NTGRX-1S
®
Wallstations ntgrx1s-1 08.20.04
Color and Finish Codes
NTGRX-1S-__-_ Entrance Control Description • Ideal for large projects that use the maximum number of Wallstations and/or Control Interfaces but still require additional control points. • Provides line-voltage three-way control for retrofit applications. Features • Wires to GRAFIK Eye 3000 Series Control Units using 120 VAC line voltage wiring. • Wires to GRAFIK Eye 4000 Series Control Units using Class 2 (PELV) wiring. • Does not require an address. • Toggles the connected GRAFIK Eye Control Unit between Scene 1 and Off. • Operates one GRAFIK Eye 3000 or 4000 Series Control Unit. • Up to ten NTGRX-1S Entrance Controls may be wired in parallel to a single Control Unit. • Not for use with 2-zone Control Units.
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name: Job Number:
Model Numbers:
Page 1
NTGRX-1S
®
Wallstations ntgrx1s-2 08.20.04
Specifications Power
Color and Finish Codes
Operating voltage: 12 to 40 VDC and 100 to 127 VAC.
Matte Finishes Standard – Ship White Ivory Beige Gray Brown Black
Key Design Features • Meets IEC 801-2. Tested to withstand 15kV electro-static discharge without damage or memory loss. • Faceplate snaps on with no visible means of attachment. • Can be ganged to share a common faceplate with NovaT*® and Vareo® Dimmers. Counts as a “small control” for ganging. System Communications and Capacity • Does not require an address. • Does not count toward the maximum number of Wallstations/Control Interfaces on a Class 2 (PELV) link. • Wires directly to and communicates directly with the GRAFIK Eye 3000 or 4000 Series Control Unit. • Up to ten NTGRX-1S Entrance Controls may be wired in parallel to the Control Unit.
in 48 hours WH IV BE GR BR BL
Metal Finishes Ship in 4 to 6 weeks Bright Brass BB Bright Chrome BC Bright Nickel BN Satin Brass SB Satin Chrome SC Satin Nickel SN Antique Brass QB Antique Bronze QZ
2 3/4” (70mm)
Anodized Aluminum Finishes Ship in 4 to 6 weeks Clear CLA Black BLA Brass BRA Engraving
Side View
E
Also available:
Wires
Dimensions Front View
2 3/4” (70mm)
4 9/16” (116mm)
-Custom Controls -Color Matching Ship in 4 to 6 weeks. Pricing may vary depending on finishes.
Two #18 AWG (1.0mm2) wires. Environment 32-104°F (0-40°C). Relative humidity less than 90% non-condensing.
1/4” (7.5mm)
1 3/8” (35mm)
Mounting
1-Gang U.S. Wallbox
Faceplate R
S P E C I F I C AT I O N S U B M I T TA L
Job Name: Job Number:
Model Numbers:
Page 2
NTGRX-1S
速
Wallstations ntgrx1s-3 08.20.04
Wiring When used with GRAFIK Eye 3000 Series Control Units NTGRX-1S connects to 3000 Series Control Units using 120 VAC. Connect to the appropriate line-voltage terminals. Connecting 120 VAC to the low-voltage Class 2 (PELV) terminals may cause damage to lighting controls or injury. Earth/Ground from Distribution Panel Distribution Panel Zone 2 Zone 4
Zone 1 CU Wire Only
Zone 6
Hot/Live 2 #12 AWG (2.5mm2)
Hot/Live
Neutral
Zone 3 Zone 5
Hot/Live
CLASS 2
SSA
1 2 3 4
USA Class 2 IEC PELV
Neutral
Rear View of GRX-3106 Neutral Black
Blue
Note: Each line-voltage terminal accepts up to two #12 AWG (2.5mm2) copper wires. NTGRX-1S (10 maximum)
When used with GRAFIK Eye 4000 Series Control Units All connections to 4000 Series Control Units are Class 2 (PELV). Connecting 120 VAC to any terminals on 4000 Series Control Units may cause damage to lighting controls or injury.
SSA RTN DO NOT USE
MUX (4) IN MUX (3) IN MUX (4) OUT MUX (3) OUT
USA: CLASS 2 IEC: PELV
SSA
2 IN, OUT 1 IN, OUT DO NOT USE
Black
Blue
GRX-4103 Control Unit
Note: Each terminal accepts up to two #12 AWG (2.5mm2) copper wires.
NTGRX-1S (10 maximum) R
S P E C I F I C AT I O N S U B M I T TA L
Job Name: Job Number:
Model Numbers:
Page 3