Electric Pressure Calibrator
Selection Guide 2008/2009
Look
inside for:
Loop Calibrators Pressure Calibrators Temperature Calibrators Multifunction Process Calibrators Intrinsically Safe Calibrators Documenting Process Calibrators ProcessMeter™ Calibration Tools
Process Tools
for industrial instrumentation and electrical technicians
Industrial Test Tools Hart Scientific Temperature Calibrators Contact and Infrared Thermometers
Process Fluke Process Tools calibration tools Get more done Working in a process control environment can be dangerous, difficult work. Maintaining, building and calibrating these systems takes special expertise and Fluke is prepared with not only the tools, but the information you need to keep your world up and running. The tools featured in this selection guide represent the tools designed for you and the unique situations you may encounter in your work life.
2
Documenting Process Calibrators
ProcessMeter™ Test Tools
Infrared Thermometers
Multifunction Calibrators
Digital Multimeters
Milliamp Clamp Meter
Loop Calibrators
Pressure Calibrators
Intrinsically Safe Calibrators
Thermal Imagers
Dry Well Calibrators
Electric pressure calibrator New! Fluke 719 Electric Pressure Calibrator Why hassle with a hand pump? With the innovative, built-in electric pump, the Fluke 719 provides pressure calibration at your fingertips! Now you can calibrate and test pressure devices quickly and easily with one hand, saving you valuable time. Use the programmable pump limit settings to eliminate over-pressurization, and to set ‘pump to’ pressure values. The compact, lightweight form, combined with one-handed use, makes this pressure calibrator the ideal tool for busy process professionals.
Features include:
• Best in class pressure measurement uncertainty of 0.025 % • Measure and source mA with best in class 0.015 % accuracy • Precision pressure adjust vernier • Variable release rate bleed valve for easy pressure adjustment • Ideal performance for high accuracy transmitter calibration • Source mA with simultaneous pressure measurement to test valves and I/Ps
Function Measure or Source
• Programmable pump limit allows: – Protection from damage due to over-pressurization – The user to program target pressures for pumping • Extended measurement range with any of twenty nine (29) 700Pxx Pressure Modules • Test pressure switches with built in switch test function • Power transmitters during test • Proven cleanout ports reduce pump failures
Range
Resolution
Accuracy
Notes
Pressure 719-30G
-12 psi to 36 psi -850 mbar to 2.4 bar
0.001 psi 0.1 mbar
0.025% of range, 6 month spec.
0.035 % of range for one year
Pressure 719-100G
-12 psi to 120 psi -850 mbar to 8 bar
0.01 psi 1 mbar
0 mA to 24 mA
0.001 mA
0.015 % Rdg + 2 counts
Max load, 1000 Ω, 750 Ω in HART mode
24 V dc
N/A
± 10 %
mA Loop supply
Ordering information Fluke-719 30G Electric Pressure Calibrator, 30 psi, 2 bar Fluke-719 100G Electric Pressure Calibrator, 100 psi, 7 bar Each calibrator includes TL75 Test Leads, AC72 Test Clips, push fit connectors, translucent test hose, NIST traceable calibration certificate with data, product overview manual (print), and users manual on CD in 14 languages. Recommended accessory: Fluke 71X Hose Kit Accessory
3
Process measurements
789
789
ProcessMeter T
Cont % 0%
Pressure indicator/ controller
mV
mA
mA
See page 16
mA mA
COM
V
14* MENU
ENTER
4-20 mA
See page 17 771
Milliamp Process Clamp Meter
Pressure transmitter
718Ex
Intrinsically Safe Loop Calibrator
24 V
Regular process instrument maintenance and calibration can improve product quality, operational efficiency, safety, environmental compliance and corporate profitability. Fluke tools are designed to perform multiple functions to assist you in this effort. This diagram shows a few examples of Fluke tools in use, measuring and servicing process instrumentation.
mA A
V V OFF
A
24 V looop supply
Hz
Measured pressure
See page 15
744
Proces vessel
Documenting Process Calibrator
744
+
Isolation Valve 7 4 1
V RTD
Process fluid
V Hz
V
8
9
5
6
2
3
0
.
mA
ENTER
mA
V
RTD TC
See page 8
4
Differential Module H
L
Hand Pump
87V Infrared Thermometer
PORT MOD NET A NET B
See page 22
Process in
Ti25
Thermal Imager
Bearing temperature
See page 24
Bu
Digital Multimeter
568
See page 25
TM
trol out PLC or DCS
JO) 0
K1
K2
K3
K4
JO) 0 PGM
EXIT
ENTER
Relief valve
Control out
Control out
Relief valve controller Dry block calibrator
$
744
Documenting Process Calibrator
744
See page 8
Flow control valve
V Hz
V
7
V RTD
8
9
4
5
6
1
2
3
0
.
mA
ENTER
mA
V
RTD TC
Process out
ss l
568
See page 24 Flow control valve
Infrared and Non-Contact Thermometer
Flow computer calibration
CO-220
Carbon Monoxide Meter
5
urner/heater
Natural gas in 744
800.00
Power Panel: circuit loading
V Hz
V
V RTD
7
8
9
4
5
6
1
2
3
0
.
mA
Pressure module ENTER
mA
744
V
RTD TC
See page 8
Documenting Process Calibrator
Process Multifunction tools selection Process Calibrator guide
Process Milliamp Clamp Meter
Loop Calibrator
6
Model Measure V dc V ac (true-rms) Resistance A dc A ac Frequency Frequency totalizer Pressure Temperature: RTDs Temperature: TCs Source/Simulate V dc Resistance mA dc/% scale mA source; auto step, auto ramp Frequency Frequency totalizer Temperature: RTDs Temperature: TCs Record Min/Max Hold As Found/As Left results Upload data to PC/log data Remote operation Features 24 V loop supply Hart communication Integrated hand pressure pump Intrinsically safe (ATEX) NIST traceable certification Accessories Pressure enabled4 See page 1. Fluke 700 Pressure Modules required
707
715
28 V
25 V
24 mA
24 mA
Pressure Calibrators
771
717
718
719
99.9 mA
24 mA
24 mA
24 mA
1 to 5,000 psi2
1 to 300 psi2
30 to 100 psi2
20 V 24 mA
24 mA
•
•
24 mA
•
•
•
707Ex • C
• A/B
18
18
2. E ither the internal sensor or a Fluke 700 Pressure Module may be used
3
• •
• •
• •
•
•
•
•
Electric
• A/B • 20
718Ex • C • 20
• C • 3
3. Accessories: A. Compatible with LockPak B. Compatible with ToolPak C. Accepts hanging straps from ToolPak
Temperature Calibrators
712
Multifunction Process Calibrator
Intrinsically Safe Calibrators
Documenting Process Calibrators
ProcessMeter™ Test Tools
714
724
725
726
725Ex
744
789
-10 to 75 mV
30 V
30 V
30 V
30 V
3200 W 24 mA
3200 W 24 mA
4000 W 24 mA
3200 W 24 mA
300 V 300 V 11 kW 110 mA
10 kHz
10 kHz
50 kHz
29 Ranges1 7 types 12 types
15 kHz • 29 Ranges1 8 types 13 types
1000 V 1000 V 40 MW 30 mA, 1 A • 20 kHz
8 Ranges5 7 types 12 types
29 Ranges1 8 types 13 types
10 V 3200 W 24 mA
20 V 4000 W 24 mA
10 V 3200 W 24 mA
15 V 11 kW 22 mA
24 mA •
3200 W
7 types 9 types
7 types 12 types 10 V 3200 W
3200 W
7 types 9 types
7 types 12 types
•
•
•
•
10 kHz
15 kHz • 8 types 13 types
10 kHz
50 kHz
7 types 10 types
8 types 13 types
7 types 12 types
•
• •
• Manual
• A/B 19
• A/B 19
•
•
•
•
•
• A/B
• A/B • 13
• A/B • 12
13
4. F luke Process Calibrators in this guide displaying the Pressure Enabled symbol display readings from the 700 Series Pressure Modules
5. F luke 700PEx Pressure Module required
• • 12 V
• •
• •
•
• 15
• 8
•
A/B 16
7
Documenting process calibrators
Pressure Enabled
With one powerful tool, you can:
• Monitor, control and calibrate HART instrumentation with integrated communication functions • Generate precision electrical, temperature or pressure signals for analog stimulus or sensor simulation
• Simultaneously measure electrical, temperature or pressure signals from transmitter output • Interrogate HART devices to determine type, manufacturer, model and tag-ID • Read HART PV, smart transmitter digital output • Make field adjustments to ranging, damping and other top-level configuration settings • Change/assign the tag of HART transmitter smart transmitters • Re-configure HART temperature sensor (e.g., TC to RTD) • Perform HART sensor trim and output trim • Perform loop test with simultaneous analog and digital mA readout • Control selected Hart Scientific Dry Blocks Versatile HART protocol support (744 only) The 744 supports these classes of instructions: • Universal commands—such as “read manufacturer and device type,” “read primary variable (PV),” or “read current output and percent of span” • Common practice commands—such as “read multiple variables,” “set damping time,” or “loop test” • Device-specific commands—functions unique to a particular field device, like “sensor trim” or output trim
8
744 upgrades available Fluke periodically releases new internal software for the Fluke 744. These upgrades include:
• New revisions of previously supported instruments.
• Device-specific command
Recommended accessories: 741B, 743B and 744 calibrators
support for new instruments.
• New HART communication capability.
For details of the latest upgrade, see www.fluke.com/744upgrade
C789 Meter and Accessory Case
BP7235 NiMH Rechargeable Battery
Fluke-700Pxx Pressure Modules
80PK-25 SureGrip Piercing Temperature Probe
For more detailed information, go to www.fluke.com/744
TL220 SureGrip Industrial Test Lead Set
Summary specifications for Fluke 741, 743B and 744 calibrators (1 year) Function V dc Current dc V ac
Measure
Sourcing
0.025 % reading + 0.005 % full scale
0.01 % output + 0.005 % full scale
0.01 % reading + 0.015 % full scale
0.01 % output + 0.015 % full scale
(0.5 % + 5)
Resistance
0.05 % reading + 50 mΩ
0.01 % output + 40 mΩ
Frequency
0.05 %
0.01 %
Thermocouples
0.3 °C
0.2 °C
RTDs
0.3 °C
0.1 °C
Pressure
To 0.25 % of full scale, per pressure module specifications.
