Panelboards
14-1
Panelboards
July 2007
Contents Description
Page
EZ Box and EZ Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type PRL1a Lighting Panelboard, 240 Vac Maximum . . . . . . . . . . . . . . . . . . Type PRL2a Lighting Panelboard, 480Y/277 Vac Maximum . . . . . . . . . . . . . Type PRL3a Lighting or Small Power Panelboard, 600 Vac Maximum . . . . Type PRL4 Power Distribution Panelboard, 600 Vac Maximum . . . . . . . . . . Type PRL1a-LX Column Type Panelboard, 240 Vac Maximum . . . . . . . . . . . Type PRL2a-LX Column Type Panelboard, 480Y/277 Vac Maximum . . . . . . Box Trim and Pricing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications (1a, 2a, 3a, 4, Column Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . Type PRL5P Power Distribution Panelboard, 600 Vac Maximum, Plug-on . . . . Pow-R-CommandELighting Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Renovation Panelboard PRL1R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Metering Service Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Stock Plus Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Regional Manufacturing Facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14-2 14-4 14-5 14-6 14-8 14-9 14-21 14-23 14-25 14-28 14-39 14-42 14-45 14-46 14-53 14-60 14-75 14-84 14-86 14-87
Type PRL1a Panelboard
CA08101001E
For more information visit: www.eaton.com
14
14-2
Panelboards EZ Box and EZ Trim July 2007
EZE Box and EZ Trim
Features ■ ■ ■ ■ ■ ■ ■
Virtually eliminates sharp edges. Trim installs in seconds rather than minutes. Door-in-door is standard. Ability to adjust flush box to wall irregularities. Trim installs without the need for tools. No exposed hardware (because there is none). Multipoint door latch over breakers.
The EZ box flanges are bent and painted, which virtually eliminates the sharp edges associated with traditional boxes. Additionally, all steel panelboard chassis parts are painted. This significantly reduces potential injury for material handlers and installers. Each flange is adjustable outward up to 3/4 inch. This feature allows the installer to adjust flush box applications to be level and flat with
the finished wall after the wall material is installed to help correct wall irregularities. The new box flange also provides the means for attaching the EZ trim.
Corner Flange Detail
14 Flange Detail
Eaton’s new EZ box and EZ trim represents the first significant change in panelboard box and trim designs in more than a half-century. The EZ box and EZ trim have been designed for faster, more secure and safer installations. The new EZ box and EZ trim are provided standard for Cutler-Hammer Pow-R-Line 1a and Pow-R-Line 2a lighting panelboards, as well as our Pow-R-Line 3a mid-range panelboard.
Stand-alone Trim and Bottom Flange Hanger with Notch
For more information visit: www.eaton.com
CA08101001E
Panelboards EZ Box and EZ Trim
14-3
July 2007
Fast Installation The EZ trim incorporates a patent pending, ground breaking design that installs in seconds, rather than minutes. The standard trim features include door-in-door construction; no exposed hardware and no tools are required for installation. Each EZ trim includes hangers attached on the right side. The bottom trim hanger has a notch in its base. To install, the bottom hanger is inserted into the bottom right side box flange opening, resting the notch on the flange.
Trim Hanger Inserted Into Box Flange
The balance of the hangers are aligned with the other flange openings and pushed in. When all hangers are in the box flange, the trim is lifted up slightly to clear the notch on the bottom hanger, and the trim in self-supported on the EZ box.
14 Trim Hanging on Surface Mounted Box
The installation is completed by swinging the trim to the closed position, then lifting and pushing slightly to the right. The trim will drop into place totally secured. The multi-point catches on the left side of the trim will lock into the left side box flange openings. To prevent the trim from being removed by non-authorized persons, a unique sliding means automatically latches in place when the trim door is closed. For added safety, a screw is provided to secure the latch for those who require extra security. The new EZ trim utilizes an exclusive catch system that fastens the door to multiple points. Along with a new lock, the EZ trim offers a high degree of door security.
Standards When used with Eaton’s Cutler-Hammer panelboard chassis, EZ boxes and EZ trims meet the following applicable industry standards: ULT 50 listed. NEMAT Standard PB1. ■ Federal specifications. ■ National Electrical CodeT.
■
■
New Lock Trim Installed with Door Open and Trim Sliding Latch
CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Line C Panelboards
14-4
July 2007
Product Selection
Product Types
Type PRL3a
Type PRL5P
Type PRL1a
Bolt-on Circuit Breakers 240 V, 480 V or 600 Vac; 250 Vdc Maximum
Plug-on Circuit Breakers 240 V, 480 V or 600 Vac; 250 Vdc Maximum
Bolt-on or Plug-on Circuit Breakers 240 Vac Maximum
■
Main Lugs Only 800 amperes maximum. ■ Main Circuit Breaker 600 amperes maximum. ■ Branch Circuit Breakers 225 amperes maximum, 1-, 2- and 3-pole.
Main Lugs Only 1200 amperes maximum. ■ Main Circuit Breaker 1200 amperes maximum. ■ Branch Circuit Breakers 1200 amperes maximum, 1-, 2- and 3-pole.
Main Lugs Only 400 amperes maximum. ■ Main Circuit Breaker 400 amperes maximum. ■ Branch Circuit Breakers 100 amperes maximum, 1-, 2- and 3-pole. ■
Type PRL3a
Type PRL1a
14
■
Type PRL5P
Type PRL2a
Type PRL4
Pow-R-Command
Bolt-on Circuit Breakers 240 V or 480Y/277 Vac; 125/250 Vdc Maximum
Circuit Breakers or Fusible Switches 240 V, 480 V or 600 Vac; 250 Vdc Maximum
Bolt-on Circuit Breakers 240 V or 480Y/277 Vac
Main Lugs Only 400 amperes maximum. ■ Main Circuit Breaker 400 amperes maximum. ■ Branch Circuit Breakers 100 amperes maximum, 1-, 2- and 3-pole.
■
■
■ ■ ■
■
Main Lugs Only 1200 amperes maximum. Main Circuit Breaker 1200 amperes maximum. Main Fusible Switch 1200 amperes maximum. Branch Circuit Breakers 1200 amperes maximum, 1-, 2- and 3-pole. Branch Fusible Switches 1200 amperes maximum, 2- and 3-pole.
Main Lugs Only 400 amperes maximum. ■ Main Circuit Breaker 400 amperes maximum. ■ Branch Circuit Breakers 225 amperes maximum, 1-, 2- and 3-pole. ■ Integral Power Switching Controls. ■
Type PRL2a Pow-R-Command
Type PRL4
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-5
July 2007
Product Description
Product Types (Continued)
Renovation Panelboard PRL-IR
Product Description
Type PRL1a-LX Column Type
Bolt-on Circuit Breakers 240 Vac Maximum
Lighting and Distribution Panelboards
Bolt-on Circuit Breakers 240 Vac Maximum Main Lugs Only 225 amperes maximum. ■ Main Circuit Breaker 225 amperes maximum. ■ Branch Circuit Breakers 100 amperes maximum, 1-, 2- and 3-pole. ■
Main Lugs Only 225 amperes maximum. ■ Main Circuit Breaker 225 amperes maximum. ■ Branch Circuit Breakers 100 amperes maximum, 1-, 2 and 3-pole.
■
Eaton’s Cutler-HammerT assembled panelboards are designed for sequence phase connection of branch circuit devices. This allows complete flexibility of circuit arrangement (1-, 2- or 3-poles) to allow balance of the electrical load on each phase. Sturdy, rigid chassis assembly ensures accurate alignment of interior with panel front; prevents flexing and minimizes possibility of loosening or damage to current carrying parts during and after installation. Four-point in-and-out adjustment of panel interior is provided to meet critical depth dimensions on flush installations. This compensates for possible misalignment of box at installation.
Renovation Panel
Metering Service Section Type PRL1a-LX Column Type
Type PRL2a-LX Column Type Bolt-on Circuit Breakers 240 V or 480Y/277 Vac; 125/250 Vdc Maximum
Bolt-on Circuit Breaker or Fusible Switch 240 V, 480 V or 600 Vac ■
Service entrance panels combining a main disconnect with a power company metering compartment. 400 – 1200 amperes.
Main Lugs Only 225 amperes maximum. ■ Main Circuit Breaker 225 amperes maximum. ■ Branch Circuit Breakers 100 amperes maximum, 1-, 2- and 3-pole.
■
Main lugs are mechanical solderless type and approved for copper or aluminum conductors.
Enclosures Boxes are code-gauge galvanized steel except for column type panelboards which include a painted box finished in ANSI-61 light gray to match the trim. Standard panelboard cabinets are designed for indoor use. Alternate types are available for indoor and special purpose applications. All enclosures are furnished in accordance with Underwriters Laboratories standards and include wiring gutters with proper wire bending space. Special cabinets can be provided at an additional charge. The box dimensions shown are inside dimensions. For outside dimensions, add 1/4-inch (6.4 mm).
Metering Service Section
Standard panelboard boxes are supplied without knockouts (blank endwalls).
Fronts Fronts (trims) for all panelboards are made of code-gauge steel and have a high durability ANSI-61 light gray finish applied by a baked-on polyester powder coating paint system.
Type PRL2a-LX, Column Type
CA08101001E
For more information visit: www.eaton.com
14
14-6
Panelboards Pow-R-Line C Panelboards July 2007
Application Description The fronts for lighting and appliance branch circuit panelboards and small power distribution panelboards include a door with rounded corners and concealed hinges. A flush-type latch and lock assembly is included. All locks are keyed alike. These trims are available in both surface and flush mounted designs.
Application Description Panelboard Selection Factors In selecting a panelboard, the following factors must be considered: Service (voltage and frequency). Interrupting capacity (fully or series rated). ■ Ampere rating of main. ■ Ampere ratings of branches. ■ Environment. ■ ■
Panelboard Short Circuit Rating The short circuit rating of Eaton’s Cutler-Hammer assembled panelboards are test verified by, and listed with, Underwriters Laboratories (ULT). Generally, these ratings are that of the lowest interrupting rated device in the panel.
14
EZ Trim Features Standard Door-in-Door with No Exposed Hardware or Sharp Edges (no Tools are Required for Installation)
Certain exceptions to this rule exist where branch devices have been UL tested in combination with specific main devices having a higher interrupting rating. Where these defined main devices and branch breaker combinations are utilized, the Series Short Circuit Rating of the assembled panelboard will be the same as the tested rating of the approved rated main device in series with the branches. Available main and branch breaker combinations are tabulated starting on Page 14-12. All combinations shown are UL tested and listed. These series ratings apply to panels having main devices, or main lug only panelboards fed remotely by the device listed in the series ratings chart as the main, for which UL listed tests were conducted.
Service Entrance Equipment The National Electrical Code (NECT) requires that: A panel used as service entrance equipment must be located near the point where the supply conductors enter the building. ■ A panelboard having main lugs only shall have a maximum of six service disconnects to de-energize the entire panelboard from the supply conductors. Where more than six disconnects are required, a main service disconnect must be provided. ■ A disconnectable electrical bond must be provided between the neutral and ground. ■
The Three-Piece Trim for Larger Power Distribution Panelboards Provides for Easy Handling and Installation
Fronts for power distribution panelboards utilize a unique breaker front cover design in which each device has a dedicated bolt-on steel cover. The individual covers form a single deadfront for the panelboard that is used in conjunction with two wiring gutter covers to complete the trim. A door is not finished as part of the standard offering on these panelboards but can be provided, for an additional charge, using a deeper than standard box.
For more information visit: www.eaton.com
A service entrance type UL label must be factory installed. ■ Ground fault protection of equipment shall be provided for each service disconnect rated 1000 amperes or more if the electrical service is a solidly grounded wye system of more than 150 volts to ground but not exceeding 600 volts phaseto-phase. ■
Note: Service entrance panels must be identified as such on the order.
Panelboard Classifications Panelboards are classified by NEC and UL in two general categories: Lighting and Appliance Panels and Power Distribution Panels.
Lighting and Appliance Panelboards Lighting and appliance branch circuit panelboards are defined in NEC (Article 408) as one having more than 10 percent of its overcurrent devices rated 30 amperes or less for which neutral connections are provided. Article 408 also limits the number of overcurrent devices (branch circuitpoles) to a maximum of 42 in any one cabinet. This rule applies to all panel types including PRL4 when the panel circuitry comes within the scope of this definition. When the 42 devices (poles) are exceeded, two or more separate panels are required.
Power Distribution Panelboards Distribution panelboards (all others not defined as lighting and appliance branch circuit panelboards) are restricted only to practical physical limitations such as standard box heights and widths. It is important to note that the NEC requires that the operating handle of the topmost mounted device be no more than 6 feet 7 inches (2006.6 mm) above the finished floor. Additional boxes and fronts are required when the components required for one panelboard exceed the standard box dimensions.
Multi-Section Panelboards When more than 42 overcurrent protective devices are required (See, Lighting and Appliance Panelboards), two or more separate enclosures are required. Separate fronts for each box are standard. A common front can be furnished at additional charge.
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-7
July 2007
Interconnecting Multi-Section Panelboards When a panelboard, for connection to one feeder, must be furnished in more than one section (Box), each section must be furnished with main bus and terminals of the same rating, unless a main overcurrent device is provided in each section. Sub-feed or through-feed provisions must also be included (and priced) to provide connection capability to the second section. Note: Sub-feed or through-feed lugs cannot be used on any panelboard that is not protected by a single main overcurrent device either in the panelboard or immediately upstream, i.e., service entrance panelboards with main lugs only using the six disconnect rule.
Sub-Feed Lugs
Through-Feed Lugs Through-feed lugs (see Figure 14-2) are another method to interconnect multi-section panelboards. The incoming feeder cables are connected to the main lugs or main breaker at the bottom of panel (Section 1). Another set of lugs (through-feed) are located at the opposite end of the main bus. The interconnecting cables are connected to the through-feed lugs in Section 1 and are carried over to the main lugs in Section 2. The connection arrangement could be reversed, i.e., main lugs at top; through-feed lugs at bottom end of panel. Cross cables are not furnished by Eaton. Note: Through-feed lugs may not be used on main lug only (six disconnect rule) service entrance panels. Box
Note: Sub-feed lugs may not be used on main lug only (six disconnect rule) service entrance panels. Box
Neutral Panel
Thru-Feed Lugs
1 1/2 (38.1)
Trim
Top Section View
3/4 (19.1)
Trim
Wall
Contractor to Mount Boxes 1-1/2-inch (38.1 mm) Apart to Allow for 3/4-inch (19.1 mm) Extension on Both Flush Trims Trim
3/4 (19.1)
Outside Edge of Box
Two Section Panelboard (Flush Mounting)
Neutral Main Lugs Conduit Incoming Feeder Cables Section 1
3/4 (19.1)
3/4 (19.1) 3/4 (19.1)
Section 2
Figure 14-2. Through-Feed Lugs
Neutral Panel
Panel
Wall
3/4 (19.1) 3/4 (19.1)
3/4 (19.1)
Section 2
Figure 14-1. Sub-Feed Lugs
CA08101001E
3/4 (19.1)
3/4 (19.1)
Main Lugs
Conduit Section 1
Conduit Nipple for Cross Wiring by Contractor
Cross Cables
Box
Neutral
Shown below is the standard method for flush mounting multiple section lighting and distribution panelboards using standard flush trims.
Box
Panel
Sub-feed lugs (see Figure 14-1) are one means of interconnecting multisection panels. The sub-feed (second set of) lugs are mounted directly beside the main lugs. These are required in each section except the last panel in the lineup. The feeder cables are brought into the wiring gutter of the first section and connected to the main lugs. Another set of the same size cables are connected to the subfeed lugs (Section 1) and are carried over to the main lugs of the adjacent panel. Cross connection cables are not furnished by Eaton. Sub-feed lugs are only available on main lug only panels.
Multiple Section Panelboard — Flush Mounted
For more information visit: www.eaton.com
rim Extends 3/4-inch (19.1 mm) Beyond Outside of Box on All Four Sides
Figure 14-3. Multiple Section Panelboard Flush Mounted — Dimensions in Inches (mm)
Overcurrent Protection The following requirements will be found in the NEC: Each lighting and appliance branch circuit panelboard shall be individually protected on the supply side by not more than two main circuit breakers or two sets of fuses having a combined rating not greater than that on the panelboard.
14
Panelboards Pow-R-Line C Panelboards
14-8
July 2007
Standards and Certifications
Branch Circuit Loading for Lighting and Appliance Panels The size of mains and branches should be selected based on the following: Lighting and distribution circuits: NEC Article 210, 215, 220 and 240. ■ Motor circuits: NEC Article 430. ■ Diversity factor. ■ Provision for future loading. ■
Exception Number 1: Individual protection for a lighting and appliance panelboard is not required when the panelboard feeder has overcurrent protection not greater than that of the panelboard. Exception Number 2: For existing installations, individual protection for lighting and appliance branch circuit panelboards is not required where such panelboards are used as service equipment in supplying an individual residential occupancy and where any bus supplying 15 or 20 ampere circuits is protected on the supply side by an overcurrent device.
14
Ambient Temperatures The primary function of an overcurrent device is to protect the conductor and its insulation against overheating. In selecting the size of the devices and conductors, consideration should be given to the ambient temperature surrounding the conductors within and external to the panelboard. Cumulative heating within the panelboard may cause premature operation of the overcurrent protective devices. Underwriters Laboratories test procedures are based, in part, on 80% loading of panelboard branch circuit devices. The NEC limits the loading of overcurrent devices in panelboards to 80% of rating where in normal operation the load will continue for three hours or more. Further derating may be required, depending on such factors as ambient temperature, duty cycle, frequency or altitude. Exception: There is one exception to this rule in both UL and NEC. It applies to assemblies and overcurrent devices which have been approved for continuous duty at 100% of its rating.
Special Conditions Standard panelboards, assembled with standard components, are adequate for most applications. However, special consideration should be given to those required for application under special conditions such as: ■ ■ ■ ■ ■
Excessive vibration or shock. Frequencies above 60 cycles. Altitudes above 6600 feet (2011.7 m). Damp environment (possible fungus growth). Compliance with federal, state and municipal electrical codes and standards.
Seismic Considerations The Uniform Building CodeT and the International Building Code 2003, as well as local and state building codes, place an emphasis on seismic building design requirements. Electrical distribution systems are treated as attachments to the building and therefore, fall into this category.
Electrical loads and microprocessorbased equipment are highly susceptible to both high and low energy transients. High energy transients include lightning induced surges and power company switching. These high energy transients can destroy components instantly. More frequently the electrical system experiences low energy transients and high frequency noise. The effects of continual low energy transients and high frequency noise can cause erratic equipment performance or sudden failure of electronic circuit board components. Eaton can provide protective and diagnostic systems integral to panelboards. The Clipper Power System Visor Series is integrated into the panelboards using a “zero lead length” direct bus bar connection.
All Eaton’s Cutler-Hammer panelboards are seismic qualified at the highest possible level, Seismic Zone 4, and have been tested in accordance with ANSI C37.81. This standard quantifies actual earthquake conditions, as well as equipment seismic capability.
Harmonic Currents Standard panelboard neutrals are rated for 100% of the panelboard current. However, since harmonic currents can cause overheated neutrals, an option is provided for neutrals to be rated at 200% (1200 ampere maximum neutral for 600 ampere main bus) of the panelboard phase current.
Pow-R-Line 4
The CPS Visor Series provides Transient Voltage Surge Suppression (TVSS) and active hybrid filtering. The CPS protects sensitive electronic equipment from the damaging effects of high and low energy transients, as well as high frequency noise.
Panelboards with the 200% rated neutral are UL listed as suitable for use with non-linear loads.
Standards and Certifications
Prior to specifying the 200% rated neutral, Eaton recommends a harmonic survey be conducted of the distribution system, be it new or existing.
Eaton’s Cutler-Hammer panelboards are designed to meet the following applicable industry standards, except where noted:
Transient Voltage Surge Suppression The quality of power feeding sensitive electronic loads is critical to the reliable operation of any facility. In modern offices, hospitals, and manufacturing facilities, the most frequent causes of microprocessor-based equipment downtime and damage are voltage transients and electrical noise.
For more information visit: www.eaton.com
■
Underwriters Laboratories: ❑ Panelboards: UL 67 ❑ Cabinets and Boxes: UL 50
Note: Only panelboards containing UL listed devices can be UL labeled.
National Electrical Code. NEMAT Standards: PB 1. ■ Federal Specification W-P-115c: ❑ Circuit Breakers — Type I Class I ❑ Fusible Switch — Type II Class I ■ ■
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-9
July 2007
Technical Data and Specifications
Technical Data and Specifications Selection Guide Table 14-1. Panelboard Selection Guide Panelboard Type
Device Type
Maximum Voltage Rating
Maximum Main Rating (Amperes)
ac
MLO
dc
Branch Circuits Ampere Range
Sub-Feed Breaker Maximum Amperes
AC Interrupting Capacity rms Symmetrical Amperes (kA)
Main Device
Fully Rated
Series Rated
PRL1a
Breaker
240
—
400
400
15 – 100
400
10 – 22
22 – 100
PRL2a
Breaker Breaker
240 480Y/277
250 250
400 400
400 400
15 – 100 15 – 100
400 400
65 14
65 – 200 22 – 150
PRL3a
Breaker Breaker Breaker
240 480 600
250 250 250
800 800 800
600 600 600
15 – 225 15 – 225 15 – 225
600 600 600
10 – 200 14 – 100 14 – 35
22 – 200 22 – 150 —
PRL4B
Breaker Breaker Breaker
240 480 600
250 250 250
1200 1200 1200
1200 1200 1200
15 – 1200 15 – 1200 15 – 1200
— — —
10 – 200 14 – 200 14 – 200
22 – 200 22 – 150 —
PRL4F
Fusible Fusible
240 600
250 250
1200 1200
1200 1200
30 – 1200 30 – 1200
— —
100 – 200 100 – 200
PRL1a-LX
Breaker
240
—
225
225
15 – 100
—
10 – 22
22 – 100
PRL2a-LX
Breaker Breaker
240 480Y/277
250 250
225 225
225 225
15 – 100 15 – 100
— —
65 14
65 – 200 22 – 150
PRC100/50 PRC25
Breaker Breaker
240 480Y/277
— —
400 400
400 400
15 – 225 15 – 225
— —
10 – 65 14
22 – 100 65 – 100
PRL5P
Breaker Breaker Breaker
240 480 600
250 250 250
1200 1200 1200
1200 1200 1200
15 – 1200 15 – 1200 15 – 1200
— — —
10 – 200 14 – 200 14 – 200
22 – 200 22 – 150 —
Terminal Wire Ranges, Pressure-Type Al/Cu Terminals Except as Noted
Where copper-aluminum terminals are supplied on designated panelboard types, best results are obtained if a suitable joint compound is applied when aluminum conductors are used.
Note: All terminal sizes are based on wire ampacities corresponding to those shown in NEC Table 310-16 under the 75°C insulation columns (75°C wire). The use of smaller size, (in circular mills), regardless of insulation temperature rating, is not permitted.
Check Eaton’s Cutler-Hammer standard terminal sizes versus customer requirements. In particular, 400 and
— —
800 ampere breakers often require nonstandard lugs. Optional 750 kcmil mechanical screw-type terminals are available upon request. Panelboard dimensions may be affected, refer to Eaton.
Table 14-2. Standard Main Lug Terminals Panel Type
Wire Size Ranges for Ampere Capacity 100 Ampere
225 Ampere
250 Ampere
400 Ampere
600 Ampere
800 Ampere
1200 Ampere
PRL1a PRL2a PRL3a PRL4
#12 – #1/0 #12 – #1/0 #12 – #1/0 —
#6 – 300 kcmil #6 – 300 kcmil — —
— — #6 – 350 kcmil #4 – 500 kcmil
(2) #4 – 500 kcmil (2) #4 – 500 kcmil (2) #4 – 500 kcmil (2) #4 – 500 kcmil
— — (2) #4 – 500 kcmil (2) #4 – 500 kcmil
— — (3) #4 – 500 kcmil (3) #4 – 500 kcmil
— — — (4) #4 – 500 kcmil
PRL1a-LX PRL2a-LX
#12 – #1/0 #12 – #1/0
#6 – 300 kcmil #6 – 300 kcmil
— —
— —
— —
— —
— —
PRC100 PRC50
#12 – #1/0
—
#6 – 350 kcmil
(2) #4 – 500 kcmil
—
—
—
PRC25
#12 – #1/0
#6 – 300 kcmil
—
(2) #4 – 500 kcmil
—
—
—
PRL5P
—
—
—
(1) #1/0 – 500 kcmil or (2) #1/0 – 250 kcmil
(2) #4 – 500 kcmil
(2) #2 – 500 kcmil or (3) #2 – 400 kcmil
(4) #4 – 750 kcmil
CA08101001E
For more information visit: www.eaton.com
14
Panelboards Pow-R-Line C Panelboards
14-10
July 2007
Technical Data and Specifications
Selection Guide (Continued)
Table 14-4. FDPW Switch Terminals Ampere Rating
Table 14-3. Standard Circuit Breaker Terminals Breaker Type BAB, QBHW HQP, QPHW
14
Ampere Rating 15 – 70 90 – 100
EDB, EDS, ED, EDH, EDC
100 – 225
EHD, FDB, FD, HFD, FDC
15 – 100 125 – 225
Wire Range #14 – #4 #8 – #1/0
30 60 100 200
Wire Range #14 – 1/0 #14 – 1/0 #14 – 1/0 #4 – 300 kcmil
400
250 – 750 kcmil or (2) 3/0 – 250 kcmil
#14 – 1/0 #4 – 4/0
600
(2) #4 – 600 kcmil or (4) 3/0 – 250 kcmil
#4 – 4/0 or #6 – 300 kcmil
FCL
15 – 100
#14 – 1/0
800
GHB, HGHB, GHQ
15 – 20 25 – 100
#14 – #10 #10 – 1/0
(3)250 – 750 kcmil or (6) 3/0 – 250 kcmil
1200
JD, HJD, JDC
70 – 250
(4) 250 – 750 kcmil or (8) 3/0 – 250 kcmil
#4 – 350 kcmil
DK
250 – 350 400
250 – 500 kcmil (2) 3/0 – 250 kcmil or (1) 3/0 – 500 kcmil
KD, HKD, KDC, CKD, CHKD
225 350 400
(1) #3 – 350 kcmil (1) 250 – 500 kcmil (2) 3/0 – 250 kcmil or (1) 3/0 – 500 kcmil
LGE, LGH
250 – 400 500 – 600
(1) #2 – 500 kcmil (2) #2 – 500 kcmil
LD, HLD, LDC, CLD, CHLD
300 – 500
(2) 250 – 350 kcmil
600
(2) 400 – 500 kcmil
MDL, HMDL, CMDL, CHMDL
400 – 600 700 – 800
(2) #1 – 500 kcmil (3) 3/0 – 400 kcmil
ND, HND, CND, CHND NDC, CNDC
800 – 1000 1200
(3) 3/0 – 400 kcmil (4) 4/0 – 500 kcmil
LCL
125 – 225 250 – 400
(1) #6 – 350 kcmil (1) #4 – 250 kcmil and (1) 3/0 – 600 kcmil
FB-P
15 – 100
LA-P
70 – 225 250 – 400
#6 – 350 kcmil (1) #4 – 250 kcmil and (1) 3/0 – 600 kcmil
NB-P
300 – 700 800
(2) #1 – 500 kcmil (3) 3/0 – 400 kcmil
#14 – 1/0
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-11
July 2007
Technical Data and Specifications
Selection Guide (Continued) Table 14-5. Molded Case Circuit Breaker Ratings Note: Circuit breakers equal or exceed Federal Specification W-C-375b requirements for the particular class associated with each circuit breaker type. Breaker Type
23,
Continuous Ampere Rating HQP 23
Number of Poles
Volts ac
UL Listed Interrupting Ratings — kA Symmetrical Amperes dc Rating Volts 1
ac Rating Volts 120/240
240
277
480
600
125
250
15 – 70 15 – 100 15 – 100
1 2 2, 3
120 120/240 240
10 10 —
— — 10
— — —
— — —
— — —
— — —
— — —
BABRP, BABRSP 2
15 – 30 15 – 30
1 2
120 120/240
10 10
— —
— —
— —
— —
— —
— —
QBGF, QBGFEP, QPGF, QPGFEP QBAF, QBAG
15 – 40 15 – 50 15 – 20 15 – 20
1 2 1 2
120 120/240 120 120/240
10 10 10 10
— — — —
— — — —
— — — —
— — — —
— — — —
— — — —
QBHW 23, QPHW 23
15 – 70 15 – 100 15 – 100
1 2 2, 3
120 120/240 240
22 22 —
— — 22
— — —
— — —
— — —
— — —
— — —
QBHGF, QBHGFEP, QPHGF, QPHGFEP
15 – 30 15 – 30
1 2
120 120/240
22 22
— —
— —
— —
— —
— —
— —
GQ, GHQ 2 GHB 23
15 – 20 15 – 100 4 15 – 100 4
1 1 2, 3
277 277 480Y/277
65 65 —
— — 65
14 14 —
— — 14
— — —
— 14 —
— — 14
HGHB 2 GHBGFEP
15 – 30 15 – 60
1 1
277 277
65 —
— —
25 14
— —
— —
— —
— —
GHBS
15 – 30 15 – 30
1 2
277 480Y/277
65 —
— 65
14 —
— 14
— —
— —
— —
EHD 23
15 – 100 15 – 100
1 2, 3
277 480
— —
— 18
14 —
— 14
— —
10 —
— 10
FDB 5 FD 23
15 – 150 15 – 150 15 – 225
2, 3 1 2, 3
600 277 600
— — —
18 — 65
— 35 —
14 — 35
14 — 18
— 10 —
10 — 10
HFD 23
15 – 150 15 – 225
1 2, 3
277 600
— —
— 100
65 —
— 65
— 25
10 —
— 22
FDC 5 FCL
15 – 225 15 – 100
2, 3 2, 3
600 480
— —
200 200
— —
100 150
35 —
— —
22 —
EDB 5 EDS 5 ED 5 EDH 5 EDC 5
100 – 225 100 – 225 100 – 225 100 – 225 100 – 225
2, 3 2, 3 2, 3 2, 3 2, 3
240 240 240 240 240
— — — — —
22 42 65 100 200
— — — — —
— — — — —
— — — — —
10 10 10 10 10
— — — — —
JD 5 HJD 5 JDC 5
70 – 250 70 – 250 70 – 250
2, 3 2, 3 2, 3
600 600 600
— — —
65 100 200
— — —
35 65 100
18 25 35
— — —
10 22 22
DK KD, CKD 6 HKD, CHKD 6
250 – 400 100 – 400 100 – 400
2, 3 2, 3 2, 3
240 600 600
— — —
65 65 100
— — —
— 35 65
— 25 35
— — —
10 10 7 22 7
KDC LCL 8 LGE LD 8, CLD 68
100 – 400 125 – 400 250 – 600 300 – 600
2, 3 2, 3 3 2, 3
600 600 600 600
— — — —
200 200 65 65
— — — —
100 200 35 35
65 100 18 25
— — — —
22 7 — 22 22 7
LGH HLD 8, CHLD 68 LDC 8, CLDC 68 MDL 8, CMDL 68
250 – 600 300 – 600 300 – 600 400 – 800
3 2, 3 2, 3 2, 3
600 600 600 600
— — — —
100 100 200 65
— — — —
65 65 100 50
35 35 50 25
— — — —
22 25 7 25 7 22 7
HMDL 8, CHMDL 68 ND 8, CND 68 HND 8, CHND 68 NDC 8, CNDC 68
400 – 800 600 – 1200 600 – 1200 600 – 1200
2, 3 2, 3 2, 3 2, 3
600 600 600 600
— — — —
100 65 100 200
— — — —
65 50 65 100
35 25 35 65
— — — —
25 7 — — —
2, 3 2, 3 2, 3
600 600 600
— — —
200 200 200
— — —
200 200 200
200 200 200
— — —
i i i
BAB
Integrally Fused, Current Limiting Circuit Breakers FB-P LA-P NB-P 1 2 3 4 5 6 7 8 i
15 – 100 70 – 400 300 – 800
dc ratings apply to substantially non-inductive circuits. 15 and 20 amperes 1-pole switching duty rated for fluorescent applications. 1-, 2- and 3-pole HACR rated. dc rated 1-pole, 15 – 70 amperes only. 2- and 3-pole HACR rated. 100% rated circuit breaker. dc rating not available with electronic trip. Available with integral ground fault protection. 100k based on NEMA test procedure.
