TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-1

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters

July 2007

CA08101001E

Contents Description

Page

Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Facility-Wide Power Protection Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . Surge Suppression Products Surge Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Residential Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Service Entrance Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clipper Power System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Visor Series Integrated. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Visor Series Retrofit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clipper VL (CVL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AEGIS Powerline Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Datacom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Conditioning Products Sag Ride Through (SRT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electronic Voltage Regulator (EVR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Factor Correction Capacitor Banks and Harmonic Filters Power Facter Correction Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UNIPUMP Power Factor Correction Capacitors . . . . . . . . . . . . . . . . . . . UNIPAK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UNIPAK Filter — Harmonic Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AUTOVAR 300 Automatic Power Factor Correction Capacitor Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AUTOVAR 600 Automatic Power Factor Correction Capacitor Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AUTOVAR Filter — LV Automatic Harmonic Filter. . . . . . . . . . . . . . . . . . . Transient-Free Static Switching Power Factor Correction Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Active-Harmonic Filter-Harmonic Correction Units . . . . . . . . . . . . . . . . . .

10-2 10-4 10-5

Industrial Surge Protection Products

For more information visit: www.eaton.com

10-6 10-6 10-7 10-13 10-15 10-16 10-20 10-21 10-25

10 10-26 10-29 10-31 10-33 10-35 10-35 10-42 10-44 10-48 10-51 10-54


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Product Overview

10-2

July 2007

Protection

Product Overview Residential Protection CHSP Series: Cutler-Hammer whole home Surge Protectors by Eaton Corporation for whole house protection installed at the loadcenter. ■ Surge Strip Series: Plug-in surge strips for home and commercial applications. ■

Family of CHSP Products

10 SurgeTrap Family

ac Electrical Distribution Protection Clipper Power System (CPS) Visor Series and CVL Clipper VL: Commercial/nonessential branch panels. ■ Visor and CVL Retrofits: Suppressors externally mounted to distribution equipment. ■ Visor Integrated Applications: Suppressors built into switchboards, panelboards, motor control centers and busways. ■ Visor OEM: Surge suppression designed to facilitate easy integration in all types of gear. ■

CVL Retrofit

Visor Retrofit

Visor Integrated Applications

Visor OEM Offering

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-3 Product Overview July 2007

Protection

Critical Load Protection

Datacom Protection

AEGIS-HW: Series filters for up to 20 amperes, single-phase (protection for PLCs, control equipment). ■ AEGIS-VL: Hardwired surge filter that protects critical loads up to 5 amperes. ■ AEGIS+: Series filter 20 – 100 amperes (single- and 3-phase) for robotics, rectifiers, automation equipment. ■ OEM Components: A wide variety of components for domestic/ international applications (including military).

Protect your data and communication lines with Eaton’s Cutler-Hammer Datacom surge protection products. Products include:

■ ■ ■ ■ ■

Modular protection for multi-pair applications. Hardwire connected (1 or 2 pair protectors). Wiring connectors (D89, DB25 and RJ11). Coaxial cable protection. Mounting hardware.

10

AEGIS Products

Datacom Products

Telecommunications Protection The Cutler-Hammer Clipper Power System — Visor Series Tc Panelboards, electrical distribution products, and family of surge protection devices are the total downtime protection package solution for your wireless telecommunications shelter.

Visor Tc Panelboards ■ ■

■ ■ ■ ■ ■

CA08101001E

Available in standard and custom configurations. Ratings: ❑ 120/240 Vac, single-phase, 3-wire ❑ 208Y/120 Vac, 3-phase, 4-wire ❑ 480Y/277 Vac, 3-phase, 4-wire ❑ 600Y/347 Vac, 3-phase, 4-wire (Other voltage configurations are available.) Copper bus. 12, 18, 24, 30, 36 and 42 circuits. Bolt-on branch breakers. A full range of factory installed modifications and accessories. Fully rated or series rated.

For more information visit: www.eaton.com

Innovative Electrical Distribution and Power Quality Solutions for Telecommunications Facilities

Power Conditioning Sag Ride Through (SRT) The Sag Ride Through (SRT) is a power conditioner that corrects voltage sags to maintain uptime and productivity.

Electronic Voltage Regulator (EVR) The Electronic Voltage Regulator (EVR) is designed to meet the needs of customers who experience voltage regulation problems due to brownout conditions from their electric utilities.


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Product Overview

10-4

July 2007

Applications

Application Recommendations Table 10-1. Application Guide for Surge Products Application Type

Eaton’s Cutler-Hammer Surge Products

Features and Competitive Advantages

■ CHSP™ Complete Home Surge Protector. ■ Surge Strip Series™ plug-in surge protection.

■ CHSP protects all residential loads. ■ Only product available with three levels of protection (ac, telephone, cable). ■ Single point ground eliminates differential ground voltages. ■ SurgePlane™ construction. ■ Value-added package for contractors and home builders.

Residential ■ Home office ■ 120/240 volt loads

Light Commercial ■ Design build ■ Chain stores ■ Small facilities

10

■ Clipper VL. ■ Ideal package for any commercial facility. ■ Clipper Power System — Visor Series Retrofit ■ Cost-effective protection using CPS100 or eight (8) models. CVL protection. ■ Clipper Power System — Visor Series Integrated eight (8) models. ■ Surge Strips plug-in surge protection (commercial grade).

Large Projects Including: ■ Commercial ■ Government ■ Schools ■ Institution ■ Military

■ Clipper Power System — Visor Series Integrated eight (8) models available in panelboards, switchboards, MCCs, switchgear, busway and automatic transfer switches. ■ Clipper VL. ■ Clipper Power System — Visor Series Retrofit eight (8) models. ■ Data signal link protectors. ■ AEGIS for critical load applications. ■ Power Conditioners (models: SRT and EVR).

■ Able to meet any competitor TVSS specification. ■ Significant performance advantage using integrated Visors (the preferred choice of consultants). ■ Quick-ship capabilities from satellites and service centers. ■ The industry’s most comprehensive diagnostics ensure safe operation. ■ Third party tested. ■ Sag correction for low and medium voltage applications.

■ Visor Series MCC (Motor Control Center). ■ Clipper VL. ■ Clipper Power System — Visor Series Integrated and Retrofit (switchgear, switchboards, busway, panelboards and automatic transfer switches). ■ AEGIS powerline filters for critical loads (PLCs, robotics, etc). ■ Datacom protectors. ■ Sag Ride Through (SRT) power conditioner. ■ Electronic Voltage Regulator (EVR).

■ Visor Series MCC offers surge suppression for drives (available for retrofit and new installations). ■ AEGIS products are industry leaders for critical load protection (DIN rail mounting, extended warranty for connected PLC power supplies). ■ Facility-wide solutions. ■ Protection for drive/motor applications. ■ SRT — power conditioning for voltage sag problems. ■ EVR — ideal for voltage regulation problems.

■ Clipper Power System — Visor Series Caseless and Retrofit. ■ Clipper VL. ■ AEGIS powerline filter. ■ Other custom components. ■ Power conditioners. ■ Datacom protectors.

■ 20 years experience in OEM applications. ■ Ability to meet customized requirements. ■ Application engineering assistance. ■ CE approval (AEGIS filters) ideal for international integrators. ■ Small footprint series and parallel power filters.

■ Tc Panelboards (Visor Series (TVSS), transfer switch). ■ QuarterWave (TQP) protectors for RF coaxial lines. ■ AEGIS+. ■ Clipper VL. ■ Engineering design support.

■ Complete solution for protecting cellular (or PCS, microwave, GPS) base stations. ■ Independently tested at lightning labs. ■ Experience in worldwide applications. ■ Ability to meet customized requirements.

Industrial Including: ■ Small and large facilities ■ WWTP

OEM Any OEM customer including: ■ Integrators ■ Medical equipment ■ Automation and control

Telecommunications Including: ■ Cellular sites ■ Microwave ■ PCS ■ Paging systems

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-5 Product Overview July 2007

Facility-Wide Power Protection Solutions

Facility-Wide Power Protection Solutions A facility-wide protection approach should be employed to address power quality issues. This approach minimizes overall lifecycle costs and optimizes facility uptime. The following is a recommended design approach for implementing facility-wide Eaton’s CutlerHammer power protection solutions.

The most accepted design methodology is based on two concepts: 1. Ensure proper grounding conditions exist. All forms of power protection/conditioning rely on good grounding, bonding and earthing practices. 2. Surge protection should be installed at key distribution panels and critical loads.

10

Figure 10-1. Application of Surge Protection/Voltage Regulation and Sag Correction Devices

CA08101001E

For more information visit: www.eaton.com


10-6

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Residential Surge Protection July 2007

Surge Protective Devices

Product Description

Application Description

Stage 1: Primary Protection for Service Entrance

The Problem

Two-Stage Protection

Due to the evolution of electronics and microprocessors in the home, we are continually challenged to provide quality (clean) power for electronic loads such as appliances, computers/ home office and entertainment systems. Surges (also known as transients) due to lighting, utility grid switching and other sources travel on current carrying conductors throughout the home, which can effect and destroy sensitive electronic loads.

The Institute of Electrical and Electronic Engineers (IEEE) recommends two stages of surge suppression to provide the best protection for electronic equipment. Two-stage surge suppression should be provided for all cables entering a home, including power, Internet, coaxial and telephone.

The best place to install surge protection is at the electrical entrance point (loadcenter or breaker panel). This is often where ac power, telephone lines and cable lines are located. Applying a CHSP product to your service entrance (stage 1) will reduce a voltage surge to an acceptable level for appliances and surge strips (see Figure 10-3). For added protection, it is recommended that you install surge protection for your cable and telephone lines at the service entrance. Your ac, cable and telephone lines will all have the same ground potential, in one common location, for passing the surge away from your equipment.

The Solution

Stage 2: Secondary Protection for Point-of-Use A quality Cutler-Hammer SurgeTrap surge strip is recommended for sensitive electronic loads like computers or entertainment centers. Using a SurgeTrap surge strip (stage 2) reduces any voltage remnant down to an acceptable level. Figure 10-2. Two-Stage Protection

20,000 V

Let Through Voltage (V)

10

Eaton has developed the most comprehensive family of surge protection devices and lightning arresters installed at service entrance and point-of-use locations, providing quality power required for sensitive electronic loads.

High Energy Transient Disturbance Input at Main Panel - IEEE Category C3 Impulse (Combination) Waveform, 20,000 V, 10,000 A

10,000 V Best Achievable Performance with CHSP at 120/240 Volt Loadcenter (Stage 1)

400 V Two stage use of Surge Strips (cascade approach ) achieves best possible surge protection (Stage 2)

0 25ÂľS Time (microseconds)

50ÂľS

Figure 10-3. Surge Voltage Remnant Comparison

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-7 Residential Surge Protection July 2007

Service Entrance

Service Entrance Surge Protection Factory Installed

Telephone and Cable Accessories Type CHSP Eaton also offers a full range of accessory products for telephone and cable, including SurgeTel which protects up to four telephone/modem lines; SurgeCable which protects up to two cable/ satellite lines; and SurgeEthernet featuring protection for high speed Internet hookups.

Home Electronics Protection Panel

Industry Breakthrough Eaton is the first to introduce a factory installed surge protection device that is mounted inside a 120/240 volt loadcenter.

Telephone, Cable and Ethernet

Lightning Arresters

Type CHSUR The CHSUR loadcenter provides a customer with the lowest system let-through voltage (best protection) when compared to traditional remote/side mounted devices. The Home Electronic Protection Panel (HEP) is an internally mounted unit that provides industrial level surge protection in a residential design. The HEP is available with 70 kA/phase surge current complete with audible alarm and thermal fusing and provides protection for all residential electrical equipment by reducing power surges, often caused by lightning, to an acceptable level for appliances and electronics.

Remote/Side Mounted Type CHSP The Cutler-Hammer Surge Protector (CHSP) is an externally mounted unit that provides industrial level surge protection in a residential design. The CHSP is available in four models and provides protection for all residential electrical equipment by reducing power surges, often caused by lightning, to an acceptable level for appliances and electronics. These units can be mounted in any manufacturer’s breaker panel (loadcenter).

For use on single-phase 120/240 Vac systems. This easily plugs into a single-phase Type BR loadcenter and occupies two 1-inch (25.4 mm) pole spaces similar to a 2-pole Type BR breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire loadcenter. If internal components are damaged, the BRSURGE LED visual indicators will signal the need for replacement. This device is suitable for service entry locations installed in accordance with NEC Article 280. The BRSURGE is ideal for protecting sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.

CHSA Surge Protector

Type CHSA For use on single-phase 120/240 Vac systems. This easily plugs into a single-phase Type CH loadcenter and occupies two 3/4-inch (19.1 mm) pole spaces similar to a 2-pole Type CH breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire loadcenter. If internal components are damaged, the CHSA LED visual indicators will signal the need for replacement. This device is suitable for service entry locations installed in accordance with NEC Article 280. The CHSA is ideal for protecting sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.

ac Power (Also Includes Cable/Telephone)

CA08101001E

BRSURGE Surge Protector

Type BRSURGE

For more information visit: www.eaton.com

CHQSA Surge Protector

Type CHQSA For use on single-phase, 120/240 Vac systems. This easily plugs into a Square D , single-phase loadcenter Type QO and occupies two 3/4-inch (19.1 mm) pole spaces similar to a standard 2-pole Type QO breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire loadcenter. If internal components are damaged, the CHQSA LED visual indicators will signal the need for replacement. This device is suitable for service entrance locations installed in accordance with NEC Article 280 and are UL Classified to be used in place of Square D Type QO surge arresters. The CHQSA is ideal for protecting sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.

10


10-8

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Residential Surge Protection July 2007

Home Electronics

Service Entrance Surge Protection (Continued)

CHSA01 Surge Protector

10

Point-of-Use Surge Protection Eaton’s Cutler-Hammer Surge Strip series, plug-in surge protectors offer exceptional protection for electrical and electronic devices. Each of the Surge Strip series, Ultra, Max and Micro are available in ac only, ac plus telephone/modem and ac plus cable. The Ultra Series 3-Way, in addition to having the above options, is available in ac plus telephone/modem and cable. Construction series surge strip products are also available.

CHSA01 — For use on single-phase, 120/240 Vac systems. This surge protector can be easily installed in the enclosure of indoor or outdoor loadcenters by using the 1/2-inch (12.7 mm) threaded nipple. It is ideal for protecting outdoor lighting, garages, sump and irrigation pumps, etc.

Point-of-Use Surge Strips CHSA03 Surge Protector

CHSA03 — For use on three-phase, 600 Vac systems. This surge protector can be easily installed in the enclosure of indoor or outdoor loadcenters by using the 1/2-inch (12.7 mm) threaded nipple. It provides protection for commercial electrical services especially those using electric motors.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-9 Residential Surge Protection July 2007

Technical Data and Specifications

Technical Data and Specifications Table 10-2. Lightning Arresters Description

Discharge Voltage, Vac 1.5 kA

Surge Protector Plug-On Type CH, Single-Phase, 120/240 Vac Surge Protector Plug-On Type BR, Single-Phase, 120/240 Vac Surge Protector Plug-On Type CHQ, Single-Phase, 120/240 Vac Surge Protector, 2-Pole Single-Phase, 3-Wire, 120/240 Vac Surge Protector, 3-Pole Single-Phase, 4-Wire, 120/240 Vac

10 kA

Lead Length Inches (mm)

500 500 500

545 545 545

8.00 (203.2) 8.00 (203.2) 8.00 (203.2)

980 2510

1410 3800

15.00 (381.0) 15.00 (381.0)

3 kA

5 kA

345 345 345

370 370 370

490 1700

640 2100

Catalog Number CHSA BRSURGE CHQSA CHSA01 CHSA03

Table 10-3. Surge Protection Devices Description

System Voltage

Protection Surge Modes Current Capacity

CHSP Micro 120/240

L-G

CHSP Max

L, L, N, G

120/240

UL Let- Telephone Coaxial through Protection Protection Voltage

20,000 A 400 per Phase 750 Joules 50,000 A 400 per Phase 1500 Joules

Maximum Continuous Operating Voltage

EMI/RFI Capac- Installation/ Noise itance Enclosures Rejection (L-N)

Agency Catalog Approvals Number

UL 1449 (2nd Ed.), CSA UL 1449 (2nd Ed.), CSA

150

150

CHSP 3-Way 120/240

L, L, N, G

75,000 A 400 per Phase 3500 Joules

4 Pair, Terminal Mount

Patented High 150 Frequency “F” Connectors 1 Line Protected — 150

CHSP Ultra

120/240

L, L, N, G

75,000 A 400 per Phase 3500 Joules

CHSP – Field 120/240 Retrofit Kit

L, L, N, G

75,000 A 400 per Phase 3500 Joules

230 Vdc — Breakdown Voltage

10,000 A per Phase

SurgeCable 145 Vdc — Breakdown Voltage

5,000 A per Phase

Surge Ethernet

300 A per Phase

2 or 4 Pair — — UTP or Category 5 Lines — Patented High — Frequency “F” Connectors 2 Lines Protected 8 Wires — — (4 Pair)

N/A

N/A

N/A

N/A

N/A

72,000 A per Phase 900 Joules Total

330

No

No

Yes

No

No

Yes

SurgeTel

30 Vdc — Breakdown Voltage Flushmount N/A N/A Kit Surge Strip 120 All Micro Modes

Indoor/ Outdoor Enclosure — Indoor/ Outdoor Enclosure Flushmount Kit Available < 15pf, Indoor/ Low Flushmount Signal Enclosure Loss — Indoor/ Outdoor Enclosure Flushmount Kit Available — Mounts in any Type CHPC Loadcenter (see Table 10-7) — Indoor Application

UL 1449 (2nd Ed.), CSA

CHSPULTRA

UL 1449 (2nd Ed.), CSA

CHSPULTRALCRK

UL 497A, CSA

DHW4PT

< 15pf, Indoor Low Application Signal Loss < 70pf Indoor Application

UL 6500, CSA

DCXCAB2

UL 497B

DRJ45D30R

N/A

N/A

N/A

N/A

CHSPFMKIT

150

Up to 15 dB (Peak)

Indoor Application

UL 1449 (2nd Ed.), UL 1363, UL 497A, CSA

UL 1449 (2nd Ed.), UL 1363, UL 497A, CSA UL 1449 (2nd Ed.), UL 1363, UL 497A, CSA

MICRONET1 SGXMICROAC6 MICRONET1 SGXMICRONET6 MICRONET1 SGXMICROTV6 SGXMAXAC SGXMAXNET SGXMAXTV

150

All Modes

90,000 A 330 per Phase 1350 Joules Total

No Yes No

No No Yes

150

Up to 15 dB (Peak)

Indoor Application

Surge Strip Ultra

120

All Modes

105,000 A 330 per Phase 1575 Joules Total

Up to 35 dB (Peak)

Indoor Application

120

All Modes

19,500 A per Phase 750 Joules Total

No No Yes Yes No

150

Construction Series

No Yes No Yes No

150

Up to 15 dB (Peak)

Indoor Application

Rack Mount 120 Surge Strip

All Modes

330 84,000 A per Phase 1575 Joules Total

No

No

150

Yes

Indoor Application

15 and 20 ampere available. 15 ampere twist lock ac cord.

