HealthcareIT Fortifying Network Closets

Page 1

Fortifying Network Closets

Improving Patient Care and Doctor Satisfaction Dan Draper Manager, Healthcare Industry Liebert Products


Agenda • Network closets in hospitals and ambulatory care facilities – Function and importance – Avoiding network downtime

• • • • • • •

Power fundamentals Power best practices Cooling fundamentals Cooling best practices Other areas of IT infrastructure in healthcare settings Critical questions to ask Q&A


Network closets • Computer room, network access room, wiring closet – Typically a 5x5, 6x6 or 8x8 room – Dedicated space containing networking and computing equipment • • • •

Routers Switches Bridges Hubs

– The equipment enabling data communications • Wireless • VOIP/ telecommunications • E-mail / Internet


Network closet differences Hospital Environment

Ambulatory Environment

Many closets, 1 per 10 beds

Single closet

Dedicated support: IT, Facilities, Network Services

If in a health system, remotely supported by parent hospital

Emergency generator on site

Likely, no emergency generator

Routers, switches, hubs

Routers, (maybe) servers and storage

Many closets Increasing heat densities Increasing need for power

Higher heat from server / storage Downtime hurts IT acceptance Lack of dedicated IT expertise


Why should we care? • Network Closet: the link to patient data

Patient

Data Storage

Doctor IT Device

Network Closet

• If the closet is down, can’t access EMR, PACS, VOIP

– Delays, inability to process patients, no orders, no billing – Remember: no more paper back up


IT equipment downtime • IT equipment needs electricity to run – When the power is off, IT won’t work – 6 ½ “momentary outages” per year

• IT equipment produces heat – Heat destroys electronics – Every 10° increase over 80° F produces a 50% reduction in long-term reliability of IT hardware Network closet’s IT infrastructure must be fortified to ensure availability

• Uninterruptible Power Supply (UPS) • Precision Cooling


UPS fundamentals • Instantaneous battery back-up – Ride through until generator assumes the load • Typically rack-mounted in network closets • Two design topologies – Line interactive – Double conversion

Back view

UPS in a rack


Line Interactive / Double Conversion Line Interactive UPS

 

Very efficient, volts in = volts out Load sees a wide range of voltages – Ex: Sag from 120 volts to 100 volts – Critical load only running on 100 volts • If this were a light bulb it would flicker and dim – Battery turns on at 90 volts, load at 120 volts – 4 millisecond transfer to battery

Double Conversion UPS 

Rebuilds voltage, always perfect Load always sees 120 volts – Ex: Sag from 120 volts to 100 volts – Double conversion changes the 100 to 120 – No Battery use until volts drop to 60 • Load never deviates from 120 volts – Zero transfer time to battery


Best practice: When to use which? Line Interactive

Double Conversion

Pro

Efficient Less expensive initially

Constant regulated output power Instantaneous battery switchover High reliability

Con

Load sees voltages sags More battery replacements

Higher initial price

Purchase Price

$1,300 for a 3 kVA UPS

Critical Question

When to use

$3,000 for a 3 kVA UPS

Is there a generator present? Key difference is how they deal with fluctuating power Do generators produce clean electricity? No!

Ambulatory environment No generator Less critical loads

Hospital environment Generator present Extremely critical loads


Is my UPS sized correctly? • Understand what the UPS nameplate means – UPS typically sized in VA (volt-amperes) – AC watts = volts x amps x power factor UPS Name Plate

Power Factor

AC Watts Available

1000 VA

.7

700

1000 VA

.75

750

1000 VA

.9

900

– If you think your 1,000 VA UPS can support 1000 watts of computer equipment, you’re wrong – Know the power factor of different UPS models

• Battery run time at different capacities


Focus on hospital network closet UPS • Dozens of closets = dozens of UPS – Difficult to maintain, high battery management – When loads grow, add more UPS – Likely redundant UPS

• Distributed UPS Strategy – One small UPS in every closet – Ex Five 8 kVA UPS Utility

Distribution

Distributed: Typical UPS strategy in hospital network closets

UPS

Network Closet

UPS

Network Closet

UPS

Network Closet

UPS

Network Closet

UPS

Network Closet


Best practice: Centralized UPS • Centralized UPS Strategy – One large UPS covering multiple closets – Ex One 40 kVA UPS (instead of five 8 kVA) – If UPS is initially over sized, easy to add loads • Instead of a 40 kVA UPS, install a 80 kVA UPS