General specifications for Fluke 741, 743B and 744 calibrators Loop power
Selectable, 24 V or 28 V; 22 mA max
Environmental
741/743 specifications apply from +18 °C to +28 °C
Operating temperature
-10 °C to 50 °C (typical specs to -20 °C) Pressure modules are totally compensated and specs apply 0 °C to 50 °C
Storage temperature
-20 °C to 60 °C
Safety
Complies with CAN/CSA C22.2 No. 1010.1-92, ANSI/ISA S82.01-1994, UL3111 and EN610-1:1993. 300 V, Over-Voltage Category II
Size (HxWxD)
130 mm x 236 mm x 61 mm (5.1 in x 9.3 in x 2.4 in)
Weight
1.4 kg (3 lb, 1 oz)
Warranty
Three years
Battery
Internal battery pack NiCd, 7.2 V, 1700 mAh; NiMH (744 only) 7.2 V, 3500 mAh, typical usage, greater than 8 hours
Application note, literature code 1262439:
HART® transmitter calibration The need for calibration of HART smart transmitters is often misunderstood. What do you calibrate and when? Here is a step-by-step procedure showing how to use the Fluke 744 to perform calibration and digital adjustments of Rosemount 3051 and 3144 transmitters and other HART devices.
itter ® n Transm HART Calibratio
Ordering information Fluke-741B Documenting Process Calibrator Fluke-743B Documenting Process Calibrator
n Note catio Appli ction Introdu plants, ts process
y’s umen In toda field instr uments. most newt digital instr processorare smar ies a micro extra Smart impl ument withal cominstr digit based ity and mulfunctional , supporting multiple pensation or types or uments tiple sens These instr accuracy, variables. offer better religenerally stability, and analog nal long-term conventio than ability ts. class of instrumen common poThe mostuments incor with col, smart instrHART proto HART rates the five million 100,000 more than ts in use in , an instrumen dwide. HART essworl way Addris an plants for High er, acronym ote Transduc defines able Remstandard that col industry unications proto es the commsmart field devic that between ol system mA contr 4-20 a l and traditiona employs required es are wiring. biliti instruTwo capa service HART source erly analog to prop precision bility and ts: men ure capa tion capabiland meas required communica digital recently, this calibrator the ity. Until rate tools, a Today, two sepa unicator. two tools comm and a es of those e HART capabilitiable in a singlCalibraare avail ting Process quickly Documencan help you HART tor that tively service and effec ts. instrumen
Fluke-744 Documenting Process Calibrator Each calibrator includes TL224 Industrial Test Leads (2 sets), AC220 Test Clips (2 sets), TP220 Test Probes (1 set), BP7217 Battery Pack, BC7217 Battery Charger, instruction manual, NIST traceable 9 calibration certificate with data, serial port cable (743B and 744 only), DPC/TRACK Sample Version with free PC communication utility software (743B and 744 only). With the 744 you also get a HART communication cable, HART users manual and a NiMH battery (instead of NiCad).
700SW DPC/TRACK Software DPC/TRACK Software is a specialized database that can help you manage your instrumentation and address the documentation requirements of quality programs and regulations. With DPC/ TRACK and a 743 or 744 DPC you can: • Manage your inventory of tags and instruments • Schedule tag IDs for calibration • Create tag specific procedures, including instruction on how to locate an instrument and how to safely isolate and connect • Load those procedures to your DPC • Select and execute automated as found/as left procedures in the field, automatically capturing the results data • Include comments as to Reasons for Work, Problems Found, and Actions taken (743 and 744 only) • Unload your results to a PC • Print a selection of pre-formatted reports • Examine the calibration histories of your tags and instruments • Import instrument data and procedures as ASCII text • Export instrument data, procedures, and results as ASCII text. DPC/TRACK operates in the same languages as the DPCs: Fluke DPC/TRACK is an easy-to-use, single-user, entry-level instrumentation English, French, German, Italian, and Spanish manager. For more sophisticated software, you may wish to investigate products from one of Fluke’s software partners below.
For more detailed information, go to www.fluke.com/software
10 Ordering information
DocuMint
Fluke-700SW DPC/ TRACK Software Supports Fluke 743 and 744 Documenting Process Calibrators and include software CD, instruction manual, serial port cable and DB9 to DB25 adapter.
Meridium
AMS from Emerson Process Management, (formerly Fisher-Rosemount).
PRM (Plant Resource Manager) from Yokogawa Electric Corporation.
On Time Support
700 Series Pressure Calibration Modules Best accuracy available in handheld pressure modules • 0.025 % reference uncertainty • Rugged, chemical resistant packaging • Temperature compensated using proprietary micro-technology linearized output
• Digital communication to calibrators, no analog losses or errors • Broad selection of ranges
Models Differential Fluke 700P00 Fluke 700P01* Fluke 700P02 Fluke 700P22 Fluke 700P03 Fluke 700P23 Fluke 700P04 Fluke 700P24* Gage Fluke 700P05* Fluke 700P06* Fluke 700P27* Fluke 700P07 Fluke 700P08 Fluke 700P09* Absolute Fluke 700PA3 Fluke 700PA4* Fluke 700PA5 Fluke 700PA6 Vacuum Fluke 700PV3 Fluke 700PV4 Dual Fluke 700PD2 Fluke 700PD3 Fluke 700PD4 Fluke 700PD5 Fluke 700PD6 Fluke 700PD7 High Fluke 700P29* Fluke 700P30 Fluke 700P31
Range/ resolution
Range (approx) resolution
1 in. H2O/0.001 10 in. H2O/0.01 1 psi/0.0001 1 psi/0.0001 5 psi/0.0001 5 psi/0.0001 15 psi/0.001 15 psi/0.001
0.25 kPa/0.0002 2.5 kPa/0.002 6900 Pa/0.7 6900 Pa/0.7 34 kPa/0.001 34 kPa/0.001 103 kPa/0.01 103 kPa/0.01
30 psi/0.001 100 psi/0.01 300 psi/0.01 500 psi/0.01 1000 psi/0.1 1500 psi/0.1
Reference uncertainty (23 ± 3 °C)
Highside media
Low side media
Fitting material
0.300 % 0.200 % 0.150 % 0.100 % 0.050 % 0.025 % 0.025 % 0.025 %
Dry Dry Dry 316 SS Dry 316 SS Dry 316 SS
Dry Dry Dry Dry Dry Dry Dry Dry
316 316 316 316 316 316 316 316
SS SS SS SS SS SS SS SS
207 kPa/0.01 690 kPa/0.07 2070 kPa/0.1 3400 kPa/0.1 6900 kPa/0.7 10 M Pa/0.001
0.025 0.025 0.025 0.025 0.025 0.025
% % % % % %
316 316 316 316 316 316
SS SS SS SS SS SS
N/A N/A N/A N/A N/A N/A
316 316 316 316 316 316
SS SS SS SS SS SS
5 psi/0.0001 15 psi/0.001 30 psi/0.001 100 psi/0.01
34 kPa/0.001 103 kPa/0.01 207 kPa/0.01 690 kPa/0.07
0.050 0.050 0.050 0.050
% % % %
316 316 316 316
SS SS SS SS
N/A N/A N/A N/A
316 316 316 316
SS SS SS SS
-5 psi/0.0001 -15 psi/0.001
-34 kPa/0.001 -103 kPa/0.01
0.040 % 0.040 %
316 SS 316 SS
Dry Dry
316 SS 316 SS
± 1 psi/0.0001 ± 5 psi/0.0001 ± 15 psi/0.001 -15/30 psi/0.001 -15/100 psi/0.01 -15/200 psi/0.01
±6900 Pa/0.7 ±34 kPa/0.001 ±103 kPa/0.01 -100/207 kPa/0.01 -100/690 kPa/0.07 -100/1380 kPa/0.1
0.150 % 0.040 % 0.025 % 0.025 % 0.025 % 0.040 %
316 316 316 316 316 316
Dry Dry Dry N/A N/A N/A
316 316 316 316 316 316
3000 psi/0.1 5000 psi/0.1 10000 psi/1
20.7 M Pa/0.001 34 M Pa/0.001 69 M Pa/0.007
0.050 % 0.050 % 0.050 %
* Intrinsically safe version available for use with 718Ex and 725Ex.
SS SS SS SS SS SS
C276 C276 C276
N/A N/A N/A
SS SS SS SS SS SS
C276 C276 C276
Pressure
Enabled Fluke Process Calibrators in this guide displaying this symbol are Pressure Enabled units and display readings from these Precision 700 Series Pressure Modules. Each pressure module includes NiST traceable certificate, metric adapter and instruction sheet.
11
Multifunction Calibrators Fluke 726 Precision Multifunction Process Calibrator The Fluke 726 Precision Multifunction Process Calibrator is designed specifically for the Process industry with broad workload coverage, calibration power and unsurpassed accuracy in mind. The 726 measures and sources almost all process parameters and can calibrate almost anything. The 726 will also interpret results without the help of a calculator and store measurement data for later analysis. • Precise measurement and calibration source performance, accuracies of 0.01 % • Transmitter error % calculation, interpret calibration results without a calculator • Memory storage for up to eight calibration results, return stored calibration data from the field for later analysis • Frequency totalizer and frequency pulse train source mode for enhanced flowmeter testing • HART mode inserts 250 ohm resistor in mA measure with loop power and source for compatibility with HART instrumentation • Integrated pressure switch test allows you to capture the set, reset and deadband of a switch • Custom RTD curves, add calibration constants for certified RTD probes for enhanced temperature measurement • New voltage input protection design for improved reliability • Three-year warranty
12
Application note, literature code 2546483:
Remote programming and measuring uncommon RTDs with the Fluke 726 This application note explains how to use the 726 to measure non-standard or characterized RTD’s. It covers the basic theory of RTD conversion formulas and shows how to load custom constants into the Fluke 726 using a Windows PC with an RS-232 serial port.
Fluke 726 and 725 Multifunction Process and 724 Temperature Calibrators The Fluke 724, 725 and 726 Multifunction Calibrators are versatile, easy-to-use field calibrators. Use them to test and calibrate almost anything with: • Easy-to-read measure/source back lit screens let you view input and output simultaneously • Perform fast linearity tests with auto step and auto ramp features • Power transmitters with internal loop supply • Store frequently-used test setups for later use • 725EX version available, see page 15
In addition, the 725 and 726 can:
• Measure pressure and frequency to test sensors and transmitters • Source/simulate mA, frequency and pressure to calibrate transmitters • Measure pressure using any of the Fluke 700Pxx Pressure Modules • Source mA with simultaneous pressure measurement to conduct valve and I/P tests
724
725
Specifications for Fluke 724, 725 and 726 Simultaneous function capability 24.000 mA dc 24.000 mA dc with 24 V loop supply 100.00 mV dc 30.000 V dc measure 20.000 V dc measure 10.000 V dc source 3200 W T/C: J, K, T, E, R, S, B, L, U, N, XK, BP RTD Ni120; Pt100 (3926); Pt100 (JIS); Pt100, 200, 500, 1000 (385) Pressure (requires Fluke 700Pxx Modules) Frequency; squarewave, 1 CPM to10 kHz; fixed amplitude 5 V p-p Frequency; squarewave, 1 CPM to 15 kHz (726) M = Measure
Channel A
Channel B
M M
M or S(1) M or S
M
M(1)
M or S M or S M or S M or S M(1) used as S(1) M(1) or S(1) M(1) or S(1)
S = Source/Simulate (1) Not available on 724
Recommended accessories: 72x calibrators
Fluke-700Pxx Pressure Modules
TL220 SureGrip Industrial Test Lead Set
C125 Meter Case Test Lead Set
ToolPak Meter Hanging Kit
For more detailed information, go to www.fluke.com/multifunction
80PK-27 SureGrip Industrial Surface Temperature Probe
Ordering information Fluke-726 Precision Multifunction Process Calibrator Fluke-725 Multifunction Process Calibrator Fluke-724 Temperature Calibrator Each calibrator includes TL75 Test Leads, AC70A Test Clips, one pair of stackable test leads, product overview manuals, users manuals on CD; NIST-traceable certificate of calibration; CE and CSA markings.
