2 012 - 2 013
SYSTEMS WITH MAINTAINED FUNCTIONALIT Y IN FIRE
Dear costumers, our new catalogue you are opening contains the offer of fire resistant systems by KOPOS KOLĂ?N a.s. Those types of products were firstly introduced on the market in year 2009. It is our pleasure, that our exertion was reward by a Czech quality certificate for cable trays range JUPITER and MARS. This reward means to us a lot more than just a piece of paper to be put in the frame on the wall or put into drawer. This reward obligates us to keep a high quality standard, improve the quality and bring to costumers sureness of top quality and uses of products. We may support this claim by a number of demanding and successfully performed tests. KOPOS KOLIN a.s. is also significant producer of electric installation materials made of plastic, as are boxes, trunkings, perimeter trunkings, pipes, cable duct protectors and many others including cable supporting systems. Costumers, who decide to choose KOPOS products have got guarantee to be never disappointed, because of our own designing, technical, construction office and qualified employees in production and business department. I believe that you will be always pleased with products of company KOPOS KOLIN. Ing. Josef Vavrouch General director
F I R E R E S I S TA N T S Y S T E M S 1
Cable supporting systems maintaining functionality in fire STANDARD CONSTRUCTIONS
NON-STANDARD CONSTRUCTIONS
The company KOPOS KOLÍN a.s. (joint-stock company) produces fire resistant systems conforming to the respective standards and regulations. They include cable trays JUPITER KZ of 1.5 mm thickness sheet steel and cable ladders KL with cross-pieces with the distance of 150 mm. page: 4-33
In its effort to oblige its customers in terms of pricing, KOPOS Kolín a.s. offers reasonably priced fire resistant systems. It is possible to reduce the price of fire resistant routes using a metal sheet of a thickness less than the one determined by the standard and applying a more sophisticated solution of the cable tray shape and the system of anchoring. The standard allows testing these routes which are then identified as not standardized (non standard).
standard routes:
cable trays cable ladders independent cable clamps
cable trays: - maximum allowable width 300 mm (perforation percentage 15 ± 5 %) - sidewall height 60 mm - thickness of metal sheet 1.5 mm - weight of cables max. 10 kg/m - distance of supports 1 200 mm cable ladders: - maximum width 400 mm - sidewall height 60 mm - thickness of metal sheet 1.5 mm - weight of cables max. 20 kg/m - ladder cross-pieces at a distance of 150 mm - distance of supports max. 1200 mm
The non standard routes include routes created by MARS and JUPITER cable trays with integrated couplings with the metal sheet thickness of 1.25 mm, and routes of cable ladders with the distance of cross-pieces 300 mm; further there are supporting metal trunkings and routes created by steel pipes. page: 34-81 not standardized routes:
trays with integrated couplings with metal sheet thickness of 1.25 mm cable ladders with the distance of cross-pieces of 300 mm supporting trunkings steel pipes
The system includes systems that have been tested in their entirety.
Cable ladder and tray routes are not provided with covers. independent cable clamps - distance 300 mm Installed cable requirements Cables with proven maintenance of operability in fire from the manufacturer with whom the particular line was tested must be used in the systems.
Cables with proven maintenance of operability in fire from any manufacturer may be used in the systems. This characteristic is convenient for both the realization of the system and when extending systems in the course of operation. It does not limit the investors of implementation companies by having to purchase cables from a particular manufacturer.
Tests and classification KOPOS cable supporting system has complied with the tests according to the achieved time of maintained operability as follows: ZP 27/2008 DIN 4102 part 12 and STN 92 0205 with action according to the standardized time temperature curve and is classified in terms of fire resistance as follows: P 120-R by ZP 27/2008 P 90-R by ZP 27/2008 P 60-R by ZP 27/2008 P30-R by ZP 27/2008 E 90 by DIN 4102 part 12 E 90 by DIN 4102 part 12 E 60 by DIN 4102 part 12 E 30 by DIN 4102 part 12 PS 90 by STN 92 0205 PS 90 by STN 92 0205 PS 60 by STN 92 0205 PS 30 by STN 92 0205 The data on resistance of the system are stated for particular assemblies and are defined in the cables chart. Temperature scenarios The results of tests obtained during testing of cable routes at increased temperature also apply to cable routes stressed by low temperatures (e.g. if the cable line is classified by operability class P, the classification also applies to operability class PH). Therefore, the systems we produce may be used even for resistance class PH 120, PH 90, PH 60 and PH 30 while observing other conditions. Surface finish Systems may be supplied with various surface finishes (coating, galvanizing) whereas the surface finish does not affect the determined maintained time of operability in fire. Special environment: subway and tunnels Part of the cable supporting system KOPOS conformed to the requirements of the test carried out in accordance with ZP 27/2008 with acting in accordance with the curve with the constant temperature of 750°C for the period of 120 minutes with inclination of 16 minutes and its fire resistance classification is as follows: ZP 27/2008 750°C/120/136-R. The system includes: cable trays JUPITER, cable ladders, steel pipes and other material In the case of interest in technical specification of systems for Prague subway, please turn to our business representatives. The contact details are available at www.kopos.com. This catalogue describes in detail installation of individual routes, use of accessories, installation elements, and application of power and data cables resistant to fire. For proper mounting KOPOS KOLÍN a.s., as a producer, recommends to abide by the instructions for installation included in the catalogue. The producer shall not be liable for any damages caused by fire in case of non-observance of the installation instructions.
2
F I R E R E S I S TA N T S Y S T E M S
Cable trays
STANDARDIZED SUPPORTING CONSTRUCTIONS
NOT STANDARDIZED SUPPORTING CONSTRUCTIONS
system for ceiling with use of ceiling profiles and threaded rods
system for ceiling with use of threaded rods
page 38, 42, 43, 45, 50, 53, 54, 55 page 5
system for wall
system for ceiling with use of threaded rods page 37, 46, 47, 56 page 6
system for ceiling with use of ceiling profiles
system for wall
page 7 page 35, 36, 39, 40, 41, 48, 49, 51, 52
Electrical wiring boxes STANDARDIZED SUPPORTING CONSTRUCTIONS
wiring boxes
page 15, 16
F I R E R E S I S TA N T S Y S T E M S 3
Cable ladders
STANDARDIZED SUPPORTING CONSTRUCTIONS
NOT STANDARDIZED SUPPORTING CONSTRUCTIONS
system for ceiling with use of ceiling profiles and threaded rods
system for wall
page 58, 60 page 8
system for ceiling with use of threaded rods
page 59
system for ceiling with use of threaded rods
page 9
system for wall
page 10
ascending cable ladder
page 11
Other systems STANDARDIZED SUPPORTING CONSTRUCTIONS
NOT STANDARDIZED SUPPORTING CONSTRUCTIONS
independent cable clamps
steel pipes
page 61
supporting trunkings
page 62
page 13
clamp OMEGA
page 14
4
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
Connection of standardized fire resistant cable tray KZ – JUPITER
KZ NSM 6X10
KSBS
KZ
Connection of the cable tray KZ is carried out using the KSBS coupling and screws NSM 6X10 (pg. 28). The number of bolts depends on the type of the coupling KSBS (see pg. 17).
Connection of standardized fire resistant cable ladder KL
KL 60... PO NSM 6X10
KL 60... PO KPBSKL
Connection of the cable ladder is carried out using the KPBSKL coupling (pg. 18) and using 12 pieces of screws NSM 6X10 (pg. 28).
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 5
T
Cable trays JUPITER - KZ
10
system designated for mounting to the ceiling with a ceiling profile SPL SPL
possible types of anchoring:
KPO 10
VS 41X16
KPO 10 MZ 10
M 10
ZT 10
KZ
KPOZ
KPO10 VS 41x16 MZ 10 M 10
0
. 120
max
M 10 PD 10 MZ 10 DTBS
KSBS NSM KPO 10 VS 41X16 MZ 10 M 10
S 10X50
ZT 10
Fire resistance classification: for power cables: P 90-R E 90 PS 90
SPL DTBS
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205
PD 10 M 10
Technical parameters of routes: spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
max. 1200 mm 10 kg 3 60 mm 50; 75; 100; 150; 200; 300 mm 1,5 mm
List of products for one mounting point: page DTBS
1
2
3
2
4
6
25
SPL
1
1
1
1
1
1
25
KPO 10
4+1*
4+1*
4
4+2*
4+2*
4+2*
31
Description of the system:
KPO 12
-
-
1*
-
-
2*
31
The base of the supporting construction is the SPL ceiling profile anchored by the anchors KPO 10. The system includes the heavy holder DTBS mounted using two bolts S 10X40, 2 pieces of nuts M 10, and 2 pieces of washers PD 10 to the ceiling profile. The heavy bracket must be fixed using threaded rod ZT 10 and at the same time the assembly accessory VS 41X16 (KPOZ 10) in the ceiling construction to secure so that the line conforms to the preconditions of fire resistance. For installation of 3 successive routes it is necessary to use the threaded rod ZT 12, nuts M 12 and MZ 12, and the washer PD 12. The distance between the individual ceiling profiles must be max. 1200 mm. The cable tray KZ is fixed to the bracket DTBS using screws NSM 6X10. This system allows hanging of not more than three routes of cable trays. The method of anchoring of a threaded rod using KPOZ anchor equals the use of VS 41X16 support part and is regarded as a standardized method of anchoring. The advantage of this system is possible dual-sided assembly of the bracket DTBS.
VS 41X16
2*
2*
2*
4*
4*
4*
26
M 10
3+1*
6+1*
6
4+2*
6+2*
6
29
PD 10
4
8
6
6
12
6
30
MZ 10
1+1*
2+1*
-
2+2*
4+2*
-
27
M 12
-
-
3+1*
-
-
6+2*
29
PD 12
-
-
6
-
-
12
30
MZ 12
-
-
3+1*
-
-
6+2*
27
S 10X40
2
4
6
-
-
-
29
S 10X50
-
-
-
2
4
6
29
ZT 10
1
1
-
2
2
-
27
ZT 12
-
-
1
-
-
2
27
NSM 6X10
2
4
6
4
8
12
28
Approved manufacturers of cables: For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire.
* marked number presents the products for suspension with VS 41X16. In the case of suspension using an anchor, this number is replaced by KPOZ anchor. KPOZ 10
1
1
-
2
2
-
31
KPOZ 12
-
-
1
-
-
2
31
6
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays JUPITER - KZ
10
system for ceiling with use of threaded rods and support profiles KPO 10
possible types of anchoring:
KZ
VS 41X16 MZ 10 M 10 ZT 10
KPOZ
KPO 10 VS 41x16 MZ 10 M 10
KSBS
NSM M 10 PD 10 PVL 10
MP 41X41
MZ 10 ZT 10 max.
1200
Fire resistance classification:
Technical parameters of routes:
for power cables: P 90-R E 90 PS 90
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205 Description of the system: The threaded rod ZT 10 is hanged using 2 pieces of support assembly accessories VS 41X16 and fire resistant anchors KPO 10 to the ceiling. The assembly profiles MP 41X41 are mounted on threaded rods from the upper part using the nut M 10. The bottom anchoring of the assembly profile is performed using the coupling nut MZ 10. This system is designed for a maximum of 2 routes above each other. The tray KZ is attached to the assembly profile using the bolt S 6X20 M and the washer PVL 6. The method of anchoring of a threaded rod using KPOZ anchor equals the use of VS 41X16 support part and is regarded as a standardized method of anchoring.
max. 1200 mm 10 kg 2 60 mm 50; 75; 100; 150; 200; 300 mm 1,5 mm
List of products for one mounting point: page MP 41X41
1
2
26
VS 41X16
4*
4*
26
KPO 10
2*
2*
31
M 10
2+2*
4+2*
29
MZ 10
2+2*
4+2*
27
Approved manufacturers of cables:
ZT 10
2
2
27
For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire.
PVL 10
2
4
30
PD 10
2
4
30
S 6X20 M
2
4
28
PVL 6
2
4
30
* marked number presents the products for suspension with VS 41X16. In the case of suspension using an anchor, this number is replaced by KPOZ anchor. KPOZ 10
2
2
27
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 7
Cable trays JUPITER - KZ
T
system for wall
10 VS 41X45
KPO 10 MZ 10
M 10
ZT 10
0
. 120
max
VS 41X45 KZ
M 10 PD 10 MZ 10
DTBS NSM KSBS
Fire resistance classification:
Technical parameters of routes:
for power cables: P 90-R E 90 PS 90
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205 Description of the system:
max. 1200 mm 10 kg 2 60 mm 50; 75; 100; 150; 200; 300 mm 1,5 mm
List of products for one mounting point:
The supporting structure is composed of the bracket DTBS anchored directly to the wall using fire resistant anchors KPO 10. The end of the bracket DTBS is fitted with a holder for the threaded rod ZT 10, which is secured from the top part of the bracket using the nut M 10. The bottom anchoring is performed using the nut MZ 10. This type of a construction enables a maximum of two routes above each other during which the top line must be attached to the wall using the threaded rod and two assembly accessories VS 41X45 at an angle of 45째. The span between individual DTBS brackets must be max. 1200 mm. The cable tray KZ is attached to the bracket DTBS using the screws NSM 6X10. In case of one line the assembly accessory VS 41X45 is attached to the holder at the end of the bracket DTBS using the bolt S 10X30, nut M 10, and washers PD 10. (see pic. A). Ends of securing threaded rods may be anchored into the ceiling instead of the wall. pic. A ZT 10 MZ 10 S 10X50 PD 10 M 10
Approved manufacturers of cables: For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire.
page DTBS
1
2
1
2
25
VS 41X45
2
2
-
-
26
KPO 10
3
5
3
5
31
ZT 10
1
2
1
2
27
M 10
3
4
1
2
29
S 10X50
1
-
-
-
29
MZ 10
3
4
1
1
27
PD 10
2
4
2
4
30
NSM 6X10
2
4
2
4
28
KPOZ 10
-
-
1
1
31
8
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable ladders - KL 60... PO
20
system designated for mounting to the ceiling with a ceiling profile SPL possible types of anchoring: KPO 10
KPO 10
VS 41X16 MZ 10
SPL
M 10
KPOZ
KPO 10 VS 41x16 MZ 10 M 10
KL 60... PO
ZT 10
M 10 PD 10 M 10 NSM 6X10 KPBSKL
200
x. 1
ma
KPO 10 VS 41X16
DTBS
MZ 10 S 10X50
M 10 ZT 10
Fire resistance classification: for power cables: P 90-R E 90 PS 90
SPL DTBS
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205
PD 10 M 10
Technical parameters of routes: spacing of hanging points maximum load on 1 m maximum number of successive routes sidewall height of the cable ladder width of cable ladders thickness of metal sheet of cable ladders
max. 1200 mm 20 kg 3 60 mm 150; 200; 300; 400 mm 1,5 mm
Description of the system: The base of the supporting construction is the SPL ceiling profile anchored by the KPO anchor. The system includes the heavy holder DTBS mounted using two bolts S 10X40, 2 pieces of nuts M 10, and 2 pieces of washers PD 10 to the ceiling profile. The heavy bracket must be fixed using threaded rod ZT 10 and at the same time the assembly accessory VS 41X16 (KPOZ) in the ceiling construction to secure so that the line conforms to the preconditions of fire resistance. For installation of 3 successive routes it is necessary to use the threaded rod ZT 12, nuts M 12 and MZ 12, and the washer PD 12. The distance between the individual ceiling profiles must be max. 1200 mm. The cable tray KZ is fixed to the bracket DTBS using screws NSM 6X10. Ladders KL 60... PO are attached to the bracket DTBS using screws NSM 6X10. This system allows hanging of not more than three routes of cable ladders. The method of anchoring of a threaded rod using KPOZ anchor equals the use of VS 41X16 support part and is regarded as a standardized method of anchoring. The advantage of this system is possible dual-sided assembly of the bracket DTBS. Approved manufacturers of cables: For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire.
List of products for one mounting point: page DTBS
1
2
3
2
4
6
25
SPL
1
1
1
1
1
1
25
KPO 10
4+1*
4+1*
4+1*
4+2*
4+2*
4+2*
31
KPO 12
-
-
1*
-
-
2*
31
2*
2*
2*
4*
4*
4*
26
M 10
4+1*
8+1*
6
6+2*
12+2*
6
29
PD 10
4
8
6
6
12
6
30
MZ 10
1*
*
-
2*
2*
-
27
M 12
-
-
6+1*
-
-
12+2*
29
PD 12
-
-
6
-
-
12
30
MZ 12
-
-
1*
-
-
2*
27
S 10X40
2
4
6
-
-
-
29
S 10X50
-
-
-
2
4
6
29
ZT 10
1
1
-
1
1
-
27
ZT 12
-
-
1
-
-
1
27
NSM 6X10
2
4
6
4
8
12
28
VS 41X16
* marked number presents the products for suspension with VS 41X16. In the case of suspension using an anchor, this number is replaced by KPOZ anchor. KPOZ 10
1
1
-
2
2
-
31
KPOZ 12
-
-
1
-
-
2
31
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 9
Cable ladders - KL 60... PO
T
system for ceiling with use of threaded rods and support profiles
20 KPO 10
possible types of anchoring:
VS 41X16 MZ 10 M 10 NSM 6X10 ZT 10
KPBSKL
KPOZ
KL 60... PO
KPO 10 VS 41x16 MZ 10 M 10
M 10 PD 10 PD 10 M 10 MP 41X21 200
x. 1
ma
Fire resistance classification:
Technical parameters of routes:
for power cables: P 90-R E 90 PS 90
spacing of hanging points maximum load on 1 m maximum number of successive routes sidewall height of the cable ladder width of cable ladders thickness of metal sheet of cable ladders
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205 Description of the system: The threaded rod ZT 10 is hanged using 2 pieces of support assembly accessories VS 41X16 and fire resistant anchors KPO 10 to the ceiling. MP 41X21 assembly section parts are anchored on the threaded rods using M 10 nut. This system is designed for a maximum of 3 routes above each other. Ladders KL 60... PO are fixed to the assembly section part using S 6X20 M bolts and PVL 6 washers. The method of anchoring of a threaded rod using KPOZ anchor equals the use of VS 41X16 support part and is regarded as a standardized method of anchoring.
max. 1200 mm 20 kg 3 60 mm 150; 200; 300; 400 mm 1,5 mm
List of products for one mounting point: page MP 41X21
1
2
3
26
VS 41X16
4*
4*
4*
26
KPO 10
2*
2*
2*
31
4+2*
8+2*
12+2*
29
MZ 10
2*
2*
2*
27
ZT 10
2
2
2
27
Approved manufacturers of cables:
PD 10
4
8
12
30
For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire.
