VRV® systems
Outdoor units new new new
Air-Cooled VRV®-Q Introduction RQEQ-P / RQYQ-P Replacement VRV®III Heat Recovery / Heat Pump Air-Cooled VRV® REY(H)Q-P VRV®III Heat Recovery – High COP REYQ-P8/P9 VRV®III Heat Recovery BSVQ / BSV Individual / Multi Branch Selector Boxes RXHQ-P VRV®III Heating only RXYHQ-P9 VRV®III Heat Pump – High COP RXYQ-P9 VRV®III Heat Pump – Small Footprint RXYRQ-P VRV®III Heat Pump – Stylish Indoors RXYSQ-P8 VRV®III-S Heat Pump ® Water-Cooled VRV RWEYQ-P Heat Pump RWEYQ-P Heat Recovery Geothermal Application (Heat Pump & Heat Recovery) RWEYQ-PR
Indoor units 1. Cassette units
For a copy of our latest Price List please call 0845 6419000
133 134 136 137 138 139 141 142 143 144 145
4. Ceiling suspended units
FXFQ-P9 FXZQ-M9 FXCQ-M8 FXKQ-MA
146 147 148 149
2. Concealed ceiling units
128 130
FXDQ-M9 FXDQ-P7 FXSQ-P FXMQ-P7 FXMQ-MA
150 151 152 153 154
FXHQ-MA FXUQ-MA
156 157
5. Floor standing units
FXNQ-P FXLQ-P
158 159
6. Air curtains new
CYQ-DK
7. Hot water module
160 161
3. Wall mounted units
FXAQ-P
155
126 VRV_contents.indd 126
30/03/2011 18:44
The simple switchover for R22 systems
REDUCED REDUCED
REDUCED
Plug in VRV®III-Q
Up to
50%
Existing System
SAVED
Act now. Virgin R22 banned in January 2010 Save time and money, without compromising performance, when you replace existing R22 equipment. VRV®III-Q is the smart way to achieve: • • • • • •
Dramatically reduced installed cost – up to 50% saving compared with complete new system. Ability to reuse all existing pipework and possibility to reuse existing fan coils. Flexibility to use with existing pipework connected to other non-Daikin systems. Automatic pipework cleaning function. Higher energy efficiency and lower CO2 emissions than retrofitting refrigerant. Major potential to increase system capacity.
your comfort. our world.
For more information, visit www.daikin.co.uk/r22r Midlands Region
Northern Region
North London
Central London
0845 641 9370
0845 641 9340
0845 641 9360
0845 641 9350
South London 0845 641 9355
Scotland Region 0845 641 9330
Western Region 0845 641 9320
127 2515_BOOK_VRV_2011.indb 127
24/03/2011 12:23
Replacement VRV®
Daikin solution to R-22 phase out
R-410A VRV®-Q outdoor unit
R-22 refrigerant piping
* All units older than the K-Series must be replaced. * For heat recovery applications, the BS-boxes need to be replaced.
R-22 or R-410A indoor
What is R-22 and why is it phased-out? R-22 is a hydrochlorofluorocarbon (HCFC) which was commonly used in air conditioning systems. When R-22 is released into the air, the ultraviolet rays of the sun cause it to decompose and chlorine is released in the stratosphere. Chlorine reacts with ozone, reducing the amount of the ozone. Due to ozone layer depletion, harmful ultraviolet rays reach the surface of the earth giving rise to a number of health and environmental issues. The international community therefore, signed the Montreal Protocol to phase out ozone depletion materials by 2030. The European Union however, decided to ban R-22 already in 2015.
Technologies of VRV®-Q VRV ® -Q
Pressure
Indoor A
}
3.3 MPa
}
3.8 MPa
Pressure sensor
B
Change over valve Temperature sensor
~
~
Enthalpy
Antireverse valve
Temperature sensor
Catcher
A Decompression to 3.3MPa(s) R-22 existing piping can be used B Extra sub cool circuit high COP
Contamination is collected by the power of the refrigerant gas
Reduced pressure
Refrigerant pipe cleaning
As R-22 VRV® systems work on a lower pressure than R-410A systems; thus the copper refrigerant piping was also designed for these lower pressures. Therefore the Replacement VRV® (VRV®-Q) must operate at lower pressures than the standard VRV®III series. However thanks to the sub cool circuit a high efficiency level can be kept even with the lower pressures.
When replacing an air conditioning system, the piping is normally replaced as well since traces of old refrigerant and oil mixed with the oil and refrigerant of the new system can cause the equipment to malfunction. In order to allow re-use of existing R-22 piping with an R-410A system Daikin developed a technology to capture and retain the contamination left in the refrigerant piping. During the charging of the system, R-410A refrigerant starts circulating through the copper piping collecting the contamination left in the refrigerant piping. The refrigerant including the remaining oil from the R-22 system is filtered in the outdoor unit and the contamination is deposited in the outdoor unit. This process is executed only once and takes about 1 hour (depending on system characteristics). Daikin is the first manufacturer in the industry to develop this combination of automatic charging and refrigerant pipe cleaning function.
128 2515_BOOK_VRV_2011.indb 128
24/03/2011 12:23
Features of VRV®-Q Warranty
Possibility to increase capacity
Unlike using drop in refrigerants, the VRV®-Q condensing unit is provided with a manufacturers warranty, providing the existing pipework condition is deemed suitable for re-use.
Cooling loads often increase subsequent to the initial installation of the air conditioning system. The Replacement VRV® (VRV®-Q) enables system capacity to be increased without changing the refrigerant piping (depending on system characteristics). For example: It is possible to install a 16 HP Replacement VRV® on the refrigerant piping of an R-22 10 HP system.
Fast installation It is not necessary to remove the existing piping and even the indoor units can remain (depending on type of indoor unit). The unit automatically charges the refrigerant and cleans the refrigerant piping. This unique Daikin feature makes the installation time even shorter.
10 HP
16 HP
1.
Limited and planned-downtime As the refrigerant piping can be maintained the installation is less intrusive and less time consuming than for a completely new system. Moreover, downtime can be carefully planned: whereas if a problem occurs when not enough reclaimed R-22 is available, a long and unplanned downtime can be the result.
2.
Limited and phased investment cost It is possible to spread the various stages of replacement over a certain period of time because the indoor units can remain in many cases. The air conditioning replacement therefore, can be incorporated in the general refurbishment schedule of the building and the investment cost can be spread. A further reduction in installation cost can be achieved by maintaining the old refrigerant copper pipe work.
No restrictions on system history
1. Keep main piping
2. Add indoor units
Environmental awareness R-410A not only has a zero ozone depletion potential, it is also proven to be more energy efficient than R-22.
High efficiency
As a result of the combined automatic charging and refrigerant pipe cleaning function, it is possible to ensure a clean piping network, even when a compressor breakdown has previously occurred.
Upgrading an old R-22 system to a Replacement VRV® system will result in increased system efficiency. Efficiency gains of more than 40% can be realised, by virtue of technological developments in heat pump technology and the more efficient R-410A refrigerant. Increased energy efficiency equals lower energy consumption, subsequent lower energy costs and lower CO2 emissions.
EER of a 10 HP system
COP of a 10 HP system
4.50
4.00
3.50
3.00
3.98
2.50
3.10
2.00
2.37
1.50
R-22
R-407C
VRV®-Q
40% More efficient
4.00 3.00
R-22
3.10
R-407C
VRV®-Q
25% More efficient
R-22: RSXY10KA7 R-407C: RSXYP10L7 R-410A: RQYQ280P
129 2515_BOOK_VRV_2011.indb 129
24/03/2011 12:23
Specifications HEAT RECOVERY RQCEQ-P
280 RQEQ140P
Outdoor unit modules
360
2
RQEQ180P
2
460
500
2
1
1
2
540
636
3
Capacity Power input
HP
10
13
16
18
20
744
1
1
816
848
2
1
3
1
2
3
4
22
24
26
28
30
RQEQ212P Capacity range
712
1
cooling
nom.
kW
28.0
36.0
45.0
50.0
54.0
63.6
71.2
74.4
81.6
84.8
heating
nom.
kW
32.0
40.0
52.0
56.0
60.0
67.2
78.4
80.8
87.2
89.6
cooling
nom.
kW
7.04
10.3
12.2
13.9
15.5
21.9
21.2
23.3
27.1
29.2
heating
nom.
kW
8.00
10.7
13.4
14.7
16.1
17.7
20.7
21.2
23.1
23.6
EER
cooling
3.98
3.48
3.77
3.61
3.48
2.90
3.36
3.19
3.01
2.90
COP
heating
4.00
3.72
3.89
3.80
3.72
3.79
3.80
3.81
3.77
3.79
Max n° of indoor units to be connected Indoor index connection
Dimensions
minimum
20
26
29
33
36
40
43
47
50
162.5
200
225
250
275
300
325
350
375
standard
250
325
400
450
500
550
600
650
700
750
maximum
325
422.5
520
585
650
715
780
845
910
975
unit
height
mm
width
mm
depth
mm
Weight Sound pressure
16 125
1680 635+ 635
nom.
dBA
635+ 635+ 635+ 635 765
kg cooling
635+ 635+ 635
175+ 175 57
175+ 175+175 61
61
62
air flow rate (nominal at 230V)
175+175 +175+179
175+175 +179+179
175+179 +179+179
179+179+ 179+179
64
63
64
65
66
63
type Fan
179+ 179+179 Propeller
cooling
external static pressure (max.)
m3/min
95+ 95
95+ 95 + 110
110+110
95+ 110+110
110+ 110 + 110
Pa
motor
type
Operation range
cooling
min. - max.
°CDB
-5~43
heating
min. - max.
°CWB
-20~15.5
Hermetically sealed scroll compressor
type
R-410A
charge
kg
10.3+ 10.3
liquid
mm
9.52
gas
mm
22.2
discharge gas
mm
pressure equiliser tube
mm
max. total length
m
10.6+ 10.6
10.3+10.3 +10.6
10.3+10.6 +10.6
control
Piping connections
110+ 110+ 110+ 110
78
Compressor
Refrigerant
95+ 110+ 110+ 110
10.6+10.6 +10.6
11.2+11.2 +11.2
10.3+10.6 +10.6+11.2
10.3+10.6 +11.2+11.2
10.6+11.2 +11.2+11.2
11.2+11.2 +11.2+11.2
Electronic expansion valve 12.7
15.9
25.4 19.1
-
19.1
28.6
34.9
22.2 -
-
25.4
-
-
-
-
28.6 -
-
-
300
max. length between
OU-IU
m
120 (actual length)
level difference
OU-IU
m
50 (outdoor unit in highest position)
Power Supply
3~. 400V. 50Hz
Notes: Nominal cooling capacities are based on : indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 7.5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Accessories VRV®III-Q - REPLACEMENT VRV® - Heat recovery
RQCEQ460PY1 RQCEQ500PY1
RQCEQ280PY1 RQCEQ360PY1
Fixing box Outdoor unit multi connection piping kit
RQCEQ540PY1 RQCEQ636PY1
RQCEQ712PY1 RQCEQ744PY1 RQCEQ816PY1 RQCEQ848PY1
KJB111A BHFP26P36C
BHFP26P63C
BHFP26P84C
130 2515_BOOK_VRV_2011.indb 130
24/03/2011 12:23
HEAT PUMP Outdoor system System Capacity range Cooling capacity Heating capacity Power input - 50Hz
RQYQ140P *RQYQ8P *RQYQ10P *RQYQ12P *RQYQ14P *RQYQ16P *RQYQ18P *RQYQ20P *RQYQ22P *RQYQ24P *RQYQ26P *RQYQ28P *RQYQ30P
Outdoor unit module 1 Outdoor unit module 2 Nom. Nom. Cooling Heating
RQYQ140P RQYQ8P
HP kW kW kW kW
Nom. Nom.
EER COP Maximum number of connectable indoor units Dimensions Unit HeightxWidthxDepth mm Weight Sound pressure level Operation range Refrigerant Piping connections
Power supply
Unit Cooling Cooling Heating Type Liquid Gas Piping length Total piping length Level difference
kg dBA °CDB °CWB
Nom. Min.~Max. Min.~Max.
OD OD Max. System OU - IU IU - IU Phase / Frequency / Voltage
OU - IU Actual Max.
mm mm m m m m Hz / V
5 14.0 16.0 3.36 3.91 4.17 4.09 10 1,680x635 x765 175 54 -5~43 -20~16 R-410A 9.5 15.9 120 300 50/40 15 3~ / 50 / 400
8 22.4 25 5.24 6.42 4.27 3.89 17
RQYQ10P RQYQ12P RQYQ14P RQYQ16P RQYQ8P RQYQ8P RQYQ10P RQYQ12P RQYQ10P RQYQ12P RQYQ14P RQYQ10P RQYQ12P RQYQ12P RQYQ12P RQYQ16P RQYQ16P RQYQ16P 10 12 14 16 18 20 22 24 26 28 30 28 33.5 40 45 50.4 55.9 61.5 67 73 78.5 85 31.5 37.5 45 50 56.5 62.5 69 75 81.5 87.5 95 7.64 10.10 11.6 13.6 12.9 15.4 17.8 20.2 21.3 23.7 25.2 8.59 10.20 12.2 13.6 15.1 16.7 18.8 20.4 22.2 23.8 25.8 3.66 3.32 3.45 3.31 3.91 3.63 3.46 3.32 3.43 3.31 3.37 3.67 3.68 3.69 3.68 3.74 3.74 3.67 3.68 3.67 3.68 3.68 21 26 30 34 39 43 47 52 56 60 64 1,680x930x765 1,680x1,240x765 -
230 57
284
381
58
-
60
61
62
63
-5~43 -20~15.5 R-410A 9.5 19.1
12.7
15.9
22.2
19.1
28.6
34.9
150 300 50 (Outdoor unit in highest position)/ 40 (Indoor unit in highest position) 15 3~ / 50 / 400
Notes: Nominal cooling capacities are based on : indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 7.5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
HEAT PUMP Outdoor system System
Cooling capacity Heating capacity Power input - 50Hz
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Nom. Nom. Cooling Nom. Heating Nom.
EER COP Maximum number of connectable indoor units Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Piping connections Liquid OD Gas OD Piping length Max. OU - IU Total piping length System Actual Level difference OU - IU IU - IU Max. Power supply Phase / Frequency / Voltage
kW kW kW kW
dBA °CDB °CWB mm mm m m m m Hz / V
*RQYQ32P
*RQYQ34P
*RQYQ36P
*RQYQ38P
*RQYQ40P
*RQYQ42P
*RQYQ44P
*RQYQ46P
*RQYQ48P
RQYQ16P RQYQ16P 90 100 27.2 27.2 3.31 3.68
RQYQ10P RQYQ10P RQYQ14P 96 108 26.9 29.4 3.57 3.67
RQYQ10P RQYQ10P RQYQ16P 101 113 28.9 30.8 3.49 3.67
RQYQ10P RQYQ12P RQYQ16P 107 119 31.4 32.4 3.41 3.67
RQYQ12P RQYQ12P RQYQ16P 112 125 33.8 34.0 3.31 3.68 64
RQYQ10P RQYQ16P RQYQ16P 118 132 34.9 35.8 3.38 3.69
RQYQ12P RQYQ16P RQYQ16P 124 138 35.3 36.0 3.51 3.83
RQYQ14P RQYQ16P RQYQ16P 130 145 38.8 39.4 3.35 3.68
RQYQ16P RQYQ16P RQYQ16P 135 150 40.8 40.8 3.31 3.68
63
64
65 -5~43 -20~15.5 R-410A 19.1
34.9
41.3 150 300 50 (Outdoor unit in highest position)/ 40 (Indoor unit in highest position) 15 3~ / 50 / 400
Notes: Nominal cooling capacities are based on : indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 7.5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Accessories VRV®III-Q - REPLACEMENT VRV® - Heat pump
RQYQ8~16P
RQYQ140P
Cool / Heat selector Fixing box Outdoor unit multi connection piping kit
RQYQ18~32P
RQYQ34~48P
BHFP22P100
BHFP22P151
KRC19-26A KJB111A -
-
131 2515_BOOK_VRV_2011.indb 131
24/03/2011 12:23
Achieve the highest energy efficiency levels in the industry Cooling
Cooling
Extracted Heat
Extracted Heat
VRV Heat Recovery System
Heating
Hot Water
Ventilation
Door Curtain
VRV®III Heat Recovery systems deliver energy efficiency levels of up to 91 VRV®III Heat Recovery is the all-in-one solution to maximise energy efficiency. A fully integrated system for heating, cooling, air curtains and hot water – to help achieve zero waste heat. • Free extracted heat from areas being cooled is diverted to areas requiring heat – to minimise operating costs. • Reclaimed heat can be used to power door air curtains and even hot water supplies. • Numerous heat recovery options, with 14 different types of indoor units available. • Suitable for all size of systems: a single outdoor unit (11kW to 170kW) can connect up to 64 indoor units.
your comfort. our world.
For more information please visit www.daikin.co.uk/heat-recovery
Midlands Region
Northern Region
North London
Central London
South London
0845 641 9370
0845 641 9340
0845 641 9360
0845 641 9350
0845 641 9355
1
Scotland Region 0845 641 9330
Western Region 0845 641 9320
REYQ8P8 model at 50% cooling – 50% heating load in conditions: outdoor temperature 11° CDB, indoor temperature: 18° CWB, 22°CDB
132 2515_BOOK_VRV_2011.indb 132
24/03/2011 12:23
REY(H)Q-P
VRV III inverter heat recovery high COP combination ®
REYHQ24P
• Only those areas calling for air conditioning need to be cooled or heated and the system can be shut down completely in unoccupied rooms • Quick cool/heat change over • Improved refrigerant containment check • Extra low noise during night time operation (step 1: 50dBA; step 2: 45dBA) • Possibility to extend the operation range in cooling down to -20°C
• Heat recovery operation can provide energy efficiency levels in excess of 9.0 • Top energy efficiency in Daikin heat recovery range, with high rate of ECA qualification • Wide range of indoor units: 13 different models in a total of 75 variations • Continuous heating during defrost (resulting in a higher integrated heating capacity) • Easy installation thanks to automatic refrigerant charging operation, automatic test operation • Increased piping flexibility: maximum piping length: 165m, increased total piping length: 1,000m • The ability to control each conditioned zone keeps VRV®III system running costs to an absolute minimum
COP
4.5 4.4 4.3 4.2 4.1 4 3.9 3.8
8
10
12
16
18
20
22
24
HP
COP – Daikin Hi COP VRV COP – Other leading brand Hi COP VRV
heat RECOVERY Outdoor units Independent unit Capacity range Capacity Power Input (Nominal) EER COP Dimensions Weight Sound Level Operation Range Refrigerant Power Supply Piping connections
INVERTER
Outdoor Unit Outdoor Unit Cooling Heating Cooling Heating Cooling Heating (Height x Width x Depth) Unit Sound Power Cooling Sound Pressure Cooling Cooling Min~Max Heating Min~Max
Liquid (OD) Gas Max total length Max n° of indoor units to be connected
HP kW kW kW kW
mm kg dBA dBA °CDB °CWB
8 REYQ8P8 REYQ8P8 8 22.4 25.0 5.20 5.71 4.31 4.38
10 REYQ10P8 REYQ10P8 10 28.0 31.5 7.09 7.38 3.95 4.27 1,680 x 1,300 x 765
12 REYQ12P8 REYQ12P8 12 33.5 37.5 8.72 8.84 3.84 4.24
16 REMQ8P9 REMQ8P9Y1B 16 45.0 50.0 10.5 11.5 4.29 4.36
18 REMQ8P9 REMQ10P9 18 50.4 56.5 12.7 13.4 3.98 4.22
20 REMQ8P9 REMQ12P9 20 56.0 62.5 13.9 14.3 4.04 4.36 85 64
331 78
78
80
82
81
58
58
60
62
61
22 REMQ10P8 REMHQ12P8 22 61.5 69.0 16.0 16.3 3.84 4.24
24 REMHQ12P8 REMHQ12P8 24 67.0 75.0 17.2 17.2 3.89 4.37
85 64
87 66
-5.0~43.0 -20.0~15.0 R-410A 3~/380-415V/50Hz
3~/400V/50Hz 12.7
mm mm m
15.9 28.6
-
26
34.9 1000 32
35
39
133 2515_BOOK_VRV_2011.indb 133
24/03/2011 12:23
REYQ-P8/P9
VRV III heat recovery compact combination ®
REYQ46-48P8Y1B
• Increased EER/COP thanks to the redesigned 8 and 12HP stand alone units and 8HP modular unit • Its operation range for example 8hp to 48hp in 2hp increment steps (21 system combinations), is wider than any of its contemporaries • Its ability to run no less than 64 indoor units in heat recovery format cannot at present be matched by other comparable systems • Continuous heating during defrost (resulting in a higher integrated heating capacity) • Easy installation thanks to automatic refrigerant charging operation, automatic test operation • Increased piping flexibility: maximum piping length: 165m, increased total piping length: 1,000m • The ability to control each conditioned zone keeps VRV®III system running costs to an absolute minimum • Only those areas calling for air conditioning need to be cooled or heated and the system can be shut down completely in unoccupied rooms
REYQ-P8
8
REYQ8P9 REYQ10P8 REYQ12P9 REYQ14P8 REYQ16P8 REMQ8P9 Modular units REMQ10P8 REMQ12P8 REMQ14P8 REMQ16P8 Number of outdoor units
1
1
REYQ-P8
30
Stand alone units
REYQ8P9 REYQ10P8 REYQ12P9 REYQ14P8 REYQ16P8 REMQ8P9 Modular units REMQ10P8 REMQ12P8 REMQ14P8 REMQ16P8 Number of outdoor units
10
12
14
• Quick cool/heat change over • Improved refrigerant containment check function • Flexible combination of outdoor units: Small footprint combination, high COP combination or any other combination of your choice
16
18
20
22
24
26
28
1 Not Applicable
1 1 1 1 1
1
Not Applicable
1
1
32
1
34
1
2
38
36
40
1
1 1
2
2
2
2
42
1
44
1 1 2
1 2
46
48
1 2 3
3 3
Stand alone units
Not Applicable
1 1 1 1 2
2 2
1 3
1 1
1 1
2
1
1 3
1 3
1 3
1 2 3
2 3
134 2515_BOOK_VRV_2011.indb 134
24/03/2011 12:23
REYQ-P8/P9 VRV®III heat recovery
heat recovery REYQ-P8 Capacity range Capacity Power Input (Nominal) EER COP Dimensions Weight Sound Level Operation Range
Cooling Heating Cooling Heating
(Height x Width x Depth) Sound Power Sound Pressure Cooling Heating
8 8 22.4 25.0 5.20 5.71 4.31 4.38
10 10 28.0 31.5 7.09 7.38 3.95 4.27
78 58
331 78 58
9.52 / 19.1
9.52 / 22.2
HP kW kW kW kW
Cooling Cooling Min~Max Min~Max
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas Max Total Length
mm kg dBA dBA o CDD o CWB
mm m
12 12 33.5 37.5 8.72 8.84 3.84 4.24 1,680x1,300x765
14 14 40.0 45.0 11.4 11.0 3.51 4.09
80 60 -5~43 -20~15 R-410A 3~/380-415V/50Hz -
83 62
16 16 45.0 50.0 14.1 12.8 3.19 3.91 339 84 63
12.7 / 28.6 1000
heat recovery REYQ-P8 Capacity range Capacity Power Input (Nominal) EER COP Dimensions Weight Sound Level Operation Range
HP kW kW kW kW
Cooling Heating Cooling Heating
(Height x Width x Depth) Sound Power Sound Pressure Cooling Heating
Cooling Cooling Min~Max Min~Max
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas Max Total Length
mm kg dBA dBA o CDD o CWB
18 18 50.4 56.5 12.7 13.4 3.98 4.22
20 22 20 22 55.9 61.5 62.5 69.0 14.9 17.0 15.2 17.1 3.76 3.62 4.11 4.04 1,680x930 + 930x765 204 + 254
81 61
254 + 254 83 62
83 63
15.9 / 28.6
mm m
24 24 67.0 75.0 19.2 18.9 3.49 3.97
83 63
26 28 26 28 73.0 78.5 81.5 87.5 21.6 23.8 20.6 22.3 3.38 3.30 3.96 3.92 1,680x930 + 1,240x765 254 + 334 83 83 63 63
-5~43 -20~15 R-410A 3~/380-415V/50Hz 15.9 / 34.9 1000
30 32 30 32 85.0 90.0 95.0 100.0 26.6 28.4 24.2 25.8 3.20 3.17 3.93 3.88 1,680x1,240 + 1,240x765 334 + 334 83 83 63 63
19.1 / 34.9
heat recovery REYQ-P8 Capacity range Capacity Power Input (Nominal) EER COP Dimensions Weight Sound Level Operation Range
HP kW kW kW kW
Cooling Heating Cooling Heating
(Height x Width x Depth) Sound Power Sound Pressure Cooling Heating
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas Max Total Length
Cooling Cooling Min~Max Min~Max
mm kg dBA dBA o CDD o CWB
mm m
34 34 95.4 107.0 26.9 26.3 3.55 4.07
36 38 40 36 38 40 101.0 107.0 112.0 113.0 119.0 125.0 29.1 31.2 33.4 28.1 30.0 31.8 3.47 3.43 3.35 4.02 3.97 3.93 1,680x930 + 930 + 1,240x765 204 + 254 + 334 254 + 254 + 334 84 85 85 85 64 64 65 65
42 44 42 44 118.0 124.0 132.0 138.0 35.8 38.0 33.5 35.2 3.30 3.26 3.94 3.92 1,680x930 + 1,240 + 1,240x765 254 + 334 + 334 85 85 65 65
46 48 46 48 130.0 135.0 145.0 150.0 40.8 42.6 37.1 38.7 3.19 3.17 3.91 3.88 1,680x1,240 + 1,240 + 1,240x765 334 + 334 + 334 85 85 65 65
-5~43 -20~15 R-410A 3~/380-415V/50Hz 19.1 / 41.3 1000
19.1 / 34.9
135 2515_BOOK_VRV_2011.indb 135
24/03/2011 12:23
BSVQ-P8
Individual branch selector for VRV® heat recovery
BSV4/6Q-PV
Multi branch selector for VRV® heat recovery
BSVQ100P8
BSVQ-P8 • High comfort levels: individual control and change over of 1 group of indoor units • Maximum design flexibility because individual and multi boxes can be combined in one system • Low built-in height • No drain piping needed • Allows multi tenant applications (option PCB required)
Maximum capacity index of connectable indoor units
BSVQ100P8
BSVQ160P8
20 < x ≤ 100
100 < x ≤ 160
Maximum number of connectable indoor units Power input Dimensions
160 < x ≤ 250
5
8
Cooling
kW
Heating
kW
0.005
(Height x Width x Depth)
mm
207 x 388 x 326
Weight Piping connections
BSVQ250P8
0.005
kg Outdoor unit
Liquid / gas / discharge gas
Type ∅ mm
Indoor unit
Liquid / gas
Type ∅ mm
12
15 Brazing connection
9.52 / 15.9 / 12.7
9.52 / 22.2 / 19.1 Brazing connection
9.52 / 15.9
Power Supply
9.52 / 22.2 1~/220-240V/50Hz
BSV4/6Q-PV • Rapid installation resulting from less brazing points and wiring • High comfort levels: individual control and change over of up to 4 or 6 groups of indoor units • Maximum design flexibility because individual and multi boxes can be combined in one system • Low built-in height • No drain piping needed
BSV4Q100PV
BSV4Q100PV Maximum capacity index of connectable indoor units
BSV6Q100PV
400
Maximum capacity index of connectable indoor units per branch
600 100
Number of branches
4
6
Maximum number of connectable indoor units
20
30
Maximum number of connectable indoor units per branch Power input Dimensions
kW
0.020
Heating
kW
0.020
0.030
(Height x Width x Depth)
mm
209 x 1,053 x 635
209 x 1,577 x 635
kg
60
Weight Piping connections
5
Cooling
Outdoor unit
Liquid / gas / discharge gas
Type ∅ mm
Indoor unit
Liquid / gas
Type ∅ mm
0.030
89 Brazing connection
12.7 x 28.6 x 19.1
15.9 x 28.6 x 28.6 Brazing connection 9.5 / 15.9
Power Supply
1~/220-240V/50Hz
136 2515_BOOK_VRV_2011.indb 136
24/03/2011 12:24
RXHQ-P
VRV®III heating only
RXHQ44-46-48P
• Compact size leaves maximum floor space • High external static pressure (up to 78.4Pa) allows indoor installation • Wide piping flexibility: maximum piping length: 165m, total piping length: 1,000m • All indoor units can be individually controlled • Phased installation possible
• Cost effective, low energy consumption heating system • Lower CO2 emissions compared to traditional heating systems • Easy installation thanks to automatic refrigerant charging and automatic testing • Easy compliance with F-gas regulation thanks to automated refrigerant containment check • Flexible combination of outdoor units
INVERTER
Heating only Outdoor system Capacity range Heating capacity Nom. Power input - 50Hz Heating Nom. COP Maximum number of connectable indoor units Dimensions Unit HeightxWidthxDepth Weight Unit Operation range Heating Min.~Max. Refrigerant Type Piping connections Liquid OD Gas OD Total piping length System Actual Level difference OU - IU Power supply Phase / Frequency / Voltage Outdoor system System Outdoor unit module 1 Outdoor unit module 2 Capacity range Heating capacity Nom. Power input - 50Hz Heating Nom. COP Maximum number of connectable indoor units Operation range Heating Min.~Max. Refrigerant Type Piping connections Liquid OD Gas OD Total piping length System Actual Level difference OU - IU Power supply Phase / Frequency / Voltage Outdoor system System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Heating capacity Nom. Power input - 50Hz Heating Nom. COP Maximum number of connectable indoor units Operation range Heating Min.~Max. Refrigerant Type Piping connections Liquid OD Gas OD Total piping length System Actual Level difference OU - IU Power supply Phase / Frequency / Voltage
HP kW kW
mm kg °CWB mm mm m m Hz / V
8 8 25.0 5.56 4.5 17 187
12 12 37.5 9.44 3.97 26
16 16 50.0 12.90 3.88 34 1,680x1,240x765
18 18 56.5 15.30 3.69 39
316
324
-20.0~15.0 R-410A 9.5 19.1
22.2
12.7 28.6
12.7
15.9 28.6
1,000 50 (outdoor unit in highest position) (optional: 90) 3N~ / 50 / 400 22 RXHQ10P RXHQ12P 22 69.00 17.08 4.04 47
20 62.50 14.95 4.18 43
24 RXHQ12P
26 RXHQ8P
28 RXHQ10P
24 75.00 18.89 3.97 52
26 81.50 20.69 3.94 56
28 88.00 22.98 3.83 60 -20.0~15.0 R-410A
°CWB mm mm m m Hz / V
HP kW kW
14 14 45.0 11.30 3.98 30
240
20 RXHQ8P HP kW kW
10 10 31.5 7.70 4.09 21 1,680x930x765
30 32 RXHQ12P RXHQ14P RXHQ18P 30 32 94.00 102.00 24.67 26.63 3.81 3.83
34 RXHQ16P
36 RXHQ18P
34 107.00 28.23 3.79
36 113.00 30.62 3.69
64
15.9
19.1
28.6
34.9
41.3
1,000 50 (outdoor unit in highest position) (optional: 90) 3N~ / 50 / 400 38 RXHQ8P
40 RXHQ10P RXHQ12P
42 RXHQ12P
38 119.00 30.13 3.95
40 126.00 32.39 3.89
42 132.00 34.20 3.86
°CWB mm mm m m Hz / V
44 RXHQ8P
46 RXHQ10P
48 50 RXHQ12P RXHQ14P RXHQ18P
RXHQ18P 46 48 145.00 151.00 38.26 39.95 3.79 3.78 64 -20.0~15.0 R-410A 19.1 41.3 1,000 50 (outdoor unit in highest position) (optional: 90) 3N~ / 50 / 400 44 138.00 35.94 3.84
50 158.00 41.91 3.77
52 RXHQ16P
54 RXHQ18P
52 163.00 43.47 3.75
54 170.00 45.95 3.70
137 2515_BOOK_VRV_2011.indb 137
24/03/2011 12:24
RXYHQ-P9
VRV III inverter heat pump high COP combination ®
• Connectable to current Daikin control systems: DS-net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF • Easy installation thanks to automatic refrigerant charging operation, automatic test operation • Refrigerant containment check function
• Top energy efficiency in Daikin heat pump range, thanks to the redesigned 8HP unit and newly developed 12HP high COP unit • Wide range of indoor units: 13 different models in a total of 75 variations • Compact size of outdoor units • Increased external static pressure: up to 78.4Pa • 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA • RoHS compliant • Easy combination with HRV
4.60 4.50 4.40
+ 13%
4.30
COP
4.20 4.10 4.00 3.90 3.80 3.70 12
16
18
20
22
24
26
28
30
32
34
36
New high COP range previous high COP range
RXYQ-P9 Modules
12 RXYQ8P9 RXYQ10P9 RXYHQ12P9
16
18
20
2
1 1
1
1
22
1
1 1
heat pump Outdoor Units Capacity range Capacity Power input (nominal) EER COP Dimensions Sound Level Operation Range
26
28
30
32
3
2 1
1 2
1 1 1
1
34
36
2
1 2
3
28 28 78.4 88.0 19.0 19.8 4.12 4.44
30 30 84.0 94.5 21.2 21.9 3.96 4.31
32 32 89.4 100.0 22.4 22.7 3.99 4.40
34 34 95.0 107.0 24.7 24.9 3.85 4.79
36 36 101.0 113.0 25.9 25.9 3.89 4.37
83 63
83 63
85 64
85 64
85 65
45
48 19.1 / 34.9
52
55
58 19.1 / 41.3
INVERTER
Cooling Heating Cooling Heating
HP kW kW kW kW
(Height x Width x Depth) Sound Power Cooling Sound Pressure Cooling Cooling Min~Max Heating Min~Max
mm dBA dBA °CDB °CWB
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
24
mm m
12 12 33.5 37.5 8.6 8.6 3.89 4.37
16 16 44.8 50.0 10.4 11.1 4.29 4.50
18 18 50.4 56.5 12.6 13.2 4.00 4.27
20 20 56.0 63.0 13.8 14.3 4.05 4.42
22 22 61.5 69.0 16.0 16.3 3.84 4.24
82 60
82 61
83 62
83 62
29
32 15.9 / 28.6
35
1680x1240x765
80 60
19 26 12.7 / 28.6 12.7 / 28.6
24 24 67.2 75.0 15.7 16.7 4.29 4.50
26 26 72.8 81.5 17.8 18.8 4.09 4.34 83 83 62 62 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 39 42 15.9 / 34.9 1000
138 2515_BOOK_VRV_2011.indb 138
24/03/2011 12:24
RXYQ-P9
VRV III inverter heat pump small footprint combination ®
RXYQ44P8 RXYQ46-48P7
• Increased EER/COP thanks to the redesigned 8HP unit • Outdoor unit capacity up to 54 HP • Wide range of indoor units: 13 different models in a total of 75 variations • Flexible combination of outdoor units: small footprint combination, high COP combination or any other combination of your choice • Compact size of outdoor units • Increased external static pressure: up to 78.4Pa • 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA • RoHS compliant
RXYQ-P9
5
RXYQ5P9
1
8
10
• Easy combination with HRV • Connectable to current Daikin control systems: DS-net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF • Easy installation thanks to automatic refrigerant charging operation, automatic test operation • Refrigerant containment check function
12
14
16
18
1
RXYQ8P9
26
28
30
1 1
1
1
1
1
2
1
1
RXYQ14P9
1
RXYQ16P9
1
1
RXYQ18P9
32
34
36
38
40
RXYQ5P9
42
44
46
48
50
1
1
52
54
Not applicable
1
RXYQ8P9
1 1
RXYQ10P9 1
RXYQ12P9
1
1 2
1
1
1 1
RXYQ16P9 RXYQ18P9
24
1
RXYQ12P9
RXYQ14P9
22
1
RXYQ10P9
RXYQ-P9
20
Not applicable
1
1
1 2
1
1
1
2
2
2
2
2
3
139 2515_BOOK_VRV_2011.indb 139
24/03/2011 12:24
RXYQ-P9
VRV III inverter heat pump small footprint combination ®
heat pump Outdoor units Capacity range Capacity Power input (nominal) EER COP Dimensions Weight Sound Level Operation Range
HP kW kW kW kW
Cooling Heating Cooling Heating
(Height x Width x Depth) Sound Power Sound Pressure Cooling Heating
Cooling Cooling Min~Max Min~Max
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas Max. total length
mm kg dBA dBA CDB CWD
mm m
5 5 14.0 16.0 3.52 4.00 3.98 4.00 1,680x635x765 159 72 54
8 8 22.4 25.0 5.22 5.56 4.29 4.50
10 10 28.0 31.5 7.42 7.70 3.77 4.09 1,680x930x765
187
12 12 33.5 37.5 9.62 9.44 3.48 3.97
14 14 40.0 45.0 12.4 11.30 3.23 3.98
240
316
78 57
8 9.52 / 15.9
16 9.52 / 22.2
-5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 19
23 12.7 / 28.6
18 18 49.0 56.5 16.2 15.30 3.02 3.69 324 83 63
80 60
58
13 9.52 / 19.1
16 16 45.0 50.0 14.2 12.90 3.17 3.88 1,680x1,240x765
26
29 15.9 / 28.6
1000
heat pump Outdoor units Capacity range Capacity Power input (nominal) EER COP Dimensions Weight Sound Level Operation Range
HP kW kW kW kW
Cooling Heating Cooling Heating
(Height x Width x Depth) Sound Power Sound Pressure Cooling Heating
Cooling Cooling Min~Max Min~Max
mm kg dBA dBA CDB CWD
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas
mm
Max. total length
m
20 20 55.9 62.5 14.7 14.9 3.80 4.18
22 22 61.5 69.0 17.0 17.1 3.62 4.04
24 24 67.0 75.0 19.2 18.9 3.49 3.97
26 26 71.4 81.5 20.9 20.7 3.41 3.94
83 62
83 63
83 63
85 64
35
39 15.9 / 34.9
42
32 15.9 / 28.6
28 28 77.0 88.0 23.6 23.0 3.26 3.83 85 65 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 45
30 30 82.5 94.0 25.8 24.7 3.20 3.81
32 32 89.0 102.0 28.6 26.6 3.11 3.83
34 34 94.0 107.0 30.4 28.2 3.09 3.79
36 36 98.0 113.0 32.4 30.6 3.02 3.69
85 65
85 65
85 65
86 66
49 19.1 / 34.9
52
55
58 19.1 / 41.3
48 48
50 50
52 52
54 54
132.0 151.0 42.0 40.0 3.14 3.78
138.0 158.0 44.8 41.9 3.08 3.77
143.0 163.0 46.6 43.5 3.07 3.75
147.0 170.0 48.6 45.9 3.02 3.70
87 67
87 67
87 67
88 68
1000
heat pump Outdoor units Capacity range Capacity Power input (nominal) EER COP Dimensions Weight Sound Level Operation Range
HP Cooling Heating Cooling Heating
kW kW kW kW
(Height x Width x Depth)
mm kg dBA dBA CDB CWD
Sound Power Sound Pressure Cooling Heating
Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas Max. total length
Cooling Cooling Min~Max Min~Max
38 38
40 40
42 42
44 44
105.0 119.0 30.6 30.1 3.43 3.95
111.0 126.0 33.2 32.4 3.34 3.89
116.0 132.0 35.4 34.2 3.28 3.86
120.0 138.0 36.9 35.9 3.25 3.84
86 66
86 66
86 66
87 67
61 mm m
46 46 126.0 145.0 39.8 38.3 3.17 3.79 87 67 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 64 19.1/41.3 1000
140 2515_BOOK_VRV_2011.indb 140
24/03/2011 12:24
RXYRQ-P
VRV III heat pump with connection to stylish indoor units ®
FXSQ-P VRV® indoor unit FVXS-F
FTXG-J
BPMKS967B3
FTXS-G BPMKS967B2
FTXG-J FXFQ-P9 VRV® indoor unit
FVXG-K
BPMKS967B2
• Innovative VRV® technology combined with stylish and silent indoor units • Wide range of indoor units: combine VRV® indoor units and stylish indoor units as Daikin Emura and Nexura • Up to 39 indoor units can be connected to a 18HP unit • Integrate temperature control, fresh air provision, Biddle air curtains and the production of hot water in one total solution system • High external static pressure (up to 78.4Pa) allows indoor installation • Night quiet mode in two steps: step 1: 50 dBA, step 2: 45 dBA • All indoor units can be individually controlled • Phased installation possible
RXYRQ8-12P
CONNECTABLE INDOOR UNITS Daikin Emura - Wall mounted unit Wall mounted unit Nexura - Floor standing unit Floor standing unit Flexi type unit Slim concealed ceiling unit Concealed ceiling unit 4-way blow ceiling mounted cassette (600x600) Round flow cassette Ceiling suspended cassette All VRV® indoor units in all available classes
20 class
25 class
35 class
42 class
50 class
60 class
71 class
FTXS20J -
FTXG25JW/S FTXS25J FVXG25K FVXS25F FLXS25B FDXS25E FDBQ25B FFQ25BV -
FTXG35JW/S FTXS35J FVXG35K FVXS35F FLXS35B FDXS35E FBQ35C FFQ35BV FCQ35C8 FHQ35B
FTXS42J -
FTXG50JW/S FTXS50J FVXG50K FVXS50F FLXS50B FDXS50C FBQ50C FFQ50BV FCQ50C8 FHQ50B
FTXS60G FLXS60B FDXS60C FBQ60C FFQ60BV FCQ60C8 FHQ60B
FTXS71G -
Heat PUMP Outdoor units Capacity range Cooling capacity Heating capacity Power input - 50Hz
Nom. Nom. Cooling Heating
Nom. Nom.