CA08101001E
For more information visit: www.eaton.com
14
14-12
Panelboards Pow-R-Line C Panelboards July 2007
Technical Data and Specifications
Series Rated Combinations
Applying Series Ratings
Table 14-6 on Page 14-13
Underwriters Laboratories permits panelboards to be labeled with a short circuit rating of up to 200,000 amperes (symmetrical) where UL listed combinations of main and branch circuit breakers are used.
The following is provided to use the series rating tables on the following pages.
120/240 Volts ac — Breaker/Breaker
These combinations consist of main breakers or fusible devices connected ahead of, and in series with approved conventional breakers used as branch devices. Two arrangements are acceptable and comply with UL standards for panelboards. The main circuit breaker or fusible switch may be installed in the panel as a main device, or it may be mounted remote, (directly upstream) from the panel. In either case, the approved main and branch combinations must be followed. These arrangements are acceptable and are UL listed having been tested in accordance with UL 67 standards.
14
From the tables that follow, specific combinations of main devices (upstream) and branch devices (downstream), series connected and electrically adjacent in the system, may be selected to qualify the assembled panelboard for the short circuit ratings shown.
1. Determine the available system voltage and fault current. 2. Select the appropriate table using the system voltage. 3. Use the appropriate “Series Equipment Rating” column equal to, or greater than, the available fault current, to determine the allowable UL recognized combinations of main (upstream) and branch (downstream) overcurrent devices. Main devices are shown in bold/shaded areas. Respective branch breakers are shown directly below their associated main device. If a rating is not initially found in a column, first look to the columns to the right for higher “Series Equipment Ratings“ within the same table. If still not found, use ratings from table of a higher system voltage (higher numbered table(s).
Table 14-7 on Page 14-14 240 Volts ac — Breaker/Breaker
Table 14-8 on Page 14-16 277 Volts ac — Breaker/Breaker
Table 14-9 on Page 14-16 480Y/277 Volts ac — Breaker/Breaker
Table 14-10 on Page 14-17 480 Volts ac — Breaker/Breaker
Table 14-11 on Page 14-18 600 Volts ac — Breaker/Breaker
Table 14-12 on Page 14-18 120/240 Volts ac — Fuse/Breaker
Table 14-13 on Page 14-19 240 Volts ac — Fuse/Breaker
Table 14-14 on Page 14-19 277 Volts ac — Fuse/Breaker
Table 14-15 on Page 14-20 480Y/277 Volts ac — Fuse/Breaker
Table 14-16 on Page 14-20 480 Volts ac — Fuse/Breaker
Table 14-17 on Page 14-20 600 Volts ac — Fuse/Breaker
Table 14-18 on Page 14-20 Triple Series Ratings
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-13
July 2007
Technical Data and Specifications
Series Rating Tables Table 14-6. 120/240 Volts ac — Breaker/Breaker Series Ratings Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. Series Equipment Rating — kA Symmetrical Main Breaker 18 22 42 65 Maximum Amperes 100
150
EHD BA, BAB BABRP BABRSP HQP QBGF QBAF QBAG
QBHW QPHW BA, BAB HQP QBGF QPGF QBAF QBAG
GB, GHB BA, BAB BABRP BABRSP HQP QBGF QPGF QBAF QBAG QBHW QPHW
600 800 1200
CA08101001E
FB-P BA, BAB BABRP BABRSP HQP QBGF QPGF QBAF QBAG QBHW QPHW EHD FD
FCL BA, BAB BABRP BABRSP HQP QBGF QPGF QBAF QBAG QBHW QPHW GB, GHB GHQ EHD FD HFD
LA-P BA, BAB HQP QBHW QPHW EHD FD EDB BA, BAB BABRP BABRSP HQP QBGF QPGF QBHGF QPHGF QBHW QPHW QBAF QBAG
EDS BA, BAB BABRP BABRSP HQP QBGF QPGF QBHGF QPHGF QBHW QPHW QBAF QBAG
250
400
200
FDB BA, BAB HQP QBGF QBAF QBAG
200
225
100
ED, FD BA, BAB BABRP BABRSP HQP QBGF QPGF QBAF QBAG QBHW QBHGF
JD, JDB BA (15 – 70 A) BAB (15 – 70 A) HQP (15 – 70 A) QBHW QPHW EHD DK, KD KDB BA, BAB BABRP BABRSP HQP QBGF QPGF QBAF QBAG
DK, KD KDB, CKD BA (15 – 70 A) BAB (15 – 70 A) BABRP BABRSP HQP (15 – 70 A) QBHW QPHW
HJD BA, BAB HQP QBHW QPHW
HKD, CHKD DK, KD KDB BA (15 – 70 A) CKD BAB (15 – 70 A) BABRP EHD BABRSP HQP (15 – 70 A) QBHW QPHW
JDC QBGF QPGF QBAF QBAG
14
EDH, EDC BA, BAB BABRP BABRSP HQP QBGF QPGF QBAF QBAG
HFD BA, BAB HQP QBGF QBAF QBAG QBHW QPHW QBHGF GB, GHB GHQ, GHQRSP EHD FD
HJD GB, GHB EHD FD
JDC BA, BAB HQP QBHW QPHW
KDC HKD CHKD BA (15 – 70 A) BAB (15 – 70 A) GB, GHB HQP (15 – 70 A) EHD FD
CHLD, HLD EHD HMDL EHD HND EHD
For more information visit: www.eaton.com
KDC QBHW QPHW
FDC BA, BAB HQP QBHW QPHW
FDC GB, GHB GHQ GHQRSP EHD FD HFD
JDC GB, GHB EHD FD HFD
KDC GB, GHB EHD FD HFD
LCL BA, BAB HQP QBGF QPGF QBAF QBAG QBHW QPHW GB, GHB EHD FD HFD
Panelboards Pow-R-Line C Panelboards
14-14
July 2007
Technical Data and Specifications Table 14-7. 240 Volts ac — Breaker/Breaker Series Ratings For 1- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 14-6. Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. Main Breaker Maximum Amperes 100
Series Equipment Rating — kA Symmetrical 18
22
EHD BAB_H HQP_H
150
42
65
QBHW_H QPHW_H
100
GB, GHB
FB-P
FCL BAB_H HQP_H QBHW_H QPHW_H GB, GHB EHD FD FDB HFD
BAB_H HQP_H EHD FDB FD
BAB_H HQP_H QBHW_H QPHW_H
BAB_H HQP_H
200
FDB BAB_H HQP_H
200
LA-P BAB_H HQP_H QBHW_H QPHW_H EHD FDB FD JD, JDB
225
EDB HQP_H BAB_H QBHW QPHW
14
250
EDS HQP_H BAB_H QBHW QPHW
ED BAB_H HQP_H QBHW_H
JD, JDB BAB_H (15 – 70 A) HQP_H (15 – 70 A) QBHW_H QPHW_H EHD FDB
FD BAB_H HQP_H QBHW_H QPHW_H EHD (15 – 70 A) FDB
EDH, EDC BAB_H HQP_H
HJD BAB_H (15 – 70 A) HQP_H (15 – 70 A) QBHW_H QPHW_H
HJD GB, GHB EHD FD FDB ED JD, JDB
For more information visit: www.eaton.com
HFD BAB_H HQP_H QBHW_H QPHW_H GB, GHB EHD FDB FD JDC BAB_H HQP_H QBHW_H QPHW_H
FDC BAB_H HQP_H QBHW_H QPHW_H
FDC GB, GHB EHD FDB FD HFD
JDC GB, GHB EHD FD FDB HFD, EDB, EDS ED EDH JD, JDB HJD
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-15
July 2007
Technical Data and Specifications Table 14-7. (Continued) 240 Volts ac — Breaker/Breaker Series Ratings For 1- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 14-6. Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. Main Breaker Maximum Amperes 400
Series Equipment Rating — kA Symmetrical 65
100
DK, KD, KDB CKD BAB_H HQP_H QBHW_H QPHW_H EHD FDB
200
HKD, CHKD QBHW_H 1 QPHW_H 1 GB, GHB EHD FDB FD, EDB, EDS ED JD, JDB DK, KD, KDB
500
KDC QBHW_H QPHW_H
KDC GB, GHB EHD FDB FD HFD, EDB, EDS ED EDH JD, JDB HJD DK, KD, KDB HKD
LCL BAB_H HQP_H QBHW_H QPHW_H GB, GHB EHD FDB FD, HFD, EDB, EDS ED EDH JD, JDB HJD DK, KD, KDB HKD
NB-P JD, JDB KD, KDB, DK CKD
600
HLD, HLDB, CHLD
LDC
GB 1, GHB 1 FD, EDB, EDS ED, EHD JD, JDB KD, KDB, DK, CKD LD, LDB NB-P
800
KD, KDB, DK 1200
EDB, EDS, ED EDH
EHD FD
HND, CHND EDB, EDS, ED EHD
2500
1
NDC EDB, EDS, ED EDH
RD
RDC
EDB, EDS, ED
EDB, EDS, ED EDH
Valid on 2- and 3-pole breakers only. Not valid for 1-pole.
CA08101001E
14
HMDL
For more information visit: www.eaton.com
Panelboards Pow-R-Line C Panelboards
14-16
July 2007
Technical Data and Specifications Table 14-8. 277 Volts ac — Breaker/Breaker Series Ratings Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to single-pole branch breakers only. For 2- and 3-pole branch breakers, see other tables. Main Breaker Maximum Amperes
Series Equipment Rating — kA Symmetrical 22
25
35
65
100
150
FCL
100
GHB GHQ, GHQRSP EHD FD HFD 225
FD
HFD
GHB GHQ GHQRSP JD, JDB
250
JD, JDB
GHB
400
GHB
14
HKD CHKD GHB
GHB EHD FD HFD
HJD
GHB (15 – 50 A)
KD, KDB CKD
FDC
GHB, GHQRSP GHQ EHD FD
KD, KDB CKD
LCL
GHB (15 – 50 A) EHD FD HKD, CHKD
GHB (15 – 50 A) EHD FD
JDC
GHBS
GHB EHD FD HFD KDC
GHB (15 – 50 A) EHD FD
LCL
GHB (15 – 50 A) EHD FD HFD
GHB EHD FD HFD
Table 14-9. 480Y/277 Volts ac — Breaker/Breaker Series Ratings Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to 2- and 3-pole branch breakers only. For single-pole branch breakers, see Table 14-8. Main Breaker Maximum Amperes
Series Equipment Rating — kA Symmetrical 22
25
35
65
100
150
FCL
100
GHB, GHQRSP 225
FD GHB, GHQRSP
250
JD, JDB
JD, JDB
GHB 400
GHB (15 – 50 A) KD, KDB CKD
GHB
HKD, CHKD GHB
KD, KDB CKD
HFD GHB, GHQRSP
FDC GHB
HJD GHB (15 – 50 A) HKD, CHKD GHB (15 – 50 A)
JDC GHB KDC GHB (15 – 50 A)
LCL GHB
GHB (15 – 50 A)
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-17
July 2007
Technical Data and Specifications Table 14-10. 480 Volts ac — Breaker/Breaker Series Ratings Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for 1-pole branch breakers. Main Breaker Maximum Amperes
Series Equipment Rating — kA Symmetrical 25
35
65
100
150
FB-P
100
FCL EHD FDB FD HFD
EHD FDB FD HFD 200
LA-P EHD FDB FD HFD JD, JDB HJD FD
225 EHD FDB
HFD EHD FDB FD
JD, JDB
250
FDC EHD FDB FD HFD
HJD
EHD FDB
EHD FDB FD JD, JDB
KD, KDB
400 EHD FDB
HKD EHD FDB FD JD, JDB KD, KDB
JDC EHD FDB FD HFD JD, JDB HJD KDC EHD FDB FD HFD JD, JDB HJD KD, KDB HKD NB-P
500
JD, JDB HJD KD, KDB HKD 600
LD, LDB CLD JD, JDB
CA08101001E
HLD, HLDB CHLD FD JD, JDB KD, KDB LD, LDB
For more information visit: www.eaton.com
LA-P JD, JDB HJD KD, KDB HKD
LCL EHD FDB FD HFD FDC JD, JDB HJD KD, KDB HKD
14
Panelboards Pow-R-Line C Panelboards
14-18
July 2007
Technical Data and Specifications Table 14-11. 600 Volts ac — Breaker/Breaker Series Ratings Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for 1-pole branch breakers. Main Breaker Maximum Amperes
Series Equipment Rating — kA Symmetrical 18
25
35
FD
225 FDB
250
HFD FDB FD
JDC FDB FD HFD JD, JDB HJD
KD, KDB CKD FDB FD JD, JDB
HKD, CHKD FDB FD HFD JD, JDB HJD
LD, LDB CLD
600
FD JD, JDB
14
100
FDC
HJD FDB FD JD, JDB
400
50
FDB FD HFD
JD, JDB FDB
42
KDC FDB FD HFD
KDC JD, JDB HJD KD, KDB HKD
LCL FDB FD HFD FDC JD, JDB HJD JDC KD, KDB HKD KDC
HLD, HLDB CHLD KD, KDB LD, LDB
Table 14-12. 120/240 Volts ac — Fuse/Breaker Series Ratings Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below. Main Fuse Maximum Amperes
Series Equipment Rating — kA Symmetrical 100
200
R
100 BA, BAB HQP QBHW QPHW GB GHB R
200 GB GHB
J
400 BA, BAB HQP QBHW QPHW
J BA, BAB HQP QBHW QPHW
T BA, BAB HQP QBHW QPHW
T BA, BAB HQP QBHW QPHW
J GB GHB
For more information visit: www.eaton.com
T GB GHB
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-19
July 2007
Technical Data and Specifications Table 14-13. 240 Volts ac — Fuse/Breaker Series Ratings For 1- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 14-12. Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below. Main Fuse Maximum Amperes
Series Equipment Rating — kA Symmetrical 100
200
R
100 BAB_H HQP_H QBHW_H QPHW_H GB GHB R
200
J
GB GHB
400
J BAB_H HQP_H QBHW_H QPHW_H
T
BAB_H HQP_H QBHW_H QPHW_H
T
J
BAB_H HQP_H QBHW_H QPHW_H
R GB 1 GHB 1
BAB_H HQP_H QBHW_H QPHW_H T
GB GHB
GB GHB
L
600
EHD FDB FD ED JD, JDB DK, KD, KDB 1
14
Valid on 2- and 3-pole breakers only. Not valid for 1-pole.
Table 14-14. 277 Volts ac Fuse/Breaker Series Ratings Main fuse class are shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to single-pole branch breakers only. For 2- and 3-pole branch breakers, consult other tables. Main Fuse Maximum Amperes
Series Equipment Rating — kA Symmetrical 65
100
J
T
GHBS GHQ GHQRSP
GHBS GHQ GHQRSP
100
200
J
T
GHBS GHQ GHQRSP
GHBS GHQ GHQRSP
200
J EHD FD HFD
R GHB
T EHD FD HFD
R GHB
J
400 GHB
CA08101001E
For more information visit: www.eaton.com
T GHB
Panelboards Pow-R-Line C Panelboards
14-20
July 2007
Technical Data and Specifications Table 14-15. 480Y/277 Volts ac — Fuse/Breaker Series Ratings Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to 2- and 3-pole branch breakers only. For single-pole branch breakers, see Table 14-14. Main Fuse Maximum Amperes
Main Series Equipment Rating — kA Symmetrical Fuse 100 200 Maximum Amperes
Series Equipment Rating — kA Symmetrical 65
100
200
J
100
GHBS J
200
GHBS
T
T
R
GHBS GHB J
400
GHB J
T
EHD FD HFD FDC
GHB EHD FD HFD FDC JD HJD JDC
T
R EHD
200
J EHD FD HFD FDC
T EHD FD HFD FDC
J
200
FD HFD FDC
T FD HFD FDC
J
400
JD HJD JDC
R JD HJD JDC
T JD HJD JDC
R KD HKD KDC J
T
KD HKD KDC
KD HKD KDC
600
Main Series Equipment Rating — kA Symmetrical Fuse 100 200 Maximum Amperes 100
FD HFD FDC
GHB
Table 14-16. 480 Volts ac — Fuse/Breaker Series Ratings Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for single-pole branch breakers.
14
R
100
GHB
R
GHBS
600
Table 14-17. 600 Volts ac — Fuse/Breaker Series Ratings Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below. All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for single-pole branch breakers.
Table 14-18. Triple Series Ratings Main Fuse Class and Maximum Amperes
Tenant Main Type
Branch Type
System Voltage
Short Circuit Series Rating (kA, Sym.)
L-6000
DK, KD, KDB
GB, GHB, EHD 1
240
100
L-6000
DK, KD, KDB
GB, GHB
120/240
100
L-6000
DK, KD, KDB
FD 1, FDB
240
100
L-6000
DK, KD, KDB
JD, JDB
240
100
L-6000
JD, JDB
GB, GHB
240
100
L-6000
JD, JDB
GB, GHB
120/240
100
L-6000
FD
GB, GHB
240
100
L-6000
FD
GB, GHB
120/240
100
L-6000
FD, FDB
BAB_H, HQP_H QBHW_H, QPHW_H
240
100
L-6000
FD, FDB
BA, BAB HQP (15 – 70A)
120/240
100
L-6000
EHD
BAB_H, HQP_H
240
100
L-6000
EHD
BA, BAB, HQP
120/240
100
1
Valid on 2- and 3-pole breakers only. Not valid for single-pole.
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-21
July 2007
PRL1a
Product Description ■ ■ ■ ■ ■ ■ ■
240 Vac maximum. 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 400 ampere maximum mains. 100 ampere maximum branch breakers. Bolt-on or plug-on branch breakers. Factory assembled. Refer to Page 14-5 for additional information.
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-19. Base Prices — PRL1a Ampere Rating
Interrupting Breaker Rating (kA Sym.) Type 240 Vac
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire, 3-Phase 1-Phase 2-Wire 3-Wire
Main Lug Only 100 225 400
— — —
— — —
Main Breaker 100 100 100 100 100 100 100 100 100
10 18 22 22 42 65 65 100 100
BAB EHD QBHW EDB EDS ED FD EDH HFD
225 225 225 225
22 42 65 100
EDB EDS ED EDH
250 250 250
65 100 200
JD HJD JDC
400 400 400 400
65 65 100 200
DK KD HKD KDC
14
Table 14-20. Branch Circuit Breakers — PRL1a Bolt-on = BAB, QBHW, QBGF, QBHGF, QBGFEP, QBHGFEP, QBAF, QBAG, QBHAF, QBHAG Plug-on = HQP, QPHW, QPGF, QPHGF, QPGFEP, QPHGFEP
Type PRL1a
Application Description ■ ■ ■ ■
■
Lighting and appliance branch panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specified on the order. See Pages 14-5 through 14-18 for additional information.
Standards and Certifications UL 67, UL 50. Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information. ■ ■
Ampere Rating
Breaker Interrupting Rating (kA Sym.) Type 1 240 Vac
15 – 60 70 80 – 100 15 – 50 3 15 – 50 3 15 – 20 15 – 20
10 10 10 10 10 10 10
BAB, HQP BAB, HQP BAB, HQP QBGF, QPGF 4 QBGFEP, QPGFEP 5 QBAF 6 QBAG 7
15 – 60 15 – 30 15 – 30 15 – 30
10 10 10 10
BAB-D, HQP-D 8 BAB-C, HQP-B 9 BABRP j BABRSP j
15 – 60 70 80 – 100 15 – 30 15 – 30 15 – 20 15 – 20
22 22 22 22 22 22 22
QBHW, QPHW QBHW, QPHW QBHW, QPHW QBHGF, QPHGF 4 QBHGFEP, QPHGFEP 5 QBHAF 6 QBHAG 7
Provision — 1 2 3 4
Options and Accessories ■
Refer to Page 14-46.
Layout and Sizing ■
Refer to Page 14-22.
5 6 7 8 9 j
Price U.S. $ 1-Pole 120 V
2-Pole 2-Pole 120/240 V 240 V 2
3-Pole 240 V
—
1-pole breakers are rated 120 Vac maximum. 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a midpoint delta grounded system. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Line C Panelboards
14-22
July 2007
PRL1a
Box Sizing and Selection Assembled Circuit Breaker Panelboards Box size and box and trim catalog numbers for all standard panelboard types are found in Table 14-21.
3.
Instructions
4.
1. Using description of the required panelboard, select the rating and type of main required. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single-poles, i.e., 3-pole breaker, count as 3 poles.
5. 6.
Determine sub-feed breaker or through-feed lug requirements. Select the main ampere rating section from Table 14-21. Select panelboard type from first column, main breaker frame, if applicable, from second column, and sub-feed breaker frame, if applicable, from the third column. From Step #2, determine the number of branch circuits in Column 4. Read box size, box and trim catalog numbers across columns to the right. Specify surface or flush mounting on the order.
Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.
Top and Bottom Gutters 5-1/2 inches (139.7 mm) minimum.
Table 14-21. PRL1a Panelboard Sizing Panelboard Types
Main Breaker Types & Mounting Position (H) = Horiz. (V) = Vert.
Sub-Feed Breaker Types & Mounting Position (H) = Horiz. (V) = Vert.
Maximum No. of Box Dimensions Branch Circuits Inches 12 Including H W D Provisions
YS Box LT Trim Catalog Catalog Number Number
EZ Box Catalog Number
EZ Trim Catalog Number
EZT2036S or F EZT2048S or F EZT2048S or F EZT2060S or F
100 Ampere Maximum
14
Main Breaker
BAB, QBHW (H)
— — — —
15 27 39 42
36.00 48.00 48.00 60.00
YS2036 YS2048 YS2048 YS2060
LT2036S or F LT2048S or F LT2048S or F LT2060S or F
EZB2036R EZB2048R EZB2048R EZB2060R
Main Lugs or Main Breaker
EHD FD, HFD (V)
— — —
18 30 42
36.00 20.00 5.75 YS2036 48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048
LT2036S or F LT2048S or F LT2048S or F
EZB2036R EZT2036S or F EZB2048R EZT2048S or F EZB2048R EZT2048S or F
Main Lugs or Main Breaker with 100 A Thru-Feed Lugs or Sub- Feed Breaker
EHD FD HFD (V)
EHD FD HFD (V)
18 30 42
48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048 60.00 20.00 5.75 YS2060
LT2048S or F LT2048S or F LT2060S or F
EZB2048R EZT2048S or F EZB2048R EZT2048S or F EZB2060R EZT2060S or F
EDB, EDS, ED, EDH, FD, HFD (V)
— — —
18 30 42
36.00 20.00 5.75 YS2036 48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048
LT2036S or F LT2048S or F LT2048S or F
EZB2036R EZT2036S or F EZB2048R EZT2048S or F EZB2048R EZT2048S or F
JD, HJD JDC (V)
— — —
18 30 42
60.00 20.00 5.75 YS2060 60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072
LT2060S or F LT2060S or F LT2072S or F
EZB2060R EZT2060S or F EZB2060R EZT2060S or F EZB2072R EZT2072S or F
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
18 30 42
48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048 60.00 20.00 5.75 YS2060
LT2048S or F LT2048S or F LT2060S or F
EZB2048R EZT2048S or F EZB2048R EZT2048S or F EZB2060R EZT2060S or F
JD, HJD JDC (V)
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
18 30 42
60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072 72.00 20.00 5.75 YS2072
LT2060S or F LT2072S or F LT2072S or F
EZB2060R EZT2060S or F EZB2072R EZT2072S or F EZB2072R EZT2072S or F
— — —
18 30 42
60.00 20.00 5.75 YS2060 60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072
LT2060S or F LT2060S or F LT2072S or F
EZB2060R EZT2060S or F EZB2060R EZT2060S or F EZB2072R EZT2072S or F
DK, KD, HKD, Main Lugs or Main Breaker with KDC (V) 225 A Thru-Feed Lugs or Sub- Feed Breaker
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
18 30 42
60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072 72.00 20.00 5.75 YS2072
LT2060S or F LT2072S or F LT2072S or F
EZB2060R EZT2060S or F EZB2072R EZT2072S or F EZB2072R EZT2072S or F
DK, KD, HKD, Main Lugs or Main Breaker with KDC (V) 400 A Thru-Feed Lugs or Sub- Feed Breaker
JD, HJD, JDC, DK, KD, HKD, KDC (V)
18 30 42
72.00 20.00 5.75 YS2072 90.00 20.00 5.75 YS2090 90.00 20.00 5.75 YS2090
LT2072S or F LT2090S or F LT2090S or F
EZB2072R EZT2072S or F EZB2090R EZT2090S or F EZB2090R EZT2090S or F
20.00 20.00 20.00 20.00
5.75 5.75 5.75 5.75
225 Ampere Maximum Main Lugs or Main Breaker
Main Lugs or Main Breaker with 225 A Thru-Feed Lugs or Sub-Feed Breaker
400 Ampere Maximum Main Lugs or Main Breaker
1
DK, KD, HKD, KDC (V)
Metric box dimensions:
Catalog Number YS Box
EZ Box
Height
Width
Depth
YS2036 YS2048 YS2060 YS2072 YS2090
EZB2036R EZB2048R EZB2060R EZB2072R EZB2090R
914.4 1219.2 1524.0 1828.8 2286.0
508.0 508.0 508.0 508.0 508.0
146.1 146.1 146.1 146.1 146.1
2
Dimensions in mm
Smaller panelboard box sizes are available if required. Contact Eaton for application information.
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-23
July 2007
PRL2a
Product Description ■ ■ ■ ■ ■ ■ ■
480Y/277 Vac maximum (125 Vdc). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 400 ampere maximum mains. 100 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled. Refer to Page 14-5 for additional Information.
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-22. Base Prices — PRL2a Ampere Rating
Interrupting Rating (kA Symmetrical)
Breaker Price U.S. $ Type
240 Vac
480Y/277 Vac 125/250 Vdc
— — —
— — —
3-Phase 1-Phase 3-Wire 1, 3-Phase 4-Wire 1-Phase 2-Wire 3-Wire 1
Main Lug Only 100 225 400
— — —
— — —
Main Breaker 100 100
65 18
14 14
14 10
GHB EHD
100 100 100
65 100 200
35 65 100
10 22 22
FD HFD FDC
225 225 225 225
65 65 100 200
— 35 65 100
— 10 22 22
ED FD HFD FDC
250 250 250
65 100 200
35 65 100
10 22 22
JD HJD JDC
400 400 400
65 100 200
35 65 100
10 22 22
KD HKD KDC
1
Type PRL2a
These system voltages apply only to 240 volts.
14
Table 14-23. Branch Circuit Breakers — PRL2a
Application Description ■ ■ ■ ■
■
Lighting and appliance branch panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specified on the order. See Pages 14-5 through 14-18 for additional information.
Ampere Rating
UL 67, UL 50. ■ Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information. ■
Breaker Type
240 Vac 2 480Y/277 Vac 125/250 Vdc 15 – 20 15 – 20 25 – 60 70 – 100 15 – 30 15 – 20 15 – 30
65 65 65 65 65 65 65
14 14 14 14 25 14 14
— 14 14 14 — — —
15 – 60 15 – 20
— —
14 14
— —
GHBGFEP 35 GHBHID 36
Provision
—
—
—
—
3 4 5 6
Price U.S. $ 1-Pole
GHQ 3 GHB 3 GHB 3 GHB 3 HGHB 3
2
Standards and Certifications
Interrupting Rating (kA Symmetrical)
2-Pole
3-Pole
GHQRSP 4 GHBS 34
Interrupting ratings in this column are applicable to 120 Vac for 1-pole breakers. At 480 volts, must be used on 480Y/277 volts grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires 2-pole spaces. 277 Vac only. HID (High Intensity Discharge) rated breaker.
Options and Accessories ■
Refer to Page 14-46.
Layout and Sizing ■
Refer to Page 14-24.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Line C Panelboards
14-24
July 2007
PRL2a
Box Sizing and Selection Assembled Circuit Breaker Panelboards Box size and box and trim catalog numbers for all standard panelboard types are found in Table 14-24.
3.
Instructions
4.
1. Using description of the required panelboard, select the rating and type of main required. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single-poles, i.e., 3-pole breaker, count as 3 poles.
5. 6.
Determine sub-feed breaker or through-feed lug requirements. Select the main ampere rating section from Table 14-24. Select panelboard type from first column, main breaker frame, if applicable, from second column, and sub-feed breaker frame, if applicable, from the third column. From Step #2, determine the number of branch circuits in Column 4. Read box size, box and trim catalog numbers across columns to the right. Specify surface or flush mounting on the order.
Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.
Top and Bottom Gutters 5-1/2 inches (139.7 mm) minimum.
Table 14-24. PRL2a Panelboard Sizing Panelboard Types
Main Breaker Types & Mounting Position (H) = Horiz. (V) = Vert.
Sub-Feed Breaker Types & Mounting Position (H) = Horiz. (V) = Vert.
