4000 Series In­staller’s Guide

Page 1

English

4000 Series In­stall­er’s Guide Control Unit Mod­els 4100 and 4500

Español

®

PLEASE READ LUTRON

1 1 11 12 12 13 13 14

Section 5: Using the GRAFIK Eye® Control Unit Selecting Scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Temporarily Adjusting Light Levels and Shade Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Control Directory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Contact Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

This installer’s guide explains how to install and program a GRAFIK Eye 4000 Series control unit. Use this guide in conjunction with installation instructions supplied separately with other GRAFIK Eye 4000 Series products.

R

LUTRON-Quality Systems Reg­is­tered to ISO 9001

Italiano

Section 4: Programming a GRAFIK Eye® Control Unit Control Unit Buttons and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Enter and Exit Setup Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Address Each GRAFIK Eye Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Identify the Load Type for Each Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Program Scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Program Scenes 1 through 16 (Setup Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Select the Save Mode You Want to Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 16- and 24-Zone GRX Control Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Chinese Português

Section 3: Programming the Circuit Selector Circuit Selector Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Normal/Emergency Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assign Load Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Address the Circuit Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assign Primary Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Low or High End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assign Link Hierarchy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Français

Section 2: Installing a GRAFIK Eye® Control Unit Step 1: Turn the Power OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Step 2: Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Step 3: Mount the Wallbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Step 4: Connect PELV (Class 2: USA) Cable to the Control Unit . . . . . . . . . . . . . . . . . . . . . . 7 Step 5: Mount the Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Step 6: Connect the Wallstations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Step 7: Connect Other Accessories — Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Step 8: Connect Multiple Control Units — Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Special Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Activate the GRAFIK Eye Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Activate the Wallstations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Check System Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Deutsch

Section 1: Introduction GRAFIK Eye® 4000 Series Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 System Communications and Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3


Section 1:

Introduction This section of the installer’s guide introduces the GRAFIK Eye® 4000 Series lighting system and control unit, and provides an overview of a panel-based system. This section also describes system communications and capacities. Read this Introduction carefully before proceeding to the installation instructions beginning on page 4.

GRAFIK Eye® 4000 Series Control Unit

• • • • • • •

• • • •

The GRAFIK Eye is part of a lighting control system that enables you to create customized scenes and control lighting and shade zones. Lighting types are set using the circuit selector and controlled by a system’s panel(s). The control unit is the centerpiece of the lighting control system. The control unit provides: Setup of lighting and shade control scenes using buttons on the control unit. Pushbutton recall of four preset scenes, plus OFF. 12 additional scenes stored in the control unit, which are accessible via optional wallstations and other control devices. Control of 2, 3, 4, 6, 8, 16, or 24 zones. Smooth light level fading between scenes. Lockout options to prevent accidental changes. A built-in infrared receiver for operation with an optional remote control. All of this can be accomplished on a single control unit. Up to 8 control units can be connected together along with wallstations, sensors, and other control interfaces to enlarge the system and add additional control functions. Additional features available with a 4500 model are accessed through PC control and include: Lighting level increments of 1% Virtual control through LiaisonTM software Shade control through RS232 and/or Ethernet interfaces Scheduling astronomic timeclock events (requires Lutron programming control interface) Hinged cover

Zone label Light level LED bar graph Zone raise/lower buttons

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

ZONE 6

FADE

Fade window   ( “S” for seconds,  “M” for minutes)

OVERRIDE

Master raise/lower buttons

ZONE M S MASTER

Infrared wireless  remote control receiver

Base

Scene 1 Scene 2 Scene 3 Scene 4 Off

LUTRON

Scene buttons

Scene indicator LEDs

Model Numbers and Ratings (all 24 V ) Model Number GRX-4102, GRX-4502 GRX-4103, GRX-4503 GRX-4104, GRX-4504 GRX-4106, GRX-4506 GRX-4108, GRX-4508 GRX-4116, GRX-4516 GRX-4124, GRX-4524 GRXSLD-4103 GRXSLD-4104 GRXSLD-4106 GRXSLD-4108

Zones Comments 2 3 4 6 8 16 No shade zones 24 No shade zones 3 Slider model; no shade zones 4 Slider model; no shade zones 6 Slider model; no shade zones 8 Slider model; no shade zones

2 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

Addresses on Link 1 1 1 1 1 2 (consecutive) 3 (consecutive) 1 1 1 1

R


Factory Presets Lutron ships each control unit with the following factory presets. For slider models, see the Addendum included with those control units. Setting

Factory Preset

Address Load type Scene 1 Scene 2 Scene 3 Scene 4 Scenes 5-16 OFF Fade times Fade time from OFF Save mode

Not addressed (A-) All zones set to incandescent 100% intensity for all zones 75% intensity for all zones 50% intensity for all zones 25% intensity for all zones 100% intensity for all zones All zones OFF 3 seconds between all scenes; 10-second fade time to OFF 4 seconds to any scene (not adjustable) Sd (save by default)

Note: Scene fade time affects lights but not shades; shades move immediately to their programmed level.

Accessories Depending on the size and requirements of the lighting system, control units can be configured to work with a variety of optional accessories, including: • Low-voltage wallstations. Wallstations, shade controllers, infrared (IR) sensors and receivers, and door-jamb controls. • Control interfaces. Contact closure devices, RS232 and Ethernet digital communications, and programming interface with astronomic timeclock (programmed using GRAFIK Eye LiaisonTM software). For part numbers and additional information on GRAFIK Eye 4000 Series accessories, visit www.lutron.com.

System Communications and Capacities PELV (Class 2: USA) cable can be used to connect GRAFIK Eye 4000 control units, wallstations, and other accessories. You can link up to 8 control units to control up to 64 zones, and add up to 16 wallstations and 8 shade controllers (SG-SVC) for a total of 32 control points. 16-zone control units count as 2 addresses and 2 control units, and 24-zone control units count as 3 addresses and 3 control units. Note that wallstations control scenes (which can include light and shade settings); shade controllers control only shades. 16- and 24-zone control units and slider models do not have shade zones.

PELV (Class 2: USA) Cables If your lighting system uses wallstations and/or multiple control units, PELV (Class 2: USA) wiring is needed to supply power and carry com­mu­ni­ca­tions be­tween the control units and the wallstations. PELV (Class 2: USA) wiring is also needed to connect other accessories. Use properly certified PELV (Class 2: USA) cable. Each twisted pair in the PELV (Class 2: USA) wiring link should consist of two stranded conductors and a drain/shield wire. • The pair of #12 AWG (2.5 mm2 ) is for the low-voltage power wiring. • The pair of #22 AWG (1.0 mm2 ) is for a data link (up to 2000 ft/610 m long). Note: Lutron offers a one-cable, low-voltage solution: P/N GRX-CBL-46L (non-plenum) or GRX-PCBL-46L (plenum). Check availability and applicable electrical codes in your area. In countries that abide by the IEC regulations, PELV is commonly referred to as Protective Extra-Low Voltage. A PELV cir­cuit is a grounded circuit in which the voltage cannot exceed 50 V or 120 V ripple-free. The power source must be supplied by a safety isolating transformer or equivalent. In Europe, acceptable types of cable include HAR certified cable with insulated cores enclosed in a sheath. This cable must bear the appropriate certification mark pertaining to national wiring rules for fixed installations. If certified cable with insulated cores enclosed in a sheath is used for the power cables, the PELV wiring can be any of the cables listed above.

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 3


Section 2:

Installing a GRAFIK Eye® Control Unit This section explains how to install a GRAFIK Eye control unit and make sure it is properly operating all connected loads.

Step 1: Turn the Power OFF CAUTION! Before continuing with the installation, make sure the power is turned OFF at the panel supplying power to the control unit. Do not perform any wiring with the power ON.

Step 2: Control Wiring Panel

Wallstation GRAFIK   Eye

Panel

Wallstation

GRAFIK   Control  Eye interface

GRAFIK   Eye

Control interface To other panels, GRAFIK Eye control units, wallstations, or control interfaces. Correct: Daisy chain OK

Incorrect: Branch or home run not acceptable

Control Link Specifications Total length of control link may be no more than 2000 feet (610 2000 ft (610 m) maximum m). This distance is based on proper shielding on the twisted 2 shielded pair, and on #12 AWG (2.5 mm ) wire on the wires to terminal 1 and terminal 2 of the control link. If unapproved cable or smaller wire is used, this limit is affected: Terminal 1 & 2 Wire Sizes Max. Control Link Length 2000 ft. (610 m)  #12 AWG (2.5 mm2) #14 AWG (1.5 mm2) 1400 ft. (425 m)  #16 AWG (1.0 mm2) 900 ft. (275 m)  #18 AWG (1.0 mm2) 600 ft. (180 m) Total number of control unit addresses = 8 maximum Note: GRX-4116/4516 has 2 addresses  GRX-4124/4524 has 3 addresses Total number of wallstation or control interface addresses = 16 maximum Total number of shade controller addresses = 8 maximum Notes: • Make wire connections inside the wallbox and panel or in a junction box (by others) within 8 ft. (2.4 m) of the terminal. • All control wiring is PELV (Class 2: USA). Do not place any of these wires in with line voltage (mains voltage) wiring. • The order of controls within the control wiring is not important.

PELV (Class 2: USA) Notice Wallstation circuits are classified as Class 2 circuits (U.S.A.) and PELV circuits (IEC). Unless otherwise specified, the voltages do not exceed 24 V . As Class 2 circuits, they comply with the requirements of NFPA 70. National Electrical Code (NEC®). As PELV circuits, they comply with the requirements of IEC 60364-4-41, VDE 0100 Part 410, BS7671:1992 and other equivalent standards. When installing and wiring to these wallstations, follow all applicable national and/or local wiring regulations. External circuits connected to input, output, RS232, DMX512, and other communication terminals of wallstations, must be supplied from a listed Class 2 source or comply with the requirements for PELV circuits, as applicable in your country.

