Children's Hopsital Design

Page 1

TECHNICAL DESIGN HOSPITAL PROJECT CURRENTLY UNDER CONSTRUCTION

I HAVE ASSISTED IN THE TECHNICAL DRAWING FOR THIS PROJECT. IT IS A CHILDREN’S HOSPITAL IN THE UNITED STATES. I COORDINATED WITH A LICENSED ARCHITECT WHILE WORKING IN REVIT.

-8" MAIN ROOF 1/2" MINERAL FIBER INSULATION SLOPED ROOF STRUCTURE SLOPE ROOFING MEMBRANE PROTECTION BOARD POLYISO INSULATION T.O. FRAMING SHEET METAL COPING NOTE: UPDATE PANEL JOINTS BASED ON FINAL PANEL DESIGN 3/4" BATT INSULATION FIBER REINFORCED CONCRETE PANELS 1/8" 11 3/8" EOS RS-1 FIBER REINFORCED CONC PANEL CLADDING WEATHER RESISTANT AIR BARRIER EXTERIOR SHEATHING MINERAL FIBER INSULATION 4" MINERAL WOOL INSULATION ALUM. STOREFRONT WINDOW 6" METAL STUD SELF-ADHERED FLASHING MEMBRANE METAL FLASHING DRIP EDGE METAL FLASHING DRIP EDGE 1/2" CEILING AS SCHEDULED 3/8" COLD FORM METAL STUD SUPPORT SPRAY-APPLIED FIREPROOFING STEEL BEAM - REF. STRUCT. DWGS SEALANT SCREEN INSECT 1/2" CEILING SCHEDULED STL BEAM -REF STRUCT. DWGS FIREPROOFING MINERAL WOOL INSULATION 5/8" EXTERIOR SHEATHING WATER RESISTANT AIR BARRIER INSULATED SPANDREL GLAZING MINERAL WOOL SPANDREL INSULATION SEALANT INTERMEDIATE METAL PANEL HORIZONTAL RAIL 1/4" MIN. METAL BACK PAN VERTICAL RAIL 1 1/4" 41' -4" FOURTH FLOOR CURTAIN WALL ASSEMBLY SECURE ASSEMBLY VERTICAL MULLIONS @CLIPS CONTINOUS EXISTING CURTAIN WALL ASSEMBLY EXISTING CONCRETE SLAB CONTINOUS EXTRUDED ALUMINUM BASE STEEL ANGLE SECURED TO EXISTING SLAB (REF.STRUCT.) EXTRUDED ALUMINUM COVER PLATE EXISTING REMAIN EXISTING FIRE BRACINGS 55' -0" FIFTH FLOOR INSULATED SPANDREL GLAZING CLEAR GLAZING BENT STL PLATE REF. STRUCT. DWGS -HOUR FIRE STOPPING DEFLECTION STUD 4' 2 13/16" MINERAL FIBER INSULATION CURTAIN WALL ASSEMBLY FOURTH FLOOR CONTINUOUS SEALANT SPRAY APPLIED FOAM INSULATION SELF ADHERED MEMBRANE FLASHING OVER METAL FLASHING. MINIMUM OVERLAP METAL FLASHING, COLOR MATCH STAINLESS STEEL TILE EXISTING PRECAST CONCRETE EXTEND AIR BARRIER OVERTOP OF PRECAST PANEL AND ANCHOR BEHIND FLASHING CLEAT STAINLESS STEEL TILE EXIST AIR BARRIER EXTERIOR SHEATHING MINERAL WOOL INSULATION 5/8" EXTERIOR SHEATHING WATER RESISTANT AIR BARRIER COLD METAL FRAMING 55' -0" FIFTH FLOOR MINERAL WOOL INSULATION METAL FLASHING METAL CLIP PROVIDED BY MFR FIRE STOPPING 5/8" GYP. SPRAY APPLIED FIREPROOFING CONC ON METAL DECK METAL STUD 1/2" 