry air)
Weight(g)
Class F
Protective Class Max. acting frequency
G1/8
-15%~10% DC:2.8W ; AC:3.0VA
DC:3.0W ; AC:4.0VA Class F IP65(DIN40050) 5 cycles/s <0.05
Activate time(S)
DC24V:0.7W AC220V:0.9VA AC110V:1.4VA
N3R231-M:295 N3R232-M:403
N4R231-M:448 N4R232-M:578
RV3241-15M RV3242-15M
14(CV=0.78)
Protective Class Max. acting frequency
-15%~10%
RV3241-10M RV3242-10M
G1/8
Insulation Class
-20~70(Dry air)
RV3231-10M RV3232-10M
12(CV=0.67)
Working medium
Power Consumption
Working temperature(℃)
RV3231-08M RV3232-08M
M5
Voltage Range
0.15~0.8
Voltage Range
RV3221-08M RV3222-08M
5.5(CV=0.31)
Working temperature(℃)
Guaranteed Pressure(MPa)
Weight(g)
30(CV=1.68)
N4R231-15M N4R232-15M
Clean air(After 40 μm filteration )
Acting type
Power Consumption
G3/8
N4R231-10M N4R232-10M
RV3211-M5M RV3211-06M RV3221-06M RV3212-M5M RV3212-06M RV3222-06M
R V 3211- M:114 R V 3212- M:171
R V 3221- M:203 RV3222- M:310
R V 3231- M:295 RV3232- M:403
R V 3241- M:448 RV3242- M:578
RV Series NAMUR Solenoid Valve(3/2 way)
RV Series NAMUR Solenoid Valve(3/2 way)
RV Series
2.39
RV Series
Flow Chart
Internal Structure Single Air Control(N.C)
Single Air Control(N.O) No. 1
2
1
N1R231 - 06、RV3211 - 06
2
Working Pressure(MPa)
Working Pressure(MPa)
N1R231 - M5、RV3211 - M5
Flow Rate(L/min)
3 4 5 6 7 8
2 13 12
11
10 9
8
7
6
5
4
9
3
Flow Rate(L/min)
Carton Steel POM Engineered plastics Aluminum Alloy
Rear Cover Filter Piston Manual Override
Aluminum Alloy NBR Engineered plastics High Molecular Material
Engineered plastics Engineered plastics
N3R231 - 08、RV3231 - 08
Working Pressure(MPa)
Working Pressure(MPa)
Pure iron+Brass +Stainless Steel
11
14
14
POM Brass+Thermoset Resin
O ring
12
Double Air Control
Material
Engineered plastics
Connector Fixing Nut Coil Pilot Units Plate Piston Pilot Seat Valve Body Spool
10
13
N2R231 - 06、RV3221 - 06
Part Name
Main Dimension Single Solenoid Valve
Flow Rate(L/min)
Flow Rate(L/min)
DIN Type
N3R231 - 10、RV3231 - 10
Flow Rate(L/min)
Working Pressure(MPa)
Working Pressure(MPa)
Working Pressure(MPa)
N2R231 - 08、RV3221 - 08
Flying Lead Type
N4R231 - 10、RV3241 - 10 N4R231 - 15、RV3241 - 15
Flow Rate(L/min)
Flow Rate(L/min)
(mm) Model\Sign RV3211-M5M RV3211-06M RV3221-06M RV3221-08M RV3231-08M RV3231-10M RV3241-10M RV3241-15M
A
B
C
D
E
29 68.5 1.5 M5 13.6 29 68.5 1.5 G1/8 13.6 31 79 1.5 G1/8 17.6 31 79 1.5 G1/4 17.6 42.1 97.6 1.5 G1/4 19.6 42.1 97.6 1.5 G3/8 19.6 45.5 108 1.8 G3/8 21.8 45.5 108 1.8 G1/2 21.8 Note: The dimensions of N series and RV series are same.
F
K
L
M
N
O
P
Q
R
S
W
W1*
18 18 22 22 27 27 34 34
3.1 3.1 4.3 4.3 5.2 5.2 5.2 5.2
16 16 15.5 15.5 18.1 18.1 17.5 17.5
14 14 20 20 24 24 33 33
22 22 29 29 32 32 41 41
27 27 35 35 40 40 50 50
55.2 55.2 66.7 66.7 69.2 69.2 74.2 74.2
33.9 33.9 40.2 40.2 40.2 40.2 40.2 40.2
21.9 23 23.5 25.5 31.1 30.1 30 32
14.2 14 18 18 21 23 31.5 31.5
98.1 98.1 115.7 115.7 134.3 134.3 144.7 144.7
138.2 138.2 166.4 166.4 185.4 185.4 199.4 199.4
2.40
V Series Standard/N Series Low Power NAMUR Solenoid Valve(3/2 way) 2.41
V Series Standard/N Series Low Power NAMUR Solenoid Valve(3/2 way)
V3211M/V3212M Series
V3211M/V3212M Series
2.42
V3211M Standard Solenoid Valve V3211HM
Series No. Ways Positions Valve Body Controls Original — Port Size Valve Type Size Status V
V3211-06M
V3212M
N
Blank: Standard type A: Amisco coil
Ways
2 : 2 positions
Controls
Original — Port Size Valve Type Status
Voltage
Connection Mode
E1:AC110V E2:AC220V E3:AC380V M : NAMUR type E4:DC24V E5:DC12V
M5: M5 06: 1/8" 08: 1/4" Blank: NC 10: 3/8" H: NO 15: 1/2"
Order Example: V series solenoid valve, 3/2 way, 1 series valve body, double control, port size 1/8", NAMUR valve type, low power coil, AC220V, flying leads coil, black color valve, G thread, ERP code is: N1M231-06ME2F. Note: Low power type with white valve body
Model No. Port size
V3211-M5 V3212-M5
V3211-06 V3212-06
M5
G1/8
V3221-06 V3222-06
V3221-08 V3222-08
Blank: Brown translucent J: Colorless and translucent
N1M231-M5 N1M232-M5
N1M231-06 N1M232-06
N2M231-06 N2M232-06
G1/8
M5
N2M231-08 N2M232-08
N3M231-08 N3M232-08
N3M231-10 N3M232-10
N4M231-10 N4M232-10
N4M231-15 N4M232-15
G1/8
G1/4
G1/4
G3/8
G3/8
G1/2
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
G1/4
G3/8
G3/8
G1/2
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
Clean air(After 40μm filteration) Pilot type
Lubrication
Not required
Working pressure(MPa)
0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing) -15%~10% DC:2.8W ; AC:3.0VA
DC:4.8W ; AC:5VA
Insulation class
Class F
Protective class
IP65(DIN40050) 5 Cycles/s
Max. acting frequency
<0.05 V3211-M: 114 V3212-M: 171
Clean air(After 40μm filteration) Not required 0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing)
N1M231 - 06、V3211 - 06
-15%~10% DC:1.0W ; AC:1.0VA
Insulation class
Class F
Protective class
IP65(DIN40050)
Max. acting frequency
5 Cycles/s <0.05
Activate time(S) N1M231-M: 114 N1M232-M: 171
Note: The technical data of NO type and NC type are same.
N2M231-M: 203 N2M232-M: 310
V3231-M: 295 V3232-M: 403
V3241-M: 448 V3242-M: 578
Flow Chart
Working pressure(MPa)
Working Pressure (MPa)
Pilot type
Lubrication
DC:0.7W
V3221-M: 203 V3222-M: 310
Note: The technical data of NO type and NC type are same.
Acting type
Voltage range
V3241-15 V3242-15
25(CV=1.40)
Acting type
Weight(g) Working medium
V3241-10 V3242-10
G1/4
N3M231-M: 295 N3M232-M: 403
N2M231 - 08、V3221 - 08
Working Pressure (MPa)
Sectional area(mm ) 5.5(CV=0.31) 12(CV=0.67)
V3231-10 V3232-10
16(CV=0.89)
Activate time(S) 2
V3231-08 V3232-08
G1/8
Working medium
Power consumption
Weight(g)
Blank:Black W:White
14(CV=0.78)
Voltage range
Power consumption
E6:AC36V E7:AC24V E8:DC110V E9:DC48V E10:DC36V
2
2 Sectional area(mm ) 5.5(CV=0.31) 12(CV=0.67)
Port size
Blank: G P: PT T: NPT
Blank: DIN connector F: Flying leads
Cover Color — Thread Type
Blank: G M : NAMUR type Blank: DIN connector P: PT F: Flying leads T: NPT E1:AC110V Blank: Brown translucent J: Colorless and translucent E2:AC220V E4:DC24V
1 : Single control 2 : Double controls
3 : 3 ways
M: Standard armature +Low power coil
Model No.
Valve — Thread Type Color
Cover Color
Connection Mode
N3M231 - 10、V3231 - 10
Working Pressure (MPa)
Series No. Valve Body ID Code Positions Size 1 : 1 series 2 : 2 series 3 : 3 series 4 : 4 series
M5:M5 06:1/8" 08:1/4" 10:3/8" 15:1/2"
Blank: NC H: NO 1 : Single control 2 : Double controls
Voltage
ID Code
Order Example: V series solenoid valve, 3/2 way, 1 series valve body, double control, port size 1/8", NAMUR valve type, standard coil, AC220V, flying leads coil, black color valve, G thread, ERP code is: V3212-06ME2F.
Low Power Solenoid Valve
2
2 : 2 positions 3 : 3 ways 1 : 1 series 2 : 2 series 3 : 3 series 4 : 4 series
N4M231-M: 448 N4M232-M: 578
400
Flow Rate (L/min)
Flow Rate (L/min)
800
1200
1600
2000
2400
Flow Rate (L/min)
V Series Standard/N Series Low Power NAMUR Solenoid Valve(3/2 way) 2.43
RV Series NAMUR Solenoid Valve(5/2,5/3 way)
V3211M/V3212M Series
2.44
NRV Series
(4 series (1,2,3 series single control valve only) single control valve)
Internal Structure Single solenoid valve
RP
Double solenoid valve
2
No.
Part Name
Material
1
Connector
Engineered plastics
2
Nut
POM+Carbon steel
3
Coil
Cu
4
Pilot units
5
Plate
6
Piston
POM
7
Screw
Carbon steel
8
Valve body
Aluminum alloy
9
Spool
Aluminum alloy
O-ring
HNBR
11
Spring
Stainless steel
12
Rear cover
13
Carbon steel Screw Manual override Engineered plastics
Single Solenoid Valve
RP
RP
L ow Power Solenoid Valve Valve Body Series No. ID Code ID Code
Positions
Ways
Controls
Initial Status
Port Size
Reset Type
Valve Body Type
Zinc alloy
Double Solenoid Valve
DIN Type
RP
Carbon steel
10
14
RP
RP
N
M5:M5 06:1/8" 1:1Series 1: Single control 2:2 positions M : NAMUR 08:1/4" 10:3/8" 2: Double control 2:2Series 3:3 positions 15:1/2" 3:3Series 5 : 5 ways R: Standard armature 4:4Series +Low power coil Blank: Spring return C: Center close P: Center pressure (4 series single solenoid control only) Q: Air return E: Center exhaust (only for 5/3 ways) (1,2,3 series single solenoid control)
Voltage
Connection Mode
Cover Color
Blank: DIN connector type K: water proof connector type E1:AC110V (only for 2,3,4 series) E2:AC220V E4:DC24V(for 1series, only DC24V available)
Thread Type
Blank: G P: PT T: NPT
Blank: Brown translucent J: Colorless and translucent B: black(only black color available for water proof connector)
Order Example: RV series low power solenoid valve , 5 / 2 ways , 1 series valve body size , double control , 1/8 " port size , NUMAR type , DC24V, DIN connector, G thread , ERP code is N1R252 - 06ME4
Flying Leads Type P Q
W1
Model Port Size
W
ΦBdepC
N1R251-M5M N1R251-06M N1R252-M5M N1R252-06M N1R352-M5M N1R352-06M
M5
Sectional area(mm) 5/2:5.5(CV=0.31)
5/3:5.5(CV=0.28)
D
2 -ΦK
S R
M L
N O
G1/8
G1/8
5/2:12(CV=0.67) 5/3:9(CV=0.50)
5/2:14(CV=0.78) 5/3:12(CV=0.67)
Working medium
2-A
F
N2R251-06M N2R251-08M N2R252-06M N2R252-08M N2R352-06M N2R352-08M
G1/4(Ex.G1/8)
Internal pilot Spring reset / Gas reset
Lubrication
Not required 1.2
Working temperature(℃)
-20~70(No freezing)
A
B
C
D
F
K
L
M
N
O
P
Q
R
S
W
W1*
Voltage Range
13.6 13.6 17.6 17.6 19.5 19.5 21.8 21.8
1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8
65 65 75.5 75.5 93.5 93.5 104.5 104.5
18 18 22 22 27 27 34 34
3.1 3.1 4.3 4.3 5.2 5.2 5.2 5.2
12.7 12.7 12.2 12.2 14 14 17.5 17.5
14 14 20 20 24 24 33 33
22 22 29 29 32 32 41 41
27 27 35 35 40 40 50 50
54.8 54.8 67.5 67.5 70 70 75 75
32.8 32.8 40.5 40.5 40.5 40.5 40.5 40.5
18.5 19.7 20.2 22.2 26.7 26 30 32
14.5 14 18 18 21.5 23 31.5 29.5
93.5 93.5 112.7 112.7 130.5 130.5 144 144
135.6 135.6 167 167 186 186 198 198
Power Consumption
G3/8
G1/2
5/2:50(CV=2.79) 5/3:30(CV=1.67)
5/2:50(CV=2.79) 5/3:30(CV=1.67)
-15%~10%
Insulation Class
DC24V:0.7W AC220V:0.9VA AC110V:1.4VA Class F
Protective Class Max. acting frequency
IP65(DIN40050) 5 cycles/s
DC24V:0.6W
Activate time(S) Weight(g)
N4R251-15M N4R252-15M N4R352-15M
0.15~0.8
Guaranteed Pressure(MPa)
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
N4R251-10M N4R252-10M N4R352-10M
Clean air(After 40 μm filteration )
Reset type
Model\Sign
G3/8(Ex.G1/8)
5/2:25(CV=1.40) 5/2:30(CV=1.68) 5/3:18(CV=1.00) 5/3:18(CV=1.00)
Acting type
V3211-M5M V3211-06M V3221-06M V3221-08M V3231-08M V3231-10M V3241-10M V3241-15M
Note: The dimensions of NO type and NC type are same, the dimensions of N series and V series are same.