S 6X20 M
2
4
6
28
PVL 6
2
4
6
30
M 10
* marked number presents the products for suspension with VS 41X16. In the case of suspension using an anchor, this number is replaced by KPOZ anchor. KPOZ 10
2
2
2
31
10
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable ladders - KL 60... PO
20
system for wall
VS 41X45 M 10
max. 1200
ZT 10 KL 60... PO NSM 6X10 KPBSKL
VS 41X45
PD 10 M 10
DTBS
Fire resistance classification:
Technical parameters of routes:
for power cables: P 90-R E 90 PS 90
spacing of hanging points maximum load on 1 m maximum number of successive routes sidewall height of the cable ladder width of cable ladders thickness of metal sheet of cable ladders
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90 ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205 Description of the system:
max. 1200 mm 20 kg 2 60 mm 150; 200; 300; 400 mm 1,5 mm
List of products for one mounting point:
The supporting structure is composed of the bracket DTBS anchored directly to the wall using fire resistant anchors KPO 10. The end of the DTBS holder is provided with a fixture for ZT 10 threaded rod which is fixed from both ends using M 10 nuts. This type of a construction enables a maximum of two routes above each other, whereas ends of DTBS holders must be fixed to the wall using the threaded rod and two pieces of VS 41X45 support parts under 45째 angle. The span between individual DTBS brackets must be max. 1200 mm. Ladders KL 60... PO are attached to the bracket DTBS using screws NSM 6X10. In case of one line the assembly accessory VS 41X45 is attached to the holder at the end of the bracket DTBS using the bolt S 10X30, nut M 10, and washers PD 10. (see pic. A). Ends of securing threaded rods may be anchored into the ceiling instead of the wall. pic. A ZT 10 M 10 S 10X50 PD 10
Approved manufacturers of cables: For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire.
page DTBS
1
2
1
2
25
VS 41X45
2
2
-
-
26
KPO 10
3
5
2
4
31
ZT 10
1
2
1
2
27
M 10
3
6
2
4
29
S 10X50
1
-
-
-
29
PD 10
3
6
2
4
30
NSM 6X10
2
4
2
4
28
KPOZ 10
-
-
1
1
31
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 11
Cable ladders
T
system of cable ladders - vertical placement, ascending line
20
Description of the system:
KL
The cable ladder is fixed on the base material by means of KLSU clamps placed in the side of the ladder with the maximum span of 1200 mm using NSM 6X10 bolts. A washer needs to be placed under the head of the bolt and the nut. The actual installation to the base material is subsequently performed using KPO 8 anchors. The cable placed in the cable ladder must be mechanically fixed to every rung using PKC clamps. In the case that the length of an ascending cable line is longer than 3500 mm, it is necessary to create a relieving elbow or to use the KPS clamp cover (pg. 13).
NSM 6X10 (2 pcs)
Technical parameters of routes:
KPO 8
spacing of hanging points distance of individual routes
max. 1200 mm 100 mm (the minimum distance for placing of KPS cover) maximum load on 1 m 20 kg maximum number of routes side by side not limited sidewall height of the cable ladder 60 mm width of cable ladders 150; 200; 300; 400 mm
KLSU
max. 1200
List of products for one mounting point: page KLSU
2
27
NSM 6X10
4
28
KPO 8
2
31
The ascending line created by a cable ladder is in terms of standardization understood as a clamp of individual cables. Clamping of cables by individual clamps every 300 mm is understood as a standardized support structure. As the ascending line may be a part of a non-standardized support structure, it is always necessary to use cables from manufacturers who have been certified for installation on the non-standardized part of the cable line. The line on the transition to the ascending section must be anchored. Relieving elbow – instead of the relieving elbow, it is possible to use the KPS cable clamp cover (pg. 33); in terms of standardization this is an equivalent solution
supporting profile NP tolerable radius of cable bending cable clamp PKC cable ladder KL cable
12
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
Cable clamp cover
KL
KLSU
KPS
ZT 8 M8 MS KPS PVL 8
PKC1
KPS
Fire resistance classification: P 60-R E 60 PS 60
ZP 27/2008 DIN 4102-12 STN 92 0205
List of products for one mounting point: page KPS
1
33
MS KPS
1
33
Description of the system: KPS cable clamp cover is fixed on the base material (concrete, solid brickwork) and creates thermal protection of the clamps, which in that way may perform its mechanical function even in fire conditions. The cover is fixed using ZT 8 threaded rods, M 8 nuts and PVL 8 washers anchored using KPOZ 8 anchors (MS KPS kit) to the base material. If the cover is to perform safely its function, it must be installed on ascending routes consisting of cable ladders by max. 3.5 m.
ÂŁ 3 500 mm
Fix the cables to every rung using clamps. According to the pitch of holes in the clamp cover (KPS 160X400) drill holes in the wall and insert anchors in them. Mount threaded rods in the anchors. Mount the clamp cover and tighten it slightly over washers. Deposit one layer of insulation wool after another. Always carefully pack cable surroundings with pieces of insulation wool. Now tighten the nuts holding the cover tightly and cover the cable surroundings and edges of insulation wool carefully with the supplied cement.
MS KPS - mounting kit – ordered separately
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 13
Independent cable clamps system of cable clamps - horizontal placement on the ceiling and wall - assembly on concrete base, solid brickwork
300
cable clamp 67xx D SB 6,3X35 cable
clamp 67xx
Fire resistance classification:
Technical parameters of routes:
for power cables: P 90-R E 90 PS 90
distance of anchoring points max. 300 mm maximum load on 1 m only one cable in the clamp maximum number of successive routes not limited
ZP 27/2008 DIN 4102-12 STN 92 0205
for communication cables: P 90-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205
Description of the system: The base of the supporting construction is created by clamps 6708-6716 (6716D) fixed on the base material using fire resistant bolts for concrete SB 6,3X35. These bolts are screwed into holes with diameter of 5 mm drilled before hand in the concrete. Then the required cable is threaded in the installed clamps. It is necessary to select the size of the clamps taking into account diameter of the installed cable. The maximum distance of installed clamps is 300 mm. The base material must conform to the conditions of maintaining operability in fire. It is possible to install only one cable of the corresponding diameter in one singlesided clamp. It is possible to install two cables of the corresponding diameter in one dual-sided clamp.
List of products for one mounting point: page 67xx
1
-
24
67xx D
-
1
24
SB 6,3X35
1
1
28
Relieving elbow – instead of the relieving elbow, it is possible to use the KPS cable clamp cover (pg. 33); in terms of standardization this is an equivalent solution. With regard to fire classification of the KPS cover, the classification of the line consisting of cable clamps is lowered to 60 minutes. Cables placed under the KPS cover must be fixed using PKC clamps (pg. 31) anchored to NP section parts (pg. 23). The supporting section part must be anchored using two KPO 8 anchors on its edges. maximum distance of anchors must be 250 mm. Therefore, it is necessary to use three KPO 8 anchors for fixing of NP 350 section part.
Two 6708 – 6712 type clamps may be installed under one SB 6,3X35 bolt and thus create a line for two cables. By using two clamps of various sizes under one screw, it is possible to create a line for cables with different diameters (see pg. 24). It is possible to use clamps also for an ascending line; the maximum length of the vertical line is 3500 mm. If longer routes are used, then it is necessary to create a lifting elbow. In the case of cables with larger cross-sections (diameter exceeding 14 mm) it is possible to use the line created using OMEGA clamps (pg. 14) – applies only to horizontal routes. Approved manufacturers of cables: For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire. tolerable radius of cable bending cable
cable clamp
14
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
Clamps OMEGA system of cable clamps - horizontal placement on the ceiling and wall - assembly on concrete base, solid brickwork
52xx 300
SB 6,3X35
cables
Fire resistance classification:
Technical parameters of routes:
for power cables: P 90-R E 90 PS 90
distance of anchoring points maximum load on 1 m
ZP 27/2008 DIN 4102-12 STN 92 0205
max. 300 mm max. 60% of the internal cross-section of the clamp maximum number of successive routes not limited
for communication cables: P 120-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 020
Description of the system: The structure consists OMEGA type clamps 52xx series, which are placed with 300 mm pitch using SB 6,3X35 bolts. These bolts are screwed into pre-drilled 5 mm diameter holes in concrete or solid brickwork. Clamps may be also fixed by KPO 6 anchors. Cables are subsequently placed in the installed clamps. However, the base material must meet the conditions of maintenance of operability of the structure in fire. Cables with cross-section up to 60% of the inner area cross-section of the clamp may be mounted in the clamps.
Approved manufacturers of cables: For supporting cable constructions it is possible to use cables of any manufacturer with proven functionality during fire. In the case that multiple cables are installed, the manufacturer must have the use of multiple cables in common mounting approved.
List of products for one mounting point: page 52xx
1
24
SB 6,3X35
1
28
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 15
Electrical wiring box for power cables
8135
Fire resistance classification: for power cables:
8110; 8117
Technical parameters of routes: maximum number of sublines
8135 PO
P120-R, E90, PS 90
8110 PO6
P120-R, E90, PS 90
8117 PO10
P90-R, E90, PS 90
8135 PO
1,5 - 6 mm2
8117 PO16
P60-R, E60, PS 60
8110 PO6
1,5 - 6 mm2
8117 PO10
1,5 - 10 mm2
8117 PO16
1,5 - 16 mm2
Description of the system: Electrical wiring boxes are mounted to the base material using fire resistant anchors. Distance columns are mounted on the installed anchors provided with washers. A support bar with ceramic terminal is boxes is subsequently mounted on the columns. The support bar is attached to the support columns using nuts. According to the type of the cable, openings are cut into the box and cables are wired. The last step of the installation is the mounting of the cover lid which is done without any tools merely by pressing the lid onto the box body. Installation of 8110 and 8117 boxes is performed using SB 6,3X45 bolts (included in the package) at which the lid is fixed by 4 pieces of bolts in corners.
Cable use depends on the type of structure of which the boxes are a part. The data for types of cables (or for the lack of some limits) may be found in individual assemblies system with maintained functionality in fire.
not limited
cable cross-section:
List of products for one mounting point: page 8135 PO
1
32
8110 PO6
1
32
8117 PO10
1
32
8117 PO16
1
32
All accessories required for installation of the wiring box (fire resistant anchors, supporting columns, terminal box) are included.
16
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
Electrical wiring box for communication cables
8117 DPO
Fire resistance classification: for communication cables: 8117 DPO
Technical parameters of routes: maximum number of sublines
not limited
P 120-R; E 90; PS 90 cable cross-section: 8117 DPO
Description of the system: Electrical wiring boxes are mounted to the base material using SB 6,3X45 bolts (included in the package). According to the type of the cable, openings are cut into the box and cables are wired. The last step of the installation is the mounting of the cover lid which is fixed by 4 pieces of bolts in corners.
Cable use depends on the type of structure of which the boxes are a part. The data on the types of cables (or on the lack of any limits) that may be used may be found with individual assemblies of systems maintaining operability in fire.
0,5 - 4 mm2
List of products for one mounting point: page 8117 DPO
1
32
An electrical wiring box includes all accessories necessary for its installation (bolts SB 6,3X45 and support elements).
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
cable tray
B
H
A
type number
A
H
B
PO
POF
KZ 60X50X1.50
50
60
3000
1,5
8595057692046
KZ 60X75X1.50
75
60
3000
1,5
8595057635838
KZ 60X100X1.50
100
60
3000
1,5
8595057635852
KZ 60X150X1.50
150
60
3000
1,5
8595057635883
KZ 60X200X1.50
200
60
3000
1,5
8595057635913
KZ 60X300X1.50
300
60
3000
1,5
8595057635951
For connecting the trays there are designated the couplings KSBS.
B
coupling for cable trays
*H *A
type number
*A
*H
B
PO
POF
KSBS 50
50
60
200
16
1,5
8595057692022
KSBS 75
75
60
200
16
1,5
8595057649804
KSBS 100
100
60
200
16
1,5
8595057649811
KSBS 150
150
60
200
16
1,5
8595057665774
KSBS 200
200
60
200
24
1,5
8595057649835
KSBS 300
300
60
200
24
1,5
8595057649842
For connecting the ladders there are designed connecting NSM 6X10 (pg. 28). * dimension of the cable tray, not the couplings
thickness of metal sheet (mm)
amount of bolts for connection
to order
PO
Pre-Galvanized
POF Hot Dip Galvanized
17
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
cable ladder
B
C
15 H
16
A
type number
A
H
B
C
PO
POF
KL 60X150
150
60
150
3000
1,5
8595057691414
KL 60X200
200
60
150
3000
1,5
8595057691421
KL 60X300
300
60
150
3000
1,5
8595057691438
KL 60X400
400
60
150
3000
1,5
8595057691445
The distance of rungs of cable ladders for standardized support structures is 150 mm. Cable ladders may be also used as an ascending line maintaining operability in fire - pg. 11, the KLSU angle part is intended for mounting on the wall (pg. 27). For the connecting there are designated the couplings KPBSKL. For ladders it is possible to use accessories to cable trays JUPITER pg. 19 - 23.
coupling for cable ladders
B
18
*H
*A
type number
*A
*H
B
PO
POF
KPBSKL 150
150
60
250
20
1,5
8595057692688
KPBSKL 200
200
60
250
20
1,5
8595057650091
KPBSKL 300
300
60
250
20
1,5
8595057650107
KPBSKL 400
400
60
250
20
1,5
8595057650114
There are used the screws NSM 6X10 for the connecting (pg. 28) - 12 pcs. * dimension of the cable ladder, not the couplings
thickness of metal sheet (mm)
amount of bolts for connection
to order
PO
Pre-Galvanized
POF Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
elbow 90°
B
H ∅7 x 17
A
type number
A
H
B
S
F
O 90X60X50
50
60
250
0,8
8
8595057627864
O 90X60X75
75
60
275
0,8
8
8595057627871
O 90X60X100
100
60
300
0,8
8
8595057627888
O 90X60X150
150
60
350
0,8
8
8595057627895
O 90X60X200
200
60
400
1,0
8
8595057627918
O 90X60X300
300
60
500
1,0
8
8595057627925
O 90X60X400
400
60
600
1,0
8
8595057627932
To fix the connection use the bolt NSM 6X10 (pg. 28). The elbow of 400 mm width has the outside right angle of sidewalls replaced by canting; this elbow is designed in fire resistant system only for cable ladders.
T- p i e c e
C
H A
∅7 x 17
B
type number
A
H
B
C
S
F
T 60X50
50
60
250
450
0,8
12
8595057637443
T 60X75
75
60
275
475
0,8
12
8595057633339
T 60X100
100
60
300
500
0,8
12
8595057630338
T 60X150
150
60
350
550
0,8
12
8595057633575
T 60X200
200
60
400
600
1,0
12
8595057631717
T 60X300
300
60
500
700
1,0
12
8595057637467
T 60X400
400
60
600
800
1,0
12
8595057631700
To fix the connection use the bolt NSM 6X10 (pg. 28). T-piece of 400 mm width is meant in fire resistant systems only for cable ladders.
thickness of metal sheet (mm)
amount of bolts for connection
to order
S
Pre-Galvanized
F
Hot Dip Galvanized
19
20
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
cross-over
H ∅7 x 17
A
B
type number
A
H
B
S
F
KR 60X50
50
60
450
0,8
16
8595057637696
KR 60X75
75
60
475
0,8
16
8595057637702
KR 60X100
100
60
500
0,8
16
8595057637719
KR 60X150
150
60
550
0,8
16
8595057637726
KR 60X200
200
60
600
1,0
16
8595057637733
KR 60X300
300
60
700
1,0
16
8595057637757
KR 60X400
400
60
800
1,0
16
8595057637764
To fix the connection use the bolt NSM 6X10 (pg. 28). Crossover of 400 mm width is meant in fire resistant systems only for cable ladders.
low elbow 90°
B
H
A
∅7 x 17
type number
A
H
B
S
F
KO 90X60X50
50
60
245
0,8
8
8595057628014
KO 90X60X75
75
60
245
0,8
8
8595057628021
KO 90X60X100
100
60
245
0,8
8
8595057628038
KO 90X60X150
150
60
245
0,8
8
8595057628045
KO 90X60X200
200
60
245
1,0
8
8595057628052
KO 90X60X300
300
60
245
1,0
8
8595057628069
KO 90X60X400
400
60
245
1,0
8
8595057628076
To fix the connection use the bolt NSM 6X10 (pg. 28). Bending elbow of 400 mm width is meant in fire resistant systems only for cable ladders. For ascending and descending of the line there are only cable ladders even in case of a horizontal line led by cable trays.
thickness of metal sheet (mm)
amount of bolts for connection
to order
S
Pre-Galvanized
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 21
rising elbow 90°
B
H ∅7 x 17
A
type number
A
H
B
S
F
SO 90X60X50
50
60
245
0,8
8
8595057628151
SO 90X60X75
75
60
245
0,8
8
8595057628168
SO 90X60X100
100
60
245
0,8
8
8595057628175
SO 90X60X150
150
60
245
0,8
8
8595057628182
SO 90X60X200
200
60
245
1,0
8
8595057628199
SO 90X60X300
300
60
245
1,0
8
8595057628205
SO 90X60X400
400
60
245
1,0
8
8595057628212
To fix the connection use the bolt NSM 6X10 (pg. 28). Bending elbow of 400 mm width is meant in fire resistant systems only for cable ladders. For ascending and descending of the line there are only cable ladders even in case of a horizontal line led by cable trays.
end-piece
H ∅7 x 25
A B
type number
H
A
B
S
F
K 60X50
50
50
44
1,0
4
8595057638235
K 60X75
50
75
44
1,0
4
8595057635470
K 60X100
50
100
44
1,0
4
8595057629974
K 60X150
50
150
44
1,0
4
8595057629981
K 60X200
50
200
44
1,0
4
8595057629998
K 60X300
50
300
44
1,0
4
8595057629639
The connection is performed using the screws NSM 6X10 (pg. 28).