EER COP Maximum number of connectable indoor units Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Piping connections Liquid OD Gas OD Total piping length System Actual Level difference OU - IU Power supply Phase / Frequency / Voltage
Branch provider Max. n° of indoor units to be connected Max. indoor unit connectable capacity Dimensions Height x Width x Depth Weight
HP kW kW kW kW
dBA dBA °CDB °CWB mm mm m m Hz / V
kW mm kg
RXYRQ8P 8 22.4 25.0 5.22 5.56 4.29 4.50 17
RXYRQ10P 10 28.0 31.5 7.42 7.70 3.77 4.09 21
RXYRQ12P 12 33.5 37.5 9.62 9.44 3.48 3.97 26
RXYRQ14P 14 40.0 45.0 12.4 11.30 3.23 3.98 30 80 60
78 57
58
RXYRQ16P 16 45.0 50.0 14.2 12.90 3.17 3.88 34
RXYRQ18P 18 49.0 56.5 16.2 15.30 3.02 3.69 39 83 63
-5.0~43.0 -20.0~15.0 R-410A 9.52 19.1
12.7 22.2
15.9 28.6
135 40 (outdoor unit in highest position) 3N~ / 50 / 400
BPMKS967B2 2 14.2 (7.1 + 7.1)
BPMKS967B3 3 20.8 (6.0 + 7.1 + 7.1) 180 x 294 x 350
7.5
8
141 2515_BOOK_VRV_2011.indb 141
24/03/2011 12:24
RXYSQ-P8
VRV III-S inverter heat pump ®
• High COP values • Easy installation thanks to automatic refrigerant charging operation, automatic test operation • Wide range of indoor units • Power consumption limit setting • Small capacities - 4, 5 & 6HP • Slim & flexible design • Space saving outdoor unit
RXYSQ4-5-6PA7V(Y)1B
Heat Pump Outdoor Unit (Single Phase) Capacity range Capacity Cooling Heating Power Input (Nominal) Cooling Heating EER COP Dimensions (Height x Width x Depth) Weight Sound Level Sound Power Cooling Sound Pressure Cooling Heating Operation Range Cooling Min~Max Heating Min~Max Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas/Drain Max total length
HP kW kW kW kW
mm kg dBA dBA dBA °CDB °CWB
RXYSQ4P8V1 4 11.2 12.5 2.81 2.74 3.99 4.56
RXYSQ5P8V1 5 14.0 16.0 3.51 3.86 3.99 4.15 1,345x900x320 120 67 51 53 -5~46 -20~15.5 R-410A 1N~/220-240V/50Hz 8
66 50 52
6 mm m
9.52 / 15.9 / 26 x 3
RXYSQ6P8V1 6 15.5 18.0 4.53 4.57 3.42 3.94
69 53 55
9 9.52 / 19.1 / 26 x 3
300
Heat Pump Outdoor Unit (Three Phase) Capacity range Capacity Cooling Heating Power Input (Nominal) Cooling Heating EER COP Dimensions (Height x Width x Depth) Weight Sound Level Sound Power Cooling Sound Pressure Cooling Heating Operation Range Cooling Min~Max Heating Min~Max Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas/Drain Max total length
HP kW kW kW kW
mm kg dBA dBA dBA °CDB °CWB
RXYSQ4P8Y1 4 11.2 12.5 2.89 2.82 3.88 4.43
RXYSQ5P8Y1 5 14.0 16.0 3.61 3.97 3.88 4.03 1,345x900x320 120 67 51 53 -5~46 -20~15.5 R-410A 3N~/380-415V/50Hz 8
66 50 52
6 mm m
9.52 / 15.9 / 26 x 3
RXYSQ6P8Y1 6 15.5 18.0 4.65 4.69 3.33 3.83
69 53 55
9 9.52 / 19.1 / 26 x 3
300
142 2515_BOOK_VRV_2011.indb 142
24/03/2011 12:24
RWEYQ-P
Water cooled VRV® heat pump
• Wide condensing unit range: 10, 20 & 30HP via 1 single| refrigerant circuit • High COP values: 5.21 nominal value • Up to 32 indoor units connectable to a 30HP condensing unit • Wide range of indoor units: 13 different models in a total of 75 variations • Compact design 1000mm (H) x 780mm (W) x 550mm (D) • Operation range (inlet water temperature): 10-45°C • Connectable to current Daikin control systems: DS-net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF • Flexible piping length
RWEYQ10MY1
Actual piping length between the VRV®-WII and indoor units: 120m (Equivalent piping length: 140m)
Water piping Refrigerant piping
(Total piping length: 300m)
Level difference between indoor units: 15m
g ipin al p m Actu h 120 t leng
Level difference between the VRV®-WII and indoor units: 50m if the VRV®-WII is above 40m if the VRV®-WII is below
VRV®-WII
ng pipi ent ival 140 m u q E th leng
Indoor installation
Water piping length depends on the heat source equipment
RWEYQ-P Modules
8 RWEYQ8P RWEYQ10P
10
1
16
18
2
1 1
1
20
24
26
28
30
3
2 1
1 2
3
26 71.5 81.5 15.1 14.5 4.74 5.62
28 75.8 88.0 16.6 16.3 4.57 5.40
30 80.1 94.5 18.1 18.2 4.43 5.19
2
heat PUMP Outdoor Units Capacity Power input (nominal) EER COP Dimensions
Cooling Heating Cooling Heating
Unit
kW kW kW kW
Height Width Depth
Weight Unit Sound pressure (nominal) Cooling Inlet water temperature Cooling Min~Max Heating Min~Max Refrigerant Power supply Piping connections Liquid (OD) Gas Discharge gas Max total length Max n° of indoor units to be connected
mm mm mm kg dBA °C °C
mm mm mm m
10 26.7 31.5 6.03 6.05 4.43 5.21
8 22.4 25.0 4.55 4.24 4.92 5.90
16 44.8 50.0 9.10 8.48 4.92 5.90
780
18 49.1 56.5 10.6 10.3 4.63 5.49
20 53.4 63.0 12.1 12.1 4.41 5.21 1,000
24 67.2 75.0 13.7 12.7 4.91 5.91
780+780
780+780+780 550
149
150 51
50
9.52 19.1 13
149+149 53
150+149
16
149+149+149 150+149+149 150+150+149 150+150+150 55 56
10~45 10~45 R-410A 3~/400V/50Hz 15.9 -
12.7 22.2
150+150 54
19.1
28.6 26
29
34.9 300 32
36
36
36
36
143 2515_BOOK_VRV_2011.indb 143
24/03/2011 12:24
RWEYQ-P
Water cooled VRV® heat recovery
• Wide condensing unit range: 10, 20 & 30HP via 1 single refrigerant circuit • High COP values: 5.21 nominal value • Up to 32 indoor units connectable to a 30HP condensing unit • Wide range of indoor units: 13 different models in a total of 75 variations • Compact design 1000mm (H) x 780mm (W) x 550mm (D) • Operation range (inlet water temperature): 10-45°C • Connectable to current Daikin control systems: DS-net, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF • Flexible piping length
Stacked configuration is possible.
RWEYQ10MY1
Ceiling height
3,200mm or higher
Floor level 100-300mm
RWEYQ-P Modules
8 RWEYQ8P RWEYQ10P
10
1
16
18
2
1 1
1
20
24
26
28
30
3
2 1
1 2
3
26 71.5 81.5 15.1 14.5 4.74 5.62
28 75.8 88.0 16.6 16.3 4.57 5.40
30 80.1 94.5 18.1 18.2 4.43 5.19
2
heat RECOVERY Outdoor Units Capacity Power input (nominal) EER COP Dimensions
Cooling Heating Cooling Heating
Unit
kW kW kW kW
Height Width Depth
Weight Unit Sound pressure (nominal) Cooling Inlet water temperature Cooling Min~Max Heating Min~Max Refrigerant Power supply Piping connections Liquid (OD) Gas Discharge gas Max total length Max n° of indoor units to be connected
10 26.7 31.5 6.03 6.05 4.43 5.21
8 22.4 25.0 4.55 4.24 4.92 5.90
mm mm mm kg dBA °C °C
149
mm mm mm m
19.1 15.9
22.2 19.1
13
16
16 44.8 50.0 9.10 8.48 4.92 5.90
780
18 49.1 56.5 10.6 10.3 4.63 5.49
20 53.4 63.0 12.1 12.1 4.41 5.21 1,000
24 67.2 75.0 13.7 12.7 4.91 5.91
780+780
780+780+780 550
150 51
50
9.52
149+149 53
150+149
150+150 54
149+149+149 150+149+149 150+150+149 150+150+150 55 56
10~45 10~45 R-410A 3~/400V/50Hz 15.9
12.7
19.1
28.6 22.2 26
29
34.9 28.6 300 32
36
36
36
36
144 2515_BOOK_VRV_2011.indb 144
24/03/2011 12:24
RWEYQ-PR
Geothermal application VRV®III water cooled inverter heat pump
• Heating with ground sourced water as a renewable energy source! - Groundwater remains at a relatively constant temperature during the year - Superior efficiency remains even at extreme outdoor temperatures - Uses renewable energy: ground water, water from a lake, water from rivers • Extension of the operation range down to -10°C in heating - Add ethylene glycol to the water when the water inlet temperature is lower than 5°C - No multi combinations possible - Heat Pump and Heat Recovery systems
RWEYQ10PR
heat PUMP and heat RECOVERY Outdoor Units Independent Unit Capacity Dimensions
Outdoor Unit Cooling Heating Unit
Height Width Depth
Weight Unit Sound Pressure (Nominal) Cooling Inlet Water Temperature Cooling Heating Refrigerant Power Supply Piping connections Liquid (OD) HP / HR Gas HP / HR Discharge gas HP / HR Max total length Max n° of indoor units to be connected
INVERTER kW kW mm mm mm kg dBA °C °C
mm mm mm m
10 RWEYQ10PY1R 26.7 31.5
8 RWEYQ8PY1R 22.4 25.0 1,000 780 550
149
150 51
50
10~45 -10~45 R-410A 3~/400V/50Hz 9.52 / 9.52 - / 19.1 19.1 / 15.9
- / 22.2 22.2 / 19.1 300
13
16
145 2515_BOOK_VRV_2011.indb 145
24/03/2011 12:24
FXFQ-P9
Round flow cassette
BRC1E51
FXFQ-P9
BRC7F532
• Fresh air intake: standard knockout and optional kit • Reduced installation height: 214mm for class 20-63 • Drain-up pump with 850mm lift fitted as standard
• Modern style decoration panel in pure white with grey louvres. Also available in white with white louvres • 360° air discharge ensures uniform air flow and temperature distribution • Air discharge from the corners avoids dead zones that may be subject to temperature differences • Comfortable horizontal air discharge ensures draught free operation and prevents ceiling soiling • 23 different air flow patterns possible • Allows multi tenant applications (option PCB required)
850 mm
• Optional daily self-cleaning filter available • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
Examples of air flow patterns possible
FXFQ-P9 Indoor units Capacity Power input Dimensions Weight Air flow rate Sound power (nominal) Sound pressure Refrigerant Power supply Piping connections Decoration panel
1
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating
High/Low High/Low High/Low High/Low
Liquid (OD)/Gas/Drain (OD) Model Colour HeightxWidthxDepth Weight
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA
mm
mm kg
20 2.20 2.50
25 2.80 3.20 0.053 0.045
32 3.60 4.00
40 4.50 5.00 0.063 0.055 204x840x840
20 12.5 / 9.0 12.5 / 9.0 49.0 31.0 / 28.0 31.0 / 28.0
13.5 / 9.0 13.5 / 9.0 50.0 32.0 / 28.0 32.0 / 28.0
50 5.60 6.30 0.083 0.067 21 15.5 / 10.0 15.0 / 9.5 51.0 33.0 / 28.0 33.0 / 28.0 R-410A 1~/220-240V/50Hz
63 7.10 8.00 0.095 0.114
16.5 / 11.0 17.5 / 12.0 52.0 34.0 / 29.0 36.0 / 30.0
6.40 / 12.7 / 32 BYCQ140CW11 / BYCQ140CW1W 2 / BYCQ140CGW13 Pure white (RAL 9010) 50x950x950 / 50x950x950 / 130x950x950 5.5 / 5.5 / 11.5
80 100 9.00 11.20 10.00 12.50 0.120 0.173 0.108 0.176 246x840x840 24 23.5 / 14.5 26.5 / 17.0 23.5 / 14.5 28.0 / 17.5 55.0 58.0 38.0 / 32.0 41.0 / 33.0 38.0 / 32.0 42.0 / 34.0
125 14.00 16.00 0.258 0.246 288x840x840 26 33.0 / 20.0 33.0 / 20.0 61.0 44.0 / 34.0 44.0 / 34.0
9.5 / 15.9 / 32
Pure white standard panel with grey louvres; 2 Pure white standard panel with white louvres; 3 Pure white auto cleaning panel
146 2515_BOOK_VRV_2011.indb 146
24/03/2011 12:24
FXZQ-M9
4-way blow ceiling mounted cassette (600mmx600mm)
BRC1E51
• Extremely compact casing (575mm in width and depth) enables unit to fit flush into ceilings and match standard architectural modules, without cutting ceiling tiles • 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices • Modern style decoration panel in white (RAL9010) • Low noise operation: down to 25 dBA sound pressure level • Excellent low draught characteristics • Vertical auto-swing function moves the discharge flaps up and down for efficient air distribution throughout the room • Since the flaps can move to a 0 degree position, virtually no draught can be experienced
FXZQ-M9
BRC7E530
• Drain up pump with 750mm lift fitted as standard • Allows multi tenant applications (option PCB required) • 5 different air flow patterns: Any one of 5 air flow patterns can be freely selected between zero and 40 degrees and will then be maintained during the operational cycle of the air conditioner • Air can be discharged in any of 4 directions • Possibility to shut 1 or 2 flaps for easy installation in corners • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
Examples of air flow patterns possible 2-way blow
4-way blow
3-way blow
FXZQ-M9 Indoor units Capacity Power input Dimensions Weight Air flow rate Sound power (nominal) Sound pressure Refrigerant Power supply Piping connections Decoration panel
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling Cooling
High/Low High/Low
Liquid (OD)/Gas/Drain (OD) Model Colour HeightxWidthxDepth Weight
kW kW kW kW mm kg m³/min dBA dBA
mm
mm kg
15 1.50 1.70 286x575x575 18 8.1/7 29/25 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / 36 BYFQ60B7W1 White (Ral 9010) 55x700x700 2.7
20 2.20 2.50
25 2.80 3.20 0.073 0.064
9.00 / 7.00 47.0 30.0 / 25.0
32 3.60 4.00 0.076 0.068 286x575x575 18 9.50 / 7.50 49.0 32.0 / 26.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / 36 BYFQ60B7W1 White (Ral 9010) 55x700x700 2.7
40 4.50 5.00 0.089 0.080
50 5.60 6.30 0.115 0.107
11.00 / 8.00 53.0 36.0 / 28.0
14.00 / 10.00 58.0 41.0 / 33.0
* Note: grey cells contain preliminary data
147 2515_BOOK_VRV_2011.indb 147
24/03/2011 12:24
FXCQ-M8
2-way blow ceiling mounted cassette
BRC1E51
BRC7C62
FXCQ20,25,32M8
• Compact dimensions, can easily be mounted in a ceiling void of only 355mm
355mm • Auto-swing function ensures efficient air and temperature distribution and prevents ceiling soiling • Drain up pump with 600mm lift fitted as standard • Leaves maximum floor and wall space for furniture, decorations and fittings • Easy to clean flat suction grille • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXCQ-M8 Indoor Units Capacity Power input Dimensions Weight Air flow rate Sound power (nominal) Sound pressure Refrigerant Power supply Piping connections Decoration panel
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating
High/Low High/Low High/Low High/Low
Liquid (OD)/Gas/Drain Model Colour HeightxWidthxDepth Weight
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA
20 2.20 2.50 0.077 0.044
7.0 / 5.0 7.0 / 5.0 45.0 33.0 / 28.0 33.0 / 28.0
25 2.80 3.20
32 3.60 4.00
0.092 0.059 305x780x600 26 9.0 / 6.5 9.0 / 6.5
50 5.60 6.30 0.130 0.097 305x995x600
31
32 12.0 / 9.0 12.0 / 9.0
50.0 35.0 / 29.0 35.0 / 29.0
mm
35.5 / 30.5 35.5 / 30.5 R-410A 1~/230V/50Hz
63 7.10 8.00 0.161 0.126 305x1,180x600 35 16.5 / 13.0 16.5 / 13.0 52.0 38.0 / 33.0 38.0 / 33.0
6.35 / 12.7 / 32 BYBC32GJW1
mm kg
40 4.50 5.00
BYBC50GJW1 White (10Y9/0.5) 53x1245x680 8.5
53x1030x680 8.0
80 125 9.00 14.00 10.00 16.00 0.209 0.256 0.176 0.223 305x1,670x600 47 48 26.0 / 21.0 33.0 / 25.0 26.0 / 21.0 33.0 / 25.0 54.0 60.0 40.0 / 35.0 45.0 / 39.0 40.0 / 35.0 45.0 / 39.0
BYBC63GJW1
9.5 / 15.9 / 32 BYBC125GJW1
53x1430x680 9.5
53x1920x680 12.0
148 2515_BOOK_VRV_2011.indb 148
24/03/2011 12:24
FXKQ-MA
Ceiling mounted corner cassette
BRC1E51
FXKQ63MA
BRC4C61
• Slim design 215mm height • Auto-swing function ensures efficient air and temperature distribution • Choice between 3 auto-swing positions for maximum comfort: standard, draught prevention, ceiling soiling prevention • Optimum air flow conditions are created by either downward air discharge or frontal air discharge (via optional grille) or a combination of both • Leaves maximum floor and wall space for furniture, decorations and fittings • Drain up pump with 500mm lift fitted as standard • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
Downward discharge
Frontal discharge
Closed decoration panel Combination
FXKQ-MA Indoor units Capacity Power input Dimensions Weight Air flow rate Sound pressure Refrigerant Power supply Piping connections Decoration panel
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling
High/Low High/Low
kW kW kW kW mm kg m³/min dBA
FXKQ25MAVE 2.80 3.20
FXKQ32MAVE 3.60 4.00
FXKQ40MAVE 4.50 5.00 0.076 0.056
0.066 0.046 215x1,110x710 31 11.00 / 9.00 38.0 / 33.0
13.00 / 10.00 40.0 / 34.0
FXKQ63MAVE 7.10 8.00 0.105 0.085 215x1,310x710 34 18.00 / 15.00 42.0 / 37.0
R-410A 1~/220-240V/50Hz Liquid (OD)/Gas/Drain Model Colour HeightxWidthxDepth Weight
mm
6.4 / 12.7 / 32 BYK45FJW1
mm kg
70x1240x800 8.5
9.5 / 15.9 / 32 BYK71FJW1 White 70x1440x800 9.5
149 2515_BOOK_VRV_2011.indb 149
24/03/2011 12:24
FXDQ-M9
Concealed ceiling unit (small)
BRC1E51
BRC4C62
FXDQ20,25M9
• Designed for hotel bedrooms • Compact dimensions (230mm high & 652mm deep), can easily be mounted in a ceiling void • The air suction direction can be altered from rear to bottom suction • Air suction filter fitted as standard • For easy mounting, the drain pan can be located to the left or the right of the unit • Allows multi tenant application • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXDQ-M9 Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Refrigerant Power Supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating
High/Low High/Low High/Low High/Low
Liquid (OD)/Gas/Drain (OD)
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA
20 2.20 2.50
25 2.80 3.20 0.050 0.050 230x502x652 17
6.70 / 5.20 6.70 / 5.20
7.40 / 5.80 7.40 / 5.80 50.0 37.0 / 32.0 37.0 / 32.0 R-410A 1~/230V/50Hz 6.4 / 12.7 / 27.2
mm
150 2515_BOOK_VRV_2011.indb 150
24/03/2011 12:24
FXDQ-P7
Slim concealed ceiling unit
BRC1E51
BRC4C65
FXDQ20-32P7
• Slim design for flexible installation • Compact dimensions, can easily be mounted in a ceiling void of only 240mm • 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices • Low noise: down to 29dBA sound pressure level • Adjustable external static pressure • Optional discharge flanger available • Drain up pump with 750mm lift fitted as standard • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
200mm
FXDQ-P7 Indoor Units Capacity Power input Dimensions Weight Air flow rate External static pressure Sound pressure Refrigerant Power supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling High/Standard Cooling
HH/H/L HH/H/L
Liquid (OD)/Gas/Drain (OD)
kW kW kW kW mm kg m³/min Pa dBA
mm
15 1.5 1.7 200x700x620 23.0 - / 7.5 / 6.5 29 / 28 / 27 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / 26.0
20 2.20 2.50
25 2.80 3.20 0.086 0.067 200x700x620 23.0 8.0 / 7.2 / 6.4 30 / 10 33.0 / 31.0 / 29.0
32 3.60 4.00 0.089 0.070
40 4.50 5.00 0.160 0.147
50 5.60 6.30 0.165 0.152
200x900x620 27.0 28.0 10.5 / 9.5 / 8.5 12.5 / 11.0 / 10.0 44 / 15 34.0 / 32.0 / 30.0 35.0 / 33.0 / 31.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / 26.0
63 7.10 8.00 0.181 0.168 200x1,100x620 31.0 16.50 / 14.5 / 13.00 36.0 / 34.0 / 32.0
9.5 / 15.9 / 26.0
* Note: grey cells contain preliminary data
151 2515_BOOK_VRV_2011.indb 151
24/03/2011 12:24
FXSQ-P
Concealed ceiling unit
BRC1E51
BRC4C65
• Reduction of power consumption of 20% (compared to FXSQ-M8 series) through use of new DC fan • Improved comfort thanks to 3-step airflow control • External static pressure up to 120 Pa facilitates the use with flexible ducts of varying lengths: ideal for shops and medium size offices • Possibility to change ESP through wired remote control allows optimisation of the supply air volume • Allows multi tenant applications (option PCB required) • Easy installation thanks to automatic air flow adjustment towards nominal air flow rate • Drain-up pump with 624mm lift fitted as standard • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXSQ20,25,32P
How does it work? • Installer calculates the total duct resistance to determine the required ESP • During test run, the unit will automatically select the correct fan curve (more than 8 fan curves available) guaranteeing the nominal AFR • Thanks to the high number of fan curves available, adjustments to duct work can be avoided, resulting in a quicker installation process Reduced installation time • After installation, it is possible that the actual duct resistance is lower than expected at the time of designing. As a consequence the air flow will be too high. With the automatic air flow adjustment function the unit can adapt its fan speed to a lower curve, so the air flow decreases • The air flow will always be within 10% of the rated air flow because of the amount of possible fan curves (more than 8 fan curves available per model) • Alternatively the installer can manually select a fan curve with the wired remote control
FXSQ-P7 Indoor units Capacity Power input Dimensions Weight Air flow rate External static pressure Sound power (nominal) Sound pressure Refrigerant Power supply Piping connections Decoration panel
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating High / Standard Cooling Cooling Heating
High/Low High/Low
High/Low High/Low
Liquid (OD)/Gas/Drain (OD) Model Colour HeightxWidthxDepth Weight
kW kW kW kW mm kg m³/min m³/min Pa dBA dBA dBA
20 2.20 2.50
25 2.80 3.20
0.073 0.073 300x550x700 23 9.00 / 6.50 9.00 / 6.50 70 / 30 55.0 32.0 / 26.0 32.0 / 26.0
mm
32 3.60 4.00 0.079 0.079
9.50 / 7.00 9.50 / 7.00 56.0 33.0 / 27.0 33.0 / 27.0
6.35 / 12.7 / 32 BYBS32DJW1
mm kg
55x650x500 3
40 50 63 80 100 125 4.50 5.60 7.10 9.00 11.20 14.00 5.00 6.30 8.00 10.00 12.50 16.00 0.192 0.192 0.142 0.163 0.247 0.303 0.192 0.192 0.142 0.163 0.247 0.303 300x700x700 300x1000x700 300x1400x700 26 35 46 16.00 / 11.00 13.50 / 16.00 25.00 / 20.00 32.00 / 23.00 39.00 / 28.00 16.00 / 11.00 13.50 / 16.00 25.00 / 20.00 32.00 / 23.00 39.00 / 28.00 100 / 30 100 / 40 120 / 40 120 / 50 63.0 59.0 63.0 61.0 66.0 37.0 / 29.0 37.0 / 30.0 38.0 / 32.0 40.0 / 33.0 37.0 / 29.0 37.0 / 30.0 38.0 / 32.0 40.0 / 33.0 R-410A 1~/220-240V/50Hz 9.5 / 15.9 / 32 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 White (10Y9/0,5) 55x800x500 55x1100x500 55x1500x500 3.5 4.5 6.5
140 16.00 18.00 0.261 0.249 47 46.00 / 32.00 46.00 / 32.00 140 / 50 67.00 42.00 / 34.00 42.00 / 34.00
152 2515_BOOK_VRV_2011.indb 152
24/03/2011 12:24
FXMQ-P7
Concealed ceiling unit (inverter fan)
BRC1E51
FXMQ40P7
BRC4C65
• Reduction of power consumption through use of new DC fan motor technology • Improved comfort thanks to 3-step airflow control • Compact height of 300mm, allows installation in narrow ceiling voids • Up to 200 Pa external static pressure allows extensive ductwork runs and flexible application • Possibility to change ESP through wired remote control allows optimisation of the supply air volume (changeable in 13 or 14 stages) • Built-in drain pump with 700mm lift fitted as standard • Allows multi tenant applications (option PCB required) • The air suction direction can be from bottom or rear • Standard air filter • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXMQ-P7 Indoor units Capacity Power input (Nominal) Dimensions Weight Air flow rate External static pressure Refrigerant Power supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling H/S/L
HH/H/L
kW kW kW kW mm kg m³/min Pa
40 4.50 5.00 0.194 0.182 300x700x700 28 16.0 / 13.0 / 11.0 160 / 100 / 30
50 5.60 6.30 0.215 0.203
18.0 / 16.5 / 15.0
63 7.10 8.00 0.23 0.218 300x1000x700 36 19.5 / 17.5 / 16.0
80 9.00 10.00 0.298 0.286
100 11.20 12.50 0.376 0.364
25.0 / 22.5 / 20.0 200 / 100 / 50
125 14.00 16.00 0.461 0.449
300x1400x700 46 32.0 / 27.0 / 23.0 39.0 / 33.0 / 28.0
R-410A 1~/220-240V/50Hz Liquid (OD)/Gas/Drain (OD)
mm
6.4 / 12.7 / 32
9.5 / 15.9 / 32
153 2515_BOOK_VRV_2011.indb 153
24/03/2011 12:24
FXMQ-MA
Concealed ceiling unit (large)
BRC1E51
FXMQ-MA
BRC4C62
Optional drain pump accessory
• Range of models 200-250 class • Up to 270 Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas • Optional drain pump (accessory): housing the drain pump inside the unit has reduced the required installation space • Optional suction air filter plenums and filters • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display 470 mm and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
0 - 250 mm
Min. 530mm
470 mm 222 mm
FXMQ-ma Indoor units Capacity Power input (nominal) Dimensions Weight Air flow rate External static pressure Sound pressure Refrigerant Power supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling High/Low High / Standard Cooling High/Low
kW kW kW kW mm kg m³/min Pa dBA
Liquid (OD)/Gas/Drain (OD)
mm
200 22.40 25.00 1.294 1.294
250 28.00 31.50 1.465 1.465 470x1,380x1100 137
58.00 / 50.00 221 / 132
72.00 / 62.00 270 / 147 48.0 / 45.0 R-410A 1~/220-240V/50Hz
9.5 / 19.1 / PS1B
9.5 / 22.2 / PS1B
154 2515_BOOK_VRV_2011.indb 154
24/03/2011 12:24
FXAQ-P
Wall mounted unit
BRC1E51
BRC7E618
FXAQ40-63P
• Modern style flat front panel • Vertical auto-swing function moves the discharge flaps up and down for efficient air distribution throughout the room • 5 different discharge angles can be programmed via the remote control
• Both horizontal flaps and front panel can easily be removed and washed • All maintenance operations can be carried out from the front of the unit • Ideal for refurbishment projects • Allows multi tenant applications (option PCB required) • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXAQ-P Indoor units Capacity Power input (50Hz) Dimensions Weight Air flow rate Refrigerant Sound power Sound pressure Power supply Piping connections Casing colour
INVERTER Cooling Nominal Heating Nominal Cooling Nominal Heating Nominal (Height x Width x Depth) Cooling Cooling Cooling
HH/H/M/L Nominal HH/H/M/L
Liquid (OD)/Gas/Drain
kW kW kW kW mm kg m³/min dBA dBA mm
20 2.20 2.50 0.019 0.029
- / 7.5 / - / 4.5
25 2.80 3.20 0.028 0.034 290x795x238 11 -/8/-/5
32 3.60 4.00 0.030 0.035
40 4.50 5.00 0.020 0.020
- / 8.5 / - / 5.5
- / 12 / - / 9
50 5.60 6.30 0.033 0.039 290x1,050x238 14 - / 15 / - / 12
63 7.10 8.00 0.050 0.060
- / 19 / - / 14
- / 42 / - / 36
- / 46 / - / 39
R-410A - / 35 / - / 29
- / 36 / - / 29
- / 37 / - / 29 - / 39 / - / 34 1~/220-240V/50Hz 6.35 / 12.7 / VP13 (I.D. 13/O.D. 18) White (3.0Y8.5 / 0.5)
9.52/15.9/VP13 (I.D. 13/O.D. 18)
155 2515_BOOK_VRV_2011.indb 155
24/03/2011 12:24
FXHQ-MA Ceiling suspended unit
BRC1E51
BRC7E63
FXHQ32MA
• Air flow distribution for ceiling heights up to 3.8m without loss of capacity • Use of W-shaped Coanda flap enhances horizontal and vertical air circulation characteristics • Wider air discharge thanks to Coanda effect: up to 100 degrees
100° • Easy installation and maintenance • Long life filter fitted as standard • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXHQ-MA Indoor units Capacity Power input Dimensions Weight Air flow rate Sound pressure Refrigerant Power supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling
High/Low High/Low
Liquid (OD)/Gas/Drain (OD)
kW kW kW kW mm kg m³/min dBA
32 3.60 4.00 0.111 0.111 195x960x680 24 12.00 / 10.00 36.0 / 31.0
mm
6.4 / 12.7 / 26
63 7.10 8.00 0.115 0.115 195x1,160x680 28 17.50 / 14.00 39.0 / 34.0 R-410A 1~/220-240V/50Hz
100 11.20 12.50 0.135 0.135 195x1,400x680 33 25.00 / 19.50 45.0 / 37.0
9.5 / 15.9 / 26
156 2515_BOOK_VRV_2011.indb 156
24/03/2011 12:24
FXUQ-MA
4-way blow ceiling suspended cassette
BRC1E51
• • • •
FXUQ71MA
BRC7C528
• Auto-swing function ensures efficient air and temperature distribution • Air flow distribution for ceiling heights up to 3.5m without loss of capacity • Air can be discharged at 5 different angles between 0 and 60 degrees • Air filter, drain pan and heat exchanger fin are mildew proof and anti-bacterial treated • Drain up pump with 500mm lift fitted as standard • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
Group control with other VRV indoor units possible 5m maximum distance between FXUQ unit and junction box Air can be discharged in any of 4 directions Possibility to shut 1 or 2 flaps for easy installation in corners
FXUQ-MA Indoor units Capacity Power input Dimensions Weight Air flow rate Sound power (nominal) Sound pressure
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating
High/Low High/Low High/Low High/Low
Refrigerant Power supply Piping connections Liquid (OD)/Gas/Drain (OD) Combination with junction box
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA
HxWxD
100 11.2 12.5
mm kg
125 14.0 14.0 0.289 0.269 230x895x895 31
BEVQ71MA
29.00 / 21.00 29.00 / 21.00 59.0 43.0 / 38.0 43.0 / 38.0 R-410A 1~/220-240V/50Hz 9.5 / 15.9 / 26 BEVQ100MA
71
100
mm
BEVQ-MA Dimensions Weight Casing Power supply
71 8.0 9.0 0.180 0.160 165x895x895 25 19.00 / 14.00 19.00 / 14.00 56.0 40.0 / 35.0 40.0 / 35.0
100x350x225 3.0 Galvanised steel plate 1~, 50Hz, 220-240V
3.0
VE
32.00 / 23.00 32.00 / 23.00 60.0 44.0 / 39.0 44.0 / 39.0
BEVQ125MA
125
3.5
157 2515_BOOK_VRV_2011.indb 157
24/03/2011 12:24
FXNQ-P
Concealed floor standing unit
BRC1E51
• • • •
BRC4C62
FXNQ20,25P
Ideal for installation beneath a window Long life filter fitted as standard Requires very little installation space, only 220mm depth The connecting port faces downward, eliminating the need to attach auxiliary piping
Connecting port
Refrigerant piping
FXNQ-P Indoor Units Capacity Power input Dimensions Weight Air flow rate Sound pressure Refrigerant Power supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling
High/Low High/Low
Liquid (OD)/Gas/Drain (OD)
kW kW kW kW mm kg m³/min dBA
20 2.20 2.50
25 2.80 3.20 0.049 0.049 610x930x220 19 7.00 / 6.00 35.0 / 32.0
mm
32 3.60 4.00
40 4.50 5.00
0.090 0.090 610x1,070x220 23 8.00 / 6.00 11.00 / 8.50 38.0 / 33.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / 21
50 5.60 6.30
63 7.10 8.00
0.110 0.110 610x1,350x220 27 14.00 / 11.00 16.00 / 12.00 39.0 / 34.0 40.0 / 35.0
9.5 / 15.9 / 21
158 2515_BOOK_VRV_2011.indb 158
24/03/2011 12:25
FXLQ-P
Floor standing unit
BRC1E51
BRC7C62
FXLQ20-25P
• New stylish modern casing: finished in RAL 9010 colour • Unit can be installed as free standing model by use of optional back plate • Ideal for installation beneath a window • The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency • Home leave operation saves energy during absence • Requires very little installation space • Running the pipes from connections at the back, enables the unit to be wall mounted which in turn allows cleaning beneath the unit where dust tends to accumulate
• Wired remote control can easily be integrated in the unit • BRC1E51A – new wired controller: allows easy navigation through menu items, via a personalised display and minimal number of buttons. Provides a 7-day schedule timer, enabling the user to program the air conditioning daily or weekly, with up to 5 different actions per day possible
FXLQ-P Indoor Units Capacity Power input (50Hz) Dimensions Weight Air Flow Rate Refrigerant Sound Power Sound Pressure Power Supply Piping connections Casing colour
INVERTER Cooling Nominal Heating Nominal Cooling Nominal Heating Nominal (Height x Width x Depth) Cooling
HH/H/M/L
kW kW kW kW mm kg m³/min
Cooling Cooling
Nominal HH/H/M/L
dBA dBA
Liquid (OD)/Gas/Drain
20 2.20 2.50
25 2.80 3.20 0.049 0.049 600x1,000x232 27 -/7/-/6
- / 35 / - / 32
mm
32 3.60 4.00
40 4.50 5.00
0.090 0.090 600x1,140x232 32 -/8/-/6 - / 11 / - / 8.5 R-410A - / 38 / - / 33 1~/220-240V/50Hz 6.35 / 12.7 / 21 Pure white (RAL9010) + Iron grey (RAL7011)
50 5.60 6.30
63 7.10 8.00
0.110 0.110 600x1,420x232 38 - / 14/ - / 11 - / 16 / - / 12
- / 39 / - / 34
- / 40 / - / 35 9.52 / 15.9 / 21
159 2515_BOOK_VRV_2011.indb 159
24/03/2011 12:25
CYQ-DK-BN Biddle standard air curtain
CYQ-DK-F
NETWORK SOLUTION
• Connectable to VRV® heat recovery and heat pump • VRV® is among the first DX systems suitable for connection to air curtains • A payback period of less then 1.5 years compared to installing an electric air curtain • Provides virtually free air curtain heating via recovered heat from indoor units in cooling mode • Easy and quick to install at reduced costs since no additional water systems, boilers and gas connections are required • All year round comfort ensured by the constant discharge velocity and adjustable jet airflow width (European patent) • Maximum energy efficiency stemming from almost zero down flow turbulence, optimised air flow and the application of advanced discharge rectifier technology • Around 85% air separation efficiency, greatly reducing both heat loss and required indoor unit heating capacity
VRV®
BIDDLE STANDARD AIR CURTAIN
SMALL Indoor units Heating capacity Power input Delta T Casing Dimensions
Fan only Nom. Heating Nom. Inlet = room temperature Colour Height Unit F/C/R* Width Unit F/C/R* Depth Unit F/C/R*
Required ceiling void > Door height Favorable/normal/unfavorable conditions Door width Max. Weight Unit Fan - Air flow rate - Heating Refrigerant Type Sound pressure - Heating Piping connections Liquid (OD) / Gas Required accessories (should be ordered separately) Power supply Voltage
kW kW kW K mm mm mm mm m m kg m³/h dBA mm
MEDIUM
CYQS150DK80*BN
CYQS200DK100*BN
CYQS250DK140*BN
CYQM100DK80*BN
9.0 0.35 0.35
11.6 0.46 0.46
16.2 0.58 0.58 16
1,500 / 1,500 / 1,548
2,000 / 2,000 / 2,048
2,500 / 2,500 / 2,548
9.2 0.37 0.37 17 BN: RAL9010 270 / 270 / 270 1,000 / 1,000 / 1,048 590 / 821 / 561 420
1.5 66 / 83 / 88 1,746
2.3 / 2.15 / 2.0 2.0 83 / 102 / 108 2,328
2.5 107 / 129 / 137 2,910
49
50
15
1.0 57 / 68 / 66 1,605 R-410A 50
CYQM150DK80*BN CYQM200DK100*BN CYQM250DK140*BN
11.0 0.56 0.56 14
13.4 0.75 0.75 13
19.9 0.94 0.94 15
1,500 / 1,500 / 1,548
2,000 / 2,000 / 2,048
2,500 / 2,500 / 2,548
2.5 / 2.4 / 2.3 1.5 2.0 73 / 88 / 93 94 / 111 / 117 2,408 3,210
51 51 9.52 / 19.0 9.52 / 16.0 Daikin wired remote control (BRC1E51A) 1~/230V/50Hz
9.52 / 16.0
V
2.5 108 / 136 / 144 4,013
53
54 9.52 / 19.0
LARGE Indoor units Heating capacity Power input Delta T Casing Dimensions
CYQL100DK125*BN Fan only Nom. Heating Nom. Inlet = room temperature Colour Height Unit F/C/R* Width Unit F/C/R* Depth Unit F/C/R*
Required ceiling void > Door height Favorable/normal/unfavorable conditions Door width Max. Weight Unit Fan - Air flow rate - Heating Refrigerant Type Sound pressure - Heating Piping connections Liquid (OD) / Gas Required accessories (should be ordered separately) Power supply Phase / Frequency / Voltage
kW kW kW K mm mm mm mm m m kg m³/h dBA mm
15.6 0.75 0.75
CYQL150DK200*BN
CYQL200DK250*BN
CYQL250DK250*BN
23.3 1.13 1.13
29.4 1.50 1.50 14
31.1 1.88 1.88 12
15 BN: RAL9010 370 / 370 / 370 1,000 / 1,000 / 1,048
1,500 / 1,500 / 1,548 2,000 / 2,000 / 2,048 774 / 1,105 / 745 520 3.0 / 2.75 / 2.5 1.5 2.0 100 / 118 / 141 126 / 151 / 155 4,650 6,200 R-410A 54 56 9.52 / 19.0 9.52 / 22.0 Daikin wired remote control (BRC1E51A) 1~/230V/50Hz
1.0 76 / 81 / 83 3,100 53 9.52 / 16.0
Hz / V
2,500 / 2,500 / 2,548
2.5 157 / 190 / 196 7,750 57 9.52 / 22.0
*F: Freehanging model, C: Cassette model, R: Recessed model
160 2515_BOOK_VRV_2011.indb 160
24/03/2011 12:25
Hot water module For VRV® heat recovery
Heating only hydrobox for VRV®
Ideally positioned for the commercial office sector Daikin UK now offers an energy efficient domestic hot water and heating solution for w.c. facilities, kitchens and staff break out areas. Hot water module The VRV®III hot water module provides an energy efficient means of producing hot water with a leaving temperature range of 25 to 80°C from recovered or recycled heat. To date, the primary operation of the VRV® heat recovery system has been to extract heat from areas being cooled and re-distribute to parts of the building with a heating requirement, often as a result of building orientation and diversity. However, if more heat is extracted than can be effectively re-used this surplus heat is generally dissipated to the atmosphere at the VRV® outdoor unit and subsequently the recovered energy is wasted and the system is not operating at its peak efficiency.