Maximum No. of Box Dimensions Branch Circuits Inches 12 Including H W D Provisions
YS Box LT Trim Catalog Catalog Number Number
EZ Box Catalog Number
EZ Trim Catalog Number
EZT2036S or F EZT2048S or F EZT2048S or F EZT2060S or F
100 Ampere Maximum
14
Main Breaker
BAB, QBHW (H)
— — — —
15 27 39 42
36.00 48.00 48.00 60.00
20.00 20.00 20.00 20.00
5.75 5.75 5.75 5.75
YS2036 YS2048 YS2048 YS2060
LT2036S or F LT2048S or F LT2048S or F LT2060S or F
EZB2036R EZB2048R EZB2048R EZB2060R
Main Lugs or Main Breaker
EHD FD, HFD (V)
— — —
18 30 42
36.00 20.00 5.75 YS2036 48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048
LT2036S or F LT2048S or F LT2048S or F
EZB2036R EZT2036S or F EZB2048R EZT2048S or F EZB2048R EZT2048S or F
Main Lugs or Main Breaker with 100 A Thru-Feed Lugs or Sub- Feed Breaker
EHD FD HFD (V)
EHD FD HFD (V)
18 30 42
48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048 60.00 20.00 5.75 YS2060
LT2048S or F LT2048S or F LT2060S or F
EZB2048R EZT2048S or F EZB2048R EZT2048S or F EZB2060R EZT2060S or F
EDB, EDS, ED, EDH, FD, HFD (V)
— — —
18 30 42
36.00 20.00 5.75 YS2036 48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048
LT2036S or F LT2048S or F LT2048S or F
EZB2036R EZT2036S or F EZB2048R EZT2048S or F EZB2048R EZT2048S or F
JD, HJD JDC (V)
— — —
18 30 42
60.00 20.00 5.75 YS2060 60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072
LT2060S or F LT2060S or F LT2072S or F
EZB2060R EZT2060S or F EZB2060R EZT2060S or F EZB2072R EZT2072S or F
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
18 30 42
48.00 20.00 5.75 YS2048 48.00 20.00 5.75 YS2048 60.00 20.00 5.75 YS2060
LT2048S or F LT2048S or F LT2060S or F
EZB2048R EZT2048S or F EZB2048R EZT2048S or F EZB2060R EZT2060S or F
JD, HJD JDC (V)
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
18 30 42
60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072 72.00 20.00 5.75 YS2072
LT2060S or F LT2072S or F LT2072S or F
EZB2060R EZT2060S or F EZB2072R EZT2072S or F EZB2072R EZT2072S or F
— — —
18 30 42
60.00 20.00 5.75 YS2060 60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072
LT2060S or F LT2060S or F LT2072S or F
EZB2060R EZT2060S or F EZB2060R EZT2060S or F EZB2072R EZT2072S or F
Main Lugs or Main DK, KD, HKD, Breaker with 225 A KDC Thru-Feed Lugs or (V) Sub- Feed Breaker
EHD, FD, HFD, EDB, EDS, ED, EDH (V)
18 30 42
60.00 20.00 5.75 YS2060 72.00 20.00 5.75 YS2072 72.00 20.00 5.75 YS2072
LT2060S or F LT2072S or F LT2072S or F
EZB2060R EZT2060S or F EZB2072R EZT2072S or F EZB2072R EZT2072S or F
Main Lugs or Main DK, KD, HKD, Breaker with 400 A KDC Thru-Feed Lugs or (V) Sub- Feed Breaker
JD, HJD, JDC, DK, KD, HKD, KDC (V)
18 30 42
72.00 20.00 5.75 YS2072 90.00 20.00 5.75 YS2090 90.00 20.00 5.75 YS2090
LT2072S or F LT2090S or F LT2090S or F
EZB2072R EZT2072S or F EZB2090R EZT2090S or F EZB2090R EZT2090S or F
225 Ampere Maximum Main Lugs or Main Breaker
Main Lugs or Main Breaker with 225 A Thru-Feed Lugs or Sub-Feed Breaker
400 Ampere Maximum Main Lugs or Main Breaker
1
DK, KD, HKD, KDC (V)
Metric box dimensions:
Catalog Number YS Box
EZ Box
Height
Width
Depth
YS2036 YS2048 YS2060 YS2072 YS2090
EZB2036R EZB2048R EZB2060R EZB2072R EZB2090R
914.4 1219.2 1524.0 1828.8 2286.0
508.0 508.0 508.0 508.0 508.0
146.1 146.1 146.1 146.1 146.1
2
Dimensions in mm
Smaller panelboard box sizes are available if required. Contact Eaton for application information.
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-25
July 2007
PRL3a
Product Description ■ ■ ■ ■ ■ ■ ■ ■
600 Vac maximum (250 Vdc). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 800 ampere maximum main lugs. 600 ampere maximum main breaker. 225 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled. Refer to Page 14-5 for additional information.
Type PRL3a
Application Description ■
■ ■ ■
■
Lighting and appliance branch panelboard or power distribution panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specified on the order. See Pages 14-5 through 14-18 for additional information.
Standards and Certification UL 67, UL 50. ■ Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information. ■
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-25. Base Prices — PRL3a Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vdc
Breaker Type
— — — — —
— — — — —
— — — — —
— — — — —
Price U.S. $ 3-Phase 1-Phase 3-Wire, 4-Wire 1-Phase 2-Wire
3-Phase 3-Wire
Main Lug Only 100 250 400 600 800 1
— — — — —
Main Breaker 100 100 100 100 100 100 100 100 100 100 100
18 18 22 42 65 100 65 100 200 200 200
14 14 — — — — 35 65 100 150 200
— 14 — — — — 18 25 35 — 200
10 10 — — — — 10 22 22 — 100 2
EHD FDB EDB EDS ED EDH FD HFD FDC FCL FB-P 3
225 225 225 225 225 225 225 225
22 42 65 100 200 65 100 200
— — — — — 35 65 100
— — — — — 18 25 35
— — — — — 10 22 22
EDB EDS ED EDH EDC FD HFD FDC
250 250 250
65 100 200
35 65 100
18 25 35
10 22 22
JD HJD JDC
400 400 400 400 400 400
65 65 100 200 200 200
— 35 65 100 200 200
— 25 35 65 — 200
10 10 22 22 — 100 2
DK KD HKD KDC LCL 4 LA-P 34
600 600 600 600 600 600 600 600
65 100 65 100 200 65 100 200
35 65 35 65 100 35 65 100
18 35 25 35 50 25 35 50
22 22 22 25 25 22 25 25
LGE LGH LD HLD LDC CLD 5 CHLD 5 CLDC 5
1 2 3 4 5
800 ampere MLO requires 28-inch (711.2 mm) wide box. 100,000 based on NEMA test procedure. Top feed only. Requires 6-1/2-inch (165.1 mm) deep box. Not available in Type 3R, 12, 4 and 4X enclosures. 100% rated circuit breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures.
Options and Accessories ■
Refer to Page 14-46.
Layout and Sizing ■
Refer to Page 14-27.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
Panelboards Pow-R-Line C Panelboards
14-26
July 2007
PRL3a Table 14-26. Branch Circuit Breakers — PRL3a Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vdc
Breaker Type
Price U.S. $ Breaker 1-Pole
15 – 60 15 – 60 70 70 80 – 100 80 – 100 15 – 50 1 15 – 50 1 15 – 20 15 – 20 15 – 60 15 – 30 15 – 30 15 – 30
10 23 10 10 23 10 10 23 10 10 23 10 10 23 10 23 10 23 10 23 10 2 10 2
— — — — — — — — — — — — — —
— — — — — — — — — — — — — —
— — — — — — — — — — — — — —
BAB BAB-H BAB BAB-H BAB BAB-H QBGF QBGFEP QBAF 4 QBAG 5 BAB-D 6 BAB-C 7 BABRP 8 BABRSP 8
15 – 60 15 – 60 70 70 80 – 100 80 – 100 15 – 30 15 – 30 15 – 20 15 – 20
22 23 22 22 23 22 22 23 22 22 22 22 23 22 23
— — — — — — — — — —
— — — — — — — — — —
— — — — — — — — — —
QBHW QBHW-H QBHW QBHW-H QBHW QBHW-H QBHGF QBHGFEP QBHAF 4 QBHAG 5
14 9j 14 9j 14 9j 14 9j 25 9j 14 9j 14 9j 14 9j 14 9j
— — — — — — — — —
— 14 14 14 — 14 14 — —
GHQ GHB GHB GHB HGHB GHQRSP 8 GHBS 8 GHBGFEP GHBHID 6
14 9 14 9
— —
10 10
EHD EHD
14 14 14
10 10 10
FDB FDB FDB
15 – 20 15 – 20 25 – 60 70 – 100 15 – 30 15 – 20 15 – 30 15 – 60 15 – 20
14
15 – 60 70 – 100
65 65 65 65 65 65 65 — — 18 k 18 k
15 – 60 70 – 100 110 – 150
18 18 18
15 – 60 70 – 100 110 – 225
65 k 65 k 65 k
35 9 35 9 35
18 18 18
10 10 10
FD FD FD l
15 – 60 70 – 100 110 – 225
100 k 100 k 100 k
65 9 65 9 65
25 25 25
22 22 22
HFD HFD HFD l
15 – 60 70 – 100 110 – 225
200 200 200
100 100 100
35 35 35
22 22 22
FDC FDC FDC l
100 – 225 100 – 225 100 – 225 100 – 225 100 – 225
22 42 65 100 200
— — — — —
— — — — —
— — — — —
EDB l EDS l ED l EDH l EDC l
1 2 3 4 5 6 7 8 9 j k l
V14 14 14
Space Only 2-Pole
3-Pole
1-Pole
2-Pole
Provision Only 3-Pole
1-Pole
2-Pole
3-Pole
50 ampere devices are available as 2-pole only. 1-pole breaker rated 120 Vac. 2-pole breaker rated 120/240 Vac. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker. 1-pole breaker rated 277 Vac. For use on 480Y/277 volt systems only. AIC rating for 2- and 3-pole breakers only. Maximum of six breakers per panel, 175 – 225 amperes.
Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-27
July 2007
PRL3a
Poles 6 - 3X 12 - 5X 18 - 8X 24 - 10X 30 - 13X 36 - 15X 42 - 18X
1X 1-Pole
1-Pole
2-Pole
2-Pole
1-Pole 2-Pole
3X 3-Pole
2- or 3-Pole
Neutral Section
Main Lug Section
Main Breaker Section
2X
Horizontal Mounting Vertical Mounting
2X 2-Pole 3X 3-Pole
BAB, QBHW, BABRP, BABRSP GHQ, GHB, HGHB
EDB, EDS, ED, EDH, EDC, EHD, FDB, FD, HFD, FDC 150 A Max. Per Branch Breaker (300 A Max. Per Connector) EDB, EDS, ED, EDH, EDC FD, HFD, FDC 100 – 250 A 400 – 800 A
11X
800A with Thru-feed Lug
2X
100 A
5X
250 A
8X
400 – 600 A
14X
800 A
2X 2-Pole
EHD, FDB, FD, HFD, FDC
3X 3-Pole
EDB, EDS, ED, EDH, EDC 3 EHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC 4 FCL, FB-P
5
14X
JD HJD, JDC
15X
DK, KD HKD, KDC
17X
LD, HLD, LDC CLD, CHLD, CLDC
18X
LGE, LGH
21X
LCL, LA-P
56
Figure 14-4. PRL3a Layout 1
2 3
4 5 6
GHB, HGHB and GHQ breakers cannot be mixed on same connector as BAB, QBHW, BABRP and BABRSP. Maximum of six breakers per panel. Horizontal mounted 15 – 150 ampere main breakers EHD, FDB, FD, HFD and FDC, will be furnished as branch breaker construction. Branch breakers 1-, 2- or 3-pole as required, may be located opposite these main breakers. If optional terminal kit 3TA225FDK is required, use 10X. FB-P and LA-P top mounting only. LCL or LA-P main breaker requires 6-1/2-inch (165.1 mm) deep box.
CA08101001E
1. Select:
1. Description of Panel Type PRL3a 3-phase, 4-wire, 120/208 Vac flush mounting. Panel to have short circuit rating of 22,000 symmetrical amperes. Main breaker 400 amperes, 3-pole, bottom mounting. Branch circuits bolt-on as follows:
a. Required mains (lugs or breaker). b. Neutral where required. c. Branch circuits as required. 2. Layout panel as shown in Figure 14-4, using appropriate “X” dimensions. 3. Using total X units (panel height) find box height in inches (mm) and box catalog number from Table 14-27. (When total X units come out to an uneven number, use next highest number; i.e., if total X comes out 25X, use 31X.)
12 – 20 ampere 1-pole QBHW 1 – 200 ampere 3-pole ED 1 – 225 ampere 3-pole ED 2. Layout Information from Figure 14-4: a. b. c. d.
2
8X
9X
Layout Example
1
5X
7X
Panel Layout Instructions
400 ampere Neutral . . . . . . = 8X 12-poles of QBHW . . . . . . . = 5X Two 3-pole ED breakers . . . .= 6X Main breaker, 400 amperes, 3-pole DK . . . . . . . . . . . . . = 15X Total Height . . . . . . . . . . . = 34X
3. From Table 14-27: a. 34X Height (use 40X box) b. Box Height . . . . . . . . . 72 inches (1828.8 mm) c. Box Catalog Number. . . . YS2072 . . . . . . . . . . . . . . . . or EZB2072R Table 14-27. Box Tabulation — PRL3a “X” Units
Box Height Inches
mm
YS Box Catalog Number
LT Trim Catalog Number
EZ Box Catalog Number
EZ Trim Catalog Number
914.4 1219.2 1524.0 1828.8 2286.0
YS2036 YS2048 YS2060 YS2072 YS2090
LT2036S or F LT2048S or F LT2060S or F LT2072S or F LT2090S or F
EZB2036R EZB2048R EZB2060R EZB2072R EZB2090R
EZT2036S or F EZT2048S or F EZT2060S or F EZT2072S or F EZT2090S or F
1219.2 1524.0 1828.8 2286.0
YS2048 YS2060 YS2072 YS2090
LTV2048S or F LTV2060S or F LTV2072S or F LTV2090S or F
EZB2048R EZB2060R EZB2072R EZB2090R
EZTV2048S or F EZTV2060S or F EZTV2072S or F EZTV2090S or F
1219.2 1524.0 1828.8 2286.0
YS2848 YS2860 YS2872 YS2890
LTV2848S or F LTV2860S or F LTV2872S or F LTV2890S or F
— — — —
— — — —
100 – 400 Amperes 14X 23X 31X 40X 53X
36 48 60 72 90
600 Amperes 23X 31X 40X 53X
48 60 72 90
800 Amperes 23X 31X 40X 53X
48 60 72 90
Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish.
Standard Depth
Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm).
Top and Bottom Gutters
Standard widths are: 20-inch (508.0 mm) 100 – 600 amperes. 28-inch (711.2 mm) 800 amperes.
For more information visit: www.eaton.com
5-3/4 inches (146.1 mm). 5-1/2 inches (139.7 mm) minimum.
Side Gutters 4 inches (101.6 mm) minimum.
14
Panelboards Pow-R-Line C Panelboards
14-28
July 2007
PRL4
Type PRL4
Standards and Certifications UL 67, UL 50. Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information. ■ ■
Options and Accessories ■
Refer to Page 14-46.
Layout and Sizing PRL4B — Refer to Pages 14-33 through 14-35. ■ PRL4F — Refer to Pages 14-36 through 14-38. ■
Type PRL4B Circuit Breaker Panelboard
Product Description ■ ■ ■ ■ ■ ■
14
■ ■ ■
600 Vac maximum (250 Vdc). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. PRL4B circuit breaker panelboard. PRL4F fusible switch panelboard. 1200 ampere maximum mains. 1200 ampere maximum branch devices. Bolt-on branch devices. Factory assembled. Refer to Page 14-5 for additional information.
Type PRL4F Fusible Panelboard
Application Description Power distribution panelboard. Fully rated or series rated. ■ Interrupting ratings up to 200 kA symmetrical. ■ Suitable for use as Service Entrance Equipment, when specified on the order. ■ See Pages 14-5 through 14-18 for additional information. ■ ■
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-29
July 2007
PRL4
Product Selection Formula Pricing: Base Price + Branch Devices + Modifications = Total Price U.S. $ Table 14-28. Base Prices — PRL4 Main Lugs and Main Breakers Ampere Rating
240 Vac
Interrupting Rating (kA Symmetrical) 480 Vac
600 Vac
250 Vdc
Breaker Type
— — — — —
— — — — —
— — — — —
— — — — —
— — — — —
250 250 250 250
65 100 200 200
35 65 100 200
18 25 35 —
10 22 22 —
JD HJD JDC LCL
400 400 400 400 400 400 400 400
65 65 65 100 100 200 200 200
— 35 35 65 65 100 200 200
— 25 25 35 35 65 — 200
10 10 — 22 — 22 — —
DK KD CKD 23 HKD CHKD 23 KDC LCL LA-P
600 600 600 600 600 600 600 600
65 100 65 65 100 100 200 200
35 65 35 35 65 65 100 100
18 35 25 25 35 35 50 50
22 22 22 — 25 — 25 —
LGE LGH LD CLD 2 HLD CHLD 2 LDC CLDC 2
800 800 800 800 800
65 100 65 100 200
50 65 50 65 200
25 35 25 35 200
22 25 — — —
MDL HMDL CMDL 2 CHMDL 2 NB-P
800 800 800 800 800 800
65 100 200 65 100 200
50 65 100 50 65 100
25 35 65 25 35 65
— — — — — —
ND HND NDC CND 24 CHND 24 CNDC 24
1200 1200 1200 1200 1200 1200
65 100 200 65 100 200
50 65 100 50 65 100
25 35 65 25 35 65
— — — — — —
ND HND NDC CND 24 CHND 24 CNDC 24
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire, 1-Phase 2-Wire
3-Phase 3-Wire
Main Lug Only 250 400 600 800 1200
Main Breaker 1
1 2 3 4
14
For ground fault protection on main devices, see Modification 14 — Applies to 310 and 310+ Trip Units or Modification 15, Page 14-48. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame. Requires 44-inch (1117.6 mm) wide box.
Table 14-29. Base Prices — PRL4 Main Fusible Switches Ampere Rating
Interrupting Rating (kA Symmetrical)
Price U.S. $
240 Vac
3-Phase 4-Wire
480 Vac
Device Type
1-Phase 3-Wire, 1-Phase 2-Wire
3-Phase 3-Wire
Main Fusible Switch 240 Vac, 250 Vdc 567 200 400 600 8 800 8 1200 8
See Table 14-32
FDPB FDPW FDPW FDPW FDPW
Main Fusible Switch 600 Vac 56 200 400 600 8 800 8 1200 8 5 6 7 8
See Table 14-32
FDPB FDPW FDPW FDPW FDPW
For ground fault protection on main devices, see Modification 15, Page 14-48. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, add $308. per switch. Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below. No dc rating on 600, 800 and 1200 ampere switches.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Line C Panelboards
14-30
July 2007
PRL4 Table 14-30. Branch Devices — PRL4 Ampere Rating
14
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vdc
Breaker Type
15 – 60 15 – 60 70 – 100 70 – 100 15 – 50 2 15 – 20 15 – 20
10 34 10 10 34 10 10 34 10 34 10 34
— — — — — — —
— — — — — — —
— — — — — — —
BAB BAB-H BAB BAB-H QBGF QBAF 5 QBAG 6
15 – 60 15 – 60 70 – 100 70 – 100 15 – 30 15 – 20 15 – 20
22 34 22 22 34 22 22 34 22 34 22 34
— — — — — — —
— — — — — — —
— — — — — — —
QBHW QBHW-H QBHW QBHW-H QBHGF QBHAF 5 QBHAG 6
15 – 20 15 – 60 70 – 100 15 – 30
65 3 65 3 65 3 65 3
14 7 14 7 14 7 25 7
— — — —
— 14 14 —
GHQ 8 GHB 8 GHB 8 HGHB 8
15 – 60 70 – 100 15 – 60 70 – 100 110 – 150
18 9 18 9 18 18 18
14 7 14 7 14 14 14
— — 14 14 14
10 10 10 10 10
EHD EHD FDB FDB FDB
15 – 60 70 – 100 110 – 225 15 – 60 70 – 100 110 – 225
65 9 65 9 65 9 100 9 100 9 100 9
35 7 35 7 35 65 7 65 7 65
18 18 18 25 25 25
10 10 10 22 22 22
FD FD FD HFD HFD HFD
15 – 60 70 – 100 110 – 225 15 – 100
200 200 200 200
100 100 100 150
35 35 35 —
22 22 22 —
FDC FDC FDC FCL
100 – 225 100 – 225 100 – 225 100 – 225 100 – 225
22 42 65 100 200
— — — — —
— — — — —
— — — — —
EDB EDS ED EDH EDC
70 – 225 250 70 – 225 250 70 – 225 250
65 65 100 100 200 200
35 35 65 65 100 100
18 18 25 25 35 35
10 10 22 22 22 22
JD JD HJD HJD JDC JDC
125 – 250
200
200
—
—
LCL
250 – 400 100 – 400 100 – 400 100 – 400 100 – 400 100 – 400
65 65 65 100 100 200
— 35 35 65 65 100
— 25 25 35 35 65
10 10 — 22 — 22
DK KD CKD jkl HKD CHKD jkl KDC
200 – 400
200
200
—
—
LCL
250 – 600 300 – 600 300 – 600
65 65 65
35 35 35
18 25 25
22 22 —
LGE LD CLD j
1 2 3 4 5 6 7 8 9 j k l
Price U.S. $ Space Only 1
Price U.S. $ 1-Pole
2-Pole
3-Pole
1-Pole
2-Pole
3-Pole
Price U.S. $ 3-Pole Provision
Includes provisions for breaker types BAB, BAB-H, QBGF, QBHW, QBHW-H, QBHGF, GHQ, GHB, HGHB. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120 Vac. 2-pole breakers rated 120/240 Vac. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. 1-pole breakers rated 277 Vac. At 480 volts, must be used on 480Y/277 volt grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame. Available in single branch mounting only.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-31
July 2007
PRL4 Table 14-30. Branch Devices — PRL4 (Continued) Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vac
Device Type
250 – 600 300 – 600 300 – 600 300 – 600 300 – 600
100 100 100 200 200
65 65 65 100 100
35 35 35 50 50
22 25 — 25 25
LGH HLD CHLD 1 LDC CLDC 1
400 – 800 400 – 800 400 – 800 400 – 800
65 100 65 100
50 65 50 65
25 35 25 35
22 25 — —
MDL HMDL CMDL 1 CHMDL 1
400 – 800 400 – 800 400 – 800 400 – 800 400 – 800 400 – 800
65 100 200 65 100 200
50 65 100 50 65 100
25 35 65 25 35 65
— — — — — —
ND HND NDC CND 23 CHND 23 CNDC 23
600 – 1200 600 – 1200 600 – 1200 600 – 1200 600 – 1200 600 – 1200
65 100 200 65 100 200
50 65 100 50 65 100
25 35 65 25 35 65
— — — — — —
ND HND NDC CND 23 CHND 23 CNDC 23
4 4 4 4 4
FB-P LA-P LA-P NB-P NB-P
Price U.S. $ 1-Pole
2-Pole
Price U.S. $ Space Only 3-Pole
1-Pole
2-Pole
3-Pole
Price U.S. $ 3-Pole Provision
Integrally Fused, Current Limiting Circuit Breaker 15 – 100 125 – 225 250 – 400 400 – 600 700 – 800
200 200 200 200 200
200 200 200 200 200
200 200 200 200 200
Fusible Switches 240 Vac, 250 Vdc 5 30/30 6 60/60 6 100/100 6 200/200 100 200 400 600 7 800 7 1200 7
See Table 14-32
FDPW-Twin FDPW-Twin FDPW-Twin FDPB-Twin FDPW-Single FDPB-Single
See Table 14-32
FDPW-Single FDPW-Single FDPW-Single FDPW-Single
14
Fusible Switches 600 Vac 5 30/30 6 60/60 6 100/100 6 200/200 8 100 200 400 600 7 800 7 1200 7 1 2 3 4 5
See Table 14-32
FDPW-Twin FDPW-Twin FDPW-Twin FDPB-Twin FDPW-Single FDPB-Single
See Table 14-32
FDPW-Single FDPW-Single FDPW-Single FDPW-Single
100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. 100% rated breaker. Requires 44-inch (1117.6 mm) wide box. 100,000 AIC based on NEMA test procedure. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, add $308. per switch (T fuse clips not available for
200/200 twin switches). 6 7 8
When branches of a twin unit are of different ampere ratings, as a 30 – 60 twin unit, price and layout as a 60 – 60 twin unit; when a 60 – 100 twin unit, price and layout as a 100 – 100 twin unit. No dc rating on 600, 800 and 1200 ampere switches. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14-32
Panelboards Pow-R-Line C Panelboards July 2007
PRL4 Table 14-31. Branch Devices Earth Leakage Ground Fault Circuit Breakers — PRL4 (Adj. Pickup from 30 mA to 30 A) Ampere Rating
kAIC (sym.) Breaker Price U.S. $ Type 480 Vac 3-Pole
35 – 60 70 – 100 110 – 150
35 35 35
ELFD ELFD ELFD
35 – 60 70 – 100 110 – 150
65 65 65
ELHFD ELHFD ELHFD
35 – 60 70 – 100 110 – 150
100 100 100
ELFDC ELFDC ELFDC
100 – 250 100 – 250 100 – 250
35 65 100
ELJD ELHJD ELJDC
200 – 400 200 – 400 200 – 400
35 65 100
ELKD ELHKD ELKDC
Table 14-32. FDPW and FDPB Switch Ratings, 240 or 600 Vac Ampere Rating
Fuse Class Used
Short Circuit Ratings (Sym. Amperes)
30 – 100 200 Single 200 Twin 400, 600 1 800, 1200 1
R, J 2 R, J 2 R 3, J 2, T R 4, J 2, T L
200,000 200,000 200,000 200,000 200,000
1 2
3 4
No dc rating on 600, 800 and 1200 ampere switches. Class J fuse provisions are applicable to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 volts and below. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. When shunt trip is required, 400 – 600 ampere switches used with Class R fuses are rated 100,000 AIC.
Note: Terminals and external accessories are the same as standard breakers. F-Frame breakers are twin mounted (3X). J-Frame (3X) and K-Frame (4X) are single mounted only. 36-inch (914.4 mm) minimum box width.
14
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-33
July 2007
PRL4
Layout and Sizing — PRL4B Main Lug (MLO), Main Breaker, Neutral, Through-Feed (TFL) and Sub-Feed Lug (SFL) “X” Space Requirements. (For other configurations not shown, refer to Eaton.)
Standard Main Lug, Through-Feed and Sub-Feed Lugs a (500 kcmil Maximum) MLO, SFL MLO, TFL 10X
N
10X
see Figure 14-7 on Page 14-35.
•=
Blank means no bus under cover, to meet NEC cable bending space.
Main Breaker with Neutral (when required) (500 kcmil Maximum)
N
250 Aa, 400 Aa, 600 Aa, 800 A
*
250 A, 400 A, 600 A, 800 A
Main Breaker
N
7X
* 7X
* = Space available for branch devices. For device sizing,
19X
Main Breaker
*
*
*
ThroughFeed Lugs
3Ph 4W, 3Ph 3W
N
3Ph 4W
3Ph 4W, 3Ph 3W
3Ph 3W
800 A Vertically Mtd. MDL Main Breaker only in 24-inch (609.6 mm) wide box. Available with 38X and 50X Panel Height only.
MLO 12X
MLO, TFL
N
12X
N
2X
N
7X
Blank
Main Breaker
1200 A 36-inch (914.4 mm) Minimum Width
*
* 2X
Blank
7X
ThroughFeed Lugs
1200 A 36-inch (914.4 mm) Minimum Width 2X
Main Breaker
*
* Blank
2X
3Ph 4W
3Ph 4W, 3Ph 3W
Blank
3Ph 3W
Optional Main Lugs, Through-Feed and Sub-Feed Lugs a (750 kcmil Maximum) MLO, SFL 20X
MLO, TFL
N
20X
N
250 Aa, 400 Aa, 600 Aa, 800 A
*
* 3X
13X
Blank
9X
ThroughFeed Lugs
13X
250 A, 400 A, 600 A, 800 A
3X
Blank
MLO
1200 A 36-inch (914.4 mm) Minimum Width
N
20X
N
15X
*
Blank
11X
ThroughFeed Lugs
1200 A 36-inch (914.4 mm) Minimum Width 5X
3Ph 4W
Figure 14-5. PRL4B Layout 1
Sub-Feed lugs are available 250 – 600 amperes. For 600 ampere use 1200 ampere “A” space.
CA08101001E
ThroughFeed Lugs
MLO, TFL
* 5X
9X
3Ph 3W
3Ph 4W
20X
*
*
For more information visit: www.eaton.com
15X
*
* Blank
11X 3Ph 3W
ThroughFeed Lugs
14
14-34
Panelboards Pow-R-Line C Panelboards July 2007
PRL4 Panel Layout and Dimensions
Layout Example
To determine the dimensions of a given panelboard enclosure, make a layout sketch by fitting together the main, branch and lug modules according to the appropriate tables in the layout guide. Assign “X” units to each module as shown and obtain a total “X” number.
■
The height of the enclosure is related to the total “X” units in the layout as shown in Table 14-33. Three standard box heights are available to accommodate any and all layout arrangements. “X” unit totals that do not exactly match those in Table 14-33 must be rounded off to the next highest standard (26X, 38X, 50X). If a calculated “X” total for a panel exceeds 50X, the panel must be split into two or more separate sections with “X” space for through-feed lugs figured in for all but one section. If a neutral is required, a separate neutral bar and appropriate “X” space must be included in each section.
14
1 – PRL4B panelboard, 480Y/277 volt, 3-phase 4-wire 65 kA, 800 amperes, main lug, consisting of: ❑ 12 – 20 A/1-Pole HFD ❑ 2 – 250 A/3-Pole HJD ❑ 1 – 400 A/3-Pole HKD
20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X
Reference Figure 14-6 1. From layout guide, total “X” height of panel = 26X, (which is a design standard and no rounding off is necessary).
3X
250A/3P
3X
400A/3P
4X
Main Lugs
2. From Table 14-33, enclosure height for 26X panel = 57 inches (1447.8 mm). 3. Width = 24 inches (609.6 mm) — directly from layout guide.
250A/3P
800A 10X
Neutral Total =
26X
Figure 14-6. PRL4B Layout Example
4. Enclosure depth = 11.31 inches (287.0 mm) — standard for all PRL4 panelboards. Table 14-33. Box Dimensions — PRL4B “X” Units
Catalog Number
Inches Height
Width
Depth 1
Height
Width
26X 38X 50X
BX2457 BX2473 BX2490
57.00 73.50 90.00
24.00 24.00 24.00
11.31 11.31 11.31
1447.8 1866.9 2286.0
609.6 609.6 609.6
287.0 287.0 287.0
38X 50X
BX3673 BX3690
73.50 90.00
36.00 36.00
11.31 11.31
1866.9 2286.0
914.4 914.4
287.0 287.0
38X 50X
BX4473 BX4490
73.50 90.00
44.00 44.00
11.31 11.31
1866.9 2286.0
1117.6 1117.6
287.0 287.0
1
mm Depth 1
Box depth is 10.40 inches (264.2 mm), cover adds .90 inches (22.9 mm) to depth.
