Installation and Operation Instructions Please Read Before Installing
Panic - Activates Scene 16 on assigned GRAFIK Eye Control Unit(s) and places them in Scene Lockout. Toggle of this closure will return controls to their status before Panic was activated.
GRX-AV
R
3/8" (10mm)
DIP SWITCH SETTINGS (1-4) 0 = ON; 1 = OFF 1 2 3 4 ADDRESS 1 2 3 4 ADDRESS 1 2 3 4 ADDRESS 1 2 3 4 ADDRESS 0 0 0 0 0 0 0 1 0 0 1 0 0 0 1 1
1 2 3 4
0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1
1 0 0 0 1 0 0 1 1 0 1 0 1 0 1 1
5 6 7 8
1 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1
9 10 11 12
13 14 15 16
Unit Label
3. 4PS Partition Control: Allows independent (Partition Closed) or parallel (Partition Open) operation of multiple GRAFIK Eye Control Units.
DIP SWITCH SETTINGS (5-8)
TYPE
CONFIGURATION
4S CONTROL 7 ON 8 ON 4S CONTROL 7 ON 8 OFF 4Q CONTROL 7 OFF 8 OFF 4PS CONTROL 7 OFF 8 ON SPECIAL CONTROL 7 OFF 8 ON
DIP SETTING
SCENES 1-4, MAINTAIN OUTPUTS SCENES 5-8, MAINTAIN OUTPUTS SCENES 9-12, MAINTAIN OUTPUTS SCENES 13-16, MAINTAIN OUTPUTS
5 ON 5 OFF 5 ON 5 OFF
6 ON 6 ON 6 OFF 6 OFF
SCENES 1-4, MOMENTARY OUTPUTS SCENES 5-8, MOMENTARY OUTPUTS SCENES 9-12, MOMENTARY OUTPUTS SCENES 13-16, MOMENTARY OUTPUTS SEQUENCE 1-4, MAINTAIN INPUTS SEQUENCE 1-4, MOMENTARY INPUTS SEQUENCE 5-16, MAINTAIN INPUTS SEQUENCE 5-16, MOMENTARY INPUTS PARTITION STATUS, MOMENTARY INPUTS PARTITION STATUS, MAINTAINED INPUTS OCCUPANCY SENSOR - SCENE 1 & OFF OCCUPANCY SENSOR - OFF ONLY
5 ON 5 OFF 5 ON 5 OFF 5 OFF 5 ON 6 OFF 6 ON 5 ON 5 OFF 5 ON 5 OFF
6 ON 6 ON 6 OFF 6 OFF 6 ON 6 ON 6 OFF 6 OFF 6 ON 6 ON 6 OFF 6 OFF
ADDRESS CONFIG.
ON
1
1
2
3
2
3
4
5
4
6
1
7
C
3
4 MUX
+V
MUX
COM
MUX LINK
C COM
2
4
5
6
7
8
Output Status LEDs
TYPE
OFF
1
2
3
4
5 1
2
INPUTS
PROGRAM SWITCH
1
3
8
MUX LINK
Program Switch
2
1
2
3
INPUTS
3
4
5
C
5
C
OUTPUTS
4
5 1
2
3
4
OUTPUTS
Terminal Blocks
COM
DIP Switches
SELV (CLASS 2:USA)
4. OS Special Control: OS1 - Occupancy Sensor Scene 1/Off - Maintained contact so occupancy sensor can turn ON assigned GRAFIK Eye Control Unit(s) while still allowing scene changes once room is entered. Note: Use 4S function if occupancy sensor provides a momentary closure. OS2 - Occupancy Sensor Off Only - Occupant must turn lights ON manually, while still allowing energy saving benefits.
Description The GRX-AV Control Interface allows customer-supplied auxiliary equipment such as timeclocks, security systems, and occupant sensors to both access and be controlled by the GRAFIK Eye Control Unit. Features The GRX-AV Control Interface can be configured as one of the following four types: 1. 4S Scene Selection Control Provides for remote control of GRAFIK Eye 3000 or 4000 Series Control Units. It can be used to select any four scenes and turn the system and all corresponding lighting Off. Maintain Outputs: Allows the selection of up to 5 contact closures to other manufacturers A/V equipment. Momentary Outputs: Allows the selection of projector screens requiring momentary output closures. 2. 4Q Special Function Control Sequencing - Cycles the preset light levels from Scene 1 through Scene 4 (or 5 through 16) and back to Scene 1 (or 5) looping indefinitely and using the programmed fade times for each scene. Zone Lockout - Prevents modifications to set light levels on the GRAFIK Eye Control Unit. Only temporary changes can be made. Scene Lockout - Prevents changing of the selected scene or preset levels on all GRAFIK Eye Control Unit(s) and Wallstations.
