Power Breakers, Contactors & Fuses
13-1
Power Breakers, Contactors & Fuses
February 2007
Contents Description Power Circuit Breakers Low Voltage Power Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Magnum Family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Magnum DS Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . Magnum SB Insulated Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . Magnum IEC Rated Air Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . Medium Voltage Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Contactors Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SL Series (160 – 400 Amperes). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SL Series (800 Amperes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lug Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expulsion Fuses Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type RBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type RDB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type DBU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type DBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Limiting Fuses Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type CLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type HLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type BHLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Types BHLE and HCL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type CLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type CLPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type CX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type CXN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type DSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type CXF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Fuse Mounting for Current Limiting Fuses . . . . . . . . . . . . . . . Pricing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Breakers, Contactors and Fuses Family
CA08101001E
For more information visit: www.eaton.com
Page 13-2 13-2 13-6 13-8 13-10 13-17 13-26 13-30 13-31 13-32 13-34 13-35 13-36 13-39 13-41 13-42 13-46 13-50 13-53 13-55 13-56 13-60 13-62 13-63 13-67 13-71 13-74 13-76 13-77 13-78 13-79 13-80
13
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-2
February 2007
Low Voltage Power Circuit Breakers
Magnum Low Voltage Power Circuit Breakers for Global Application Magnum Low Voltage Power Circuit Breakers enable comprehensive solutions to meet and exceed the unique and wide-ranging requirements of today’s global power distribution systems. This powerful circuit breaker offering is designed for ultimate custom configuration and application flexibility, with the needs of the power distribution equipment user and the electrical equipment manufacturer in mind.
Magnum IEC Air Circuit Breakers for IEC Rated Switchboards ■
Up to 690 Vac. 200 to 6300 A continuous. ■ 40 to 100 kA Icu/Ics.
■
Three Product Families Magnum consists of three product families; each provides specific ratings features and approvals to optimize performance when applied in power distribution equipment and custom enclosures:
Magnum DS Low Voltage Power Circuit Breakers for ANSI Rated Switchgear Applications
Magnum IEC Low Voltage Air Circuit Breaker Family
■
Up to 635 Vac. 200 to 6000 A continuous. ■ 42 to 200 kA interrupting.
■
13
Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications
Magnum SB Low Voltage Insulated Case Circuit Breakers for Switchboard Applications ■
Up to 635 Vac. 200 to 5000 A continuous. ■ 50 to 150 kA interrupting. ■
Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-3
February 2007
Low Voltage Power Circuit Breakers
Features, Benefits and Functions ■
■ ■
■ ■
■ ■ ■ ■ ■
■
■
200 kA interruption ratings with current limiting performance and low current let-through to reduce damaging energy to downstream equipment at high fault levels. Withstand ratings up to 100 kA to maximize system coordination and selectivity. Three physical frame sizes (Narrow, Standard and Double) to promote breaker application in compact modular enclosures. Continuous current ratings from 800 to 6300 A with 100% rating at 40ºC and no derating on most ratings up to 50ºC. Fixed breaker mounting configurations with horizontal and optional vertical and front connected terminal connections. Drawout breaker mounting configurations with cassette and optional safety shutters. 3- and 4-pole breaker configurations. Through-the-door design for human interface with the breaker compartment door closed. Two-step stored energy mechanism for manually and electrical operated breakers. Digitrip RMS Trip Unit family with four models, each providing increasing levels of features: ❑ Basic to advanced programmable overcurrent protection with communications, power metering and power quality ❑ New Arcflash Reduction Maintenance Switch setting (enabled locally or remotely) to reduce arc flash potential on downstream circuits during maintenance operations Field installable accessories (UL approved) common across the breaker frames and designed to be easily installed in the field to service or modify the breaker at the point of use. Secondary terminal contacts mounted at the top front of the breaker and away from the primary voltage areas for improved safety and access. Finger-proof terminal blocks accommodate ring-tongue or spade type terminals as standard.
13 Through-the-Door Design for Human Interface with the Breaker Compartment Door Closed
High Technology Microprocessor-Based Digitrip RMS 1150+ Trip Units are Available With Advanced Features Like Programmable Overcurrent Settings, Power Metering, Power Quality and Communications
CA08101001E
For more information visit: www.eaton.com
13-4
Power Breakers, Contactors & Fuses Power Circuit Breakers February 2007
Low Voltage Power Circuit Breakers
Breaker Features on Front Cover
The controls and indicators are functionally grouped on the breaker faceplate to optimize the human interface, visibility, and ease of use. For maximum safety, a modern, through-thedoor design permits access to the breaker levering system, trip unit, controls and indicators with the door closed.
Mechanical Trip Flag Pop-out Indicator (Optional) — Red
Accessory Viewing Windows for:
❑
Shunt Trip Attachment (STA) ❑ Spring Release Device (SR) ❑ Undervoltage Release (UVR) Device or Second STA
Digitrip RMS Trip Unit (Model 520M Shown) Protected by Clear Cover
Contact Status Indicators:
13
❑ ❑
OPEN — Green CLOSED — Red
Magnum DS Drawout Breaker
Spring Status Indicators: ❑ ❑
Charged — Yellow Discharged — White
Push OFF (Open) Pushbutton —Red Push ON (Close) Pushbutton — Green Manual Spring Charging Handle for Manually Charging the Stored Energy Springs
Mechanical Operations Counter (Optional) Key Off Lock (Optional)
Accessory Viewing Windows Visibly Confirm the Breaker Shunt Trip, Spring Release, and UVR Installation and Their Control Voltage Rating Drawout Breaker Levering Can be Accomplished With the Compartment Door Closed Without the Need for a Special Levering Tool
Padlockable Levering Device Shutter for Drawout Breakers Color-Coded Position Indicator for Drawout Breakers: ❑
CONNECT — Red ❑ TEST — Yellow ❑ DISCONNECT — Green
Through-the-Door Design for Human Interface with the Breaker Compartment Door Closed, for Example, Manually Charging the Stored Energy Springs
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-5
February 2007
Low Voltage Power Circuit Breakers
Breaker Internal Features
Magnum is designed for ease of access for inspection, modification and maintenance at the point of use. The breaker front cover is easily removed with four captive bolts, revealing the modular internal breaker features.
Secondary Terminal Points for Internal Breaker Wiring Connections Breaker Accessory Mounting Deck with Three Positions for Mounting: ❑
Shunt Trip Attachment (STA) Spring Release Device (SR) ❑ Undervoltage Release (UVR) Device or Second STA
❑
Digitrip RMS Trip Unit (Model 1150+ Shown)
Spring Charging Motor (Optional) for Electrically Charging the Stored Energy Springs
Manual Spring Charging Handle for Manually Charging the Stored Energy Springs Padlockable Levering Device Shutter for Drawout Breakers
13
Magnum Drawout Breaker Front View With Front Cover Removed Showing Easy Access to the Breaker Internal Devices
Color-Coded Position Indicator for Drawout Breakers: ❑
CONNECT — Red TEST — Yellow ❑ DISCONNECT — Green ❑
Secondary Contact Blocks for Connection to External Cell Control Wiring
Removable Arc Chute Covers for Easy Access to Breaker Main Contacts Primary Finger Cluster Disconnecting Contacts for Drawout Breaker are Mounted on the Breaker Element (Not in the Breaker Compartment) for Ease of Access for Inspection and Maintenance
Current Sensor Viewing Windows to View and Confirm Breaker Sensor Rating Rigid Frame Housing (Thermoset Composite Resin) Providing Increased Strength and Durability
Magnum Drawout Breaker Rear View Showing Primary Disconnecting Finger Clusters Mounted on the Breaker for Ease of Inspection
CA08101001E
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-6
February 2007
Low Voltage Power Circuit Breakers
Magnum DS Low Voltage Power Circuit Breakers
UL and ANSI Test Certifications
Comprehensive Enclosure Solutions
Magnum DS is a true UL 1066 listed low voltage power circuit breaker family, designed for the highest performance requirements of switchgear and specialty enclosure applications.
Magnum DS meets or exceeds the applicable ANSI, NEMA , UL and CSA standards, including:
Magnum DS has proven performance in Eaton manufactured switchgear and switchboards with the following test certifications:
■
■
Magnum DS Low Voltage Power Circuit Breakers have short time withstand and interruption ratings up to 100 kA at 635 Vac with continuous current ratings up to 6000 amperes to maximize system coordination and selectivity. ■ Magnum MDSX Current Limiting Power Circuit Breakers have 200 kA interrupting ratings at 480 Vac with continuous current ratings up to 5000 amperes. ■ Magnum MDSL Current Limiting Power Circuit Breakers have 200 kA interrupting ratings at 600 Vac with continuous current ratings up to 2000 amperes.
13
■
■
■
■
■
ANSI C37.13 (Low Voltage ac Power Circuit Breakers Used in Enclosures). ANSI C37.16 (Preferred Ratings, Related Requirements, and Application Recommendations for Low Voltage Power Circuit Breakers and ac Power Circuit Breakers). ANSI C37.17 (Trip Devices for ac and General Purpose dc Low Voltage Power Circuit Breakers). ANSI C37.50 (Test Procedures for Low Voltage ac Power Circuit Breakers Used in Enclosures). UL 1066 (Standard for Low Voltage ac and dc Power Circuit Breakers Used in Enclosures). NEMA SG3 (This standard adopts ANSI C37.16 in its entirety).
■
UL 1558 (Certified Magnum DS Low Voltage Metal-Enclosed Switchgear). ■ UL 891 (Certified Pow-R-Line C Low Voltage Switchboards). ■ UL 1008 Standard for Transfer Switch Equipment. ■ UL, CSA 22.2.31 Low Voltage Assemblies. Approvals ■
UL listed: Magnum DS Breaker UL File No. E52096 and Cassette UL File No. E204565. ABS (American Bureau of Shipping) Type Listed Certificate Number 04-HS422844A-DUB.
Magnum DS, MDSL and MDSX Circuit Breakers
Magnum DS Low Voltage Power Circuit Breakers have high withstand ratings from 42 kA to 100 kA to provide for maximum system coordination and selectivity.
The new Magnum MDSL Current Limiting Power Circuit Breakers have integral current limiters to provide interrupting ratings of 200 kA at 600 Vac.
For more information visit: www.eaton.com
The new Magnum MDSX Current Limiting Power Circuit Breakers have fast opening contacts to provide interrupting ratings up to 200 kA at 480 Vac without fuses.
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-7
February 2007
Low Voltage Power Circuit Breakers
Magnum DS Switchgear Class UL 1066
Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications
Table 13-1. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers Frame Amperes
Breaker Type
Frame Type
MDN-408 MDN-508 MDN-608 MDN-C08
rms Symmetrical Current Ratings kA 50/60 Hz
Fixed Internal Instantaneous Trip
Available Current Sensor & Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In rating)
— — — 18 x In
200, 250, 300, 400, 600, 800
Interrupting at 508 Vac
Narrow Narrow Narrow Narrow
42 50 65 100
42 50 65 100
42 50 65 65
42 50 65 20
MDS-408 MDS-608 MDS-808 MDS-C08 MDS-L08 MDS-X08
Standard Standard Standard Standard Standard Standard
42 65 85 100 200 200
42 65 85 100 200 200
42 65 85 100 200
42 65 85 85 — 30
MDN-416 MDN-516 MDN-616 MDN-C16
Narrow Narrow Narrow Narrow
42 50 65 100
42 50 65 100
42 50 65 65
42 50 65 30
MDS-616 MDS-816 MDS-C16 MDS-L16 MDS-X16
Standard Standard Standard Standard Standard
65 85 100 200 200
65 85 100 200 200
65 85 100 200
65 85 85 — 30
MDN-620 MDN-C20
Narrow Narrow
65 100
65 100
65 65
65 35
MDS-620 MDS-820 MDS-C20 MDS-L20 MDS-X20
Standard Standard Standard Standard Standard
65 85 100 200 200
65 85 100 200 200
65 85 100 200
65 85 85 — 30
— — 85 — 30
MDS-632 MDS-832 MDS-C32
Standard Standard Standard
65 85 100
65 85 100
65 85 100
65 85 85
— — 85
MDS-X32
Double
200
200
50
50
MDS-840 MDS-C40 MDS-X40
Double Double Double
85 100 200
85 100 200
85 100
85 100 50
— — 50
2000, 2500, 3200, 4000
5000
MDS-850 MDS-C50 MDS-X50
Double Double Double
85 100 200
85 100 200
85 100
— — 50
2500, 3200, 4000, 5000
85 100 50
6000
MDS-C60
Double
100
100
100
100
—
3200, 4000, 5000, 6000
800
1600
2000
3200
4000
Interrupting at 635 Vac
Short Time Withstand Rating
Interrupting at 254 Vac
13
— — — 85 — 30 — — — 18 x In
200, 250, 300, 400, 600, 800, 1000, 1200, 1600
— — 85 — 30 — 18 x In
200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000
200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000, 3200
Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods. Magnum MDSL Current Limiting Power Circuit Breaker With Integral Current Limiters. Current Limiter selected determines short time and fixed instantaneous trip rating. Maximum voltage rating is 600 Vac. Magnum MDSX Current Limiting Power Circuit Breaker With Fast Opening Contacts. Product to be tested. Contact Eaton for product rating. Breaker applied in a tested fan-cooled enclosure.
CA08101001E
For more information visit: www.eaton.com
13-8
Power Breakers, Contactors & Fuses Power Circuit Breakers February 2007
Low Voltage Power Circuit Breakers
Magnum SB Low Voltage Insulated Case Circuit Breakers
Magnum SB is a Low Voltage Insulated Case Circuit breaker family designed for the performance and economic requirements of UL 891 switchboards. ■
Magnum SB Low Voltage Insulated Case Circuit Breakers are Designed for the Performance and Economic Requirements of UL 891 Switchboards
13
Magnum SB Insulated Case Circuit Breakers have Interruption ratings up to 100 kA at 635 Vac with continuous current ratings up to 5000 amperes. ■ Magnum SB Insulated Case Circuit Breakers have lighter-duty Short Time Withstand ratings and fixed internal instantaneous trips on most ratings, which is characteristic of UL 489 molded case breakers commonly used in UL 891 switchboards. This provides for greater economy and excellent coordination and selectivity for most commercial applications. ■ Fixed internal instantaneous trips will be phased in on all SB Insulated Case Circuit Breakers rated 3200 amperes and below to provide an extra safety factor by reducing the energy let-through to downstream circuits at the maximum instantaneous trip point and to facilitate feeder circuit breaker protection in UL 891 switchboards with 3-cycle bus bracing. ■ Magnum SBSE Current Limiting Power Circuit Breakers have 150 kA Interrupting Ratings at 480 Vac with continuous current ratings up to 5000 amperes. The Short Time Withstand Rating is 30 kA for standard frame and 50 kA for double frame breakers.
UL & ANSI Test Certifications Magnum SB meets or exceeds the applicable ANSI, NEMA, UL and CSA standards, including: ■ ■
■
■
■
■
ANSI C37.13 (Low Voltage AC Power Circuit Breakers Used in Enclosures) ANSI C37.16 (Preferred Ratings, Related Requirements, and Application Recommendations for Low Voltage Power Circuit Breakers and AC Power Circuit Breakers) ANSI C37.17 (Trip Devices for AC and General Purpose DC Low Voltage Power Circuit Breakers) ANSI C37.50 (Test Procedures for Low Voltage AC Power Circuit Breakers Used in Enclosures) UL 1066 (Standard for Low Voltage AC and DC Power Circuit Breakers Used in Enclosures) NEMA SG3 (This standard adopts ANSI C37.16 in its entirety)
Comprehensive Enclosure Solutions Magnum DS has proven performance in Eaton manufactured switchgear and switchboards with the following test certifications: ■
UL 1558 (Certified Magnum DS Low Voltage Metal-Enclosed switchgear) ■ UL 891 (Certified Pow-R-Line C Low Voltage Switchboards) ■ UL, CSA 22.2.31 Low Voltage Assemblies
Approvals ■
UL listed: Magnum DS Breaker UL File E52096 and Cassette UL File E204565.
Typical Magnum SB Low Voltage Insulated Case Circuit Breaker Nameplate
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-9
February 2007
Low Voltage Power Circuit Breakers
Magnum SB Switchboard Class UL 1066 Insulated Case
Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications
Table 13-2. Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breaker Frame Amperes
800
1200
1600
2000
2500
3000
Breaker Type
Frame Type
SBN-508 SBN-608 SBN-C08
rms Symmetrical Current Ratings kA 50/60 Hz Interrupting Interrupting Interrupting Short Time at 254 Vac at 508 Vac at 635 Vac Withstand Rating
Fixed Internal Inst Trip
Narrow Narrow Narrow
50 65 100
50 65 100
35 42 65
20 20 20
SBS-608 SBS-C08 SBS-E08
Standard Standard Standard
65 100 200
65 100 150
65 85
20 20 30
SBN-512 SBN-612 SBN-C12
Narrow Narrow Narrow
50 65 100
50 65 100
35 42 65
25 25 25
SBS-612 SBS-C12 SBS-E12
Standard Standard Standard
65 100 200
65 100 150
65 85
25 25 30
SBN-516 SBN-616 SBN-C16
Narrow Narrow Narrow
50 65 100
50 65 100
35 42 65
30 30 30
SBS-616 SBS-C16 SBS-E16
Standard Standard Standard
65 100 200
65 100 150
65 85
30 30 30
SBN-620 SBN-C20
Narrow Narrow
65 100
65 100
65 65
35 35
SBS-620 SBS-C20 SBS-E20
Standard Standard Standard
65 100 200
65 100 150
65 85
35 35 30
SBS-625 SBS-C25
Standard Standard
65 100
65 100
65 85
45 45
SBS-E25
Double
200
150
SBS-630 SBS-C30
Standard Standard
65 100
65 100
65 85
Available Current Sensor & Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In rating) 200, 250, 300, 400, 600, 800
18 x In
13
30 200, 250, 300, 400, 600, 800, 1000, 1200
18 x In
30 200, 250, 300, 400, 600, 800, 1000, 1200, 1600
18 x In
30 18 x In
200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000
30
50
50
50 50
200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500 200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000
SBS-E30
Double
200
150
50
50
4000
SBS-840 SBS-C40 SBS-E40
Double Double Double
85 100 200
85 100 150
85 100
85 100 50
— — 50
2000, 2500, 3000, 4000
5000
SBS-850 SBS-C50 SBS-E50
Double Double Double
85 100 200
85 100 150
85 100
— — 50
2500, 3000, 4000, 5000
85 100 50
6000
SBS-C60
Double
100
100
100
100
—
3000, 4000, 5000, 6000
Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods. Fixed Internal Instantaneous Trip set at approximately 18 x In symmetrical will be phased into the product. Product to be tested. Contact Eaton for product rating. Magnum SBSE Current Limiting Power Circuit Breaker With Fast Opening Contacts. Breaker applied in a tested fan-cooled enclosure.
CA08101001E
For more information visit: www.eaton.com
13-10
Power Breakers, Contactors & Fuses Power Circuit Breakers February 2007
Low Voltage Power Circuit Breakers
Magnum IEC Rated Air Circuit Breakers
Magnum Air Circuit Breakers are designed to enable global power distribution solutions in IEC switchboards and other custom enclosures. ■
Magnum Narrow Frame Drawout Air Circuit Breaker With Cassette
13
Magnum IEC Air Circuit Breakers have interruption ratings up to 100 kA at 690 Vac with continuous current ratings up to 6300 amperes. ■ Magnum IEC Air Circuit Breaker continuous current frames are 100% rated. No thermal de-rating is required when applying the breaker in the low voltage systems enclosure at ambient temperatures of 40°C. ■ Magnum IEC Breakers carry the KEMA Keur Mark, which requires periodic follow-up testing, witnessed by KEMA, to demonstrate our product performs to its published nameplate ratings. This differentiates Magnum Air Circuit Breakers from competition, who generally self-tests their product when it is first introduced and is not bound to perform subsequent follow-up third-party testing.
IEC Test Certifications Magnum Air Circuit Breakers meet or exceed the applicable IEC standards, including: The KEMA Keur Mark on the Magnum ACB Label Confirms Third-Party Witness and Follow-up Testing
■ ■
EN/IEC 60947-2. KEMA third-party witness and follow-up testing.
For more information visit: www.eaton.com
Comprehensive Enclosure Solutions Magnum Air Circuit Breakers have proven performance in IEC switchboards and custom enclosures manufactured by Eaton and Low Voltage Systems Builders (OEMs) to the following standards: ■
EN/IEC 60947-1. EN/IEC 60439-1. ■ Eaton manufactured IEC Low Voltage Switchboard solutions include: ❑ Eaton MEM M-Form (UK) Low Voltage Switchboards ❑ Eaton Holec Capitole 40 and Capitole 20 (Holland) Low Voltage Switchboards ❑ Eaton Tabula Low Voltage Switchboard Systems (Global) for Low Voltage Systems Builders ❑ Eaton Elatis (Germany) Low Voltage Switchboards ■
Approvals and Marks Magnum Air Circuit Breakers carry the following approvals and approval marks: ■
CE. KEMA Keur mark. ■ ABS (American Bureau of Shipping) Type Listed Certificate Number 04-HS422844B-PDA-DUB. ■ CCC (Certificate for China Compulsory Product Certification) to GB14048.2-2001, Certificate Numbers: ❑ 2005010307139381 ❑ 2003010307094561 ❑ 2003010307094558 ■
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-11
February 2007
Low Voltage Power Circuit Breakers
Magnum IEC 60947-2 Rated
Magnum IEC Low Voltage Air Circuit Breaker Family
Table 13-3. Magnum IEC 60947-2 Rated Air Circuit Breakers Frame Breaker Amperes Type
800
Frame Type
MWN-408 MWN-508 MWN-608
Narrow Narrow Narrow
MWI-608 MWI-808 MWI-C08
Standard Standard Standard
MWN-410 MWN-510 MWN-610
Narrow Narrow Narrow
MWI-610 MWI-810 MWI-C10
Standard Standard Standard
MWN-412 MWN-512 MWN-612
Narrow Narrow Narrow
MWI-612 MWI-812 MWI-C12
Standard Standard Standard
MWN-516 MWN-616
Narrow Narrow
MWI-616 MWI-816 MWI-C16
Standard Standard Standard
MWN-520 MWN-620
Narrow Narrow
MWI-620 MWI-820 MWI-C20 2500
rms Symmetrical Current Ratings kA Interrupting at 240 Vac Icu = Ics
Interrupting at 440 Vac Icu = Ics
Interrupting at 690 Vac Icu = Ics
Withstand Rating Icw 1-Sec / 3-Sec
Fixed Internal Inst. Trip
Available Current Sensor & Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In Rating)
40 50 65
40 50 65
40 50 65
40 / — 50 / — 65 / 40
— — —
65 85 100
65 85 100
65 85 85
65 / — 85 / 65 85 / 65
— — 85
40 50 65
40 50 65
40 50 65
40 / — 50 / — 65 / 40
— — —
65 85 100
65 85 100
65 85 85
65 / — 85 / 65 85 / 65
— — 85
40 50 65
40 50 65
40 50 65
40 / — 50 / — 65 / 40
— — —
65 85 100
65 85 100
65 85 85
65 / — 85 / 65 85 / 65
— — 85
50 65
50 65
50 65
50 / — 65 / 40
— —
65 85 100
65 85 100
65 85 85
65 / — 85 / 65 85 / 65
— — 85
50 65
50 65
50 65
50 / 30 65 / 40
— —
Standard Standard Standard
65 85 100
65 85 100
65 85 85
65 / 50 85 / 65 85 / 65
— — 85
MWI-625 MWI-825 MWI-C25
Standard Standard Standard
65 85 100
65 85 100
65 85 85
65 / — 85 / 65 85 / 65
— — 85
200, 250, 300, 400, 630, 800, 1000, 1250, 1600, 2000, 2500
3200
MWI-632 MWI-832 MWI-C32
Standard Standard Standard
65 85 100
65 85 100
65 85 85
65 / 50 85 / 65 85 / 65
— — 85
200, 250, 300, 400, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200
4000
MWI-64N MWI-84N MWI-C4N
Double Double Double
65 85 100
65 85 100
65 85 100
65 / — 85 / — 100 / —
— — —
2000, 2500, 3200, 4000
5000
MWI-85N MWI-C5N
Double Double
85 100
85 100
85 100
85 / — 100 / —
— —
2500, 3200, 4000, 5000
6300
MWI-86N MWI-C6N
Double Double
85 100
85 100
85 100
85 / — 100 / —
— —
3200, 4000, 5000, 6300
1000
1250
1600
2000
200, 250, 300, 400, 630, 800
13 200, 250, 300, 400, 630, 800, 1000
200, 250, 300, 400, 630, 800, 1000, 1250
200, 250, 300, 400, 630, 800, 1000, 1250, 1600
200, 250, 300, 400, 630, 800, 1000, 1250, 1600, 2000
Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal to the published breaker Icw Rating.
CA08101001E
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-12
February 2007
Low Voltage Power Circuit Breakers Table 13-4. Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers
Trip Unit Type
Digitrip 520
Digitrip 520M
Digitrip 520MC
Digitrip 1150+
Ampere Range Interrupting Rating at 480 V rms Sensing
200 A – 6000 A 42 through 200 kA Yes
200 A – 6000 A 42 through 200 kA Yes
200 A – 6000 A 42 through 200 kA Yes
200 A – 6000 A 42 through 200 kA Yes
Protection and Coordination
13
Protection
Ordering Options Fixed Rating Plug (In) Overtemperature Trip
LI, LSI, LSIG Yes Yes
LSI, LSIG, LSIA Yes Yes
LSI, LSIG, LSIA Yes Yes
LSI, LSIG, LSIA Yes Yes
Long Delay Protection (L)
Long Delay Pickup Long Delay Time I2t at 6 x Ir Long Delay Time I4t IEEE Curves
0.4 – 1.0 x (In) 2 – 24 Seconds No No
0.4 – 1.0 x (In) 2 – 24 Seconds No No
0.4 – 1.0 x (In) 2 – 24 Seconds No No
0.4 – 1.0 x (In) 2 – 24 Seconds 1 – 5 Seconds Yes
Long Delay Thermal Memory High Load Alarm
Yes No
Yes No
Yes No
Yes 0.5 – 1.0 x (Ir)
Short Delay Protection (S)
Short Delay Pickup Short Delay Time I2t at 8 x Ir Short Delay Time Flat Short Delay Time ZSI
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
Instantaneous Protection (I)
Instantaneous Pickup Making Current Release Off Position
200 – 1000% x (In) & M1 Yes LSI & LSIG
200 – 1000% x (In) & M1 Yes Yes
200 – 1000% x (In) & M1 Yes Yes
200 – 1000% x (In) & M1 Yes Yes
Ground Fault Protection (G)
Ground Fault Alarm No Ground Fault Pickup 25 – 100% x (In) Ground Fault Delay I2t at .625 x In 100 – 500 ms
Yes 25 – 100% x (In) 100 – 500 ms
Yes 25 – 100% x (In) 100 – 500 ms
Yes 24 – 100% x (In) 100 – 500 ms
Ground Fault Delay Flat Ground Fault ZSI Ground Fault Thermal Memory
100 – 500 ms Yes Yes
100 – 500 ms Yes Yes
100 – 500 ms Yes Yes
100 – 500 ms Yes Yes
Disable Ground Fault Protection
No
No
No
No
Neutral Protection (N)
Model LSI
Model LSI
Model LSI
Model LSI
Cause of Trip LEDs Magnitude of Trip Information
Yes No
Yes Yes
Yes Yes
Yes Yes
Remote Signal Contacts Programmable Contacts
No No
Yes No
Yes No
Yes Yes
Digital Display Current (% ) Full Scale Sensor
No No
4-Character LCD Yes +/- 2%
4-Character LCD Yes +/- 2%
24-Character LED Yes +/- 1%
Voltage (%) L to L Power and Energy (%) Apparent Power kVA and Demand
No No No
No No No
No No No
Yes +/- 1% Yes +/- 2% Yes
Reactive Power kvar Power Factor Crest Factor
No No No
No No No
No No No
Yes Yes Yes
Power Quality — Harmonics % THD
No No
No No
No No
Yes Yes
No N/A
No Optional
INCOM/PowerNet Standard
INCOM/PowerNet/TripLink Standard
Trip Log (3 Events) Electronic Operations Counter
No No
No No
No No
Yes Yes
Testing Method Waveform Capture
Test Set No
Test Set No
Test Set No
Integral and Test Set Yes
ARMs (Arc Flash Reduction Mode) Breaker Health Monitor Programmable Relay Functions
No No No
No No No
Yes No No
Yes Yes Yes
System Diagnostics
System Monitoring
System Communications Type Power Supply in Breaker
Additional Features
Over and Undervoltage Alarm or Trip, Over and Underfrequency Alarm or Trip, Voltage Unbalance Alarm or Trip, Reverse Power Trip, and Phase Rotation Alarm are included.
1200 ampere maximum ground fault setting per UL/NEC. Test set for secondary injection. Contact Eaton for availability.
For more information visit: www.eaton.com
Legend: In = Rating Plug and Sensor Rating. Ir = Long Delay Pickup setting.
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-13
February 2007
Low Voltage Power Circuit Breakers Table 13-5. Digitrip Trip Units for Magnum IEC Rated Air Circuit Breakers
Trip Unit Type
Digitrip 520i
Digitrip 520Mi
Digitrip 520MCi
Digitrip 1150i+
Ampere Range Interrupting Rating at 690 V rms Sensing
200 A – 6300 A 40 – 100 kA Yes
200 A – 6300 A 40 – 100 kA Yes
200 A – 6300 A 40 – 100 kA Yes
200 A – 6300 A 40 – 100 kA Yes
Protection Ordering Options Fixed Rate Plug (In) Overtemperature Trip Long Long Delay Setting Delay Long Delay Time I2t at 6 x Ir Protection Long Delay Time I4t (L) IEC Type A, B, C Curves Long Delay Thermal Memory High Load Alarm
LI, LSI, LSIG Yes Yes 0.4 – 1.0 x (In) 2 – 24 Seconds No No Yes No
LSI, LSIG, LSIA Yes Yes 0.4 – 1.0 x (In) 2 – 24 Seconds No No Yes No
LSI, LSIG, LSIA Yes Yes 0.4 – 1.0 x (In) 2 – 24 Seconds No No Yes No
Short Delay Protection (S) Instantaneous Protection (I)
Short Delay Pickup Short Delay Time I2t at 8 x Ir Short Delay Time Flat Short Delay Time ZSI Instantaneous Pickup Making Current Release Off Position
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes 200 – 1000% x (In) & M1 Yes Yes
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
200 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
LSI, LSIG, LSIA Yes Yes 0.4 – 1.0 x (In) 2 – 24 Seconds 1 – 5 Seconds Yes Yes 0.7 – 1.0 x Ir 150 – 1000% x (Ir) & M1 100 – 500 ms 100 – 500 ms Yes
200 – 1000% x (In) & M1 Yes Yes
200 – 1000% x (In) & M1 Yes Yes
200 – 1000% x (In) & M1 Yes Yes
Earth Fault Protection (G)
Earth Fault Alarm Earth Fault Pickup Earth Fault Delay I2t at .625 x In
No 25 – 100% x (In) 100 – 500 ms 100 – 500 ms Yes Yes No Model LSI
Yes 25 – 100% x (In) 100 – 500 ms 100 – 500 ms Yes Yes No Model LSI
Yes 25 – 100% x (In) 100 – 500 ms 100 – 500 ms Yes Yes No Model LSI
Yes 24 – 100% x (In) 100 – 500 ms 100 – 500 ms Yes Yes Yes Model LSI
Yes No No No
Yes No Yes No
Yes No Yes No
Yes Yes Yes 2
No No No No No No No No No No
4 Character LCD Yes +/- 2% No No No No No No No No
4 Character LCD Yes +/- 2% No No No No No No No No
24 Character LED Yes +/- 1% Yes +/- 1% Yes +/- 2% Yes Yes Yes Yes Yes Yes
No N/A
No Optional
INCOM/PowerNet Standard
INCOM/PowerNet/TripLink Standard
No No
No No
No No
Yes Yes
Test Set No No No No
Test Set No No No No
Test Set No Yes No No
Integral and Test Set Yes Yes Yes Yes
Protection and Coordination
Earth Fault Delay Flat Earth Fault ZSI Earth Fault Memory Disable Ground Fault Protection Neutral Protection (N)
System Diagnostics Cause of Trip LEDs Magnitude of Trip Information Remote Signal Contacts Programmable Contacts
System Monitoring Digital Display Current (%) Full Scale Sensor Voltage (%) L to L Power and Energy (%) Apparent Power kVA and Demand Reactive Power kvar Power Factor Crest Factor Power Quality — Harmonics % THD
System Communications Type Power Supply in Breaker
Additional Features Trip Log (3 Events) Electronic Operations Counter Testing Method Waveform Capture ARMs (Arc Flash Reduction Mode) Breaker Health Monitor Programmable Relay Functions
Over and Undervoltage Alarm or Trip, Over and Underfrequency Alarm or Trip, Voltage Unbalance Alarm or Trip, Reverse Power Trip, and Phase Rotation Alarm are included.
Test set for secondary injection. Contact Eaton for availability.
