Daylighting Portfolio

Page 1

Daylighting TOOLS IN LEARNING ESTEFANIA SANTACRUZ



Daylight Source Qualities PHYSICAL MODEL, OBSERVATION

Cybernarium West Faรงade Analysis PHSYICAL MODEL, SUNDIAL, HELIODON, LIGHT METER, PHOTOSPHERE

Glare Analysis LIGHT METER, PHOTOSPHERE, HDR SCOPE

LakeFlato Accion LEED Report ECOTECT, RADIANCE, DAYSIM



Daylight Source Qualities PHYSICAL MODEL, OBSERVATION




Cybernarium West Faรงade Analysis PHSYICAL MODEL, SUNDIAL, HELIODON, LIGHT METER, PHOTOSPHERE


CYBERNARIUM BRYAN, TX




OFFICE SPACE


WEST FAÇADE ANALYSIS 10:00 A.M. JUNE 21

PHYSICAL MODEL, PHOTOSPHERE, LIGHT METER


WEST FAÇADE ANALYSIS 2:00 P.M. JUNE 21

PHYSICAL MODEL, PHOTOSPHERE, LIGHT METER


WEST FAÇADE ANALYSIS 5:00 P.M. JUNE 21

PHYSICAL MODEL, PHOTOSPHERE, LIGHT METER


WEST FAÇADE ANALYSIS

SUNDIAL VS. HELIODON


WEST FAÇADE ANALYSIS

SUNDIAL VS. HELIODON


Glare Analysis LIGHT METER, PHOTOSPHERE, HDR SCOPE


IN ACTION! GLARE ANALYSIS MEMORIAL STUDENT CENTER TEXAS A&M UNIVERSITY


PHOTOSPHERE 1.4 1.39e+03 cd/m2 1 983 cd/m2 4.8 7.9 4.69e+03 cd/m2 7.79e+03 cd/m2

HDR

False Color


HDR SCOPE

dgp,dgi,ugr,vcp,cgi,Lveil: 0.279939 21.646196 25.297592 35.107758 29.081692 108.315483


PHOTOSPHERE

2.2 3.65e+03 cd/m2 3.3 5.42+03 cd/m2

3.14

1 1.64e+03 cd/m2

HDR

5.15e+03 cd/m2

False Color


HDR SCOPE

dgp,dgi,ugr,vcp,cgi,Lveil: 0.264675 20.319077 24.135490 46.264282 27.705086 77.381180


Space

DGP

DGI

UGR

VCP

CGI

Hall of Honor

0.264632

22.030331

26.896809

29.285284

28.980310

Stairway

0.279939

21.646196

25.297592

35.107758

29.081692

Red Couches

0.264675

20.319077

24.135490

46.264282

27.705086

Red Hallway

0.230131

18.625053

21.703674

66.664009

24.340231

Rev’s

0.293982

23.129681

28.112429

24.895445

31.565866

Small Table

0.257263

19.206589

22.895218

47.157619

26.490305

RESULTS FROM EVALGLARE-HDRSCOPE


Space

Yahaira

Estefania

Yesenia

Hall of Honor

Red

Orange

Yellow

Stairway

Yellow

Red

Orange

Red Couches

Green

Orange

Yellow

Red Hallway

Orange

Yellow

Red

Rev’s

Red

Red

Orange

Small Table

Orange

Green

Yellow

RESULTS FROM EVALGLARE-HDRSCOPE


LakeFlato Accion LEED 3.0 Report ECOTECT, RADIANCE, DAYSIM


LAKEFLATO’S ACCION TEXAS SAN ANTONIO, TX

RENDERING BY LAKEFLATO


LAKEFLATO’S ACCION TEXAS SAN ANTONIO, TX Objective: To evaluate the daylighting conditions of the new headquarters of Accion Texas in San Antonio using LEED 3.0 (2009) Credits 8.1 & 8.2 Credits. LEED 3.0 8.1 requirements are to demonstrate that 75% or more of all regularly occupied spaces achieve daylight illuminance levels at a minimum of 25 fc (269 lux) and a maximum of 500 fc (5381 lux) in a clear sky condition on September 21 9:00 am and 3:00 pm. Any areas above or below this range will not comply with the LEED requirements. 8.2 requirements are to achieve a direct line of sight to the outdoor environment through glazing between 30 and 90 inches above the finish floor for all occupants in 90% of the spaces. Objective of these credits is to provide occupants with a connection between the interior and exterior spaces in a building through the use of daylight in regularly occupied spaces.