Using the surplus heat By using the hot water module with VRV®III heat recovery the surplus heat can be effectively used as renewable heat for the generation and storage of domestic hot water as well as for heating, via under floor circuits, fan coil units, and low temperature radiators. In combination the hot water module and the VRV®III heat recovery system means that less energy is wasted and the overall system efficiency is greatly improved, reducing running costs and reducing carbon emissions.
Hot water Use heat pump technology to produce hot water • Free hot water production possible • Possibility to connect to solar panels • P ossible applications: bathrooms, sinks, underfloor heating and radiators
For applications requiring either chilled water, different capacities and configurations, or connection to the full Heat Recovery range, please contact your local sales office for advice.
p to
u savE
17%
ed to r a p com s boiler a ga
• Hot water up to 80°C
161 Hot water module.indd 161
30/03/2011 19:24
HXHD125A
Heating only hydrobox for VRV®
Heating only hydrobox for VRV®
• VRV® plug & play, all necessary components integrated • Use heat pump technology to efficiently produce hot water, up to 17% savings compared to a gas boiler • Free hot water production possible by recovery of heat from areas requiring cooling • Leaving water temperature from 25 up to 80°C, without electric heater • Hot water production possible up to 35°C ambient outdoor temperature
• Possibility to connect thermal solar panels to the domestic hot water tank • Possible applications: bathrooms, sinks, under floor heating and radiators • No gas connection needed • Only connectable to REYAQ10-16P
Heating only Heating capacity Casing
Nom. Colour Material HeightxWidthxDepth
Dimensions Weight Refrigerant Sound pressure level (1) Sound pressure level (2) Sound pressure level (3) Heating operation Ambient range
Power supply Recommended fuses
Type
Minimum Maximum Waterside Minimum LW Maximum LW Phase / Frequency / Voltage
HXHD125A 14.0 Metallic Grey Pre coated sheet metal 705x600x695 92 R-134a / R-410A 40 43 38 -15 20 25 80 1~ / 50 / 220-240 20
kW
mm kg Cascade dBA dBA dBA °C °C °C °C Hz / V A
(1) Measuring conditions: Entering water: 55°C, leaving water: 65°C (3) Measuring conditions: Entering water: 55°C, leaving water: 65°C, low sound mode
(2) Measuring conditions: Entering water: 70°C, leaving water: 80°C Reversible hydrobox for VRV® (EKHBHV80,140BA) available on request.
OUTDOOR UNITS REYAQ-P Capacity
Dimensions Weight Heat exchanger Fan Air flow rate Fan Compressor Refrigerant
Piping connections Piping diameter Defrost method Power supply (±10%) Fuse Safety devices
Cooling (*1) EER Heating (*2) COP HeightxWidthxDepth Tube type Type Cooling Motor (drive) Output motor Motor type Name Charge Liquid (OD) / Gas / Discharge Gas Liquid (OD) / Gas / Discharge Gas
kW kW
10 28.0 3.95 31.5 4.27
mm kg
12 33.5 3.84 37.5 4.24
14 40.0 3.51 45.0 4.09
16 45.0 3.19 50.0 3.91
1680x1300x765 331
339 Cross finned coil Propeller
m³/min
190
210
235
240
Direct drive W
350x2
kg
(10.6)
mm
9.52 / 22.2 /19.1
Hz / V A
750x2 Hermetically sealed scroll compressor R-410A (10.8) (11.1) Braze connection 12.7 / 28.6 / 19.1 De-icer 3~ / 50 / 380-415
3~ / 25
(11.1) 12.7 / 28.6 / 22.2
3~ / 40 HPS Fan motor driver overload protector Over current relay Inverter overload protector
(*1) Rated cooling conditions: Outdoor temperature: 35°CDB, indoor unit: 27°C DB / 19 °C WB, equivalent refrigerant piping length: 5m, level difference: 0m. (*2) Rated heating conditions: Outdoor temperature: 7°C DB / 6°C WB, indoor unit: 20°C DB, equivalent refrigerant piping length: 5m, level difference: 0m.
162 HXHD125A.indd 162
30/03/2011 19:26
2515_BOOK_VRV_2011.indb 163
24/03/2011 12:25
Ventilation Air conditioning and air movement of course, are not the same. Neither actually includes the other but both are necessary components of a comfortable and energy efficient indoor climate.
Ventilation by itself cannot cope with the high heat gains generated by modern office complexes and indoor temperature and humidity levels can fluctuate wildly if ventilation alone is installed. On the other hand, air conditioning cannot supply the necessary fresh air needed for a balanced system. The ideal solution therefore, requires air conditioning and ventilation in combination.
Daikin manufactures and markets a range of fresh air reclaim, treatment and handling systems, carefully designed for integration with its air conditioning systems in order to achieve the most economic, environmentally conscious and best possible indoor comfort conditions.
1. Heat reclaim ventilation (HRV)
VAM-FA VKM-GA
165 166
2. Outdoor air processing unit
FXMQ-MF
167
3. Air handling applications
VRV Air handling application ERQ Air handling application VAP(W)-L Air handling units
168 169 171
For a copy of our latest Price List please call 0845 6419000
164 VentillationSubContents.indd 164
30/03/2011 19:33
VAM-FA
Heat reclaim ventilation
Clean outdoor air Total heat exchanged foul air
The Daikin heat recovery ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly. HRV units can be controlled individually or integral with the air conditioning system (Daikin VRV® or Sky Air series).
Foul indoor air
Total heat exchanged clean air
• 9 models to choose from • Compact, energy saving ventilation • Specially developed heat exchange element with HEP (High Efficiency Paper) • Easy integration into the VRV® system • Connectable to current Daikin control systems:
[iPU]
VAM-FA Ventilation Air flow rate Sound pressure level (max.) (1) External static pressure (max.) Temperature exchange efficiency Enthalpy exchange efficiency Dimensions
Weight Duct diameter Power supply
heating cooling H W D
m3/h dBA Pa % % % mm mm mm kg mm VE
VAM150FA8 VAM250FA8 VAM350FA8 VAM500FA8 VAM650FA8 VAM800FA8 VAM1000FA8 VAM1500FA8 VAM2000FA8 150 250 350 500 650 800 1,000 1,500 2,000 27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5 69 64 98 98 93 137 157 137 137 74 72 75 74 74 74 75 75 75 58 58 61 58 58 60 61 61 61 64 64 65 62 63 65 66 66 66 285 285 308 308 364 364 364 726 726 776 776 828 828 1,004 1,004 1,004 1,514 1,514 525 525 816 816 868 868 1,156 868 1,156 24 24 33 33 48 48 61 132 158 ø 100 ø 150 ø 150 ø 200 ø 200 ø 250 ø 250 ø 350 ø 350 1 ~, 50Hz, 220-240V
(1) Sound pressure level is measured in heat exchange mode.
165 2515_BOOK_Ventilation_2011.indb 165
21/03/2011 08:50
VKM-GA
Heat reclaim ventilation with DX coil
• Heat purge (economiser): heat accumulated indoors is discharged at night • Integration of air conditioning into HRV unit • Increased static pressure thanks to improved fan performance • Integrated control with VRV® system only • Connectable to current Daikin control systems:
[iPU]
VKM-GA Ventilation & DX coil Fresh air conditioning load Air flow rate Sound pressure level - 220V Sound pressure level - 240V Static pressure Temperature exchange efficiency Enthalpy exchange efficiency - cooling Enthalpy exchange efficiency - heating Dimensions
Weight Power supply
Cooling Heating UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L Height Width Depth
kW kW m3/h dBA dBA Pa % % % mm mm mm kg V1
VKM50GA 4.71 5.58 500 - 500 - 440 38 - 36 - 33.5 39 -37 - 33.5 180 - 150 - 110 76 - 76 - 77.5 64 - 64 - 67 67 - 67 - 69 387 1,764 832 96
VKM80GA 7.46 8.79 750 - 750 - 640 40 - 37.5 - 34.5 41.5 - 39 - 37 170 - 120 - 80 78 - 78 - 79 66 - 66 - 68 71 - 71 - 73 387 1,764 1,214 109 1 ~, 220-240V, 50Hz
VKM100GA 9.12 10.69 950 - 950 - 820 40 - 38 - 35 41 - 39 - 36.5 150 - 100 - 70 74 - 74 - 76.5 62 - 62 - 66 65 - 65 - 69 387 1,764 1,214 114
166 2515_BOOK_Ventilation_2011.indb 166
21/03/2011 08:50
FXMQ-MF
Outdoor air processing unit
• 100% fresh air intake possible • Operation range: -5°C to 43°C • 225 Pa external static pressure allows extensive ductwork
FXMQ250MF
runs and flexible application: ideal for use in large areas
• Drain pump kit available as accessory
FXMQ-MFV1 Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Power Supply Piping connections
Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating
Medium Medium
Liquid (OD)/Gas/Drain
kw kw kw kw mm kg m³/min m³/min mm
FXMQ125MFV1 14.0 8.9 0.359 0.359 470x744x1100 86 18.0 18.0 9.5 / 15.9 / PS1B
FXMQ200MFV1 22.4 13.9 0.548 0.548
FXMQ250MFV1 28.00 17.40 0.638 0.638 470x1380x1100 123
28.0 28.0 220-240V/50Hz 9.5 / 19.1 / PS1B
35.0 35.0 9.5 / 22.2 / PS1B
167 2515_BOOK_Ventilation_2011.indb 167
21/03/2011 08:50
VRV®
Air handling applications
Air handling unit
EXV-kit
A R-410A inverter condensing units range for multi application with air handling units. • • • • •
Inverter controlled units Large capacity range (from 5 to 18HP) Cooling only and heat pump R-410A
EKEXMCB gas pipe
Control z: control of air temperature (suction temperature, room temperature) via Daikin control (no DDC controller needed)
liquid pipe F1,F2 communication
• Large range of expansion valve kits available • BRC1E51A is used to set the set point temperature (connected to the EKEXMCB).
Outdoor Unit RXYQ-P9 Capacity range Capacity Power Input Dimensions Weight Sound Level
Cooling Cooling (Height x Width x Depth)
Sound Power Cooling Sound Cooling Air Flow Rate (Nominal) at 230V) Cooling Operation Range Cooling Min~Max Refrigerant Power Supply Max n° of indoor units to be connected Piping connections Liquid (OD)/Gas
HP kW kW mm kg dBA dBA m3/min °CDB
mm
5 5 14.0 3.52 1,680x635x765 157 72 54 95
8 8 22.4 5.56
10 10 28.0 7.42 1,680x930x765
57 171
58 185
8 9.5 / 15.9
13 9.5 / 19.1
16 9.5 / 22.2
185
12 12 33.5 9.62
14 14 40.0 12.4
238
16 16 45.0 14.2 1,680x1,240x765 315
78
323 83 63 239
80 60 196 -5.0~43.0 R-410A 3N~/400V/50Hz 19 12.7 / 22.2
233
23
18 18 49.0 16.2
26 12.7 / 28.6
29 15.9 / 28.6
Combination Table Control box
3ph
Expansion valve kit
Outdoor units
control z
class 50
class 63
class 80
class 100
class 125
class 140
class 200
class 250
RXYQ5P9 RXYQ8P9 RXYQ10P9 RXYQ12P9 RXYQ14P9 RXYQ16P9 RXYQ18P9
EKEXMCB X X X X X X X
EKEXV50 X X X X X X X
EKEXV63 X X X X X X X
EKEXV80 X X X X X X X
EKEXV100 X X X X X X X
EKEXV125 X X X X X X X
EKEXV140 X X X X X X X
EKEXV200 X X X X X X X
EKEXV250 X X X X X X X
168 VRV.indd 168
30/03/2011 19:37
ERQ
Condensing units for air handling applications (pair)
A range of R-410A inverter condensing units for pair application with air handling units. Inverter controlled heat pump units with R-410A refrigerant. • • • • •
Large capacity range (from 100 to 250 class) Wide range of expansion valve kits available (from 63 to 250 class) Ventilation and air conditioning in one solution EKEXV-kit & control boxes are designed for outdoor installation and can be wall mounted Outdoor unit operation range: -5°CDB ~ 43°CDB
• F lexible control possibilities: Control x: control of air temperature (discharge temperature, suction temperature, room temperature) via external device (DDC controller) Control y: control of evaporating temperature via Daikin control (no DDC controller needed) Control z: control of air temperature (suction temperature, room temperature) via Daikin control (no DDC controller needed).
Air handling unit Liquid pipe
Liquid pipe
Gas pipe
Gas pipe
(Field Supply)
Expansion valve kit: EKEXV
F1,F2 communication
Control box: EKEQDCB: control z EKEQFCB: control x,y
DDC control (control x)
169 2515_BOOK_Ventilation_2011.indb 169
21/03/2011 08:50
HEAT PUMP Outdoor units Capacity Power input
Cooling Heating Cooling Heating
EER COP Casing Dimensions Weight Sound power level Sound pressure level Operation range
Nominal Nominal Nominal Nominal
kW kW kW kW
ERQ100AV1 11.2 12.5 2.81 2.74
ERQ125AV1 14.0 16.0 3.51 3.86
ERQ140AV1 15.5 18.0 4.53 4.57 3.42 3.94
3.99 4.56 Colour Material HxWxD Cooling Cooling Heating Cooling Heating
Refrigerant type Piping connections
Piping length Power supply
Nominal Nominal Nominal Min-Max Min-Max
mm kg dBA dBA dBA °CDB °CWB
Liquid Gas Drain Max total length
mm mm mm m
Nominal Nominal Nominal Nominal
kW kW kW kW
4.15 Daikin White Painted galvanized steel plate 1,345 x 900 x 320 120 67 51 53 -5 ~ 46 -20 ~ 15.5 R-410A ø9.52
66 50 52
69 53 55
ø15.9
ø19.1 3 x ø26 55 1 ~, 220-240V, 50Hz
HEAT PUMP Outdoor units Capacity Power input
Cooling Heating Cooling Heating
EER COP Casing Dimensions Weight Sound power level Sound pressure level Operation range
Colour Material HxWxD Cooling Cooling Cooling Heating
Refrigerant type Piping connections Piping length Power supply
Nominal Nominal Min-Max Min-Max
mm kg dBA dBA °CDB °CWB
Liquid mm Gas mm Max total length m
ERQ125AW1 14.0 16.0 3.52 4.00 3.98 4.00
ERQ200AW1 22.4 25.0 5.22 5.56 4.29 4.50 Daikin White Painted galvanized steel plate
1,680 x 635 x 765 159 72 54
ø15.9
ERQ250AW1 28.0 31.5 7.42 7.70 3.77 4.09
1,680 x 930 x 765 187
240 78
57 -5 ~ 43 -20 ~ 15 R-410A ø9.52 ø19.1 55 3N~, 400V, 50Hz
58
ø22.2
170 2515_BOOK_Ventilation_2011.indb 170
21/03/2011 08:50
VAP(W)-L
Air handling units
Air handling units The Daikin range has 5 air flow volumes from 1750 m3/hr (0.48 m/3s) to 9000 m/3hr (2.54 m/3s) all capable of 250 pa external static. They can be broken down into 3 distinct groups all of which are available in both Internally mounted plant room - VAP and externally mounted weatherproofed types - VAW. The range VAP/WLA-D is a straight forward supply only unit • Type A with heating by LTHW, Type B with heating by Electric, Type C with heating by LTHW & DX cooling, Type D with heating by Electric & DX cooling,
The range VAP/WLE-H is a Supply & Extract with a Heat cube plate heat exchanger which recovers sensible heat thus reducing energy • Type E Heat Cube with heating by LTHW, Type F Heat Cube with heating by Electric, Type G Heat Cube with heating by LTHW & DX cooling, Type H Heat Cube with heating by Electric & DX cooling,
The range VAP/WLI-L is a Supply & Extract with a Thermal Wheel heat exchanger which recovers sensible heat thus reducing energy • Type I Thermal Wheel with heating by LTHW, Type J Thermal Wheel with heating by Electric, Type K Thermal Wheel with heating by LTHW & DX cooling, Type L Thermal Wheel with heating by Electric & DX cooling.
Capacity conditions The heating conditions are based on Airside - 5°C db on and 20°C db off, LTHW on 82°C & off @ 71°C The cooling conditions are based on Airside on coil 32°C db / 22°C wb, off @ 22°C db & 18°C wb using R410A @ 6°C Evaporating Notes Units come as standard with left hand connections (in direction of airflow) but right hand are available at no extra charge. Filtration - All models with heating coils have G4 (panel) Class filtration all units with heating & cooling coils have G4 (panel) + F6 (bag) Class filtration. The larger internal units are delivered in a number of sections which will assist in getting these units into plant room areas the number of sections are shown on the following pages (indicated as shipped in pcs) further details are shown on the General Arrangement drawings. These units will need bolting together on site (by others). The noise levels shown are Sound power levels (dbA) at source you should note that the models with supply and extract fans (models E to L) may have different noise levels which is why they are shown separately. For further details please refer to the Technical Manual, Data Sheets or General Arrangement drawings.
Type
Fan
Damper
Filter – G4 Panel
A
3
3
3
B
3
3
3
Filter - F6 Bag Rigid
3
3
3
3
3
3
3
3
E
3
3
3
F
3
3
3
3
3
3
3
H
3
3
3
3
I
3
3
3
3
3
3
3
3
L
3
3
3
3
Recoup
Wheel
3 3
3
3
G
3
Cooling DX R410A
3
C
J
Electric
3
D
K
Heating LTHW
3 3
3 3
3 3
3
3
3
3
3 3
3 3
3
3 3
3
3
3
171 2515_BOOK_Ventilation_2011.indb 171
21/03/2011 08:50
VAP-L
Specification tables Types A, B, C
Internally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Heating Grade Power Supply
Fan Run Current Start Current
Complete with LPHW heating coil Type A m3/hr pa mm mm mm kg Pcs dB kW V Hz ph kW A A
VAPLA1750AW 1750
VAPLA3000AW 3000
1400 790 654 126 1 79.9 14.54
1630 890 754 170 1 83.1 23.94
0.75 1.79 12.26
1.1 2.5 17.5
VAPLB1750AW 1750
VAPLB3000AW 3000
2030 790 654 133 1 79.8 15
2030 890 754 178 1 82.9 24
0.75 2.05 11.1
1.1 2.5 17.5
Internally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Heating Grade Power Supply
Fan Run Current Start Current
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Cooling Heating Grade Power Supply
Fan Run Current Start Current Condensing Unit Expansion Valve Kit Control box option
VAPLA7000AW 7000
VAPLA9000AW 9000
1830 1190 1054 280 1 81.1 60
1630 1190 1354 304 1 84.9 76.97
2.2 4.59 35.8
3 6.19 46.42
Complete with Electric heating coil Type B m3/hr pa mm mm mm kg Pcs dB kW V Hz ph kW A A
Internally Mounted Air Handling Unit Air flow External Static Dimensions
VAPLA4000AW 4000 250 1480 890 1054 181 1 81.1 34.24 G4 400 50 3 1.1 2.5 17.5
VAPLB4000AW 4000 250 2080 890 1054 191 1 80.9 36 G4 400 50 3 1.1 2.5 17.5
VAPLB7000AW 7000
VAPLB9000AW 9000
2380 1190 1054 290 1 81.1 60
2200 1190 1354 319 1 84.8 82.5
2.2 4.59 35.8
3 6.19 46.43
Complete with LPHW heating coil & R410a DX Cooling coil Type C m3/hr pa mm mm mm kg Pcs dB kW kW V Hz ph kW A A
VAPLC1750AW 1750 2330 790 754 205 1 82.2 7.68 14.54
0.55 1.27 8.84 ERQ100A EKEXV63 EKEQFCB
VAPLC3000AW 3000
VAPLC4000AW VAPLC7000AW 4000 7000 250 2510 2560 2670 890 990 1190 854 954 1254 248 252 383 2 2 2 81.6 82.5 85.9 12.57 18.10 31.80 23.94 34.24 60 F6 + G4 400 50 3 1.1 1.5 2.2 2.31 3.05 4.28 17.09 24.1 35.52 Recommendation for connection to Daikin condensing units ERQ125A ERQ200A 2 x ERQ140A EKEXV125 EKEXV200 2 x EKEXV140 EKEQFCB EKEQFCB 2 x EKEQFCB
VAPLC9000AW 9000 2810 1240 1354 443 2 86 40.42 76.97
3 6.2 46.5 2 x ERQ200A 2 x EKEXV200 2 x EKEQFCB
172 2515_BOOK_Ventilation_2011.indb 172
21/03/2011 08:50
VAP-L
Specification tables Types D, E, F
Internally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Cooling Heating Grade Power Supply
Fan Run Current Start Current
Complete with Electric heating coil & R410a DX Cooling coil Type D m3/hr pa mm mm mm kg Pcs dB kW kW V Hz ph kW A A
Condensing Unit Expansion Valve Kit Control box option
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
0.55 1.27 8.84
Length Height Width Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
VAPLD3000AW 3000
VAPLD4000AW VAPLD7000AW 4000 7000 250 2600 2630 2820 890 990 1190 854 954 1254 259 297 395 2 2 2 81.5 82.3 85.9 12.57 18.10 31.80 24 36 60 F6 + G4 400 50 3 1.1 1.5 2.2 2.31 3.05 4.28 17.01 24.1 35.52 Recommendation for connection to Daikin condensing units ERQ125A ERQ200A 2 x ERQ140A EKEXV125 EKEXV200 2 x EKEXV140 EKEQFCB EKEQFCB EKEQFCB
VAPLD9000AW 9000 2970 1240 1354 458 2 85.9 40.42 82.5
3 6.19 46.43 2 x ERQ200A 2 x EKEXV200 EKEQFCB
Heat Recovery (Plate Heat Exchanger) Complete with LPHW heating coil Type E m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
Internally Mounted Air Handling Unit Air flow External Static Dimensions
2440 790 754 214 1 82 7.68 15
ERQ100A EKEXV63 EKEQFCB
Internally Mounted Air Handling Unit Air flow External Static Dimensions
VAPLD1750AW 1750
VAPLE1750AW 1750
VAPLE3000AW 3000
2580 1480 654 538
2780 1680 754 548
82.3 82.1 14.54
85.2 85.1 23.94
1.1 2.31 17.09 1.1 2.31 17.09
1.5 3.19 22.6 1.1 2.5 17.5
VAPLE4000AW 4000 250 2630 1680 1054 616 2 83.5 83.4 34.24 G4 400 50 3 1.5 3.19 22.6 1.5 3.19 22.6
VAPLE7000AW 7000
VAPLE9000AW 9000
3280 2280 1054 810
3010 2280 1354 910
82.9 82.8 60
86.5 86.5 76.97
3 6.19 46.42 3 6.19 46.42
4 7.81 56.23 4 7.81 56.23
Heat Recovery (Plate Heat Exchanger) Complete with Electric heating coil Type F m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
VAPLF1750AW 1750
VAPLF3000AW 3000
2580 1480 654 538
2780 1680 754 548
82.1 82.1 15
85 85.1 24
1.1 2.31 17.09 1.1 2.31 17.09
1.5 3.19 22.65 1.1 2.5 17.5
VAPLF4000AW 4000 250 2730 1680 1054 627 2 83.3 83.4 36 G4 400 50 3 1.5 3.19 22.65 1.5 3.19 22.65
VAPLF7000AW 7000
VAPLF9000AW 9000
3280 2280 1054 822
3060 2280 1354 923
82.6 82.8 60
86.4 86.5 82.5
3 6.19 46.43 3 6.19 46.43
4 7.81 56.23 4 7.81 56.23
173 2515_BOOK_Ventilation_2011.indb 173
21/03/2011 08:50
VAP-L
Specification tables Types G, H, I
Internally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
Heat Recovery Plate Heat Exchanger LPHW heating & R410a DX Cooling Type G m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
Condensing Unit Expansion Valve Kit Control box option
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
Capacity Filter Electrical Details
3650 1680 854 603 2 83.6 85.1 6.47 23.94
82.6 82.1 4.02 14.54
Length Height Width Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
VAPLG7000AW 7000
VAPLG9000AW 9000
4480 2280 1254 990
4290 2380 1354 1080 3
87.4 87.2 83.7 82.7 10.02 17.83 34.24 60 F6 + G4 400 50 3 1.1 2.2 3 2.31 4.28 5.6 17.09 35.52 40.88 1.1 1.5 3 2.5 3.19 6.19 17.5 22.65 46.53 Recommendation for connection to Daikin condensing units ERQ100A ERQ100A ERQ200A EKEXV63 EKEXV100 EKEXV200 EKEQFCB EKEQFCB EKEQFCB
0.75 1.79 12.28 1.1 2.5 17.5
VAPLH1750AW 1750
VAPLH3000AW 3000
3580 1480 754 510
3830 1680 854 620 2 84.8 82.5 6.47 24
82 84 4.02 15
87.2 86.5 21.82 76.97
4 7.81 56.23 4 7.81 56.23 ERQ200A EKEXV200 EKEQFCB
VAPLH4000AW 4000 250 3480 1680 1154 670
VAPLH7000AW 7000
VAPLH9000AW 9000
4480 2280 1254 990
4340 2380 1354 1080 3
87.3 87.2 83.7 84.2 10.02 17.83 36 60 F6 + G4 400 50 3 1.1 2.2 3 2.31 4.28 6.19 17.09 26.96 46.42 1.1 1.5 3 2.5 3.19 6.19 17.5 22.6 46.42 Recommendation for connection to Daikin condensing units ERQ100A ERQ100A ERQ200A EKEXV63 EKEXV100 EKEXV200 EKEQFCB EKEQFCB EKEQFCB
0.75 1.79 12.28 1.1 2.5 17.5 ERQ100A EKEXV63 EKEQFCB
Internally Mounted Air Handling Unit
Weight Shipped in Sound Power Level
3330 1480 754 503
VAPLG4000AW 4000 250 3230 1680 1154 659
Heat Recovery Plate Heat Exchanger Electric heating & R410a DX Cooling Type H
Condensing Unit Expansion Valve Kit Control box option
Air flow External Static Dimensions
VAPLG3000AW 3000
ERQ100A EKEXV63 EKEQFCB
Internally Mounted Air Handling Unit Air flow External Static Dimensions
VAPLG1750AW 1750
88.4 83.1 21.82 82.5
4 7.11 50.48 3 6.19 46.53 ERQ200A EKEXV200 EKEQFCB
Heat Recovery (Thermal Wheel) Complete with LPHW heating coil Type I m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
VAPLI4000AW 4000 2630 1680 1154 649 3 83.6 83.2 34.24
1.5 3.19 22.6 1.5 3.19 22.6
VAPLI7000AW 7000 250 2840 2080 1354 826 3 91.1 91.2 60 G4 400 50 3 3 6.19 46.43 3 6.19 46.43
VAPLI9000AW 9000 2960 2280 1454 997 3 86.4 86.2 76.97
4 7.81 56.23 4 7.81 56.23
174 2515_BOOK_Ventilation_2011.indb 174
21/03/2011 08:50
VAP-L
Specification tables Types J, K, L
Internally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
Heat Recovery (Thermal Wheel) Complete with Electric heating coil Type J m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
Internally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Dry Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
Internally Mounted Air Handling Unit
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current Condensing Unit Expansion Valve Kit Control box option
2630 1680 1154 649 83.4 83.2 36
1.5 3.19 22.65 1.5 3.19 22.65
VAPLK4000AW 4000
VAPLK7000AW 7000 250 3540 2080 1354 948
3330 1680 1154 649 2 87.3 83.2 5.15 34.24
86.9 82 9.02 60 F6 + G4 400 50 3 3 5.6 40.88 3 6.19 46.43 Recommendation for connection to Daikin condensing units ERQ100A EKEXV80 EKEQFCB
2.2 4.28 35.52 1.5 3.19 22.6 ERQ100A EKEXV63 EKEQFCB
Length Height Width Dry
VAPLJ7000AW 7000 250 2840 2080 1354 872 2 82.1 82 60 G4 400 50 3 3 6.19 46.43 3 6.19 46.43
VAPLJ9000AW 9000 2960 2280 1454 997 86.3 86.2 82.5
4 7.81 56.23 4 7.81 56.23
Heat Recovery (Thermal Wheel) LPHW heating & R410a DX Cooling coil Type K
Condensing Unit Expansion Valve Kit Control box option
Air flow External Static Dimensions
VAPLJ4000AW 4000
VAPLK9000AW 9000 3610 2280 1454 1065 3 91.2 86.2 11.6 76.97
4 7.11 50.48 4 7.81 56.23 ERQ125A EKEXV100 EKEQFCB
Heat Recovery (Thermal Wheel) Electric heating & R410a DX Cooling coil Type L m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
VAPLL4000AW 4000
VAPLL7000AW 7000 250 3680 2080 1354 971
3610 1680 1154 649 2 87.3 83.2 5.15 36
2.2 4.28 35.52 1.5 3.19 22.65 ERQ100A EKEXV63 EKEQFCB
86.9 82 9.02 60 F6 + G4 400 50 3 3 5.6 40.88 3 6.19 46.43 Recommendation for connection to Daikin condensing units ERQ100A EKEXV80 EKEQFCB
VAPLL9000AW 9000 3730 2280 1454 1065 3 91.1 86.2 11.6 82.5
4 7.11 50.48 4 7.81 56.23 ERQ125A EKEXV100 EKEQFCB
175 2515_BOOK_Ventilation_2011.indb 175
21/03/2011 08:50
VAW-L
Specification tables Types A, B, C
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Heating Grade Power Supply
Fan Run Current Start Current
Complete with LPHW heating coil Type A m3/hr pa mm mm mm kg Pcs dB kW V Hz ph kW A A
VAWLA1750AW 1750
VAWLA3000AW 3000
1600 790 654 176 1 79.9 14.54
1670 890 754 176 1 83.4 23.94
0.75 2.06 11.1
1.1 2.5 17.5
VAWLB1750AW 1750
VAWLB3000AW 3000
2070 790 654 137 1 80.2 15
2130 890 754 182 1 83.2 24
0.75 2.06 11.1
1.1 2.5 17.5
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Heating Grade Power Supply
Fan Run Current Start Current
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Cooling Heating Grade Power Supply
Fan Run Current Start Current Condensing Unit Expansion Valve Kit Control box option
VAWLA7000AW 7000
VAWLA9000AW 9000
1900 1190 1054 289 1 81.3 60
1700 1190 1354 315 1 85 76.97
2.2 4.59 35.8
3 6.19 46.42
Complete with Electric heating coil Type B m3/hr pa mm mm mm kg Pcs dB kW V Hz ph kW A A
Externally Mounted Air Handling Unit Air flow External Static Dimensions
VAWLA4000AW 4000 250 1750 890 1054 222 1 81.3 34.24 G4 400 50 3 1.5 3.19 22.6
VAWLB4000AW 4000 250 2090 890 1054 203 1 81.1 36 G4 400 50 3 1.1 2.5 17.5
VAWLB7000AW 7000
VAWLB9000AW 9000
2380 1190 1054 289 1 81.1 60
2310 1190 1354 330 1 84.9 82.5
2.2 4.59 35.8
3 6.19 46.42
Complete with LPHW heating coil & R410a DX Cooling coil Type C m3/hr pa mm mm mm kg Pcs dB kW kW V Hz ph kW A A
VAWLC1750AW 1750 2350 790 754 213 1 82.3 7.68 14.54
0.55 1.27 8.84 ERQ100A EKEXV63 EKEQFCB
VAWLC3000AW 3000
VAWLC4000AW VAWLC7000AW 4000 7000 250 2400 2400 2550 890 990 1190 854 954 1254 252 290 385 1 1 1 81.8 82.6 86 12.57 18.10 31.80 23.94 34.24 60 F6 + G4 400 50 3 1.1 1.5 2.2 2.31 3.05 4.28 17.09 24.1 35.52 Recommendation for connection to Daikin condensing units ERQ125A ERQ200A 2 x ERQ140A EKEXV125 EKEXV200 2 x EKEXV140 EKEQFCB EKEQFCB 2 x EKEQFCB
VAWLC9000AW 9000 2700 1240 1354 447 1 86.1 40.42 76.97
3 6.19 46.43 2 x ERQ200A 2 x EKEXV200 2 x EKEQFCB
176 2515_BOOK_Ventilation_2011.indb 176
21/03/2011 08:50
VAW-L
Specification tables Types D, E, F
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Cooling Heating Grade Power Supply
Fan Run Current Start Current
Complete with Electric heating coil & R410a DX Cooling coil Type D m3/hr pa mm mm mm kg Pcs dB kW kW V Hz ph kW A A
Condensing Unit Expansion Valve Kit Control box option
VAWLD1750AW 1750 2560 790 754 219 1 82.2 7.68 15
0.55 1.27 8.84 ERQ100A EKEXV63 EKEQFCB
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
VAWLD4000AW VAWLD7000AW 4000 7000 250 2630 2680 2850 890 990 1190 854 954 1254 259 298 385 1 1 1 81.7 82.5 86 12.57 18.10 31.80 24 36 60 F6 + G4 400 50 3 1.1 1.5 2.2 2.31 3.05 4.59 17.09 24.1 35.8 Recommendation for connection to Daikin condensing units ERQ125A ERQ200A 2 x ERQ140A EKEXV125 EKEXV200 2 x EKEXV140 EKEQFCB EKEQFCB EKEQFCB
VAWLD9000AW 9000 2980 1240 1354 447 1 86 40.42 82.5
3 6.19 46.43 2 x ERQ200A 2 x EKEXV200 EKEQFCB
Heat Recovery (Plate Heat Exchanger) with LPHW heating coil Type E m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
VAWLE1750AW 1750
VAWLE3000AW 3000
2550 1480 654 380 1 82.7 82.4 14.54
2900 1680 754 555 1 85.5 85.4 23.94
1.1 2.31 17.09 1.1 2.31 17.09
1.5 3.19 22.33 1.5 3.19 22.65
Externally Mounted Air Handling Unit Air flow External Static Dimensions
VAWLD3000AW 3000
VAWLE4000AW 4000 250 2750 1680 1054 655 1 83.7 83.6 34.24 G4 400 50 3 2.2 4.59 35.6 1.5 3.19 22.6
VAWLE7000AW 7000
VAWLE9000AW 9000
3480 2280 1054 830 1 83.2 83 60
3130 2280 1354 940 1 86.7 86.7 76.97
3 6.19 46.42 3 6.19 46.42
4 7.81 56.23 4 7.81 56.23
Heat Recovery (Plate Heat Exchanger) with Electric heating coil Type F m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
VAWLF1750AW 1750
VAWLF3000AW 3000
2600 1480 654 382 1 82.5 82.4 15
2900 1680 754 570 1 85.3 85.4 24
1.1 2.31 17.09 1.1 2.31 17.09
1.5 3.19 22.65 1.5 3.19 22.65
VAWLF4000AW 4000 250 2850 1680 1054 645 1 83.5 90.1 36 G4 400 50 3 1.5 3.19 22.65 1.5 3.19 22.65
VAWLF7000AW 7000
VAWLF9000AW 9000
3400 2280 1054 850 1 82.9 83 60
3180 2280 1354 960 1 86.6 86.7 82.5
3 6.19 46.43 3 6.19 46.43
4 7.81 56.23 4 7.81 56.23
177 2515_BOOK_Ventilation_2011.indb 177
21/03/2011 08:50
VAW-L
Specification tables Types G, H, I
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
Heat Recovery Plate Heat Exchange LPHW heating & R410a DX Cooling Type G m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
Condensing Unit Expansion Valve Kit Control box option
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
Capacity Filter Electrical Details
3350 1480 754 522 1 84.2 82.5 4.02 14.54
0.75 1.79 12.28 1.1 2.5 17.5
VAWLH1750AW 1750
VAWLH3000AW 3000
VAWLH4000AW VAWLH7000AW 4000 7000 250 3950 3600 4450 1680 1680 2280 854 1154 1254 640 695 1030 1 1 1 85 87.4 87.3 82.8 83.8 84.2 6.47 10.02 17.83 24 36 60 F6 + G4 400 50 3 1.5 2.2 3 3.05 4.28 6.19 24.01 26.96 46.42 1.1 1.5 3 2.5 3.19 6.19 17.5 22.6 46.42 Recommendation for connection to Daikin condensing units ERQ100A ERQ100A ERQ200A EKEXV63 EKEXV100 EKEXV200 EKEQFCB EKEQFCB EKEQFCB
3600 1480 754 525 1 84.2 82.2 4.02 15
0.75 1.79 12.28 1.1 2.5 17.5 ERQ100A EKEXV63 EKEQFCB
Externally Mounted Air Handling Unit
Weight Shipped in Sound Power Level
VAWLG4000AW VAWLG7000AW 4000 7000 250 3750 3350 4350 1680 1680 2280 854 1154 1254 630 683 1005 1 1 1 83.8 87.5 87.3 85.3 83.8 82.9 6.47 10.02 17.83 23.94 34.24 60 F6 + G4 400 50 3 1.1 2.2 3 2.31 4.28 5.6 17.09 35.52 40.88 1.5 1.5 3 3.19 3.19 6.19 22.65 22.65 46.53 Recommendation for connection to Daikin condensing units ERQ100A ERQ100A ERQ200A EKEXV63 EKEXV100 EKEXV200 EKEQFCB EKEQFCB EKEQFCB
Length Height Width Delivered Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
VAWLG9000AW 9000 4350 2380 1354 1105 1 87.3 86.7 21.82 76.97
4 7.81 56.23 4 7.81 56.23 ERQ200A EKEXV200 EKEQFCB
Heat Recovery Plate Heat Exchanger Electric heating & R410a DX Cooling Type H
Condensing Unit Expansion Valve Kit Control box option
Air flow External Static Dimensions
VAWLG3000AW 3000
ERQ100A EKEXV63 EKEQFCB
Externally Mounted Air Handling Unit Air flow External Static Dimensions
VAWLG1750AW 1750
VAWLH9000AW 9000 4500 2380 1354 1220 1 85.6 83.3 21.82 82.5
4 7.81 56.23 4 7.81 56.23 ERQ200A EKEXV200 EKEQFCB
Heat Recovery (Thermal Wheel) Complete with LPHW heating coil Type I m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
VAWLI4000AW 4000 2650 1680 1154 705 1 83.8 83.3 34.24
2.2 4.59 35.8 1.5 3.19 22.6
VAWLI7000AW 7000 250 2860 2080 1354 930 1 82.4 82.1 60 G4 400 50 3 3 6.19 46.43 3 6.19 46.43
VAWLI9000AW 9000 2980 2280 1454 1060 1 86.5 86.3 76.97
4 7.81 56.23 4 7.81 56.23
178 2515_BOOK_Ventilation_2011.indb 178
21/03/2011 08:50
VAW-L
Specification tables Types J, K, L
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Return Fan Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
Heat Recovery (Thermal Wheel) Complete with Electric heating coil Type J m3/hr pa mm mm mm kg Pcs dB dB kW V Hz ph kW A A kW A A
Externally Mounted Air Handling Unit Air flow External Static Dimensions
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Length Height Width Delivered Dry Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current
m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
Externally Mounted Air Handling Unit
Weight Shipped in Sound Power Level Capacity Filter Electrical Details
Supply Fan Return Fan Cooling Heating Grade Power Supply
Supply Fan Run Current Start Current Return Fan Run Current Start Current Condensing Unit Expansion Valve Kit Control box option
2650 1680 1154 664 1 83.6 83.3 36
1.5 3.19 22.6 1.5 3.19 22.6
VAWLK4000AW 4000 3350 1680 1154 758 1 87.5 83.3 5.15 34.24
2.2 4.28 35.52 1.5 3.19 22.6 ERQ100A EKEXV63 EKEQFCB
Length Height Width Delivered Dry
VAWLJ7000AW 7000 250 2860 2080 1354 940 1 82.2 82.1 60 G4 400 50 3 3 6.19 46.43 3 6.19 46.43
VAWLJ9000AW 9000 2980 2280 1454 1070 1 86.4 86.3 82.5
4 7.81 56.23 4 7.81 56.23
Heat Recovery (Thermal Wheel) LPHW heating & R410a DX Cooling coil Type K
Condensing Unit Expansion Valve Kit Control box option
Air flow External Static Dimensions
VAWLJ4000AW 4000
VAWLK7000AW 7000 250 2560 2080 1354 992 1 87 82.1 9.02 60 F6 + G4 400 50 3 3 5.6 40.88 3 6.19 46.43 Recommendation for connection to Daikin condensing units ERQ100A EKEXV80 EKEQFCB
VAWLK9000AW 9000 3630 2280 1454 1130 1 91.2 86.3 11.6 76.97
4 7.11 50.48 4 7.81 56.23 ERQ125A EKEXV100 EKEQFCB
Heat Recovery (Thermal Wheel) Electric heating & R410a DX Cooling coil Type L m3/hr pa mm mm mm kg Pcs dB dB kW kW V Hz ph kW A A kW A A
VAWLL4000AW 4000 3630 1680 1154 762 1 87.4 83.3 5.15 36
2.2 4.28 35.52 1.5 3.19 22.65 ERQ100A EKEXV63 EKEQFCB
VAWLL7000AW 7000 250 3700 2080 1354 971 1 86.9 82.1 9.02 60 F6 + G4 400 50 3 3 5.6 40.88 3 6.19 46.43 Recommendation for connection to Daikin condensing units ERQ100A EKEXV80 EKEQFCB
VAWLL9000AW 9000 3750 2280 1454 1133 1 91.2 86.3 11.6 82.5
4 7.11 50.48 4 7.81 56.23 ERQ125A EKEXV100 EKEQFCB
179 2515_BOOK_Ventilation_2011.indb 179
21/03/2011 08:50
180 2515_BOOK_Ventilation_2011.indb 180
21/03/2011 08:50
2515_BOOK_ControlSystems_2011.indb 181
21/03/2011 07:34
Control systems In order to realise maximum efficiency, commercial air conditioning systems must be subject to precise, 24 hour control.