4" MINERAL WOOL 5/8" EXTERIOR SHEATHING WATER RESISTANT AIR BARRIER PLYWOOD BASE SOLID SURFACE WINDOW STOOL 4" EOS 1/2" -4" FOURTH FLOOR EXIST. PRECAST CONCRETE PANEL SPRAY APPLIED FOAM INSULATION- CONT. INSUL. MIN. SELF ADHERED MEMBRANE FLASHING 5/8" GYP SEALANT WITH BACKER ROD INSULATED GLASS SPANDREL ALUM. FIXED WINDOW SYSTEM SEALANT ALUM. SILL EXTRUSION WINDOW MFR EXIST MEMBRANE FLASHING EXISTING CONRETE SLAB SOLID SURFACE WINDOW STOOL PLYWOOD BASE SEALANT METAL STUD O.C. SEALANT EXISTING EXTERIOR FLASHING SELF-ADHERED MEMBRANE FLASHING MINERAL FIBER INSULATION FIBER REINFORCED CONCRETE PANEL 5/8" EXTERIOR SHEATHING WATER RESISTANT AIR BARRIER METAL CLIP BY FRCP MFR METAL STUD 5/8" GYP. METAL STUD SEALANT INSULATED GLAZING WOOD BLOCKING HORIZONTAL RAIL FASTENER CEILING AS SCHEDULED 3/8" 1/4" ALUMINUM WINDOW SEALANT W/ BACKER ROD STAINLESS STEEL RIVET PAINTED MATCH FRCP VERTICAL RAIL VERTICAL BRACKET SELF ADHERED MEMBRANE FLASHING 1/2" INSECT SCREEN OT OR ONST PRELIMINAUCTION RY Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 EXTERIOR WALL SECTION DETAILS BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 1/2" 1'-0" B1 EXTERIOR WALL @PARAPET 1/2" 1'-0" B2 DETAIL AT WALL INSET 1/2" 1'-0" B3 CURTAINWALL HEAD DETAIL 1/2" 1'-0" A2 NEW/ EXISTING CURTAINWALL TRANSITION 1/2" 1'-0" A3 DETAIL THRU CURTAINWALL 1/2" 1'-0" A4 SILL DETAIL AT STAINLESS STEEL TILE AND EXISTING 1/2" 1'-0" A1 SECTION DETAIL AT WINDOW INSET 1'-0" B4 DETAIL AT FIXED WINDOW SILL 1'-0" D4 HEAD DETAIL @ FIXED WINDOW EXTRUDED ALUM. TRIM CLEAR ANODIZED ALUM. WINDOW PARTITION AS SCHEDULED ICE WATER SHIELD STAINLESS STEEL PANEL BREAK METAL LINE OF EXIST PRECAST PANEL BELOW ALUMINUM WINDOW WITH SHADOW BOX STAINLESS STEEL TILE 5/8" GYP. BOARD METAL STUD SEALANT BEYOND WINDOW SILL BELOW PARTITION AS SCHEDULED LINE EXISTING PRECAST CONCRETE PANEL BELOW MINERAL FIBER INSULATION SOLID SURFACE WINDOW SILL BELOW SEALANT BELOW ALUMINUM COLUMN COVER 2HR RATED CEMENTITIOUS FIREPROOFING BUTT JOINT VERTICAL REVEAL 1/2" 5/8" EXTERIOR SHEATHING MINERAL FIBER INSULATION FIBER REINFORCED CONCRETE PANELS METAL STUD -1/2" METAL STUD 5/8" GYP. SPRAY APPLIED FIREPROOFING -5/8" METAL STUD METAL STUD 5/8" GYP BD BATT INSULATION SS RIVET - COLOR TO MATCH FRCP PANEL WATER RESISTANT AIR BARRIER HORIZONTAL RAIL KNIGHT WALL VERTICAL RAIL CORNER CLOSURE PAINTED BLACK 