13
Multifunction calibrators Measure and source Function
Range or type
Resolution
Accuracy
Notes
V
0 to 100 mV 0 to 10 V (source) 0 to 20 V (source) 0 to 30 V (measure)
0.01 0.01 0.01 0.01
0.01 %, 0.02 % Rdg + 2 counts
Max load, 1 mA
mA (724 measure only)
0 to 24
0.001 mA
0.01 %, 0.02 % Rdg + 2 counts
Max load, 1000 W
mV (TC terminals)
-10.00 mV to +75.00 mV
.01 mV
0.01 %, 0.02 % of range + 1 count
W
15 Ω to 3,200 W 5 Ω to 4,000 W
0.01 W to 0.1 W
0.10 W to 1.0 W 0.015 %
Hz - CPM (725 and 726)
2.0 CPM to 1,000 CPM 1 Hz to 1000 Hz 1.0 kHz to 10.0 kHz 10.0 kHz to 15.0 kHz
0.1 CPM 1 Hz 0.1 kHz 0.1 kHz
± ± ± ±
mV V V V
0.05 % 0.05 % 0.25 % 0.5 %
Source; 5 V p-p, 1 V to 20 V p-p squarewave, -0.1 V offset
Loop supply
24 V dc
N/A
10 %
T/C
J, K, T, E, L, N, U, XK
0.1 °C, 0.1 °F
to 0.7 °C , to 0.2 °C
T/C
B, R, S, BP
1 °C, 1 °F
to 1.7 °C , to 1.2 °C
RTDs
Cu (10), Ni120 (672) Pt 100, 200, 500, 1000 (385) Pt 100 (3916), Pt 100 (3926)
0.01 °C, 0.01 °F
to 0.15 °C
0.1 °C, 0.1 °F
to 0.2 °C
Unique 726 specifications are bolded
General specifications for Fluke 724, 725 and 726 calibrators
14
Maximum voltage
30 V
Storage temperature
-20 °C to 71 °C
Operating temperature
-10 °C to 55 °C
Relative humidity
90 % (10 °C to 30 °C); 75 % (30 °C to 40 °C); 45 % (40 °C to 50 °C); 35 % (50 °C to 55 °C)
Shock
30 g, 11ms, half-sine shock
Vibration
Random, 2 g, 5 Hz to 500 Hz
Safety
CSA C22.2 No.1010.1:1992
EMC
EN50082-1:1992 and EN55022:1994 Class B
Size
96 mm x 200 mm x 47 mm (3.8 in x 7.9 in x 1.9 in)
Weight (HxWxD)
650 g (23 oz)
Battery
Four AA alkaline batteries
Battery life
25 hours typical
Warranty
Three years
For more detailed information, go to www.fluke.com/multifunction
Thermocouple (T/C) accuracy specifications (Fluke 724/725/726) T/C
Measure or source
J
-200 °C to 0 °C 0 °C to 1200 °C
1.0 °C 0.7 °C
K
-200 °C to 0 °C 0 °C to 1370 °C
1.2 °C 0.8 °C
E
-200 °C to 0 °C 0 °C to 950 °C
0.9 °C 0.7 °C
R
-20 °C to 0 °C 0 °C to 500 °C 500 °C to 1750 °C
2.5 °C 1.8 °C 1.4 °C
Note: Accuracy specifications include 0.2 °C cold junction uncertainty.
RTD types, ranges and accuracies
Pt 100 - 385
-200 °C to 800 °C
Measure (4 wire)
Source
0.33 °C
0.33 °C
Intrinsically safe products Application note, literature code 2096400:
What is “intrinsically safe”? Intrinsic safety is a protection method employed in potentially explosive atmospheres. Devices that are certified as “intrinsically safe” are designed to be unable to release sufficient energy, by either thermal or electrical means, to cause ignition of flammable material (gas or dust/particulates).
Making sense of intrinsic safety and intrinsically safe tools Want to know what industries Intrinsically Safe products are designed for? Want to know why intrinsic safety is so important? Go to www.fluke.com/ex
Ordering information Fluke products
ATEX certified
North American Certification
87VEX: Intrinsically Safe True-rms Multimeter
II 2 G EEx ia IIC T4
707Ex: Intrinsically Safe mA Calibrator
718Ex: Intrinsically Safe Pressure Calibrator
725Ex: Intrinsically Safe Multifunction Calibrator
700PEx: Intrinsically Safe Pressure Modules
II 2 G EEx ia IIC T4
II 1 G EEx ia IIC T4
II 1 G EEx ia IIB 171 °C
II 1 G EEx ia IIC T4
N.I. Class I, Div 2, Groups A-D T4
I.S. Class I, Div 1, Groups A-D T4
I.S. Class I, Div 1, Groups B-D, 171 °C
I.S. Class I, Div 1, Groups A-D T4
Fluke-87-5-EX IS True-rms Multimeter Fluke-707Ex IS Loop Calibrator Fluke-718Ex IS Pressure Calibrator Fluke-725Ex IS Multifuction Process Calibrator Fluke-700PEx Pressure Modules (700P01Ex, 700P05Ex, 700P06Ex, 700P09Ex, 700P24Ex, 700P27Ex, 700P29Ex and 700PA4Ex) Fluke-574-NI Precision Infrared Thermometer w/Logging SW Nonincendive Fluke-68IS Infrared Thermometer Intrinsically Safe
15
ProcessMeter ™ test Test tools Tools Multimeter and Loop Calibrator—all in one Fluke 789 ProcessMeter™ Test Tool The Fluke 789 has a display that’s twice as large as the 787 and adds a 24 V loop power supply that the 787 does not include.
Key features:
• 24 V loop power supply • 20 mA drive into 1200 W • 0 % to 100 % mA Span Check buttons to toggle from 4 mA to 20 mA
• Infrared I/O serial port compatible with FlukeView® Software
789
787
• PLUS all the proven 787 features below Fluke 787 ProcessMeter™ Test Tool • Simultaneous mA and % of scale readout on mA output • 25 % manual step plus auto step and auto ramp on mA output • CAT III, 1000 V safety rated DMM • Measure volts, amps, resistance, and frequency
Designed and Conforms to
IEC 1010-1
600V CAT IV
Specifications for Fluke 789 and 787 (18 °C to 28 °C, 1 year)
16
Measurement function
Best accuracy range and resolution
(% of reading + count)
V dc
400.0 mV, 4.000 V, 40.00 V
0.1 % + 1
V ac (true-rms) to 500 Hz
400.0 mV, 4.000 V, 40.00 V, 400.0 V, 1000 V
0.7 % + 2
mA dc
30.000 mA
.05 % + 2
A dc
1.000 A (0.440 A continuous)
0.2 % + 2
A ac
1.000 A (0.440 A continuous)
1%+2
Resistance
400.0 W, 4.000 k, 40.00 k
0.2 % + 1
Frequency
199.99 Hz, 1999.9 Hz, 19.999 kHz
.005 % +1 (0.5 Hz to 20 kHz)
Diode test
789: 2.000 V (shows diode voltage drop)
2%+1
787: 2.400 V (shows diode voltage drop) Continuity
Beeps for resistance < approx. 100 W
Output function
Range and resolution
Drive capability
Accuracy (% of span)
DC current output (internal battery operation)
0.000 mA to 20.000 mA or 4.000 mA to 20.000 mA (selectable at power-up) Over-range to 24.000 mA
789: 24 V compliance or, 1200 Ω @ 20 mA
.05 %
787: 12 V compliance or, 500 Ω @ 24 mA DC current simulate (ext. 24 V loop supply) 24 V loop supply
0.000 mA, to 20.000 mA or 4.000 mA, to 20.000 mA, (selectable at power-up) Over-range to 24.000 mA
789: 15 V to 48 V
789: minimum 24 V
≥ 24 V @ 24 mA, 1200 Ω (789 only)
787: not available
787: 15 V to 30 V
.05 %
Milliamp process clamp meter Fluke 771 Milliamp Process Clamp Meter Measure 4 mA to 20 mA signals without breaking the loop Features include:
• Measure mA signals for PLC and control system analog I/O • Measure 4 mA to 20 mA output signals from transmitters without breaking the loop • Best in class 0.2 % accuracy • Resolution and sensitivity to 0.01 mA • Hold function captures and displays changing measurements • Dual backlit display with both mA measurement and percent of 4 mA to 20 mA span • Measurement spotlight illuminates hard to see wires in dark enclosures • Detachable clamp with extension cable for measurements in tight locations • Measure 10 mA to 50 mA signals in older control systems using the 99.9 mA range Range/resolution
Accuracy
Features
Note
-20.99 mA to +20.99 mA
0.2 % of reading + 5 counts
Zero, Hold, backlight measurement spotlight
Use for measuring and troubleshooting 4 mA to 20 mA signals
-21.0 mA to -99.9 mA +21.0 mA to +99.9 mA
1 % reading + 5 counts
Zero, Hold, backlight measurement spotlight
Use for measuring and troubleshooting 10 mA to 50 mA signals
Performance specifications (1 year) Operating temperature
-10 °C to 55 °C
Storage temperature
-25 °C to 70 °C
Operating humidity
<95 % @ <30 °C, <75 % @ 30 °C to 55 °C
Size (HxWxD)
59 mm x 38 mm x 212 mm (2.32 in x 1.5 in x 8.35 in)
Weight
260 g (9.1 oz)
Temperature coefficients
0.01 %/°C
Power, battery life
(2) AA 1.5 V Alkaline, IEC LR6, 20 hours typical
Warranty
Three years for electronics, one year for clamp cable assembly
Ordering information Fluke-789 ProcessMeter™ Test Tool Each process meter includes TL71 Premium Test Lead Set plus Alligator Clips, 4 AA alkaline batteries (installed), product overview and users manuals on CD.
Fluke-787 ProcessMeter™ Test Tool Fluke-771 Milliamp Process Clamp Meter
Recommended accessories
LVD2 Volt Light
C550 Carrying Case
Each process meter includes soft carrying case, users manual.
C101 Hard Case
17
Intrinsically Loop Safe Products calibrators All Fluke mA–loop calibrators feature: • Simultaneous mA and % readout for quick, easy, interpretation of readings
• Push button 25 % steps for fast, easy linearity checks • Selectable ramp, step modes to provide smooth outputs for valve slewing and loop functional tests
• 24 V internal loop supply 715 Volt/mA Calibrator • Source voltage to 200 mV or 20 V • Measure loop current with 0.010 % accuracy and 0.001 mA resolution
• Measure voltage output process signals Fluke 705
Fluke 707
Fluke 715
Summary specifications (18 °C to 28 °C, one year) 705, 707, 715 Function
Range
Resolution
705
707
715
Accuracy
Accuracy
Accuracy
mA measure
0 to 24 mA
.001 mA
.02 % Rdg + 2 counts
.015 % Rdg + 2 counts
.01 % Rdg + 2 counts
mA source1
0 to 24 mA
.001 mA
.02 % Rdg + 2 counts
.015 % Rdg + 2 counts
.01 % Rdg + 2 counts
mA simulate2
0 to 24 mA
.001 mA
.02 % Rdg + 2 counts
.015 % Rdg + 2 counts
.01 % Rdg + 2 counts
Voltage measure
0 to 28 V
.001 V
.025 % Rdg + 1 count
.015 % Rdg + 2 counts
.01 % Rdg + 2 counts
Voltage source (715 only)
0 to 20 V
.001 V (715)
N/A
N/A
.01 % + 2 counts
Temperature coefficient, -10 °C to 18 °C, 28 °C to 55 °C, ± .005 % of range per °C 1 Max load, 1200 Ohms; 950 Ohms at 20 mA in HART mode 2Max applied voltage for simulation, 30 V
18
Ordering information Fluke-707 Loop Calibrator Fluke-705 Loop Calibrator Fluke-715 Volt/mA Calibrator Each calibrator includes test leads, test clips, holster, instruction sheets, NIST-traceable certificate of calibration; CE and CSA markings and 9 V alkaline battery.