Daikin manufactures and markets a complete suite of advanced computerised central control and monitoring systems designed to simplify air conditioning management and reduce energy usage running costs. Daikin computerised control systems not only provide the highly sophisticated regulation and day to day monitoring necessary for modern, hi tech air
conditioning installations â&#x20AC;&#x201C; they also provide owners, landlords and tenants of commercial buildings with valuable performance data on consumption as well as a wide range of operating parameters. Dedicated Daikin central control can be applied to both VRVÂŽ and mixed VRVÂŽ/Sky Air and Split installations with up to 1,024 indoor units and can also be integrated with building management systems.
1. Individual control systems
Wired remote control Simplified remote control Infrared remote control
183 183 183
2. Network solutions
Intelligent Touch Controller Intelligent Manager DMS-IF BACnet Gateway DNSS EcoSave
184 186 187 187 189
For a copy of our latest Price List please call 0845 6419000
182 Control systems.indd 182
30/03/2011 19:38
Individual control systems
BRC1E51A
BRC2C51
BRC4*/BRC7*
BRC1E51A
BRC2C51
BRC4*/BRC7*
User-friendly remote control with contemporary design.
Simple, compact and easy to operate unit, suitable for use in hotel bedrooms.
Operation buttons: ON/OFF, operating mode selection, fan speed control, temperature setting, menu management.
Operation buttons: ON/OFF, operating mode selection, fan speed control, temperature setting.
Easy Setup: All main functions directly accessible, improved graphical user interface for advanced menu settings.
Display: Cool/heat changeover control, Heat Recovery Ventilation (HRV) in operation, set temperature, operating mode, centralised control indication, fan speed, defrost/hot start, malfunction adjustment, operating mode selection, fan speed control, filter sign reset, inspection test/operation.
Operation buttons: ON/OFF, timer mode start/stop, timer mode on/off, programme time, temperature setting, air flow direction (FXHQ, FXFQ, FXCQ and FXAQ models only), operating mode, fan speed control, filter sign reset, inspection / test indication.
Wired remote control
Display: Real time clock with auto update to daylight saving time, schedule timer with holiday setting, weekly timer and home leave operation, built-in backup power when a power failure occurs, all settings remain stored up to 48 hours.
Multilingual display Guide on display Backlight Contrast adjustment Keylock Built-in, backup power Schedule and setback capabilities User restriction options Louver position adjustment Reports system malfunctions Space temperature sensor Simultaneous operation with Daikin multi-zone controllers Simultaneous operation with BACnet® and LonWorks® Group control capacity Communications 1
Simplified remote control
Infrared remote control
Display: Operating mode, battery change, set temperature, air flow direction (FXHQ, FXFQ, FXCQ and FXAQ models only), programmed time, inspection/test operation, fan speed.
Wired remote control BRC1E51A
'Simplified' (built-in) wired remote BRC2C51 / BRC3A61
Wireless remote control BRC4* / BRC7*
Up to 16 indoor units 2-wire / P1-P2
Up to 16 indoor units 2-wire / P1-P2
1 Up to 16 indoor units Infrared
Audible tones from the indoor unit indicate existing malfunction details
183 2515_BOOK_ControlSystems_2011.indb 183
21/03/2011 07:34
Network solutions Allows detailed & easy monitoring and operation of VRV® systems (max. 2 X 64 groups/indoor units). third party controller (domotics, BMS, etc.)
Public line Airconditioning Network Service System
Onboard modem
Fire alarm
Ethernet Forced OFF contact input
PCMCIA flash memory
DIII-NET
• CSV output of PPD (option) result
Indoor units
HRV
Pi-port Onboard Ethernet port
DIO unit Links to the wattmeter when using the PPD (option) function
Controls drain pump lighting etc.
Malfunction
Monitoring of room enter/ exit sign DI unit
Remote monitoring/control via internet, e-mail PPD data is available on the internet RS-232C
DIII-NET Allows monitoring/control of up to 64 units (groups) of A/Cs and equipment
DIII-NET PLUS adapter Indoor units
Languages • English • German • Portuguese
• French • Italian
• Spanish • Dutch
System layout • Up to 2 x 64 indoor units can be controlled • Onboard Ethernet port (web browser + e-mail) • Digital i/o contacts (option) • Touch panel (full colour LCD via icon display)
Management • Web application & internet compatibility - Monitoring & control according to user - Remote monitoring & control of more than one building - Remote monitoring & control of more than one building via internet • Power Proportional Distribution: PPD (option) • PPD data is available on the internet • Easy management of electricity consumption • Enhanced history function
HRV
Control
Monitoring
• Individual control (set point, start/stop, fan speed) (max. 2 x 64 groups/indoor units) • Enhanced scheduling function (8 schedules, 17 patterns) • Flexible grouping in zones • Yearly schedule • Fire emergency stop control • Interlocking control • Increased HRV monitoring and control function • Automatic cooling / heating change-over • Heating optimization • Temperature limit • Password security: 3 levels (general, administration & service) • Quick selection and full control • Simple navigation • Set back schedule new
• • • •
Visualisation via Graphical User Interface (GUI) Icon colour display change function Indoor units operation mode Error messages via e-mail & mobile phone (option) • Indication filter replacement • Multi PC
Cost performance • Free cooling function new • Labour saving • Easy installation • Compact design: limited installation space • Overall energy saving
Open interface • Communication to any third party controller (domotics, BMS, etc.) is possible via open interface
Connectable to: • VRV® • HRV
• Sky Air (via interface adapter) • Split (via interface adapter)
184 2515_BOOK_ControlSystems_2011.indb 184
21/03/2011 07:34
Network solutions Free Cooling function The combined application of the VRV system with VAM Heat Recovery Ventilation units can be greatly enhanced with the use of the Intelligent Touch Controller with it’s optional software which can support free cooling interlock with the VAM units providing cooling whilst restricting the VRV Indoor Units whenever the external temperature is within free cooling limits.
Advantages • Reduces the energy consumption and uses energy in a more efficient way, by directly introduction of fresh air into rooms. • Maintains indoor comfort through the introduction of low temperature outdoor air.
Free cooling function is possible when the outdoor temperature is less than the indoor room temperature
To perform this feature the Intelligent Touch Controller is required with the Free Cooling Software Update and also the use of the optional Outdoor Temperature Sensor Kit DAM101A51.
185 2515_BOOK_ControlSystems_2011.indb 185
21/03/2011 07:34
Network solutions [iPU]
The ideal solution for control and management of maximum 1,024 VRV® indoor units.
~
Intranet/Internet Web Access
Web Access Malfunction report by E-Mail
Air Conditioning Network Service System (Optional Maintenance Service)
(Via Internet) Ai unit
DAM602B51/52
DIII-NET DIII-NET Dio unit
~
Sub PC
DIII-NET
ETHERNET
DIII-NET
Fire alarm
Power supply facility · Elevator · Pump · Lighting,...
Electricity Measurement
VRV® System
Local monitoring & control
Daikin Central Air Conditioning System HRV
Languages
Management
Monitoring
• • • • • • •
• Web access (option) • Power Proportional Distribution (option) • Operational history management (start/stop, malfunction, operation hours) • Generation of reports (graphics & tables) (daily, weekly, monthly) • Peak load shedding • Advanced tenant management • Sliding temperature • Eco mode (option) • Pre cooling and heating function new
• Visualisation via a Graphical User Interface (GUI) featuring free layout • Operation mode of indoor units • Fault indication • Indication filter replacement • Setpoint indication • Operation time monitoring • Multi PC • On-line help
English French German Italian Spanish Dutch Portuguese
System layout • Up to 1,024 indoor units can be controlled (by 4 iPUs) • Ethernet TCPIP / 10 base / T communication • Integrated digital contacts on the Intelligent Processing Unit (iPU) · 20 general input ports · 2 digital outputs • Stand alone operation of the iPU for minimum 48 hours • Compatible with UPS shutdown software
Control • Individual control (setpoint, start/stop, fan speed) (max. 1,024 indoor units) • Group control (100 groups) • Schedule control (128 programs) • Fire emergency stop control (32 programs) • Interlocking control • Setpoint limitation • Automatic cooling/heating change-over • Power failure/release control • Temperature limit (automatic start) • Timer extension
Cost performance • Labour saving • Easy installation • Compact design: limited installation space • Overall energy saving
Connectable to: • VRV® • HRV • Sky Air (via interface adapter) • Split (via interface adapter)
186 2515_BOOK_ControlSystems_2011.indb 186
21/03/2011 07:34
Network solutions LON BMS ®
dms504b51
LonWorks® Networks Compatible Gateway
LonTalk
DIII- NET
ETHERNET (TCP/IP)
adapter
• Interface for Lon connection to LonWorks® networks • Communication via Lon® protocol (twisted pair wire) • 64 units connectable per DMS-IF • Unlimited sitesize • Quick and easy installation
Local Control VRV® Outdoor unit HRV
LonTalk adapter Remote Control LonPoint
LonPoint
BUILDING CONTROL NETWORK
DAIKIN A/C INFRASTRUCTURE
Security
BMS
Fire alarm System
DMS502A51
Integrated control system connecting VRV® system with BMS system Local Control
VRV® Outdoor unit BACNET / ETHERNET
• PPDdata is available on BMS system • Interface for BMS system • Communication via BACnet protocol (connection via Ethernet) • 256 units connectable per BACnet gateway • Unlimited sitesize • Easy and fast installation
DIII- NET
HRV
DAIKIN A/C INFRASTRUCTURE
Remote Control
Fire alarm
BUILDING CONTROL NETWORK
Pump
Security
Lighting
Power supply facility
Elevator
187 2515_BOOK_ControlSystems_2011.indb 187
21/03/2011 07:34
2515_BOOK_ControlSystems_2011.indb 188
21/03/2011 07:34
Daikin network service system Remote monitoring and diagnostics system for professionals The Daikin Network Service System is designed to optimise the running of your air conditioning equipment, increasing its operational efficiency, minimising possible down time and increasing customer comfort levels.
189 2515_BOOK_ControlSystems_2011.indb 189
21/03/2011 07:34
Unique innovation by Daikin What is the Daikin Network Service System (DNSS)? The DNSS is a remote monitoring system, which will allow you to continuously optimise the running of your Daikin equipment; control your energy consumption (so reduce your Carbon Footprint), extend the lifespan of your equipment and reduce operational costs.
YOUR INSTALLATION UNDER CONTINUOUS MONITORING • 24/7/365 remote monitoring • Predictive maintenance
Prevent product malfunctions The DNSS will analyse the data from your equipment every minute of the day and will alert us before the equipment actually breaks down. In this way, failures can be prevented and possible down time reduced to an absolute minimum.
Remote diagnostics
• Improved reliability • Improved comfort levels • Helps increase efficiency • Helps reduce maintenance costs • Extends product lifetime
The DNSS continuously checks the cleanliness of the system filters and heat exchanger. Furthermore, the DNSS manages a wide range of data (pressures, temperatures, running hours, etc.) in order to let your equipment run as efficiently and trouble free as possible. This will also prevent your equipment from using too much energy.
Extend product lifetime
extra value at low cost • A strategy of preventing breakdowns and limiting unnecessary maintenance visits
The DNSS is designed to make sure that your equipment is maintained and running as efficiently as possible. This optimisation will extend the lifespan of your equipment.
• Efficiently organising site interventions by diagnosing the nature and the extent of the problem before going to site
Malfunction messages
• Innovative technology that helps to optimise your equipment’s potential
In the unlikely event of a problem occurring, your regional Daikin office will contact you directly. Our engineers, who are dedicated to your installation, will inform you regarding the nature of the problem and will help you towards the next step of solving the problem.
• Ensures the most comfortable environment in your premises
190 2515_BOOK_ControlSystems_2011.indb 190
21/03/2011 07:34
2515_BOOK_AppliedSystems_2011.indb 191
25/03/2011 08:38
Applied systems Precise environmental control is vital in many industrial and commercial applications. Daikin offers an outstanding range of powerful air cooled, water cooled and condenserless chiller systems that will maintain ideal conditions in even the largest premises.
Daikin water chillers are of advanced design, compact and easy to install and maintain. They prove flexible and effective in multiple process cooling applications in for example, fish farms, wine cellars, maritime transport, agricultural, pharmaceutical or industrial processes. When combined with air handling units or Daikin fan coil units of course, they are ideal for air conditioning offices, hotels, restaurants and even domestic premises. Matched and flexible equipment/refrigerant combinations enable Daikin to offer a
1. Air cooled chiller
For a copy of our latest Price List please call 0845 6419000
new new new new new new new new new new
complete range of chillers, genuinely optimised for use with R-134a, R-407C and R-410A. All chiller components â&#x20AC;&#x201C; evaporator, condenser, dryer, oil etc â&#x20AC;&#x201C; have been specially selected for use with either R-407C, R-410A or R-134a refrigerants. The end result is a range of hi tech, high performance units, indicated by published EUROVENT data to be among the most energy efficient of their type on the market. Advanced technology, unsurpassed product reliability and quality, make Daikin chillers the first choice for professionals.
2. Condensing unit
EWAQ-ACV3 EWAQ-ACW1 EWYQ-ACV3 EWYQ-ACW1 EUWAC-FBZW1 EUWA*-KBZW1 EUWY*-KBZW1 EWAQ-DAYN EWYQ-DAYN EWAD-E-SS EWAD-E-SL EWAD-D-SS EWAD-D-SL EWAD-D-SR EWAD-D-SX EWAD-D-XS EWAD-D-XR EWAD-D-HS EWAD-BZSS/SL EWAD-BZXS/XL/XR EWYD-BZSS EWYD-BZSL EWAD-C-SS/SL EWAD-C-SR EWAD-C-XS/XL EWAD-C-XR EWAD-C-PS/PL EWAD-C-PR
195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222
ERAD-E-SS ERAD-E-SL
225 226
3. Water cooled chiller new
new new new new new
EWWP-KBW1N EWWD-MBYN EWWD-G-SS EWWD-G-XS EWWD-I-SS EWWD-I-XS EWWD-BJYNN EWWQ-AJYNN EWWQ-AJYNN/A EWWD-FZXS
229 231 232 233 234 235 236 237 238 239
4. Water cooled condenserless chiller new new
EWLP-KBW1N EWLD-MBYN EWLD-G-SS EWLD-I-SS
241 242 243 244
DICN (Daikin Integrated Chiller Network)
245
EHMC, EKBT (Hydraulic Module)
246
192 2515_BOOK_AppliedSystems_2011.indb 192
25/03/2011 08:38
Daikin chiller range Daikinâ&#x20AC;&#x2122;s 50 years of experience manufacturing chillers, has given us a comprehensive portfolio of cooling only, heat pumps and heat recovery models.
The range includes 5 kW to 2,200 kW, utilising both scroll and screw compressors designed and manufactured by Daikin. Now introducing a new range of inverter screw chillers with ESEERs over 5.
2000
1750
1500
1250
1000
Cooling Capacity (kW)
800
600
400
300
200
100
0
2000
1750
1500
1250
1000
50
Condenserless Range
Cooling Capacity (kW)
800
600
400
300
200
100
0
2000
1750
1500
1250
1000
800
50
Water Cooled Range
Cooling Capacity (kW)
600
400
300
200
100
50
0
Air Cooled Range
EWAQ080-260DY
R407c
EWYQ005-013AC
R410a
R410a
EWAQ005-013AC EWWQ400-C22A
EWLP012-065KB
EUWA5-24KB EUWY5-24KB
EWWP014-065KB
R134a
EWLD120-540MB EWLD340-C17I
EWWD170-600G
EWAD180-620D
EWAD650-C120
EWLD160-550G
EWWD120-540MB
EWAD330-490B
EWYD260-580BZ
R134a
R407c
R407c
EWYQ080-250DY
EWWD380-C11B EWWD340-C19I
COOLING ONLY
EWWD320-C10FZ
HEAT PUMP
193 2515_BOOK_AppliedSystems_2011.indb 193
25/03/2011 08:38
Air cooled chiller In the chilled water market, chillers of the air cooled type are most frequently used. Out of its wide range of chillers in cooling only or heat pump version, with or without integrated hydronic components, Daikin always offers you a chiller fitting your application needs.
Air cooled chiller new new new new new new
EWAQ-ACV3 EWAQ-ACW1 EWYQ-ACV3 EWYQ-ACW1 EUWAC-FBZW1 EUWA*-KBZW1 EUWY*-KBZW1 EWAQ-DAYN EWYQ-DAYN EWAD-E-SS EWAD-E-SL EWAD-D-SS EWAD-D-SL EWAD-D-SR
195 196 197 198 199 200 201 202 203 204 205 206 207 208
new new new new
EWAD-D-SX EWAD-D-XS EWAD-D-XR EWAD-D-HS EWAD-BZSS/SL EWAD-BZXS/XL/XR EWYD-BZSS EWYD-BZSL EWAD-C-SS/SL EWAD-C-SR EWAD-C-XS/XL EWAD-C-XR EWAD-C-PS/PL EWAD-C-PR
209 210 211 212 213 214 215 216 217 218 219 220 221 222
For a copy of our latest Price List please call 0845 6419000
194 2515_BOOK_AppliedSystems_2011.indb 194
25/03/2011 08:38
EWAQ-ACV3
EWAQ005-011ACV3
Air cooled mini chiller inverter
Options (factory mounted) • Evaporator heater tape
Strengths • Optimised for use with R-410A • Inverter controlled swing compressor (size 005-007) - Precise temperature control • Inverter controlled scroll compressor (size 009-011) • ESEER up to 4.57 • Cooling operation from 10°C to 46°C (to 43°C for size 005-007) • PE treated condenser coil • Built-in hydraulic module: - No buffer tank required - 2-speed or 3-speed pump • Sound power down to 62dBA • Main switch accessible without removing panels • Refrigerant charge less than 3 kg • Easy ‘plug and play’ installation
Option kit • Digital Input/Output PCP (size 009-011 only) Control • Leaving water control Available inputs • Voltage free contact: - ON/OFF Schedule timer: - ON/OFF - Silent operation
Cooling ONLY Capacity class Cooling capacity Power input EER ESEER Dimensions Weight Water heat exchanger
Nom. Cooling
Unit Unit Type Water volume Nominal water flow Air heat exchanger Type Pump Nominal ESP unit Hydraulic components Expansion vessel Fan Air flow rate Fan motor Speed Sound power level Sound pressure level Compressor Operation range Refrigerant
Water circuit Piping connections Power supply
INVERTER kW kW
Nom.
005 5.2 1.89 2.75 3.75
006 6.0 2.35 2.55 3.83 805x1,190x360 100
HeightxWidthxDepth mm kg
007 7.1 2.95 2.41 3.87
009 8.5 2.74 3.11 4.57
010 9.5 3.19 2.98 4.52 1,435x1,418x382 180
011 11.0 3.82 2.88 4.46
Brazed plate l l/min
Cooling Cooling Volume Cooling Cooling Steps Nom. Nom. Cooling
Nom. Nom.
Cooling Cooling Night quiet mode Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Control Circuits Quantity Piping connections diameter Piping Water heat exchanger inlet / outlet Water heat exchanger drain Phase / Frequency / Voltage
kPa l m³/min rpm dBA dBA dBA °CDB °CDB
17.2 Tube type 45.1 6 -
14.9 49.4
62 48
20.4
24.4
38.3
58.0 96
63 50
Hermetically sealed swing compressor 5~20 10~43
1.01 27.2 Hi-XSS 54.6 10 100 780 8 64 51 45 Hermetically sealed scroll compressor 5~22 10~46
31.5 49.1 97
R-410A kg
1.7
2.95 Electronic expansion valve 1
inch inch
1" MBSP Hose nipple 1/2" FBSP
G 5/4" (female) 5/4" 1~ / 50 / 230
Hz / V
195 2515_BOOK_AppliedSystems_2011.indb 195
25/03/2011 08:38
EWAQ-ACW1
EWAQ009-013ACW1
Air cooled mini chiller inverter
Options (factory mounted) • Evaporator heater tape
Strengths • Optimised for use with R-410A • Precise temperature control • Inverter controlled scroll compressor • ESEER up to 4.68 • Cooling operation from 10°C to 46°C • PE treated condenser coil • Built-in hydraulic module: - No buffer tank required - 2-speed or 3-speed pump • Sound power down to 62dBA • Main switch accessible without removing panels • Refrigerant charge less than 3kg • Easy ‘plug and play’ installation
Option kit • Digital Input/Output PCP Control • Leaving water control Available inputs • Voltage free contact: - ON/OFF Schedule timer: - ON/OFF - Silent operation
Cooling ONLY Indoor units Cooling capacity Power input EER ESEER Dimensions Weight Water heat exchanger
Nom. Cooling
Unit Unit Type Water volume Nominal water flow Air heat exchanger Type Pump Nominal ESP unit Hydraulic components Expansion vessel Fan motor Speed Sound power level Sound pressure level Compressor Operation range Refrigerant
Water circuit Power supply
INVERTER kW kW
Nom.
009 9.0 2.96 3.04 4.68
011 11.0 3.82 2.88 4.63 1,435x1,418x382 180 Brazed plate 1.01 31.5 Hi-XSS 49.1 10 780 8
HeightxWidthxDepth mm kg l l/min
Cooling Cooling Volume Cooling Steps Nom. Nom. Cooling
Cooling Cooling Night quiet mode Type Water side Cooling Air side Cooling Type Charge Control Circuits Quantity Piping connections diameter Piping Phase / Frequency / Voltage
Nom.
kPa l rpm
25.8 56.4
dBA dBA dBA Min.~Max. Min.~Max.
64 51 45
013 13.2 5.10 2.59 4.52
37.8 40.9
66 52 46 Hermetically sealed scroll compressor 5~22 10~46 R-410A 2.95 Electronic expansion valve 1 G 5/4" (female) 5/4" 3N~ / 50 / 400
°CDB °CDB kg
inch inch Hz / V
196 2515_BOOK_AppliedSystems_2011.indb 196
25/03/2011 08:38
EWYQ-ACV3
EWYQ005-011ACV3
Air cooled mini chiller inverter
• • •
Strengths • Optimised for use with R-410A • Inverter controlled swing compressor (size 005-007) - Precise temperature control • Inverter controlled scroll compressor (size 009-011) • ESEER up to 4.57 • COP up to 3.44 • Cooling operation from 10°C to 46°C (to 43 °C for size 005-007) • Heating operation from -15°C to 35°C (to 25 °C for size 005-007) • PE treated condenser coil
Nom. Nom. Cooling Heating
EER COP ESEER Dimensions Weight
Nom. Nom.
Available inputs • Voltage free contact: - ON/OFF - Cooling/Heating changeover • Schedule timer: - ON/OFF - Dual setpoint - Silent operation
Options (factory mounted) • Evaporator heater tape Option kit • Digital Input/Output PCP (size 009-011 only)
HEATING & Cooling Capacity class Cooling capacity Heating capacity Power input
Control • Leaving water control • Setpoint in heating & cooling
Built-in hydraulic module - No buffer tank required - 2-speed or 3-speed pump Sound power down to 62dBA Main switch accessible without removing panels • Refrigerant charge less than 3kg • Easy ‘plug and play’ installation
INVERTER kW kW kW kW
Unit HeightxWidthxDepth mm Unit kg Operation weight kg Water heat exchanger Type Water volume l Nominal water flow Cooling l/min Heating l/min Air heat exchanger Type Pump Nominal ESP unit Cooling kPa Hydraulic components Expansion vessel Volume l Fan Air flow rate Cooling Nom. m³/min Heating Nom. m³/min Fan motor Speed Cooling Nom. rpm Heating Nom. rpm Steps Sound power level Cooling Nom. dBA Heating Nom. dBA Sound pressure level Cooling Nom. dBA Heating Nom. dBA Night quiet mode Cooling dBA Heating dBA Compressor Type Operation range Water side Cooling Min.~Max. °CDB Heating Min.~Max. °CDB Air side Cooling Min.~Max. °CDB Heating Min.~Max. °CDB Refrigerant Type Charge kg Control Circuits Quantity Water circuit Piping connections diameter inch Piping inch Piping connections Water heat exchanger inlet / outlet Water heat exchanger drain Power supply Phase / Frequency / Voltage Hz / V
005 5.2 5.65 1.89 1.97 2.75 2.87
006 6.0 6.35 2.35 2.24 2.55 2.83 805x1,190x360 100 104
007 7.1 7.75 2.95 2.83 2.41 2.74
009 8.5 10.0 2.74 2.91 4.37 3.44 4.57
010 9.5 11.5 3.19 3.38 2.98 3.40 4.52 1,435x1,418x382 180 -
011 11.0 13.0 3.82 3.86 2.88 3.37 4.46
Brazed plate 17.2 19.5 Tube type 45.1 6 -
14.9 17.5 49.4
62
20.4 23.5
24.4 28.7
38.3
58.0 96
63 -
48 48
50 49
Hermetically sealed swing compressor 5~20 25~50 10~43 -15~25
1.01 27.2 33.0 Hi-XSS 54.6 10 100 90 780 760 8 64 64 51 51 45 42 Hermetically sealed scroll compressor 5~22 25~50 10~46 -15~35
31.5 37.3 49.1 97
R-410A 1.7
2.95 Electronic expansion valve 1
1" MBSP Hose nipple 1/2" FBSP
G 5/4" (female) 5/4" 1~ / 50 / 230
197 2515_BOOK_AppliedSystems_2011.indb 197
25/03/2011 08:38
EWYQ-ACW1
EWYQ009ACW1
Air cooled mini chiller inverter
Options (factory mounted) • Evaporator heater tape
Strengths • Optimised for use with R-410A • Precise temperature control • Inverter controlled scroll compressor (size 009-011) • ESEER up to 4.68 • COP up to 3.41 • Heating operation from -15°C to 35°C (to 25 °C for size 005-007) • PE treated condenser coil • Built-in hydraulic module - No buffer tank required - 2-speed or 3-speed pump • Sound power down to 62dBA • Main switch accessible without removing panels • Refrigerant charge less than 3kg • Easy ‘plug and play’ installation
Available inputs • Voltage free contact: - ON/OFF - Cooling/Heating changeover • Schedule timer: - ON/OFF - Dual setpoint - Silent operation
Option kit • Digital Input/Output PCP (size 009-013 only) Control • Leaving water control • Setpoint in heating & cooling
HEATING & Cooling Indoor units Cooling capacity Heating capacity Power input
Nom. Nom. Cooling Heating
Nom. Nom.