5/8" GYP SEALANT METAL STUD BATT INSULATION STAINLESS STEEL TILE MINERAL FIBER INSULATION VAPOR RESISTIVE AIR BARRIER 5/8" EXTERIOR SHEATHING FACE OF EXISTING PRECAST PANEL LINE SLAB EDGE BELOW 1/2" -CHANNEL ANODIZED ALUMINUM MULLION CAP ALUMINUM COLUMN COVER 2HR RATED CEMENTITOUS FIREPROOFING ALUMINUM CORNER CAP SEALANT MINERAL FIBER INSULATION BUTT JOINT VERTICAL REVEAL 1'-5 1/2" PLUMBING LINE, REF. PLUMBING DWGS 5/8" GYB BD. BATT INSULATION METAL STUD SPRAY APPLIED FIREPROOFING MINERAL FIBER INSULATION EXTERIOR SHEATHING METAL STUD -5/8" METAL STUD FIREPROOFED COLUMN, REF. STRUCT. DWGS 1'-10" 3/4" 1'-8 1/2" FRCP PANEL EXPANDABLE FOAM TAPE HORIZONTAL RAIL VERTICAL RAIL THERMAL ISOLATOR SHIMS STAINLESS STEEL RIVET MATCH FRCP COLOR WATER RESISTANT AIR BARRIER 3/8" G 2" MINERAL FIBER INSULATION 5/8" EXTERIOR SHEATHING METAL STUD SPRAY APPLIED FIREPROOFING BATT INSULATION LINE EXIST. PRECAST CONC PANEL BELOW STAINLESS STEEL TILE WATER RESISTANT AIR BARRIER STEEL COLUMN - REF. STRUCT. DWGS 1/2" -PIECE OUTSIDE CORNER CAP, FINISH TO MATCH TILE 2' 8 1/2" 1' 3" -5/8" METAL STUD 5/8" GYP BD. SPRAY APPLIED FIREPROOFING ON STRUCT. COL. - REF. STRUCT. DWGS BATT INSULATION MINERAL FIBER INSULATION METAL STUD 5/8" EXTERIOR SHEATHING -1/2" METAL STUD 1'-1" 1'-2" STAINLESS STEEL TILE FACE EXIST PRECAST CONCRETE BELOW BREAK METAL TRIM PAINT TO MATCH STAINLESS STEEL TILE 1/2" HIDDEN ATTACHMENT SHEATHING H2.8 THE COLUMN COVER CUT AROUND THE WINDOW MULLION, ADD SEALANT BETWEEN THE TWO MINERAL FIBER INSULATION ANODIZED ALUM CORNER CAP TO MATCH CURTAINWALL 1 1/2" 1/2" PRELIMINANOTFORCONSTRUCTION RY Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 2/14/2023 4:43:31 PMAutodesk Docs://10325067_Niswonger Children's Hospital_2022/10325067-A-CENTRAL_NISWONGER CHILDRENS HOSPITAL EXTERIOR DETAILS BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 1'-0" B1 PLAN DETAIL AT VERTICAL FIN 1'-0" B3 LEVEL 4 -PLAN DETAIL AT STAINLESS STEEL TILE 1/2" 1'-0" A2 METAL COLUMN COVER DETAIL 1/2" 1'-0" A3 PLAN DETAIL AT COLUMN WRAP 1'-0" B4 LEVEL -PLAN DETAIL AT CURTAINWALL AND RECESSED METAL TILE 1/2" 1'-0" A1 PLAN DETAIL AT INSIDE CURTAINWALL CORNER 1/2" 1'-0" C1 5TH FLOOR COL. WRAP @ TRANSP STOR 1/2" 1'-0" C2 4TH FLOOR COL. WRAP PLAN DETAIL 1/2" 1'-0" C3 COL. WRAP BETWEEN PATIENT ROOMS 1/2" 1'-0" A4 COLUMN DETAIL AT CONNECTOR