Recommended accessories: 707, 705 and 715 calibrators
TL28A Heavy Duty Test Lead Set
TL220 SureGrip Industrial Test Lead Set
C25 Large Soft Case
For more detailed information, go to www.fluke.com/loop
C550 Tool Bag
PV350 Pressure Vacuum Module
Temperature calibrators 712 RTD Calibrator
714 Thermocouple Calibrator
Complete RTD calibration tool
Complete thermocouple calibration tool
• Measure temperature from RTD output • Simulate RTD output • Rosemount pulsed RTD transmitter
• Measure temperature from TC output
compatible • Operates with seven types of RTDs • Auto step and auto ramp output function
• Simulate TC output • Nine types of thermocouples • Auto step and auto ramp output function • Calibrate linear TC transmitter with mV source function
Summary specifications (18 °C to 28 °C, one year) RTD (712)
TC (714)
Function Measure/simulate RTD(712) Measure/simulate resistance
Range -200 °C to 800 °C (Pt 100) 0 Ω to 3200 Ω
Measure/simulate thermocouple
-200 to 1800 °C, 0.1 °C or °F depending on type (1 °C or °F; BRS) (K, -200 °C to 1370 °C) -10 mV to 75 mV 0.01 mV
Measure/simulate mV
Resolution 0.1 °C, 0.1 °F
Accuracy 0.2 °C, 0.4 °F (Pt 100)
0.1 Ω
0.025 % + 0.1 Ω to 0.55 Ω
Notes Pt; 100 200 500 1000 (385); Pt 100 (3926); Pt 100 (3916) JIS; Ni 120 (672)
0.5 °C or 0.9 °F 9 TC types; J K T E R S B per NIST, (K, -200 °C to 1370 °C) 175 and ITS-90 L U per DIN 43710 and IPTS-68 0.02 % + 1 count
General specifications for Fluke 712 and 714 calibrators Maximum voltage Non-operating temperature Operating temperature Relative humidity Safety EMC Size (LxWxD) (with holster) Weight (with holster)
30 V -40 °C to 60 °C -10 °C to 55 °C 95 % (10 °C to 30 °C); 75 % (30 °C to 40 °C); 45 % (40 °C to 50 °C); 35 % (50 °C to 55 °C) CSA C22.2 No. 1010.1:1992 EN50082-1:1992 and EN55022:1994 Class B 201 x 98 x 52 mm (7.93 x 3.86 x 2.06 in) 600 g (21 oz)
Recommended accessories: 712 and 714 calibrators
TL75 (712) Hard Point Test Lead Set
C550 Tool Bag
ToolPak Meter Hanging Kit
C25 Large Soft Case
For more detailed information, go to www.fluke.com/tempcal
80PK-24 (714) SureGrip Air Temperature Probe
Ordering information Fluke-712 RTD Calibrator Fluke-714 Themocouple Calibrator Fluke-724 Temperature Calibrator Each calibrator includes protective yellow holster with test lead storage, test leads and alligator clips (excluding model 714), single 9 V alkaline battery and instruction sheet in 14 languages.
19
Pressure calibrators
Pressure Enabled
Fluke 718 Pressure Calibrators 1 psi and 300 psi models in addition to the 30 and 100 psi models previously available
â&#x20AC;˘ Compact size, lightweight â&#x20AC;˘ New built-in pressure switch test feature â&#x20AC;˘ Built-in pressure/vacuum hand pump, with vernier and bleed valve â&#x20AC;˘ Pressure and vacuum measurement to 0.05 % of full span, using an internal pressure sensor (dry air only)
â&#x20AC;˘ Pressure measurement to 10,000 psi/700 bar using any of 29 Fluke 700Pxx Pressure Modules
â&#x20AC;˘ Measure mA with 0.015 % accuracy and 0.001 mA resolution â&#x20AC;˘ 24 V loop power supply â&#x20AC;˘ Clean out ports minimize the possibility of fluid damage to the pump Intrinsically safe 718 version available (see page 15)
Fluke 717 Pressure Calibrators Now with 9 ranges: 1 psi, 30 psi, 100 psi, 300 psi, 500 psi, 1000 psi, 1500 psi, 3000 psi and 5000 psi
â&#x20AC;˘ Measure pressure and vacuum to 0.05 % of full scale with internal psig 718
sensor â&#x20AC;&#x201C; Compatible with non-corrosive gasses and liquids â&#x20AC;˘ Measure pressure to 10,000 psi/69 mPa using one of 29 Fluke 70Pxx Pressure Modules â&#x20AC;˘ Measure mA with 0.015 % accuracy and 0.001 mA resolution, while providing 24 V loop power â&#x20AC;˘ New built-in pressure switch test feature â&#x20AC;˘ Min/Max/Hold functions
717
Application note, literature code 2577485:
Pressure calibration with the Fluke 718 20
New design protects on-board pump from fluid damage. This application note explains how to drain pressure lines safely before calibration, and how to clean the pressure pump on the new Fluke 718. www.fluke.com/library
0RESSURE CALIBRATION WITH THE &LUKE .EW DESIGN PROTECTS ON BOARD PUMP FROM FLUID DAMAGE
!PPLICATION .OTE
0ROTECT YOUR TOOLS 0RESSURE CALIBRATION TYPICALLY INVOLVES A PNEUMATIC CALIBRATION PUMP AND A PRESSURE CALIBRA TION TOOL OR REFERENCE GAUGE 4HE PUMP APPLIES PRESSURE TO BOTH THE DEVICE UNDER TEST $54 AND 6 THE CALIBRATION TOOL SEE FIGURE 4HE TRICK IS THAT BEFORE YOU 6 CAN APPLY PRESSURE WITH A PNEU MATIC HAND PUMP YOU ABSOLUTELY MUST FIRST DRAIN ALL CONDENSATE AND OIL FROM THE LINES 7HY )F THERE S OIL OR WATER TRAPPED IN THE LINE WHEN THE PUMP IS CON 2ED NECTED THAT FLUID CAN BE PULLED BACK INTO THE PUMP WHEN THE PRESSURE IS RELEASED 4HAT CAN "LACK EITHER CAUSE COSTLY DAMAGE TO THE PUMP OR AT THE VERY LEAST FORCE YOU TO DISASSEMBLE AND CLEAN THE PUMP BEFORE RE USE &IGURE 4O DRAIN PROCESS m UIDS CLOSE 6 AND OPEN 6 BEFORE CONNECTING THE #ALIBRATOR &OR THIS REASON THE UPDATED &LUKE 0RESSURE #ALIBRA THE COMPLEXITY AND COST OF REPAIR ENTERING THE PUMP AND CAUSING TOR NOW CONTAINS AN INNOVATIVE OF A PUMP FOULED BY PROCESS DAMAGE 4HESE TWO CHECK VALVES NEW PUMP DESIGN THAT IS EASILY MEDIA IS NORMALLY HIGHER THAN A ALLOW THE BI DIRECTIONAL FLOW OF CLEANED IN THE FIELD AND INHIBITS STAND ALONE PUMP AIR INTO OR OUT OF THE DAMAGE FROM PROCESS FLUIDS %VEN AFTER DRAINING THE PRO
0NEUMATIC PRESSURE CALIBRATORS WITH INTEGRATED TEST PUMPS
Recommended accessories: 717 and 718 calibrators
5SING THE UPDATED #ALIBRATOR PUMP
CESS FLUID FROM THE CALIBRATION PORT OF THE DEVICE UNDER TEST MINUTE AMOUNTS OF PROCESS 4HE NEW &LUKE IS A UNIQUELY FLUIDS MAY OFTEN STILL BE LURKING PROTECTED PNEUMATIC PRESSURE BEHIND )N THE EVENT THESE FLUIDS CALIBRATOR AND PUMP 4HE NEW ENTER THE PUMP CAVITIES THE PUMP DESIGN USES PROTECTIVE NEW PUMP DESIGN ENABLES QUICK CHECK VALVES THAT ALLOW AIR TO CLEANING AND MAINTENANCE EVEN PASS THROUGH THE PUMP FOR CALI IN THE FIELD BRATION BUT INHIBITS FLUIDS FROM
)NSTEAD OF THE PUMP PLUS CALIBRATOR METHOD DESCRIBED ABOVE MANY TECHNICIANS NOW USE A HANDHELD PNEUMATIC PRES SURE CALIBRATOR THAT INCLUDES AN ONBOARD PNEUMATIC PUMP MAR RYING TWO DEVICES INTO ONE HANDY INTEGRATED TOOL 7HILE THE INTE GRATED PUMP IS MORE CONVENIENT !IR FLOW TO INPUT )NLET AND EASIER TO USE IT IS DOUBLY CONNECTOR IMPORTANT TO MAKE SURE PROCESS AND VERNIER /UTLET FLUIDS ARE PROPERLY DRAINED BEFORE ADJUSTMENT MAKING A CONNECTION "ECAUSE THE PUMP ITSELF NORMALLY NEEDS TO BE REMOVED FROM THE CALIBRA TOR BEFORE CLEANING REBUILDING OR &IGURE 4HE &LUKE IS DESIGNED TO PROTECT THE HAND PUMP AND SIMPLIFY MAINTENANCE REPLACEMENT CAN BE PERFORMED
4O PUMP
Ă&#x20AC;Â&#x153;Â&#x201C;Ă&#x160;Ă&#x152;Â&#x2026;iĂ&#x160; Â?Ă&#x2022;Â&#x17D;iĂ&#x160; Â&#x2C6;}Â&#x2C6;Ă&#x152;>Â?Ă&#x160; Â&#x2C6;LĂ&#x20AC;>Ă&#x20AC;Ă&#x17E;Ă&#x160;JĂ&#x160;Ă&#x153;Ă&#x153;Ă&#x153;°vÂ?Ă&#x2022;Â&#x17D;i°VÂ&#x153;Â&#x201C;Ă&#x2030;Â?Â&#x2C6;LĂ&#x20AC;>Ă&#x20AC;Ă&#x17E;
700ILF In-Line Filter
700LTP-1 Low Pressure Test Pump
700PTP-1 Pneumatic Test Pump
C25 (717 only) Large Soft Case
700HTP-1 Hydraulic Test Pump
For more detailed information, go to www.fluke.com/pressure
Pressure calibrators Specifications for 717 and 718 Calibrators 717-1 718-1G 717-30G 718-30G* 717-100G 718-100G* 717-300G 718-300G* 717-500G 717-1000G 717-1500G 717-3000G 717-5000G Pressure accuracy mA measurement Loop power
Range ± 1 psi, 27.5 in H20, (-7 to +7 kPa)
Resolution Comment +0.0001 psi, 0.0001 kPa, Fluke 718 dry air only and includes on board pump 0.0001 in H20
-12 to + 30 psi, (-83 to 207 kPa)
0.001 psi, 0.001 kPa, 0.001 in H20
-12 to + 100 psi, (-83 to 690 kPa)
0.01 psi, 0.01 kPa, 0.01 in H20
-12 to +300 psi, (-83 to +2070 kPa)
0.01 psi, 0.01 kPa, 0.01 in H20
0-500 psi, 0-3450 kPa 0-1000 psi, 0-6900 kPa 0-1500 psi, 0-10342 kPa 0-3000 psi, 0-20700 kPa 0-5000 psi, 0-34500 kPa 0.05 % of range 0 mA to 24 mA range
0.01 psi, 0.1 kPa 0.01 psi, 0.1 kPa 0.1 psi, 1 kPa 0.1 psi, 1 kPa 0.1 psi, 1 kPa
Compatible with noncorrosive gases and fluids
0.001 mA resolution
Accuracy: ± 0.015 % +1 count Accuracy: ± 10 %
24 V dc
*These ranges/models available as Intrinsically Safe
General specifications for all Fluke 717 and 718 calibrators Pressure input fitting Maximum voltage Non-operating temperature Operating temperature Relative humidity Operating altitude Shock Vibration Safety EMC Size (LxWxD)/weight (717 with holster) Size (LxWxD)/weight (718 with holster) Power Battery life Warranty
1⁄8 inch NPT female 30 V -40 °C to 60 °C -10 °C to 55 °C 95 % (10 °C to 30 °C); 75 % (30 °C to 40 °C); 45 % (40 °C to 50 °C); 35 % (50 °C to 55 °C) 3,000 m max 1 m drop test Random, 2 g, 5 Hz to 500 Hz CSA C22.2 No. 1010.1:1992 (Call Fluke for 718Ex safety ratings) EN50082-1:1992 and EN55022:1994 Class B 201 mm x 98 mm x 52 mm (7.93 in x 3.86 in x 2.06 in)/ 600 g (21 oz) 216 mm x 94 mm x 66 mm (8.50 in x 3.72 in x 2.60 in)/ 992 g (35 oz) 9 V battery ANSI/NEDA 1604 A or IEC 6LR61 9 V alkaline; two batteries in 718 4 to 20 hours, typical, depending on functions used Three years (one year on pressure pump in Fluke 718); one year for 718Ex
For more detailed information, go to www.fluke.com/pressure
Ordering information Fluke-718 Fluke-718 Calibrator Fluke-718 Calibrator Fluke-718 Calibrator Fluke-717 Fluke-717 Fluke-717 Calibrator Fluke-717 Calibrator Fluke-717 Calibrator Fluke-717 Calibrator Fluke-717 Calibrator Fluke-717 Calibrator Fluke-717 Calibrator
1G Pressure Calibrator 30US Pressure 100US Pressure 300G Pressure 1G Pressure Calibrator 30G Pressure Calibrator 100G Pressure 300G Pressure 500G Pressure 1000G Pressure 1500G Pressure 3000G Pressure 5000G Pressure
Each calibrator includes protective holster, test leads and alligator clips, 9 V alkaline battery (two on the 718), product overview in 14 languages, users manual on CD (718 only), NIST-traceable certificate of calibration; CE and CSA markings.