CA08101001E

10 CHSPCHSR4P

120

CHSPMAX

UL 1449, UL497A, CSA

Surge Strip Max

330

CHSPMICRO

For more information visit: www.eaton.com

UL 1449 (2nd Ed.), UL 1363, UL 497A, CSA UL 1449 (2nd Ed.), UL 1363, UL 497A, CSA

SGXULTAC SGXULTNET SGXULTTV SGXULT3WAY SGXCONST6 SGXCONST8

SGXRM19B SGXRM19BTL


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Residential Surge Protection

10-10

July 2007

Technical Data and Specifications Table 10-4. Residential Surge Protection Devices and Lightning Arresters Product

Protection Levels and Application

Features

Warranty

Installation/ Enclosures

Catalog Number

Price U.S. $

CHSA

Basic Surge Protection

2-Pole Breaker Design

1-Year Product Warranty

Inside Type CH Loadcenter

CHSA

BRSURGE

Basic Surge Protection

2-Pole Breaker Design

1-Year Product Warranty

Inside Type BR Loadcenter/ Classified Listed

BRSURGE

CHQSA

Basic Surge Protection

2-Pole Breaker Design

1-Year Product Warranty

Inside Square D Type QO Loadcenter

CHQSA

CHSA01

Basic Surge Protection for Outdoor Lighting, Garages, Sump and Irrigation Pumps

120/240 Vac Systems

1-Year Product Warranty

Indoor/Outdoor Enclosure

CHSA01

CHSA03

Basic Surge Protection for Commercial Electrical Services

600 Vac Systems

1-Year Product Warranty

Indoor/Outdoor Enclosure

CHSA03

CHSP Micro

Basic Surge Protection for Appliances

Surge Current Rating 20 kA, 2-Year Product Metal Enclosure, Warranty Easy-to-Install Mounting

Indoor/Outdoor Enclosure

CHSPMICRO

CHSP Max

Standard Surge Protection for Major Appliances and Home Electronics

Surge Current Rating 50 kA, Thermal Fusing, Compact, Small Footprint, Status Monitor

Indoor/Outdoor Enclosure, Flushmount Kit Available

CHSPMAX

CHSP 3-Way

Standard 3-Way Protection (ac Power, Phone, Cable) for All Home Electronic Equipment

Indoor/Flushmount Surge Current Rating 75 kA, 5-Year Product Enclosure 4 Telephone Lines, Warranty , $10,000 Connected 1 Cable/Satellite Line Equipment

CHSP Ultra

Ultimate Surge Protection Surge Current Rating 75 kA, for Major Appliances, Home Audible Alarm, Electronics, Computers/Home Thermal Fusing Office and Entertainment Systems

Lifetime Product Warranty , $25,000 Connected Equipment

Indoor/Outdoor Enclosure, Flushmount kit available

CHSPULTRA

SurgeTel

Telephone/Modems

4 Telephone Lines

DHW4PT

SurgeCable

Cable/Satellite TV

2 Cable/Satellite Lines

DCXCAB2

SurgeEthernet

Ethernet

Protection for High Speed Internet

DRJ45D30R

Flushmount Kit

Cover for CHSP Max or Ultra When Used on a Finished Wall

CHSPFMKIT

Surge Strip Series Micro

Appliances

1 and 6 Outlets; Wallmount

5-Year Product Warranty, $1,500 Connected Equipment

— — —

SGXMICROAC6 SGXMICRONET6 SGXMICROTV6 SGXMICRONET1

Surge Strip Series Max

Less Critical Electronic Equipment

7 Outlets; Angled Plug-in

Lifetime Product Warranty, $5,000 Connected Equipment

— — —

SGXMAXAC SGXMAXNET SGXMAXTV

Surge Strip Series Ultra

Home Entertainment Systems and Computer/Home Office

8 Outlets; Angled Plug-in, Lifetime Product Transformer Spacing, Warranty, Series Filter and TCO Fuses $25,000 Connected Equipment

— — — —

SGXULTAC SGXULTNET SGXULTTV SGXULT3WAY

SurgeTrap ValueLine

Basic Surge Protection

6 Outlets

— —

SGXCONST6 SGXCONST8

Stage 1

10

5-Year Product Warranty , $10,000 Connected Equipment

CHSPCHSR4P

Accessories

Stage 2

5-Year Product Warranty

Warranty coverage applicable when CHSP products are used in conjunction with SurgeTrap point-of-use strips and appropriate cable and telephone protectors (see accessories). Please contact your local Eaton sales office. ac power. ac + telephone/modem. ac + cable. ac + telephone/modem + cable. ac power and coaxial cable. 6-foot (1.83 m) cord. 15-foot (4.57 m) cord.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 22-CD For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-11 Residential Surge Protection July 2007

Technical Data and Specifications

Factory Installed Surge Suppression — Main Circuit Breaker Loadcenter Table 10-5. Home Electronic Protection Panel (HEP — Surge Panel) Single-Phase 3-Wire — 120/240 Vac Factory Bonded Split Neutral Main Breaker Type

Maximum Main Ampere Rating

Maximum Number 3/4-Inch (19.1 mm) Single Poles

Box Size

Wire Range Size

Loadcenter Box and Panel

CH 10 kAIC

100

22

D

#6 – 4/0

CHSUR22B100D

CHPC8DF

CSR 25 kAIC

150 200 200

32 32 42

L L L

#2 – 300 kcmil

CHSUR32B150L CHSUR32B200L CHSUR42B200L

CHPC8B32LF CHPC8B32LF CHPC8B42LF

Catalog Number

Price U.S. $

Combination Catalog Number

Price U.S. $

Factory Installed Surge Suppression — Main Lug Loadcenter Table 10-6. Home Electronic Protection Panel (HEP — Surge Panel) Single-Phase 3-Wire — 120/240 Vac Factory Bonded Split Neutral Maximum Main Ampere Rating

Maximum Number 3/4-Inch (19.1 mm) Single Poles

125

24

D

#6 – 2/0

CHSUR24L125D

CHPC8DF

225

32 42

L L

#2 – 300 kcmil

CHSUR32L225L CHSUR42L225L

CHPC8B32LF CHPC8L42LF

Box Size

Wire Range Size

Loadcenter Box and Panel Catalog Number

Price U.S. $

Combination Catalog Number

Price U.S. $

10

Surge Suppression Ready Loadcenter (Field Installation Provision) Table 10-7. Type CHPC — Single-Phase, 3-Wire, 120/240 Vac, NEMA Type 1 Indoor and NEMA Type 3R Outdoor Type of Main Device

Main Ampere Rating

Maximum Number of Circuits

Power Center AIC Rating

Power Center

Catalog Number

Combination Style Cover Price U.S. $

Catalog Number

Top Feed Outdoor Power Center (Cover Included) Price U.S. $

Catalog Number

Bottom Feed Outdoor Power Center (Cover Included) Price U.S. $

Catalog Number

Breaker Breaker Lug Lug

100 100 125 125

22 30 12 24

10,000 10,000 10,000 10,000

CHPC22B100D CHPC30B100J CHPC12L125C CHPC24L125D

CHPC8DF CHPC8JF CHPC8CF CHPC8DF

CHPC22B100TR CHPC30B100TR CHPC12L125TR —

CHPC22B100BR CHPC30B100BR CHPC12L125BR —

Breaker Lug Breaker

125 150 150

32 32 32

25,000 25,000 25,000

CHPC32B125L CHPC32L150J CHPC32B150L

CHPC8B32LF CHPC8JF CHPC8B32LF

CHPC32B125TR — CHPC32B150TR

— — CHPC32B150BR

Breaker Breaker Convert.

150 200 200

42 32 32

25,000 25,000 25,000

CHPC42B150L CHPC32B200L CHPC32N200L

CHPC8B42LF CHPC8B32LF CHPC8B32LF

CHPC42B150TR CHPC32B200TR CHPC32N200TR

— CHPC32B200BR —

Breaker Convert. Lug

200 200 225

42 42 42

25,000 25,000 25,000

CHPC42B200L CHPC42N200L CHPC42L225L

CHPC8B42LF CHPC8B42LF CHPC8L42LF

CHPC42B200TR CHPC42N200TR —

CHPC42B200BR — —

Price U.S. $

Note: Factory provision to field install a CHSPULTRALCRK surge protection device: ■ ■ ■ ■ ■

Surge current rating 70 kA. Audible alarm. Thermal fusing. Lifetime product warranty. $25,000 connected equipment.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22-CD CA08101001E

For more information visit: www.eaton.com


10-12

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Residential Surge Protection July 2007

Cross-Reference

Cross-Reference Note: Cross-Reference continues on the following page.

Table 10-8. Surge Products Cutler-Hammer

Square D

General Electric

Siemens

Leviton

Intermatic

Pass & Seymour

120/240 Vac, Single-Phase, 3-Wire

CHSA01

SDSA1175

N/A

N/A

55175-ASA, 55175-SSA

AG2401

N/A

600 Vac, 3-Phase, 4-Wire, 3-Phase

CHSA03

SDSA3650

N/A

N/A

55650-ASA

AG6503, AG6503L

N/A

120/240 Vac, Type BR Circuit Breaker

BRSURGE

HOM2175SB

THQLSurge

QSA Series

N/A

N/A

N/A

120/240 Vac, Type CH Circuit Breaker

CHSA

QO2175SB

N/A

N/A

N/A

N/A

N/A

120/240 Vac, 20 kA Surge Current

CHSPMICRO

N/A

N/A

N/A

N/A

N/A

N/A

120/240 Vac, 50 kA Surge Current

CHSPMAX

N/A

THQLSurge60

SBPRIMAX, SSPRIMAX

51120-1, 51120-3R

IG1240RC

1224-SL

120/240 Vac, 70 kA Surge Current

CHSPULTRA

N/A

N/A

N/A

IG250LA, IG251

N/A

120/240 Vac, ac, Telephone, Coax, 40 kA Surge Current

CHSPCHSR4P

SDSB1175C, SDSB1175DP

N/A

N/A

51120-PTC, 51110-PTC

N/A

N/A

SurgeTel, 4 Telephone Lines

DHW4PT

N/A

SurgePro THSATEL140

N/A

5350-TLL

N/A

N/A

SurgeCable, 2 Cable/Satellite Lines

DCXCAB2

N/A

SurgePro THQLCOAX

N/A

5350-BNC

N/A

N/A

SurgeEthernet, High Speed Internet

DRJ45D30R

N/A

N/A

N/A

5360-TBT, 3861-ETH

N/A

N/A

Flushmount Kit

CHSPFMKIT

N/A

N/A

N/A

N/A

IG1240FMP2

N/A

NEMA 3R Outdoor Enclosure

CHSPN3R

N/A

N/A

N/A

N/A

N/A

N/A

6 Outlets, Wallmount, ac Only

SGXMICROAC6

N/A

N/A

N/A

N/A

EG33IB

N/A

6 Outlets, Wallmount, ac, Cable

SGXMICROTV6

N/A

N/A

N/A

N/A

EG33EIB

N/A

1 and 6 Outlets, Wallmount, ac, Telephone Modem

SGXMICRONET1 N/A SGXMICRONET6

N/A

N/A

N/A

EG33TIB

N/A

7 Outlets, ac Only

SGXMAXAC

N/A

SU93940

N/A

4950 Series

EG79

PS7

7 Outlets, ac, Cable

SGXMAXTV

N/A

N/A

N/A

4950 Series

N/A

N/A

7 Outlets, ac, Telephone Modem

SGXMAXNET

N/A

SU93942, SU93944

N/A

4950 Series

EG79ASO

PS7P

8 Outlets, ac Only

SGXULTAC

N/A

N/A

SPOWERMAX8

5950 Series

N/A

N/A

8 Outlets, ac, Cable

SGXULTTV

N/A

N/A

SPOWERMAX8_C 5950 Series

EG856EALI

PS8C

8 Outlets, ac, Telephone Modem

SGXULTNET

N/A

SU93950

SPOWERMAX8_T 5950 Series

EG856TALI

PS8P

8 Outlets, ac, Cable, Telephone Modem

SGXULT3WAY

N/A

SU93916

N/A

5950 Series

EG858DSALI, EG858ESALI

N/A

6 Outlets, ac, 6-Foot (1.83 m) Cord

SGXVAL6

N/A

N/A

N/A

4800, 4900, 5100, 5200 and 5300 Series

EG636L1

PS6

6 Outlets, ac, 15-Foot (4.57 m) Cord

SGXVAL15

N/A

N/A

N/A

4800, 4900, 5100, 5200 and 5300 Series

N/A

PS7L

Description

Lightning Arresters

Surge Breakers

Service Entrance

10

Accessories

Surge Strips

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-13 Facility-Wide Surge Protection July 2007

Clipper Power System

Clipper Power System — Visor Series Product Description Eaton has developed the Cutler-Hammer Clipper Power System (CPS) — Visor Series family of products to ensure that the quality power required to maximize productivity in today’s competitive environment is supplied to commercial, industrial, institutional, medical and telecommunications facilities. The Clipper Power System family of products used for Surge Protection Devices (SPDs), also known as Transient Voltage Surge Suppression (TVSS), incorporates clamping and filter components that are integrated into low voltage distribution equipment or assemblies — switchboards, switchgear, panelboards, MCCs, automatic transfer switches, and busway. Eaton also offers CPS units that can be externally mounted to any manufacturers distribution equipment on new or existing installations (Retrofit CPS).

Ten (10) Year Extended Warranty An extended ten (10) year warranty is provided on all CPS units.

Clipper Power System — Visor Series: Integrated Surge Suppression for Low Voltage Distribution Assemblies

Application Flexibility 100, 120, 160, 200, 250, 300, 400 and 500 kA/phase ratings are available. ■ All units utilize our low impedance SurgePlane suppression platform to ensure surge currents are equally diverted to all suppression components, therefore extending life expectancy. ■

Standards and Certifications

Visor Monitoring Options Surge C Currrent Equally D Diverted

Industry Performance and Safety Standards The CPS has been tested by all industry standards (UL 1449 2nd Edition, UL 1283, ANSI/IEEE C62.41 and C62.45, NEMA LS 1-1992, MIL-STD-220AS, and CSA C22.2). All CPS products have been independently tested to verify published surge current ratings.

Features, Benefits and Functions Industry Leadership ■

■ ■

The Visor is an intelligent surge suppression device that offers advanced monitoring options. It offers improved safety and reliability from a new patent-pending technology — Thermo-Dynamic Fusing . Independently tested by lightning laboratories to ensure performance, long-term reliability, and quality standards are met. Installation flexibility for all low voltage distribution equipment. Worldwide customer, engineering, and application support.

CA08101001E

Pha ase

SurgePlanes

Figure 10-4. SurgePlane Technology

Comprehensive Diagnostics

Our patent-pending Thermo-Dynamic Fusing System provides both safety and performance. This technology uses a fuse trace on each individual metal oxide varistor (MOV) that can sustain high surge currents and provide the necessary interruption of high fault currents (kAIC). ■ Thermo-Dynamic Fusing System also includes a thermal fuse spring (TFS) that provides the needed disconnection from low level fault currents. ■

Maintenance-free surge suppression. (No external test set or routine maintenance required.) ■ The NetVisor, our premium display, allows you to monitor your surge protective device from across the plant or across the world. ■ All monitoring display panels are completely removable and can be installed horizontally or vertically, offering four mounting positions. ■

Components of the Thermo-Dynamic Fusing System

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Facility-Wide Surge Protection

10-14

July 2007

Clipper Power System

Technical Data and Specifications Table 10-9. Eaton’s Cutler-Hammer Clipper Power System Specifications

10

CPS Models

CPS-100

CPS-120 CPS-160

CPS-200 CPS-250 CPS-300 CPS-400 CPS-500

Surge Current Per Phase Surge Current Mode L-N (Line-to-Neutral) L-G (Line-to-Ground) N-G (Neutral-to-Ground) L-L (Line-to-Line, Delta, and Ungrounded Applications Only)

100 kA

120 kA

160 kA

200 kA

250 kA

300 kA

400 kA

500 kA

50 kA 50 kA 50 kA

60 kA 60 kA 60 kA

80 kA 80 kA 80 kA

100 kA 100 kA 100 kA

125 kA 125 kA 125 kA

150 kA 150 kA 150 kA

200 kA 200 kA 200 kA

250 kA 250 kA 250 kA

50 kA

60 kA

80 kA

100 kA

125 kA

150 kA

200 kA

250 kA

Single Pulse Surge Current Test Based on IEEE C62.41 8x20 microsecond waveform Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Modes of Protection 3-Phase Wye System 3-Phase Delta System

All 7 6

All 7 6

All 7 6

All 7 6

All 7 6

All 7 6

All 7 6

All 7 6

Filter Attenuation (Based on MIL-STD-220A) at 100 kHz

50 dB

50 dB

50 dB

50 dB

50 dB

50 dB

50 dB

50 dB

Surge Withstand Capabilities IEEE C3 Wave (10 kA)

8,000

9,000

10,000

11,000

12,000

13,000

14,000

15,000

Thermo-Dynamic Fusing System Overcurrent Protection (Thermal Fuse Spring) 200 kAIC capability Individually Fused MOVs

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Monitoring Display Options SuperVisor (Standard) AdVisor NetVisor

Yes Optional Optional

Yes Optional Optional

Yes Optional Optional

Yes Optional Optional

Yes Optional Optional

Yes Optional Optional

Yes Optional Optional

Yes Optional Optional

Direct Bus Bar Connection

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Warranty — Clipper Power System

10 Years

10 Years

10 Years

10 Years

10 Years

10 Years

10 Years

10 Years

CPS-250 recommended for service entrance, CPS120 recommended for branch locations using IEEE recommended cascade approach. Optional sizes to meet competitive specifications. All CPS have been independently tested to verify all suppressor components can survive published surge current ratings. Test documents are available upon request.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-15 Facility-Wide Surge Protection July 2007

Clipper Power System

Clipper Power System — Visor Series Integrated

Product Description Eaton’s Cutler-Hammer Clipper Power System — Visor Series Integrated Design Provides the Lowest System Let-Through Voltage at the Bus Bar Compared to Traditional Cable Connected TVSS Units The Clipper Power System — Visor Series utilizes a direct bus bar connection to achieve the industry’s lowest let-through voltage — effectively suppressing both high and low energy transients. This design provides superior suppression ratings and eliminates poor performance that results from cable connections and/or long lead lengths.

Let-Through Voltage at Bus Bar

Due to the integrated design, the Visor Series also eliminates:

Expensive horizontal “outboard” wall space. ■ Field installation costs. ■ Potential electrical code violations due to improper installation. ■ Invalidation of third party certifications when connecting to existing products. ■

Other suppressor manufacturers’ measurements are made at the TVSS module or the suppressor terminal, not at the distribution equipment bus bar. The distance between the module or suppressor terminals and the distribution equipment bus bar is often 14 inches (355.6 mm) or more. The impedance associated with this lead length can significantly increase the transient let-through voltage.

800

*Based on IEEE C62.41 (1991) Combination Waveform Category B3/C1 (6000 V, 3000 A, 8 x 20 µs) Using #10 AWG Wire.

Cable Connected TVSS (14" Cable Lead Length to Bus Bar)

400 Integrated Clipper Power System

0 0

5

10

15

Time (Microseconds)

Figure 10-5. Panelboard Let-Through Voltage Using Direct Bus Bar Connections

Clipper Power System — Visor Series Integrated Offering Includes Panelboards, Switchboards, Switchgear, MCC and Busway

CA08101001E

Note: Optional sizes to meet competitive specifications. All Visor units have been independently tested to verify all suppressor components can survive published surge current ratings. Test documents are available upon request.

For more information visit: www.eaton.com

Cross-Reference Contact local sales office for competitor cross-reference.

10


10-16

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Facility-Wide Surge Protection July 2007

Clipper Power System

Clipper Power System — Visor Series Retrofit

Visor Series Retrofit

10

Product Description Retrofit Installation Recommendations to Reduce Installed Let-Through Voltage Eaton’s revolutionary Cutler-Hammer surge suppression system for retrofit applications offers the widest variety of surge current ratings, monitoring features, and enclosure options. The Visor Series is the most respected line of surge protection devices in the industry due to its exceptional performance at lightning labs, two decades of experience in the surge suppression industry, worldwide installations, and extensive R & D initiatives.

