Submittal Data: RXYMQ48MVJU 4 Ton Outdoor Unit – Heat Pump VRV-S Job Name: Purchaser: Engineer: Submitted To: Submitted By: Unit Designation: Schedule #:
Location:
For: Reference Date: Model No.:
Approval
Construction
Capacities: Cooling Capacity Cooling Input Power Heating Capacity Heating Input Power Cooling Mode Nominal Conditions: Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB Pipe Length: 25 ft Level Difference: 0 ft
48,000 Btu/h 4.73 kW 54,000 Btu/h 4.26 kW (14,535 Btu/h) Heating Mode Nominal Conditions: Indoor: 70°F DB Outdoor: 47°F DB / 43°F WB Pipe Length: 25 ft Level Difference: 0 ft
Operating Range: Cooling
23°F – 115°F DB 0°F DB – 64°F DB -5°F WB – 60°F WB
Heating
Compressor: Type Quantity Capacity Control Range Motor Rating Output
Hermetically Sealed Scroll 1 29% - 100% 3.1 kW
Fan: Fan Type x Quantity Fan Motor Output Airflow Rate Drive
Propeller Fan x 2 0.070 kW 3,740 CFM Direct Drive
Power Supply: V/PH/Hz Minimum Circuit Amps (MCA) Maximum Fuse Amps (MFA) Maximum Starting Current (MSC) Total Overcurrent Amps (TOCA)
208-230/1/60 27 Amps 30 Amps 24.1 Amps 27 Amps
Refrigerant & Piping: Refrigerant Type/Charge Control Liquid Refrigerant Piping Suction Gas Refrigerant Piping
R-410A / 12.8 lbs Electronic Expansion Valve φ3/8” Flare φ5/8” Flare
Unit Data: Max. Number of Indoor Units Sound Pressure Level at 3 ft Weight
8 58 dBA 310 lbs
Standard Features: • • • • • •
Six year compressor warranty One year parts warranty One year limited labor warranty Heating or cooling operation Inverter driven (variable speed) scroll compressor VFD controlled outdoor motor fan
D a i k i n AC ( Am e r i c a s ) , I n c . ♦ 1 6 4 5 W a l l a c e D r i ve – S u i t e 1 1 0 ♦ C a r r o l l t o n , T X 7 5 0 0 6 SDS RXYMQ48MVJU 04-07
www.daikinac.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)