thickness of metal sheet (mm)
amount of bolts for connection
to order
S
Pre-Galvanized
F
Hot Dip Galvanized
22
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
reduction B
H A
∅7 x 25
type number
H
A
B
S
F
SR 60X25
50
25
44
1,0
4
8595057638426
SR 60X50
50
50
44
1,0
4
8595057633582
SR 60X75
50
75
44
1,0
4
8595057638433
SR 60X100
50
100
44
1,0
4
8595057631755
SR 60X125
50
125
44
1,0
4
8595057638440
SR 60X150
50
150
44
1,0
4
8595057638457
SR 60X200
50
200
44
1,0
4
8595057638464
SR 60X250
50
250
44
1,0
4
8595057638471
The fastening of the joint is performed with the screws NSM 6X10 (pg. 28). The reduction is designed for the purpose of adjustment of the widths of the cable trays or ladders in the line.
universal coupling H
238
4
8 23
∅7
x1
2
∅7
x3
∅7 x 17
type number
H
S
F
SU 60
60
1,0
4
8595057628380
Two pieces for one branching are used for additional diverting of cables from the cable line instead of a T-piece. The connection is performed using the screws NSM 6X10 (pg. 28).
thickness of metal sheet (mm)
amount of bolts for connection
to order
S
Pre-Galvanized
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 23
hinged joint
H
∅7 x 17
type number
H
S
F
SK 60
60
0,8
4
8595057627772
For the connection of the hinged joint to the tray there are used the screws NSM 6X10 (pg. 28). The coupling is supplied by 1 piece; in order to create one connection, 2 pieces are needed. The couplings to be used on the right or left side do not differ.
partition
B
H
D
C
A
type number
H
A
B
C
D
S
F
P 60
54
17,5
3000
∅7 x 25
50
0,8
8595057627734
The connection is performed using the screws NSM 6X10 (pg. 28), 2 pcs per 1 meter. The partition is determined for branching in cable trays.
load bearing profile
A
C B
D
A
B
C
D
S
F
NP 100
100
30
15
∅9 x 35
1,2
100
0,06
8595057639768
NP 150
150
30
15
∅9 x 35
1,2
100
0,08
8595057639775
NP 200
200
30
15
∅9 x 35
1,2
100
0,11
8595057639782
NP 250
250
30
15
∅9 x 35
1,2
100
0,14
8595057639799
NP 350
350
30
15
∅9 x 35
1,2
100
0,20
8595057630864
to order
type number
thickness of metal sheet (mm)
max. load (kg)
amount of bolts for connection
weight kg/m
S
Pre-Galvanized
F
Hot Dip Galvanized
24
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
clamps for cables
20
type number
∅ of cable
PO
PO GMT
clamps single-sided 6708
6
0,01
100
8595568909930
8595568912459
6710
8
0,01
100
8595568909947
8595568912466
6712
10
0,01
100
8595568909954
8595568912473
6716E
14
0,015
250
8595057698031
8595568912503
8595057698079
8595568912510
clamps dual-sided 6716ED
14
0,02
250
Clamps are fixed to the base material using SB 6.3X35 concrete bolts (pg. 28). Two 6708-6712 clamps may be placed under one screw and in this way a line for two cables is created.
clamp OMEGA
∅ cable min. - max.
S
F
5220 ZNM
18 - 21
0,015
8595057692091
-
5225 ZNM
22 - 25
0,018
8595057692107
-
5232 ZNM
25 - 39
0,022
8595057692114
-
5250 ZNM
38 - 50
0,028
8595057692138
-
5263 ZNM
51 - 60
0,032
8595057692145
-
5216E ZN
12 -14
0,014
-
8595568915269
5220 ZN
14 - 18
0,015
-
8595568915276
5225 ZN
18 - 22
0,018
-
8595568915283
5232 ZN
22 - 30
0,022
-
8595568915290
5240 ZN
30 - 38
0,025
-
8595568915306
5250 ZN
38 - 50
0,028
-
8595568915313
5263 ZN
51 - 60
0,032
-
8595568915320
type number
To facilitate installation the clamp is provided with a groove for insertion; it is not necessary to separate completely the top part of the clamp at the installation. For attaching to the base material it is suitable to use anchors or bolts in the concrete SB 6.3X35 (pg. 28).
weight kg/pcs
pieces in a package
GMT
non electrolytic plating
S
Pre-Galvanized
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 25
ceiling profile B
A
C
15 x 15
41
21
A
B
C
F
SPL 200
214
120
120
0,74
8595057628557
SPL 300
304
120
120
0,85
8595057632097
SPL 400
424
120
120
1,01
8595057628564
SPL 500
514
120
120
1,13
8595057635067
SPL 600
604
120
120
1,23
8595057628571
SPL 800
814
120
120
1,45
8595057634978
SPL 1000
1024
120
120
1,75
8595057640061
SPL 1200
1204
120
120
1,95
8595057640078
type number
Designated for attaching of brackets DTBS with the use of the bolt S 10X40 (S 10X50 for dual sided assembly), nuts M 10 and washers PD 10.
bracket
B
A
C
E D
A
B
C
D
E
PO
DTBS 100
120
50
∅12 x 20
∅14
∅7 x 20
0,43
8595057649866
DTBS 150
120
50
∅12 x 20
∅14
∅7 x 20
0,52
8595057634954
DTBS 200
120
50
∅12 x 20
∅14
∅7 x 20
0,58
8595057649873
DTBS 300
135
50
∅12 x 20
∅14
∅7 x 20
0,83
8595057634961
DTBS 400
135
50
∅12 x 20
∅14
∅7 x 20
1,03
8595057649880
type number
DTBS holders are designed for creating of a standardized cable line of cable trays or ladders. Is used for direct mounting to the wall using fire resistant anchors or for mounting to the ceiling profile SPL. The end of the holder needs to be fixed to the wall or ceiling using ZT threaded rod. DTBS holders are supplied by default with galvanized surface finish and in disassembled condition (without screwed on securing lug).
weight kg/pcs
F
Hot Dip Galvanized
PO
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
assembly profile
D F E
A
26
C B
type number
A
B
C
F
S
F
MP 41X21
21
41
22
3000 ∅13 x 30
50
2,5
1,85
8595057699557
8595057633469
MP 41X41
41
41
22
3000 ∅13 x 30
50
2,5
2,70
8595057631526
8595057632103
D
E
It is used as a support for the installation of ladders or trays when placed on the threaded rods. PD and PVL washers must be put under the nuts.
assembly accessory between the anchor and the threaded rod
20
4
∅1
40
type number
F
VS 41X16
5
0,27
8595057634985
For attaching the threaded rod to the ceiling. For the creation of a single hanging point it is necessary to use two pieces placed against each other. As an alternative, it is also possible to use anchoring of the threaded rod using KPOZ hammer-in anchors. This anchoring is also regarded as a standardized method of anchoring.
assembly accessory between the anchor and the threaded rod - 45°
35 ∅13 16
type number
F
VS 41X45
5
0,10
8595057667570
For attaching the threaded rod to the wall at an angle of 45°.
thickness of metal sheet (mm)
S
Pre-Galvanized
weight kg/pcs; weight kg/m
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 27
cable ladder wall bracket
2
x7
70
∅2
∅9
65
type number KLSU
S
F
1,5
0,07
8595568908681
8595568908698
Mounting to the ladder is performed using NSM 6X10 bolts (pg. 28). The 8 mm anchor is used for mounting on the wall. The wall mounting of KLSU cable ladder fully replaces the previously used DRIPN.
threaded rod
A
Ø
A
ZNCR
ZT 10
M10
2000
0,46
8595057628922
ZT 12
M12
2000
0,70
8595057639591
type number
It is used for suspending of a cable line under the ceiling. In the case of standardized structures for securing of ends of outriggers to the wall or ceiling. The specification is stated on each cable line assembly.
hang nut
A
Ø
A
ZNCR
MZ 10
M10
28
0,04
8595057629929
MZ 12
M12
40
0,06
8595057639584
type number
It is used for connecting of two threaded rods or as a nut for some standardized support systems.
weight kg/pcs; weight kg/m
S
Pre-Galvanized
F
Hot Dip Galvanized
ZNCR Bichromatic galvanised
28
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
carriage bolt and locknut
ZNCR
NSM 6X10
0,007
100
8595057667129
-
NSM 6X10-GMT
0,007
100
-
8595057692947
type number
GMT
GMT surface finish is necessary for galvanized systems; however, it may be used even for systems with Sendzimir surface finish.
bolt with a round head and lock nut
type number S 6X20 M
ZNCR
0,01
250
8595057640825
bolt to concrete
type number SB 6.3X35
PO GMT
100
8595057697904
It serves for attaching OMEGA clamps or independent cable clamps to the base material. The bolt may be mounted in concrete, natural stone, or solid brickwork. A ∅ 5 mm hole needs to be pre-drilled for mounting of the bolt. The supplied surface finish may be used for installation of clamps with PO and PO GMT surface finish (type 6708-6716) and both types of surface finish of OMEGA clamps.
weight kg/pcs
ZNCR Bichromatic galvanised
pieces in a package
GMT non electrolytic plating
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 29
bolt with hexagonal head
ZNCR
S 6X20
0,01
250
8595057630451
S 6X30
0,01
250
8595057640733
S 8X20
0,01
250
8595057638822
S 8X30
0,02
250
8595057640740
S 8X40
0,02
250
8595057640757
S 8X50
0,02
250
8595057640764
S 8X70
0,03
250
8595057640771
S 10X20
0,02
250
8595057628724
S 10X30
0,03
250
8595057628731
S 10X40
0,03
250
8595057640788
S 10X50
0,05
250
8595057698123
S 10X70
0,05
250
8595057698123
S 12X20
0,03
250
8595057633124
S 12X30
0,04
250
8595057633131
S 12X40
0,05
250
8595057640795
S 12X50
0,06
250
8595057640801
type number
hexagon nut
ZNCR
M6
0,01
250
8595057633636
M8
0,01
250
8595057633643
M 10
0,01
250
8595057630406
M 12
0,02
250
8595057640818
type number
weight kg/pcs
pieces in a package
ZNCR Bichromatic galvanised
30
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
washer
A
type number
A
ZNCR
PD 6
12
0,01
250
8595057640832
PD 8
17
0,01
250
8595057633438
PD 10
20
0,01
250
8595057633445
PD 12
24
0,01
250
8595057640849
large washer
A
type number
A
ZNCR
PVL 6
18
0,001
250
8595057629523
PVL 10
20
0,01
250
8595057633797
PVL 12
24
0,02
250
8595057640856
weight kg/pcs
pieces in a package
ZNCR Bichromatic galvanised
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 31
A
clamp
B
type number
A min.
B
F
PKC1 1198
6
12
0,03
8595057644878
PKC1 1199
7
16
0,03
8595057644885
PKC1 1200
10
19
0,04
8595057642232
PKC1 1201
14
23
0,04
8595057642249
PKC1 1202
20
26
0,04
8595057635586
PKC1 1203
24
30
0,06
8595057635517
PKC1 1204
25
35
0,07
8595057635401
PKC1 1205
28
38
0,08
8595057635524
PKC1 1206
32
43
0,09
8595057644892
PKC1 1207
42
47
0,10
8595057644908
PKC1 1208
43
51
0,10
8595057635531
PKC1 1209
50
55
0,11
8595057635593
PKC1 1210
52
59
0,14
8595057644915
PKC1 1211
54
63
0,16
8595057644922
PKC1 1212
57
69
0,16
8595057635609
The information means the minimum and maximum diameter of the cable being fastened. The mentioned dimensions are used for basic guidance when selecting clamps for cables. Based on an order, it is possible to supply PKC2 clamps for two cables conforming the conditions of systems maintaining operability in fire.
D
anchor
B
C
B
A
A
type number
A
B
*C
*D
*E
thread
PO
KPO 6X50
6
50
35
5
45
M6
0,01
8595057691162
KPO 6X70
6
70
35
10
70
M6
0,02
8595057691179
KPO 8X77
8
77
45
10
75
M8
0,03
8595057691100
KPO 8X97
8
97
45
30
95
M8
0,04
8595057691117
KPO 10X95
10
95
60
10
90
M10
0,06
8595057691124
KPO 10X115
10
115
60
30
110
M10
0,08
8595057691131
KPO 12X120
12
120
70
10
115
M12
0,10
8595057691148
KPO 12X150*
12
150
70
30
145
M12
0,13
8595057691155
KPOZ 10
12
40
-
-
-
M10
0,03
8595057692855
KPOZ 12
14
50
-
-
-
M12
0,06
8595057692862
*C - anchor depth *D - maximum thickness of the material being attached *E - minimum depth of the drilled hole The fire resistant anchors serve for the attaching of construction elements to the base material (concrete, stone). The knock in anchors KPOZ serve for the direct attachment of the threaded rods. * until the sell-out of stocks
weight kg/pcs
PO F
Pre-Galvanized Hot Dip Galvanized
32
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
electrical installation box fire resistant - power cables
dimension
8135
PO
105 x 105 x 40
orange RAL 2004
IP54
0,2
8595057691612
8110
PO6
117 x 117 x 58
orange RAL 2004
IP54
0,5
8595568904812
8117
PO10
167 x 167 x 78
orange RAL 2004
IP54
0,7
8595568904829
8117
PO16
167 x 167 x 78
orange RAL 2004
IP54
0,7
8595057699021
type number
The box is fitted with a ceramic terminal block while maintaining the functionality during a fire and is fixed by using the enclosed fire resistant anchors or bolts for concrete. The boxes are intended only for use with cables with proven operability in fire. Fire resistant boxes are made of halogen-free material. 8135:
cover is mounted without bolts terminal block is designated for 5 wires with a cross-section from 1,5 to 6 mm2 fire resistance classification: P 120-R ZP 27/2008 E 90 DIN 4102-12 PS 120 STN 92 0205
8117 PO10: the cover is secured by bolts terminal block is designated for 5 wires with fire resistance classification: P 90-R E 90 PS 90
a cross-section to 10 mm2 ZP 27/2008 DIN 4102-12 STN 92 0205
8110 PO6: the cover is secured by bolts terminal block is designated for 5 wires with a cross-section 1,5 - 6 mm2 fire resistance classification: P 120-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205 8117 PO16: terminal block is designated for 5 wires with a cross-section to 16 mm2 fire resistance classification: P 60-R ZP 27/2008 E 60 DIN 4102-12 PS 60 STN 92 0205
electrical installation box fire resistant - data cables
dimension
167 x 167 x 78
orange RAL 2004
IP54
0,7
type number 8117
DPO
8595568912480
The box is equipped with a ceramic terminal block - 12 poles maintaining operability in fire. They are fixed using the attached bolts for concrete (included in the package). The boxes are intended for use only with data cables with proven operability in fire. Fire resistant boxes are made of halogen-free material. 8117 DPO: the cover is secured by bolts terminal block is designated for 12 wires with a cross-section to 4 mm2 fire resistance classification: P120-R ZP 27/2008 E 90 DIN 4102-12 PS 90 STN 92 0205
weight kg/pcs
color
degree of shielding
F I R E R E S I S TA N T S Y S T E M S - s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 33
cable clamp cover
C
A
B
type number KPS 160x400
A
B
C
PO
3,1
530
160
155
8595568912497
Anchoring to the base material using MS KPS mounting kit. KPS cover includes insulation wool and a cartridge with insulation cement. One mounting kit needs to be ordered for cover installation.
mounting kit for cable clamp cover
type number MS KPS
PO
1,0
8595568912527
The kit always needs to be ordered with the clamp cover - 1 piece of the kit with one cover. The kit contains fire resistant anchors, threaded rods, washers, nuts, and a knife for cutting of thermally insulating wool.
weight kg/pcs
PO
Hot Dip Galvanized
34
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
Connection of fire resistant cable tray KZI – JUPITER
KZI NSM 6X10 KZI
Cable tray KZI with maintained functionality in case of fire must be made of a metal sheet 1.25 mm thick. Connection of the cable tray KZI KZI is carried out using the integrated coupling which is included within the tray and using screws NSM 6X10 or NSM 6X10-GMT. To width of the tray maintain stability of the supporting line at very difficult conditions of fire it is necessary to install these bolts to all holes which appear after 50 inserting one end of the tray to the end of the subsequent tray. 75
NSM 6X10 number of bolts 4 4
100
4
150
4
200
6
300
6
Connection of fire resistant cable tray NKZI, NKZIN – MARS
NKZI
NSM 6X10
NKZI
Cable tray NKZI with maintained functionality in case of fire must be made of a metal sheet 1.25 mm thick. Connection of the cable tray NKZI is carried out using the integrated coupling which is included within the tray and using screws NSM 6X10 or NSM 6X10-GMT. To maintain stability of the supporting line at very difficult conditions of fire it is necessary to install these bolts to all holes which appear after inserting one end of the tray to the end of the subsequent tray. In the case of not perforated tray, it is necessary to drill the holes for NSM 6X10 (2 pieces) bolts in the tray bottom. * The number of bolts applies only to NKZI 50X125 cable tray suspended under the ceiling using ZVNI suspension; in case of this type of suspension it is necessary to use the connection of trays in the bottom using 2 pieces of NSM 6X10 bolts.