MINERAL FIBER INSULATION STAINLESS STEEL TILE 5/8" EXTERIOR SHEATHING WATER RESISTANT AIR BARRIER BATT INSULATION METAL STUD 1/2" 1/2" 5/8" METAL STUD 5/8" GYP SEALANT EXTRUDED ALUMINUM TRIM MATCH WINDOW MULLION FACE OF EXISTING PRECAST CONCRETE BELOW SEALANT WITH BACKER ROD 4"MINERAL FIBER INSULATION 5/8" INTERIOR GYP. 5/8" EXTERIOR SHEATHING WATER RESISTANT AIR BARRIER SEALANT 5/8" METAL STUD METAL STUD FIBER REINFORCED CONCRETE PANEL 1/2" ALUM CURTAIN WALL MULLION WOOD BLOCKING SEALANT WITH BACKER ROD KNIGHT WALL VERTICAL -RAIL KNIGHT WALL THERMABRACKET END CAP COVER TRIM EXPANSION JOINT COVER FLOOR BELOW EXPANSION JOINT 5/8" METAL STUD BATT INSULATION SPRAY APPLIED FIREPROOFING 5/8" GYP. BD. PARTITION SCHEDULED MULLION MATE BRAKE FORMED MULLION MATE END CAP 1/2" EXPANSION JOINT COVER BELOW MINERAL FIBER METAL STUD ANODIZED ALUMINUM TRIM EDGE FLOOR SLAB BELOW GYP. CORNER BEAD, EA. SIDE -5/8" METAL STUD WITH 5/8" GYP EACH SIDE COMPRESSIBLE NEOPRENE GASKET WITH SEALANT EA. SIDE TYP. MULLION PARTITION SILL BELOW BRAKE METAL END CAP 1/2" NOTE DO NOT ATTACH STUD TO MULLION OT OR ONST PRELIMINAUCTION RY Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer 4'8' SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 EXTERIOR DETAILS BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 1'-0" A2 PLAN DETAIL AT CONNECTOR 1'-0" B1 PLAN DETAIL AT SERVICE VESTIBULE 1'-0" A3 PLAN DETAIL AT EXPANSION JOINT 1/2" 1'-0" B3 PLAN DETAIL AT PARENT LOUNGE 1'-0" A4 PLAN DETAIL AT EXPANSION JOINT 1'-0" B2 PLAN DETAIL CURTAINWALL MULLION J2 EXIST EXTERIOR PLASTER INSULATION SYSTEM FIBER REINFORCED CONCRETE PANEL MINERAL FIBER INSULATION CAST PLACE CONCRETE REF. STRUCT DRAWINGS WATER RESISTANT AIR BARRIER METAL FLASHING SELF ADHERED MEMBRANE FLASHING EXIST CONC ELEVATOR SHAFT WALL 10" 47' VERTICAL RAIL HORIZONTAL RAIL THERMAL ISOLATOR SHIMS 5/8" 68' -8" MAIN ROOF J2 MINERAL FIBER INSULATION FIBER REINFORCED CONC PANEL CAST PLACE CONC REF. STRUCT. DWGS WATER RESIST. AIR BARRIER 3/4" RS-2 1/2" REVEAL HORIZONTAL RAIL THERMAL ISOLATORS SHIMS VERTICAL RAIL A-504 MEMBRANE FLASHING OVER ALUMINUM TRIM (MINIMUM OVERLAP) FRCP CLADDING VERTICAL RAIL MINERAL WOOL INSULATION FIBER REINFORCED CONCRETE PANEL 5/8" EXTERIOR SHEATHING VERTICAL RAIL BRACKET HORIZONTAL RAIL MINERAL WOOL INSULATION STAINLESS STEEL TILE 1/2" METAL ANGLE CLIP METAL FLASHING THERMAL