Controller
Ceiling-Mounted RF Receiver rta-rx-f-1 03.17.07
RadioTouchTM Controller for Dimmable Lights
RTA-RX-F RTA-RX-F-347
120/277 V 16 A Max.
TM
1-800-523-9466 1-888-235-2910
USA, Canada Mexico www.lutron.com
CONFIGURACIONES REGLAGES SETTINGS PWR
STAT
ON
5
5
6 7
®
8
+
4
_
3
PS S ig
Occ. S ig
Occ. Com
1 2
24 V
4
15 V
3
Cir Com
2
PELV (Class 2: USA)
1
0-10 V
Description The RadioTouch controller for dimmable lights is designed to work in conjunction with RadioTouch transmitters that have been addressed to the controller. The controller can be addressed to respond to signals from up to 16 RadioTouch transmitters. The controller has the ability to control Lutron Hi-lume® and ECO-10TM ballasts directly. The controller can be connected to a Lutron FDI interface to dim Lutron Tu-wireTM ballasts, incandescent, magnetic low-voltage, and electronic low-voltage loads.
60 Hz
LISTED 243C Ind. Cont. E q.
Coopersburg, PA 18036 USA
®
Refer to the Installers Guide for more detailed instructions. Consulte la Guía de Instaladores para información más detallada. Référer au Guide d’installation pour plus de renseignements détaillés.
PROG
100 Hr/100% P/N 500-10633 © 2006 Lutron Electronics Co., Inc.
RadioTouch RTA-RX-F
The controller mounts to a standard 4 x 4 in. (120 x 120 mm) junction box or to the knockout of a fluorescent fixture. The controller can directly accept inputs from standard 15 and 24 V occupant sensors as well as Lutron’s MW-PS-WH and MW-FPS-WH daylight sensors. The controller operates at either 120/277 V or 347 V , depending on the model number.
Ratings Model Number RTA-RX-F RTA-RX-F-347
R
Voltage 120 or 277 V 347 V
Maximum Current 16 A (20 A breaker) 16 A (20 A breaker)
S P E C I F I C AT I O N S U B M I T TA L
Job Name: Job Number:
Model Numbers:
Page 1
Controller
Ceiling-Mounted RF Receiver rta-rx-f-2 03.17.07
Dimensions
RadioTouch RTA-RX-F
120/277 V 16 A Max.
TM
1-800-523-9466 1-888-235-2910
CONFIGURACIONES REGLAGES SETTINGS PWR
STAT
PROG
ON
5
6 7
8
+
5
_
4
15 V
Occ. Com
Occ. S ig
3
PS S ig
4
1 2
24 V
3
Cir Com
2
PELV (Class 2: USA)
1
0-10 V
®
®
Refer to the Installers Guide for more detailed instructions. Consulte la Guía de Instaladores para información más detallada. Référer au Guide d’installation pour plus de renseignements détaillés.
100 Hr/100% P/N 500-10633 © 2006 Lutron Electronics Co., Inc.
USA, Canada Mexico www.lutron.com
60 Hz
LISTED 243C Ind. Cont. E q.
Coopersburg, PA 18036 USA
7.75 in. (197 mm)
ON
1
2
3
4
5
1
TX
2
3
4
5
6
7
8
RX
4 in. (100 mm)
2.5 in. (17.8 mm)
Mounting Using two screws, mount the unit to a 4 x 4 in. (120 x 120 mm) junction box or directly to a wall (screws and wall anchors are provided) as shown.
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name: Job Number:
Model Numbers:
Features • Provides direct control of a full circuit of Lutron Hi-lume® and ECO-10TM ballasts. • Capable of switching 16 amps of Lutron ballasts. • Provides control of Lutron Tu-wireTM ballasts, incandescent, magnetic low-voltage, and electronic low-voltage loads using an FDI load interface. • RTA-RX-F operates at 120 or 277 V line voltage. • RTA-RX-F-347 operates at 347 V line voltage. • Each controller can be programmed to accept control information from 16 unique RadioTouch transmitters. • Accepts inputs from standard 15 and 24 V occupant sensors and provides power to them (not to exceed 30 mA). • One required per lighting zone to be controlled. • Accepts an input from a Lutron MW-PS-WH or MW-FPS-WH daylight sensor to regulate the electric light based on the presence or absence of sunlight and provides power to the sensor (not to exceed 30 mA). • Accepts control signals from RadioTouch transmitters at 418 MHz. • Provides a burn-in function to assist in the seasoning of new fluorescent bulbs for 100 hours. • Mounts to a standard 4 x 4 in. (120 x 120 mm) junction box or to the knockout of a fluorescent fixture.
Page 2
Controller
Ceiling-Mounted RF Receiver rta-rx-f-3 03.17.07
Power Wiring Diagram
Green White Black (120 V Black/Red
Ground Neutral Switched Hot (blue) Dimmed Hot (orange)
)
Distribution panel 120/277 V 16 A Max.
TM
LISTED 243C Ind. Cont. E q.
Coopersburg, PA 18036 USA
1-800-523-9466 1-888-235-2910
USA, Canada Mexico www.lutron.com
CONFIGURACIONES REGLAGES SETTINGS PWR
STAT
ON
5
6 7
®
8
+
_
5
PS S ig
4 24 V
3 15 V
4
1 2
Cir Com
3
Occ. S ig
2
Occ. Com
1
PELV (Class 2: USA)
Ground Neutral Hot
60 Hz
0-10 V
Fixture ground Lutron FDB or ECO dimming ballast
®
Refer to the Installers Guide for more detailed instructions. Consulte la Guía de Instaladores para información más detallada. Référer au Guide d’installation pour plus de renseignements détaillés.
PROG
100 Hr/100 P/N 500-10633 © 2006 Lutron Electronics Co., Inc.
RadioTouch RTA-RX-F
Green White Black Orange
Fixture ground Green White Black Orange
Red (277/347 V ) Cap the wire that is not being used (red or black, depending on voltage)
Lutron FDB or ECO dimming ballast
To additional dimming ballasts
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name: Job Number:
Model Numbers:
Page 3