NKZI, NKZIN 50 width of the tray
NSM 6X10 number of bolts
NKZI, NKZIN 100 NSM 6X10 width of the tray number of bolts
62
2
125
4
125
2, 4*
250
6
250
4
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 35
Cable trays JUPITER - KZI
T
dual sided system for ceiling with use of ceiling profile SPS
10 KPO 10
500
.1 max
SPS S 10X70; M 10; PD 10 DT
NSM 6X10 KZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile always two brackets DT are mounted always opposite to each other from both sides using bolts S 10X70, nuts M 10, and two pieces of washers PD 10. The cable trays KZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than three levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Lamela Electric a.s.
power
max. 1500 mm 10 kg 3 60 mm 50; 75; 100; 150; 200; 300 mm 1,25 mm
data
type
resistance
type
resistance
1-CHKE-V B2ca,s1,d0
90
JXFE-V B2ca,s1,d0
60
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page SPS
1
1
1
70
KPO 10
4
4
4
77
DT
2
4
6
71
S 10X70
2
4
6
76
M 10
2
4
6
74
PD
4
8
12
76
NSM 6X10
4
8
12
75
36
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays JUPITER - KZI
10
single sided system for ceiling with use of ceiling profile SPS KPO 10
00 x. 15
ma
SPS S 10X20; PM 41 M 10; PD 10 DT NSM 6X10 KZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile the bracket DT is attached from one side using the bolt S 10X20, the sliding nut PM 41 M 10, and the washer PD 10. The cable trays KZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than two levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Lamela Electric a.s.
power
max. 1500 mm 10 kg 2 60 mm 50; 75; 100; 150; 200; 300 mm 1,25 mm
data
type
resistance
type
resistance
1-CHKE-V B2ca,s1,d0
90
JXFE-V B2ca,s1,d0
60
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page SPS
1
1
70
KPO 10
4
4
77
DT
1
2
71
S 10X20
2
4
76
PM 41 M 10
2
4
72
PD 10
2
4
76
NSM 6X10
2
4
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 37
Cable trays JUPITER - KZI
T
system of cable trays for walls
10
KPO 10 DT
00 x. 15
NSM 6X10
ma
KZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The supporting construction is created by two brackets DT attached by two fire resistant anchors KPO 10 with the distance not exceeding 1500 mm on the base material. The cable trays are connected using the integrated coupling and screws NSM 6X10 (see connecting of trays). Then, the cable trays must be attached to brackets DT using screws NSM 6X10.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer PRAKAB PRAŽSKÁ KABELOVNA a.s. Kabelovna Kabex a.s.
power
data
type
resistance
1-CSKH-V180/P30-R (N) HXH-J RE FE180/P90-R
30
1-CHKE-V
max. 1500 mm 10 kg not limited 60 mm 50; 75; 100; 150; 200; 300 mm 1,25 mm
type
resistance
SSKFH-V180
90
60 90
JCXFE-V
30
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page DT
1
2
3
71
KPO 10
2
4
6
77
NSM 6X10
2
4
6
75
38
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays JUPITER - KZI
10; 20
system for ceiling with use of threaded rods and assembly profiles MP 41X41
KPOZ ZT
0 . 120
max
NSM 6X10 KZI
M PD PD M 10 MP 41X41
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10. MP 41X41 assembly section parts are anchored on threaded rods using M 10 nuts with PD 10 washers. The maximum distance of cable hangers is 1200 mm. The cable trays KZI are firmly attached to the assembly profiles MP 41X41 using screws NSM 6X10 and large washers PVL 6. This system allows assembling of not more than two levels under each other using threaded rods ZT 10.
spacing of hanging points maximum load on 1 m
max. 1200 mm 10 kg
maximum load on 1 m
20 kg
maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
3 60 mm 50; 75; 100; 150; 200; 300 mm 1,25 mm
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer EUPEN
power type NHXH RE FE 180 E 90
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s. Kabelovna Kabex a.s.
1-CSKE-V/h/E90
(EUPEN, Kabelovna Kabex a.s.) (PRAKAB PRAŽSKÁ KABELOVNA a.s.)
data resistance
90
90
30
type JE-H(St)H Bd FE 180 E 90 SSKFH-V180
-
page
resistance
90
60
-
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
ZT 10
2
2
2
74
KPOZ 10
2
2
2
77
MP 41X41
1
2
3
69
M 10
4
8
12
74
PD 10
4
8
12
76
NSM 6X10
2
4
6
75
PVL 6
2
4
6
76
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 39
Cable trays MARS - NKZI - height of sidewall is 50
T
dual sided system for ceiling with use of ceiling profile SPS
10 KPO 10
500
.1 max
SPS S 10X70; M 10; PD 10 DT
NSM 6X10 NKZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile always two brackets DT are mounted always opposite to each other from both sides using bolts S 10X70, nuts M 10, and two pieces of washers PD 10. The cable trays NKZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than three levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Lamela Electric a.s.
power
max. 1500 mm 10 kg 3 50 mm 62; 125; 250 mm 1,25 mm
data
type
resistance
1-CHKE-V B2ca,s1,d0
90
type JXFE-V B2ca,s1,d0
page
resistance
60
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
SPS
1
1
1
70
KPO 10
4
4
4
77
DT
2
4
6
71
S 10X70
2
4
6
76
M 10
2
4
6
74
PD 10
4
8
12
76
NSM 6X10
4
8
12
75
40
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZI - height of sidewall is 50
10
dual sided system for ceiling with use of ceiling profile SPL
KPO 10
0
. 150
max
SPL S 10X50; M 10; PD 10 DT NSM 6X10 NKZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPL anchored with four anchors KPO 10. To this ceiling profile always two brackets DT are mounted always opposite to each other from both sides using bolts S 10X50, nuts M 10, and two pieces of washers PD 10. The cable trays NKZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than two levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Kabelovna Kabex a.s.
power type 1-CHKE-V
max. 1500 mm 10 kg 2 50 mm 62; 125; 250 mm 1,25 mm
data resistance
90
type JCXFE-V
page
resistance
60
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
SPL
1
1
70
KPO 10
4
4
77
DT
2
4
71
S 10X50
2
4
76
M 10
2
4
74
PD 10
4
8
76
NSM 6X10
4
8
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 41
Cable trays MARS - NKZI - height of sidewall is 50
T
single sided system for ceiling with use of ceiling profile SPS
10 KPO 10
00 x. 15
ma
SPS S 10X20; PM 41 M 10; PD 10 DT NSM 6X10 NKZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile the bracket DT is attached from one side using the bolt S 10X20, the sliding nut PM 41 M 10 (PMP 41 M 10), and the washer PD 10. The cable trays NKZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than two levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Lamela Electric a.s. Kabelovna Kabex a.s.
power
data
type
resistance
1-CHKE-V B2ca,s1,d0
90
1-CHKE-V
max. 1500 mm 10 kg 2 50 mm 62; 125; 250 mm 1,25 mm
90
type JXFE-V B2ca,s1,d0 JCXFE-V
page
resistance
60 60
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
SPS
1
1
70
KPO 10
4
4
77
DT
1
2
71
S 10X20
2
4
76
PM 41 M 10
2
4
72
PD 10
2
4
87
NSM 6X10
2
4
75
42
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZI - height of sidewall is 50; 100
10;20
system for ceiling with use of threaded rods and assembly profiles MP 41X21 KPOZ 10 .
max
1200
ZT 10
MP 41X21
M 10
NKZI
NSM 6X10 PD 10
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10. MP 41X41 assembly section parts are anchored on threaded rods from top using M 10 nuts and from bottom using PD 10 washers. The maximum distance of cable hangers is 1200 mm. The cable trays NKZI are firmly attached to the assembly profiles MP 41X21 using screws NSM 6X10 and large washers PVL 6. This system allows assembling of not more than three levels under each other using threaded rods ZT 10.
spacing of hanging points maximum load on 1 m
Fire resistance classification, approved manufacturers of cables: NKZI 50
List of products for one mounting point:
Manufacturer
power type
Prysmian Group
data resistance
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s.
type
10 kg - 30 SSKFH-V180 20 kg - 30
(N) HXHX-J FE 180 10 kg - 60
JE-H(St)H FE 180
power type
10 kg - 30 20 kg - 30 10 kg - 90
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s. Prysmian Group
data resistance
type
resistance
10 kg - 30 SSKFH-V180 20 kg - 30
10 kg - 30 20 kg - 30
JE-H(St)H FE 180
10 kg - 120
(N) HXHX-J FE 180 10 kg - 90
page
resistance
NKZI 100 Manufacturer
max. 1200 mm 10 kg 20 kg (PRAKAB PRAŽSKÁ KABELOVNA a.s.) maximum number of successive routes 3 height of the side-wall of cable tray 50; 100 mm widths of cable trays 62; 125; 250 mm thickness of metal sheet of cable trays 1,25 mm
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx 120 classification is valid according to ZP 27/2008, 90 classification applies to other standards.
ZT 10
2
2
2
74
KPOZ 10
2
2
2
77
MP 41X21
1
2
3
69
M 10
4
8
12
74
PD 10
4
8
12
76
NSM 6X10
2
4
6
75
PVL 6
2
4
6
76
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 43
Cable trays MARS - NKZI - height of sidewall is 50; 100
T
system for ceiling with use of threaded rods and assembly profiles MP 41X21X1,50
10
KPOZ 10 .
max
1200
ZT 10
MP 41X21X1,50
M 10
NKZI
NSM 6X10 PD 10
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10. MP 41X21X1,50 assembly section parts are anchored on threaded rods from top using M 10 nuts and from bottom using PD 10 washers. The maximum distance of cable hangers is 1200 mm. The cable trays NKZI are firmly attached to the assembly profiles MP 41X21 using screws NSM 6X10 and large washers PVL 6. This system allows assembling of not more than three levels under each other using threaded rods ZT 10.
spacing of hanging points maximum load on 1 m
Fire resistance classification, approved manufacturers of cables: NKZI 50
List of products for one mounting point:
Manufacturer Kabelovna Kabex a.s.
power type 1-CSKE-V/h/E90
data resistance
type
resistance
60
-
-
NKZI 100 Manufacturer Kabelovna Kabex a.s.
power type 1-CSKE-V/h/E90
max. 1200 mm 10 kg (Kabelovna Kabex a.s.) maximum number of successive routes 3 height of the side-wall of cable tray 50; 100 mm widths of cable trays 62; 125; 250 mm thickness of metal sheet of cable trays 1,25 mm
data resistance
type
resistance
30
-
-
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page ZT 10
2
2
2
74
KPOZ 10
2
2
2
77
MP 41X21X1,50
1
2
3
69
M 10
4
8
12
74
PD 10
4
8
12
76
NSM 6X10
2
4
6
75
PVL 6
2
4
6
76
44
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZI - height of sidewall is 50
10
system for ceiling with use of threaded rods and assembly profiles MP 41X41
KPOZ ZT
0 . 120
max
NKZI M PD PVL M MP 41X41
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10 (12). MP 41X41 assembly section parts are anchored on threaded rods using M 10 (12) nuts with PD 10 (12) washers. The maximum distance of cable hangers is 1200 mm. The cable trays NKZI are firmly attached to the assembly profiles MP 41X41 using bolts S 6X20 M and large washers PVL 6. This system allows assembling of not more than two levels under each other using threaded rods ZT 10 and not more than three levels under each other using threaded rods ZT 12.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Lamela Electric a.s.
power
max. 1200 mm 10 kg 3 50 mm 62; 125; 250 mm 1,25 mm
data
type
resistance
type
resistance
1-CHKE-V B2ca,s1,d0
60
JXFE-V B2ca,s1,d0
30
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page ZT 10
2
2
-
74
ZT 12
-
-
2
74
KPOZ 10
2
2
-
77
KPOZ 12
-
-
2
77
MP 41X41
1
2
3
69
M 10
4
8
-
74
M 12
-
-
12
74
PD 10
2
4
-
76
PD 12
-
-
12
76
S 6X20 M
2
4
6
75
PVL 6
2
4
6
76
PVL 10
2
4
-
76
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 45
Cable trays MARS - NKZI - height of sidewall is 50
T
ceiling assembly with the use of ZVNI internal suspension – one threaded rod
5
x.
ma
00
12
ZT 8
ZVNI
MN 8
NSM 6X10 PD 8 M8
Description of the system:
Technical parameters of routes:
ZT 8 threaded rod is suspended from the ceiling using KPOZ 8 fire resistant anchors and using ZVNI internal suspension and MN 8 nut it carries NKZI cable tray. At the bottom, the connection is secured by PD 8 washer and M 8 nut. The assembly allows mounting of only one cable tray floor.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer
power type
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s.
data resistance
type
resistance
90*
-
-
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx * Classification applies to cables with cross-section up to 16 mm2.
page ZT 8
1
74
KPOZ 8
1
77
ZVNI
1
72
MN 8
1
74
PD 8
1
76
NSM 6X10
4
75
max. 1200 mm 5 kg 1 50 mm 62; 125 mm 1,25 mm
46
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZI - height of sidewall is 50, 100
10
system of cable trays for walls
KPO 10 NSM 6X10
500 ax. 1
m
DT NKZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The supporting construction is created by two brackets DT attached by two fire resistant anchors KPO 10 with the distance not exceeding 1500 mm on the base material. The cable trays are connected using the integrated coupling and screws NSM 6X10 (see connecting of trays, pg. 34). Then, the cable trays must be attached to brackets DT using screws NSM 6X10.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables: NKZI 50
List of products for one mounting point:
Manufacturer Lamela Electric a.s. PRAKAB PRAŽSKÁ KABELOVNA a.s.
power
data
type
resistance
type
resistance
1-CHKE-V B2ca,s1,d0
90
JXFE-V B2ca,s1,d0
60
1-CSKH-V180/P30-R (N) HXH-J RE FE180/P90-R
30 SSKFH-V180
90
90
NKZI 100 Manufacturer
power
data
type
resistance
type
resistance
1-CHKE-V B2ca,s1,d0
90
JXFE-V B2ca,s1,d0
60
PRAKAB PRAŽSKÁ KABELOVNA a.s.
1-CSKH-V180/P30-R (N) HXH-J RE FE180/P90-R
30 SSKFH-V180
90
Kabelovna Kabex a.s.
1-CHKE-V
90
JCXFE-V
60
Lamela Electric a.s.
max. 1500 mm 10 kg not limited 50; 100 mm 62; 125; 250 mm 1,25 mm
60
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page DT
1
2
3
71
KPO 10
2
4
6
77
NSM 6X10
2
4
6
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 47
Cable trays MARS - NKZI - height of sidewall is 50, 100
T
system of cable trays for walls
10
00 max. 15
NPS
NKZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The support structure consists of NPS holders fixed by two KPO 8 fire resistant anchors with the maximum pitch 1500 mm on the base material. NKZI cable trays are connected using an integrated coupling and NSM 6X10 bolts (see connecting of trays pg. 34). Subsequently, it is necessary to attach the cable trays to NPS holders using NSM 6X10 bolts.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables: NKZI 50
List of products for one mounting point:
Manufacturer PRAKAB PRAŽSKÁ KABELOVNA a.s.
Kabelovna Kabex a.s.
power type (N) HXH-J RE FE180/P90-R 1-CSKE-V/h/E90
data resistance
30
60
type SSKFH-V180
JCSFE-V/h/E90
power type
60
30
data resistance
page
resistance
NKZI 100 Manufacturer
max. 1500 mm 10 kg not limited 50; 100 mm 62; 125; 250 mm 1,25 mm
type
resistance
PRAKAB PRAŽSKÁ KABELOVNA a.s.
(N) HXH-J RE FE180/P90-R
30
SSKFH-V180
90
Kabelovna Kabex a.s.
1-CSKE-V/h/E90
60
JCSFE-V/h/E90
30
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
NPS
1
2
3
69
KPO 8
2
4
6
77
NSM 6X10
2
4
6
75
48
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZI - height of sidewall is 100
10
dual sided system for ceiling with use of ceiling profile SPS
max.
KPO 10
1500
SPS S 10X70; M 10; PD 10 DT
NKZI
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile always two brackets DT are mounted always opposite to each other from both sides using bolts S 10X70, nuts M 10, and two pieces of washers PD 10. The cable trays NKZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than three levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Lamela Electric a.s. NKT Cables Kabelovna Kabex a.s. PRAKAB PRAŽSKÁ KABELOVNA a.s.
power
data
type
resistance
type
resistance
1-CHKE-V B2ca,s1,d0
90
JXFE-V B2ca,s1,d0
30
1-CHKE-V
60 -
1-CSKH-V180/P30-R
max. 1500 mm 10 kg 3 100 mm 125; 250 mm 1,25 mm
-
30
JCXFE-V
SSKFH-V180
60
90
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page SPS
1
1
1
70
KPO 10
4
4
4
77
DT
2
4
6
71
S 10X70
2
4
6
76
M 10
2
4
6
74
PD 10
4
8
12
76
NSM 6X10
4
8
12
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 49
Cable trays MARS - NKZI - height of sidewall is 100
T
single sided system for ceiling with use of ceiling profile SPS
10
KPO 10 500
1 max.
SPS
NKZI DT
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile the bracket DT is attached from one side using the bolt S 10X20, the sliding nut PM 41 M 10 (PMP 41 M 10), and the washer PD 10. The cable trays NKZI are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than two levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer NKT Cables
power type 1-CHKE-V
Lamela Electric 1-CHKE-V B2ca,s1,d0 a.s.
max. 1500 mm 10 kg 2 100 mm 125; 250 mm 1,25 mm
data resistance
type
resistance
60
-
-
90
JXFE-V B2ca,s1,d0
30
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page SPS
1
1
70
KPO 10
4
4
77
DT
1
2
71
S 10X20
2
4
76
PM 41 M 10
2
4
77
PD 10
2
4
76
NSM 6X10
2
4
75
50
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZI - height of sidewall is 100
10
system for ceiling with use of threaded rods and assembly profiles MP 41X41
KPOZ ZT
max.
1200
M PD PVL NKZI
MZ MP 41X41
NSM 6X10
Description of the system:
Technical parameters of routes:
The threaded rod ZT is hanged to the ceiling by using of fire resistant anchors KPOZ 10 (12). The assembly profiles MP 41X41 are mounted on threaded rods from the upper part using the nut M 10 (M 12) with the washer PD 10 (PD 12). The bottom anchoring of the assembly profile is carried out using the connecting nut MZ 10 (MZ 12) with the washer PVL 10 (PD 12). The maximum distance of cable hangers is 1200 mm. The cable trays NKZI are firmly attached to the assembly profiles MP 41X41 using bolts S 6X20 M and large washers PVL 6. This system allows assembling of not more than two levels under each other using threaded rods ZT 10 and not more than three levels under each other using threaded rods ZT 12.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer NKT Cables
power type 1-CHKE-V
Lamela Electric 1-CHKE-V B2ca,s1,d0 a.s.
max. 1200 mm 10 kg 3 100 mm 125; 250 mm 1,25 mm
data resistance
type
resistance
60
-
-
90
JXFE-V B2ca,s1,d0
30
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page ZT 10
2
2
-
74
ZT 12
-
-
2
74
KPOZ 10
2
2
-
77
KPOZ 12
-
-
2
77
MP 41X41
1
2
3
69
M 10
2
4
-
74
M 12
-
-
6
76
MZ 10
2
4
-
74
MZ 12
-
-
6
74
PD 10
2
4
-
76
PD 12
-
-
12
76
S 6X20 M
2
4
6
75
PVL 6
2
4
6
76
PVL 10
2
4
-
76
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 51
Cable trays MARS - NKZIN - height of sidewall is 100
T
dual sided system for ceiling with use of ceiling profile SPS
10
max.