G1/4
5/2:16(CV=0.89) 5/3:12(CV=0.67)
Working pressure(MPa) (mm)
N3R251-08M N3R251-10M N3R252-08M N3R252-10M N3R352-08M N3R352-10M
<0.05 N1R251-M:113 N1R252-M:176 N1R352-M:186
N2R251-M:208 N2R252-M:306 N2R352-M:349
N3R251-M:300 N3R252-M:409 N3R352-M:459
N4R251-M:533 N4R252-M:666 N4R352-M:755
2
RV Series NAMUR Solenoid Valve (5/2,5/3 way) 2.45
RV Series NAMUR Solenoid Valve(5/2,5/3 way)
RV Series
RV Series
2.46
Flow Chart N1R251 - M5、RV5211 - M5
2:2 positions 3:3 positions
Port Size Reset Type
C: Center close P: Center pressure E: Center exhaust (only for 5/3 ways)
ID Code
Voltage
M : NAMUR type
1: Single control 2: Double control Solenoid valve: M5:M5 06:1/8" 08:1/4" 10:3/8" 15:1/2"
Valve Body Type
Air control valve: 1 series 3 series M5:M5 08:1/4" 06:1/8" 10:3/8" 2 series 4 series 06:1/8" 10:3/8" 08:1/4" 15:1/2"
Blank: Spring return (Only apply to 4 series single control valve) Q: Air return (Only apply to 1,2,3 series single control valve)
Connection Mode
Cover Color
Blank: DIN connector type F: Flying leads K: Water proof connector type (only for 2,3,4 series)
Blank: Standard type A: Amisco coil E1:AC110V E2:AC220V E3:AC380V E4:DC24V E5:DC12V
E6:AC36V E7:AC24V E8:DC110V E9:DC48V E10:DC36V
Thread Type
Blank: G P: PT T: NPT
Blank: Brown translucent J: Colorless and translucent B: black(only black color availale for water proof connector)
Flow Rate(L/min)
Flow Rate(L/min)
N2R251 - 06、RV5221 - 06
N3R251 - 08、RV5231 - 08
2 Order Example: RV series solenoid valve , 5 / 2 ways , 1 series valve body size , double control , 1/8 " port size , NUMAR type , standard coil, DC24V, Fly leads connector, G thread , ERP code is RV5212 - 06ME2F
2
Flow Rate(L/min)
Flow Rate(L/min)
Port Size Sectional area(mm)
RV5211-M5M RV5211-06M RV5221-06M RV5212-M5M RV5212-06M RV5222-06M RV5312-M5M RV5312-06M RV5322-06M
M5
G1/8
5/2:5.5(CV=0.31) 5/2:12(CV=0.67) 5/3:5.5(CV=0.28) 5/3:9(CV=0.50)
G1/8 5/2:14(CV=0.78) 5/3:12(CV=0.67)
RV5221-08M RV5222-08M RV5322-08M
RV5231-08M RV5232-08M RV5332-08M
G1/4(Ex.G1/8) 5/2:16(CV=0.89) 5/3:12(CV=0.67)
G1/4
Acting type
Internal pilot
Reset type
Spring reset / Gas reset
Lubrication
Not required
RV5241-15M RV5242-15M RV5342-15M
G3/8
G1/2
Flow Rate(L/min)
5/2:50(CV=2.79) 5/2:50(CV=2.79) 5/3:30(CV=1.67) 5/3:30(CV=1.67)
0.15~0.8
Guaranteed Pressure(MPa)
1.2 -20~70(No freezing)
Working temperature(℃)
Flow Rate(L/min)
Internal Structure Single Air Control
Double Air Control
DC:2.8W ; AC:3.0VA
2
R V 5221: M:208 RV5222: M:306 RV5322: M:349
Rear Cover Filter Piston Spring Manual Override Back Seat Spring Seat C type buckle
8 3
4
5
6
7
8
9 10
11
12 13
<0.05 R V 5211: M:113 RV5212: M:176 RV5312: M:186
O ring
7
5/2:5 cycles/s;5/3:3 cycles/s
Activate time(S)
11
5 6
IP65(DIN40050)
Protective Class Max. acting frequency
9
4
Class F
Insulation Class
10
2 3
DC:3.0W ; AC:4.0VA
R V 5231: M:300 RV5232: M:409 RV5332: M:459
R V 5241: M:533 RV5242: M:666 RV5342: M:755
15
12
14
13 5/3 Ways Solenoid Valve
14 15 16 17 16
17 18
Part Name
Connector Fixing Nut Coil Pilot Units Plate Piston Pilot Seat Valve Body Spool
1
1
-15%~10%
Voltage Range
Flow Rate(L/min)
No.
Working pressure(MPa)
Weight(g)
G3/8(Ex.G1/4)
5/2:25(CV=1.40) 5/2:30(CV=1.68) 5/3:18(CV=1.00) 5/3:18(CV=1.00)
RV5241-10M RV5242-10M RV5342-10M
Clean air(After 40 μm filteration )
Working medium
Power Consumption
RV5231-10M RV5232-10M RV5332-10M
Working Pressure(MPa)
Model
N4R251 - 10、RV5241 - 10 N4R251 - 15、RV5241 - 15
N3R251 - 10、RV5231 - 10
Working Pressure(MPa)
N2R251 - 08、RV5221 - 08
Working Pressure(MPa)
1:1Series 2:2Series 3:3Series 4:4Series
Controls Initial Status
Working Pressure(MPa)
5 : 5 ways RV(Solenoid valve) RVA(Air control valve )
Valve Body ID Code
Working Pressure(MPa)
Positions
Working Pressure(MPa)
Ways
Series No.
N1R251 - 06、RV5211 - 06
Working Pressure(MPa)
Standard Solenoid Valve
18
Material
Engineered plastics POM Brass+Thermoset Resin Pure iron+Brass +Stainless Steel
Carton Steel POM
Engineered plastics Aluminum Alloy Aluminum Alloy NBR
Engineered plastics High Molecular Material
Engineered plastics Stainless Steel
Engineered plastics Aluminum Alloy Aluminum Alloy
65Mn
RV Series NAMUR Solenoid Valve(5/2,5/3 way) 2.47
V Series Standard/N Series Low Power NAMUR Solenoid Valve(5/2 way) V5211M/V5212M Series
RV Series
2.48
V5211M
Main Dimension Single Solenoid Valve DIN Type
Flying Lead Type
V5212M
Manual Override
Low Power Solenoid Valve Series No. Valve body ID Code Positions size
2
1 : 1 series 2 : 2 series 3 : 3 series 4 : 4 series
N Depth
(mm) Model/Sign
A
B
C
D
E
F
G
G1
H
RV5211-M5M RV5211-06M RV5221-06M RV5221-08M RV5231-08M RV5231-10M RV5241-10M RV5241-15M
22.3 1.5 13.6 18 21.2 22 14 M5 M5 22.3 1.5 13.6 18 21.2 22 14 G1/8 G1/8 23.5 1.5 17.6 22 21.7 29 20 G1/8 G1/8 23.5 1.5 17.6 22 21.7 29 20 G1/4 G1/8 32.1 1.5 19.5 27 28 32 24 G1/4 G1/4 32.1 1.5 19.5 27 28 32 24 G3/8 G1/4 38.8 1.8 21.8 34 40.5 41 33 G3/8 G3/8 38.8 1.8 21.8 34 40.5 41 33 G1/2 G1/2 Note: N series energy saving solenoid valve have same sizes as above table.
Double Solenoid Valve
J
O
P
Q
R
S
T
W
18.5 18.5 23 23 24 24 36.5 36.5
3.3 3.3 4.3 4.3 5.2 5.2 6 6
27 27 35 35 40 40 50 50
55.2 55.2 66.7 66.7 69.2 69.2 74.2 74.2
33.9 33.9 40.2 40.2 40.2 40.2 40.2 40.2
17.9 17.9 17 17 21.6 21.6 25.5 25.5
27.2 28 36 36 45 45 63 63
31.5 31.5 35 35 44.1 44.1 57 57
103.1 103.1 120.7 120.7 139.3 139.3 168.7 168.7
5/3 Ways Solenoid Valve
DIN type
E MC
Flying Lead Type
E MC
E MC
E MC
DIN Type
I
RV5212-M5M RV5212-06M RV5222-06M RV5222-08M RV5232-08M RV5232-10M RV5242-10M RV5242-15M
—
1 : Single control 2 : Double controls
5 : 5 ways
Port Size
M5 : 06 : 08 : 10 : 15 :
Valve Type
Voltage
Connection Mode
Cover Color —
Thread Type
M5 M : NAMUR type Blank: DIN connector Blank: G F: Flying leads P: PT 1/8" T: NPT 1/4" E1:AC110V Blank: Brown translucent 3/8" J: Colorless and translucent E2:AC220V 1/2" E4:DC24V
Order Example: V series solenoid valve, 5/2 way, 1 series valve body, double control, port size 1/8", NAMUR valve type, low power coil, AC220V, flying leads coil, black color valve, G thread, ERP code is: N1M251-06ME2F. Note: Low power type with white valve body
Port size Model/Sign
2 : 2 positions
Controls
M: Standard armature +Low power coil
Model Flying Lead Type
Ways
N1M251-M5 N1M252-M5
N1M251-06 N1M252-06
M5
G1/8
N2M251-06 N2M252-06
N2M251-08 N2M252-08
N3M251-08 N3M252-08
N3M251-10 N3M252-10
N4M251-10 N4M252-10
N4M251-15 N4M252-15
G1/8
G1/4(Ex.G1/8)
G1/4
G3/8(Ex.G1/4)
G3/8
G1/2
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
W1
143.2 143.2 171.4 171.4 190.4 190.4 223.4 223.4
Model/Sign
W2
RV5312-M5M RV5312-06M RV5322-06M RV5322-08M RV5332-08M RV5332-10M RV5342-10M RV5342-15M
158.2 158.2 190.4 190.4 209.4 209.4 244.4 244.4
2 Sectional area(mm ) 5.5(CV=0.31) 12(CV=0.67)
Working medium
Clean air(After 40μm filteration)
Acting type
Pilot type
Lubrication
Not required
Working pressure(MPa)
0.15~0.8
Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing) -15%~10%
Voltage range Power consumption
DC:1.0W ; AC:1.0VA
DC:0.7W
Insulation class
Class F
Protective class
IP65(DIN40050)
Max. acting frequency
5 Cycles/s <0.05
Activate time(S) Weight(g)
N1M251-M: 113 N1M252-M: 176
N2M251-M: 208 N2M252-M: 306
N3M251-M: 300 N3M252-M: 409
N4M251-M: 533 N4M252-M: 666
2
V Series Standard/N Series Low Power NAMUR Solenoid Valve(5/2 way)
V Series Standard/N Series Low Power NAMUR Solenoid Valve(5/2 way)
V5211M/V5212M Series
2.49
V5211M/V5212M Series
2.50
Internal Structure Single Solenoid Valve
Standard Solenoid Valve Series No. Ways Positions Valve Body Controls Size V
2 : 2 positions 5 : 5 ways 1 : 1 series 2 : 2 series 3 : 3 series 4 : 4 series
—
Port Size Valve Type
M5:M5 1 : Single control 06:1/8" 2 : Double controls 08:1/4" 10:3/8" 15:1/2"
Voltage
ID Code
Blank: Standard type A: Amisco coil
Valve — Thread Type Color
Cover Color
Connection Mode
E1:AC110V E2:AC220V E3:AC380V M : NAMUR type E4:DC24V E5:DC12V
E6:AC36V E7:AC24V E8:DC110V E9:DC48V E10:DC36V
NO.
Part Name
Material
1
Connector
Engineered plastics
Blank: G P: PT T: NPT
Blank: DIN connector F: Flying leads Blank:Black W:White
Blank: Brown translucent J: Colorless and translucent
Double Solenoid Valve
Order Example: V series solenoid valve, 5/2 way, 1 series valve body, double control, port size 1/8", NAMUR valve type, standard coil, AC220V, flying leads coil, black color valve, G thread, ERP code is: V5212-06ME2F.