Legend: In = Rating plug rating. Ir = LDPU setting. Note: i Trip units are only used on IEC breakers with earth fault.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-14
February 2007
Low Voltage Power Circuit Breakers
Breaker-Mounted Options and Accessories
■
■
■
Arc Chutes are Easily Removable for Inspection and Access to Breaker Contacts
■
■
13
Heel-Toe Contact Design Provides Demonstrated Long Life and Includes Wear Indicator for Visual Inspection
Magnum breakers are available with a comprehensive array of factoryinstalled breaker options to enable configured-to-order solutions for specified customer requirements. Field option kits are available to provide easy service, modification and customization of the breaker at the point of use. ■
Shunt Trip device (ST). Provides for remote electrically controlled breaker opening when energized by a rated voltage input. ■ Spring Charge Motor (MOT). Charges the breaker closing springs automatically, facilitating remote or local closing. The motor assembly includes its own cut-off switch that changes state at the end of the charging cycle. This contact can be wired out for external indication. ■ Spring Release device (SR). Provides for remote electrically controlled breaker closing when its coils are energized by a rated voltage input. ■ Undervoltage Release (UVR). Trips the breaker when an existing voltage signal is lost or falls below an established threshold.
■
■
Auxiliary Switch. Up to 6a/6b auxiliary individual dedicated contacts are available for customer use to indicate if the breaker is in the OPEN or CLOSE position. Mechanical Trip Indicator Flag. The red trip indicator flag pops out to provide local visual indication when the Digitrip RMS trip unit acts to trip the breaker on an overcurrent condition. Bell Alarm/Overcurrent Trip Switch (OTS). Provides 2 Form C (changeover) contacts that change state when the Digitrip RMS trip unit acts to trip the breaker on an overcurrent condition. The contacts are available for external indication or customer use and are manually reset by the Mechanical Trip Indicator. Padlockable Pushbutton Cover. Permits padlocking hinged cover plates to block access to the PUSH ON and PUSH OFF buttons on the breaker faceplate. Mechanical Operations Counter. Records mechanical operations of the breaker over its installed life. Key Off Lock Provisions. Enables mounting of a single cylinder Kirk , Castell, or Ronis Key Lock to lock the breaker in the OPEN position. Latch Check Switch. Provides 1 Form C (changeover contact) that changes state when the breaker is ready to close. Can be wired to the Spring Release Device for fast transfer applications or wired for external ready-to-close indication.
Auxiliary Switches Come in Modular 2a/2b Contact Stages Providing up to 6a/6b Dedicated Contacts
Mechanical Trip Indicator With Bell Alarm (OTS) Switches Mounted
Shunt Trip, Spring Release and Undervoltage Release Device Installed on Accessory Deck
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-15
February 2007
Low Voltage Power Circuit Breakers Table 13-6. Magnum Breaker Control Device Application Guide — Vdc Breaker Control Device Nominal Voltage
24 Vdc
Shunt Trip (ST) Operational Voltage Range Power Consumption (Inrush) Opening Time
Trip Circuit 70 to 110% (Required for 35 ms) Seconds
17 – 26 Vdc 250 Watts 35 ms
Spring Release (SR) Operational Voltage Range Power Consumption (Inrush) Closing Time
Close Circuit 70 to 110% (Required for 200 ms) Seconds
17 – 26 Vdc 250 Watts 40 ms
Spring Charge Motor (MOT) Operational Voltage Range Amps (Running) Amps (Inrush) Power Consumption Charging Time Undervoltage Release (UVR) Operational Voltage Range Drop-out Voltage Range Power Consumption (Inrush) Power Consumption (Continuous) Opening Time Auxiliary Switches Minimum Load Contact Rating
32 Vdc
48 Vdc
125 Vdc
250 Vdc
34 – 53 Vdc 250 Watts 35 ms
77 – 138 Vdc 450 Watts 35 ms
154 – 275 Vdc 450 Watts 35 ms
34 – 53 Vdc 250 Watts 40 ms
77 – 138 Vdc 450 Watts 40 ms
154 – 275 Vdc 450 Watts 40 ms
41 – 53 Vdc 5.0 Amps 500% 250 Watts 5 Sec
94 – 138 Vdc 2.0 Amps 600% 250 Watts 5 Sec
187 – 225 Vdc 1.0 Amp 600% 250 Watts 5 Sec
41 – 53 Vdc 14 – 29 Vdc 275 Watts 18 Watts 70 ms
94 – 138 Vdc 33 – 75 Vdc 450 Watts 10 Watts 70 ms
187 – 275 Vdc 66 – 150 Vdc 450 Watts 10 Watts 70 ms
0.5 Amps
0.5 Amps
0.25 Amps
415 Vac
480 Vac
600 Vac
—
—
—
—
—
—
—
—
—
323 – 457 Vac 114 – 249 Vac 480 VA 10 VA 70 ms
408 – 528 Vac 144 – 288 Vac 400 VA 10 VA 70 ms
510 – 660 Vac 180 – 360 Vac 400 VA 10 VA 70 ms
—
—
—
—
—
— 85 to 110% Voltage Running % of Running Seconds
20 – 26 Vdc 12.0 Amps 300% 300 Watts 5 Sec
85 to 110% Voltage 30 to 60% Voltage Required for 200 ms Required for 400 ms Seconds
20 – 26 Vdc 7 – 14 Vdc 250 Watts 18 Watts 70 ms
27 – 35 Vdc 10 – 19 Vdc 275 Watts 15 Watts 70 ms —
Inductive Load
0.5 Amps
Table 13-7. Magnum Breaker Control Device Application Guide — Vac Breaker Control Device Nominal Voltage
120 Vac
240 Vac
13
Shunt Trip (ST) Operational Voltage Range Power Consumption (Inrush) Opening Time
Trip Circuit 70 to 110% (Required for 35 ms) Seconds
77 – 140 Vac 450 VA 35 ms
146 – 264 Vac 450 VA 35 ms
Spring Release (SR) Operational Voltage Range Power Consumption (Inrush) Closing Time
Close Circuit 70 to 110% (Required for 200 ms) Seconds
77 – 140 Vac 450 VA 40 ms
146 – 264 Vac 450 VA 40 ms
Seconds
93 – 140 Vdc 2.0 Amps 600% 250 VA 5 Sec
177 – 264 Vdc 1.0 Amp 600% 250 VA 5 Sec
85 to 110% Voltage 30 to 60% Voltage Required for 200ms Required for 400 ms Seconds
94 – 140 Vac 33 – 76 Vac 450 VA 10 VA 70 ms
177 – 264 Vac 62 – 144 Vac 400 VA 10 VA 70 ms
Spring Charge Motor (MOT) Operational Voltage Range Amps (Running) Amps (Inrush) Power Consumption Charging Time Undervoltage Release (UVR) Operational Voltage Range Drop-out Voltage Range Power Consumption (Inrush) Power Consumption (Continuous) Opening Time Auxiliary Switches Minimum Load Contact Rating
CA08101001E
85 to 110% Voltage Running % of Running
Inductive Load
10 Amps
10 Amps
For more information visit: www.eaton.com
13-16
Power Breakers, Contactors & Fuses Power Circuit Breakers February 2007
Low Voltage Power Circuit Breakers
Legend: LS Limit Switch for Closing Spring MOT Motor for Spring Charging ST Shunt Trip SR Spring Release UVR Undervoltage Release OTS Overcurrent Trip Switch Description of Operation: 1 — Motor is energized through LS contact. 2 — Motor runs and charges closing spring. 3 — When closing spring is fully charged, LS contacts change state. 4 — Close contacts energize SR coil. 5 — When breaker closes, “b” opens. 6 — LS contacts change state and motor recharges closing springs.
Close
Open
B12
B15
G
Open
B26
B10
Lever in Door Switch (Drawout Only)
Control Power
L.S.
SR
R
B24
A7
A1
A2
A3
a. b.
ST
a.
UVR
OTS 1* OTS 2*
MOT
B13
B14
B27
B11
B25
A8
A4
A5
A6
* Contacts shown for breaker open (not fully charged), not tripped. Dotted line denotes Magnum Breaker.
13
MDSEOBKR
Figure 13-1. Typical Magnum Breaker Control Circuit Diagram
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-17
February 2007
Medium Voltage Circuit Breakers
Medium Voltage Breakers
Application Description Eaton’s Cutler-Hammer Type VCP-W, VCP-T, T-VAC and W-VAC vacuum breakers provide centralized control and protection of medium voltage power equipment and circuits in industrial, commercial and utility installations involving generators, motors, feeder circuits, and transmission and distribution lines.
VCP-W Standard Features ■
Type VCP-W/VCP-T Medium Voltage Vacuum Circuit Breaker
Product Description
■ ■ ■
Breakers and structures for switchgear assemblies: ■
■ ■ ■ ■
ANSI 4.76 kV, 8.25 kV, 15 kV, 27 kV and 38 kV: ❑ 250 to 1500 MVA ❑ IEC 3.6 kV thru 17.5 kV ❑ 16 kA to 63 kA Metal-clad, compartmented design. Power modules. Mini modules. Breaker compartment kits.
■ ■ ■
■
■ ■ ■ ■ ■ ■ ■
CA08101001E
Eaton’s maintenance-free CutlerHammer vacuum interrupters with visual contact erosion indicator. Patented non-sliding/non-rolling V-flex current transfer system. Glass polyester insulation. Cycloaliphatic Epoxy Insulation (optional with Type VCPW-SE breakers) for 27 kV and 38 kV breakers. Front-accessible operating mechanism. Electrically operated trip-free, spring stored energy mechanism. Interlocks which prevent moving a closed circuit breaker into or out of the connected position. Closing springs automatically discharge before moving the circuit breaker into or out of the enclosure. Provisions for manual charging of closing springs. Manual close and trip pushbuttons. Operations counter. Closing spring charged/discharged indicator. Circuit breaker Open/Closed indicator. Auxiliary switch with 2A/3B for dc and 1A/3B for ac spare contacts. Spring charging motor, close coil, trip coil, latch check switch, and anti-pump relay.
For more information visit: www.eaton.com
VCP-T Standard Features ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Grounded steel barrier between mechanism and primary conductors. Spring loaded, silver-plated primary disconnects (drawout breaker). Silver-plated primary connections (fixed circuit breaker). Manual charging of closing springs (includes shunt trip). Integral spring charging handle. Auxiliary switch (5a and 5b contacts). Mechanical operations counter. 24, 48, 125 and 250 Vdc, 120 and 240 Vac control. Shunt trip. ON and OFF pushbuttons. Integral lifting hooks. Through or behind door operation. Identified/dedicated secondaries. Secondary umbilical cord (drawout circuit breaker). Secondary disconnect block (fixed circuit breaker). Two-step stored energy mechanism. O – 0.3s – CO – 15s – CO. Anti-pump. Trip free. Latch check switch. Visible contact erosion indicator. Visible contact wipe indicator. Disconnect, Test and Connect (drawout circuit breaker). Integral levering mechanism (drawout circuit breaker). Field installable accessories.
Standards and Certifications ■
Designed, tested and certified in accordance with ANSI and IEC standards. ■ Applicable ANSI standards C37.04-1979 or 1999, C37.09-1979 or 1999, C37.06-2000 and C37.013. ■ Internal arc resistance tested to IEC 298, Appendix AA, 25 kA for 1 second. ■ Drawout circuit breaker fully qualified to IEC 56 by testing inside the IEC 298 switchgear cubicle.
13
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-18
February 2007
Medium Voltage Circuit Breakers
ANSI Standards Table 13-8. ANSI Standard Ratings — VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis
kV
I
kV kV Amperes kA rms Peak rms
Maximum Voltage Divided by K
Short Circuit Current (at Rated Max. kV)
Permissible Tripping Delay
Current Values
Interrupting Time
Impulse
K
Current
Withstand ContinTest uous Voltage Current at 60 Hz Power Frequency (1 Min.)
Voltage Range Factor
E
MVA kV rms
Weight
Insulation Level
Y
E/K
Cycles Seconds kV rms
Maximum Symmetrical Interrupting Capability
Closing and Latching Capability
Closing and Latching Momentary Capability
kA Peak
kA rms Total Lbs. (kg)
Short Time Current
Kx1 kA rms
50 VCP-WND250
4.16
250
4.76 1.24 19
60
1200
29
5
2
3.85 36
97
58
345 (157)
50 VCP-W250
4.16
250
4.76 1.24 19
60
1200 2000 3000
29
5
2
3.85 36
97
58
350 (159) 410 (186) 525 (238)
50 VCP-W350
4.16
350
4.76 1.19 19
60
1200 2000 3000
41
5
2
4.0
49
132
78
460 (209) 490 (223) 525 (238)
50 VCP-W500 (63 kA)
4.16 —
4.76 1.00 19
60
1200 2000 3000
63
5
2
4.76 63
170
101
525 (238) 530 (241) 550 (250)
75 VCP-W500
7.2
8.25 1.25 36
95
1200 2000 3000
33
5
2
6.6
41
111
66
375 (170) 410 (186) 525 (238)
150 VCP-W500
13.8
500 15
1.30 36
95
1200 2000 3000
18
5
2
11.5
23
62 97
37 58
350 (159) 410 (186) 525 (238)
150 VCP-W750
13.8
750 15
1.30 36
95
1200 2000 3000
28
5
2
11.5
36
97 130
58 77
350 (159) 410 (186) 525 (238)
150 VCP-W1000
13.8
1000 15
1.30 36
95
1200 2000 3000
37
5
2
11.5
48
130
77
460 (209) 490 (223) 525 (238)
150 VCP-W1500 (63 kA)
13.8
—
1.00 36
95
1200 2000 3000
63
5
2
15.0
63
170
101
525 (238) 530 (241) 550 (250)
500
15
50 VCP-W25C
4.16 —
5.95 1.00 24
75
1200 2000 3000
25
3
2
5.95 25
97
58
350 (159) 410 (186) 525 (238)
50 VCP-W40C
4.16 —
5.95 1.00 24
75
1200 2000 3000
40
3
2
5.95 40
139
83
460 (209) 490 (223) 525 (238)
50 VCP-W50C
4.16 —
5.95 1.00 24
75
1200 2000 3000
50
3
2
5.95 50
139
83
525 (238) 530 (241) 550 (250)
50 VCP-W63C
4.16 —
5.95 1.00 24
75
1200 2000 3000
63
3
2
5.95 63
175
104
350 (159) 410 (186) 525 (238)
75 VCP-W50C
7.2
—
10.3
1.00 42
95
1200 2000 3000
50
3
2
10.3
50
139
83
460 (209) 490 (223) 525 (238)
150 VCP-W25C
13.8
—
17.5
1.00 42
95
1200 2000 3000
25
3
2
17.5
25
97
58
350 (159) 410 (186) 525 (238)
150 VCP-W40C
13.8
—
17.5
1.00 42
95
1200 2000 3000
40
3
2
17.5
40
139
83
350 (159) 410 (186) 525 (238)
150 VCP-W50C
13.8
—
17.5
1.00 42
95
1200 2000 3000
50
3
2
17.5
50
139
83
460 (209) 490 (223) 525 (238)
150 VCP-W63C
13.8
—
15.0
1.00 42
95
1200 2000 3000
63
3
2
15.0
63
175
104
525 (238) 530 (241) 550 (250)
Tested for 3 Seconds
Extra Capability Breakers
Standard Circuit Breakers
13
Maximum Voltage
Voltage Nominal 3-Phase MVA Class
Rated Values
Circuit Breaker Type Nominal Voltage Class
Identification
Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K >1 and K =1 ratings) and C37.09-1999. See Consulting Application Guide for further information.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-19
February 2007
Medium Voltage Circuit Breakers Table 13-8. ANSI Standards — VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis (Continued)
I
kV
MVA kV rms
kV kV Amperes kA rms Peak rms
50 VCP-WG50
4.16
—
4.76
1.00 19
60
1200 2000 3000
50 VCP-WG63
4.16
—
4.76
1.00 19
60
150 VCP-WG50
13.8
—
15.0
1.00 36
150 VCP-WG63
13.8
—
15.0
1.00 36
Maximum Voltage Divided by K
Short Circuit Current (at Rated Max. kV)
Permissible Tripping Delay
Current Values
Interrupting Time
Impulse
K
Current
Withstand ContinTest uous Voltage Current at 60 Hz
Power Frequency (1 Min.)
Voltage Range Factor
E
Weight
Insulation Level
Y
E/K
Maximum Symmetrical Interrupting Capability
Closing and Latching Momentary Capability
kA rms Total Lbs. (kg)
Short Time Current
Kx1 kA rms
kA Peak
50
3
1
4.76
50
137
82
525 (238) 530 (241) 550 (250
1200 2000 3000
63
3
1
4.76
63
173
103
525 (238) 530 (241) 550 (250
95
1200 2000 3000
50
3
1
15.0
50
137
82
525 (238) 530 (241) 550 (250)
95
1200 2000 3000
63
3
1
15.0
63
173
103
525 (238) 530 (241) 550 (250)
Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K >1 and K =1 ratings), and C37.09-1999. See Consulting Application Guide for further information.
CA08101001E
Closing and Latching Capability
Cycles Seconds kV rms
Tested for 3 Seconds
Generator Breakers (to ANSI C37.013)
Maximum Voltage
Voltage Nominal 3-Phase MVA Class
Rated Values
Circuit Breaker Type Nominal Voltage Class
Identification
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-20
February 2007
Medium Voltage Circuit Breakers Table 13-9. VCP-W Vacuum Breaker Types rated on Symmetrical Current Rating Basis
270 VCP-W750
13
Weight
T2
kV rms kV Peak Amperes kA rms ms (Cy) Seconds kV Peak µs
Capacitor Switching Cable Charging
E2
Current Values
Closing and Latching Capability (2.6 K Times Rated Short Circuit Current)
Maximum Permissible Tripping Delay Y
Interrupting Time
Impulse
Transient Recovery Voltage
kA Peak
Amperes lbs.
1.0
60
125
600 1200 2000
16
83 (5)
2
51
105
¥43
31.5
460 480 500
27
750
270 VCP-W1000 27
1000
27
1.0
60
125
600 1200 2000
22
83 (5) 2
51
105
60
31.5
460 480 500
270 VCP-W1250 27
1250
27
1.0
60
125
600 1200 2000
25
83 (5) 2
51
105
68
31.5
460 480 500
270 VCP-W1600 27
1600
27
1.0
60
125
1200 2000
25
83 (5) 2
51
105
85
31.5
545 560
270 VCP-W2000 27
2000
27
1.0
60
125
1200 2000
40
83 (5) 2
51
105 106
31.5
545 600
270 VCP-W25C
27
—
27
1.0
60
125
1200 1600
25
50 (3)
2.5
50
50
85
31.5
545 560
270 VCP-W32C
27
—
27
1.0
60
125
1200 1600
31.5
50 (3)
1.6
50
50 100
31.5
545 560
270 VCP-W40C
27
—
27
1.0
60
125
1200 1600
40
50 (3)
1.0
50
50 112
31.5
545 560
27
Power Frequency (1 min.)
MVA kV rms
Voltage Range Factor K
Nominal 3-Phase MVA Class
kV
Maximum Voltage E
Nominal Voltage Class
Withstand Test Voltage
Current
Insulation Level
Short Circuit Current (at Rated max. kV) I
Rated Values Voltage
Continuous Current at 60 Hz
Identification Circuit Breaker Type
CESI tested to applicable ANSI standards C37.04, C37.09 and C37.06. Consult Eaton for CESI copies of test reports on file. Operating duty cycle CO-15 seconds-CO. Operating time values: Opening 33 – 55 ms, closing 50 – 60 ms and reclosing 18 cycles (300 ms). Tested at 28.5 kV. K = 1.0, therefore E = E/K and I = KI. Also maximum interrupting rating and short-time current rating. Duration of short-time current = 3 seconds, except as noted in Optional interrupting time of 50 ms (3 cycles) is available.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-21
February 2007
Medium Voltage Circuit Breakers
IEC Standards Table 13-10. IEC Standards — VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis Identification
Rated Values
Circuit Breaker Type
Voltage
kV rms
Weight
Insulation Level
Normal Current
Short Circuit Breaking Current and 3-Second Short Time Current
Short Circuit Making Current
Cable Charging Breaking Current
kV Peak
Amperes
Power Frequency
Impulse Withstand
kV rms Peak
kV Peak
Amperes
kA rms
Lbs. (kg)
36 VCP-WND25
3.6
10
40
630 1250
25
65
10
350 (159)
36 VCP-WND32
3.6
10
40
630 1250
31.5
82
10
350 (159)
72 VCP-WND25
7.2
20
60
630 1250
25
65
10
350 (159)
72 VCP-WND32
7.2
20
60
630 1250
31.5
82
10
350 (159)
36 VCP-W25
3.6
10
40
630 1250 2000
25
65
10
414 (188) 430 (195) 496 (225)
36 VCP-W32
3.6
10
40
1250 2000
31.5
82
10
414 (188) 496 (225)
36 VCP-W40
3.6
10
40
1250 2000
40
104
10
496 (225) 550 (250)
72 VCP-W25
7.2
20
60
630 1250 2000
25
65
10
414 (188) 414 (188) 496 (225)
72 VCP-W32
7.2
20
60
1250 2000
31.5
82
10
414 (188) 430 (195)
72 VCP-W40
7.2
20
60
1250 2000
40
104
10
430 (195) 496 (225)
120 VCP-W25
12.0
28
75
630 1250 2000
25
65
25
430 (195) 496 (225) 496 (225)
120 VCP-W32
12.0
28
75
1250 2000
31.5
82
25
430 (195) 496 (225)
120 VCP-W40
12.0
28
75
1250 2000
40
104
25
496 (225) 550 (250)
175 VCP-W25
17.5
38
95
630 1250 2000
25
65
—
430 (195) 496 (225) 496 (225)
175 VCP-W32
17.5
38
95
1250 2000
31.5
82
—
430 (195) 496 (225)
175 VCP-W40
17.5
38
95
1250 2000
40
104
—
496 (225) 550 (250)
175 VCP-W50
17.5
38
95
1250 2000 3150
50
130
—
1013 (460) 1079 (490) 1156 (525)
IEC Standards 60056 and 60694 apply.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-22
February 2007
Medium Voltage Circuit Breakers
Type VCP-W Vacuum Circuit Breaker Ratings Table 13-11. Type VCP-W Ratings on Symmetrical Current Rating Basis
kA kA kA kA kA kA s rms rms rms Peak rms rms Total Total Total
%
Transient Recovery Voltage (RRRV) Mechanical Endurance
Maximum Permissible Tripping Delay
Duration of Short Time Current Operating Duty (Duty Cycle) Rated Reclosing Factor (R) rms
Short Time Current
Momentary Current Withstand Capability
Closing and Latching Capability
Sym. Interrupting at V (Isc) % dc Component (Idc)
Max. Asym. Interrupting at V/K (Kxlsc) Max. Asym. Interrupting at V/K (SxKxlsc)
Continuous Current at 60 Hz
kA % rms
Asym. Interrupting (It)
Lightning Impulse 1.2x50
Amps rms
Asym. Factor S (Ref.)
Power Frequency (1 Minute)
kV Peak
Sec. kV/ µs
1
38
80
170
600 1200 1600 2000
16
47
1.2 19.2
16
19.3
43
26
16
3
100 83 5
2
0.6
380 VCP-W 25 34.5 38 and 380 VCP-WR 25
1
38
80
170
600 1200 1600 2000
25
47
1.2 30.0
25
30.0
68
40
25
3
100 83 5
2
0.6
380 VCP-W 32 34.5 38 and 380 VCP-WR 32
1
38
80
170
600 31.5 47 1200 1600 2000 3000FC
1.2 37.8
31.5 37.8
85
50
31.5 3
100 83 5
2
0.6
—
380 VCP-W 21 34.5 38 and 380 VCP-WR 21
1.65 23
170
1200 21 2000 3000FC
47
1.2 39.5
35
42.0
95
56
35
3
80
100 83 5
2
0.6
—
380 VCP-W 40 34.5 38 and 380 VCP-WR 40
1
38
80
170
1200 40 2000 3000FC 2500
47
1.2 48.0
40
48.0
107
63
40
3
100 83 5
2
0.6
2500
2000
2500
2000
2000
2000
380 VCP-W 6 34.5 38 and 380 VCP-WR 16
2000
13
kV kV rms rms
Voltage Range Factor K V/K
kV kV rms rms
Interrupting Time
Insulation Current Level Withstand Test Short Circuit Current
Cyc.
Rated Values Voltage
Nominal Voltage Class Maximum Voltage V
Identification Circuit Breaker Type
KEMA tested to applicable ANSI standards C37.04-1979, C37.09-1979 and C37.06-1979 (operating duty sequence CO - 15s - CO). Typical operating time values: operating 45 ms, closing 75 ms and reclosing 300 ms (18 cycles). The standard breaker is not rated for capacitor switching. If you require capacitor switching, please refer to the “C” breakers. K = 1.0, therefore E = E/K and I = KI. Refer to the Consulting Application Guide for more information. The ANSI C37.06 standard requires 150 kV BIL. If higher BIL levels are required, please refer to the “C” breakers. For force air cooled fixed breaker applications, consult Eaton. If you require 50 ms (3 cycle) interrupting time, please refer to the “C” breakers. No-load operations. At 23 kV rms (rated maximum voltage/K). Rated maximum symmetrical interrupting capability = 35kA rms (K x 1). CO – 15s – CO. Rated and tested also for rapid reclosing capability O - 0.3s - CO. Not rated for rapid reclosing.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-23
February 2007
Medium Voltage Circuit Breakers
T-VAC and T-VACR Vacuum Breaker Ratings
Table 13-13. T-VAC and T-VACR Ratings (Certified to IEC62271-100)
Table 13-12. VCP-T and VCP-TR Ratings (ANSI C37.04 and C37.09)
Lightning Impulse (Uw) Withstand Voltage
Normal Current (In)
Short Circuit Making Current (Isc)
Mechanical Endurance C–0
kV rms
kV rms
kV Peak
Amperes
kA rms
kA Peak
Operations
72 T-VAC16 and 72 T-VACR16
7.2
20
60
630 800 1250 1600
16
40
20,000 20,000 10,000 10,000
10,000 10,000 10,000 10,000
72 T-VAC20 and 72 T-VACR20
7.2
20
60
630 800 1250 1600
20
50
10,000 10,000 10,000 10,000
65
10,000 10,000 10,000 10,000
72 T-VAC25 and 72 T-VACR25
7.2
20
60
630 800 1250 1600
25
63
10,000 10,000 10,000 10,000
16
42
20,000 20,000 10,000 10,000
120 T-VAC16 and 120 T-VACR16
12
28
75
630 800 1250 1600
16
40
20,000 20,000 10,000 10,000
600 800 1200 1600
20
52
10,000 10,000 10,000 10,000
120 T-VAC20 and 120 T-VACR20
12
28
75
630 800 1250 1600
20
50
10,000 10,000 10,000 10,000
60
600 800 1200 1600
25
65
10,000 10,000 10,000 10,000
120 T-VAC25 and 120 T-VAC25
12
28
75
630 800 1250 1600
25
63
10,000 10,000 10,000 10,000
36
95
600 800 1200 1600
16
42
10,000 10,000 10,000 10,000
175 T-VAC16 and 175 T-VACR16
17.5
38
95
630 800 1250 1600
16
40
10,000 10,000 10,000 10,000
15
36
95
600 800 1200 1600
20
52
10,000 10,000 10,000 10,000
175 T-VAC20 and 175 T-VACR20
17.5
38
95
630 800 1250 1600
20
50
10,000 10,000 10,000 10,000
15
36
95
600 800 1200 1600
25
65
10,000 10,000 10,000 10,000
175 T-VAC25 and 175 T-VACR25
17.5
38
95
630 800 1250 1600
25
63
10,000 10,000 10,000 10,000
Voltage Class
Power Frequency
Impulse Withstand
Continuous Current
Short Circuit Breaking Current
Short Circuit Making Current
kV rms
kV Peak
Amperes
kA rms
kA Peak
50 VCP-T16 and 50 VCP-TR16
4.76
19
60
600 800 1200 1600
16
42
20,000 20,000 10,000 10,000
50 VCP-T20 and 50 VCP-TR20
4.6
19
60
600 800 1200 1600
16
52
50 VCP-T25 and 50 VCP-TR25
4.76
19
60
600 800 1200 1600
25
75 VCP-T16 and 75 VCP-TR16
8.25
20
60
600 800 1200 1600
75 VCP-T20 and 75 VCP-TR20
8.25
20
60
75 VCP-T25 and 75 VCP-TR25
8.25
20
150 VCP-T16 and 150 VCP-TR16
15
150 VCP-T20 and 150 VCP-TR20 150 VCP-T25 and 150 VCP-TR25
Use 15 kV breaker and cassette when 95 kV impulse withstand required. 1600 A VCP-T breaker available. Also 2 second short time current rating.
CA08101001E
Short Circuit Breaking Current
Power Frequency Withstand Voltage
Operations
Insulation Level
kV rms
Insulation Level
Voltage Class
Rated Values
Circuit Breaker Type
Rated Values
Circuit Breaker Type Mechanical Endurance C–0
Identification
Identification
Use 17.5 kV breaker and cassette when 95 kV impulse withstand required. 1600 A T-VAC breaker available. Also 3 second short time current rating.
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-24
February 2007
Medium Voltage Circuit Breakers
Technical Data and Specifications
Mini Module
Type VCP-W Circuit Breaker Shown from Rear
VCP-W Circuit Breaker with Deadfront Panel Removed
5/15 kV VCPW-ND and VCP-W Power Modules — Dimensions in Inches (mm)
13
Figure 13-2. Power Module, 5/15 kV VCPW-ND 26.00 (660) Wide, VCP-W 36.00 (914) Wide
VCPW-ND Dimensions of Breaker Travel 15.00 (381.0 mm).
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Circuit Breakers
13-25
February 2007
Medium Voltage Circuit Breakers
5/15 kV VCPW-ND and VCP-W Mini Modules — Dimensions in Inches (mm)
13 Figure 13-3. 5 kV VCPW-ND Mini Module 25.88 (657) Wide
Current transformers not supplied.
5/15 kV VCP-W Mini Module — Dimensions in Inches (mm)
Figure 13-4. 5/15 kV VCP-W Mini-Module 35.88 (911) Wide
Current transformers not supplied.
CA08101001E
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Power Contactors
13-26
February 2007
Product Description
SL MV Power Contactor Size 160 – 400 Amperes
Fully applicable to:
Options and Accessories
■
Full voltage starting. ■ Reduced voltage starting.
SL Series — Accessory Kits
The perfect choice for harsh duty applications:
Mechanical Latch Kit — SL Vacuum Contactor Sizes 160 – 400 Amperes
■
Field Mount to 160 – 400 amperes SL Vacuum Contactor. Coil voltages available in a wide range of ac and dc selections. Easy to install on new and existing units.
■ ■ ■ ■ ■
Mining. Pulp and paper. HVAC. Petrochemical. Automotive. Many others.
Features, Benefits and Functions SL Medium Voltage Contactor
Product Description ■
■
13 ■ ■ ■ ■ ■ ■
■
■
■
■
A single family of contactors for any medium voltage control application. Voltage range of 2200 to 7200 volts. Ampere ratings from 160 through 400 amperes with Induction Motor Horsepower ranges from 600 to 5500 hp. Three different altitude versions. Leading-edge vacuum technology. Fully complies with global standards. Third-party qualified by UL, CSA, KEMA. Long life — 300,000 electrical and over 2 million mechanical. Mounting flexibility — panel or pedestal mounting provisions are standard. Unit can be mounted in horizontal or vertical position. Field-selectable settings for coil voltage, ac/dc, and coil dropout time. Field kits available for auxiliary contacts and mechanical latch. Accessories are common for all sizes. Special ordering allows unit to be factory pre-set to customer specification, including field kit installation. Highest quality available — all contactors manufactured within state-of-the-art “ISO-Certified” facilities. 100% made in America.
The SL Contactor Ratings ■
Voltages of 2200 – 7200 volts. Amperages from 160 – 400 amperes. ■ Interrupting ratings as high as 8500 amperes. ■
Control Voltages (Field Adjustable) ■
110, 220 Vac 50 Hz. 120, 240 Vac 60 Hz. ■ 125 Vdc. ■
Drop-out Time (Field Adjustable) ■
30 ms 50 ms ■ 130 ms ■ 250 ms ■ 330 ms ■
NEMA ANSI ■ IEC ■
Third-Party Verification ■
UL CSA ■ KEMA ■
Auxiliary Contact Kit
Easy-to-Install Option Kits (Field Addition)
Mechanical Interlock Kit
■
Field Mount mechanical interlock kits for 160 – 400 amperes SL Vacuum Contactor.
Up to 6 extra auxiliary contacts. ■ Mechanical latch — many coil voltages.
Long Life Guarantees High Quality ■ ■
300,000 electrical operations. 2.5 million mechanical operations.
Standards and Certifications
Eaton’s Cutler-Hammer SL Medium Voltage Contactor starting applications:
■
Squirrel-cage induction motors. Synchronous motors. ■ Wound-rotor.
Field Mount auxiliary contact kits for 160 – 400 amperes SL Vacuum Contactor. Contact kits are available in many configurations of NO-NC.