ISOLATORS SHIMS 55' -0" FIFTH FLOOR -HR PERIMETER FIRE STOPPING DO NOT FASTEN BOTTOM EDGE OR SHEATHING STUD BELOW SELF-ADHERED AIR BARRIER BELOW AT SLIP JOINT DO NOT FASTEN UPPER EDGE OF SHEATHING TO DEFLECTION TRACK SEALANT COLD FORMED METAL FRAMING 5/8" EXTERIOR GYP. SHEATHING WATER RESISTANT AIR BARRIER MINERAL FIBER INSULATION MAX. SPACING PER MANUFACTURE 1/2" 1/8" E.O.S. 3/8" HORIZONTAL RAIL DEFLECTION TRACK 4" -8" MAIN ROOF FIBER REINFORCED CONCRETE PANELS HORIZONTAL RAIL VERTICAL RAIL MINERAL WOOL WATER RESISTANT AIR BARRIER OT OR ONST PRELIMINAUCTION RY Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 EXTERIOR DETAILS BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 1'-0" A1 SECTION DETAIL AT SERVICE ELEVATOR 1/2" 1'-0" A3 PARAPET DETAIL AT SOUTH ELEVATOR 1'-0" A5 HEAD DETAIL AT STAINLESS STEEL TILE 1/2" 1'-0" B1 EXTERIOR WALL @FLOOR SLAB 1'-0" B3 1-1/2" REVEAL AT SOUTH STAIR
- 5/8" METAL STUD BATT INSULATION 5/8" GYPSUM BOARD SPRAY APPLIED FIREPROOFING 29/32" C.2 3/8" -5/8" METAL STUD 5/8" GYP. BD BATT INSULATION SPRAY APPLIED FIREPROOFING 3/4" 7/16" 5/8" GYP. METAL STUD SPRAY APPLIED FIREPROOFING BATT INSULATION 1/4" 0" BATT INSULATION SPRAY APPLIED FIREPROOFING -1/2" METAL STUD 5/8" GYP. BD -5/8" METAL STUD 1HR RATED WALL, REF. LIFE SAFETY PLAN FIRE EXTINGUISHER CABINET -5/8" METAL STUD BATT INSULATION 11" 3/16" 5/8" GYP. BD BATT INSULATION SPRAY APPLIED FIREPROOFING -5/8" METAL STUD C.2PATIENT ROOM DOOR JAMB 8 -5/8" METAL STUD WITH 5/8" GYP. EACH SIDE BATT INSULATION C4004A NURSE SERVER 1HR FIRE/SMOKE COMPARTMENT WALL METAL STUD 5/8 GYP BD -1/2 METAL STUD RECESSED STRIKER MFR FOR NARROW LEAD POST CONTINUOUS BACKING, EA SIDE 1HR RATED CONSTRUCTION AT DOOR POCKET WOOD POCKET COVER DOOR WITH SPRINGOPEN HINGE MAGNETIC DOOR CATCH DOOR BUMPER 1/4"D3 A-553FILLER PANEL SEALANT EACH SIDE SERVER TO DOOR FRAME MIN. RATED DOOR5/8" GYP. BD -5/8" METAL STUD BATT INSULATION SPRAY APPLIED FIREPROOFING ZONE VALVE BOX - REF. PLUMBING DWGS RECESSED FIRE EXTINGUISHER CABINET 1/2" METAL STUD NURSE SERVER METAL STUD 5/8" GYP. BD SPRAY APPLIED FIREPROOFING 7/16" REMOVABLE CLOSURE 5/8" GYP BD SOFFIT -5/8" MTL STUD FRAMING MTL STUD FRAMING PLYWOOD BLOCKING INSIDE GYP BD FACE EXTERIOR WALL WOOD BLOCKING DRIVE CHAIN SHADE CLOTH B.O. CEILING REF. RCP 1/2" THREADED RODS W/NUTS WASHERS BY MFR 3/8" +/HR RATED WALL EA. SIDE