Hattersley PICV & Hook-Up Brochure - MEA Edition

Page 14

VARIABLE FLOW

Fig. EP801P

Fig. EP801PF

Hook-Up Elite Prime with PICV & Strainer Drain

Hook-Up Elite Prime with PICV, Strainer Drain and FMD

Features & Benefits

PN16

Material Specification

1. Compact, pre-fabricated unit – now available with Elite Prime PICV with a wide range of settable flows to suit all applications

2. All valves are subject to both a pressure test, in accordance with BS EN 12266-1, as well as a flow limitation test, in accordance to BSRIA BTS1. This provides reassurance of performance and accuracy within each valve

3. Provides accurate flow rates & differential pressure control as well as flow measurement (Fig. EP801PF), system flushing and isolation

4. DZR H Body tested to 3.1X Design Working Pressure (DWP)and bronze H Body tested to 3.9 X DWP during development for design robustness and tested to EN12516-2 to comply with the Pressure Equipment Directive (PED)

Part No.

Description

Material

Specification

1A

Bypass H-Body DN15

Bronze

BS EN 1982 (CC491K)

1B

Bypass H-Body DN20, DN25

DZR Brass

BS EN 12165 (CW602N)

2

D299P Strainer

DZR Brass

BS EN 12165 (CW602N)

3

Fig. 1934 PICV

DZR Brass

BS EN 12165 (CW602N)

4

Tailpiece

DZR Brass

BS EN 1982 (CC491K)

5

Fig. 1000 FMD

DZR Brass

BS EN 12165 (CW602N)

5. Fully assembled & factory tested unit reduces installation time, costs and specification risks

6. Can be tailored to suit customer’s specification: • Available with extension stems (Fig. EP801PEXT) or without (Fig. EP801P)

Specification

• Add an extra Flow Measurement device for verification of flow rates (Fig. EP801PF & Fig. EP801PFEXT)

Bronze (BS EN 1982 CC491K) fan-coil valve/ terminal unit valve assembly. Pre-assembled to the requirements of each individual terminal unit to include a flushing by-pass with integral isolation valves, Elite Prime Pressure Independent Control Valve (PICV), with options for low flow to high flow, flow measurement device, strainer, drain and pressure test points as and where specified. Extended handles will be fitted for Chilled Water applications.

7. Available in 400 kPa & 800 kPa rated variants 8. On-Off, modulating or feedback actuators are available separately to match specification

Pressure / Temperature Rating PN16: -10 to 100

End Connections

On-Off or modulating actuator is required to control the PICV. Valve assembly will be labeled to include the terminal unit reference number and flow rate. Generally as Hattersley Fig. EP801P & Fig. EP801PF Hook-Up Elite Prime system with PICV.

Flushing bypass body - BSP Parallel, Strainers & Tailpieces - BSP Taper

Dimensional Drawings

Fig. EP801PF

Dimensions & Weights

[Left-hand configuration shown]

EP801P

14

EP801PF

DN DN DN DN DN DN DN DN DN DN 15/15 20/15 20/20 25/20 25/25 15/15 20/15 20/20 25/20 25/25

A

mm

184

184

197

197

248

229

229

241

261

298

B

mm

173

173

178

178

224

173

173

178

198

224

C

mm

76

76

82

82

89

76

76

82

82

89

D

mm

67

67

77

77

77

67

67

77

77

77

Weight

kg

2.52

2.54

2.91

2.91

4.22

2.75

2.75

3.21

3.51

4.55

Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing. Hattersley Ltd assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the information within the publication and reserves the right to change without notice.

de Ma in

re

G

Valid as of 220519

Nom Size

in

Fig. EP801P

a t B rita

TECHNICALTECHNICAL HELPLINE: +44 HELPLINE: (0) 1473 ???????? 277400 E: techenquiries@hattersley.com W: www.hattersley.com


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.