When installing a surge suppressor in a retrofit environment, it is important to mount the suppressor as close to the electrical equipment as possible. Keep the wiring (lead length) between the electrical equipment and the suppressor as short as possible (less than 14 inches (355.6 mm) is recommended), and twist/wire tie the conductors to reduce inductive effects. Installation lead length reduces the performance of any surge suppressor. For each inch of wiring (installation lead length), add 15 to 25 volts to the surge suppressor’s published let-through voltage at 400 volts and installation of 3 feet (.9 m) of cable = 1000 volts installed rating.

Features, Benefits and Functions

Application Flexibility 100, 120, 160, 200, 250, 300, 400 and 500 kA ratings are available. ■ All units utilize our low impedance SurgePlane suppression platform to ensure surge currents are equally diverted to all suppression components, therefore extending life expectancy. ■ All Visor Series designs have been independently tested to verify published ratings and long-term reliability. ■

Comprehensive Diagnostics ■

■ ■

Industry Leadership Patented designs provide superior performance and reliability. ■ Independently tested by lightning laboratories to ensure performance, reliability and quality standards are met. ■ Installation flexibility for all low voltage distribution equipment. ■ Worldwide customer, engineering and applications support. ■

Increased Protection ■

The UL 1283 listed filter protects against ringing transients and EMI/ RFI noise disturbances. The tuned suppression filter achieves 50 dB attenuation at 100 kHz.

■ ■

Patent pending Thermo-Dynamic Fusing System utilizes individually fused MOVs and Thermal Fuse Spring (TFS) to provide high and low fault current protection. 200 kAIC internal fusing system. Three levels of monitoring display: ❑ AdVisor ❑ SuperVisor ❑ NetVisor Remote mountable monitoring displays. Maintenance-free SPD (no external test kit or routine maintenance required).

Standards and Certifications All Visor units have been tested by UL and meet the requirements under UL 1449 for surge suppression devices. ■ All Visor units have been tested per NEMA LS-1 and ANSI/IEEE recommended high energy impulses (Cat. C3, 20 kV, 10 kA), and internally generated ringwave surges (Cat. B3, 6 kV 500 A at 100 kHz). ■

Visor Series Retrofit — NEMA 1/3R with Disconnect Switch

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-17 Facility-Wide Surge Protection July 2007

Clipper Power System

Product Selection Table 10-10. Visor Series — Retrofit Unit Catalog Numbering System

CPS 100 480Y S K Surge Ratings 100 120 160 200 250 300 400 500

= = = = = = = =

100 kA/phase 120 kA/phase 160 kA/phase 200 kA/phase 250 kA/phase 300 kA/phase 400 kA/phase 500 kA/phase

Diagnostics Packages

Enclosure Cross Reference

A = AdVisor complete with — Status indicator lights on each phase, Form C, Audible Alarm — Enable/Disable. S = SuperVisor complete with — Status indicator lights on each phase, Form C, Audible Alarm — Enable/ Disable, Transient Counter, Push-to-Test, PQ Meter (no date stamp). N = NetVisor complete with — Status indicator lights on each phase, Form C, Audible Alarm — Enable/ Disable, Transient Counter, Push-to-Test, PQ Meter (date stamp), Modbus and Ethernet Communication Port, % Life Remaining, % Voltage THD. Voltage Code

220/127 Three-Phase Wye (4W+G) (Mexico) 120/240 Single Split Phase (3W+G) Three-Phase Delta High Leg (4W+G) Three-Phase Wye (4W+G) Three-Phase Delta (3W+G)

120/208 127/220 240 V 220Y 240S 240H 208Y 240D

10

230/400 400 V

277/480 480 V

347/600 600 V

400Y

480Y 480D

600Y 600D

For voltage codes not shown, please call factory. Disconnect Switch — FDC3030 breaker.

CA08101001E

K = Standard (NEMA 1, 3R) L = Flushmount (NEMA 1) M = Standard (NEMA 1, 3R) complete with Disconnect Switch N = NEMA 4X O = NEMA 4X complete with Disconnect Switch P = NEMA 12 Q = NEMA 12 complete with Disconnect Switch

For more information visit: www.eaton.com


10-18

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Facility-Wide Surge Protection July 2007

Clipper Power System

Technical Data and Specifications Dimensions 15.00 (381.0) CLIPPER POWER SYSTEM

CLIPPER POWER SYSTEM

20.00 (508.0)

16.00 (406.4)

3.90 (99.1)

10

Figure 10-6. NEMA 1 — Flushmount up to 200 kA (480 Volts or Less)

18.00 (457.2)

22.60 (574.0)

CLIPPER POWER SYSTEM

5.20 (132.1)

14.10 (358.1)

Figure 10-9. NEMA 1/3R c/w Disconnect Switch (up to 500 kA/All Voltages)

3.90 (99.1)

13.00 (330.2)

Figure 10-11. NEMA 1/3R 250 kA and up (480 Volts or Less/600 Volts, 100 kA – 500 kA)

CLIPPER POWER SYSTEM

CLIPPER POWER SYSTEM

CLIPPER POWER SYSTEM

16.00 (406.4)

11.00 (279.4)

22.00 (558.8)

3.90 (99.1)

Figure 10-7. NEMA 1/3R up to 200 kA (480 Volts or Less)

17.00 (431.8)

21.90 (556.3)

18.00 (457.2)

3.90 (99.1)

Figure 10-10. NEMA 1 — Flushmount 250 kA and up (480 Volts or Less/600 volts, 100 kA – 500 kA)

18.00 (457.2)

10.40 (264.2)

Figure 10-12. NEMA 4X c/w Disconnect Switch (up to 500 kA/All Voltages)

8.60 (218.4)

CLIPPER POWER SYSTEM

18.00 (457.2)

16.00 (406.4)

Figure 10-8. NEMA 4X up to 500 kA (All Voltages)

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-19 Facility-Wide Surge Protection July 2007

Clipper Power System

Application Description Table 10-11. Service Entrance Applications Switchboard

Switchgear

Motor Control Centers

■ Available on all switchgear designs. ■ Disconnect switch is a standard feature. ■ Unique design minimizes installation impedance. ■ CPS 250 ideal for critical industrial switchgear applications.

■ Ideal protection for PLCs, sensors, drives, electronic starters, or other digital equipment. ■ Visor designed to fit in a standard (2x size) compartment without breaker disconnect and 3x size with breaker disconnect for Freedom 2100 and Advantage MCCs. ■ May be used in new/aftermarket applications. ■ Ideal for water treatment, petrochemical and other industrial applications.

■ UL 891 (Switchboard) ■ UL 1449 2nd Edition (Surge Suppressor) ■ UL 1283 (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor)

■ UL 1558 (Switchgear) ■ UL 1449 2nd Edition (Surge Suppressor) ■ UL 1283 (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor)

■ UL 845 (MCC) ■ UL 1449 2nd Edition (Surge Suppressor) ■ UL 1283 (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor)

Panelboards

Busway

Retrofit

■ Ideal for busway fed distribution systems. ■ Easy-to-install Visor units, fit in standard bus plug assembly. ■ Full diagnostic and monitoring capabilities. ■ Isolates critical busway sections from nearby disturbance producing loads. ■ Designed for new and existing facilities. ■ Integral disconnect.

■ SPDs can be externally mounted to existing distribution equipment. ■ Standard NEMA 1/3R enclosures. ■ Requires field installation. ■ Visor Series 100 to 500 kA/phase units. ■ Clipper VL 50, 80 and 100 kA/phase units.

■ UL 857 (Busway) ■ UL 1449 2nd Edition (Surge Suppressor) ■ UL 1283 (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor)

■ UL 1449 2nd Edition (Surge Suppressor) ■ UL 1283 (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor)

Features ■ Visor can be integrated into any switchboard. ■ Specifiers have the flexibility to install the Visor in any location within the switchboard. ■ Disconnect switch is a standard feature. ■ Unique design minimizes installation impedance.

Safety Standards

Pow-R-Line 3a

Pow-R-Line 4

Features ■ Visor used extensively on branch panelboards for computer rooms, laboratories, schools, hospitals, industrial applications. ■ 200% rated neutral is provided for non-linear loads. ■ Cost-effective branch protection (assumes main panel protection employed).

Safety Standards ■ UL 67 (Panelboards) ■ UL 1449 2nd Edition (Surge Suppressor) ■ UL 1283 (EMI/RFI Filter) ■ CSA C22.2 Certified (Suppressor)

Note: The CPS Surge components can be integrated into Safety Switches, Automatic Transfer Switches (ATS) and other assemblies.

CA08101001E

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Hardwire Surge Protection

10-20

July 2007

Clipper Power System

Clipper VL (CVL)

Product Selection ■ ■

■ ■ ■ ■ ■

CVL — Prevents Downtime and Equipment Damage

10

Individually fused surge suppression components. Status indicator lights to monitor supply power, surge suppression component status and fusing. Can be remotely monitored using Form C contacts. Audible alarm. Ideal for OEM panel applications. Proven track record in international applications. Independently tested at lightning laboratories to verify published surge current ratings.

Standards and Certifications UL 1449 2nd edition listed, UL 1283 listed, CSA approved, CE marked. ■ All Clipper VL units have been tested per NEMA LS-1 and ANSI IEEE recommended high energy impulses (Category C3, 20 kV, 10 kA), and internally generated ringwave surges (Category B3, 6 kV, 500 A at 100 kHz). ■ The UL listed filter protects against ringing transients and EMI/RFI noise disturbances. The tuned suppression filter achieves 40 dB attenuation at 100 kHz (IEEE Category B3 Ringwave). ■

Product Description Surge Protection Device to Prevent Downtime and Equipment Damage The Cutler-Hammer Clipper VL by Eaton Corporation is a commercial grade and light industrial surge protection device (SPD) that combines surge suppression components and EMI/RFI filtering to provide effective protection for sensitive electronic loads.

Features, Benefits and Functions

Product Specifications

SurgePlane technology to ensure reliability and performance by using a low impedance copper platform. ■ Compact design to enable close mounting to electrical distribution equipment. ■ Parallel hybrid filter technology. ■

Three surge current ratings are available to meet a variety of applications — the CVL050 (50 kA/phase), CVL080 (80 kA/phase) and CVL100 (100 kA/phase).

Table 10-12. Clipper VL Catalog Numbering System

CVL

CH

BD

Table 10-13. Clipper VL Price List Catalog Number

Price U.S. $

CVL050CH208YBDRSX CVL050CH208YBDR3R CVL050CH240DBDRSX CVL050CH240DBDR3R CVL050CH240SBDRSX CVL050CH240SBDR3R CVL050CH400YBDRSX CVL050CH400YBDR3R CVL050CH480DBDRSX CVL050CH480DBDR3R CVL050CH480YBDRSX CVL050CH480YBDR3R CVL050CH600DBDRSX CVL050CH600DBDR3R CVL050CH600YBDRSX CVL050CH600YBDR3R CVL080CH208YBDRSX CVL080CH208YBDR3R CVL080CH240DBDRSX CVL080CH240DBDR3R CVL080CH240SBDRSX CVL080CH240SBDR3R CVL080CH400YBDRSX CVL080CH400YBDR3R CVL080CH480DBDRSX CVL080CH480DBDR3R CVL080CH480YBDRSX CVL080CH480YBDR3R CVL080CH600DBDRSX CVL080CH600DBDR3R CVL080CH600YBDRSX CVL100CH208YBDRSX CVL100CH208YBDR3R CVL100CH240DBDRSX CVL100CH240DBDR3R CVL100CH240SBDRSX CVL100CH240SBDR3R CVL100CH400YBDRSX CVL100CH400YBDR3R CVL100CH480DBDRSX CVL100CH480DBDR3R CVL100CH480YBDRSX CVL100CH480YBDR3R CVL100CH600DBDRSX CVL100CH600DBDR3R CVL100CH600YBDRSX CVL100CH600YBDR3R

Voltage Code See Table 10-10 Surge Rating

Enclosure

050 = 50 kA/phase 080 = 80 kA/phase 100 = 100 kA/phase

RSX = Standard Retrofit R3R = Outdoor

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22-CD For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-21 Critical Load Surge Filter July 2007

AEGIS Powerline Filters

AEGIS Powerline Filters

Application Description The AEGIS is the ideal protection solution for your critical loads and facilities.

Loads ■ ■ ■ ■

AEGIS Solutions

■ ■

Product Description Eaton’s Cutler-Hammer AEGIS solutions are specifically designed to protect expensive electronics from the hazards that exist within a facility. This critical load protection is effective at reducing harmful surges and noise. Applying this high performance series powerline filter at your critical loads results in “clean” power entering the electronics and reduction of “soft” errors, operational malfunction, and damage to components.

Standards and Certifications Cutler-Hammer products are designed in accordance with ANSI/IEEE C62.41 (1991) recommended spectrum of transient waveforms. The AEGIS protects against all ringing and impulse disturbances.

■ ■ ■ ■

Programmable controllers (PLCs). Scanning devices. ATMs (Automatic Teller Machines). Cash registers. Alarm systems. Microprocessor-controlled OEM products. Robotics. CAD/CAM systems. Control equipment. Medical electronics and devices.

10

Why Should Sensitive Electronic Loads be Protected? PLC manufacturers and service technicians recommend the use of surge suppressors and filters to prevent downtime and equipment damage due to surges and electrical line noise. One study shows failure to protect sensitive electronic loads costs American manufacturing, commercial and service industries over $39 billion per year in lost time and revenue. Preventing these losses is a major cost-saving opportunity.

AEGIS Powerline Filters Protect Against the Full Spectrum of Transient Disturbances AEGIS filters the entire sine wave and is effective against both frequently occurring low energy and occasional high energy transients. High energy transients can create immediate damage, while low energy transients cause microprocessor failure over time.

Hardwired Surge Filter that Protects Critical Loads (3, 5, 10, 15 or 20 Ampere Models)

CA08101001E

Lightning Protection for ac Powerline Applications (1-, 2-, 3-Phase Applications to 100 Amperes)

For more information visit: www.eaton.com

AEGIS VL Hardwired Critical Load Filter 1, 3 and 5 Ampere Modules Only


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Critical Load Surge Filter

10-22

July 2007

AEGIS Powerline Filters

Features, Benefits and Functions

Standards and Certifications

Table 10-14. AEGIS Powerline Filters Features and Benefits

Based on ANSI/IEEE C62.41, 1991 and C62.45, 1992.

Features

Benefits

Unique Series Hybrid Design (AEGIS-HW, AEGIS+)

■ Protection against high and low energy transients and noise. ■ The tracking filter reacts instantly to changes in frequency and voltage, regardless of phase angle, magnitude or polarity. ■ Active at all times, providing more protection than a conventional surge suppressor. ■ Extends the life of your microprocessors by eliminating degrading power disturbances.

High Performance Suppression Capabilities (AEGIS-HW, AEGIS+)

10

AEGIS-HW and AEGIS-PR have up to 45,500 amperes of surge current suppression and 75 dB of noise attenuation at 100 kHz. This guarantees a superior level of protection and reliability. AEGIS+ has additional protection up to 160 kA/phase.

Status Monitoring Lights (AEGIS-HW, AEGIS+)

No more testing or guessing whether your unit is working properly. Filter indicator lights expedite your troubleshooting efforts during downtime situations.

5-Year Downstream Equipment Warranty (AEGIS-HW only)

Eaton provides a 5-year Extended Warranty on the microprocessor power supply protected by AEGIS. No other manufacturer offers this level of assurance in backing up its claim of product performance, quality and reliability.

Value (AEGIS-HW, AEGIS+)

AEGIS provides superior value when considering the level of performance and benefits offered. It truly delivers the best “bang” for your dollar.

Optional Remote Monitoring Capabilities (AEGIS-HW, AEGIS VL, and AEGIS+ only)

Observe all your operations on a remote basis, including the power protection devices used to safeguard your critical and sensitive electronic loads.

Table 10-15. Let-Through Voltages (L-N) Description

AEGIS-HW (L-N Mode)

Category A3 Ringwave (600 V, 200 A)

6V

Category B3 Ringwave (600 V, 500 A)

9.6 V

Category B3/C1 Combination 70 V (Impulse) Wave (600 V, 300 A) (206 V, dynamic at 90°)

Static testing.

DIN-Rail, J-Rail or Flange Mounting Connections The DIN-Rail mountable enclosures greatly (AEGIS-HW only) reduce installation time, effort and cost. This unique container is the preferred choice among OEMs and contractors. Thermal Cut-Off Protection (TCO) (AEGIS-HW only)

Thermal fuse improves indication, monitor and control during fault conditions.

AEGIS Hybrid Series Powerline Filters Primary Transient Status High High Series Voltage Surge Suppression Frequency Blocking Performance Secondary Indicator Lights TVSS Tracking Filter Capacitor Inductors (TVSS) Power Input Normal Mode

L

Normal Mode

LED

Optional Form C Contacts Power Output Form C

N G

L N

Common Mode

Common Mode

G

Figure 10-13. 3-Wire Design has Normal and Common Mode Protection (L-N, L-G, N-G)

Option for AEGIS and AEGIS+.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-23 Critical Load Surge Filter July 2007

AEGIS Powerline Filters

B3/C1 Combination (Impulse) Wave (6000 V, 3000 A)

8000 6000

0 -2000 -4000 -6000

400 300 200 100 0 -100 -200 -300 -400

2 Microseconds/Division

Volts

2000

Volts

Volts

4000

7000 6000 5000 4000 3000 2000 1000 0 -1000 -2000 -3000 -4000

2 Microseconds/Division

Before

Volts

A3 Ringwave (Line-to-Neutral) (6000 V, 200 A)

700 600 500 400 300 200 100 0 -100 -200 -300 -400

20 Microseconds/ Division

After

Before

20 Microseconds/ Division

After

Figure 10-14. IEEE C62.41 (1991) Test Waveforms for AEGIS-HW and PR Versions

Product Specifications Table 10-16. Specifications Application

AEGIS-HW 2 W&G Grounded Systems

AEGIS-VL 2 W&G Grounded Systems

AEGIS+ 1-, 2- and 3-Pole Systems

Input Voltage Single-Phase

120, 220, 240 Vac, single-phase

120, 220, 240 Vac, single-phase

120, 208, 240, 400, 480, 600 Vac; Wye, Delta and International systems

Amperage

3, 5, 10, 15, 20 amperes

1, 3, 5 amperes

20, 30, 50, 70, 100 amperes

Frequency

50/60 Hz

50/60 Hz

50/60 Hz

Protection Modes

L-N, L-G, N-G

L-N, L-G, N-G

L-N, L-G, and N-G modes (Wye system); L-L and L-G (Delta system)

MCOV

150, 320 volts

150, 320 volts

150, 320, 420 volts (Wye system) 300, 550, 680 volts (Delta system)

Noise Attenuation Normal Mode: Common Mode:

75 dB at 100 kHz 50 dB at 5 MHz

75 dB at 100 kHz 50 dB at 5 MHz

65 dB at 100 kHz 40 dB from 60 kHz to 5 MHz

Filter Bandwidth

10 kHz to 100 MHz

10 kHz to 100 MHz

10 kHz to 100 MHz

Total Peak Surge Current

45.5 kA per phase

39 kA per phase

40, 80 or 160 kA per phase

Operating Temperature

-40º to +50°C

-40º to +50°C

-40º to +40°C

Response Time

Less than 1 nanosecond

Less than 1 nanosecond

Less than 1 nanosecond

Options

Form C relay contacts

N/A

Form C relay contacts; NEMA 3R/4X container; disconnect switch; 40 kA or 160 kA

Agency Approvals

UL 1449, UL 1283, CSA

UL 1449, UL 1283, CSA

CE, UL 1449 (20 to 70 amperes up to 480 volts)

Warranty

5 years plus downstream connected 5 years warranty

CA08101001E

For more information visit: www.eaton.com

5 years

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Critical Load Surge Filter

10-24

July 2007

AEGIS Powerline Filters

Product Selection Table 10-17. AEGIS-HW (Hardwire Application) Catalog Numbering System

Table 10-19. AEGIS+ Catalog Numbering System

AGSHW CH

AGS+ CH

X

Voltage Code

Voltage Code

Current Capacity

120N 230L

03 05 10 15 20

120N = 120 (1-Phase, 2W + G) 208Y = 208Y/120 (3-Phase, 4W + G) 240S = 240/120 (2-Phase, Delta 2W + G) 230L = 230 (1-Phase, 2W + G) 240D = 240D (3-Phase, Delta 3W + G) 400Y = 400Y/230 (3-Phase, 4W + G) 480Y = 480Y/277 (3-Phase, 4W + G) 480D = 480D (3-Phase, Delta 3W + G) 600Y = 600/347 (3-Phase, 4W + G) 600D = 600 (3-Phase, 3W + G)

Options S = Standard C = Form C contact for Remote Monitor

Model rated at 15 amperes UL/CSA = 16 amperes CE.