2 Model No. Port size
V5211-M5M V5212-M5M
V5211-06M V5212-06M
V5221-06M V5222-06M
V5221-08M V5222-08M
V5231-08M V5232-08M
V5231-10M V5232-10M
V5241-10M V5242-10M
V5241-15M V5242-15M
M5
G1/8
G1/8
G1/4
G1/4
G3/8
G3/8
G1/2
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
2 Sectional area(mm ) 5.5(CV=0.31) 12(CV=0.67)
Working medium
14(CV=0.78)
Clean air(After 40μm filteration)
Acting type
Pilot type
Lubrication
Not required
2
Nut
POM+Carbon steel
3
Coil
Cu
4
Pilot units
5
Plate
6
Piston
POM
7
Screw
Carbon steel
8
Carbon steel
Valve body
Aluminum alloy
9
Spool
Aluminum alloy
10
O-ring
HNBR
11
Spring
Stainless steel
12
Rear cover
13
Screw Manual override
14
Single Solenoid Valve
Zinc alloy Carbon steel Cu
Double Solenoid Valve
DIN Type
Flying Leads Type
0.15~0.8
Working pressure(MPa) Guaranteed pressure(MPa)
1.2
Working temperature(℃)
-5~60(No freezing) -15%~10%
Voltage range Power consumption
DC:1.0W ; AC:1.0VA
DC:0.7W
Insulation class
Class F
Protective class
IP65(DIN40050)
Manual override
5 Cycles/s
Max. acting frequency
<0.05
Activate time(S) V5211-M: 113 V5212-M: 176
Weight(g)
V5221-M: 208 V5222-M: 306
V5231-M: 300 V5232-M: 409
V5241-M: 533 V5242-M: 666 2-ΦGdepG1
Flow Chart N3M251 - 10M、V5231 - 10M
Working Pressure (MPa)
N2M251 - 08M、V5221 - 08M
Working Pressure (MPa)
Working Pressure (MPa)
N1M251 - 06M、V5211 - 06M
(mm)
400
Flow Rate (L/min)
Flow Rate (L/min)
800
1200
1600
2000
2400
Flow Rate (L/min)
Model\Sign
A
B
C
D
E
F
G
G1
H
I
J
O
P
Q
R
S
T
W
W1*
V5211-M5M V5211-06M V5221-06M V5221-08M V5231-08M V5231-10M V5241-10M V5241-15M
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
M5 G1/8 G1/8 G1/8 G1/4 G1/4 G3/8 G1/2
14 14 20 20 24 24 33 33
22 22 29 29 32 32 41 41
21.2 21.2 21.7 21.7 28 28 40.5 40.5
18 18 22 22 27 27 34 34
13.6 13.6 17.6 17.6 19.5 19.5 21.8 21.8
1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8
19 19 20 20 28 28 39 39
18.5 18.5 23 23 24 24 36 36
3.3 3.3 4.3 4.3 5.2 5.2 6 6
27 27 35 35 40 40 50 50
54.8 54.8 67.5 67.5 70 70 75 75
32.8 32.8 40.5 40.5 40.5 40.5 40.5 40.5
14.5 14.2 14.2 14.2 17.5 17.5 25.5 25.5
27.5 28 35 35 45 45 63 63
28.2 28.2 31.7 31.7 40 40 57 57
97 97 117 117 135 135 168 168
138 138 171 171 190 190 221 221
Note: The dimensions of NO type and NC type are same, the dimensions of N series and V series are same.
2
RV Series NAMUR Air Control Valve(3/2, 5/2, 5/3 Way) 2.51
RV Series NAMUR Air Control Valve(3/2, 5/2, 5/3 Way)
RVA Series
RVA Series
2.52
RVA Series 3 / 2 way
RVA3211-M5M RVA3211-06M RVA3221-06M RVA3221-08M RVA3231-08M RVA3231-10M RVA3241-10M RVA3241-15M RVA3212-M5M RVA3212-06M RVA3222-06M RVA3222-08M RVA3232-08M RVA3232-10M RVA3242-10M RVA3242-15M
Model
(1,2,3 Series Single Air Control Valve)
Port Size (4 Series Single Air control Valve)
Sectional area(mm)
M5
G1/8
G1/8
G1/4
G1/4
G3/8
G3/8
G1/2
5.5(CV=0.31)
12(CV=0.67)
14(CV=0.78)
16(CV=0.89)
25(CV=1.40)
30(CV=1.68)
50(CV=2.79)
50(CV=2.79)
Working Medium Acting type
RVA Series 5 / 2 , 5 / 3 way
Outer air control
Reset type (4 Series Single Air Control Valve)
(1,2,3 Series Single Air Control Valve)
RP
RP
Air return
Lubrication Working Pressure(MPa) RP
RP
Spring return+Air return
Not Required 0.15~0.8
Guatranteed Pressure(MPa)
1.2
Working Temperature(℃)
-20~70(No freezing) 5 Cycles/s
Max.acting frequnency RP
Clean air(After 40μm filteration)
RP
2
2
Internal Structure 3 / 2 Way Series No. RVA
Ways
Positions
3:3 ways 5:5 ways
2:2 positions 3:3 positions
Valve body ID code
Controls
Initial Status
—
Port size
1:1Series 2:2Series 3:3Series 4:4Series
1 series 3/2 Way Blank:Normal close M5:M5 06:1/8" H:Normal open 2 series 5/3 Way 06:1/8" C: Center close 08:1/4" 1: Single control P: Center pressure 2: Double control E: Center exhaust (Only for 5/3 ways)
Single Air Control(N.C)
Reset Type —Thread Type
Single Air Control(N.O)
Bland:G P : PT T : NPT
3 series 08:1/4" 10:3/8"
No.
4 series 10:3/8" Blank: Spring return 15:1/2" (Apply to 4 series single control valve) Q: Air return (Apply to 1,2,3 series single control valve)
1 2
Order Example: Double Air Control
RV series air control valve , 3 / 2 ways , 2 series valve body size , normal close, single control , 1/4 " port size , gas reset, NUMAR type , PT thread, ERP code is RVA3221-08QM-P
3
Nut
4
RVA5211-M5M RVA5211-06M RVA5221-06M RVA5221-08M RVA5231-08M RVA5231-10M RVA5241-10M RVA5241-15M RVA5212-M5M RVA5212-06M RVA5222-06M RVA5222-08M RVA5232-08M RVA5232-10M RVA5242-10M RVA5242-15M RVA5312-M5M RVA5312-06M RVA5322-06M RVA5322-08M RVA5332-08M RVA5332-10M RVA5342-10M RVA5342-15M
Port Size
M5
G1/8
G1/8
Sectional area(mm) 2P:5.5(CV=0.31) 2P:12(CV=0.67) 2P:14(CV=0.78) 3P:5.5(CV=0.28) 3P:9(CV=0.50)
Working Medium Acting type Reset type
3P:12(CV=0.67)
G1/4(Exhaust G1/8) 2P:16(CV=0.89) 3P:12(CV=0.67)
G1/4 2P:25(CV=1.40) 3P:18(CV=1.00)
Air return
Guatranteed Pressure(MPa)
1.2
Working Temperature(℃)
-20~70(No freezing)
Note: 2P:2 Position 3P:3 Position
2P:30(CV=1.68) 2P:50(CV=2.79) 3P:18(CV=1.00) 3P:30(CV=1.67)
G1/2
Single Air Control
5 6
O-ring
7
Piston Rear cover
Zinc Alloy
Part Name
Material
F Class
Aluminum alloy NBR POM
Double Air Control
2P:50(CV=2.79) 3P:30(CV=1.67)
No. 1 2
Spring return+Air return
3 4
0.15~0.8
2 Positon:5 Cycles/s;3 Positon:3 Cycles/s
Carbon steel Aluminum alloy
5/2 ,5/3 Way
Outer air control Not Required
Insulation Class
G3/8
Clean air(After 40μm filteration)
Lubrication Working Pressure(MPa)
Max.acting frequnency
G3/8(Exhaust G1/4)
Material
Valve body Spool
8
Model
Part Name
Air Control Cover Aluminum alloy POM Piston
3 Positions
5 6 7 8 9 10 11
Air Control Cover Aluminum alloy POM Piston Nut Carbon steel Valve body Aluminum alloy Spool Aluminum alloy O-ring
NBR
POM Piston Zinc Alloy Rear cover Aluminum alloy Back seat Spring seat Aluminum alloy 65Mn C type buckle
V Series NAMUR Air Control Valve(3/2,5/2,5/3 Way)
RV Series NAMUR Air Control Valve(3/2, 5/2, 5/3 Way) 2.53
VAM Series 3RV /2, 5/2, 5/3 Series
RVA Series
Main Dimension 3 / 2 Way
2.54
VAM Series 3 / 2
Single Air Control
Double Air Control
VAM Series 5 / 2 , 5 / 3
Depth
VA5231-08M
VA3231-08M
2
2 Model/Sign
RVA3211-M5QM RVA3211-06QM RVA3221-06QM RVA3221-08QM RVA3231-08QM RVA3231-10QM RVA3241-10M RVA3241-15M
A
B
C
D
E
F
K
L
M
N
O
P
R
S
W
W1*
M5 G1/8 G1/8 G1/4 G1/4 G3/8 G3/8 G1/2
13.6 13.6 17.6 17.6 19.5 19.5 21.8 21.8
1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8
19 19 21 21 23 23 23 23
29 29 31 31 42.1 42.1 45.5 45.5
18 18 22 22 27 27 34 34
3.3 3.3 4.3 4.3 5.2 5.2 6 6
16 16 15.5 15.5 18.1 18.1 17.5 17.5
14 14 20 20 24 24 33 33
22 22 29 29 32 32 41 41
27 27 35 35 40 40 50 50
G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8
21.9 23 23.5 25.5 31.1 30.1 30 32
14.2 14 18 18 21 23 31.5 31.5
67 67 76 76 94.6 94.6 103 103
76 76 87 87 106 106 116 116
Note: The dimensions of N.O type and N.C type are same, w1 is double control direction valve's dimensions.
Series No.
Ways
Positions
VA
3:3 ways 5:5 ways
2:2 positions 3:3 positions
Valve B ody Size
Controls
Original Status —
Valve type
Port Size
Valve color —
1 Series 3 Series M: NAMUR type Blank:Black 08:1/4" M5:M5 W:White 06:1/8" 10:3/8"
1 : Single control 2:Double control Blank: NC 1:1 Series H:NO 2:2 Series C: Center close 3:3 Series P: Center pressure 4:4 Series E: Center exhaust (Only for 5/3 way)
Thread Type
Blank: G P: PT T: NPT
2 Series 4 Series 06:1/8" 10:3/8" 08:1/4" 15:1/2"
Order Example: V series air control valve, 3/2 way, 2 series valve body, NC type, single control, 1/4" port size, NAMUR valve type,white valve body, PT thread, ERP code is : VA3221-08MW-P
5/2 ,5/2 Way Single Air Control
3 Positions
Double Air Control
Depth
VA3211/VA3212-M5
VA3211/VA3212-06
M5 2 5.5mm (Cv=0.31)
1/8 2 12.0mm (Cv=0.67)
Pressure range
VA3221/VA3222-06 Air (40um filter) The external air control In=Out=1/8 2 14.0mm (Cv=0.78)
VA3221/VA3222-08
VA3231/VA3232-08
In=Out=1/4 2 16.0mm (Cv=0.89)
In=Out=1/4 25.0mm2(Cv=1.39)
VA5211/VA5212-06
VA5322C/P/E-06
In=Out=1/8 12.0mm2(Cv=0.67)
In=Out=1/8 9.0mm2(Cv=0.50)
0.15~0.8Mpa(21~114psi) 1.5Mpa(215psi) -20~70
Guarantee pressure Body material
5
VA3231/VA3232-10
Model/Sign
A
B
C
D
E
F
G
G1
H
I
J
M
O
RVA5211-M5QM M5 27 19 3.3 22.3 18.5 1.5 13.6 18 24.5 22 14 M5 RVA5211-06QM G1/8 G1/8 27 19 3.3 22.3 18.5 1.5 13.6 18 24.5 22 14 RVA5221-06QM G1/8 G1/8 35 21 4.3 23 23.5 1.5 17.6 22 25 29 20 RVA5221-08QM G1/4 G1/8 35 21 4.3 23 23.5 1.5 17.6 22 25 29 20 RVA5231-08QM G1/4 G1/4 40 23 5.2 24 32.1 1.5 19.6 27 32.1 32 24 RVA5231-10QM G3/8 G1/4 40 23 5.2 24 32.1 1.5 19.6 27 32.1 32 24 RVA5241-10M 50 23 6 38.8 36.5 1.8 21.8 34 40.5 41 33 G3/8 G3/8 RVA5241-15M 50 23 6 38.8 36.5 1.8 21.8 34 40.5 41 33 G1/2 G1/2 Note:W1 is double control direction valve's dimensions, W2 is three position air control valve's demensions.
P
R
S
T
W
W1*
W2*
G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8 G1/8
17.9 17.5 17 17 21.6 21.6 25.5 25.5
27.2 28 36 36 45 45 63 63
31.5 31.5 35 35 44.1 44.1 57 57
72 72 81 81 99.6 99.6 127 127
81 81 92 92 111 111 140 140
96 96 111 111 130 130 161 161
In=Out=3/8 30.0mm2(Cv=1.67)
VA5211/VA5212-M5
In=Out=M5 5.5mm2(Cv=0.31)
Pressure range Guarantee pressure
VA5322C/P/E-M5 Air (40um filter) The external air control In=Out=M5 5.0mm2(Cv=0.28) 0.15~0.8Mpa(21~114psi) 1.5Mpa(215psi) -20~70
Body material 5 Note: The technical data of NO type and NC type are same.
3
5
3
V Series NAMUR Air Control Valve(3/2,5/2,5/3 Way) VAM Series 3/2, 5/2, 5/3
VAM Series 3/2, 5/2, 5/3
VA3211M
VA5231M
VA3221M
2-Φ19.5 depth 1.5
depth
2.56
VA5241M
2-Φ21.8 depth 1.8
2.55
V Series NAMUR Air Control Valve(3/2,5/2,5/3 Way)
10
VA3241M
VA5212M
2-Φ13.6 depth 1.5
VA5222M
2-Φ17.6 depth 1.5
Φ21.8 depth 1.8
10
17.5
27
Φ19.5 depth 1.5
VA5221M
VA5211M
VA5232M
2-Φ19.5 depth 1.5
21.7
14.2
31.7 6.7
21.2
14.7 14.2
6.7
28.2
20.2
2-Φ17.6 depth 1.5
2-Φ13.6 depth 1.5
VA5242M
2-Φ21.8 depth 1.8
40.5
25.5
57
22.2
12.2
38.75
6.7
12.7
6.7
18.45 19.7
25.7
VA3231M
18.95
2
27.7
depth
2
V Series NAMUR Air Control Valveďź&#x2C6;3/2,5/2,5/3 Wayďź&#x2030; 2.57
SR Integrated Manifold (Plug-in Type)
VAM Series 3/2, 5/2, 5/3
VA5312M
2-ÎŚ13.6 depth 1.5
SR Series
2.58
VA5322M
2-ÎŚ17.6 depth 1.5
2
2
SR Valve Group:
VA5332M
VA5342M
Valve Body Size
Series No.