Important Notes 1. Install in accordance with all local and national electrical codes. 2. CAUTION! Do not connect line voltage/mains cable to Class 2/PELV terminals 3. GRAFIK Eye wallstations are connected to the GRAFIK Eye Control Unit using Class 2/PELV wiring methods per the National Electrical Code. 4. All A/V components are provided by others. 5. Lutron recommends that separate commons be used for "MUX LINK", "INPUTS", and "OUTPUTS". 6. Five input terminals accept maintained inputs and momentary inputs with 40ms minimum pulse times. Switch inputs must have: a. On-state saturation voltage less than 2.0VDC. b. Off-state leakage current less than 10µA. 7. Five output terminals provide maintained outputs with a solid-state output closure and momentary outputs with a one second solid-state output closure. Can drive only Class 2/PELV output devices that exceed 2.0VDC at 200mA. To drive Class 2/PELV output devices, you must add a Class 2/PELV power supply (Lutron offers a 12VDC transformer for 120V applications. Please ask for P/N GRX-12VDC): a. For solid-state output devices, use a power supply that does not exceed 30VDC (Class 2/PELV) output. b. For contact-closure output devices, use a relay and a power supply that does not exceed 30VDC (Class 2/PELV) output.
Español
INTERFACE CONTROL SELV(CLASS 2:USA)
R
COOPERSBURG, PA 18036
English
GRX-AV Control Interface Class 2/PELV
Installation 1. Mount the GRX-AV Interface Control. Mount the GRX-AV using a 4"x4" junction box or directly on a wall as shown in the Mounting Diagram. If the unit is not mounted to a junction box, ensure proper grounding of the metal casing by connecting a ground wire to the ground screw. Remove front enclosure cover to expose terminal blocks, DIP switches, and status LEDs.
4” x 4” Junction Box
GRX-AV
WALL
WALL
GRX-AV
Insert Wires Through Punch-Outs
2. Strip 3/8" (10mm) of insulation from # 18 AWG (1.0mm2) wires. Each terminal will accept two such wires.
3/8" (10mm)
3. Connect wiring as shown in the Wiring Diagram below.
Wiring Diagram
HOT/LIVE SSA
NEUTRAL
+ V –
2 3
1
Power Supply†
Output 5
Output 4
Output 3
Output 2
Output 1
USA Class 2 IEC PELV
Input 5
CLASS 2 1 2 3 4
Input 4
CU WIRE ONLY
Input 3
ZONE 1 ZONE 3 ZONE 5
Input 1
ZONE 2 ZONE 4 ZONE 6
Input 2
†
5
To up to 7 more Control Units and 15 Wallstations or Control Interfaces
1
2 3 4 Inputs
5 1
2
3 4 5 Outputs
Note: Inputs may be Maintained or Momentary depending on control type selection (Momentary shown).
2
C COM
COM
C Program Switch
MUX
MUX
2 3 4 MUX Link +V
1
COM
GRAFIK Eye 3000 Series shown. For GRAFIK Eye 4000 Series wiring, refer to the GRAFIK Eye 4000 Installers Guide.
GRX-AV
Power supply to be supplied by customer (30VDC Max.).
4. Address the GRX-AV. Up to 16 Controls can be configured in a system. Each Control in a system must be assigned a unique address. Set Address Switches 1-4 of the GRX-AV to one of the following for the specified address.
Address Chart Address Location
6
1 1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
11 1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
7
2
4
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
13 14
9
5
2
12
8
3
1
15
10
16* *
Reserved for GRX-PRG.