4 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Link Wiring Detail: Link A (1 to 1, 2 to 2, 3 to 3, etc.) To additional control units, 2 #12 AWG (2.5 mm2) wallstations, panels, or from terminals 1 to 1, control interfaces and 2 to 2

4 3 2 1

Lutron cable   GRX-CBL-46L or equivalent

2 #22 AWG (1.0 mm2) twisted, shielded pair from terminals 3 to 3, and 4 to 4

SSA SSARET

3 4 3 4 OUT

Wallstation

2 1

IN

GRAFIK Eye control unit To additional single scene activators

SSA Control  (NTGRX-1S)

Drain/Shield:  keep short and isolated

Power panel

2 #12 AWG (2.5 mm2) 4 3 2 1

C

1 #18 AWG  (1.0 mm2) 1 2 3 4 D 5

C

Data B OK

Power

Drain Sense

MUX

Common

Notes: • Use the wire connector required by local code (those shown are common in the USA). • Connect the drain/shield to terminal ‘D’, if this terminal is available. The drain is a bare wire – care must be taken so that it does not touch ground (earth) or wallstation circuitry.

24VFW MUX

Data A OK

D

1 2 3 4 D 5

Link

Link

A B

C

Drain

Wallstation

1 #18 AWG (1.0 mm2)   5 to 5 (sense for panel to panel)

D

SELECT C IRCUIT 1 2 Circuit

Circuit selector in the panel

MUX

24 V

MUX

Common

Sense

1 2 3 4 D 5

C

Data B OK

1 2 3 4 D 5

AB C

MUX

Link Link

MUX

Power OK

Drain Sense

MUX

MUX

24VFW

Data A OK

Drain

Link A terminals

Common

D

Drain/Shield

Comm

A

MUX

B

1 #18 AWG (1.0 mm2)

Comm

1 #18 AWG (1.0 mm2)

MUX

2 #12 AWG (2.5 mm2)

D

SELECT CIRCUIT

1 2 Circuit

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 5


Link Wiring Detail: Link B (C to C, + to +, - to -) To additional control units, wallstations, panels, or control interfaces

Lutron cable GRX-CBL-46L or equivalent

SSA SSARET

2 1

3 4 3 4 OUT

IN

GRAFIK Eye control unit

Power panel

STAGEBOARD RECEPT ACL E

To panels where Link B controls circuits. A Lutron LT-1 (link terminator) should be used to terminate Link B at the last panel.

LT-1

NT-DMXJIN-WH

Typical Wiring: DMX to Link B (2Link™ only) Wires must be daisy chained and capped off C at both ends of Link B.

DMX512 Stageboard on Link B

Cable recommended by stageboard manufacturer or from Lutron as GRX-CBL-DMX250/500.

1

– 2 +

C 1

3 4

– 2

STAGEBOARD RECEPT ACLE

5

To next panel

1 2 3 4 D 5

C

+

D

3

4 Data B OK

Common (Pin 1) 1 2 3 4 D 5

C

2

Link B as   DMX-512

DMX Cable Type   Belden 9729/89729:            Lutron GRX-CBL-DMX-250/500:

Data B OK

Power OK

Link Link

AB

Comm

Drain Sense

24VFW

MUX

Common

MUX

Data A OK

Circuit selector in the panel

C   1 2 3 4 D From  5 Wire  Circuit Selector  SELECT CIRCUIT     (2) drain/shield  C  white  + Circuit black  –  black  No Connect  red  No Connect      drain/shield  C  white  +  black  –  green  No Connect  red No Connect

Drain

Circuit

DMX Cable Wiring Table

D

MUX

D 1

5

Drain

MUX

Comm

Link Link

AB C

SELECT CIRCUIT

DMX– (Pin 2)

DMX+ (Pin 3)

MUX

1 2 3 4 D 5

MUX

Power OK

Drain Sense

MUX

24VFW

MUX

Common

Data A OK

D 1 2

To DMX Jack  (Pin #)    C (1)  + (3)*  – (2)*  – (4)  + (5)    C (1)  + (3)*  – (2)*  – (4)  + (5)

*Wire in daisy-chain configuration as follows: C to C, + to +, and – to –.

6 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Step 3: Mount the Wallbox 1. Mount a standard U.S. wallbox on a dry, flat indoor surface that is accessible and allows for system programming and operation. See the table below for the recommended wallbox for each model. Use a minimum depth of 2 3/4 in. (68 mm), preferably 3 1/2 in. (87 mm). Allow at least 4 1/2 in. (110 mm) clearance above and below the faceplate to ensure proper heat dissipation. Allow 1 in. (25 mm) for faceplate overhang on all sides. Control Unit Model

Wallbox size

GRX-4102/4502 GRX-4103/4503 GRXSLD-4103/4104 GRX-4104/4504 GRX-4106/4506 GRX-4108/4508 GRX-4116/4516 GRX-4124/4524 GRXSLD-4106/4108

2-gang wallbox* 3-gang wallbox*

* You may substitute two single-gang wallboxes for a 2-gang wallbox, or three single-gang wallboxes for a 3-gang wallbox.   Single-gang wallbox (Lutron P/N 241218);   4-gang wallbox (Lutron P/N 241400).

4-gang wallbox

2. Pull the PELV (CLass 2: USA) wiring into the wallbox using the rearmost knockouts. This will provide the most clearance when mounting the control 3.5 in. unit. Use recommended cable as specified in “PELV (Class 2: USA) Cables” (87 mm) on page 3.

7.9 in. (200 mm)

3.75 in. (95 mm)

Step 4: Connect PELV (Class 2: USA) Cable to the Control Unit GRAFIK Eye 4000 series control units use PELV (Class 2: USA) wiring to supply power and carry com­mu­ni­ca­tions be­tween the panels, control units, and wallstations.

Important Wiring Information • Lutron requires that you connect (daisy-chain) con­trol units and wallstations with two twisted pairs for operation: One pair of #12 AWG (2.5 mm2 ) for the low-voltage power wiring, and one pair of #22 AWG (1.0 mm2 ) for a data link. • Use properly certified PELV (Class 2: USA) cable. For a description of recommended cable types, refer to   “PELV (Class 2: USA) Cables” on page 3. • Install in accordance with all local and national electrical codes. • The control unit’s low-voltage PELV (Class 2: USA) circuit is 24 V . To connect the PELV (Class 2: USA) wires to the control unit: 1. Strip 1 in. (25 mm) of insulation from the PELV (Class 2: USA) cable in the wallbox. 2. Strip 3/8 in. (9.5 mm) of insulation from each wire. 3. Connect the twisted pair for low-voltage power wiring to terminal 1 (common) and terminal 2 (24 V ) on the control unit. NOTE: You will daisy-chain this low-voltage power wiring to wallstations and/or other control units. Refer to pages 8 and 9. 4. Con­nect the twisted pair data link to terminal 3 (MUX) and terminal 4 (MUX) of the control unit. NOTE: You will daisy-chain this data link to wallstations and/or GRX-CBL-46L other control units. Refer to pages 8 and 9. 5. If shield­ed wire is used, connect the drain wires to each other or to ter­mi­nal D on the wallstation, if present. Do NOT connect drain wires to earth/ground. WARNING! Make sure no bare wire is ex­posed after making connections. The rec­om­mend­ed installation torque is 3.5 in.-lbs. (0.4 N•m) for PELV (Class 2: USA) con­nec­ tions.

R

PELV   (Class 2: USA)   cable 1.0 in. (25 mm)

3/8 in. (9.5 mm) Terminal 1 Terminal 2 Terminal 3 Terminal 4 Drain/daisy chain Emergency/daisy chain

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 7


Step 5: Mount the Control Unit 1. Mount the control unit in the wallbox as shown   using the four screws pro­vid­ed. 2. Reattach the cover and faceplate to the control unit   by push­ing in­ward at each corner.

Step 6: Connect the Wallstations If your lighting system uses wallstations, make the appropriate connections at the wallstation using PELV (Class 2: USA) cabling. NOTE: For procedures on how to install and address wallstations, refer to the separate instructions included with each device. Wallstations must be installed by a qualified electrician in Each terminal can accept   accordance with all local and national electrical codes. 2 #18 AWG (1.0 mm2) wires 1. Daisy-chain the PELV (Class 2: USA) twisted pair for low-voltage power Data link: wiring from the control unit to terminal 1 (common) and terminal 2 (24 V ). 4: MUX  3: MUX 2. Daisy-chain the PELV (Class 2: USA) twisted pair data link from the control unit to terminal 3 (MUX) and terminal 4 (MUX) on each wallstation. 4 3 WARNING! Make sure no bare wire is ex­posed after making 2 1 connections. The rec­om­mend­ed installation torque is 3.5 in.-lbs. (0.4 N•m) for PELV (Class 2: USA) con­nec­tions. PELV   (Class 2: USA)   power wiring:  2: 24 V   1: common

2 twisted pairs  #18 AWG   (1.0 mm2)

Control Unit Connected to Wallstations GRAFIK Eye  4000 con­trol unit SSA

CU WIRE ONLY

SSA RTN DO NOT USE

4 IN 3 IN 4 OUT 3 OUT

USA CLASS 2 IEC PELV

2 IN, OUT 1 IN, OUT

PELV (Class 2: USA) power wiring:  2: 24 V   1: common

DO NOT USE

Data link: 4: MUX  3: MUX From panel

4 3 2 1

Wallstation

4 3 2 1

Wallstation

4 3 2 1

Wallstation

Step 7: Connect Other Accessories — Optional If your lighting system uses accessories other than wallstations (shade controllers, control interfaces), make the connections at the accessory using the appropriate wiring. For procedures on how to install and connect accessories, refer to the separate instructions provided with each accessory.

Important Wiring Information • Accessories must be installed by a qualified electrician in accordance with all local and national electrical codes. • Use properly certified cable as described in the instructions shipped with the accessory.

8 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Step 8: Connect Multiple Control Units — Optional If your lighting system has multiple control units, connect them using PELV (Class 2: USA) cabling as described here. Daisy-chain the PELV (Class 2: USA) cabling to terminal 1, terminal 2, terminal 3, and terminal 4 on all control units and wallstations. WARNING! Make sure no bare wire is ex­posed after making connections. The rec­om­mend­ed installation torque is 3.5 in.-lbs. (0.4 N•m) for PELV (Class 2: USA) con­nec­tions.