S: Common type SN: Low power type
ID code
3:3valves 4:4valves 5:5valves 6:6valves 7:7valves 8:8valves
2-ÎŚ21.8 depth 1.8
Controls â&#x20AC;&#x201D; Port Size S: Single coil
R: RV series valve
1: 1 series 2: 2 series 2-ÎŚ19.5 depth 1.5
Valve Numbers
M5: M5 06: 1/8" 08: 1/4"
Voltage
Coil Type â&#x20AC;&#x201D; Thread Type
Blankďź&#x161;Plug-in type E4:DC24V E5:DC12V
9:9valves 10:10valves 11:11valves 12:12valves 13:13valves 14:14valves
Blank: G P: PT T: NPT
ďź&#x2C6;Only DC24V for low power typeďź&#x2030;
:Order Example: SR series integrated manifold, 1 series valve body, RV series valve, 6 valves, single control, 1/8 port size, voltage DC24V, plug-in type coil, G thread, no accessory, ERP code is: S1R6S-06E4
SR Connecting Cable Connector
â&#x20AC;&#x201D;
D15: 15 pins D-sub Connector
Number of cable core 15:15 cores ďź&#x2C6;14 stations include below 14 ďź&#x2030;
â&#x20AC;&#x201D;
Length of cable
1M: 1 meter 2M: 2 meter 3M: 3 meter â&#x20AC;Śâ&#x20AC;Ś Note: Length can be customized
Mounting Type
Blank: No accessory D: Din guide rail clip with 1 meter din guide rail DO: Din guide rail clip without din guide rail ďź&#x2C6;Din guide rail packed separatlyďź&#x2030;
SR Integrated Manifold (Plug-in Type) 2.59
SR Integrated Manifold (Plug-in Type)
SR Series
SR Series
Dimensions
2.60
Installation
S1R
SR Series integrated manifold( plug-in type) wiring diagram:
DIN Din guide rail clip (SIR-020) M5(Ground protection mounting hole)
DIN Din guide rail (SIR-021)
SH
SH
SH
(106)
SH
(106)
PU
PU
PU
PU
SH
SH
PU
PU
Hexagon socket cap screw (GSA4X30B)
1
5
25
1
7
20
49
19
6
9
5
29
Valve number
4
2
3
4
5
6
7
8
9 10 1 1 12 13 14
8
COM
3
4 -Ø 4.5 Through hole
2
9 01 11 21 31 41 51
2
2
M
6-1/4"(2 Sides) 7.5
L
(8.5)
(54.7)
*The hole positions of Din guide rail can't be specified, its may change randomly.
Connecting cable dimension and wiring diagram: (mm) S1R9S
L
76
95
114
133
152
171
M
66
85
104
123
142
161
S1R10S
S1R11S
S1R12S
S1R13S
S1R14S
190
209
228
247
266
285
180
199
218
234
256
275
(40.3)
L
16
Ø 10
S1R8S
4
40
S1R7S
5
S1R6S
6
S1R5S
7
S1R4S
8
S1R3S
3
51 41 31 21 11 01
Sign/Model
2
9 1
S2R
Pin number DIN Din guide rail clip (SIR-020)
M5(Ground protection mounting hole)
(123.8)
Relative valve number
Black/ White
9
9
2
2
Beige
10
10
Dark brown/white
3
3
Transparent
11
11
Black
4
4
Grey
12
12
Red
5
5
Dark brown
13
13
Purple
6
6
Orange
14
14
7
7
White
15
COM
8
8
Blue
SH
SH
SH
SH
SH
Pin number
1
Relative valve number
PU
PU
PU
PU
PU
SH
25
21 9
19.75
30.25
51.5
5
Hexagon socket cap screw (GSA4X30B)
PU
(123.8)
DIN Din guide rail (SIR-021)
Cable colour
1
4 -Ø 4.5 Through hole
6-1/4"(2 Sides) M
7.5 (8.5)
(64)
L
*The hole positions of Din guide rail can't be specified, its may change randomly.
(mm) Sign/Model
S2R3S
L
92
115
M
80
103
S2R4S
S2R5S
S2R6S
S2R7S
S2R8S
S2R9S
S2R10S
138
161
126
149
S2R11S
S2R12S
S2R13S
S2R14S
184
207
230
253
276
299
322
345
172
195
218
241
264
287
310
333
Cable colour Blue/white
Pink Grey/White
L Series Hand Pull Valve (3/2, 5/2 Way) 2.61
L Series Hand Pull Valve (3/2, 5/2 Way)
L Series
L Series
L522-08 14.7
2 Series No.
Ways
Positions
L 3:3 ways 5:5 ways
Valve Body Original Status — size
2:2 positions 1:1 Series 3:3 positions 2:2 Series 3:3 Series 4:4 Series
Port Size
Reset
Valve Color —
1 Series 3 Series Blank:Manual reset Blank: Black 06:1/8" 08:1/4" S:Spring return W: White 10:3/8" Blank: NC H:NO 2 Series 4 Series C: Center close 06:1/8" 10:3/8" P: Center pressure 08:1/4" 15:1/2" E: Center exhaust (Only for 5/3 way)
Thread Type
Blank: G P: PT T: NPT
24 20.5
18.45 16.45
0 111.3 111.3 105.7 105.7
31.5 29.25
31.5 29.8
141 136 87.5
141 136 87.5
31
31
45
45
25.5
25.5
57 165 160 111.5
84.5 80.5 44.7
89.7 54.7
89.7 54.7
15.7
17.7
17.7
22.7
0 27.7
27.7
14.2
14.2
14.2
28.2 95.5 91.5 55.7
31.7
31.7
62.7
62.7
57 165 160 111.5
21.2
21.7
21.7
43
43
22.7 18
21.7 20
39
39
0
Order Example: L series hand pull valve, 3/2 way, 2 series valve body, NC type, 1/4" port size, manual reset, black valve body, G thread, ERP code is: L322-08
G1/8
126.3 126.3 120.7 120.7
40
(MPa) (MPa)
0~0.8 1.2 -5~60
3 20.2
2.62
2
H Series Hand Push Valve (5/2, 5/3 Way) 2.63
H Series Hand Push Valve (5/2, 5/3 Way)
H Series
H Series
2.64
H522-08
2
2 Series No.
Ways
Positions
H 3:3 ways 5:5 ways
Valve Body Size
2:2 positions 1:1 Series 3:3 positions 2:2 Series 3:3 Series 4:4 Series
Original Status
Blank: NC H:NO C: Center close P: Center pressure E: Center exhaust (Only for 5/3 way)
—
Port Size
Reset
—
1 Series 3 Series Blank:Manual reset M5:M5 08:1/4" S:Spring return 06:1/8" 10:3/8" 2 Series 06:1/8" 08:1/4"
Thread Type
Blank: G P: PT T: NPT
4 Series 10:3/8" 15:1/2"
Order Example: H series hand push valve, 3/2 way, 2 series valve body, NC type, 1/4" port size, manual reset, black valve body, G thread, ERP code is: H322-08
G1/8 G1/4 G3/8 G1/2
6.7 6.7 7.5 10
38.7 48.7 57.5 80
23.7 28.7 32.5 45
58.7 68.7 77.7 108
27 35 40 50
19 24 28 36
Φ3 . 1 Φ4 . 3 Φ4 . 3 Φ5 . 5
14 20 24 28
83.8 90 99 . 3 105.8
16 22 . 5 24 31 . 5
18 22 27 34
2 0 2 0
40
(MPa) (MPa)
0~0.8 1.2 -5~60
28 35 45 63
G1/8 G1/8 G1/4 G1/2
6.7 6.7 7.5 10
28 . 2 31 . 7 40 57
49 . 7 56 . 7 72 . 5 104
69 . 7 76 . 7 92 . 5 132
27 35 40 50
19 24 28 36
Φ3 . 3 Φ4 . 3 Φ4 . 3 Φ5 . 5
14 20 24 28
83.8 91.3 96 . 5 105
16 20 24 36
G1/8 G1/4 G3/8 G1/2
3 3 4 4
18 22 27 34
H Series Hand Push Valve (5/2, 5/3 Way) 2.65
M Series Mechanical Valve (3/2, 5/2 Way)
H Series
M Series
2.66
3 / 2 way
5 / 2 way
M52-S3
2
28 35 45 63
G1/8 G1/8 G1/4 G1/2
6.7 6.7 7.5 10
28 . 2 31 . 7 40 57
49 . 7 56 . 7 72 . 5 104
69 . 7 76 . 7 92 . 5 132
19 24 28 36
27 35 40 50
Φ3 . 3 Φ4 . 3 Φ4 . 3 Φ5 . 5
87.5 90 96 . 5 105.8
14 20 24 28
16 20 24 36
G1/8 G1/4 G3/8 G1/2
3 3 4 4
18 22 27 34
2 Series No.
MV MJ M
Ways
Positions
3: 3 ways 2: 2 position 5: 5 ways
—
Port Size
06:1/8" 08:1/4"
Button Type
Thread Type
—
Blank: No button S1B: The button with arrow mark(Black) S2: Roller type S3R : Button with '' Reset '' mark(Red) S4G : Concave button(Green) S5R : Flat button(Red) S6R : Mushroom head button(Red) S6B : Mushroom head button(Black) Note: S1 and S3 with manual return, Others with spring return.
Blank:G P :PT T :NPT
Order Example: M series mechanical valve, 3/2 way, 1/8" port size, with black button with arrow mark, G thread, ERP code is: M32-06S1B Note: Button mechanical valve assembly comprising: a Button component, the mounting bracket, under mounting brackets and mounting screws.
28 35 44 63
G1/8 G1/8 G1/4 G1/2
6.5 6.5 7.5 10
28 . 2 31 . 7 40 57
49 . 7 56 . 7 72 . 5 104
64 . 5 75 . 5 91 . 5 124
84 . 7 97.7 113 . 5 154
27 35 40 50
19 24 28 36
Φ3 . 3 Φ4 . 3 Φ4 . 3 Φ5 . 5
14 20 24 28
92 . 5 94.2 100 109.6
16 20 24 36
G1/8 G1/4 G3/8 G1/2
3 3 4 4
18 22 27 34
MS32-06
MJ32-08
M32-08
40
(MPa) (MPa)
28 36 44 63
G1/8 G1/8 G1/4 G1/2
6.5 6.5 7.5 10
28 . 2 31 . 7 40 57
49 . 7 56 . 7 72 . 5 104
84.5 97 113 . 5 152
27 35 40 50
19 24 28 36
Φ3 . 3 Φ4 . 3 Φ4 . 3 Φ5 . 5
14 20 24 28
9 4. 5 95.5 100 108
16 20 24 36
G1/8 G1/4 G3/8 G1/2
3 3 4 4
18 22 27 34
64 . 5 75 . 5 91 . 5 124
0~0.8 1.2 -5~60
M52-08
M Series Mechanical Valve (3/2, 5/2 Way) 2.67
M Series Mechanical Valve (3/2, 5/2 Way)
M Series
M Series
2.68
2-Φ
59
20
10
MJ32 Series
5.5
29
2
2 MJ32-08S2
MJ32-08S1
MJ32-08S3
M32 Series
MJ32-08S4
MJ32-08S5
MJ32-08S6
3.6
3-G1/8
24
24
M32-08S1
Mv32 Series
M32-08S2
M32-08S3
M52 Series
M32-08S4
M32-08S5
M32-08S6
M32-08
3.6
4.6
MV32-06S1
MV32-06S2
MV32-06S3
MV32-06S4
MV32-06S5
MV32-06S6
06:21 . 5 08:20.5
13.3
06:20 08:22
84 . 5
3-G1/8
4
M52-08S1
M52-08S2
M52-08S3
M52-08S4
M52-08S5
M52-08S6
M52-08
F Series Foot Valve (3/2, 4/2, 5/2 Way) 2.69
F Series Foot Valve (3/2, 4/2, 5/2 Way)
F Series
F Series
2.70
F522-08
2
2 Series No.
Ways
Positions
F: F series foot valve
3: 3 ways 4: 4 ways 5: 5 ways
2: 2 position
Valve Body Size
Type
2: 2 series Blank: No cover C:With cover
—
Port Size 06:1/8" 08:1/4"
Valve Type
—
Thread Type
Blank: G P: PT Blank: Basic type T: NPT L: With lock N: New valve body LB: With lock,big valve body
Order Example: F series foot valve, 5/2 way, 2 series valve body, without cover, 1/4" port size, with lock, G thread, ERP code is: F522-08L
40
(MPa) Max pressure (MPa)
0~0.8 1.2 -5~60 1/8", 1/4"
F Series Foot Valve (3/2, 4/2, 5/2 Way) 2.71
R Series Hand Switch Valve (4/3 Way)
F Series
R Series
2.72
4/3 way
R432-08
2
2 Series No.
Ways
M:M series U:U series R:R series MR:MR series
4: 4 ways
Positions
Valve Body Size
3: Three position 2 : 2 series
—
Port Size
—
M432/U432:08:1/4" R432/MR432:08 : 1/4" 10:3/8" 15:1/2"
Thread Type
Blank: G P: PT T: NPT
Order Example: R series hand switch valve, 4/3 way, 2 series valve body, G thread, ERP code is: R432-08
40
F522C-06LB
(MPa) 3-G1/8''
(MPa)
0~1.0 1.5 -5~60 1/4", 3/8", 1/2"
R Series Hand Switch Valve (4/3 Way) 2.73
Flow Control Valve (Precise Type) QSC Series
R Series
2.74
105 73
A
P
100
74
22
How to order
2
Series No.
Product Features Port Size -
Thread Type
2
1.Compact structure and high precision
61
2 .Install in several positions to facilitate ,installation and application QSC:Flow control valve (precise type) 49
4-Φ5.5
06:1/8" 08:1/4" 10:3/8" 15:1/2"
Blank:G P :PT T :NPT
3 .Apply to exhaust and cut off flow, widely used for cylinder speed adjustment
Order sample: QSC series flow control valve, 1/4" port size, G thread, the ERP code is QSC-08
138
Specification Model (mm)
88
80.6
Internal Structure
7~145 217
Working Pressure (psi) Guaranteed pressure (psi) Working temperature(℉) Port size
4-Φ6
62.5
62.5
1
62.5 74 156
No.
Clean air(After 40 μm filteration )
Working medium
-5~60℃(-4~158℉)(No freezing) 1/8 1
1/4 1
G、PT、 NPT thread type is optional .