INVERTER kW kW kW kW
EER COP ESEER Dimensions Unit HeightxWidthxDepth mm Weight Unit kg Water heat exchanger Type Water volume l Nominal water flow Cooling l/min Heating l/min Air heat exchanger Type Pump Nominal ESP unit Cooling kPa Hydraulic components Expansion vessel Volume l Fan motor Speed Cooling Nom. rpm Heating Nom. rpm Steps Sound power level Cooling Nom. dBA Heating Nom. dBA Sound pressure level Cooling Nom. dBA Heating Nom. dBA Night quiet mode Cooling dBA Heating dBA Compressor Type Operation range Water side Cooling Min.~Max. °CDB Heating Min.~Max. °CDB Air side Cooling Min.~Max. °CDB Heating Min.~Max. °CDB Refrigerant Type Charge kg Control Circuits Quantity Water circuit Piping connections diameter inch Piping inch Power supply Phase / Frequency / Voltage Hz / V
009 9.0 11.0 2.96 3.23 3.04 3.41 4.68
011 11.0 12.5 3.82 3.70 2.88 3.38 4.63 1,435x1,418x382 180 Brazed plate 1.01 31.5 35.8 Hi-XSS 49.1 10 780 760 8
25.8 31.5 56.4
64
013 13.2 14.0 5.10 4.19 2.59 3.34 4.52
37.8 40.1 40.9
66 64
51
52 51
45 42
46 43 Hermetically sealed scroll compressor 5~22 25~50 10~46 -15~35 R-410A 2.95 Electronic expansion valve 1 G 5/4" (female) 5/4" 3N~ / 50 / 400
198 2515_BOOK_AppliedSystems_2011.indb 198
25/03/2011 08:38
Air cooled chiller with centrifugal fan
EUWAC-FBZW1
EUWAC8FBZW1
Air cooled chiller with centrifugal fan
Control • Water inlet temperature control
Strengths • Daikin scroll compressor • Standard reverse phase protection • High fan static pressure (up to 150Pa) • Operation down to -10°C ambient temperature • Pressure gauges
Available inputs / outputs • Input - ON / OFF (per circuit) - Pump / flow switch • Output - Compressor operation - Summary alarm - Pump relay contact
Options (factory mounted) • Chilled water temperature down to - 5°C (OPZH) or -10°C (OPZL)
* OPZH: Option LWE high glycol OPZL: Option LWE low glycol
Accessories (kit) • Filter • BMS gateway (MODBUS / J-BUS protocol) • Remote user interface • Hydraulic module (see also EHMC)
Cooling ONLY Capacity class Cooling capacity Capacity steps Power input EER Dimensions Weight
Nom. Cooling
Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type - evaporator Minimum water volume in the system Water flow rate Nom. Nominal water Cooling Heat pressure drop exchanger Model Type Quantity Air heat exchanger Type Fan Air flow rate Nom. Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Evaporator water drain Power supply Phase / Frequency / Voltage
kW % kW mm kg kg l l/min kPa
m³/min dBA
5 11.6 5.2 2.23 1,345x856x630 164 166 101 33
10 23.8 9.67 2.46 1,395x1,330x630 261 266 212 68
26
42
48
AC70-24
AC70-34 1 Cross fin coil/Hi-X tubes and PE coated waffle louvre fins 109.8 66 Hermetically sealed scroll compressor -10 (OPZL) ~ 21 -10 ~ 43 R-407C Thermostatic expansion valve 1 3.9 FBSP 1" Field installation 3N~ / 50 / 400
AC70-40
70.2 63
°CDB °CDB
kg
8 18.4 100-0 7.66 2.40 1,290x1,180x630 224 228 Brazed plate, one per circuit 153 53
2.1
Hz / V
126 69
4.7
199 2515_BOOK_AppliedSystems_2011.indb 199
25/03/2011 08:38
EUWA*-KBZW1 Air cooled chiller
EUWA*16KBZW1
Options (factory mounted) • Chilled water temperature down to - 5°C (OPZH) or -10°C (OPZL) • High ESP fans (50Pa) (OPHF) • Pump size up (OPHP)
Strengths • Optimised for use with R-407C • Integrated hydraulic module (models B and P) • Built-in buffer tank (model B) • Daikin scroll compressor • Standard main isolator switch • Standard water flow switch • Standard filter (delivered as a kit with the unit) • Operation down to -15°C ambient temperature • Standard reverse phase protection • Standard condenser protection grille • Freeze-up protection and prevention • PE treated condenser coil
Accessories (kit) • Refrigerant pressure gauges • Address card and BMS gateway (MODBUS / J-BUS protocol) • Remote user interface • 200l buffer tank • Soft starter (single circuit)
Control • Water inlet temperature control Available inputs / outputs • Input - Remote ON / OFF - Pump contact • Output - Compressor operation - Summary alarm - Pump relay contact
Cooling ONLY Capacity class Cooling capacity Capacity steps Power input EER Dimensions Weight
N5 Nom. Cooling
Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Hydraulic components Expansion vessel Volume Fan group Air flow rate Cooling Nom. Fan group 2 Air flow rate Cooling Nom. Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Refrigerant circuit 2 Charge Water circuit Piping connections diameter Piping Power supply Phase / Frequency / Voltage
kW % kW mm kg kg l l/min kPa
l m³/min m³/min dBA
150 152
P5 11.3
B5
N8
N10 P10 B10 N12 P12 B12 N16 P16 B16 N20 P20 B20 N24 P24 B24 22.5 26.5 34.6 46.6 55.3 0-100 0-50-100 4.48 7.27 8.64 11.50 14.70 17.90 23.80 2.53 2.46 2.60 2.30 2.35 2.60 2.32 1,230x1,290x734 1,450x1,290x734 1,321x2,580x734 1,541x2,580x734 168 180 215 229 241 245 259 271 248 262 274 430 448 460 490 508 520 496 514 526 171 239 218 232 300 248 262 330 251 265 335 436 457 525 496 518 545 503 524 592 Brazed plate 1.14 1.615 1.9 2.375 2.964 3.9 4.524 32 51 64 76 99 134 158 24
12 160 (per 2 fans)
P8 19.7
B8
38 -
43
37
22
Cross fin coil/Hi-X tubes and PE coated waffle louvre fins 12 12 12 170 (per 2 fans)
12 -
67
76
3.9
4.6
12
-
12
170 (per 2 fans) 78 79 Hermetically sealed scroll compressor -10 (OPZL) ~ 25 -15 ~ 43 R-407C Thermostatic expansion valve
°CDB °CDB
1 kg kg inch inch Hz / V
-
5.9
6.0
G 1"1/4 (male) 1-1/4"
4.6 4.6
81
2 5.9 5.9 2" male -
6.0 6.0
3N~ / 50 / 400
200 2515_BOOK_AppliedSystems_2011.indb 200
25/03/2011 08:38
EUWY*-KBZW1 Air cooled chiller
EUWY*16KBZW1
Options (factory mounted) • Chilled water temperature down to - 5°C (OPZH) or -10°C (OPZL) • High ESP fans (50Pa) (OPHF) • Pump size up (OPHP)
Strengths • Optimised for use with R-407C • Integrated hydraulic module (models B and P) • Built-in buffer tank (model B) • Daikin scroll compressor • Standard main isolator switch • Standard water flow switch • Standard filter (delivered as a kit with the unit) • Operation down to -15°C ambient temperature in cooling mode, down to -10°C in heating mode • Standard reverse phase protection • Standard condenser protection grille • Freeze-up protection and prevention • PE treated condenser coil
Accessories (kit) • Refrigerant pressure gauges • Address card and BMS gateway (MODBUS / J-BUS protocol) • Remote user interface • 200l buffer tank • Soft starter (single circuit)
Control • Water inlet temperature control Available inputs / outputs • Input - Remote ON / OFF - Pump contact - Remote cool / heat selection • Output - Compressor operation - Summary alarm - Pump relay contact
HEATING & Cooling Capacity class Cooling capacity Heating capacity Capacity steps Power input
N5
Nom. Nom. Cooling Heating
EER COP Dimensions Weight
Nom. Nom.
kW kW % kW kW
Unit HeightxWidthxDepth mm Unit kg Operation weight kg Water heat exchanger Type Water volume l Nominal water flow Cooling l/min Heating l/min Nominal water Cooling Filter kPa pressure drop Heating Filter kPa Air heat exchanger Type Hydraulic components Expansion vessel Volume l Fan group Air flow rate Cooling Nom. m³/min Fan group 2 Air flow rate Cooling Nom. m³/min Sound power level Cooling Nom. dBA Compressor Type Operation range Water side Cooling Min.~Max. °CDB Heating Min.~Max. °CDB Air side Cooling Min.~Max. °CDB Heating Min.~Max. °CDB Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge kg Refrigerant circuit 2 Charge kg Water circuit Piping connections diameter inch Piping inch Power supply Phase / Frequency / Voltage Hz / V
P5 9.1 11.9
B5
N8
P8 17.1 18.5
B8
N10 P10 B10 N12 P12 B12 N16 P16 B16 N20 P20 B20 N24 P24 B24 21.0 25.0 34.2 40 50.0 24.0 27.0 37.0 46 54.0 0-100 0-50-100 3.77 7.38 8.49 11.3 14.8 16.2 22.6 4.56 7.01 8.98 10.7 14.10 17.3 21.4 2.41 2.32 2.47 2.21 2.3 2.5 2.2 2.61 2.64 2.67 2.52 2.62 2.66 2.52 1,230x1,290x734 1,450x1,290x734 1,321x2,580x734 1,541x2,580x734 163 181 193 227 241 253 258 272 284 258 272 284 455 473 485 516 534 546 516 534 546 165 184 252 230 244 312 261 275 343 261 275 343 461 482 550 522 544 612 522 544 612 Brazed plate 1.140 1.615 1.900 2.375 2.964 3.900 4.524 26 49 60 72 98 115 143 34 53 69 77 106 132 155 10 25 24 33 12 19 17 29 31 38 14 16 22 Cross fin coil/Hi-X tubes and PE coated waffle louvre fins 12 12 12 12 12 12 12 160 (per 2 fans) 170 (per 2 fans) 170 (per 2 fans) 67 76 78 79 81 Hermetically sealed scroll compressor -10(OPZL) ~ 20 35 ~ 50 -15 ~ 43 -10 ~ 21 R-407C Thermostatic expansion valve 1 2 4.6 4.7 5.4 5.1 5.4 5.6 5.1 5.4 5.6 G 1"1/4 (male) 2" male 1-1/4" 2" 3N~ / 50 / 400
201 2515_BOOK_AppliedSystems_2011.indb 201
25/03/2011 08:38
EWAQ-DAYN
EWAQ130-150DAYN
Air cooled chiller, multiple scroll
Strengths • Wide capacity range: 80 to 254kW with 8 cooling only models • Optimised for use with R-410A refrigerant • Multiple refrigerant circuits and multiple compressors per circuit • Reliable and efficient scroll with high EER values • Good part load efficiency (seasonal EER) • Anti-corrosion treated aluminium coils • Low operating noise levels • Easy ’plug and play’ installation • Unit dimensions allow easy transport • Fans protected against abnormal operation (4 - 8 fans depending on unit size) • Safety valves in each circuit • Electronic circuit breakers • Electronic expansion valve
• • • • • • • • •
True dual plate brazed plate heat exchanger Sight glass All hydronics can be accessed easily from 3 sides (no surrounding cabinet) Separate switchbox for easy access Compressors and controls at side of unit Increased reliability via 2 independent refrigerant circuits Dual circuit heat exchanger (from >100 kW) Non hermetic filter/dryer Daikin controller (Pcaso) with user friendly and powerful LCD interface
Options (factory mounted) • Single pump contactor (OPSC) • Twin pump contactor (OPTC) • Single pump (OPSP) • Twin pump (OPTP) (1 pump casing, dual motor) • High ESP pump (OPHP) (single pump only) • Buffer tank (OPBT) • Inverter fans (OPIF) (Not available with option OPLN) • Glycol 0°C / -10°C (OPZL) • Dual pressure relief valve (OP03) • Evaporator heater tape (OP10) • Option valves (discharge, liquid line and suction stop valve) • A-meter / V-meter (OP57) • Low Noise (OPLN) (=OPIF + compressor housing) • Condenser protection grills (OPCG)
Cooling ONLY Capacity class Cooling capacity Capacity steps Power input EER ESEER Dimensions Weight
Nom.
Cooling
kW % Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Nominal water flow Cooling Nominal water Cooling Total pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Water heat exchanger inlet / outlet Water heat exchanger drain Power supply Phase / Frequency / Voltage
kW
mm kg kg l/min kPa
m³/min rpm dBA
080 80
100 105
180 210 240 260 182 209 236 254 21/29-43/50/5722/28-40/50/560-25-50-75-100 0-25-50-75-100 0-25-50-75-100 71/79-100 72/78-100 46.6 56.3 64.5 74.6 82.8 94.0 2.81 2.70 2.82 2.80 2.85 2.70 4.34 4.22 4.36 4.32 4.20 4.00 2,311x2,000x2,631 2,311x2,000x3,081 2,311x2,000x4,850 1,500 1,550 1,800 1,850 3,150 3,250 1,517 1,569 1,825 1,877 3,189 3,292 Brazed plate 377 436 522 599 677 728
0-50-100 26.4 36.2 3.03 2.90 4.12 4.00 2,311x2,000x2,566 1,350 1,400 1,365 1,415 229
301
59
58
150 152
52
49
52
53
Cross fin coil/Hi-Xss tubes and poly ethylene coated waffle fins 800 860 1,290 900 970 88 89 90 Scroll compressor -10 (OPZL) ~ 25 -15 ~ 43 R-410A 19 25 29 28 Electronic expansion valve 2 3" OD 1/2"G 3~ / 50 / 400
780 880 86
°CDB °CDB kg
130 131
33 1
Hz / V
51
47 1,600 900 91
39
3"
202 2515_BOOK_AppliedSystems_2011.indb 202
25/03/2011 08:38
EWYQ-DAYN
EWYQ130-150DAYN
Air cooled chiller, multiple scroll
Strengths • Wide capacity range: 77 to 252kW with 8 heat pump models • Optimised for use with R-410A refrigerant • Multiple refrigerant circuits and multiple compressors per circuit • Reliable and efficient scroll with high EER values • Good part load efficiency (seasonal EER) • Anti-corrosion treated aluminium coils • Low operating noise levels • Easy 'plug and play' installation • Unit dimensions allow easy transport • Fans protected against abnormal operation (4 - 8 fans depending on unit size) • Safety valves in each circuit • Electronic circuit breakers • Electronic expansion valve
• • • • • • • • •
True dual plate brazed plate heat exchanger Sight glass All hydronics can be accessed easily from 3 sides (no surrounding cabinet) Separate switchbox for easy access Compressors and controls at side of unit Increased reliability via 2 independent refrigerant circuits Dual circuit heat exchanger (from >100 kW) Non hermetic filter/dryer Daikin controller (Pcaso) with user friendly and powerful LCD interface
Options (factory mounted) • Single pump contactor (OPSC) • Twin pump contactor (OPTC) • Single pump (OPSP) • Twin pump (OPTP) (1 pump casing, dual motor) • High ESP pump (OPHP) (single pump only) • Buffer tank (OPBT) • Inverter fans (OPIF) (Not available with option OPLN) • Glycol 0°C / -10°C (OPZL) • Dual pressure relief valve (OP03) • Evaporator heater tape (OP10) • Option valves (discharge, liquid line and suction stop valve) • A-meter / V-meter (OP57) • Low Noise (OPLN) (=OPIF + compressor housing) • Condenser protection grills (OPCG)
HEATING & Cooling Capacity class Cooling capacity Heating capacity Capacity steps Power input
Nom. Nom.
Cooling Heating
EER COP ESEER Dimensions Weight
kW kW % Nom. Nom.
kW kW
Unit HeightxWidthxDepth mm Unit kg Operation weight kg Water heat exchanger Type Nominal water flow Cooling l/min Heating l/min Nominal water Cooling Total kPa pressure drop Heating Total kPa Air heat exchanger Type Fan Air flow rate Nom. m³/min Speed rpm Sound power level Cooling Nom. dBA Compressor Type Operation range Water side Cooling Min.~Max. °CDB Water side Heating Min.~Max. °CDB Air side Cooling Min.~Max. °CDB Air side Heating Min.~Max. °CDB Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge kg Refrigerant circuit 2 Charge kg Piping connections Water heat exchanger inlet / outlet Water heat exchanger drain Power supply Phase / Frequency / Voltage Hz / V
080 77 87.7
100 100 114
130 136 149
180 210 230 250 183 211 231 252 199 225.00 258 281 21/29-43/50/5722/28-44/50/560-25-50-75-100 0-25-50-75-100 0-25-50-75-100 71/79-100 72/78-100 47.6 55.7 63.8 75.3 82.2 93.5 49.6 58.8 68.0 77.0 84.2 96.6 2.86 2.60 2.87 2.80 2.81 2.70 3.00 2.81 2.93 2.92 3.06 2.91 4.31 4.07 4.33 4.23 4.20 4.00 2,311x2,000x2,631 2,311x2,000x3,081 2,311x2,000x4,850 1,550 1,600 1,850 1,900 3,200 3,300 1,567 1,619 1,875 1,927 3,239 3,342 Brazed plate, one per unit 390 416 525 605 662 722 427 473 570 645 740 806 43 38 41 44 39 38 51 49 48 50 48 46 Cross fin coil/Hi-Xss tubes and poly ethylene coated waffle fins 800 860 1,290 1,600 900 970 900 88 89 90 91 Scroll compressor -10 (OPZL) ~ 25 25 ~ 50 -15 ~ 43 -10 ~ 21 R-410A Electronic expansion valve 2 22 32 39 22 32 39 3" OD 3" 1/2"G 3~ / 50 / 400
0-50-100 26.5 36.2 30.0 38.1 2.91 2.76 2.92 2.99 4.00 3.81 2,311x2,000x2,566 1,400 1,450 1,415 1,465 221 251
287 327 36
47
46 780 880 86
1 33
37 -
150 145 165
203 2515_BOOK_AppliedSystems_2011.indb 203
25/03/2011 08:38
Air cooled chiller, standard efficiency, standard sound
EWAD-E-SS
EWAD140,160E-SS
Air cooled chiller, standard efficiency, standard sound
• • • • • •
Strengths • Wide capacity range (101kW - 413kW) • Single refrigerant circuit with single screw compressor • Compact design with brazed plate heat exchanger Standard available • Wye delta starter (y - d) • Double setpoint • Fans circuit breakers with thermal overload relays • Phase monitor • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Suction line shut off valve • Low pressure side manometers
• • • • • • • • • • • • • • • • •
Ambient outside temperature sensor and set-point reset Hour run meter General fault contactor Set-point reset, demand limit and alarm from external device Fans circuit breakers Main switch interlock
Options (factory mounted) • Total heat recovery • Partial heat recovery • Soft starter • Brine version • Compressor thermal overload relays • Under / Over voltage control • Energy meter • Capacitors for power factor correction
Current limit - display 20 mm evaporator insulation Speedtrol Condenser coil guards Cu-cu condenser coil Cu-cu sn condenser coil Alucoat fins coil Evaporator flow switch High pressure side manometers Container kit Rubber anti vibration mount Spring anti vibration mount Single pump (low or high lift) Twin pump (low or high lift) Not available on sizes 100 and 120 Double pressure relief valve with diverter Compressor circuit breakers Fan speed regulation
Cooling ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
100 101
120 121
Hz / V
160 163
180 183
210 214
260 256
310 307
360 360
410 413
68.5 71.7 2.67 2.98 2.81 3.02 2,273x1,292x3,965 2,086 2,116 Plate to plate 24 30 8.74 10.22
86.7 2.95 3.18
111 133 2.77 2.71 3.05 3.23 2,223x2,236x3,070 2,919 2,963
146 2.84 3.34
25 12.22
30 14.65
44 19.74
Stepless 25 38.7 2.61
46.9 2.57
2.93 2,273x1,292x2,165 1,684 1,699
53.4 60.3 2.58 2.70 2.75 2.93 2,273x1,292x3,065 1,861 1,881
12 4.83
15 5.76
17 6.58
24
25
10,922
10,575 91.5 73.5
°CDB °CDB kg
140 138
18
21
20 7.77 24
22
21
High efficiency fin and tube type with integral subcooler 16,383 15,863 21,844 21,150 32,767 920 92.3 93.0 94.2 73.7 73.9 75.1 75.0 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 23 28 30 33 46 1 3" 3~ / 50 / 400
36 17.21
48
45 31,725 94.5 75.3
95.2 76.0
56
60
204 2515_BOOK_AppliedSystems_2011.indb 204
25/03/2011 08:38
EWAD-E-SL
EWAD130,160E-SL
Air cooled chiller, standard efficiency, low sound
• • • • • •
Strengths • Wide capacity range (97.9kW - 398kW) • Single refrigerant circuit with single screw compressor • Low operating sound levels • Compact design with brazed plate heat exchanger Standard available • Wye delta starter (y - d) • Double setpoint • Fans circuit breakers with thermal overload relays • Phase monitor • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Suction line shut off valve • Low pressure side manometers
• • • • • • • • • • • • • • • •
Ambient outside temperature sensor and set-point reset Hour run meter General fault contactor Set-point reset, demand limit and alarm from external device Fans circuit breakers Main switch interlock
Options (factory mounted) • Total heat recovery • Partial heat recovery • Soft starter • Brine version • Compressor thermal overload relays • Under / Over voltage control • Energy meter • Capacitors for power factor correction • Current limit - display
20mm evaporator insulation Speedtrol Condenser coil guards Cu-cu condenser coil Cu-cu sn condenser coil Alucoat fins coil Evaporator flow switch High pressure side manometers Container kit Rubber anti vibration mount Spring anti vibration mount Single pump (low or high lift) Twin pump (low or high lift) Not available on sizes 100 and 120 Double pressure relief valve with diverter Compressor circuit breakers Fan speed regulation
Cooling ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
100 97.9
120 116
Hz / V
160 157
180 177
210 209
250 249
300 296
350 345
400 398
67.8 72.1 2.61 2.89 3.07 3.32 2,273x1,292x3,965 2,186 2,216 Plate to plate 24 30 8.47 9.97
84.5 2.95 3.55
110 134 2.69 2.58 3.41 3.34 2,223x2,236x3,070 3,029 3,073
150 2.65 3.45
25 11.90
30 14.15
36 16.50
44 19.01
46
45
44
42
Stepless 25 38.8 47.9 2.52 2.42 3.01 2.97 2,273x1,292x2,165 1,784 1,799
53.0 60.6 2.53 2.60 2.85 3.00 2,273x1,292x3,065 1,961 1,981
12 4.68
17 6.40
15 5.54 23
8,372
8,144 89.0 71.0
°CDB °CDB kg
130 134
18
21
20 7.51
21
20
High efficiency fin and tube type with integral subcooler 12,558 12,217 16,744 16,289 25,117 715 89.8 90.5 91.7 71.2 71.4 72.6 72.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 23 28 30 33 46 1 3" 3~ / 50 / 400
24,433 92.0 72.8
92.7 73.5
56
60
205 2515_BOOK_AppliedSystems_2011.indb 205
25/03/2011 08:38
EWAD-D-SS
EWAD390D-SS
Air cooled chiller, standard efficiency, standard sound
Strengths • Eurovent EER up to 2.93 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 389-578kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops • Four noise level versions standard / low / reduced & quiet. Standard available • Electronic expansion valve • Evaporator heater • Suction stop valve • Main switch
Options (factory mounted) • Glycol application • Single pump • Twin pump • High ESP pump • High ESP twin pump • Total heat recovery • Partial heat recovery • Fan silent • Low ambient • Power factor 0.9 • Gauges • Coil guards
Cooling ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
390 389
440 436
470 466
152 2.56 3.36 2,223x2,234x3,139 2,960 3,090
164 2.66 3.54
167 2.79 3.55
4,030 4,195
4,220
130 18.60
165 20.80
175 22.20
45.6
37.9 32,772
95.8 76.5
96.7
56
60
°CDB °CDB
kg Hz / V
66.5
510 502 Stepless 12.5 184 2.73
530 532
560 556
580 578
194 2.74
205 2.72 3.56
197 2.93 3.39
3.52 2,223x2,234x4,040 4,230 4,395 Single pass shell & tube 165 24.00 25.40 47.1
52.1
High efficiency fin and tube type with integral subcooler 43,694 43,455 43,694 920 96 96.7 98.2 77.0 78.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 70 76 82 139.7mm 3 / 50 / 400
4,235
26.50
160 27.60
57.4
51.2 42,300 98.7 79.0
87
92
206 2515_BOOK_AppliedSystems_2011.indb 206
25/03/2011 08:38
EWAD-D-SL
EWAD400-530D-SL
Air cooled chiller, standard efficiency, low sound
Strengths • Eurovent EER up to 2.78 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 184-533kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops • Four noise level versions standard / low / reduced & quiet. Standard available • Electronic expansion valve • Evaporator heater • Suction stop valve • Main switch
Options (factory mounted) • Glycol application • Single pump • Twin pump • High ESP pump • High ESP twin pump • Total heat recovery • Partial heat recovery • Fan silent • Low ambient • Power factor 0.9 • Gauges • Coil guards
Cooling ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
180 184
200 198
81.4 79.7 2.26 2.48 3.00 3.12 2,355x2,234x2,239 2,475 2,470 2,500 Plate to plate 25 30 8.80 9.40 28.9
21.8
15,300
230 225
250 245
10.70
11.70
100 12.50
13.10
300 320 370 298 321 370 Stepless 12.5 119 123 133 2.50 2.60 2.78 3.20 3.24 3.41 2,223x2,234x3,139 2,960 3,090 Single pass shell & tube 130 14.20 15.30 17.70
84.5 2.66 3.31
93.4 101 108 2.62 2.58 2.54 3.21 3.26 3.23 2,355x2,234x3,139 2,860 2,960
57.8
49.0
53.9
58.9
59.5
14,900
260 261
22,900 900
93.7
94.3 75.0
36
42
48
55.2
67.4
400 404
440 440
510 505
530 533
169 2.39 3.65
195 2.73 3.77
4,029 4,194
170 186 203 2.59 2.57 2.49 3.67 3.57 3.67 2,223x2,234x4,040 4,224 4,229 4,394
165 19.30
21.00
50
88.9
54 114.3
97.2 77.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 58 66
480 477
22.80
165 24.10
160 25.40
47.5
62.1
54.0
48.4
43.4
170
High efficiency fin and tube type with integral subcooler 22,600 22,300 24,428
°CDB °CDB
kg
280 275
33,489 715 94.2 74.5
94.7
70
76 139.7
82
4,234
32,572 95.7 76.0
96.2 76.5
84
86
3 / 50 / 400
Hz/V
207 2515_BOOK_AppliedSystems_2011.indb 207
25/03/2011 08:38
EWAD-D-SR
EWAD400-530D-SR
Air cooled chiller, standard efficiency, reduced sound
Strengths • Eurovent EER up to 2.73 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 177-533kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops • Four noise level versions standard / low / reduced & quiet. Standard available • Electronic expansion valve • Evaporator heater • Suction stop valve • Main switch
Options (factory mounted) • Glycol application • Single pump • Twin pump • High ESP pump • High ESP twin pump • Total heat recovery • Partial heat recovery • Fan silent • Low ambient • Power factor 0.9 • Gauges • Coil guards
COOLING ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
180 177
190 190
84.0 82.7 2.11 2.30 2.89 3.00 2,355x2,234x2,239 2,620 2,650 Plate to plate 25 30 8.50 9.10 26.9
20.1
15,300
220 219
240 238
250 252
85.2 2.57 3.34
94.7 103 111 2.51 2.44 2.38 3.21 3.23 3.16 2,355x2,234x3,139 2,890 3,100
10.40
11.30
100 12.00
55.1
46.6
50.8
14,900
22,900 680
88.7
89.3 70.0
36
42
48
280 310 370 278 312 366 Stepless 12.5 122 125 138 2.28 2.49 2.65 3.13 3.25 3.42 2,223x2,234x3,139 3,110 3,240 Single pass shell & tube 130 13.30 14.90 17.40
12.60 55.2
52.7
65.1
400 404
440 440
510 505
530 533
169 2.39 3.65
195 2.73 3.77
4,040 4,342
170 186 203 2.59 2.57 2.49 3.67 3.57 3.67 2,223x2,234x4,040 4,240 4,542
165 19.30
21.00
50
88.9
54
92.2 72.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 58 66 2
22.80
165 24.10
160 25.40
47.5
62.1
54.0
48.4
43.4
33,489 715 90.7 71.0
89.7
114.3
480 477
170
High efficiency fin and tube type with integral subcooler 22,600 22,300 24,428
°CDB °CDB kg
270 265
70
76
82
32,572 92.2 72.5
92.7 73.0
84
86
139.7 3 / 50 / 400
Hz / V
208 2515_BOOK_AppliedSystems_2011.indb 208
25/03/2011 08:38
EWAD-D-SX
EWAD230-410D-SX
Air cooled chiller, standard efficiency, extra low sound
Strengths • Eurovent EER up to 2.71 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 203-492kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops • Four noise level versions standard / low / reduced & quiet. Standard available • Electronic expansion valve • Evaporator heater • Suction stop valve • Main switch
Options (factory mounted) • Glycol application • Single pump • Twin pump • High ESP pump • High ESP twin pump • Total heat recovery • Partial heat recovery • Fan silent • Low ambient • Power factor 0.9 • Gauges • Coil guards
Cooling ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
210 203
230 231
250 253
270 271
79.9 2.54 3.39 2,420x2,234x3,139 3,110 3,200
85.2 2.71 3.63
93.5 2.70 3.52
104 2.59 3.55
3,475
3,425
310 309
370 370
410 413
450 451
11.00
44.7
33.8
490 492
136 2.27 3.25
148 2.49 3.24
169 2.44 3.49
3,560 3,735
4,302 4,472
173 187 2.60 2.63 3.61 3.58 2,420x2,234x4,940 4,506 4,581 4,676 4,746
12.10
165 12.90
Single pass shell & tube 160 13.70 14.30 14.70
175 17.70
19.70
21.50
165 23.50
38
38.3
34.9
44.5
43.9
50
44.8
25,933
28,625
33,116
85.7 65.5
86.2 66.0
76
82
115
37.7
40.5
High efficiency fin and tube type with integral subcooler 17,200 26,495 500 84.7 65.0 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 60 65 114.3 3 / 50 / 400
17,900
84.3
°CDB °CDB
kg
300 299 Stepless 12.5 114 126 2.50 2.37 3.44 3.39 2,420x2,234x4,040 3,430 3,590
90 9.70
12,900
290 286
56
Hz / V
170
70 139.7
209 2515_BOOK_AppliedSystems_2011.indb 209
25/03/2011 08:38
EWAD-D-XS
EWAD250D-XS
Air cooled chiller, high efficiency, standard sound
Strengths • High efficiency levels • Eurovent EER up to 3.2 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 247–622kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops
Options (factory mounted) • Glycol application • Total heat recovery • Partial heat recovery • Fan silent • Power factor 0.9 • Gauges • Coil guards
Standard available • Evaporator heater • Suction stop valve • Electronic expansion valve • Main switch
Cooling ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
250 247
280 275
300 302
330 327
79.1 3.12 3.56 2,355x2,234x3,138 2,905 3,000
87.1 3.16 3.60
94.1 3.20 3.62
380 376 Stepless 12.5 120 3.14 3.58
400 401
95 11.80
13.10
14.40
104 113 127 3.15 3.12 3.16 3.85 3.67 3.59 2,355x2,234x4,040 3,235 3,240 3,400 Single pass shell & tube 165 160 15.60 16.70 17.90 19.10
48.1
44.9
48.8
46.1
22,300
3,285
115
50.8
57.6
63.5
470 469
520 524
150 3.12 3.84 2,223x2,234x4,040 3,510 3,780
166 3.15 4.00
30,600
96.8
66
620 622
181 194 3.18 3.20 4.01 3.88 2,223x2,234x4,940 4,670 4,685 4,940
270
255 25.00
27.40
29.70
47.4
62.9
56.2
37.9
77.5
58
580 575
22.40
High efficiency fin and tube type with integral subcooler 29,700 44,000 43,000 43,695 900 97.2 98.7
54,616 920 99.2 79.0
°CDB °CDB
kg
350 351
76 114.3
Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 73 76
86
100 168.3
3 / 50 / 400
Hz / V
210 2515_BOOK_AppliedSystems_2011.indb 210
25/03/2011 08:38
EWAD-D-XR
EWAD270-390D-XR
Air cooled chiller, high efficiency, reduced sound
Strengths • High efficiency levels • Reduced sound levels • Eurovent EER up to 3.12 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 243–600kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops
Options (factory mounted) • Glycol application • Total heat recovery • Partial heat recovery • Fan silent • Power factor 0.9 • Gauges • Coil guards
Standard available • Evaporator heater • Suction stop valve • Electronic expansion valve • Main switch
Cooling ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
240 243
270 272
300 296
80.6 3.01 3.63 2,355x2,234x3,138 3,005 3,100
87.0 3.12 3.70
95.1 3.11 3.69
320 322
370 370 Stepless 12.5 119 3.12 4.01
390 394
95 11.60
13.00
14.10
106 115 127 3.05 2.99 3.10 3.82 3.71 3.82 2,355x2,234x4,040 3,335 3,340 3,500 Single pass shell & tube 165 160 15.40 16.40 17.70 18.80
46.7
44.0
47.5
44.7
3,385
115
49.2
56.2
55.6
91.8 72.5
60
460 455
510 512
152 2.99 3.89 2,223x2,234x4,040 3,610 3,880
167
560 561
600 600
183 198 3.07 3.03 4.11 3.93 2,223x2,234x4,940 4,770 4,785 5,040
270
255
21.70
24.40
26.80
28.60
44.8
60.4
53.7
36.1
High efficiency fin and tube type with integral subcooler 12,500 33,488 680 92.2 93.2
41,861
41,864 715 93.7
73.5 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 80
°CDB °CDB
kg
350 345
68 114.3
104 168.3
3 / 50 / 400
Hz/V
211 2515_BOOK_AppliedSystems_2011.indb 211
25/03/2011 08:38
EWAD-D-HS
EWAD340-450D-HS
Air cooled chiller, high ambient
Strengths • High ambient mode HS • Eurovent EER up to 3.07 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 195–587kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops
Options (factory mounted) • Glycol application • Total heat recovery • Partial heat recovery • Fan silent • Power factor 0.9 • Gauges • Coil guards
Standard available • Evaporator heater • Suction stop valve • Electronic expansion valve • Main switch
Cooling ONLY Capacity Class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Fan motor Speed Cooling Nom. Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW
mm kg kg l l/s kPa
l/s rpm dBA dBA
200 195
210 208
230 234
77.2 75.5 2.52 2.76 3.11 3.26 2,223x2,234x2,239 2,475 2,470 2,500 Plate to plate 25 30 9.30 9.90
83.0
11.10
12.20
13.10
90 13.80
31.5
46.1
52.1
53.7
59.3
23.7
23,900
22,800
260 256
290 289
310 306
97.7 104 2.80 2.78 3.34 3.21 3.30 3.28 2,223x2,234x3,339 2,865 2,870 2,960
112 2.73 3.27
91.0
2.81
95
35,900
95.7
°CDB °CDB
kg
36
42 88.9
Hz / V
270 274
44
340 336 Stepless 12.5 120 2.80 3.25
380 381
420 415
14.60
127 141 150 162 175 182 191 3.00 2.94 2.98 2.95 2.94 3.00 3.07 3.57 3.61 3.68 3.66 3.71 3.79 2,223x2,234x4,040 2,223x2,234x4,940 3,185 3,277 3,942 4,356 4,361 4,366 3,300 3,447 4,112 4,526 Single pass shell & tube 115 170 165 160 16.00 18.20 19.80 21.40 22.80 24.50 26.10 28.00
64.4
58.3
69.9
45.8
450 448
52.5
High efficiency fin and tube type with integral subcooler 35,000 34,100 47,900 43,694 42,300 900 96.3 96.7 98.7 96.7 77.0 79.0 77.0 Semi-hermetic single screw compressor -15~15 -18~48 R-134a 2 55 56 58 66 70 90 114.3 3 / 50 / 400
480 478
510 514
58.0
50.9
550 547
55.7
590 587
52.6
54,616 920 97.7 77.5
99.2 79.0
95
100
99.7 79.5
139.7
212 2515_BOOK_AppliedSystems_2011.indb 212
25/03/2011 08:38
EWAD-BZSS/SL
EWAD330,360BZS(S,L)
Air cooled inverter chiller, standard efficiency, standard/low sound
Strengths • ESEER up to 4.70 • All models are PED pressure vessel approved • Inverter stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 329~515kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Quick start-up • Standard electronic expansion valve • Power factor > 0.95 Standard available • Double setpoint • Fans thermal relays • Phase monitor • Inverter compressor starter • Evaporator victaulic kit • Fan silent mode • Fan speed regulation • Evaporator electric heater
• • • • • • •
Electronic expansion valve Discharge line shut off valve Suction line shut off valve Low pressure side manometers Hour run meter General fault contactor Main switch interlock
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP pump • High ESP twin pump • Double pressure relief valve with diverter • Refrigerant high pressure side gauge • Coil guards • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
Cooling ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (SS)
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Weight (SL) Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level (SS) Cooling Nom. Sound power level (SL) Cooling Nom. Sound pressure level (SS) Cooling Nom. Sound pressure level (SL) Cooling Nom. Compressor Type Operation range Water side Cooling Min.~Max. Air side Cooling Min.~Max. Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
INVERTER kW % kW
mm kg kg kg kg l l/s kPa
l/s rpm dBA dBA dBA dBA
330 329
360 358
400 395
120.0 136 2.74 2.63 4.59 4.60 2,355x2,234x4,381 4,190 4,440 4,340 4,590 271 15.72
17.10
264
60
61
72
67
460 459
490 488
520 515
168 2.73 4.57
181 2.70 4.70 2,355x2,234x6,181 4,990 5,240 5,140 5,390
193 2.67 4.60
21.93
23.32
24.61
78
69
76
248
High efficiency fin and tube type with integral subcooler 40,833 700 103.2 97.3
32,667 102.8 96.9 83.0 77.0
Semi-hermetic single screw compressor -9.5~15 -10~45 R-134a 99 105 114 2 168.3mm 3~ / 50 / 400
°CDB °CDB kg
420 423 Stepless 13.5 147 159 2.69 2.66 4.55 4.59 2,355x2,234x5,281 4,590 4,840 4,740 4,990 Single pass shell & tube 256 18.87 20.21
73
Hz / V
49,000 103.6 98.2 83.5 77.5
118
121
213 2515_BOOK_AppliedSystems_2011.indb 213
25/03/2011 08:38
EWAD-BZXS/XL/XR
EWAD330,360BZX(S,L,R)
Air cooled inverter chiller, high efficiency, standard/low/reduced sound
Strengths • ESEER up to 5.01 • All models are PED pressure vessel approved • Inverter stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 329~515kW • 2 truly independent refrigerant circuits • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Quick start-up • Standard electronic expansion valve • Power factor > 0.95
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP pump • High ESP twin pump • Double pressure relief valve with diverter • Refrigerant high pressure side gauge • Coil guards • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
Standard available • Double setpoint • Fans thermal relays • Phase monitor • Inverter compressor starter • Evaporator victaulic kit • Fan silent mode • Fan speed regulation • Evaporator electric heater • Electronic expansion valve • Discharge line shut off valve • Suction line shut off valve • Low pressure side manometers • Hour run meter • General fault contactor • Main switch interlock
Cooling ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions Weight (XS) Weight (XL) Weight (XR) Water heat exchanger
Air heat exchanger Fan Sound power level (XS) Sound pressure level (XS) Sound power level (XL) Sound pressure level (XL) Sound power level (XR) Sound pressure level (XR) Compressor Operation range Refrigerant
Piping connections Power supply
INVERTER
Nom. Method Minimum capacity Cooling Nom.
kW
Unit HeightxWidthxDepth Unit Operation weight Unit Operation weight Unit Operation weight Type Water volume Nominal water flow Cooling Nominal water Cooling Heat pressure drop exchanger Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Cooling Nom. Type Water side Cooling Min.~Max. Air side Cooling Min.~Max. Type Charge Circuits Quantity Evaporator water inlet/outlet Phase / Frequency / Voltage
mm kg kg kg kg kg kg
% kW
l l/s kPa
l/s rpm dBA dBA dBA dBA dBA dBA
330 329
360 358
400 395
118.0 135 2.79 2.65 4.79 4.82 2,355x2,234x4,381 4,190 4,440 4,340 4,590 4,390 4,640 271 15.72
17.10
264
60
61
72
67
460 459
490 488
520 515
165 2.78 4.81
178 2.74 5.01 2,355x2,234x6,181 4,990 5,240 5,140 5,390 5,190 5,440
190 2.71 4.84
21.93
23.32
24.61
78
69
76
248
High efficiency fin and tube type with integral subcooler 40,833 700 103.2
32,667 102.8 83.0 96.9
97.3 77.0
92.9
93.3 73.0 Semi-hermetic single screw compressor -9.5~15 -10~45 R-134a 99 105 114 2 168.3 3~ / 50 / 400
°CDB °CDB kg
420 423 Stepless 13 145 157 2.72 2.69 4.78 4.84 2,355x2,234x5,281 4,590 4,840 4,740 4,990 4,790 5,040 Single pass shell & tube 256 18.87 20.21
73
Hz / V
49,000 103.6 83.5 98.2 77.5 94.2 73.5
118
121
214 2515_BOOK_AppliedSystems_2011.indb 214
25/03/2011 08:38
EWYD-BZSS
EWYD260BZSS
Air cooled heat pump inverter chiller, standard efficiency, standard sound
Strengths • Optimised for use with R-134a • Cooling range: 254 - 583kW • Heating range: 270 - 615kW • EER range up to 2.87 • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Seasonal quietness • Low starting current • No gas boiler required • Optimised defrost cycles • Optimum ESEER values • PID microprocessor control • Power factor up to 0.95 • 2-3 truly independent refrigerant circuits • Standard operation range down to -12°C
Standard available • Double setpoint • Fans thermal relays • Phase monitor • Inverter compressor starter • Evaporator electric heater • Discharge line shut off valve • Suction line shut off valve • Low pressure side manometers • Hour run meter • General fault contactor Options • Partial heat recovery • Fan silent mode • Double pressure relief valve with diverter • Condenser coil guards • Spring Anti Vibration Mounts
HEATING & COOLING Capacity class Cooling capacity Heating capacity Capacity control Power input
Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.