Global Acceptability
Design and Test Standards
■
Auxiliary Contact Kit — SL Vacuum Contactor Sizes 160 – 400 Amperes
■
Application Description ■
Mechanical Latch Kit
UL 347, File No. E63257. CSA T.I.L. D-21, File No. LR28548. ■ IEC No. 60470. ■ ANSI/NEMA ICS 3 – 1993 (R2000) ■
Mechanical Interlock Kit
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Contactors
13-27
February 2007
Product Description
SL MV Power Contactor Size 800 Amperes
Application Description
Standards and Certifications
Eaton’s Cutler-Hammer SL Medium Voltage Contactors starting applications:
Design and Test Standards
■
Squirrel-cage induction motors. ■ Synchronous motors. ■ Wound-rotor.
■
UL 347, File No. E63257. CSA T.I.L. D-21, File No. LR28548. ■ ANSI/NEMA ICS 3 – 1993 (R2000) ■ IEC 60470 ■
Fully applicable to: ■ ■
Full voltage starting. Reduced voltage starting.
SL Series — Accessory Options 800 Amperes
The perfect choice for harsh duty applications: ■ ■ ■
SL Medium Voltage Contactor
Product Description ■
■
■ ■ ■ ■ ■
■
■
A single family of contactors for any medium voltage control application. Voltage range of 2200 to 7200 volts. Ampere rating of 800 amperes with Induction Motor Horsepower ranges from 3000 to 10,000 hp. Two different altitude versions. Leading-edge vacuum technology. Third-party qualified by UL, CSA, KEMA. Long life — 100,000 electrical and over 1 million mechanical. Mounting flexibility — panel or pedestal mounting provisions are standard. Unit can be mounted in horizontal or vertical position. Special ordering allows unit to be factory pre-set to customer specification, including field kit installation. Highest quality available — all contactors manufactured within state-of-the-art “ISO-Certified” facilities. 100% made in America.
■ ■ ■
Mining. Pulp and paper. HVAC. Petrochemical. Automotive. Many others.
Features, Benefits and Functions The SL Contactor Ratings Voltages of 2200 – 7200 volts. 800 amperes (720 amperes enclosed). ■ Interrupting rating of 12,500 amperes. ■
Control Voltages ■
110, 220 Vac 50 Hz. 120, 240 Vac 60 Hz. ■ 125 Vdc. ■
Drop-out Time ■
50 – 330 ms ■ Field Selectable
Acceptability ■
NEMA ■ ANSI ■ IEC
Third-Party Verification ■
UL CSA ■ KEMA ■
Factory Installed Option Kit ■
Mechanical latch — many coil voltages.
Long Life Guarantees High Quality ■ ■
CA08101001E
13
■
100,000 electrical operations. 1 million mechanical operations.
For more information visit: www.eaton.com
Mechanical Latch Assembly 800 Amperes
Mechanical Latch Option — SL Vacuum Contactor Size 800 Ampere Factory installed for 800 ampere SL Vacuum Contactor. Coil voltages available in a wide range of ac and dc selections.
Power Breakers, Contactors & Fuses Power Contactors
13-28
February 2007
SL Series Fuses
SL Series Fuses Table 13-14. Fuse Application Table for SL Contactors Motor FLA
Fuse Application Table for SL Contactors (Continued)
Voltage
Suggested Cutler-Hammer Fuse
Rating
11 – 18 18 – 31 31 – 46 46 – 62 62 – 74 74 – 93 93 – 137 137 – 160
2400 – 4800
5BCLS-30 5BCLS-2R 5BCLS-3R 5BCLS-4R 5BCLS-5R 5BCLS-6R 5BCLS-9R 5BCLS-12R
30 – 1R 30 70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 130 230 – 12R 130
11 – 34 34 – 46 46 – 56 56 – 68 68 – 85 85 – 137 137 – 160
5500 – 6600
7BCLS-2R 7BCLS-3R 7BCLS-4R 7BCLS-5R 7BCLS-6R 7BCLS-9R 7BCLS-12R
70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 50 230 – 12R 250
5BCLS-30 5BCLS-2R 5BCLS-3R 5BCLS-4R 5BCLS-5R 5BCLS-6R 5BCLS-9R 5BCLS-12R
30 – 1R 30 70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 130 230 – 12R 130
7BCLS-2R 7BCLS-3R 7BCLS-4R 7BCLS-5R 7BCLS-6R 7BCLS-9R 7BCLS-12R
70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 50 230 – 12R 250
Minimum Opening Time
SL-160
11 – 18 18 – 31 31 – 46 46 – 62 62 – 74 74 – 93 93 – 137 137 – 200
2400 – 4800
11 – 34 34 – 46 46 – 56 56 – 68 68 – 85 85 – 137 137 – 200
5500 – 6600
Voltage
Suggested Cutler-Hammer Fuse
Rating
Minimum Opening Time
11 – 18 18 – 31 31 – 46 46 – 62 62 – 74 74 – 93 93 – 137 137 – 187 187 – 200 200 – 360
2400 – 4800
5BCLS-30 5BCLS-2R 5BCLS-3R 5BCLS-4R 5BCLS-5R 5BCLS-6R 5BCLS-9R 5BCLS-12R 5BCLS-12R N/A
30 – 1R 70 – 2R 100 – 3R 130 – 4R 150 – 5R 170 – 6R 200 – 9R 230 – 12R 230 – 12R —
30 30 30 30 30 30 130 130 130 —
11 – 34 34 – 46 46 – 56 56 – 68 68 – 85 85 – 137 137 – 200 187 – 200 200 – 360
5500 – 6600
7BCLS-2R 7BCLS-3R 7BCLS-4R 7BCLS-5R 7BCLS-6R 7BCLS-9R 7BCLS-12R 7BCLS-12R N/A
70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 50 230 – 12R 250 230 – 12R 250 — —
11 – 18 18 – 31 31 – 46 46 – 62 62 – 74 74 – 93 93 – 137 137 – 187 187 – 273 273 – 400
2400 – 4800
5BCLS-30 5BCLS-2R 5BCLS-3R 5BCLS-4R 5BCLS-5R 5BCLS-6R 5BCLS-9R 5BCLS-12R 5BCLS-18R 5BCLS-24R
30 – 1R 30 70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 30 230 – 12R 30 390 – 18R 50 450 – 24R 130
11 – 34 34 – 46 46 – 56 56 – 68 68 – 85 85 – 137 137 – 187 187 – 273 273 – 400
5500 – 6600
7BCLS-2R 7BCLS-3R 7BCLS-4R 7BCLS-5R 7BCLS-6R 7BCLS-9R 7BCLS-12R 7BCLS-18R 7BCLS-24R
70 – 2R 30 100 – 3R 30 130 – 4R 30 150 – 5R 30 170 – 6R 30 200 – 9R 30 230 – 12R 30 390 – 18R 50 450 – 24R 250
225 – 360 360 – 449 450 – 720
2400 – 4800
5BCLS-24R 5BCLS-36R 5BCLS-44R
450 – 24R 50 650 – 36R 130 800 – 44R 250
225 – 400 400 – 449 450 – 720
5500 – 6600
7BCLS-24R 7BCLS-36R 7BCLS-44R
450 – 24R 50 650 – 36R 130 800 – 44R 250
SL-360
SL-200
13
Motor FLA
For FLA > 180, maximum acceleration time = 4.5 seconds.
SL-400
SL-800
For FLA > 360, maximum acceleration time = 6 seconds.
Note: Fuse selections based on LRC = FLA x 6 with acceleration time of 10 seconds except where otherwise noted.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Contactors
13-29
February 2007
SL Series Ratings
SL Series Ratings Table 13-15. Type SL Vacuum Contactor Ratings Rated Utilization Voltage
Interrupting Rating NEMA Unfused (E1) kA
Application Table
Transformer kVA
Capacitor kvar
Maximum Insulation Voltage
800 1000 1400 2200
600 800 1000 1600
480 640 960 1320
7200
800 1100 1500 2250
1000 1250 1750 2750
750 1000 1250 2000
600 800 1200 1650
7200
1500 2000 2500 4000
1500 2000 2500 4000
1750 2500 3000 5000
1200 1600 2000 3200
1000 1475 2150 2950
7200
50 50 50 50
1750 2250 3000 4500
1750 2250 3000 4500
2000 2500 3500 5500
1500 2000 2500 4000
1200 1650 2400 3300
7200
50 (200 MVA at 2300 V) 50 (285 MVA at 3300 V) 50 (400 MVA at 4600 V) 50 (570 MVA at 6600 V)
3000 4000 5000 8000
3000 4000 5000 8000
3500 5000 6000 10,000
2500 3500 4500 6000
2400 3200 4000 4800
7200
NEMA Fused (E2) kA
Induction Motor Horsepower
Synchronous Motor Horsepower
4.5 4.5 4.5 4.5
50 50 50 50
600 900 1200 1800
600 900 1200 1800
4.5 4.5 4.5 4.5
50 50 50 50
800 1100 1500 2250
4.5 4.5 4.5 4.5
50 50 50 50
8.5 8.5 8.5 8.5
(0.8 PF)
(1.0 PF)
160 Ampere Frame 2200 – 2500 3000 – 3600 3800 – 4800 6000 – 6900
200 Ampere Frame 2200 – 2500 3000 – 3600 3800 – 4800 6000 – 6900
360 Ampere Frame 2200 – 2500 3000 – 3600 3800 – 4800 6000 – 6900
400 Ampere Frame 2200 – 2500 3000 – 3600 3800 – 4800 6000 – 6900
800 Ampere Frame 2200 – 2500 3000 – 3600 3800 – 5000 6000 – 7200
12.5 (50 MVA) 12.5 (50 MVA) 12.5 (75 MVA) 12.5 (100 MVA)
Table 13-16. Rating Specifications Ampere Rating
160 A
200 A
360 A
400 A
800 A
Maximum Interrupting Current (3 Operations — Amperes)
4500
4500
4500
8500
12,500
160
200
360
400
1600 1280
2000 1600
3600 2880
4000 3200
Rated Current IEC Make-Break Capability — AC4 (Amperes) Make Break
CA08101001E
For more information visit: www.eaton.com
800 (720 Enclosed) 8000 6400
13
Power Breakers, Contactors & Fuses Power Contactors
13-30
February 2007
Product Specifications
Product Specifications
160 – 400 Amperes ■
Voltage Class Eaton’s Cutler-Hammer SL Medium Voltage Vacuum Contactors are designed to operate on voltage systems rated from 2200 to 7200 volts. Typical system voltages are 2400, 3300, 4160 and 6600 volts.
■
Altitude
■
SL Contactors are capable of operating in virtually any altitude range. Three versions are offered in Standard, High and Low altitude configurations. No de-rating is necessary for proper operation. Altitude designations are listed in the table below.
■
Table 13-17. Altitude Altitude
Low
■
Standard
High
160 – 400 A
■
Feet
-11,500 to -3300 to -3300 +6600
+6600 to +13,100
■
Meters
-3500 to -1000
-1000 to +2000
+2000 to +4000
■
Feet
N/A
-3300 to +11,800
+11,800 to +16,000
Meters
N/A
-1000 to +3600
+3600 to +4900
800 A
13
Control Voltage Control coil voltage should be selectable in the field. Standard voltages available should be 120/60, 110/50, 240/60, 220/50 and 125 Vdc. Coil should pickup at 80% of rated coil voltage and dropout not sooner than 60% of rated coil voltage. Opening time should be field selectable within the range of 30 ms – 330 ms for 160 – 400 A and 50 ms – 330 ms for 800 A.
■ ■ ■ ■
■
■
Short-time current: ❑ 30 seconds: 2400 amperes ❑ 1 second: 6000 amperes ❑ 8.7 ms: 63 kA Peak (0.5 cycle) Normal service altitude: -3281 to +6562 ft. (-1000 to +2000 meters). Mechanical life: 2.5 million. Electrical life: ❑ 6 x Rated Make/ 1x Rated Break: 300,000 operations ❑ 6 x Rated Make/ 6 x Rated Break: 300,000 operations BIL (impulse withstand): 60 kV (1.2 x 50 microseconds) Dielectric strength: 20 kV rms (1 minute) Closing time: 80 milliseconds (energization to contact touch). Selectable opening times: ❑ 30 milliseconds (2 cycles) ❑ 50 milliseconds (3 cycles) ❑ 130 milliseconds (8 cycles) ❑ 250 milliseconds (15 cycles) ❑ 330 milliseconds (20 cycles) Arcing time: 12 ms (0.75 cycle) or less. Pickup voltage: 80% rated coil voltage. Dropout voltage: 60% rated coil voltage. Control voltages: ❑ ac/Hz: 110/50, 120/60, 220/50, 240/60 ❑ dc: 125 Control circuit burden: ❑ Closing: (200 milliseconds) – 110/120 ac, 125 dc 1 kVA – 220/240 ac 1.8 kVA ❑ Holding: – 110/120 ac 125 dc 40 VA – 220/240 ac 50 VA Auxiliary contact rating: ❑ 600 volts (maximum) ❑ 10 amperes continuous current ❑ Making capacity – ac: 7200 VA – dc: 125 VA ❑ Breaking capacity – ac: 720 VA – dc: 125 VA
For more information visit: www.eaton.com
■
Latch (when specified) ❑ Mechanical life: 250,000 operations ❑ Trip voltage – dc: 24 volts – dc: 125 volts – ac: 110/120 volts ❑ Minimum trip voltage: 80% rated coil voltage ❑ Trip burden – 24 Vdc: 400 VA – 48 and 125 Vdc: 400 VA – 110 and 120 Vac: 400 VA – 220 and 240 Vac: 400 VA ❑ Trip Time (2 cycles): 30 ms ■ Weight ❑ 150 – 360 A: 47 Lbs. (21.3 kg) ❑ 400 A: 49 Lbs. (22.2 kg)
800 Amperes ■
■ ■ ■ ■ ■ ■
■
■ ■ ■ ■
■
Short-time current ❑ 30 seconds: 4320 amperes ❑ 1 second: 10,800 amperes ❑ 8.7 ms (0.5 cycle) 86 kA peak Normal service altitude: -3281 to +6562 ft. (-1000 to +2000 meters). Mechanical life: 1 million. Electrical life: 100,000 operations. BIL (impulse withstand): 60 kV (1.2 x 50 microseconds). Dielectric strength: 18.2 kV rms (1 minute). Closing time (energization to contact touch): 80 milliseconds. Opening times (deenergization to full open): ❑ 50 ms (3 cycles) ❑ 130 ms (8 cycles) ❑ 250 ms (12 cycles) ❑ 330 ms (20 cycles) Arcing time: 12 ms (0.75 cycle) or less. Pickup voltage: 80% rated coil voltage. Dropout voltage: 60% rated coil voltage. Control voltages: ❑ ac/Hz: 110/50, 120/60 Vac, 220/50, 240/60 ❑ dc: 125 Vdc Control circuit burden: ❑ Closing (120/240): 1700 VA/2600 VA ❑ Holding (120/240): 80 VA/100 VA
CA08101001E
Power Breakers, Contactors & Fuses Power Contactors
13-31
February 2007
Product Specifications
800 Amperes (Continued) ■
Auxiliary contact rating: ❑ 600 volts (maximum) ❑ 10 amperes continuous current ❑ Making capacity – ac: 7200 VA – dc: 200 VA ❑ Breaking capacity – ac: 720 VA – dc: 200 VA ■ Latch (when specified): ❑ Mechanical life: 250,000 operations ❑ Trip voltage – dc: 24, 48, 96 volts – ac: 110/120, 220/240 volts 50/60 Hz ❑ Minimum trip voltage: 80% rated coil voltage ❑ Trip burden – 24 Vdc: 1200 VA – 48 and 96 Vdc: 400 VA – 110 and 220 Vac: 500 VA ❑ Trip time (2 cycles): 30 milliseconds ■ Weight: 95 Lbs. (43.1 kg).
Technical Data and Specifications Electrical Connections Diagrams (160 – 400 Amperes) 8 7
White
6
Black
5
White
dc Coil 1
dc Coil 2
Black
4 3 Control Voltage (On/Off)
2 1
Figure 13-5. Connection for Magnetically Held Contactor (+)
M dc M Control Voltage (Open)
(–) Latch Coil
8 7
13
White
6
Black
5
White
dc Coil 1
dc Coil 2
Black
4 3 Control Voltage (Close)
2 1
Figure 13-6. Connections for Mechanically Latched Contactor
M contacts are connected in parallel for ≤ 48 V. M contacts are connected in series for > 48 V.
Table 13-18. Control Voltage Settings Setting
SW1
SW2
SW3
110 Vac 50 Hz 120 Vac 60 Hz 220 Vac 50 Hz
Off On Off
Off Off On
Off Off Off
240 Vac 60 Hz 125 Vdc
On Off
On Off
Off On
Note: Stock units pre-set to 120/60 Vac.
Table 13-19. Dropout Time Settings Delay Setting
SW4
SW5
SW6
30 ms 50 ms 130 ms
Off On Off
Off Off On
Off Off Off
250 ms 330 ms
On Off
On Off
Off On
Table 13-20. Altitude Designations
CA08101001E
Altitude
Low
Standard
High
Feet Meters
-11,483 to -3281 -3500 to -1000
-3281 to +6562 -1000 to +2000
+6562 to +13,123 +2000 to +4000
For more information visit: www.eaton.com
13-32
Power Breakers, Contactors & Fuses Power Contactors February 2007
SL Series (160 – 400 Amperes)
SL Series (160 – 400 Amperes)
Panel-Mount Provisions
Panel-Mount Provisions Vacuum Interrupters
Panel-Mount Provisions Actuator Assembly
Control Terminal Strip
Contactor Nameplate
Auxiliary Contact Blocks
Auxiliary Contact Blocks
Pedestal-Mount Provisions
Pedestal-Mount Provisions
13
Coil Control Board (Behind Control Terminal Strip)
Magnet Coil
Mechanical Latch Provision
SL Series Features
Control Settings
Coil Control Board
DIP Switches Note: Refer to Table 13-18 for Control Voltage Settings and Table 13-19 for Dropout Time Settings.
Control Terminal Strip
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Contactors
13-33
February 2007
SL Series (160 – 400 Amperes)
Front and Rear View (160 – 400 Amperes)
Front View 160 – 400 Amperes
Rear View 160 – 400 Amperes
Dimensional Drawings (160 – 400 Amperes) in Inches (mm) 14.00 (355.6) 4.38 4.38 (111.3) (111.3)
Upper Te erminals
4.38 (111.3)
4.38 (111.3)
15.50 (393.7)
Lower Terminalss 15.06 (382.5)
6.85 (174.0) 174.0 16.00 0 (406.4) 406.4
16.00 (406.4) 8.75 (222.2))
15 25 15.25 (387.4) (387 4)
7.36 (186.9) 186.9
16 25 16.25 (412.8) (412 8)
Figure 13-9. Rear Dimensions 160 – 400 Amperes 15.25 (387.4)
16.25 (412.8) Rear Mounting .328 (8.3) DIA
Figure 13-7. Front Dimensions 160 – 400 Amperes .406 406 (10 (10.3) 3) DIA (6)
.78 (19.8)
6.85 (174.0)
Front Mounting .328 (8.3) DIA
15.50 (393.7)
16.00 (406.4)
8.70 (221.0) 221.0 7.70 (195.6) 195.6
7.36 (186.9) 186.9 .313 (8.0) DIA
.83 83 (21.1))
Front
13.60 (345.4)
1.77 (45.0)
.83 83 (21.1) (21 1)
15.25 (387.4)
Figure 13-8. Base Plate Dimensions 160 – 400 Amperes CA08101001E
Front
.27 (6.9)
4.44 9.09 (112.8) (230.9)
Figure 13-10. Side Dimensions 160 – 400 Amperes
For more information visit: www.eaton.com
8.70 (221.0)
13
13-34
Power Breakers, Contactors & Fuses Power Contactors February 2007
SL Series (800 Amperes)
Front and Rear View 800 Amperes
Front View 800 Amperes
Rear View 800 Amperes
Dimensional Drawings 800 Amperes in Inches (mm)
2.75 (69.9)
13
3 70 3.70 (94.0) (94 0)
Latch Trip Target (When Used)
I l’k Intl’
4 38 4.38 (111.3) 111 3
4 38 4.38 (111.3) 111 3
.50 (12.7) DIA Mounting Hole (4) Places .625 (15.9) square shaft with the axis vertical when the contactor is closed. Rotates 3.8 counterclockwise to open.
Intl’k 10.25 (260.4)
14.89 (378.2) Optional 12 Point Plug
8.50 (216.0) 216.0
.50 50 (12.7) DIA Bolt Hole (6) Places
11.25 (2 285.8)
2.35 5 (59.7) 4.01 (101.9) 5.01 (127.3)
4.34 (110.2) .39 (9.9) ( .80 (20.3)
6.12 (155.4)
16 93 16.93 (430.0) (430 0)
8.07 (205.0)
Figure 13-11. Front Dimensions 800 Amperes Latch (When Used) 1.30 (33.0)
16.41 (416.8)
16.15 (410.2)
Figure 13-13. Top Dimensions 800 Amperes
4.50
Plug (When Used) 1.15 (29.2)
Line Terminals
Latch Trip when Used
17.12 (434.8)
0.3 (7.62) Travel Required to Trip when Latch is Used
Load 11.36 Terminals (288.5) 10.70 (271.8)
Optional 12 Point Plug 4.06 (103.1)
13.94 (354.0)
2.69 (68.3)
Figure 13-12. Side Dimensions 800 Amperes
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Power Contactors
13-35
February 2007
Lug Terminal
Lug Terminal Table 13-21. Lug Terminal Dimensions in Inches (mm) Contactor Width Ampere Rating
Depth
Hardware (Bolt Diameter)
1.31 (33.3) 1.31 (33.3) 1.31 (33.3) 1.31 (33.3) 2.00 (50.8)
10 10 10 10 10
1.10 (27.9) 1.10 (27.9) 1.10 (27.9) 1.10 (27.9) 1.50 (38.1)
10 10 10 10 10
Upper Terminal 160 200 360 400 800
0.75 (19.1) 1.00 (25.4) 1.00 (25.4) 1.00 (25.4) 1.75 (44.5)
Lower Terminal Width
De
pt
h
Hardware Diameter
160 200 360 400 800
1.25 (31.8) 1.25 (31.8) 1.25 (31.8) 1.25 (31.8) 1.50 (38.1)
Lug Terminal
13
CA08101001E
For more information visit: www.eaton.com
13-36
Power Breakers, Contactors & Fuses Power Contactors February 2007
Product Selection
Product Selection Table 13-22. Power Contactors Catalog Numbering System
SL N 01 2 S 5 A - 22 0 Mechanical Latch
SL Contactor Series
160 – 400 Amperes (Coil Voltage) 0= 1= 2= 3= 4=
None 24 Vdc 32 Vdc 48 Vdc 110/50,120/60, or 125 Vdc 5 = 220/50, 240/60
Design N = NEMA C = IEC
800 Amperes (Coil Voltage) 0 = None 1 = 24 Vdc 3 = 48 Vdc 4 = 110 (50/60) 5 = 220 (50/60) 6 = 96 – 125 Vdc
Type Auxiliary Contacts
01 = Open Contactor
160 – 400 Amperes Ampere Rating
22 = 2 NO, 2 NC 28 = 2 NO, 8 NC 37 = 3 NO, 7 NC 46 = 4 NO, 6 NC 55 = 5 NO, 5 NC 64 = 6 NO, 4 NC 73 = 7 NO, 3 NC 82 = 8 NO, 2 NC
1 = 160 2 = 200 3 = 360 4 = 400 8 = 800
13
800 Amperes 22 = 2 NO, 2 NC
Altitude 160 – 400 Amperes
800 Amperes
S = Standard -3281 to +6562 ft. (-1000 to +2000 m) L = Low -11,483 to -3281 ft. (-3500 to -1000 m) H = High +6562 to +13,123 ft. (+2000 to +4000 m)
S = Standard -3281 to +11,811 ft. (-1000 to +3600 m) H = High +11,811 to +16,076 ft. (+3600 to +4900 m)
Coil Voltage A B S U W
= 120/60 = 240/60 = 125 Vdc = 110/50 = 220/50
Coil Dropout Time 160 – 400 Amperes 5 = 30 ms 6 = 50 ms 7 = 130 ms 8 = 250 ms 9 = 330 ms
For more information visit: www.eaton.com
800 Amperes 6 = 50 ms 7 = 130 ms 8 = 250 ms 9 = 330 ms
CA08101001E
Power Breakers, Contactors & Fuses Power Contactors
13-37
February 2007
SL Series Factory Modified
SL Series Factory Modified
Ordering Information
When Ordering Specify
Table 13-23. Factory Modified
■
Refer to Catalog Number Selection Guide. ■ Select Option Codes required. ■ Select Base Unit Price. ■ Add Pricing for Options Required.
Design and Test Standards ■
UL 347, File No. E63257. ■ CSA T.I.L. D-21, File No. LR28548. ■ ANSI/NEMA ICS 3. ■ IEC #60470.
Description
Option Code
Price U.S. $
Base Price 160 Ampere SL Contactor 200 Ampere SL Contactor 360 Ampere SL Contactor 400 Ampere SL Contactor 800 Ampere SL Contactor
1 2 3 4 8
Enclosure Open
01
Coil Voltage 110/50, 120/60 ac 220/50, 240/60 ac 125 Vdc
A, U B, W S
Coil Dropout Time 30 ms (160 – 400 Amperes Only) 50 ms 130 ms 250 ms 330 ms
5 6 7 8 9
Auxiliary Contacts 2NO – 2NC 2NO – 8NC (160 – 400 Amperes Only) 3NO – 7NC (160 – 400 Amperes Only) 4NO – 6NC (160 – 400 Amperes Only) 5NO – 5NC (160 – 400 Amperes Only) 6NO – 4NC (160 – 400 Amperes Only) 7NO – 3NC (160 – 400 Amperes Only) 8NO – 2NC (160 – 400 Amperes Only)
22 28 37 46 55 64 73 82
Mechanical Latch None 24 Vdc Coil 32 Vdc Coil (160 – 400 Amperes Only) 48 Vdc Coil 96 – 125 Vdc Coil (800 Ampere Only) 110/50, 120/60 Coil 125 Vdc Coil (160 – 400 Amperes Only) 220/50, 240/60, Coil
0 1 2 3 6 4 4 5
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CB-2 CA08101001E
For more information visit: www.eaton.com
13
13-38
Power Breakers, Contactors & Fuses Power Contactors February 2007
Accessory Kits
SL Vacuum Contactor Series — Accessory Kits (160 – 400 Amperes) Mechanical Latch Kit
Auxiliary Contact Kit
Mechanical Interlock Kit
Field Mount to 160 – 400 amperes SL Vacuum Contactor. Coil voltages available in a wide range of ac and dc selections. Easy to install on new and existing units.
Field Mount auxiliary contact kits for 160 – 400 amperes SL Vacuum Contactor. Contact kits are available in many configurations of NO-NC.
Field Mount mechanical interlock kits for 160 – 400 amperes SL Vacuum Contactor.
Mechanical Latch Kit
Auxiliary Contact Kit
Table 13-24. Ordering Information — Mechanical Latch Kit Coil Voltage
Catalog Number
24 Vdc 32 Vdc 48 Vdc 110/50, 120/60, 125 Vdc Selectable 220/50, 240/60 Selectable
SLA-ML24 SLA-ML32 SLA-ML48 SLA-ML120
13
SLA-ML240
Table 13-25. Ordering Information — Auxiliary Contact Kit Price U.S. $
Description
Catalog Number
3NO – 3NC Additional 6NO Additional 6NC Additional 5NO – 1NC Additional 4NO – 2NC Additional 2NO – 4NC Additional 1NO – 5NC Additional
SLA-AS33 SLA-AS60 SLA-AS06 SLA-AS51 SLA-AS42 SLA-AS24 SLA-AS15
Price U.S. $
Mechanical Interlock Kit
Table 13-26. Ordering Information — Mechanical Interlock Kit Description
Catalog Number
Vertical or Horizontal Arrangement
SLA-MI
Price U.S. $
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . N/A For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-39
February 2007
Product Description
Power Fuse Overview Eaton’s Cutler-Hammer roots in the power fuse business began over 60 years ago under Westinghouse Electric. In 1935, Westinghouse introduced the medium voltage boric acid expulsion fuse followed by the medium voltage current limiting fuse. Even today, medium voltage fuses continue to use the core Westinghouse technology. Eaton continues to build on the Westinghouse technology legacy by engineering higher performance, cost-effective power fuse products. Westinghouse and Cutler-Hammer medium voltage fuses are manufactured and tested to the requirements of the C37.4X series of standards. These standards are: IEEE Std. C37.40-1933 – IEEE Standard Service Conditions and Definitions for High Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories (ANSI) IEEE Std. C37.41-2000 – IEEE Standard Design Tests for High Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories (ANSI) ANSI C37.42-1996 – American National Standard Specifications for High Voltage Expulsion Type Distribution Class Fuses, Cutouts, Fuse Disconnecting Switches and Fuse Links
A better understanding of some fuse terminology will help you understand and select the correct fuse. The following is a brief overview of those terms.
Power vs. Distribution The differentiation is intended to indicate the test conditions and where fuses are normally applied on an electrical system, based on specific requirements for generating sources, substations and distribution lines. Each class has its own unique set of voltage, current and construction requirements (see ANSI C37.42, .44, .46 and .47).
Low vs. Medium vs. High Voltage While fuses are defined in the ANSI standards as either low or high voltage, Eaton has elected to name their fuses to correspond with the equipment in which they are installed. Therefore, per ANSI C84, our fuses are named as follows:
IEEE Std. C37.48-1997 – IEEE Guide for Application, Operation and Maintenance of High Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories (ANSI) IEEE Std. C37.48-1-2001 – IEEE Guide for the Operation, Classification, Application and Coordination of Current Limiting Fuses with Rated Voltages 1 – 38 kV
CA08101001E
Expulsion vs. Current Limiting (Definitions per ANSI C47.40-1993) An expulsion fuse is a vented fuse in which the expulsion effect of the gases produced by internal arcing, either alone or aided by other mechanisms, results in current interruption. An expulsion fuse is not current limiting and as a result limits the duration of a fault on the electrical system, not the magnitude. A current limiting fuse is a fuse that, when its current responsive element is melted by a current within the fuse’s specified current limiting range, abruptly introduces a high resistance to reduce current magnitude and duration, resulting in subsequent current interruption. Refer to Figure 13-14 for a features comparison.
Expulsion
Current Limiting
Vented Electromechanical Interrupts at Current Zero Generally Higher Voltage & Current Application Capabilities Different Time/Current Characteristics
Sealed Static Limits Fault Current Generally Higher Interrupting Ratings Different Time/Current Characteristics
i max. — i min. — i hr. — i —
maximum rated interrupting current minimum rated interrupting current current causing element melting in 1 hour any current melting element with no time limit
BACKUP
Current Limiting Type
The following IEEE standards are also applicable to the fuse products covered in this publication:
Low voltage — 1000 volts and below. Medium voltage — Greater than 1000 to 69,000 volts. ■ High voltage — Greater than 69,000 volts. ■
Table 13-27. General High Voltage Fuse Comparison
ANSI C37.46-2000 – American National Standard for High Voltage Expulsion and Current Limiting Type Power Class Fuses and Fuse Disconnecting Switches ANSI C37.47-2000 – American National Standard for High Voltage Current Limiting Type Distribution Class Fuses and Fuse Disconnecting Switches
■
GENERAL PURPOSE FULL RANGE i
i hr.
Interrupting Current Figure 13-14. Fuse Types Protection Range
For more information visit: www.eaton.com
i min.
i max.
13
13-40
Power Breakers, Contactors & Fuses Expulsion Fuses February 2007
Product Description
Fuse Types
General Fuse Component Terms
There are three current limiting fuse types: Backup, General Purpose and Full Range. It is important that the user have an understanding of these definitions to ensure proper application of the fuse (Figure 13-14).
Replaceable Fuse Unit: A replaceable fuse unit is a phrase used to describe a fuse that does not have a separate holder and refill assembly. In a replaceable fuse unit, the fuse is its own holder and is completely replaced after interruption.
Backup Fuses: A fuse capable of interrupting all currents from the maximum rated interrupting current down to the rated minimum interrupting current. Backup fuses are always used in a series with another interrupting device capable of interrupting currents below the fuse’s minimum interrupting current. General Purpose Fuses: A fuse capable of interrupting all currents from the rated interrupting current down to the current that causes melting of the fusible element in no less than one hour. General Purpose fuses are typically used to protect feeders and components such as transformers.
13
Full Range Fuses: A fuse capable of interrupting all currents from the rated interrupting current down to the minimum continuous current that causes melting of the fusible element, with the fuse applied at the maximum ambient temperature specified by the manufacturer.
Mounting: A mounting provides all the necessary parts to safely mount a fuse in its intended piece of equipment. The base is the metal support to which all other pieces attach. Insulators attach to the base and insulate the live fuse unit from the base and everything beyond the base. Live parts are the parts of the mounting that are energized once electricity is flowing. The live parts provide the means to hold the fuse unit in place, electrical contact, and a place to make line and load connections. Non-Disconnect Mounting: A nondisconnect mounting does not provide a means for removing the fuse unit until the circuit is dead and the fuse unit can be removed manually. The fuse unit is held in place by friction through the use of fuse clips or by a cross bar.