Note: 230 V applies to 220 and 240 volt applications.

10

Table 10-18. AEGIS-VL (Hardwire Application) Catalog Numbering System

AGSVL

Operating Current

Voltage Code

Current Capacity

120N 230L

1 3 5

020 030 050

Note: 230 V applies to 220 and 240 volt applications.

070 100

Surge Current Rating/Phase 040 080 160 Enclosure R4X = NEMA 4X Container RSD = Disconnect Switch (with NEMA 12 Container) Blank = Caseless Options (if required) CXX = Form C contacts (remote monitor)

400/230 valid for 380/220 and 415/240 per IEC. Contact factory for resistive ground applications.

Table 10-20. AEGIS Price List Catalog Number

Price U.S. $

AGSHWCH120N03XC AGSHWCH120N03XS AGSHWCH120N05XC AGSHWCH120N05XS AGSHWCH120N10XC AGSHWCH120N10XS AGSHWCH120N15XC AGSHWCH120N15XS AGSHWCH120N20XC AGSHWCH120N20XS AGSHWCH230L03XC AGSHWCH230L03XS AGSHWCH230L05XC AGSHWCH230L05XS AGSHWCH230L10XC AGSHWCH230L10XS AGSHWCH230L15XC AGSHWCH230L15XS AGSHWCH230L20XC AGSHWCH230L20XS AGSPRCH120N15HG AGSPRCH120N15HW AGSPRCH120N15XX AGSPRCH230L15HG AGSPRCH230L15HW AGSVL120N1 AGSVL120N3 AGSVL120N5 AGSVL230L1 AGSVL230L3 AGSVL230L5

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22-CD For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-25 Power Conditioning Products July 2007

Datacom

Datacom

Power Conditioner

away, the voltage during the sag is typically 40% – 90% of nominal utility voltage. The operation of circuit breakers, fuses and reclosers limits most sags to less than 15 cycles.

Product Description Eaton’s Cutler-Hammer Sag Ride Through — The First of Its Kind The Cutler-Hammer Sag Ride Through (SRT) Power Conditioner prevents electrical downtime. The SRT represents our state-of-the-art solutions to today’s power conditioning challenges.

Voltage sags are experienced 10 to 20 times more frequently than complete outages. However, voltage sags are equally disruptive to sensitive equipment.

The Problem

1. Fault occurs on the transmission or distribution system

Generation

Voltage Sags and Brownouts Datacom Products

Product Description Cutler-Hammer Datacom surge protection products by Eaton Corporation are designed for all industries and applications. The wide range of products offer rugged surge protection in convenient, easy-to-install configurations. Exceptional performance is achieved using three-stage hybrid technology: Gas tubes for shunting high energy. ■ Silicon avalanche components for responsive, low let-through voltages. ■ PTC resettable fuses for mitigating fault current. ■ Our modular design enables customers to protect complete facilities or individual loads. Customers also save significant time and money due to our unique plug-in components and protection modules. ■

The ability of a plant to ride through voltage sags can have a significant impact on operations and competitiveness. In the United States, voltage sags cost billions of dollars in lost production, interruption, damaged materials, retooling and scrap. In addition, sags can cause: increased operating costs, the need for product reworks, safety hazards, equipment damage and/or failure, reduced product quality, increased clean-up, additional labor costs, increased scrap material and costs associated with investigations into the problem.

End Users Transmission Distribution

10 Feeder Breakers

2. Creates a sag event for all users on the system

End User

End User

Figure 10-16. Voltage Sags

Regularity of Voltage Sags Input A

Input A

Input A

600 400 200 0 -200 -400 -600

Figure 10-15. Deep, Single-Phase Sag Today’s industrial and large commercial electricity customers are becoming more sensitive to power disturbances and are demanding better electric quality. However, the quality of power grids is not significantly improving. Customers still experience power quality problems that affect plant operations and profitability.

EPRI conducted a two-year study of power quality levels on distribution systems in the United States. A variation event was recorded every time the voltage dropped below 90% of the nominal. The results are shown in Figure 10-17. A typical distribution system customer experiences about 50 events per year when the voltage drops below 90%, and only about two events per year when the voltage drops below 30% of nominal. The utility study concluded that sags represented almost all of the events experienced at a typical facility.

Definition of Voltage Sag

6

A voltage sag is a sudden, momentary decrease in supply voltage. It can last from a cycle to several seconds. Voltage sags are most often caused by faults on the electrical transmission or distribution system. They can be caused by lightning strikes, animal contact, starting of large motors or an internal fault within a customer’s facility.

5

3 2 1 0 2

1

Figure 10-17. Events per Year CA08101001E

For more information visit: www.eaton.com

0 –7 40

0 5 50 – – –1 20 10 6

0 –1

Depending on the proximity to the fault, which can be hundreds of miles

4


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Conditioning Products

10-26

July 2007

Sag Ride Through

Continuous SAG Regulation

Equipment or Processes ■ ■ ■ ■ ■ ■ ■ ■ ■

Sag Ride Through (SRT)

Sag Correction Using the Sag Ride Through

10

The SRT meets the stringent requirements of the Semi-F47 standard; a key requirement for SAG correction in the semi-conductor industry.

Eaton’s Cutler-Hammer Sag Ride Through (SRT) Power Conditioner prevents expensive, electrical downtime. It is a state-of-the-art solution to today’s power conditioning challenges.

The Cutler-Hammer SRT is a high performance, inverter-based voltage conditioning device developed to provide protection to sensitive loads against commonly occurring voltage sags.

The SRT monitors the incoming supply voltage and when it deviates from the nominal voltage level, the SRT achieves voltage conditioning by injecting the appropriate correction voltage in series with the power supply. The SRT provides an extremely fast reaction time and subcycle response to sag events that would otherwise cause loads to drop out. The SRT is designed for low voltage systems (600 to 208, 3-phase) and is also offered in medium voltage applications from 25 kVA to 4 MVA. Installation is simple and the SRT provides customers with a new solution to improve productivity and reduce downtime for sag related problems.

Industries and Applications Affected by Sags

Manufacturing Process Controllers. Variable Speed Drives. Robotics. Motor Conductor. Telephone Systems. HID Lighting. HVAC Controls. Medical Equipment. Computers.

Complete correction of singlephase voltage sags down to 63% for 30 seconds. Partial correction of three-phase sags down to 50% for 30 seconds. Continuous regulation of threephase utility undervoltage and sags down to 90% of nominal. Correction of utility voltage imbalance (from network side of transformer). Attenuation of voltage flicker.

3-Phase Utility Supply Distribution Transformer

The Sag Ride Through is an active voltage conditioner. This means it will constantly respond to voltage sags in the -10% range with a regulated output in ±1% range. The SRT can be applied to the main service entrance, at branch locations or in front critical loads. The Cutler-Hammer SRT provides an outstanding return on investment. It delivers operation productivity that is just not possible with traditional tap switching or ferroresonant technologies. The SRT consists of a voltage source inverter, bypass circuit and an injection transformer connected in series between the incoming utility supply and the load, as shown in Figure 10-18. For the standard sag correcting model, the injection transformer consists of a boost component. The SRT monitors the incoming supply voltage and when it deviates from the nominal voltage level the SRT inserts an appropriate compensating voltage using the IGBT inverter and series injection transformer. Energy is sourced from the supply during this time. This regulates the load voltage to its nominal value, thus eliminating voltage disturbances from the utility supply affecting the load.

3-Phase Compensating Voltage Secondary Injection Transformer Primary

3-Phase Load Voltage

Bypass Circuit SRT Input SRT Output

Key Industries ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Semi-conductor manufacturers. Communications. Steel mills. Petroleum & chemical processing. Health care. Paper mills. Automotives. Textile. Printing. Plastics. Other manufacturing.

Voltage Source Inverter

Figure 10-18. Block Diagram of the SRT Active Voltage Conditioner

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-27 Power Conditioning Products July 2007

Sag Ride Through

Table 10-21. SRT Features and Specifications Features

Specifications

Load Capacity Capacity (kVA) Displacement Power Factor of Connected Load Crest Factor for Rated kVA Overload — 30 Seconds

25 – 6 MVA (as specified per model) 0 – 1, leading or lagging 1.63 at 100% of rated load for continuous operation (including up to 10% voltage correction) 150% with up to 10% of voltage correction

Input Supply Nominal Supply Voltage Maximum Supply Voltage Minimum 3-Phase Supply Voltage – Running – Starting Minimum Single-Phase-to-Ground Supply Voltage – Running – Starting Efficiency of System

208/480/600 V, 60 Hz 3-phase, 3-wire plus ground (higher system voltages supplied to requirement) 110% of nominal supply voltage 50% of nominal supply voltage 75% of nominal supply voltage 25% of nominal supply voltage 63% of nominal supply voltage 98 – 99%

Output Supply Nominal Voltage (V) 3-Phase Balanced Correction Single-Phase-to-Ground Correction Voltage Regulation Response (to Sag Event)

208/480/600 V, 60 Hz; 3-phase, 3-wire plus ground (higher system voltages supplied to requirement) +30% for at least 30 seconds +45% for at least 30 seconds; +10% continuous 3-phase correction (all models). Consult factory for specialist correction requirements. +/- 1% up to 10% continuous 3-phase correction +/- 2.5% at 30% 3-phase correction Initial sag correction applied within 1 ms, remainder over the next cycle

Bypass Nominal Power Maximum Overload Capacity (in Bypass): – For 10 Minutes (%) – For 1 Minute (%) – For 600 Milliseconds (%) – For 100 Milliseconds (%) Transfer Time – Inverter to Bypass (ms) – Bypass to Inverter (ms)

SRT rating (kVA) 125 150 700 1000 < 0.5 < 40 – 750

Environmental Operating Temperature Cooling Capacity Derating with Elevation Humidity Warranty

0 – 40°C; 50°C maximum with 20% load derating Forced ventilation -1.2% every 100 m above 1000 m < 95%, non-condensing 1 year

If SRT has tripped (off-line) due to below threshold input voltages, it cannot be restarted until the system voltage is at least this % of the nominal. Single-phase-to-ground fault occurring on the utility side of a delta-wye distribution transformer. The SRT provides continuous correction and only transitions to and from BYPASS when manually starting and stopping or under fault or overload conditions. The transition from bypass to inverter takes up to 750 ms. The autoresettable bypass mode of operation includes an additional 5-second delay allowing time for the fault to clear.

CA08101001E

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Conditioning Products

10-28

July 2007

Sag Ride Through Table 10-22. SRT Controller Cabinet Dimensions Inverter Frame Size

Load Capacity (kVA) 380/400 V 50/60 Hz

Controller Cabinet Dimensions 208 /480/600 V H x W x D Inches (mm) 60 Hz

Controller Weight Lbs. (kg)

Controller Dissipation (Worst Case) %

Airflow m3/min.

kW

1S 2S 3S

20 40 60

25 50 75

35.43 x 23.62 x 27.56 (900 x 600 x 700) 35.43 x 23.62 x 27.56 (900 x 600 x 700) 35.43 x 23.62 x 27.56 (900 x 600 x 700)

551 (250) 727 (330) 881 (400)

1.8 1.8 1.8

0.5 0.9 1.4

2 2 2

2M 3M 1L

140 200 300

175 250 350

84.84 x 31.50 x 31.69 (2155 x 800 x 805) 84.84 x 31.50 x 31.69 (2155 x 800 x 805) 84.84 x 31.50 x 31.69 (2155 x 800 x 805)

1674 (760) 2070 (940) 1542 (700)

1.8 1.8 0.8

3.2 4.5 2.8

4 6 6

2K 2L 3L

400 500 750

500 650 1000

84.84 x 55.12 x 31.69 (2155 x 1400 x 805) 84.84 x 55.12 x 31.69 (2155 x 1400 x 805) 84.84 x 63.00 x 31.69 (2155 x 1600 x 805)

1982 (900) 2093 (950) 2423 (1100)

0.8 0.8 0.8

4.0 5.2 8.0

12 12 18

4L 5L 6L

1000 1250 1500

1250 1500 2000

84.84 x 78.74 x 31.69 (2155 x 2000 x 805) 84.84 x 78.74 x 31.69 (2155 x 2000 x 805) 84.84 x 94.49 x 31.69 (2155 x 2400 x 805)

2753 (1250) 3084 (1400) 3634 (1650)

0.8 0.8 0.8

10.0 12.0 16.0

24 30 36

208 V models are available in 25 – 250 kVA only.

Table 10-23. SRT Transformer Cabinet Dimensions Transformer Cabinet Dimensions H x W x D Inches (mm)

Transformer Weight Lbs. (kg)

1S 2S 3S

In Controller Cabinet In Controller Cabinet In Controller Cabinet

2M 3M 1L

Inverter Frame Size

10

Transformer Dissipation (Worst Case) %

kW

— — —

— — —

— — —

In Controller Cabinet In Controller Cabinet 35.43 x 32.48 x 27.95 (900 x 825 x 710)

— — 1211 (550)

— — <1.0

— — 3.0

2K 2L 3L

39.37 x 35.43 x 35.43 (1000 x 900 x 900) 39.37 x 39.37 x 37.40 (1000 x 1000 x 950) 43.30 x 39.37 x 37.40 (1100 x 1000 x 950)

1762 (800) 1982 (900) 2423 (1100)

<1.0 <1.0 <1.0

4.0 5.0 6.0

4L 5L 6L

51.18 x 55.12 x 47.24 (1300 x 1400 x 1200) 51.18 x 55.12 x 47.24 (1300 x 1400 x 1200) 55.12 x 59.06 x 47.24 (1400 x 1500 x 1200)

3084 (1400) 3744 (1700) 4405 (2000)

<1.0 <1.0 <1.0

7.0 8.0 9.0

Nominal dimensions and weights. Consult factory for precise values.

Table 10-24. 30% Correction Model Catalog Numbering System

Table 10-25. SRTS — SEMI F47 Compliant Version 40% Correction Model Catalog Numbering System

SRT

SRTS

kVA Rating 25 50 75 175 250 350

500 650 1000 1250 1500 2000

Keypad Voltage 208 480 600

Frequency A = 60 Hz B = 50 Hz

kVA Rating

K = Yes Blank = No

17 33 50 110 175 250

Bypass A = No B = Yes

3-phase, 3-wire. Keypad is standard on 175 kVA and larger.

350 425 650 900 1100 1300

Keypad Voltage 208 480 600

Frequency A = 60 Hz B = 50 Hz

K = Yes Blank = No

Bypass A = No B = Yes

3-phase, 3-wire. Keypad is standard on 110 kVA and larger.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-29 Power Conditioning Products July 2007

Electronic Voltage Regulator

Electronic Voltage Regulator

The IEEE defines voltage regulation as overvoltage or undervoltage. Voltage regulation events last from a few minutes to many hours with voltage varying by +/- 20%. Long-term regulation problems differ from short duration sags and dips, which are much deeper voltage drops.

The Solution

Electronic Voltage Regulator (EVR) Tap Changer

Product Description Electronic Voltage Regulator The Cutler-Hammer Electronic Voltage Regulator (EVR) is the ideal solution for keeping your facility and equipment up and running during brownouts, undervoltage conditions and other power problems. The EVR can significantly reduce the costs of equipment damage and downtime when these situations occur. The state-ofthe-art design provides rapid response time, high efficiency, high inrush current capability, and operating advantages exclusive to Eaton.

Prior to installing an expensive solution, Eaton encourages customers to monitor incoming voltage to determine if voltage regulation is a problem. The local utility may also be able to provide information on voltage expected at the facility. Using a meter, it can quickly be determined if a voltage regulation problem or brownout condition exists. The appropriate solution would be an Electronic Voltage Regulator (EVR). EVRs can be installed at the service entrance, branch panel or at critical loads

Features and Benefits ■

■ ■ ■

■ ■

Coordinated with standard thermalmagnetic breakers to allow motor starts. Optional 100 kA per phase surge protection. Input frequency range operation from 57 – 63 Hz. Not affected by load power factor. Can operate effectively in low-load applications due to “unique leakage reactance” technology. Failsafe bypass circuit, isolation transformer and overtemperature protection. Less than 1% THD. Monitoring panel displays rms metering, output voltage and current, kVA, under- and overvoltage, phase rotation, phase loss, first and second stage temperature alarm, shut-off, EPO tripped and eight optional external ports.

The Cutler-Hammer Electronic Voltage Regulator is a solid-state tap changing power conditioner designed to protect against brownouts and long duration voltage regulation problems. Table 10-26. EVR Specification (10 to 1250 kVA) Feature

Description

Technology

Electronic Tap Changer

Input Voltages

240 – 600 Vac; 3-phase (3-wire)

The EVR maintains a tightly regulated output voltage by automatically activating the appropriate transformer tap through a silicone controlled rectifier (SCR). Tap changer response time is initiated at one cycle, ensuring rapid and precise regulation. Switching at zero current enables noise reduction during tap transitions.

Input Voltage Range

+ 10/-26%

Brownouts

Noise Attenuation Common Mode Normal Mode

In the United States, most facilities have sufficient voltage regulation. However, in some U.S. locations and many developing countries, regulation problems occur because of overstressed utility distribution systems. In some cases, due to the excessive demand on the utility system, voltage may be below 10% of nominal (-10%) during the day. This condition is called a voltage regulation or brownout. Customers may notice dim lights and reduced power. During the evening, voltage may rise above 10% of nominal (+10%) because large facilities and loads are shut down. This shutdown reduces the power demand on the grid and results in a voltage increase.