Note: 800 ampere maximum bus size in 24-inch (609.6 mm) wide box. Flush trims not available on PRL4B panels.
Top and Bottom Gutters 10.63-inch (269.9 mm) minimum.
Side Gutters — Minimum 24-inch (609.6 mm) wide box — 5-inch (127.0 mm). 36-inch (914.4 mm) wide box — 6-inch (152.4 mm). 44-inch (1117.6 mm) wide box — 8-inch (203.2 mm).
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-35
July 2007
PRL4
Filler
Breaker To Fusible Transition, All Widths
1X
Sub Panel 12X
18 Poles
20X
42 Poles
BAB ab 100 Amp QBHW ab GHB, HGHB, GHQ cd Max.
400 Amp. Maximum Bus Rating
1P
1X
2P
2P
2X
3P
3P
2P
2P
3P
24-Inch (609.6 mm) Wide Box
1P
3P
EHD, 225 Amp FDB, FD, Max. e HFD, FDC
3X
2X
225 Amp EDB, EDS, ED, EDH, EDC Max. f 3X
250 Amp JD, HJD, JDC Max.
2 or 3P
4X
400 Amp DK, KD, HKD, KDC, Max. CKD, CHKD
3P
2 or 3P
Load
3X
4X
600 Amp LGE, LGH Max.
Load
2 or 3P
6X
600 Amp LD, HLD, CLD, CHLD, LDC Max.
2 or 3P
3X
100 Amp FCL, FB-P Max.
2 or 3P
2 or 3P
3X
250 Amp JD, HJD, JDC Max.
36-Inch (914.4 mm) Wide Box
2 or 3P
2 or 3P
2 or 3P
2 or 3P
2 or 3P
400 Amp LCL, LA-P Max. 6X
800 Amp MDL, HMDL, Max. g CMDL, CHMDL
1200 Amp ND, HND, NDC Max. h
6X 44-Inch (1117.6 mm) Wide Box
2 or 3P
4X
400 Amp Max.
DK, KD, HKD, KDC
800 Amp Max.
NB-P
6X
▲ Breaker may be used as main.
1200 Amp CND, CHND, CNDC Max.
Figure 14-7. Layout for Branch and Horizontally Mounted Main Devices — PRL4B 1 2 3 4 5 6 7 8
BAB and QBHW breakers with shunt trips require one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size, and 3-pole is 4-pole size. If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. GHB, HGHB or GHQ breakers cannot be mixed on same subchassis as BAB, QBHW. If panel contains only GHB, HGHB or GHQ branch breakers, use a PRL2a panelboard. When only one single-pole breaker of the group is required on either side of chassis, the single-pole breaker space required changes from 1X to 2X. Minimum 36-inch (914.4 mm) wide box is required if optional #6 – 300 kcmil lug is required. MDL main breaker in 24-inch (609.6 mm) wide box, refer to Page 14-33. Optional 750 kcmil terminal requires 44-inch (1117.6 mm) wide box.
Note: See Page 14-33 for MLO or Neutral and Vertically Mounted Mains space requirements.
CA08101001E
For more information visit: www.eaton.com
14
Panelboards Pow-R-Line C Panelboards
14-36
July 2007
PRL4
Layout and Sizing — PRL4F Main Lug (MLO), Main Switch, Neutral, Through-Feed (TFL) and Sub-Feed Lug (SFL) “X” Space Requirements. (For other configurations not shown, refer to Eaton.)
Standard Main Lug, Through-Feed and Sub-Feed Lugs a (500 kcmil Maximum) MLO, SFL MLO, TFL 10X
N
10X
see Figure 14-10 on Page 14-38.
•=
Blank means no bus under cover, to meet NEC cable bending space.
Main Switch with Neutral (when required) (500 kcmil Maximum)
N
250 A a, 400 A a, 600 A a, 800 A
*
Main Switch
N
7X
* 7X
* = Space available for branch devices. For device sizing,
200 A, 400 A, 600 A
22X
Main Switch
* *
ThroughFeed Lugs
3Ph 4W
3Ph 4W, 3Ph 3W
* 7X
3Ph 3W
N
3Ph 4W, 3Ph 3W
400 A and 600 A Vertically Mounted Main Switch MLO 12X
MLO, TFL
N
12X
N
800 A 25X 1200 A 26X
1200 A
14
*
* 2X
Blank
7X
800 A, 1200 A
Through-Feed Lugs
* N
7X
800 A & 1200 A Vertically Mounted Main Switch b 36-inch (914.4 mm) or 44-inch (1117.6 mm) Wide Box
3Ph 4W
3Ph 4W, 3Ph 3W Optional Main Lugs, Through-Feed and Sub-Feed Lugs a (750 kcmil Maximum) MLO, SFL 20X
MLO, TFL
N
20X
N
250 A a, 400 A a, 600 A a, 800 A
*
* 3X
13X
Blank
9X
13X
250 A, 400 A, 600 A, 800 A
ThroughFeed Lugs
3X
Blank
3Ph 4W
9X
ThroughFeed Lugs
3Ph 3W
MLO 20X
*
*
MLO, TFL
N
20X
N
15X
1200 A
15X
1200 A
*
* 5X
Blank
11X
ThroughFeed Lugs
*
* 5X
Blank
11X
ThroughFeed Lugs
3Ph 3W
3Ph 4W
Figure 14-8. PRL4F Layout 1 2
Sub-Feed lugs are available 250 – 600 amperes, for 600 ampere use 1200 ampere “A” space. 800 ampere and 1200 ampere mains available only in vertical mounting.
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-37
July 2007
PRL4 Panel Layout and Dimensions
Layout Example
To determine the dimensions of a given panelboard enclosure, make a layout sketch by fitting together the main, branch and lug modules according to the appropriate tables in the layout guide. Assign “X” units to each module as shown and obtain a total “X” number.
PRL4F, 3-phase 4-wire, 208Y/120 volt complete with 400 ampere main switch and the following branches: ❑ 1 – 200 A/3-Pole ❑ 2 – 100 A/3-Pole ❑ 2 – 30 A/3-Pole Panel to have short circuit rating of 100,000 amperes symmetrical.
The height of the enclosure is related to the total “X” units in the layout as shown in Table 14-34. Three standard box heights are available to accommodate any and all layout arrangements. “X” unit totals that do not exactly match those in Table 14-34 must be rounded off to the next higher standard (38X, 50X). If a calculated “X” total for a panel exceeds 50X, the panel must be split into two or more separate sections with “X” space for through-feed lugs figured in for all but one section. If a neutral is required, a separate neutral bar and appropriate “X” space must be included in each section.
■
400 A Neutral 30 A/3P
Reference Figure 14-9
30 A/3P
7X 4X
100 A/3P 100 A/3P
4X
200 A/3P
6X
400 A 3-Pole Main Switch (Vert. Mounted)
22X
Total =
43X
Figure 14-9. Type PRL4F Layout Example
1. From layout guide, total “X” height of panel = 43X.
Note: In the above example if a horizontally mounted 400 ampere main switch were used, the enclosure size would be 73.50 H x 44.00 W x 11.31 D (1866.9 mm H x 1117.6 mm W x 287.0 mm D)
2. Rounded off to next higher standard = 50X. 3. From Table 14-34, enclosure height for 50X panel = 90 inches (2286.0 mm). 4. Width = 36 inches (914.4 mm). 5. Enclosure depth is standard for all PRL4 panelboards = 11.31 inches (287.0 mm). Table 14-34. Box Dimensions — PRL4F “X” Units
Catalog Number
Inches Height
Width
Depth 1
Height
Width
38X 50X
BX3673 BX3690
73.50 90.00
36.00 36.00
11.31 11.31
1866.9 2286.0
914.4 914.4
287.0 287.0
38X 50X
BX4473 BX4490
73.50 90.00
44.00 44.00
11.31 11.31
1866.9 2286.0
1117.6 1117.6
287.0 287.0
1
mm
Box depth is 10.40-inch (264.2 mm) cover adds .90-inch (22.8 mm) to depth.
Note: Flush trims not available on PRL4F panels.
Top and Bottom Gutters 10.63 inches (269.9 mm) minimum.
Side Gutters — Minimum 36-inch (914.4 mm) wide box: ❑ 8-inch (203.2 mm) — 200 ampere maximum ❑ 6-inch (152.4 mm) 400 — 1200 ampere maximum ■ 44-inch (1117.6 mm) wide box: ❑ 10-inch (254.0 mm) 200 — ampere maximum ❑ 8-inch (203.2 mm) 400 — 1200 ampere ■
CA08101001E
For more information visit: www.eaton.com
Depth 1
14
Panelboards Pow-R-Line C Panelboards
14-38
July 2007
PRL4
Fusible to Breaker Transition Requires 1X Filler
1X
30 Amperes
30 Amperes
4X
60 Amperes
60 Amperes
4X
100 Amperes 100 Amperes 250 Volts Max. 250 Volts Max.
200 Amperes Main or Branch Switch
100 Amperes
5X
6X
5X
100 Amperes
400 Amperes Branch Switch
9X
600 Amperes Branch Switch
11X
200 Amperes
200 Amperes
400 Amperes Main or Branch
600 Amperes Main or Branch
800 Amperes Branch
(11X With Shunt Trip)
6X
44-inch (1117.6 mm) Wide Box
14
36-inch (914.4 mm) Wide Box
100 Amperes
4X
1200 Amperes Branch
9X
(11X With Shunt Trip)
11X
11X
(16X With Shunt Trip)
15X
(16X With Shunt Trip)
Figure 14-10. Branch and Horizontally Mounted Main Device Layout — PRL4F
▲ Fusible switch may be used as horizontally main. ●
400 and 600 ampere horizontally mounted feeder switches in 36-inch (914.4 mm) or 44-inch (1117.6 mm) wide box. 400 and 600 ampere horizontally mounted main switches only in 44-inch (1117.6 mm) wide box. For vertically mounted main see Page 14-36 for sizing.
Note: See Page 14-36 for MLO or Neutral and Vertically Mounted Main space requirements.
For more information visit: www.eaton.com
CA08101001E
Panelboards Column Type
14-39
July 2007
Type PRL1a-LX
Product Description ■ ■ ■ ■ ■ ■ ■
240 Vac maximum. 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 225 ampere maximum mains. 100 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled. Refer to Page 14-5 for additional information.
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-35. Base Prices — PRL1a-LX Ampere Rating
Interrupting Rating (kA Sym.) 240 Vac
Breaker Type
— —
— —
100 100 100 100 100 100 100 100 100
10 18 22 22 42 65 65 100 100
BAB EHD QBHW EDB EDS ED FD EDH HFD
255 255 225 225
22 42 65 100
EDB EDS ED EDH
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire, 3-Phase 1-Phase 2-Wire 3-Wire
Main Lug Only 100 225
Main Breaker
Table 14-36. Branch Circuit Breakers — PRL1a-LX
Type PRL1a-LX, Column Type
Application Description ■ ■ ■ ■ ■
Lighting and appliance branch panelboard. Column mounting width. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. See Pages 14-5 through 14-18 for additional information.
Standards and Certification UL 67, UL 50. ■ Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information.
Ampere Rating
Breaker Interrupting Rating (kA Sym.) Type 1 240 Vac
15 – 60 70 80 – 100 15 – 50 3 15 – 50 3 15 – 20 15 – 20 15 – 30 15 – 30
10 10 10 10 10 10 10 10 10
BAB BAB BAB QBGF 4 QBGFEP 5 QBAF 6 QBAG 7 BABRP 8 BABRSP 8
15 – 60 70 80 – 100 15 – 30 15 – 30 15 – 20 15 – 20
22 22 22 22 22 22 22
QBHW QBHW QBHW QBHGF 4 QBHGFEP 5 QBHAF 6 QBHAG 7
Provision
—
—
1 2
■
Options and Accessories Pullbox and trough extensions. ■ See also Page 14-46. ■
Layout and Sizing ■
Refer to Page 14-40.
3
1-pole breakers are rated 120 Vac maximum. 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a midpoint delta grounded system. 50 ampere devices are available as 2-pole only.
Table 14-37. Pull Box With Extension Trough Includes pull box with trough extension. For additional trough extensions, refer to Table 14-38. Description
Catalog Number
Pullbox with 36" Trough Pullbox with 48" Trough Pullbox with 60" Trough Pullbox with 72" Trough Pullbox with 84" Trough
XCTXB036 XCTXB048 XCTXB060 XCTXB072 XCTXB084
Price U.S. $
Neutral Bars When Column Type panels are furnished with trough extensions and pull box, the neutral bar will be placed in the pull box unless otherwise specified. CA08101001E
For more information visit: www.eaton.com
Price U.S. $ 1-Pole 120 V
2-Pole 2-Pole 120/240 V 240 V 2
3-Pole 240 V
14
4 5 6 7 8
GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. Solenoid operated breaker.
When troughs and pull box are not furnished, the neutral bar will be located on the panel at the same end as the main. Table 14-38. Additional Trough Extensions Width and depth are the same as the panelboard. Length Inches
mm
Catalog Number
36.00 48.00 60.00 72.00 84.00
914.4 1219.2 1524.0 1828.8 2133.6
CTXB036 CTXB048 CTXB060 CTXB072 CTXB084
Price U.S. $
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
14-40
Panelboards Column Type July 2007
Type PRL1a-LX
Box Sizing and Selection
Cabinets
Assembled Circuit Breaker Panelboards
Boxes and trims are code-gauge steel, ANSI-61 light gray painted finish.
Box size, box and trim catalog numbers for standard Column Type panelboards listed are available from Tables 14-40 and 14-41.
Instructions 1. Using description of the required panelboard, select the rating and type of main required. a. 100 ampere panelboards — Table 14-40. b. 225 ampere panelboards — Table 14-41. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single poles, i.e., 3-pole breaker, count as 3 poles. Determine subfeed breaker or through-feed lug requirements.
14
16.00 (406.4)
6.00 (152.4)
12.00 (304.8)
Boxes are furnished without knockouts. Standard depth is 6.00 inches (152.4 mm). Standard width is 8.63 inches (219.1 mm).
Additional Extensions (If Required)
Top and Bottom Gutters 4.50 inches (114.3 mm) minimum.
Left Side Gutter 4.38 inches (111.2 mm) minimum. H Box Height
Pull Box Pull box is furnished without knockouts. Standard dimensions: 6.00 (152.4)
Table 14-39. Pull Box Dimensions Height
Width
Depth
Inches mm
Inches mm
Inches mm
12.00
304.8 16.00
406.4 6.00
152.4
8.63 (219.1)
Figure 14-11. PRL1a-LX Trough Extension, Dimensions in Inches (mm)
Trough Extension When extension troughs are used, Section 362-5 of the National Electrical Code, reading as follows, should be observed: 362-5. Number of Conductors. Wireways shall not contain more than 30 conductors at any cross section, unless the conductors are for signal circuits or are control conductors between a motor and its starter and used only for starting duty. The sum of the cross-sectional areas of all contained conductors at any cross section of a wireway shall not exceed 20 percent of the interior cross-sectional area of the wireway.
3. Select the panelboard main ampere rating from Tables 14-40 or 14-41. 4. Panelboard Type from first column, main breaker Frame and Designation, if applicable from second column, and sub-feed breaker Frame and Designation, if applicable, from the third column. 5. From Step #2, determine the number of branch circuits in Column 4. 6. Read box size, box and trim catalog numbers across columns to the right. All panels are surface mounted.
For more information visit: www.eaton.com
CA08101001E
Panelboards Column Type
14-41
July 2007
Type PRL1a-LX
Box Sizing and Selection (Continued) Table 14-40. 100 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing Panelboard Types
Main Breaker Types Mounting : (H) = Horizontal (V) = Vertical
Sub-Feed Breaker Types Vertical Mounting
Maximum Number of Branch Circuits Including Provisions
Main Breaker
BAB, QBHW (H)
— —
27 39
69.00 (1752.6) 8.63 (219.2) 6.00 (152.4) YSC969 81.00 (2057.4) 8.63 (219.2) 6.00 (152.4) YSC981
LTC969S LTC981S
Main Lugs or Main Breaker
EHD, EDB, EDS, ED, FD, HFD (V)
— —
30 42
69.00 (1752.6) 8.63 (219.2) 6.00 (152.4) YSC969 81.00 (2057.4) 8.63 (219.2) 6.00 (152.4) YSC981
LTC969S LTC981S
Main Lugs or Main Breaker with 100 A Through-Feed Lugs or Sub-Feed Breaker
EHD, EDB, EDS, ED, FD, HFD (V)
EHD, FD, HFD
30 42
78.00 (1981.2) 8.63 (219.2) 6.00 (152.4) YSC978 90.00 (2286.0) 8.63 (219.2) 6.00 (152.4) YSC990
LTC978S LTC990S
Maximum Number of Branch Circuits Including Provisions
Box Dimensions Inches Height
Width
Trim Catalog Number 2
1
Box Dimensions Inches (mm) Height
Width
Depth
Box Catalog Number
Trim Catalog Number 1
Add suffix B to trim catalog number for bottom fed panelboards (i.e., LTC969SB).
Table 14-41. 225 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing Panelboard Types
Main Breaker Types
Sub-Feed Breaker Types
Vertical Mounting
Depth
Box Catalog Number
Main Lugs or Main Breaker
EDB, EDS, ED, EDH
— —
30 42
69.00 (1752.6) 81.00 (2057.4)
8.63 (219.2) 6.00 (152.4) YSC969 8.63 (219.2) 6.00 (152.4) YSC981
LTC969S LTC981S
Main Lugs or Main Breaker with 225 A Through-Feed Lugs or Sub-Feed Breaker
EDB, EDS, ED, EDH
EHD, FD, HFD, EDB, EDS, ED, EDH
30 42
78.00 (1981.2) 90.00 (2286.0)
8.63 (219.2) 6.00 (152.4) YSC978 8.63 (219.2) 6.00 (152.4) YSC990
LTC978S LTC990S
2
Add suffix B to trim catalog number for bottom fed panelboards (i.e., LTC969SB).
CA08101001E
For more information visit: www.eaton.com
14
Panelboards Column Type
14-42
July 2007
Type PRL2a-LX
Product Description ■ ■ ■ ■ ■ ■ ■
480Y/277 Vac maximum (125 Vdc). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 225 ampere maximum mains. 100 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled. Refer to Page 14-5 for additional information.
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-42. Base Prices — PRL2a-LX Ampere Interrupting Rating (kA Symmetrical) Breaker Price U.S. $ Rating 240 Vac 480Y/277 Vac 125/250 Vdc Type 3-Phase 1-Phase 3-Wire 1, 4-Wire 1-Phase 2-Wire
3-Phase 3-Wire
Main Lug Only 100 225
— —
— —
— —
— —
Main Breaker 100 100
65 18
14 14
14 10
GHB EHD
100 100 100
65 100 200
35 65 100
10 22 22
FD HFD FDC
225 225 225 225
65 65 100 200
— 35 65 100
— 10 22 22
ED FD HFD FDC
1
These system voltages apply to 240 volts.
Table 14-43. Branch Circuit Breakers — PRL2a-LX
14
Type PRL2a-LX, Column Type
Application Description ■ ■ ■ ■ ■
Lighting and appliance branch panelboard. Column mounting width. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. See Pages 14-5 through 14-18 for additional information.
Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac 2
480Y/277 Vac
125/250 Vdc
Breaker Type
15 – 20 15 – 20 25 – 60 70 – 100 15 – 30 15 – 20 15 – 30
65 65 65 65 65 65 65
14 14 14 14 25 14 14
— 14 14 14 — — —
GHQ 3 GHB 3 GHB 3 GHB 3 HGHB 3 GHQRSP 4 GHBS 34
15 – 60
—
14
—
GHBGFEP 35
Provision
—
—
—
—
2 3 4 5
Table 14-44. Pull Box With Extension Trough Includes pull box with trough extension. For additional trough extensions, refer to Table 14-45. Description
Catalog Number
UL 67, UL 50. Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information.
Pullbox with 36" Trough Pullbox with 48" Trough Pullbox with 60" Trough Pullbox with 72" Trough Pullbox with 84" Trough
XCTXB036 XCTXB048 XCTXB060 XCTXB072 XCTXB084
■
Price U.S. $
Options and Accessories
Neutral Bars
Pullbox and trough extensions. ■ See also Page 14-46.
When Column Type panels are furnished with trough extensions and pull box, the neutral bar will be placed in the pull box unless otherwise specified.
■
Layout and Sizing ■
Refer to Page 14-43.
1-Pole
2-Pole
3-Pole
Interrupting ratings in this column are applicable to 120 Vac for 1-pole breakers. At 480 volts, must be used on 480Y/277 volt grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires two pole spaces.
Standards and Certifications ■
Price U.S. $
Table 14-45. Additional Trough Extensions Width and depth are the same as the panelboard. Length Inches
mm
Catalog Number
36.00 48.00 60.00 72.00 84.00
914.4 1219.2 1524.0 1828.8 2133.6
CTXB036 CTXB048 CTXB060 CTXB072 CTXB084
Price U.S. $
When troughs and pull box are not furnished, the neutral bar will be located on the panel at the same end as the main.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Column Type
14-43
July 2007
Type PRL2a-LX
Box Sizing and Selection
Cabinets
Assembled Circuit Breaker Panelboards
Boxes and trims are code-gauge steel, ANSI-61 light gray painted finish.
Box size, box and trim catalog numbers for standard column type panelboards listed are available from Tables 14-47 and 14-48.
Instructions 1. Using description of the required panelboard, select the rating and type of main required. a. 100 ampere panelboards — Table 14-47. b. 225 ampere panelboards — Table 14-48. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single poles, i.e., 3-pole breaker, count as 3 poles.
12.00 (304.8)
Boxes are furnished without knockouts. Standard depth is 6.00 inches (152.4 mm). Standard width is 8.63 inches (219.1 mm).
Additional Extensions (If Required)
Top and Bottom Gutters 4.50 inches (114.3 mm) minimum.
Left Side Gutter 3.31 inches (84.2 mm) minimum. H Box Height
Pull Box Pull box is furnished without knockouts. Standard dimensions: 6.00 (152.4)
Table 14-46. Pull Box Dimensions Height
Width
Depth
Inches mm
Inches mm
Inches mm
12.00
304.8 16.00
406.4 6.00
152.4
8.63 (219.1)
Figure 14-12. PRL2a-LX Trough Extension, Dimensions in Inches (mm)
Trough Extension When extension troughs are used, Section 362-5 of the National Electrical Code, reading as follows, should be observed: 362-5. Number of Conductors. Wireways shall not contain more than 30 conductors at any cross section, unless the conductors are for signal circuits or are control conductors between a motor and its starter and used only for starting duty. The sum of the cross-sectional areas of all contained conductors at any cross section of a wireway shall not exceed 20 percent of the interior cross-sectional area of the wireway.
Determine sub-feed breaker or through-feed lug requirements. 3. Select the panelboard main ampere rating from Tables 14-47 or 14-48. 4. Panelboard Type from first column, main breaker Frame and Designation, if applicable from second column, and sub-feed breaker Frame and Designation, if applicable, from the third column. 5. From Step #2, determine the number of branch circuits in Column 4. 6. Read box size, box and trim catalog numbers across columns to the right. All panels are surface mounted.
CA08101001E
16.00 (406.4)
6.00 (152.4)
For more information visit: www.eaton.com
14
Panelboards Column Type
14-44
July 2007
Type PRL2a-LX
Box Sizing and Selection (Continued) Table 14-47. 100 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing Panelboard Types
Main Breaker Types Mounting: (H) = Horizontal (V) = Vertical
Sub-Feed Breaker Types Vertical Mounting
Maximum Number of Branch Circuits Including Provisions
Main Breaker
GHB (H)
— —
27 39
69.00 (1752.6) 8.63 (219.2) 6.00 (152.4) YSC969 81.00 (2057.7) 8.63 (219.2) 6.00 (152.4) YSC981
LTC969S LTC981S
Main Lugs or Main Breaker
EHD, FD HFD, FDC (V)
— —
30 42
69.00 (1752.6) 8.63 (219.2) 6.00 (152.4) YSC969 81.00 (2057.7) 8.63 (219.2) 6.00 (152.4) YSC981
LTC969S LTC981S
Main Lugs or Main Breaker with 100 A Through-Feed Lugs or Sub-Feed Breaker
EHD, FD HFD, FDC (V)
EHD, FD, HFD
30 42
78.00 (1981.2) 8.63 (219.2) 6.00 (152.4) YSC978 90.00 (2286.0) 8.63 (219.2) 6.00 (152.4) YSC990
LTC978S LTC990S
Maximum Number of Branch Circuits Including Provisions
Box Dimensions Inches
Trim Catalog Number 2
1
Box Dimensions Inches Height
Width
Depth
Box Catalog Number
Trim Catalog Number 1
Add suffix B to trim catalog number for bottom fed panelboards (i.e., LTC969SB).
Table 14-48. 225 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing Panelboard Types
Main Breaker Types
Sub-Feed Breaker Types
Vertical Mounting
14
Height
Width
Depth
Box Catalog Number
Main Lugs or Main Breaker
ED, FD HFD, FDC
— —
30 42
69.00 (1752.6) 8.63 (219.2) 6.00 (152.4) YSC969 81.00 (2057.7) 8.63 (219.2) 6.00 (152.4) YSC981
LTC969S LTC981S
Main Lugs or Main Breaker with 225 A Through-Feed Lugs or Sub-Feed Breaker
ED, FD HFD, FDC
EHD, FD, HFD, ED, EDH
30 42
78.00 (1981.2) 8.63 (219.2) 6.00 (152.4) YSC978 90.00 (2286.0) 8.63 (219.2) 6.00 (152.4) YSC990
LTC978S LTC990S
2
Add suffix B to trim catalog number for bottom fed panelboards (i.e., LTC969SB).
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line C Panelboards
14-45
July 2007
Boxes and Trims
Boxes and Trims Only — Type 1 Table 14-49. Types PRL1a, PRL2a and PRL3a (400 Amperes Maximum) Box Dimensions
20.00-inch W x 5.75-inch D (508.0 mm W x 146.1 mm D)
1
Height
YS Box
Inches
mm
Catalog Number
36.00 42.00 48.00 60.00 72.00 90.00
914.4 1066.8 1219.2 1524.0 1828.8 2286.0
YS2036 YS2042 YS2048 YS2060 YS2072 YS2090
Inches
mm
Catalog Number
36.00 48.00 60.00 72.00 90.00
914.4 1219.2 1524.0 1828.8 2286.0
YS2036 YS2048 YS2060 YS2072 YS2090
EZ Box 1
LT Trim Price U.S. $
Catalog Number
Price U.S. $
LT2036S or F LT2042S or F LT2048S or F LT2060S or F LT2072S or F LT2090S or F
Catalog Number
EZ Trim 1 Price U.S. $
EZB2036R EZB2042R EZB2048R EZB2060R EZB2072R EZB2090R
Catalog Number
Price U.S. $
EZT2036S or F EZT2042S or F EZT2048S or F EZT2060S or F EZT2072S or F EZT2090S or F
EZ box must be used with EZ trim.
Table 14-50. Type PRL3a (600 Amperes) Box Dimensions
20.00-inch W x 5.75-inch D (508.0 mm W x 146.1 mm D)
2
Height
YS Box
EZ Box 2
LT Trim Price U.S. $
Catalog Number
Price U.S. $
LTV2036S or F LTV2048S or F LTV2060S or F LTV2072S or F LTV2090S or F
Catalog Number EZB2036R EZB2048R EZB2060R EZB2072R EZB2090R
EZ Trim 2 Price U.S. $
Catalog Number
Price U.S. $
EZTV2036S or F EZTV2048S or F EZTV2060S or F EZTV2072S or F EZTV2090S or F
EZ box must be used with EZ trim.
Table 14-51. Type PRL3a (800 Amperes) Box Dimensions
28.00-inch W x 5.75-inch D (711.2 mm W x 146.1 mm D)
Height
YS Box
Inches
mm
Catalog Number
36.00 48.00 60.00 72.00 90.00
914.4 1219.2 1524.0 1828.8 2286.0
YS2836 YS2848 YS2860 YS2872 YS2890
LT Trim Price U.S. $
Catalog Number
Price U.S. $
LTV2836S or F LTV2848S or F LTV2860S or F LTV2872S or F LTV2890S or F
14
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Modifications
14-46
July 2007
Types PRL1a, 2a, 3a, 4, Column Table 14-52. Modifications — Alphabetical Index Modification
14
Item
Available on Panelboard Types PRL1a
PRL2a
PRL3a
PRL4B
PRL4F
Column Type 1
Ambient Compensating Breakers Bus Density Cabinets — Special: Types 2, 3R, 4, 4X, 12
1 2 3
No Yes Yes
No Yes Yes
Yes Yes Yes
Yes Yes Yes
— Yes Yes
No Yes No
Complete Assembly Compression Type Lugs, Mains Only Concealed Trim Clamps (LT Trim)
4 5 6
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes No
Yes Yes No
Yes Yes No
Conduit Covers Copper Lugs Copper Main Bus
7 8 9, 9a, 9b
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
No Yes Standard
Directory Frame — Metal Doors, Special
10 11
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
No Yes
Fungus Proof Ground Bar Electronic Trip Units
12 13 14
Yes Yes No
Yes Yes No
Yes Yes No
Yes Yes Yes
Yes Yes —
Yes Yes No
Ground Fault Protection (Zero Sequence) Handle Lockoff Device Hinges, Special (LT Trim)
15 16 17
No Yes Yes
No Yes Yes
No Yes Yes
Yes Yes Yes
Yes Std. Yes
No Yes No
Increased Dimensions Increased Panel Bus Rating Interiors to Fit Existing Boxes
18 19 20
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
No No Yes
No No Yes
No No No
Locks, Special (LT Trim) Metering Devices Molded Case Switches
21 31 22
Yes No Yes
Yes No Yes
Yes No Yes
Yes Yes Yes
Yes Yes No
No No Yes
Nameplates Engraved Neutral Rated 200% Painting and Special Coating
23 24 25
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Permanent Circuit Numbers Remote Control Switches (ASCO 920) Service Entrance
26 27 28
Yes No Yes
Yes No Yes
Yes Yes Yes
Yes No Yes
Yes No Yes
Yes No No
Shunt Trips Split Bus or Meter Loop Sub-Feed Breakers
29 30 33
Yes No Yes
Yes No Yes
Yes Yes Yes
Yes No No
Yes No No
Yes No Yes
Sub-Feed Lugs Sub-Metering, IQ Energy Sentinel Surge (Lightning) Arrester
34 32 35
Yes No Yes
Yes No Yes
Yes No Yes
Yes Yes Yes
Yes No Yes
No No No
Tamperproof Screws (LT Trim) Through-Feed Lugs Time Clock Space Only
36 37 38
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes —
Yes Yes —
Yes Yes No
Touchup Paint TVSS (Transient Voltage Surge Suppression) Terminals, Copper Only for Breakers
39 40 41
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
Yes Yes —
Yes No Yes
1
Where modifications are listed as available for Column Type panelboards (PRL1a–LX, PRL2a–LX), the list price additions are the same as shown for PRL1a and PRL2a panelboards unless shown otherwise.