For more information visit: www.eaton.com
Disconnect Mounting: The disconnect mounting allows the fuse unit to be removed (off load) using an insulated hook stick. The hookstick grabs a pull ring and disconnects the fuse unit, which may then be lifted out of its mounting. Live Parts: Live parts were briefly discussed as part of the “Mounting” definition. Everything above the insulators on the mounting excluding the fuse unit, fuse holder, and the fuse end fittings (if required) are considered the live parts. Fuse end fittings are discussed next and are not required with non-disconnect live parts, but are required and included with disconnect live parts. Live parts may be sold separately as replacement parts or for new OEM applications. End Fittings: End fittings are metal parts that attach to each end of a fuse unit’s ferrules (end caps). As previously mentioned, they are used solely with disconnect fuse applications or when converting a non-disconnect to a disconnect fuse configuration. When end fittings are ordered, a fitting for each end of the fuse is included. Keep in mind that end fittings can become damaged in use and, therefore, are sold separately from the live parts when necessary. It is not necessary to purchase an entire set of live parts when only the end fittings are required.
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-41
February 2007
Product Selection
Expulsion Fuse
Table 13-28. Expulsion Fuse Units Catalog Numbering System
DBU 17 - 100 E
Easy to Use, Easy to Order! Eaton’s Cutler-Hammer fuse catalog numbering system makes it easy to order the right fuse. The catalog numbers are easy to remember, unique to each fuse, and are broken down in three descriptive segments: Fuse Type, Voltage Rating and Current Rating. These Catalog Numbers can be entered directly and easily:
Type
Maximum kV
RBA DBU DBA RDB RBT BA
8 15 17 25 27 38 48 72 92 121 145
■
No change in order processing will occur if you use either a style number or its corresponding catalog number. You will get the same fuse. ■ In the back of this ordering guide is a style number to catalog number cross-reference chart.
Amperes .5 3 5 7 10 15 20 25 30 40
50 65 80 100 125 150 200 250 300 400
Speed E K SE
Table 13-29. Expulsion Fuse Accessories Catalog Numbering System
15 RBA2 - P NM C
Examples: 8RBA2-10E
8.3 max. kV, RBA-200 refill, 10E amperes
DBU17-30K
17.1 max. kV, DBU fuse unit, 30 amperes
15RBA8-INH
15.5 max. kV, RBA-800, indicating nondisconnect holder
RBA4-FLTR
RBA-400 filter
Maximum kV
Type
8 15 17 25 27 38 48 72 92 121 145
RBA DBU DBA RDB RBT BA
Diameter Size
Insulator
A = 1-5/8 Inch 0.5E – 1.5E, Single Barrel B = 1-5/8 Inch 3E – 10E, Single Barrel C = 2-Inch Single Barrel D = 3-Inch Single Barrel E = 3-Inch Double Barrel F = 4-Inch Double Barrel G = 5/8 Inch Ferrule
G = Glass Polyester P = Porcelain H = High BIL
Hardware UM = VM = DL = NL = DH = NH = NM = UL = VL = I = O = V = M = VO = MO = FLTR = COND = MFLR = SHNT =
CA08101001E
For more information visit: www.eaton.com
Underhung Mounting Vertical Mounting Disconnect Live Parts Nondisconnect Live Parts Disconnect Holder Nondisconnect Holder Nondisconnect Mounting Underhung Live Parts Vertical Live Parts Indicating Outdoor Vented Muffled Vented Outdoor Muffled Outdoor Filter Condenser Muffler Shunt and Spring Assembly
13
Power Breakers, Contactors & Fuses Expulsion Fuses
13-42
February 2007
Type RBA
RBA/RBT Refill Units
Catalog Number
Catalog Number
Catalog Number
Spring and Shunt Assy.
Catalog Number
Catalog Number
BIL
Maximum
Glass Polyester
Fuse Filters and Condensers
8RBA2-65E 8RBA2-80E 8RBA2-100E 8RBA2-125E 8RBA2-150E 8RBA2-200E
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
8RBT2-65E 8RBT2-80E 8RBT2-100E 8RBT2-125E 8RBT2-150E 8RBT2-200E
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11) (10,11)
8.3 kV Maximum (7.2 kV Nominal) 800 Ampere (2)8RBT4-250E (12) (2)8RBT4-300E (12) (2)8RBT4-400E (12)
8RBA4-SHNT
8RBT4-40E 8RBT4-50E 8RBT4-65E 8RBT4-80E 8RBT4-100E 8RBT4-125E 8RBT4-150E 8RBT4-200E 8RBT4-250E 8RBT4-300E 8RBT4-400E
4.8 5.5 60 5RBA4-PDM 5RBA4-GDM 14RBA4-DL 7.2 8.3 75 8RBA4-PDM 8RBA4-GDM
8.3 kV Maximum (7.2 kV Nominal) 800 Ampere (For Use with 8RBA8 Fuseholders)
4.8 5.5 60 5RBA8-PNM 5RBA8-GNM 15RBA8-NL (2)RBA4-FLTR (2)RBA4-COND 7.2 8.3 75 8RBA8-PNM 8RBA8-GNM
8RBA8-SHNT
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
8RBA4-INH
8RBA4-40E 8RBA4-50E 8RBA4-65E 8RBA4-80E 8RBA4-100E 8RBA4-125E 8RBA4-150E 8RBA4-200E 8RBA4-250E 8RBA4-300E 8RBA4-400E
BRBA2-IDH
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E 400E
4.8 5.5 60 5RBA4-PNM 5RBA4-GNM 15RBA4-NL RBA4-FLTR 7.2 8.3 75 8RBA4-PNM 8RBA4-GNM RBA4-COND
8RBA8-INH
— — — — — — (7,8) (7,8) (7,8)
.5E to 400E
— — — — — — 8RBT4-20E 8RBT4-25E 8RBT4-30E
Disconnect 8RBA4-DH
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
450E to 720E Non-Disconnect 8RBA8-NH
8RBA4-.5E 8RBA4-3E 8RBA4-5E 8RBA4-7E 8RBA4-10E 8RBA4-15E 8RBA4-20E 8RBA4-25E 8RBA4-30E
2.1 (.95)
.5E 3E 5E 7E 10E 15E 20E 25E 30E
450E (2)8RBA4-250E (9) 540E (2)8RBA4-300E (9) 720E (2)8RBA4-400E (9)
4.8 5.5 60 5RBA2-PDM 5RBA2-GDM 14RBA2-DL 7.2 8.3 75 8RBA2-PDM 8RBA2-GDM
8.3 kV Maximum (7.2 kV Nominal) 400 Ampere (For Use with 8RBA4 Fuseholders) Non-Disconnect 8RBA4-NH
8.3 kV Maximum (7.2 kV Nominal) 400 Ampere
4.8 5.5 60 5RBA2-PNM 5RBA2-GNM 15RBA2-NL RBA2-FLTR 7.2 8.3 75 8RBA2-PNM 8RBA2-GNM RBA2-COND 8RBA2-SHNT
65E 80E 100E 125E 150E 200E
8RBA2-INH
— — (3,4) (3,4) (3,4) (3,4) (3,4)
BRBA2-IDH
— — 8RBT2-20E 8RBT2-25E 8RBT2-30E 8RBT2-40E 8RBT2-50E
10E to 200E Disconnect Non-Disconnect 8RBA2-DH 8RBA2-NH
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
1.0 (.45)
8RBA2-10E 8RBA2-15E 8RBA2-20E 8RBA2-25E 8RBA2-30E 8RBA2-40E 8RBA2-50E
Porcelain Insulator
Live Parts
8.3 kV Maximum (7.2 kV Nominal) 200 Ampere (For Use with 8RBA2 Fuseholders)
10E 15E 20E 25E 30E 40E 50E
Mounting (including Live Parts less Holder)
RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Indoor or Enclosure Applications)
8.3 kV Maximum (7.2 kV Nominal) 200 Ampere
13
Nominal
Curve Reference 36-635
Ampere Rating
Curve Reference 36-635
Catalog Number
Catalog Number
Fuse- Voltage holder (kV)
Indicating Catalog Number
Time Lag (Fuse Refills)
Ampere Rating Style Non-Indicating Catalog Number
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs. (kg)
Table 13-30. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure
Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 8.3 kV fuse, order 2 pieces of an 8RBA4-400E. Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-43
February 2007
Type RBA
RBA/RBT Refill Units
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Glass Polyester
BIL
Maximum
Nominal
Indicating Catalog Number
Porcelain Insulator
Spring and Shunt Assy.
15RBA2-SHNT
15RBA2-NL 38RBA2-DL 15RBA4-NL 15RBA4-DL
15RBA4-SHNT
14RBA4-GNM 14RBA4-GDM
15RBA4-INH
13.8 15.5 95 14RBA8-PNM 13.8 15.5 110 15RBA8-PNM
(2)RBA4-FLTR (2)RBA4-COND
15RBA8-SHNT
15.5 kV Maximum (14.4 kV Nominal) 800 Ampere (For Use with 15RBA8 Fuseholders) 15RBA8-NL
(2)15RBT4-250E (12) (2)15RBT4-300E (12) (2)15RBT4-400E (12)
RBA4-FLTR RBA4-COND
13.8 15.5 95 14RBA4-PDM 13.8 15.5 110 15RBA4-PDM
14RBA8-GNM
15.5 kV Maximum (14.4 kV Nominal) 800 Ampere
13.8 15.5 95 14RBA4-PNM 13.8 15.5 110 15RBA4-PNM
15RBA4-IDH
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11) (10,11)
15RBA8-INH
15RBT4-40E 15RBT4-50E 15RBT4-65E 15RBT4-80E 15RBT4-100E 15RBT4-125E 15RBT4-150E 15RBT4-200E 15RBT4-250E 15RBT4-300E 15RBT4-400E
15RBA4-NH
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
15RBA4-DH
15RBA4-40E 15RBA4-50E 15RBA4-65E 15RBA4-80E 15RBA4-100E 15RBA4-125E 15RBA4-150E 15RBA4-200E 15RBA4-250E 15RBA4-300E 15RBA4-400E
15RBA8-NH
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E 400E
.5E to 400E
— — — — — — (7,8) (7,8) (7,8)
Disconnect
— — — — — — 15RBT4-20E 15RBT4-25E 15RBT4-30E
450E to 720E
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
Non-Disconnect
15RBA4-.5E 15RBA4-3E 15RBA4-5E 15RBA4-7E 15RBA4-10E 15RBA4-15E 15RBA4-20E 15RBA4-25E 15RBA4-30E
2.3 (1.0)
.5E 3E 5E 7E 10E 15E 20E 25E 30E
450E (2)15RBA4-250E (9) 540E (2)15RBA4-300E (9) 720E (2)15RBA4-400E (9)
RBA2-FLTR RBA2-COND
15.5 kV Maximum (14.4 kV Nominal) 400 Ampere (For Use with 15RBA4 Fuseholders) Non-Disconnect
15.5 kV Maximum (14.4 kV Nominal) 400 Ampere
13.8 15.5 95 14RBA2-PDM 13.8 15.5 110 15RBA2-PDM
14RBA2-GNM
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
13.8 15.5 95 14RBA2-PNM 13.8 15.5 110 15RBA2-PNM
14RBA2-GDM
15RBT2-65E 15RBT2-80E 15RBT2-100E 15RBT2-125E 15RBT2-150E 15RBT2-200E
15RBA2-INH
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
15RBA2-IDH
15RBA2-65E 15RBA2-80E 15RBA2-100E 15RBA2-125E 15RBA2-150E 15RBA2-200E
15RBA2-NH
65E 80E 100E 125E 150E 200E
15RBA2-DH
— — (3,4) (3,4) (3,4) (3,4) (3,4)
Non-Disconnect
— — 15RBT2-20E 15RBT2-25E 15RBT2-30E 15RBT2-40E 15RBT2-50E
10E to 200E
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
Disconnect
15RBA2-10E 15RBA2-15E 15RBA2-20E 15RBA2-25E 15RBA2-30E 15RBA2-40E 15RBA2-50E
1.1 (.5)
15.5 kV Maximum (14.4 kV Nominal) 200 Ampere (For Use with 15RBA2 Fuseholders)
10E 15E 20E 25E 30E 40E 50E
Mounting (including Live Live Fuse Filters and Parts less Holder) Parts Condensers
RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Indoor or Enclosure Applications)
15.5 kV Maximum (14.4 kV Nominal) 200 Ampere
Non-Indicating Catalog Number
Curve Reference 36-635
Ampere Rating
Curve Reference 36-635
Catalog Number
Catalog Number
Fuse- Voltage (kV) holder
Style
Time Lag (Fuse Refills)
Ampere Rating
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs. (kg)
Table 13-31. Type RBA Expulsion Fuses for Use Outdoors
Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 15 kV fuse, order 2 pieces of an 8RBA4-400E. Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Expulsion Fuses
13-44
February 2007
Type RBA
RBA/RBT Refill Units
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
BIL
Maximum
Nominal
Indicating Catalog Number
Glass Polyester
25RBA2-SHNT
38RBA2-NL
25.5 kV Maximum (23.0 kV Nominal) 400 Ampere (For Use with 25RBA4 Fuseholders)
38RBA4-NL
25RBA4-INH
38RBA4-DL
25RBA4-IDH
23.0 25.5 150 25RBA8-PNM —
(2)RBA4-FLTR (2)RBA4-COND
25RBA8-SHNT
25.5 kV Maximum (23.0 kV Nominal) 800 Ampere (For Use with 25RBA8 Fuseholders) 38RBA8-NL
25.5 kV Maximum (23.0 kV Nominal) 800 Ampere (2)25RBT4-250E (12) (2)25RBT4-300E (12)
RBA4-FLTR RBA4-COND
23.0 25.5 150 25RBA4-PDM —
25RBA8-INH
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11)
25RBA4-NH
25RBT4-40E 25RBT4-50E 25RBT4-65E 25RBT4-80E 25RBT4-100E 25RBT4-125E 25RBT4-150E 25RBT4-200E 25RBT4-250E 25RBT4-300E
25RBA4-DH
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
25RBA8-NH
25RBA4-40E 25RBA4-50E 25RBA4-65E 25RBA4-80E 25RBA4-100E 25RBA4-125E 25RBA4-150E 25RBA4-200E 25RBA4-250E 25RBA4-300E
.5E to 300E
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E
23.0 25.5 150 25RBA4-PNM — Non-Disconnect
— — — — — — (7,8) (7,8) (7,8)
Disconnect
— — — — — — 25RBT4-20E 25RBT4-25E 25RBT4-30E
450E to 540E
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
Non-Disconnect
25RBA4-.5E 25RBA4-3E 25RBA4-5E 25RBA4-7E 25RBA4-10E 25RBA4-15E 25RBA4-20E 25RBA4-25E 25RBA4-30E
2.7 (1.2)
.5E 3E 5E 7E 10E 15E 20E 25E 30E
450E (2)25RBA4-250E (9) 540E (2)25RBA4-300E (9)
23.0 25.5 150 25RBA2-PDM —
RBA2-FLTR RBA2-COND
25RBA4-SHNT
25.5 kV Maximum (23.0 kV Nominal) 400 Ampere
23.0 25.5 150 25RBA2-PNM —
38RBA2-DL
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
25RBA2-INH
25RBT2-65E 25RBT2-80E 25RBT2-100E 25RBT2-125E 25RBT2-150E 25RBT2-200E
25RBA2-IDH
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
25RBA2-NH
25RBA2-65E 25RBA2-80E 25RBA2-100E 25RBA2-125E 25RBA2-150E 25RBA2-200E
25RBA2-DH
65E 80E 100E 125E 150E 200E
Non-Disconnect
— — (3,4) (3,4) (3,4) (3,4) (3,4)
10E to 200E
— — 25RBT2-20E 25RBT2-25E 25RBT2-30E 25RBT2-40E 25RBT2-50E
Disconnect
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
1.3 (.6)
25RBA2-10E 25RBA2-15E 25RBA2-20E 25RBA2-25E 25RBA2-30E 25RBA2-40E 25RBA2-50E
Porcelain Insulator
Spring and Shunt Assy.
25.5 kV Maximum (23.0 kV Nominal) 200 Ampere (For Use with 25RBA2 Fuseholders)
10E 15E 20E 25E 30E 40E 50E
Mounting (including Live Live Fuse Filters and Parts less Holder) Parts Condensers
RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Indoor or Enclosure Applications)
25.5 kV Maximum (23.0 kV Nominal) 200 Ampere
13
Non-Indicating Catalog Number
Curve Reference 36-635
Ampere Rating
Curve Reference 36-635
Catalog Number
Catalog Number
Fuse- Voltage (kV) holder
Style
Time Lag (Fuse Refills)
Ampere Rating
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs (kg)
Table 13-32. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure
Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 25 kV fuse, order 2 pieces of an 8RBA4-400E. Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-45
February 2007
Type RBA
RBA/RBT Refill Units
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Glass Polyester
BIL
Maximum
Porcelain Insulator
Spring and Shunt Assy.
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
38RBT2-65E 38RBT2-80E 38RBT2-100E 38RBT2-125E 38RBT2-150E 38RBT2-200E
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
38.0 kV Maximum (34.5 kV Nominal) 400 Ampere (For Use with 38RBA4 Fuseholders)
450E (2)38RBA4-250E (9) 540E (2)38RBA4-300E (9)
(2)38RBT4-250E (12) (2)38RBT4-300E (12)
34.5 38.0 150 38RBA4-PDM —
38.0 kV Maximum (34.5 kV Nominal) 800 Ampere (For Use with 38RBA8 Fuseholders)
34.5 38.0 150 38RBA8-PNM —
(2)RBA4-FLTR (2)RBA4-COND
38RBA8-SHNT
38.0 kV Maximum (34.5 kV Nominal) 800 Ampere
38RBA4-NL
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11)
38RBA4-DL
38RBT4-40E 38RBT4-50E 38RBT4-65E 38RBT4-80E 38RBT4-100E 38RBT4-125E 38RBT4-150E 38RBT4-200E 38RBT4-250E 38RBT4-300E
RBA4-FLTR RBA4-COND
38RBA8-NL
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
38RBA4-INH
38RBA4-40E 38RBA4-50E 38RBA4-65E 38RBA4-80E 38RBA4-100E 38RBA4-125E 38RBA4-150E 38RBA4-200E 38RBA4-250E 38RBA4-300E
38RBA4-IDH
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E
34.5 38.0 150 38RBA4-PNM —
38RBA8-INH
— — — — — — (7,8) (7,8) (7,8)
.5E to 300E Non-Disconnect 38RBA4-NH
— — — — — — 38RBT4-20E 38RBT4-25E 38RBT4-30E
Disconnect 38RBA4-DH
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
450E to 540E Non-Disconnect 38RBA8-NH
38RBA4-.5E 38RBA4-3E 38RBA4-5E 38RBA4-7E 38RBA4-10E 38RBA4-15E 38RBA4-20E 38RBA4-25E 38RBA4-30E
3.1 (1.4)
.5E 3E 5E 7E 10E 15E 20E 25E 30E
38RBA4-SHNT
38.0 kV Maximum (34.5 kV Nominal) 400 Ampere
34.5 38.0 150 38RBA2-PDM —
RBA2-FLTR RBA2-COND 38RBA2-SHNT
38RBA2-65E 38RBA2-80E 38RBA2-100E 38RBA2-125E 38RBA2-150E 38RBA2-200E
38RBA2-NL
65E 80E 100E 125E 150E 200E
34.5 38.0 150 38RBA2-PNM —
38RBA2-DL
— — (3,4) (3,4) (3,4) (3,4) (3,4)
38RBA2-INH
— — 38RBT2-20E 38RBT2-25E 38RBT2-30E 38RBT2-40E 38RBT2-50E
38RBA2-IDH
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
10E to 200E Disconnect Non-Disconnect 38RBA2-DH 38RBA2-NH
38RBA2-10E 38RBA2-15E 38RBA2-20E 38RBA2-25E 38RBA2-30E 38RBA2-40E 38RBA2-50E
1.4 (.6)
38.0 kV Maximum (34.5 kV Nominal) 200 Ampere (For Use with 38RBA2 Fuseholders)
10E 15E 20E 25E 30E 40E 50E
Mounting (including Live Live Fuse Filters and Parts less Holder) Parts Condensers
RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Indoor or Enclosure Applications)
38.0 kV Maximum (34.5 kV Nominal) 200 Ampere
Nominal
Curve Reference 36-635
Ampere Rating
Curve Reference 36-635
Catalog Number
Catalog Number
Fuse- Voltage (kV) holder
Indicating Catalog Number
Time Lag (Fuse Refills)
Ampere Rating Style Non-Indicating Catalog Number
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs (kg)
Table 13-32. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure (Continued)
Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 38 kV fuse, order 2 pieces of an 8RBA4-400E. Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Expulsion Fuses
13-46
February 2007
Types RBA and RDB
— — (3,4) (3,4) (3,4) (3,4) (3,4)
65E 80E 100E 125E 150E 200E
8RBA2-65E 8RBA2-80E 8RBA2-100E 8RBA2-125E 8RBA2-150E 8RBA2-200E
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
8RBT2-65E 8RBT2-80E 8RBT2-100E 8RBT2-125E 8RBT2-150E 8RBT2-200E
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
Vertical
Underhung
Catalog Number
BIL
Maximum
Nominal
Catalog Number
Underhung (90°) Mounting
8.3 95 8RDB2-VM
8RDB2-UM
7.2
8.3 95 8RDB2-HVM 8RDB2-HUM
RDB2-VL RDB2-UL
— — — — — — (7,8) (7,8) (7,8)
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E 400E
8RBA4-40E 8RBA4-50E 8RBA4-65E 8RBA4-80E 8RBA4-100E 8RBA4-125E 8RBA4-150E 8RBA4-200E 8RBA4-250E 8RBA4-300E 8RBA4-400E
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
8RBT4-40E 8RBT4-50E 8RBT4-65E 8RBT4-80E 8RBT4-100E 8RBT4-125E 8RBT4-150E 8RBT4-200E 8RBT4-250E 8RBT4-300E 8RBT4-400E
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11) (10,11)
8.3 95 8RDB4-VM
8RDB4-UM
7.2
8.3 95 8RDB4-HVM 8RDB4-HUM
RDB4-VL RDB4-UL
(12) (12) (12)
7.2
8.3 95 8RDB8-VM
8RDB8-UM
7.2
8.3 95 8RDB8-HVM 8RDB8-HUM
RDB8-VL RDB8-UL
8RDB8-SHNT
(2)8RBT4-250E (2)8RBT4-300E (2)8RBT4-400E
8RDB8-NH
8.3 kV Maximum (7.2 kV Nominal) 800 Ampere Disconnect
8.3 kV Maximum (7.2 kV Nominal) 800 Ampere
7.2
8RDB4-SHNT
— — — — — — 8RBT4-20E 8RBT4-25E 8RBT4-30E
8RDB4-DH
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
.5E to 400E
8RBA4-.5E 8RBA4-3E 8RBA4-5E 8RBA4-7E 8RBA4-10E 8RBA4-15E 8RBA4-20E 8RBA4-25E 8RBA4-30E
Disconnect
.5E 3E 5E 7E 10E 15E 20E 25E 30E
(9) (9) (9)
7.2
8.3 kV Maximum (7.2 kV Nominal) 400 Ampere
2.1 (.95)
8.3 kV Maximum (7.2 kV Nominal) 400 Ampere
Catalog Number
8RDB2-SHNT
— — 8RBT2-20E 8RBT2-25E 8RBT2-30E 8RBT2-40E 8RBT2-50E
8RDB2-DH
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
Disconnect
8RBA2-10E 8RBA2-15E 8RBA2-20E 8RBA2-25E 8RBA2-30E 8RBA2-40E 8RBA2-50E
10E to 200E
10E 15E 20E 25E 30E 40E 50E
(2)8RBA4-250E (2)8RBA4-300E (2)8RBA4-400E
Catalog Number
Spring and Shunt Assy.
8.3 kV Maximum (7.2 kV Nominal) 200 Ampere
1.0 (.45)
8.3 kV Maximum (7.2 kV Nominal) 200 Ampere
450E 540E 720E
Live Parts
RBD Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Outdoor Applications)
450E to 720E
Ampere Rating RBA/RBT Refill Units
13
Mounting (including Live Parts less Holder)
Vertical (180°) Mounting
Style
Catalog Number
Fuse- Voltage (kV) holder
Ampere Rating
Catalog Number
Curve Reference 36-635
Time Lag (Fuse Refills)
Curve Reference 36-635
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs (kg)
Table 13-33. Type RDB Expulsion Fuses for Use Outdoors
Requires two fuse refills as shown. Price each refill individually.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-47
February 2007
Types RBA and RDB
Catalog Number
Catalog Number Vertical
Underhung
Catalog Number
BIL
Maximum
Nominal
Catalog Number
Underhung (90°) Mounting
Spring and Shunt Assy.
15.5 kV Maximum (14.4 kV Nominal) 200 Ampere — — (3,4) (3,4) (3,4) (3,4) (3,4)
65E 80E 100E 125E 150E 200E
15RBA2-65E 15RBA2-80E 15RBA2-100E 15RBA2-125E 15RBA2-150E 15RBA2-200E
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
15RBT2-65E 15RBT2-80E 15RBT2-100E 15RBT2-125E 15RBT2-150E 15RBT2-200E
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
13.8 15.5 110 15RDB2-VM
13.8 15.5 150 15RDB2-HVM 15RDB2-HUM
13.8 15.5 110 15RDB4-VM
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E 400E
15RBA4-40E 15RBA4-50E 15RBA4-65E 15RBA4-80E 15RBA4-100E 15RBA4-125E 15RBA4-150E 15RBA4-200E 15RBA4-250E 15RBA4-300E 15RBA4-400E
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
15RBT4-40E 15RBT4-50E 15RBT4-65E 15RBT4-80E 15RBT4-100E 15RBT4-125E 15RBT4-150E 15RBT4-200E 15RBT4-250E 15RBT4-300E 15RBT4-400E
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11) (10,11)
15RDB4-UM
RDB4-VL RDB4-UL
13.8 15.5 150 15RDB4-HVM 15RDB4-HUM
13.8 15.5 110 15RDB8-VM
15RDB8-UM
13.8 15.5 150 15RDB8-HVM 15RDB8-HUM
RDB8-VL RDB8-UL
15RDB8-SHNT
(12) (12) (12)
15RDB8-NH
15.5 kV Maximum (14.4 kV Nominal) 800 Ampere Disconnect
15.5 kV Maximum (14.4 kV Nominal) 800 Ampere
15RDB4-DH
— — — — — — (7,8) (7,8) (7,8)
.5E to 400E
— — — — — — 15RBT4-20E 15RBT4-25E 15RBT4-30E
Disconnect
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
2.3 (1.0)
15RBA4-.5E 15RBA4-3E 15RBA4-5E 15RBA4-7E 15RBA4-10E 15RBA4-15E 15RBA4-20E 15RBA4-25E 15RBA4-30E
(2)15RBT4-250E (2)15RBT4-300E (2)15RBT4-400E
RDB2-VL RDB2-UL
15.5 kV Maximum (14.4 kV Nominal) 400 Ampere
.5E 3E 5E 7E 10E 15E 20E 25E 30E
450E (2)15RBA4-250E (9) 540E (2)15RBA4-300E (9) 720E (2)15RBA4-400E (9)
15RDB2-UM
15RDB4-SHNT
15.5 kV Maximum (14.4 kV Nominal) 400 Ampere
15RDB2-DH
— — 15RBT2-20E 15RBT2-25E 15RBT2-30E 15RBT2-40E 15RBT2-50E
Disconnect
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
10E to 200E
15RBA2-10E 15RBA2-15E 15RBA2-20E 15RBA2-25E 15RBA2-30E 15RBA2-40E 15RBA2-50E
1.1 (.50)
10E 15E 20E 25E 30E 40E 50E
15RDB2-SHNT
15.5 kV Maximum (14.4 kV Nominal) 200 Ampere
Live Parts
RDB Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Outdoor Applications)
450E to 720E
Ampere Rating RBA/RBT Refill Units
Mounting (including Live Parts less Holder)
Vertical (180°) Mounting
Style
Catalog Number
Fuse- Voltage (kV) holder
Ampere Rating
Catalog Number
Curve Reference 36-635
Time Lag (Fuse Refills)
Curve Reference 36-635
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs (kg)
Table 13-33. Type RDB Expulsion Fuses for Use Outdoors (Continued)
Requires two fuse refills as shown. Price each refill individually.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Expulsion Fuses
13-48
February 2007
Types RBA and RDB
Catalog Number Vertical
Underhung
Catalog Number
BIL
Maximum
Nominal
Catalog Number
Underhung (90°) Mounting
25.5 kV Maximum (23.0 kV Nominal) 200 Ampere — — (3,4) (3,4) (3,4) (3,4) (3,4)
65E 80E 100E 125E 150E 200E
25RBA2-65E 25RBA2-80E 25RBA2-100E 25RBA2-125E 25RBA2-150E 25RBA2-200E
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
25RBT2-65E 25RBT2-80E 25RBT2-100E 25RBT2-125E 25RBT2-150E 25RBT2-200E
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
23.0 25.5 150 25RDB2-VM
RDB2-VL RDB2-UL
23.0 25.5 200 25RDB2-HVM 25RDB2-HUM
25.5 kV Maximum (23.0 kV Nominal) 400 Ampere
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
25RBT4-40E 25RBT4-50E 25RBT4-65E 25RBT4-80E 25RBT4-100E 25RBT4-125E 25RBT4-150E 25RBT4-200E 25RBT4-250E 25RBT4-300E
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11)
25.5 kV Maximum (23.0 kV Nominal) 800 Ampere (2)25RBT4-250E (12) (2)25RBT4-300E (12)
25RDB4-UM
RDB4-VL RDB4-UL
23.0 25.5 200 25RDB4-HVM 25RDB4-HUM
25.5 kV Maximum (23.0 kV Nominal) 800 Ampere
23.0 25.5 150 25RDB8-VM
25RDB8-UM
23.0 25.5 200 25RDB8-HVM 25RDB8-HUM
RDB8-VL RDB8-UL
25RDB8-SHNT
25RBA4-40E 25RBA4-50E 25RBA4-65E 25RBA4-80E 25RBA4-100E 25RBA4-125E 25RBA4-150E 25RBA4-200E 25RBA4-250E 25RBA4-300E
25RDB4-DH
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E
23.0 25.5 150 25RDB4-VM
25RDB8-NH
— — — — — — (7,8) (7,8) (7,8)
.5E to 300E
— — — — — — 25RBT4-20E 25RBT4-25E 25RBT4-30E
Disconnect
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
Disconnect
25RBA4-.5E 25RBA4-3E 25RBA4-5E 25RBA4-7E 25RBA4-10E 25RBA4-15E 25RBA4-20E 25RBA4-25E 25RBA4-30E
2.7 (1.2)
.5E 3E 5E 7E 10E 15E 20E 25E 30E
450E (2)25RBA4-250E (9) 540E (2)25RBA4-300E (9)
25RDB2-UM
25RDB4-SHNT
25.5 kV Maximum (23.0 kV Nominal) 400 Ampere
25RDB2-DH
— — 25RBT2-20E 25RBT2-25E 25RBT2-30E 25RBT2-40E 25RBT2-50E
Disconnect
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
10E to 200E
25RBA2-10E 25RBA2-15E 25RBA2-20E 25RBA2-25E 25RBA2-30E 25RBA2-40E 25RBA2-50E
1.3 (.6)
10E 15E 20E 25E 30E 40E 50E
Catalog Number
Spring and Shunt Assy.
25RDB2-SHNT
25.5 kV Maximum (23.0 kV Nominal) 200 Ampere
13
Live Parts
RDB Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Outdoor Applications)
450E to 540E
Ampere Rating RBA/RBT Refill Units
Mounting (including Live Parts less Holder)
Vertical (180°) Mounting
Style
Catalog Number
Fuse- Voltage (kV) holder
Ampere Rating
Catalog Number
Curve Reference 36-635
Time Lag (Fuse Refills)
Curve Reference 36-635
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs (kg)
Table 13-33. Type RDB Expulsion Fuses for Use Outdoors (Continued)
Requires two fuse refills as shown. Price each refill individually.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-49
February 2007
Types RBA and RDB
Catalog Number
Catalog Number Vertical
Underhung
Catalog Number
BIL
Maximum
Nominal
Catalog Number
Underhung (90°) Mounting
Spring and Shunt Assy.