CA08101001E

Output Voltage Range

± 3% typical

Response Time

1 cycle, zero current switching

Frequency

60 Hz standard (other frequencies available)

Efficiency

96% at full load, 98.5% at light loads

Minimum Load

None

Inrush Current Capabilities

1000% for one cycle; 200% for 10 seconds; or as limited by upstream overcurrent protection – 120 dB at 100 kHz – 40 dB at 100 kHz

Monitoring (Option)

Refer to “Features and Benefits” for details

Bypass Panel

Yes

Surge Protection Device (Option)

100 kA per phase

Operating Temperature

0 to +50°C

Altitude

Up to 7,000 ft. (2,134 m)

Standard Warranty

12/18 months

Extended Warranty (Startup Service)

12/18 months factory on-site warranty

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Conditioning Products

10-30

July 2007

Electronic Voltage Regulator

Product Selection Table 10-27. EVR Catalog Numbering System

EVR EVR Dimensions (Without Monitoring Option) kVA

10

Weight in Pounds (kg)

BTUs/HR

I/O Regulator (Input/Output Regulator)

Dimensions (H" x W" x D")

Code

Option

Input Voltage Range

Output Voltage Range

S P

Standard Premium

+10/-26% +8/-10%

+/-3% +/-1.5%

10 15 20 30

400 (182) 400 (182) 450 (204) 500 (227)

2040 2040 3050 4080

32.00 x 26.50 x 17.00 32.00 x 26.50 x 17.00 32.00 x 26.50 x 17.00 32.00 x 26.50 x 17.00

50 75 100 150

700 (318) 850 (386) 1000 (454) 1100 (499)

6800 10,200 13,600 17,000

40.50 x 31.50 x 22.00 40.50 x 31.50 x 22.00 66.00 x 50.50 x 32.00 66.00 x 50.50 x 32.00

200 250 300 400

2000 (908) 2450 (1112) 2900 (1317) 3900 (1771)

27,200 34,000 40,800 50,700

66.00 x 50.50 x 32.00 66.00 x 50.50 x 32.00 66.00 x 50.50 x 32.00 73.00 x 67.00 x 35.50

500 600 750 875

4250 (1930) 6500 (2951) 7500 (3405) 8500 (3859)

60,600 70,400 80,800 90,600

73.00 x 67.00 x 35.50 73.00 x 67.00 x 35.50 73.00 x 67.00 x 35.50 73.00 x 67.00 x 35.50

1000 1250

9500 (4313) 99,600 10,500 (4767) 105,000

Monitoring Option X = No M = Monitoring Surge Protection X = No S = Yes Frequency

73.00 x 100.00 x 35.50 73.00 x 100.00 x 35.50

A = 60 Hz B = 50 Hz

EVR Dimensions (With Monitoring Option) kVA

BTUs/HR

Dimensions (H" x W" x D")

Output Voltage Code (Delta Input: L, L, L, N, G)

10 15 20 30

440 (200) 440 (200) 500 (227) 550 (250)

2040 2040 3050 4080

73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50

50 75 100 150

770 (350) 940 (427) 1100 (499) 1250 (568)

6800 10,200 13,600 17,000

73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50

Input Voltage Code (Delta Input: L, L, L, G)

200 250 300 400

2200 (999) 2750 (1249) 3200 (1453) 4300 (1952)

27,200 34,000 40,800 50,700

73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50 73.00 x 34.00 x 35.50 73.00 x 67.00 x 35.50

240D = 240 400D = 400 480D = 480 600D = 600

500 600 750 875

4350 (1975) 7150 (3246) 8250 (3746) 9350 (4250)

60,600 70,400 80,800 90,600

73.00 x 67.00 x 35.50 73.00 x 67.00 x 35.50 73.00 x 67.00 x 35.50 73.00 x 67.00 x 35.50

1000 1250

Weight in Pounds (kg)

10,450 (4744) 99,600 11,550 (5244) 105,000

73.00 x 100.00 x 35.50 73.00 x 100.00 x 35.50

208Y = 120/208 400Y = 230/400 480Y = 277/480 600Y = 347/600

Examples: Catalog Number: EVR0075480D480YAXXS – 75 kVA EVR, 480 V in, 277/480 V out, 60 Hz, no options Extended Description: EVR-75-480D-480Y/277-AXXS Catalog Number: EVR0500208D208YASMP – 500 kVA EVR, 208 V in, 120/208 V out, 60 Hz, with: Surge, Monitoring and Premium Regulation options Extended Description: EVR-500-208D-208Y/120-ASMP

For dimensions in mm, multiply by 25.4. Dimensions listed are for 208 V in model. Dimensions for 480 V in model are: 100 kVA – 40.5"H x 31.5"W x 22.0"D, 100 kVA – 51.5"H x 40.5"W x 26.5"D.

Note: All weights are approximate. Monitor option includes main input circuit breaker. Note: Refer to PAD for pricing and availability.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-31 Power Factor Capacitors and Harmonic Filters July 2007

Power Factor Correction Capacitors

Power Factor Correction Capacitors

When capacity becomes a problem, the choice of a solution will be dependent upon the size of the increase needed. Like all power quality solutions, there are many factors that need to be considered when determining which solution will be best to solve your power factor problem.

Harmonic Filtering As the world becomes more dependent on electric and electronic equipment, the likelihood that the negative impact

of harmonic distortion increases dramatically. The efficiency and productivity gains from these increasingly sophisticated pieces of equipment have a negative side effect…increased harmonic distortion in the power lines. The difficult thing about harmonic distortion is determining the cause. Once this has been determined, the solution can be easy. Passive and active harmonic filtering equipment will mitigate specific harmonic issues, and correct poor power factor as well.

Product Selection Table 10-28. Capacitor Cell Chart Voltage

kvar

Dimensions in Inches (mm) D

Capacitor Cell With M12 Threaded Mounting Bolt, Washer, Nut

Product Description Eaton introduces Cutler-Hammer power factor correction capacitor banks and harmonic filters. Power factor correction capacitors and harmonic filters are an essential part of modern electric power systems. Power factor correction capacitors are the simplest and most economical means of increasing the capacity of any power system, minimizing energy losses and correcting load power factor. In addition, power factor penalties can be reduced and power quality can be greatly enhanced. There are several reasons to correct poor power factor. The first is to reduce or eliminate a power factor penalty charged by the utility. Another reason is that your existing transformer is, or shortly will be, at full capacity and installing power factor correction capacitors can be a very cost-effective solution to installing a brand new service. Depending on the amount of power factor correction (kvar that needs to be injected into the electrical system to improve the power factor) and the dynamic nature of the load, a fixed or switched capacitor bank may be the best solution.

CA08101001E

H

Weight in Lbs. (kg)

Part Number

240 240 240

1.5 2 2.5

3.1 (79.5) 3.1 (79.5) 3.1 (79.5)

7.9 (200.0) 9.4 (238.0 9.4 (238.0)

1.1 (0.5) 1.3 (0.6) 1.3 (0.6)

643PCRMA 8B43PCRMA 1043PCRMA

240 240 240

3 4 5

3.5 (89.5) 3.1 (79.5) 3.5 (89.5)

9.4 (238.0) 7.9 (200.0) 12.3 (313.0)

1.8 (0.8) 1.1 (0.5) 2.6 (1.2)

12X43PCRMA 423PCRMA 2043PCRMA

240 240 240

6.3 7.5 8.3

3.1 (79.5) 3.1 (79.5) 3.5 (89.5)

9.4 (238.0) 9.4 (238.0) 9.4 (238.0)

1.3 (0.6) 1.3 (0.6) 1.8 (0.8)

6B23PCRMA 7X23PCRMA 8B23PCRMA

240 240 240

10 12.5 15

3.5 (89.5) 3.5 (89.5) 3.5 (89.5)

9.4 (238.0) 12.3 (313.0) 12.3 (313.0)

1.3 (0.6) 2.6 (1.2) 2.6 (1.2)

1023PCRMA 12X23PCRMA 1523PCRMA

240 240 480

16.7 17.5 1.5

3.5 (89.5) 3.5 (89.5) 2.1 (53.0)

15.3 (388.0) 15.3 (388.0) 5.0 (125.8)

3.3 (1.5) 3.3 (1.5) 0.7 (0.3)

16S23PCRMA 17X23PCRMA 1X43PCRMA

480 480 480

2 2.5 3

2.5 (63.5) 2.5 (63.5) 2.5 (63.5)

5.5 (140.8) 5.5 (140.8) 5.5 (140.8)

0.9 (0.4) 0.9 (0.4) 0.9 (0.4)

243PCRMA 2X43PCRMA 343PCRMA

480 480 480

4 5 6

2.5 (63.5) 2.5 (63.5) 3.1 (79.5)

6.5 (165.8) 6.5 (165.8) 7.9 (200.0)

0.9 (0.4) 0.9 (0.4) 1.1 (0.5)

443PCRMA 543PCRMA 643PCRMA

480 480 480

7.5 8.3 9

3.1 (79.5) 3.1 (79.5) 3.1 (79.5)

7.9 (200.0) 9.4 (238.0) 9.4 (238.0)

1.1 (0.5) 1.3 (0.6) 1.3 (0.6)

7X43PCRMA 8B43PCRMA 943PCRMA

480 480 480

10 12.5 15

3.1 (79.5) 3.5 (89.5) 3.5 (89.5)

9.4 (238.0) 9.4 (238.0) 9.4 (238.0)

1.3 (0.6) 1.8 (0.8) 1.8 (0.8)

1043PCRMA 12X43PCRMA 1543PCRMA

480 480 480

18 20 25

3.5 (89.5) 3.5 (89.5) 3.5 (89.5)

12.3 (313.0) 12.3 (313.0) 12.3 (313.0)

2.6 (1.2) 2.6 (1.2) 2.6 (1.2)

1843PCRMA 2043PCRMA 2543PCRMA

480 600 600

30 5 7.5

3.5 (89.5) 3.1 (79.5) 3.1 (79.5)

15.3 (388.0) 9.4 (238.0) 9.4 (238.0)

3.3 (1.5) 1.3 (0.6) 1.3 (0.6)

3043PCRMA 563PCRMA 7X63PCRMA

600 600 600

10 12.5 15

3.1 (79.5) 3.5 (89.5) 3.5 (89.5)

9.4 (238.0) 9.4 (238.0) 12.3 (313.0)

1.3 (0.6) 1.8 (0.8) 2.6 (1.2)

1063PCRMA 12X63PCRMA 1563PCRMA

600 600

17.5 20

3.5 (89.5) 3.5 (89.5)

12.3 (313.0) 15.3 (388.0)

2.6 (1.2) 3.3 (1.5)

2063PCRMA 2563PCRMA

Note: Kvar rating standard. NEMA kvar tolerance is +15% to 0%. Part number shown is for 3-phase units. Up to 5 kvar at 480 V — fast-on terminals are standard. Above 5 kvar at 480 V (and on all other voltages) — sigut terminals are standard.

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-32

July 2007

Power Factor Correction Capacitors Table 10-29. Harmonic Rated Capacitor Cell Chart Voltage

kvar

D

Dimensions in Inches (mm) H

Weight in Lbs. (kg)

Part Number

240 480 480

12.5 15.0 25.0

3.5 (89.5) 3.5 (89.5) 3.5 (89.5)

15.3 (388.0) 12.3 (313.0) 15.3 (388.0)

3.3 (1.5) 2.6 (1.2) 3.3 (1.5)

12X23PHRMA 1543PHRMA 2543PHRMA

600 600 600

12.3 14.7 16.7

3.5 (89.5) 3.5 (89.5) 3.5 (89.5)

12.3 (313.0) 15.3 (388.0) 15.3 (388.0)

2.6 (1.2) 3.3 (1.5) 3.3 (1.5)

12A63PHRMA 14S63PHRMA 16S63PHRMA

Technical Data and Specifications Dimensions

10

Figure 10-19. Capacitor Cell Dimensions

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-33 Power Factor Capacitors and Harmonic Filters July 2007

UNIPUMP

UNIPUMP Power Factor Correction Capacitors

Capacitor Cells Terminals: Insulated finger-safe terminals rated for 3 kVAC withstand. Rated for 30 kV BIL. ■ Dielectric fill: Dry-type cells utilize soft organic polymer resin — Resinol. ❑ Eliminates potential for corona / partial discharge / electrochemical oxidation. ❑ Excellent heat dissipation ❑ Flash point: +444°F (+229°C) ❑ Fire point: +840°F (+449°C) ■

Design: Self-healing metallized high crystalline polypropylene with ramp metallization film. Total losses less than .45 watt per kvar. (Dielectric losses less than .2 watt per kvar.) ■ Ramp metallization: Provides thicker film at higher current density areas, allowing for reduced internal losses, lower operating temperatures and longer life expectancy. ■

UNIPUMP

Product Description

Product Selection

Non-fused capacitors for outdoor irrigation and oil field installations.

Table 10-30. UNIPUMP Selection Chart

■ ■ ■ ■ ■ ■ ■

Designed expressly for outdoor pumping applications. Pole or wall mounting. Small, light-weight enclosure for easy installation. SO-WA type flexible cable facilitates installation (4-conductor). Gland-type weatherproof bushings. Strong outer case. UL and CSA listed.

Applications Outdoor irrigation and oil and gas field pumping.

Features and Specifications Configuration ■

Outer case: Heavy, No. 14 gauge steel finished with durable baked-on enamel. Integral strap mounting bracket with keyhole at top for pole or wall installation. No knockouts.

CA08101001E

kvar

Rated Current

■ ■ ■

Also prevents chain reaction breakdown by limiting propagation of film vaporization. Pressure sensitive interrupter: Builtin, three-phase pop-up interrupter design. UL recognized. Removes capacitor from line before internal pressure can cause case rupture. Bulged capacitor cell top provides easy visual indication of interrupter operation. Ceramic discharge resistors: Reduce residual voltage to less than 50 volts within one minute of de-energization. Selected for 20-year nominal life. Exceeds NEC requirements. Capacitor operating temperature: -40°F (-40°C) to +115°F (+46°C). Case: Weatherproof aluminum housing. Warranty: The longest in the industry — five full years of warranty on capacitor cells.

Case Size

Cable Size

Shipping Weight in Lbs. (kg)

Catalog Number

240 Vac 2 2.5 3

4.8 6.0 7.2

AA AA AA

14.0 14.0 14.0

10.0 (4.7) 10.0 (4.7) 10.0 (4.7)

223JMR 2X23JMR 323JMR

4 5 6 7.5

9.6 12.0 14.4 18.0

AA AA BB BB

14.0 14.0 12.0 12.0

11.0 (4.8) 11.0 (4.8) 15.0 (6.6) 15.0 (6.6)

423JMR 523JMR 623JMR 7X23JMR

2 2.5 3

2.4 3.0 3.6

AA AA AA

14.0 14.0 14.0

10.4 (4.7) 10.4 (4.7) 10.4 (4.7)

243JMR 2X43JMR 343JMR

4 5 6

4.8 6.0 7.2

AA AA AA

14.0 14.0 14.0

10.4 (4.7) 10.4 (4.7) 10.6 (4.8)

443JMR 543JMR 643JMR

7.5 10 12.5

9.0 12.0 15.0

AA AA BB

14.0 14.0 12.0

10.6 (4.8) 10.8 (4.9) 15.0 (6.8)

7X43JMR 1043JMR 12X43JMR

15 17.5 20 25

18.0 21.0 24.0 30.0

BB BB BB BB

12.0 8.0 8.0 8.0

15.0 (6.8) 15.8 (7.2) 16.8 (7.7) 16.8 (7.7)

1543JMR 17X43JMR 2043JMR 2543JMR

5 6 7.5

4.9 5.9 7.4

AA AA AA

14.0 14.0 14.0

10.8 (4.9) 10.8 (4.9) 10.8 (4.9)

563JMR 663JMR 7X63JMR

10 12.5 15

9.8 12.3 14.7

AA AA BB

14.0 12.0 12.0

10.8 (4.9) 15.0 (6.8) 15.8 (7.2)

1063JMR 12X63JMR 1563JMR

17.5 20

17.2 19.6

BB BB

8.0 8.0

16.8 (7.7) 16.8 (7.7)

17X63JMR 2063JMR

480 Vac

600 Vac

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-34

July 2007

UNIPUMP

Technical Data and Specifications Dimensions Table 10-31. UNIPUMP Dimension Chart Size Code

Dimensions in Inches (mm) A

B

C

D

AA

11.0 (279.7)

14.2 (360.9)

12.6 (320.0)

13.2 (335.5)

BB

14.0 (354.5)

17.1 (435.6)

15.5 (394.7)

16.1 (410.2)

10

Figure 10-20. UNIPUMP Dimensions

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-35 Power Factor Capacitors and Harmonic Filters July 2007

UNIPAK

UNIPAK

■ ■ ■ ■ ■ ■ ■

Wall (up to 180 kvar) and floor-mounted units available. Fuse protection standard. Blown-fuse indicating lights standard. Quick lead-times. Harmonic filters available. Slim profile allows reduced footprint, conserving valuable floor space. New capacitor configuration leads to cooler operating conditions, extending capacitor life.

Options: ❑ No fuses ❑ Fused, no indicating lights ❑ Air filters for units 200 kvar and above

Standards and Certifications ■

UL and CSA listed.

Features and Specifications Configuration Outer case: Heavy, No. 14 gauge steel finished with durable baked-on enamel. Wall mounting flanges and floor mounting feet. Elimination of knockouts permits indoor/outdoor use. Manufactured to NEMA requirements 1, 3R and 12. ■ Elevated floor mounting feet allow access for easy maintenance.

UNIPAK with Optional Air Filter

UNIPAK Filter — Harmonic Filtering

UNIPAK

Capacitor Cells ■

Note: NEMA 12 up to 180 kvar only.

Cover: “L” shaped gasketed cover with multiple fasteners provides front opening for ease of installation and service. ■ Ground terminal: Furnished inside case. ■ Power terminal lugs: Large size provided for easy connection. ■ Fusing: ❑ Size Code A1: Three midget-type fuses with 100,000 ampere interrupting capacity ❑ Size Code A2 and larger: Three slotted-blade type fuses with 200,000 ampere interrupting capacity; Fuses mounted on stand-off bushings or fuse blocks; Solderless connectors for easy hookup of incoming line conductors ❑ Fuse indicating lights: Red, neon blown-fuse indicating lights are protected by transparent weatherproof guard ■

UNIPAK Interior

Features, Benefits and Functions Five-year warranty on capacitor cells. Designed for heavy-duty applications. ■ Twenty-year life design. ■ Indoor/outdoor service. ■ ■

CA08101001E

For more information visit: www.eaton.com

Terminals: Insulated finger-safe terminals rated for 3 kVAC withstand. Rated for 30 kV BIL. Dielectric fill: Dry-type cells utilize soft organic polymer resin — Resinol. ❑ Eliminates potential for corona / partial discharge / electrochemical oxidation. ❑ Excellent heat dissipation ❑ Flash point: +444°F (+229°C) ❑ Fire point: +840°F (+449°C) Design: Self-healing metallized high crystalline polypropylene with ramp metallization film. Total losses less than .45 watt per kvar. (Dielectric losses less than .2 watt per kvar.) Ramp metallization: Provides thicker film at higher current density areas, allowing for reduced internal losses, lower operating temperatures and longer life expectancy. Also prevents chain reaction breakdown by limiting propagation of film vaporization. Pressure sensitive interrupter: Builtin, three-phase pop-up interrupter design. UL recognized. Removes capacitor from line before internal pressure can cause case rupture. Bulged capacitor cell top provides easy visual indication of interrupter operation.

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-36

July 2007

UNIPAK Ceramic discharge resistors: Reduce residual voltage to less than 50 volts within one minute of de-energization. Selected for 20-year nominal life. Exceeds NEC requirements. ■ Capacitor operating temperature: -40°F (-40°C) to +115°F (+46°C). ■ Case: Weatherproof aluminum housing. ■ Warranty: The longest in the industry — five full years of warranty on capacitor cells. ■

UNIPAK Filter — Harmonic Filtering Harmonic filter systems for low voltage, heavy-duty applications. ■ ■

Harmonic Rated Capacitor Cells Standard voltage rated capacitor cells designed for higher dielectric strength and with added ability to withstand stress caused by dv/dt voltage transients caused by harmonics. ■ Better suited for harmonic applications than higher voltage rated cells. ■

10

UNIPAK with Harmonic Rated Capacitor Cells Standard capacitor systems utilizing harmonic rated capacitor cells. ■ For use in moderate harmonic environments where engineering supervision allows in place of harmonic filter designs. ■ Provides future conversion capability into a harmonic filter design due to facility growth or increased non-linear load levels. ■

■ ■ ■ ■

Reduce harmonics and correct power factor. Tuned for maximum efficiency in reducing harmonic currents associated with non-linear load environments (such as VFDs). Two-enclosure design isolates capacitors from high-temperature operating reactors, and allows for flexible installation. Twenty-year life design. Five-year cell warranty / one-year reactor warranty. Three-phase cell capacitor construction. Three-phase interrupter system. UL and CSA listed.