System Maximums: Up to 8 Control Units and 16 Wallstations and 8 Shade Controllers Power panel

4 3 2 1

SSA

A1

CU WIRE ONLY

SSA

A3

SSA RTN DO NOT USE

1 IN, OUT DO NOT USE

USA CLASS 2 IEC PELV

4 3 2 1

4 3 2 1

4 3 2

3 1

2 IN, OUT 1 IN, OUT DO NOT USE 4 3 2 1

a

4 2

SSA RTN DO NOT USE

4 IN 3 IN 4 OUT 3 OUT

4 IN 3 IN 4 OUT 3 OUT

2 IN, OUT

USA CLASS 2 IEC PELV

CU WIRE ONLY

f 4 3 2

b

1

4 3 2

1

g

1 4 3 2 1

4 3 2 1

Total PELV (Class 2: USA) wir­ing length is 2000 ft. (610 m).

e

c

4 3 2 1

4 3 2

DO NOT USE SSA RTN SSA

4 IN 3 IN 4 OUT 3 OUT

A4

CU WIRE ONLY

USA CLASS 2 IEC PELV

DO NOT USE 1 IN, OUT 2 IN, OUT DO NOT USE SSA RTN

CU WIRE ONLY

SSA

2

2 IN, OUT

3

1 IN, OUT

d 4

DO NOT USE

4 3 2 1

USA CLASS 2 IEC PELV

A2

4 IN 3 IN 4 OUT 3 OUT

1

1

Special Mounting Considerations Wallbox Mounting and Spacing When mounting multiple control units or interface devices, be sure to follow spacing requirements to ensure proper operation. • All control units MUST be mount­ed in a standard U.S. wallbox. (For mounting procedures, refer to page 7.) • Allow 1 in. (25 mm) for faceplate overhang on all sides. 4.5 in. (110 mm) minimum for cover

Limited by physical size of unit.   Must be able to open front cover.

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 9


Activate the GRAFIK Eye® Control Unit

C

Data B OK

1 2 3 4 D 5

AB C

MUX

Link Link

Comm

Power OK

Drain Sense

MUX

24VFW

Common

MUX

Data A OK

Power OK LED

D

Drain

1 2 3 4 D 5

MUX

Once all controls are installed and wiring verified, turn the power to the control unit back on. Check that the Power OK LED at the top of the circuit selector is ON. If the Power OK LED is OFF, turn OFF the control circuit breaker, check for a short between wires 1 and 2, or 2 and ground. Turn the power ON for all panels.

D

SELECT CIRCUIT

1 2 Circuit

Activate the Wallstations

• • • • •

To perform this double-check, refer to page 16 and program one of your GRAFIK Eye control units to ‘A1’. Push scene buttons on wallstations. All GRX-4000 series control units and wallstations should act in parallel (e.g,. pressing scene 1 on a wallstation will select scene 1 on all control units, pressing a master raise button will raise all zones). Notes Lights will not dim at this point. NTGRX-4PS, and NTGRX-4M will be inactive until control setup steps are completed. GRX-AV will be active only if set to affect scenes 1-4 and OFF   (switches 5, 6, 7, and 8 all UP). NTGRX-2B-SL will be active only if set to affect scene 1 and OFF (switches 5, 6, and 7 all UP). Check for miswires if the controls do not act as described.

VIEW VALUE SELECT VALUE Link A

4

Push Value

SELECT VALUE DISPLAYED

LUTRON

Circuit Level

5

Load Type (See Instructions) GRX-4000 series control unit (6 zone unit shown) Zone Assignment w/ Circuit Schedule Zone Assignment w/ Zone CaptureTM Low-End Trim High-End Trim

Push

Address ('Ad' displayed)

Warning - Read instructions to set the Load Type. Instructions show more load types. Load Type Quick Reference: LUTRON

--- Unassigned

3-1 Neon / CC

1-1 Incandescent

4-1 Non-Dim

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

Wallstation (NTGRX-4S shown)

Check System Communication Until zones are assigned, all circuits will be controlled by the first GRX-4000 series control unit addressed to ‘A1’. Locate zone 1 control (referred to as A1-1 in the circuit selector) and use it to circuits are wired correctly. Note: All circuits will switch on and off only until the load type is in the next section.

3

Link B

LINK 1

LINK 2

(Non-Ess)

(Essential)

Normal

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

ZONE 6

FADE

OVERRIDE

ZONE M S MASTER

LUTRON

Emergency

zone of the of this ‘A1’ check that all programmed

A1-6 A1-5 A1-4 A1-3 A1-2 A1-1 First zone of GRX-4000 Series control unit ad­dressed ‘A1’

10 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Section 3:

Programming the Circuit Selector Before proceeding, you must have one or more of the following: preassigned setup, knowledge of how the system is to operate, plans and specifications from owner’s representative on how the system is to be set up, or owner or owner’s representative present.

Set Normal/Emergency Switch

C

Data B OK

1 2 3 4 D 5

MUX

Comm

Link Link

AB C

MUX

Power OK

Drain Sense

MUX

24VFW

Data A OK

D

Drain

1 2 3 4 D 5

MUX

There is a circuit selector in every lighting control panel. It is used to communicate with GRX-4000 Series control unit(s) or DMX512 stageboards – and then to tell the dimmers their intensity levels. It is also used to select Values for each circuit: • Circuit Level - allows a way to view the intensity being sent to the dimmer or manually take over control of the dimmer’s output. See description in the Troubleshooting section. • Load Type - to be changed to match the load to the Load Type value. NonDim 4 must be used if the Load is not dimmable. • Control and Zone Assigned - allows two ways of assigning a control and zone to a specific circuit. 1. ‘w/ Circuit Schedule’ allows a Control and Zone (such as ‘A2’,‘3’) to be directly entered into the Circuit Selector. 2. ‘w/ Zone Capture’ allows a Control and Zone to be ‘captured’ by the Circuit Selector by doing the following: A. Press and hold buttons 1 and 5 until the Select Value LED lights. B. Press button 5 repeatedly until the Zone Capture LED lights. The circuit will now flash. C. Use buttons 1 and 2 to choose the correct circuit to be assigned. D. Go to the GRX-4000 Series control unit to be assigned to this circuit. E. Select Scene 1. F. Identify the zone to be assigned to this circuit. G. Press the zone 6 button until all zone LEDs are off. H. Press the zone 5 button until the load starts tracking the zone intensity LEDs. I. Press the zone 6 button until all zone LEDs are off.  (Steps H. and I. must take less than 15 seconds or the circuit selector will not lock on the captured zone.) J. Go back to the Circuit Selector and the proper control and zone should be displayed. Repeat this process for any other circuits. K. Press and hold buttons 1 and 5 until the VIEW VALUE LED lights. • Low and High End trims - allows the circuit’s range limits to be adjusted. • The Value window will display the software revision level of the circuit selector 20 minutes after the last button press.

Data OK LED(s) blink when the circuit selector is properly receiving data

Power OK LED indicates whether   24 V is present from the PELV (Class 2: USA) transformer

Common

Circuit Selector Functions

D

SELECT CIRCUIT

1 2 Circuit

VIEW VALUE SELECT VALUE Link A

3

Link B

4 Value

SELECT VALUE DISPLAYED Circuit Level Load Type (See Instructions)

5

Zone Assignment w/ Circuit Schedule Zone Assignment w/ Zone CaptureTM Low-End Trim High-End Trim Address ('Ad' displayed) Warning - Read instructions to set the Load Type. Instructions show more load types. Load Type Quick Reference: --- Unassigned

3-1 Neon / CC

1-1 Incandescent

4-1 Non-Dim

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

SW6 LINK 1

LINK 2

(Non-Ess)

(Essential)

Emergency Note: This step is only performed if there are any panels with Emergency (Essential) lighting circuits on the job. Panels are shipped with switch 6 The circuit selector can also provide or (located at the base of each circuit selector) in the center position for normal receive a sense line depending on the operation (without any Emergency/Essential lighting circuits). When switch 6 location of switch 6 (SW6). is in its center position (as shipped), terminal 5 has no affect on the circuit SW6 Switch Settings selector operation. Normal   1. Identify a panel supplied with Normal (Non-Essential) power. Move its switch 6 (non-essential) to the left position. 2. For all the Emergency (Essential) lighting panels, move switch 6 to the right Normal   position. (as shipped) In this arrangement, the Emergency (Essential) Lighting panel will “sense” the Emergency   Normal (Non-Essential) panel’s power. When Normal (Non-Essential) power (essential) is removed, the Emergency (Essential) lighting will go to ‘ord’ override levels (factory set to 100%). Notes • If there is no Normal panel, contact Lutron Technical Support. • Override (‘ord’) Level is factory set to full output (100). If less than full output is needed, contact Lutron. • Loss of Normal (Non-Essential) power can be simulated by turning off all connected Normal (Non-Essential) panel’s control breaker. GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 11 Normal

R


Assign Load Types Assigning load types is done using the circuit selector located in each panel.

To view present load types: Press button 5 to step through the Value displays until Load Type LED lights. Use buttons 1 and 2 to view present load type of each circuit. Note that ‘ - - - ’ in the Value display means a load type is not assigned to the circuit. If 1 2 3 4 D 5 load types are already assigned, compare them to the circuit directory (if provided). If there areC no changes to be made, go to page 13, Assign Primary Zones. D

Load Type Display

Drain

Comm

MUX

MUX

24VFW

Drain Sense

MUX

MUX

Link Link

AB C

D

SELECT CIRCUIT

1

Steps A and F: Press and hold Buttons 1 and 5

2 Circuit

VIEW VALUE SELECT VALUE Link A

3

Link B

4 Value

1 2 3 4 D 5

C

D

SELECT VALUE DISPLAYED Circuit Level Load Type (See Instructions) Data A OK

5 Data B OK

Power OK

Drain

Comm

AB

MUX

Low-End Trim Link Link C 3 4 DTrim 1 2High-End 5 Address ('Ad' displayed) IRCUIT SELECT C

MUX

Drain Sense

24VFW

MUX

Zone Assignment w/ Circuit Schedule Zone Assignment w/ Zone CaptureTM MUX

A. Press and hold buttons 1 and 5 until SELECT VALUE LED blinks once per second. B. Press button 5 until the Load Type LED lights. C. Choose circuit number with buttons 1 and 2. D. Use buttons 3 or 4 to display the load type (see below) in Value window. E. Repeat steps C and D for each circuit. F. Press and hold buttons 1 and 5 until the VIEW VALUE LED lights.