For more information visit: www.eaton.com
CA08101001E
Panelboards Modifications
14-47
July 2007
Types PRL1a, 2a, 3a, 4, Column 1. Ambient Compensating Breakers For ambient compensating breakers (where available) in lieu of standard breakers, add 10 percent to panelboard branch breaker and to main breaker list prices, if required. (Not UL listed.)
2. Bus Density Main bus ampere rating is determined by UL listed temperature test. For 750 ampere per square inch aluminum or 1000 ampere per square inch copper, make price addition as follows: Table 14-53. Modification 2 Panel Type
Maximum Amperes
Price U.S. $
Aluminum — 750 Amperes per Square Inch PRL1a, 2a
100 225 400
PRL3a
250 400
PRL4
400 800 100 225 400
PRL3a
250 600
PRL4
Modification
Price U.S. $
PRL1a, PRL2a (20-inch (508.0 mm) wide) PRL1a, PRL2a (28-inch (711.2 mm) wide)
Fabricated sheet metal to cover open conduits above and/or below standard Type 1 box.
PRL3a 2 (28-inch (711.2 mm) wide) (600 ampere maximum)
Table 14-59. Modification 7 Cover Type
PRL4 (24-inch (609.6 mm) or 36-inch (914.4) wide only) Must also add bus density price from Modification 2 for PRL4
Type 4 Enclosure or Type 4X Stainless Steel Enclosure At 600 amperes, PRL3a requires the addition of density rated copper bus for Type 3R or 12 enclosure.
Complete assembly of panelboard box, interior and trim prior to shipment when required. Description
Price U.S. $
400 1200 Add per Panel
Modification
Price U.S. $
Type 1 Enclosure 28-inch (711.2 mm) wide in place of standard 20-inch (508.0 mm) wide PRL1a, PRL2a, PRL3a
Type 2 Enclosure (Drip-proof with gasketed trim) PRL1a, PRL2a, PRL3a (20-inch (508.0 mm) wide)
Type 3R Enclosure PRL1a, PRL2a (20-inch (508.0 mm) wide) PRL1a, PRL2a (28-inch (711.2 mm) wide) PRL3a 1 (20-inch (508 mm) wide) (600 ampere maximum) PRL3a 1 (28-inch (711.2 mm) wide) (600 ampere maximum) PRL4 (24-inch (609.6 mm) or 36-inch (914.4) wide only) 1
At 600 amperes, PRL3a requires the addition of density rated copper bus for Type 3R or 12 enclosure.
5. Compression Main Lugs — Type VCEL For other terminal types and box sizes, refer to Eaton. Table 14-56. Modification 5 Main Amperes
Wire Range and No. of Lugs Per Phase
100 225 250
Price U.S. $ Per Panel
(1) #8 – 1/0 (1) #4 – 300 kcmil (1) #2/0 – 500 kcmil
400 (PRL1a, 2a, 3a) (2) #2/0 – 500 kcmil 400 (PRL4) (2) 500 – 750 kcmil 600 (PRL3a) 600 (PRL4) 800 (PRL4) 1200
(2) #2/0 – 500 kcmil (2) 500 – 750 kcmil (3) 500 – 750 kcmil (4) 500 – 750 kcmil
100 225 250 400 600
PRL1a, PRL2a 0 0 — 0 —
8. Copper Lugs Optional copper mechanical main lugs only. (Includes main incoming neutral lug.) Table 14-60. Modification 8 Main Amperes
Wire Range and Number Price of Lugs Per Phase U.S. $
100 225 250 400 600 800 1200
(1) #14 – 1/0 (1) #6 – 250 kcmil (1) #6 – 250 kcmil (2) #1/0 – 600 kcmil (2) #1/0 – 600 kcmil (2) #1/0 – 600 kcmil (3) #1/0 – 600 kcmil
Table 14-61. Modification 8 — Box Height Additions Main PRL1a, PRL3a PRL3a PRL4 Amperes PRL2a without with Neutral Neutral 100 225 250 400 600 800 1200
PRL3a without Neutral
PRL3a with Neutral
0X — 2X 0X 0X
0X — 5X 0X 0X
0 0 — 0 — — —
0X — 0X 0X 1X — —
0X — 0X 0X 1X — —
— — 0X 0X 0X 0X 0X
9. Copper Main Bus Table 14-62. Modification 9 Main Bus Ampere Rating
Table 14-57. Modification 5 — Box Height Additions Main Amperes
Price U.S. $ Per Foot
Conduit Enclosing Shield (open back) PRL1a, PRL2a, PRL3a PRL4 — Refer to Eaton Conduit Enclosure (solid back) PRL1a, PRL2a, PRL3a PRL4 — Refer to Eaton
Table 14-55. Modification 4
Table 14-54. Modification 3
Price U.S. $
7. Conduit Covers
PRL3a 2 (20-inch (508 mm) wide) (600 ampere maximum)
4. Complete Assembly
3. Special Cabinet (Box) Construction
Description Add per panel PRL1a, PRL2a, PRL3a
Refer to Eaton
Note: Copper bus density adder is in addition to copper bus price per modification 9.
Table 14-58. Modification 6
Type 12 Enclosure
2
Copper — 1000 Amperes per Square Inch PRL1a, 2a
6. Concealed Trim Clamps — LT Trim
Table 14-54 Modification 3 (Continued)
Price U.S. $ Addition Per Panel Panel Type PRL1a, PRL3a PRL4 PRL2a
100 225 – 250 400 600 800 1200
Maximum size for PRL1a and PRL2a panels: 1 – 750 kcmil per phase, or 2 – 500 kcmil per phase. For PRL4 panels, see layout pages.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
Panelboards Modifications
14-48
July 2007
Types PRL1a, 2a, 3a, 4, Column 9a. Silver-Plated Copper Main Bus Table 14-63. Modification 9a Main Bus Ampere Rating
Price U.S. $ Addition Per Panel PRL3a
Common trim for two section panels with boxes bolted together. (LT Trim) (PRL1a, PRL2a, PRL3a only)
9b. Tin-Plated Copper Main Bus (PRL1a, 2a, 3a, Only) Table 14-64. Modification 9b Price U.S. $ Addition Per Panel Panel Type PRL1a, PRL2a
PRL3a
100 225 – 250 400
Standard flush lock with quarter turn fasteners at top and bottom of trim door (LT Trim) (standard on doors 48-inch (1219.2 mm) high and over). (PRL1a, PRL2a, PRL3a only) To provide a trim with a lockable door for PRL4 panels (door-in-door is standard with this adder). Includes National lock with standard keying. 1 Add per panel 1
600 800
Extra depth box is required. Box will be 12.82-inch (325.6 mm) deep.
10. Directory Frame — Metal Table 14-65. Modification 10
For fungus proofing external portions of circuit breakers and all non-metallic parts, add 10 percent of total panelboard list price. For fungus proofing fusible switches and all non-metallic parts, add 20 percent of total panelboard list price.
Metal Frame, Plastic Cover
Price U.S. $
Table 14-68. Modification 14 — Applies to 310 and 310+ Trip Units Description
13. Ground Bar
N-Frame Circuit Breaker Digitrip RMS310 LS Digitrip RMS310 LSI Digitrip RMS310 LSG 3 Digitrip RMS310 LSIG 3 Digiview Ammeter for 310+ Trip Unit 3
Main breaker only.
For main devices only (circuit breakers or FDPW switch) in PRL4 assembled panels. Available in 250 – 1200 ampere panels. Price includes current monitors, ground bar, static sensor, shunt trip, necessary space, mounting and connecting in panelboards. Price does not include circuit breaker or FDPW switch. Zero sequence ground fault is available with the following family of main devices: Table 14-69. Modification 15 Main Device
Table 14-67. Modification 13 Panel Type
Price U.S. $ Aluminum Terminal Bar for Aluminum or Copper Cable
Copper Terminal Bar for Copper Cable Only
Std. Insulated/ Std. Insulated/ Isolated 2 Isolated 2 PRL1a PRL2a PRL3a PRL4
Column Type In Pull Box In Gutter 2
Price U.S. $ Addition
15. Zero Sequence Ground Fault Protection
12. Fungus Proofing
Frame Type
14. Electronic Trip Units (Type PRL4 Only)
K-, L- and M-Frame Circuit Breaker (3-pole only) Digitrip RMS310 LS Digitrip RMS310 LSI Digitrip RMS310 LSG 3 Digitrip RMS310 LSIG 3
Door-in-door, one door over interior and one which exposes gutter. (LT Trim) (PRL1a, PRL2a, PRL3a only)
600 800 1200
14
Price U.S. $ Addition
PRL4
100 225 – 250 400
Main Bus Ampere Rating
Table 14-66. Modification 11 Description
Panel Type PRL1a, PRL2a
11. Trim and Door Modifications — Special Fronts and Doors
For PRL1a, 2a, 3a and Column Type panelboards. The insulated/isolated ground bar includes a standard ground bar.
Price U.S. $ Each
JD, KD, LD, MDL, ND, LCL, LA-P, NB-P FDPW Switches (400 – 1200 amperes)
16. Circuit Breaker Handle Lockoff Devices Table 14-70. Modification 16 Breaker Types
Price U.S. $ Each
Non-Padlockable BAB, QBHW, GHB, EHD, FDB, FD, ED, EDH, EDC, HQP, QPHW JD, KD, MDL, ND
Padlockable EHD, FDB, FD, HFD, FDC, ED, EDH, EDC, GHB, BAB, QBHW, HQP, QPHW JD, KD, LD, MDL, ND
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Modifications
14-49
July 2007
Types PRL1a, 2a, 3a, 4, Column 17. Special Hinges — LT Trim
22. Molded Case Switches
25. Painting and Special Coatings
Piano hinges in lieu of standard hinges.
The following table gives list price deductions when molded case switches are substituted for standard breakers:
Standard boxes are code-gauge galvanized sheet steel. Standard trims are code-gauge sheet steel with a rust inhibiting phosphatized coating and finished with ANSI-61.
Table 14-71. Modification 17 Description
Price U.S. $
Add for each panel door
Table 14-75. Modification 22 Not UL Listed
18. Increased Dimensions (PRL1a, PRL2a and PRL3a Only) Type 1 Enclosure Only
Breaker Frame
Table 14-72. Modification 18
EHD FD
480 600
100 225
JD DK KD
600 240 600
250 400 400
LD MDL ND
600 600 600
600 800 1200
Description
Max. Volts
Max. Amps
3-Pole
Price U.S. $
Increased End Gutters 4 inch (101.6 mm) Top or Bottom 7 inch (177.8 mm) Top or Bottom 12 inch (304.8 mm) Top or Bottom
Increased Side Gutters 4 inch (101.6 mm) Left or Right 7 inch (177.8 mm) Left or Right 12 inch (304.8 mm) Left or Right
Table 14-73. Modification 19
Mastic back and installed by purchaser, per nameplate
Price U.S. $ 3Ph 4W
1Ph 3W
PRL1a, PRL2a, PRL3a 100 – 225/250 A 225 – 400 A 400 – 600 A (PRL3a)
26. Permanent Circuit Numbers Table 14-80. Modification 26 Description
Refer to Eaton.
21. Special Locks Table 14-74. Modification 21 Description
Price U.S. $
27. Remote Control Switches — ASCO 920 Electrically operated, mechanically held remote control switch directly mounted to panelboard bus for total or split bus switching applications. (For split bus applications, make price addition from Modification 30.)
Table 14-77. Modification 24
20. Interior and Fronts to Fit Existing Boxes
Price U.S. $
LT Type Trim Yale 511S with rosette Yale 4651S (LL803 Key) Master keying — above locks or standard lock — per panelboard Corbin 15767 (Cat. #60 Key) PRL1a, PRL2a, PRL3a Tee handle and 3-point catch PRL1a, PRL2a, PRL3a National metal lock with standard keying PRL1a, PRL2a, PRL3a National metal lock with GE75 keyway PRL1a, PRL2a, PRL3a, PRL4
Neutral Price U.S. $ Rating PRL1a, PRL3a PRL2a
100 225 250
225 450 500
400 600
800 1200
PRL4
480 Vac maximum short circuit rating of panelboard will be 22 kAIC maximum. List prices include complete installation in the panelboard with a screw cover over the switch compartment. Pushbuttons or other control devices are not included. For control circuit modifications, refer to Eaton.
Table 14-78. Modification 24 — Box Height Additions Main Bus Rating
Price U.S. $ Per Panel
To provide permanently attached MicartaT circuit numbers.
Fixed to panel trim with two screws or rivets, per nameplate PRL1a, PRL2a, PRL3a only
Main Bus Rating
Price U.S. $ Each Box
Painted Trims or Boxes (other than ANSI-61)
24. Neutral Rated 200%
PRL4 250 – 400 A 400 – 600 A 600 – 800 A 800 – 1200 A
Description Painted Boxes (ANSI-61)
Table 14-76. Modification 23 Type
Table 14-79. Modification 25
2-Pole
23. Nameplates, Engraved
19. Increased Panel Main Bus Rating Panel Type
Price U.S. $ Deduction
Neutral PRL1a, Rating PRL2a
PRL3a
PRL4
Table 14-81. Modification 27 — Remote Control Switches (PRL3a Only) Switch Rating Amperes
100 225 250
225 450 500
0 0 —
0X — 3X
— — 0X
30 60 75
400 600
800 1200
0 —
3X 3X
0X 0X
100 150 200 225
Note: Prices and dimensions based on mechanical lugs. For compression or copper lugs, refer to Eaton.
For 800 and 1200 ampere PRL4 with 200% neutral, refer to Eaton.
Price U.S. $ Additions 3-Pole
2-Pole
Table 14-82. Modification 27 — Remote Control Switch Modifications Description
Price U.S. $ Additions
2-wire control relay 3-wire control relay Control power transformer To provide hinged cover in place of standard screw cover
EZ Type Trim Standard Lock, Keyed GE75 Standard Lock, Keyed to Corbin TEU-1 Standard Lock, Keyed to Corbin Cat 60 Standard Lock, Keyed to Corbin WEM1
Note: PRL4 with door includes National lock with standard keying. See Modification 11.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
14-50
Panelboards Modifications July 2007
Types PRL1a, 2a, 3a, 4, Column 28. Service Entrance
30. Split Bus or Meter Loop (250 A Max.)
To provide a Service Entrance Label as detailed under the “Service Entrance Equipment” in application considerations. Only panelboards meeting these requirements can be labeled as such. The requirement for a Service Entrance Label must be noted on order entry. Includes neutral disconnect link and Service Entrance Equipment Label. (Ground bar not included — see Modification 13.)
Panel type PRL3a only. For enclosure size, refer to Eaton.
Table 14-83. Modification 28 Panel Type
Price U.S. $
PRL1a, PRL2a, PRL3a PRL4
14
Table 14-85. Modification 30 Main Bus Amperes
Price U.S. $ Addition 3Ph 4W, 3Ph 3W 1Ph 3W, 1Ph 2W
100 – 250
31. Metering Devices (PRL4 Only) IQ digital metering for incoming service. Devices are installed in chassis mounted compartment with hinged door. Standard CTs (1200 amperes maximum) are included with devices. Requires copper bus at 1200 amperes.
32. Sub-Metering IQ Energy Sentinel (PRL4 Only) Microprocessor-based breaker mounted device to monitor power and energy (kW, kWH, kW demand). Device mounts on the load side of 3-pole F-, J- and K-Frame feeder breakers. Units are shipped with the interior for field installation. Minimum box width of 36 inches (914.4 mm) is required. Table 14-87. Modification 32 IQ Energy Sentinel
Price U.S. $
F-Frame 3-pole (150 A maximum) J-Frame 3-pole K-Frame 3-pole
Table 14-86. Modification 31
29. Shunt Trip for Main or Branch Circuit Breaker and FDPW Switches
Device
Box Height Addition
For tripping device from a remote point. Voltage and frequency must be specified. Wiring to terminal blocks is not included. Standard leads extend 18-inches (457.2 mm) out of device.
IQ 110, CTs IQ 115, CTs
13X 13X
IQ 210, CTs (240 V maximum)
13X
IQ 220, CTs IQ 230, CTs IQ 230M, CTs
13X 13X 13X
IQ 320, CTs IQ 330, CTs IQ 330M, CTs
16X 16X 16X
Factory installed 120, 240 or 480 Vac shunt trips are available with UL listing as shown in table below. Underwriters Laboratories listing is not available for shunt trip mounted on molded case switches.
Price U.S. $
Table 14-84. Modification 29 Device
Price U.S. $
BAB, QBHW Requires one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size and 3-pole is 4-pole size. GHB (3-pole only) All Other Circuit Breakers FDPW Switch (400 – 1200 amperes)
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Modifications
14-51
July 2007
Types PRL1a, 2a, 3a, 4, Column 34. Sub-Feed Lugs
33. Sub-Feed Breakers Table 14-88. Modification 33 — Panel Types PRL1a, PRL2a, PRL3a. One Breaker Per Panel Maximum Amperes
Number of Poles
Breaker Type
Interrupting Rating (kA Symmetrical) 240 Volts
480 Volts
Box Height Addition PRL3a
100 150 225 225 225
2 2 2 2 2
EHD FDB FD HFD FDC
18 18 65 100 200
14 14 35 65 100
NA NA NA NA NA
225 225 225 225 225 225 225
2 2 2 2 2 2 2
EDB EDS ED EDH JD HJD JDC
22 42 65 100 65 100 200
— — — — 35 65 100
NA NA NA NA 14X 14X 14X
250 250 250
2 2 2
JD HJD JDC
65 100 200
35 65 100
14X 14X 14X
400 400 400 400
2 2 2 2
DK KD HKD KDC
65 65 100 200
— 35 65 100
15X 15X 15X 15X
100 150 225 225 225
3 3 3 3 3
EHD FDB FD HFD FDC
18 18 65 100 200
14 14 35 65 100
NA NA NA NA NA
225 225 225 225 225 225 225
3 3 3 3 3 3 3
EDB EDS ED EDH JD HJD JDC
22 42 65 100 65 100 200
— — — — 35 65 100
NA NA NA NA 14X 14X 14X
250 250 250
3 3 3
JD HJD JDC
65 100 200
35 65 100
14X 14X 14X
400 400 400 400
3 3 3 3
DK KD HKD KDC
65 65 100 200
— 35 65 100
15X 15X 15X 15X
Price U.S. $
Note: Not available on service entrance panels with main lugs only (six disconnect rule).
Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modification 5 or Modification 8 as appropriate. Available on main lug panels only. Table 14-90. Modification 34 Main Box Amperes Height Addition
Price U.S. $ Addition 3Ph 4W, 3Ph 3W
Panel Types PRL1a, PRL2a 100 – 225 0X
Panel Type PRL3a 100 – 250 1X
Panel Type PRL4 1 250 – 400 0X 600 4X 1
Refer to PRL4 layout.
35. Surge (Lightning) Arrester Table 14-91. Modification 35 Description
Breaker Type
Interrupting Rating (kA Symmetrical) 240 Volts
480 Volts
Box Height Addition PRL3a
225 225 225
2 2 2
JD HJD JDC
65 100 200
35 65 100
20X 20X 20X
250 250 250
2 2 2
JD HJD JDC
65 100 200
35 65 100
20X 20X 20X
225 225 225
3 3 3
JD HJD JDC
65 100 200
35 65 100
20X 20X 20X
250 250 250
3 3 3
JD HJD JDC
65 100 200
35 65 100
20X 20X 20X
14
Note: Arrester is shipped uninstalled and included in same carton as interior along with necessary mounting bracket for field installation. Adder includes required extra 4-inch (101.6 mm) top or bottom gutter space (same end as incoming feed) for PRL1a, PRL2a and PRL3a panels. PRL4 panel does not require additional gutter space.
36. Tamperproof Screws — LT Trim Table 14-92. Modification 36 Description
Table 14-89. Modification 33 — Panel Type PRL3a Only. Two Breakers Per Panel — Twin Mounted Number of Poles
Price U.S. $ Per Panel
3-Phase 4-Wire or 1-Phase 3-Wire
Note: 225 amperes maximum on Column Type panels. Sub-feed breaker not available on PRL3a panel with subchassis.
Maximum Amperes
1Ph 3W, 1Ph 2W
Price U.S. $ Two Breakers
Price U.S. $ Per Panel
Tamperproof screws for trims, in lieu of standard screws.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Modifications
14-52
July 2007
Types PRL1a, 2a, 3a, 4, Column 37. Through-Feed Lugs Note: 225 amperes maximum on Column Type panels. Not available on service entrance panels with main lugs only (six disconnect rule).
Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modification 5 or Modification 8 as appropriate. Not available on panels with sub-feed breaker. Table 14-93. Modification 37 Main Amperes
Box Height Addition
Price U.S. $ Addition 3Ph 4W, 3Ph 3W
1Ph 3W, 1Ph 2W
Panel Types PRL1a, PRL2a 100 225 400
1 1 1
14
1 2
2X 5X 8X 8X 14X
Package includes TVSS/Filter unit and integral circuit breaker disconnect (30 amperes) connected to the panel bus.
Type PRL1a, PRL2a and PRL 3a Panelboards
Available for all enclosure types.
Package includes TVSS/Filter unit connected to the panelboard bus.
The TVSS unit and integral circuit breaker disconnect will require 10X of chassis space. (Only available in 36-inches (914.4 mm) or 44-inches (1117.6 mm) wide enclosure.)
Available for all enclosure types. Sizing: PRL1a, PRL2a: Add 8 inches (203.2 mm) to the standard box height. PRL3a: Add 6X for 100 – 200 kA TVSS units. Add 8X for 250 – 500 kA TVSS units. Table 14-96. Modification 40 Description Surge Current Rating (kA/Phase)
Price U.S. $ Additions 100 kA 120 kA 160 kA
200 kA
250 kA 300 kA
400 kA 500 kA
Monitor Package Options – Clipper Visor Series AdVisor — Status indicating lights, Form C Contacts, Audible Alarm — Enable/disable SuperVisor — AdVisor features plus: Transient Counter, Push-toTest Button, Power Quality Meter (no date stamp) NetVisor — SuperVisor features plus: Power Quality Meter (with date stamp), Modbus and Ethernet Communication Port
7X 7X 7X 7X 5X
Refer to panelboard sizing charts. Refer to PRL4 layout.
38. Time Clock Space Only Includes box, trim, door and mounting pan. Table 14-94. Modification 38 Enclosure Type
Clipper Power System — Visor Series
PRL1a, PRL2a PRL3a, PRL4
Panel Type PRL4 2 250 400 600 800 1200
Type PRL4 Panelboards
Clipper Power System
Panel Type PRL3a 100 250 400 600 800
40. Transient Voltage Surge Suppression (TVSS)
Price U.S. $ Addition
Type 1 PRL1a, PRL2a, PRL3a (24-inch (609.6 mm) space)
Table 14-97. CVL Unit (PRL1a, PRL2a, PRL3a Only) 3 PRL1a, PRL2a: Add 7 inches (177.8 mm) to standard box height. PRL3a: Add 4X. Surge Current Rating (kA/Phase)
Price U.S. $ Additions
50 80 100
PRL1a, PRL2a, PRL3a (36-inch (914.4mm) space)
3
Type 3R PRL1a, PRL2a, PRL3a (24-inch (609.6 mm) space)
Surge Current Rating (kA/Phase)
Price U.S. $ Additions
120 160 200
Requires 15 ampere branch breaker for cable connection — 3P (3-Phase) or 2P (1-Phase). (Add breaker separately, not included in price.)
41. Copper Wire Only Terminals for Molded Case Circuit Breakers (To replace standard Al/Cu terminals.)
39. Touchup Paint
Table 14-98. Modification 41
Table 14-95. Modification 39 Description 12 oz. Spray Can. ANSI-61 Light Gray Indoor
Price U.S. $
Breaker Frame
Maximum Breaker Ampere Rating
Terminal Material
Wire Range
F J K
225 250 225 350 400 600 600 800 700 1000 1200
Copper Stainless Steel Copper Copper Copper Copper Copper Copper Copper Copper Copper
#4 – 4/0 #4 – 350 (1) #3 – 350 (1) 250 – 500 (2) 3/0 – 250 (2) 250 – 500 (2) #2/0 – 500 (3) #3/0 – 300 (2) #2/0 – 500 (3) #3/0 – 500 (4) #3/0 – 400
Case Lot of 12 — 12 oz. Spray Cans ANSI-61 Light Gray Indoor Single Style L M N
Price U.S. $ Per Breaker
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line
14-53
July 2007
Type PRL5P
Product Description The PRL5P panelboard incorporates Eaton’s proven Cutler-Hammer plugon power panelboard experience with modern manufacturing technology to provide the most flexible plug-on design in the industry. Designed to eliminate the multitude of parts associated with other similar products, the PRL5P panelboard is the choice for applications where additions and changes must be fast and convenient.
Two Enclosure Widths Provide Greater Flexibility
Circuit Breaker and Lug Adapter Units
30-Inch (762.0 mm) Wide. The narrowest enclosure in the industry for an 800 ampere main, breaker or lug, and up to 600 ampere branch breakers — while providing ample wiring bending space. An industry exclusive is the ability to mount two 225 ampere, 480 Vac breakers on the same adapter unit. It requires half the space necessitated by other products.
Breaker adapter units utilize Molded Case Circuit Breakers that provide increased performance in considerably less space than standard breakers. They’re available from 15 through 1200 amperes at 600 Vac maximum. A wide range of integrally mounted breaker accessories are available. Main and through-feed lug adapter units are available and are mounted similar to the breakers. Lug units are available up to 1200 amperes. Breaker and lug attachment units can withstand fault currents up to 200 kA rms symmetrical.
Type PRL5P — 30-inch (762.0 mm) Wide
Panelboard Installation
Plug-on Mains and Branches provide the flexibility to move devices on factory assembled panels after the boards are received at the job site. The electrician may move branch devices and place them into a configuration that fits the particular wiring needs of that installation.
48-Inch (1219.2 mm) Wide. Provides for mains up to 1200 amperes. The 1200 ampere lug adapter unit accepts up to 750 kcmil conductors. Two 600 ampere breakers can be mounted across from one another. Another exclusive allows breakers of different sizes to be mounted across from one another, providing the ability to maximize space within the panel. There are no restrictions or predetermined spaces where branch devices must be placed.
Breakers are mounted to an adapter which includes the bus connection hardware. The breaker to bus bar connection is positive and secure. This proven connection has been utilized by Eaton in plug-on power panelboards since 1984.
14 400 Ampere K-Frame Breaker
Dual-Mounted 225 Ampere F-Frame Breakers
1200 Ampere Main Lug Unit
Type PRL5P — 48-inch (1219.2 mm) Wide
CA08101001E
600 Ampere L-Frame Breaker
For more information visit: www.eaton.com
An Oversized Area is Provided for Neutral Connections with Ample Lugs for Ease of Installation
Panelboards Pow-R-Line
14-54
July 2007
Type PRL5P
Product Description ■ ■ ■ ■ ■ ■ ■
600 Vac maximum (250 Vdc). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire. 1200 ampere maximum mains. 1200 ampere maximum branch devices. Plug-on branch devices. Factory assembled. Refer to Pages 14-5 and 14-53 for additional information.
Product Selection Panelboard Selection and Layout Select either single-row or double-row bus chassis. Single-row bus chassis — maximum 800 ampere main breaker or main lug only. Select main device and “X” space from Table 14-99. Select branch devices and corresponding “X” space from Tables 14-100 through 14-103.
Refer to layout data on Tables 14-104 and 14-105. Make a layout sketch of the main and branch devices utilizing either a single-row or double-row bus chassis indicating the “X” space for each device. The maximum total “X” space cannot exceed 40X for any panelboard. Should more than 40X be required, add the appropriate throughfeed lug adapter or breaker to feed an additional panelboard.
Formula Pricing: Base Price + Branch Devices + Modifications = Total Price U.S. $ Table 14-99. Base Prices — PRL5P Main Interrupting Rating (kA Symmetrical) Main Ampere 240 Vac 480 Vac 600 Vac 250 Vdc Device Rating Type
Main “X” Space
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire
3-Phase 3-Wire
Main Lug Only Single-Row Bus 400 600 800
— — —
— — —
— — —
— — —
Lug Lug Lug
8X 8X 8X
— —
— —
Lug Lug
7X 7X
Main Lug Only Double-Row Bus 800 1200
— —
— —
Main Breaker Single-Row Bus
Type PRL5P
14
Application Description ■ ■ ■ ■
■
Power distribution panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specified on the order. See Pages 14-5 through 14-18 for additional information.
400 400 400 400
65 65 100 200
— 35 65 100
— 25 35 65
10 10 22 22
DK KD HKD KDC
4X 4X 4X 4X
600 600 600
35 100 200
35 65 100
25 35 35
22 25 25
LD HLD LDC
6X 6X 6X
800 800
65 100
50 65
25 35
22 25
MDL HMDL
6X 6X
Main Breaker Double-Row Bus 800 800
65 100
50 65
25 35
22 25
MDL HMDL
6X 6X
1200 1200 1200
65 100 200
50 65 100
25 35 65
— — —
ND HND NDC
6X 6X 6X
Note: Includes aluminum bus chassis, box, trim, main and neutral (if required).
Standards and Certifications UL 67, UL 50. Federal Specification W-P-115c. ■ Refer to Page 14-5 for additional information. ■ ■
Options and Accessories ■
Refer to Page 14-58.
Layout and Sizing ■
Refer to Page 14-57.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line
14-55
July 2007
Type PRL5P Table 14-100. Branch Devices — Single-Pole Breakers in Single Adapter Units — PRL5P Ampere Rating
15 – 60 15 – 60 15 – 60
120 Vac
Interrupting Rating (kA Symmetrical) 240 Vac
277 Vac
125 Vdc
Breaker Type
“X” Space
14 35 65
— — —
14 35 65
10 10 10
EHD FD HFD
2X 2X 2X
2 Each — 1-Pole Price U.S. $
Price U.S. $ Space Only
“X” 3 Each — 1-Pole Space Price U.S. $ Price U.S. $ Space Only 3X 3X 3X
Note: Price includes, as indicated, two or three single-pole 15 through 60 ampere breakers assembled on one adapter.