1500
KPO 10
SPS S 10X70; M 10; PD 10 DT
NKZIN NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile always two brackets DT are mounted always opposite to each other from both sides using bolts S 10X70, nuts M 10, and two pieces of washers PD 10. The cable trays NKZIN are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than three levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Kabelovna Kabex a.s.
power type 1-CHKE-V
max. 1500 mm 10 kg 3 100 mm 125; 250 mm 1,25 mm
data resistance
60
type JCXFE-V
page
resistance
30
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
SPS
1
1
1
70
KPO 10
4
4
4
77
DT
2
4
6
71
S 10X70
2
4
6
76
M 10
2
4
6
74
PD 10
4
8
12
76
NSM 6X10
4
8
12
75
52
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZIN - height of sidewall is 50; 100
10
single sided system for ceiling with use of ceiling profile SPS KPO 10 max.
1500
SPS S 10X20; PM 41 M 10; PD 10 DT
NKZIN
NSM 6X10
Description of the system:
Technical parameters of routes:
The base of the supporting construction with maintained functionality during a fire is a ceiling profile SPS anchored with four anchors KPO 10. To this ceiling profile the bracket DT is attached from one side using the bolt S 10X20, the sliding nut PM 41 M 10 (PMP 41 M 10), and the washer PD 10. The cable trays NKZIN are attached to brackets DT using screws NSM 6X10. This system allows assembling of not more than two levels under each other with the maximum distance of hanging points of 1500 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Kabelovna Kabex a.s.
power type 1-CHKE-V
max. 1500 mm 10 kg 2 50; 100 mm 62; 125; 250 mm 1,25 mm
data resistance
60
type JCXFE-V
page
resistance
30
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
SPS
1
1
70
KPO 10
4
4
77
DT
1
2
71
S 10X20
2
4
76
PM 41 M 10
2
4
72
PD 10
2
4
76
NSM 6X10
2
4
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 53
Cable trays MARS - NKZIN - height of sidewall is 50
T
system for ceiling with use of threaded rods and assembly profiles MP 41X21
20, 10
KPOZ 10 0
120 max.
NKZIN ZT
M 10
NSM 6X10
MP 41X21
PD 10
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10. MP 41X41 assembly section parts are anchored on threaded rods using M 10 nuts with PD 10 washers.The maximum distance of cable hangers is 1200 mm. The cable trays NKZIN are firmly attached to the assembly profiles MP 41X21 using screws NSM 6X10 and large washers PVL 6. This assembly allows mounting of up to three floors on top of each other.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer
power type
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s. Prysmian Group
max. 1200 mm 10; 20 kg 3 50 mm 62; 125; 250 mm 1,25 mm
data resistance
type
10 kg - 90 SSKFH-V180 20 kg - 60
(N) NXHX-J FE180 10 kg - 90
JE-H(St)H FE 180
page
resistance
10 kg - 90 20 kg - 60 10 kg - 120
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx 120 classification is valid according to ZP 27/2008, 90 classification applies to other standards.
ZT 10
2
2
2
74
KPOZ 10
2
2
2
77
MP 41X21
1
2
3
69
M 10
4
8
12
74
PD 10
4
8
12
76
NSM 6X10
2
4
6
75
PVL 6
2
4
6
76
54
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZIN - height of sidewall is 50
10
system for ceiling with use of threaded rods and assembly profiles MP 41X21X1,50
KPOZ 10 0
120 max.
NKZIN ZT
M 10
NSM 6X10
MP 41X21X1,50
PD 10
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10. MP 41X21X1,50 assembly section parts are anchored on threaded rods using M 10 nuts with PD 10 washers. The maximum distance of cable hangers is 1200 mm. The cable trays NKZIN are firmly attached to the assembly profiles MP 41X21X1,50 using screws NSM 6X10 and large washers PVL 6. This assembly allows mounting of up to three floors on top of each other.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer Kabelovna Kabex a.s.
power type 1-CSKE-V/h/E90
max. 1200 mm 10 kg 3 50 mm 62; 125; 250 mm 1,25 mm
data resistance
type
resistance
30
-
-
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page ZT 10
2
2
2
74
KPOZ 10
2
2
2
77
MP 41X21X1,50
1
2
3
69
M 10
4
8
12
74
PD 10
4
8
12
76
NSM 6X10
2
4
6
75
PVL 6
2
4
6
76
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 55
Cable trays MARS - NKZIN - height of sidewall is 50, 100
T
system for ceiling with use of threaded rods and assembly profiles MP 41X41
10
max.
KPOZ
1200
ZT
NKZIN
M PD PVL MZ MP 41X41 NSM 6X10
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10 (12). The assembly profiles MP 41X41 are mounted on threaded rods from the upper part using the nut M 10 (M 12) with the washer PD 10 (PD 12). The bottom anchoring of the assembly profile is carried out using the connecting nut MZ 10 (MZ 12) with the washer PVL 10 (PD 12). The maximum distance of cable hangers is 1200 mm. The cable trays NKZIN are firmly attached to the assembly profiles MP 41X41 using bolts S 6X20 M and large washers PVL 6. This system allows assembling of not more than two levels under each other using threaded rods ZT 10 and not more than three levels under each other using threaded rods ZT 12.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer NKT Cables
power type 1-CHKE-V
max. 1200 mm 10 kg 3 50; 100 mm 62; 125; 250 mm 1,25 mm
data resistance
type
resistance
60
-
-
The number stated in “resistance� column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page ZT 10
2
2
-
74
ZT 12
-
-
2
74
KPOZ 10
2
2
-
77
KPOZ 12
-
-
2
77
MP 41X41
1
2
3
69
M 10
2
4
-
74
M 12
-
-
6
74
MZ 10
2
4
-
74
MZ 12
-
-
6
74
PD 10
2
4
-
76
PD 12
-
-
12
76
S 6X20 M
2
4
6
75
PVL 6
2
4
6
76
PVL 10
2
4
-
76
56
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable trays MARS - NKZIN - height of sidewall is 50, 100
10
system of cable trays for walls
KPO 10 NSM 6X10 DT (NPS)
0 . 150
max
NKZIN
NSM 6X10
Description of the system:
Technical parameters of routes:
The supporting construction is created by two brackets DT (NPS) attached by two fire resistant anchors KPO 10 (KPO 8) with the distance not exceeding 1500 mm on the base material. The cable trays are connected using the integrated coupling and screws NSM 6X10 (see connecting of trays, pg. 34). Then, the cable trays must be attached to brackets DT using screws NSM 6X10. NPS holders may be used for routes fitted with Kabelovna Kabex a.s. cables – this applies only to the side height of 50 mm.
spacing of hanging points maximum load on 1 m maximum number of successive routes height of the side-wall of cable tray widths of cable trays thickness of metal sheet of cable trays
Fire resistance classification, approved manufacturers of cables: NKZIN 50
List of products for one mounting point:
Manufacturer
power type
data resistance
type
resistance
-
-
NKT Cables
1-CHKE-V
60
Kabelovna Kabex a.s.
1-CSKE-V/h/E90
30
JCXFE-V/h/E90
30
NKZIN 100 Manufacturer NKT Cables Kabelovna Kabex a.s.
power type 1-CHKE-V -
max. 1500 mm 10 kg not limited 50; 100 mm 62; 125; 250 mm 1,25 mm
data resistance
type
resistance
60
-
-
-
JCXFE-V/h/E90
30
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
page DT; NPS - for cable routes fitted with Kabelovna Kabex a.s. cables
1
2
3
71
KPO 10
2
4
6
77
NSM 6X10
2
4
6
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 57
Connection of fire resistant cable ladder KL
KL NSM 6X10
S 60X200
KL
Connection of the cable ladder KL is carried out by using of S 60X200 coupling (pg. 69) and by using of bolts NSM 6X10 (pg. 75)
58
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable ladders
20
system of cable ladders for walls
NSM 6X10 DT KL
0
50 ax. 1
m
Description of the system:
Technical parameters of routes:
The supporting construction is created by two brackets DT attached by two fire resistant anchors KPO 10 with the distance not exceeding 1500 mm on the base material. The cable ladders are connected using couplings S 60X200 and screws NSM 6X10, and are firmly connected to brackets DT using screws NSM 6X10.
spacing of hanging points maximum load on 1 m maximum number of successive routes sidewall height of the cable ladder width of cable ladders
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer PRAKAB PRAŽSKÁ KABELOVNA a.s. Kabelovna Kabex a.s.
power
data
type
resistance
1-CSKH-V180/P30-R (N) HXH-J RE FE180/P90-R
30
1-CSKE-V/h/E90
type SSKFH-V180
30
90 60
-
page
resistance
-
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
DT
1
71
KPO 10
2
77
NSM 6X10
2
75
max. 1500 mm 20 kg not limited 60 mm 150; 200; 300; 400 mm
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 59
Cable ladders
T
system for ceiling with use of threaded rods and assembly profiles MP 41X41 (MP 41X21)
20
KPOZ ZT
0
. 120
max
NSM 6X10 KL
M PD PVL MZ MP 41X41 (MP 41X21)
Description of the system:
Technical parameters of routes:
The threaded rod ZT is is hanged to the ceiling by using of fire resistant anchors KPOZ 10. The assembly profiles MP 41X41 (MP 41X21) are mounted on threaded rods from the upper part using the nut M 10 with the washer PD 10. The maximum distance of cable hangers is 1200 mm. Cable ladders are fixed to MP 41X41 (MP 41X21) assembly section parts using NSM 6X10 bolts and PVL 6 large washers. This assembly allows mounting of up to three floors on top of each other.
spacing of hanging points maximum load on 1 m maximum number of successive routes sidewall height of the cable ladder width of cable ladders
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer
power type
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s. Kabelovna Kabex a.s.
1-CSKE-V/h/E90
max. 1200 mm 20 kg 3 60 mm 150; 200; 300; 400 mm
data resistance
90
60
type SSKFH-V180
-
page
resistance
90
-
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
ZT 10
2
2
2
74
KPOZ 10
2
2
2
77
MP 41X41 (MP 41X21 - for cable routes fitted with Kabelovna Kabex a.s. cables)
1
2
3
69
M 10
4
8
12
74
PD 10
4
8
12
76
NSM 6X10
2
4
6
75
PVL 6
2
4
6
76
60
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T
Cable ladders
20
system of cable ladders directly on walls
KL
NSM 6X10 (2 pcs) KPO 8 KLSU
00 max. 12
S 60X200 NSM 6X10
Description of the system:
Technical parameters of routes:
The cable ladder is fixed on the base material using angle brackets KLSU attached to the sidewall of the ladder in the maximum distance of 1200 mm using screws NSM 6X10 (2 pcs.). The proper installing on the base material is then carried out by means of anchors KPO 8. At this method of anchoring it is possible to install the cable ladder also to ceiling. At this method of anchoring it is necessary to attach the cable using the clamp PKC1 to every cross-piece of the cable ladder.
spacing of hanging points distance of individual levels maximum load on 1 m maximum number of successive routes sidewall height of the cable ladder width of cable ladders
Fire resistance classification, approved manufacturers of cables:
List of products for one mounting point:
Manufacturer
power type
data resistance
60
90
JXFE-V B2ca,s1,d0
60
PRAKAB (N) HXH-J RE PRAŽSKÁ FE180/P90-R KABELOVNA a.s.
90
SSKFH-V180/E90
30
Kabelovna Kabex a.s.
60
Lamela Electric a.s.
90
1-CHKE-V B2ca,s1,d0
page resistance
JE-H(St)H Bd FE 180 E 90
EUPEN
NHXH RE FE 180 E 90
type
1-CSKE-V/h/E90
-
-
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
KLSU
2
71
NSM 6X10
4
75
KPO 8
2
77
max. 1200 mm 100 mm 20 kg not limited 60 mm 150; 200; 300; 400 mm
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 61
Steel pipes system of steel pipes - horizontal placement on ceiling and wall
max.
1200
pipe 60xx
SB 6,3X35 clamp OMEGA 52xx
Description of the system:
Technical parameters of routes:
The base of the supporting construction is formed by steel pipes of the 60xx attached in the row to the base material using Omega clamps. Clamps Omega type 52xx must be attached using bolts for concrete SB 6.3X35. These bolts are screwed into holes with diameter of 5 mm drilled before hand in the concrete. KPO 6 anchor may be used for fixing of clamps. Then, the fire resistant steel pipe is attached to the installed clamps. It is possible to pull a cable of a corresponding diameter through it. For mechanical protection of the cables it is possible to put edge protectors - the installation material offered by KOPOS - on the ends of the pipes.
distance of anchoring points max. 1200 mm maximum load on 1 m only one cable in the pipe maximum number of successive routes not limited
One fire resistant tube may be used for installation of only one cable with the corresponding diameter so that the inner cross-section of the tube is used up maximally up to 60%.
List of products for one mounting point:
The maximum distance of installed clamps is 1200 mm.
page
It is not possible to use systems of pipes for building ascending routes.
Fire resistance classification, approved manufacturers of cables:
Manufacturer
power type
data resistance
type
resistance
Kabelovna Kabex a.s.
1-CHKE-V
60
JCXFE-V
60
Lamela Electric a.s.
1-CHKE-V B2ca,s1,d0
90
JXFE-V B2ca,s1,d0
90
30
SSKFH-V180
60
PRAKAB 1-CSKH-V180/P30-R PRAŽSKÁ KABELOVNA a.s.
The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
52xx
1
80
SB 6,3X35
1
75
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
Metal supporting trunking system of supporting trunking
SPK 200X4,6
600
cable
VPO 6,5X60 trunking 5820
Description of the system:
Technical parameters of routes:
The base of the supporting construction is created by support trunkings 5820 fixed on the base material using fire resistant bolts VPO 6.5X60 anchoring the support trunkings. It is attached to the trunking using metal tightening belts SPK 200X4.6 in the maximum distance 600 mm. The tightening belt should be placed under the trunking and tightened for the diameter of the cable. The unnecessary end of the tightening belt must be removed.
distance of anchoring points max. 600 mm maximum load on 1 m only one cable for one trunking maximum number of successive routes not limited maximální průměr kabelu 16 mm
It is possible to use the line for a wall, ceiling, and also as an ascending line. The maximum length of the vertical line is 3500 mm. If longer routes are used, then it is necessary to create a lifting elbow.
List of products for one mounting point: page
It is possible to use only one cable for one fire resistant support trunking. The maximum distance of anchoring bolts is 600 mm.
power type
1
81
SPK 200X4,6
1
81
Relieving elbow – instead of the relieving elbow, it is possible to use the KPS cable clamp cover (pg. 33); in terms of standardization this is an equivalent solution. With regard to fire classification of KPS cover, the classification of the line consisting of cable clamps is lowered to 60 minutes. Cables placed under the KPS cover must be fixed using PKC clamps (pg. 77) anchored to NP section parts (pg. 23). The supporting section part must be anchored using two KPO 8 anchors on its edges. The maximum distance of anchors must be 250 mm. Therefore, it is necessary to use three KPO 8 anchors for fixing of NP 350 section part.
Fire resistance classification, approved manufacturers of cables:
Manufacturer
VPO 6,5X60
data resistance
type
resistance
NKT Cables
1-CHKE-V
90
-
-
Lamela Electric a.s.
1-CHKE-V B2ca,s1,d0
60
JXFE-V B2ca,s1,d0
60 300
1-CSKH-V180/P30-R
PRAKAB PRAŽSKÁ (N) HXH-J RE KABELOVNA a.s. FE180/P90-R
tolerable radius of cable bending
30 SSKFH-V180
60
90*
* this classification applies only to (N)HXH FE 180/P90-R type cables with the crosssection of 1.5 mm2. The number stated in “resistance” column states the value of maintenance of operability in minutes according to: ZP 27/2008 marked Pxx - R DIN 4102 marked Exx STN 92 0205 marked PSxx
300
62
cable tightening belt SPK 200X4.6 trunking 5820
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 63
cable tray with integrated coupling B
H A
D C
type number
A
H
B
C
D
PO
POF
KZI 60X50X1.25
50
60
3000
∅7 x 25
50
1,25
8595057696082
KZI 60X75X1.25
75
60
3000
∅7 x 25
50
1,25
8595057635661
KZI 60X100X1.25
100
60
3000
∅7 x 25
50
1,25
8595057633551
KZI 60X150X1.25
150
60
3000
∅7 x 25
50
1,25
8595057633568
KZI 60X200X1.25
200
60
3000
∅7 x 25
50
1,25
8595057635685
KZI 60X300X1.25
300
60
3000
∅7 x 25
50
1,25
8595057634930
To secure connections of trays with the integrated coupling it is necessary to use screws NSM 6X10 (pg. 75). Accessories suitable for trays are stated in the part standardized supporting constructions (pg. 19-23).
cable tray with integrated coupling
B
H A D C
type number
A
H
B
C
D
S
F
NKZI 50X62X1.25
62
50
2098
∅7 x 25
50
1,25
2
8595057697447
NKZI 50X125X1.25
125
50
2098
∅7 x 25
50
1,25
2
8595057697454
NKZI 50X250X1.25
250
50
2098
∅7 x 25
50
1,25
2
8595057694538
NKZI 100X125X1.25
125
100
2098
∅7 x 25
50
1,25
4
8595057697515
NKZI 100X250X1.25
250
100
2098
∅7 x 25
50
1,25
4
8595057694552
To secure connections of trays with the integrated coupling it is necessary to use screws NSM 6X10 (pg. 75).
thickness of metal sheet (mm)
amount of bolts for connection
to order
PO
Pre-Galvanized
POF Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
cable tray with integrated coupling - non-perforated
B
H A
type number
A
H
B
S
F
NKZIN 50X62X1.25
62
50
2098
1,25
2
8595057698789
NKZIN 50X125X1.25
125
50
2098
1,25
2
8595057698796
NKZIN 50X250X1.25
250
50
2098
1,25
2
8595057694545
NKZIN 100X125X1.25
125
100
2098
1,25
4
8595057698802
NKZIN 100X250X1.25
250
100
2098
1,25
4
8595057694569
To secure connections of trays with the integrated coupling it is necessary to use screws NSM 6X10 (pg. 75).