Data B OK

Power OK

1 2 3 4 D 5

Common

To change load types:

Common

Data A OK

D

Warning - Read instructions to set the 1 Load Type. Instructions show more load types.

The load type is shown in the Value window. Use buttons 3 and 4 on the V V circuit selector to scroll through the choices and find the appropriate type. S V - - - Unassigned (All intensities except 0 = On) Value window 1 - 1 Incandescent, Tungsten S V D 2 - 1 Fluorescent: Lutron Hi-Lume FDB or Eco-10 2 - 2 Fluorescent: Lutron Tu-Wire® 2 - 3 Fluorescent: 0-10 V, with TVM module Hi-2 Baud Rate 2 - 4 Fluorescent: PWM, with TVM module 4 - 1 Non-Dim: All intensities except 0% = On   2 - 5 Fluorescent: Tridonic® DSI, with TVM (first on, last off) module 4 - 2 Non-Dim: Intensities above 60% = On,   2 - 6 Fluorescent: Tridonic® DSI (electronic off),   below 40% = Off (non-dim slider) with TVM module 4 - 3 Non-Dim: All intensities except 0% = On   2 - 7 DALI1, with TVM module (first on, last off) 2 - 8 Fluorescent: Tridonic® DSI (logarithmic 4 - 4 Non-Dim: All intensities except 0% = On   dimming curve), with TVM module (first on, last off) 2 - 9 DALI1 (logarithmic dimming curve),   with TVM module Hi-1 and Lo Baud Rates 2 - A Fluorescent: 10-0 V (10 V = 1%;   4 - 1 Non-Dim: 0-99% = Off;   0 V = 100%), with TVM module 100% = On (last on, first off) 3 - 1 Neon/Cold Cathode 4 - 2 Non-Dim: Intensities above 60% = On, 5 - 1 Electronic Low-Voltage below 40% = Off (non-dim slider) 6 - 1 Magnetic Low-Voltage 4 - 3 Non-dim: 0-99% = Off;   7 - 1 Fan 100% = On (last on, first off) 8 - 1 Motor 4 - 4 Non-Dim: 0% = Off, 0-1% = turn On, - - A Auto phase 100-99% = turn Off (first on, first off) 1 Intensity broadcasts only; individual ballast addressing not possible 2 Circuit 3-1 Neon / CC

Load Type Quick Reference: --- Unassigned

1-1 Incandescent

4-1 Non-Dim

IEW ALUE 2-1 Fluorescent Lutron Hi-lume FDB Ballast ELECT Lutron ALUETu-WireTM Ballast 2-2 Fluorescent R

Link A

3

Link B

4

Value

ELECT

ALUE

ISPLAYED

Circuit Level Load Type (See Instructions)

5

Zone Assignment w/ Circuit Schedule Zone Assignment w/ Zone CaptureTM

LINK 1

Low-End Trim LINK 2 High-End Trim (Non-Ess)

(Essential)

Address ('Ad'Normal displayed)

Emergency

Warning - Read instructions to set the Load Type. Instructions show more load types.

Load Type Quick Reference: --- Unassigned

3-1 Neon / CC

1-1 Incandescent

4-1 Non-Dim

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

(Non-Ess)

(Essential)

12 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

Link Link

Comm

Drain Sense

24VFW

MUX

MUX

Common

D

Data B OK

Power OK

1 2 3 4 D 5

AB C

D

SELECT CIRCUIT

1 2 Circuit

VIEW VALUE SELECT VALUE 1 2Link 3 A4 D 5

C

Link B

3

D

Steps A and D: Press and hold Buttons 1 and 5

4 Value

SELECT VALUE DISPLAYED Data A OK Power OK

Drain

MUX

Comm

Data B OK

5 MUX

Drain Sense

24VFW

Circuit Level Load Type (See Instructions) MUX

If you are using GRAFIK Liaison software, the circuit selector must be addressed to download information. A. To set or change the address, press and hold buttons 1 and 5 until the Select Value LED flashes once per second. B. Press button 5 on the circuit selector until “Ad” is displayed in the Circuit window. If the Value window displays an address other than ‘–’, the address has already been set (proceed to Step D). C. Use button 3 or 4 to assign an address (1-512) to the circuit selector. This address should match the address in the job drawing. D. Press and hold buttons 1 and 5 until the View Value LED lights. Notes • Mark addresses on a circuit directory for future reference. • If ‘LC’ is displayed in the circuit window, the circuit selector is locked out. Contact Lutron for assistance.

C

Data A OK

MUX

Address the Circuit Selector

1 2 3 4 D 5

Common

Warning! Failure to correctly assign load type may damage loads–especially certain electronic transformers, electronic ballasts, and motors. Verify with transformer or ballast manufacturer that product can be dimmed with phase control dimming before setting to any load type other than non-dim.

Emergency

Drain

Normal

MUX

LINK 2

MUX

LINK 1

Link Link Zone Assignment w/ Circuit Schedule w/ ZoneC CaptureTM D D 5 3 4Assignment 1 2Zone

AB

IRCUIT SELECT CTrim Low-End High-End Trim

1

Address ('Ad' displayed)

2

Warning - Read Circuit instructions to set the Load Type. Instructions show more load types.

VIEWQuick VALUE Load Type Reference: SELECT VALUE --- Unassigned

3-1 Neon / CC

1-1 Incandescent

4-1 Non-Dim

Link A 3 2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

Link B

4

Value

SELECT VALUE DISPLAYED Circuit Level Load Type (See Instructions)

Circuit window Assign address

5

Zone Assignment w/ Circuit Schedule Zone Assignment w/ Zone CaptureTM Low-End Trim High-End Trim

R


Assign Primary Zones

1 2 3 4 D 5

C

D

See page 25 for the Control Directory worksheets for recording zone assignments. A. Press and hold buttons 1 and 5 until the Select Value LED flashes once per 1 2S 3 4 C 5 A B second. Steps A and B. Press button 5 repeatedly until the Zone Assignment w/Circuit Schedule E: Press and V V S V LED lights. hold Buttons 1 and 5 C. Select the primary zone assignment. S V D For GRX 4000 Series: Press button 3 or 4 to select both control unit and zone assignment. Example: If the control desired is ad­dressed to ‘A2’ and 1 2 3 4 D 5 C the zone desired is the 3rd from the left, use buttons 3 and 4 to get ‘A23’ as a value for the appropriate circuit. For DMX512: (2Link only) Press button 3 or 4 to select zone assignment 1 2 3 4 5 AB (1-512). S C D. Use buttons 1 and 2 to change to the next circuit, then repeat Step C. Do this for all affected circuits. Record each circuit’s control and zone on a V V S V Circuit Directory. Value window E. Press and hold buttons 1 and 5 until the View Value LED lights. S V D Notes • The circuit selector’s display will go out automatically 20 minutes after the last button press. • More than one circuit can be assigned to the same zone. • Zone Capture™ is an alternate method for assigning zones. It is described on the opposite page. • 2Link only- The Link A and Link B LEDs located next to the Value window indicate which link is being assigned as per the hierarchy. To set the hierarchy, see page 15. Drain

Comm

MUX

MUX

Link Link

D

ELECT

Data B OK

Power OK

Drain Sense

24VFW

MUX

MUX

Common

Data A OK

C

D

IRCUIT

1 2

Circuit

IEW ALUE ELECT ALUE

Link A

3

Link B

4

Value

ALUE

ISPLAYED

Circuit Level Load Type (See Instructions)

5

Comm

Link Link

MUX

MUX

Drain Sense

Address ('Ad' displayed)

D

Data B OK

Power OK

MUX

24VFW

Low-End Trim Data A OK High-End Trim MUX

Common

Zone Assignment w/ Circuit Schedule Zone Assignment w/ Zone CaptureTM

Warning - Read instructions to set the Load Type. Instructions show more load types.

D

C

Load Type Quick Reference:

ELECT

IRCUIT

--- Unassigned

Drain

ELECT

D

3-1 Neon / CC

1 4-1 Non-Dim

1-1 Incandescent

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2 2-2 Fluorescent Lutron Tu-WireTM Ballast R

Circuit

IEW ALUE ELECT ALUE

Link A

3

Link B

4

Value

ELECT

ALUE

ISPLAYED

Circuit Level Load Type (See Instructions)

LINK 1

5

LINK 2 Assignment w/ Circuit Schedule Zone (Non-Ess) (Essential) Zone Assignment CaptureTM Normal w/ Zone Emergency

Low-End Trim High-End Trim

Address ('Ad' displayed)

Warning - Read instructions to set the Load Type. Instructions show more load types.

