EAO_ECOPOWER_pss

Page 1

EcoPower PSS

Technical Data General characteristics The switching power supplies use a FLYBACK converter. The output voltage is regulated with a tolerance of +/- 3 % with a charge variation from 0 to 100% and with input voltage variations (See the limits on the table). • No minimum load required The equipment starts regularly in all the nominal input range with zero load on the output, while maintaining the output voltage within 0,5% of nominal output voltage. • No Hiccup-mode during overload or short circuit The equipment works regularly in constant current mode during overload up to a full short-circuit (zero output voltage), without stopping or going in burst mode (called Hiccup-mode). This condition can be maintained indefinitely without any damage or performance degradation. This feature helps starting loads with high inrush current or great capacitive load. • High stability / high open loop bandwidth and phase margin This features gives very good behavior of the equipment with rapidly changing load (from zero to max load and vice versa) and during start up, without ringing and overshoot. • Operating-condition signaling A LED provides the optical indication of the output voltage: good operation, overload condition, short-circuit condition. • Continuous input voltage The power supplies accept a continuous input voltage from 130VDC to 350VDC.

Scheme

Fuse NTC

EMC Filter

Rectifier Input

PWM Control

Rectifier Output

Input Lines

Output Supply Optocoupler

Auxiliary converter

Power supplies

Alarm Systems

U/I Measure

Data Logger


EcoPower PSS Technical data Input voltage Nom. Output voltage Output voltage Ripple Min. load Nominal power Overload protection Ambient temperature Technology Safety norm Test voltage prim/sec Weight Color of housing Connections

Table 1 Table 1 Fix < 100 mV 0 Table 1 Electronic -20 .. +40 째C Primary switched EN 60950 3750 V / 1 min. Table 1 RAL 7035 2 Screw terminal 1.5mm

Input frequency Tolerance of output voltage Nominal output current Output current limitation Short circuit output current Efficiency Short circuit protection Relative humidity Switching frequency EMC-Norm MTBF(MIL HDBK217) Housing Protection degree Operation signaling

Operation signaling:

LED on during nominal function range LED off on overload and short circuit Output

Part no.

Type

Input

862.331.212 862.331.220 862.331.230 862.331.240 862.331.250 862.332.406 862.332.410 862.332.420 862.332.425 862.332.430 862.332.440

PSS121.2 PSS122 PSS123 PSS124 PSS125 PSS240.6 PSS241 PSS242 PSS242.5 PSS243 PSS244

90-260VAC 90-260VAC 90-260VAC 90-260VAC 230VAC +/-15% 90-260VAC 90-260VAC 90-260VAC 90-260VAC 230VAC +/-15% 230VAC +/-15%

Nominal 12VDC 12VDC 12VDC 12VDC 12VDC 24VDC 24VDC 24VDC 24VDC 24VDC 24VDC

1,25A 2A 3A 4A 5A 0,63A 1A 2A 2,5A 3A 4A

15W 24W 36W 48W 60W 15W 24W 48W 60W 72W 96W

I lim

I cc

1,5A 2,5A 4,4A 4,4A 5,2A 0,8A 1,5A 2,25A 3A 5A 5A

2A 3A 5A 5A 5,2A 1,2A 2A 2,7A 3,3A 5,8A 5,8A

48 .. 63 Hz +/- 3 % Table 1 Table 1 (I lim) Table 1 (I cc) > 85 % Electronic 90 % max. Table 1 EN 55055 /B 120'000 h Table 1 IP 20 Green LED

Frequency

M

Form

100kHz 100kHz 70kHz 70kHz 70kHz 100kHz 100kHz 70kHz 70kHz 70kHz 70kHz

135g 135g 380g 390g 400g 135g 185g 355g 355g 400g 400g

3M 5M 8M 8M 8M 3M 5M 8M 8M 8M 8M

Table 1

Form 3M (b x h x t) 52 x 93 x 68

1 2

3 4

Housing Connection cover Clip for DIN-rail mounting Label

Form 5M (b x h x t) 87 x 93 x 66

5 6

7 8

Form 8M (b x h x t) 140 x 93 x 66

Guide for DIN-rail mounting Input clamps Output clamps Connection cover D475.51622e Index -

APS electronic AG Bahnhofstrasse 135 CH-4626 Niederbuchsiten

www.apsag.com Facsimile +41 (0)62-389 88 80 Phone +41 (0)62-389 88 88