TO DECK ABOVE - SOUND BAFFLES STC RATING TO MATCH THAT OF ACCORDIAN PARTITION PRE-FINISHED TRACK ASSEMBLY MFR POCKET DOOR BEYOND CEILING PERIMETER TRIM CEILING SCHEDULED NOTFOR ONST PRELIMINAUCTION RY Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 g pINTERIOR DETAILS BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 1'-0" A1 COLUMN DETAIL 1'-0" B1 COLUMN DETAIL 1'-0" B2 LEVEL 4 -AREA C -Callout 1'-0" B4 COLUMN DETAIL 1'-0" C1 COL. WRAP @ SOIL HOLD 1'-0" B3 LEVEL -COL. WRAP @ CLEAN SUPPLY 1'-0" A2 PLAN DETAIL AT HORIZONTAL SLIDING DOOR 1'-0" A5 PLAN DETAIL AT COLUMN WRAP 1'-0" C2 PLAN DETAIL AT PNEUMATIC TUBE 1'-0" C4 ROLLER SHADE DETAIL 1/2" 1'-0" D3 FOLDING PARTITION HEAD DETAIL DEMOLITION LEGEND SHEET KEYNOTES DEMOLITION GENERAL NOTES AREAS TO BE AFFECTED. COORDINATE WITH MEP DRAWINGS FOR EXACT LOCATIONS AND SCOPE WORK. DOOR REMOVED WALLS TO BE REMOVED A4 -202 -203 A4 -204 -201 1.2 1.8 2.6 3.6 C.2 E.6 F.4 D3 D9 AD-104 H2 H2.8 H3 -473 B2 B3 -473 B4 -205 A1 -472 -475 B4 -475 B3 A4 A5 -602 -602 D11 37 37 35 G1 -471 D1 -474 -471 -473 A3 -473 -443 D5 -443 B2 B3 B4 -205 -205 -474 C2 -477 -477 -602 -476 -602 - 0 -602C5 AD-104 D1 D10 D10 D10 D10 D12 D10 D10 D10 D13 D10 D15 D11 D11 D10 D10 D17 D1 D2 D16 D17 -443 C4 C2 C5 C3 -205 D1 D3 -515 -515 -515 -515 -515 D5 -515 D3 -515 D2 -515 -200 B5 -201 -200 C5.1 C3 -205 D4 -515 D18 D16 D19 D20 AD-104 D21 D22 D23 A5 -523 -520 A5 -522 19' 32' 27' 20' 19' 0" 11' D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 A-352 D5 C5.2 B5.2 -201 D5 -201 B5.1 -201 -200 A5.1A5.2 C4 -420 41' -4" FOURTH FLOOR C PRECAST PANEL TO BE REMOVED METAL COPING TO BE REMOVED STRUCTURE REMAIN CURTAINWALL TO REMAIN PANLE SUPPORT STRUCTURE TO BE REMOVED EXISTING ROOF AND INSULATION REMOVED CONC SLAB TO REMAIN FIRESTOPPING TO REMAIN HSS STRUCTURE TO BE REMOVED 41' -4" FOURTH FLOOR E.6 F.4 PORTION OF EXISTING WALL REMOVED EXISTING ART WALL TO REMAIN EXIST ROOF TOP FAN RELOCATED - REF. MECH DWGS PORTION OF EXISTING CONCRETE CURB TO BE REMOVED - COORDINATE WITH STRUCTURAL 41' -4" FOURTH FLOOR C EXISTING ROOF AND INSULATION TO BE REMOVED CONC SLAB TO REMAIN 11" STRUCTURE REMAIN SPRAY APPLIED FIREPROOFING FIRESTOPPING TO REMAIN PRECAST PANEL TO BE REMOVED METAL COPING TO BE REMOVED Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer 4'8' SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 DEMOLITION PLANROOF BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 3/32" 1'-0" A3 FOURTH FLOOR DEMOLITION PLAN 23.HATCHED AREAS INDICATE WORK ABOVE CEILING NEEDED FOR MEP UTILITY CONNECTIONS. REFERENCE MEP DRAWINGS FOR EXACT WORK NEEDED. 