Load Type Quick Reference: --- Unassigned

3-1 Neon / CC

1-1 Incandescent

4-1 Non-Dim

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

Set Low or High End

LINK 1

LINK 2

(Non-Ess)

(Essential)

Normal

Emergency

Drain

MUX

Comm

MUX

Drain Sense

MUX

24VFW

MUX

Common

Note: Low end and high end light levels are set automatically when load type is assigned. This step is to be done if the default settings need to be changed. Warning! Do not reduce the low end or increase the high end on a fluorescent load type. This will decrease lamp life and may damage the ballasts. Do not increase the1 high end of neon/coldCcathode. This may 2 3 4 D 5 D overdrive the lamps and cause decreased tube life. To change the setting: Data A OK Data B OK Power OK A. Press and hold buttons 1 and 5 until the Select Value LED lights. Link Link B. Press button 5 repeatedly until the Low End Trim LED or the D 1 2 3 4 D 5 AB C High End Trim LED lights. SELECT CIRCUIT C. Use buttons 1 and 2 to go to the circuit that needs to be 1 changed. 2 Circuit D. Use buttons 3 and 4 to reset the trim as desired. The load Steps A and will go to the new setting while in this mode despite the VIEW VALUE F: Press and SELECT VALUE hold Buttons GRX control’s intensity. 1 and 5 Notes Link A 3 Link B 4 • Low end and high end ranges are limited to avoid Value overlapping. SELECT VALUE DISPLAYED • ‘1’ is the minimum low end and ‘99’ is the maximum high Circuit Level 5 Load Type (See Instructions) end. Zone Assignment w/ Circuit Schedule • ‘Value’ is a relative number. It is not a % intensity, but Zone Assignment w/ Zone Capture rather a reference point to help set other circuits, if desired. Low-End Trim Record the new trim setting on a Circuit Di­rec­to­ry so that it High-End Trim is documented. Address ('Ad' displayed) Read instructions E. Use buttons 1 and 2 to go to another circuit that needs to be changedWarning and -repeat Step toD.set the Load Type. Instructions show more load types. F. Press and hold buttons 1 and 5 until the VIEW VALUE LED lights. Load Type Quick Reference: --- Unassigned 3-1 Neon / CC Note: The circuit selector’s display will go out au­to­mat­i­cal­ly 20 minutes after the last 4-1 button press. Non-Dim 1-1 Incandescent TM

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 13


Assign Link Hierarchy (2LinkTM only)

1 2 3 4 D 5

C

D

Drain

MUX

Comm

MUX

Drain Sense

MUX

24VFW

MUX

Common

Link hierarchy is used only when there are two control links. Each circuit can be assigned to a hierarchy listed below (see job prints if predetermined). If you are not sure if you have a 2Link circuit selector, please call Lutron Data A OK Data B OK Power OK Technical Support. A. To view or assign the Link Hierarchy, press and hold Link Link buttons 2 and 5 until Select Value LED flashes twice D 1 2 3 4 D 5 AB C repeatedly. SELECT CIRCUIT B. Press button 5 until the Circuit Level LED lights. 1 C. Use buttons 1 and 2 to choose circuit number. 2 Circuit D. Use buttons 3 and 4 to assign the Link Hierarchy (see Step A:   Table for options). Press and VIEW VALUE SELECT VALUE hold Buttons • If Link Hierarchy A or b is selected, go to Step I. 2 and 5 Link A 3 • If Link Hierarchy A2 or b2 is selected, go to Step E. Link B 4 • If Link Hierarchy A1, b1, Ab1, or Ab2 is selected, go to Value Step G. SELECT VALUE DISPLAYED Circuit Level 5 E. Press button 5 until Load Type LED lights. Load Type (See Instructions) F. Select Zone X. Zone Assignment w/ Circuit Schedule 4000 Series on Secondary Link: Press button 3 or 4 to Zone Assignment w/ Zone Capture select both control unit and zone assignment. Example Low-End Trim High-End Trim - If the control desired is ad­dressed to ‘A2’ and the zone Address ('Ad' displayed) desired is the 3rd from the left, use buttons 3 and 4 to get Warning - Read instructions to set the Load ‘A23’ as a value for the appropriate circuit. Type. Instructions show more load types. Load Type Quick Reference: DMX512: Press button 3 or 4 to select zone assignment (1-512). --- Unassigned 3-1 Neon / CC G. Press button 5 until the Zone Assignment w/Circuit Schedule LED lights. 1-1 Incandescent 4-1 Non-Dim 2-1 Fluorescent Lutron Hi-lume FDB Ballast H. Select the Secondary zone assignment. 2-2 Fluorescent Lutron Tu-Wire Ballast 4000 Series on Secondary Link: Press button 3 or 4 to select both control unit and zone assignment. Example: If the control desired is ad­dressed to ‘A2’ and the zone desired is the 3rd from the left, use buttons 3 and 4 to get ‘A23’ as a value for the appropriate circuit. DMX512: Press button 3 or 4 to select zone assignment (1-512). Note: Primary Zone assignment is covered on page 13 of this guide; if primary link is changed to B, repeat those steps to update your system. I. Repeat steps C and D for each and every circuit to be changed. J. Press and hold buttons 1 and 5 until VIEW VALUE LED lights. (Non-Ess) (Essential) TM

R

TM

LINK 1

LINK 2

Normal

Code

Definition

A

Emergency

Link A only.

Primary Link A

Secondary Application Example Link None Circuit to follow Link A (standard operation).

b

Link B only.

b

None

Panel is shared by two links to save on panel costs.

A1

Link A unless Link B is present.

A

b

When the DMX-512 Stageboard is plugged in on Link B, listen to Link B. Return to Link A when the DMX-512 Stageboard is unplugged.

A2

Link A unless Link B is present and Zone X intensity on Link B is >50%.

A

b

DMX-512 Stageboard is plugged in on Link B, but does not take control until the light intensity of Zone X on Link B is above 50%.

b1

Link B unless Link A is present.

b

A

Redundant system. If Link A fails, circuits follow Link B.

b2

Link B unless Link A is present and Zone X intensity on Link A is >50%.

b

A

DMX-512 Stageboard plugged in on Link B, but is not given control until the light intensity of Zone X on Link A is below 50%.

Ab1

Highest intensity of the zone assignments of Link A and Link B.

A

b

Redundant system. If Link A fails, circuits follow Link B.

Ab2

Lowest intensity of the zone assignments of Link A and Link B.

A

b

Redundant system. If either Link A or Link B fails, the other will have higher intensities. Energy management.

14 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Section 4:

Programming a GRAFIK Eye® Control Unit NOTE: For slider units, this section is covered in the Addendum included with those units. This section identifies buttons and indicators on a GRAFIK Eye 4000 Series control unit. This section also explains how to enter setup mode, program a control unit, and select a save mode. Most programming operations are typically performed only once, when the control unit is installed. Other operations, such as selecting scenes and making temporary adjustments, are performed as needed to achieve the right lighting and shade effects. For systems with multiple control units, refer to page 17 for addressing. NOTE: Lutron ships each control unit with factory-set programming. For a description of the factory presets, refer to page 3.

Control Unit Buttons and Indicators

Hinged cover Zone label

ZONE 1

Light level/shade position  LED bar graph

ZONE 2

FADE

00

TEMPORARY

ZONES

MS

ZONE raise/lower buttons

MASTER

FADE window (if ‘S’ is lit, time is in seconds, if ‘M’ is lit, time is in minutes) TEMPORARY ZONES button MASTER raise/lower buttons FADE buttons Scene 1 Scene 2 Scene 3 Scene 4 OFF

Infrared wireless  remote control receiver

Faceplate

SCENE buttons

Scene indicator LEDs

Enter and Exit Setup Mode You must enter setup mode to access the programming functions on the control unit. To enter setup mode: Press and hold the SCENE 1 and OFF buttons for about three sec­onds, until the scene LEDs start cycling. When the buttons are released, the LEDs should continue to cycle. In setup mode, the FADE window displays the first setup code available for programming. To scroll up and down through the menu of setup codes, press the FADE 5 or 6buttons. To exit setup mode: Press and hold the SCENE 1 and OFF buttons for about three seconds, until the scene LEDs stop cycling. The control unit returns to normal operating mode.

The setup codes include: Code

Stands for

Sd

Save modes Select from several save options (page 21).

Sc

Scene Set up any of the scenes, including unaffected zones (page 20).

To enter (exit)   setup mode:

A-

Press and hold for about three seconds until LEDs cycle (stop cycling)

Address Identify control units for system communi­ca­tions (page 16).

LS

Load Select Identify load types (page 15).

Use 5 and 6 to scroll through setup codes  (LS is the first code to display)

ZONE 5

ZONE 6

FADE

TEMPORARY

ZONES MS

MASTER

Scene indicator LEDs

R

Description

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 15


Address Each GRAFIK Eye Control Unit Assign a unique system address (A1 through A8) to each control unit. See page 25 for the Control Directory worksheets for recording zone assignments. NOTE: A single control unit operating shade zones must also be addressed. Note: If using a 16 or 24 zone control unit, address these first.

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

ZONE 6

FADE

OVERRIDE

ZONE M S MASTER

Fade 5 Master 5 Step 1, 4:   Press and hold top and bottom buttons

LUTRON

GRX-4000 series control unit FADE

TEMPORAR Y

M S MASTER

LUTRON

Fade 5 Master 5 Step 1, 4:   Press and hold top and bottom buttons

GRXSLD control unit  (before installing faceplate and knobs)

To address each control unit: 1. Enter setup mode. Press and hold the top and bottom scene buttons for about three seconds, until the scene LEDs cycle. 2. Select A-. Press the FADE 5 button until A- (the factory default address) displays in the FADE window. 3. Assign a unique address. Press the MASTER 5 button once; the next “free” (unassigned) address automatically displays in the FADE window. This will be the control unit’s address. (If you are working on the first control unit in the lighting system, A1 will display.) 4. Exit setup mode. Press and hold the top and bottom scene buttons for about three seconds, until the LEDs stop cycling. 5. Repeat steps 1 through 4 for each control unit.

Data OK LED will be Off before addressing, then flash after ad­dress­ing (ap­prox­i­mate­ly once per second)

C

Data B OK

1 2 3 4 D 5

MUX

Comm

Link Link

AB C

MUX

Power OK

Drain Sense

MUX

24VFW

MUX

Data A OK

D

Drain

1 2 3 4 D 5

Common

As soon as a GRX-4000 series control unit is addressed, check that the Data OK LED begins to flash on the circuit selector. Flashing in­di­cates that the panel recognizes the communication from a GRX-4000 series control unit. Note: As soon as a GRX-4000 series control unit is addressed, wallstations will no longer have any affect on the GRX-4000 series control units. The wallstation communication will be reestablished later. Refer to the instructions that accompanied your wallstation(s).