Reference Chart: Distributed

Network Closet Network Closet

Utility

UPS

Distribution

Network Closet Network Closet

Centralized: Best practice among new build and high IT growth hospitals

Network Closet


Distributed vs. centralized

Disadvantage

Advantages

Distributed

Centralized

• • • • •

Easier capital appropriation Smaller individual footprint Easy to install Easy to relocate Lower perceived cost

• • • • • •

Greater energy efficiency Single system to service Frees up rack / room space Sized for future kVA requirements Lower UPS capital cost Lower UPS operating cost

• • • • •

Utilizes vital rack space • Equipment room needed Higher failure rate • Electrical contractor for installation Lower energy efficiency • Up front capital allocation Individual batteries to service Aggregate cost of total UPS higher

TCO for centralized is 25% to 35% less than distributed


Precision Cooling Fundamentals • American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) – Recommends inlet temperature range of 64 to 80 degrees F – Humidity level (dew point) should fall within 42 to 59 degrees F

• 2008 change: was 68-77 degrees and 40%-50% RH

• Quick hits: – Inlet temperature, don’t go by a wall reading – Higher temps = more equipment fan use – 72 degrees is the norm, with 45% RH (data center avg. closets run warmer) • Most IT equipment has an upper operating temp of 95 - 100 degrees  

What is precision cooling? When do I need precision cooling?


Why traditional building A/C won’t cut it Comfort Cooling

Precision Cooling

Designed for critical electronic Designed for people equipment • 2500 hrs / year operation • 8760 hrs / year operation • Allow for a large range of (24 hours / 365 days) fluctuations in temperature and humidity • Microprocessor control of temperature and humidity ratios • High cost to operate • Energy efficient technology


When do I need precision cooling? • • • •

Too warm to work in comfortably Switches / servers failing (too late!) Over 1000 watts of heat It all depends… – Room size, amount of IT – Existing air exchanges

• Heat is a major problem in ambulatory network closets – Switch produces 1000 watts of heat, but what else is in the room? – Possibly servers and storage for local EMR – Building A/C turns off at night and in winter


Precision cooling Air cooled – most common solution • Heat will need to be rejected – Outdoor condenser • Other Options: Water, Glycol, Chilled Water 

Cooling Best Practices – Save space, use overhead – Ceiling units not install directly above equipment – Are Cooling units on emergency power? – At least have a plan, think about supply lines, install ducting today

Overhead 3.5 kW to 28 kW

Integrated Rack 2 kW to 14 kW


More best practices • Physical security – HIPAA: “safeguard equipment from unauthorized physical access, tampering and theft” – Box fan in the open door way…

No cooling = Open door = Security risk – Lack of cooling results in possible HIPAA violation – Solutions: Cooling and rack with a locking door


More best practices • Remote monitoring – Hospital systems have dozens of remote offices • IT Staff not physically on site

– Infrastructure monitoring: power and environmental – Web interface using HTTP and SNMP support – Provides alarm notifications via email and text messaging – Address issues before they take the network down


More best practices • Consult with experts – Contractor, Value Added Reseller, IT Integrator – 85% of hospitals had to upgrade their power and cooling within one year of an IT implementation • 40% upgraded after the HW & SW were implemented – If your IT vendor isn’t bringing up power and cooling, ask why • Complicated, unfamiliar, expensive • Look for a VAR who proposes power and cooling • VARs: become a true solution provider


More best practices • Have everyone at the table – Who “owns” the closet?

• IT, network services, facilities? – Who maintains it?

• Decision maker buying twenty UPS units may not be the guy who has to check batteries and temperatures

– Decisions impacting the network closet should incorporate all players


Critical questions to ask • Have I considered the need for power and cooling? – What is my current IT growth plan? – What can my existing IT Infrastructure support

• Is my IT load on the generator? – Which UPS is best: Double conversion or line interactive? – How much battery do I need?

• If distributed UPS, can I centralize? – If distributed (even remotely), can I monitor?

• Do I need cooling? – What about in 2 years?

• Is my cooling on emergency power? – How long can I operate without cooling my IT?


Summary • • • •

Network closet is the link to patient data IT availability is potentially life critical Power and cooling solutions protect and ensure uptime Consult with the experts, follow best practices

UPS

Cooling

IT Availability

Power and cooling solutions prevent: • • • • •

Lost patient data / missing images Patients and staff waiting for IT reboot Hospital staff dissatisfaction / reluctance to IT Equipment damage from heat Unauthorized equipment access


Q&A

Dan Draper Manager, Healthcare Industry Liebert Products


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.