cable ladder 60
C B
15
H A
16
64
type number
A
H
B
C
S
F
KL 60X150
150
60
300
3000
1,5
2,21
8595057691681
KL 60X200
200
60
300
3000
1,5
2,30
8595057635487
KL 60X300
300
60
300
3000
1,5
2,47
8595057634947
KL 60X400
400
60
300
3000
1,5
2,64
8595057635494
Connection of ladders is carried out using couplings S 60X200 (pg. 67) and using 16 pieces of screws NSM 6X10 (pg. 75). Perforated sidewalls create the L-profile with a bended tag. Perforated cross-pieces of the C-profile are attached to the sidewalls by pressing through in the distance of 300 mm with the open side of the profile upwards. Accessories suitable for ladders are stated in the part standardized supporting constructions (pg. 19-23). In order to create cable tray branches, it is possible to use the part of the accessories stated in Cable Support Systems catalogue. Sales representative will provide the details.
thickness of metal sheet (mm)
amount of bolts for connection
S
Pre-Galvanized
weight kg/m
to order
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 65
elbow 90°
B
∅7 x 19
H A
type number
A
H
B
S
F
NO 90X50X62
62
50
265
0,8
4
0,31
8595057653900
NO 90X50X125
125
50
328
0,8
4
0,50
8595057653870
NO 90X50X250
250
50
453
1,0
4
1,77
8595057653894
NO 90X100X125
125
100
328
0,8
8
0,70
8595057619012
NO 90X100X250
250
100
453
1,0
8
2,22
8595057653887
O 90X60X50
50
60
250
0,8
8
0,63
8595057627864
O 90X60X75
75
60
275
0,8
8
0,74
8595057627871
O 90X60X100
100
60
300
0,8
8
0,86
8595057627888
O 90X60X150
150
60
350
0,8
8
1,11
8595057627895
O 90X60X200
200
60
400
1,0
8
1,67
8595057627918
O 90X60X300
300
60
500
1,0
8
2,51
8595057627925
O 90X60X400
400
60
600
1,0
8
3,06
8595057627932
Connecting is carried out by direct putting the cable tray on the shaped piece and subsequent fixing by screws NSM 6X10 (pg. 75).
elbow 45°
H
B
A
∅7 x 19
type number
A
H
B
S
F
NO 45X50X62
62
50
168
0,8
4
0,24
8595057678019
NO 45X50X125
125
50
194
0,8
4
0,36
8595057677951
NO 45X50X250
250
50
245
1,0
4
1,12
8595057677975
NO 45X100X125
125
100
194
0,8
8
0,52
8595057677890
NO 45X100X250
250
100
245
1,0
8
1,41
8595057653818
Connecting is carried out by direct putting the cable tray on the shaped piece and subsequent fixing by screws NSM 6X10 (pg. 75).
thickness of metal sheet (mm)
amount of bolts for connection
S
Pre-Galvanized
weight kg/pcs
to order
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
T- p i e c e H
A
C
B
9
∅7
x1
A
type number
A
H
B
C
S
F
NT 50X62
62
50
468
265
0,8
0,39
6
8595057654457
NT 50X125
125
50
531
328
0,8
0,60
6
8595057654396
NT 50X250
250
50
656
453
1,0
2,18
6
8595057654419
NT 100X125
125
100
531
328
0,8
1,03
12
8595057654389
NT 100X250
250
100
656
453
1,0
2,62
12
8595057654402
T 60X50
50
250
450
0,8
12
0,94
12
8595057637443
T 60X75
75
275
475
0,8
12
1,07
12
8595057633339
T 60X100
100
300
500
0,8
12
1,20
12
8595057630338
T 60X150
150
350
550
0,8
12
1,50
12
8595057633575
T 60X200
200
400
600
1,0
12
2,15
12
8595057631717
T 60X300
300
500
700
1,0
12
3,09
12
8595057637467
Connecting is carried out by direct putting the cable tray on the shaped piece and subsequent fixing by screws NSM 6X10 (pg. 75).
cross-over 9
B
∅7
x1
C
A
A
H
66
type number
A
H
B
S
F
NKR 50X62
62
50
468
0,8
0,50
8
8595057676411
NKR 50X125
125
50
531
0,8
0,72
8
8595057676312
NKR 50X250
250
50
656
1,0
2,60
8
8595057676350
NKR 100X125
125
100
531
0,8
0,92
16
8595057676213
NKR 100X250
250
100
656
1,0
3,00
16
8595057653849
KR 60X50
50
60
450
0,8
1,35
16
8595057637696
KR 60X75
75
60
475
0,8
1,50
16
8595057637702
KR 60X100
100
60
500
0,8
1,65
16
8595057637719
KR 60X150
150
60
550
0,8
1,98
16
8595057637726
KR 60X200
200
60
600
1,0
2,67
16
8595057637733
KR 60X300
300
60
700
1,0
3,72
16
8595057637757
KR 60X400
400
60
800
1,0
4,93
16
8595057637764
Connecting is carried out by direct putting the cable tray on the shaped piece and subsequent fixing by screws NSM 6X10 (pg. 75).
thickness of metal sheet (mm)
amount of bolts for connection
S
Pre-Galvanized
weight kg/pcs
to order
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 67
reduction piece H
23
8 2
x3
4
∅7
x1
∅7 x 17
∅7
8
23
type number
H
S
F
NRD 50
50
0,8
0,12
4
8595057667037
NRD 100
100
0,8
0,25
8
8595057667044
SU 60
60
1,0
0,37
4
8595057628380
D
The connection is performed using the screws NSM 6X10 (pg. 75). Serves for additional branching instead of a T-piece. Always to be used in a pair. *length of cut out side wall of the “continual” tray
branch to a tray
D*
NKZI 50X62
262
NKZI 50X125
325
NKZI 100X125
325
NKZI 50X250
450
NKZI 100X250
450
reduction
H ∅7
x2
5
A
B
type number
A
H
B
S
F
NR 50X62
62
44
41
0,8
0,04
2
8595057678842
NR 50X125
125
44
41
0,8
0,05
2
8595057678804
NR 100X125
125
94
41
0,8
0,11
4
8595057678767
SR 60X25
25
50
44
1,0
0,04
4
8595057638426
SR 60X50
50
50
44
1,0
0,05
4
8595057633582
SR 60X75
75
50
44
1,0
0,06
4
8595057638433
SR 60X100
100
50
44
1,0
0,07
4
8595057631755
SR 60X125
125
50
44
1,0
0,08
4
8595057638440
SR 60X150
150
50
44
1,0
0,09
4
8595057638457
SR 60X200
200
50
44
1,0
0,11
4
8595057638464
SR 60X250
250
50
44
1,0
0,13
4
8595057638471
The connection is performed using the screws NSM 6X10 (pg. 75). The reduction is used for the transition between various tray widths with identical height of side walls.
thickness of metal sheet (mm)
amount of bolts for connection
S
Pre-Galvanized
weight kg/pcs
to order
F
Hot Dip Galvanized
68
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
end-piece B
H ∅7
A
x2
5
type number
A
H
B
S
F
NK 50X62
62
44
41
0,8
0,04
2
8595057675537
NK 50X125
125
44
41
0,8
0,05
2
8595057675476
NK 50X250
250
44
41
0,8
0,09
2
8595057675490
NK 100X125
125
94
41
0,8
0,11
4
8595057675391
NK 100X250
250
94
41
0,8
0,19
4
8595057675414
K 60X50
50
50
44
1,0
0,05
4
8595057638235
K 60X75
75
50
44
1,0
0,06
4
8595057635470
K 60X100
100
50
44
1,0
0,07
4
8595057629974
K 60X150
150
50
44
1,0
0,10
4
8595057629981
K 60X200
200
50
44
1,0
0,12
4
8595057629998
K 60X300
300
50
44
1,0
0,16
4
8595057629639
The connection is performed using the screws NSM 6X10 (pg. 75). The end-piece serves for the ending off a line.
partition
B
A1
H A
type number
A
A1
H
B
S
F
NPZ 50
35
10
45
2000
0,7
0,47
5
8595057654198
NPZ 100
35
10
95
2000
0,7
0,75
5
8595057654181
17,5
-
54
3000
0,8
0,50
-
8595057627734
P 60
The fixing of the partition is carried out by screws NSM 6X10 (pg. 75).
thickness of metal sheet (mm)
amount of bolts for connection
S
Pre-Galvanized
weight kg/pcs
to order
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 69
coupling
A
H
∅7 x 25
type number S 60X200
A
H
S
F
200
50
1,25
8
8595057627796
It serves for connecting trays. Fixing is carried out by screws NSM 6X10 (pg. 75).
assembly profile
D F
A
E
C B
type number
A
B
C
F
S
F
MP 41X21
21
41
22
3000 ∅13 x 30
50
2,5
1,85
8595057699557
8595057633469
MP 41X21X1.50
21
41
22
3000 ∅13 x 30
50
1,5
1,13
8595057628939
-
MP 41X41
41
41
22
3000 ∅13 x 30
50
2,5
2,53
8595057631526
8595057632103
D
E
It is used as a support for the installation of ladders or trays when placed on the threaded rods.
wall bracket
A
7
x
B
∅
19
∅9 x 18
type number
A
B
ZNCR
F
NPS 62
82
42
1,5
0,08
1
8595057654136
8595057696266
NPS 125
145
70
2
0,17
2
8595057654112
8595057696273
NPS 250
270
100
2
0,38
2
8595057678712
8595057696280
It is used as a support for mounting of cable trays on the wall.
thickness of metal sheet (mm)
amount of bolts for connection
S
Pre-Galvanized
weight kg/pcs
to order
F
Hot Dip Galvanized
ZNCR Bichromatic galvanised
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
ceiling profile B
A
C
15 x 15
41
21
A
B
C
F
SPL 200
214
120
120
0,74
8595057628557
SPL 300
304
120
120
0,85
8595057632097
SPL 400
424
120
120
1,01
8595057628564
SPL 500
514
120
120
1,13
8595057635067
SPL 600
604
120
120
1,23
8595057628571
SPL 800
814
120
120
1,45
8595057634978
SPL 1000
1024
120
120
1,75
8595057640061
type number
It is designed for fixing of DT holders using two S 10X40 bolts, nuts and PD 10 washers (pg. 76) or PM 41 M 10 sliding nut (pg. 72) and S 10X70 hexagon head bolt (pg. 76).
ceiling profile - medium B
C
A
70
41
41
A
B
C
F
SPS 200
200
120
120
1,03
8595057640139
SPS 300
300
120
120
1,33
8595057633452
SPS 400
400
120
120
1,60
8595057628618
SPS 500
500
120
120
1,90
8595057640146
SPS 600
600
120
120
2,15
8595057628625
SPS 800
800
120
120
2,70
8595057628632
SPS 1000
1000
120
120
3,25
8595057628649
type number
It is designed for single-sided installation of the bracket with use of the sliding nut PM 41 M 10 (pg. 72) and the bolt with hexagonal head S 10X20 (pg. 76).
weight kg/pcs
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 71
bracket - heavy ∅1
2x
20
C D
A
B
∅7
x2
0
A
B
C
D
F
DT 100
100
120
50
44,5
120
0,30
8595057631786
DT 150
150
120
50
52
230
0,36
8595057632592
DT 200
200
120
50
56
340
0,43
8595057631779
DT 250
250
120
50
60,5
450
0,53
8595057636996
DT 300
300
135
50
65
320
0,73
8595057628519
type number
For assembly to the ceiling profile SPL and SPS there are used the sliding nuts PM 41 M 10 together with the bolts S 10X20 (2 pcs, pg. 76).
cable ladder wall bracket
2
x7
70
∅2
∅9
65
type number KLSU
S
F
1,5
0,07
8595568908681
8595568908698
Mounting to the ladder is performed using NSM 6X10 bolts (pg. 75). The 8 mm anchor is used for mounting on the wall. The wall mounting of KLSU cable ladder fully replaces the previously used DRIPN.
weight kg/pcs
F
Hot Dip Galvanized
max. load (kg)
S
Pre-Galvanized
72
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
inner hanger
30
A
90
type number
A
S
F
ZNCR
ZVNI 50X62
57
0,10
8595568903006
-
-
ZVNI 50X125
120
0,18
8595568902726
8595568902733
-
-
0,01
-
-
8595568903594
MN 8
It is mounted using the threaded rod ZT 8. The MN Nut is not part of the hangings.
sliding nut, sliding nut with spring
34
19 6
34
6
19
type number
ZNCR
PM 41 M 10
0,03
8595057628717
PMP 41 M 10
0,04
8595057630468
weight kg/pcs
ZNCR
Bichromatic galvanised
S
Pre-Galvanized
F
Hot Dip Galvanized
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 73
assembly accessory between the anchor and the threaded rod
20
4
∅1
40
type number
F
VS 41X16
5
0,27
8595057634985
For the attaching of the threaded rod to the ceiling. For the creation of a single hanging point it is necessary to use two pieces placed against each other. The threaded bolt may be also anchored using KPOZ type anchors. Both ways are equivalent in terms of the standard.
assembly accessory between the anchor and the threaded rod - 45°
35 ∅13 16
type number
F
VS 41X45
5
0,10
8595057667570
For attaching the threaded rod to the wall at an angle of 45°.
thickness of metal sheet (mm)
weight kg/pcs
F
Hot Dip Galvanized
74
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
threaded rod
A
Ø
A
ZNCR
ZT 10
M10
2000
0,46
8595057628922
ZT 12
M12
2000
0,70
8595057639591
type number
hang nut
A
Ø
A
ZNCR
MZ 10
M10
28
0,04
8595057629929
MZ 12
M12
40
0,06
8595057639584
type number
hexagon nut
ZNCR
M6
0,01
250
8595057633636
M8
0,01
250
8595057633643
M 10
0,01
250
8595057630406
M 12
0,02
250
8595057640818
type number
weight kg/m, weight kg/pcs
pieces in a package
ZNCR Bichromatic galvanised
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 75
carriage bolt and locknut
ZNCR
NSM 6X10
0,007
100
8595057667129
-
NSM 6X10-GMT
0,007
100
-
8595057692947
type number
GMT
bolt with a round head and lock nut
type number S 6X20 M
ZNCR
0,01
250
8595057640825
bolt to concrete
type number SB 6.3X35
PO GMT
100
8595057697904
It serves for fixing OMEGA clamps or independent cable clamps to the base material. The bolt may be used for concrete, natural stone, or solid brickwork. A ∅ 5 mm hole needs to be pre-drilled for mounting of the screw. The supplied surface finish may be used for installation of clamps with PO and PO GMT surface finish (type 6708-6716) and both types of surface finish of OMEGA clamps.
weight kg/pcs
pieces in a package
ZNCR Bichromatic galvanised
GMT non electrolytic plating
76
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
bolt with hexagonal head
ZNCR
S 6X20
0,01
250
8595057630451
S 6X30
0,01
250
8595057640733
S 8X20
0,01
250
8595057638822
S 8X30
0,02
250
8595057640740
S 8X40
0,02
250
8595057640757
S 8X50
0,02
250
8595057640764
S 8X70
0,03
250
8595057640771
S 10X20
0,02
250
8595057628724
S 10X30
0,03
250
8595057628731
S 10X40
0,03
250
8595057640788
S 10X50
0,05
250
8595057698123
S 10X70
0,05
250
8595057698130
S 12X20
0,03
250
8595057633124
S 12X30
0,04
250
8595057633131
S 12X40
0,05
250
8595057640795
S 12X50
0,06
250
8595057640801
type number
washer
A
type number
A
ZNCR
PD 6
12
0,01
250
8595057640832
PD 8
17
0,01
250
8595057633438
PD 10
20
0,01
250
8595057633445
PD 12
24
0,01
250
8595057640849
large washer
A
type number
A
ZNCR
PVL 10
20
0,01
250
8595057633797
weight kg/pcs
pieces in a package
ZNCR Bichromatic galvanised
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 77
A
clamp
B
type number
A min.
B
F
PKC1 1198
6
12
0,03
8595057644878
PKC1 1199
7
16
0,03
8595057644885
PKC1 1200
10
19
0,04
8595057642232
PKC1 1201
14
23
0,04
8595057642249
PKC1 1202
20
26
0,04
8595057635586
PKC1 1203
24
30
0,06
8595057635517
PKC1 1204
25
35
0,07
8595057635401
PKC1 1205
28
38
0,08
8595057635524
PKC1 1206
32
43
0,09
8595057644892
PKC1 1207
42
47
0,10
8595057644908
PKC1 1208
43
51
0,10
8595057635531
PKC1 1209
50
55
0,11
8595057635593
PKC1 1210
52
59
0,14
8595057644915
PKC1 1211
54
63
0,16
8595057644922
PKC1 1212
57
69
0,16
8595057635609
The information means the minimum and maximum diameter of the cable being fastened. The mentioned dimensions are used for basic guidance when selecting clamps for cables. Based on an order, it is possible to supply PKC2 clamps for two cables conforming the conditions of systems maintaining operability in fire.