EER COP ESEER Dimensions Weight
INVERTER kW kW % kW kW
Unit HeightxWidthxDepth mm Unit kg Operation weight kg Water heat exchanger Type Water volume l Nominal water flow Cooling l/s Heating l/s Nominal water Cooling Heat kPa pressure drop exchanger Heating Heat kPa exchanger Air heat exchanger Type Fan Air flow rate Nom. l/s Speed rpm Sound power level Cooling Nom. dBA Heating Nom. dBA Sound pressure level Cooling Nom. dBA Heating Nom. dBA Compressor Type Operation range Water side Cooling Min.~Max. °CDB Air side Cooling Min.~Max. °CDB Refrigerant Type Charge kg Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage Hz / V
250 254 270
270 273 297
290 292 324
320 324 333
90.3 100 109 90.4 99 107 2.81 2.74 2.69 2.98 2.99 3.03 4.05 4.04 4.01 2,335x2,254x3,547 3,410 3,455 3,500 3,550 3,595 3,640
340 339 349
370 365 379
380 382 410 Stepless
410 413 443
13 124 134 142 152 163 124 132 141 155 165 2.74 2.73 2.68 2.72 2.68 2.80 2.87 2.90 2.85 2.81 4.01 4.02 3.94 4.03 4.01 2,335x2,254x4,381 2,335x2,254x5,281 3,870 3,940 4,010 4,390 4,010 4,068 4,138 4,518 Single pass shell & tube 133 128 15.46 16.21 17.42 18.25 19.72 20.81 15.89 16.66 18.11 19.57 21.15 22.14 116 117 2.79 2.84 4.07
12.12 12.89
138 13.03 14.18
13.94 15.49
37
42
48
53
58
53
57
46
42
49
58
55
60
57
65
52
100.5 100.5 82.1 82.1
94
100
460 457 475
510 505 530
161 164 2.83 2.90 4.31
178 176 2.83 3.02
520 522 558
580 583 615
186 184 2.81 3.04
215 205 2.71 3.00 4.05
9
5,015 5,255
4.13 2,335x2,254x6,583 5,495 5,735 5,724 5,964 5,953
240 21.83 22.68
24.11 25.33
24.92 26.65
218 27.87 29.39
51
61
50
53
65
57
66
55
60
71
High efficiency fin and tube type with integral subcooler 42,304 52,880 920 101.2 101.8 101.2 101.8 82.3 82.5 82.3 82.5 Semi-hermetic single screw compressor -8~15 -10~45 R-134a 118 121.0 124 148 2 139.7 3~ / 50 / 400
31,728
88
440 436 463
229
63,456 103.6 103.6 83.7 83.7
177
183
186
3 219.1mm
215 2515_BOOK_AppliedSystems_2011.indb 215
25/03/2011 08:38
EWYD-BZSL
EWYD260BZSL
Air cooled heat pump inverter chiller, standard efficiency, low sound
Strengths • Optimised for use with R-134a • Cooling range: 248 - 567kW • Heating range: 270 - 615kW • EER range up to 2.87 • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Seasonal quietness • Low starting current • No gas boiler required • Optimised defrost cycles • Optimum ESEER values • PID microprocessor control • Power factor up to 0.95 • 2-3 truly independent refrigerant circuits • Standard operation range down to -12°C • Low operating sound levels
Standard available • Double setpoint • Fans thermal relays • Phase monitor • Inverter compressor starter • Fans speed control device • Evaporator electric heater • Discharge line shut off valve • Suction line shut off valve • Low pressure side manometers • Hour run meter • General fault contactor Options • Partial heat recovery • Double pressure relief valve with diverter • Condenser coil guards • Spring Anti Vibration Mounts
HEATING & COOLING Capacity class Cooling capacity Heating capacity Capacity control Power input
Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.
EER COP ESEER Dimensions Weight
INVERTER kW kW % kW kW
Unit HeightxWidthxDepth mm Unit kg Operation weight kg Water heat exchanger Type Water volume l Nominal water flow Cooling l/s Heating l/s Nominal water Cooling Heat kPa pressure drop exchanger Heating Heat kPa exchanger Air heat exchanger Type Fan Air flow rate Cooling Nom. l/s Heating Nom. l/s Fan motor Speed Cooling Nom. rpm Heating Nom. rpm Sound power level Cooling Nom. dBA Heating Nom. dBA Sound pressure level Cooling Nom. dBA Heating Nom. dBA Compressor Type Operation range Water side Cooling Min.~Max. °CDB Air side Cooling Min.~Max. °CDB Refrigerant Type Charge kg Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage Hz / V
250 248 270
270 266 297
290 291 324
88.5 98 109 90.4 99 107 2.80 2.70 2.66 2.98 2.99 3.03 4.18 4.16 4.11 2,335x2,254x3,547 3,750 3,795 3,840 3,888 3,933 3,978
320 316 333
370 372 410 Stepless
400 403 443
430 425 463
13 122 132 142 149 161 124 132 141 155 165 2.72 2.68 2.62 2.71 2.64 2.80 2.87 2.90 2.85 2.81 4.18 4.16 4.13 4.19 4.14 2,335x2,254x4,381 2,335x2,254x5,281 4,210 4,280 4,350 4,730 4,343 4,408 4,478 4,858 Single pass shell & tube 133 128 15.12 15.83 16.98 17.77 19.28 20.30 15.89 16.66 18.11 19.57 21.15 22.14
138 12.70 14.18
13.89 15.49
36
40
48
51
42
49
58
55
94.0 94.9 75.6 76.5
100
450 448 475
156 164 2.87 2.90 4.31 5,525 5,765
490 493 530
510 510 558
570 567 615
9 174 183 214 176 184 205 2.83 2.79 2.65 3.02 3.04 3.00 4.29 4.23 4.10 2,335x2,254x6,583 6,005 6,245 6,234 6,474 6,463
240 21.39 22.68
23.56 25.33
229 24.34 26.65
218 27.11 29.39
55
50
55
44
48
59
48
51
62
60
57
65
52
57
66
55
60
71
High efficiency fin and tube type with integral subcooler 32,576 40,720 42,304 52,880 715 920 94.7 95.3 96.1 96.7 75.8 76.0 77.2 77.4 Semi-hermetic single screw compressor -8~15 -10~45 R-134a 118 121 124 148 2 139.7 3 ~/ 50 / 400
24,432 31,728
94
360 355 379
113 117 2.79 2.84 4.29
11.83 12.89
88
330 331 349
48,864 63,456
97.0 98.4 77.2 78.6
177
183
186
3 219.1mm
216 2515_BOOK_AppliedSystems_2011.indb 216
25/03/2011 08:38
EWAD-C-SS/SL
EWAD-C-
Air cooled chiller, standard efficiency, standard/low sound
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • 11 sizes to cover a range from 647 up to 1,922kW • EER range up to 2.99 • 2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Partial and heat recovery option available • New MicroTech III controller
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP fans • Fan silent • Low ambient • Power factor 0.9 • Dual pressure relief valve • Suction line shut off valve • A/V meter • Condenser coil guards • Soft starter • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
Standard available • Wye Delta Starter (Y - D) • Double setpoint • Fans thermal relays • Phase monitor • Evaporator victaulic kit • 20mm Evaporator insulation • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock • Emergency stop
COOLING ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions
Nom. Method Minimum capacity Cooling Nom.
Unit
650 647
740 744
830 832
910 912
970 967
221 2.93 3.95
262 2.84 3.87
299 2.78 3.89
318 2.87 3.84
12.5 351 2.76 3.8
kg kg kg kg
5,630 5,910 5,920 6,200
5,740 5,990 6,030 6,280
5,760 6,010 6,050 6,300
6,280 6,530 6,570 6,820
6,560 6,810 6,850 7,100
l l/s kPa
30.9
266 35.56
39.74
251 43.6
46.21
52
61
68
kW % kW
HeightxWidthxDepth mm
Weight (SS)
Unit Operation weight Weight (SL) Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. (SS) Sound pressure level (SS) Cooling Nom. Sound power level Cooling Nom. (SL) Sound pressure level (SL) Cooling Nom. Compressor Type Operation range Water side Cooling Air side Cooling Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
Heat exchanger
l/s rpm dBA
Min.~Max. Min.~Max.
2,540x2,285x6,185
73
59 53,444
64,133 101.1
C11 1,064
63
100.0
100.9
79.0
79.5
80.4
96.0
96.1
97.5
97.1
97.6
dBA
75.5
75.6
76.5
76.6
76.8
146
144 2
128
C14 1,419
C15 1,538
C16 1,622
72
54
58
47
59
C17 1,714
65
73
High efficiency fin and tube type with integral subcooler 74,822 85,510 96,199 106,888 920
99.5
101.5
101.7
80.6
°CDB °CDB
C13 H14 1,319 1,418 Stepless
C18 1,802
7 378 402 441 474 500 551 580 618 665 2.82 2.86 2.99 2.84 2.79 2.8 2.77 2.71 3.88 3.84 4.08 4.07 3.88 3.9 3.87 3.78 3.79 2,540x2,285 2,540x2,285 2,540x2,285x8,885 2,540x2,285x10,185 2,540x2,285x11,085 x7,085 x7,985 7,010 7,280 7,900 10,310 10,320 10,710 10,770 11,240 7,250 7,520 8,280 10,730 11,110 11,260 12,110 7,300 7,570 8,190 10,750 10,770 11,150 11,210 11,680 7,540 7,810 8,570 11,170 11,550 11,700 12,560 Single pass shell & tube 243 386 421 408 474 50.85 55.04 62.9 67.7 67.78 73.5 77.51 81.89 86.00
dBA dBA
kg
C12 1,152
98.1
101.9
102.9
80.7
81.0
98.2
103.0
117,577 103.2
99.1
C20 1,922
682 2.75 3.81
714 2.69 3.77
2,540x2,285x11,985 11,600 12,480 12,040 12,920 850 89.50
91.70
39
40
128,266
103.3
103.5
103.7
81.2
81.5
81.9
99.9
101
77.9
78
275
305
81.1
76.9 77 77.2 Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 46 R-134a 162 178 196 260
36
C19 1,875
99.5 77.3
77.4
261 3
168.3mm
219.1mm
273mm
3 / 50 / 400
Hz / V
217 2515_BOOK_AppliedSystems_2011.indb 217
25/03/2011 08:38
EWAD-C-SR
EWAD-C-
Air cooled chiller, standard efficiency, reduced sound
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • 11 sizes to cover a range from 647 up to 1,714 kW • EER range up to 2.93 • 2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Partial and heat recovery option available • New MicroTech III controller
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP fans • Fan silent • Low ambient • Power factor 0.9 • Dual pressure relief valve • Suction line shut off valve • A/V meter • Condenser coil guards • Soft starter • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
Standard available • Wye Delta Starter (Y - D) • Double setpoint • Fans thermal relays • Phase monitor • Evaporator victaulic kit • 20 mm Evaporator insulation • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock • Emergency stop
COOLING ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions
Nom. Method Minimum capacity Cooling Nom.
Unit
kW % kW
620 619
720 715
790 789
880 876
920 922
C10 1,020
C11 1,112
C12 H14 1,270 1,321 Stepless
C13 1,367
C14 1,471
C15 1,556
C14 1,623
C17 1,714
C18 1,795
C19 1,833
223 2.77 4.08
272 2.62 3.96
315 2.51 3.98
331 2.65 3.99
12.5 369 2.5 4
395 2.59
417 2.67
457 2.78 4.12
517 2.64 3.9
576 2.55 3.87
603 2.58 3.9
7 647 2.51 3.83
702 2.44 3.79
718 2.50 3.82
757 2.42 3.77
HeightxWidthxDepth mm
Weight
Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Air side Cooling Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
Heat exchanger
kg kg
5,920 6,200
6,030 6,280
6,050 6,300
6,750 6,820
l l/s kPa
266 29.57 34.15
37.71
251 41.83
47
57
l/s rpm dBA dBA Min.~Max. Min.~Max.
2,540x2,285x6,185
67
55 41,006
91.5 71.0
92.0 71.5
3.96 2,540x2,285 2,540x2,285 2,540x2,285x8,885 2,540x2,285x10,185 2,540x2,285x11,085 x7,085 x7,985 6,850 7,300 7,570 8,190 10,750 10,770 11,150 11,210 11,680 7,100 7,540 7,810 8,570 11,170 11,550 11,700 12,560 Single pass shell & tube 243 386 421 408 474 44.05 48.75 53.11 60.67 63.11 65.32 70.28 74.32 77.57 81.80 62
49,207 92.5 72
93.0 72.5
°CDB °CDB kg
128
495 2.67 4.00
144 2 168.3mm
Hz / V
58
68
50
54
44
54
60
66
High efficiency fin and tube type with integral subcooler 57,408 65,610 73,811 82,012 90,213 715 93.5 93.8 94 94.8 94.9 95.1 95.2 72.6 72.7 72.9 73.0 73.1 Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 46 R-134a 162 178 196 260 261 3 219.1mm 3 / 50 / 400
33 90,216 95.5 73.4
275
2,540x2,285x11,985 12,040 12,920 850 85.60
87.50
36
37
98,417 95.9 73.7
74
305 273mm
218 2515_BOOK_AppliedSystems_2011.indb 218
25/03/2011 08:38
EWAD-C-XS/XL
EWAD-C-
Air cooled chiller, high efficiency, standard/low sound
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • 11 sizes to cover a range from 760 up to 2,008kW • EER range up to 3.29 • 2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Partial and heat recovery option available • New MicroTech III controller
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP fans • Fan silent • Low ambient • Power factor 0.9 • Dual pressure relief valve • Suction line shut off valve • A/V meter • Condenser coil guards • Soft starter • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
Standard available • Wye Delta Starter (Y - D) • Double setpoint • Fans thermal relays • Phase monitor • Evaporator victaulic kit • 20 mm Evaporator insulation • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock • Emergency stop
COOLING ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions
Nom. Method Minimum capacity Cooling Nom.
Unit
kW % kW
HeightxWidthxDepth mm
Weight (XS)
Unit Operation weight Weight (XL) Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Fan motor Speed Cooling Sound power level (XL) Cooling Nom. Sound pressure Cooling Nom. level (XL) Sound power level (XL) Cooling Nom. Sound pressure Cooling Nom. level (XL) Compressor Type Operation range Water side Cooling Air side Cooling Refrigerant Type Charge Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kg kg kg kg
Heat exchanger
Nom.
Min.~Max. Min.~Max.
l l/s kPa
760 756
830 830
890 889
233 3.25 4.02 2,540x2,285 x6,185 5,990 6,240 6,280 6,520
253 278 3.28 3.2 4.11 4.02 2,540x2,285 x7,085 6,340 6,360 6,580 6,600 6,630 6,650 6,870 6,890
251 36.1
243 39.67 42.49
80
56
64
990 C10 C11 C12 C13 H14 H15 C14 C15 C16 1,001 1,074 1,196 1,280 1,349 1,415 1,525 1,409 1,526 1,596 Stepless 12.5 307 338 364 400 411 444 475 437 474 504 3.26 3.18 3.29 3.2 3.29 3.19 3.21 3.23 3.22 3.17 4.11 4.05 4.14 4.02 4.28 4.31 4.35 4.23 4.19 4.17 2,540x2,285 2,540x2,285x9,785 2,540x2,285x11,985 x7,985 7,190 7,470 8,220 8,240 8,900 10,560 11,310 11,570 7,600 7,870 8,610 8,630 9,890 11,040 12,170 12,430 7,480 7,760 8,510 8,530 9,190 11,000 11,760 12,010 7,880 8,160 8,900 8,920 10,180 11,490 12,610 12,870 Single pass shell & tube 403 386 979 491 850 47.82 51.32 57.13 61.18 64.45 67.50 72.86 67.34 72.9 76.24 61
69
45
51
71
77
64,133
80.2
80.7
80.3
80.4
dBA dBA
96.8
97.4
98
98.2
98.8
98.9
76.3
76.5
76.9
77.1
76.7
76.8
100.2
100.5 79.7
°CDB °CDB kg
146
162
77
57
533 3.16 4.16 2,540x2,285 x12,885 11,900 12,760 12,350 13,200
871 850 80.48 84.47 88.79 90.77 93.2
62
68
182
214
80.5
80.7
80.9
168.3
64
37
77.1
77.2
100 77.3
312
219.1 3~ / 50 / 400
248 273 3 / 50 / 400
43
100.4
77
328 3
77.5
343
219.1
95.8
41
81 100.2
77.4
Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 50 R-134a 225 291 297
39
160,332 920 103.9
80.8
99.6
2 kg mm Hz / V
7 561 590 615 642 672 3.15 3.09 3.04 2.99 4.13 4.12 4.03 4.01 2,540x2,285 2,540x2,285x14,685 x13,785 12,260 12,600 13,140 13,470 12,700 13,040 13,580 13,910
High efficiency fin and tube type with integral subcooler 85,510 106,888 128,266 138,954 149,643 920 920 920 101.4 101.9 102.4 102.5 102.9 103.1 103.2 103.5 103.7
l/s rpm rpm dBA dBA
74,822
84
C17 C18 C19 C20 C21 C22 1,685 1,768 1,858 1,901 1,953 2,008
343
273 3~ / 50 / 400
3 / 50 / 400
219 2515_BOOK_AppliedSystems_2011.indb 219
25/03/2011 08:38
EWAD-C-XR
EWAD-C-
Air cooled chiller, high efficiency, reduced sound
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • 11 sizes to cover a range from 736 up to 1959kW • EER range up to 3.2 • 2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Partial and heat recovery option available • New MicroTech III controller
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP fans • Fan silent • Low ambient • Power factor 0.9 • Dual pressure relief valve • Suction line shut off valve • A/V meter • Condenser coil guards • Soft starter • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
Standard available • Wye Delta Starter (Y - D) • Double setpoint • Fans thermal relays • Phase monitor • Evaporator victaulic kit • 20mm Evaporator insulation • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock • Emergency stop
COOLING ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions
Nom. Method Minimum capacity Cooling Nom.
Unit
kW % kW
HeightxWidthxDepth mm
Weight
Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Air side Cooling Refrigerant Type Charge Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kg kg
Heat exchanger
l l/s kPa
l/s rpm dBA dBA Min.~Max. Min.~Max.
740 736
C10 C11 C12 C13 H14 H15 C14 C15 C16 C17 1,041 1,168 1,247 1,302 1,367 1,468 1,378 1,486 1,550 1,639 Stepless 12.5 235 254 281 309 343 365 404 415 454 491 438 479 513 541 3.14 3.2 3.08 3.15 3.03 3.2 3.08 3.14 3.01 2.99 3.15 3.1 3.03 4.29 4.36 4.23 4.34 4.24 4.38 4.25 4.33 4.38 4.43 4.34 4.26 4.2 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285 2,540x2,285x9,785 2,540x2,285x11,985 x6,185 x7,085 x7,985 x12,885 6,280 6,630 6,650 7,480 7,760 8,510 8,530 9,190 11,000 11,760 12,010 12,350 6,520 6,870 6,890 7,880 8,160 8,900 8,920 10,180 11,490 12,610 12,870 13,200 Single pass shell & tube 251 243 403 386 979 491 850 35.17 38.74 41.36 46.54 49.76 55.78 59.56 62.21 65.20 70.00 65.85 70.98 74.07 78.32 76 49,207
810 811
870 866
54
61
57,408
92
92.3 71.5
146
162
°CDB °CDB kg kg mm Hz / V
168.3
970 974
58
65
43
49
67
73
79
74
54
59
65
C18 C19 C20 C21 C22 1,722 1,813 1,854 1,902 1,959 7 567 595 624 658 692 3.04 2.97 2.89 2.83 4.21 4.2 4.1 4.08 2,540x2,285 2,540x2,285x14,685 x13,785 12,700 13,040 13,580 13,910 871 82.3
86.61
61
35
High efficiency fin and tube type with integral subcooler 65,610 82,012 82,014 98,414 106,616 114,817 123,018 715 93.5 93.7 94.3 94.5 94.4 94.6 95.1 95.2 95.3 95.6 95.7 95.9 72.3 72.5 72.2 72.3 72.5 72.6 72.8 72.9 73 Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 50 R-134a 182 214 225 291 297 312 328 343 2 3 248 219.1 273 219.1 273 3 / 50 / 400
850 88.5 90.7 37
93.5
39
41
123,021 96.2 73.3
96.6 73.7
343
220 2515_BOOK_AppliedSystems_2011.indb 220
25/03/2011 08:38
EWAD-C-PS/PL
EWAD-C-
Air cooled chiller, premium efficiency, standard/low sound
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • 11 sizes to cover a range from 821 up to 1,562kW • EER range up to 3.64 • 2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Partial and heat recovery option available • New MicroTech III controller
Standard available • Wye Delta Starter (Y - D) • Double setpoint • Fans thermal relays • Phase monitor • Evaporator victaulic kit • 20mm Evaporator insulation • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock • Emergency stop
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP fans • Fan silent • Low ambient • Power factor 0.9 • Dual pressure relief valve • Suction line shut off valve • A/V meter • Condenser coil guards • Soft starter • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
COOLING ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions
Nom. Method Minimum capacity Cooling Nom.
Unit
kW % kW
820 821
225 3.64 4.44
HeightxWidthxDepth mm
Weight (PS)
Unit Operation weight Weight (PL) Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level (PS) Cooling Nom. Sound pressure level (PS) Cooling Nom. Sound power level (PL) Cooling Nom. Sound pressure level (PL) Cooling Nom. Compressor Type Operation range Water side Cooling Air side Cooling Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
Heat exchanger
249 3.58 4.5
7,530 8,130 7,820 8,420
274 3.56 4.41
7,660 8,700 7,950 8,990
39.22
599 42.53
1,043 46.6
57
65
30
96,199
l/s rpm dBA dBA dBA dBA Min.~Max. Min.~Max.
980 975
2,540x2,285x8,885
kg kg kg kg l l/s kPa
890 890
101 79.5 98.4 76.9
°CDB °CDB kg mm Hz / V
204
202
204
219.1
C11 1,074
C12 1,158
301
Stepless 12.5 330 3.51 4.39
C13 1,279
363 3.52 4.53 4.44 2,540x2,285 2,540x2,285x9,785 x11,085 8,290 8,550 9,390 9,330 9,590 10,380 8,580 8,840 10,380 9,620 9,880 10,670 Single pass shell & tube 1,027 995 51.3 55.31 61.12 61
69
60
C14 1,390
C15 1,474
C16 1,562
396 3.51 4.31
424 3.48 4.33
453 3.45 4.32
2,540x2,285x11,985 9,730 10,720 10,720 11,010
66.41
979 70.30
74.50
73
81
89
High efficiency fin and tube type with integral subcooler 106,888 117,577 128,266 920 101.8 102.3 102.6 102.9 80 80.5 80.4 80.5 98.8 99.9 99.3 99.6 77 77.1 77.2 Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 52 R-134a 220 252 2 273 3 / 50 / 400
128,266 103.2 80.8 99.9 77.5
103.5 81.1 100.2 77.8
254
221 2515_BOOK_AppliedSystems_2011.indb 221
25/03/2011 08:38
EWAD-C-PR
EWAD-C-
Air cooled chiller, premium efficiency, reduced sound
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • 11 sizes to cover a range from 809 up to 1,521W • EER range up to 3.7 • 2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator - one pass refrigerant side to minimize pressure drops • Partial and heat recovery option available • New MicroTech III controller
Standard available • Wye Delta Starter (Y - D) • Double setpoint • Fans thermal relays • Phase monitor • Evaporator victaulic kit • 20mm Evaporator insulation • Evaporator electric heater • Electronic expansion device • Discharge line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock • Emergency stop
Options • Total heat recovery • Partial heat recovery • Single pump • Twin pump • High ESP fans • Fan silent • Low ambient • Power factor 0.9 • Dual pressure relief valve • Suction line shut off valve • A/V meter • Condenser coil guards • Soft starter • Blank Cu/Al coils • Cu/Sn coils • Cu/Cu coils • Spring Anti Vibration Mounts
COOLING ONLY Capacity class Cooling capacity Capacity control Power input EER ESEER Dimensions
Nom. Method Minimum capacity Cooling Nom.
Unit
kW % kW
810 809
880 875
960 956
C10 1,053
219 3.7 4.63
244 3.58 4.59
272 3.51 4.54
299 3.52 4.59
HeightxWidthxDepth mm
Weight
Unit Operation weight Water heat exchanger Type Water volume Nominal water flow Cooling Nominal water Cooling pressure drop Air heat exchanger Type Fan Air flow rate Nom. Speed Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Water side Cooling Air side Cooling Refrigerant Type Charge Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
2,540x2,285x8,885
kg kg
Heat exchanger
l l/s kPa
7,820 8,420
38.65
599 41.81
1,043 45.69
56
63
29
73,811
l/s rpm dBA dBA Min.~Max. Min.~Max.
7,950 8,990
92.7 71.2
°CDB °CDB kg mm Hz / V
204
202
204
219.1
C11 1,132 Stepless 12.5 330 3.43 4.5
C13 1,251
364 3.44 4.53 2,540x2,285 2,540x2,285x9,785 x11,085 8,580 8,840 10,380 9,620 9,880 10,670 Single pass shell & tube 1,027 995 50.3 54.11 59.76 59
66
58
High efficiency fin and tube type with integral subcooler 82,012 90,213 715 93.4 93.8 94.1 71.7 72.0 Semi-hermetic single screw compressor -8 ~ 15 -18 ~ 52 R-134a 220 252 2 273 3 / 50 / 400
C14 1,359
C15 1,439
C16 1,521
396 3.43 4.51
425 3.39 4.50
457 3.33 4.45
2,540x2,285x11,985 10,720 11,010
64.95
979 68.7
72.6
70
77
84
98,414 94.4
98,417 94.7 72.3
95 72.6
254
222 2515_BOOK_AppliedSystems_2011.indb 222
25/03/2011 08:38
2515_BOOK_AppliedSystems_2011.indb 223
25/03/2011 08:38
Condensing unit The Daikin condensing units can be used in a wide variety of air conditioning, refrigeration and ventilation applications.
Condensing unit ERAD-E-SS ERAD-E-SL
225 226
For a copy of our latest Price List please call 0845 6419000
224 2515_BOOK_AppliedSystems_2011.indb 224
25/03/2011 08:38
ERAD-E-SS
ERAD170,200E-SS
Air cooled condensing unit, standard efficiency, standard sound
Options (factory mounted) • Total heat recovery • Partial heat recovery • Soft starter • Brine version • Compressor thermal relays • Under / over voltage control • Energy meter • Capacitors cosfi 0.9 • Current limit - display • Speedtrol • Condenser coil guards • Cu-cu condenser coil • Cu-cu sn condenser coil • Alucoat fins coil • High pressure side manometers • Container kit • Rubber anti vibration mount • Spring anti vibration mount • Double pressure relief valve with diverter • Compressor circuit breakers • Fan speed regulation
Strengths • Wide capacity range (121kW - 488kW) • Single refrigerant circuit with single screw compressor • Two sound versions available • Compact design with brazed plate heat exchanger Standard available • Wye delta starter (y - d) • Double setpoint • Fans circuit breakers with thermal overload relays • Phase monitor • Discharge line shut off valve • Suction line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock
COOLING ONLY Indoor units Cooling capacity Capacity control Power input EER Dimensions Weight Air heat exchanger Fan Fan motor Sound power level Sound pressure level Compressor Operation range Refrigerant
Power supply
Nom. Method Minimum capacity Cooling Nom.
kW
Unit HeightxWidthxDepth Unit Operation weight Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Type SST Min-Max Condenser Min-Max Type Charge Circuits Quantity Phase / Frequency / Voltage
mm kg kg
% kW
l/s rpm dBA dBA
120 121
140 144
Hz / V
200 196
220 219
250 252
310 306
370 370
440 435
490 488
Stepless 25 41.8 51.0 2.90 2.83 2,273x1,292x2,165 1,584 1,617 10,922
10,575 91.5 73.5
°C °C kg
170 165
17
20
57.4 65.2 73.7 76.6 92.8 122.0 147.2 160.8 2.87 3.00 2.97 3.28 3.30 3.04 2.96 3.03 2,273x1,292x3,065 2,273x1,292x3,965 2,223x2,236x3,070 1,741 1,936 2,679 1,781 1,981 2,756 High efficiency fin and tube type with integral subcooler 16,383 15,863 21,844 21,150 32,767 31,725 920 92.3 93.0 94.2 94.5 95.2 73.7 73.9 75.1 75.0 75.3 76.0 Semi-hermetic single screw compressor -9~12 -18~48 R-134a 22 27 29 32 45 54 58 1 3~ / 50 / 400
225 2515_BOOK_AppliedSystems_2011.indb 225
25/03/2011 08:38
ERAD-E-SL
ERAD160,190E-SL
Air cooled condensing unit, standard efficiency, low sound
Options (factory mounted) • Total heat recovery • Partial heat recovery • Soft starter • Brine version • Compressor thermal relays • Under / over voltage control • Energy meter • Capacitors cosfi 0.9 • Current limit - display • Speedtrol • Condenser coil guards • Cu-cu condenser coil • Cu-cu sn condenser coil • Alucoat fins coil • High pressure side manometers • Container kit • Rubber anti vibration mount • Spring anti vibration mount • Double pressure relief valve with diverter • Compressor circuit breakers • Fan speed regulation
Strengths • Wide capacity range (116kW - 462kW) • Single refrigerant circuit with single screw compressor • Two sound versions available • Compact design with brazed plate heat exchanger • Low operating sound levels Standard available • Wye delta starter (y - d) • Double setpoint • Fans circuit breakers with thermal overload relays • Phase monitor • Discharge line shut off valve • Suction line shut off valve • Ambient outside temperature sensor and set-point reset • Hour run meter • General fault contactor • Set-point reset, demand limit and alarm from external device • Fans circuit breakers • Main switch interlock
COOLING ONLY Indoor units Cooling capacity Capacity control Power input EER Dimensions Weight Air heat exchanger Fan Fan motor Sound power level Sound pressure level Compressor Operation range Refrigerant
Power supply
Nom. Method Minimum capacity Cooling Nom.
kW
Unit HeightxWidthxDepth Unit Operation weight Type Air flow rate Nom. Speed Cooling Nom. Cooling Nom. Cooling Nom. Type SST Min-Max Condenser Min-Max Type Charge Circuits Quantity Phase / Frequency / Voltage
mm kg kg
% kW
l/s rpm dBA dBA
120 116.0
140 137
Hz / V
190 187
210 209
240 243
300 295
350 352
410 409
460 462
Stepless 25 42.3 52.5 2.74 2.61 2,273x1,292x2,165 1,684 1,717 8,372
8,144 89.0 71.0
°C °C kg
160 159
17
20
57.6 66.3 73.9 78.2 91.5 122 150 167 2.75 2.82 2.83 3.11 3.23 2.88 2.73 2.76 2,273x1,292x3,065 2,273x1,292x3,965 2,223x2,236x3,070 1,841 2,036 2,789 1,881 2,081 2,886 High efficiency fin and tube type with integral subcooler 12,558 12,217 16,744 16,289 25,117 24,433 715 89.8 90.5 91.7 92.0 92.7 71.2 71.4 72.6 72.5 72.8 73.5 Semi-hermetic single screw compressor -9~12 -18~48 R-134a 22 27 29 32 45 54 58 1 3~ / 50 / 400
226 2515_BOOK_AppliedSystems_2011.indb 226
25/03/2011 08:38
2515_BOOK_AppliedSystems_2011.indb 227
25/03/2011 08:38
Water cooled chiller Daikin offers you compact water cooled chiller units which require only very limited space in a machine room. Used for commercial or industrial applications, these chillers generate cold and hot water, which can be used for chilling, heating, or even both at the same time.
Water cooled chiller new
new new new new new
EWWP-KBW1N EWWD-MBYN EWWD-G-SS EWWD-G-XS EWWD-I-SS EWWD-I-XS EWWD-BJYNN EWWQ-AJYNN EWWQ-AJYNN/A EWWD-FZXS
229 231 232 233 234 235 236 237 238 239
For a copy of our latest Price List please call 0845 6419000
228 2515_BOOK_AppliedSystems_2011.indb 228
25/03/2011 08:38
EWWP-KBW1N
EWWP014-035KBW1N
Water cooled chiller
Options (factory mounted) • Chilled water temperature down to - 5°C (OPZH) or -10°C (OPZL)
Strengths • One of the most compact units in the market (60cm x 60cm x 60cm for models 014 to 035) • Daikin scroll compressor • Standard reverse phase protection • Extension possible up to 195kW For single module units • Standard main isolator switch • Basic hydraulic components for KB-series included with the unit as a kit: flow switch, air purge, filter + shut-off valves for both condenser and evaporator
Available inputs/outputs • Input - Remote ON / OFF - Pump contact - Cool/heat selection • Output - Compressor operation - Summary alarm - Pump relay contact
Accessories (kit) • Compressor soundproof material (-3dBA) • Hydraulic module (see page EHMC) • BMS gateway (MODBUS protocol) • Remote user interface Control • Microprocessor control • Water inlet temperature control • Cold water or hot water regulation
HEATING ONLY & COOLING ONLY Capacity class Cooling capacity Nom. Heating capacity Nom. Capacity steps number Power input Cooling Nom. EER Dimensions Unit HeightxWidthxDepth Weight Unit Operation weight Water heat exchanger Type - evaporator Minimum water volume in the system Water flow rate Min. Nom. Max. Water heat exchanger Type - condenser Water flow rate Min. Nom. Max. Sound power level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Evaporator water drain Condenser water inlet/outlet Condenser water drain Power supply Phase / Frequency / Voltage
kW kW
014 13.0 16.6
022 21.5 27.3
028 28.0 35.4
035 32.5 41.2
045 43.0 54.8
055 065 56.0 65.0 71.4 82.7 2 11.80 15.50 17.60 3.64 3.61 3.69 600x600x1,200 300 320 334
mm kg kg
118
1 5.79 7.48 3.71 3.74 600x600x600 155 165
l l/min l/min l/min
62 19 37 75
103 31 62 123
134 40 80 161
155 47 93 186
205 62 123 247
268 80 161 321
311 93 186 373
l/min l/min l/min dBA
24 48 95
39 78 157 64
51 102 203
59 118 237 71
79 157 314
102 205 410
118 237 474 74
kW
3.61 3.60
8.75 3.71 172
67
°CDB °CDB
kg
1.2
1 2 2.5 FBSP 25mm FBSP 25mm
3.1
2 4.6 5.6 FBSP 40mm FBSP 40mm
Hz / V
090 86.0 110
100 99.0 126
110 120 130 112 121 130 143 154 165 4 23.6 27.3 31.0 33.1 35.2 3.64 3.63 3.61 3.66 3.69 1,200x600x1,200 600 620 640 654 668 Brazed plate 205 268 311 123 142 161 173 186 247 284 321 347 373 493 568 642 694 745 Brazed plate 157 181 205 221 237 314 362 410 442 474 629 724 819 883 948 71 75 77 Hermetically sealed scroll compressor -10 (OPZL) ~ 25 20 ~ 55 R-407C Thermostatic expansion valve 4 9.2 10.2 11.2 2 x 2 x FBSP 38mm Field installation 2 x 2 x FBSP 38mm Field installation 3N~ / 50 / 400
145 142 181
155 155 198
39.1 3.63
42.8 3.62
165 168 214
175 177 226
6 46.5 48.6 50.7 3.61 3.64 3.67 1,800x600x1,200 940 960 974 988
920
205 204 407 814
185 186 237
222 444 889
195 195 248 52.8 3.69 1.002
268 311 254 267 280 507 533 559 1,015 1,066 1,118
241 482 963
260 283 307 323 339 355 519 567 614 647 679 711 1,038 1,133 1,229 1,293 1,357 1,422 73 76 78 79
6 13.8
14.8 15.8 3 x 2 x FBSP 38mm
16.8
3 x 2 x FBSP 38mm
229 2515_BOOK_AppliedSystems_2011.indb 229
25/03/2011 08:38
EWWP
Water cooled chiller
EWWP014-035KBW1N
EWWP090-130KBW1N
EWWP145-195KBW1N
SELECTION TABLE
1 MODULE (KB-SERIES)
2 MODULES (KB-SERIES)
3 MODULES (KB-SERIES)
Capacity index
014
022
028
035
045
055
065
090
100
110
120
130
145
155
165
175
185
195
Cooling capacity (kW)
13.0
21.5
28.0
32.5
43.0
56.0
65.0
86.0
99.0
112
121
130
142
155
168
177
186
195
16.6 1 -
27.3 1 -
35.4 1 -
41.2 1 -
54.8 1 1 -
71.4 1 1 -
82.7 1 1 -
110 2 1 -
126 1 1 1 -
143 2 1 -
154 1 1 1 -
165 2 1 -
181 2 1 1
198 1 2 1
214 3 1
226 2 1 1
237 1 2 1
248 3 1
Heating capacity (kW) UNIT + CONTROL (Factory mounted) MODULAR UNITS (Controller available as accessory) CONTROL (kit)
EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB2MUAW ECB3MUAW
For example: for a 121 kW HP system, select: EWWP055KBW1N + EWWP065KBW1N
230 2515_BOOK_AppliedSystems_2011.indb 230
25/03/2011 08:38
EWWD-MBYN
EWWD120MBYN
Water cooled chiller
Strengths • Compact and modular design • DAIKIN stepless single screw compressor • Standard reverse phase protection • VICTAULIC joints • DICN operation as standard within same series • Standard discharge shut-off valve • Standard filter, flow switch Options (factory mounted) • Main isolator switch • Low noise (-5 to -7dB(A)) • Compressor suction stop valve • Ampere & Voltmeter (read-out on switchbox) • Dual pressure relief valve
Accessories • Gateway BACnet RS232 (EKBMSBNA) • Gateway ModBus RS232/RS485 (EKBMSMBA) • Address card screw chillers (EKAC’200A) • Remote controller kit screw chillers Control • Microprocessor control • Water inlet or outlet temperature control • Weekly operating schedule
Available inputs/outputs • Input - ON / OFF - Pump contact - Dual setpoint through analog signal - Floating setpoint • Output - Compressor operation - Summary alarm (per circuit) - Pump relay contact
HEATING ONLY & COOLING ONLY Capacity class Cooling capacity Heating capacity Capacity steps Power input EER COP Dimensions
Nom. Nom. Cooling Heating
Unit
Unit Operation weight Water heat exchanger Water flow rate - evaporator
kW kW % kW kW
Nom. Nom.