21
Industrial multimeters Fluke 87V Industrial True-rms Multimeter The Fluke 87V has measurement functions, troubleshooting features, resolution, and accuracy to solve more problems on motor drives, in-plant automation, power distribution, and electro-mechanical equipment.
Features include:
• Unique function for accurate voltage and frequency measurements on variable speed motor drives and electrically noisy equipment
• Measure 20 A for up to 30 sec, 10 A continuously • Built-in thermometer
Available in intrinsically safe version as the Fluke 87V Ex (see page 15)
Specifications Function
Range and resolution
Basic accuracy
V dc V ac Current dc
600.0 mV, 6.000 V, 60.00 V, 600.0 V, 1000 V 600.0 mV, 6.000 V, 60.00 V, 600.0 V, 1000 V 600.0 μA, 6000 μA, 60.00 μA, 600.O mA, 6.000 A, 10.00 A
0.05 % 0.7 % (true-rms) 0.20 %
Current ac
600.0 μA, 6000 μA, 60.00 μA, 600.O mA, 6.000 A, 10.00 A -200 °C to 1090 °C (-328 °F to 1994 °F) -40 °C to 260 °C (-40 °F to 500 °F) 600.0 Ω, 6.000 kΩ, 60.00 kΩ, 600.0 kΩ, 6.000 mΩ, 50.00 MΩ 10.00 nF, 100.0 nF, 1.000 μF, 10.00 μF, 100.0 μF, 9,999 μF 199.99 Hz, 1.9999 kHz, 19.999 kHz, 199.99 kHz
1.0 % (true-rms)
Temperature (excl. probe) 80BK Temperature Probe Resistance N10140
Capacitance Frequency
General specifications
22
Size (HxWxL)/weight
52 mm x 98 mm x 201 mm (2.06 in x 3.86 in x 7.93 in)/ 22.5 oz (637.80 g)
Battery
Single 9 V alkaline battery
Battery life
400 hours (without backlight)
Warranty
Limited lifetime warranty
Ordering information Fluke-87-5 Industrial True-rms Multimeter Each multimeter includes protective yellow holster with test lead storage, TL75 Test Lead Set plus AC70A Alligator Clips, one 9 V alkaline battery, users manual.
Recommended accessories
TL220 SureGrip Industrial Test Lead Set
C35 Lightweight Soft Accessory Case
i400 AC Current Clamp
For more detailed information, go to www.fluke.com/87v
1.0 % 2.2 °C or 2 % 0.20 % 1.0 % 0.001 %
New! Fluke 289 Digital Multimeter with TrendCapture The Fluke 289 Digital Multimeter is the next generation high performance industrial logging multimter. With the ability to log data and review it graphically on-screen you can solve problems and help minimize downtime.
Features include:
•
• • • • • •
50,000 count, 1/4 VGA display with white backlight for fast, accurate viewing of measurements Logging function with TrendCapture plots measurements as single line to help detect anomalies New zoom on trend allows you to view analyze TrendCapture data; Zoom in up to 14 times Logging function with expanded memory for unattended monitoring of signals over time. Users can graphically review logged readings without a PC. Store up to 15,000 recorded events. Saved measurements allows you to name and recall measurements made in the field Rotary switch memory when switching positions between ac or dc A/mA and uA LoZ: low input impedance function helps prevents false readings due to “ghost voltage”
Specifications Function
Range and resolution
Basic accuracy
V dc V ac Current dc
50.000 mV, 500.00 mV, 5.0000 V, 50.000 V, 500.00 V, 1000.0V
0.03 % 0.4 % (true-rms) 0.15 %
Current ac Temperature (excl. probe) Resistance Capacitance Frequency
500.00 µA, 5000.0 µA, 50.000 mA, 400.00 mA, 5.0000 A, 10.000 A -200.0 °C to 1090.0 °C (-328.0 °F to 1994.0 °F) 50.000Ω, 500.00 Ω, 5.0000 kΩ, 50.000 kΩ, 500.00 kΩ, 5.0000 MΩ, 50.00 MΩ, 500.0 MΩ 1.000 nF,10.00 nF 100.0 nF, 1.000 µF, 10.00 µF, 100.0 µF, 1000 µF, 10.00 mF, 100.00 mF 999.99 kHz
0.7 % (true-rms) 1.00 % 0.05 %
23
1.00 % 0.005 % +1
Ordering information Fluke-289 True-rms Industrial Logging Multimeter with TrendCapture
Recommended accessories
Each multimeter includes two AC72 Alligator Clips, TL71 Silicon Test Lead Set, Probe holder, 6 AA batteries (installed), users manual. TLK289 Industrial Master Test Lead Set
TL220 SureGrip Industrial Test Lead Set
i400 AC Current Clamp
For more detailed information, go to www.fluke.com/289
Thermometers Thermometers Fluke 54 Series II Contact Thermometer Lab accuracy in a field thermometer
• Dual thermocouple inputs • Accuracy: ± (0.05 % + 0.3 °C) • Large backlit dual display presents all the information you need at a glance
• Min, Max, and Avg—with time reference—captures major events and logs up to 500 points
• Electronic offset function allows you to compensate for thermocouple errors
Fluke 568 Thermometer The two-in-one infrared and contact thermometer with an innovative graphical display
54-II
Ordering information Fluke-54-2 Thermometer
568
62
Recommended accessories: 54 Series II and 568 Thermometers
Fluke 62 Infrared Thermometer
Each thermometer includes two bead thermocouples, batteries, overview manual and instructional guide on CD. Also available: 51-2, 52-2 and 53-2 models.
24
Fluke-62 Mini Infrared Thermometer Each thermometer includes storage pouch and instruction sheet
Quick and reliable surface temperature readings
80PK-8 Pipe Clamp Temperature Probe
Fluke 568 Thermometer Each thermometer includes Thermocouple K bead probe, hard case, two AA batteries, FlukeView Forms software, USB cable, Getting Started Guide, users manual on CD.
Quickly and simply adjust emissivity, start data logging, or turn on and off alarms, with just a few pushes of a button. • Measure -40 °C to 800 °C (-40 °F to 1470 °F) • Easily access advanced features with soft-key buttons and graphical display • Measure from further away, with a distance-to-spot ratio of 50:1 • Compatibility with most type K thermocouples
80PK-22 SureGrip™ Immersion Temperature Prove
The Fluke 62 pistol grip thermometer offers an easy-to-use solution for temperature measurement in hard-to-reach, hot, rotating or dangerous situations. • Measure -30 °C to 500 °C (-20 °F to 932 °F) • Rugged, small design with protective boot • Distance-to-spot ratio of 10:1 is ideal for distances up to 2 m (6 ft)
80PK-11 Type K Velcro Thermocouple Temperature Probe
For more detailed information, go to www.fluke.com/thermometers
Thermal imagers New Fluke Ti25 Thermal Imager The ultimate tool for process monitoring Built for tough work environments, this high-performance, fully radiometric imager is ideal for troubleshooting process equipment. • Patent-pending IR-Fusion® Technology: blends visual and infrared images in different viewing modes including picture-in-picture • Withstands 2 m (6.5 ft) drop; Resistant to dust/water Ti55FT (IP54 rating) • Detects small temperature differences with excellent thermal sensitivity (NETD) • Easy-to-use three-button menu
Ti50 and Ti55 IR FlexCam® Thermal Imagers Choose the Fluke Ti5x models when you need the best images. They feature 320 x 240 detectors with industry leading thermal sensitivity (≤ 0.05 °C NETD for Ti55 models and ≤ 0.07 °C NETD for Ti50 models) for high resolution, ultra high-quality images. • Comes with patent-pending IR-Fusion® Technology • Large display with low-noise VOx sensors for high quality images • The 180° articulating lens makes it possible to view and capture images in areas with poor accessibility
Detector (sensor type)
Fluke Ti25 160 x 120
Field of view Min focus distance Spatial resolution Multiple lens option Hot/cold spot Thermal sensitivity (NETD) Temp range Temp accuracy # of palettes Digital zoom Display Annotation Articulating lens
Ordering information Fluke-Ti25 9Hz Thermal Imager
Specifications Function
Ti25
Ti50FT
Ti55FT
320 x 240 Focal plane array, uncooled microbolometer 23° x 17° 0.15 m
2.5 mrad
2.6 mrad 2.6 mrad No Yes Yes Yes No Yes ≤0.1 °C at 30 °C (100 mK) ≤0.07 °C at 30 °C (70 mK) ≤0.05 °C at 30 °C (50 mK) -20 °C to 350 °C –20 °C to 350 °C –20 °C to 600 °C ± 2 °C or 2% whichever is greater 6 8 8 No 2X, 4X 2X, 4X, 8X 3.6 in high resolution LCD 5 in high resolution color LCD Voice No Text No Yes Yes
For more detailed information, go to www.fluke.com/thermography
Each thermal imager includes SmartView™ software (free software upgrades for life), rugged hard carrying case, ac power supply and battery charger, SD memory card and USB reader and users manual.
Fluke-Ti55FT-20 IR Flexcam Thermal Imager with IR-Fusion Each thermal imager includes SmartView™ software (free software upgrades for life), 2 rechargeable battery packs, battery charger, ac adapter, video cable, 5512 MB compact flash card and reader, USB cable, users manual on CD.
25
120 Series ScopeMeter ScopeMeter® 120 Series Handheld Oscilloscope For industrial electrical, electronic and process troubleshooting applications The compact ScopeMeter 120 Series is the rugged solution for industrial troubleshooting and installation applications. It’s a truly integrated test tool, with oscilloscope, multimeter and “paperless” recorder in one affordable, easy-to-use instrument. Find fast answers to problems in machinery, instrumentation, control and power systems. The ScopeMeter 125 also features Bus Health Test for industrial bus systems and has power measurement capabilities. • Two 5,000-count true-rms digital multimeters • A dual-input TrendPlot™ recorder • Connect-and-View™ trigger simplicity for hands-off operation • Shielded test leads for oscilloscope, resistance and continuity measurements
Specifications Function Bandwidth Max. real time sample rate Equivalent time sample rate
125
Ordering information Fluke-123 Industrial
26 ScopeMeter, 20 MHz
Fluke-123/S with SCC120 Kit Fluke-124 Industrial ScopeMeter, 40 MHz Fluke-124/S with SCC120 Kit Fluke-125 Industrial ScopeMeter (40MHz)
Max. record length (per input) Number of inputs Input sensitivity Display and display modes Display Envelop Mode FFT Triggering Edge, single, free run Video Video line select External Advance Functions Cursors
Bus Health test mode Advanced power measurements Save set-ups and screens
Fluke 125 40 MHz 2.5 GS/s
Fluke 124 40 MHz 25 MS/s 2.5 GS/s 512 points (min/max pairs)
Fluke 123 20 MHz 1.25 GS/s
2 scope or DMM inputs 5 mV/div. to 50 V/div. Monochrome
• Harmonics mode
– • • • Using optional ITP 120
• • •
•
20
20
– – – 10
aximum input voltage 1000 V CAT II with VPS40, 40 MHz, 10:1 voltage probe (standard included with M Fluke 125 and Fluke 124) Detailed technical specifications and optional accessories can be found in the technical datasheet and on the Fluke web site.