D
anchor
B
C
B
A
A
type number
A
B
*C
*D
*E
thread
PO
KPO 6X50
6
50
35
5
45
M6
0,01
100
8595057691162
KPO 6X70
6
70
35
10
70
M6
0,02
100
8595057691179
KPO 8X77
8
77
45
10
75
M8
0,03
50
8595057691100
KPO 8X97
8
97
45
30
95
M8
0,04
50
8595057691117
KPO 10X95
10
95
60
10
90
M10
0,06
50
8595057691124
KPO 10X115
10
115
60
30
110
M10
0,08
25
8595057691131
KPO 12X120
12
120
70
10
115
M12
0,10
20
8595057691148
*KPO 12X150*
12
150
70
30
145
M12
0,13
20
8595057691155
KPOZ 10
12
40
-
-
-
M10
0,03
100
8595057692855
KPOZ 12
14
50
-
-
-
M12
0,06
50
8595057692862
*C - anchor depth *D - maximum thickness of the material being attached *E - minimum depth of the drilled hole The fire resistant anchors serve for the attaching of construction elements to the base material (concrete, stone). The knock in anchors KPOZ serve for the direct attachment of the threaded rods. * until the sell-out of stocks
weight kg/pcs
pieces in a package
PO F
Pre-Galvanized Hot Dip Galvanized
78
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
electrical installation pipes
A
∅
B
ČSN type number
∅ outside ∅ inside B (thread)
A
S
F
EOZ
6013 ZNM
20,4
18,2
P13,5
3000
1,7
30
8595057627208
-
-
6016 ZNM
22,5
20,3
P16
3000
1,8
30
8595057626157
-
-
6021 ZNM
28,3
25,7
P21
3000
2,7
30
8595057626164
-
-
6029 ZNM
37
34,4
P29
3000
3,6
15
8595057626171
-
-
6036 ZNM
47
44
P36
3000
5,3
15
8595057626188
-
-
6042 ZNM
54
51
P42
3000
6,1
15
8595057626195
-
-
6013 ZN
20,4
18,2
P13,5
3000
1,7
30
-
8595057618718
-
6016 ZN
22,5
20,3
P16
3000
1,8
30
-
8595057618725
-
6021 ZN
28,3
25,7
P21
3000
2,7
30
-
8595057618732
-
6029 ZN
37
34,4
P29
3000
3,6
15
-
8595057618749
-
6036 ZN
47
44
P36
3000
5,3
15
-
8595057618756
-
6042 ZN
54
51
P42
3000
6,1
15
-
8595057618763
-
6013
20,4
18,2
P13,5
3000
1,7
30
-
-
8595057618657
6016
22,5
20,3
P16
3000
1,8
30
-
-
8595057618664
6021
28,3
25,7
P21
3000
2,7
30
-
-
8595057618671
6029
37
34,4
P29
3000
3,6
15
-
-
8595057618688
6036
47
44
P36
3000
5,3
15
-
-
8595057618695
6042
54
51
P42
3000
6,1
15
-
-
8595057618701
For connection of pipes ČSN it is necessary to order couplings (pg. 78), which replace the already supplied couplings, supplied with tubes.
EN type number
∅ outside ∅ inside B (thread)
A
F
ECZ
6016E ZN
16
12,6
M16x1,5
3000
1,5
30
8595057631304
-
6020 ZN
20
16,2
M20x1,5
3000
2,3
30
8595057631311
-
6025 ZN
25
21,2
M25x1,5
3000
3,0
30
8595057631328
-
6032 ZN
32
28,2
M32x1,5
3000
3,8
21
8595057631335
-
6040 ZN
40
36,2
M40x1,5
3000
5,0
15
8595057631342
-
6050 ZN
50
46,2
M50x1,5
3000
6,0
15
8595057631359
-
6063 ZN
63
58,8
M63x1,5
3000
8,5
15
8595057631595
-
6016E
16
12,6
M16x1,5
3000
1,5
30
-
8595057634152
6020
20
16,2
M20x1,5
3000
2,3
30
-
8595057634169
6025
25
21,2
M25x1,5
3000
3,0
30
-
8595057634176
6032
32
28,2
M32x1,5
3000
3,8
21
-
8595057634183
6040
40
36,2
M40x1,5
3000
5,0
15
-
8595057634190
6050
50
46,2
M50x1,5
3000
6,0
15
-
8595057634206
6063
63
58,8
M63x1,5
3000
8,5
15
-
8595057634213
Couplings are mounted on EN pipes from one side.
weight kg/m
F
Hot Dip Galvanized
EOZ powder coating
meters in a package
S
Pre-Galvanized
ECZ
powder coating
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 79
electrical installation elbows
ČSN ∅ pipes
thread
*90°
S
F
EOZ
6113 ZNM
20,4
P13,5
80
0,17
25
8595057627277
-
-
6116 ZNM
22,5
P16
100
0,22
25
8595057627284
-
-
6121 ZNM
28,3
P21
120
0,37
20
8595057627291
-
-
6129 ZNM
37
P29
155
0,55
20
8595057627307
-
-
6136 ZNM
47
P36
185
1,00
5
8595057627314
-
-
6142 ZNM
54
P42
200
1,38
5
8595057627321
-
-
6113 ZN
20,4
P13,5
80
0,17
25
-
8595057618954
-
6116 ZN
22,5
P16
100
0,22
25
-
8595057618961
-
6121 ZN
28,3
P21
120
0,37
20
-
8595057618978
-
6129 ZN
37
P29
155
0,55
20
-
8595057618985
-
6136 ZN
47
P36
185
1,00
5
-
8595057618992
-
6142 ZN
54
P42
200
1,38
5
-
8595057619005
-
6113
20,4
P13,5
80
0,17
25
-
-
8595057618893
6116
22,5
P16
100
0,22
25
-
-
8595057618909
6121
28,3
P21
120
0,37
20
-
-
8595057618916
6129
37
P29
155
0,55
20
-
-
8595057618923
6136
47
P36
185
1,00
5
-
-
8595057618930
6142
54
P42
200
1,38
5
-
-
8595057618947
type number
*90° - elbow radius For connection of ČSN elbows and pipes it is necessary to order couplings (pg. 78), which replace the already supplied couplings, supplied with elbows and tubes.
EN ∅ pipes
thread
*90°
F
ECZ
6116E
16
M16x1,5
55
0,21
15
-
8595057634367
6120
20
M20x1,5
70
0,27
25
-
8595057634374
6125
25
M25x1,5
115
0,35
25
-
8595057634381
6132
32
M32x1,5
125
0,49
20
-
8595057634398
6140
40
M40x1,5
140
0,55
15
-
8595057634404
6150
50
M50x1,5
170
0,69
5
-
8595057634411
6163
63
M63x1,5
210
0,78
3
-
8595057634428
6116E ZN
16
M16x1,5
55
0,21
15
8595057631366
-
6120 ZN
20
M20x1,5
70
0,27
25
8595057631373
-
6125 ZN
25
M25x1,5
115
0,35
25
8595057631380
-
6132 ZN
32
M32x1,5
125
0,49
20
8595057631397
-
6140 ZN
40
M40x1,5
140
0,55
15
8595057631403
-
6150 ZN
50
M50x1,5
170
0,69
5
8595057631410
-
6163 ZN
63
M63x1,5
210
0,78
3
8595057631670
-
type number
*90° - elbow radius Couplings are mounted on EN elbows from one side.
weight kg/pcs
F
Hot Dip Galvanized
EOZ powder coating
pieces in a package
S
Pre-Galvanized
ECZ
powder coating
80
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s
couplings for electrical installation pipes
ČSN type number
thread
PO
313/3
P13,5
0,04
10
8595057692695
316/3
P16
0,05
10
8595057692701
321/3
P21
0,06
10
8595057692718
329/3
P29
0,07
10
8595057692725
336/3
P36
0,08
10
8595057692732
342/3
P42
0,09
10
8595057692749
Steel couplings are used for connecting of tubes supplied in dimensions according to ČSN. Aluminium couplings, which are the part of supply of tubes according to ČSN, must be replaced by 313/3 - 342/3 series couplings, according to the respective tube diameter.
clamp OMEGA
ČSN pipes
EN pipes
S
F
5220 ZNM
0,015
6013,6213,6016,6216
6020,622
8595057692091
-
5225 ZNM
0,018
6021,6221
6025,6225
8595057692107
-
5232 ZNM
0,022
6029,6229
6032,6232,6040,6240
8595057692114
-
5250 ZNM
0,028
6036,6236
6050,6025
8595057692138
-
5263 ZNM
0,032
6042,6242
6063,6263
8595057692145
-
5216E ZN
0,014
-
6016E, 6216E
-
8595568915269
5220 ZN
0,015
-
6020, 6220
-
8595568915276
5225 ZN
0,018
-
6025, 6225
-
8595568915283
5232 ZN
0,022
-
6032, 6232
-
8595568915290
5240 ZN
0,025
-
6040, 6240
-
8595568915306
5250 ZN
0,028
-
6050, 6250
-
8595568915313
0,032
-
6063, 6263
-
8595568915320
type number
5263 ZN
To facilitate installation the clamp is provided with a groove for insertion; it is not necessary to separate completely the top part of the clamp at the installation. For attaching to the base material it is suitable to use anchors or bolts in the concrete SB 6.3X35.
weight kg/pcs
pieces in a package
F
Hot Dip Galvanized
S PO
Pre-Galvanized Bichromatic galvanised
F I R E R E S I S TA N T S Y S T E M S - n o t s t a n d a r d i z e d s u p p o r t i n g c o n s t r u c t i o n s 81
supporting trunking
C
B
A
type number
A
B
C
5820/20
20
10
3000
0,23
8595057605657
5820/21
20
10
3000
0,22
8595057605664
5820/30
20
10
3000
0,23
8595057605671
5820/31
20
10
3000
0,22
8595057605688
Trunkings Trunkings Trunkings Trunkings Trunkings
are designed for attaching cables using metal tightening belts. 5820/21 and 5820/31 have holes 4.3 x 15 mm cut in the central axis for attaching to the base material. 5820/20 and 5820/30 are without holes. 5820/20 and 5820/21 are with surfacing Zn (layer Zn 10 - 19 Âľm). 5820/30 and 5820/31 are without surfacing.
screw
type number
ZNCR
VPO 6.5X60
0,015
100
8595057698482
It is designed for attaching support trunking to the base material.
tightening belt
type number
IX
SPK 200X4.6
0,002
100
8595057698116
The tightening belt serves for attaching the cable to the support trunking.
weight kg/pcs; weight kg/m
pieces in a package
ZNCR Bichromatic galvanised IX
stainless
82
F I R E R E S I S TA N T S Y S T E M S
cable supporting systems while maintaining the functionality during a fire The risk of fire can never be eliminated, even with the use of various regulations and measures. During a fire the electrical distribution is exposed to high load. Especially in gathering areas the delivery of electricity must be maintained as long as possible for selected electrical equipment in protected escape and intervention routes. Maintaining the delivery of electricity for a stipulated time is achieved using the cable support systems, which function during a fire. The fire resistant cable supporting system, manufactured in Kopos Kolín, fulfills the requirements given by the relevant standard and regulation.
During the designing of the fire resistant cable support systems (up to 1 kV), it is necessary to: - on the basis of the fire report: - know the level of the fire safety of the fire zone, which is determined on the basis of the calculation of the fire risk, the construction system of the building and the height of the building or the floor - characterize the fire resistance of the load bearing constructions inside the fire zone, which do not secure the stability of the building and which do not carry the fire separating structures nor do they form them - know the type of the protected escape line - design and secure the methods of the delivery of electricity from two sources that are independent of each other, serving for securing of fire prevention of the buildings (for example fire elevator, evacuation elevator, firewater boost pump, emergency lighting) so that during the outage of the delivery from one source the deliveries are fully secured from the second source for a period of the assumed function of the equipment - eliminate the effect of the surrounding installations on the cable supporting system - support the suitable construction of the support system according to the level of the necessary fire resistance - select the wires and cables securing the function and the control of the equipment used for the securing of fire prevention for the buildings and stipulate their placement; electrical equipment which does not serve for securing fire prevention of a building are evaluated with regards to fire prevention when a) the wires and cables are placed loose without further protection, b) the weight of the insulation of the wires and cables, eventually the flammable parts of the electrical distributions, exceeds 0.2 kg per m3 - elaborate a “Report about determining external effects” according to the ČSN 33 2000-3 commission wise. The members of the commission are the electrical engineer, the fire technician, the safety technician and the investor. Furthermore, according to the focus of the building there is also present the technology expert and specialists with electrical requirements, as for example air technician, heating technician etc. The members of the commission must also be specialists in the field for which the building is being built.
Testing the fire resistance of the cable supporting systems for integrated maintaining of functionality The fire resistance test is to verify the activity of the cable supporting system of the cable supporting system during a fire and to prove that essential life functions in thebuilding (fire elevators, evacuation elevator, firewater boost pump, emergency lighting, fire alarm, emergency exits…) remain maintained for the stipulated time. A uniform European standard for safety resistance and its testing does not yet exist. The German standard DIN 4102 section 12 is considered as a reference standard: Maintaining the functionality of the cable supporting systems. In the Czech Republic the testing of the fire resistance of the construction of the cable supporting systems is specified by the harmonized standard ČSN EN 1363. Based on this, in the Czech Republic there was created the test regulation ZP 27/2008, stipulating the methods and the conditions for the testing of the resistance of cable routes.
Identical elements of the test regulation ZP 27/2008 and the German standard DIN 4102 sec. 12: -
composition of test samples and norm constructions connection of electrical circuits possibility of partial compensation of placed cables by a steel weight dimensions of cable trays and cable ladders: cable trays: - maximum allowable width 300 mm (perforation percentage 15 ± 5 %) - sidewall height 60 mm - thickness of metal sheet 1.5 mm - weight of cables max. 10 kg/m - distance of supports 1 200 mm cable ladders: - maximum width 400 mm - sidewall height 60 mm - thickness of metal sheet 1.5 mm - weight of cables max. 20 kg/m - ladder cross-pieces at a distance of 150 mm - distance of supports max. 1200 mm
The certified constructions the design of which is consistent with the parameters of the standard are called standardized (standard). KOPOS Kolín produces fire resistant systems conforming to the above stated standards and the regulation. They include cable trays JUPITER KZ with metal sheets thick 1.5 mm and a cable tray with cross-pieces distant 150 mm. The certified constructions the design or dimensions of which are different from the above stated standard and regulation are called non-standardized (non-standard). KOPOS tries to accommodate the demands of its customers as for price and offers them fire-resistant systems for more favourable prices. It is possible to reduce the price of fire resistant routes using a metal sheet of a thickness smaller than the one determined by the standard, fewer supports etc. The standard allows testing of the routes which are then marked as not standardized (non-standard). The non standard routes include the routes created by MARS and JUPITER cable trays with integrated couplings with the metal sheet thickness of 1.25 mm, routes of cable ladders with the distance of cross-pieces 300 mm; further there are supporting metal trunkings, systems with cable catches, routes created by steel pipes, and fire resistant boxes. Differences between the test regulation ZP 27/2008 in the German standard DIN 4102 p. 12: ZP 27/2008
DIN 4102 p. 12
Reference to the standard / regulation
ČSN EN 1363
DIN 4102 part 2
Temperature course of the test
The standard Constant Other fire temperature temperature scenario time curve (°C) (°C)
The standard temperature time curve (°C)
Identifying the classes of fire functionality
part 12
part 2
P 15-R
PH 15-R
-
-
P 30-R
PH 30-R
E 30
F 30
P 60-R
PH 60-R
-
F 60
P 90-R
PH 90-R
E 90
F 90
P 120-R
PH 120-R
E 90
F 120
-
PH 180-R
-
F 180
Cables for systems while maintaining the functionality during a fire: Safety power and data cables with the functionality of resistance against fire must likewise pass fire resistance tests according to the valid regulations.
F I R E R E S I S TA N T S Y S T E M S 83
basic terms and definitions The Czech technical standards providing of rules, instructions or characteristics of activities or their results focused on achieving the optimum level of composition in outlined relations.
Acting by constant temperature: the acting by constant temperature relates to the stressing according to the standard temperature time curve temperature/time at the instant of reaching the temperature of 842 °C. Temperatura Increase
Cable system: includes power cables, insulated power cables, installation cables and wires for telecommunication and equipment for data processing, bus-bars, cable channels, paints, load bearing structures, brackets and clamps. Not standardized construction (non-standard): a certified construction deviating from the standard as for one or more specifications. It doesn't allow transferability of test results to cables of various manufacturers. Standardized construction (standard): the certified construction conforms to the standard in all aspects. It allows transferability of test results to cables of various manufacturers. The standard temperature time curve: the temperatures in relation to time must be maintained for the entire duration of the test according to the so-called “standard temperature time curve”. It is an internationally used temperature course according to the ČSN EN 1363 /formula T = 345 log (8t + 1) + 20, where T= average temperature in the oven in °C and t = time in minutes/, and also according to the DIN 4102-2 /formula ν - νo = 345 log (8t + 1), where ν = fire temperature in K, no = temperature of the testing sample at the beginning of the test in K, t = Time in minutes/. The temperature curve comes forth from the entire course of the fire temperatures. The beginning of the fire = fire occurrence phase. In a very short time there occurs the full unfolding of the fire = “flash-over”. The instance of the flash over and the unfolding of a full fire is displayed by the standard temperature time curve.
TEMPERATURE (°C)
Protected escape line: constantly free communication area, leading to an exit to open space, protected against the effects of fire
Increase of temperatures during the heating up of the test oven according to the standard temperature curve ETK ČSN EN 1363 total temperature time T in °C including (min) the ambient temperature + 20 °C 0 5 10 15 20 30 45 60 90 120 150 180 210 240 300 360
20 576 678 738 781 842 902 945 1006 1049 1082 1110 1133 1153 1186 1214
DIN 4102 part 2 temperature increase ν - νo stated in K 0 556 658 719 822 925 986 1029 1090 1133 1194
TEMPERATURE (°C)
Temperatura Increase
TIME (min)
Constant-temperature curve with the launch according to the ZP 27/2008. Fire safety equipment and measures: the technical and organizational measures for the reduction of the theoretical intensity of an eventual fire, and for the reduction of the economic risk in the evaluated building or its part (for example the fire alarm, automatic stable fire extinguishing equipment, fire ventilation, constant supervision of fire prevention units). Fire safety of buildings: the capability of buildings to prevent, during a fire, the losses of lives or health of persons and losses of property; it is achieved by suitable urban classification of the building’s measures, its structural, area and material design, eventually fire safety equipment and measures. Fire risk of building or its part is determined by the character of the building, its function, technical and technological equipment, construction, area or urban design, fire safety measures etc. and it is expressed by the calculated fire load. Maintaining the functionality of the resistance of the electrical cable systems during fire conditions: during a fire, the thermal acting of the fire does not cause a short or outage of the electrical circuit in the cable system, for a time period determined ahead of time. Acts, decrees, standards The requirements for the characteristics of the cable support systems with integrated maintaining of functionality during a fire arise from the stipulated laws, regulations and standards. The issue of the safety of buildings in relation to the danger of persons during a fire is solved here by the Building Act by its general regulations together with the Law about fire protection. The regulations and government orders then specify and generally condition the technical requirements for the construction, fire protection and prevention. Technical standards in relation to the fire safety of persons specify the general technical accompanying procedures for the securing of the fire safety and resistance. Besides the technical design of constructions, they also address fire safety equipment and delivery of electrical energy. Test of the functionality of the resistance of the system during a fire: test of the support system with installed cables.