RENDERING BY LAKEFLATO


PROJECT DESCRIPTION The new headquarters for the national non-profit micro-lender Accion Texas, are being designed by LakeFlato Architects. The project consists of 13,580 sq. ft. of office space. In addition, a separate 1500 sq. ft will serve as accessory area for meetings and community-centered activities. The office space and accessory area are to include spaces for: Lobby/reception Administration area Offices

Meeting rooms Staff kitchen/dining area Storage rooms/server room Restrooms The additional building for the project is a 2000 sq. ft incubator. The overall conditioned space is 17,080 sq. ft. Project address is: 2015 W. Martin San Antonio, TX 78207

RENDERING BY LAKEFLATO




GLAZING PROPERTIES TYPE

SHGC

U-VALUE

REFLECTANCE

GL-1

VISIBLE TRANSMITTANCE .40

.22

GL-2

.48

.24

.16 OUTDOOR .15 INDOOR .33

GL-3

.70

.38

.26 SUMMER DAY .29 WINTER NIGHT .27 SUMMER DAY .29 WINTER NIGHT .29

.11

REFLECTANCE OF MATERIALS Walls 0.7 Ceiling 0.75 Floor 0.3 Door 0.4 Roof 0.5 Cistern Tank 0.48



ECOTECT MODEL


ECOTECT MODEL


REGULARLY OCCUPIED SPACES- ACCESSORY SPACE


RADIANCE GRID RESULTS ACCESSORY SPACE 9:00 A.M.

BELOW 269 LUX TIME ON SEPTEMBER 21 9:00 AM 3:00 PM

TOTAL # SENSORS 936 936

ABOVE 5381 LUX SENSORS BELOW 269 LUX 0 0

SENSORS ABOVE 5381 LUX 152 1 TOTAL

SENSORS OUT OF LEED RANGE 152 or 16.2% 1 or 0% 8.1%

SENSORS WITHIN LEED RANGE 784 or 83.7% 935 or 99.9% 91.8%


RADIANCE GRID RESULTS ACCESSORY SPACE 3:00 P.M.

BELOW 269 LUX TIME ON SEPTEMBER 21 9:00 AM 3:00 PM

TOTAL # SENSORS 936 936

ABOVE 5381 LUX SENSORS BELOW 269 LUX 0 0

SENSORS ABOVE 5381 LUX 152 1 TOTAL

SENSORS OUT OF LEED RANGE 152 or 16.2% 1 or 0% 8.1%

SENSORS WITHIN LEED RANGE 784 or 83.7% 935 or 99.9% 91.8%


DAYSIM SIMULATION REPORT ACCESSORY SPACE


DAYSIM SIMULATION-DAYLIGHT AUTONOMY ACCESSORY SPACE


DAYSIM SIMULATION-USEFUL DAYLIGHT INDEX ACCESSORY SPACE


LEED 8.2 CREDITS ACCESSORY SPACE


RADIANCE RENDER ACCESSORY SPACE EAST WALL 9:00 A.M.


RADIANCE RENDER ACCESSORY SPACE SOUTH WALL 3:00 P.M.


CONLUSIONS AND RECOMMENDATIONS

ACCESSORY SPACE • Provide adequate shading device in the east wall of the building. Vertical shading fins could be a solution to this problem. • Recommendations in order to enhance the daylighting levels in the northwestern corner would be to lower the skylights in the north wall.


OFFICE SPACE • Place an interior storefront/glazing wall between the Breakroom and Open Office space that provides a view between the spaces and would allow for shared views/daylighting between the spaces. Another possibility would be to open up a small or high window towards the west wall with adequate shading strategies for west facades. • Recommendations for the 8.2 Credits for the Administration space would be to open up a small window towards the north façade that would allow for views towards the exterior and would also provide higher daylighting levels in the space. • Recommendations for the Large Meeting Room would be to provide adequate shading devices in the south windows in order to avoid the possibility of glare on September 21 at 3:00 p.m.

INCUBATOR SPACE • The Incubator space is very uniformly lit and daylighting levels appear to be evenly distributed within the space. • Recommendations for this space would be to adequately provide shading devices for the south windows.


LEED 8.1 CREDITS TOTAL For the Accessory, Office Space and Incubator: The total percentage of illuminance levels that achieve LEED compliance is 95%. The total percentage of illuminance levels that DO NOT achieve LEED compliance is 5%

Accessory

Office Space

Incubator

TIME ON SEPTEMBER 21

TOTAL # SENSORS

SENSORS BELOW 269 LUX

SENSORS ABOVE 5381 LUX

SENSORS OUT OF LEED RANGE

SENSORS WITHIN LEED RANGE

9:00 AM

936

0

152

152 or 16.2%

784 or 83.7%

3:00 PM

936

0

1

1 or 0%

935 or 99.9%

TOTAL

8.1%

91.8%

SENSORS BELOW 269 LUX 23 76

SENSORS ABOVE 5381 LUX 5 12 TOTAL

SENSORS OUT OF LEED RANGE 28 or 2.8% 88 or 8.9% 5.8%

SENSORS WITHIN LEED RANGE 950 or 97% 890 or 91% 94%

SENSORS BELOW 269 LUX 0 0

SENSORS ABOVE 5381 LUX 10 3

SENSORS OUT OF LEED RANGE 10 or 1.1% 3 or 0.3%

SENSORS WITHIN LEED RANGE 910 or 9.9% 917 or 99.6%

TOTAL

0.7%

99.25%

TIME ON SEPTEMBER 21 9:00 AM 3:00 PM

TOTAL # SENSORS

TIME ON SEPTEMBER 21 9:00 AM 3:00 PM

TOTAL # SENSORS

978 978

920 920