Construction: 100% copper windings for cool operating temperatures; designed operating temperature rise less than 80ºC. Open frame construction with 220ºC insulation system. ■ Thermal sensors: One per phase, self-resetting thermistors provide reactor over-temperature protection and indication. ■ Reactor indicating light: Thermal overload indicating light activates when reactor temperature reaches 180ºC. ■ Warranty: One-year replacement of reactors. ■

Applications Designed for power factor correction in plants experiencing harmonics problems due to high amounts of non-linear loads.

Reactors Tuning: Tuned to 4.7 harmonic order. ■ Detuning: Reactor designs can be detuned upon request (4.2nd, 6.7th for example) to protect capacitors against alternate harmonics. ■

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-37 Power Factor Capacitors and Harmonic Filters July 2007

UNIPAK

Product Selection UNIPAK Low Voltage Fixed Capacitor Banks Table 10-32. 240 Vac UNIPAK Selection Chart kvar

Rated Current

Table 10-33. 480 Vac UNIPAK Selection Chart

Enclosure Shipping Weight in Lbs. (kg)

Part Number

kvar

Enclosure

Rated Current

Shipping Weight in Lbs. (kg)

Part Number

1 1.5 2

2.4 3.6 4.8

A1 A1 A1

18 (8) 18 (8) 19 (9)

123PMURF 1X23PMURF 223PMURF

1.5 2 2.5

A1 A1 A1

1.8 2.4 3

17 (8) 18 (8) 18 (8)

1X43PMURF 243PMURF 2X43PMURF

2.5 3 4

6 7.2 9.6

A1 A1 A1

19 (9) 19 (9) 20 (9)

2X23PMURF 323PMURF 423PMURF

3 4 5

A1 A1 A1

3.6 4.8 6

19 (9) 19 (9) 19 (9)

343PMURF 443PMURF 543PMURF

5 6 7.5

12 14.4 18

A2 A2 A2

29 (13) 29 (13) 30 (14)

523PMURF 623PMURF 7X23PMURF

6 7.5 8

A1 A1 A1

7.2 9 9.6

19 (9) 20 (9) 20 (9)

643PMURF 7X43PMURF 843PMURF

8 10 12.5

19.2 24 30

A2 A2 A2

31 (14) 31 (14) 32 (14)

823PMURF 1023PMURF 12X23PMURF

9 10 12.5

A1 A1 A2

10.8 12 15

20 (9) 20 (9) 29 (13)

943PMURF 1043PMURF 12X43PMURF

15 17.5 20

36 42 48

A2 B1 B1

33 (15) 44 (20) 45 (20)

1523PMURF 17X23PMURF 2023PMURF

15 17.5 20

A2 A2 A2

18 21 24

29 (13) 30 (14) 31 (14)

1543PMURF 17X43PMURF 2043PMURF

22.5 25 30

54 60 72

B1 B1 B1

46 (21) 46 (21) 47 (21)

22X23PMURF 2523PMURF 3023PMURF

22.5 25 27.5

B1 A2 B1

27 30 33

44 (20) 32 (15) 44 (20)

22X43PMURF 2543PMURF 27X43PMURF

32.5 35 40

78 84 96

B1 B1 C1

47 (22) 48 (22) 64 (29)

32X23PMURF 3523PMURF 4023PMURF

30 32.5 35

B1 B1 B1

36 39 42

44 (20) 45 (20) 45 (20)

3043PMURF 32X43PMURF 3543PMURF

42.5 45 50

102 108 120

C1 C1 C1

65 (30) 66 (30) 68 (31)

42X23PMURF 4523PMURF 5023PMURF

37.5 40 42.5

B1 B1 B1

45 48 51

46 (21) 46 (21) 47 (21)

37X43PMURF 4043PMURF 42X43PMURF

60 70 75

144 168 180

C1 C2 C2

69 (31) 99 (45) 100 (46)

6023PMURF 7023PMURF 7523PMURF

45 50 55

B1 B1 B1

54 60 66

47 (22) 48 (22) 48 (22)

4543PMURF 5043PMURF 5543PMURF

80 90 100

192 216 240

C2 C2 C2

101 (46) 103 (47) 104 (47)

8023PMURF 9023PMURF 10023PMURF

60 65 70

B1 C1 C1

72 78 84

48 (22) 64 (29) 65 (30)

6043PMURF 6543PMURF 7043PMURF

120 140 150

288 336 360

D1 D1 D1

133 (60) 137 (62) 140 (64)

12023PMURF 14023PMURF 15023PMURF

75 80 85

C1 C1 C1

90 96 102

65 (30) 66 (30) 68 (31)

7543PMURF 8043PMURF 8543PMURF

160 180 200

384 432 480

E1 E1 E1

175 (80) 182 (83) 189 (86)

16023PMURF 18023PMURF 20023PMURF

90 100 120

C1 C1 C1

108 120 144

68 (31) 69 (31) 69 (31)

9043PMURF 10043PMURF 12043PMURF

125 140 150

C2 C2 C2

150 168 180

99 (45) 100 (46) 101 (46)

12543PMURF 14043PMURF 15043PMURF

160 180 200

C2 C2 D1

192 216 240

103 (47) 104 (47) 137 (62)

16043PMURF 18043PMURF 20043PMURF

225 250 300

D1 E1 E1

270 300 360

140 (64) 170 (77) 175 (80)

22543PMURF 25043PMURF 30043PMURF

350 400

E1 E1

420 480

182 (83) 189 (86)

35043PMURF 40043PMURF

Notes:

Multiply the 240 Vac kvar rating by 0.75 to calculate the kvar value at 208 Vac. ■ Fused with blown-fuse indication available standard. Non-fused and no lights also available — please consult the factory. ■ Other ratings available, consult factory. ■ For dimensional information, refer to Page 10-40. ■

Part Numbers: ■

Notes:

PMURF – 3 Fuses + 3 Lights. PMUR3 – 3 Fuses + No Lights. ■ PMURN – Non-Fused.

CA08101001E

Fused with blown-fuse indication available standard. Non-fused and no lights also available — please consult the factory. ■ Other ratings available, consult factory. ■ For dimensional information, refer to Page 10-40. ■

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-38

July 2007

UNIPAK

UNIPAK Low Voltage Fixed Capacitor Banks (Continued)

UNIPAK — with Harmonic Cells

Table 10-34. 600 Vac UNIPAK Selection Chart

Table 10-35. Low Voltage Fixed Capacitor Systems with Harmonic Cells

kvar

Enclosure

Rated Current

Shipping Weight in Lbs. (kg)

Part Number

5 7.5 10

A1 A1 A1

4.9 7.4 9.8

19 (9) 19 (9) 20 (9)

563PMURF 7X63PMURF 1063PMURF

12.5 15 17.5

A1 A2 A2

12.3 14.7 17.2

20 (9) 29 (13) 29 (13)

12X63PMURF 1563PMURF 17X63PMURF

20 22.5 25

A2 B1 A2

19.6 22.1 24.5

30 (14) 44 (20) 31 (14)

2063PMURF 22X63PMURF 2563PMURF

27.5 30 32.5

B1 B1 B1

27.0 29.4 31.9

44 (20) 45 (20) 45 (20)

27X63PMURF 3063PMURF 32X63PMURF

35 37.5 40

B1 B1 B1

34.3 36.8 39.2

46 (21) 46 (21) 47 (21)

3563PMURF 37X63PMURF 4063PMURF

42.5 45 50

B1 B1 B1

41.7 44.1 49.0

47 (22) 48 (22) 48 (22)

42X63PMURF 4563PMURF 5063PMURF

55 60 65

C1 C1 C1

53.9 58.8 63.7

64 (29) 64 (29) 65 (30)

5563PMURF 6063PMURF 6563PMURF

70 75 80

C1 C1 C1

68.6 73.5 78.4

65 (30) 66 (30) 68 (31)

7063PMURF 7563PMURF 8063PMURF

85 90 100

C1 C1 C1

83.3 88.2 98.0

68 (31) 69 (31) 69 (31)

8563PMURF 9063PMURF 10063PMURF

120 125 140

C2 C2 C2

117.6 122.5 137.2

99 (45) 100 (46) 101 (46)

12063PMURF 12563PMURF 14063PMURF

150 160 180

C2 D1 D1

147.0 156.8 176.4

103 (47) 135 (61) 137 (62)

15063PMURF 16063PMURF 18063PMURF

200 225 250

D1 D1 E1

196.0 220.5 245.0

140 (64) 143 (65) 170 (77)

20063PMURF 22563PMURF 25063PMURF

300 350 400

E1 E1 E1

294.0 343.0 392.0

175 (80) 182 (83) 189 (86)

30063PMURF 35063PMURF 40063PMURF

10

kvar

Rated Current

Case Size

Shipping Weight in Lbs. (kg)

Fused Catalog Number

240 V 15 25 30

36 60 72

B1 B1 C1

38.4 (17) 38.4 (17) 55.2 (25)

1523HURF 2523HURF 3023HURF

50 60 75

120 144 180

C1 C2 C2

57.6 (26) 100.8 (46) 104.4 (47)

5023HURF 6023HURF 7523HURF

100 125

240 300

D1 E1

136.8 (62) 189.6 (86)

10023HURF 12523HURF

15 25 30

18 30 36

A2 B1 B1

25.2 (11) 37.2 (17) 38.4 (17)

1543HURF 2543HURF 3043HURF

50 60 75

60 72 90

B1 C1 C1

39.6 (18) 52.8 (24) 55.2 (25)

5043HURF 6043HURF 7543HURF

100 125 150

120 150 180

C1 C2 C2

57.6 (26) 100.8 (46) 104.4 (47)

10043HURF 12543HURF 15043HURF

200 250 300

240 300 360

D1 E1 E1

136.8 (62) 186.0 (84) 189.6 (86)

20043HURF 25043HURF 30043HURF

480 V

600 V 15 25 30

14.7 24.5 29.4

B1 B1 B1

37.2 (17) 38.4 (17) 39.6 (18)

1563HURF 2563HURF 3063HURF

50 60 75

49 58.8 73.5

C1 C1 C2

55.2 (25) 57.6 (26) 100.8 (46)

5063HURF 6063HURF 7563HURF

100 125 150

98 122.5 147

C2 D1 D1

104.4 (47) 136.8 (62) 136.8 (62)

10063HURF 12563HURF 15063HURF

200 250

196 245

E1 E1

186.0 (84) 189.6 (86)

20063HURF 25063HURF

Notes:

Fused with blown-fuse indication available standard. Non-fused and no lights also available — please consult the factory. ■ Other ratings available, consult factory. ■ For dimensional information, refer to Page 10-40. ■

Part Numbers: PMURF – 3 Fuses + 3 Lights. PMUR3 – 3 Fuses + No Lights. ■ PMURN – Non-Fused. ■ ■

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-39 Power Factor Capacitors and Harmonic Filters July 2007

UNIPAK

UNIPAK Low Voltage Fixed Harmonic Filters Table 10-36. Fixed UNIPAK Harmonic Filters kvar

Rated Current

Case Size

Shipping Weight Lbs.

Reactor Shipping Weight

Combined Shipping Weight

kg

Reactor Cabinet Case Size

Lbs.

Lbs.

kg

kg

Fused Catalog Number

240 V 15 25 30

36 60 72

B1 B1 C1

48.4 48.4 65.2

22.0 22.0 29.6

R R R

90.0 105.0 110.0

40.9 47.7 49.9

138.4 153.4 175.2

62.8 69.6 79.5

15232HMURF 25232HMURF 30232HMURF

50 60 75

120 144 180

C1 C2 C2

67.6 110.8 114.4

30.7 50.3 51.9

R R R

130.0 160.0 185.0

59.0 72.6 84.0

197.6 270.8 299.4

89.7 122.9 135.9

50232HMURF 60232HMURF 75232HMURF

100 125 150

240 300 360

D1 E1 E1

146.8 199.6 220.0

66.6 90.6 99.9

R S S

240.0 280.0 280.0

109.0 127.1 127.1

386.8 479.6 500.0

175.6 217.7 227.0

100232HMURF 125232HMURF 150232HMURF

15 25 30

18 30 36

A2 B1 B1

35.2 47.2 48.4

16.0 21.4 22.0

R R R

90.0 105.0 110.0

40.9 47.7 49.9

125.2 152.2 158.4

56.8 69.1 71.9

15432HMURF 25432HMURF 30432HMURF

50 60 75

60 72 90

B1 C1 C1

49.6 62.8 65.2

22.5 28.5 29.6

R R R

130.0 160.0 185.0

59.0 72.6 84.0

179.6 222.8 250.2

81.5 101.2 113.6

50432HMURF 60432HMURF 75432HMURF

100 125 150

120 150 180

C1 C2 C2

67.6 110.8 114.4

30.7 50.3 51.9

R R S

240.0 280.0 280.0

109.0 127.1 127.1

307.6 390.8 394.4

139.7 177.4 179.1

100432HMURF 125432HMURF 150432HMURF

200 250 300

240 300 360

D1 E1 E1

146.8 196.0 199.6

66.6 89.0 90.6

S T T

330.0 570.0 575.0

149.8 258.8 261.1

476.8 766.0 774.6

216.5 347.8 351.7

200432HMURF 250432HMURF 300432HMURF

480 V

600 V 15 25 30

14.7 24.5 29.4

B1 B1 B1

47.2 48.4 49.6

21.4 22.0 22.5

R R R

90.0 90.0 105.0

40.9 47.7 49.9

137.2 153.4 159.6

62.3 69.6 72.5

15632HMURF 25632HMURF 30632HMURF

50 60 75

49 58.8 73.5

C1 C1 C2

65.2 67.6 110.8

29.6 30.7 50.3

R R R

110.0 130.0 160.0

59.0 72.6 84.0

195.2 227.6 295.8

88.6 103.3 134.3

50632HMURF 60632HMURF 75632HMURF

100 125 150

98 122.5 147

C2 D1 D1

114.4 146.8 146.8

51.9 66.6 66.6

R S S

185.0 240.0 280.0

109.0 127.1 127.1

354.4 426.8 426.8

160.9 193.8 193.8

100632HMURF 125632HMURF 150632HMURF

200 250

196 245

E1 E1

196.0 199.6

89.0 90.6

T T

330.0 570.0

149.8 258.8

526.0 769.6

238.8 349.4

200632HMURF 250632HMURF

Note: Other ratings available, please consult factory.

Technical Data and Specifications

Dimensions

Power Lines from Disconnect Lugs

Fuses

Reactor

Figure 10-22. Reactor Cabinet

Lugs Interconnects (Provided by Customer) í–˛ Lugs

Table 10-37. Reactor Cabinet Dimensions Case Size

Width

Depth

R

24.75 (628.7)

20.00 (508.0)

18.13 (460.5)

S

25.00 (635.0)

24.25 (616.0)

20.25 (514.4)

T

31.00 (787.4)

25.00 (635.0)

32.75 (831.9)

Capacitor Bank

Figure 10-21. Filter Schematic with Wiring Interconnects

Dimensions in Inches (mm) Height

Refer to NEC.

CA08101001E

For more information visit: www.eaton.com

10


10-40

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters July 2007

UNIPAK

Low Voltage Fixed Capacitor Banks and Fixed Harmonic Filters — Dimensions in Inches (mm)

10

Figure 10-23. Case A1, A2

Figure 10-25. Case C1, C2

Figure 10-24. Case B1

Figure 10-26. Case D1, E1 For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-41 Power Factor Capacitors and Harmonic Filters July 2007

UNIPAK Table 10-38. UNIPAK Enclosures Case Size

Dimensions in Inches (mm) A

B

D

E

F

H

L

X1

X2

X3

Y

Z

A1

5.3 (133.5)

8.5 (215.9)

3.5 (88.7)

3.8 (96.8)

10.6 (270.2)

17.3 (439.4)

6.8 (173.9)

2.0 (51.5)

N/A

N/A

7.7 (195.6)

7.2 (181.7)

A2

6.0 (151.2)

8.5 (215.9)

5.6 (141.9)

4.5 (114.6)

13.3 (336.7)

22.3 (567.6)

6.8 (173.9)

2.3 (58.3)

N/A

N/A

7.7 195.6)

7.2 (181.7)

B1

11.1 (280.8)

10.1 (257.3)

5.8 (148.0)

9.6 (244.1)

15.7 (399.0)

25.3 (642.6)

8.5 (215.3)

4.1 (104.4)

4.5 (114.3)

N/A

9.3 (237.0)

8.8 (223.1)

C1

10.6 (270.4)

12.1 (306.8)

7.1 (180.0)

9.1 (231.5)

16.2 (412.5)

26.3 (668.0)

10.4 (264.8)

3.4 (86.9)

1.1 (27.3)

3.6 (92.0)

11.3 (286.5)

10.7 (272.6)

C2

12.0 (304.2)

19.3 (490.7)

16.9 (428.3)

9.5 (240.5)

16.3 (413.0)

36.0 (914.4)

17.7 (448.8)

3.0 (75.3)

1.5 (38.1)

3.8 (95.3)

18.3 (465.3)

18.0 (456.5)

D1

16.8 (426.6)

19.3 (490.7)

16.9 (428.3)

14.6 (370.1)

N/A

36.0 (914.4)

17.7 (448.8)

5.1 (129.1)

2.4 (59.7)

5.0 (127.9)

18.3 (465.3)

N/A

E1

22.3 (566.4)

24.4 (618.7)

16.8 (425.5)

19.5 (494.1)

N/A

36.0 (914.4)

22.7 (576.7)

6.5 (165.1)

4.4 (111.9)

5.0 (127.0)

22.4 (567.9)

N/A

Legend: A = Total depth

H = Total height

B = Total width

L = Width without feet and brackets

D = Height of removable front cover

X = Depth between front and rear mounting holes in inches

E = Depth of feet F = Height of middle mounting hole in wall bracket

Y = Width between floor mounting holes Z = Width between wall bracket mounting holes

CA08101001E

For more information visit: www.eaton.com

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-42

July 2007

AUTOVAR 300

AUTOVAR 300 Automatic Power Factor Correction Capacitor Systems

Applications Service entrance power factor correction installations requiring precise maintenance of target power factor in a very small footprint.

Features and Specifications Configuration ■

■ ■

10

Cabinet: Wall mounting 12 gauge steel with ANSI 61 gray, NEMA 1 (gasketed). Power line interconnect: Rugged, power distribution block connection. Fusing: 200,000 ampere interrupting capacity provided on all three phases of each bank. Blade-type fuses mounted on insulator stand-offs with blown-fuse indicating lights. Blown-fuse lights: Blown-fuse indicating lights for each phase and stage located on the door. Door interlock: Door interlock automatically disengages capacitors. Power continues to be provided to the unit until the disconnect is open. Exhaust fans: Provide ventilation. Dust filtering included.

Controller ■

AUTOVAR 300

Product Description Automatically switched power factor correction systems for low voltage applications. ■ ■

■ ■ ■

Wall-mount design is ideal for minimum space requirements. Programmable to automatically add/ subtract capacitor banks to maintain preset target power factor. Heavy-duty, three-phase capacitor construction. Five-year warranty of cells. UL and CSA listed.

■ ■

■ ■ ■

■ ■

Visual indication of incorrect CT polarity. Digital display of power factor and number of energized banks. Automatic setting of c/k value (sensitivity based on CT ratio and kvar available). Alarm on failed step. Visual indication of insufficient kvar to reach target power factor. Capacitors disabled in steps within 35 milliseconds of main power interruption. Automatic sensing of kvar values per step. Optional communications capability from controller.