D

SELECT CIRCUIT

1 2 Circuit

VIEW VALUE

SELECT VALUE LED Status Meaning Flashes once per second Control link data OK. Link A 3 Blank No data present on link or circuit breaker Link B is Off. 4 Value Flashes rapidly* Incorrect data detected. Possible causes: terminal 3 or 4 is not properly connected, or terminals 3 and 4 are miswired. SELECT VALUE DISPLAYED Circuit Level Load Type (See Instructions)

5

* The circuit selector may take up to 1 minute to properly identify a device on the link. During this time, a rapid Zone Assignment w/ Circuit Schedule flashing pattern may be observed. Zone Assignment w/ Zone CaptureTM

Low-End Trim High-End Trim Address ('Ad' displayed) Warning - Read instructions to set the Load Type. Instructions show more load types. Load Type Quick Reference: --- Unassigned

3-1 Neon / CC

1-1 Incandescent

4-1 Non-Dim

2-1 Fluorescent Lutron Hi-lume FDB Ballast 2-2 Fluorescent Lutron Tu-WireTM Ballast R

16 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Identify the Load Type for Each Zone In a GRAFIK 4000 Series system, lighting load types are set using the circuit selector in the panel. For other load types (AC motors, Sivoia QED shades, and projection screens), the load type must be specified at the control unit. For all loads, setting the load type at the control unit changes the LED display for that load type (see below). 3 Set the load type for each zone ZONE 5

FADE

ZONE 6

TEMPORARY

ZONES MS

MASTER

Zone LEDs

To set this load type:

Lighting Loads

To identify the load type for each zone: 1. Enter setup mode. Press and hold the SCENE 1 and OFF but­tons for about three seconds, until the scene LEDs cycle. 2 2. Check for LS in FADE window. LS is the first code to Check for LS display when you enter setup mode. In LS mode, ZONE LEDs turn on from top to bottom. 3. Set the load type for each zone. Press the ZONE 5 1 , 4 or 6 button until the ZONE LEDs match the load type Enter (exit) connected to each zone. Refer to the following table for setup mode each load type and its corresponding LEDs. 4. Exit setup mode. Press and hold the SCENE 1 and OFF but­tons for about three seconds, until scene LEDs stop cycling. In the sample 6-zone control unit shown here, Zone 5 is set for a dimmable load, and Zone 6 is set for non-dim (first on, first off).

Select this LED display

Important Notes

Dimmable Loads Use for any dimmable load. NOTE: This is the factory preset load type for each zone.

Non-Dim (last on, first off) Use non-dim for any lights to be switched ON and OFF only— not dimmed when fading between scenes. This load will be the last to switch on and the first to switch off.

Non-Dim (first on, first off) Use non-dim for any lights to be switched ON and OFF only— not dimmed when fading between scenes. This load will be the first to switch on and the first to switch off.

Motorized Shades AC Shades AC shades zones are factory set to unaffected in each scene. Blinking LED To program shade positions for a scene, refer to page 18. GRAFIK Eye 4000 control units must be addressed to control shades. To assign addresses, refer to page 16. Blinking   Sivoia QED Shades Sivoia QED shade zones are factory set to unaffected in each LED scene. To program shade positions for a scene, refer to page 18. GRAFIK Eye 4000 control units must be addressed to control shades. To assign addresses, refer to page 16.

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 17


Program Scenes Scenes are preset lighting levels, fade times, and shade positions stored in the control unit. (Note that AC shades can be programmed in a scene as only fully open, fully closed, or unaffected; Sivoia QEDTM shades can be programmed at any preset level or unaffected.) You can program up to 16 scenes, plus OFF (scene 0). Any time a scene button is pressed or input from an optional control interface is received, the system activates the desired scene.

Program Scenes 1 through 4 (Save Mode) If the control unit is set to the factory default Sd save mode (adjustments to zone settings are saved for the current scene), you can program scenes 1 through 4 without entering setup mode. NOTE: To program scenes using setup mode, refer to page 21. To select a save mode, refer to page 22. 2 Set the scene settings for each zone

ZONE 5

ZONE 6

FADE

TEMPORARY

ZONE ZONES MS

MASTER

Select a

1 scene

Scene 1 Scene 2 Scene 3 Scene 4 OFF

To program scenes 1 through 4 using save mode: 1. Select a scene. Press the SCENE button for the scene you want to program. 2. Set the scene settings for each zone. For lighting zones, press the ZONE 5 or 6 button to set the right visual intensity for this scene. For AC shade zones, press the ZONE 5 or 5 button until the ZONE LEDs match the right shade position for this scene. See the illustration below. For Sivoia QED shade zones, press the ZONE 5 or 6 button until the ZONE LEDs match the right shade position for this scene. See the illustration below. NOTE: To quickly set a shade zone to fully open or fully closed, press and hold the ZONE 5 or 6 button for about three seconds. For unaffected zones, press and hold the ZONE 6 button until all its LEDs go out and the middle three LEDs light (this may take up to 10 seconds). This zone’s settings will not be affected when this scene is selected. To reprogram an unaffected zone as affected, follow the steps above. Then press the ZONE 5 button for about three seconds until the middle three ZONE LEDs are no longer lit. Program the zone’s settings.

LED Displays for Programming Scene Settings Lighting Zones

AC Shade Zones

Sivoia QED Shade Zones

Off

Fully open

Fully open

Preset 1

On 50%

Fully closed

Fully closed

Preset 2

On 100%

Unaffected

Unaffected

Preset 3

Unaffected

Legend: LED lit LED off 18 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


ZONE 5

ZONE 6

FADE

TEMPORARY

ZONE ZONES MS

MASTER

3

Set scene’s   fade-in time

R

3. Set the fade-in time for this scene (does not apply to shades). Press the FADE 5 or 6 button to make the fadein time anything from 0–59 seconds or 1–60 minutes. The M and S indicators under the FADE window show whether fade is “M”inutes or “S”econds. To set the fade in minutes, press the FADE 5 button to scroll through 0–59 seconds to 1–60 minutes, then M lights. Fade is now expressed in min­utes. To get back to seconds, press the FADE 6 button until the win­dow shows “S”econds. 4. Repeat steps 1 through 3 to set up each of the remaining scenes. To set a Fade-to-OFF time, press the OFF scene button, then set the seconds or minutes to fade to OFF from this scene.

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 19


Program Scenes 1 through 16 (Setup Mode) You can program any scene using setup mode. If your lighting system requires more than 4 scenes, scenes 5 through 16 must be programmed using setup mode. NOTE: To program scenes 1 through 4 using Sd save mode, refer to page 18.

2 Select flashing Sc/1

ZONE 1

ZONE 2

FADE

TEMPORARY

ZONES MS

5 Set scene’s   fade-in time 3 Select scene

MASTER

1 , 6

4 Program lighting or shade scene settings for each zone

ZONE 5

ZONE 6

Enter (exit) setup mode

FADE

TEMPORARY

ZONES MS

MASTER

4 To set unaffected zone, press ZONE 6 twice and then hold un­til mid­ dle three LEDs light

20 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

To program scenes using setup mode: 1. Enter setup mode. Press and hold the SCENE 1 and OFF but­tons for about three seconds until the scene LEDs start cycling. 2. Select Sc (scene setup) by pressing the FADE 5 button twice. Sc and 1 (scene 1) will al­ter­nate­ly flash in the FADE win­dow. 3. Select scene. Press the MASTER 5 or 6 button to select the number of the scene to be programmed (1 through 15; 0 is the OFF scene). 4. Program scene settings for each zone. For lighting zones, press the ZONE 5 or 6 button to set the zone in­ten­si­ty. (GRX-3500 units will display exact per­cent­age light output; press again to adjust light levels in 1% increments.) For AC shade zones, press the ZONE 5 or 6 button until the ZONE LEDs match the right shade position for this scene. See the illustration on page 18. For Sivoia QED shade zones, press the ZONE 5 or 6 button until the ZONE LEDs match the right shade position for this scene. See the illustration on page 18. For unaffected zones, press and hold the ZONE 6 button until all its LEDs go out and the middle three LEDs light (this may take up to 10 seconds). This zone’s settings will not be affected when this scene is selected. To reprogram an unaffected zone as affected, follow the steps above. Then press the ZONE 5 button for about three seconds until the middle three ZONE LEDs are no longer lit. Program the zone’s settings. 5. Set the scene’s fade-in time. Press and hold the TEM­PO­RARY ZONES button. The current fadein time will be displayed. Adjust using the FADE 5 or 6 button while still holding the TEMPORARY ZONES button. (Fade time does not apply to shade zones.) 6. Exit setup mode. Press and hold the SCENE 1 and OFF but­tons until the LEDs stop cycling.

R


Select the Save Mode You Want to Use Save modes enable you to specify how buttons on the control unit work. For example, adjustments to a zone’s settings can be temporary or saved for the current scene. Buttons can also be disabled to prevent accidental changes. To select the save mode you want to use: 2 Select Sd 3 1. Enter setup mode. Press and hold the SCENE 1 and Select   OFF but­tons for about three seconds un­til scene LEDs save mode FADE TEMPORARY ZONE 5 ZONE 6 start cy­cling. 2. Select Sd. Press the FADE 5 button until Sd is dis­ ZONES played in the FADE win­dow. MS 3. Select save mode. Press the MASTER 5 or 6 MASTER button to scroll through the save modes and select one. Refer to the save mode descriptions in the table 1 , 4 below. Enter   4. Exit setup mode. Press and hold the SCENE 1 and (exit)  OFF but­tons until scene LEDs stop cycling. setup mode

Code

Stands for

Sd

Save by Default Changes to a zone’s intensity/shade position or fade time are saved for the current scene. To make temporary adjustments in Sd mode, refer to page 19. Typical user: Home theater owner.

Description

Sb

Save by Button TEMPORARY ZONES LED is nor­mal­ly ON and all in­ten­si­ty/shade position and fade chang­es are tem­po­rary unless the TEM­PO­RARY ZONES LED is turned OFF with the TEM­PO­RARY ZONES button. Typical user: Restaurant manager.

Sn

Save Never TEMPORARY ZONES LED is per­ma­nent­ly ON and cannot be turned OFF. In this mode, all in­ten­si­ty changes are temporary. Typical user: Lighting designer.

4S

Four Scenes Allows only the four SCENE but­tons, OFF button, IR receiver, and MASTER 5 or 6 buttons to operate. All other buttons on the control unit are disabled. Typical use: Rented meeting space.

bd

Button Disable All buttons on the control unit are dis­abled. IR receiver and wallstations are still functional. (Setup mode is still accessible by re­peat­ing Step 1.) Typical use: Public space.

16- and 24-Zone GRX Control Units The 16 and 24 zone GRAFIK Eye control units offer an expanded number of zones that can be controlled from a single wall station. The zone intensity LEDs on the GRX-4x16 or GRX-4x24 will display the light level of a set of eight zones at a time. Other sets of zones may be displayed and controlled by pressing the Zone Select Button.