Table 14-101. Branch Devices — Two- and Three-Pole Breakers in Single Adapter Units — PRL5P Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vdc
Breaker Type
“X” Space
100 – 225 100 – 225 100 – 225 100 – 225 100 – 225
22 42 65 100 200
— — — — —
— — — — —
— — — — —
EDB EDS ED EDH EDC
3X 3X 3X 3X 3X
15 – 60 70 – 100
18 18
14 14
— —
10 10
EHD EHD
3X 3X
15 – 60 70 – 100 110 – 225
65 65 65
35 35 35
18 18 18
10 10 10
FD FD FD
3X 3X 3X
15 – 60 70 – 100 110 – 225
100 100 100
65 65 65
25 25 25
22 22 22
HFD HFD HFD
3X 3X 3X
15 – 60 70 – 100 110 – 225
200 200 200
100 100 100
35 35 35
22 22 22
FDC FDC FDC
3X 3X 3X
70 – 225 250 70 – 225 250 70 – 225 250
65 65 100 100 200 200
35 35 65 65 100 100
18 18 25 25 35 35
10 10 22 22 22 22
JD JD HJD HJD JDC JDC
3X 3X 3X 3X 3X 3X
100 – 400 250 – 400 250 – 400 250 – 400
65 65 100 200
— 35 65 100
— 25 35 65
— 10 22 22
DK KD HKD KDC
4X 4X 4X 4X
300 – 600 300 – 600 300 – 600
65 100 200
35 65 100
25 35 50
22 25 25
LD HLD LDC
6X 6X 6X
400 – 800 400 – 800
65 100
50 65
25 35
22 25
MDL 1 HMDL 1
6X 6X
400 – 800 400 – 800 400 – 800
65 100 200
50 65 100
25 35 65
— — —
ND 1 HND 1 NDC 1
6X 6X 6X
600 – 1200 600 – 1200 600 – 1200
65 100 200
50 65 100
25 35 65
— — —
ND 1 HND 1 NDC 1
6X 6X 6X
1
Price U.S. $ 2-Pole
Price U.S. $ Space Only 3-Pole
2-Pole
3-Pole
14
For use only in double-row chassis panelboards only.
Table 14-102. Branch Devices — Sub-Feed Lug Units — PRL5P Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vdc
Breaker Type
“X” Space
400 600 800 1200
— — — —
— — — —
— — — —
— — — —
Lug Lug Lug Lug 2
8X 8X 8X 7X
2
Price U.S. $ 2-Pole
Price U.S. $ Space Only 3-Pole
2-Pole
3-Pole
For use only in double-row chassis panelboards only.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Line
14-56
July 2007
Type PRL5P Table 14-103. Branch Devices — Dual Breaker Adapters — PRL5P Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac
480 Vac
600 Vac
250 Vdc
Breaker Type
“X” Space
100 – 225 100 – 225 100 – 225
65 100 200
— — —
— — —
— — —
ED EDH EDC
3X 3X 3X
15 – 60 70 – 100
18 18
14 14
— —
10 10
EHD EHD
3X 3X
15 – 60 70 – 100 110 – 225
65 65 65
35 35 35
18 18 18
10 10 10
FD FD FD
3X 3X 3X
15 – 60 70 – 100 110 – 225
100 100 100
65 65 65
25 25 25
22 22 22
HFD HFD HFD
3X 3X 3X
15 – 60 70 – 100 110 – 225
200 200 200
100 100 100
35 35 35
22 22 22
FDC FDC FDC
3X 3X 3X
Price U.S. $ 2-Pole
Price U.S. $ Space Only 3-Pole
2-Pole
3-Pole
Note: Any two breakers listed above may be mounted on the same 2X or 3X dual breaker adapter. Dual breaker adapters may be in singleor double-row chassis. Dual breaker adapters can NOT be mounted across from another in a double-row chassis. Always price two breakers. Price each breaker separately.
Table 14-104. Layout Information — PRL5P Box Sizes and Maximum Component Unit Ampere Rating Total “X” Space 1
Box Width
Single-Row Bus
24X 32X 40X
30.00 30.00 30.00
Double-Row Bus
24X 32X 40X
48.00 48.00 48.00
Bus Chassis Type
14
1
Inches
Box Height mm
Maximum Ampere Rating of Plug-on Components
Inches
mm
Main Lugs
762.0 762.0 762.0
64.00 75.00 86.00
1625.6 1905.0 2184.4
800 800 800
Branch Lugs 600 600 600
Main Breaker 800 800 800
Branch Breaker 600 600 600
1219.2 1219.2 1219.2
64.00 75.00 86.00
1625.6 1905.0 2184.4
1200 1200 1200
1200 1200 1200
1200 1200 1200
1200 1200 1200
Deduct “X“ space for main breaker or lugs from the total available “X“ spaces listed above.
Table 14-105. Main Lug and Sub-Feed Lug Unit — PRL5P Ampere Rating
“X” Space
Mechanical Lug Size and Number Al/Cu Rated
Single Bus Connection 400 600 800
8X 8X 8X
(1) 1/0 – 500 kcmil or (2) 1/0 – 250 kcmil (2) #4 – 500 kcmil (2) #2 – 500 kcmil or (3) #2 – 400 kcmil
Double Bus Connection 400 – 1200
7X
(4) #4 – 750 kcmil
Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line
14-57
July 2007
Type PRL5P
Chassis Layout
Single-Bus Interior in 30-Inch (762.0 mm) Wide Enclosure
Double-Bus Interior Mounted in 48-Inch (1219.2 mm) Wide Enclosure 48.00 (1219.2)
30.00 (762.0)
10.00 (254.0)
Neutral — No "X" Space Required Top or Bottom 2X 3X
2-Pole 2-Pole EHD, FD, HFD, FDC, ED, EDH, EDC EHD, FD, HFD, FDC, ED, EDH, EDC 3-Pole 3-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, C ED, EDH, EDC 2-Pole 2-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC
Neutral — No "X" Space Required Top or Bottom 2-Pole EHD, FD, HFD, FDC, ED, EDH, EDC
2X
3X
2-Pole 2-Pole EHD, FD, HFD, FDC, ED, EHD, FD, HFD, FDC, ED, EDH, EDC EDH, EDC
2X
3-Pole 3-Pole EHD, FD, HFD, FDC, ED, EHD, FD, HFD, FDC, ED, EDH, EDC EDH, EDC
3X
3-Pole EHD, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC
3X
2- or 3-Pole JD, HJD, JDC
3X
Bus Cover c
1X-6X
2- or 3-Pole b DK, KD, HKD, KDC Main or Branch
4X
2X
Blank Wireway a
2X
2-Pole 2-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC ED, EDH, EDC
2X
3-Pole 3-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC ED, EDH, EDC
Blank Wireway a
3X
4X
Filler Plate
2- or 3-Pole DK, KD, HKD, KDC
3X
2- or 3-Pole JD, HJD, JDC
2X
a
2X 3X
2- or 3-Pole LD, HLD, LDC
10.00 (254.0)
4X
6X
Filler Plate
3X
6X 800 A MDL, HMDL b Main or Branch
6X
800 A ND, HND, NDC b Main or Branch
6X
1200 A ND, HND, NDC b Main or Branch
6X
6X
Main Lug or Sub-feed Lug Kit 1200 A Maximum
10.00 (254.0)
10.00 (254.0)
6X
Main Lug or Sub-feed Lug Kit b 800 A Max.
8X
6X
6X
7.00 (177.8) 7X
800 A MDL, HMDL b Main Only
10.00 (254.0)
7X
10.00 (254.0)
Figure 14-13. PRL5P Chassis Layout — “X” Unit Layout of Circuit Breaker and Lug Units — X = 1.38 Inches (34.9 mm) — Dimensions in Inches (mm) 1 2 3
Blank wireway fillers are required opposite any dual breaker unit. If used as a main device, must be mounted at the neutral end of panel. Fixed bus covers are required for unused spaces if NEC six circuit disconnect rule is to be met.
CA08101001E
For more information visit: www.eaton.com
10.00 (254.0)
14
14-58
Panelboards Pow-R-Line July 2007
Type PRL5P — Modifications 1. Ambient Compensating Breakers
6. Copper Main Bus
For ambient compensating breakers (where available) in lieu of standard breakers, add 10 percent to panelboard branch breaker and to main breaker list prices, if required. (Not UL listed.)
Table 14-109. Modification 6
2. Bus Density
6a. Silver-Plated Copper Main Bus
Main bus ampere rating is determined by UL listed temperature test. 1000 ampere per square inch copper is available and included in copper bus price addition.
For silver-plated copper panelboard main bus and/or connectors, add as follows:
3. Special Cabinet (Box) Construction
Panel Construction
Price U.S. $ Addition
Type 3R Enclosure
Table 14-110. Modification 6a Main Bus Ratings Amperes
Panel Construction Single-Bus — 800 A maximum Double-Bus — 1200 A maximum
Table 14-107. Modification 4
14
Add per Panel
5. Conduit Covers
Table 14-108. Modification 5 Cover Type Conduit Enclosing Shield (open back)
Price U.S. $ Addition
Optional copper only mechanical main lugs (includes main incoming neutral lugs).
Price U.S. $ Per Foot
Main Lug Amperes
Price U.S. $
11. Solid-State Trip Units Table 14-116. Modification 11 Price U.S. $ Addition
Digitrip RMS310 LS Digitrip RMS310 LSI Digitrip RMS310 LSG Digitrip RMS310 LSIG Digitrip RMS310 LS Digitrip RMS310 LSI Digitrip RMS310 LSG Digitrip RMS310 LSIG
12. Circuit Breaker Handle Lockoff Devices Table 14-117. Modification 12 Description
Price U.S. $
400 600 800 1200
Price U.S. $
Non-padlockable Padlockable
13. Nameplates, Engraved Table 14-118. Modification 13 Type
8. Directory Frame — Metal Table 14-113. Modification 8 Frame Type
Description
N-Frame Circuit Breaker
Table 14-112. Modification 7
Fabricated sheet metal to cover open conduits above and/or below standard Type 1 box.
Table 14-115. Modification 10
K-, L-, M-Frame Circuit Breaker
7. Copper Lugs Price U.S. $
Price U.S. $ Addition
10. Ground Bar
Description
Table 14-111. Modification 6b
Complete assembly of panelboard box, interior and trim prior to shipment when required.
Type
Add per Panel Price U.S. $ Addition Per Panel
Single-Bus Interior Double-Bus Interior
4. Complete Assembly
Table 14-114. Modification 9
Hinged Door Over Devices for Type 1 Enclosure
6b. Copper Neutral
Add per Panel
Description
Price U.S. $ Per Panel
Single-Bus Interior Double-Bus Interior
Table 14-106. Modification 3 Modification
9. Trim and Door Modifications — Special Fronts and Doors
Price U.S. $
Metal Frame, Plastic Cover
Price U.S. $
Mastic back and installed by purchaser, per nameplate Fixed to panel trim with two screws or rivets, per nameplate
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Line
14-59
July 2007
Type PRL5P — Modifications 18. Shunt Trip for Main or Branch Circuit Breaker
14. Copper Wire Only Terminals for Molded Case Circuit Breakers To replace standard Al/Cu terminals) Table 14-119. Modification 14 Breaker Frame
Maximum Breaker Ampere Rating
Terminal Material
Wire Range #4 – 4/0
F
225
Copper
J
250
Stainless Steel
#4 – 350
K
225 350 400
Copper Copper Copper
(1) #3 – 350 (1) 250 – 500 (2) 3/0 – 250
Price U.S. $ Per Breaker
For tripping circuit breaker from a remote point. Voltage and frequency must be specified. Wiring to terminal blocks is not included. Standard leads extend 18 inches (457.2 mm) out of breaker.
L
600
Copper
(2) 250 – 500
Circuit breakers with factory installed 120, 240 or 480 Vac shunt trips are available with UL listing as shown in table below.
M
600 800
Copper Copper
(2) #2/0 – 500 (3) #3/0 – 300
Table 14-123. Modification 18
N
700 1000 1200
Copper Copper Copper
(2) #2/0 – 500 (3) #3/0 – 500 (4) #3/0 – 400
Description
Price U.S. $
Add per Device
15. Painting and Special Coatings
16. Permanent Circuit Numbers
Standard boxes are code-gauge galvanized sheet steel. Standard trims are code-gauge sheet steel with a rust inhibiting phosphatized coating and finished with ANSI-61.
Table 14-121. Modification 16
Table 14-120. Modification 15 Description Painted Boxes (ANSI-61) Painted Trims or Boxes (other than ANSI-61)
Price U.S. $ Each Box
Description
19. Touchup Paint Price U.S. $ Per Panel
To provide permanently attached Micarta circuit numbers.
Table 14-124. Modification 19 Type
Price U.S. $
12 oz. Spray Can ANSI-61 Light Gray Indoor
17. Service Entrance To provide a Service Entrance Label as detailed under the “Service Entrance Equipment” in application considerations. Only panelboards meeting these requirements can be labeled as such. The requirement for a Service Entrance Label must be noted on order entry. Includes neutral disconnect link and Service Entrance Equipment Label. (Ground bar not included — see Modification 10.)
Case Lot of 12 — 12 oz. Spray Cans ANSI-61 Light Gray Indoor Single Style
14
Table 14-122. Modification 17 Description
Price U.S. $
Add per Panel
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14-60
Panelboards Pow-R-Command July 2007
Product Description
Product Description Eaton’s Cutler-Hammer Pow-RCommand is designed to meet the needs for microprocessor-based programmable lighting control. Used as a stand-alone panelboard or networked as a system, the Pow-R-Command PRC100™ offers the broadest range of energy control in the industry. The PRC100 panelboard system is ideal for large, medium and small building applications. The Pow-R-Command panelboard mounts the same as traditional panelboards. Power and branch wiring is also the same. It can be applied to distribution systems rated 1-phase 3-wire and 3-phase 4-wire 120, 120/240, 208Y/120 and 480Y/277 Vac.
Application Description PRC100 Panelboard
14
Pow-R-Command PRC100 Panelboard Standard Features ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Universal System Controller
■
The heart of the PRC100 panelboard is the Universal System Controller. Integral to the panelboard, this controller provides the PRC100 panelboard with distributed intelligence to control solenoid operated circuit breakers. The controller has the ability to communicate with other panelboard mounted controllers using a shielded twisted pair network cable.
■ ■
Time-of-Day scheduling — Each breaker may be individually time scheduled. Holiday scheduling. Astronomical scheduling. Memory loss protection. Real-time clock. Hardware diagnostics. Power failure recovery. Brownout recovery. Alarms and alarm log. Local programming port. Network communications port. Breaker bypass On/Off and restore buttons. Lights-off warning. Load priority management. Plug-and-play installation. Data logging. 12 dry contact switch inputs.
Pow-R-Command PRC100 Panelboard Network Should more than one panelboard be required for a facility, Pow-R-Command panelboards can be networked to form a system. This allows each panelboard to communicate with each other and to a central computer over a shielded twisted pair network cable.
Pow-R-Command PRC100 Panelboard Optional Features: The Pow-R-Command PRC100 panelboard may be ordered with an optional factory installed Expansion Chassis in addition to the factory installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC) which may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond Time-of-Day power switching.
PRC100EC Panelboard
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Command
14-61
July 2007
Product Description
PRC100SCC Control Cabinet with Application Specific Controllers
PRC100 Application Specific Controllers Eaton’s Cutler-Hammer Pow-RCommand Application Specific Controllers (ASCs) are designed to expand the PRC100 panelboard system beyond Time-of-Day power switching requirements. The controllers may be plugged into the PRC100EC panelboard and the PRC100SCC Control Cabinet.
Switch Override Controller (PRC100SOC) The Switch Override Controller provides the ability to connect and monitor up to 48 dry contact closures from Wall Switches, Occupancy Sensors, Photocells, Building Automation System relay contacts or any remotely mounted device with a dry contact relay. Input connections to the controller are self powered with 28 Vac and may be individually custom programmed to operate differently. It is possible to program any connected input to control any breaker or group of breakers in the panelboard or system. Inputs have adjustable priorities and are capable of being individually time schedule enabled for different days of the week.
Telephone Override Controller (PRC100TOC)
PRC100 Set-up Software (PRC100LOS)
The Telephone Override Controller provides a voice prompted method for On/Off override control of lighting. The telephone override controller is connected the same as an extension telephone, simply plug it into a local analog telephone extension wall jack. The telephone override controller allows voice prompted control of lighting circuits for up to 1000 individual users. It is possible to program any of the 1000 users to override any breaker, or group of breakers in the panelboard, or system on or off during scheduled or non-scheduled hours, using any touch-tone telephone.
WindowsT-based set-up software is required for programming the PRC100 Panelboard and Application Specific Controllers.
Remote Access Controller (PRC100RAC) Allows programming and monitoring of the Pow-R-Command System from a remote location using a personal computer with a modem. The RAC is ideal for multi-location systems, such as campus and chain stores. Only one RAC is required per system to accomplish this task. The system can be designed to allow various levels of access. All programming and monitoring functions are available from the central location.
PRC100 Network Interface Box (PRC100NIB)
PRC100 System Support Application Engineering support is available from the Pow-R-Command Applications Engineering Group located in the Sumter, SC Plant.
PRC100 Field Technical Support Programming, Startup, Training and Field Service are available from a professional team of factory trained engineers. Startup services are recommended to assure peak system performance.
On-Line Support Available to those customers who choose Remote Access Controllers. Factory technicians can help diagnose systems, set up or change programs and troubleshoot online.
Standards and Certifications ■ ■ ■ ■
UL 67 Panelboards. UL 50 Enclosures. UL 916 Energy Management Equipment. National Electrical Code. Federal Specification W-P-115C. FCC Emissions Standards: Part 15, Subject J for Class A Application. UBC Zone 4 Seismic Qualified Equipment is available.
The Network Interface Box allows the central computer to be located more than 25 feet (7.6 m) from the closest Pow-R-Command Panelboard. The Network Interface Box comes complete with serial interface cable and power cord.
■
PRC100 Control Cabinet
The PRC50 panelboard is a PRC100 panelboard with additional programming capability added that provides the ability to group up to 42 remotely operated circuit breakers into 8 individual zones. Each zone is designed to be switched by a dry contact from an external time clock, switch or Interposing relay.
The PRC100 Control Cabinet incorporates a power supply and the Universal System Controller from the PRC100 panelboard into a cabinet that may house up to three ASCs. The PRC100 Control Cabinet is ideal for retrofit applications when the existing panelboards may be reused or new construction applications where two or more panelboards requiring switched loads are located within the same electrical closet. The PRC100 Control Cabinet will control up to 48 remotely mounted circuit breakers using pre-terminated pigtail cables.
■ ■
Pow-R-Command PRC50
The PRC50 programming board included with the controller allows the breakers to be grouped locally without the need of special equipment or software. The groupings can be easily changed without the need of any field rewiring. The grouping configurations are made using simple pushbutton inputs. The panelboards are available with a full line of ratings and accessories.
CA08101001E
For more information visit: www.eaton.com
14
Panelboards Pow-R-Command
14-62
July 2007
Type PRC100
PRC100 Panelboard
Product Selection Formula Pricing: Base Price + Branch Devices + Modifications = Total Price U.S. $ Table 14-125. Base Prices — Pow-R-Command PRC100 Panelboard Ampere Rating
Interrupting Rating (kA Symmetrical) 240 V
Device Type
Price U.S. $ 3-Phase 4-Wire
480Y/277 V
1-Phase 3-Wire
Main Lug Only 1 100 250 400
— — —
— — —
MLO MLO MLO
Main Breaker 2
PRC100 Panelboard
Product Description
14
Eaton’s Cutler-Hammer Pow-RCommand is designed to meet the needs for microprocessor-based programmable lighting control. Used as a stand-alone panelboard or networked as a system the Pow-RCommand PRC100 offers the broadest range of energy control in the industry. The PRC100 panelboard system is ideal for large, medium and small building applications. The Pow-R-Command panelboard mounts the same as traditional panelboards. Power and branch wiring is also the same. It can be applied to distribution systems rated 1-phase 3-wire and 3-phase 4-wire 120, 120/240, 208Y/120 and 480Y/277 Vac.
100 100 100 100 100 100 100
18 18 65 100 200 200 200
14 14 35 65 100 150 200
EHD FDB FD HFD FDC FCL FB-P 3
225 225 225 225 225 225 225 225
22 42 65 100 200 65 100 200
— — — — — 35 65 100
EDB EDS ED EDH EDC FD HFD FDC
250 250 250
65 100 200
35 65 100
JD HJD JDC
400 400 400 400 400
65 65 100 200 200
— 35 65 100 100
DK KD HKD KDC LCL 4
Main Integral Fuse Disconnect — Series Rated Combinations 5 Ampere Rating
100
100
100
T Fuse Disconnect 6
GHB, GHBS, EHD, FDB, FD
200
65
65
T Fuse Disconnect 6
GHB, GHBS, EHD, FDB, FD
Branch Breakers
2 3 4
Options and Accessories ■
Refer to Pages 14-67, 14-73 and 14-74.
Layout and Sizing ■
Approved Branch Devices
480Y/277 V
1
Refer to Table 14-126, on Page 14-63.
Device Type
240 V
See Page 14-60 for additional information.
■
Interrupting Rating (kA Symmetrical)
5 6
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire
The short circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short circuit rating of the lowest rated main or branch device. Top feed only. Requires 6.50-inch (165.1 mm) deep box. The short circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included.
Note: Includes Smart Chassis (system controller integral to the panelboard chassis). Lighting optimization software and start-up support must be included with each system — see Page 14-67.
Refer to Page 14-64.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Command
14-63
July 2007
Branch Circuit Breakers
BABRP Remote Control Circuit Breaker
GHBS Remote Control Circuit Breaker
Table 14-126. Branch Circuit Breakers — 480Y/277 Volt Maximum Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Volt
Breaker Type
480 Volt
Price U.S. $ Breaker 1-Pole
Provisions Only 2-Pole
3-Pole
1-Pole
2-Pole
Space Only 3-Pole
1-Pole
2-Pole
3-Pole
Remote Controllable Branch Circuit Breakers 10 10 65 65
15 – 30 15 – 30 15 – 20 15 – 30
— — 14 14
BABRP 1 BABRSP 1 GHQRSP 28 GHBS 2
Conventional Branch Circuit Breakers — Not Controllable BAB 1 BAB-H BAB 1 BAB-H BAB 1 BAB-H QBGF 4 QBGFEP 5 QBAF 6 QBAG 7
15 – 60 15 – 60 70 70 80 – 100 80 – 100 15 – 50 3 15 – 50 3 15 – 20 15 – 20
10 10 10 10 10 10 10 10 10 10
15 – 20 15 – 20 25 – 60 70 – 100
65 65 65 65
14 14 14 14
GHQ 28 GHB 28 GHB 28 GHB 28
15 – 60 70 – 100
18 18
14 14
EHD EHD
15 – 60 70 – 100 110 – 150
18 18 18
14 14 14
FDB FDB FDB
15 – 60 70 – 100 110 – 225
65 65 65
35 35 35
FD 2 FD 2 FD
15 – 60 70 – 100 110 – 225
100 100 100
65 65 65
HFD 2 HFD 2 HFD
15 – 60 70 – 100 110 – 225
200 200 200
100 100 100
FDC FDC FDC
100 – 225 100 – 225 100 – 225 100 – 225 100 – 225
22 42 65 100 200
— — — — —
EDB EDS ED i EDH i EDC i
1 2 3 4 5 6 7 8 i
— — — — — — — — — —
14
1-pole breaker rated 120 Vac. 2-pole breaker rated 120/240 Vac. 1-pole breakers are rated 277 Vac maximum. 2- and 3-pole breakers are rated 480Y/277 Vac maximum. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. For use on 480Y/277 Vac maximum. Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Command
14-64
July 2007
Application Description 1-Pole 1
1-Pole 1
1X
EHD
2-Pole 1
2-Pole 1
2X
FDB FD
1-Pole 1
3-Pole 1
3X
HFD FDC
2-Pole 12
2X
EDB, EDS, ED, EDH EDC
3X
EDB, EDS, ED, EDH EDC
2-Pole 1
3-Pole 12
5X 12 Poles 10X 24 Poles
ckt 2 4 6 8 10 12 14 16 18
ckt 1 3 5 7 9 11 13 15 17 Pow-R-Command Smart Chassis and 18 Pole Spaces
14
BABRP BABRSP BAB GHBS GHQRSP GHB
34
13X Smart Chassis includes spaces for 18 Poles GHBS, GHQRSP, GHB, BABRP, BABRSP, BAB
PRC100 Panel Layout Instructions
Layout Example
1. Select:
1. Panel description:
a. Smart Chassis from Figure 14-14.
a. Pow-R-Command, 3-phase, 4-wire 480Y/277 Vac, inter-rupting rating of 14,000 AIC symmetrical, 250 ampere main lugs only at bottom, surface mounted and the following branch breakers: b. 36 – 20 ampere, 1-pole GHBS. c. 6 – 20 ampere, 1-pole GHBS spaces.
Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker.
b. Required mains (lugs, breaker or fuse pullout). c. Appropriate neutral. d. Branch breakers and additional chassis space, as needed. 2. Layout panel as shown in Figure 14-14, using appropriate “X” units. Total “X” units determine box height shown in Table 14-127. (When total “X” units exceeds the number shown, use next size box size.
2. Layout information from Figure 14-14: a. Smart Chassis . . . . . . . . . b. 24 circuit add-on chassis . . . . . . . . . c. 250 ampere Neutral. . . . . d. 250 ampere Main Lugs only . . . . . . . . . . . . . Total Panelboard Height . . . . . . . . . . . . . . . .
34
Smart Chassis is always located at the bottom of the panelboard chassis immediately below all GHBS/GHB or BABR/ BABRS/BAB breakers.
Neutral Section
5X 100 – 250 A 8X 400 A
Main Lug Section
2X 100 A 5X 250 A 8X 400 A
= 13X = 10X = 5X = 5X = 33X
3. From Table 14-127: 33X Height (use 40X box). Box Catalog Number . . . . . . . . .YS2072 Trim Catalog Number . . . . . . . LT2072S OR Box Catalog Number . . . . . . EZB2072R Trim Catalog Number . . . . . .EZT2072S Table 14-127. Box Tabulation “X” Units
Box Height Inches
mm
YS Box Catalog Number
LT Trim Catalog Number
EZ Box Catalog Number
EZ Trim Catalog Number
1219.2 1524.0 1828.8 2286.0
YS2048 YS2060 YS2072 YS2090
LT2048S or F LT2060S or F LT2072S or F LT2090S or F
EZB2048R EZB2060R EZB2072R EZB2090R
EZT2048S or F EZT2060S or F EZT2072S or F EZT2090S or F
100 – 400 Amperes
Main Device Horizontally Mounted
See branch mounted — EHD, FD, FDB, HFD, FDC, EDB, EDS, ED, EDH, EDC above
Main Device Vertically Mounted
7X — EHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC
Cabinets
Top and Bottom Gutters
7X — 100 A Class T fusible pullout
Fronts are code-gauge steel, ANSI-61 light gray painted finish.
5.50 inches (139.7 mm) minimum.
Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100 – 400 amperes.
4.00 inches (101.6 mm) minimum.
9X — 200 A Class T fusible pullout 9X — FB-P 5 14X — JD, HJD, JDC 15X — DK, KD, HKD, KDC
23X 31X 40X 53X
48.00 60.00 72.00 90.00
Side Gutters
Figure 14-14. Pow-R-Command PRC100 Layout 1
2
3 4
5
All F-Frame branch breakers must be mounted above (top) of all controllable breakers on the chassis. EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on branch spaces must be adjacent to smart chassis poles. GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers. Top-mounted main — only.
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Command
14-65
July 2007
Type PRC100 EC
Pow-R-Command PRC100EC Panelboard
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-128. Base Prices — Pow-R-Command PRC100EC Panelboard Ampere Rating
Interrupting Rating (kA Symmetrical) 240 V
Device Type
Price U.S. $ 3-Phase 4-Wire
480Y/277 V
1-Phase 3-Wire
Main Lug Only 1 100 250 400
— — —
— — —
MLO MLO MLO
Main Breaker 2
PRC100EC Panelboard
Product Description Eaton’s Cutler-Hammer Pow-RCommand PRC100 panelboard may be ordered with an optional factory installed Expansion Chassis in addition to the factory installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC) which may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond Time-of-Day power switching.
Branch Breakers ■
Refer to Table 14-126, Page 14-63.
Application Specific Controllers (ASC) ■
Select up to two ASCs per panel from Page 14-67.
Options and Accessories ■
100 100 100 100 100 100 100
18 18 65 100 200 200 200
14 14 35 65 100 150 200
EHD FDB FD HFD FDC FCL FB-P 3
225 225 225 225 225 225 225 225
22 42 65 100 200 65 100 200
— — — — — 35 65 100
EDB EDS ED EDH EDC FD HFD FDC
250 250 250
65 100 200
35 65 100
JD HJD JDC
400 400 400 400
65 65 100 200
— 35 65 100
DK 3 KD 3 HKD 3 KDC 3
14
Main Integral Fuse Disconnect — Series Rated Combinations 4 Ampere Rating
Interrupting Rating (kA Symmetrical)
Device Type
Approved Branch Devices
240 V
480Y/277 V
100
100
100
T Fuse Disconnect 5
GHB, GHBS, EHD, FDB, FD
200
65
65
T Fuse Disconnect 5
GHB, GHBS, EHD, FDB, FD
1 2 3 4 5
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire
The short circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short circuit rating of the lowest rated main or branch device. Top feed only. The short circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included.
Note: Includes Smart Chassis (system controller integral to the panelboard chassis) and the Expansion Chassis for ASCs — factory installed. Lighting optimization software and start-up support must be included with each system — see Page 14-67.
Refer to Pages 14-67, 14-73 and 14-74.
Layout and Sizing ■
Refer to Page 14-66.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Command
14-66
July 2007
Type PRC100 EC 1-Pole 1
1-Pole 1
1X
EHD
2-Pole 1
2-Pole 1
2X
FDB FD
1-Pole 1
3-Pole 1
3X
2-Pole 1 2-Pole 12 3-Pole 12
HFD FDC
2X
EDB, EDS, ED, EDH EDC
3X
EDB, EDS, ED, EDH, EDC
PRC100EC Panel Layout Instructions
ckt 2 4 6 8 10 12 14 16 18
20X Smart Chassis includes spaces for 18 Poles GHBS, GHQRSP, GHB, BABRP, BABRSP, BAB 34
1. Panel description:
1. Select: (from Figure 14-15)
a. Pow-R-Command, 3-phase, 4-wire 480Y/277 Vac, interrupting rating of 14,000 AIC symmetrical, 250 ampere main lugs only at bottom, surface mounted and the following branch breakers: b. 36 – 20 ampere, 1-Pole GHBS. c. 6 – 20 ampere, 1-Pole GHBS spaces.
a. Smart Chassis with Expansion Chassis. Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker.