For more information visit: www.eaton.com

Optional metering capability: ❑ Voltage ❑ Current (sensed phase only) ❑ Frequency ❑ Active power (kW) ❑ Reactive power (kvar) ❑ Apparent power (kVA) ■ Optional thermostatic control exhaust fans. ■

Contactor Fully rated for capacitor switching up to 60 kvar at 600 V. ■ Integral pre-charge/pre-insertion module standard. The contactor reduces damaging switching transients. This provides safety and durability for the system: ❑ Lessens the chance of disrupting sensitive electronic equipment ❑ Reduced inrush current extends the life of the capacitor cells ■ UL/CSA recognized. ■

Additional Features Optional molded case circuit breaker rated 65 kAIC at 480 V and 600 V. ■ Personnel ground fault interruption provides protection in case of accidental contact with control power and ground. ■ NEMA 3R weatherproofing. ■

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-43 Power Factor Capacitors and Harmonic Filters July 2007

AUTOVAR 300

Product Selection

Dimensions

Table 10-39. Wall-Mounted Switched Capacitor Banks — Low Voltage Applications kvar

Step x kvar

Rated Current Amperes

Case Size

Shipping Weight Lbs. (kg)

Fused Catalog Number

25 50 75

5x5 5 x 10 5 x 15

60 120 180

J J J

217 (98.5) 255 (115.8) 260 (118.0)

25MCSR231 50MCSR231 75MCSR231

100 125

4 x 25 5 x 25

240 300

J J

270 (122.6) 292 (132.6)

100MCSR231 125MCSR231

50 75 100

5 x 10 5 x 15 5 x 20

60 90 120

J J J

200 (90.8) 210 (95.3) 210 (95.3)

50MCSR4313 75MCSR4313 100MCSR4313

125 150 175

5 x 25 5 x 30 5 x 35

150 180 210

J J J

240 (109.0) 240 (109.0) 260 (118.0)

125MCSR4313 150MCSR4313 175MCSR431

200 225 250 300

5 x 40 5 x 45 5 x 50 5 x 60

241 270 300 361

J J J J

270 (122.6) 290 (131.7) 292 (132.6) 310 (140.7)

200MCSR431 225MCSR431 250MCSR431 300MCSR431

50 75 100

5 x 10 5 x 15 5 x 20

48 72 96

J J J

200 (90.8) 210 (95.3) 210 (95.3)

50MCSR6313 75MCSR6313 100MCSR6313

125 150 175

5 x 25 5 x 30 5 x 35

120 144 168

J J J

240 (109.0) 240 (109.0) 260 (118.0)

125MCSR6313 150MCSR6313 175MCSR631

200 225 250 300

5 x 40 5 x 45 5 x 50 5 x 60

192 216 240 288

J J J J

270 (122.6) 290 (131.7) 292 (132.6) 310 (140.7)

200MCSR631 225MCSR631 250MCSR631 300MCSR631

Enclosure J — Dimensions in Inches (mm)

240 Volt On/Off Switch Power Factor Controller

480 Volt

Keylock Handle

Blown Fuse Lights

600 Volt 29.88 (759.0) 36.00 (914.4)

Figure 10-27. Front View of Enclosure J

0.63 (16.0)

Note: Other ratings available, please consult factory.

Table 10-40. Options Description

Option Code

Current transformer — Multi-tap, split core current transformer (3000:5 A)

TX2

Hands-off Auto Switch — Provides manual control to connect or disconnect capacitor stages regardless of controller output

H

Remote Alarm Relay — Relay for a remote alarm to indicate inability to reach target power factor

A

Molded case circuit breaker (65 kAIC at 480 V)

M

Weatherproofing (NEMA 3R)

W

Communicating Controller

C

Metering Option Controller

D

Thermostatic Temp Control

L

A

A current transformer with a 5 ampere secondary is required to operate an automatic capacitor bank. Rating based on Service Entrance Ampacity. For other ratios, please consult factory.

0.63 (16.0)

B

Figure 10-28. Side View of Enclosure J Table 10-41. Enclosure J — Dimensions in Inches (mm) Description

CA08101001E

For more information visit: www.eaton.com

Dimensions in Inches (mm) Height A

Depth B

Without MCCB

36.00 (914.4)

12.00 (304.8)

With MCCB

60.00 (1524.0) 12.00 (304.8)

10


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-44

July 2007

AUTOVAR 600

AUTOVAR 600 Automatic Power Factor Correction Capacitor Systems

■ ■

10

AUTOVAR 600

Applications

Service entrance power factor correction installations requiring precise maintenance of target power factor.

Programmable to automatically add/ subtract capacitor banks to maintain preset target power factor. ■ Heavy-duty, three-phase capacitor construction. ■ Five-year warranty of cells. ■ UL and CSA listed. ■

Features and Specifications

Modular tray design: Capacitor banks arranged in modular trays with capacitors, fuses, blown-fuse indicating lights, and contactors grouped in a logical, easily understood layout. This permits easy access, quick identification of operating problems and ease of expandability. Fusing: UL recognized, 200,000 ampere interrupting capacity provided on all three phases of each bank. Blade-type fuses mounted on insulator stand-offs. Blown-fuse lights: Blown-fuse indicating lights located on the doormounted blown and at individual fuses to facilitate tracing of cleared fuses. Push-to-test: Allows testing of doormounted blown fuse indicating lights. AutoLocate: When door is open and bus energized, fuse circuit automatically checks for cleared fuses. If a fuse has cleared, the light at the fuse comes on for easy troubleshooting. Door interlock: Door interlock automatically turns off control circuit when engaged. Power continues to be provided to the unit until disconnect is open. Exhaust fans: Two fans per cabinet provide thermal protection. Dust filtering provided. Ease of expansion: Capacitor stage nests are self-contained and can be added in the field. Two bolts mount the nest in the field. Control wire plugs connect to factory standard wire harness on the left side of the cabinet. Ease of replacement: Cells can be easily individually replaced by removing the mounting bolt and lifting out of the nest without removal of any other components.

Configuration

Controller

Cabinet: 12 gauge steel with ANSI 61 gray, baked enamel finish. Lift bolts standard, NEMA 1. ■ Power line interconnect: Rugged, copper bus bar connection with access provided for top or bottom entry. Bus bars are braced for 65 kAIC at 480 V. All internal power wiring connections from bus are laid out on a most direct basis with minimum bends for ease of troubleshooting. Clear barrier limiting access to live parts included standard.

■ ■

■ ■

Visual indication of incorrect CT polarity. Digital display of power factor and number of energized banks. Automatic setting of c/k value (sensitivity based on CT ratio and kvar available). Alarm on failed step. Visual indication of insufficient kvar to reach target power factor.

For more information visit: www.eaton.com

■ ■ ■

Capacitors disabled in steps within 35 milliseconds of main power interruption. Automatic sensing of kvar values per step. Optional communications capability from controller. Optional metering capability: ❑ Voltage ❑ Current (sensed phase only) ❑ Frequency ❑ Active power (kW) ❑ Reactive power (kvar) ❑ Apparent power (kVA) Optional thermostatic control exhaust fans.

Contactor Fully rated for capacitor switching up to 60 kvar at 600 V. ■ Integral pre-charge/pre-insertion module standard. The contactor reduces damaging switching transients. This provides safety and durability for the system: ❑ Lessens the chance of disrupting sensitive electronic equipment ❑ Reduced inrush current extends the life of the capacitor cells ■ UL/CSA recognized. ■

Additional Features ■

■ ■

Optional molded case circuit breaker, rated 65 kAIC at 480 V and 600 V. Personnel ground fault interruption provides protection in case of accidental contact with control power and ground. Control wiring — standard NEC color-coded modular bundles with quick disconnect feature for ease of troubleshooting or ease of expendability. Optional digital metering — IQ 220. Bottom cable entry spacing.

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-45 Power Factor Capacitors and Harmonic Filters July 2007

AUTOVAR 600

IQ 220 Electronic Meter

Modular Step Nest Assembly

10

AUTOVAR 600 — Interior View

Bottom Entry Location

CA08101001E

Factory Pre-wired for Future Expansion

For more information visit: www.eaton.com


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-46

July 2007

AUTOVAR 600

Product Selection

Table 10-43. Options Description

Table 10-42. Floor-Mounted Switched Capacitor Banks — Low Voltage Applications kvar

Step x kvar

Rated Current Amperes

Enclosure Size

Shipping Weight Lbs. (kg)

Fused Catalog Number

240 Vac 75 100 125

3 x 25 4 x 25 5 x 25

180 214 300

L L L

150 200 250

6 x 25 8 x 25 10 x 25

316 481 600

L L L

300 350 400

12 x 25 7 x 50 8 x 50

720 844 965

L KK KK

644 (292.4) 692 (314.2) 740 (336.0)

75TPCSR231 100TPCSR231 125TPCSR231

788 (357.8) 884 (401.3) 944 (428.6)

150TPCSR231 200TPCSR231 250TPCSR231

1022 (464.0) 1616 (734.0) 1704 (774.0)

300TPCSR231 350TPCSR231 400TPCSR231

10

150 200 250

3 x 50 4 x 50 5 x 50

180 240 300

L L L

632 (287.0) 676 (306.9) 720 (326.9)

150TPCSR431 200TPCSR431 250TPCSR431

300 350 400

6 x 50 7 x 50 8 x 50

360 420 480

L L L

764 (346.9) 808 (366.8) 852 (386.8)

300TPCSR431 350TPCSR431 400TPCSR431

450 500 550

9 x 50 10 x 50 11 x 50

540 600 660

L L L

896 (406.8) 944 (428.6) 984 (446.7)

450TPCSR431 500TPCSR431 550TPCSR431

600 660 700

12 x 50 11 x 60 7 x 100

720 792 840

L L KK

1022 (464.0) 1010 (458.5) 1616 (734.0)

600TPCSR431 660TPCSR431 700TPCSR431

720 800 840

12 x 60 864 8 x 100 960 14 x 60 1008

L KK KK

1050 (476.7) 1704 (774.0) 1690 (767.7)

720TPCSR431 800TPCSR431 840TPCSR431

9 x 100 10 x 100 11 x 100 12 x 100

1080 1200 1320 1440

KK KK KK KK

1792 (814.0) 1888 (857.0) 1966 (893.0) 2044 (928.0)

900TPCSR431 1000TPCSR431 1100TPCSR431 1200TPCSR431

150 200 250

3 x 50 4 x 50 5 x 50

144 192 240

L L L

632 (287.0) 676 (306.9) 720 (326.9)

150TPCSR631 200TPCSR631 250TPCSR631

300 350 400

6 x 50 7 x 50 8 x 50

288 336 384

L L L

764 (346.9) 808 (366.8) 852 (386.8)

300TPCSR631 350TPCSR631 400TPCSR631

450 500 550

9 x 50 10 x 50 11 x 60

432 480 528

L L L

896 (406.8) 944 (428.6) 984 (446.7)

450TPCSR631 500TPCSR631 550TPCSR631

600 660 700

12 x 50 11 x 60 7 x 100

576 634 672

L L KK

1022 (464.0) 1010 (458.5) 1616 (734.0)

600TPCSR631 660TPCSR631 700TPCSR631

720 800 840

12 x 60 692 8 x 100 768 14 x 60 1008

L KK KK

1050 (476.7) 1704 (774.0) 1690 (767.7)

720TPCSR631 800TPCSR631 840TPCSR631

900 1000 1100 1200

9 x 100 864 10 x 100 960 11 x 100 1056 12 x 100 1152

KK KK KK KK

1792 (814.0) 1888 (857.0) 1966 (893.0) 2044 (928.0)

900TPCSR631 1000TPCSR631 1100TPCSR631 1200TPCSR631

900 1000 1100 1200

Current transformer — Multi-tap, split core current transformer TX2 (3000:5 A) Hands-off Auto Switch — Provides manual control to connect or disconnect capacitor stages regardless of controller output

H

Remote Alarm Relay — Relay for a remote alarm to indicate inability to reach target power factor

A

Molded case circuit breaker (65 kAIC at 480 V)

M

Weatherproofing (NEMA 3R)

W

Communicating Controller

C

Metering Option Controller

D

Thermostatic Temp Control

L

IQ 220 Solid-State Meter

IQ

480 Vac

Option Code

A current transformer with a 5 ampere secondary is required to operate an automatic capacitor bank. Rating based on Service Entrance Ampacity. For other ratios, please consult factory. Not available with weatherproofing option.

600 Vac

Note: Other ratings available, please consult factory.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-47 Power Factor Capacitors and Harmonic Filters July 2007

AUTOVAR 600

Technical Data and Specifications Dimensions in Inches (mm) (Note: Fans are Vertical Toward Back of Enclosure) Fans

38.50 (977.9)

26.25 (666.8)

(Note: Fans are Side by Side) Fans

1

Ground Lug

2 DANGER

HIGH VOLTAGE PHASE A

PHASE B

PHASE C

CAUTION

DISCONNECT BEFORE SERVICING

3

71.25 (1809.8)

11.75 (298.5)

75.00 (1905.0)

46.00 (1168.4)

10

3.00 (76.2) Filter Tray

Legend 1. Controller 2. On/Off Switch 3. Blown Fuse Indicator Lights

6.00 (152.4)

13.00 (330.2) 25.00 (635.0)

.438 ø Mounting Holes 2 Per Channel

Figure 10-29. Front View of Enclosure L 78.25 (1987.6)

Fans

1

(Note: Fans are Vertical Towards Back of Enclosure)

26.25 (666.8)

Fans

(Note: Fans are Side by Side) Ground Lug

2 DANGER PHASE A

PHASE B

PHASE C

HIGH VOLTAGE CAUTION

DISCONNECT BEFORE SERVICING

3 71.25 (1809.8)

11.75 (298.5)

75.00 (1905.0)

46.00 (1168.4)

.438 ø Mounting Holes 2 Per Channel 3.00 (76.2) Legend 1. Controller 2. On/Off Switch 3. Blown Fuse Indicating Light

Filter Tray

Filter Tray

Figure 10-30. Front and Side View of Enclosure KK CA08101001E

For more information visit: www.eaton.com

6.00 (152.4)

13.00 (330.2) 25.00 (635.0)


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters

10-48

July 2007

AUTOVAR Filter

AUTOVAR Filter — LV Automatic Harmonic Filter

Applications Service entrance power factor correction installations requiring precise maintenance of target power factor in three-phase, non-linear, high harmonic environments.

Features and Specifications Configuration ■

AUTOVAR Filter

10

AUTOVAR Filter — Interior View

Product Description Automatically switched harmonic filter/ power factor corrections systems. ■

Programmable to automatically add/subtract filter banks to maintain preset target power factor. Filter steps tuned for maximum efficiency in reducing harmonic currents in three-phase environments with heavy non-linear loads. Efficient modular design for short lead times, ease of maintenance and ease of future expansion. Heavy-duty, three-phase capacitor construction with reliable, threaded terminal connections. Cool operating, 100% copper wound, thermal protected reactors are sized up to 150% of rated capacitor current. UL and CSA listed.

■ ■

Operation: AUTOVAR harmonic filters are designed to be sized the same as any power factor correction unit. In most low voltage applications where harmonics are generated by non-linear loads, no harmonic audit is necessary to design the AUTOVAR filter because it is already designed for typical harmonic spectrums at the kvar size specified. Cabinet: 12 gauge steel with ANSI 61 gray, baked enamel finish. Lift bolts standard, NEMA 1. Power line interconnect: Rugged, copper bus bar connection with access provided for top or bottom entry. Bus bars are braced for 65 kAIC at 480 V. All internal power wiring connections from bus are laid out on a most direct basis with minimum bends for ease of troubleshooting. Clear barrier limiting access to live parts included standard. Modular tray design: Capacitor banks arranged in modular trays with capacitors, fuses, blown-fuse indicating lights, and contactors grouped in a logical, easily understood layout. This permits easy access, quick identification of operating problems and ease of expandability. Fusing: UL recognized, 200,000 ampere interrupting capacity provided on all three phases of each bank. Blade-type fuses mounted on insulator stand-offs. Blown-fuse lights: Blown-fuse indicating lights located on the doormounted blown and at individual fuses to facilitate tracing of cleared fuses. Push-to-test: Allows testing of doormounted blown fuse indicating lights. AutoLocate: When door is open and bus energized, fuse circuit automatically checks for cleared fuses. If a fuse has cleared, the light at the fuse comes on for easy troubleshooting.

For more information visit: www.eaton.com

Door interlock: Door interlock automatically turns off control circuit when engaged. Power continues to be provided to the unit until disconnect is open. ■ Exhaust fans: Two fans per cabinet provide thermal protection. Dust filtering provided. ■ Ease of expansion: Capacitor stage nests are self-contained and can be added in the field. Control wire plugs connect to factory standard wire harness on the left side of the cabinet. ■ Ease of replacement: Cells can be easily individually replaced by removing the mounting bolt and lifting out of the nest without removal of any other components. ■

Controller ■ ■ ■

■ ■ ■

■ ■ ■

Visual indication of incorrect CT polarity. Digital display of power factor and number of energized banks. Automatic setting of c/k value (sensitivity based on CT ratio and kvar available). Alarm on failed step. Visual indication of insufficient kvar to reach target power factor. Capacitors disabled in steps within 35 milliseconds of main power interruption. Automatic sensing of kvar values per step. Optional communications capability from controller. Optional metering capability: ❑ Voltage ❑ Current (sensed phase only) ❑ Frequency ❑ Active power (kW) ❑ Reactive power (kvar) ❑ Apparent power (kVA) Optional thermostatic control exhaust fans.

Contactor Fully rated for capacitor switching up to 60 kvar at 600 V. ■ Integral pre-charge/pre-insertion module standard. The contactor reduces damaging switching transients. This provides safety and durability for the system: ❑ Lessens the chance of disrupting sensitive electronic equipment ❑ Reduced inrush current extends the life of the capacitor cells ■ UL/CSA recognized. ■

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-49 Power Factor Capacitors and Harmonic Filters July 2007

AUTOVAR Filter

Reactors ■

■ ■

Tuning: Reactors tuned to the 4.7th harmonic order (nominal 5th). This provides maximum effectiveness in reducing harmonic currents in three-phase systems with harmonics caused by 6-pulse devices. Detuning: Reactor designs can be detuned upon request (4.2nd, 6.7th for example) to protect capacitors against alternate harmonics. Windings: 100% copper windings for minimal temperature rise under load. Thermal overload protection: Each reactor includes three normally closed, auto reset thermostats that open at 180°C. When thermostats engage, the contactor opens. Insulation: 220°C insulation system. Warranty: One-year replacement of reactors.