3/8 1
1/2 1
Name
1 2 3 4 5 6 7 8 9
Valve body Diaphragm Throttle body O-ring O-ring Throttle sheath Fixed nut Throttle column Lock nut
10
Adjustment cap
BRE Series Flow Control Valve
Flow Control Valve (Precise Type) 2.75
QSC Series
BRE Series
2.76
Model QSC-06 QSC-10 QSC-15
BRE-08
O
Model
--18 18
8.5 13.3 16.5 16.5
2
2 Series No.
â&#x20AC;&#x201D;
BRE: The large flow control valve
Flow Chart
Port Size
06ï¼&#x161;1/8ï¼&#x201A; 08ï¼&#x161;1/4ï¼&#x201A; 10ï¼&#x161;3/8ï¼&#x201A; 15ï¼&#x161;1/2ï¼&#x201A;
â&#x20AC;&#x201D; Thread Type Blank: G P: PT T: NPT
Order Example: 1000 1000
1000 1000
900 900
900 900
Flowï¼&#x2C6;L / minï¼&#x2030;
Flowï¼&#x2C6;L / minï¼&#x2030;
QSC - 08
700 700 600 600 500 500 400 400 300 300
QSC - 06
(MPa)
QSC - 08
700 700 600 600 500 500
QSC - 06
400 400
BRE-06/08/10
300 300
100 100
100 100
00
11
22
33
44
5
6
77
88
9
10 10
11 11
12 12
13 13
14 14
15 16 16 15
17 17
18 18
19 19
00
20 20
00
11
22
33
44
55
ï¼&#x2C6;Nï¼&#x2030; Turns of adjusting nut
77
88
99
10 10
11 11 12 12 13 13
14 14 15 15 16 16 17 17 18 18 19 19
20 20
QSC-10/15 P Flow Chart (Inlet pressure0.6 MPa) QSC-10/15 Aâ&#x2020;&#x2019; Aâ&#x2020;&#x2019;P ( 0.6MPa)
QSC-10/15 Pâ&#x2020;&#x2019;APâ&#x2020;&#x2019;A ( 0.6MPa) Flow Chart (Inlet pressure0.6 MPa) QSC-10/15 22100 100
11800 800
22000 000 QSC - 15
QSC - 15
11900 900
11600 600
11800 800
1200 1200
Flowï¼&#x2C6;L / minï¼&#x2030;
1400 1400
QSC - 10
1000 1000 800 800
600 600
11700 700 1600 1600 QSC - 10
1500 1500 1400 1400 1300 1300 1200 1200 1100 1100
400 400
1000 1000
200 200
00
66
ï¼&#x2C6; Nï¼&#x2030; Turns of adjusting nut
2000 2000
900 900 00
1
22
33
4
55
66
77
ï¼&#x2C6; Nï¼&#x2030;
Turns of adjusting nut
88
99
10 10
11 11
12 12
800 800
BRE-08
BRE-10
0.05~1.0 1.5 -5~60
200 200
200 200
Flowï¼&#x2C6;L / minï¼&#x2030;
(MPa)
800 800
800 800
0 0
BRE-06
BRE series large flow control valve, 1/4" port size, G thread, ERP code is: BRE-08
QSC-06/08 QSC-06/08 Aâ&#x2020;&#x2019;P Aâ&#x2020;&#x2019;P ( 0.6MPa) Flow Chart (Inlet pressure0.6 MPa)
QSC-06/08 A Flow Chart (Inlet pressure0.6 MPa) QSC-06/08Pâ&#x2020;&#x2019; Pâ&#x2020;&#x2019;A ( 0.6MPa)
00
11
22
33
44
55
66
7 7
8 8
ï¼&#x2C6; Nï¼&#x2030; Turns of adjusting nut
9 9
1010
1111
12 12
BRE-06 BRE-08 BRE-10
BRE-15
BRE-15
KKP Series Quick Exhaust Valve
Shuttle Valve QS Series
2.77
KKP Series
2.78
A P1
P2
KKP-08
2
How to order Series No.
-
Product Features
2
Valve provides complete control for the function of your
Port Size - Thread Type
Series No.
—
Port Size
—
Thread Type
pneumatic system. QS:Shuttle valve
06:1/8" 08:1/4"
KKP: Quick exhaust valve
Blank:G P :PT T :NPT
06:1/8" 10:3/8" 08:1/4" 15:1/2"
Blank: G P: PT T: NPT
Order Example: KKP quick exhaust valve. 1/4" port size, G thread, ERP code is: KKP - 08
Order sample: QS series shuttle valve, port size: 1/4", G thread, the ERP code is: QS-08
Internal Structure 1
Specification
2
3
4
A
Model (mm) Working medium
Clean air(After 40 μm filteration )
Working Pressure (psi)
7~116 174
Guaranteed pressure (psi) Working temperature (℉)
P1
P2
No.
Name
1 2 3 4
Valve body Rubber ball End cover O-ring
-5~60℃(-4~158℉)(No freezing)
1/8 1 Port size 1 G、PT、NPT thread type is optional.
1/4 1
40 (MPa)
0.15~0.8 (MPa)
1.2 -5~60
Model
45.5 56 67
38 46.5 54
EA Series One Way Valve 2.79
YHS Series Slide Valve (3/2 Way)
EA Series
YHS Series
EA-10
YHS-08
2.80
YHS-08FF
2
2 Series No.
—
EA: One-way valve
Port Size
06:1/8" 08:1/4" 10:3/8" 15:1/2"
— Thread Type
Series No.
20:3/4" Blank: G 25:1" P: PT 32:11 / 4" T: NPT 40:1-1 / 2" 50:2"
YHS: Slide valve
—
Type
Port Size
—
Thread Type
* Generally do not separate in pneumatic systems use, Usually use and the main valve.Provide a good help to the overall control of the main valve,In order to complete the control function of the whole system.
06: 1/8" 15: 1/2" Blank: G 08: 1/4" 20: 3/4" Blank: Standard type P: PT 10: 3/8" 25: 1" MM: Double male thread type T: NPT FF:Double female thread type MF:One male and the other female type
Order Example: Order Example:
YHS slide valve,1/4" port size, double male thread type, G thread ,ERP code is: YHS - 08MM
EA series one way valve. 1/4" port size, G thread, ERP code is : EA - 08
40
40
0~1.0
(MPa)
1.5
(MPa) (MPa) (MPa)
-5~60
0.05~0.8 1.2 -5~60
Standard type
Out
63 63 81 81 109 109 160 160 160
Double female thread type (FF)
In
One male and the other female thread type (MF)
Out
In
Out
In
Double male thread type(MM)
Out
In
20 32 32 40 45 45
38 58 58 80 85 85
38 58 58 80 85 85
38 58 58 80 85 85
46 68 69 94 101 101
20 26 32 38 46 52
QPC Series Pilot No-returen Valve 2.81
QPC Series
2.82
Note. Z
P
A
Product Features
2 Series
—
QPC
1. 2. 3. 4.
Port Size 08:1/4" 10:3/8" 15:1/2"
2
Can make cylinder stopped in any position, accurate orientation; Prevent cylinder moving after stopped; Can be used for safety loop of presure holding; Can be used special loop。 Accurate positioning
Order Example: QPC series valve, 1/4" port size, ERP code is: QPC-08
Pressure maintenance
Specifications QPC-08
Model Working medium
QPC-10
QPC-15
Clean air(After 40 μm filteration)
Sectional(mm)
24
79
79
0.1~1.0 1.5 -20~70
Working pressure(MPa) Guaranteed pressure(MPa) Working temperture(℃)
Operating Frequency(Times / min) Valve material Port size
60 Nickel plated brass 1/4”
40 Aluminum alloy 3/8”
1/2”
1/8”
Pilot Port Size
Main Deminsion
Q P C -08
Q P C -10
40 Aluminum alloy
Q P C -15
Solenoid Valve USA Manufactured by a high precision CNC machine. Over 20 years experience in solenoid valve and coil manufacturing. Low power coils maintain a lower operating temperature, extending the life cycle and performance of your component. We offer an extensive line of solenoid valves ranging from 1mm-300mm, and can accommodate pressures exceeding 100Bar and temperatures from -100â&#x201E;&#x192; to +250â&#x201E;&#x192; . Fully automated solenoid valve testing system. Fully automated production of the solenoid pilot valves. Our coils are specifically treated to reduce the residual magnetism of the valve.
2-Way Solenoid Valve
2-Way Solenoid Valve
2-Way Valve Series
2-Way Valve Series
Key Points for Installation and Usage
Internal Structure & Categories of Two Way Solenoid Valves
1.Before installing, check if the products are damaged during transportation. Check the technical specifications(working pressure, working temperature, working voltage, etc). 2. Complete cleaning of pipeline is required, in order to remove dust,particles,oil, etc(complete blow via air-blow gun, or empty the front-end
Direct acting solenoid valves utilize a simple structure to provide dependable performance at high frequencies and are available in both normal close style (N.C) and normal open style (N.O). The N.C style is designed to stay closed while the power is off. When the power is on, an electro-magnetic force accumulates in the coil which extends the spring and opens the valve.
piplines completely) 3. Particles in the medium will speed-up the wearing of valve seat and amature, causing leakage or even completely disabling the product. Filter should be installed at the inlet of the valve.40μm air filter element or filter nets of 80-100μm is recommended. And filter element/filter net should be cleaned/replaced regularly. 4. The debris of piple thread and sealing tape shall not get inside the valve when mounting the valve fittings to the pipe. When using sealing tape, do not apply the tape onto the first 1.5-2 thread pitchs.
The diaphragm pilot solenoid valve works with the main valve. When the power is on, electro-magnetic force pulls the pilot valve open. When power is off or disconnected, gravity and spring force function to close the valve. These valves are typically larger with greater working pressure.
5. The coil shall be mounted vertically and upward. The inlet and outlet of the valve should be horizontal(for the inlet/outlet,a tilt angle up to 45 degree is acceptable if mounting space is limited. However, the coil should never be pointed downward). Also, make sure the direction of pipe connection matches the marks on the valve(examples of signs/marks: In/out, or 1/2, In/1(inlet) or other marks like directional arrow(→)
2
6. No external force is allowed on the coil.When the coil is screwed into the pipe, clamp the wrench on the mounting position on the pipe only. 7. Grounding of the pipline is not allowed. Oitherwise, this will cause electrochemical corrosion of the system.
Similar to the diaphragm pilot solenoid, the piston pilot solenoid valve functions in a normal open/normal closed style, but supports even higher pressure and temperatures.
8. Please install overflow valve in pipeline, in order to prevent the accumulation of fluid in the pipe. 9. Do not cover the coil with any thermal insulation material. This will cause the coil overheat and damage the coil. 10. Do not mount the valve in the places that have strong vibration. If this cannot be avoided,please set the arm of force to minimal to avoid resonance.
Applicable Fluid Counterpart Table
11. The diameter of the cable should be larger than 5mm2 . No additional force should be applied to the cable. 12. No Electro-self-sustained oscillation is allowed in the electrical circuit for the valve.
Working Medium Material
Dry Air
Carbon Nitrogen Dioxide
Argon
Oxygen
Hydrogen
Natural Gas*
Pipeline Water Gas*
Pure Water
High Low Pressure Temperature Water Vapor (120℃)
13. The fluctuation of the voltage should be within -10% ~ +10% of the standard voltage. When DC responsiveness is very important,the Turbine Oil ISO VG32
JIS# 1Oil
fluctuation of the voltage should be within -5% ~ +5% of the standard voltage. The voltage should be lowered to the voltage of the cable connecting to the coil. 14. The disconnecting voltage for AC type solenoid valve should be lower than 20% of the standard voltage. For DC type, the disconnecting
NBR
voltage should be lower than 2% of the DC valve.
EPDM
15. If the valve needs to be storaged for prelonged peroid after using water-type fluid, the water and moisture should be completely removed,to
VITON
16. The required period for valve-state changing is influenced by the type and characteristics of the fluid. When using pure water as standard,
prevent the generation of stain and the corrosion of the rubber parts. please change the state of the valve(from open to close, and vice-versa) at least once every 10 days. If the peroid is longer than 10 days,
Brass
detecting system should be installed. The valves should be inspected every half a year at the minimal, in order to keep the valve in optimal
Stainless Steel
working condition. 17. Tips against harmful condensation and freezing:Condensation and freezing of water should be prevented when the valve is used under low temperateure. A high dew-point temperature, the low temperature of the environment and large flow passing through the valve may lead to
Working Medium Material
JIS# 2Oil
Heavy Vegetable Inorganic Oil Oil Engine Oil
Lipid Engine Oil
Conductive Silicone Oil
Glycol*
Glycol (High Purity Alcohol)*
Vacuum Vacuum Acetone* Glycol (Medium Vacuum) (Medium Vacuum) (Industrial Ethyl Alcohol)*
freezing. Air dryer and thermal insulation of the valve body should be used as prevention method. However, the coil should not be exposed to heater, or covered by thermal insulation material. 18. Please ensure the compatibility of the fluid and valve materal when choosing the valve type. As a general reference, the maximum viscosity
NBR EPDM
of the fluid should be no higher than 50cst. 19.The leakage of valve's inlet and outlet should be strictly prohibited when the valve is used for combustable oil and gas. Also, Explosion-proof coil should be chosen.
VITON Brass Stainless Steel
20. When the pipeline does not accept oil, please choose oil-prohibitive types of valve and parts. 21. Before maintainence of the solenoide valve, Electricity should be cut off, upstream fluid should be shut down, the pressure inside the pipeline must be removed. 22. The surface temperature is high for coil surface(especially true when the valve is used for high temperature fluid), therefore, there's a risk of injury due to burn when personall directly contacts the valve and coil.
Note: 1. ◎=Excellent(Has Little or no effect); ○=Good(Has little effect or can be used on certain condition); △=Unavailable(Has a great effect); 2. The symbol “*” means that working medium is inflammable & explosive. The corresponding explosion-proof coil should be used in this case; 3. Only Direct Acting Solenoid Valve ( the exit end connected with negative voltage) could be used in vacuum environment. Pilot Solenoid Valve is unavailable; 4. If the working medium is not in the above list, Please consult our technical department before using.