TIME (min)
Standard temperature time curve according to the ČSN EN 1363 and according to the DIN 4102 art. 2.
84
F I R E R E S I S TA N T S Y S T E M S
stated and related acts, regulations, standards Act 183/2006 Coll., about ground planning and building order Act no. 133/1985 Coll., about fire protection Act no. 22/1997 Coll., about technical requirements for products Regulation no.137/1998 Coll., about general requirements for construction Regulation no. 246/2001 Coll., about fire prevention Regulation no. 23/2008 Coll., about technical conditions of fire protection of buildings Decree of the government no. 17/2002 Coll. for electrical equipment (lv) Decree of the government no. 163/2002 Coll. and no. 190/2002 Coll. for construction products ČSN 73 0802 Fire safety of buildings- Nonproduction buildings ČSN 73 0804 Fire safety of buildings- Production buildings ČSN 73 0831 Fire safety of buildings – Gathering areas ČSN 73 0810 Fire safety of buildings – Mutual stipulation ČSN 73 0833 Fire safety of buildings – Buildings for living and accommodations ČSN 73 0835 Fire safety of buildings – Buildings for health establishments ČSN 73 0848 Fire safety of buildings - Cable distribution systems DIN 4102-12: November 1998: Conduct of construction material and parts during a fire. Part 12 - Maintaining the functionality of electrical cable devices, requirements and tests. ČSN EN 1363 – 1 Testing the fire resistance ČSN EN 60 332 – 1 - 1 – Mutual methods of tests for cables in fire conditions – Test of resistance against the vertical spreading of flame for wires or cables with a single insulation ČSN EN 50 266 – 1 Mutual methods of tests for cables in fire conditions – test of vertical spreading of flame on vertically mounted bundles 1 or cables ČSN EN 50 267 – 1 Mutual methods of tests for cables in fire conditions – Tests of gases occurring during the burning of the cable material ČSN EN 61 0341 – 1 Measuring the density of the smoke during the burning of electrical cables under defined conditions ČSN IEC 60 331 – 11 Functional capability of the cable during a fire ČSN EN 50 200 – / ed.2 Test method of resistance during a fire for small diameter unprotected cables, designed for use in emergency circuits ZP 27/2008
five levels of corrosion aggressiveness
level
C1
C2
C3
C4
C5
corrosion environment
Interior: dry
Interior: occasional humidity Exterior: free landscape
Interior: high humidity and slightly polluted air Exterior: industrial environment, location close to sea shore Interior: swimming pools, chemical plants etc. Exterior: industrial locations and seaside environment Exterior: industrial pollution with high humidity and high effect of sea environment
Corrosion aggressiveness
average corrosion depletion of the zinc thickness (µm / year)
very low
less than 0,1
low
medium
high
very high
0,1 - 0,7
0,7 - 2
recommended Surface finish ZnCr
(bolts)
S
(trays)
ZnCr - limited
(bolts)
GMT
(bolts)
S
(trays)
GMT
(bolts)
S - limited
(trays)
F, E, P
(trays)
F, E, P
(trays)
IX
(bolts)
F, E, P - limited
(trays)
IX
(trays)
2-4
4-8
The risk of corrosion depends on the intensity of the acting of the external effects according to the standards ČSN EN ISO 14713-1 and ČSN EN ISO 14713-2.
F I R E R E S I S TA N T S Y S T E M S 85
surface treatments and protection against corrosion Corrosion Corrosion is the undesired devaluation of material caused by chemical physically-chemical effects of the environment. These physically-chemical events result in partial or complete disturbance of the material. White rust White rust resembles a cosmetic effect of the coating but does not decrease the resistance against corrosion. It optically damages the zinc picture, but the silver coating and the shine of the freshly zinc coated material will cure and within several weeks it will transfer to a dim grey color. This is the result of the reaction between the zinc and air. That is why according to the standard ČSN EN ISO 1461 the occurrence of this phenomenon can not be the reason for a warranted claim.
zinc steel zinc
Cathodic protection Cathodic protection is a protective mechanism of the zinc layer, which relies on the capability of the transfer zinc ions onto the damaged part of the steel sheet metal. The acting of rainwater, condensation and other electrolytes causes the creation of a galvanic cell between two various metals. A voltage difference occurs here and a less noble metal (zinc) transitions as an anode into the solution, see the picture. That means that with regards to the normal potential the zinc acts as a consumed anode and therefore protects the basic material. This principle applies to the sheet metal thickness of 1.5 mm.
It is possible to protect the steel against corrosion by the following methods of surface treatments
ZNCR electrolytic galvanized products – Bichromatic galvanized – ČSN EN ISO 2081 , DIN 12 330 electrolytic galvanized according to DIN 50 961 with a layer of zinc 10 µm +/- 4 µm (supports for the wall, fastening material, bolts, washers, nuts …)
S
Pre-Galvanized – ČSN EN 10 327, ČSN EN 10 143 galvanized steel Sendzimir: while cold the hot-rolled steelbelt goes after preparation through a continuous bath with liquid zinc. Through this, a layer zinc arises which guarantees the increased corrosion protection. Depending on the product type the thickness of both zinc layers varies from 235 - 275 g/m2, which corresponds to 15 - 27 µm.
F
Hot Dip Galvanized – ČSN EN ISO 1461 The finished pieces made from bare (black) sheet metal are plunged in a melt-bath with liquid zinc, after pre-treatment, at a temperature of 450°C. After removal from the zinc bath a zinc/iron alloy layer system is formed on the bare (black) sheet metal, which is covered with a pure zinc layer. The thickness of the zinc-layer is 50-100 µm, depending on the material thickness.
GMT
non electrolytic plating The base of the DELTA surfacing includes Delta Tone 9000 materials. They are inorganic coats filled with zinc and aluminium micro-lamellas spread in a titanium binder. The method creates a cathodic protection coating the layer of which is 5-15 micrometer thick. This thickness of the layer provides better protection of metals than a thicker layer of zinc created by the zinc dipping method. The method conforms to the European Directive on recycling since it does not include any heavy metals and hexavalent chromium and it is also suitable for small parts. KOPOS KOLÍN supplies also bolts, nuts, couplings and other small connecting accessories with this surfacing and the company also carried out the salt fog test in accordance with ČSN EN ISO 9227 which proved that the coating was not damaged during the action of the salt fog for the period of 300 hours. The long-term temperature constancy is guaranteed up to 180 °C while the surfacing does not show any hydrogen fragility. Based on the above stated reasons we may fully recommend this method of surfacing as an alternative to the zinc dipping method.
painting applying plastic powder in an electrostatic field onto the galvanized product. Increases resistance against corrosion in an aggressive environment (C2 - C5) + esthetic reasons EPOXY - for indoor environment (does not resist UV radiation) - 60 µm POLYESTER - for outdoor environment (resists UV radiation) - 60 µm or 100 µm Color basic design - 19 shades of RAL 9001, 9002, 9003, 9005, 9010, 9016, 7000, 7001, 7012, 7016, 7030, 7035, 7038, 7040, 7042, 7047, 6002, 6005, 6011 (According to individual agreement with the sales department it is possible to deliver other coders in the RAL scale.)
Corrosion resistance of cable trays treated with powder paint A laboratory test has proven that galvanized cable trays painted with powder polyester that were tested in the salt spray for a period of 1 500 hours did not exhibit any signs of blisters or rusting through (the test ISO 6270 for galvanized steel treated with powder plastic prescribes the acting of water only for a period of 720 hours, meanwhile we tested the galvanized trays treated with powder polyester according to the more demanding test ISO 7253 for steel treated with powder plastic, which prescribes the acting of salt spray for a period of 1440 hours). The resistance, tested by us, of the galvanized tray treated with polyester coating also suits the environments with very high corrosive aggressiveness. The polyester coating remains undamaged after the acting of the corrosive effects of the environment, it has high adhesiveness and under it there remains the undamaged zinc coating of the steel core of the cable tray. Galvanized steel treated with powder plastic does not have coating depletion (galvanized steel always has depletion of the zinc coating, according to the environment see table 5 levels of corrosion aggressiveness. With lower financial expenses the painting by powder polyester will secure at least the same corrosion resistance values as Hot-dip galvanization.
86
F I R E R E S I S TA N T S Y S T E M S
alphabetical list of products type number
page
type number
page
type number
page
type number
page
type number
page
6013
78
6013 ZN
78
KL 60X200
18
KZI 60X100X1.25
63
NR 50X125
67
6016
78
6013 ZNM
78
KL 60X200
64
KZI 60X150X1.25
63
NR 50X62
67
6020
78
6016 ZN
78
KL 60X300
18
KZI 60X200X1.25
63
NRD 100
67
6021
78
6016 ZNM
78
KL 60X300
64
KZI 60X300X1.25
63
NRD 50
67
6025
78
6016E
78
KL 60X400
18
KZI 60X50X1.25
63
NSM 6X10
28
6029
78
6016E ZN
78
KL 60X400
64
KZI 60X75X1.25
63
NSM 6X10
75
6032
78
6020 ZN
78
KLSU
27
M 10
29
NSM 6X10-GMT
28
6036
78
6021 ZN
78
KLSU
71
M 10
74
NSM 6X10-GMT
75
6040
78
6021 ZNM
78
KO 90X60X100
20
M 12
29
NT 100X125
66
6042
78
6025 ZN
78
KO 90X60X150
20
M 12
74
NT 100X250
66
6050
78
6029 ZN
78
KO 90X60X200
20
M6
29
NT 50X125
66
6063
78
6029 ZNM
78
KO 90X60X300
20
M6
74
NT 50X250
66
6113
79
6032 ZN
78
KO 90X60X400
20
M8
29
NT 50X62
66
6116
79
6036 ZN
78
KO 90X60X50
20
M8
74
O 90X60X100
19
6120
79
6036 ZNM
78
KO 90X60X75
20
MN 8
72
O 90X60X100
65
6121
79
6040 ZN
78
KPBSKL 150
18
MP 41X21
69
O 90X60X150
19
6125
79
6042 ZN
78
KPBSKL 200
18
MP 41X21
26
O 90X60X150
65
6129
79
6042 ZNM
78
KPBSKL 300
18
MP 41X21X1,50
69
O 90X60X200
19
6132
79
6050 ZN
78
KPBSKL 400
18
MP 41X41
69
O 90X60X200
65
6136
79
6063 ZN
78
KPO 10X115
31
MP 41X41
26
O 90X60X300
19
6140
79
6113 ZN
79
KPO 10X115
77
MS KPS
33
O 90X60X300
65
6142
79
6113 ZNM
79
KPO 10X95
31
MZ 10
27
O 90X60X400
19
6150
79
6116 ZN
79
KPO 10X95
77
MZ 10
74
O 90X60X400
65
6163
79
6116 ZNM
79
KPO 12X120
31
MZ 12
27
O 90X60X50
19
6708
24
6116E
79
KPO 12X120
77
MZ 12
74
O 90X60X50
65
6710
24
6116E ZN
79
KPO 12X150
31
NK 100X125
68
O 90X60X75
19
6712
24
6120 ZN
79
KPO 12X150
77
NK 100X250
68
O 90X60X75
65
8110 PO6
32
6121 ZN
79
KPO 6X50
31
NK 50X125
68
P 60
23
8117 DPO
32
6121 ZNM
79
KPO 6X50
77
NK 50X250
68
P 60
68
8117 PO10
32
6125 ZN
79
KPO 6X70
31
NK 50X62
68
PD 10
30
8117 PO16
32
6129 ZN
79
KPO 6X70
77
NKR 100X125
66
PD 10
76
8135 PO
32
6129 ZNM
79
KPO 8X77
31
NKR 100X250
66
PD 12
30
313/3
80
6132 ZN
79
KPO 8X77
77
NKR 50X125
66
PD 12
76
316/3
80
6136 ZN
79
KPO 8X97
31
NKR 50X250
66
PD 6
30
321/3
80
6136 ZNM
79
KPO 8X97
77
NKR 50X62
66
PD 6
76
329/3
80
6140 ZN
79
KPOZ 10
31
NKZI 100X125X1.25
63
PD 8
30
336/3
80
6142 ZN
79
KPOZ 10
77
NKZI 100X250X1.25
63
PD 8
76
342/3
80
6142 ZNM
79
KPOZ 12
31
NKZI 50X125X1.25
63
PKC1 1198
31
5216E ZN
24
6150 ZN
79
KPOZ 12
77
NKZI 50X250X1.25
63
PKC1 1198
77
5216E ZN
80
6163 ZN
79
KPS
33
NKZI 50X62X1.25
63
PKC1 1199
31
5220 ZN
24
6716E
24
KR 60X100
20
NKZIN 100X125X1.25
64
PKC1 1199
77
5220 ZN
80
6716ED
24
KR 60X100
66
NKZIN 100X250X1.25
64
PKC1 1200
31
5220 ZNM
24
DT 100
71
KR 60X150
20
NKZIN 50X125X1.25
64
PKC1 1200
77
5220 ZNM
80
DT 150
71
KR 60X150
66
NKZIN 50X250X1.25
64
PKC1 1201
31
5225 ZN
24
DT 200
71
KR 60X200
20
NKZIN 50X62X1.25
64
PKC1 1201
77
5225 ZN
80
DT 250
71
KR 60X200
66
NO 45X100X125
65
PKC1 1202
31
5225 ZNM
24
DT 300
71
KR 60X300
20
NO 45X100X250
65
PKC1 1202
77
5225 ZNM
80
DTBS 100
25
KR 60X300
66
NO 45X50X125
65
PKC1 1203
31
5232 ZN
24
DTBS 150
25
KR 60X400
20
NO 45X50X250
65
PKC1 1203
77
5232 ZN
80
DTBS 200
25
KR 60X400
66
NO 45X50X62
65
PKC1 1204
31
5232 ZNM
24
DTBS 300
25
KR 60X50
20
NO 90X100X125
65
PKC1 1204
77
5232 ZNM
80
DTBS 400
25
KR 60X50
66
NO 90X100X250
65
PKC1 1205
31
5240 ZN
24
K 60X100
21
KR 60X75
20
NO 90X50X125
65
PKC1 1205
77
5240 ZN
80
K 60X100
68
KR 60X75
66
NO 90X50X250
65
PKC1 1206
31
5250 ZN
24
K 60X150
21
KSBS 100
17
NO 90X50X62
65
PKC1 1206
77
5250 ZN
80
K 60X150
68
KSBS 150
17
NP 100
23
PKC1 1207
31
5250 ZNM
24
K 60X200
21
KSBS 200
17
NP 150
23
PKC1 1207
77
5250 ZNM
80
K 60X200
68
KSBS 300
17
NP 200
23
PKC1 1208
31
5263 ZN
24
K 60X300
21
KSBS 50
17
NP 250
23
PKC1 1208
77
5263 ZN
80
K 60X300
68
KSBS 75
17
NP 350
23
PKC1 1209
31
5263 ZNM
24
K 60X50
21
KZ 60X100X1.50
17
NPS 125
69
PKC1 1209
77
5263 ZNM
80
K 60X50
68
KZ 60X150X1.50
17
NPS 250
69
PKC1 1210
31
5820/20
81
K 60X75
21
KZ 60X200X1.50
17
NPS 62
69
PKC1 1210
77
5820/21
81
K 60X75
68
KZ 60X300X1.50
17
NPZ 100
68
PKC1 1211
31
5820/30
81
KL 60X150
18
KZ 60X50X1.50
17
NPZ 50
68
PKC1 1211
77
5820/31
81
KL 60X150
64
KZ 60X75X1.50
17
NR 100X125
67
PKC1 1212
31
F I R E R E S I S TA N T S Y S T E M S 87
alphabetical list of products type number
page
type number
page
PKC1 1212
77
SPL 800
25
PM 41 M 10
72
SPL 800
70
PMP 41 M 10
72
SPS 1000
70
PVL 10
30
SPS 200
70
PVL 10
76
SPS 300
70
PVL 12
30
SPS 400
70
PVL 6
30
SPS 500
70
S 10X20
29
SPS 600
70
S 10X20
76
SPS 800
70
S 10X30
29
SR 60X100
22
S 10X30
76
SR 60X100
67
S 10X40
29
SR 60X125
22
S 10X40
76
SR 60X125
67
S 10X50
29
SR 60X150
22
S 10X50
76
SR 60X150
67
S 10X70
29
SR 60X200
22
S 10X70
76
SR 60X200
67
S 12X20
29
SR 60X25
22
S 12X20
76
SR 60X25
67
S 12X30
29
SR 60X250
22
S 12X30
76
SR 60X250
67
S 12X40
29
SR 60X50
22
S 12X40
76
SR 60X50
67
S 12X50
29
SR 60X75
22
S 12X50
76
SR 60X75
67
S 60X200
69
SU 60
22
S 6X20
29
SU 60
67
S 6X20
76
T 60X100
19
S 6X20 M
28
T 60X100
66
S 6X20 M
75
T 60X150
19
S 6X30
29
T 60X150
66
S 6X30
76
T 60X200
19
S 8X20
29
T 60X200
66
S 8X20
76
T 60X300
19
S 8X30
29
T 60X300
66
S 8X30
76
T 60X400
19
S 8X40
29
T 60X50
19
S 8X40
76
T 60X50
66
S 8X50
29
T 60X75
19
S 8X50
76
T 60X75
66
S 8X70
29
VPO 6.5X60
81
S 8X70
76
VS 41X16
26
SB 6.3X35
28
VS 41X16
73
SB 6.3X35
75
VS 41X45
26
SK 60
23
VS 41X45
73
SO 90X60X100
21
ZT 10
27
SO 90X60X150
21
ZT 10
74
SO 90X60X200
21
ZT 12
27
SO 90X60X300
21
ZT 12
74
SO 90X60X400
21
ZVNI 50X62
72
SO 90X60X50
21
ZVNI 50X125
72
SO 90X60X75
21
SPK 200X4.6
81
SPL 1000
25
SPL 1000
70
SPL 1200
25
SPL 200
25
SPL 200
70
SPL 300
25
SPL 300
70
SPL 400
25
SPL 400
70
SPL 500
25
SPL 500
70
SPL 600
25
SPL 600
70
type number
page
type number
page
88
F I R E R E S I S TA N T S Y S T E M S
Electrotechnical world LIVE!
NO.1 in the Czech Republic JUST WRITE!
www.elektrika.TV
www.kopos.com www.pozarniodolnost.cz