HeightxWidth (incl. filter space)xDepth
Weight
Nominal water pressure drop (circuit1/circuit2)
Min. Nom. Max. Cooling
180 240 183 249.0 216 290.0 stepless 30 - 100 45.2 61.6 54.0 72.8 4.05 4.04 4.00 3.98
Power supply
Circuits Quantity Relief device outlet Evaporator water inlet/outlet Evaporator water drain Condenser water inlet/outlet Phase / Frequency / Voltage
360 366 431
440 432 505
69.2 83.4 3.95 3.92
90.5 108.0
107.0 127.0
3.99
3.98
500 498 580 stepless 15 - 100 123.0 146.0 4.05 3.97
520 522 617
540 546 655
131.0 156.0 3.98 3.96
138.0 167.0 3.96 3.92
1,273 1,318 265 525 1,070
1,527 1,588 350 714 1,400
1,623 1,693 400 783 1,600
2,546 2,636 525 1,049 2,100
2,800 2,906 625 1,238 2,500
3,034 3,156 700 1,428 2,800
3,150 3,281 750 1,496 3,000
3,346 3,485 800 1,565 3,200
21 / -
25 / -
26 / -
22 / -
25 / 25
25 / 26
26 / 26
26 / 22
22 / 22
2/23 / -
3/28 / -
7/33 / -
9/31 / -
7/7 33 / 33
7/9 33 / 31
9/9 31 / 31
l
600
890
1,220
1,215
1,275
1,335
l/min l/min l/min kPa
217 435 800
336 654 1,050
450 890 1,230
3/3 3/7 28 / 28 28 / 33 Brazed plate, one per circuit 1,330 895 1,055 Shell and tube 520 670 790 981 1,309 1,545 1,370 2,100 2,290
900 1,781 2,470
970 1,871 2,600
1,040 1,962 2,730
30 / 38
38 / 38
mm kg kg l/min l/min l/min kPa
25 / dBA °CDB °CDB kg
30 / -
87
93
2,000x2,681(3,254)x930
38 / -
30 / 30
94
93 Semi-hermetic single screw compressor -10 ~ 20 20 ~ 60 20 ~ 50 R-134a 37 38 70 72 Thermostatic Electronic expansion Electronic expansion valve expansion valve. Thermostatic valve expansion valve
20 ~ 50 18
4.04
1,018x2,681(3,254)x930
35
Thermostatic expansion valve
Piping connections
280 273.0 327.0
28.7 34.5 4.29 4.26 1,018x2,681(3,051) x930 1,000 1,032 175 353 700
Heat exchanger Filter kPa Total kPa
Type Minimum water volume in the system Water heat exchanger Type - condenser Water flow rate Min. Nom. Max. Nominal water Heating pressure drop (circuit1/circuit2) Sound power level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control
120 123 147
1 1x1"
20 ~ 60 74
75
76
Electronic expansion valve 2
2 x 1"
76.1mm
96
3 x 1"
4 x 1"
88.9mm Field installation 88.9mm 3~ / 50 / 400
76.1mm Hz / V
231 2515_BOOK_AppliedSystems_2011.indb 231
25/03/2011 08:38
EWWD-G-SS
Water cooled chiller, standard efficiency, standard sound EWWD-G-SS
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 165.5–555.7kW • EER range up to 4 • 1-2 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return Standard available • Suction stop valve • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Glycol application • Total heat recovery • Partial heat recovery • Power factor 0.9 • A/V meter • Low noise • Soft starter • Cu/Ni heat exchanger Accessories • Communication cards (EKAC200J –EKACBC – EKACLON) • Remote user interface (EKRUPCK) • Buffer tanks (EKBT500N - EKBTC10N - EKBT500C - EKBTC500C) • Daikin serial sequencing panel (EKDSSP) • Modem (EKMODEM – EKG SMOD) • Converter RS485 to RS232 (EKCON) or to USB (EKCONUSB)
HEATING ONLY & COOLING ONLY Indoor units Cooling capacity Heating capacity Capacity control Power input
Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.
EER COP ESEER Dimensions Weight
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type - evaporator Water volume Nominal water Cooling Total pressure drop Water heat exchanger Type - condenser Water flow rate Nom. Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW kW
170 166 204
210 201 247
260 253 310
300 280 343
320 334 410
380 372 456
420 403 494
460 448 552
500 494 610
600 556 674
129 161 3.83 3.79 5.1
150 177 3.70 3.81 4.93
Stepless % kW kW
mm kg kg l kPa
l/s kPa
25 42.2 52.7 3.93 3.87 5.00
50.6 64.9 63.5 80.8 3.97 3.90 3.89 3.84 5.04 4.95 1,860x920x3,435 1,410 1,503 1,480 1,650
1,393 1,470 60
56
48
69
4.72
123 43
84.3 106 3.96 3.88 5.28
93 117 4.00 3.91 5.33
2,687 2,697 2,840 2,850 Single pass shell and tube 118 113 53
9.95
12.02
15.19
16.98
39
41
63
77
dBA dBA
64
63
Single pass shell and tube 19.99 22.22 40
50
12.5 101 115 127 144 3.97 3.89 3.89 3.84 5.29 5.19 1,880x860x4,305 2,702 2,757 2,860
2,762 2,970
173 72
168 54
24.08 41
87.7 69.7
68
26.90
29.77
33.73
57
60
75
90.2 71.7
°CDB °CDB kg
75.3 89.2 3.72
55
Semi-hermetic single screw compressor -8~15 20~55 R-134a 110 50 Electronic expansion valve
1
55
110
2
88.9mm
114.3mm
139.7mm
5" 3 / 50 / 400
Hz / V
232 2515_BOOK_AppliedSystems_2011.indb 232
25/03/2011 08:38
EWWD-G-XS
EWWD-G-XS
Water cooled chiller, high efficiency, standard sound
Strengths • High efficiency • EER range up to 4.73 • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 186.4–603.9kW • 1-2 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return Standard available • Suction stop valve • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Glycol application • Total heat recovery (EWWD190500DJYNN/A) • Partial heat recovery • Power factor 0.9 • A/V meter • Low noise • Soft starter • Cu/Ni heat exchanger Accessories • Communication cards (EKAC200J - EKACBAC - EKACLON) • Remote user interface (EKRUPCK) • Buffer tanks (EKBT500N - EKBTC10N - EKBT500C - EKBTC500C) • Daikin Serial Sequencing panel (EKDSSP) • Converter RS485 to RS232 (EKCON) or to USB (EKCONUSB)
HEATING ONLY & COOLING ONLY Indoor units Cooling capacity Heating capacity Capacity control Power input
Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.
EER COP ESEER Dimensions Weight
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type - evaporator Water volume Nominal water Cooling Total pressure drop Water heat exchanger Type - condenser Water flow rate Nom. Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW kW
190 186 220
230 223 264
280 277 326
320 307 354
380 366 434
400 408 482
460 444 524
500 496 585
550 541 638
650 604 712
87.2 110 4.68
95.1 120 4.67
105 132 4.73 4.38 4.42 6.24 6.23 6.31 1,880x860x4,305 2,800 2,945 2,955 2,975 3,020 3,280 3,290 3,315 Single pass shell and tube 170 285
115 144 4.72 4.43 6.30
137 162 4.39 4.40 5.85
Stepless % kW kW
mm kg kg l kPa
l/s kPa dBA dBA
25 39.6 50.1 4.70 4.38 5.97 1,650 1,800 125
12.5
48.1 59.4 60.6 74.5 4.64 4.66 4.35 4.38 5.9 5.92 1,860x920x3,435 1,665 1,680 1,810 1,820 120
110
25
35
44
10.78
12.95
16.07
18.08
17
20
25
28
79.2 99.9 4.62 4.34 6.15
30
24
Single pass shell and tube 21.27 23.66
1 114.3mm
280
39
46
57
25.76
28.71
31.34
35.40
16
15
19
90.9 71.7 Semi-hermetic single screw compressor -8~15 20~55 R-134a 110 105 Electronic expansion valve
55
2,990 3,340
28
17
88.2 69.7
°CDB °CDB kg
71.4 83.7 4.30 4.23 5.46
100 2
139.7mm
168.3mm
5" 3 / 50 / 400
Hz / V
233 2515_BOOK_AppliedSystems_2011.indb 233
25/03/2011 08:38
EWWD-I-SS
Water cooled chiller, standard efficiency, standard sound
EWWD-I-SS
Strengths • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 333-1,510kW • EER range up to 4.66 • 1-2-3 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops
Options (factory mounted) • Glycol application • Total heat recovery • Partial heat recovery • Power factor 0.9 • Suction stop valve • A/V meter • Soft starter • Cu / Ni heat exchanger • Dual pressure relief valve
Standard available • Main switch • Gauges • Electronic expansion valve
Accessories • Communication cards (EKAC200J – EKACBAC – EKACLON) • Remote user interface (EKRUPCK) • Buffer tanks (EKBT500N - EKBTC10N - EKBT500C - EKBTC500C) • Daikin serial sequencing panel (EKDSSP) • Modem (EKMODEM – EKG SMOD) • Converter RS485 to RS232 (EKCON) or to USB (EKCONUSB)
HEATING ONLY & COOLING ONLY Indoor units Cooling capacity Heating capacity Capacity control Power input
Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.
EER COP ESEER Dimensions Weight
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type - evaporator Water volume Nominal water Cooling Heat pressure drop exchanger Water heat exchanger Type - condenser Water flow rate Nom. Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW kW % kW kW
mm kg kg l kPa
l/s kPa dBA dBA
340 333 388.4
900 950 C10 C12 C13 C14 C15 C16 C17 910 986 1,027 1,155 1,204 1,274 1,346 1,401 1,455 1,072 1,161 1,217 1,363 1,427 1,507 1,227 1,661 1,730 Stepless 25 12.5 8.3 71.5 85.8 101 120 141 156 171 186 200 218 237 254 268 282 298 317 335 87.4 104 122 143 174 191 208 225 243 262 282 309 326 344 363 383 401 4.66 4.59 4.56 4.47 4.53 4.52 4.57 4.55 4.51 4.33 4.54 4.50 4.51 4.43 4.35 4.44 4.42 4.41 4.35 4.36 4.42 4.41 4.43 4.32 4.41 4.38 3.38 4.34 4.31 5.06 4.96 4.93 4.86 5.54 5.75 5.56 5.7 5.47 5.61 5.36 5.51 5.56 5.54 5.55 5.45 1,821x1,430x3,398 2,113x1,350x4,361 2,323x2,135x4,426 2,150 2,160 2,179 2,224 3,909 3,927 3,945 3,971 3,996 4,080 4,092 6,079 6,097 6,136 6,174 6,192 6,210 2,380 2,396 2,410 2,457 4,217 4,228 4,243 4,262 4,288 4,369 4,386 6,628 6,646 6,670 6,699 6,717 6,735 Single pass shell and tube 193 183 172 271 263 256 248 241 233 472 504 489 472 37
400 394 460
50
460 460 538
550 538 630
54
650 640 757
62
700 705 832
55
44
850 844 993
58
53
66
51
62
56
47
58
62
66
C18 1,510 1,790
353 420 4.28 4.26 5.27 6,228 6,761
71
Single pass shell and tube 19.33 22.92 26.80 31.44 37.31 41.14 45.53 49.21 53.03 57.52 60.39 67.32 70.33 74.34 78.55 82.08 85.52 89.01 26
28
93.7 75.2
96.6 76.2
54
52
30
26
25
96.7 78.2
28
96.9 77.8
97.3 78.2
108
106 168.3mm
°CDB °CDB
1 kg
800 782 919
51
50
26
23
24
25
97.8 98.9 99.8 100.4 100.8 101.2 78.7 79.8 80.7 80.4 80.8 81.2 Semi-hermetic single screw compressor -8~15 20~55 R-134a Electronic expansion valve 2 104 100 156 155 154
24
23 103.0 83.0
3 153 152 219.1mm
151
150
5" 3 / 50 / 400
Hz / V
234 2515_BOOK_AppliedSystems_2011.indb 234
25/03/2011 08:38
EWWD-I-XS
Water cooled chiller, high efficiency, standard sound
EWWD-I-XS
Strengths • High efficiency • All models are PED pressure vessel approved • Stepless single-screw compressor • Optimised for use with R-134a • Cooling range: 362-1,134 kW • EER range: 4.72-5.1 • 1 or 2 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator – one pass refrigerant side to minimize pressure drops Standard available • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Glycol application • Partial heat recovery • Power factor 0.9 • Suction stop valve • A/V meter • Soft starter • Cu / Ni heat exchanger • Dual pressure relief valve Accessories • Communication cards (EKAC200J – EKACBAC – EKACLON) • Remote user interface (EKRUPCK) • Buffer tanks (EKBT500N - EKBTC10N - EKBT500C - EKBTC500C) • Daikin serial sequencing panel (EKDSSP) • Plant visor (EKPV 2J) • Modem (EKMODEM – EKG SMOD) • Converter RS485 to RS232 (EKCON) or to USB (EKCONUSB)
HEATING ONLY & COOLING ONLY Indoor units Cooling capacity Heating capacity Capacity control Power input
Nom. Nom. Method Minimum capacity Cooling Nom. Heating Nom.
EER COP ESEER Dimensions Weight
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type - evaporator Water volume Nominal water Cooling Heat pressure drop exchanger Water heat exchanger Type - condenser Water flow rate Nom. Water flow rate 2 Nom. Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW kW % kW kW
mm kg kg l kPa
360 362 410.9
71 85.9 5.10 4.78 5.34 2,594 2,998
440 433 493
500 506 577
600 573 660
25 85.4 100 103 121 5.07 5.06 4.79 4.77 5.27 5.22 1,883x1,430x4,081 2,667 2,704 3,078 3,116
326
317
64
48
121 143 4.75 4.62 5.11
308 54
l/s l/min kPa
20.69
24.77
48
47
dBA dBA
93.7 75.20
96.6 76.2
90
87
750 720 823
28.95
33.16
51
°CDB °CDB
156 189 5.10 4.80 6.31
48
47
48
85
180
177
168.3mm
174
C10 976 1,126
C11 1,038 1,203
C12 1,134 1,313
199 240 4.9 4.69 5.9
219 263
240 285 4.73
4.57 6.05
5,097 5,729
4.61 5.67 5,132 5,741 504
50
72
46
52
23.31 28
28.07 28.07
27.10 33
32.82 32.82
47
96.9 97.3 97.8 77.8 78.2 78.7 Semi-hermetic single screw compressor -8~15 20~55 R-134a Electronic expansion valve
1 kg
950 933 1,069
170 206 5.08 4.81 6.01
Single pass shell and tube 20.58 20.44 24.75 20.58 24.98 24.75
66 96.7 78.2
850 866 990
12.5 185 223 5.05 4.79 6.14 2,245x1,350x4,769 4,964 4,997 5,049 5,073 5,582 5,615 5,671 5,695 Single pass shell and tube 539 528 141 172 5.09 4.78 6.13
68
-
800 795 908 Stepless
50
65
98.9 79.8
99.8 80.7
2 172 219.1mm
170
5" 3 / 50 / 400
Hz / V
235 2515_BOOK_AppliedSystems_2011.indb 235
25/03/2011 08:38
EWWD-BJYNN
EWWDC11BJYNN
Water cooled chiller, high efficiency, flooded evaporator
Strengths • All models are PED pressure vessel approved • 1 and 2 stepless single-screw compressors • Optimised for use with R-134a • Cooling range: 369–1050kW • Super high efficiency: EER up to 5.84 • Very high EER values at part loads condition • Flooded evaporator • Expansion valve with liquid level control Standard available • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Glycol application • Suction stop valve • A / V meter • Soft starter • Cu / Ni heat exchanger Accessories • Communication cards (EKAC200J – EKACBAC – EKACLON) • Remote user interface (EKRUPCK) • Buffer tanks (EKBT500N - EKBTC10N - EKBT500C - EKBTC500C) • Daikin serial sequencing panel (EKDSSP) • Modem (EKMODEM – EKG SMOD) • Converter RS485 to RS232 (EKCON) or to USB (EKCONUSB)
COOLING ONLY Capacity class Cooling capacity Capacity steps Power input EER ESEER Dimensions Weight
Nom. Cooling
Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Type - evaporator Minimum water volume in the system Water flow rate Min. Nom. Max. Nominal water Cooling Heat pressure drop exchanger Water heat exchanger Minimum water volume in the system - condenser Water flow rate Min. Nom. Max. Nominal water Heating pressure drop Water heat exchanger - heat recovery condenser Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water drain Power supply Phase / Frequency / Voltage
380 369
750 734
l l/min l/min l/min kPa
78 565 1,058 1,788
129 142 5.65 5.71 7.16 7.23 2,300x4,145x1,743 5,546 5,636 5,911 6,045 Flooded shell and tube 184 932 1,216 2,104 2,339 2,946 3,846
35
43
37
51
37
l l/min l/min l/min kPa
83 665 1,244 2,103
111 948 1,499 2,998
133 1,086 1,752 3,435
181 1,478 2,474 4,675
199 1,703 2,746 5,386
35
25
26
28
26
kW % kW
mm kg kg
Type dBA
460 550 445 521 stepless 25 - 100 65 77.9 90 5.68 5.71 5.79 6.44 6.47 6.56 2,250x3,625x1,551 2,250x3,860x1,551 3,089 3,370 3,603 3,250 3,588 3,870 107 615 1,276 1,945
134 776 1,494 2,455
900 895 Stepless 12.5 - 100 155 5.77 7.32 2,300x4,145x1,808 6,007 6,460 210
C10 976
167 180 5.81 5.83 7.37 7.40 2,300x4,145x1,910 6,448 6,598 6,972 7,163 281 1,382 2,798 4,370
1,209 2,566 3,825 45
C11 1,050
302 1,632 3,010 5,162
41
34
1,904 3,010 6,020
1,924 3,277 6,085
263 2,146 3,526 6,786
25
29
27
82
82.5
83
230
274
290
243
Shell and tube 78
79
80
130
165
180
°CDB °CDB kg
850 816
Hz / V
81 81.5 Semi-hermetic single screw compressor -8 ~ 15 21 ~ 50 R-134a 200 215 Electronic expansion valve 1 1/2" gas 3~ / 50 / 400
236 2515_BOOK_AppliedSystems_2011.indb 236
25/03/2011 08:38
EWWQ-AJYNN
EWWQC19-C20AJYNN
Water cooled chiller, standard efficiency
Strengths • Cooling range: 388-2,093kW • EER range up to 4.64 • ESEER up to 5.37 • 1 or 2 stepless single-screw compressors • 1 or 2 truly independent refrigerant circuits • Optimised for use with R-410A • Shell and tube heat exchanger • Standard electronic expansion valve • Compact design • Partial heat recovery available • All models are PED pressure vessel approved Standard available • Glycol application • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Partial heat recovery • Power factor 0.9 • A/V meter • Soft starter • Pressure relief valve • Suction stop valve Accessories • Communication cards (EKAC200J – EKACBAC –EKACLON) • Modem (EKMODEM – EKG SMOD) • Remote user interface (EKRUPCK) • Converter RS485 to RS232 (EKCON) or to USB (EKCONUSB)
COOLING ONLY Capacity class Cooling capacity Capacity control
Nom. Method Minimum capacity
kW
480 474.13
750 742.14
800 812.53
850 880.09
106.27 130.44 147.86 169.73 4.46 4.40 4.41 4.37 4.98 4.97 4.72 1,846x1,266 1,846x1,065x3,431 2,000x1,226x3,440 x3,561 1,933 1,967 2,283 2,332 2,407 2,135 2,169 2,543 2,628 2,777
12.5 stepless 12.5 - 100 175.22 4.64 5.37 2,170x1,350 x4,902 3,921 4,422
25 stepless 25 - 100 206.4 4.26 4.60 1,846x1,266 x3,561 2,427 2,795
% %
Capacity steps Power input EER ESEER Dimensions
400 387.96
Cooling
Nom.
Unit
HeightxWidthxDepth mm
Unit Operation weight Water heat exchanger Type Water heat exchanger Water flow rate Nom. - evaporator Nominal water Cooling pressure drop Water heat exchanger Water flow rate Nom. - condenser Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Condenser Cooling Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Refrigerant circuit 2 Charge Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW
Weight
kg kg l/min Heat kPa exchanger l/min kPa dBA dBA Min.~Max. Min.~Max.
600 574.36
650 651.45
25 stepless 25 - 100 87.37 4.44 4.95
1,111.8 1,359 1,646.4 1,867.2 2,124.6 2,328.6 2,519.4
C13 C14 C15 C16 C17 C18 C19 C20 1,210.09 1,281.09 1,352.09 1,488.14 1,620.34 1,783.43 1,928.13 2,092.73 12.5 stepless 12.5 - 100 261.72 279.05 296.39 339.95 375.37 408.72 441.58 475.47 4.62 4.59 4.56 4.38 4.32 4.36 4.37 4.40 5.36 5.35 5.29 4.93 4.82 4.89 4.87 2,455x1,350x4,835
2,547x1,350x4,844
2,547x1,350x4,809
4,529 4,536 4,607 4,988 4,999 5,053 5,204 5,289 5,186 5,200 5,280 5,602 5,615 5,670 5,881 5,970 3,468 3,671.4 3,875.4 4,260
4,636 5,105.4 5,519.4 5,990.4
1,372.2 1,675.2 2,034.6 2,307.6 2,632.2 2,851.2 3,136.2 3,132.6 3,445.2 3,676.8 3,794.4 4,249.2 4,504.2 4,759.2 5,277.6 5,760.6 6,328.8 6,841.2 7,413.6 60.15 64.35 67.91 66.02 16.46 64.44 20.43 66.55 67.64 25.92 70.09 100.2 101.2 82.2 83.0
102.3 83.9
1 80
90 -
168.3mm 5" Hz / V
C10 C11 C12 980.45 1.028.15 1,077.43 stepless 12.5 25 stepless Stepless 12.5 - 100 25 - 100 194.02 212.97 245.47 236.90 4.59 4.60 4.19 4.55 5.36 5.34 4.53 5.33 1,846x1,266 2,379x1,350 2,170x1,350x4,902 x3,561 x4,912 3,949 3,988 2,457 4,344 4,463 4,496 2,812 4,780 Shell and tube 2,554.2 2,809.8 2,943 3,088.2
49.43 64.65 45.04 47.92 54.74 53.80 50.22 63.54 59.07 57.23 70.01 45.37 50.28 55.40 59.86 69.74 89.42 98.78 122.57
°CDB °CDB
kg kg
900 891.19
73.40
69.77 16.52 19.31 16.93 17.08 15.02
101.5 104.7 102.3 104.7 105.1 103.2 104.7 105.2 106.5 83.2 84.0 84.9 85.2 85.6 86 86.5 86.9 Semi-hermetic single screw compressor -4~10 25~45 R-410A Electronic expansion valve 2 1 2 1 100 85 100 85 100 95 100 85 85 95 100 219.1mm 6" 5" 6" 5" 6" 5" 3~ / 50 / 400
105.8 106.2 106.6 107.1 107.5 86.2 86.6 87 87.5 87.9
2 130 130 273mm 6"
237 2515_BOOK_AppliedSystems_2011.indb 237
25/03/2011 08:38
EWWQ-AJYNN/A
EWWQC19-C22AJYNN/A
Water cooled chiller, high efficiency
Strengths • Cooling range: 431-2,196kW • EER range up to 5.09 • ESEER up to 5.98 • 1 or 2 stepless single-screw compressors • 1 or 2 truly independent refrigerant circuits • Optimised for use with R-410A • Shell and tube heat exchanger • Standard electronic expansion valve • Compact design • Partial heat recovery available • All models are PED pressure vessel approved Standard available • Glycol application • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Partial heat recovery • Power factor 0.9 • A/V meter • Soft starter • Pressure relief valve • Suction stop valve Accessories • Communication cards (EKAC200J – EKACBAC –EKACLON) • Converter RS485 to RS232 • Converter RS485 to USB • Modem (EKMODEM – EKG SMOD) • Remote user interface (EKRUPCK) • Daikin serial sequencing panel (EKDSSP)
COOLING ONLY Capacity class Cooling capacity Capacity steps Power input EER ESEER Dimensions
Nom.
kW %
Cooling
Nom.
Unit
HeightxWidthxDepth mm
Unit Operation weight Water heat exchanger Type Water heat exchanger Water flow rate Nom. - evaporator Nominal water Cooling pressure drop Water heat exchanger Type - condenser Water flow rate Nom. Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Condenser Cooling Refrigerant Type Control Circuits Quantity Refrigerant circuit Charge Refrigerant circuit 2 Charge Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW
Weight
kg kg l/min Heat kPa exchanger
Min.~Max. Min.~Max.
440 431
550 527
650 635
750 740
800 818
950 993
86.67 104.72 128.28 145.95 4.97 5.03 5.09 5.07 5.58 5.61 5.69 5.67 2,001x1,218 2,000x1,211x3,987 x3,855 2,322 2,403 2,464 2,738 2,594 2,685 2,745 3,158
162.04 196.57 5.05 5.64 5.39 2,000x1,266 2,001x1,448 x3,854 x3,891 2,407 2,427 2,815 3,056
1,197
1,463.4 1,813.2
2,058
2,272.8
2,760
C11 C12 C13 C14 C15 C16 C18 1,139 1,182 1,297 1,397 1,479 1,605 1,769 stepless stepless 12.5 - 100 25 - 100 232.06 233.11 257.54 274.77 291.86 321.48 356.36 4.91 5.07 5.04 5.08 5.07 4.99 4.96 5.28 5.87 5.88 5.98 5.93 5.67 5.71 2,001x1,448 2,453x1,350x4,985 2,547x1,350x4,844 x3,891 2,457 4,831 4,873 4,919 4,969 5,117 3,086 5,479 5,512 5,546 5,606 5,794 5,843 Shell and tube 2,944.2 3,164.4 3,286.2 3,606.0 3,882.6 4,108.8 4,459.8 4,957.0
55.77
68.81
64.27
57.46
53.85
53.69
stepless 25 - 100
71.54
C10 1,059 stepless 12.5 - 100 209.49 5.06 5.89 2,453x1,350 x4,985 4,775 5,431
68.89
64.23
55.13
67.85
75.14
4,708.8
4,986
49.20
46.82
l/min kPa
1,457.4 1,778.4
2,199
2,496.6
2,760
3,350.4 3,573.6
Shell and tube 3,861 3,986.4 4,380
50.16
39.75
42.38
46.94
59.79
64.73
40.10
83.56
dBA dBA
100.9 82.2
101.7 83.0
102.6 102.7 83.9
102 83.2
102.9 84.0
110
130
105.2 103.8 105.6 106.1 106.5 85.6 84.9 86 86.5 86.9 Semi-hermetic single screw compressor -4~10 25~45 R-410A Electronic expansion valve 2 1 120 130 120 120 120 273mm 5" 3~ / 50 / 400
°CDB °CDB
1 kg kg
95 219.1mm
Hz / V
47.93
48.17
70.1
89.12
C19 1,901
C20 2,061
C22 2,196
390.31 425.94 460.72 4.87 4.84 4.77 5.48 5.50 5.38 2,547x1,350x4,809 5,388 6,110
5,408 6,118
5,414 6,124
5,283
5,727
6,103.8
91.3
113.04 126.77
5,425.2 5,985.6 6,454.8 7,005.6 7,485.6 44.26
61.21
60.50
105.8 86.2
106.2 86.6
106.6 87
79.00 107.1 87.5
107.5 87.9
2 130 130
238 2515_BOOK_AppliedSystems_2011.indb 238
25/03/2011 08:38
EWWD-FZXS
EWWD640-C10FZXS
Water cooled chiller with centrifugal compressor
Standard available • Inverter compressor starter • Evaporator victaulic kit • Evaporator water side design pressure 10 bar • 20 mm evaporator insulation • Condenser victaulic kit • Condenser water side design 16 bar • Electronic expansion device • Hour run meter • General fault contactor
Strengths • Oil free centrifugal compressor (with magnetic bearings) • Integrated VFD to reach outstanding partial load efficiencies (ESEER up to 9.60), resulting in great energy savings • Reduced maintenance thanks to the elimination of oil • Low sound level (sound pressure at 1m around 80 dB(A)) • Extensive options list • Easy integration with control systems (BMS, Sequencing Panels)
COOLING ONLY Indoor units Cooling capacity Capacity control Power input
Min. Max. Method Cooling Cooling
EER ESEER Dimensions Weight
Min. Max.
HeightxWidthxDepth Unit Unit Operation weight Water heat Type exchanger Nominal water Cooling Heat evaporator exchanger pressure drop Water heat Type exchanger Water flow rate Nom. condenser Nominal water Cooling pressure drop Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water inlet/outlet Condenser water inlet/outlet Power supply Phase / Frequency / Voltage
kW kW
320 114 317
430 128 429
kW kW
21.6 65.9
27.7 85.7
mm kg kg
5.40 8.60 1,823x1,276x3,254 2,360 2,416 2,520 2,634
kPa
30
31
l/s kPa
18.3
24.6
24
25
dBA dBA
89.0 70.9
90.1 72.0
210
190
°CDB °CDB kg
mm mm Hz / V
168.3
520 640 172 114 521 635 Variable speed centrifugal compressor 33.1 21.6 104 132 6.00 5.40 9.40 8.80 1,823x1,276x3,419 1,755x1,790x3,441 2,546 3,709 2,812 4,074 Flooded shell and tube (2 passes) 23
18
Flooded shell and tube (2 passes) 29.9 36.7 28
24
91.2 92.4 73.0 73.8 Oil free centrifugal compressor with magnetic bearings 2~15 18~46 R-134a 180 220 Electronic expansion valve 1 219.1
168.3
860 128 856
C10 172 1,048
27.7 171 5.50 8.60 1,748x1,853x3,289 4,095 4,548
33.1 206 5.90 9.60 1,794x1,904x3,401 4,765 5,330
21
11
49.1
59.9
25
29
93.6 75.1
94.6 75.9
300
273 219.1
3~ / 50 / 400
239 2515_BOOK_AppliedSystems_2011.indb 239
25/03/2011 08:38
Condenserless chiller Daikin offers you flexible and compact chillers with remote condenser, which can be used to satisfy applications with special requirements in the field of available space, sound level or extreme operating conditions. In these exceptional cases, remote condenser solutions can be preferred over standard air cooled or water cooled solutions.
Water cooled condenserless chiller new new
EWLP-KBW1N EWLD-MBYN EWLD-G-SS EWLD-I-SS
241 242 243 244
For a copy of our latest Price List please call 0845 6419000
240 2515_BOOK_AppliedSystems_2011.indb 240
25/03/2011 08:38
EWLP-KBW1N
EWLP014KBW1N
Water cooled condenserless chiller
Strengths • One of the most compact units in the market (60cm x 60cm x 60cm for models 012 to 030) • Daikin scroll compressor • Standard main isolator switch • Basic hydraulic components : included as a kit with the unit: flow switch, air purge, filter + shut-off valves • Standard reverse phase protection Options (factory mounted) • Chilled water temperature down to - 5°C (ZH) or -10°C (ZL)
Control • Microprocessor control • Water inlet temperature control Available inputs/outputs • Input - Remote ON / OFF - Pump contact • Output - Compressor operation - Summary alarm - Pump relay contact
Accessories (kit) • Compressor soundproof material (-3dBA). • Hydraulic module (see also EHMC) • BMS gateway (MODBUS) • Remote user interface
COOLING ONLY Indoor units Cooling capacity Power input EER Dimensions Weight Water heat exchanger - evaporator
Sound power level Compressor Operation range Refrigerant
Piping connections Power supply
Nom. Cooling
Nom.
Unit HeightxWidthxDepth Unit Minimum water volume in the system Water flow rate Min. Nom. Max. Model Quantity Type Cooling Nom. Type Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Type Control Circuits Quantity Evaporator water inlet/outlet Evaporator water drain Phase / Frequency / Voltage
kW kW mm kg l l/min l/min l/min
dBA
012 12.1 4.2 2.88
020 20.0 6.6 3.03
108 62 17 35 69
141 103 29 57 115
026 26.8 8.5 3.15
030 31.2 10.1 3.09
040 40.0 13.4 2.99
147 134 38 77 153
151 155 45 89 179 1 Brazed plate 71 Hermetically sealed scroll compressor -10~20 25~60 R-407C Thermostatic expansion valve
252 205 57 115 229
055 53.7 17.8 3.02 600x600x1,200 265 268 77 154 307
600x600x600
64
°CDB °CDB
1 FBSP 25mm
67
065 62.4 20.3 3.07 274 311 89 179 358
74
2 FBSP 40mm Field installation 3N~ / 50 / 400
Hz / V
241 2515_BOOK_AppliedSystems_2011.indb 241
25/03/2011 08:38
EWLD-MBYN
EWLD120MBYN
Water cooled condenserless chiller
Control • Microprocessor control • Water inlet temperature control • Weekly operation schedule
Strengths • Daikin stepless single screw compressor • Compact and modular design • Standard phase sequence controller • VICTAULIC joints • DICN operation as standard within same series • Standard discharge shut-off valve • Standard flow switch • Standard filter • Ampere and Voltmeter (read-out on switchbox) • Dual pressure relief valve
Available inputs/outputs • Input - ON / OFF - Pump contact - Dual setpoint through analog signal - Floating set point • Output - Compressor operation - Summary alarm - Fan-condenser relay contacts - Pump relay contact
Accessories (kit) • BMS gateway (MODBUS / J-BUS / BACNET protocol) • Remote user interface
COOLING ONLY Capacity class Cooling capacity Capacity steps Power input EER Dimensions Weight
Nom. Cooling
Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Minimum water volume in the system - evaporator Water flow rate Min. Nom. Max. Nominal water Cooling Heat pressure drop exchanger (circuit 1) Filter Total Nominal water Cooling Heat pressure drop exchanger (circuit 2) Filter Total Model 1 Quantity Type Model 2 Quantity Type Type Sound power level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Control
kW % kW mm kg kg l l/min l/min l/min kPa kPa kPa kPa
120 116
170 240 170 235 stepless 30 - 100 49.8 66.5 3.41 3.53 1,018x2,681x930 1,110 1,342 1,130 1,369 830 1,150 265 350 487 674 1,070 1,400
32.0 3.63 891 907 570 175 333 700
Circuits Quantity Evaporator water inlet/outlet
Power supply
Evaporator water drain Phase / Frequency / Voltage
77.9 3.40
99.6 3.41
116 3.49
1,428 1,462 1,300 400 760 1,600
2,220 2,260 830 525 975 2,100
2,452 2,497 990 625 1,161 2,500
480 470 stepless 15 - 100 133 3.53 2,000x2,681x930 2,684 2,738 1,150 700 1,347 2,800
500 500
540 530
144 3.47
156 3.40
2,770 2,831 1,220 750 1,434 3,000
2,856 2,924 1,295 800 1,520 3,200
25
26
22
25
26
22
3 28
6 32
8 30
3 28
7 33
9 31
-
25
26
22
1
3 28 2
7 33
9 31
AC250Q-NP96
87
AC250Q-NP128 -
93
AC250Q-NP162
1 AC250Q-NP96
1 AC250Q-NP128 Brazed plate, one per circuit
94
93 Semi-hermetic single screw compressor -10 ~ 20 25 ~ 62 25 ~ 55 R-134a Thermostatic Thermostatic expansion Electronic expansion valve expansion valve valve Electronic expansion valve
25 ~ 55
Thermostatic expansion valve
Piping connections
400 405
2 23
AC120EQ-NP156
°CDB °CDB
340 340
21
kPa kPa
dBA
260 265
1 3" OD victaulic coupling
2 AC250Q-NP128 -
1 AC250EQ-NP128 1 AC250EQ-NP162
2 AC250EQ-NP162 -
96
25 ~ 62
Electronic expansion valve 2
3" victaulic coupling Field installation 3~ / 50 / 400
Hz / V
242 2515_BOOK_AppliedSystems_2011.indb 242
25/03/2011 08:38
EWLD-G-SS
Water cooled condenserless chiller, standard efficiency, standard sound EWLD-G-SS
Strengths • Cooling range: 161-526kW • EER range: 3.48-3.70 • Stepless single-screw compressor • Optimised for use with R-134a • 1-2 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return • All models are PED pressure vessel approved Standard available • Main switch • Suction stop valve • Gauges • Electronic expansion valve
Options (factory mounted) • Glycol application • Partial heat recovery • Power factor 0.9 • A/V meter • Low noise • Soft starter • Liquid receiver Accessories • Communication cards (EKAC200J – EKACBAC –EKACLON) • Converter RS485 to RS232 or to USB • Modem (EKMODEM – EKG SMOD) • Bacnet gateway (EKBMSBNJ) • Remote user interface (EKRUPCK) • Daikin serial sequencing panel (EKDSSP) • Buffer tanks (EKBT500N – EKBTC10N – EKBT500C – EKBTC10C)
COOLING ONLY Indoor units Cooling capacity Capacity steps Power input EER Dimensions Weight
Nom. Cooling
Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Minimum water volume in the system - evaporator Water flow rate Min. Nom. Max. Nominal water Cooling Heat pressure drop exchanger Model Quantity Type Type Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW mm kg kg l l/min l/min l/min kPa
160 161
190 240 189 244 stepless 25 - 100 54.3 65.9 3.48 3.70 1,860x1,000x3,700
45.4 3.54 1,280 1,337
280 270
320 316
74.6 3.62 1,398 1,516
1,151 230.20 460.39 649.15
1,354 270.90 541.81 763.95
1,749 349.74 699.47 986.26
1,938 387.58 775.16 1,092.97
48
69
43
53
360 352
380 420 381 428 stepless 12.5 - 100 90.6 99.7 108.6 120 3.48 3.53 3.51 3.57 1,942x1,100x4,400 2,442 2,446 2,501 2,560 1,130 1,262 1,365 1,535 452.22 504.83 546.25 613.90 904.44 1,009.65 1,092.50 1,227.81 1,275.27 1,423.61 1,540.42 1,731.21 64
63
72
480 476
550 526
131.5 3.62
148 3.55 2,506
2,670 1,704 681.84 1,363.69 1,922.80 54
1,884 753.80 1,507.60 2,125.71 68
1 EV19270055
EV27270066
EV27270077 EV27270088 Shell and tube - direct expansion
88 69.7
dBA dBA
EV32270088
EV32270099
90.5 71.7 Semi-hermetic single screw compressor -8~15 25~60 R-134a
°CDB °CDB 5
kg
10 Electronic expansion valve
1
2
88.9
114.3 3~ / 50 / 400
Hz / V
139.7
243 2515_BOOK_AppliedSystems_2011.indb 243
25/03/2011 08:38
EWLD-I-SS
EWLD-
Water cooled condenserless chiller, standard efficiency, standard sound
Strengths • Cooling range: 328-1,422kW • EER range: 3.51-3.91 • Stepless single-screw compressor • Optimised for use with R-134a • 1 or 2 truly independent refrigerant circuits • Standard electronic expansion valve • DX shell and tube evaporator – one pass refrigerant side for easy oil circulation and return • All models are PED pressure vessel approved Standard available • Main switch • Gauges • Electronic expansion valve
Options (factory mounted) • Glycol application • Total heat recovery • Partial heat recovery • Power factor 0.9 • A/V meter • Soft starter • Liquid receiver Accessories • Communication cards (EKAC200J – EKACBAC –EKACLON) • Converter RS485 to RS232 • Converter RS485 to USB • Modem (EKMODEM – EKG SMOD) • Bacnet gateway (EKBMSBNJ) • Remote user interface (EKRUPCK) • Sequencing panel (EKCSCII) • Buffer tanks (EKBT500N – EKBTC10N – EKBT500C – EKBTC10C) • Plant visor (EKPV 2J)
COOLING ONLY Indoor units Cooling capacity Capacity control Power input EER Dimensions Weight
Nom. Method Minimum capacity Cooling Nom.