38.0 kV Maximum (34.5 kV Nominal) 200 Ampere — — (3,4) (3,4) (3,4) (3,4) (3,4)
65E 80E 100E 125E 150E 200E
38RBA2-65E 38RBA2-80E 38RBA2-100E 38RBA2-125E 38RBA2-150E 38RBA2-200E
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
38RBT2-65E 38RBT2-80E 38RBT2-100E 38RBT2-125E 38RBT2-150E 38RBT2-200E
(3,4) (3,4) (3,4) (3,4) (3,4) (3,4)
34.5 38.0 200 38RDB2-VM
34.5 38.0 250 38RDB2-HVM 38RDB2-HUM
34.5 38.0 150 38RDB4-VM
40E 50E 65E 80E 100E 125E 150E 200E 250E 300E
38RBA4-40E 38RBA4-50E 38RBA4-65E 38RBA4-80E 38RBA4-100E 38RBA4-125E 38RBA4-150E 38RBA4-200E 38RBA4-250E 38RBA4-300E
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
38RBT4-40E 38RBT4-50E 38RBT4-65E 38RBT4-80E 38RBT4-100E 38RBT4-125E 38RBT4-150E 38RBT4-200E 38RBT4-250E 38RBT4-300E
(7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (7,8) (10,11) (10,11)
38RDB4-UM
RDB4-VL RDB4-UL
34.5 38.0 200 38RDB4-HVM 38RDB4-HUM
34.5 38.0 150 38RDB8-VM
38RDB8-UM
34.5 38.0 200 38RDB8-HVM 38RDB8-HUM
RDB8-VL RDB8-UL
38RDB8-SHNT
(12) (12)
38RDB8-NH
38.0 kV Maximum (34.5 kV Nominal) 800 Ampere Disconnect
38.0 kV Maximum (34.5 kV Nominal) 800 Ampere
38RDB4-DH
— — — — — — (7,8) (7,8) (7,8)
.5E to 300E
— — — — — — 38RBT4-20E 38RBT4-25E 38RBT4-30E
Disconnect
(5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6) (5,6)
3.1 (1.4)
38RBA4-.5E 38RBA4-3E 38RBA4-5E 38RBA4-7E 38RBA4-10E 38RBA4-15E 38RBA4-20E 38RBA4-25E 38RBA4-30E
(2)38RBT4-250E (2)38RBT4-300E
RDB2-VL RDB2-UL
38.0 kV Maximum (34.5 kV Nominal) 400 Ampere
.5E 3E 5E 7E 10E 15E 20E 25E 30E
450E (2)38RBA4-250E (9) 540E (2)38RBA4-300E (9)
38RDB2-UM
38RDB4-SHNT
38.0 kV Maximum (34.5 kV Nominal) 400 Ampere
38RDB2-DH
— — 38RBT2-20E 38RBT2-25E 38RBT2-30E 38RBT2-40E 38RBT2-50E
Disconnect
(1,2) (1,2) (1,2) (1,2) (1,2) (1,2) (1,2)
10E to 200E
38RBA2-10E 38RBA2-15E 38RBA2-20E 38RBA2-25E 38RBA2-30E 38RBA2-40E 38RBA2-50E
1.4 (.6)
10E 15E 20E 25E 30E 40E 50E
38RDB2-SHNT
38.0 kV Maximum (34.5 kV Nominal) 200 Ampere
Live Parts
RDB Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for Outdoor Applications)
450E to 540E
Ampere Rating RBA/RBT Refill Units
Mounting (including Live Parts less Holder)
Vertical (180°) Mounting
Style
Catalog Number
Fuse- Voltage (kV) holder
Ampere Rating
Catalog Number
Curve Reference 36-635
Time Lag (Fuse Refills)
Curve Reference 36-635
Standard Speed (Fuse Refills)
Approximate Shipping Weight. in Lbs (kg)
Table 13-34. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure
Requires two fuse refills as shown. Price each refill individually.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be substituted for the mounting if the user is supplying base support and insulators.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Expulsion Fuses
13-50
February 2007
Type DBU
Catalog Number
BIL
Maximum
Nominal
Style
Fuse Mounting
Ampere Rating
Catalog Number
End Fittings
Live Parts Only
Mounting (Includes Live Parts)
BIL
Maximum
Nominal
3K to 200K
DBU-EFOD
DBU17-NL DBU17-DL
DBU17-GNM DBU17-GDM
DBU-EFOD
5E to 200E
DBU-EFOD
DBU17-DL DBU17-NL DBU17-DL
DBU17-GDM
14.4 17.0 95
DBU17-GNM
DBU17-GDM
14.4 17.0 95
15SE to 200SE
DBU17-GNM
DBU17-NL
Style Non-Loadbreak
Disconnect Fuse Mounting
Ampere Rating
End Fittings
Catalog Number DBU-EFID
3K to 200K
Loadbreak 14.4 17.0 95
DBU17-80SE DBU17-100SE DBU17-125SE DBU17-150SE DBU17-175SE DBU17-200SE
Non-Loadbreak
80E 100E 125E 150E 175E 200E
10, 13 14
14.4 17.0 95
Loadbreak
DBU17-15SE DBU17-20SE DBU17-25SE DBU17-30SE DBU17-40SE DBU17-50SE DBU17-65SE
Voltage
14.4 17.0 95
14.4 17.0 95
Non-Loadbreak
15E 20E 25E 30E 40E 50E 65E
Catalog Number
Loadbreak
DBU17-40E DBU17-50E DBU17-65E DBU17-80E DBU17-100E DBU17-125E DBU17-150E DBU17-175E DBU17-200E
DBU-EFID
40E 50E 65E 80E 100E 125E 150E 175E 200E
11, 14 14
5E to 200E
DBU17-5E DBU17-7E DBU17-10E DBU17-13E DBU17-15E DBU17-20E DBU17-25E DBU17-30E
DBU-EFID
5E 7E 10E 13E 15E 20E 25E 30E
Outdoor Voltage
15SE to 200SE
DBU17-30K DBU17-40K DBU17-50K DBU17-65K DBU17-80K DBU17-100K DBU17-140K DBU17-200K
2.1 (.95)
30K 40K 50K 65K 80K 100K 140K 200K
Indoor
12, 15 14
2.1 (.95)
DBU17-3K DBU17-6K DBU17-8K DBU17-10K DBU17-12K DBU17-15K DBU17-20K DBU17-25K
2.1 (.95)
13
3K 6K 8K 10K 12K 15K 20K 25K
Approximate Shipping Weight. in Lbs (kg)
Catalog Number
Curve Reference 36-643
Ampere Rating
Maximum Interrupting Rating (kA Symm)
Table 13-35. Type DBU Expulsion Fuses for Use Indoors or Outdoors
To complete the Catalog Number, specify “-R” for right side cable termination or “-L” for left side cable termination.
Note: Muffler can be ordered separately. Order Catalog Number DBU-MFLR.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-51
February 2007
Type DBU
Catalog Number
BIL
Maximum
Nominal
Style
Ampere Rating
Fuse Mounting
Catalog Number
3K to 200K
DBU27-GNM
DBU27-NL
DBU27-GDM
DBU27-DL
Non-Loadbreak
3K to 200K
DBU-EFID
Loadbreak
13
DBU-EFOD
5E to 200E
DBU-EFOD
15SE to 200SE
DBU27-NL DBU27-DL
DBU27-GDM
DBU27-GNM
DBU27-NL DBU27-DL
25 27.0 125
DBU27-GNM
25 27.0 125
To complete the Catalog Number, specify “-R” for right side cable termination or “-L” for left side cable termination.
Note: Muffler can be ordered separately. Order Catalog Number DBU-MFLR.
CA08101001E
DBU-EFOD
End Fittings
Live Parts Only
Mounting (Includes Live Parts)
BIL
Maximum
Nominal
Style
Disconnect Fuse Mounting
Ampere Rating
Catalog Number
End Fittings
10, 16 12.5
DBU27-GDM
DBU27-100SE DBU27-125SE DBU27-150SE DBU27-175SE DBU27-200SE
Non-Loadbreak
100E 125E 150E 175E 200E
Loadbreak
DBU27-15SE DBU27-20SE DBU27-25SE DBU27-30SE DBU27-40SE DBU27-50SE DBU27-65SE DBU27-80SE
Non-Loadbreak
15E 20E 25E 30E 40E 50E 65E 80E
25 27.0 125
Loadbreak
DBU27-65E DBU27-80E DBU27-100E DBU27-125E DBU27-150E DBU27-175E DBU27-200E
Voltage
25 27.0 125
5E to 200E
65E 80E 100E 125E 150E 175E 200E
Catalog Number
25 27.0 125
11, 17 12.5
15SE to 200SE
DBU27-5E DBU27-7E DBU27-10E DBU27-13E DBU27-15E DBU27-20E DBU27-25E DBU27-30E DBU27-40E DBU27-50E
DBU-EFID
5E 7E 10E 13E 15E 20E 25E 30E 40E 50E
DBU-EFID
DBU27-40K DBU27-50K DBU27-65K DBU27-80K DBU27-100K DBU27-140K DBU27-200K
Outdoor Voltage
25 27.0 125
2.1 (.95)
40K 50K 65K 80K 100K 140K 200K
Indoor
12, 18 12.5
2.1 (.95)
DBU27-3K DBU27-6K DBU27-8K DBU27-10K DBU27-12K DBU27-15K DBU27-20K DBU27-25K DBU27-30K
2.1 (.95)
3K 6K 8K 10K 12K 15K 20K 25K 30K
Approximate Shipping Weight. in Lbs (kg)
Catalog Number
Curve Reference 36-643
Ampere Rating
Maximum Interrupting Rating (kA Symm)
Table 13-35. Type DBU Expulsion Fuses for Use Indoors or Outdoors (Continued)
For more information visit: www.eaton.com
13-52
Power Breakers, Contactors & Fuses Expulsion Fuses February 2007
Type DBU
Catalog Number
BIL
Maximum
Nominal
Style
Fuse Mounting
Ampere Rating
Catalog Number
End Fittings
Live Parts Only
Mounting (Include Live Parts)
BIL
Maximum
Nominal
3K to 200K
DBU-EFOD
DBU38-NL
DBU38-GNM
Style Non-Loadbreak
Disconnect Fuse Mounting
Ampere Rating
End Fittings
Catalog Number DBU-EFID
3K to 200K
Loadbreak
DBU-EFOD
5E to 200E 15SE to 200SE
DBU38-NL DBU38-NL
DBU-EFOD
DBU38-GNM DBU38-GNM
DBU38-100SE DBU38-125SE DBU38-150SE DBU38-175SE DBU38-200SE
Non-Loadbreak
100E 125E 150E 175E 200E
Loadbreak
DBU38-15SE DBU38-20SE DBU38-25SE DBU38-30SE DBU38-40SE DBU38-50SE DBU38-65SE DBU38-80SE
34.5 38.0 150
10, 16 10
Non-Loadbreak
15E 20E 25E 30E 40E 50E 65E 80E
34.5 38.0 150
34.5 38.0 150
34.5 38.0 150 Loadbreak
DBU38-65E DBU38-80E DBU38-100E DBU38-125E DBU38-150E DBU38-175E DBU38-200E
Voltage
34.5 38.0 150
5E to 200E
65E 80E 100E 125E 150E 175E 200E
Catalog Number
34.5 38.0 150
11, 17 10
15SE to 200SE
DBU38-5E DBU38-7E DBU38-10E DBU38-13E DBU38-15E DBU38-20E DBU38-25E DBU38-30E DBU38-40E DBU38-50E
DBU-EFID
5E 7E 10E 13E 15E 20E 25E 30E 40E 50E
Outdoor Voltage
DBU-EFID
DBU38-30K DBU38-40K DBU38-50K DBU38-65K DBU38-80K DBU38-100K DBU38-140K DBU38-200K
2.8 (1.3)
30K 40K 50K 65K 80K 100K 140K 200K
Indoor
12, 18 10
2.8 (1.3)
DBU38-3K DBU38-6K DBU38-8K DBU38-10K DBU38-12K DBU38-15K DBU38-20K DBU38-25K
2.1 (.95)
13
3K 6K 8K 10K 12K 15K 20K 25K
Approximate Shipping Weight. in Lbs (kg)
Catalog Number
Curve Reference 36-643
Ampere Rating
Maximum Interrupting Rating kA Sym.
Table 13-35. Type DBU Expulsion Fuses for Use Indoors or Outdoors (Continued)
Note: Muffler can be ordered separately. Order Catalog Number DBU-MFLR.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Expulsion Fuses
13-53
February 2007
Type DBA
Type DBA Expulsion Fuses for Use Indoors or Outdoors Table 13-36. Type DBA Expulsion Fuses for Use Indoors or Outdoors Ampere Rating
DBA-1 Fuse Units Catalog Number
Curve Reference 36-623
Approximate Shipping Weight Lbs. (kg)
Type DBA-1 Fuse Refills 8.3 kV Maximum (7.2 kV Nominal) 0.5E 3E 5E 7E 10E 15E 20E 25E 30E
8DBA1-.5E 8DBA1-3E 8DBA1-5E 8DBA1-7E 8DBA1-10E 8DBA1-15E 8DBA1-20E 8DBA1-25E 8DBA1-30E
40E 50E 65E 80E 100E 125E 150E 200E
8DBA1-40E 8DBA1-50E 8DBA1-65E 8DBA1-80E 8DBA1-100E 8DBA1-125E 8DBA1-150E 8DBA1-200E 15DBA1-.5E 15DBA1-3E 15DBA1-5E 15DBA1-7E 15DBA1-10E 15DBA1-15E 15DBA1-20E 15DBA1-25E 15DBA1-30E
40E 50E 65E 80E 100E 125E 150E 200E
15DBA1-40E 15DBA1-50E 15DBA1-65E 15DBA1-80E 15DBA1-100E 15DBA1-125E 15DBA1-150E 15DBA1-200E
(10, 11)
2.1 (.95)
25DBA1-.5E 25DBA1-3E 25DBA1-5E 25DBA1-7E 25DBA1-10E 25DBA1-15E 25DBA1-20E 25DBA1-25E 25DBA1-30E
40E 50E 65E 80E 100E 125E 150E 200E
25DBA1-40E 25DBA1-50E 25DBA1-65E 25DBA1-80E 25DBA1-100E 25DBA1-125E 25DBA1-150E 25DBA1-200E
CA08101001E
DBA-1 Fuse Units Catalog Number
Curve Reference 36-623
Approximate Shipping Weight Lbs. (kg)
0.5E 3E 5E 7E 10E 15E 20E 25E 30E
38DBA1-.5E 38DBA1-3E 38DBA1-5E 38DBA1-7E 38DBA1-10E 38DBA1-15E 38DBA1-20E 38DBA1-25E 38DBA1-30E
(10, 12)
4.2 (1.9)
40E 50E 65E 80E 100E 125E 150E 200E
38DBA1-40E 38DBA1-50E 38DBA1-65E 38DBA1-80E 38DBA1-100E 38DBA1-125E 38DBA1-150E 38DBA1-200E (10, 12)
4.2 (1.9)
48 kV Maximum (46 kV Nominal) (10, 11)
2.1 (.95)
25 kV Maximum (23 kV Nominal) 0.5E 3E 5E 7E 10E 15E 20E 25E 30E
Ampere Rating
Type DBA-1 Fuse Refills 38 kV Maximum (34.5 kV Nominal)
15.5 kV Maximum (14.4 kV Nominal) 0.5E 3E 5E 7E 10E 15E 20E 25E 30E
Type DBA Expulsion Fuses for Use Indoors or Outdoors (Continued)
0.5E 3E 5E 7E 10E 15E 20E 25E 30E
48DBA1-.5E 48DBA1-3E 48DBA1-5E 48DBA1-7E 48DBA1-10E 48DBA1-15E 48DBA1-20E 48DBA1-25E 48DBA1-30E
40E 50E 65E 80E 100E 125E 150E 200E
48DBA1-40E 48DBA1-50E 48DBA1-65E 48DBA1-80E 48DBA1-100E 48DBA1-125E 48DBA1-150E 48DBA1-200E
13
72 kV Maximum (69 kV Nominal) (10, 11)
2.1 (.95)
0.5E 3E 5E 7E 10E 15E 20E 25E 30E
72DBA1-.5E 72DBA1-3E 72DBA1-5E 72DBA1-7E 72DBA1-10E 72DBA1-15E 72DBA1-20E 72DBA1-25E 72DBA1-30E
40E 50E 65E 80E 100E 125E 150E 200E
72DBA1-40E 72DBA1-50E 72DBA1-65E 72DBA1-80E 72DBA1-100E 72DBA1-125E 72DBA1-150E 72DBA1-200E
For more information visit: www.eaton.com
(10, 12)
7.1 (3.2)
13-54
Power Breakers, Contactors & Fuses Expulsion Fuses February 2007
Type DBA Table 13-36. Type DBA Expulsion Fuses for Use Indoors or Outdoors (Continued) Ampere Rating
DBA-2 Fuse Units Catalog Number
Curve Reference 36-623
Type DBA Expulsion Fuses for Use Indoors or Outdoors (Continued) Approximate Shipping Weight Lbs. (kg)
Type DBA-2 Fuse Refills 38 kV Maximum (34.5 kV Nominal) 0.5E 3E 5E 7E 10E 15E 20E 25E 30E
38DBA2-.5E 38DBA2-3E 38DBA2-5E 38DBA2-7E 38DBA2-10E 38DBA2-15E 38DBA2-20E 38DBA2-25E 38DBA2-30E
40E 50E 65E 80E 100E 125E 150E 200E
38DBA2-40E 38DBA2-50E 38DBA2-65E 38DBA2-80E 38DBA2-100E 38DBA2-125E 38DBA2-150E 38DBA2-200E
13
48DBA2-.5E 48DBA2-3E 48DBA2-5E 48DBA2-7E 48DBA2-10E 48DBA2-15E 48DBA2-20E 48DBA2-25E 48DBA2-30E
40E 50E 65E 80E 100E 125E 150E 200E
48DBA2-40E 48DBA2-50E 48DBA2-65E 48DBA2-80E 48DBA2-100E 48DBA2-125E 48DBA2-150E 48DBA2-200E
(10, 12)
8 (3.6)
72DBA2-.5E 72DBA2-3E 72DBA2-5E 72DBA2-7E 72DBA2-10E 72DBA2-15E 72DBA2-20E 72DBA2-25E 72DBA2-30E
40E 50E 65E 80E 100E 125E 150E 200E
72DBA2-40E 72DBA2-50E 72DBA2-65E 72DBA2-80E 72DBA2-100E 72DBA2-125E 72DBA2-150E 72DBA2-200E
Catalog Number
Curve Reference 36-623
Approximate Shipping Weight Lbs. (kg)
0.5E 3E 5E 7E 10E 15E 20E 25E 30E
92DBA2-.5E 92DBA2-3E 92DBA2-5E 92DBA2-7E 92DBA2-10E 92DBA2-15E 92DBA2-20E 92DBA2-25E 92DBA2-30E
(10, 13)
16 (7.3)
40E 50E 65E 80E 100E 125E 150E 200E
92DBA2-40E 92DBA2-50E 92DBA2-65E 92DBA2-80E 92DBA2-100E 92DBA2-125E 92DBA2-150E 92DBA2-200E (10, 13)
15 (6.8)
(10, 13)
14 (6.4)
121 kV Maximum (115 kV Nominal) (10, 12)
8 (3.6)
72 kV Maximum (69 kV Nominal) 0.5E 3E 5E 7E 10E 15E 20E 25E 30E
DBA-2 Fuse Units
Type DBA-2 Fuse Refills 92 kV Maximum (92 kV Nominal)
48 kV Maximum (46 kV Nominal) 0.5E 3E 5E 7E 10E 15E 20E 25E 30E
Ampere Rating
0.5E 3E 5E 7E 10E 15E 20E 25E 30E
121DBA2-.5E 121DBA2-3E 121DBA2-5E 121DBA2-7E 121DBA2-10E 121DBA2-15E 121DBA2-20E 121DBA2-25E 121DBA2-30E
40E 50E 65E 80E 100E 125E 150E 200E
121DBA2-40E 121DBA2-50E 121DBA2-65E 121DBA2-80E 121DBA2-100E 121DBA2-125E 121DBA2-150E 121DBA2-200E
145 kV Maximum (138 kV Nominal) (10, 12)
16 (7.3)
0.5E 3E 5E 7E 10E 15E 20E 25E 30E
145DBA2-.5E 145DBA2-3E 145DBA2-5E 145DBA2-7E 145DBA2-10E 145DBA2-15E 145DBA2-20E 145DBA2-25E 145DBA2-30E
40E 50E 65E 80E 100E 125E 150E 200E
145DBA2-40E 145DBA2-50E 145DBA2-65E 145DBA2-80E 145DBA2-100E 145DBA2-125E 145DBA2-150E 145DBA2-200E
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-55
February 2007
Product Selection
Current Limiting Fuse
Table 13-37. Current Limiting Fuses Catalog Numbering System
Easy to Use, Easy to Order! Eaton’s Cutler-Hammer fuse catalog numbering system makes it easy to order the right fuse. The catalog numbers are easy to remember, unique to each fuse, and are broken down in three descriptive segments: Fuse Type, Voltage Rating and Current Rating. These Catalog Numbers can be entered directly and easily: ■
No change in order processing will occur if you use either a style number or its corresponding catalog number. You will get the same fuse. ■ In the back of this ordering guide is a style number to catalog number cross reference chart.
15 CLE – 100 E – D Maximum kV 2 = (2.4, 2.5, 2.75) 4 = (4.3, 4.8) 5 = (5.08, 5.5) 7 = (7.2) 8 = (8.3) 15 = (15.5) 25 = (25.5) 38 = (38.0)
Type CLE HLE BHLE CLPT NCLPT CLS BCLS CLS70 CLS75
Size
HCLS LCLS CX CXN CLT AHLE CXF ACLS
Amperes 0.5 – 1350
Class
A D
E R C X
Table 13-38. Current Limiting Fuse Accessories Catalog Numbering System
15 CLE – P NM – C
Examples: 5CLE-30E
5.5 max. kV, CLE fuse unit, 30E amperes
15CXN-45C
15.5 max. kV, CXN fuse unit, 45C amperes
5CLS-GDM-E
5.5 max. kV, CLS fuse unit, Glass Polyester Nondisconnect Mounting
CLE-DL-D
CLE, Disconnect Live Parts Size D
CA08101001E
Maximum kV 2 = (2.4, 2.5, 2.75) 4 = (4.3, 4.8) 5 = (5.08, 5.5) 7 = (7.2) 8 = (8.3) 15 = (15.5) 25 = (25.5) 38 = (38.0)
Type CLE HLE CLPT NCLPT CLS CLS75
HCLS LCLS CX CXN CLT
Diameter Size Hardware DM = Disconnect Mounting NM = Nondisconnect Mounting DL = Disconnect Live Parts NL = Nondisconnect Live Parts DF = Disconnect End Fittings Insulator G = Glass Polyester P = Porcelain H = High BIL
For more information visit: www.eaton.com
A = 1-5/8 inches (41.3 mm) 0.53E – 1.5E Single Barrel B = 1-5/8 inches (41.3 mm) 3E – 10E Single Barrel C = 2-inch (50.8 mm) Single Barrel D = 3-inch (76.2 mm) Single Barrel E = 3-inch (76.2 mm) Double Barrel F = 4-inch (101.6 mm) Double Barrel G = 5/8-inch (15.9 mm) Ferrule (CX/CXN Only)
13
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-56
February 2007
Type CLE Table 13-39. Type CLE Current Limiting Fuses
2CLE-10E 2CLE-30E 2CLE-40E 2CLE-50E 2CLE-65E 2CLE-80E 2CLE-100E 2CLE-125E 2CLE-150E 2CLE-200E 2CLE-225E
1 1 1 1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3 3 3 3
250E 300E 350X 400X 450X
2CLE-250E 2CLE-300E 2CLE-350X 2CLE-400X 2CLE-450X
2 2 2 2 2
50 50 50 50 50
15E 5CLE-15E 20E 5CLE-20E 25E 5CLE-25E
1 1 1
10E 15E 20E 25E 30E
5CLE-10E-D 5CLE-15E-D 5CLE-20E-D 5CLE-25E-D 5CLE-30E-D
40E 50E 65E 80E 100E 125E
Live Parts
End Fittings
Peak Let-Through Current
10E 30E 40E 50E 65E 80E 100E 125E 150E 200E 225E
GlassPolyester
Performance Curves
Total Clearing Time
8.13 8.13 8.13
Porcelain
Catalog Number
Minimum Melting Time
2 2 2
Voltage (BIL) kV
Clip Center (Inches)
50 50 50
Catalog Number
Type Indoor/Outdoor
Diameter (Inches)
1 1 1
Approx. Shipping Weight (lbs.) Heritage Product
Interrupting Rating rms (kA Sym.)
2CLE-15E 2CLE-20E 2CLE-25E
Length (Inches)
Barrel Number
Mounting (Includes Live Parts, End Fittings)
15E 20E 25E
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
Non60 2CLE-PNM-C 2CLE-GNM-C CLE-NL-C — Disconnect
7 7 7 7 7 7 7 7 7 7 7
10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9
7 7 7 7 7 7 7 7 7 7 7
H H H H H H H H H H H
I I I I I I I I I I I
Non60 2CLE-PNM-D 2CLE-GNM-D CLE-NL-D — Disconnect
3 3 3 3 3
7 7 7 7 7
10.9 10.9 10.9 10.9 10.9
15 15 15 15 15
H H H H H
I I I I I
Non60 2CLE-PND-E Disconnect
2CLE-GNM-E CLE-NL-E —
Disconnect 60 2CLE-PDM-E
2CLE-PDM-E
50 50 50
2 2 2
11.5 12.9 11.5 12.9 11.5 12.9
3 3 3
H I H I H I
1 1 1 1 1
63 63 63 63 63
3 3 3 3 3
14 14 14 14 14
17.9 17.9 17.9 17.9 17.9
9 9 9 9 9
— — — — —
I/O Non60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D — I/O Disconnect I/O Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D I/O I/O
5CLE1-40E 5CLE1-50E 5CLE1-65E 5CLE1-80E 5CLE1-100E 5CLE1-125E
1 1 1 1 1 1
50 50 50 50 50 50
3 3 3 3 3 3
14 14 14 14 14 14
17.9 17.9 17.9 17.9 17.9 17.9
9 9 9 9 9 9
H H H H H H
I I I I I I
150E 175E 200E 250E
5CLE-150E 5CLE-175E 5CLE-200E 5CLE-250E
1 1 1 1
63 63 63 63
3 3 3 3
14 14 14 14
17.9 17.9 17.9 17.9
9 9 9 9
— — — —
I/O Non60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D — I/O Disconnect I/O Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D I/O
300E 350E 400E 450E
5CLE-300E 5CLE-350E 5CLE-400E 5CLE-450E
2 2 2 2
63 63 63 63
3 3 3 3
14 14 14 14
17.9 17.9 17.9 17.9
19 19 19 19
— — — —
I/O Non60 5CLE-PNM-E I/O Disconnect I/O Disconnect 60 5CLE-PDM-E I/O
600E 750E 1100E 1350E
5CLE-600E 5CLE-750E 5CLE-1100E 5CLE-1350E
2 2 4 4
40 40 31 31
4 4 4 4
N/A
N/A 40 40 80 80
— — — —
I I I I
Disconnect 60 2CLE-PDM-C
2CLE-GDM-C CLE-DL-C CLE-DF-C
63931702
H I H I H I
56353302
2 2 2
53686204
63931704 63931802
CLE-DL-E CLE-DF-E
53690102
53686104
Disconnect 60 2CLE-PDM-D 2CLE-GDM-D CLE-DL-D CLE-DF-D
53690002
13
9.5 9.5 9.5
56353202
2.75 kV Maximum (2.4 kV Nominal)
63931702 70548701 62908904 70547601 70547601 63931704
56353304 70548601
5CLE-GDM-C CLE-DL-C CLE-DF-C
62908903 70546101 70545901 53686204
Disconnect 60 5CLE-PDM-C
70548501
Non60 5CLE-PNM-C 5CLE-GNM-C CLE-NL-C — Disconnect
56353204
5.5 kV Maximum (4.8 kV Nominal)
Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
5CLE-GNM-E CLE-NL-E — 5CLE-GDM-E CLE-DL-E CLE-DF-E
Non60 Refer to Factory. Disconnect
62908902 70546001 70545801 53686104
Non60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D — Disconnect
Includes end fittings. Disconnect only.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-57
February 2007
Type CLE Table 13-40. Type CLE Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings) Porcelain Insulator
Glass-Polyester Insulator
Catalog Number
Catalog Number
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Catalog Number
Catalog Number
CLE Mountings and Hardware 2.75 kV Maximum (2.4 kV Nominal) 10E
Non-Disconnect Disconnect
60 60
2CLE-PNM-D 2CLE-PDM-D
2CLE-GNM-D 2CLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
15E to 30E
Non-Disconnect Disconnect
60 60
2CLE-PNM-C 2CLE-PDM-C
2CLE-GNM-C 2CLE-GDM-C
CLE-NL-C CLE-DL-C
— CLE-DF-C
30E to 225E
Non-Disconnect Disconnect
60 60
2CLE-PNM-D 2CLE-PDM-D
2CLE-GNM-D 2CLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
250E to 450E
Non-Disconnect Disconnect
60 60
2CLE-PNM-E 2CLE-PDM-E
2CLE-GNM-E 2CLE-GDM-E
CLE-NL-E CLE-DL-E
— CLE-DF-E
10E
Non-Disconnect Disconnect
60 60
5CLE-PNM-D 5CLE-PDM-D
5CLE-GNM-D 5CLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
15E to 25E
Non-Disconnect Disconnect
60 60
5CLE-PNM-C 5CLE-PDM-C
5CLE-GNM-C 5CLE-GDM-C
CLE-NL-C CLE-DL-C
— CLE-DF-C
40E to 250E
Non-Disconnect Disconnect
60 60
5CLE-PNM-D 5CLE-PDM-D
5CLE-GNM-D 5CLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
300E to 450E
Non-Disconnect Disconnect
60 60
5CLE-PNM-E 5CLE-PDM-E
5CLE-GNM-E 5CLE-GDM-E
CLE-NL-E CLE-DL-E
— CLE-DF-E
600E and 750E
Non-Disconnect
60
9078A70G01
9078A70G02
—
—
1100 and 1350
(Consult Factory)
CLE Mountings and Hardware 5.5 kV Maximum (4.8 kV Nominal)
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-58
February 2007
Type CLE Table 13-41. Type CLE Current Limiting Fuses
2 2 2
14 15.5 14 15.5 14 15.5
3 3 3
H I H I H I
10E 15E 20E 25E 30E
8CLE-10E-D 8CLE-15E-D 8CLE-20E-D 8CLE-25E-D 8CLE-30E-D
1 1 1 1 1
50 50 50 50 50
3 3 3 3 3
14 14 14 14 14
17.9 17.9 17.9 17.9 17.9
9 9 9 9 9
— — — — —
I/O Non75 I/O Disconnect I/O Disconnect 75 I/O I/O
8CLE-PNM-D
8CLE-GNM-D
CLE-NL-D —
8CLE-PDM-D
8CLE-GDM-D
CLE-DL-D CLE-DF-D
40E 50E 65E 80E 100E 125E 150E 175E
8CLE-40E 8CLE-50E 8CLE-65E 8CLE-80E 8CLE-100E 8CLE-125E 8CLE-150E 8CLE-175E
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
14 14 14 14 14 14 14 14
17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9
9 9 9 9 9 9 9 9
— — — — — — — —
I/O Non75 I/O Disconnect I/O Disconnect 75 I/O I/O I/O I/O I/O
8CLE-PNM-D
8CLE-GNM-D
CLE-NL-D —
8CLE-PDM-D
8CLE-GDM-D
CLE-DL-D CLE-DF-D
200E 250E 300E 350E
8CLE-200E 8CLE-250E 8CLE-300E 8CLE-350E
2 2 2 2
50 50 50 50
3 3 3 3
14 14 14 14
17.9 17.9 17.9 17.9
19 19 19 19
— — — —
I/O Non75 I/O Disconnect I/O Disconnect 75 I/O
8CLE-PNM-E
8CLE-GNM-E
CLE-NL-E —
8CLE-PDM-E
8CLE-GDM-E
CLE-DL-E CLE-DF-E
Voltage (BIL) kV
Indoor/Outdoor
Barrel Number
Catalog Number
Type
Live Parts
End Fittings
Porcelain
GlassPolyester
Non75 Disconnect
8CLE-PNM-C
8CLE-GNM-C
CLE-NL-C —
Disconnect 75
8CLE-PDM-C
8CLE-GDM-C
CLE-DL-C CLE-DF-C
Minimum Melting Time Total Clearing Time Peak Let-Through Current
50 50 50
Approx. Shipping Weight (lbs.) Heritage Product
1 1 1
Length (Inches)
Clip Center (Inches)
Performance Curves
Diameter (Inches)
Catalog Number
Interrupting Rating rms (kA Sym.)