(1)
Fluke-125/S with SCC120 Kit
For more detailed information, go to www.fluke.com\scopemeter
Flukeâ&#x20AC;Ś more than just great tools Service A comprehensive, worldwide network of service support for your tools Fluke process calibrators help keep your companyâ&#x20AC;&#x2122;s process accurate and online. Keep your calibrators in top shape with annual scheduled calibrations and factory updates. Fluke has calibration and factory service facilities located in North America, Europe and Asia to make it easy to receive fast, efficient, factory level service for your Fluke calibrator. Our European center also has the distinction of Ex certification for repair and calibration of your Ex rated equipment. In addition to these Fluke competence centers we have a Fluke CalNetÂŽ calibration network of service partners throughout Europe to assist with your service needs.
Training Stay at the forefront of your profession with training from Fluke Fluke is dedicated to providing programs, training and resources to help you stay at the forefront of your profession. Training ranges from application specific hands on seminars, web based training and virtual demos to classroom style and onsite training delivered by Fluke topic experts. www.fluke.com/caltraining
27
Calibrator Calibrators selection Selection guide Guide Temperature sources Handheld dry-wells
Model Temperature range Accuracy
Thermocouple furnace
Field dry-wells
9100S Page 29
9102S Page 29
9009 Page 31
9141 Page 30
9103 Page 30
9140 Page 30
9150 Page 30
35 °C to 375 °C
–10 °C to 122 °C
–15 °C to 35 °C
50 °C to 650 °C
–25 °C to 140 °C
35 °C to 350 °C
150 °C to 1200 °C
± 0.25 °C
± 0.25 °C
± 0.2 °C
± 0.5 °C
± 0.25 °C
± 0.5 °C
± 5 °C
Temperature sources continued Metrology wells
Model
9142 Page 32
Temperature range –25 °C to 150 °C Accuracy
± 0.2 °C
Micro-baths
Infrared calibrators
9143 Page 32
9144 Page 32
6102 Page 33
7102 Page 33
7103 Page 33
418X Series Page 34
33 °C to 350 °C ± 0.2 °C
50 °C to 660 °C ± 0.35 °C
35 °C to 200 °C
–5 °C to 125 °C
–30 °C to 125 °C
–15 °C to 500 °C
± 0.25 °C
± 0.25 °C
± 0.25 °C
± 0.35 °C
Temperature sensors and indicators PRT
28
Model
Thermistor
5626 Page 37
5615 Page 37
5627 Page 37
Temperature range –200 °C to 660 °C –200 °C to 420 °C –200 °C to 420 °C
5611T Page 37 0 °C to 100 °C
Handheld
1523/1524 Page 36
1502A Page 35
1529 Page 35
–200 °C to 2315 °C –200 °C to 962 °C –200 °C to 962 °C
Accuracy
± 0.014 °C
± 0.03 °C
± 0.05 °C
± 0.01 °C
± 0.002 °C
Channels
N/A
N/A
N/A
N/A
1/2
Fluke’s Hart Scientific is pleased to offer a selection dry-wells and reference thermometers made specifically for industrial applications. See your local Fluke distributor or go to www.hartscientific.com.
Bench top
0.004 °C to 0.24°C 0.004 °C to 0.24°C 1
4
Handheld dry-wells Hart Scientific 9100S and 9102S Handheld Dry-Well Temperature Calibrators A temperature source that you can take anywhere • Fast and easy calibrations of temperature sensors • Temperature ranges from -10 °C to 375 °C • Stability during calibrations to ± 0.05 °C • Direct interface to the Fluke 744 Each unit includes RS-232 interface, instrument control software and a NIST-traceable calibration. Recommended accessories: Carrying case, additional inserts, reference temperature sensor and indicator, and battery pack.
Specifications Function Range Accuracy Stability Heating times Cooling times Well depth
Size (HxWxD) Weight Computer interface
9100S
9102S
35 °C to 375 °C (95 °F to 707 °F) –10 °C to 122 °C (14 °F to 252 °F) at 23 °C ambient ± 0.25 °C at 50 °C; ± 0.25 °C at ± 0.25 °C 100 °C; ±0.5 °C at 375 °C ± 0.07 °C at 50 °C; ± 0.1 °C at ± 0.05 °C 100 °C; ±0.3 °C at 375 °C ambient to 375 °C: 9.5 minutes ambient to 100 °C: 10 minutes 375 °C to 100 °C: 16 minutes ambient to 0 °C: 10 minutes
102 mm (4 in); 1.6 mm (1/16 in) hole is 89 mm (3.5 in) deep
102 mm (4 in)
57 mm x 125 mm x 150 mm
99 mm x 140 mm x 175 mm
Temperature sensor calibration is easy with a handheld dry-well.
Ordering information 9100S-V-X Handheld Dry-Well 9300 Rugged Carrying Case, 9100
(2.25 in x 4.9 in x 5.9 in) (3.9 in x 5.5 in x 6.9 in) 1 kg (2 lb 3 oz) 1.8 kg (4 lb) RS-232 included with free Interface-it software
9102S-V Handheld Dry-Well, comes with your choice of two 3102 inserts 9308 Hard Carrying Case, 9102/9132 9320A-156 Battery Pack, 115V (9102S run time: 4 hrs)
9100 fixed-block options
3102-1 Insert, AL 1/16 in (1.6 mm) 3102-2 Insert, AL 1/8 in (3.2 mm) 3102-3 Insert, AL 3/16 in (4.8 mm) 3102-4 Insert, AL 1/4 in (6.4 mm) (Standard) 3102-6 Insert, AL 3/8 in (9.5 mm) (Standard) 3102-7 Insert, AL 7/16 in (11.1 mm) (Standard) 3102-8 Insert, AL 5/32 in (4 mm) (Standard) 2514 Dry-well interface cable V= voltage. Specify “156”(115 V 50/60 Hz), “256” (220 V 50/60 Hz) X = Fixed-block. Specify “A”, “B”, “D”
See www.hartscientific.com for additional specifications and information.
29
Field dry-wells and furnaces Hart Scientific 9103, 9140 and 9141 Field Dry-Wells and 9150 Thermocouple Furnace Temperature sensor test and calibration • Lightweight and very portable • Accuracy to 0.25 °C • RS-232 and Interface-it software included • Interchangeable inserts • 9103 goes as low as –25 °C • 9140 is 6 pounds (2.7 kg) and 9141 is 3.6 kg (8 lb) • 9140 and 9141 reach max temp in 12 minutes • 9150 extends up to 1200 °C covering a wide range of T/C types • Direct interface to Fluke 744 Each dry-well includes one of four available well inserts, an optional carrying case, RS-232 interface, instrument control software and a NIST-traceable calibration. Recommended accessories: Carrying case, additional inserts, reference temperature sensor and indicator.
Ordering information 9103-V-X Dry-Well, –25 °C to 140 °C 9140-V-X Dry-Well, 35 °C to 350 °C
30 9316 Carrying Case, 9103 9308 Carrying Case, 9140 9309 Carrying Case, 9141 9315 Carrying Case, 9150
Significant performance improvement can realized by optimizing the loop calibration measurement system to better accommodate the unique characteristics of the temperature sensing element. All temperature probes and their sensing elements are unique, with variations in materials, construction and usage, or exposure to different environments. This uniqueness continues throughout the useful life of the sensor, in the form of drift due to mechanical shock and vibration or to contamination of the materials when exposed to the material they are measuring. Only through periodic verification can these differences and changes be accommodated, improving total measurement performance. Temperature plays an important role in many industrial and commercial processes. Examples range from sterilization in pharmaceutical companies, metal heat-treatment to ensure optimal strength in aerospace applications, temperature verification in a cold storage warehouse, and atmospheric and oceanographic research. In all temperature measurement applications, the sensor strongly affects the results; unfortunately, many measurements are made without optimizing the system to get the best performance from the temperature transducer. The majority of process temperature measurements are performed using a sensing element connected to a trans-
Application Note Digital temperature indicator/controller
100 ° C MENU
In control room
Temperature sensor Temperature transmitter
Process temperature measured Process vessel
4-20 mA
9150-V-X Thermocouple Furnace, 150 °C to 1200 °C
Calibrating a loop is more than just 4 mA to 20 mA
4-20 mA
9141-V-X Dry-Well, 50 °C to 650 °C
Application note, literature code 2148146:
Eliminating sensor errors in loop calibrations
ENTER
24 VDC load supply
ZERO SPAN
Flow control valve
Burner/heater
Figure 1. Diagram of a typical process temperature measurement system
mitter. Figure 1 shows a diagram of a common configuration. In many applications, it is common to verify the elements of the measurement system separately, but in doing so, significant improvements made possible by considering the system as a whole are ignored. One of the main reasons the elements are verified or calibrated separately is that it is often considered to be more efficient. Verifying the measurement component is done simply and quickly with an electronic thermocouple (TC) or
resistance temperature detector (RTD) simulator. This approach does not verify the performance of the associated temperature probe, and assumes all probes are identical and closely follow some standard. In practice, no two probes are identical; they all vary from the ideal standard, and over time and usage their characteristics change. Understanding how probes vary from the ideal will allow you to optimize the measurement system to achieve the best performance.
Eliminating sensor errors in loop calibrations The secret to effective loop calibration is in the temperature sensor. You can make huge gains in accuracy. We’ll show you how.
2514 Dry-well Interface Cable V= voltage. Specify “156”(115 V 50/60 Hz), “256” (220 V 50/60 Hz) X = insert (interchangeable). Specify “A”, “B”, “C”, “D”
9103, 9140, 9141 and 9150 insert options 1/16 in (1.6 mm) 1/2 in (12.7 mm)
1/8 in (3.2 mm)
Insert “A”
1/4 in (6.35 mm)
Insert “B”
3/16 in (4.8 mm)
3/8 in (9.5 mm) 3/8 in (9.5 mm) 3/16 in (4.8 mm) 1/4 in (6.35 mm)
1/4 in (6.35 mm)
Insert “C”
3/8 in (9.5 mm)
3/16 in 1/4 in (4.8 mm) (6.35 mm)
Insert “D”
3 mm
4 mm
6 mm 6 mm 4 mm
3 mm
Field dry-wells Hart Scientific 9009 Industrial Dual-Block Calibrator Cut your calibration time in half
• Calibrate temperature sensors fast • Independently controlled cold and hot blocks • –15 °C to 110 °C (cold block), 50 °C to 350 °C (hot block) • Self-contained in a rugged watertight case • Four removable inserts • Direct interface to Fluke 744 Each unit includes four removable inserts, including two with holes that are 6.4 mm (1/4 in) and two with holes that are 4.8 mm (3/16 in) in diameter. Each unit also includes a power cord, insert removal tool, RS-232 interface, instrument control software and a NIST-traceable calibration Recommended accessories: Additional inserts, reference temperature sensor and indicator.