Additional Features Optional molded case circuit breaker rated 65 kAIC at 480 V and 600 V. ■ Personnel ground fault interruption provides protection in case of accidental contact with control power and ground. ■ Control wiring — standard NEC color-coded modular bundles with quick disconnect feature for ease of troubleshooting or ease of expendability. ■

Product Selection Low Voltage Switched Harmonic Filters Table 10-44. Floor-Mounted Switched Harmonic Filters — Low Voltage kvar

Step x kvar

Rated Current Amperes

Enclosure Size

Shipping Weight Lbs. (kg)

Fused Catalog Number

480 Vac 200 250 300

4x 50 5 x 50 6 x 50

240 300 360

L L KK or L + L

1438 (652.9) 1634 (741.8) 1830 (830.8)

200THFSR431 250THFSR431 300THFSR432

350 400 450

7 x 50 8 x 50 9 x 50

420 480 540

KK or L + L KK or L + L KK or L + L

2026 (919.8) 2222 (1008.8) 2371 (1076.4)

350THFSR432 400THFSR432 450THFSR432

500 550 600

10 x 50 11 x 50 12 x 50

600 660 720

KK or L + L KK or L + L KK or L + L

2525 (1146.4) 2750 (1248.5) 2830 (1284.8)

500THFSR432 550THFSR432 600THFSR432

300 350 400

6 x 50 7 x 50 8 x 50

288 336 384

KK or L + L KK or L + L KK or L + L

1830 (830.8) 2026 (919.8) 2222 (1008.8)

300THFSR632 350THFSR632 400THFSR632

450 500 550 600

9 x 50 10 x 50 11 x 50 12 x 50

432 480 528 576

KK or L + L KK or L + L KK or L + L KK or L + L

2371 (1076.4) 2525 (1146.4) 2750 (1248.5) 2830 (1284.8)

450THFSR632 500THFSR632 550THFSR632 600THFSR632

600 Vac

Notes:

L + L under Enclosure Size denotes two Size L enclosures — one for the capacitors, one for the reactor case. ■ For KK enclosure design, change the last digit of the catalog number to 1. For example, 500THFSR431. ■

Table 10-45. Options Description

Option Code

Current transformer — Multi-tap, split core current transformer

TX2

Hands-off Auto Switch — Provides manual control to connect or disconnect capacitor stages regardless of controller output

H

Remote Alarm Relay — Relay for a remote alarm to indicate inability to reach target power factor

A

Molded case circuit breaker (65 kAIC at 480 V)

M

Weatherproofing (NEMA 3R)

W

Communicating Controller

C

Metering Option Controller

D

Thermostatic Temp Control

L

IQ 220 Solid-State Meter

IQ

A current transformer with a 5 ampere secondary is required to operate an automatic capacitor bank. Rating based on Service Entrance Ampacity. For other ratios, please consult factory. Not available with weatherproofing option.

AUTOVAR Filter — Reactor Cabinet

CA08101001E

Other ratings available, please consult factory. ■ Enclosures for 550 and 600 kvar at 480 and 600 V will be one doubledoor section wide if circuit breakers are required. (Enclosure Size KK.) ■

For more information visit: www.eaton.com

10


10-50

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters July 2007

AUTOVAR Filter

Technical Data and Specifications Dimensions in Inches (mm) 89.00 (2260.6)

(Note: Fans are Vertical Towards Back of Enclosure)

38.50 (977.9)

(Note: Fans are Side by Side)

38.50 (977.9)

Fans

26.25 (666.8)

Fans (Note: Fans are Side by Side)

1

(Note: Fans are Vertical Towards Back of Enclosure)

Ground Lug

Fans

2

Fans DANGER

DANGER

PHASE A

HIGH VOLTAGE CAUTION DISCONNECT

PHASE C

BEFORE SERVICING

3

10

71.25 (1809.8)

75.00 (1905.0)

11.75 (298.5)

46.00 (1168.4) 12.00 (304.8) 3.00 (76.2) Legend 1. Controller 2. On/Off Switch 3. Phase A, B and C Blown Fuse Indicating Lights

6.00 (152.4) Filter Tray

Power Wire Interconnect Conduit

Filter Tray

13.00 (330.2 25.00 (635.0)

.438 ø Mounting Holes 2 per Channel

Figure 10-31. Front and Side View of Enclosures L + L

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-51 Power Factor Capacitors and Harmonic Filters July 2007

Transient-Free Static Switching Units

Transient-Free Static Switching Power Factor Correction Units

Acquisition Time

Unique SCAN feature reduces capacitor duty cycles. ■ Remote control of compensation systems available via LAN or Ethernet. ■ Integrated three-phase network analyzer: ❑ Measures all power parameters on each phase (V, I, kW, kvar, kVA) ❑ Measures voltage and current harmonics to the 63rd harmonic ■

FTE — 5 – 20 ms for a 50 Hz network. FTE — 4 – 16 ms for a 60 Hz network. ■ FTA — 1 – 4 second maximum. ■ ■

Enclosure Applicable Standards ■

FTE unit includes all of the above, plus:

Reduces voltage flicker and voltage sag. ■ Provides network reactive power support. ■ Offers voltage control options. ■

■ ■

EMC — EN50081-2, EN50082-2, EN55011, EN61000-4-2/3/4/5, ENV50204, ENV50141. CE Mark — 73/23/EEC am. 93/68, 98/37/EC art. 4(2). Safety — EN61010-1, EN60439-1, EN60204. UL 508. CSA.

Applications Motor starting. On-site generation support. ■ Spot welding. ■ Wind turbines. ■ Other dynamic loads. ■

Product Configurations Network Voltage Transient-Free Power Factor Correction System

■ ■

210 – 690 V. Engineered solutions up to 15 kV.

Product Description

Frequency

Transient-free static switching units are available in two models.

The FTA model is a fast transient-free system, used to compensate any loads within 3 – 4 seconds. Units are available as tuned (designed to absorb the 5th and higher order harmonics), or detuned (designed to prevent resonance in a system and absorb up to 50% of the 5th harmonic).

Features

Three current transformers with a 5 ampere secondary are required to operate this capacitor bank. Rating based on Service Entrance Ampacity. For other ratios, please consult factory.

45 – 55 Hz for 50 Hz network. 55 – 65 Hz for 60 Hz network.

Capacitor Group Configurations ■ ■

Up to 12 groups per one controller. Switching sequence: ❑ 1:1:1:1 (all equal) ❑ 1:2:2:2 (half group) ❑ 1:2:4:4 (quarter, half groups)

Startup and Commissioning by factory trained personnel is required for proper operation and warranty of this system.

Spot Welding (Auto Manufacturer)

L1-Voltage (V)

The FTE model is a real-time transientfree system, used to compensate extremely rapid loads within one cycle of operation (typically 5 – 20 msec).

230

220

210 Without

■ ■ ■

CA08101001E

With

1800 L1-Current (A)

Transient-free capacitor group switching, using electronic switching elements. Simultaneous connection/disconnection of all required steps. Consistent capacitor values and stable filter characteristics. Harmonic filtration. Three independent control modes: ❑ Power factor control. ❑ Voltage control. ❑ Load sharing with another compensation system connected to the same transformer.

1400

1000 L1-Q (kVAR)

10

300 150 0

21:33:38

:40

:42

:44

:46

:48

:50

:52

Figure 10-32. Application Example — Spot Welding

For more information visit: www.eaton.com

:54

:56

:58

:00

:02

:04

:06

:08


10-52

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters July 2007

Transient-Free Static Switching Units

Product Selection Transient-Free Reactive Power Compensation Systems Table 10-46. Real-Time Transient-Free Systems — 480 Vac Output kvar

Output per Step (kvar)

Dimensions WxDxH

Recommended Integral Breaker Option available (Amperes)

Catalog Number

Compensate Rapid Loads Within One Cycle (Typically 5 – 20 ms) — Standard 6% Inductors — Detuned to 245 Hz (4.08th Harmonic)

10

156 187 219

31 37.5 31

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

400 400 400

FTE15652480 FTE18752480 FTE21974480

250 262 312

50 37.5 62.5

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

600 600 600

FTE25052480 FTE26274480 FTE31252480

375 437 450

75 62.5 150

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

800 800 800

FTE37552480 FTE43774480 FTE45031480

600 687 750

100 62.5 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7

1200 1200 1600

FTE60661480 FTE687112480 FTE75061480

825 900 1125

75 150 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 94.5 x 23.6 x 82.7

1600 1600 2000

FTE825112480 FTE90061480 FTE112591480

1350 1500 1800

150 125 150

94.5 x 23.6 x 82.7 126.0 x 23.6 x 82.7 126.0 x 23.6 x 82.7

2500 2500 3200

FTE135091480 FTE1500121480 FTE1800121480

Compensate Rapid Loads Within One Cycle (Typically 5 – 20 ms) — 4.5% Inductors — Tuned to 282 Hz (4.7th Harmonic) 156 187 219

31 37.5 31

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

400 400 400

FTE15652480T FTE18752480T FTE21974480T

250 262 312

50 37.5 62.5

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

600 600 600

FTE25052480T FTE26274480T FTE31252480T

375 437 450

75 62.5 150

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

800 800 800

FTE37552480T FTE43774480T FTE45031480T

600 687 750

100 62.5 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7

1200 1200 1600

FTE60661480T FTE687112480T FTE75061480T

825 900 1125

75 150 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 94.5 x 23.6 x 82.7

1600 1600 2000

FTE825112480T FTE90061480T FTE112591480T

1350 1500 1800

150 125 150

94.5 x 23.6 x 82.7 126.0 x 23.6 x 82.7 126.0 x 23.6 x 82.7

2500 2500 3200

FTE135091480T FTE1500121480T FTE1800121480T

Note: Standard systems have separate individual connections on each phase in individual cabinets. Note: Systems with internal phase connections are available — contact Asheville PFC group for pricing. Note: Systems with integral breakers/disconnects have internal phase connections between each cabinet.

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-53 Power Factor Capacitors and Harmonic Filters July 2007

Transient-Free Static Switching Units

Transient-Free Reactive Power Compensation Systems (Continued) Table 10-47. Fast Transient-Free Switching Systems — 480 Vac Output kvar

Output per Step (kvar)

Dimensions WxDxH

Recommended Integral Breaker Option available (Amperes)

Catalog Number

Compensate Any Load Within 3 – 4 Seconds — Standard 6% Inductors — Detuned to 245 Hz (4.08th Harmonic) 156 187 219

31 37.5 31

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

400 400 400

FTA15652480 FTA18752480 FTA21974480

250 262 312

50 37.5 62.5

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

600 600 600

FTA25052480 FTA26274480 FTA31252480

375 437 450

75 62.5 150

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

800 800 800

FTA37552480 FTA43774480 FTA45031480

600 687 750

100 62.5 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7

1200 1200 1600

FTA60661480 FTA687112480 FTA75061480

825 900 1125

75 150 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 94.5 x 23.6 x 82.7

1600 1600 2000

FTA825112480 FTA90061480 FTA112591480

1350 1500 1800

150 125 150

94.5 x 23.6 x 82.7 126.0 x 23.6 x 82.7 126.0 x 23.6 x 82.7

2500 2500 3200

FTA135091480 FTA1500121480 FTA1800121480

Compensate Any Load Within 3 – 4 Seconds — 4.5% Inductors — Tuned to 282 Hz (4.7th Harmonic) 156 187 219

31 37.5 31

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

400 400 400

FTA15652480T FTA18752480T FTA21974480T

250 262 312

50 37.5 62.5

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

600 600 600

FTA25052480T FTA26274480T FTA31252480T

375 437 450

75 62.5 150

31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7 31.5 x 23.6 x 82.7

800 800 800

FTA37552480T FTA43774480T FTA45031480T

600 687 750

100 62.5 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7

1200 1200 1600

FTA60661480T FTA687112480T FTA75061480T

825 900 1125

75 150 125

63.0 x 23.6 x 82.7 63.0 x 23.6 x 82.7 94.5 x 23.6 x 82.7

1600 1600 2000

FTA825112480T FTA90061480T FTA112591480T

1350 1500 1800

150 125 150

94.5 x 23.6 x 82.7 126.0 x 23.6 x 82.7 126.0 x 23.6 x 82.7

2500 2500 3200

FTA135091480T FTA1500121480T FTA1800121480T

Note: Standard systems have separate individual connections on each phase in individual cabinets. Note: Systems with internal phase connections are available — contact Asheville PFC group for pricing. Note: Systems with integral breakers/disconnects have internal phase connections between each cabinet.

CA08101001E

For more information visit: www.eaton.com

10


10-54

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters July 2007

Active Harmonic Filters

Active-Harmonic FilterHarmonic Correction Unit — NEMA 1 Enclosure Specifications

Typical applications include locations with large amounts of non-linear loads including 6- and 12-pulse PWM AC variable frequency drives, DC drives, as well as other switch-mode power supply equipment. This equipment can be found in water and wastewater treatment facilities, industrial manufacturing and warehousing plants, military bases, and commercial (HVAC) locations. Unlike passive filters, by providing dynamic correction, HCUs can provide effective harmonic correction for varying load conditions and harmonic spectrums up to their rated capacity. HCUs also have the secondary benefit of providing power factor correction with any excess capacity after correcting all harmonic conditions.

10

Advantages ■

Harmonic Correction Units — NEMA 1 Enclosure

■ ■

Product Description Active Harmonic Filters (Harmonic Correction Units — HCU) provide dynamic harmonic correction by actively injecting equal and opposite currents into the customer’s electrical distribution system that cancel the entire spectrum of harmonic currents at the point of connection.

■ ■ ■ ■

Can be sized to guarantee specific levels of harmonic correction, such as meeting IEEE 519 recommended levels. Cannot be overloaded. Can be expanded without affecting performance. Broad spectrum of cancellation (2nd to 50th harmonic). Power factor improvement. Easier and less expensive installation. Comprehensive control.

For more information visit: www.eaton.com

Features, Benefits and Functions ■ ■ ■ ■ ■ ■ ■ ■

■ ■

Fast action. 20 kHz switching carrier frequency. UL / CSA approved. 208 – 480 V +/- 10%, 600 V with autotransformer. 50/60 Hz +/- 3 Hz frequency. Ambient temperature 0°C – +40°C enclosed. Seismic Zone 4. NEMA 1 and NEMA 12 enclosures available: ❑ Wall-mount (50 and 100 ampere designs) ❑ Floor-standing (300 ampere design) Output capacity — self limited to 100% current rated. Corrective capability — <5% TDD and near unity displacement power factor.

Note: Requires at least 3% series input line reactor or equivalent 6% DC bus choke in each AC drive for optimum performance. ■

2-line, 20 character per line alphanumeric display.

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-55 Power Factor Capacitors and Harmonic Filters July 2007

Active Harmonic Filters

Product Selection and Sizing Table 10-48. Harmonic Control Unit Ratings — NEMA 1 Enclosed Model

Voltage

Frequency

HCU050D5N1

208 – 480

50/60 Hz

HCU100D5N1

208 – 480

HCU300D5N1

208 – 480

Total Current Amperes (rms)

Watt Losses (kw)

H x W x D Exterior Dimensions in Inches (mm)

Unit Weight Lbs. (kg)

Enclosure Type

Disconnect

50

1.8

51.80 x 20.70 x 18.50 (1315.7 x 525.8 x 469.9)

250 (113.5)

Wall-Mount/ NEMA 1

50/60 Hz

100

3.0

68.70 x 20.70 x 18.50 (1745.0 x 525.8 x 469.9)

350 (158.9)

Wall-Mount/ NEMA 1

50/60 Hz

300

8.0

74.90 x 32.20 x 19.50 (1902.5 x 817.9 x 495.3)

775 (351.9)

Free-Standing/ NEMA 1

X

Table 10-49. Current transformer Ratings — Dimensions in Inches (mm) Model

Internal Diameter in Inches (mm)

Table 10-50. Autotransformer Required for 600 V operation

ac Line Current Rating

Type

CT500SC CT1000SC

500 1000

Split Split

2.25 (57.2) 4.65 (118.1)

HCUNWL106740EN

39.2

CT3000SC CT5000SC

3000 5000

Split Split

6.50 (165.1) 7.50 (190.5)

50 A 30.00 x 24.00 x 21.00 (762.0 x 609.6 x 533.4)

290 (131.7)

HCUNWL106742EN

78.3

100 A 37.00 x 31.00 x 22.00 (939.8 x 787.4 x 558.8)

500 (227.0)

HCUNWL106744EN

235

300 A 44.00 x 39.00 x 30.00 (1117.6 x 990.6 x 762.0)

1100 (499.4)

Note: Current transformers are rated for 400 Hz. Two current transformers are required for 3-phase loads. Three current transformers are required when single-phase loads are present.

Model

Rating based on Service Entrance Ampacity and optional parallel operation. For other ratios, please consult factory. Startup and Commissioning by factory trained personnel is required for proper operation and warranty of this system.

Technical Data and Specifications Load(s)

Source Transformer

Alternate CT Placement

Typical CT Placement

HCU

Figure 10-33. Installation Diagram

CA08101001E

Amperes Total HCU Current Size

For more information visit: www.eaton.com

H x W x D Dimensions in Inches (mm)

Unit Weight Lbs. (kg)

10


10-56

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters July 2007

Active Harmonic Filters

Source CT Schematics

10

Figure 10-34. Source CT Location

Figure 10-36. Source or Load CT Location

NEED IMAGE!

Figure 10-35. Source or Load CT Location

Figure 10-37. Load CT Location

For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-57 Power Factor Capacitors and Harmonic Filters July 2007

Active Harmonic Filters

Dimensions Drawings — NEMA 1 Enclosure HCU050 Layout Dimensions The HCU050 series offers 50 amperes of corrective current in a convenient package. The enclosed model comes standard with a digital interface panel for control diagnostics and programming. Input fuses are included. The enclosed unit includes a removable panel for bottom conduit entry.

4.57 (116.1)

8.73 (221.6)

10 16.67 (423.4)

4.69 (119.1)

16.06 (408.0)

7.46 (189.5)

50.33 (1278.4)

48.00 (1219.2)

6.00 (152.4)

.53 (13.5)

20.67 (525.0)

3.17 (80.5)

Conduit Plate 6.25 (158.8) 2.17 (55.1)

5.25 (133.4)

9.98 (253.5)

1.63 (41.4)

.85 (21.6)

4.63 (117.6)

2.75 (69.9)

6.25 (158.8)

Figure 10-38. HCU050 — 50 Amperes — Dimensions in Inches (mm) CA08101001E

7.70 (195.6)

For more information visit: www.eaton.com


10-58

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Power Factor Capacitors and Harmonic Filters July 2007

Active Harmonic Filters

Drawings — NEMA 1 Enclosure HCU100 Layout Dimensions The HCU100 series offers 100 amperes of corrective current in a wall-mounted NEMA 1 enclosure. The enclosed model comes standard with a digital interface module for control, diagnostics and programming. Input fuses are included. The enclosed unit includes a removable panel for bottom conduit entry.

9.79 (248.7)

4.62 (117.3)

20.67 (525.0)

10

16.67 (423.4)

19.94 (506.5)

8.81 (223.8)

67.19 (1706.6) 3.75 (95.3)

65.23 (1656.8)

5.00 (127.0)

16.67 (423.4)

Conduit Plate

6.25 (158.8) 2.55 (64.8)

5.25 (133.4)

1.38 (35.1)

7.70 (195.6)

.51 (13.0) 3.05 (77.5)

1.10 (27.9) 5.25 (133.4) 6.25 (158.8)

11.08 (281.4)

2.38 (60.5)

Figure 10-39. HCU100 — 100 Amperes — Dimensions in Inches (mm) For more information visit: www.eaton.com

CA08101001E


TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-59 Power Factor Capacitors and Harmonic Filters July 2007

Active Harmonic Filters

Drawings — NEMA 1 Enclosure HCU300 Layout Dimensions The HCU300 series offers 300 amperes of corrective current for large capacity applications. It is available in a floor-standing NEMA 1 enclosure (including a door-interlocking disconnect). The enclosed model comes standard with digital interface module for control, diagnostics and programming. Input fuses are included. The enclosed unit includes a removable panel for top conduit entry.

23.10 (586.7)

3.00 (76.2)

6.50 (165.1)

Conduit Plate

10 22.08 (560.8)

5.02 (127.5)

8.00 (203.2)

7.00 (177.8)

19.23 (488.4)

31.50 (800.1)

17.38 (441.5) 5.00 (127.0) 13.62 (345.9) 3.63 (92.2)

70.95 (1802.2) 74.71 (1897.6) 12.22 (310.4)

2.72 (69.1)

13.98 (355.1)

4.32 (109.7)

27.13 (689.1)

0.55 TYP (14.0)

0.55 TYP (14.0)

15.31 (389.0)

Figure 10-40. HCU300 — 300 Amperes — Dimensions in Inches (mm) CA08101001E

For more information visit: www.eaton.com


10-60

TVSS, Power Conditioning, PF Capacitors & Harmonic Filters July 2007

This page intentionally left blank.

10

For more information visit: www.eaton.com