Mounting (Includes Live Parts, End Fittings)
15E 8CLE-15E 20E 8CLE-20E 25E 8CLE-25E
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
63931703 70548801 70547301 70547301
56353304 70548601 70546501 70546301
70548501 70546401 70546201
13
56353204
8.3 kV Maximum (7.2 kV Nominal)
10E 15E 20E 25E 30E
15CLE-10E-D 15CLE-15E-D 15CLE-20E-D 15CLE-25E-D 15CLE-30E-D
1 1 1 1 1
63 63 63 63 63
3 3 3 3 3
20 20 20 20 20
23.9 23.9 23.9 23.9 23.9
11 11 11 11 11
— — — — —
I/O Non95 15CLE-PNM-D I/O Disconnect 110 15CLE-HPNM-D I/O I/O Disconnect 95 15CLE-PDM-D I/O 110 15CLE-HPDM-D
15CLE-GNM-D CLE-NL-D —
40E 50E 65E 80E 100E 125E 150E
15CLE-40E 15CLE-50E 15CLE-65E 15CLE-80E 15CLE-100E 15CLE-125E 15CLE-150E
1 1 1 1 1 1 1
63 63 63 63 63 63 63
3 3 3 3 3 3 3
20 20 20 20 20 20 20
23.9 23.9 23.9 23.9 23.9 23.9 23.9
11 11 11 11 11 11 11
— — — — — — —
I/O Non95 15CLE-PNM-D I/O Disconnect 110 15CLE-HPNM-D I/O I/O Disconnect 95 15CLE-PDM-D I/O 110 15CLE-HPDM-D I/O I/O
15CLE-GNM-D CLE-NL-D —
175E 200E 250E 300E
15CLE-175E 15CLE-200E 15CLE-250E 15CLE-300E
2 2 2 2
63 63 63 63
3 3 3 3
20 20 20 20
23.9 23.9 23.9 23.9
23 23 23 23
— — — —
I/O Non95 15CLE-PNM-E I/O Disconnect 110 15CLE-HPNM-E I/O I/O Disconnect 95 15CLE-PDM-E 110 15CLE-HPDM-E
15CLE-GNM-E CLE-NL-E —
80E 15CLE2-80E 2 100E 15CLE2-100E 2 125X 15CLE2-125X 2
85 85 85
3 3 3
20 23.9 23 20 23.9 23 20 23.9 23
H I H I H I
For Replacement Only
150E 15CLE3-150E 3 175E/ 15CLE3-175E/ 3 200X 200X
50 50
3 3
20 23.9 36 20 23.9 36
H I H I
For Replacement Only
— 15CLE-GDM-D CLE-DL-D CLE-DF-D —
63931703 70548802
15CLE-GDM-C CLE-DL-C CLE-DF-C
56353304
— 15CLE-GDM-E CLE-DL-E CLE-DF-E —
70547501
—
70547501
— 15CLE-GDM-D CLE-DL-D CLE-DF-D
63931604
95 15CLE-PDM-C
110 15CLE-HPDM-C —
70546901
Disconnect
70548601
Non95 15CLE-PNM-C 15CLE-GNM-C CLE-NL-C — Disconnect 110 15CLE-HPNM-C —
70547101
4.5 H I 4.5 H I 4.5 H I
59878402
20 21.5 20 21.5 20 21.5
70548501
31.5 2 31.5 2 31.5 2
70546801
1 1 1
70547001
15CLE-15E 15CLE-20E 15CLE-25E
59878302
15E 20E 25E
56353204
15.5 kV Maximum (4.8 kV Nominal)
Includes end fittings. Disconnect only.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-59
February 2007
Type CLE Table 13-42. Type CLE Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings) Porcelain Insulator
Glass-Polyester Insulator
Catalog Number
Catalog Number
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Catalog Number
Catalog Number
CLE Mountings and Hardware 8.3 kV Maximum (7.2 kV Nominal) 15E to 25E
Non-Disconnect Disconnect
75 75
8CLE-PNM-C 8CLE-PDM-C
8CLE-GNM-C 8CLE-GDM-C
CLE-NL-C CLE-DL-C
— CLE-DF-C
30E to 200E
Non-Disconnect Disconnect
75 75
8CLE-PNM-D 8CLE-PDM-D
8CLE-GNM-D 8CLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
Non-Disconnect
95 110
15CLE-PNM-C 15CLE-HPNM-C
15CLE-GNM-C —
CLE-NL-D —
— —
Disconnect
95 110
15CLE-PDM-C 15CLE-HPDM-C
15CLE-GDM-C —
CLE-DL-C —
CLE-DF-C —
Non-Disconnect
95 110
15CLE-PNM-D 15CLE-HPM-D
15CLE-GNM-D —
CLE-NL-D —
— —
Disconnect
95 110
15CLE-PDM-D 15CLE-HPDM-D
15CLE-GNM-D —
CLE-DL-D —
CLE-DF-D —
Non-Disconnect Disconnect
110 110
15CLE-PNM-E 15CLE-PDM-E
— —
CLE-DL-E —
CLE-DF-E —
CLE Mountings and Hardware 15.5 kV Maximum (14.4 kV Nominal) 15E to 25E
30E to 150E
150E to 300E
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
CA08101001E
13
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-60
February 2007
Type HLE Table 13-43. Type HLE Current Limiting Fuses
63 63 63 63 63
3 3 3 3 3
12 12 12 12 12
15.9 15.9 15.9 15.9 15.9
8 8 8 8 8
— — — — —
I/O Non60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D I/O Disconnect I/O Disconnect 60 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D I/O I/O
40E 50E 65E 80E 100E 125E 150E 175E 200E 250E
5HLE-40E 5HLE-50E 5HLE-65E 5HLE-80E 5HLE-100E 5HLE-125E 5HLE-150E 5HLE-175E 5HLE-200E 5HLE-250E
1 1 1 1 1 1 1 1 1 1
63 63 63 63 63 63 63 63 63 63
3 3 3 3 3 3 3 3 3 3
12 12 12 12 12 12 12 12 12 12
15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
8 8 8 8 8 8 8 8 8 8
— — — — — — — — — —
I/O Non60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D I/O Disconnect I/O Disconnect 60 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D I/O I/O I/O I/O I/O I/O I/O
300E 350E 400E 450E
5HLE-300E 5HLE-350E 5HLE-400E 5HLE-450E
2 2 2 2
63 63 63 63
3 3 3 3
12 12 12 12
15.9 15.9 15.9 15.9
17 17 17 17
— — — —
I/O Non60 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E I/O Disconnect I/O Disconnect 60 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E I/O
GlassPolyester
Live Parts
End Fittings Minimum Melting Time
Voltage (BIL) kV
Indoor/Outdoor
Barrel Number
Porcelain
Peak Let-Through Current
Length (Inches)
1 1 1 1 1
Catalog Number
Type
Performance Curves
Total Clearing Time
Clip Center (Inches)
5HLE-10E 5HLE-15E 5HLE-20E 5HLE-25E 5HLE-30E
Approx. Shipping Weight (lbs.) Heritage Product
Diameter (Inches)
Catalog Number
Interrupting Rating rms (kA Sym.)
Mounting (Includes Live Parts, End Fittings)
10E 15E 20E 25E 30E
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
5.5 kV Maximum (4.8 kV Nominal)
70548607
70548703
70546105 70545905
70547603 70547603
70548507
CLE-DF-D
— CLE-DF-D
— CLE-DF-E
70546005 70545805
13
—
Includes end fittings. Disconnect only.
Table 13-44. Type HLE Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings) Porcelain Insulator
Glass-Polyester Insulator
Catalog Number
Catalog Number
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Catalog Number
Catalog Number
SCLE Mountings and Hardware 5.5 kV Maximum (4.8 kV Nominal) 30E to 225E
Non-Disconnect Non-Disconnect
60 60
5HLE-PNM-D 5HLE-PDM-D
5HLE-GNM-D 5HLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
250E to 400X
Non-Disconnect Disconnect
60 60
5HLE-PNM-E 5HLE-PDM-E
5HLE-GNM-E 5HLE-GDM-E
CLE-NL-E CLE-DL-E
— CLE-DF-E
30E to 450E
Non-Disconnect Disconnect
60 60
5HLE-PNM-D 5HLE-PDM-D
5HLE-GNM-D 5HLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
300E to 450E
Non-Disconnect Disconnect
60 60
5HLE-PNM-E 5HLE-PDM-E
5HLE-GNM-E 5HLE-GDM-E
CLE-NL-E CLE-DL-E
— CLE-DF-D
HLE Mountings and Hardware 5.5 kV Maximum (4.8 kV Nominal)
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-61
February 2007
Type HLE Table 13-45. Type HLE Current Limiting Fuses
Length (Inches)
Approx. Shipping Weight (lbs.) Heritage Product
Indoor/Outdoor
8HLE-10E 8HLE-15E 8HLE-20E 8HLE-25E 8HLE-30E
1 1 1 1 1
50 50 50 50 50
3 3 3 3 3
12 12 12 12 12
15.9 15.9 15.9 15.9 15.9
8 8 8 8 8
— — — — —
I/O Non75 8HLE-PNM-D I/O Disconnect I/O Disconnect 75 8HLE-PDM-D I/O I/O
8HLE-GNM-D
CLE-NL-D —
8HLE-GDM-D
CLE-DL-D CLE-DF-D
40E 50E 65E 80E 100E 125E 150E 175E
8HLE-40E 8HLE-50E 8HLE-65E 8HLE-80E 8HLE-100E 8HLE-125E 8HLE-150E 8HLE-175E
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
12 12 12 12 12 12 12 12
15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
8 8 8 8 8 8 8 8
— — — — — — — —
I/O Non75 8HLE-PNM-D I/O Disconnect I/O Disconnect 75 8HLE-PDM-D I/O I/O I/O I/O I/O
8HLE-GNM-D
CLE-NL-D —
8HLE-GDM-D
CLE-DL-D CLE-DF-D
200E 250E 300E 350E
8HLE-200E 8HLE-250E 8HLE-300E 8HLE-350E
2 2 2 2
50 50 50 50
3 3 3 3
12 12 12 12
15.9 15.9 15.9 15.9
8 8 8 8
— — — —
I/O Non75 5HLE-PNM-E I/O Disconnect I/O Disconnect 75 5HLE-PDM-E I/O
5HLE-GNM-E
CLE-NL-E —
5HLE-GDM-E
CLE-DL-E CLE-DF-E
GlassPolyester
Live Parts
End Fittings Total Clearing Time
Porcelain
Minimum Melting Time
Voltage (BIL) kV
Barrel Number
Catalog Number
Type
Peak Let-Through Current
Clip Center (Inches)
Performance Curves
Diameter (Inches)
Catalog Number
Interrupting Rating rms (kA Sym.)
Mounting (Includes Live Parts, End Fittings)
10E 15E 20E 25E 30E
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
70548507
70548607
70548804
70546403 70546203
70546503 70546303
70547201 70547201
8.3 kV Maximum (7.2 kV Nominal)
15 15 15 15 15
18.9 18.9 18.9 18.9 18.9
10 10 10 10 10
— — — — —
I/O Non95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D — I/O Disconnect I/O Disconnect 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D I/O I/O
40E 50E 65E 80E 100E 125E
15HLE-40E 15HLE-50E 15HLE-65E 15HLE-80E 15HLE-100E 15HLE-125E
1 1 1 1 1 1
63 63 63 63 63 63
3 3 3 3 3 3
15 15 15 15 15 15
18.9 18.9 18.9 18.9 18.9 18.9
10 10 10 10 10 10
— — — — — —
I/O Non95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D — I/O Disconnect I/O Disconnect 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D I/O I/O I/O
150E 175E 200E 250E
15HLE-150E 15HLE-175E 15HLE-200E 15HLE-250E
2 2 2 2
63 63 63 63
3 3 3 3
15 15 15 15
18.9 18.9 18.9 18.9
21 21 21 21
— — — —
I/O Non95 15HLE-PNM-E 15HLE-GNM-E CLE-NL-E — I/O Disconnect I/O Disconnect 95 15HLE-PDM-E 15HLE-GDM-E CLE-DL-E CLE-DF-E I/O
70548805
3 3 3 3 3
70547401 70547401
63 63 63 63 63
70548607
1 1 1 1 1
70546701 70546701
15HLE-10E 15HLE-15E 15HLE-20E 15HLE-25E 15HLE-30E
70548507
10E 15E 20E 25E 30E
70546601 70546601
15.5 kV Maximum (14.4 kV Nominal)
Includes end fittings. Disconnect only.
Table 13-46. Type HLE Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings) Porcelain Insulator
Glass-Polyester Insulator
Catalog Number
Catalog Number
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Catalog Number
Catalog Number
HLE Mountings and Hardware 8.3 kV Maximum (7.2 kV Nominal) 20E to 180E
Non-Disconnect Disconnect
75 75
8HLE-PNM-D 8HLE-PDM-D
8HLE-GNM-D 8HLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
200E to 350E
Non-Disconnect Disconnect
75 75
8HLE-PNM-E 8HLE-PDM-E
8HLE-GNM-E 8HLE-GDM-E
CLE-NL-E CLE-DL-E
— CLE-DF-E
20E to 125E
Non-Disconnect Disconnect
95 95
15HLE-PNM-D 15HLE-PDM-D
15HLE-GNM-D 15HLE-GDM-D
CLE-NL-D CLE-DL-D
— CLE-DF-D
150E to 250E
Non-Disconnect Disconnect
95 95
15HLE-PNM-E 15HLE-PDM-E
— —
CLE-NL-E CLE-DL-E
— CLE-DF-E
HLE Mountings and Hardware 15.5 kV Maximum (14.4 kV Nominal)
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-62
February 2007
Type BHLE Table 13-47. Type BHLE Current Limiting Fuses (5.5 kV Maximum, 4.8 kV Nominal)
8 8 8 8 8
— — — — —
I I I I I
NonDisconnect
40E 50E 65E 80E 100E 125E 150E 175E 200E 250E
5BHLE-40E 5BHLE-50E 5BHLE-65E 5BHLE-80E 5BHLE-100E 5BHLE-125E 5BHLE-150E 5BHLE-175E 5BHLE-200E 5BHLE-250E
1 1 1 1 1 1 1 1 1 1
63 63 63 63 63 63 63 63 63 63
3 3 3 3 3 3 3 3 3 3
15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
8 8 8 8 8 8 8 8 8 8
— — — — — — — — — —
I I I I I I I I I I
NonDisconnect
300E 350E 400E 450E
5BHLE-300E 5BHLE-350E 5BHLE-400E 5BHLE-450E
1 1 1 1
63 63 63 63
3 3 3 3
15.9 15.9 15.9 15.9
8 8 8 8
— — — —
I I I I
NonDisconnect
Peak Let-Through Current
Indoor/Outdoor
15.9 15.9 15.9 15.9 15.9
Bolt-on. Not applicable.
Disconnect
70548703
Heritage Product
End Fittings
Total Clearing Time
Approx. Shipping Weight (Lbs.)
3 3 3 3 3
Live Parts
70548607
Length (Inches)
63 63 63 63 63
GlassPolyester
Minimum Melting Time
Clip Center (Inches)
1 1 1 1 1
Catalog Number Porcelain
Performance Curves
70548507
Diameter (Inches)
5BHLE-10E 5BHLE-15E 5BHLE-20E 5BHLE-25E 5BHLE-30E
Voltage (BIL) kV
Interrupting Rating rms (kA Sym.)
10E 15E 20E 25E 30E
Type
Catalog Number
70547603 70547603
Disconnect
70546105 70545905
70546005 70545805
Disconnect
Includes end fittings. Disconnect only. Bolt-in.
Table 13-48. Type BHLE Current Limiting Fuses (8.3 kV Maximum, 7.2 kV Nominal)
40E 50E 65E 80E 100E 125E 150E 175E
8BHLE-40E 8BHLE-50E 8BHLE-65E 8BHLE-80E 8BHLE-100E 8BHLE-125E 8BHLE-150E 8BHLE-175E
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
8 8 8 8 8 8 8 8
— — — — — — — —
I I I I I I I I
200E 250E 300E 350E
8BHLE-200E 8BHLE-250E 8BHLE-300E 8BHLE-350E
1 1 1 1
50 50 50 50
3 3 3 3
15.9 15.9 15.9 15.9
17 17 17 17
— — — —
I I I I
Peak Let-Through Current
I I I I I
Bolt-on. Not applicable. 70548804
— — — — —
70547201 70547201
8 8 8 8 8
Total Clearing Time
15.9 15.9 15.9 15.9 15.9
End Fittings
70548607
Indoor/Outdoor
Live Parts
70546503 70546303
Heritage Product
3 3 3 3 3
GlassPolyester
Minimum Melting Time
Approx. Shipping Weight (Lbs.)
50 50 50 50 50
Catalog Number Porcelain
Performance Curves
70548507
Length (Inches)
1 1 1 1 1
Catalog Number
70546403 70546203
Clip Center (Inches)
8BHLE-10E 8BHLE-15E 8BHLE-20E 8BHLE-25E 8BHLE-30E
Type
Voltage (BIL) kV
Diameter (Inches)
10E 15E 20E 25E 30E
Current Rating (Amperes)
Interrupting Rating rms (kA Sym.)
8.3
Mounting (Includes Live Parts, End Fittings)
Barrel Number
Catalog Number Maximum Design Voltage (kV)
13
Mounting (Includes Live Parts, End Fittings)
Barrel Number
5.5
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
Includes end fittings. Disconnect only. Bolt-in.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-63
February 2007
Types BHLE and HCL Table 13-49. Type BHLE Current Limiting Fuses (15.5 kV Maximum, 14.4 kV Nominal)
— — — — —
I/O Bolt-on. Not applicable. I/O I/O I/O I/O
40E 50E 65E 80E 100E 125E
15BHLE-40E 15BHLE-50E 15BHLE-65E 15BHLE-80E 15BHLE-100E 15BHLE-125E
1 1 1 1 1 1
63 63 63 63 63 63
3 3 3 3 3 3
18.9 18.9 18.9 18.9 18.9 18.9
10 10 10 10 10 10
— — — — — —
I/O I/O I/O I/O I/O I/O
150E 175E 200E 250E
15BHLE-150E 15BHLE-175E 15BHLE-200E 15BHLE-250E
2 2 2 2
63 63 63 63
3 3 3 3
18.9 18.9 18.9 18.9
21 21 21 21
— — — —
I/O I/O I/O I/O
Voltage (BIL) kV
Peak Let-Through Current
10 10 10 10 10
70548805
18.9 18.9 18.9 18.9 18.9
70547401
Indoor/Outdoor
Total Clearing Time
Heritage Product
3 3 3 3 3
End Fittings
70548607
Approx. Shipping Weight (lbs.)
63 63 63 63 63
Live Parts
70546701
Length (Inches)
1 1 1 1 1
GlassPolyester
Minimum Melting Time
Clip Center (Inches)
15BHLE-10E 15BHLE-15E 15BHLE-20E 15BHLE-25E 15BHLE-30E
Catalog Number Porcelain
Performance Curves
70548507
Diameter (Inches)
10E 15E 20E 25E 30E
Type
Catalog Number
70546601
Interrupting Rating rms (kA Sym.)
Mounting (Includes Live Parts, End Fittings)
Barrel Number
15.5
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
Includes end fittings. Disconnect only. Bolt-in.
13
Table 13-50. Type HCL Current Limiting Fuses (5.5 kV Maximum, 4.8 kV Nominal)
CA08101001E
Performance Curves Minimum Melting Time
Total Clearing Time
Peak Let-Through Current
Indoor/Outdoor
Catalog Number Live Parts (Includes End Fittings)
Heritage Product
Mounting Type Approx. Shipping Weight (lbs.)
Clip Center Diameter (Inches)
Catalog Number
Interrupting Rating rms (kA Sym.)
5.5
Current Rating (Amperes)
Barrel Number
Maximum Design Voltage (kV)
10E 15E 20E 25E 30E
5HCL-10E 5HCL-15E 5HCL-20E 5HCL-25E 5HCL-30E
1 1 1 1 1
63 63 63 63 63
3 3 3 3 3
Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock
9 9 9 9 9
— — — — —
I I I I I
NonDisconnect
HCL-NL-1
70548505
70548605
70548702
40E 50E 65E 80E 100E 125E 150E
5HCL-40E 5HCL-50E 5HCL-65E 5HCL-80E 5HCL-100E 5HCL-125E 5HCL-150E
1 1 1 1 1 1 1
63 63 63 63 63 63 63
3 3 3 3 3 3 3
Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock
9 9 9 9 9 9 9
— — — — — — —
I I I I I I I
NonDisconnect
HCL-NL-1
70545803
70545903
70547602
200E 250E
5HCL-200E 5HCL-250E
1 1
63 63
3 3
Clip-Lock Clip-Lock
10 10
— I — I
NonDisconnect
HCL-NL-1
300E 400E 450E
5HCL-300E 5HCL-400E 5HCL-450E
2 2 2
63 63 63
3 3 3
Clip-Lock Clip-Lock Clip-Lock
20 20 20
— I — I — I
NonDisconnect
HCL-NL-1
70546003
70516103
70547602
500E 600E
5HCL-500E 5HCL-600E
2 2
63 63
3 3
Clip-Lock Clip-Lock
20 20
— I — I
NonDisconnect
HCL-NL-1
66703401
66703501
66703701
750E 900E
5HCL-750E 5HCL-900E
3 3
63 63
3 3
Bolt-in Bolt-in
30 30
— I — I
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-64
February 2007
Type HCL Table 13-51. Type HCL Current Limiting Fuses (15.5 kV Maximum, 14.4 kV Nominal) Performance Curves Minimum Melting Time
Total Clearing Time
Peak Let-Through Current
Indoor/Outdoor
Catalog Number Live Parts (Includes End Fittings)
Heritage Product
Mounting Type Approx. Shipping Weight (lbs.)
Clip Center Diameter (Inches)
Catalog Number
Interrupting Rating rms (kA Sym.)
15.5
Current Rating (Amperes)
Barrel Number
Maximum Design Voltage (kV)
10E 15E 20E 25E 30E
15HCL-10E 15HCL-15E 15HCL-20E 15HCL-25E 15HCL-30E
1 1 1 1 1
63 63 63 63 63
3 3 3 3 3
Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock
10 10 10 10 10
— — — — —
I I I I I
NonDisconnect
HCL-NL-1
70548503
70548603
70548803
40E 50E
15HCL-40E 15HCL-50E
1 1
63 63
3 3
Clip-Lock Clip-Lock
10 10
— I — I
NonDisconnect
HCL-NL-1
66703201
66703301
70547402
65E 80E 100E 125E
15HCL-65E 15HCL-80E 15HCL-100E 15HCL-125E
1 1 1 1
50 50 50 50
3 3 3 3
Clip-Lock Clip-Lock Clip-Lock Clip-Lock
12 12 12 12
— — — —
I I I I
NonDisconnect
HCL-NL-1
150E 200E 250E 300E
15HCL-150E 15HCL-200E 15HCL-250E 15HCL-300E
2 2 2 2
50 50 50 50
3 3 3 3
Clip-Lock Clip-Lock Clip-Lock Clip-Lock
24 24 24 24
— — — —
I I I I
NonDisconnect
HCL-NL-1
66703201
66703301
70547402
13
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-65
February 2007
Types CLE, HLE and BHLE
Fuse Dimensional Details
Table 13-52. CLE Fuse Dimensional Details
"B" Dia. 1.56 Ref.
CLE kV
“L”
“B” Dia.
2.75 5.50 8.30 15.50
9.50 ± .06 17.88 ± .03 17.88 ± .03 23.88 ± .03
2.00 3.00 3.00 3.00
Table 13-53. HLE Fuse Dimensional Details
"L" 17.88
Figure 13-15. CLE Fuse Dimensional Details — Inches
HLE kV
L ± 0.03
5.50 8.30 15.50 25.80
15.88 15.88 18.88 23.88
3.00 Dia. 3.56
L ± .03
L ± .03
Figure 13-16. HLE Fuse Dimensional Details — Inches
Indicator to be Located Here
3.31 2.12 3.00 Ref.
17.88 ± .06 19.25 Ref.
17.88 ± .06 19.25 Ref. Single Barrel
3.00 Ref.
Double Barrel Type 5BHLE & 8BHLE Fuses
3.00 3.56
1.53
3.00
20.88 ± .06 22.25 Ref.
20.88 ± .06 22.25 Ref.
Double Barrel
Single Barrel Type 15BHLE Fuses
Figure 13-17. BHLE Fuse Dimensional Details — Inches
CA08101001E
3.56
For more information visit: www.eaton.com
Ref.
13
13-66
Power Breakers, Contactors & Fuses Current Limiting Fuses February 2007
Type HCL Table 13-54. 15.5 kV Clip Lock Mounted Ampere Number Figure Dimensions in Inches Rating of Number A B C Barrels
Type HCL-14 Fuses Indicator Flush with Surface in Untripped Position A B
15.5 kV Maximum — Clip Lock Style — 21.25-Inch Clip Centers — 3-Inch Barrel Diameter
Indicator .25
1.25
3.00
C Figure A
Indicator Flush with Surface in Untripped Position
A
150E 200E 250E 300E
2
B
22.81
22.12
0.5 Tripped Force 2 Lb.
1.25
3.00
C
10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E
Indicator Flush with Surface in Untripped Position B
.38 A Blown Fuse Indicator
.44 x .91 Slots
.44 Dia. Hole
C Figure C
63,000
50,000
Interrupting Rating rms Sym. Amperes
5.5 kV Maximum — Clip Lock Style — 15.25-Inch Clip Centers — 3-Inch Barrel Diameter
Figure B
1.50
1
Ampere Number Figure Dimensions in Inches Rating of Number A B C Barrels 5
13
65E 80E 100E 125E
Table 13-55. 5.5 and 15.5 kV Clip Lock Mounted
A B
1.25
Interrupting Rating rms Sym. Amperes
1
A
16.81
16.12
0.5 Tripped Force 2 Lb.
63,000
5.5 kV Maximum — Clip Lock Style — 21.25-Inch Clip Centers — 3-Inch Barrel Diameter 200E 250E 300E 400E
1
A
450E 500E 600E
2
B
22.81
22.12
0.5 Tripped Force 2 Lb.
63,000
15.5 kV Maximum — Clip Lock Style-18.25-Inch Clip Centers — 3-Inch Barrel Diameter
Type HCL Fuses 16.38 ± .06 for HCL-8 19.38 ± .06 FOR HCL-15
10E 15E 20E 25E 30E 40E 50E
Figure 13-18. HCL Fuse Dimensional Details — Inches
1
A
19.81
19.12
0.5 Tripped Force 2 Lb.
63,000
Table 13-56. Bolt-in-Series — 5.5 kV Ampere Number Figure Dimensions in Inches Rating of Number A B C D Barrels
Interrupting Rating rms Sym. Amperes
5.5 kV Maximum — Bolt-in Style — 23.73-Inch Hole Centers — 3-Inch Barrel Diameter 750E 900E
3
For more information visit: www.eaton.com
C
25.11 22.37 23.73 0.5 63,000 Tripped Force 2 Lb.
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-67
February 2007
Type CLS Table 13-57. CLS Type Current Limiting Fuses
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
390 450
18R 2ACLS-18R 24R 2ACLS-24R
2 2
50 50
3 3
10.8 16 10.8 16
25 70 100 130 150 170 200 230
— 2R 3R 4R 5R 6R 9R 12R
2BCLS-25 2BCLS-2R 2BCLS-3R 2BCLS-4R 2BCLS-5R 2BCLS-6R 2BCLS-9R 2BCLS-12R
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
390 450
18R 2BCLS-18R 24R 2BCLS-24R
2 2
50 50
3 3
10.8 17 10.8 17
25 70 100 130 150 170 200 230
— 2R 3R 4R 5R 6R 9R 12R
2HCLS-25 2HCLS-2R 2HCLS-3R 2HCLS-4R 2HCLS-5R 2HCLS-6R 2HCLS-9R 2HCLS-12R
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
390 450
18R 2HCLS-18R 24R 2HCLS-24R
2 2
50 50
3 3
10.8 16 10.8 16
30 70 100 130 150 170 200 230
— 2R 3R 4R 5R 6R 9R 12R
5CLS-30 5CLS-2R 5CLS-3R 5CLS-4R 5CLS-5R 5CLS-6R 5CLS-9R 5CLS-12R
1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3
12 12 12 12 12 12 12 12
15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
390 450
18R 5CLS-18R 24R 5CLS-24R
2 2
50 50
3 3
12 15.9 17 12 15.9 17
7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8
7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8
CLE-DF-D
NonDisconnect
60 2CLE-PNM-E
2CLE-GNM-E
CLE-NL-E
—
Disconnect
60 2CLE-PDME
2CLE-GDM-E
CLE-DL-E
CLE-DF-E
Peak Let-Through Current
For use with AMPGARD 400 A Motor Starters
Bolt-in
Hermetically Sealed Fuses for use with AMPGARD 400 A Motor Starters
NonDisconnect
60 5HLE-PNM-D
5HLE-GNM-D
CLE-NL-D
—
Disconnect
60 5HLE-PDM-D
5HLE-GDM-E
CLE-DL-D
CLE-DF-D
NonDisconnect
60 5HLE-PNM-E
5HLE-GNM-E
CLE-NL-E
—
Disconnect
60 5HLE-PDME
5HLE-GDM-E
CLE-DL-E
CLE-DF-E
Includes end fittings. Disconnect only. Not applicable.
CA08101001E
66700202
2ACLS-25 2ACLS-2R 2ACLS-3R 2ACLS-4R 2ACLS-5R 2ACLS-6R 2ACLS-9R 2ACLS-12R
CLE-DL-D
66700202
— 2R 3R 4R 5R 6R 9R 12R
2CLE-GDM-E
66700202
25 70 100 130 150 170 200 230
60 2CLE-PDM-D
For more information visit: www.eaton.com
66700202
10.8 16 10.8 16
Disconnect
66700203
7 7
—
Total Clearing Time
3 3
CLE-NL-D
66664704
50 50
2CLE-GNM-D
66664704
2 2
60 2CLE-PNM-D
66664704
18R 2CLS-18R 24R 2CLS-24R
NonDisconnect
66664704
390 450
7 7 7 7 7 7 7 7
66690702
10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
Minimum Melting Time
7 7 7 7 7 7 7 7
End Fittings
66664702
3 3 3 3 3 3 3 3
Live Parts
66664702
Length (Inches)
50 50 50 50 50 50 50 50
GlassPolyester
66664702
Clip Center (Inches)
1 1 1 1 1 1 1 1
Porcelain
Performance Curves
66664702
Diameter (Inches)
2CLS-25 2CLS-2R 2CLS-3R 2CLS-4R 2CLS-5R 2CLS-6R 2CLS-9R 2CLS-12R
Catalog Number
Type Voltage (BIL) kV
Interrupting Rating rms (kA Sym.)
— 2R 3R 4R 5R 6R 9R 12R
Approx. Shipping Weight (Lbs.)
Barrel Number
25 70 100 130 150 170 200 230
Catalog Number
66690602
5.5
“R” Designation
2.54
Mounting (Includes Live Parts, End Fittings)
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
13
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-68
February 2007
Type CLS Table 13-57. CLS Type Current Limiting Fuses (Continued)
13
— 2R 3R 4R 5R 6R 9R 12R 18R 24R
5BCLS-30 5BCLS-2R 5BCLS-3R 5BCLS-4R 5BCLS-5R 5BCLS-6R 5BCLS-9R 5BCLS-12R 5BCLS-18R 5BCLS-24R
1 1 1 1 1 1 1 1 2 2
50 50 50 50 50 50 50 50 50 50
Bolt-in
480
26R 4BCLS-26R
2
50
3
15.9 17
30 70 100 130 150 170 200 230 390 450
— 2R 3R 4R 5R 6R 9R 12R 18R 24R
5HCLS-30 5HCLS-2R 5HCLS-3R 5HCLS-4R 5HCLS-5R 5HCLS-6R 5HCLS-9R 5HCLS-12R 5HCLS-18R 5HCLS-24R
1 1 1 1 1 1 1 1 2 2
50 50 50 50 50 50 50 50 50 50
3 3 3 3 3 3 3 3 3 3
15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 17 15.9 17
Hermetically Sealed for use with AMPGARD 400 A Motor Starters
5.08
70 100 130 150 170 200 230 390 450 600 650 700
2R 3R 4R 5R 6R 9R 12R 18R 24R 32R 36R 44R
5CLS70-2R 5CLS70-3R 5CLS70-4R 5CLS70-5R 5CLS70-6R 5CLS70-9R 5CLS70-12R 5CLS70-18R 5CLS70-24R 5CLS70-32R 5CLS70-36R 5CLS70-44R
2 2 2 2 2 2 2 2 2 2 2 2
50 50 50 50 50 50 50 50 50 50 50 50
3 3 3 3 3 3 4 4 4 4 4 4
15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
20 20 20 20 20 20 40 40 40 40 40 40
For use with AMPGARD 800 A Motor Starters
5.5
70 100 130 150 170 200 230
2R 3R 4R 5R 6R 9R 12R
5LCLS-2R 5LCLS-3R 5LCLS-4R 5LCLS-5R 5LCLS-6R 5LCLS-9R 5LCLS-12R
1 1 1 1 1 1 1
50 50 50 50 50 50 50
3 3 3 3 3 3 3
14 14 14 14 14 14 14
17.9 17.9 17.9 17.9 17.9 17.9 17.9
11 11 11 11 11 11 11
NonDisconnect
60 5CLE-PNM-D
5CLE-GNM-D
CLE-NL-D
—
Disconnect
60 5CLE-PDM-D
5CLE-GDM-D
CLE-DL-D
CLE-DF-D
Disconnect
75 8CLE-PDM-D
8CLE-GDM-D
390 450
18R 5LCLS-18R 24R 5LCLS-24R
2 2
50 50
3 3
14 17.9 22 14 17.9 22
NonDisconnect
60 5CLE-PNM-E
5CLE-GNM-E
CLE-NL-E
—
CLE-DL-E
CLE-DF-E
66690602
66690602
4.3 5.08
Peak Let-Through Current
15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 17 15.9 17
30 70 100 130 150 170 200 230 390 450
66700203
15.9 17
3 3 3 3 3 3 3 3 3 3
5.08
Disconnect
60 5CLE-PDM-E
5CLE-GDM-E
Disconnect
75 8CLE-PDM-E
8CLE-PDM-E
66700203
66700203
3
66700203
50
66700204
2
Total Clearing Time
26R 4ACLS-26R
66690702
480
66690702
4.3
For use with AMPGARD 400 A Motor Starters
66690702
15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 8 15.9 17 15.9 17
66690702
51285402
3 3 3 3 3 3 3 3 3 3
End Fittings Minimum Melting Time
50 50 50 50 50 50 50 50 50 50
Live Parts
66690602
Length (Inches)
1 1 1 1 1 1 1 1 2 2
GlassPolyester
66690602
Clip Center (Inches)
5ACLS-30 5ACLS-2R 5ACLS-3R 5ACLS-4R 5ACLS-5R 5ACLS-6R 5ACLS-9R 5ACLS-12R 5ACLS-18R 5ACLS-24R
Porcelain
Performance Curves
51285302
Diameter (Inches)
— 2R 3R 4R 5R 6R 9R 12R 18R 24R
Catalog Number
Catalog Number
Type Voltage (BIL) kV
Interrupting Rating rms (kA Sym.)