Specifications Function Range
Accuracy
Hot block
Cold block
50 °C to 350 °C (122 °F to 662 °F)
–15 °C to 110 °C (5 °F to 230 °F) –8 °C (18 °F) with hot block at 350 °C (662 °F) ± 0.2 °C
± 0.6 °C
± 0.05 °C
Stability Well-to-well uniformity Display resolution Heating times Cooling times Stabilization times Well depth
Removable inserts Computer interface Power Size (HxWxD) Weight
± 0.1 °C 0.1 ° 10 minutes from 25 °C to 350 °C 15 minutes from 25 °C to 110 °C
30 minutes from 16 minutes from 350 °C to 100 °C 25 °C to –15 °C 8 minutes 102 mm (4 in) Two 6.4 mm (1/4 in) and two 4.8 mm (3/16 in) inserts included; see Ordering Information for other available inserts RS-232 included with free Interface-it software 115 V ac (± 10 %), 3 A, or 230 V ac (± 10 %), 2 A, specify, 50/60 Hz, 280 W 178 mm x 267 mm x 248 mm (7 in x 10.5 in x 9.75 in) 4.5 kg (10 lb.)
Ordering information 9009-B-V Dual Block Dry-Well (Black), –15 °C to 350 °C 9009-Y-V Dual Block Dry-Well (Yellow), –15 °C to 350 °C 3102-1 Insert 1.6 mm (1/16 in) 3102-2 Insert 3.2 mm (1/8 in) 3102-3 Insert 4.8 mm (3/16 in) 3102-4 Insert 6.4 mm (1/4 in) 3102-5 Insert 7.9 mm (5/16 in) 3102-6 Insert 9.5 mm (3/8 in) 3102-7 Insert 11.1 mm (7/16 in) 3102-8 Insert 4 mm (5/32 in) 2514 Dry-well interface cable V= voltage. Specify “156”(115 V 50/60 Hz), “256” (220 V 50/60 Hz)
See www.hartscientific.com for additional specifications and information.
31
Field dry-wells and furnaces Field metrology wells Hart Scientific 9140 Series Automate for fast, accurate, documented results: Built-in measure capability for a reference PRT, and an RTD/PRT, thermocouple, and 4 mA to 20 mA transmitter.
Typical automated applications
• Loop calibrations of temperature transmitters • Thermocouple calibration or verification • Calibrations of RTDs or PRTs • Testing of thermostatic switches • Verification of industrial thermometers Recommended accessories: Reference PRT, transportation case, additional inserts.
Ordering information 9142-V-X-P Field Metrology Well, -25 °C to 150 °C, process version 9143-V-X-P Field Metrology Well, 33 °C to 350 °C, process version 9144-V-X-P Field Metrology Well, 50 °C to 660 °C, process version 9142-INS[X] Additional insert, 9142 9143-INS[X] Additional insert, 9143
32
Specifications Function Temperature range at 23 °C Display accuracy Stability Environmental conditions Immersion (well) depth Heating time Cooling time Size (H xWxD) Weight Computer interface
9142
9143
–25 °C to 150 °C
33 °C to 350 °C ± 0.2 °C full range
9144 50 °C to 660 °C ± 0.2 °C full range ± 0.35 °C at 50 °C ± 0.5 °C at 660 °C ± 0.01 °C full range ± 0.02 °C at 33 °C ± 0.03 °C at 50 °C ± 0.03 °C at 350 °C ± 0.05 °C at 660 °C 13 °C to 33 °C for all specifications except temperature range 150 mm (5.9 in) 16 min: 23 °C to 140 °C 5 min: 33 °C to 350 °C 15 min: 50 °C to 660 °C 15 min: 23 °C to –25 °C 14 min: 350 °C to 100 °C 25 min: 660 °C to 100 °C 290 mm x 185 mm x 295 mm (11.4 x 7.3 x 11.6 in) 8.16 kg (18 lb) 7.3 kg (16 lb) 7.7 kg (17 lb) RS-232 and 9930 Interface-it control software included
9144-INS[X] Additional insert, 9144 9142-CASE Carrying Case, 9142-9144
9142 insert options
5615-12-A PRT 305 mm x 6.35 mm (12 in x 1/4 in) w/accredited calibration 5626-15-A PRT 381 mm x 6.35 mm (15 in x 1/4 in) with accredited calibration V= voltage. Specify “156” (115 V 50/60 Hz), “256” (220 V 50/60 Hz)
9143/9144 insert options
X = insert (interchangeable). Specify “A”, “B”, “D”, “E”
See www.hartscientific.com for additional specifications and information.
Micro-baths Hart Scientific 6102, 7102 and 7103 Micro-Baths Portability and extreme stability
• Temperature sensor calibration • Stability to ± 0.015 °C • Ranges from -30 °C to 200 °C • Accepts oddly shaped sensors • Exceptional bath portability • Direct interface to Fluke 744 Each unit includes a stir bar, power cord, RS-232 interface, instrument control software and a NIST-traceable calibration. Recommended accessories: Fluid, case, reference probe and meter, extra stir bar, tank extension for LIG, MET/TEMP II.
Hart Scientific 9938 MET/TEMP II Software Easy-to-use temperature calibration automation software
• Fully automated calibration of RTDs, thermocouples, thermistors and many heat sources • Calibrates up to 100 sensors at up to 40 points • Performs coefficient calculations and generates tables and reports • Reports conform to ANSI and NCSL standards Each unit includes: CD-ROM, RS-232 multiplexer box, adapter, and PC cable.
Hart Scientific 9934/9935 LogWare Data Logging and Analysis Software Turns any Hart Scientific thermometer readout into a real-time data logger
• Calculates statistics and displays customized graphs • User-selectable alarms,
delayed start times, and sample intervals • Logging intervals from 1 second to 24 hours • User-settable alarm functions
Tip: For improved accuracy use an external reference temperature indicator and sensor such as a 1521 and 5615-12-I combination.
Ordering information 7103 Micro-Bath, 30 °C to 125 °C (includes a transport lid and test lid) 7102 Micro-Bath, -5 °C to 125 °C (includes a transport lid and test lid) 6102 Micro-Bath, 35 °C to 200 °C (includes a transport lid and test lid) (Specify 110 V or 220 V power) 5010-L Silicone Oil, 1 liter (-40 °C to 130 °C) 5013-L Silicone Oil, 1 liter (10 °C to 230 °C) 9317 Carrying Case, 7103 9310 Carrying Case, 6102 9311 Carrying Case, 7102 9938 MET/TEMP II Software (specify 110 V or 220 V) 9934 LogWare, single channel logging software 9935 LogWare II, multiple channel logging software 2514 Dry-Well Interface Cable *Software requires Windows® 98 or higher
See www.hartscientific.com for additional specifications and information.
33
Precision infrared calibrators Hart Scientific 4180 and 4181 Precision Infrared Calibrators Accurate yet portable
• Infrared display accuracy as good as ± 0.35 °C on both units • Convenient handle and weight of 9.5 kg (21 lb) or less for portability Easy to get dependable results
• Each unit is given an accredited radiometric calibration for consistent, reliable, and traceable results
• Audio/visual stability indication provided for ease of use • Stores thermometer configurations including temperature set-points, calibration distance, emissivity setting
A superior target
• 152 mm (6 in) diameter target addresses critical size-of-source effect issues for infrared thermometers
Each unit includes accredited radiometric report of calibration, protective target cover and manual.
Application note, literature code 3187781:
Infrared Temperature Calibration 101 Infrared temperature calibration is not so hard when you are on the right wavelength. View the necessary background information for spot on calibration.
Specifications Feature Temperature range (@ 23 °C ambient, 0.95 emissivity) Total accuracy
Stability Uniformity (2.0 in dia of center of target)
34
4181 35 °C to 500 °C
± 0.40 °C at –15 °C
± 0.35 °C at 35 °C
± 0.40 °C at 0 °C
± 0.70 °C at 200 °C
± 0.55 °C at 120 °C
± 1.60 °C at 500 °C
± 0.10 °C at –15 °C
± 0.05 °C at 35 °C
± 0.10 °C at 120 °C
± 0.40 °C at 500 °C
± 0.10 °C at -15 °C
± 0.10 °C at 35 °C
± 0.10 °C at 0 °C
± 0.25 °C at 200 °C
± 0.20 °C at 120 °C
± 0.50 °C at 500 °C
Heating time
15 min: –15 °C to 120 °C
20 min: 35 °C to 500 °C
Cooling time
20 min: 23 °C to –15 °C
40 min: 500 °C to 100 °C
Nominal emissivity
Ordering information
Thermometer emissivity compensation
4180 Precision Infrared Calibrator, –15 °C to 120 °C
Target diameter
4181 Precision Infrared Calibrator, 35 °C to 500 °C
Size (HxWxD)
4180-CASE Protective Carrying Case
4180 –15 °C to 120 °C
0.95
0.95 0.9 to 1.0 152.4 mm (6 in) RS-232
Computer interface
Weight
356 mm x 241 mm x 216 mm (14 in x 9.5 in x 8.5 in)
356 mm x 241 mm x 216 mm (14 in x 9.5 in x 8.5 in)
9.1 kg (20 lb)
9.5 kg (21 lb)
4180-DCAS Protective Carrying Case with wheels
See www.hartscientific.com for additional specifications and information.
Thermometer readout Hart Scientific 1529 Chub-E4 Thermometer Lab-quality accuracy on four channels
• Four channels for PRTs, thermistors and thermocouples • Simultaneous measurement on four channels • Displays eight user-selected data fields • Logs up to 8,000 readings • Battery provides eight hours of continuous operation • Compatible with LogWare and MET/TEMP II software Recommended accessories: PRT (5626-12-L, 5615-12-L, or 5627A-12-L), thermistor (5611T-L or 5610-L), rugged carrying case (holds 1529 and four probes), LogWare II multi-channel logging software.
Hart Scientific 1502A “Tweener” Thermometer Great price and performance in one package
• PRT readout with accuracy to ± 0.006 °C • Reads both 100 W and 25 W probes • 0.0001° resolution • Optional battery pack available • Compatible with LogWare and MET/TEMP II software Recommended accessories: PRT (5626-12-D, 5615-12D, or 5627A-12-D), 9301 carrying case fits Tweener and 12 in probe, LogWare II single channel logging software.
Specifications
1529
Feature
PRT/RTD
Thermistor
1502A Thermocouple
Tweener
Inputs
4 channels PRT/RTD/thermistor and/or thermocouple
1 channel PRT/RTD
Temperature range
–189 °C to 960 °C –50 °C to 150 °C (-308 °F to 1760 °F) (-58 °F to 302 °F)
–270 °C to 1800 °C (-454 °F to 3272 °F)
-200 °C to 962 °C (-328 °F to 1764 °F)
Measurement range
0 Ω to 400 Ω
0 KΩ to 500 KΩ
–10 mV to 100 mV
0 Ω to 400 Ω
Temperature accuracy, typical (meter only)
± 0.006 °C at 0 °C ± 0.009 °C at 100 °C
± 0.0025 °C at 0 °C Ext. RJC: Int. RJC ± 0.006 °C at 0 °C ± 0.025 °C at K at 600 °C ± 0.15 °C: ± 0.4 °C ± 0.009 °C at 100 °C 100 °C T at 200 °C ± 0.1 °C: ± 0.3 °C
Temperature resolution
0.001 °C
0.0001 °C
Communications
RS-232 (tweener) and IR ports included, IEEE-488 (GPIB) optional
Size (HxWxD)
102 mm x 191 mm x 208 mm (4.0 in x 7.5 in x 8.2 in)
61 x 143 x 181 mm (2.4 x 5.6 x 7.1 in)
Weight
2 kg (4.5 lb)
1.0 kg (2.2 lb)
Calibration
Accredited NIST-traceable resistance calibration and NIST-traceable voltage calibration provided
0.01 °C to 0.001 °C
0.001 °C
Ordering Information 1529 Chub-E4, 2 TC and 2 PRT/Thermistor Inputs 1529-R Chub-E4, 4 PRT/Thermistor Inputs 1529-T Chub-E4, 4 TC Inputs 5611T-L Flexible Teflon Coated Precision Thermistor, 0 °C to 100 °C 5610-9-L Precision Thermistor, 0 °C to 100 °C 2506-1529 IEEE Option 9322 Rugged Carrying Case 1502A-156 “Tweener” PRT Thermometer (110 V) 1502A-256 “Tweener” PRT Thermometer (220 V) 9313 Battery Pack 9301 Carrying Case, fits Tweener and 12 in. probe 9308 Carrying Case, fits Tweener and 6 in. probe 5626-12-X Secondary PRT (12 in x 1/4 in), –200 °C to 660 °C 5615-12-X Secondary PRT (12 in x 1/4 in), –200 °C to 420 °C 5627A-12-X Precision Industrial PRT (12 in x 1/4 in), –200 °C to 420 °C Specify 110 V or 220 V power X= Lead termination. Specify “D” for Tweener, “L” for Chub-E4
See www.hartscientific.com for additional specifications and information.