23. For pilot type 2/2 solenoid valves,the moment of start-up of fluid supplying source(pumps, compressors, etc) will introduce a a sudden increase of pressure, this may cause the valve to open momentarily, even when the valve is closed. This may cause the leakage of the fluid, please be cautious. 24. The thread size of the fluid inlet should not be smaller than the orifice of the valve body. Otherwise, when the valve is opened, the difference between in/out air pressure may be lower than the minimal difference of acting pressure. This may cause the vibration of diaphragm for pilot type solenoid valves. 25. Please refer to low power solenoid valve instructions when using low power solenoid valves.
2
ELP Series Solenoid Valve 2.83
ELP Series Solenoid Valve
ELP Series
ELP Series
2.84
Specifications A
A
P
Direct Acting N.O
A
A
Code
ELP06 -015
ELP08 -015
ELP06 -020
ELP08 -020
ELP06 -030
Port Size
1/8"
1/4"
1/8"
1/4"
1/8"
Orifice(mm) Cv
P
P Pilot Type N.C
Direct Acting N . C
Model
P
Direct Acting N.C
Pressure Difference(Bar)
Pilot Type N.O
1.5
1/4"
2
3
Direct Acting N . O ELP06 -040
ELP08 -040
ELP06H -015
ELP08H -015
ELP06H -020
ELP08H -020
ELP06H -030
ELP08H -030
ELP06H -040
1/8"
1/4"
1/8"
1/4"
1/8"
1/4"
1/8"
1/4"
1/8"
4
1.5
0 . 18
0 . 33
0 . 55
0.1
0 . 18
0 . 33
0 . 55
0~13
0~8
0~30
0~16
0~8
0~5
Direct Acting NC. Standard type:AC:15VA DC10W
Direct Acting NO.
Low power type:AC:4VA DC3W AC110V:7.0VA
Blank:NC H:NO
ELP 06:1/8" 08:1/4"
Orifice
ID Code
Voltage
Blank:Standard Type N:Energy Saving Type 015:1 . 5mm 020:2.0mm 030:3.0mm 040:4.0mm
10:3 / 8" 15:1 / 2" 20:3/4"
150:15mm
25: 1"
250:25mm
200:20mm
E1:AC110V E2:AC220V E4:DC24V E5:DC12V E7:AC24V
Cover Col o r
Valve Body Material
-15~10%
Blank:Brass
F Class
Protection grade
Seal Material — Thread Type
Blank:NBR E:EPDM V:VITON
Brass
Seal Material
VITON
Blank:G P:PT T:NPT
Model
ELP15
ELP20
ELP25
ELP10H-150
ELP15H
ELP20H
Port Size
3/8"
1/2"
3 / 4"
1"
3/8"
1/2"
3 / 4"
1"
20
25
20
25
9.5
12 . 5
9.5
12 . 5
Orifice(mm)
15 5.0
5.5
Power consumption
Working Temperature(℃) Voltage Range Insulations Protection grade Valve Body Material Seal Material
15 5.0
5.5
0 .5~16
Pressure Difference(Bar) Acting Type
Medium
* 2/2 solenoid valve, brass valve body, compact design, saving space. * Three types seals are optional, including NBR, EPDM and VITON, catering to different medium requirements. * Direct acting solenoid valve with VITON seal, 4 pressure types are optional: standard, high pressure. ultra high pressure and large flow type. * Well sealed water proof connector, protection grade of IP65. * Reduce power consumption up to 80%.
Direct Type N . O
ELP10-150
Guaranteed Pressure(Bar)
Product Features
Direct Type N . C
Code
Cv
Order Example: ELP series solenoid valve, 1/2 port size, NC, 15mm orifice, AC220V, black cover color, brass valve body, NBR seal, G thread, ERP code is: ELP15E2
IP65(DIN40050)
Valve Body Material
Blank:Black (only for DBK waterproof type) J:Colorless and translucent (only for DB type)
(Note: If orifice size same with port size, omit the orifice size.)
2
-20~80(No freezing)
Insulations
—
Low power type:AC:4VA DC3W AC110V:7.0VA
Air、Water、Hot water、Oil(≤20CST)
Working Temperature(℃)
Original Status
Standard type:AC:12VA DC10W 45
Voltage Range
Port Size
1/4" 4
0~2 0
Medium
Series NO.
3
0.1
Guaranteed Pressure(Bar)
2
2
ELP08H -040
0~30
Acting Type Power consumption
ELP08-030
0. 5~13
Diaphragm pliot type N.C Standard type:AC:15VA DC10W
ELP25H
Diaphragm pliot type N.O
Low power type:AC:4VA DC3W AC110V:7.0VA
Standard type:AC:12VA DC10W
25
Low power type:AC:4VA DC3W AC110V:7.0VA 20
Air、Water、Hot water、Oil(≤20CST) -20~80(No freezing) -15~10% F Class IP65(DIN40050) Brass NBR、EPDM、VITON
ELP Series Solenoid Valve 2.85
ELP Series Solenoid Valve
ELP Series
2.86
ELP Series
Pilot Type:
Flow Chart
Medium: Air
No.
Part Name
1 2 3 4 5 6 7 8 9 10 11
Valve Body
Medium: Air Min working pressure
S
Inlet Pressure P1
on ubs
C ri ti
cal
ic F
P re
Son
lo w
ssu
ic F
re
lo w
Inlet PressureP2(Bar)
Outlet Pressure P2(Bar)
Inlet Pressure P1
Su
n ic bso
C ri ti
cal
P re
Son
2
F lo
w
ssu
ic F
re
lo w
Spacer Diaphragm Components Spring O-ring Iron Core Components Coil Water Proof Connector Gasket Internal Teeth Washer
2
Screw
Flow Q : (L / min) Flow Q : (L / min)
Medium: Water
Medium: Water
Flow Q : (L / min)
Flow Q : (L / min)
Mounting Dimension
ELP06/08 Direct Acting Type :
Pilot Type:
F
2-M 5@5
Differential pressure:△P =( P1 - P2 ) Bar
E
30
N.O 73.7
C
N.C 78.2
E MC
Internal Structure ELP06/08 Direct Acting Type:
N.C
N.O
No.
Part Name
1 2 3 4 5 6 7
Valve Body
D
E MC
3
13
Differential pressure:△P =( P1 - P2 ) Bar
39
06:1/8" 08:1/4"
G
23
A
B
75
O-ring Iron Core Components Coil
Model
A
B
66 66 75 96
47 47 56 71
Water Proof Connector Internal Teeth Washer Hexagon nut
ELP10 ELP15 ELP20 ELP25
C N.C
N .O
95 95 102 111
99.2 99.2 106.2 115.2
D
E
F
G(Port)
30 30 30 30
74 74 74 74
74 74 79 98
3/8" 1/2" 3/4" 1"
2.87
SLP/SLP-S1 Series
SLP/SLP-S1 Series
SLP-08
SLPF-S1
Port Size
SLP : Thread connection SLPF : Flange connection
Original Status — Orifice
Blank : NC H : NO
06 : 1/8" 25 : 1" 08 : 1/4" 32 : 1-1/4" 10 : 3/8" 40 : 1-1/2" 15 : 1/2" 50 : 2" 20 : 3/4"
ID Code
Voltage
Valve Body Material
Seal Material — Thread Type
Blank: Brass Blank: NBR E: EPDM S1: SS316 V: VITON E1 : AC110V E6 : AC36V E2 : AC220V E7 : AC24V E3 : AC380V E8 : DC110V E4 : DC24V E9 : DC48V E5 : DC12V E10 : DC36V
Blank : Standard type N : Low power type
250 : 25mm 010 : 1mm 015 : 1.5mm 350 : 35mm 025 : 2.5mm 400 : 40mm 500 : 50mm 030 : 3mm 650 : 65mm 040 : 4mm 105 : 10.5mm 800 : 80mm 1000 : 100mm 130 : 13mm 200 : 20mm (Note : cancel if same with port size)
SLP06-030E2S1 SLP06-030E2S1E SLP06-030E2S1V
SLP08-030E2 SLP08-030E2E SLP08-030E2V SLP08-105E2 SLP08-105E2E SLP08-105E2V
SLP08-030E2S1 SLP08-030E2S1E SLP08-030E2S1V
SLP10-030E2 SLP10-030E2E SLP10-030E2V SLP10-040E2 SLP10-040E2E SLP10-040E2V SLP10-105E2 SLP10-105E2E SLP10-105E2V SLP10-130E2 SLP10-130E2E SLP10-130E2V
2 Series No.
SLP06-030E2 SLP06-030E2E SLP06-030E2V
Blank: G P: PT T: NPT
Order Example: SLP series solenoid valve, 1/2 port size, NC, 13mm orifice, standard type, AC110V, Brass valve body, NBR seal, G thread, ERP code is: SLP15-130E1
SLP10-030E2S1 SLP10-030E2S1E SLP10-030E2S1V SLP10-040E2S1 SLP10-040E2S1E SLP10-040E2S1V
2
SLP10-130E2S1 SLP10-130E2S1E SLP10-130E2S1V
SLP15-105E2 SLP15-105E2E SLP15-105E2V SLP15-130E2 SLP15-130E2E SLP15-130E2V
SLP15-130E2S1 SLP15-130E2S1E SLP15-130E2S1V
SLP20E2 SLP20E2E SLP20E2V
SLP20E2S1 SLP20E2S1E SLP20E2S1V
SLP25E2 SLP25E2E SLP25E2V
SLP25E2S1 SLP25E2S1E SLP25E2S1V
SLP32-350E2 SLP32-350E2E SLP32-350E2V SLP40E2S1 SLP40E2S1E SLP40E2S1V
SLP50E2 SLP50E2E SLP50E2V
SLP50E2S1 SLP50E2S1E SLP50E2S1V
Flange connection
SLPF25E2S1 SLPF25E2S1E SLPF25E2S1V
Flange connection
SLPF32-350E2S1 SLPF32-350E2S1E SLPF32-350E2S1V
Flange connection
SLPF40E2S1 SLPF40E2S1E SLPF40E2S1V
Flange connection
SLPF50E2S1 SLPF50E2S1E SLPF50E2S1V
* To reduce the power consumption of 80% energy-saving
Large port
SLP40E2 SLP40E2E SLP40E2V
Flange connection
65 65 65
52 52 52
0.5 0.5 0.5
12 12 12
12 12 12
8
Flange connection
80 80 80
80 80 80
0.5 0.5 0.5
12 12 12
12 12 12
8
Flange connection
100 100 100
128 128 128
0.5 0.5 0.5
12 12 12
12 12 12
8
8
8
8
2.88
80 120 120
33 33 33
20 20 20
SLPF65E2S1 SLPF65E2S1E SLPF65E2S1V
250×185×250 250×185×250 250×185×250
80 120 120
33 33 33
20 20 20
SLPF80E2S1 SLPF80E2S1E SLPF80E2S1V
270×185×262 270×185×262 270×185×262
80 120 120
33 33 33
20 20 20
SLPF100E2S1 SLPF100E2S1E SLPF100E2S1V
342×222×287 342×222×287 342×222×287
2.89
SLP-H Series
SLP H Series
SLP H small orifice
SLP-HS1 small orifice
SLP H
SLP HS1
2 * To reduce the power consumption of 80% energy-saving
3
Large diameter
1
SLP06H-010E2
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
SLP08H-010E2
SLP08H-010E2S1
SLP08H-010E2E
SLP08H-010E2S1E
SLP08H-010E2V
SLP08H-010E2S1V
SLP08H-015E2
SLP08H-015E2S1
SLP08H-015E2E
SLP08H-015E2S1E
SLP08H-015E2V
SLP08H-015E2S1V
SLP08H-025E2
SLP08H-025E2S1
SLP08H-025E2E
SLP08H-025E2S1E
SLP08H-025E2V
SLP08H-025E2S1V
SLP08H-030E2
SLP08H-030E2S1
SLP08H-030E2E
SLP08H-030E2S1E
SLP08H-030E2V
SLP08H-030E2S1V
22
13
SLP10H-130E2
SLP10H-130E2S1
22
13
SLP10H-130E2E
SLP10H-130E2S1E
8
22
13
SLP10H-130E2V
SLP10H-130E2S1V
8
22
13
SLP15H-130E2
SLP15H-130E2S1
22
13
SLP15H-130E2E
SLP15H-130E2S1E
8
22
13
SLP15H-130E2V
SLP15H-130E2S1V
8
22
13
SLP20HE2
SLP20HE2S1
22
13
SLP20HE2E
SLP20HE2S1E
8
22
13
SLP20HE2V
SLP20HE2S1V
8
22
13
SLP25HE2
SLP25HE2S1
22
13
SLP25HE2E
SLP25HE2S1E
8
22
13
SLP25HE2V
SLP25HE2S1V
8
22
13
SLP32H-350E2
SLP32H-350E2S1
22
13
SLP32H-350E2E SLP32H-350E2S1E
8
22
13
SLP32H-350E2V SLP32H-350E2S1V
8
22
13
SLP40HE2
SLP40HE2S1
22
13
SLP40HE2E
SLP40HE2S1E
8
22
13
SLP40HE2V
SLP40HE2S1V