30 70 100 130 150 170 200 230 390 450
Approx. Shipping Weight (Lbs.)
Barrel Number
5.08
Maximum Design Voltage (kV)
“R” Designation
Mounting (Includes Live Parts, End Fittings)
Current Rating (Amperes)
Catalog Number
Includes end fittings. Disconnect only. Not applicable.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-69
February 2007
Type CLS Table 13-57. CLS Type Current Limiting Fuses (Continued)
—
Disconnect
75 8HLE-PDM-D
8HLE-GDM-D
CLE-DL-D
CLE-DF-D
200 230
9R 7CLS-9R 12R 7CLS-12R
1 1
50 50
3 3
12 15.9 12 15.9
7.2
390 450
18R 7CLS-18R 24R 7CLS-24R
2 2
50 50
3 3
12 15.9 16 12 15.9 16
NonDisconnect
75 8HLE-PDM-E
8HLE-GNM-E
CLE-NL-E
—
Disconnect
75 8HLE-PDM-E
8HLE-GDM-E
CLE-DL-E
CLE-DF-E
8.3
70 100 130 150 170 200 230
2R 3R 4R 5R 6R 9R 12R
7BCLS-2R 7BCLS-3R 7BCLS-4R 7BCLS-5R 7BCLS-6R 7BCLS-9R 7BCLS-12R
1 1 1 1 1 1 1
50 50 50 50 50 50 50
3 3 3 3 3 3 3
15.9 15.9 15.9 15.9 15.9 15.9 15.9
Bolt-in
7.2
390 450
18R 7BCLS-18R 24R 7BCLS-24R
2 2
50 50
3 3
15.9 16 15.9 16
8.3
70 100 130 150 170
2R 3R 4R 5R 6R
8ACLS-2R 8ACLS-3R 8ACLS-4R 8ACLS-5R 8ACLS-6R
1 1 1 1 1
50 50 50 50 50
3 3 3 3 3
15.9 15.9 15.9 15.9 15.9
7.2
200 230 390 450
9R 12R 18R 24R
7ACLS-9R 7ACLS-12R 7ACLS-18R 7ACLS-24R
1 1 2 2
50 50 50 50
3 3 3 3
15.9 8 15.9 8 15.9 17 15.9 17
450 650 700
24R 7CLS70-24R 2 36R 7CLS70-36R 3 44R 7CLS70-44R 2
50 50 50
3 3 4
15.9 20 15.9 30 15.9 40
For use with AMPGARD 800 A Motor Starters
15 30 60 70 90 110 125
8CLS-15 8CLS-30 8CLS-60 8CLS-70 8CLS-90 8CLS-110 8CLS-125
1 1 1 1 1 1 1
50 50 50 50 50 50 50
3 3 3 3 3 3 3
14 14 14 14 14 14 14
17.9 17.9 17.9 17.9 17.9 17.9 17.9
NonDisconnect
75 8CLE-PNM-D
8CLE-GNM-D
CLE-NL-D
—
Disconnect
75 8CLE-PDM-D
8CLE-GDM-D
CLE-DL-D
CLS-DF-D
150 200 225
8CLS-150 8CLS-200 8CLS-225
2 2 2
50 50 50
3 3 3
14 17.9 22 14 17.9 22 14 17.9 22
NonDisconnect
75 8CLE-PNM-E
8CLE-GNM-E
CLE-NL-E
—
Disconnect
75 8CLE-PDM-E
8CLE-GDM-E
CLE-DL-E
CLE-DF-E
Includes end fittings. Disconnect only. Not applicable.
CA08101001E
For more information visit: www.eaton.com
Peak Let-Through Current
Total Clearing Time
66740205
11 11 11 11 11 11 11
For use with AMPGARD 400 A Motor Starters
66679802
8 8 8 8 8
66700702
8.3
7 7 7 7 7 7 7
66700205
CLE-NL-D
66740205
8HLE-GNM-D
66700702
75 8HLE-PNM-D
66700702
NonDisconnect
66664302
7 7
Minimum Melting Time
7 7 7 7 7
End Fittings
66700602
15.9 15.9 15.9 15.9 15.9
Live Parts
66700602
12 12 12 12 12
GlassPolyester
66700602
3 3 3 3 3
Porcelain
Performance Curves
66664202
50 50 50 50 50
Catalog Number
Catalog Number
Type Voltage (BIL) kV
Length (Inches)
1 1 1 1 1
Approx. Shipping Weight (Lbs.)
Clip Center (Inches)
8CLS-2R 8CLS-3R 8CLS-4R 8CLS-5R 8CLS-6R
Diameter (Inches)
“R” Designation 2R 3R 4R 5R 6R
Interrupting Rating rms (kA Sym.)
70 100 130 150 170
Mounting (Includes Live Parts, End Fittings)
Barrel Number
8.3
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
13
13-70
Power Breakers, Contactors & Fuses Current Limiting Fuses February 2007
Types CLS and BCLS
Fuse Dimensional Details — Inches
3.56 Ref.
15.85 ±
± .06 for 2CLS
10.81 ± .06 for 2CLS 15.85 ± .06 for 5, 7 & 8CLS
Figure 13-19. CLS Fuse
.455 Dia. x .91 Slot (4) 1.53
13
3.31 2.12 3.00 Ref.
17.88 19.25
17.88 ± .06 19.25 Ref.
3.00 Ref.
Type 5BCLS & 7BCLS Fuses
1.53
3.00 Ref.
12.81 ± .06 14.18 ± .06
12.81 ± .06 14.18 ± .06
3.00 Ref.
Type 2BCLS Fuse
Figure 13-20. BCLS Fuse
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-71
February 2007
Type CLPT Table 13-58. Type CLPT Current Limiting Fuses
Approx. Shipping Weight (lbs.)
— — — — —
4.5 4.5 4.5 4.5 4.5
0.25 Not applicable. 0.25 0.25 0.25 0.25
Voltage (BIL) kV
GlassPolyester
Live Parts
End Fittings
Peak Let-Through Current
Length (Inches)
0.81 0.81 0.81 0.81 0.81
Porcelain
Performance Curves
Total Clearing Time
Clip Center (Inches)
63 63 40 40 25
Catalog Number
Type
Catalog Number
Minimum Melting Time
Diameter (Inches)
Mounting (Includes Live Parts, End Fittings)
Interrupting Rating rms
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
59883702
63933702 66704101
2NCLPT-.25E 2NCLPT-.5E 2NCLPT-1E 2NCLPT-2E 2NCLPT-5E
66702502
0.25E 0.5E 1E 2E 5E
56357202
Indicating
66702402
2.475 kV Maximum (2.4 kV Nominal)
— — — — — — — — — — —
5.63 5.63 5.63 5.63 5.63 5.63 5.63 5.63 5.63 5.63 5.63
0.25 Not applicable. 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
0.5E 1E 1.5E 3E 5E 10E
5CLPT-.5E 5CLPT-1E 5CLPT-1.5E 5CLPT-3E 5CLPT-5E 5CLPT-10E
80 80 80 80 80 80
1.6 1.6 1.6 1.6 1.6 1.6
8.1 8.1 8.1 8.1 8.1 8.1
9.5 9.5 9.5 9.5 9.5 9.5
1.2 1.2 1.2 1.2 1.2 1.2
NonDisconnect
60 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
Disconnect
60 5CLPT-PDM-A 5CLPT-GDM-A CLPT-DL CLPT-DF
0.5E 1E 2E 3E 5E 10E
5NCLPT-.5E-A 5NCLPT-1E-A 5NCLPT-2E-A 5NCLPT-3E-A 5NCLPT-5E-A 5NCLPT-10E-A
63 63 63 63 63 63
1.6 1.6 1.6 1.6 1.6 1.6
8.1 8.1 8.1 8.1 8.1 8.1
9.5 9.5 9.5 9.5 9.5 9.5
1.2 1.2 1.2 1.2 1.2 1.2
NonDisconnect
60 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
0.81 0.81 1.1 1.1 1.1
8 8 5 5 5
0.25 Not applicable. 0.25 0.5 0.5 0.5
9.5
1.5
Disconnect 60 5CLPT-PDM-A 5CLPT-GDM-A CLPT-DL CLPT-DF
63934001
0.81 0.81 0.81 0.81 0.81 0.81 1 1 1 1 1
63934002
63 63 63 63 63 63 50 50 50 50 50
56353306
5NCLPT-.5E 5NCLPT-1E 5NCLPT-2E 5NCLPT-3E 5NCLPT-4E 5NCLPT-5E 317B487H02 317B487H06 317B487H03 317B487H04 317B487H05
70548402
Indicating
0.5E 1E 2E 3E 4E 5E 0.5E 1E 2E 3E 5E
70548302
Non-Indicating
56353206
5.5 kV Maximum (4.8 kV Nominal)
25 25 50 50 50
.5E
8CLPT-.5E
80 1.6
8.1
Disconnect
75 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
3E 5E 10E
8CLPT-3E 8CLPT-5E 8CLPT-10E
80 1.6 50 1.6 50 1.6
11.5 12.9 1.5 11.5 12.9 1.5 11.5 12.9 1.5
NonDisconnect
75 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —
Disconnect
75 8CLPT-PDM-B 8CLPR-GDM-B CLPT-DL CLPT-DF
0.5E 1E 2E
8NCLPT-.5E-A 8NCLPT-1E-A 8NCLPT-2E-A
50 1.6 50 1.6 50 1.6
8.1 8.1 8.1
NonDisconnect
75 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
3E 5E 10E
8NCLPT-3E-A 50 1.6 8NCLPT-5E-A 50 1.6 8NCLPT-10E-A 50 1.6
Disconnect
75 8CLPT-PDM-B 8CLPT-GDM-B CLPT-DL CLPT-DF
Includes end fittings. Disconnect only.
CA08101001E
For more information visit: www.eaton.com
63934001
75 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —
63934002
75 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
NonDisconnect
56353306
Disconnect
70548403
11.5 12.9 1.6 11.5 12.9 1.6 11.5 12.9 1.6
56353206
1.5 1.5 1.5
75 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
70548303
9.5 9.5 9.5
NonDisconnect
63933704
8NCLPT-2E 8NCLPT-4E 8NCLPT-1E 8NCLPT-5E 8NCLPT-0E
59883706
2E 4E 1E 5E 10E
56357206
8.3 kV Maximum (7.2 kV Nominal)
13
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-72
February 2007
Type CLPT
Live Parts
End Fittings
Peak Let-Through Current
GlassPolyester
Minimum Melting Time
Porcelain
Performance Curves
Total Clearing Time
Catalog Number
Catalog Number
Type Voltage (BIL) kV
Approx. Shipping Weight (lbs.)
Mounting (Includes Live Parts, End Fittings) Length (Inches)
Clip Center (Inches)
Diameter (Inches)
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
Interrupting Rating rms
Table 13-58. Type CLPT Current Limiting Fuses (Continued)
—
Disconnect 95 15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL
CLPT-DF
3E 5E 10E
15CLPT-3E 15CLPT-5E 15CLPT-10E
80 1.6 80 1.6 50 1.6
16.1 17.6 1.6 16.1 17.6 1.6 16.1 17.6 1.6
Non95 15CLPT-PNM-B 15CLPT-GNM-B CLPT-NL Disconnect
—
Disconnect 95 15CLPT-PDM-B
CLPT-DF
0.5E 1E 2E
15NCLPT-.5E 63 1.6 15NCLPT-1E 63 1.6 15NCLPT-1.5E 63 1.6
11.5 12.9 1.6 11.5 12.9 1.6 11.5 12.9 1.6
Non95 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL Disconnect
—
Disconnect 95 15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL
CLPT-DF
3E 5E 10E
15NCLPT-3E 15NCLPT-5E 15NCLPT-10E
63 1.6 63 1.6 63 1.6
16.1 17.6 1.6 16.1 17.6 1.6 16.1 17.6 1.6
Non95 15CLPT-PNM-B 15CLPT-GNM-B CLPT-NL Disconnect
—
Disconnect 95 15CLPT-PDM-B
CLPT-DF
44 1.6 44 1.6
16.1 17.6 2 16.1 17.6 2
NonDisconnect
15CLPT-GDM-B CLPT-DL
15CLPT-GDM-B CLPT-DL
63934001
Non95 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL Disconnect
63934002
11.5 12.9 1.6 11.5 12.9 1.6 11.5 12.9 1.6
56353306
80 1.6 80 1.6 80 1.6
70548403
15CLPT-.5E 15CLPT-1E 15CLPT-1.5E
70548303
0.5E 1E 2E
56353206
15.5 kV Maximum (7.2 kV Nominal)
25CLPT-DL CLPT-DF
63933901
Disconnect
13
25CLPT-NL —
63933901
Not applicable.
56353308
25CLPT-.5E 25CLPT-1E
56353308
0.5E 1E
56353208
25.5 kV Maximum (14.4 kV Nominal)
0.5E
38CLPT-.5E
44 1.6
17.1 18.6 2
NonDisconnect
Not applicable.
Disconnect
25CLPT-NL — 25CLPT-DL CLPT-DF
56353208
38.0 kV Maximum (34.5 kV Nominal)
Includes end fittings. Disconnect only.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-73
February 2007
Type CLPT Table 13-59. Type CLPT Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings)
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Porcelain Insulator
Glass-Polyester Insulator
Catalog Number
Catalog Number
Catalog Number
Catalog Number
CLPT Mountings and Hardware 2.475 kV Maximum (2.4 kV Nominal) Consult Factory
CLPT Mountings and Hardware 5.5 kV Maximum (4.8 kV Nominal) 0.5 to 1.5
Non-Disconnect Disconnect
60 60
5CLPT-PNM-A 5CLPT-PDM-A
5CLPT-GNM-A 5CLPT-GDM-A
CLPT-NL —
— —
3 to 10
Non-Disconnect Disconnect
60 60
5CLPT-PNM-B 5CLPT-PDM-B
5CLPT-GNM-B 5CLPT-GDM-B
CLPT-NL —
— —
0.5
Non-Disconnect Disconnect
75 75
8CLPT-PNM-A 8CLPT-PDM-A
8CLPT-GNM-A 8CLPT-GDM-A
CLPT-NL CLPT-DL
— CLPT-DF
3 to 10
Non-Disconnect Disconnect
75 75
8CLPT-PNM-B 8CLPT-PDM-B
8CLPT-GNM-B 8CLPT-GDM-B
CLPT-NL CLPT-DL
— CLPT-DF
0.5 to 1.5
Non-Disconnect Disconnect
95 95
15CLPT-PNM-A 15CLPT-PDM-A
15CLPT-GNM-A 15CLPT-GDM-A
CLPT-NL CLPT-DL
— CLPT-DF
3 to 10
Non-Disconnect Disconnect
95 95
15CLPT-PNM-B 15CLPT-PDM-B
15CLPT-GNM-B 15CLPT-GDM-B
— —
— —
Non-Disconnect Disconnect
150 150
25CLPT-PNM-A 25CLPT-PDM-A
— —
25CLPT-NL 25CLPT-DL
— —
CLPT Mountings and Hardware 8.3 kV Maximum (7.2 kV Nominal)
CLPT Mountings and Hardware 15.5 kV Maximum (14.4 kV Nominal)
CLPT Mountings and Hardware 25.5 kV Maximum (23.0 kV Nominal) 0.5 to 1.5
CLPT Mountings and Hardware 38.0 kV Maximum (34.5 kV Nominal) Consult Factory
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
CA08101001E
For more information visit: www.eaton.com
13
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-74
February 2007
Type CX Table 13-60. Type CX Current Limiting Fuses
Length (Inches)
Approx. Shipping Weight (lbs.)
1 1 1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50 50 50
1.13 1.13 2 2 2 2 2 2 2 2
10 10 10 10 10 10 10 10 10 10
1 1 1 2 2 2 2 2 2 2
Non60 5CX-GNM-G Disconnect
CX-NL
—
70544101
70544501
Disconnect 60 5CX-GDM-G
CX-DL
CX-DF
70544102
70544502
70544101
70544501
70544102
70544502
70544101
70544501
1 1 1 1 1 1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50 50 50 50 50 50
1.13 1.13 1.13 1.13 2 2 1.13 2 2 2 2 2 2
10 10 10 10 10 10 10 10 10 10 10 10 10
1 1 1 1 2 2 1 2 2 2 2 2 2
Non60 5CX-GNM-G Disconnect
CX-NL
70544201
70544601
70544202
70544602
70544201
70544602
Disconnect 60 5CX-GDM-G
CX-DL
70544202
70544602
70544201
70544602
70544202
70544602
70544201
70544601
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 2 2 2 2 2 2
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Non75 8CX-GNM-G Disconnect
70544302
70544702
70544301
70544701
70544302
70544702
70544301
70544701
70544302
70544702
70544301
70544701
70544302
70544702
70544301
70544701
50 50 50 50 50 50 50 50 50 50 50 50
2 2 2 2 2 2 2 2 2 2 2 2
14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3
70544401
70544801
70544402
70544802
70544101
70544801
70544402
70544802
Voltage (BIL) kV
Diameter (Inches)
Performance Curves
Interrupting Rating rms (kA Sym.)
Mounting (Includes Live Parts, Catalog Number End Fittings) Type
Barrel Number
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
Catalog Number GlassPolyester
End Minimum Total Live Parts Fittings Melting Clearing Time Time
Peak LetThrough Current
I2t
70544901
70545101
70544902
70545201
70545001
70545301
70545002
40545401
4.3 kV Maximum (2.4 kV Nominal) 18C 25C 35C 45C 50C 60C 65C 75C 80C 100C
4CX-18C 4CX-25C 4CX-35C 4CX-45C 4CX-50C 4CX-60C 4CX-65C 4CX-75C 4CX-80C 4CX-100C
5.5 kV Maximum (4.8 kV Nominal) 10C 12C 18C 20C 21C 25C 30C 35C 40C 50C 60C 65C 75C
13
5CX-10C 5CX-12C 5CX-18C 5CX-20C 5CX-21C 5CX-25C 5CX-30C 5CX-35C 5CX-40C 5CX-50C 5CX-60C 5CX-65C 5CX-75C
—
CX-DF
8.3 kV Maximum (7.2 kV Nominal) 3.5C 4C 4.5C 6C 7C 8C 10C 12C 15C 18C 20C 25C 30C 35C 40C
8CX-3.5C 8CX-4C 8CX-4.5C 8CX-6C 8CX-7C 8CX-8C 8CX-10C 8CX-12C 8CX-15C 8CX-18C 8CX-20C 8CX-25C 8CX-30C 8CX-35C 8CX-40C
Disconnect 75 8CX-GDM-G
CX-NL
CX-DL
—
CX-DF
15.5 kV Maximum (14.4 kV Nominal) 4C 6C 7C 8C 10C 12C 15C 18C 20C 25C 30C 40C
15CX- 4C 15CX- 6C 15CX- 7C 15CX- 8C 15CX- 10C 15CX- 12C 15CX- 15C 15CX- 18C 15CX- 20C 15CX- 25C 15CX- 30C 15CX- 40C
1 1 1 1 1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2 2 2 2 2
Non95 15CX-GNM-G Disconnect
CX-NL
Disconnect 95 15CX-GDM-G
CX-DL
—
CX-DF
Includes end fittings. Disconnect only.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-75
February 2007
Type CX Table 13-61. Type CX Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Size
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings)
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Porcelain Insulator
Glass-Polyester Insulator
Catalog Number
Catalog Number
Catalog Number
Catalog Number
CX Mountings and Hardware 4.3 kV Maximum (2.4 kV Nominal) 18C to 100C
Non-Disconnect Disconnect
A
60 60
— —
5CX-GNM-G 5CX-GDM-G
CX-NL CX-DL
— CX-DF
Non-Disconnect Disconnect
A
60 60
— —
5CX-GNM-G 5CX-GDM-G
CX-NL CX-DL
— CX-DF
Non-Disconnect Disconnect
B
75 75
— —
8CX-GNM-G 8CX-GDM-G
CX-NL CX-DL
— CX-DF
Non-Disconnect Disconnect
C
95 95
— —
15CX-GNM-G 15CX-GDM-G
CX-NL CX-DL
— CX-DF
CX Mountings and Hardware 5.5 kV Maximum (4.8 kV Nominal) 10C to 75C
CX Mountings and Hardware 8.3 kV Maximum (7.2 kV Nominal) 3.5C to 40C
CX Mountings and Hardware 15.5 kV Maximum (14.4 kV Nominal) 4C to 40C
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
13
CA08101001E
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-76
February 2007
Type CXN
Diameter (Inches)
Length (Inches)
Approx. Shipping Weight (lbs.)
1 1 1 1 1 1
50 50 50 50 50 50
3 3 4 4 4 4
18.8 18.8 18.8 18.8 18.8 18.8
8 8 14 14 14 14
Catalog Number
Performance Curves
Live Parts
End Fittings
Minimum Total Peak I2t Melting Clearing LetTime Time Through Current
66675102
66675202 66664902
66675104
66675204
Type
Voltage (BIL) kV
Interrupting Rating rms (kA Sym.)
Mounting (Includes Live Parts, End Fittings)
Barrel Number
Catalog Number
Current Rating (Amperes)
Maximum Design Voltage (kV)
Table 13-62. Type CXN Current Limiting Fuses
NonDisconnect
95 15CXN-GNM-D
15CXN-NL-D
—
Disconnect
95 15CXN-GDM-G
15CXN-DL-G
15CXN-DF-G
NonDisconnect
95 15CXN-GNM-F
15CXN-NL-F
—
NonDisconnect
95 15CXN-GNM-G
15CXN- NL-G
Disconnect
95 15CXN-GDM-F
15CXN-DL-F
NonDisconnect
95 15CXN-GNM-D
15CXN-NL-D
Disconnect
95 15CXN-GNM-F
15CXN-NL-F
NonDisconnect
95 15CXN-GNM-F
15CXN-NL-F
NonDisconnect
95 15CXN-GNM-G
15CXN-NL-G
Disconnect
95 15CXN-GDM-G
15CXN-DL-G
15CXN-DF-G
NonDisconnect
95 15CXN-GNM-F
15CXN-NL-F
—
NonDisconnect
95 15CXN-GNM-G
15CXN-NL-G
Catalog Number GlassPolyester
8.3 kV Maximum 60C 100C 125C 150C 200C 250C
120C 200C 250C 300C
8CXN-60C 8CXN-100C 8CXN-125C 8CXN-150C 8CXN-200C 8CXN-250C
8CXN-120C 8CXN-200C 8CXN-250C 8CXN-300C
2 2 2 2
50 50 50 50
3 3 3 4
18.8 18.8 18.8 18.8
16 16 16 28
—
2 X 60C 2 X 100C 2 X 125C 2 X 150C
15.5 kV Maximum 45C 60C 75C 85C 100C
13
15CXN-45C 15CXN-60C 15CXN-75C 15CXN-85C 15CXN-100C
1 1 1 1 1
50 50 50 50 50
3 3 4 4 4
18.8 18.8 18.8 18.8 18.8
8
8 14 14 14
Disconnect
95 15CXN-GDM-F
15CXN-DL-F
90C 15CXN-90C 120C 15CXN-120C
2 2
50 50
3 3
18.8 16 18.8 16
NonDisconnect
95 15CXN-GNM-D
15CXN-NL-D
150C 15CXN-150C 175C 15CXN-175C
2 2
50 50
4 4
18.8 28 18.8 28
NonDisconnect
95 15CXN-GNM-F
15CXN-NL-F
—
—
66674802
66675002 66665002
66674804
66675004 2 X 45C 2 X 60C 2 X 75C 2 X 85C
Includes end fittings. Disconnect only.
Table 13-63. Type CXN Current Limiting Fuses Ampere Rating
Fuse Mounting Type
Voltage BIL (kV)
Mounting (Including Live Parts, End Fittings) Porcelain Insulator
Live Parts (Including End Fittings)
End Fittings (Disconnect Only)
Catalog Number
Catalog Number
Glass-Polyester Insulator Catalog Number
Catalog Number
CXN Mountings and Hardware 8.3 kV Maximum (7.2 kV Nominal) 60C to 100C
Non-Disconnect Non-Disconnect Disconnect
95 95 95
— — —
15CXN-GNM-D 15CXN-GNM-G 15CXN-GDM-G
15CXN-NL-D 15CXN-NL-G 15CXN-DL-G
— — 15CXN-DF-G
125C to 250C
Non-Disconnect Non-Disconnect Disconnect
95 95 95
— — —
15CXN-GNM-F 15CXN-GNM-G 15CXN-GDM-F
15CXN-NL-F 15CXN-NL-G 15CXN-DL-F
— — 15CXN-DF-G
300C
Non-Disconnect
95
—
15CXN-GNM-F
15CXN-NL-F
—
CXN Mountings and Hardware 15.5 kV Maximum (14.4 kV Nominal) 45C to 60C
Non-Disconnect Non-Disconnect Disconnect
95 95 95
— — —
15CXN-GNM-D 15CXN-GNM-G 15CXN-GDM-G
15CXN-NL-D 15CXN-NL-G 15CXN-DL-G
— — 15CXN-DF-G
75C to 100C
Non-Disconnect Non-Disconnect Disconnect
95 95 95
— — —
15CXN-GNM-F 15CXN-GNM-G 15CXN-GDM-F
15CXN-NL-F 15CXN-NL-G 15CXN-DL-F
— — 15CXN-DF-G
120C
Non-Disconnect
95
—
15CXN-GNM-D
15CXN-NL-D
—
150C and 175C
Non-Disconnect
95
—
15CXN-GNM-F
15CXN-NL-F
—
See Page 13-79 for diagram of typical mounting. End fittings supplied only when required.
For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-77
February 2007
Type DSL Table 13-64. Type DSL Low Voltage Current Limiting Fuse Fuse Type/Voltage
Catalog Number
Diameter Inches (mm)
Length Inches (mm)
Interrupting Rating Amperes, rms (Symmetrical)
Application Data (Time Current Curves)
6DSL-A150 6DSL-A200 6DSL-A250 6DSL-A300 6DSL-A400 6DSL-A600 6DSL-A800
— — — — — — —
— — — — — — —
200,000 200,000 200,000 200,000 200,000 200,000 200,000
33 – 792 (2) 33 – 792 (2) 33 – 792 (2) 33 – 792 (2) 33 – 792 (2) 33 – 792 (2) 33 – 792 (2)
3.00 (1.4) 3.00 (1.4) 3.00 (1.4) 3.00 (1.4) 3.00 (1.4) 3.00 (1.4) 3.00 (1.4)
6DSL-B1200 6DSL-B1600 6DSL-B2000
— — —
— — —
200,000 200,000 200,000
33 – 792 (2) 33 – 792 (2) 33 – 792 (2)
4.00 (1.8) 4.00 (1.8) 4.00 (1.8)
6DSL-C800 6DSL-C1000 6DSL-C1200 6DSL-C1600 6DSL-C2000
— — — — —
— — — — —
200,000 200,000 200,000 200,000 200,000
33 – 792 (3) 33 – 792 (3) 33 – 792 (3) 33 – 792 (3) 33 – 792 (3)
5.50 (2.5) 5.50 (2.5) 5.50 (2.5) 5.50 (2.5) 5.50 (2.5)
6DSL-D2500 6DSL-D3000
— —
— —
200,000 200,000
33 – 792 (3) 33 – 792 (3)
8.50 (3.9) 8.50 (3.9)
6DSL-E2500 6DSL-E3000 6DSL-E4000
— — —
— — —
200,000 200,000 200,000
33 – 792 33 – 792 33 – 792
20.00 (9.1) 20.00 (9.1) 20.00 (9.1)
6DSL-F5000
—
—
200,000
33 – 792
24.00 (10.9)
Approximate Ship Wt. Lbs. (kg)
Type DSL Fuse Units 600 Volts Nominal
13
CA08101001E
For more information visit: www.eaton.com
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-78
February 2007
Type CXF
11.85
6.5
100 8CXF-100 125 8CXF-125 17.2
15.5
6 8 10 12 18
15CXF-6 15CXF-8 15CXF-10 15CXF-12 15CXF-18
20 25 30 40 50
15CXF-20 15CXF-25 15CXF-30 15CXF-40 15CXF-50
65 15CXF-65 80 15CXF-80
50
50
2.25
3.32
12.24
14.66
2
8
100 15CXF-100 23
6 8 10 12 18
23CXF-6 23CXF-8 23CXF-10 23CXF-12 23CXF-18
20 25 30 40 50
23CXF-20 23CXF-25 23CXF-30 23CXF-40 23CXF-50
50
2.25
15.05
4
Non— Disconnect
—
CXN-NL-G
—
Disconnect —
—
CXN-DL-G
CXN-DF-G
Non95 Disconnect
15CX-GNM-G CX-NL
—
Disconnect 95
15CX-GDM-G CX-DL
CX-DF
Non— Disconnect
—
CXN-NL-G
—
Disconnect —
—
CXN-DL-G
CXN-DF-G
Non— Disconnect
—
CX-NL
—
Disconnect —
—
CX-DL
CX-DF
For more information visit: www.eaton.com
Maximum Total (Amp2Sec)
CX-DF
I2t
Minimum Melt (Amp2Sec)
CX-DL
Peak Let-Through Current
8CX-GDM-G
70541902
Disconnect 75
70541902
—
Total Clearing Time
CX-NL
Voltage (BIL) kV
8CX-GNM-G
70541902
3.32
Non75 Disconnect
70541902
50
2
CXN-DF-G
70541902 70541902
65 8CXF-65 80 8CXF-80
7.93
CXN-GL-G
70541202
8CXF-20 8CXF-25 8CXF-30 8CXF-40 8CXF-50
2.25
—
70541802
20 25 30 40 50
50
Disconnect —
70541402
13
8CXF-6 8CXF-8 8CXF-10 8CXF-12 8CXF-18
—
70541802
8.3
6 8 10 12 18
CXN-NL-G
70541802 66704602
10
—
Minimum Melting Time
Non— Disconnect
70541102
6.5
End Fittings
70541702
11.85
Live Parts
70541302
3.32
Catalog Number
Type
Performance Curves
70541702
Approximate Shipping Weight (Lbs.)
50
125 5CXF-125 150 5CXF-150 200 5CXF-200
Catalog Number
70541702 66704202
Tube Length (Inches)
80 5CXF-80 100 5CXF-100
Mounting
Tube Diameter (Inches)
5.5
Current Rating (Amperes)
Maximum Design Voltage (kV)
Catalog Number
Interrupting Rating (rms kA Sym.)