BABRP BABRSP BAB 5X GHQRSP 12 Poles GHBS 10X GHB 24 Poles 34 ckt 1 3 5 7 9 11 13 15 17
Layout Example
b. Required mains (lugs, breaker or fuse pullout). c. Appropriate neutral. d. Branch breakers and additional chassis space, as needed. 2. Layout panel as shown in Figure 14-15, using appropriate “X” units. Total “X” units determine box height shown in Table 14-129. (When total “X” units exceeds the number shown, use next size box size.)
2. Layout Information from Table 14-129: a. b. c. d.
Smart Chassis with EC . . 24 circuit add-on chassis 250 ampere Neutral. . . . . 250 ampere Main Lugs only . . . . . . . .
= 20X = 10X = 5X = 5X
Total Panelboard Height . . . . . . . = 40X 3. From Table 14-129: (40X box)
Pow-R-Command Smart Chassis and 18 Pole Spaces
Expansion Chassis Accepts 1 Application Specific Controller
14
Smart Chassis is always located at the bottom of the panelboard chassis immediately below all GHBS/GHB or BABR/ BABRS/BAB breakers.
Table 14-129. Box Tabulation
Neutral Section
5X 100 – 250 A 8X 400 A
Main Lug Section
2X 100 A 5X 250 A 8X 400 A
Main Device Horizontally Mounted
See branch mounted — EHD, FD, FDB, HFD, FDC, EDB, EDS, ED, EDH, EDC above
Main Devices Vertically Mounted
Box Catalog Number . . . . . . . . .YS2072 Trim Catalog Number . . . . . . . LT2072S OR Box Catalog Number . . . . . . EZB2072R Trim Catalog Number . . . . . .EZT2072S
7X — EHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC 7X — 100 A Class T fusible pullout 9X — 200 A Class T fusible pullout
“X” Units
Box Height Inches
mm
YS Box Catalog Number
LT Trim Catalog Number
EZ Box Catalog Number
EZ Trim Catalog Number
1524.0 1828.8 2286.0
YS2060 YS2072 YS2090
LT2060S or F LT2072S or F LT2090S or F
EZB2060R EZB2072R EZB2090R
EZT2060S or F EZT2072S or F EZT2090S or F
100 – 400 Amperes 31X 40X 53X
60.00 72.00 90.00
Cabinets
Top and Bottom Gutters
Fronts are code-gauge steel, ANSI-61 light gray painted finish.
5.50 inches (139.7 mm) minimum.
Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100 – 400 amperes.
4.00 inches (101.6 mm) minimum.
Side Gutters
9X — FB-P 5 14X — JD, HJD, JDC 15X — DK, KD, HKD, KDC 4
Figure 14-15. Pow-R-Command PRC100EC Layout 1
2
3 4
5
All F-Frame branch breakers must be mounted above (top) of all controllable breakers on the chassis. EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on branch spaces must be adjacent to smart chassis poles. GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers. Top mounted main — only.
For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Command
14-67
July 2007
Type PRC100
Pow-R-Command PRC100 Panelboard Optional Features: Eaton’s Cutler-Hammer Pow-R-Command PRC100 panelboard may be ordered with an optional factory installed Expansion Chassis in addition to the factory installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC) which may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond Time-of-Day power switching.
Table 14-130. PRC100 Optional Features Description
Catalog Number
Price U.S. $
Control Cabinet — With Power Supply, System Controller and Space for Up to Three ASCs Control Cabinet — Surface Mount Control Cabinet — Flush Mount GHBS Pigtail Cable — 8 feet (2.4 m) GHBS Pigtail Cable — 16 feet (4.9 m) GHBS Pigtail Cable — 24 feet (7.3 m) GHBS Pigtail Cable — 32 feet (9.8 m)
PRC100CCS PRC100CCF PRL100ECP PRC100ECP-16 PRC100ECP-24 PRC100ECP-32
Relay Switching Equipment Smart Relay Panel — Surface Mount 1 Smart Relay Panel — Flush Mount 1 Latching Lighting Relay — 20 A, 277 Vac Maximum
PRC100SRPS PRC100SRPF PRC100RLY
Application Specific Controllers (ASC) Switch Override Controller Telephone Override Controller Universal System Controller PRC50 Programming Board
PRC100SOC PRC100TOC PRC100USC PRC50SPB
Computers and Peripherals Serial Communications Cable — 7 feet (2.1 m) Serial Communications Cable — 25 feet (7.6 m) Network Interface Box Laptop Computer Central Operator’s Station Data Logging Printer Data Fax Modem — 56K Central Operator’s Station with 17-inch CRT Touch Monitor Hand-Held Programmer with Cable and Software
PRC100SCC-7 PRC100SCC-25 PRC100NIB PRC100LTC PRC100COS PRC100DLP PRC100DFM PRC100COT PRC100HHP
Hand-Held Programmer Touch Screen Display JCI N2-Gate
PRC100HHP PRC100TSD PRL100N2G
Software Software 2
Lighting Optimization Web Server Software with Hardware Server Key Building Graphics Software with PC Hardware Key Custom Graphics Screens Programming 2
PRC100SLO PRC100SWS PRC100SBG PRC100SCG
Technical Support Startup, Training and/or Programming First Day of Trip (includes expenses) 3 Additional Consecutive Days of Same Trip 4 Additional User’s Guide 5 1 2 3 4 5
PRC100SUT1 PRC100SUT2 PRC100UG
Relay Panels have provisions for 48, 20 ampere Latching Lighting Relays. Relays sold separately. One software package required per system. One day required per system (up to 6 panels). Required to start up 6 panels per day after the first day. One user’s guide included with each system at no charge.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
Panelboards Pow-R-Command
14-68
July 2007
Type PRC50
Pow-R-Command PRC50 Panelboard
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-131. Base Prices — Pow-R-Command PRC50 Panelboard Ampere Rating
Interrupting Rating (kA Symmetrical) 240 V
Device Type
Price U.S. $ 3-Phase 4-Wire
480Y/277 V
1-Phase 3-Wire
Main Lug Only 1 100 225 400
— — —
— — —
MLO MLO MLO
100 100 100 100 100 100 100
18 18 65 100 200 200 200
14 14 35 65 100 150 200
EHD FDB FD HFD FDC FCL FB-P 3
225 225 225 225 225 225 225 225
22 42 65 100 200 65 100 200
— — — — — 35 65 100
EDB EDS ED EDH EDC FD HJD FDC
250 250 250
65 100 200
35 65 100
JDC HJD JDC
400 400 400 400 400
65 65 100 200 200
— 35 65 100 100
DK KDC HKD KDC LCL 4
Main Breaker 2
PRC50 Panelboard
Product Description Eaton’s Cutler-Hammer PRC50 panelboard is similar to a PRC100 panelboard with additional programming capability added that provides the ability to group up to 42 remotely operated circuit breakers into 8 individual zones. Each zone is designed to be switched by a dry contact from an external time clock, switch or interposing relay.
14
The PRC50 programming board included with the controller allows the breakers to be grouped locally without the need of special equipment or software. The groupings can be easily changed without the need of any field rewiring. The grouping configurations are made using simple pushbutton inputs.
Service 120/240 Vac single-phase 3-wire, 208Y/120 Vac 3-phase 4-Wire. ■ 240/120 Vac 3-phase 4-wire, 480Y/277 Vac 3-phase 4-wire.
Main Integral Fuse Disconnect — Series Rated Combinations 5 Ampere Rating
Interrupting Rating (kA Symmetrical)
■ ■ ■ ■ ■
Eight (8) Zones of Event Driven Control. Simple two key field programming. Matrix wiring allows breakers to be assigneD to multiple zones. Eight (8) integrated digital override inputs. Four (4) integrated analog override inputs.
Approved Branch Devices
240 V
480Y/277 V
100
100
100
T Fuse Disconnect 6
GHB, GHBS, EHD, FDB, FD
200
65
65
T Fuse Disconnect 6
GHB, GHBS, EHD, FDB, FD
■
Zone Configuration
Device Type
1 2 3 4 5 6
Price U.S.$ 3-Phase 4-Wire
1-Phase 3-Wire
The short circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short circuit rating of the lowest rated main or branch device. Top feed only. Requires 6.50-inch (165.1 mm) deep box. The short circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included.
Note: Includes Pow-R-Command Universal System Controller integral to the panelboard chassis (Smart Chassis) and the PRC50 Programming Board. Lighting optimization software and start-up support are not required.
Branch Breakers ■
Refer to Table 14-132, on Page 14-69.
Options and Accessories ■
Refer to Pages 14-73 and 14-74.
Layout and Sizing ■
Refer to Page 14-64. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Command
14-69
July 2007
Type PRC50 — Branch Circuit Breakers
BABRP Remote Control Circuit Breaker
GHBS Remote Control Circuit Breaker
Table 14-132. Branch Circuit Breakers — 480Y/277 Volt Maximum Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Volt
Breaker Type
480 Volt
Price U.S. $ Breaker 1-Pole
Provisions Only 2-Pole
3-Pole
1-Pole
2-Pole
Space Only 3-Pole
1-Pole
2-Pole
3-Pole
Remote Controllable Branch Circuit Breakers 15 – 30 15 – 30 15 – 20 15 – 30
10 10 65 65
— — 14 14
BABRP 1 BABRSP 1 GHQRSP 28 GHBS 2
Conventional Branch Circuit Breakers — Not Controllable BAB 1 BAB-H BAB 1 BAB-H BAB 1 BAB-H QBGF 4 QBGFEP 5 QBAF 6 QBAG 7
15 – 60 15 – 60 70 70 80 – 100 80 – 100 15 – 50 3 15 – 50 3 15 – 20 15 – 20
10 10 10 10 10 10 10 10 10 10
15 – 20 15 – 20 25 – 60 70 – 100
65 65 65 65
14 14 14 14
GHQ 28 GHB 28 GHB 28 GHB 28
15 – 60 70 – 100
18 18
14 14
EHD EHD
15 – 60 70 – 100 110 – 150
18 18 18
14 14 14
FDB FDB FDB
15 – 60 70 – 100 110 – 225
65 65 65
35 35 35
FD 2 FD 2 FD
15 – 60 70 – 100 110 – 225
100 100 100
65 65 65
HFD 2 HFD 2 HFD
15 – 60 70 – 100 110 – 225
200 200 200
100 100 100
FDC FDC FDC
100 – 225 100 – 225 100 – 225 100 – 225 100 – 225
22 42 65 100 200
— — — — —
EDB EDS ED i EDH i EDC i
1 2 3 4 5 6 7 8 i
— — — — — — — — — —
14
1-pole breaker rated 120 Vac. 2-pole breaker rated 120/240 Vac. 1-pole breakers are rated 277 Vac maximum. 2- and 3-pole breakers are rated 480Y/277 Vac maximum. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. For use on 480Y/277 Vac maximum. Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Command
14-70
July 2007
Type PRC25
Pow-R-Command — PRC25 Panelboard
Branch Breakers
Options and Accessories
Refer to Table 14-135.
■
Standards and Certifications
Layout and Sizing
UL 67, UL 50 ■ Federal Specification W-P-115c ■ Refer to Page 14-61 for additional information.
■
■
Refer to Page 14-73.
Refer to Page 14-72.
Product Selection Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $ Table 14-133. Base Prices — Pow-R-Command PRC25 Panelboard Includes 6 Zone Grouping Board Kit PRC256ZK42 (for 42 remote controlled breakers) (maximum of 7 breakers per zone). For fewer zones, or zones requiring more than 7 breakers, refer to Eaton. Ampere Rating
Interrupting Rating (kA Sym.)
Breaker Type
240 Vac
480Y/277 Vac
— — —
— — —
— — —
Price US. $ 208Y/120V 3Ph 4W
120/240 V 1Ph 3W
480Y/277 V 3Ph 4W
Main Lug Only 100 225 400
Main Breaker
Pow-R-Command PRC25 Panelboard
14
Product Description The PRC25 panelboard is designed to meet the needs for control of lighting and small branch circuits. Used as a stand-alone panelboard controlled by a time clock or wall switch, the PRC25 offers a solution for replacement of contactor and relay-based lighting control schemes. It can be applied to distribution systems rated: ■ ■
Single-phase 3-wire and 3-phase 4-wire 120/240, 208Y/120 and 480Y/277 Vac
The heart of the PRC25 panel is the Zoning Board integral to the panelboard. This controller provides the ability to group individual breakers into zones that may be switched on/off by a dry contact from a time clock, photocell, wall switch or building automation system.
100 100 100 100
18 22 42 65
14 — — —
EHD EDB EDS ED
100 100 100 100
65 100 100 100
35 — 65 100
FD EDH HFD FDC
225 225 225
22 42 65
— — —
EDB EDS ED
225 225 225 225
100 65 100 200
— 35 65 100
EDH FD HFD FDC
250 250 250
65 100 200
35 65 100
JD HJD JDC
400 400 400 400
65 65 100 200
— 35 65 100
DK KD HKD KDC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Pow-R-Command
14-71
July 2007
Type PRC25 Table 14-134. Branch Circuit Breakers — PRC25 Ampere Rating
Interrupting Rating (kA Symmetrical) 240 Vac 1
Breaker Type
15 – 60 70 80 – 100 15 – 50 3 15 – 50 3 15 – 20 15 – 20
10 10 10 10 10 10 10
BAB BAB BAB QBGF 4 QBGFEP 5 QBAF 6 QBAG 7
15 – 60 15 – 30 15 – 30 15 – 30
10 10 10 10
BAB-D 8 BAB-C 9 BABRP j BABRSP j
Provision
—
—
1 2 3 4 5 6 7 8 9 j
Price U.S. $ 1-Pole 120 V
2-Pole 120/240 V
2-Pole 240 V 2
3-Pole 240 V
2-Pole
3-Pole
Single-pole breakers are rated 120 Vac maximum. 240 volt breakers must be used on the high leg of a mid-point delta grounded system. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching neutral breaker. Single-pole device requires 2-pole space; 2-pole device requires 3-pole space. Solenoid operated breaker.
Table 14-135. Branch Breakers — PRC25 Ampere Rating
Interrupting Rating (kA Symmetrical) 480Y/277 Vac
Breaker Type
15 – 20 15 – 20 25 – 60 70 – 100 15 – 30 15 – 20
14 14 14 14 25 14
GHQ GHB GHB GHB HGHB GHQRSP k
15 – 60 15 – 20
14 14
GHBGFEP l GHBHID m
Provision
—
—
k l m
Price U.S. $ 1-Pole
14
Solenoid operated breaker. GFP for 30 mA equipment protection. HID (High Intensity Discharge) rated breaker.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Command
14-72
July 2007
Type PRC25 ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
31 in. - Includes Class II Chassis and spaces for 42 poles
Note: PRC25 Chassis may be located at the Top or Bottom of the panelboard immediately above or below the breakers.
PRC25 Panel Layout Instructions
Layout Example
1. Select PRC25 Panelboard Chassis from Figure 14-16.
1. Panel Description: a. PRC25, 3-phase 4-wire, 208Y/ 120 Vac, interrupting rating of 10,000 AIC symmetrical: 225 ampere main lugs only at bottom, surface mounted and the following branch breakers b. 36 – 20 ampere, 1-pole BABRP c. 6 – 20 ampere, 1-pole BABRP spaces 2. Layout information from Figure 14-16.
a. Determine required mains (lugs or breaker) b. Select appropriate Main Lug c. Select appropriate Main Device d. Select appropriate branch breakers 2. Layout panel as shown in Figure 14-16. Total inches determine box height shown in Table 14-136. (When total inch units exceed the number shown, use next size box size.
a. PRC25 with 42-circuit Interior 31 in. b. 225 ampere Main Lugs Section 4 in. c. Total Panelboard Height 35 in. 3. From Table 14-136:
PRC25 Class II Chassis
14
Deadfront Cover
2 in. for Deadfront Cover Supports
Main Lug Section
2 in. — 100 Amp MLO 4 in. — 225 Amp MLO 21 in. — 400 Amp MLO
Vertically Mounted
8 in. — 100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 9 in. — 225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 24 in. — JD, HJD, JDC 24 in. — DK, KD, HKD, KDC
Figure 14-16. Pow-R-Command PRC25 Layout Note: Controlled circuits must be grouped in maximum of 6 Zones. All circuits within a zone must be together on the same side of the panelboard.
Panel Height: 20 in. wide x 5.75 in. deep ■ Box Height: 35 in. 60 in. ■ Box Catalog Number: YS2060 or EZB2060R ■ Trim Catalog Number: LT2060S or EZT2060S Table 14-136. Box Selection — Dimensions in Inches (mm) ■
Maximum Panel Height
Box Height, Inches
Catalog Number YS Box
LT Trim
EZ Box
EZ Trim
20-Inch Wide x 5.75-Inch Deep Boxes 33.00 35.00 38.00
48.00 60.00 60.00
YS2048 YS2060 YS2060
LT2048S or F LT2060S or F LT2060S or F
EZB2048R EZB2060R EZB2060R
EZT2048S or F EZT2060S or F EZT2060S or F
40.00 44.00 55.00
60.00 60.00 72.00
YS2060 YS2060 YS2072
LT2060S or F LT2060S or F LT2072S or F
EZB2060R EZB2060R EZB2072R
EZT2060S or F EZT2060S or F EZT2072S or F
Cabinets
Top and Bottom Gutters
Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20 in. wide x 5.75 in. deep.
6.38 in.
For more information visit: www.eaton.com
Minimum Side Gutters 4 in. (minimum) on 20 in. wide box size.
CA08101001E
Panelboards Pow-R-Command
14-73
July 2007
Pow-R-Command — Modifications 1. Special Cabinet (Box) Construction
7. Tamperproof Screws — LT Trim
12. Increased Dimensions
Table 14-137. Modification 1
Table 14-143. Modification 7
Table 14-148. Modification 12
Modification
Price U.S. $ Addition
Type 1 Enclosure
Description
8. Trim and Door Modifications — Special Fronts and Doors
Type 2 Enclosure (Drip-proof with gasketed trim)
Table 14-144. Modification 8
Type 3R Enclosure
Description
(20-inch (508 mm) wide) (28-inch (711.2 mm) wide)
Price U.S. $ Addition
(20-inch (508 mm) wide) (28-inch (711.2 mm) wide)
Common LT trim for two section panels with boxes bolted together
2. Complete Assembly Complete assembly of panelboard box, interior and trim prior to shipment when required. Table 14-138. Modification 2 Price U.S. $
Price U.S. $
Increased Side Gutters 4-inch (101.6 mm) Left or Right 7-inch (177.8 mm) Left or Right 12-inch (304.8 mm) Left or Right
13. Painting and Special Coatings Standard boxes are code-gauge galvanized sheet steel. Standard trims are code-gauge sheet steel with a rust inhibiting phosphatized coating and finished with ANSI-61.
Door-in-door, one door over interior and one which exposes gutter (LT Trim)
Type 12 Enclosure
Description
Increased End Gutters 4-inch (101.6 mm) Top or Bottom 7-inch (177.8 mm) Top or Bottom 12-inch (304.8 mm) Top or Bottom
Tamperproof screws for trims, in lieu of standard screws
28-inch (711.2 mm) wide in place of standard 20-inch (508.0 mm) wide
Description
Price U.S. $ Per Panel
Standard flush lock with quarter turn fasteners at top and bottom of trim door (standard on doors 48-inch (1219.2 mm) high and over) (LT Trim)
Table 14-149. Modification 13 Description
Price U.S. $ Each Box
Painted Boxes (ANSI-61)
9. Special Hinges — LT Trim Piano hinges in lieu of standard hinges.
Painted Trims or Boxes (other than ANSI-61)
Add per panel
Table 14-145. Modification 9
3. Concealed Trim Clamps — LT Trim Table 14-139. Modification 3 Description
Description
14. Copper Main Bus Price U.S. $
Price U.S. $
10. Special Locks
Add per panel
Table 14-146. Modification 10
4. Nameplate, Engraved
Description
Table 14-140. Modification 4 Type
Fixed to panel trim with two screws or rivets, per nameplate
For silver-plated copper panelboard main bus and/or connectors, add as follows: Table 14-151. Modification 14a
National metal lock with standard keying
Main Bus Ratings Amperes
National metal lock with GE75 keyway
Table 14-141. Modification 5 Price U.S. $
EZ Trim Standard Lock, Keyed to Corbin TEU-1
6. Permanent Circuit Numbers
14b. Tin-Plated Copper Main Bus
Standard Lock, Keyed to Corbin Cat 60
Table 14-142. Modification 6 Price U.S. $ Per Panel
Price U.S. $ Addition Per Panel
100 – 250 400
Standard Lock, Keyed GE75
Metal Frame, Plastic Cover
To provide permanently attached Micarta circuit numbers
100 225 – 250 400
14a. Silver-Plated Copper Main Bus
Yale 511S with rosette Yale 4651S (LL803 Key) Master keying — above locks or standard lock — per panelboard Tee handle and 3-point catch
5. Directory Frame — Metal
Description
Price U.S. $
Price U.S. $ Addition Per Panel
LT Type Trim Price U.S. $
Mastic back and installed by purchaser, per nameplate
Frame Type
Table 14-150. Modification 14 Main Bus Ratings Amperes
Add for each panel door
For tin-plated copper panelboard main bus and/or connectors, add as follows:
Standard Lock, Keyed to Corbin WEM1
Table 14-152. Modification 14b
11. Conduit Covers
Main Bus Ratings Amperes
Fabricated sheet metal to cover open conduits above and/or below standard NEMA Type 1 box.
100 – 250 400
Price U.S. $ Addition Per Panel
Table 14-147. Modification 11 Cover Type
Price U.S. $ Per Foot
Conduit Enclosing Shield (open back) Conduit Enclosure (solid back)
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
Panelboards Pow-R-Command
14-74
July 2007
Pow-R-Command — Modifications 15. Ground Bar
20. Copper Lugs
Table 14-153. Modification 15
Optional copper mechanical main lugs only. (Includes main incoming neutral lug.)
Price U.S. $ Aluminum Terminal Bar for Aluminum or Copper Cable
Copper Terminal Bar for Copper Cable Only
Standard Insulated/ Standard Insulated/ Isolated 1 Isolated 1
1
Insulated/isolated ground bar includes a standard ground bar.
Table 14-158. Modification 20 Main Wire Range and No. Amperes of Lugs Per Phase 100 225 –250 400
Main bus ampere rating is determined by UL listed temperature test. For 750 ampere per square inch aluminum or 1000 ampere per square inch copper, make price addition as follows: Table 14-154. Modification 16 Amperes Per Square Inch
Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modification 19 or Modification 20 as appropriate. Available on main lug panels only.
For tripping circuit breaker from a remote point. Voltage and frequency must be specified. Wiring to terminal blocks is not included. Standard leads extend 18 inches (457.2 mm) out of breaker. Circuit breakers with factory installed 120, 240 or 480 Vac shunt trips are available with UL listing as shown in table below. Table 14-162. Modification 24 Device
Price U.S. $
Main Amperes
Box Height Addition
250 A Maximum 400 A Maximum
100 – 250
1X
Price U.S. $
GHB (3-pole only) All Other Circuit Breakers 2 2
Table 14-159. Modification 21
Aluminum — 750 Amperes
BAB breakers with shunt trips require one additional pole space, i.e., 3-pole breaker with shunt trip requires 4-pole space.
Price U.S. $ Addition 3-Phase 4-Wire
1-Phase 3-Wire
25. Circuit Breaker Handle Lockoff Devices Table 14-163. Modification 25 Breaker Type
Price U.S. $
Non-Padlockable
Copper — 1000 Amperes
22. Through-Feed Lugs
250 A Maximum 400 A Maximum
Note: Copper bus density adder is in addition to copper bus price per Modification 14 — Applies to 310 and 310+ Trip Units.
17. Neutral Rated 200%
Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modification 19 or Modification 20 as appropriate. Table 14-160. Modification 22 Main Amperes
Box Height Addition
100 250 400
2X 5X 8X
Table 14-155. Modification 17 Main Bus Rating Amperes
Neutral Rating Amperes
Box Height Addition
100 225 250 400
225 450 500 800
0 0 3X 3X
Price U.S. $
18. Increased Panel Main Bus Rating Table 14-156. Modification 18 Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire
EHD, FDB, FD, HFD, FDC, ED, EDH, EDC, GHB, BAB
3-Phase 4-Wire
(To replace standard Al/Cu terminals)
1-Phase 3-Wire
Table 14-164. Modification 26 Frame Max. Terminal Wire Breaker Material Range Ampere Rating
To provide a Service Entrance label as detailed under the “Service Entrance Equipment” in application considerations. Only panelboards meeting these requirements can be labeled as such. The requirement for a Service Entrance Label must be noted on order entry. Includes neutral disconnect link and Service Entrance Equipment Label. (Ground bar not included — see Modification 15.)
Device
Padlockable
26. Copper Wire Only Terminals for Molded Case Circuit Breakers
F
225
Copper
J
250
Stainless #4–350 Steel
K
225 350 400
Copper Copper Copper
Price U.S. $ Each
#4–4/0
(1)#3–350 (1)250–500 (2)3/0–250
27. Touchup Paint Table 14-165. Modification 27 Description
Price U.S. $
12 oz. Spray Can. ANSI-61 Light Gray Indoor
Table 14-161. Modification 23
100 to 250 250 to 400 400 to 600
GHB, EHD, FDB, FD, ED, EDH, EDC, BAB
Price U.S. $ Addition
23. Service Entrance
Note: Prices and dimensions based on mechanical lugs. For compression or copper lugs, refer to Eaton.
Ampere Rating Change
(1) #14 – 1/0 (1) #6 – 250 kcmil (2) #1/0 – 600 kcmil
21. Sub-Feed Lugs — PRC100 & PRC50 Only
16. Bus Density
14
Price U.S. $
24. Shunt Trip for Main or Branch Circuit Breaker
Price U.S. $
Add per Panel
Case Lot of 12 — 12 oz. Spray Cans. ANSI-61 Light Gray Indoor Single Style
19. Compression Main Lugs — Type VCEL For other terminal types, refer to Eaton. Table 14-157. Modification 19 Main Amperes
Wide Range and Number of Lugs Per Phase
100 225 – 250
(1) #8 – 1/0 (1) #2/0 – 500 kcmil
400
(2) #2/0 – 500 kcmil
Price U.S. $
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Renovation Panelboard
14-75
July 2007
Product Description
Renovation Panel
Product Selection Table 14-166. Catalog Numbering System
P1R B 1 A 1 42 BAB 100 Main Breaker
Panel Type
MLO = Blank BAB EHD QBHW ED EDH
P1R Bus Type
Main Device L = MLO B = Main Breaker
A = Aluminum C = Copper Bus Ampere Rating
System Type 1 = Single-Phase (3W or 2W) 3 = 3-Phase (3W or 4W)
1 = 100 A 2 = 225 A
Circuits 18 = 18 24 = 24 30 = 30 42 = 42
Main Breaker Amperes MLO = Blank 030 = 30 060 = 60 100 = 100 125 = 125 150 = 150 175 = 175 200 = 200 225 = 225
Renovation Panel
Product Description ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■
240 Vac maximum. Single-phase 3-wire or single-phase 2-wire. 3-phase 3-wire or 3-phase 4-wire. 225 amperes maximum. 100 ampere maximum branch breakers. Fits existing box depths from 4.50 to 6.00 inches (114.3 to 152.4 mm) deep. Integrally mounted neutral assembly. Ground bar and bonding conductor included. Neutral and ground convertible from left-right. Bolt-on branch breakers. Factory assembled.
Table 14-167. Base Chassis Prices — PRL1R — Aluminum Bus, Single-Phase or 3-Phase 3 Ampere Number Interrupt- Main Rating of ing Rating Breaker Circuits (kA Sym.) Type 240 Vac
18 30 42
— — —
MLO
P1RL1A118 P1RL1A130 P1RL1A142
P1RL3A118 P1RL3A130 P1RL3A142
225
18 30 42
— — —
MLO
P1RL1A218 P1RL1A230 P1RL1A242
P1RL3A218 P1RL3A230 P1RL3A242
UL 67. Federal Specification W-P-115c. ■ CSAT C22.2 No. 29. ■
Price U.S. $
Main Breaker 100
225
1 2
■
Price Catalog U.S. $ Number
100
■
Standards and Certifications
Catalog Number
3-Phase 3-Wire — 3-Phase 4-Wire
Main Lug Only
Application Description Lighting and appliance branch panelboards. ■ Fully rated or series rated. ■ Interrupting capacities to 100 kA symmetrical. ■ Suitable for use as Service Entrance Equipment where specified on the order.
Single-Phase 3-Wire — Single-Phase 2-Wire
3
18 30 42
10
BAB 1
P1RB1A118BAB 2 P1RB1A130BAB 2 P1RB1A142BAB 2
P1RB3A118BAB 2 P1RB3A130BAB 2 P1RB3A142BAB 2
18 30 42
18
EHD
P1RB1A118EHD 2 P1RB1A130EHD 2 P1RB1A142EHD 2
P1RB3A118EHD 2 P1RB3A130EHD 2 P1RB3A142EHD 2
18 30 42
22
QBHW 1 P1RB1A118QBHW 2 P1RB1A130QBHW 2 P1RB1A142QBHW 2
18 30 42
65
ED
P1RB1A118ED 2 P1RB1A130ED 2 P1RB1A142ED 2
P1RB3A118ED 2 P1RB3A130ED 2 P1RB3A142ED 2
18 30 42
100
EDH
P1RB1A118EDH 2 P1RB1A130EDH 2 P1RB1A142EDH 2
P1RB3A1-8EDH 2 P1RB3A130EDH 2 P1RB3A142EDH 2
18 30 42
65
ED
P1RB1A218ED 2 P1RB1A230ED 2 P1RB1A242ED 2
P1RB3A218ED 2 P1RB3A230ED 2 P1RB3A242ED 2
18 30 42
100
EDH
P1RB1A218EDH 2 P1RB1A230EDH 2 P1RB1A242EDH 2
P1RB3A218EDH 2 P1RB3A230EDH 2 P1RB3A242EDH 2
P1RB3A118QBHW 2 P1RB3A130QBHW 2 P1RB3A142QBHW 2
BAB and QBHW main devices consume available circuit space positions. (2 circuits for Single-Phase; 3 circuits for 3-Phase.) Add main breaker ampere rating suffix. May NOT exceed main bus rating. Standard trim included in price shown. Select standard trim from either Table 14-179 or Table 14-180 on Page 14-79. Custom trims are available for an additional charge. Refer to Table 14-181 on Page 14-80 for custom trim details.