8
22
13
SLP50HE2
SLP50HE2S1
22
13
SLP50HE2E
SLP50HE2S1E
8
22
13
SLP50HE2V
SLP50HE2S1V
8
22
13
SLPF25HE2S1
22
13
SLPF25HE2S1E
8
22
13
SLPF25HE2S1V
8
22
13
SLPF32-350HE2S1
22
13
SLPF32-350HE2S1E
8
22
13
SLPF32-350HE2S1V
8
22
13
SLPF40HE2S1
22
13
SLPF40HE2S1E
8
22
13
SLPF40HE2S1V
8
22
13
SLPF50HE2S1
22
13
SLPF50HE2S1E
22
13
SLPF50HE2S1V
8
SLP06H-010E2S1
SLP06H-010E2E
SLP06H-010E2S1E
SLP06H-010E2V
SLP06H-010E2S1V
SLP06H-015E2
SLP06H-015E2S1
SLP06H-015E2E
SLP06H-015E2S1E
SLP06H-015E2V
SLP06H-015E2S1V
SLP06H-025E2
SLP06H-025E2S1
SLP06H-025E2E
SLP06H-025E2S1E
SLP06H-025E2V
SLP06H-025E2S1V
SLP06H-030E2
SLP06H-030E2S1
SLP06H-030E2E
SLP06H-030E2S1E
SLP06H-030E2V
SLP06H-030E2S1V
8
2.90
2
2.91
ZS/ZSF Series
ZS/ZSF Series
VA CV
ZS small orifice
ZS S2 small orifice
ZS
ZS S2
(mm) AC
DC
1/8"
2.5 2.5 2.5
0.23 0.23 0.23
0 0 0
7 7 7
5 5 5
7 7 7
5 5 5
7 7
5 5
80 120 120
13 13 13
8.5 8.5 8.5
ZS06-025E2 ZS06-025E2E ZS06-025E2V
ZS06-025E2S2 ZS06-025E2S2E ZS06-025E2S2V
46.8×31×67 46.8×31×67 46.8×31×67
1/4"
2.5 2.5 2.5 10 10 10
0.23 0.23 0.23 1 1 1
0 0 0 0 0 0
7 7 7 20 20 20
5 5 5 16 16 16
7 7 7 20 20 20
5 5 5 16 16 16
7 7 20 20
5 5 16 16
80 120 120 80 120 120
13 13 13 22 22 22
8.5 8.5 8.5 13 13 13
ZS08-025E2 ZS08-025E2E ZS08-025E2V ZS08-100E2 ZS08-100E2E ZS08-100E2V
ZS08-025E2S2 ZS08-025E2S2E ZS08-025E2S2V -
46.8×31×67 46.8×31×67 46.8×31×67 50×40.5×98 50×40.5×98 50×40.5×98
3/8"
4 4 4 10 10 10 16 16 16
0.6 0.6 0.6 1.8 1.8 1.8 4.8 4.8 4.8
0 0 0 0 0 0 0 0 0
8 8 8 20 20 20 10 10 10
5 5 5 16 16 16 6 6 6
8 8 8 20 20 20 10 10 10
5 5 5 16 16 16 6 6 6
5 5 20 20 7
5 5 16 16 4 4
33 33 33 22 22 22 33 33 33
20 20 20 13 13 13 20 20 20
ZS10-040E2 ZS10-040E2E ZS10-040E2V ZS10E2 ZS10E2E ZS10E2V ZS10-160E2 ZS10-160E2E ZS10-160E2V
ZS10-040E2S2 ZS10-040E2S2E ZS10-040E2S2V -
7
80 120 120 80 120 120 80 120 120
52.5×47.5×83 52.5×47.5×83 52.5×47.5×83 50×40.5×83 50×40.5×83 50×40.5×83 69×75×106 69×75×106 69×75×106
10 10 10 16 16 16
1.9 1.9 1.9 4.8 4.8 4.8
0 0 0 0 0 0
20 20 20 10 10 10
16 16 16 6 6 6
20 20 20 10 10 10
16 16 16 6 6 6
20 20 7
16
7
4
80 130 120 80 130 120
22 22 22 33 33 33
13 13 13 20 20 20
ZS15-100E2 ZS15-100E2E ZS15-100E2V ZS15-160E2 ZS15-160E2E ZS15-160E2V
20 20 20
7.6 7.6 7.6
0 0 0
10 10 10
6 6 6
10 10 10
6 6 6
7
4
7
4
80 130 120
33 33 33
20 20 20
25 25 25 25
12 12 12 12
0 0 0 0
10 10 10 10
6 6 6 6
10 10 10 3
6 6 6 3
7
4
1"
7
4
80 120 120 120
33 33 33 33
35 35 35
24 24 24
0 0 0
10 10 10
6 6 6
10 10 10
6
7
4
1-1/4"
6
7
4
80 120 120
40 40 40
29 29 29
0 0 0
10 10 10
6 6 6
10 10 10
6
7
4
6
7
7
50 50 50
48 48 48
0 0 0
10 10 10
6 6 6
10 10 10
6
7
4
6
7
4
25 25 25 32 32 32 40 40 40 50 50 50 65 65 65 80 80 80 100 100 100
12 12 12 24 24 24 29 29 29 48 48 48 75 75 75 90 90 90 160 160 160
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
10 10 10 10 10 10 10 10 10 10 10 10 6 6 6 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 6 6 6 5 5 5 5 5 5 5 5 5
10 10 10 10 10 10 10 10 10 10 10 10 6 6 6 6 6 6 6 6 6
6
7
4
6 6
7 7
4 4
6 6
7 7
4 4
6 6 6 6 5 5 5 5 5 5 5 5 5
7 7
4 4
7 3
4 2
3 3
2 2
3 3
2 2
3
2
ZSF S2
2 Series No. ZS : Thread connection ZSF : Flange connection
Port size
Original status —
06 : 1/8" 25 : 1" Blank : NC 08 : 1/4" 32 : 1-1/4" H : NO 10 : 3/8" 40 : 1-1/2" 50 : 2" 15 : 1/2" 20 : 3/4"
Orifice
ID Code
Voltage
Blank : Standard type 025 : 2.5mm 200 : 20mm N : Low power type 030 : 3mm 250 : 25mm 040 : 4mm 350 : 35mm 050 : 5mm 400 : 40mm E1 : AC110V 060 : 6mm 500 : 50mm E2 : AC220V 075 : 7.5mm 650 : 65mm E3 : AC380V 100 : 10mm 800 : 80mm E4 : DC24V 160 : 16mm 1000 : 100mm E5 : DC12V (Note : cancel if same with port size)
Valve body Seal material material
— Thread type
Blank: G Blank: Brass Blank: NBR E: EPDM P: PT S1: SS316 V: VITON T: NPT S2: SS304 Si: Slilicon E6 : AC36V (smaller than Φ25mm E7 : AC24V is optional) E8 : DC110V E9 : DC48V E10 : DC36V
1/2"
3/4"
Order Example:
220VAC
W
AC DC 220 24V
(G )
AC DC
ZS series solenoid valve, 1/2" port size, NC, 16mm orifice, standard type, AC110V, Brass valve body, NBR seal, G thread, ERP code is: ZS15-160E1 Note: 2.5mm small orifice valve only with flying leads coil, other orifice with DIN connector coil.
1-1/2"
* To reduce the power consumption of 80% energy-saving 2"
Large port
Flange 4 hole
≤20CST AC DC
16 4
(℃)
2.92
A×B×H(mm)
ZS10-160E2S2 ZS10-160E2S2E ZS10-160E2S2V ZS15-160E2S2 ZS15-160E2S2E ZS15-160E2S2V
69×75×106 69×75×106 69×75×106 69×75×106 69×75×106 69×75×106
ZS20E2 ZS20E2E ZS20E2V
ZS20E2S2 ZS20E2S2E ZS20E2S2V
73×57×114 73×57×114 73×57×114
20 20 20 20
ZS25E2 ZS25E2E ZS25E2V ZS25E2G
ZS25E2S2 ZS25E2S2E ZS25E2S2V ZS25E2S2G
99×77×121 99×77×121 99×77×121 99×77×121
70 70 70
40 40 40
ZS32-350E2 ZS32-350E2E ZS32-350E2V
ZS32-350E2S2 ZS32-350E2S2E ZS32-350E2S2V
112×86.5×150 112×86.5×150 112×86.5×150
80 120 120
70 70 70
40 40 40
ZS40E2 ZS40E2E ZS40E2V
ZS40E2S2 ZS40E2S2E ZS40E2S2V
123×94×160 123×94×160 123×94×160
80 120 120
70 70 70
40 40 40
ZS50E2S2 ZS50E2S2E ZS50E2S2V
168×123×183 168×123×183 168×123×183
80 130 120 80 130 120 80 130 120 80 130 120 80 120 120 80 120 120 80 120 120
70 70 70 70 70 70 70 70 70 70 70 70 55 55 55 55 55 55 55 55 55
40 40 40 40 40 40 40 40 40 40 40 40 64 64 64 64 64 64 64 64 64
ZS50E2 ZS50E2E ZS50E2V -
ZSF25E2S2 ZSF25E2S2E ZSF25E2S2V ZSF32-350E2S2 ZSF32-350E2S2E ZSF32-350E2S2V ZSF40E2S2 ZSF40E2S2E ZSF40E2S2V ZSF50E2S2 ZSF50E2S2E ZSF50E2S2V ZSF65E2S2 ZSF65E2S2E ZSF65E2S2V ZSF80E2S2 ZSF80E2S2E ZSF80E2S2V ZSF100E2S2 ZSF100E2S2E ZSF100E2S2V
140×115×160 140×115×160 140×115×160 152×135×215 152×135×215 152×135×215 152×135×215 152×135×215 152×135×215 195×160×220 195×160×220 195×160×220 250×185×308 250×185×308 250×185×308 270×202×320 270×202×320 270×202×320 342×222×345 342×222×345 342×222×345
2
ZSH Series 2/2 Solenoid Valve (Normal Open) 2.93
EYP Series 2/2 Solenoid Valve(Normal Close)
ZSH Series
EYP Series
ZS-10H
ZS-15HS2
EYP 25
2.94
EYP 40
2
2 * 2/2 ways Solenoid valve, Normally open. Copper and stainless steel 304 valve selection
Series No. EYP
3/ 8
* To reduce the power consumption of 80% energy-saving
Port Size
ID Code
15 : 1/2" 32 : 1-1/4" 20 : 3/4" 40 : 1-1/2" 50 : 2 " 25 : 1"
Voltage
Blank : Standard type
E1 : AC110V E2 : AC220V E3 : AC380V E4 : DC24V E5 : DC12V
—
Thread Type
E6 : AC36V Blank: G E7 : AC24V P: PT E8 : DC110V T: NPT E9 : DC48V E10 : DC36V
Order Example: EYP series solenoid valve, 3/8 port size, standard type, AC110V, PT thread, ERP code is: EYP10E1-P
The maximum temperature of fluid
Brass ZS10H-040E2 ZS10H-040E2E ZS10H-040E2V ZS10H-160E2 ZS10H-160E2E ZS10H-160E2V ZS15H-160E2 ZS15H-160E2E ZS15H-160E2V ZS20HE2 ZS20HE2E ZS20HE2V ZS25HE2 ZS25HE2E ZS25HE2V ZS32HE2 ZS32HE2E ZS32HE2V ZS40HE2 ZS40HE2E ZS40HE2V ZS50HE2 ZS50HE2E ZS50HE2V
Flange 4 hole
* Individual inlet filter can protect medium clean, it is easy for maintenance. * Manual switch can contrarotate to open the valve when power off * Flowrate adjusting handle is available on DN32-50mm valves * When installing the connector, it is suggested have 5 turns of teflon tape, on the connector, keep 8-9mm distance from the thread, be gentle to avoid damage on the body.
A×B×H(mm)
ZS10H-040E2S2 ZS10H-040E2S2E ZS10H-040E2S2V ZS10H-160E2S2 ZS10H-160E2S2E ZS10H-160E2S2V ZS15H-160E2S2 ZS15H-160E2S2E ZS15H-160E2S2V ZS20HE2S2 ZS20HE2S2E ZS20HE2S2V ZS25HE2S2 ZS25HE2S2E ZS25HE2S2V ZS32HE2S2 ZS32HE2S2E ZS32HE2S2V ZS40HE2S2 ZS40HE2S2E ZS40HE2S2V ZS50HE2S2 ZS50HE2S2E ZS50HE2S2V ZSF25HE2S2 ZSF25HE2S2E ZSF25HE2S2V ZSF32HE2S2 ZSF32HE2S2E ZSF32HE2S2V ZSF40HE2S2 ZSF40HE2S2E ZSF40HE2S2V ZSF50HE2S2 ZSF50HE2S2E ZSF50HE2S2V
52.5×32.5×115 52.5×32.5×115 52.5×32.5×115 69×57×135 69×57×135 69×57×135 69×57×135 69×57×135 69×57×135 73×57×142 73×57×142 73×57×142 99×77.5×150 99×77.5×150 99×77.5×150 112×86.5×180 112×86.5×180 112×86.5×180 123×94×190 123×94×190 123×94×190 168×123×216 168×123×216 168×123×216 140×115×180 140×115×180 140×115×180 152×135×235 152×135×235 152×135×235 152×145×240 152×145×240 152×145×240 195×160×255 195×160×255 195×160×255
EYP15
EYP20
EYP15
85
73
126
EYP20
90
73
128
EYP25
125
90
148
EYP32
150
128
173
EYP40
152
128
176
EYP50
170
140
190
EYP25
EYP32
32 Psi Psi
4.35~116 130.5 32-149℉ Reinforced Nylon
EYP40
2V Series 2/2 Solenoid Valve (Normal Close) 2.95
2P Series 2/2 Solenoid Valve (Normal Close)
2V Series
2P Series
2.96
2P025
Series No. 2V
Port Size
—
025 : 2.5mm 130 : 13mm 250 : 25mm
025 06 : 1/8" 08 : 1/4" 130 10 : 3/8"
15 : 1/2" 250 20 : 3/4" 25 : 1"
ID Code
Voltage
Blank: Standard type N: Low power type
E1 : AC110V E5 : DC12V E2 : AC220V E6 : AC36V E3 : AC380V E7 : AC24V E4 : DC24V
Seal Material — Thread Type Blank: NBR E: EPDM V: VITON
Blank: G P: PT T: NPT
Order Example: 2V series solenoid valve, 13mm orifice, 1/2 port size, standard type, DC24V, EPDM seal, G thread, ERP code is: 2V130-15E4E Note: Connection type is DIN connector.