5. Configure the GRX-AV. Set Function Switches 5-8 on the front of the GRX-AV Interface Control according to the function desired and type of contact closure provided. Refer to the table below. Mode
Dip Switches
5 Inputs. Contact closures invoke . . .
Partitioninga
Occupant Sensor
Maintained or Momentary
Maintained
Maintained or Momentary
Momentary
Momentary only
Maintained
Maintained only
Maintained
2
Scene 1
Scene 2
Scene 3
Scene 4
Off
Scene 5
Scene 6
Scene 7
Scene 8
Off
Scene 9
Scene 10
Scene 11
Scene 12
Off
Scene 13
Scene 14
Scene 15
Scene 16
Off
Scene 1
Scene 2
Scene 3
Scene 4
Off
Scene 5
Scene 6
Scene 7
Scene 8
Off
Scene 9
Scene 10
Scene 11
Scene 12
Off
Scene 13
Scene 14
Scene 15
Scene 16
Off
Sequence Scenes 1-4 Sequence Scenes 5-16 Sequence Scenes 1-4 Sequence Scenes 5-16 Wall1
Zone lockout Scene lockout allows disables scene temporary buttons. adjustments. No changes to preset scenes.
Wall 2
Wall 3
Wall 4
Wall 5
Momentary only
Maintained
Wall 1
Wall 2
Wall 3
Wall 4
Wall 5
Maintained only
Maintained
Occ. Sensor 1b Occ. Sensor 2b
Occ. Sensor 3b
Maintained onlyd
Maintained
Occ. Sensor 1c Occ. Sensor 2c
Occ. Sensor 3c
Occ. Sensor 4b Occ. Sensor 5b c Occ. Occ. Sensor 4 Sensor 5c
Maintained onlyd
Maintained
3
4
5
“Panic” mode Not Used turns lights full on (to scene16), locks Control Units.
Chinese
Special Functions
Outputs are:
1
5 6 7 8 Scene Selection
Inputs are:
a
Movable walls toggle Control Units between “in combination” and “independent” modes of operation. Each input is setup to operate the Control Units associated with a movable wall (or walls). • When a motorized wall opens, the wall’s switch contact closes. This makes the Control Units work “in combination.” Scene changes at one Control Unit occur on all the Control Units. • When a wall closes, the switch contact opens. The Control Units return to independent operation.
b
Sensor input toggles Control Units on to scene 1 and off.
c
Sensor input Control Units off. Occupant must turn lights on.
d
If occupant sensor input provides momentary closure, use scene selection mode.
3
Programming Note: All GRAFIK Eye Wallstations must be assigned a unique address. 1. Put the GRX-AV Control in "Talk". Press and hold the program switch for 3-5 seconds until: • The first Output Status LED blinks or, • The first four Output Status LEDs begin to cycle. 2. Identify the Control Unit(s) to “listen” to this GRX-AV. Press and hold the Control Unit’s Scene 1 button for about 3 seconds until LEDs flash in unison, showing that these Control Unit(s) are “listening”. Repeat for each GRAFIK Eye Control Unit.
3. Take the GRX-AV out of "Talk". Press and hold the program switch for 3-5 seconds until the first Output Status LEDs STOP cycling or blinking. 4. Replace front enclosure cover using the screws provided. * To make a GRAFIK Eye Control Unit stop "Listening" to a GRXAV, put the GRX-AV in "Talk" mode. Press and hold the OFF button on the GRAFIK Eye Control Unit until the LEDs stop blinking. Take the GRX-AV out of "Talk" mode.
4S or 4Q functions - Go to Step 3. 4PS or OS functions - Each input must be programmed separately. A. Press the program switch to cycle through each input. These represent a partition switch, occupancy sensor, etc. The corresponding Output Status LED will blink. B. Program GRAFIK Eye Control Units to communicate with the GRX-AV by using the above procedure. C. When the fifth input is programmed, the GRX-AV will cycle back to the first input.
Internet: www.lutron.com E-mail: product@lutron.com World Headquarters Lutron Electronics Co. Inc., TOLL FREE: (800) 523-9466 (U.S.A., Canada, Caribbean) Tel: (610) 282-3800; International 1-610-282-3800 Fax: (610) 282-3090; International 1-610-282-3090 European Headquarters Lutron EA Ltd., FREEPHONE: 0800 282107 (U.K.) Tel: (207) 702-0657; International 44-207-702-0657 Fax: (207) 480-6899; International 44-207-480-6899 Asian Headquarters Lutron GL, Ltd. (Hong Kong) Tel: (852) 2104-7733; International ++-852 2104-7733 Fax: (852) 5575-8420; International ++852 5575-8420
Lutron Electronics Co., Inc. Made and printed in U.S.A. P/N 040-216 Rev. A 12/04
LIMITED WARRANTY Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid. This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages. Lutron’s liability on any claim for damages arising out of or in connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of the unit. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. Lutron and GRAFIK Eye are registered trademarks of Lutron Electronics Co., Inc. © 2003 Lutron Electronics Co., Inc.