Note: A neutral assembly is included with the base chassis. For Single-Phase 2-Wire systems or for 3-Phase, 3-Wire systems, do not connect.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
Panelboards Renovation Panelboard
14-76
July 2007
Options and Accessories
Options and Accessories Table 14-168. Branch Circuit Breakers — PRL1R Ampere Rating
Interrupting Rating (kA Sym.) 240 Vac 1
Breaker Type
15 – 60 70 80 – 100
10 10 10
BAB BAB BAB
15 – 30 15 – 30 15 – 50 3
10 10 10
BABRP 4 BABRSP 4 QBGF 5
— — —
— — —
15 – 50 3 15 – 20 15 – 20
10 10 10
QBGFEP 6 QBAF 7 QBAG 8
— — —
— — —
15 – 60 15 – 30
10 10
BAB-D 9 BAB-C j
— —
— —
15 – 60 70 80 – 100 15 – 30
22 22 22 22
QBHW QBHW QBHW QBHGF
15 – 30 15 – 20 15 – 20
22 22 22
QBHGFEP QBHAF 7 QBHAG 8
— — —
— — —
Provision
—
—
1 2 3 4 5
14
6 7 8 9 j
1-Pole 120 V
2-Pole 120/240 V
2-Pole 240 V 2
3-Pole 240 V
Included in base chassis pricing
Single-pole breakers are rated 120 Vac maximum. 240 volt breakers must be used on 3-phase, 3-wire 240 volt delta systems or on the high leg of a mid-point delta grounded system. 50 ampere devices available as 2-pole only. Remote controllable circuit breaker. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching neutral breaker. Single-pole device requires two pole spaces; 2-pole device requires three pole spaces.
Table 14-172. Neutral Kit (Separately Mounted) l
Table 14-169. Copper Main Bus Adder Main Bus Ampere Rating
Catalog Number
100 225
k k
k
Price U.S. $
Price U.S. $
To convert base chassis catalog number from aluminum main bus to copper main bus, change the 6th digit of the aluminum base chassis catalog number to “C.” (i.e., P1RL1A1-42 becomes P1RL1C1-42).
Table 14-170. Copper Terminal Ground Bar for Copper Cable Only Copper Ground Bar Catalog Number
Number of Termination Points
Aluminum
18 30 42
P1RNKA18 P1RNKA30 P1RNKA42
l
Catalog Number
Copper Price U.S. $
Catalog Number
Price U.S. $
P1RNKC18 P1RNKC30 P1RNKC42
Each base chassis includes a neutral bar that contains one connection point for every circuit space available. Use this kit when additional connection points are required or the neutral must be separately mounted to meet existing cable locations.
Price U.S. $
P1RGBC
Table 14-171. Insulated/Isolated Ground Bus (Separately Mounted) Aluminum Catalog Number P1RGKA
Copper Price U.S. $
Catalog Number
Price U.S. $
P1RNKC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Renovation Panelboard
14-77
July 2007
Options and Accessories Table 14-173. Field Survey of Existing Equipment Number of Panels
Catalog Number
10 to 24 25 to 50 50 Plus
— — —
1
Table 14-175. Mounting Plate Extensions (2 per Chassis) Price U.S. $ 1
Extension Height Inches
mm
Catalog Number
2.00 4.00 6.00
50.8 101.6 152.4
P1RMP2 P1RMP4 P1RMP6
Price Per Pair U.S. $
List price is per panel. Minimum of 10 panels required. Travel expenses may be extra. Contact local satellite for details.
Table 14-174. Match Existing Mounting Studs Match chassis mounting holes to existing stud locations. 2
Catalog Number
Per Panel
—
2
Price U.S. $
This option includes any mounting plate extensions (from Table 14-175) required to match existing mounting studs. Detailed stud location drawings must accompany the order or a Field Survey (Table 14-173) must be purchased.
Table 14-176. Depth Adder Support (2 per chassis) Support Depth
Existing Box Depth Range Minimum
Inches
mm
1.00 2.50 4.00 5.50 6.00
Catalog Number
Maximum
Inches
mm
Inches
mm
25.4 63.5 101.6
5.50 7.00 8.50
139.7 177.8 215.9
7.00 8.50 10.00
177.8 215.9 254.0
P1RDA10 P1RDA25 P1RDA40
139.7 152.4
10.00 10.50
254.0 266.7
11.50 12.00
292.1 304.8
P1RDA55 P1RDA60
Price U.S. $
Table 14-177. Box Collar Kit Collar Depth
Existing Box Depth Range Minimum
Catalog Number
Maximum
Inches
mm
Inches
mm
Inches
mm
1.00
25.4
3.50
88.9
5.00
127.0
Price U.S. $
P1RBC10
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
14
Panelboards Renovation Panelboard
14-78
July 2007
Application Guidelines
Application Guidelines Instructions
Using the electrical requirement data, select a base chassis and any required breakers, options and accessories. ■ Table 14-178 provides the minimum dimensions of the enclosure, in which each base chassis may be installed, These dimensions assume that the chassis is mounted in the center of the existing box, both vertically and horizontally. Where site conditions require the chassis to be offset from this centrally mounted position, it is the installer's responsibility to ensure wire bending space and electrical clearance requirements are met. ■
In order to meet minimum wire bending space requirements and to ensure ease of installation, minimum enclosure space dimensions have been defined for each chassis. In order to ensure a proper fit, every panelboard to be renovated must be carefully surveyed prior to installation. ■ Determine the electrical requirements of the panelboard to be renovated (i.e., main breaker or main lugs, amperes, interrupting rating, circuit space, branch breakers, accessories). ■
■
Table 14-178 provides a “Trim Door Size Code.” Using this code, select a standard trim from Tables 14-179 and 14-180 that will fit the outside dimensions of the existing box. Refer to Table 14-181 to define non-standard trim requirements.
Table 14-178. Minimum Enclosure Sizing Ampere Rating
Number of Circuits
Main Device Type
Trim Door Size Code
Minimum Enclosure Dimensions Height Inches
Width mm
Depth
Inches
mm
Inches
mm
Main Lug Only 100
18 30 42
MLO
A B C
21.00 27.00 34.00
533.4 685.8 863.6
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
225
18 30 42
MLO
A B C
21.00 27.00 34.00
533.4 685.8 863.6
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
BAB
A B C
21.00 27.00 34.00
533.4 685.8 863.6
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
EHD
B D E
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
QBHW
A B C
21.00 27.00 34.00
533.4 685.8 863.6
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
ED
B D E
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
EDH
B D E
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
ED
B D E
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
18 30 42
EDH
B D E
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
4.50 4.50 4.50
114.3 114.3 114.3
14 Main Breaker 100
225
For more information visit: www.eaton.com
CA08101001E
Panelboards Renovation Panelboard
14-79
July 2007
Trim Selection
Trim Selection Instructions
Using the electrical requirement data, select a base chassis and any required breakers, options and accessories. ■ Table 14-178 provides the minimum dimensions of the enclosure, in which each base chassis may be installed, These dimensions assume that the chassis is mounted in the center of the existing box, both vertically and horizontally. Where site conditions require the chassis to be offset from this centrally mounted position, it is the installer's responsibility to ensure wire bending space and electrical clearance requirements are met. ■
In order to meet minimum wire bending space requirements and to ensure ease of installation, minimum enclosure space dimensions have been defined for each chassis. In order to ensure a proper fit, every panelboard to be renovated must be carefully surveyed prior to installation. ■ Determine the electrical requirements of the panelboard to be renovated (i.e., main breaker or main lugs, amperes, interrupting rating, circuit space, branch breakers, accessories). ■
■
Table 14-178 provides a “Trim Door Size Code.” Using this code, select a standard trim from Tables 14-179 and 14-180 that will fit the outside dimensions of the existing box. Refer to Table 14-181 to define non-standard trim requirements.
Table 14-179. Standard Trim Selection — 20-Inch (508.0 mm) Wide Enclosure Trim Door Enclosure Size Code Height
Inches
Surface Type Catalog Number mm
Flush Type
Trim Dimensions Height Inches
Catalog Number
Width mm
Inches
mm
Trim Dimensions Height Inches
Width mm
Inches
mm
A A A
24.00 30.00 36.00
609.6 762.0 914.4
RTA2024 RTA2030 RTA2036
24.00 30.00 36.00
609.6 762.0 914.4
20.00 20.00 20.00
508.0 508.0 508.0
RTA2226 RTA2232 RTA2238
26.00 32.00 38.00
660.4 812.8 965.2
22.00 22.00 22.00
558.8 558.8 558.8
B B B
30.00 36.00 42.00
762.0 914.4 1066.8
RTB2030 RTB2036 RTB2042
30.00 36.00 42.00
762.0 914.4 1066.8
20.00 20.00 20.00
508.0 508.0 508.0
RTB2232 RTB2238 RTB2244
32.00 38.00 44.00
812.8 965.2 1117.6
22.00 22.00 22.00
558.8 558.8 558.8
C C C
36.00 42.00 48.00
914.4 1066.8 1219.2
RTC2036 RTC2042 RTC2048
36.00 42.00 48.00
914.4 1066.8 1219.2
20.00 20.00 20.00
508.0 508.0 508.0
RTC2238 RTC2244 RTC2250
38.00 44.00 50.00
965.2 1117.6 1270.0
22.00 22.00 22.00
558.8 558.8 558.8
D D D
30.00 36.00 42.00
762.0 914.4 1066.8
RTD2030 RTD2036 RTD2042
30.00 36.00 42.00
762.0 914.4 1066.8
20.00 20.00 20.00
508.0 508.0 508.0
RTD2232 RTD2238 RTD2244
32.00 38.00 44.00
812.8 965.2 1117.6
22.00 22.00 22.00
558.8 558.8 558.8
E E E
36.00 42.00 48.00
914.4 1066.8 1219.2
RTE2036 RTE2042 RTE2048
36.00 42.00 48.00
914.4 1066.8 1219.2
20.00 20.00 20.00
508.0 508.0 508.0
RTE2238 RTE2244 RTE2250
38.00 44.00 50.00
965.2 1117.6 1270.0
22.00 22.00 22.00
558.8 558.8 558.8
Table 14-180. Standard Trim Selection — 14-Inch (355.6 mm) Wide Enclosure Deadfront Enclosure Size Height
Inches
Surface Type Catalog Number mm
Flush Type
Trim Dimensions Height Inches
Catalog Number
Width mm
Inches
mm
Trim Dimensions Height Inches
Width mm
Inches
mm
A A A
24.00 30.00 36.00
609.6 762.0 914.4
RTA1424 RTA1430 RTA1436
24.00 30.00 36.00
609.6 762.0 914.4
14.00 14.00 14.00
355.6 355.6 355.6
RTA1626 RTA1632 RTA1638
26.00 32.00 38.00
660.4 812.8 965.2
16.00 16.00 16.00
406.4 406.4 406.4
B B B
30.00 36.00 42.00
762.0 914.4 1066.8
RTB1430 RTB1436 RTB1442
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
RTB1632 RTB1638 RTB1644
32.00 38.00 44.00
812.8 965.2 1117.6
16.00 16.00 16.00
406.4 406.4 406.4
C C C
36.00 42.00 48.00
914.4 1066.8 1219.2
RTC1436 RTC1442 RTC1448
36.00 42.00 48.00
914.4 1066.8 1219.2
14.00 14.00 14.00
355.6 355.6 355.6
RTC1638 RTC1644 RTC1650
38.00 44.00 50.00
965.2 1117.6 1270.0
16.00 16.00 16.00
406.4 406.4 406.4
D D D
30.00 36.00 42.00
762.0 914.4 1066.8
RTD1430 RTD1436 RTD1442
30.00 36.00 42.00
762.0 914.4 1066.8
14.00 14.00 14.00
355.6 355.6 355.6
RTD1632 RTD1638 RTD1644
32.00 38.00 44.00
812.8 965.2 1117.6
16.00 16.00 16.00
406.4 406.4 406.4
E E E
36.00 42.00 48.00
914.4 1066.8 1219.2
RTE1436 RTE1442 RTE1448
36.00 42.00 48.00
914.4 1066.8 1219.2
14.00 14.00 14.00
355.6 355.6 355.6
RTE1638 RTE1644 RTE1650
38.00 44.00 50.00
965.2 1117.6 1270.0
16.00 16.00 16.00
406.4 406.4 406.4
CA08101001E
For more information visit: www.eaton.com
14
14-80
Panelboards Renovation Panelboard July 2007
Trim Selection Table 14-181. Custom Trim Selection Catalog Number
Price U.S. $
Follow the instructions below
Product Selection Table 14-182. Catalog Numbering System
CRT B 20.00 – 9.00 – 11.00 – 48.00 – 24.00 – 24.00
Instructions In order to accommodate instances where the standard trims (Tables 14179 and 14-180) do not suit an installation, custom-sized trims may be ordered. Since the trim mounts to the retrofit chassis, and not the existing enclosure, custom trims can solve many problems encountered with differing enclosure sizes and configurations. Use the dimension and sizing parameters listed below to define a custom trim catalog number. Contact your local satellite plant to ensure manufacturability and determine lead time required.
Outer Dimensions
14
The outer dimensions are the overall OUTSIDE dimensions of the trim. In surface-mounted applications, this is usually the same as the outside dimensions of the enclosure to be renovated. For flush-mounted applications, an additional amount of trim material extends beyond the outer edge of the box, in order to cover any gap between the wall material and the box. Extending the outer dimensions can cover larger than normal wall gaps or imperfections that may be encountered.
Trim Width
Trim Height
Offset Top
Dimension in Inches (2 Decimals)
Dimension in Inches (2 Decimals)
Dimension in Inches (2 Decimals)
Door Code A, B, C, D, E, F, G, H
Offset Left
Offset Right
Offset Bottom
Dimension in Inches (2 Decimals)
Dimension in Inches (2 Decimals)
Dimension in Inches (2 Decimals)
Trim Type CRT
Note: This example is for a custom trim that has overall dimensions of 20 inches (508.0 mm) in width and 48 inches (1219.2 mm) in height. The trim door is offset 1.00 inch (25.4 mm) to the RIGHT, in order to accommodate a flush-mounted, double-tub arrangement in which the boxes are bolted together without any spacers.
Technical Data and Specifications W
W = Trim Width — Total outside width of the TRIM, including that required to overlap the box in a flush application.
OT
H = Trim Height — Total outside length of the TRIM, including that required to overlap the box in a flush application.
Offset
H
Offset allows a retrofit chassis to be relocated from the central mounting position required for standard trims. This can accommodate many challenging site conditions such as short cables, physical obstructions, closecoupled boxes…etc.
OB
OR = Offset Right — This is the distance from the centerline of the CHASSIS to the right-hand edge of the TRIM. OL = Offset Left — This is the distance from the centerline of the CHASSIS to the left-hand edge of the TRIM. OT = Offset Top — This is the distance from the centerline of the CHASSIS to the top edge of the TRIM.
OL
OR
Figure 14-17. Custom Trim Dimensions
OB = Offset Bottom — This is the distance from the centerline of the CHASSIS to the bottom edge of the TRIM.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Renovation Panelboard
14-81
July 2007
Technical Data and Specifications
Application Guide Surface-Mount Panelboards — Data Sheet Electrical Data
Table 14-183. Branch Breakers
Panel Designation or Location
Breaker Type
Amps
Poles
CCT
Poles
Amps
Breaker Type
_________________________________________________________ 1
2
_________________________________________________________
3
4
Service:________Vac ________Phase ________Wire
5
6
7
8
9
10
Bus Amps:________(A)
11
12
❏ Main Lugs Only ❏ Main Breaker ❏ Top Entry ❏ Bottom Entry
13
14
15
16
17
18
19
20
Amps:________(A)
21
22
23
24
Existing Enclosure Dimensions
25
26
Select only one dimension F or FF
27
28
H:________
29
30
31
32
W:________
33
34
D:________
35
36
37
38
39
40
41
42
Circuits:________
F:________ or FF:________ ❏ Enclosure has no Flange
End View
14
Side View FF
F
W F
D
Finished Wall
H W FF
Finished Wall
D
Figure 14-18. Surface Mount Panelboards — Dimensions
CA08101001E
For more information visit: www.eaton.com
H
14-82
Panelboards Renovation Panelboard July 2007
Technical Data and Specifications
Flush-Mount Panelboards — Data Sheet Electrical Data
Table 14-184. Branch Breakers
Panel Designation or Location
Breaker Type
Amps
Poles
CCT
Poles
Amps
Breaker Type
_________________________________________________________ 1
2
_________________________________________________________
3
4
Service:________Vac ________Phase ________Wire
5
6
7
8
9
10
Bus Amps:________(A)
11
12
❏ Main Lugs Only ❏ Main Breaker ❏ Top Entry ❏ Bottom Entry
13
14
15
16
17
18
19
20
Amps:________(A)
21
22
23
24
Existing Enclosure Dimensions
25
26
Select only one dimension F or FF
27
28
H:________
29
30
31
32
W:________ WW:________
33
34
D:________
35
36
37
38
39
40
41
42
Circuits:________
HH:________
DD:________
F:________ or FF:________ ❏ Enclosure has no Flange
14 End View
Side View
WW W
Finished Wall
FF
F
F DD
D
HH HH WW
H
H
W
Finished Wall FF
DD
D
Figure 14-19. Flush-Mount Panelboards — Dimensions
For more information visit: www.eaton.com
CA08101001E
Panelboards Renovation Panelboard
14-83
July 2007
Technical Data and Specifications
Chassis Mounting Front View
In some applications it is required to drill mounting holes that match the location of hardware points (studs or bolts) in the existing panel. All dimensions to these hardware points are measured from the CENTERLINE of the enclosure. Follow the guidelines below to ensure that these holes are located properly, ensuring a quick and easy installation.
W SL
1. Measure and mark the vertical centerline point. This measurement should be taken from the INSIDE surface of the enclosure’s END. 2. Measure and mark the horizontal centerline point. This measurement should be taken from the INSIDE surface of the enclosure’s SIDE. 3. Measure the distance from the centerline marks to the center of the hardware point to be matched and record below.
SR
Mounting Studs ST
Centerline
H
SB
4. Measure and record the diameter of the stud or bolt to be matched.
14
In some cases the mounting hardware may NOT be placed symmetrically about the center of the enclosure. Ensure that all desired hardware locations are measured to the CENTERLINE. H:________
Figure 14-20. Chassis Mounting Dimensions
W:________ ST:________ SB:________ SL:________ SR:________ D:________ (Bolt or Stud Diameter)
CA08101001E
For more information visit: www.eaton.com
Panelboards Metering Service Sections
14-84
July 2007
Product Description
Product Description ■ ■ ■
■ ■ ■
■ ■
Product Selection
600 Vac maximum. 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire. Service entrance panel combining a main disconnect with a power company metering compartment. Circuit breaker or fusible switch disconnect. 400 – 1200 ampere ratings. Provision for power company metering: ❑ Hinged sealable door over CT section ❑ Arranged for bar-type, 200 – 1200 ampere utility-furnished CTs ❑ Barriered CT compartment Factory assembled. Wall-mounted enclosure.
Table 14-186. Type WBM Circuit Breaker Sections Max. Interrupting Rating Ampere (kA Symmetrical) Rating 240 Vac 480 Vac 600 Vac
Breaker Type 12
Base Catalog Number 3
400 400 400 400 400
65 65 100 200 200
— 35 65 100 200
— 25 35 50 —
DK KD HKD KDC LCL
WBMDK WBMKD WBMHKD WBMKDC WBMLCL
600 600 600
65 100 200
35 65 100
25 35 50
LD HLD LDC
WBMLD WBMHLD WBMLDC
800 800 800 800
65 100 65 100
50 65 50 65
25 35 25 35
MDL HMDL ND HND
WBMMDL WBMHMDL WBMND800 WBMHND800
1200 1200 1200 1200
65 65 100 100
50 50 65 65
25 25 35 35
ND NDG 4 HND HNDG 4
WBMND1200 WBMNDG1200 WBMHND1200 WBMHNDG1200
1 2 3 4
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire
3-Phase 3-Wire
For other breaker types, refer to Eaton. In cold sequence metering only, a 9X or 21X feeder breaker section can be supplied downstream from the CT compartment. Refer to Eaton. Complete catalog number according to Catalog the Number Selection Guide — Table 14-188. Integral ground fault.
Table 14-187. Modifications for WBM Metering Service Sections Description
14
Price U.S. $
Copper Bus Circuit Breaker Shunt Trip Installed Circuit Breaker Undervoltage Release Installed Type 3R Outdoor Enclosure Provisions for PTs
Table 14-188. Panelboard Catalog Number Selection Guide Metering Service Section
Application Description ■
■ ■ ■ ■
For use in areas where the disconnect and current transformer combination is required by utilities. Suitable for use as Service Entrance Equipment. Top or bottom entrance. Hot or cold sequence metering. The current transformer compartment will accommodate the following 12-inch (304.8 mm) bar-type CTs:
1st Panel Type
2nd Device Type
3rd Service and Voltage
4th Ampere Rating
5th Bus Bar Type
WSM = Fusible Switch WBM = Circuit Breaker
Fusible Switch = FDPW Circuit Breaker = 5
2 = 1-Phase 3-Wire 3 = 3-Phase 3-Wire 4 = 3-Phase 4-Wire
4 = 400 Ampere 6 = 600 Ampere 8 = 800 Ampere 12 = 1200 Ampere
A = Aluminum C = Copper
Example WBM
DK
2
4
A
Circuit Breaker Type
Circuit Breaker Type from Table 14-186
1-Phase 3-Wire
400 Ampere
Aluminum Bus Bar
5
See Table 14-186 above.
Table 14-185. Bar-Type CTs ABB
General Electric
Sangamo
Astra
CTB CSF CMF CBH
JCT-10 JCM-0 JCW-0 JAK-0
R6B R6BA R6M
TAB, TA TCB, AA AB
Standards and Certifications ■ ■
UL 67, UL 50. NEC. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com
CA08101001E
Panelboards Metering Service Sections
14-85
July 2007
Product Description Table 14-189. WSM Fusible Switch Sections Ampere Rating
Interrupting Rating (kA Symmetrical)
Fusible Switch 1
Base Catalog Number 2
Table 14-192. FDPW Switch Ratings, 250 or 600 Vac
Price U.S. $ 3-Phase 4-Wire
1-Phase 3-Wire
3-Phase 3-Wire
240 Vac Fusible Devices 3 400 600 800 1200
Refer to Table 14-192 FDPW FDPW FDPW FDPW
WSMFDPW WSMFDPW WSMFDPW WSMFDPW
1 2 3
Refer to Table 14-192 FDPW FDPW FDPW FDPW
Fuse Class Used
Short Circuit Ratings (kA Sym.)
400, 600 400, 600 800, 1200
R J4 L
200 200 200
4
600 Vac Fusible Devices 3 400 600 800 1200
Ampere Rating
WSMFDPW WSMFDPW WSMFDPW WSMFDPW
Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below.
Note: Fuses are not included.
Fuses are not included. Complete catalog number according to Catalog Number Selection Guide — Table 14-188. Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below.
Table 14-190. Modifications for WSM Metering Service Sections Description
Price U.S. $
Copper Bus Shunt Trip Installed Type 3R Outdoor Enclosure Provisions for PTs FDPW Fusible Switch Ground Fault System Includes Zero Sequence Current Monitor, Static Sensor, Shunt Trip and Fused Control Power Transformer
14
H
W
D
Figure 14-21. Type 1 Enclosure — Metering Service Section Table 14-191. Dimensions — Type 1 Enclosure Panelboard Type
Ampere Rating
Enclosure Dimensions — Inches (mm) Height
Width
Depth
Box Catalog Number
WBM, Circuit Breaker WSM, Fusible
400 – 1200 400 – 1200
73.50 (1866.9) 90.50 (2286.0)
36.00 (914.4) 36.00 (914.4)
11.31 (287.0) 11.31 (287.0)
BX3673 BX3690
Note: Not to be used for construction purposes unless approved.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E
For more information visit: www.eaton.com
Panelboards Pow-R-Stock Plus Program
14-86
July 2007
Program Features
Pow-R-Stock Plus Offering two options to meet the demanding schedule requirements of today's customers.
Factory-Assembled Panelboard Option
Unassembled Panelboard Option
The Pow-R-Stock Plus factory-assembled panelboard option offers key advantages over programs that offer only unassembled panelboards.
Reduced Installation Time ■
Unassembled panelboards must be assembled at the job site before the true installation process can begin, adding time and labor cost to the process. Pow-R-Stock Plus assembled panelboards are ready to install the moment they arrive at the job site.
Reduced On-Site Material Handling ■
A typical 42 circuit unassembled panelboard has a minimum of 46 parts to receive and handle, taking up valuable time at the job site. A Pow-RStock Plus assembled panelboard is just one item to receive and handle (two if the box is shipped ahead).
Factory Warranty ■
14
Type PRL1a Panelboard
Factory-assembled panelboards available from your local satellite plant in 24 to 72 hours. ■ Unassembled panelboards in stock at authorized Pow-R-Stock Plus distributors. ■
The Product Offering Pow-R-Stock Plus panels, available either as factory-assembled or as unassembled from distributor stock, are based on the most frequently ordered panelboards, including: ■ ■ ■ ■ ■ ■ ■ ■ ■
Field assembly of unassembled panelboards adds to contractor warranty responsibility. Pow-R-Stock Plus assembled panelboards carry a full factory warranty.
Simplicity ■
Order your Pow-R-Stock Plus Panelboard by description and it will arrive at the job site complete. No need to worry about matching catalog number kits at the job site or chasing after miscellaneous parts and pieces.
Contact your local satellite plant (see next page for a listing) for more information on the Pow-R-Stock Plus factory-assembled panelboard option.
Pow-R-Line 1a and 2a Panelboards are Designed to Provide Application Flexibility with Off-the-Shelf Service
The Pow-R-Stock Plus unassembled panelboard interior is designed specifically for distributor stock and field assembly. Its modular design allows for easy configuration in the field. Top or bottom incoming, main lugs or main breaker...all with the same Pow-R-Stock Plus unassembled interior. Lug and breaker kits provide greater flexibility with fewer boxes, interiors and trims to stock.
Color-Coded Package Labels The box, interior and trim packaging are clearly identified with brightly colored labels (a different color for each box size). This facilitates stocking, filling orders, and matching components in the field. Contact your local Eaton distributor for more details on the Pow-R-Stock Plus unassembled panelboard option.
Eaton Distributors
120/240 volt, 208Y/120 volt, and 480Y/277 volt ratings. 100 through 400 ampere mains. Single- and 3-phase. Surface and flush mounted. Aluminum or copper bus. Type 1 or Type 3R enclosures. Service Entrance available. Options for 200% neutrals and isolated ground bars. Full menu of branch breakers available.
Contact your Eaton sales engineer or local satellite manager and arrange to review the program details and criteria for qualification as a Pow-R-Stock Plus distributor.
Pow-R-Stock Plus Program Includes the EZ Trim and EZ Box
For more information visit: www.eaton.com
CA08101001E
Panelboards Regional Manufacturing Facilities
14-87
July 2007
Manufacturing Locations
•
SEATTLE
CHICAGO
•
•
DENVER
•
SAN FRANCISCO
CLEVELAND
• •
ST. LOUIS
•
•
•
NE EW JERSEY
BALTIMORE L LT RALEIGH
SUMTER
LOS ANGELES A AT ATLANT TA TA
•
•
HARTFORD
•
PHOENIX DALLAS
•
•
★
HOUSTON
•
•
OR RLANDO
Figure 14-22. Manufacturing Plant Locations
Main Plant Sumter 11 Corporate Circle P.O. Box 2258 Sumter, SC 29150 (803) 481-3131
Satellite Plants Atlanta 7000 Highlands Parkway SE Suite 102 Smyrna, GA 30082 Fax (770) 433-1863 Phone (678) 309-4260 Baltimore 6671 Santa Barbara Court Suite F Elk Ridge, MD 21227 Fax (410) 796-7755 Phone (410) 796-7777 Chicago 959 AEC Drive Wood Dale, IL 60191 Fax (630) 860-3569 Phone (630) 860-3500 Cleveland 5565 Venture Drive Unit B Parma, OH 44130 Fax (216) 433-0545 Phone (216) 433-0616 Dallas 631 Westport Parkway Suite 100 Grapevine, TX 76051 Fax (817) 251-6249 Phone (817) 251-6797 CA08101001E
Denver 14101 East 33rd Place Suite F Aurora, CO 80011 Fax (303) 366-9993 Phone (303) 366-2080 Hartford 625 Day Hill Road Windsor, CT 06095 Fax (860) 688-4982 Phone (860) 688-5330 Houston 10810 West Little York Suite 100 Houston, TX 77041 Fax (713) 688-3764 Phone (713) 688-8430 Los Angeles Electrical Group — Satellite 11120 Philadelphia Street Mira Loma, CA 91752 Fax (951) 685-3775 Phone (951) 685-5788 New Jersey 96 Stemmers Lane Westampton, NJ 08060 Fax (609) 835-4777 Phone (609) 835-4230 Orlando 3827 St. Valentine Way Orlando, FL 32811 Fax (407) 841-9135 Phone (407) 843-3863
For more information visit: www.eaton.com
Phoenix 921 South Park Lane Tempe, AZ 85281 Fax (480) 449-4223 Phone (480) 449-4222 Raleigh 2933 S. Miami Boulevard Suite 111 Durham, NC 27703 Fax (919) 572-9751 Phone (919) 544-7074 St. Louis 12947 Gravois Road St. Louis, MO 63127 Fax (314) 842-2552 Phone (314) 842-7662 San Francisco 20923 Cabot Boulevard Hayward, CA 94545 Fax (510) 784-8980 Phone (510) 784-8981 Seattle 1604 15th Street SW Suite 114 Auburn, WA 98001 Fax (253) 833-5058 Phone (253) 833-5021
14
14-88
Panelboards Regional Manufacturing Facilities July 2007
Satellites
Satellites A unique concept of facilities close to customer locations, assuring fast delivery of standard and customassembled equipment when it’s needed. Located at strategic locations throughout the United States, these facilities manufacture and deliver standard or custom-assembled panelboards, switchboards and enclosed circuit breakers…when and where you need them. And, when you have an emergency, they can have your equipment ready in hours.
Highly trained and experienced personnel will manage your order and ensure that you receive on-time delivery of high quality equipment that meets your specifications.
Special Configurations The unique capabilities of these plants and people can provide solutions for special products to meet special needs. Typical examples include special dimensions, retrofit equipment and panelboard interiors to fit existing boxes.
Speedy Delivery Panelboards: from one to five days. Switchboards: between five and 10 days. ■ Assembled Enclosed Circuit Breakers: from one to 10 days. ■ ■
Save Time and Money No matter your location, you will save time and money when ordering from a satellite. For more information, contact your Eaton representative or authorized distributor. Cutler-Hammer is a federally registered trademark of Eaton Corporation. CSA is a registered trademark of the Canadian Standards Association. National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, Mass. Uniform Building Code (UBC) is a trademark of the International Conference of Building Officials (ICBO). UL is a federally registered trademark of Underwriters Laboratories Inc. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. Micarta is a registered trademark of Micarta Industrial Composites. Windows is a registered trademark of Microsoft Corporation.