Addressing The GRX-4x16 and the GRX-4x24 control units take multiple, consecutive addresses. The GRX-4x16 control unit takes up two consecutive addresses, and the GRX-4x24 control unit requires three. To ensure there are sufficient addresses available, any GRX-4x16 and/or GRX-4x24 control units in the system should be addressed first.

Assigning Zones When assigning zones use the chart below as a guide to see how zones are displayed on the Circuit Selector. The chart is for a 24-zone control unit, which uses three addresses. A 16-zone control unit uses only two addresses. Control Unit Addresses A1, A2, A3 A2, A3, A4 . . . . . . A6, A7, A8 R

Zones on Control Unit 1-8 9-16 17-24 1-8 9-16 17-24 . . . . 1-8 9-16 17-24

Circuit Selector Display A11-A18  A21-A28  A31-A38  A21-A28  A31-A38  A41-A48  .  .  .  .  A61-A68 A71-A78 A81-A88

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 21


Section 5:

Using the GRAFIK Eye® Control Unit NOTE: For slider units, this section is covered in the Addendum included with those units. This section describes how to use your GRAFIK Eye control unit, including selecting scenes, making temporary changes, and setting up system communications.

Selecting Scenes ZONE 5

FADE

ZONE 6

TEMPORARY

ZONES MS

MASTER

Scene 1 Scene 2 Scene 3 Scene 4 OFF

To select a scene, press the corresponding SCENE button on the control unit. The first button calls up scene 1; the sec­ond button, scene 2; and so on. The last button is the OFF scene. Scenes 1 through 4 (and OFF) can be selected on the control unit. Scenes 5 through 16 are se­lect­ed only by using wallstations and other optional control interfaces. (For installation and setup procedures, refer to the separate instructions provided with the wallstation or interface.)

Tem­po­rari­ly Adjusting Light Levels and Shade Positions You can temporarily adjust the light level or shade position of a zone. Temporary adjustments remain in effect only until a new scene selection occurs. NOTE: For control units set to bd save mode (refer to page 21), temporary adjustments can be made only using a wallstation, shade controller, or IR control.

ZONE 5

FADE

ZONE 6

TEMPORARY

ZONES

TEMPORARY LED TEMPORARY ZONES

MS

MASTER

MASTER  raise/lower SCENE buttons

ZONE  raise/lower  buttons

To temporarily adjust all lighting zones: 1. Press the appropriate scene button. 2. To raise or lower the intensity of all lighting zones in the scene, press the MASTER 5 or 6 button. (This will not affect shade zones or unaffected lighting zones.) To temporarily adjust a lighting zone: 1. Press the TEMPORARY ZONES button so the TEMPORARY LED above the TEMPORARY ZONES button lights. 2. Press the ZONE 5 or 6 button to adjust any zone’s light level.

LED Displays for Temporarily Changing Lighting Settings Lighting Level (%)

LED DIsplay

Lighting Level (%)

0

43-56

1-13

57-70

14-28

71-85

29-42

86-100

LED DIsplay

Legend: LED lit LED off 22 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


ZONE 5

FADE

ZONE 6

TEMPORARY

ZONES MS

To temporarily adjust a Sivoia QEDTM shade zone: 1. Press the TEMPORARY ZONES button so the TEMPORARY LED above the TEMPORARY ZONES button lights. 2. Press the ZONE 5 or 6 button to adjust any zone’s shade position to a preset position. 3. Use the raise/lower buttons on the wallstation that controls the shade zone to adjust it to a position that is not a preset.

TEMPORARY LED TEMPORARY ZONES

MASTER

To temporarily adjust an AC shade zone: 1. If fully open, press the ZONE 6 button. At the desired position, press the ZONE 6 button again to stop the AC shade. 2. If fully closed, press the ZONE 5 button. At the desired position, press the ZONE 5 button again to stop the AC shade.

ZONE  raise/lower  buttons

LED Displays for Temporarily Changing Shade Settings Scene Status/Control

AC Shade Zones Stopped

Raising

Sivoia QED Shade Zones Lowering

Stopped

Raising

Lowering

Affected/Control unit

Unaffected/Control unit

Affected/Wallstation

Unaffected/Wallstation Legend: LED lit LED off

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 23


Setting Up Com­mu­ni­ca­tions be­tween Two or More Con­trol Units Two-way com­mu­ni­ca­tions between control units enables you to set up lighting and shade ef­fects for more than one control unit. Depending on the room or facility, you can set up two-way communications so that all control units “talk” and “listen” to each other. In this configuration, selecting a scene at any one of the control units automatically ac­ti­vates the same scene in the others. Optionally, you set up some control units to share two-way communications while others do not. This configuration enables you to specify which control units activate the same scenes and which work independently. NOTE: The control units must be addressed (as described on page 17) be­fore setting up two-way communications.

A1 “talks” . . . LEDs cycle

. . . A2 “listens” LEDs flash

A1 “listens” . . . LEDs flash

To set up communications between control units: 1. Put A1 in setup mode. Press and hold the SCENE 1 and OFF buttons for about three sec­onds, until the LEDs cycle. 2. Identify the control units that should “listen” to A1 (A2 and up to six others). At each of the other control units, press and hold the SCENE 1 button for about three seconds until the LEDs flash in unison, show­ing that these control unit(s) are “listening” to A1 and will respond to its commands. To make a “listening” control unit not listen to A1: Put A1 in setup mode, then press the “listening” control unit’s OFF button until the LEDs stop flashing. 3. Take A1 out of setup mode. Press and hold the SCENE 1 and OFF buttons for about three seconds, until the LEDs on A1 and all other linked control units stop cycling. You have set up com­mu­ni­ca­tions in one direction between A1 and all “lis­ten­ ing” control units. 4. To complete the two-way communication, reverse the process described above. Put A2 in setup mode; then make A1 (and any oth­er control units) “listen”; then take A2 out of setup mode. Continue for each control unit.

. . . when A2 “talks” LEDs cycle

Example: Three Control Units All Communicating for 40-Zone Control

A1, A2, A3

Selecting a scene on A1 . . .

24 zones A4 8 zones

A5 8 zones

. . . Activates the same scene on A2 and A3.

All three control units are programmed to communicate with one another and act like a 16-zone control unit. Note that com­mu­ni­ca­tions are set up both ways among all control units: • A1 “talks” and “listens” to A2 and A3. • A2 “talks” and “listens” to A1 and A3. • A3 “talks” and “listens” to A1 and A2.

Setting Up Com­mu­ni­ca­tions be­tween Control Units, Wallstations, and Other Accessories Wallstations and other optional accessories (refer to page 3) must be set up to communicate with control units on the GRAFIK Eye link. For procedures on how to set up communications with wallstations and accessories, refer to the separate instructions included with the device.

24 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Control Directory Use this Directory as GRX-4000 series control units are addressed and zones are assigned. Keep this directory for job records and maintenance information.

Area: Zone: A1 1 A1 2 A1 3 A1 4 A1 5 A1 6 A1 7 A1 8

A1 LUTRON

Area: Zone: A2 1 A2 2 A2 3 A2 4 A2 5 A2 6 A2 7 A2 8

A2 LUTRON

Area: Zone: A3 1 A3 2 A3 3 A3 4 A3 5 A3 6 A3 7 A3 8

A3 LUTRON

Area: Zone: A4 1 A4 2 A4 3 A4 4 A4 5 A4 6 A4 7 A4 8

A4 LUTRON

R

Area: Zone: A5 1 A5 2 A5 3 A5 4 A5 5 A5 6 A5 7 A5 8 Area: Zone: A6 1 A6 2 A6 3 A6 4 A6 5 A6 6 A6 7 A6 8 Area: Zone: A7 1 A7 2 A7 3 A7 4 A7 5 A7 6 A7 7 A7 8 Area: Zone: A8 1 A8 2 A8 3 A8 4 A8 5 A8 6 A8 7 A8 8

A5 LUTRON

A6 LUTRON

A7 LUTRON

A8 LUTRON

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 25


Troubleshooting Problem Control unit does not turn lights on

Possible Cause Miswire Incorrect programming

Control unit does not control load or ZONE control does not work

Miswire Incorrect programming

Solution Check wiring (refer to wiring details on pages 5 and 6). Check programming. Check wiring (refer to wiring details on pages 5 and 6). Check programming/addressing.

Wallstation does not function properly

Miswire or loose connection

T ighten loose connections at PELV (Class 2: USA) terminals on unit and wallstations (refer to page 7).

Control unit does not allow scene changes or zone adjustments

Incorrect programming Wrong save mode

Check wallstation programming. Refer to page 21 for a description of   save modes.

Control unit does not allow shade changes or adjustments

Incorrect programming

Check programming. Control unit must   be correctly addressed; see page 16.

Fluorescent load flickers

Dimmed hot and switched hot wires crossed Low end set too low

Check wiring (refer to wiring details on pages 5 and 6). Set low end; see page 13.

Panel is warm

Normal operation

Make sure panel has adequate airflow and ventilation

Two control units have the same address (usually A1)

One control unit has wires 3 and 4 crossed or open

Check wiring (refer to wiring details on pages 5 and 6).