35
Handheld thermometer readouts Hart Scientific 1523/1524 Reference Thermometer Visual trending and measurement of PRTs, thermocouples and thermistors with 1 or 2 channels Use with PRTs, thermocouples, or thermistors to read, document, and visually trend temperature data. Smart connectors automatically load calibration coefficients for easy and accurate plug and play operation. The single channel 1523 records up to 25 readings, and the dual channel 1524 logs up to 15,000 time and date stamped readings. A free software program makes it easy to download logged data and program new calibration coefficients. • Accuracy to ±0.002 °C with thermistors and ± 0.015 °C with PRTs (Readout only) • Simultaneously measures two channels • Reads PRTs, thermocouples, and thermistors • “Plug-and-play” calibration coefficients with SMART LEMO connector • Trends data graphically Each unit includes NIST traceable certificate of calibration, users guide, CD-ROM (contains technical manual) RS-232 serial cable, software for computer interface, and power supply.
Summary specifications 1523
Ordering Information
Channels
1523 Thermometer, Handheld, 1 Channel
Documenting (includes statistics)
1524 Thermometer, Handheld, 2 Channel, Data Logger 5610-9-P Probe, Thermistor .125 in x 9 in SST
Environmental conditions for all specifications
5615-6-P Probe, Secon. PRT, 100 ohm (.1875 in x 6 in) 5616-12-P Probe, Secon. PRT, 100 ohm
36 (.25 in x 12 in)
5627A-12P Probe, RTD Industrial 12 in x .25 in OD 9935-S Software, LogWare II, Single User 1523-CASE Case, 1523/1524 Readout and Probe Carrying FLUKE TPAK ToolPak, Meter Hanging Kit 2373-LPRT Adapter, Lemo to Mini Grabbers (4-wire) 2373-LTC Adapter, Lemo to Universal TC (TC)
1524
1
2
25 readings
0.036
Logging
None
15,000 readings
Statistics
Average, Stdev, Max, Min
N/A
Thermocouple voltage accuracy/RJC
13°C to 33°C and 0 to 90% RH 0.005 % of reading + 5 μV floor/± 0.35 °C Types J, K, T, E, R, S, B, L, U, C, M and N
TC measurement capability Dimensions (WxHxL)/ weight
96 mm x200 mm x47 mm/0.65 kg
PC communications/ baud rate
RS-232/2400/9600
Power requirements
3 AA Batteries (20 hours) dc universal power supply
Accuracies of selected readout/probe combinations (± °C) T (°C)
5616-12
5615-6
5627A-12
5610-9
-200
0.014
0.025
0.027
n/a
0
0.021
0.021
0.049
0.009
100
0.027
0.028
0.065
0.009
300
0.040
0.043
0.103
n/a
420
0.050
n/a
0.130
n/a
Includes readout accuracy, probe calibration, and drift
See www.hartscientific.com for additional specifications and information
Temperature sensors Each probe includes: • Individual report of calibration • Probe linearization coefficients • Resistance vs. temperature table • Termination to match your thermometer readout
(see spec chart) Tip: Improve the accuracy of your calibration by using an external reference thermometer. Calibrated temperature sensors and indicators can improve your results by a factor of 2 or more. Recommended accessories: 2601 probe carrying case (for probes up to 12 in long), 2609 probe carrying case with handle (for probes up to 20 in long).
Summary specifications for PRT’s Model
Range
Type of Cal
Accuracy w/ Chub-E4 or Tweener (includes drift) –200 °C
0 °C
Dimensions
Unique selling point
Max °C
5626-12-X
–200 °C to 661 °C
Accredited
± 0.006
± 0.009
± 0.037
6.35 x 305 mm
Best reference
5609-12-X
–200 °C to 670 °C
Order 1930-4-7†
± 0.010
± 0.011
± 0.054
6.35 x 305 mm
Highest temperature
5608-12-X
–200 °C to 500 °C
Order 1930-4-R†
± 0.010
± 0.011
± 0.031
3.2 x 305 mm
Excellent immersion
5616-12-X
–200 °C to 420 °C
Traceable
± 0.012
± 0.013
± 0.035
6.35 x 298 mm
Best value
5615-12-X
–200 °C to 420 °C
Accredited
± 0.024
± 0.014
± 0.041
6.35 x 305 mm
Accredited calibration
5615-9-X
–200 °C to 420 °C
Accredited
± 0.024
± 0.014
± 0.041
4.76 x 229 mm
Accredited calibration
5615-6-X
–200 °C to 300 °C
Accredited
± 0.024
± 0.014
± 0.041
4.76 x 152 mm
Smallest
5627A-12
–200 °C to 420 °C
Accredited
± 0.030
± 0.050
± 0.125
4.76 x 305 mm
Most rugged
5627A-9
–200 °C to 300 °C
Accredited
± 0.030
± 0.050
± 0.100
4.76 x 229 mm
Most rugged
5627A-6
–200 °C to 300 °C
Accredited
± 0.030
± 0.050
± 0.100
4.76 x 152 mm
Most rugged
5610-9-X
0 °C to 100 °C
Traceable
N/A
± 0.009
± 0.023
3.2 x 229 mm
High accuracy
5611T-X
0 °C to 100 °C
Traceable
N/A
± 0.009
± 0.023
3 x 6100 mm
Teflon, flexible
Thermistor
X= Lead termination. Specify “A” for 9142/9143/9144, “D” for Tweener, “L” for Chub-E4, and “I” for 1521/1522. Accuracy calculated at k=2 95 % confidence interval. †Calibration ordered separately. For individual probe calibration order the 1923-4-7 or 1923-4-R calibration.
See www.hartscientific.com for additional specifications and information.
37
TPAK Magnetic Hanger 700TC1 and 700TC2 Thermocouple Plug Kits 80CJ-M or 80CK-M Mini-connectors 80PK Thermocouple Probes (all) 700-IV Current Shunt 700LTP-1 Low-pressure Test Pump 700PMP Pressure Pump 700PTP-1 Pneumatic Test Pump 700HTH-1 Hydraulic Test Hose 700HTP-1 Hydraulic Test Pump i410 AC/DC Current Clamp i1010 AC/DC Current Clamp C10 Holster, C12A Case C25/C100 Cases C781 Soft Carrying Case C789 Soft Carrying Case C700 Hard Carrying Case
38
C510 Leather Case C530 Leather Accessory Case C550 Tool Bag H6 Infrared Thermometer Holster PV350 Pressure Vacuum Module 71X Hose Kit
• • •
• • •
• •
• •
•
•
• • • •
717
• • • • •
• • • • •
•
• • • •
289
87V
568
•
51/52, 53/54
• • • •
78X
• • • •
705
•
707
717, 718, 719
• • • • • • • • • • •
725, 726
• • • • • • • • • • •
•
715
BC7217 Battery Charger
•
724
BE9005 Battery Eliminator
• • • • •
714
BP7235 NiMH Battery Pack
• • • • •
712
BP7217 NiCd Battery Pack
741B
700Pxx Pressure Modules
743B, 744
Multifunction Accessories Process Calibrator compatibility chart
• • •
3
•
3
•
3
2 2 2 2
•
• •
•
• •
• •
• •
•
• •
• • • •
• • •
• • •
• • •
• • •
• • •
• • •
• • •
• • •
• • •
•
•
•
•
•
•
•
• • • •
• • •
1. 20 A ac minimum 2. External pump for 718 required only when using high pressure modules 3. Requires 80AK adapter
•
• •
• • •
•
•
•
Accessories—test leads and probes, temperature and pressure
Fluke 700HTP-1
Fluke 700PTP-1
TL224 SureGrip™ Silicone Insulated Test Leads • 1.5 m silicone-insulated wire resists heat and cold • CAT III 1000 V, 10 A, CAT IV 600 V, 10 A
TLK-225 SureGrip™ Master Accessory Kit • AC220 plunger style alligator clips • AC280 plunger style hook clips • AC283 plunger style pincer clips • AC285 large jaw alligator clips • TP220 sharp test probes • TL224 right to straight test leads • 6-pocket storage pouch Fluke-700LTP-1 Low Pressure Test Pump
Hand operated pressure pump designed to generate either vacuum to -13 psi/-.90 bar or pressures to 100 psi/6.9 bar. Ideal for low pressure applications requiring accurate low pressure testing.
Fluke 700LTP-1
C700
TL224
Fluke 700PTP-1 Pneumatic Test Pump
The Fluke 700PTP-1 is a handheld pressure pump designed to generate either vacuum to -11.6 psi/-0.8 bar or pressure to 600 psi/ 40 bar.
Fluke 700HTP-1 Hydraulic Test Pump
The Fluke 700HTP-1 is designed to generate pressures up to 10,000 psi/700 bar. Use the Fluke 700PRV adjustable relief valves to limit pressures from 1360 psi to 5450 psi.
C700 Hard Carrying Case (700 Series)
Hard carrying case with custom-cut foam liner.
Fluke 71X Hose Kit Accessory
Kit includes 5 hoses and 2 push fit fittings with 1/8” NPT connectors and 1 NPT to BSP/ ISO adapter.
39 TLK-225
Multifunction Fluke... Process Calibrator more than just tools Since 1949, the Fluke Corporation has been dedicated to the design and manufacturing of innovative test and measurement instruments. Fluke also leads the way in providing programs, training and resources that help you stay at the forefront of your profession. Electrical Measurement Safety Program www.fluke.com/safety Get a free safety video, a summary of safety standards and helpful articles on safe electrical measurement practices. (Available only in the U.S.)
Online newsletter FlukePlus is a web site for test tool users who want to learn more.
• How-to information, product details, expert tips and case studies
• Preview new Fluke tools • Q&A with tool professionals • Special contests and promotions
Find out more!
www.fluke.com/flukeplus
Fluke Plant News www.fluke.com/flukenews For electricians, electrical supervisors, field service technicians, plant and process engineers maintaining industrial equipment in the field or plant.
Fluke Education Partnership Program www.fluke.com/education
40
We’ve teamed up with colleges, trade, technical, vocational schools, and apprenticeship programs to bring the latest application information and tools into the classroom. Currently available in USA, Canada, Brunei, Burma, India, Indonesia, Laos, Malaysia, Philippines, Singapore, Taiwan, Thailand, Vietnam, Australia, New Zealand and Mexico.
Test Tool Users Online Community www.fluke.com/community See what other test tool users are saying and get your questions answered, fast! The Test Tool Community online bulletin board is free and open to everyone.
Fluke. Keeping your world up and running. ®
Fluke Corporation PO Box 9090, Everett, WA 98206 U.S.A. Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com ©1994-2008 Fluke Corporation. PRM is a trademark of Yokogawa Electric Corporation. Specifications subject to change without notice. Printed in U.S.A. 7/2008 1264563 B-US-N Rev M Modification of this document is not permitted without written permission from Fluke Corporation.