Low Voltage Relay Card L U T R O N
S P E C I F I C A T I O N
HW-LVOC-8
S U B M I T T A L
Job Name
Job Number
Location
Zones Controlled
Model No. HW-LVOC-8 Relay No.
Description
Latching or Momentary
Load
1
Low Voltage Relay Card
2 3 4 5 6 7 8
Removable Terminal Blocks 1
2
3
4
5
6
Manual Switches 7
8
1
2
3
4
5
6
7
Terminal Blocks handle 8 Remote Power Modules (RPMs), with capacity of 4 Zones Per Module
8
DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L
N N N N N DL 1 DL 2 DL 3 DL 4
L
RPM Module Locations (8 Maximum Per Panel)
N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N
Ribbon Cable Connector C
DL 1 DL 2 DL 3 DL 4
H
NC NO
N N N N N L L N N
Typical of 8 contacts
Specifications
Maximum Contact Rating
0.4A @ 30VAC 30 VDC 0.1A @ 30VAC 0.3A @ 30VDC
Resistive Inductive Inductive
Function
The HomeWorks Low Voltage Relay Card (HW-LVOC-8) can be used to control external equipment via contact closures. Typical applications include motor controllers, audio, and video controllers. Each relay card supports 8, form C, dry contact
outputs. It is mounted to the chassis of an HW-MA-8 Microprocessor Unit. Master Keypad buttons can be programmed to use outputs as latching or momentary with selectable time durations of .75, 1.5, or 2.1 seconds.
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036, USA 7/98 P/N 362-818/A4
For additional submittal sheets, call our Hotline and Fax-on-Demand Service at 1-800-523-9466, or visit Lutron’s Web site at http://www.lutron.com/resi
Remote Power Panel (model shown HW-RPM8/32-230CE)
Overview of HomeWorks Integrated System Preferred Feed and Load Wiring Entry
DL 1 DL 2 DL 3 DL 4
L
Terminal Blocks handle 8 Remote Power Modules (RPMs), with capacity of 4 Zones Per Module
N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L
N N N N N DL 1 DL 2 DL 3 DL 4
L
RPM Module Locations (8 Maximum Per Panel)
Master Keypads - 32 keypads maximum with 16 unique addresses possible
N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
L N N N N N DL 1 DL 2 DL 3 DL 4
H N N N N N L L
Master keypads can select pre-programmed lighting scenes, control pathways of light, raise or lower lights, and activate motor driven accessories
N N
HW-LVOC-8 Low-Voltage Relay Card Location
GRAFIK Eye System - Up to 8 GRAFIK Eye 3100 series controls per panel, with a maximum of 15 accessory controls
HW-MA-8 Microprocessor Assembly Location Alternate Load Wiring Entries To next panel (Max. 8 Panels)
Interpanel Link
Control Wiring Entry (Class 2, PELV)
Installation
Remove HW-LVOC-8 from its packing while observing cautionary handling practices. Touch fingers to earth-grounded rough-in panel. Place the HW-LVOC-8 into the mounting channel of the microprocessor assembly. Place one edge of the panel into a channel and push the other edge of the panel until it snaps into the other mounting channel.
Warranty Lutron will, at its option, repair or replace any control that is defective in materials or manufacture within two years after the purchase. This warranty is in lieu of any other warranties, express or implied, and the implied warranty of merchantability is limited to two years from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or improper wiring or insulation. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, or limitations on how long an implied warranty may last, so the above limitations and exclusions may not apply to you. Printed in U.S.A. Š 1998 Lutron Electronics Co., Inc.