Module LED Diagnostics Unit LED Status Possible Cause Off No power or defective module “Heartbeat” (~1 per sec) Normal operation “Lighthouse” (~1 per 7 sec.) Not communicating with processor; open control harness; module set to invalid or diagnostic address; system not properly configured or addressed in software Zone LED Diagnostics (4A; 4E - 230-CE ONLY!) Zone LED Status Load Status Description Off Off Normal; load Off Continuously On On Incandescent/electronic dimming “Heartbeat” (~1 per sec.) On Magnetic dimming Error Codes 1 blink, pause, repeat 2 blinks, pause, repeat 3 blinks, pause, repeat 4 blinks, pause, repeat

Off Off On full Off

Load short-circuit/overload1 Inductive load2 Shorted component3 DC detection4

Locate and repair fault; cycle power to the module Check software configuration; MLV load detected with ELV software setting 3 Replace the module; internal device shorted 4 Possible faulty MLV load 1 2

NOTE: Contact Lutron Technical Support for additional troubleshooting assistance. 26 GRAFIK Eye® 4000 Series Control Unit Installer’s Guide

R


Warranty Lutron Electronics Co., Inc. One Year Limited Warranty For a period of one year from the date of purchase, and subject to the exclusions and restrictions described below, Lutron warrants each new unit to be free from manufacturing defects. Lutron will, at its option, either repair the defective unit or issue a credit equal to the purchase price of the defective unit to the Customer against the purchase price of comparable replacement part purchased from Lutron. Replacements for the unit provided by Lutron or, at its sole discretion, an approved vendor may be new, used, repaired, reconditioned, and/or made by a different manufacturer. If the unit is commissioned by Lutron or a Lutron approved third party as part of a Lutron commissioned lighting control system, the term of this warranty will be extended, and any credits against the cost of replacement parts will be prorated, in accordance with the warranty issued with the commissioned system, except that the term of the unit’s warranty term will be measured from the date of its commissioning. EXCLUSIONS AND RESTRICTIONS This Warranty does not cover, and Lutron and its suppliers are not responsible for: 1. Damage, malfunction or inoperability diagnosed by Lutron or a Lutron approved third party as caused by normal wear and tear, abuse, misuse, incorrect installation, neglect, accident, interference or environmental factors, such as (a) use of incorrect line voltages, fuses or circuit breakers; (b) failure to install, maintain and operate the unit pursuant to the operating instructions provided by Lutron and the applicable provisions of the National Electrical Code and of the Safety Standards of Underwriter’s Laboratories; (c) use of incompatible devices or accessories; (d) improper or insufficient ventilation; (e) unauthorized repairs or adjustments; (f) vandalism; or (g) an act of God, such as fire, lightning, flooding, tornado, earthquake, hurricane or other problems beyond Lutron’s control. 2. On-site labor costs to diagnose issues with, and to remove, repair, replace, adjust, reinstall and/or reprogram the unit or any of its components. 3. Equipment and parts external to the unit, including those sold or supplied by Lutron (which may be covered by a separate warranty). 4. The cost of repairing or replacing other property that is damaged when the unit does not work properly, even if the damage was caused by the unit. EXCEPT AS EXPRESSLY PROVIDED IN THIS WARRANTY, THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF ANY TYPE, INCLUDING ANY IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY. LUTRON DOES NOT WARRANT THAT THE UNIT WILL OPERATE WITHOUT INTERRUPTION OR BE ERROR FREE. NO LUTRON AGENT, EMPLOYEE OR REPRESENTATIVE HAS ANY AUTHORITY TO BIND LUTRON TO ANY AFFIRMATION, REPRESENTATION OR WARRANTY CONCERNING THE UNIT. UNLESS AN AFFIRMATION, REPRESENTATION OR WARRANTY MADE BY AN AGENT, EMPLOYEE OR REPRESENTATIVE IS SPECIFICALLY INCLUDED HEREIN, OR IN STANDARD PRINTED MATERIALS PROVIDED BY LUTRON, IT DOES NOT FORM A PART OF THE BASIS OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE ENFORCEABLE BY CUSTOMER. IN NO EVENT WILL LUTRON OR ANY OTHER PARTY BE LIABLE FOR EXEMPLARY, CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS, CONFIDENTIAL OR OTHER INFORMATION, OR PRIVACY; BUSINESS INTERRUPTION; PERSONAL INJURY; FAILURE TO MEET ANY DUTY, INCLUDING OF GOOD FAITH OR OF REASONABLE CARE; NEGLIGENCE, OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER), NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON’S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED TO THE INSTALLATION, DEINSTALLATION, USE OF OR INABILITY TO USE THE UNIT OR OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY, OR ANY AGREEMENT INCORPORATING THIS WARRANTY, EVEN IN THE EVENT OF THE FAULT, TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY, BREACH OF CONTRACT OR BREACH OF WARRANTY OF LUTRON OR ANY SUPPLIER, AND EVEN IF LUTRON OR ANY OTHER PARTY WAS ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. NOTWITHSTANDING ANY DAMAGES THAT CUSTOMER MIGHT INCUR FOR ANY REASON WHATSOEVER (INCLUDING, WITHOUT LIMITATION, ALL DIRECT DAMAGES AND ALL DAMAGES LISTED ABOVE), THE ENTIRE LIABILITY OF LUTRON AND OF ALL OTHER PARTIES UNDER THIS WARRANTY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, USE, REPAIR, OR REPLACEMENT OF THE UNIT, OR ANY AGREEMENT INCORPORATING THIS WARRANTY, AND CUSTOMER’S SOLE REMEDY FOR THE FOREGOING, WILL BE LIMITED TO THE AMOUNT PAID TO LUTRON BY CUSTOMER FOR THE UNIT. THE FOREGOING LIMITATIONS, EXCLUSIONS AND DISCLAIMERS WILL APPLY TO THE MAXIMUM EXTENT ALLOWED BY APPLICABLE LAW, EVEN IF ANY REMEDY FAILS ITS ESSENTIAL PURPOSE. TO MAKE A WARRANTY CLAIM To make a warranty claim, promptly notify Lutron within the warranty period described above by calling the Lutron Technical Support Center at (800) 523-9466. Lutron, in its sole discretion, will determine what action, if any, is required under this warranty. To better enable Lutron to address a warranty claim, have the unit’s serial and model numbers available when making the call. If Lutron, in its sole discretion, determines that an on-site visit or other remedial action is necessary, Lutron may send a Lutron Services Co. representative or coordinate the dispatch of a representative from a Lutron approved vendor to Customer’s site, and/or coordinate a warranty service call between Customer and a Lutron approved vendor. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. These products may be covered under one or more of the following U.S. patents: 4,893,062; 4,924,151; 5,191,265; 5,430,356; 5,463,286; 5,949,200; 6,188,181; DES 344,264; and corresponding foreign patents. National Electrical Code (NEC) is a registered trademark of the National Fire Protection Association, Inc., Quincy, Massachusetts. Lutron, the sunburst logo, Hi-Lume, Tu-Wire, and GRAFIK Eye are reg­is­tered trademarks, and Eco-10, Sivoia QED, and Liaison are trademarks of Lutron Electron­ics Co., Inc. © 2007 Lutron Electronics Co., Inc.

R

GRAFIK Eye® 4000 Series Control Unit Installer’s Guide 27


Contact Information Internet: www.lutron.com E-mail: product@lutron.com World Headquarters USA Lutron Electronics Co., Inc. 7200 Suter Road, Coopersburg, PA 18036-1299 TEL +1.610.282.3800 FAX +1.610.282.1243 Toll-Free 1.888.LUTRON1 Technical Support 1.800.523.9466 Brazil Lutron BZ do Brasil Ltda. AV, Brasil, 239, Jardim America Sao Paulo-SP, CEP: 01431-000, Brazil TEL +55.11.3885.5152 FAX +55.11.3887.7138 North and South America Technical Hotlines USA, Canada, Caribbean: 1.800.523.9466 Mexico: +1.888.235.2910 Central/South America: +1.610.282.6701 European Headquarters United Kingdom Lutron EA Ltd. 6 Sovereign Close, London, E1W 3JF United Kingdom TEL +44.(0)20.7702.0657 FAX +44.(0)20.7480.6899 FREEPHONE (UK) 0800.282.107 Technical support +44.(0)20.7680.4481 France Lutron LTC, S.A.R.L. 90 rue de Villiers, 92300 Levallois-Perret France TEL +33.(0)1.41.05.42.80 FAX +33.(0)1.41.05.01.80 FREEPHONE 0800.90.12.18 Germany Lutron Electronics GmbH, Landsberger Allee 201, 13055 Berlin, Germany TEL +49.(0)30.9710.4590 FAX +49.(0)30.9710.4591 FREEPHONE 00800.5887.6635 Italy Lutron LDV, S.r.l. FREEPHONE 800.979.208 Spain, Barcelona Lutron CC, S.R.L. Gran Via del Carlos III, 84, planta 3a, 08028, Barcelona, Spain TEL +34.93.496.57.42 FAX +34.93.496.57.01 FREEPHONE 0900.948.944 Spain, Madrid Lutron CC, S.R.L. Calle Orense, 85, 28020 Madrid, Spain TEL +34.91.567.84.79 FAX +34.91.567.84.78 FREEPHONE 0900.948.944

Lutron Electronics Co., Inc. Made and printed in U.S.A. 01/07 P/N 032-165 Rev. A

ASIAN Headquarters Singapore Lutron GL Ltd. 15 Hoe Chiang Road, #07-03 Euro Asia Centre, Singapore 089316 TEL +65.6220.4666 FAX +65.6220.4333 China, Beijing Lutron GL Ltd. Beijing Representative Office 5th Floor, China Life Tower No. 16 Chaowai Street, Chaoyang District, Beijing 100020 China TEL +86.10.5877.1817 FAX +86.10.5877.1816 China, Guangzhou Lutron GL Ltd. Guangzhou Representative Office Suite A09, 23/F Tower A, Centre Plaza 161 Lin He Xi Lu, Tian He District, Guangzhou 510620 China TEL +86.20.2885.8266 FAX +86.20.2885.8366 China, Shanghai Lutron GL Ltd., Shanghai Representative Office Suite 07, 39th Floor, Plaza 66 1266 Nan Jing West Road, Shanghai, 200040 China TEL +86.21.6288.1473 FAX +86.21.6288.1751 China, Hong Kong Lutron GL Ltd. Unit 2808, 28/F, 248 Queen’s Road East Wanchai, Hong Kong TEL +852.2104.7733 FAX +852.2104.7633 Japan Lutron Asuka Co. Ltd. No. 16 Kowa Building, 4F, 1-9-20 Akasaka, Minato-ku, Tokyo 107-0052 Japan TEL +81.3.5575.8411 FAX +81.3.5575.8420 FREEPHONE 0120.083.417 Asia Technical Hotlines Northern China: 10.800.712.1536 Southern China: 10.800.120.1536 Hong Kong: 800.901.849 Indonesia: 001.803.011.3994 Japan: +81.3.5575.8411 Macau: 0800.401 Singapore: 800.120.4491 Taiwan: 00.801.137.737 Thailand: 001.800.120.665853 Other countries: +800.120.4491

R


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.