Table 13-65. Type CXF Indicated Full-Range Current-Limiting Fuses
22,100 56,700
110,000 280,000
78,300 380,000 176,000 860,000 259,000 1,270,000 620 800 800 920 1,310
2,700 4,000 4,000 8,000 9,500
1,620 3,660 5,250 8,700 12,800
11,000 22,000 30,000 50,000 70,000
25,200 47,200
100,000 185,000
78,300 115,150
330,000 480,000
620 800 800 920 1,310
2,600 3,700 3,700 6,500 8,000
1,620 3,660 5,250 8,700 12,800
10,000 22,000 30,000 50,000 70,000
25,200 39,400
110,000 185,000
80,000
380,000
620 800 800 920 1,310
3,100 4,800 4,800 8,300 11,200
1,620 3,660 5,250 8,700 12,800
13,000 28,000 38,000 61,000 82,000
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-79
February 2007
Typical Fuse Mounting
Typical Fuse Mounting for Current Limiting Fuses
Figure 13-21. Single Barrel Disconnect with 2-Inch (50.8 mm) Diameter CLE Fuses
Figure 13-25. Disconnect (CX)
Figure 13-29. Disconnect (15CXN-GNM-G)
13 Figure 13-22. Single Barrel Disconnect All 3-Inch (76.2 mm) Diameter CLE Fuses
Figure 13-26. Single-Barrel Non-Disconnect All 2-Inch (50.8 mm) and 3-Inch (76.2 mm) Diameter CL Fuses
Figure 13-23. Double Barrel Disconnect All 3-Inch (76.2 mm) Diameter CLE Fuses
Figure 13-27. Double-Barrel Non-Disconnect All 2-Inch (50.8 mm) and 3-Inch (76.2 mm) Diameter CL Fuses
Figure 13-24. Non-Disconnect (CX)
Figure 13-28. Non-Disconnect (15CXN-GNM-G)
CA08101001E
For more information visit: www.eaton.com
Figure 13-30. Non-Disconnect (15CXN-GNM-F and 15CXN-GNM-D)
Figure 13-31. Disconnect (15CXN-GNM-F)
13-80
Power Breakers, Contactors & Fuses Current Limiting Fuses February 2007
Pricing Table 13-66. Pricing Catalog Number 121DBA2-100E 121DBA2-10E 121DBA2-125E 121DBA2-150E 121DBA2-15E 121DBA2-200E 121DBA2-20E 121DBA2-25E 121DBA2-30E 121DBA2-3E 121DBA2-40E 121DBA2-50E 121DBA2-5E 121DBA2-65E 121DBA2-7E 121DBA2-80E
13
145DBA2-100E 145DBA2-10E 145DBA2-125E 145DBA2-150E 145DBA2-15E 145DBA2-200E 145DBA2-20E 145DBA2-25E 145DBA2-30E 145DBA2-3E 145DBA2-40E 145DBA2-50E 145DBA2-5E 145DBA2-65E 145DBA2-7E 145DBA2-80E 14RBA2-DL 14RBA2-GDM 14RBA2-GNM 14RBA2-PDM 14RBA2-PNM 14RBA4-GDM 14RBA4-GNM 14RBA4-PDM 14RBA4-PNM 14RBA8-GNM 14RBA8-PNM 15CLE-100E 15CLE-10E-D 15HLE-10E 15CLE-125E 15CLE2-125X 15CLE-40E 15CLE-150E 15CLE-50E 15CLE-15E 15CLE-15E-D 15HLE-15E 15CLE-65E 15CLE-175E 15CLE-200E 15CLE-20E 15CLE-20E-D 15HLE-20E 15CLE2-100E 15CLE2-125X 15CLE-250E 15CLE-25E 15CLE-25E-D 15HLE-25E 15CLE2-80E 15CLE-300E 15HLE-30E
Pricing (Continued) Price U.S. $
Catalog Number
Pricing (Continued) Price U.S. $
15CLE3-150E 15CLE3-175E/200X 15CLE-40E 15HLE-40E 15CLE-50E 15HLE-50E 15CLE-65E 15HLE-65E 15CLE-80E 15HLE-80E 15CLE-GDM-C 15CLE-GDM-D 15CLE-GNM-C 15CLE-GNM-D 15CLE-HPDM-C 15CLE-HPDM-D 15CLE-HPNM-C 15CLE-HPNM-D 15CLE-PDM-C 15CLE-PDM-D 15CLE-PDM-E 15CLE-PNM-C 15CLE-PNM-D 15CLE-PNM-E 15CLE-100E 15CLE2-125X 15CLE-50E 15CLE-65E 15CLE-80E 15CLPT-.5E 15CLPT-1.5E 15CLPT-10E 15CLPT-1E 15CLPT-3E 15CLPT-5E 15CLPT-GDM-A 15CLPT-GDM-B 15CLPT-GNM-A 15CLPT-GNM-B 15CLPT-HPDM-A 15CLPT-HPDM-B 15CLPT-HPNM-A 15CLPT-HPNM-B 15CLPT-PDM-A 15CLPT-PDM-B 15CLPT-PNM-A 15CLPT-PNM-B 15CLT-12 15CLT-18 15CLT-30 15CLT-4 15CLT-5 15CLT-8 15CX-10C 15CX-12C 15CX-15C 15CX-18C 15CX-20C 15CX-25C 15CX-30C 15CX-40C
Catalog Number
Price U.S. $
15CX-4C 15CX-6C 15CX-7C 15CX-8C 15CX-GDM-G 15CX-GNM-G 15CXN-100C 15CXN-45C 15CXN-60C 15CXN-75C 15CXN-85C 15CXN-DF-G 15CXN-DL-F 15CXN-DL-G 15CXN-GDM-F 15CXN-GDM-G 15CXN-GNM-D 15CXN-GNM-F 15CXN-GNM-G 15CXN-NL-D 15CXN-NL-F 15CXN-NL-G 15DBA1-.5E 15DBA1-100E 15DBA1-10E 15DBA1-125E 15DBA1-150E 15DBA1-15E 15DBA1-200E 15DBA1-20E 15DBA1-25E 15DBA1-30E 15DBA1-3E 15DBA1-40E 15DBA1-50E 15DBA1-5E 15DBA1-65E 15DBA1-7E 15DBA1-80E 15HLE-100E 15HLE-10E 15HLE-125E 15HLE-150E 15HLE-15E 15HLE-175E 15HLE-200E 15HLE-20E 15HLE-250E 15HLE-25E 15HLE-30E 15HLE-40E 15HLE-50E 15HLE-65E 15HLE-80E 15HLE-GDM-D 15HLE-GDM-E 15HLE-GNM-D 15HLE-GNM-E 15HLE-PDM-D 15HLE-PDM-E 15HLE-PNM-D 15HLE-PNM-E 15NCLPT-.5E-A 15NCLPT-1E-A
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-81
February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number 15RBA2-100E 15RBA2-10E 15RBA2-125E 15RBA2-150E 15RBA2-15E 15RBA2-200E 15RBA2-20E 15RBA2-25E 15RBA2-30E 15RBA2-40E 15RBA2-50E 15RBA2-65E 15RBA2-80E 15RBA2-DH 15RBA2-IDH 15RBA2-INH 15RBA2-ISHNT 15RBA2-LBDH 15RBA2-NH 15RBA2-NL 15RBA2-PDM 15RBA2-PNM 15RBA2-SHNT 15RBA4-.5E 15RBA4-100E 15RBA4-10E 15RBA4-125E 15RBA4-150E 15RBA4-15E 15RBA4-200E 15RBA4-20E 15RBA4-250E 15RBA4-25E 15RBA4-300E 15RBA4-30E 15RBA4-3E 15RBA4-400E 15RBA4-40E 15RBA4-50E 15RBA4-5E 15RBA4-65E 15RBA4-7E 15RBA4-80E 15RBA4-DH 15RBA4-DL 15RBA4-IDH 15RBA4-INH 15RBA4-ISHNT 15RBA4-LBDH 15RBA4-LBDL 15RBA4-NH 15RBA4-NL 15RBA4-PDM 15RBA4-PNM 15RBA4-SHNT 15RBA8-INH 15RBA8-NH 15RBA8-NL 15RBA8-PNM 15RBT2-100E 15RBT2-125E 15RBT2-150E 15RBT2-200E 15RBT2-20E 15RBT2-25E 15RBT2-30E 15RBT2-40E 15RBT2-50E 15RBT2-65E 15RBT2-80E
Price U.S. $
Pricing (Continued) Catalog Number
Pricing (Continued) Price U.S. $
15RBT4-100E 15RBT4-125E 15RBT4-150E 15RBT4-200E 15RBT4-20E 15RBT4-250E 15RBT4-25E 15RBT4-300E 15RBT4-30E 15RBT4-400E 15RBT4-40E 15RBT4-50E 15RBT4-65E 15RBT4-80E 15RDB2-DH 15RDB2-HUM 15RDB2-HVM 15RDB2-SHNT 15RDB2-UM 15RDB2-VM 15RDB4-DH 15RDB4-HUM 15RDB4-SHNT 15RDB4-UM 15RDB4-VM 15RDB8-HUM 15RDB8-HVM 15RDB8-UM 15RDB8-VM 25CLPT-.5E 25CLPT-1E 25CLPT-DL 25CLPT-NL 25CLPT-PDM-A 25CLPT-PNM-A 25DBA1-.5E 25DBA1-100E 25DBA1-10E 25DBA1-125E 25DBA1-150E 25DBA1-15E 25DBA1-200E 25DBA1-20E 25DBA1-25E 25DBA1-30E 25DBA1-3E 25DBA1-40E 25DBA1-50E 25DBA1-5E 25DBA1-65E 25DBA1-7E 25DBA1-80E 25RBA2-100E 25RBA2-10E 25RBA2-125E 25RBA2-150E 25RBA2-15E 25RBA2-200E 25RBA2-20E 25RBA2-25E 25RBA2-30E 25RBA2-40E 25RBA2-50E 25RBA2-65E 25RBA2-80E
Catalog Number
Price U.S. $
25RBA2-DH 25RBA2-IDH 25RBA2-INH 25RBA2-ISHNT 25RBA2-LBDH 25RBA2-NH 25RBA2-PDM 25RBA2-PNM 25RBA2-SHNT 25RBA4-.5E 25RBA4-100E 25RBA4-10E 25RBA4-125E 25RBA4-150E 25RBA4-15E 25RBA4-200E 25RBA4-20E 25RBA4-250E 25RBA4-25E 25RBA4-300E 25RBA4-30E 25RBA4-3E 25RBA4-40E 25RBA4-50E 25RBA4-5E 25RBA4-65E 25RBA4-7E 25RBA4-80E 25RBA4-DH 25RBA4-IDH 25RBA4-INH 25RBA4-ISHNT 25RBA4-LBDH 25RBA4-NH 25RBA4-PDM 25RBA4-PNM 25RBA4-SHNT 25RBA8-INH 25RBA8-NH 25RBA8-PNM 25RBT2-100E 25RBT2-125E 25RBT2-150E 25RBT2-200E 25RBT2-20E 25RBT2-25E 25RBT2-30E 25RBT2-40E 25RBT2-50E 25RBT2-65E 25RBT2-80E 25RBT4-100E 25RBT4-125E 25RBT4-150E 25RBT4-200E 25RBT4-20E 25RBT4-250E 25RBT4-25E 25RBT4-300E 25RBT4-30E 25RBT4-40E 25RBT4-50E 25RBT4-65E 25RBT4-80E 25RDB2-DH 25RDB2-HUM 25RDB2-HVM 25RDB2-SHNT 25RDB2-UM 25RDB2-VM
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F CA08101001E
For more information visit: www.eaton.com
13
13-82
Power Breakers, Contactors & Fuses Current Limiting Fuses February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number 25RDB4-DH 25RDB4-HUM 25RDB4-HVM 25RDB4-SHNT 25RDB4-UM 25RDB4-VM 25RDB8-HUM 25RDB8-HVM 25RDB8-UM 25RDB8-VM 2ACLS-12R 2ACLS-18R 2ACLS-24R 2ACLS-25 2ACLS-2R 2ACLS-3R 2ACLS-4L 2ACLS-4R 2ACLS-5R 2ACLS-6R 2ACLS-9R
13
2CLE-100E 2CLE-10E 2CLE-125E 2CLE-150E 2CLE-15E 2CLE-200E 2CLE-20E 2CLE-225E 2CLE-250E 2CLE-25E 2CLE-300E 2CLE-30E 2CLE-350X 2CLE-400X 2CLE-40E 2CLE-450X 2CLE-50E 2CLE-65E 2CLE-80E 2CLE-GDM-C 2CLE-GDM-D 2CLE-GDM-E 2CLE-GNM-C 2CLE-GNM-D 2CLE-GNM-E 2CLE-PDM-C 2CLE-PDM-D 2CLE-PDM-E 2CLE-PNM-C 2CLE-PNM-D 2CLE-PNM-E 2CLS-200 2CLS-230 2CLS-24R 2CLS-25 2CLS-2R 2CLS-390 2CLS-3R 2CLS-4R 2CLS-5R 2CLS-6R 2CLS-GDM-D 2CLS-GDM-E 2CLS-PDM-D 2CLS-PDM-E 2CLT-12 2CLT-150 2CLT-18 2CLT-25 2CLT-30 2CLT-5 2CLT-75 2CLT-90
Price U.S. $
Pricing (Continued) Catalog Number
Pricing (Continued) Price U.S. $
2HCLS-200 2HCLS-230 2HCLS-24R 2HCLS-25 2HCLS-2R 2HCLS-390 2HCLS-3R 2HCLS-4R 2HCLS-5R 2HCLS-6R 2NCLPT-.25E 2NCLPT-.5E 2NCLPT-1E 2NCLPT-2E 2NCLPT-5E 38CLPT-.5E 38CLPT-PNM-A 38DBA1-.5E 38DBA1-100E 38DBA1-10E 38DBA1-125E 38DBA1-150E 38DBA1-15E 38DBA1-200E 38DBA1-20E 38DBA1-25E 38DBA1-30E 38DBA1-3E 38DBA1-40E 38DBA1-50E 38DBA1-5E 38DBA1-65E 38DBA1-7E 38DBA1-80E 38DBA2-.5E 38DBA2-100E 38DBA2-10E 38DBA2-125E 38DBA2-150E 38DBA2-15E 38DBA2-200E 38DBA2-20E 38DBA2-25E 38DBA2-30E 38DBA2-3E 38DBA2-40E 38DBA2-50E 38DBA2-5E 38DBA2-65E 38DBA2-7E 38DBA2-80E 38RBA2-100E 38RBA2-10E 38RBA2-125E 38RBA2-150E 38RBA2-15E 38RBA2-200E 38RBA2-20E 38RBA2-25E 38RBA2-30E 38RBA2-40E 38RBA2-50E 38RBA2-65E 38RBA2-80E 38RBA2-DH 38RBA2-DL 38RBA2-IDH 38RBA2-INH 38RBA2-ISHNT 38RBA2-NH 38RBA2-NL 38RBA2-PDM 38RBA2-PNM
Catalog Number
Price U.S. $
38RBA2-SHNT 38RBA4-.5E 38RBA4-100E 38RBA4-10E 38RBA4-125E 38RBA4-150E 38RBA4-15E 38RBA4-200E 38RBA4-20E 38RBA4-250E 38RBA4-25E 38RBA4-300E 38RBA4-30E 38RBA4-3E 38RBA4-40E 38RBA4-50E 38RBA4-5E 38RBA4-65E 38RBA4-7E 38RBA4-80E 38RBA4-DH 38RBA4-DL 38RBA4-IDH 38RBA4-INH 38RBA4-ISHNT 38RBA4-NH 38RBA4-NL 38RBA4-PDM 38RBA4-PNM 38RBA4-SHNT 38RBA8-INH 38RBA8-NH 38RBA8-NL 38RBA8-PNM 38RBT2-100E 38RBT2-125E 38RBT2-150E 38RBT2-200E 38RBT2-20E 38RBT2-25E 38RBT2-30E 38RBT2-40E 38RBT2-50E 38RBT2-65E 38RBT2-80E 38RBT4-100E 38RBT4-125E 38RBT4-150E 38RBT4-200E 38RBT4-20E 38RBT4-250E 38RBT4-25E 38RBT4-300E 38RBT4-30E 38RBT4-40E 38RBT4-50E 38RBT4-65E 38RBT4-80E 38RDB2-DH 38RDB2-HUM 38RDB2-HVM 38RDB2-SHNT 38RDB2-UM 38RDB2-VM 38RDB4-DH 38RDB4-HUM 38RDB4-HVM 38RDB4-SHNT 38RDB4-UM 38RDB4-VM
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-83
February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number 38RDB8-HUM 38RDB8-HVM 38RDB8-UM 38RDB8-VM 48DBA1-.5E 48DBA1-100E 48DBA1-10E 48DBA1-125E 48DBA1-150E 48DBA1-15E 48DBA1-200E 48DBA1-20E 48DBA1-25E 48DBA1-30E 48DBA1-3E 48DBA1-40E 48DBA1-50E 48DBA1-5E 48DBA1-65E 48DBA1-7E 48DBA1-80E 48DBA2-.5E 48DBA2-100E 48DBA2-10E 48DBA2-125E 48DBA2-150E 48DBA2-15E 48DBA2-200E 48DBA2-20E 48DBA2-25E 48DBA2-30E 48DBA2-3E 48DBA2-40E 48DBA2-50E 48DBA2-5E 48DBA2-65E 48DBA2-7E 48DBA2-80E 4ACLS-26R 4CX-100C 4CX-18C 4CX-25C 4CX-35C 4CX-45C 4CX-50C 4CX-60C 4CX-65C 4CX-75C 4CX-80C 5ACLE-100E 5AHLE-100E 5AHLE-10E 5ACLE-125E 5ACLE-150E 5AHLE-15E 5ACLE-200E 5AHLE-20E 5ACLE-225E 5ACLE-250E 5ACLE-25E 5AHLE-25E 5ACLE-300E 5ACLE-30E 5AHLE-30E 5ACLE-400X 5AHLE-40E 5ACLE-50E
Price U.S. $
Pricing (Continued) Catalog Number
Pricing (Continued) Price U.S. $
5AHLE-50E 5ACLE-65E 5AHLE-65E 5ACLE-80E 5AHLE-80E 5ACLS-12R 5ACLS-18R 5ACLS-24R 5ACLS-2R 5ACLS-30 5ACLS-3R 5ACLS-4R 5ACLS-5R 5ACLS-6R 5ACLS-9R 5AHLE-100E 5AHLE-10E 5AHLE-125E 5AHLE-150E 5AHLE-15E 5AHLE-175E 5AHLE-200E 5AHLE-20E 5AHLE-250E 5AHLE-25E 5AHLE-300E 5AHLE-30E 5AHLE-350E 5AHLE-400E 5AHLE-40E 5AHLE-450E 5AHLE-50E 5AHLE-65E 5AHLE-80E 5HLE-100E 5CLE-10E-D 5HLE-10E 5CLE1-100E 5CLE1-10E 5CLE1-125E 5CLE1-225E 5CLE-30E 5CLE1-40E 5CLE1-50E 5CLE-15E 5CLE-15E-D 5HLE-15E 5CLE1-65E 5CLE-175E 5CLE1-80E 5CLE-20E 5CLE-20E-D 5HLE-20E 5CLE2-250E/280X 5CLE2-350X 5CLE2-365X 5CLE2-400X 5CLE2-450X 5CLE-25E 5CLE-25E-D 5CLE-300E 5CLE-30E 5HLE-30E 5CLE-350E 5CLE-400E 5HLE-40E 5CLE-450E 5HLE-50E 5CLE-600E 5HLE-65E 5CLE-750E 5HLE-80E
Catalog Number
Price U.S. $
5CLE-GDM-C 5CLE-GDM-D 5CLE-GDM-E 5CLE-GNM-C 5CLE-GNM-D 5CLE-GNM-E 5CLE-PDM-C 5CLE-PDM-D 5CLE-PDM-E 5CLE-PNM-C 5CLE-PNM-D 5CLE-PNM-E 5CLPT-.5E 5CLPT-1.5E 5CLPT-10E 5CLPT-1E 5CLPT-3E 5CLPT-5E 5CLPT-GDM-A 5CLPT-GDM-B 5CLPT-GNM-A 5CLPT-GNM-B 5CLPT-PDM-A 5CLPT-PDM-B 5CLPT-PNM-A 5CLPT-PNM-B 5CLS-12R 5CLS-18R 5CLS-24R 5CLS-2R 5CLS-30 5CLS-3R 5CLS-4R 5CLS-5R 5CLS-6R 5CLS70-100E 5CLS70-125E 5CLS70-12R 5CLS70-150E 5CLS70-200E 5CLS70-24R 5CLS70-250E 5CLS70-2R 5CLS70-32R 5CLS70-36R 5CLS70-3R 5CLS70-44R 5CLS70-4R 5CLS70-5R 5CLS70-600E 5CLS70-6R 5CLS70-750E 5CLS70-80E 5CLS70-9R 5CLS75-24R 5CLS75-32R 5CLS75-36R 5CLS-9R 5CLS-GDM-D 5CLS-GDM-E 5CLS-HGDM-D 5CLS-HGDM-E 5CLS-HPDM-D 5CLS-HPDM-E 5CLS-PDM-D 5CLS-PDM-E
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F CA08101001E
For more information visit: www.eaton.com
13
13-84
Power Breakers, Contactors & Fuses Current Limiting Fuses February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number 5CLT-12 5CLT-18 5CLT-25 5CLT-30 5CLT-45 5CLT-60 5CLT-8 5CX-10C 5CX-12C 5CX-18C 5CX-20C 5CX-21C 5CX-25C 5CX-30C 5CX-35C 5CX-40C 5CX-50C 5CX-60C 5CX-65C 5CX-75C 5CX-GDM-G 5CX-GNM-G
13
5HCLS-12R 5HCLS-18R 5HCLS-24R 5HCLS-2R 5HCLS-30 5HCLS-3R 5HCLS-4R 5HCLS-5R 5HCLS-6R 5HCLS-9R 5HLE-100E 5HLE-10E 5HLE-125E 5HLE-150E 5HLE-15E 5HLE-175E 5HLE-200E 5HLE-20E 5HLE-250E 5HLE-25E 5HLE-300E 5HLE-30E 5HLE-350E 5HLE-400E 5HLE-40E 5HLE-450E 5HLE-50E 5HLE-65E 5HLE-80E 5HLE-GDM-D 5HLE-GDM-E 5HLE-GNM-D 5HLE-GNM-E 5HLE-PDM-D 5HLE-PDM-E 5HLE-PNM-D 5HLE-PNM-E 5LCLS-12R 5LCLS-18R 5LCLS-24R 5LCLS-2R 5LCLS-3R 5LCLS-4R 5LCLS-5R 5LCLS-6R 5LCLS-9R
Price U.S. $
Pricing (Continued) Catalog Number
Pricing (Continued) Price U.S. $
5NCLPT-2E 5NCLPT-3E 5NCLPT-4E 5NCLPT-5E 5RBA2-GDM 5RBA2-GNM 5RBA2-PDM 5RBA2-PNM 5RBA4-GDM 5RBA4-GNM 5RBA4-PDM 5RBA4-PNM 5RBA8-GNM 5RBA8-PNM 5SCLE-100E 5SCLE-125E 5SCLE-150E 5SCLE-200E 5SCLE-225E 5SCLE-250E 5SCLE-300E 5SCLE-400X 5SCLE-50E 5SCLE-65E 5SCLE-80E 6DSL-A150 6DSL-A200 6DSL-A250 6DSL-A300 6DSL-A400 6DSL-A600 6DSL-A800 6DSL-B1200 6DSL-B1600 6DSL-B2000 6DSL-C1000 6DSL-C1200 6DSL-C1600 6DSL-C2000 6DSL-C800 6DSL-D2500 6DSL-D3000 6DSL-E2500 6DSL-E3000 6DSL-E4000 6DSL-F5000 72DBA1-.5E 72DBA1-100E 72DBA1-10E 72DBA1-125E 72DBA1-150E 72DBA1-15E 72DBA1-200E 72DBA1-20E 72DBA1-25E 72DBA1-30E 72DBA1-3E 72DBA1-40E 72DBA1-50E 72DBA1-5E 72DBA1-65E 72DBA1-7E 72DBA1-80E
Catalog Number
Price U.S. $
72DBA2-.5E 72DBA2-100E 72DBA2-10E 72DBA2-125E 72DBA2-150E 72DBA2-15E 72DBA2-200E 72DBA2-20E 72DBA2-25E 72DBA2-30E 72DBA2-3E 72DBA2-40E 72DBA2-50E 72DBA2-5E 72DBA2-65E 72DBA2-7E 72DBA2-80E 7ACLS-12R 7ACLS-18R 7ACLS-24R 7ACLS-9R 7CLS-24R 7CLS-36R 7CLS-44R 8AHLE-100E 8AHLE-10E 8AHLE-15E 8AHLE-20E 8AHLE-25E 8AHLE-30E 8AHLE-40E 8AHLE-50E 8AHLE-65E 8AHLE-80E 8ACLS-2R 8ACLS-3R 8ACLS-4L 8ACLS-4R 8ACLS-5R 8ACLS-6R 8AHLE-100E 8AHLE-10E 8AHLE-125E 8AHLE-150E 8AHLE-15E 8AHLE-175E 8AHLE-200E 8AHLE-20E 8AHLE-250E 8AHLE-25E 8AHLE-300E 8AHLE-30E 8AHLE-350E 8AHLE-40E 8AHLE-50E 8AHLE-65E 8AHLE-80E 8CLE-100E 8HLE-100E 8CLE-10E-D 8CLE-100E 8CLE-125E 8CLE-30E 8CLE-40E 8CLE-150E 8CLE-50E
5NCLPT-.25E 5NCLPT-.5E 5NCLPT-.5E-A 5NCLPT-1E 5NCLPT-1E-A
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-85
February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number 8CLE-15E 8CLE-15E-D 8HLE-15E 8CLE-65E 8CLE-175E 8CLE-80E 8CLE-200E 8CLE-20E 8CLE-20E-D 8HLE-20E 8CLE2-100E 8CLE2-150E 8CLE-250E 8CLE-25E 8CLE-25E-D 8HLE-25E 8CLE-300E 8CLE-30E 8HLE-30E 8CLE-350E 8CLE-40E 8HLE-40E 8CLE-50E 8HLE-50E 8CLE-65E 8HLE-65E 8CLE-80E 8HLE-80E 8CLE-GDM-C 8CLE-GDM-D 8CLE-GDM-E 8CLE-GNM-C 8CLE-GNM-D 8CLE-GNM-E 8CLE-PDM-C 8CLE-PDM-D 8CLE-PDM-E 8CLE-PNM-C 8CLE-PNM-D 8CLE-PNM-E 8CLPT-.5E 8CLPT-10E 8CLPT-3E 8CLPT-5E 8CLPT-GDM-A 8CLPT-GDM-B 8CLPT-GNM-A 8CLPT-GNM-B 8CLPT-PDM-A 8CLPT-PDM-B 8CLPT-PNM-A 8CLPT-PNM-B 8CLS-110 8CLS-125 8CLS-15 8CLS-150 8CLS-200 8CLS-225 8CLS-30 8CLS-60 8CLS-70 8CLS-90
Price U.S. $
Pricing (Continued) Catalog Number
Pricing (Continued) Price U.S. $
8CX-10C 8CX-12C 8CX-15C 8CX-18C 8CX-20C 8CX-25C 8CX-3.5C 8CX-30C 8CX-35C 8CX-4.5C 8CX-40C 8CX-4C 8CX-6C 8CX-7C 8CX-8C 8CX-GDM-G 8CX-GNM-G 8CXN-100C 8CXN-125C 8CXN-150C 8CXN-200C 8CXN-250C 8CXN-60C 8DBA1-.5E 8DBA1-100E 8DBA1-10E 8DBA1-125E 8DBA1-150E 8DBA1-15E 8DBA1-200E 8DBA1-20E 8DBA1-25E 8DBA1-30E 8DBA1-3E 8DBA1-40E 8DBA1-50E 8DBA1-5E 8DBA1-65E 8DBA1-7E 8DBA1-80E 8HLE-100E 8HLE-10E 8HLE-125E 8HLE-150E 8HLE-15E 8HLE-175E 8HLE-200E 8HLE-20E 8HLE-250E 8HLE-25E 8HLE-300E 8HLE-30E 8HLE-350E 8HLE-40E 8HLE-50E 8HLE-65E 8HLE-80E 8HLE-GDM-D 8HLE-GDM-E 8HLE-GNM-D 8HLE-GNM-E
Catalog Number
Price U.S. $
8HLE-PDM-D 8HLE-PDM-D 8HLE-PDM-E 8HLE-PNM-E 8NCLPT-1E 8NCLPT-2E 8NCLPT-4E 8NCLPT-5E 8NCLPT-8E 8RBA2-100E 8RBA2-10E 8RBA2-125E 8RBA2-150E 8RBA2-15E 8RBA2-200E 8RBA2-20E 8RBA2-25E 8RBA2-30E 8RBA2-40E 8RBA2-50E 8RBA2-65E 8RBA2-80E 8RBA2-DH 8RBA2-GDM 8RBA2-GNM 8RBA2-IDH 8RBA2-INH 8RBA2-ISHNT 8RBA2-LBDH 8RBA2-NH 8RBA2-PDM 8RBA2-PNM 8RBA2-SHNT 8RBA4-.5E 8RBA4-100E 8RBA4-10E 8RBA4-125E 8RBA4-150E 8RBA4-15E 8RBA4-200E 8RBA4-20E 8RBA4-250E 8RBA4-25E 8RBA4-300E 8RBA4-30E 8RBA4-3E 8RBA4-400E 8RBA4-40E 8RBA4-50E 8RBA4-5E 8RBA4-65E 8RBA4-7E 8RBA4-80E 8RBA4-DH 8RBA4-GDM 8RBA4-GNM 8RBA4-IDH 8RBA4-INH 8RBA4-ISHNT 8RBA4-LBDH 8RBA4-NH 8RBA4-PDM 8RBA4-PNM 8RBA4-SHNT 8RBA8-GNM 8RBA8-INH 8RBA8-NH 8RBA8-PNM
8CLT-12 8CLT-18 8CLT-25 8CLT-30CL 8CLT-30CS 8CLT-45 8CLT-5 8CLT-8
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F CA08101001E
For more information visit: www.eaton.com
13
13-86
Power Breakers, Contactors & Fuses Current Limiting Fuses February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number 8RBT2-100E 8RBT2-125E 8RBT2-150E 8RBT2-200E 8RBT2-20E 8RBT2-25E 8RBT2-30E 8RBT2-40E 8RBT2-50E 8RBT2-65E 8RBT2-80E 8RBT4-100E 8RBT4-125E 8RBT4-150E 8RBT4-200E 8RBT4-20E 8RBT4-250E 8RBT4-25E 8RBT4-300E 8RBT4-30E 8RBT4-400E 8RBT4-40E 8RBT4-50E 8RBT4-65E 8RBT4-80E
13
8RDB2-DH 8RDB2-HUM 8RDB2-HVM 8RDB2-SHNT 8RDB2-UM 8RDB2-VM 8RDB4-DH 8RDB4-HUM 8RDB4-HVM 8RDB4-SHNT 8RDB4-UM 8RDB4-VM 8RDB8-HUM 8RDB8-HVM 8RDB8-UM 8RDB8-VM 92DBA2-100E 92DBA2-10E 92DBA2-125E 92DBA2-150E 92DBA2-15E 92DBA2-200E 92DBA2-20E 92DBA2-25E 92DBA2-30E 92DBA2-3E 92DBA2-40E 92DBA2-50E 92DBA2-5E 92DBA2-65E 92DBA2-7E 92DBA2-80E CLE-DF-C CLE-DF-D CLE-DF-E CLE-DL-C CLE-DL-D CLE-DL-E CLE-NL-C CLE-NLC-C CLE-NLC-D CLE-NLC-E CLE-NL-D CLE-NL-E
Price U.S. $
Pricing (Continued) Catalog Number
Pricing (Continued) Price U.S. $
CLS700-DUMMY CLS-BAND CX-DF CX-DL CXN-CLMP CX-NL DBU17-100E DBU17-100K DBU17-100SE DBU17-10E DBU17-10K DBU17-125E DBU17-125SE DBU17-12K DBU17-13E DBU17-140K DBU17-150E DBU17-150SE DBU17-15E DBU17-15K DBU17-15SE DBU17-175E DBU17-175SE DBU17-200E DBU17-200K DBU17-200SE DBU17-20E DBU17-20K DBU17-20SE DBU17-25E DBU17-25K DBU17-25SE DBU17-30E DBU17-30K DBU17-30SE DBU17-3K DBU17-40E DBU17-40K DBU17-40SE DBU17-50E DBU17-50K DBU17-50SE DBU17-5E DBU17-65E DBU17-65K DBU17-65SE DBU17-6K
Catalog Number
Price U.S. $
DBU27-200E DBU27-200K DBU27-200SE DBU27-20E DBU27-20K DBU27-20SE DBU27-25E DBU27-25K DBU27-25SE DBU27-30E DBU27-30K DBU27-30SE DBU27-3K DBU27-40E DBU27-40K DBU27-40SE DBU27-50E DBU27-50K DBU27-50SE DBU27-5E DBU27-65E DBU27-65K DBU27-65SE DBU27-6K DBU27-7E DBU27-80E DBU27-80K DBU27-80SE DBU27-8K DBU38-100E DBU38-100K DBU38-100SE DBU38-10E DBU38-10K DBU38-125E DBU38-125SE DBU38-12K DBU38-13E DBU38-140K DBU38-150E DBU38-150SE DBU38-15E DBU38-15K DBU38-15SE DBU38-175E DBU38-175SE
Discount Symbol for DBU fuses is Y1-FE.
DBU17-7E DBU17-80E DBU17-80K DBU17-80SE DBU17-8K DBU27-100E DBU27-100K DBU27-100SE DBU27-10E DBU27-10K DBU27-125E DBU27-125SE DBU27-12K DBU27-13E DBU27-140K DBU27-150E DBU27-150SE DBU27-15E DBU27-15K DBU27-15SE DBU27-175E DBU27-175SE
CLPT-DF CLPT-DL CLPT-NL CLPT-NLC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F For more information visit: www.eaton.com
CA08101001E
Power Breakers, Contactors & Fuses Current Limiting Fuses
13-87
February 2007
Pricing Table 13-66. Pricing (Continued) Catalog Number
Price U.S. $
DBU38-200E DBU38-200K DBU38-200SE DBU38-20E DBU38-20K DBU38-20SE DBU38-25E DBU38-25K DBU38-25SE DBU38-30E DBU38-30K DBU38-30SE DBU38-3K DBU38-40E DBU38-40K DBU38-40SE DBU38-50E DBU38-50K DBU38-50SE DBU38-5E DBU38-65E DBU38-65K DBU38-65SE DBU38-6K DBU38-7E DBU38-80E DBU38-80K DBU38-80SE DBU38-8K
13
DBU-EFID DBU-EFOD DBU-MFLR RBA2-COND RBA2-FLTR RBA2-IND RBA4-COND RBA4-FLTR RBA4-FLTR-HC RBA4-IND RDB2-UL RDB2-VL RDB4-UL RDB4-VL RDB8-UL RDB8-VL
Discount Symbol for DBU fuses is Y1-FE.
CSA is a registered trademark of the Canadian Standards Association. ISO is the registered trademark and sole property of the International Organization for Standardization. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. UL is a federally registered trademark of Underwriters Laboratories Inc. Cutler-Hammer is a federally registered trademark of Eaton Corporation. Kirk is a registered trademark of the Kirk Key Interlock Company LLC.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . Y1-F CA08101001E
For more information visit: www.eaton.com
13-88
Power Breakers, Contactors & Fuses February 2007
This page intentionally left blank.
13
For more information visit: www.eaton.com
CA08101001E