Submittal Data: REYQ168MTJU 14 Ton VRV ® Outdoor Unit – Heat Recovery (R E YQ9 6 MT JU + R EYQ 72 MTJU + Man if o ld K it) Job Name: Purchaser: Engineer: Submitted To: Submitted By: Unit Designation: Schedule #:
Location:
For: Reference Date: Model No.:
Approval
Construction
Capacities: Cooling Capacity Cooling Input Power Heating Capacity Heating Input Power Cooling Mode Nominal Conditions: Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB Pipe Length: 25 ft Level Difference: 0 ft
168,000 Btu/h 14.4 kW 189,000 Btu/h 15.8 kW (53,910 Btu/h) Heating Mode Nominal Conditions: Indoor: 70°F DB Outdoor: 47°F DB / 43°F WB Pipe Length: 25 ft Level Difference: 0 ft
Operating Range: Cooling
23°F – 110°F DB 0°F – 64°F DB -5°F – 60°F WB
Heating
Compressor: Type Quantity Capacity Control Range Motor Rating Output
Daikin High Pressure Dome Scroll 4 (2 PAM inverter and 2 on/off) 7% - 100% (2.7 + 4.5) x 2 kW
Fan: Fan Type x Quantity Fan Motor Output Airflow Rate Drive
Propeller Fan x 2 750 + 750 Watts 7,400 + 7,400 cfm Direct Drive
Power Supply: V/PH/Hz Minimum Circuit Amps (MCA) Maximum Fuse Amps (MFA) Maximum Starting Current (MSC) Total Overcurrent Amps (TOCA)
208-230/3/60 44.8 + 44.8 Amps 60 + 60 Amps 142 Amps 90.9 Amps
Refrigerant & Piping: Refrigerant Type/Charge Control Liquid Refrigerant Piping Gas Refrigerant Piping Discharge Gas Piping Oil equalizing pipe
R-410A/27.3 + 27.3 lbs Electronic Expansion Valve φ5/8” Brazing φ1-1/8” Brazing φ7/8” Brazing φ1/4“ Flare
Unit Data: Max. Number of Indoor Units Sound Pressure Level at 3 ft Weight
20 63 dBA 666 + 666 lbs
Standard Features: • • • • • • •
Six year compressor warranty One year limited labor warranty One year parts warranty Simultaneous operation of heating and cooling PE coated condenser coil to prevent corrosion VFD controlled outdoor motor fan Internal ground fault circuit breaker
For further information about the installation allowances on manifolded systems, please refer to the Installation and Engineering Guides
D a i k i n AC ( Am e r i c a s ) , I n c . ♦ 1 6 4 5 W a l l a c e D r i ve – S u i t e 1 1 0 ♦ C a r r o l l t o n , T X 7 5 0 0 6 SDS REYQ168MTJU 04-07
www.daikinac.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)