Series No. 2P
Orifice — Port Size
Voltage
Connection Type
Seal Material — Thread Type
025: 2.5mm 06: 1/8" E1: AC110V Blank : NBR 08: 1/4" E2: AC220V E : EPDM E3: AC380V V : VITON E4: DC24V Blank : DIN connector E5: DC12V F : Flying leads E6: AC36V E7: AC24V
2
Blank : G
Order Example: 2P series solenoid valve, 2.5mm orifice, 1/8 port size, standard type, DC24V, DIN connection, NBR seal, G thread, ERP code is: 2P025-06E4
* To reduce the power consumption of 80% energy-saving * To reduce the power consumption of 80% energy-saving
9.5
9.5
2
Orifice
72
AC:5VA
DC:4.8W
Power consumption 102
AC:7VA DC:6.5W Engineering plastic
EAM22/EAT22 Series Solenoid Valve
SLG Series 2/2 Solenoid Valve (Normal Close) 2.97
SLG5404 Series
EAM22/EAT22 Series
SLG5404-15F
Series No.
—
Port Size
ID Code
15:1/2" 20:3/4" 25:1"
Blank : Standard type N : Low power type
Connection Mode
2.98
SLG5404-15
Coil Form
—
Thread Type
Series No.
Blank: G P: PT T: NPT
EAM22
Valve OD Size
—
Drive Voltage
Series No.
—
Port size
Orifice
Voltage
10: 3/8"
080: 8mm
E4: DC24V
—
Thread Type
2
2 SLG5404
E1:AC110V E2:AC220V E3:AC380V E4:DC24V
E5:DC12V E6:AC36V E7:AC24V
Blank: DIN connector F: Flying leads
Order Example: SLG5404 Series solenoid valve, 1/2"port size, AC220V, DIN connecter, G thread, ERP code is: SLG5404-15E2
E11: DC100V
19mm
EAT22
Blank: G P: PT T: NPT
Order Example:
Order Example:
EAM series solenoid valve, 19mm valve OD size,Drive voltage DC100V, ERP code is: EAM22-19E11
EAT series solenoid valve, 3/8 port size, orifice 8mm, DC24V, G thread, ERP code is: EAT22-10080E4
* High pressure,PTFE seal
* To reduce the power consumption of 80% energy-saving
Two way two position solenoid valve High frequency valve Long lifetime with 1.1 billion cycles Stable quality, gurantee two years
High frequency: 1000HZ Drive voltage: 100VDC Working pressure: 0.5Mpa Rated flow rate: 100L/min Special treatment with long lifetime
Pressure Difference (Bar)
Max frequency
Air
Liquid
Air
Liquid
Air
Liquid 1000Hz
Power consumption Body material
Rated flow rate 100L/min
Min.
Max. (air, inet gas)
0
5
Working Insulation temperature class
5~40℃
class F
Main dimensions 19.8*31.5
Port Size Orifice (mm) 3/8"
8
Pressure Difference (Bar)
Min. 0
Working Insulation Weight temperature Resistance Max. class (air, inet gas)
7
5~40℃
31±2Ω
class B
300g
Main dimensions 50*30*75.1
EMCJ Series Full Stainless Steel Series Angle Valve 2.99
EMCJ Series Full Stainless Steel Series Angle Valve EMCJ Series
EMCJ Series
2.100
EMCJ Series Full Stainless Steel Series Angle Valve
Series No.
2
—
Port Size
—
Actuator Size
Acting Type
Valve Body Material — ThreadType
EMCJ: Stainless Steel Series Angle Valve
10: 3/8" 40 : Φ40mm Blank : NC Single Acting S1 : SS316 15: 1/2" 50 : Φ50mm H : NO Single Acting S2 : SS304 20: 3/4" 63 : Φ63mm D : Double acting 25: 1" 80 : Φ80mm 32: 1-1/4" 100 : Φ100mm 40: 1-1/2" 50: 2" Order Example: EMCJ series full stainless steel angle seat valve, 3/8 port size, 40mm actuator size, NC single acting, SS316 valve body, G thread, ERP code is: EMCJ-10-40S1
2
Blank : G P : PT T : NPT
50.5 62 50.5 62 62 62 45
34 34 34 34 41.5 41.5
41.5
41.5
2
100 100
22 22 25 25 31 39 39
56 56 56 68 68 68
4.5
EMCJ10-40
EMCJ10-40H
EMCJ10-50
EMCJ10-50H
EMCJ15-40
EMCJ15-40H
EMCJ15-50
EMCJ15-50H
EMCJ20-50
EMCJ20-50H
EMCJ25-50
EMCJ25-50H
EMCJ25-63
EMCJ25-63H
EMCJ32-63
EMCJ32-63H
EMCJ40-63
EMCJ40-63H
EMCJ50-63
EMCJ50-63H
EMCJ50-80
EMCJ50-80H
EMCJ Series Full Stainless Steel Series Angle Valve 2.101
EMCP Plastic Actuator Series Angle Valve
EMCJ Series
EMCP Series
2.102
EMCP Plastic Actuator Series Angle Valve
Series No. —
2
Port Size — Actuator Size
EMCP: 15:1/2" Plastic Actuator 20:3/4" Angle Valve 25:1" 32:1-1/4" 40:1-1/2" 50:2"
Valve Body Material
— Thread Type
50:Φ50mm Blank : NC Single S1:SS316 63:Φ63mm Acting 80:Φ80mm H : NO Single S2:SS304 100:Φ100mm Acting D : Double acting
Acting Type
Blank:G P :PT T :NPT
2
Order Example: EMCP series Plastic Actuator Angle Valve, 3/8 port size, 40mm actuator size, NC single acting, SS316 valve body, G thread, ERP code is: EMCP-10-40S1
EMCJ10-40DC
EMCJ10-40D
EMCJ10-50DC
EMCJ10-50D
EMCJ15-40DC
EMCJ15-40D
EMCJ15-50DC
EMCJ15-50D
EMCJ20-50DC
EMCJ20-50D
EMCJ25-50DC
EMCJ25-50D
EMCJ25-63DC
EMCJ25-63D
EMCJ32-63DC
EMCJ32-63D
EMCJ40-63DC
EMCJ40-63D
EMCJ50-63DC
EMCJ50-63D
EMCJ50-80DC
EMCJ50-80D
170 185 190 200 240 280 295
DN15-DN50 Stainless steel
50
Cable Type Energy Saving Module
Connector+ Coil
NF Series
2.103
Connector+ Coil
2
2.104
2 Series No.
—
N F : Cable type energy saving module
Voltage
—
E1:AC110V E2:AC220V E4:DC24V
Series No.
Power
—
Power type
Voltage
Cover Color
Logo
LED Lamp
DA : DIN43650 A : AC 1 : 12V-48V Blank : Brown translucent A type ( ISO4400) D : DC 2 : 110V-220V J : Colorless and translucent 3 : 380V DB : B type ( Industrial ) B : Black translucent DC : C type ( Industrial ) Without this code Note: All with rubber pad. for the new RV valve
Blank : Not with LED lamp L : With LED lamp Note : DC current is with colorless and transparent lamp, with red light when power on. If wrong wiring with green light. Blank : Not with“EMC”logo AC current is with red lamp E : With“EMC”logo and with red light if be power on. Note : can make with customer ' s logo
Blank:Low-power type 2:High-power type
Order Example: Cable type energy saving module,DC24V,Low-power type,ERP code is: NF - E4。
Order Example: * * * *
Industial B type, AC220V, Brown translucent cover, with “EMC”logo and LED lamp, with Piezoresistor, the model No. is: DB-A2ELR
Increase valve's frequency and response time Reduce the power of valve Reduce the valve coil heating temperature Improve the reliability of the valve opening
DC
How to use No need external power supply, Directly connect between electricity signal (IN) and solenoid valve (OUT). Brown line-the input signal of module (IN), connecting controller's output port, the length of the wire is about 130mm. Blue line-the output signal of module (OUT), connecting solenoid valve. The module is two-wire type. The input and output are both positive and negative. Note: IN and OUT are not allowed wrong connection, otherwise module will be damaged.
Model NO. Voltage
NF-E1
NF-E1 - 2
Input signal(IN) Output signal(OUT) Power consumption
NF-E2
AC110V
NF-E2 - 2 AC220V
NF-E4
NF-E4 - 2 DC24V
rated voltage (1±20%) > 1000Ω( < 10VA) > 110Ω( < 50VA)
> 3500Ω( < 10VA) > 155Ω( < 50VA) > 1 00Ω( < 5.5W) 20% of the original power
Working temperature(℃) Protective class Note:The output signal(OUT) AC type is based on the coil resistance, and the power in brack is for reference only.
-40~100 IP65
> 1 6Ω( < 35W)
DB
DA
Coil 2.105
Coil
Coil
Coil
Original code ESP-C Orifice:Φ13mm H:40mm
Coil(with connector)code XD-ESP-E1 XD-ESP-E2 XD-ESP-E3 XD-ESP-E4 XD-ESP-E5 XD-ESP-E6 XD-ESP-E7 XD-ESP-E8 XD-ESP-E9 XD-ESP-E10
2 Series No.
Coil Type
X : Coil
Blank : standard coil A : Amisco coil H: Thermosetting Coil
Connection Mode —
D : DIN Coil+ connector C : DIN coil F : Flying leads coil
Suitable Series
V1 : V5211 series V2 : V5221 series ……
New RV valve wire coil is standard coil pins coil is thermosetting coil
—
Voltage
E1 : AC110V E2 : AC220V E3 : AC380V E4 : DC24V E5 : DC12V
Cover color
E6 : AC36V Blank : Brown translucent E7 : AC24V J : Colorless and translucent E8 : DC110V B : Black translucent E9 : DC48V E10 : DC36V
Note : Pls check following attachment for connetors and coil. Others be with non standard.
Original code VC1-DJ Orifice:Φ8mm L×W×H: 22×17× 23.5mm
Coil(with connector)code X(A)D-V1-E1J X(A)D-V1-E2J X(A)D-V1-E3J X(A)D-V1-E4J X(A)D-V1-E5J X(A)D-V1-E6J X(A)D-V1-E7J X(A)D-V1-E8J X(A)D-V1-E9J X(A)D-V1-E10J
Connector code DC-A2JEL DC-A2JEL DC-A3JEL DC-D1JEL DC-D1JEL DC-A1JEL DC-A1JEL DC-D2JEL DC-D1JEL DC-D1JEL
Original code VC2-DJ
Original code 2VC
Orifice:Φ9.2mm L×W×H: 28.2×22× 29.5mm
Orifice:Φ9.2mm L×W×H: 28.2×22× 31.5mm
Coil(with connector)code X(A)D-V2-E1J X(A)D-V2-E2J X(A)D-V2-E3J X(A)D-V2-E4J X(A)D-V2-E5J X(A)D-V2-E6J X(A)D-V2-E7J X(A)D-V2-E8J X(A)D-V2-E9J X(A)D-V2-E10J
Connector code DB-A2JELR DB-A2JELR DB-A3JELR DB-D1JELR DB-D1JELR DB-A1JELR DB-A1JELR DB-D2JELR DB-D1JELR DB-D1JELR
Coil(with connector)code XD-2V-E1 XD-2V-E2 XD-2V-E3 XD-2V-E4 XD-2V-E5 XD-2V-E6 XD-2V-E7 XD-2V-E8 XD-2V-E9 XD-2V-E10
Original code SLG5404C-D
Original code SLPC
Original code 2PC
Orifice:Φ16.3mm L×W×H: 41.4×39.4× 79.5mm
Orifice:Φ14.7mm L×W×H: 38.5×29× 42mm
Orifice:Φ9.2mm H:29mm
Coil(with connector)code XD-SLG5404D-E1 XD-SLG5404D-E2 XD-SLG5404D-E3 XD-SLG5404D-E4 XD-SLG5404D-E5 XD-SLG5404D-E6 XD-SLG5404D-E7 XD-SLG5404D-E8 XD-SLG5404D-E9 XD-SLG5404D-E10
Connector code DA-A2B DA-A2B DA-A3B DA-D1B DA-D1B DA-A1B DA-A1B DA-D2B DA-D1B DA-D1B
Coil(with connector)code XD-SLP-E1 XD-SLP-E2 XD-SLP-E3 XD-SLP-E4 XD-SLP-E5 XD-SLP-E6 XD-SLP-E7 XD-SLP-E8 XD-SLP-E9 XD-SLP-E10
Connector code DA-A2B DA-A2B DA-A3B DA-D1B DA-D1B DA-A1B DA-A1B DA-D2B DA-D1B DA-D1B
Coil(with connector)code XF-2P-E1 XF-2P-E2 XF-2P-E3 XF-2P-E4 XF-2P-E5 XF-2P-E6 XF-2P-E7 XF-2P-E8 XF-2P-E9 XF-2P-E10
Connector code DB-A2ELR DB-A2ELR DB-A3ELR DB-D1ELR DB-D1ELR DB-A1ELR DB-A1ELR DB-D2ELR DB-D1ELR DB-D1ELR
Connector code DA-A2JL DA-A2JL DA-A3JL DA-D1JL DA-D1JL DA-A1JL DA-A1JL DA-D2JL DA-D1JL DA-D1JL
Original code ZSC-1D
Original code ZSC-2D
Orifice:Φ16.3mm L×W×H: 54×38.5× 40mm
Orifice:Φ20.3mm H:50mm
Coil(with connector)code XD-ZS1-E1 XD-ZS1-E2 XD-ZS1-E3 XD-ZS1-E4 XD-ZS1-E5 XD-ZS1-E6 XD-ZS1-E7 XD-ZS1-E8 XD-ZS1-E9 XD-ZS1-E10
Connector code DA-A2B DA-A2B DA-A3B DA-D1B DA-D1B DA-A1B DA-A1B DA-D2B DA-D1B DA-D1B
Coil(with connector)code XD-ZS2-E1 XD-ZS2-E2 XD-ZS2-E3 XD-ZS2-E4 XD-ZS2-E5 XD-ZS2-E6 XD-ZS2-E7 XD-ZS2-E8 XD-ZS2-E9 XD-ZS2-E10
Connector code DA-A2B DA-A2B DA-A3B DA-D1B DA-D1B DA-A1B DA-A1B DA-D2B DA-D1B DA-D1B
2.106