Unit HeightxWidthxDepth Unit Operation weight Water heat exchanger Water flow rate Nom. - evaporator Nominal water Cooling Total pressure drop Type Sound power level Cooling Nom. Sound pressure level Cooling Nom. Compressor Type Operation range Evaporator Cooling Min.~Max. Condenser Cooling Min.~Max. Refrigerant Type Charge Control Circuits Quantity Piping connections Evaporator water inlet/outlet Power supply Phase / Frequency / Voltage
kW % kW mm kg kg l/min kPa
dBA dBA
320 328
400 391
420 428
500 504
600 596
650 657
750 730
800 788
850 850
900 950 919 966 Stepless
C10 C11 C12 C13 C14 C15 C16 C17 1,033 1,078 1,125 1,188 1,267 1,319 1,370 1,422
25 12.5 8.3 83.8 100 116 137 165 181 198 214 231 252 271 279 296 312 329 347 366 386 405 3.91 3.9 3.7 3.67 3.61 3.63 3.69 3.67 3.65 3.56 3.59 3.64 3.60 3.61 3.65 3.60 3.55 3.51 1,899x1,464x3,114 2,325x1,464x4,391 2,415x2,135x4,426 1,861 1,869 1,884 3,331 3,339 3,347 3,356 3,364 3,412 5,146 5,167 5,188 5,208 2,054 2,052 2,056 3,602 3,603 3,604 3,605 3,645 5,667 5,671 5,677 5,680 940.2 1,120.8 1,227.0 1,444.8 1,708.8 1,883.4 2,092.8 2,259.0 2,436.6 2,634.6 2,769.0 2,961.0 3,090.0 3,225.0 3,405.6 3,631.8 3,781.2 3,927.6 4,076.4 34 93.7 75.2
47 96.6 76.2
54
49
96.7 78.2
96.9 77.8
39 97.3 78.2
°CDB °CDB kg 1
52
47
168.3mm Hz / V
45
52
46
49
Single pass shell and tube 97.8 98.9 99.8 100.4 100.8 101.2 78.7 79.8 80.7 80.4 80.8 81.2 Semi-hermetic single screw compressor -8~15 25~60 R-134a 5 Electronic expansion valve 2
41 103 83
51
55
59
100.4 100.8 101.2 80.4 80.8 81.2
63 103 83
3 219.1mm
3~ / 50 / 400
244 2515_BOOK_AppliedSystems_2011.indb 244
25/03/2011 08:38
D.I.C.N.
Daikin Integrated Chiller Network
Applicable series: • EWAQ080-260DAYN (R-410A) • EWYQ080-250DAYN (R-410A) • EWWD120-540MBYN (R-134a) • EWLD120-540MBYN (R-134a)
Daikin chillers can be equipped with DICN which allows the simultaneous operation of up to 4 chillers as if they were a single unit, in order to deliver the required cooling capacity. This results in precise and efficient capacity control and is also useful for back up purposes, ensuring that the necessary amount of cooling is available and guaranteeing reliable operation of the chiller plant. This function enables a Daikin 2MW chiller plant to be operated via a single controller. Please note that DICN is only possible within the same series.
245 2515_BOOK_AppliedSystems_2011.indb 245
25/03/2011 08:38
Hydraulic Module
EHMC
Hydraulic module
EHMC10-15-30AV1010
mH2O 55 50 45
• • • • • •
3 models available 100 l tank for all sizes Freeze up protection High static pump (option) Standard drain kit (for indoor use) Standard dual pressure ports (before & behind the pump)
40 35
LEGENDS 30
Pump characteristics 1. EHMC30AV1080 2. EHMC10AV1080 & EHMC15AV1080 3. EHMC30AV1010 4. EHMC10AV1010 & EHMC15AV1010
25 20 15
Hydraulic module + filter pressures losses 5. EHMC15/30AV1010 & EHMC15/30AV1080 6. EHMC10AV1010 & EHMC10AV1080
10 5 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 WF (l/min)
Water flow
HYDRAULIC MODULE 10
EHMC-AV Nominal flow Nominal static height Nominal input Dimensions (HxWxD) Machine weight Sound power Sound pressure Power supply Operation range Piping connections
1010
Water side Air side Water inlet/outlet Drain connection
l/min mH2O W mm kg dBA dBA V1 °C °CDB
15 1080
1010
62 17 630
1010
88 34 1,050
15 650
101
102
1,284x635x688 99
30 1080 27 1,070
10 1,070
104
105
1,284x635x688
63 52
27 2,090 1,284x635x688
63 52
111 63 52
1~/230V/50Hz -10°C ~ 55°C -10°C ~ 43°C 2" BSPF 1/2"
1" BSPF
1080 187
2-1/2" BSPF
BUFFER TANK Description
Volume
Dimensions
Unit weight
Buffer tank with cabinet
200l
1,284x637x754
86.5
EKBT500N
Buffer tank
500l
710x1,670
70
EKBTC10N
Buffer tank
1,000l
860x2,020
100
EKBT500C
Buffer tank with cabinet
500l
1,200x1,200x1,950
160
EKBTC10C
Buffer tank with cabinet
1,000l
1,200x1,450x1,950
185
MODEL EKBT
246 2515_BOOK_AppliedSystems_2011.indb 246
25/03/2011 08:38
2515_BOOK_AppliedSystems_2011.indb 247
25/03/2011 08:38
Fan coil units Fan coil units are a highly efficient means of turning a water chiller, heat pump or hot water boiler into an efficient, quiet air conditioning system.
These units are an effective solution to provide a comfortable environment for both commercial and residential applications. Daikin offers a wide range of fan coil units for both concealed and exposed applications.
3 models are available in flexible application. The only moving part in the units is the fan, making them ideal for use in offices, hotels and at home. The goal is to obtain the right solution, both technically and aesthetically.
1. Fan coil units
Controllers
249
2. Floor standing unit
FWV-DT/DF
250
3. Flexi type units
FWL-DT/DF FWM-DT/DF FWD-AT/AF
251 252 253
4. Wall mounted unit
FWT-BT
254
5. Concealed ceiling units
FWB-BT
255
6. Cassette units new
new
FWC-BT/BF FWF-BT/BF
256 257
For a copy of our latest Price List please call 0845 6419000
248 FanCoilSubContents.indd 248
29/03/2011 18:52
Fan coil unit Controllers
The fan coil units can be operated by different controllers according to the model.
ECFWMB6
FWEC1AA/FWEC2AA/FWEC3AA
Electronic controller FWEC1AA • Control of on-off valves for two or four pipes systems • Control of auxiliary heating element • Cooling/heating switching in the following modes: local or remote manual (centralised), automatic (depending on water temperature (optional) or air temperature) • Possibility, by means of clean contacts, of remote centralised cooling/heating switching and external activation • Temperature sensor kit (accessory FWTSKAA) • Economy function (setpoint correction by 2.5°C and forcing of the fan to run at minimum available speed) • Composed by: - lc display - keyboard • On board and wall mounted installation
EPIMSA6/EPIA6
Electromechanical built-in controller ECFWMB6 • Fan speed selector • Manual cooling/heating changeover • ON / OFF valves can also be controlled with ECFWMB6 Master / slave interface EPIMSA6 • Available as an additional interface, which is required for units with a current greater than 1.12A • Optional for remote control of up to 4 fan coil units • Up to 3 Master / Slave interfaces can be connected in parallel, enabling control over up to 12 fan coil units
FWEC2AA same as FWEC1AA with following additional functions: 1) Humidity management: - display of relative humidity - dehumidification function (cooling mode) Manual activation 2) Serial communication interface (RS485 bus) - possibility to set up a masterslave system up to 247 slave units, in which one of the controls plays the role of master and manages all the other slave units (modbus protocol) FWEC3AA same as FWEC2AA with following additional functions: 1) Back light
Power interface EPIA6 • Available as an additional interface, which is required for units with a current greater than 1.12A • Required for connection of ECFWER6 to FWD12-18 • Can be used as an alternative for Master / Slave interface
2) Proportional valve control (two voltage outputs for the proportional valves) 3) Voltage contact 0-10V (same as 2) 4) Time clock and weekly schedule (on / off or setpoint air) 5) Integration in BMS (already included in the FWEC2AA version) 6) Two digital outputs (voltage free) to manage electric heaters with the weekly schedule
MERCA
Standard wired remote controller • • • • • • • • • •
Fan speed Sleep function Swing Temperature setting Operating mode LCD display ON / OFF switch Real time clock Timer active Timer ON / OFF
SRC-COB/HPB
WRC-COB/HPB
Simplified wired remote controller for cooling only & heat pump
Wireless controller for cooling only & heat pump
• • • • • • • •
• • • • • • • • • •
Temperature display Temperature setting Timer switch setting ON / OFF switch Fan speed Operating mode Swing 'Sleep' function
LCD display Temperature setting Operating mode Timer switch setting Turbo mode Swing 'Sleep' function Real time clock ON / OF switch Fan speed
249 2515_BOOK_FanCoilUnits_2011.indb 249
21/03/2011 19:45
FWV-DT/DF
Floor standing unit
FWV01, 02DT/DF
FWEC1, 2, 3A
ECFWMB6
• Low sound power levels and electrical absorption thanks to plastic impeller, ABS winding staircase and improved electric motor • Quick fixing system for wall mounted installation • Pre-assembled 3-way/4-port ON/OFF valves are available • Valve packages are insulated, no extra drain pan required • Valve packages contain balancing valves and sensor pocket • Fast-on connections for electrical options: no tools needed • Quick removal of washable filter • Electric heater: no relay up to 2kW capacity • Electronic controller with water probe, available in standard, advanced and advanced plus version
Indoor units Cooling capacity Heating capacity Power input Dimensions Weight Heat exchanger Additional heat exchanger Water flow
Total capacity Sensible capacity 2-Pipe 4-Pipe High Unit
High High High High HeightxWidthxDepth
Unit Water volume Water volume
Cooling Heating Water pressure drop Cooling Heating Fan Type Air flow rate High Sound power level High Piping connections Drain OD Water connections Std. heat exchanger Power supply Phase / Frequency / Voltage Current input High
kW kW kW kW W mm
01 1.54 1.20 2.14
02 2.09 1.51 2.57
37 53 564x774x226
03 2.93 2.11 3.81 56 564x984 x226
2-PIPE 04 4.33 3.15 5.63 -
98 564x1,194x226
kg l l
19 0.5
20 0.7
25 1
30
l/h l/h kPa kPa
265 265
359 359
504 504 11
745 745 12
m³/h dBA mm inch Hz / V A
06 4.77 3.65 6.36
31 1.4
08 6.71 4.91 7.83
10 8.02 5.96 10.03
137 175 564x1,404x251 41 2.1
01 1.46 1.14
02 1.90 1.51
03 2.87 2.07
1.90 2.10 37 53 564x774x226
3.08 56
20 0.5
820 1,154 1,343 820 1,154 1,343 13 14 12 19 9 11 9 10 9 16 Centrifugal multi-blade, double suction 319 344 442 706 785 1,011 1,393 45 50 47 52 56 58 64 16 1/2 3/4 1 / 50 / 230 0.17 0.24 0.25 0.44 0.43 0.60 0.76
21 0.7 0.2
251 196
564x984 x226 26 1 0.3
4-PIPE 04 4.33 3.15 5.05
06 4.67 3.57
5.30 98 564x1,194x226 32
33
08 6.64 4.85
10 7.88 5.85
7.91 9.30 137 175 564x1,404x251
1.4
44 2.1
0.4
0.6
327 182
494 745 803 1,142 1,355 286 396 465 694 816 13 11 12 14 12 19 7 8 5 10 8 9 Centrifugal multi-blade, double suction 307 327 431 690 763 998 1,362 45 50 47 52 56 58 64 16 1/2 3/4 1 / 50 / 230 0.17 0.24 0.25 0.44 0.43 0.60 0.76
250 2515_BOOK_FanCoilUnits_2011.indb 250
21/03/2011 19:45
FWL-DT/DF Flexi type unit
FWL03DT/DF
FWL03DT/DF
ECFWMB6
FWEC1, 2, 3A
• Low sound power levels and electrical absorption thanks to plastic impeller, ABS winding staircase and improved electric motor • Quick fixing system for wall or ceiling mounted installation • Pre-assembled 3-way/4-port ON/OFF valves are available • Valve packages are insulated, no extra drain pan required • Valve packages contain balancing valves and sensor pocket • Fast-on connections for electrical options: no tools needed • Quick removal of washable filter • Electric heater: no relay up to 2kW capacity • Electronic controller with water probe, available in standard, advanced and advanced plus version
Indoor units Cooling capacity Heating capacity Power input Dimensions Weight Heat exchanger Additional heat exchanger Water flow Water pressure drop Fan Sound power level Water connections Power supply Current input
Total capacity Sensible capacity 2-Pipe 4-Pipe High Unit
High High High High HeightxWidthxDepth
kW kW kW kW W mm
01 1.54 1.20 2.14
02 2.09 1.51 2.57
37 53 564x774x226
03 2.93 2.11 3.81 56 564x984 x226
2-PIPE 04 4.33 3.15 5.63 -
98 564x1,194x226
Unit Water volume Water volume
kg l l
20 0.5
21 0.7
27 1
32
Cooling Heating Cooling Heating Type Air flow rate High High Std. heat exchanger Phase / Frequency / Voltage High
l/h l/h kPa kPa
265 265
359 359
504 504 11
745 745 12
m³/h dBA inch Hz / V A
06 4.77 3.65 6.36
33 1.4
08 6.71 4.91 7.83
10 8.02 5.96 10.03
137 175 564x1,404x251 44 2.1
01 1.46 1.14
02 1.90 1.51
03 2.87 2.07
1.90 2.10 37 53 564x774x226
3.08 56
21 0.5
820 1,154 1,343 820 1,154 1,343 13 14 12 19 9 11 9 10 9 16 Centrifugal multi-blade, double suction 319 344 442 706 785 1,011 1,393 45 50 47 52 56 58 64 1/2 3/4 1 / 50 / 230 0.17 0.24 0.25 0.44 0.43 0.60 0.76
22 0.7 0.2
251 196
564x984 x226 28 1 0.3
4-PIPE 04 4.33 3.15 5.05
06 4.67 3.57
5.30 98 564x1,194x226 34
35
08 6.64 4.85
10 7.88 5.85
7.91 9.30 137 175 564x1,404x251
1.4
46 2.1
0.4
0.6
327 182
494 745 803 1,142 1,355 286 396 465 694 816 13 11 12 14 12 19 7 8 5 10 8 9 Centrifugal multi-blade, double suction 307 327 431 690 763 998 1,362 45 50 47 52 56 58 64 1/2 3/4 1 / 50 / 230 0.17 0.24 0.25 0.44 0.43 0.60 0.76
251 2515_BOOK_FanCoilUnits_2011.indb 251
21/03/2011 19:45
FWM-DT/DF Flexi type unit
FWM01, 02DT/DF
FWEC1, 2, 3A
FWM01, 02DT/DF
• Low sound power levels and electrical absorption thanks to plastic impeller, ABS winding staircase and improved electric motor • Quick fixing system for wall or ceiling mounted installation • Pre-assembled 3-way/4-port ON/OFF valves are available • Valve packages are insulated, no extra drain pan required • Valve packages contain balancing valves and sensor pocket • Fast-on connections for electrical options: no tools needed • Quick removal of washable filter • Electric heater: no relay up to 2kW capacity • Electronic controller with water probe, available in standard, advanced and advanced plus version
Indoor units Cooling capacity Heating capacity Power input Dimensions Weight Heat exchanger Additional heat exchanger Water flow Water pressure drop Fan Sound power level Piping connections Water connections Power supply Current input
Total capacity Sensible capacity 2-Pipe 4-Pipe High Unit Unit Water volume Water volume
High High High High HeightxWidthxDepth
Cooling Heating Cooling Heating Type Air flow rate High High Drain OD Std. heat exchanger Phase / Frequency / Voltage High
kW kW kW kW W mm kg l l
01 1.54 1.20 2.14
02 2.09 1.51 2.57
37 53 535x584x224 14 15 0.5 0.7
03 2.93 2.11 3.81 56 535x794x224 19 1
2-PIPE 04 4.33 3.15 5.63 -
06 4.77 3.65 6.36
98 535x1,004x224 23 1.4
08 6.71 4.91 7.83
10 8.02 5.96 10.03
137 175 535x1,214x249 32 2.1
01 1.46 1.14
265 265
359 359
9
11
m³/h dBA mm inch Hz / V A
319 45
344 50
0.17
0.24
13
504 504 11
745 745 12
820 1,154 1,343 820 1,154 1,343 14 12 19 9 10 9 16 Centrifugal multi-blade, double suction 442 706 785 1,011 1,393 47 52 56 58 64 17 1/2 3/4 1~ / 50 / 230 0.25 0.44 0.43 0.60 0.76
03 2.87 2.07
1.90 2.10 37 53 535x584x224 15 16 0.5 0.7
3.08 56 535x794x224 20 1
0.2
0.3
-
l/h l/h kPa kPa
02 1.90 1.51
251 196
4-PIPE 04 4.33 3.15 5.05
06 4.67 3.57
08 6.64 4.85
10 7.88 5.85
5.30 98 535x1,004x224 25 1.4
7.91 9.30 137 175 535x1,214x249 34 2.1
0.4
0.6
327 182
494 745 803 1,142 1,355 286 396 465 694 816 13 11 12 14 12 19 7 8 5 10 8 9 Centrifugal multi-blade, double suction 307 327 431 690 763 998 1,362 45 50 47 52 56 58 64 17 1/2 3/4 1~ / 50 / 230 0.17 0.24 0.25 0.44 0.43 0.60 0.76
252 2515_BOOK_FanCoilUnits_2011.indb 252
21/03/2011 19:45
FWD-AT/AF
Flexi type unit
FWD04AT/AF
FWD04AT/AF
FWEC1,2,3A
• Quick fixing system for wall or ceiling mounted installation • Straight duct connector is mounted to discharge side • Electronic controller with water probe, available in standard, advanced and advanced plus version • The air filter can easily be removed for cleaning
Indoor units Cooling capacity Heating capacity Power input Dimensions Weight Heat exchanger Additional heat exchanger Water flow Water pressure drop Fan
Sound power level Piping connections Water connections Power supply Current input
Total capacity Sensible capacity 2-Pipe 4-Pipe High Unit Unit Water volume Water volume
High High High High
kW kW kW kW W HeightxWidthxDepth mm kg l l
Cooling Heating Cooling Heating Type Air flow rate High Available pressure High High Drain OD Std. heat exchanger Phase / Frequency / Voltage High
04 3.90 3.08 4.05
06 6.20 4.65 7.71
234 349 280x754x559 280x964x559 33 41 1.06 1.42
2-PIPE 10 12 8.82 11.90 7.16 9.36 10.79 14.45 443 714 280x1,174x559 352x1,174x718 47 49 65 1.79 2.38 2.5 08 7.80 6.52 9.43
16 16.40 12.80 19.81
18 18.30 14.10 21.92
1,197 352x1,384x718 77 80 4.02 5.03
-
l/h l/h kPa kPa
674 674 17 14
m³/h Pa dBA mm inch Hz / V A
800 66 66
0.95
1,064 1,064
1,339 1,339
1,514 2,056 2,833 3,140 1,514 2,056 2,833 3,140 24 16 26 34 45 20 13 21 28 37 Centrifugal multi-blade, double suction 1,250 1,600 2,200 3,000 58 68 64 97 145 134 69 72 74 78 16 3/4 1 1~ / 50 / 230 1.58 1.97 3.21 5.37
04 3.90 3.08
06 6.20 4.65
4.49 6.62 234 349 280x754x559 280x964x559 35 43 1.06 1.42 0.35
0.47
674 349 17 9
1,064 581
800 63 66
0.95
4-PIPE 10 12 8.82 11.90 7.16 9.36 9.21 15.86 443 714 280x1,174x559 352x1,174x718 50 52 71 1.79 2.38 2.50 08 7.80 6.52
0.59 1,339
1.42
16 16.40 12.80
18 18.30 14.10
21.15 1,197 352x1,384x718 83 86 4.02 5.03 1.72
1,514
2,056 2,833 3,140 808 1,392 1,856 24 16 26 34 45 15 13 12 16 Centrifugal multi-blade, double suction 1,250 1,600 2,200 3,000 53 63 59 92 138 128 69 72 74 78 16 3/4 1 1~ / 50 / 230 1.58 1.97 3.21 5.37
253 2515_BOOK_FanCoilUnits_2011.indb 253
21/03/2011 19:45
FWT-BT
Wall mounted unit
FWT05, 06BT
MERCA
SRC-COB/HPB
WRC-COB/HPB
• • • • • • • • • • •
Wide operating range Easy installation and maintenance 3-speed fan motor Double-intake centrifugal fans Excellent air flow and air distribution Flexibility via interchangeable water connection side High power air flow Insulated with self-extinguishing class 1 heat insulation Removable washable air filter (self-extinguishing class 1) Slim and compact aesthetic design Wireless remote control up to 9m distance, availability of a wired or simplified controller • LED indicator gives run and fault indication
Indoor units Cooling capacity Heating capacity Power input Dimensions Weight Heat exchanger Water flow Water pressure drop Fan Sound power level Sound pressure level Piping connections Water connections Power supply Current input
Total capacity High Sensible capacity High 2-Pipe High High Unit HeightxWidthxDepth Unit Operation weight Water volume Cooling Heating Cooling Heating Type Air flow rate High High High Drain OD Std. heat exchanger Phase / Frequency / Voltage High
kW kW kW W mm kg kg l l/h l/h kPa kPa m³/h dBA dBA mm inch Hz / V A
02 2.34 1.74 3.02 24 260x799x198 10 10 0.49 402 402 48.3 42
2-PIPE 04 3.22 2.35 4.10 29
03 2.78 2.03 3.75 25
05 4.54 3.65 6.01 66
260x899x198 12 13 0.57 478 478 64.7 58.6
467
510 53
40
39 16
0.11
554 554 69.3 60.6 Centrifugal-direct driven fan motor 586 55 42
06 5.28 4.33 6.74 69 304x1,062x222 16 17 0.85
781 781 50.3 50.6
908 908 69.3 70.6
1,070 61 49
1,121 64 50 20
1/2 1~ / 50 / 220-240 0.13
0.29
0.30
254 2515_BOOK_FanCoilUnits_2011.indb 254
21/03/2011 19:45
FWB-BT
Concealed ceiling unit
FWB04BT
FWEC1, 2, 3A
• Low sound power levels and electrical absorption thanks to plastic impeller, ABS winding staircase and improved electric motor • Compact dimensions, can easily be mounted in a narrow ceiling void 3, 4 or 6 stage row cooling coil • Drain pan to collect the condensate from: heat exchanger and regulating valves • 7-speed electrical motors (with thermal protection on windings) • All 7 speeds pre-wired in the factory in the terminal block of the switch box • The air filter can easily be removed for cleaning
Indoor units Cooling capacity Heating capacity Power input Dimensions Weight Heat exchanger Additional heat exchanger Water flow
Water pressure drop
Fan
Sound power level Sound pressure level Piping connections Water connections Power supply Current input
Total capacity Sensible capacity 2-Pipe 4-Pipe High Unit Unit Operation weight Water volume Water volume
High High High High
kW kW kW kW W HeightxWidthxDepth mm kg kg l l
Cooling Heating Additional heat exchanger Cooling Heating Additional heat exchanger Type Air flow rate High Available pressure High High High Drain OD Std. heat exchanger Add. heat exchanger Phase / Frequency / Voltage High
l/h l/h l/h kPa kPa kPa m³/h Pa dBA dBA mm inch inch Hz / V A
02 2.61 1.88 5.47
23 24 1.1
03 3.14 2.16 6.01 3.14 79 239x1,039x609 24 26 1.5
04 3.49 2.34 6.47
05 5.08 3.6 10.31
26 28 2.2
31 33 1.6
598 567
873 904
0.4 448 480 8 7
539 527 275 14 10 3
2-PIPE 06 5.45 3.87 11.39 5.99 154 239x1,389x609 33 35 2.1
07 6.47 4.4 12.28
08 7.57 5.23 15.05
35 38 3.2
43 45 2.1
09 8.67 5.96 16.85 12.8 294 239x1,739x609 45 48 2.8
0.6
11 8
400 71 56 44.5
0.36
936 1,111 1,299 999 1,077 1,319 526 15 8 14 12 7 10 16 5 Centrifugal - forward blades - directly coupled on fan motor 800 65 59 47.5 16 3/4 3/4 1~ / 50 / 230 0.73
10 10.34 6.9 18.78
48 52 4.2
1.7 1,488 1,479 1,123 21 15 8
1,774 1,647 26 18
1,200 59 69 57.5
1 1.28
255 2515_BOOK_FanCoilUnits_2011.indb 255
21/03/2011 19:45
FWC-BT/BF Round flow cassette
FWC-BT/BF
BRC315D7
BRC7E532/3
• 360° air discharge ensures uniform air flow and temperature distribution • DC Fan motor: Low Power input • Modern stylish decoration panel in white (RAL9010) • Fresh air intake kit available • Comfortable horizontal air discharge ensures draught free operation and prevents ceiling soiling • Possibility to close 1 or 2 flaps for different air flow patterns Examples of air flow patterns possible
• Drain pump standard mounted (lift: 850mm)
850 mm
Indoor units Cooling capacity Heating capacity Power input Dimensions Water pressure drop Fan Sound power level Sound pressure level Piping connections Power supply
2-PIPE Total capacity High 2-Pipe High 4-Pipe High High Unit HeightxWidthxDepth Cooling Heating Type Air flow rate High High High Drain OD Phase / Frequency / Voltage
kW kW kW kW mm kPa
m³/h dBA dBA mm Hz / V
06 6.0 8.0
07 7.0 8.9
4-PIPE 08 8.0 10.6
09 9.0 12.1
29
40
19 19
22 22
06 6.0
07 6.7 8.4 40 25 20
09 8.9
9.7 64
11.0 93
32 27
41 34
-
65
94
7.5 28
29 29
35 35
20 17
30.8 59 44
17.1 43 29
288x840x840
17.7 46 30
08 7.8
288x840x840
Turbo fan 20.6 25.4 49 55 34 39 VP25 (external dia. 32, internal dia. 25) 1~ / 50 / 220-240
Turbo fan 19.9 24.6 47 53 33 39 VP25 (external dia. 32, internal dia. 25) 1~ / 50 / 220-240
29.0 57 43
* Note: grey cells contain preliminary data
256 2515_BOOK_FanCoilUnits_2011.indb 256
21/03/2011 19:45
FWF-BT/BF
4-way blow ceiling mounted cassette
FWF-BT/BF
BRC315D7
BRC7E530/1
• Extremely compact casing (575mm in width and depth) enables unit to fit flush into ceilings and match standard architectural modules, without cutting ceiling tiles • Modern stylish decoration panel in white (RAL9010) • Comfortable horizontal air discharge ensures draught free operation and prevents ceiling soiling
• Possibility to close 1 or 2 flaps for different air flow patterns Examples of air flow patterns possible 2-way blow
4-way blow
3-way blow
• Drain pump standard mounted (lift: 750mm)
Indoor units Cooling capacity Heating capacity Power input Dimensions Water pressure drop Fan Sound power level Sound pressure level Piping connections Power supply
2-PIPE Total capacity High 2-Pipe High 4-Pipe High High Unit HeightxWidthxDepth Cooling Heating Type Air flow rate High High High Drain OD Phase / Frequency / Voltage
kW kW kW kW mm kPa
m³/h dBA dBA mm Hz / V
02 2.0 2.9
03 3.2 4.0
4-PIPE 04 4.2 5.4
05 5.4 6.9
66
66
5 5
18 18
02 2.0
03 2.7 3.8 62 13 5
05 4.5
4.9 86
6.1 117
21 9
33 13
-
89
116
3.9 66
29 29
46 46
5 11
14.9 55 42
7.9 44 27
260x575x575
7.9 44 27
04 3.5
260x575x575
Turbo fan 7.9 11.2 44 50 27 35 VP20 (external dia. 26, internal dia. 20) 1~ / 50 / 220-240
Turbo fan 7.2 10.4 46 52 31 36 VP20 (external dia. 26, internal dia. 20) 1~ / 50 / 220-240
13.9 57 41
* Note: grey cells contain preliminary data
257 2515_BOOK_FanCoilUnits_2011.indb 257
21/03/2011 19:45
Air purifiers Allergens are impurities in the air that can bring on an allergic reaction. In an urban environment, a mixture of these allergens with other impurities present in the air can turn allergens into heavy allergens. These in turn can have increased negative health effects such as aggravated symptoms and the triggering of latent allergies.
Daikin’s latest air purifier model, the MC707, is the result of many years of investment in innovation at the service of the customer’s well-being. These efforts place the MC707 among the best residential air purifiers on the market today. Besides a number of practical features, the MC707 owes its enhanced performance to an advanced 7-layer filtering system, the product of Daikin’s continuous drive for innovation and efficiency.
The unique Flash Streamer technology decomposes chemical substances such as odours and formaldehyde into harmless byproducts. It also promotes a photocatalytic reaction on the surface of the Titanium Apatite Photocatalytic Filter that removes bacteria and viruses. Daikin has already received great praise for its air purifiers. A UK Allergy Certificate and the Daikin TüV Award confirm the efficiency of our units.
Photocatalytic air purifier MC707VM-S
259
For a copy of our latest Price List please call 0845 6419000
258 2515_BOOK_AirPurifier_2011.indb 258
23/03/2011 11:47
Photocatalytic air purifier MC707VM-S
MC707VM-S
Pure air for free and healthy breathing • Stylish design • Improved performance • Unprecedented comfort • Super quiet operation • Easy to maintain • Portable • No installation
Three times purification, a good deed for your health Pollen, dust and pet hair are just some of the potential causes of allergies, asthma and respiratory problems. A Daikin air purifier cleans the air and relieves you of these troubles thanks to a three-part operation: • Allergen removal • Virus and bacteria removal • Odour removal
Flash Streamer unit
Pre-filter (with catechin*) Removes large dust particles and pet hairs.
Bio-Antibody Filter Airborne viruses are captured and removed.
Plasma Ionizer Dust and pollen are positively charged and sent to the Electrostatic Filter.
Flash Streamer High-speed electrons are generated by the Flash Streamer. These electrons powerfully break down odours and formaldehyde.
Deodorising Catalyst Odours are adsorbed and broken down before the air is returned to the room.
Electrostatic Dust Collection Filter (front) Positively charged dust and pollen are adsorbed by the negatively charged filter.
*
polluted air
>
>
>
>
>
PLEATED FILTER
>
>
purified air
Titanium Apatite Photocatalytic Filter (back) Odour, bacteria and viruses are adsorbed and decomposed. * Catechin is a natural anti-bacterial substance derived from tea leaves that kills germs that can attach to these particles.
* The filtering surface of a pleated filter is approximately 1.5 times larger than that of a conventional flat filter.
MC707VM-S Model Power supply Dimensions Colour Weight Mode (50Hz) Power input Sound pressure level Sound power level Air flow rate Dust collecting method Deodorising
Bacteria filtering method Filter
HxWxD
mm Kg kW dB(A) dB(A) m3/h
Method Deodorising performance (%) Regenerate method Dust collection and deodorisation
Form Function Lifetime Bio-Antibody filter Pre-filter
Turbo 0.055 47 62 420
MC707VM-S 1~, 220-240/220-230V, 50/60Hz 533x425x213 Sparkling silver + metallic ocean blue 8.7 H M L 0.023 0.014 0.010 38 31 24 52 40 39 285 180 120 Plasma ionizer (electrostatic dust collection) + Electrostatic dust collection filter Flash Streamer + Titanium apatite photocatalytic filter + Deodorising catalyst 95 The Flash Streamer activates the photocatalytic reaction Bio-Antibody filter + Flash Streamer + Titanium apatite photocatalytic filter Pleated filter Deodorisation + disinfection + dust collection + adjuvant removal 1 filter/1 year New Catechin pre-filter
Silent 0.008 16 31 60
259 2515_BOOK_AirPurifier_2011.indb 259
23/03/2011 11:47
260 2515_BOOK_AirPurifier_2011.indb 260
23/03/2011 11:48
261 2515_BOOK_AirPurifier_2011.indb 261
23/03/2011 11:48
Foreword
Power supply
Daikin UK is a leading supplier of heating, cooling and refrigeration solutions for commercial, residential and industrial applications.
T1 = 3~, 220V, 50Hz V1 = 1~, 220-240V, 50Hz VE = 1~, 220-240V, 50Hz/60Hz V3 = 1~, 230V, 50Hz VM = 1~, 220~240V/220~230V, 50Hz/60Hz W1 = 3N~, 400V, 50Hz Y1 = 3~, 400V, 50Hz
Daikin – the leader in manufacturing quality and customer service Daikin was founded in 1924 in Osaka, Japan. The company we now know as Daikin Industries Ltd (DIL) is the parent company of Daikin Europe N.V. (DENV) which was established in Ostend, Belgium in 1972. Daikin Europe is continuously updating and expanding its manufacturing facilities, to a point where they are now acknowledged as the most advanced in their field in Europe. This is backed by zero defect production, efficient supply chain management and unrivalled research and development support from DIL. These substantial production facilities are underpinned by a network of wholly owned affiliate companies in the UK, France, Germany, Italy, Spain, Portugal, Poland, Greece, Belgium, Holland and Central Europe. There are also numerous independent distributors throughout Europe, Africa and the Middle East.
With more than 50 years experience in the production of heat pumps now manufacturing over a million units a year, Daikin has been at the forefront of the drive for energy efficient heat pump technology. The systems are manufactured entirely ‘in-house’ in Daikin’s state of the art factories – this includes the all important energy efficient inverter driven compressor unit. As one of many wholly owned affiliate companies, Daikin UK is a leading supplier of heating, cooling and refrigeration solutions for commercial, residential and industrial applications. Our product portfolio comprises a wide range of highly energy efficient climate control systems which provides the public and private sectors with the right product for any application and requirement.
• State of the art direct expansion air conditioning
Measuring conditions COOLING ONLY 1) nominal cooling capacities are based on: indoor temperature outdoor temperature refrigerant piping length level difference
27°CDB/19°CWB 35°CDB 7.5m 0m
HEAT PUMP 1) nominal cooling capacities are based on: indoor temperature outdoor temperature refrigerant piping length level difference 2) nominal heating capacities are based on: indoor temperature outdoor temperature refrigerant piping length level difference
27°CDB/19°CWB 35°CDB 7.5m 0m 20°CDB 7°CDB/6°CWB 7.5m 0m
CHILLERS: Air-cooled
• H eat pump residential and light commercial heating, domestic hot water and cooling
cooling only heat pump
Water-cooled
cooling only
• Applied central cooling and heating
Remote condenser
• Medium to low temperature refrigeration
heating only
Remote evaporator
cooling capacity/power input conditions
Fan coil units
cooling heating
evaporator: 12°C/7°C ambient: 35°C evaporator: 12°C/7°C ambient: 35°C condenser: 40°C/45°C ambient: 7°CDB/6°CWB evaporator: 12°C/7°C condenser: 30°C/35°C evaporator: 12°C/7°C condenser: 40°C/45°C evaporator: 12°C/7°C condensing temperature: 45°C / liquid temperature: 40°C suction dew point: 5°C ambient: 35°C superheat: 10°C room temperature: 27°C/19°C entering water temperature: 7°C/12°C room temperature: 20°C water inlet temperature: 50°C (2-pipe) / 70°C (4-pipe)
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment (for measuring conditions: please refer to the technical databooks). The sound power level is an absolute value indicating the ‘power’ which a sound source generates. For more detailed information please consult our technical databooks.
1 2515ProductCatCover_2011_artwork.indd 2
262 28/03/2011 18:39
Daikin UK Product Catalogue 2011
your comfort. our world.
Head Office Daikin Airconditioning UK Limited The Heights, Brooklands, Weybridge, Surrey KT13 0NY Tel 0845 6419000 Fax 0845 6419009
www.daikin.co.uk Unique solutions for every environment
FSC Carbon Balanced Paper
Visit www.eca.gov.uk/etl and type â&#x20AC;&#x2DC;Daikinâ&#x20AC;&#x2122; in the quick search box for details of the latest ECA qualifying Daikin units Daikin units comply with the European regulations that guarantee the safety of the product.
The present catalogue is drawn up by way of information only and does not constitute an offer binding upon Daikin UK. Daikin UK has compiled the content of this catalogue to the best of its knowledge. No express or implied warranty is given particular purpose of its content and the products and services
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory. Multi units are Eurovent certified for combinations up to 2 indoor units. VRV products, Rooftops, FWB-J and FWD-units are not within the scope of the Eurovent Certification Programme.
presented therein. Specifications are subject to change without prior notice. Daikin UK explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this catalogue. All content is copyrighted by Daikin UK.
Unique solutions for every environment www.daikin.co.uk
for the completeness, accuracy, reliability or fitness for
UKEPCEN11-500 / 04.11 / DesignHQ. Copyright 2011 Daikin The present publication supersedes UKEPCEN10-500 Printed in the UK on FSC certified paper from sustainable sources.
Daikin UK is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin UK Product Catalogue 2011