22.DURING DEMOLITION, THE ADJACENT EXISTING FACILITIES SHALL REMAIN FULL OPERATION DURING ALL CONSTRUCTION WORK. MAINTAIN ACCESS THE BUILDING AT ALL TIMES. PREVENT INTERRUPTION IN UTILITIES OR SERVICES. COORDINATE WITH REQUIREMENTS OF THE OWNER MAINTAIN CONTINUITY OF OWNER'S OPERATIONS. DO NOT BLOCK ANY REQUIRED FIRE EXITS. 21.PROVIDE PROTECTION FROM ELEMENTS FOR THAT PORTION OF WORK WHICH MAY BE EXPOSED. 20.WHEN USING BUILDING ELEVATORS FOR REMOVAL OF DEBRIS AND STOCKING OF PROJECT, ELEVATOR ARE TO PROPERLY PROTECTED. DAMAGE TO BUILDING ELEVATORS, PUBLIC AREAS OR CIRCULATION AREAS WILL REQUIRE REPAIR OR REPLACEMENT. 19.COORDINATE WITH OWNER THE DISPOSITION OF SALVAGEABLE MATERIALS. 18.PROTECT ALL EXISTING FIREPROOFING FROM DAMAGE DURING DEMOLITION. 17.PROVIDE OPERATIONS INSURE LEAST INCOVENIENCE TO THE GENERAL PUBLIC. 16.OBTAIN COPY AND FOLLOW OWNER'S INFECTION CONTROL RISK ASESSMENT (ICRA). PROVIDE TEMPORARY SEPARATION BETWEEN AREA OF WORK AND OCCUPIED SPACES DURING DEMOLITION AND CONSTRUCTION REQUIRED BY ICRA AND APPLICABLE CODES. 15.PATCH AND REPAIR FIREPROOFING WHERE DAMAGED OR REMOVED DURING CONSTRUCTION ACTIVITIES. ENSURE SFRM MATERIAL COMPATIBLE WITH ANY APPLIED PRIMERS. PROTECT EXISTING DUCTWORK, PIPING, ELECTRICAL DEVICE, WIRING, FIRE ALARM DEVICE, CABLING, OR ANY OTHER UTILITY PRESENT FROM SFRM OVERSPRAY. 14.PATCH AND REPAIR WALLS TO REMAIN WHERE PIPES, DUCTS, ETC. WERE REMOVED. EXISTING SMOKE AND FIRE RESISTANCE RATING SHALL BE MAINTAINED WHERE APPLICABLE. PREPARE WALLS RECEIVE NEW FINISHES. 13.PATCH AND REPAIR ANY DAMAGE WHICH MAY OCCUR DURING DEMOLITION ON ANY ADJACENT CEILINGS, WALLS OR FLOORS TO REMAIN. PREPARE WALLS AND FLOORS TO RECEIVE NEW FINISH. 12.PROTECT FROM DAMAGE ALL EXISTING FLOORS, WALLS, CEILINGS, ETC. DURING CONSTRUCTION AND PROVIDE TEMPORARY PARTITIONS NEEDED. CONTRACTOR IS RESPONSIBLE FOR REPAIR AND REPLACEMENT ALL DAMAGED FLOORING, WALLS, CEILINGS, ETC. FINISHES MATCH EXISTING. 11.WHERE PARTITION, EQUIPMENT, OR ACCESSORIES, ETC. ARE REMOVED AND REPLACEMENT FINISH CALLED FOR, THE GENERAL CONTRACTOR SHALL REPAIR MATCH ADJACENT FINISH. 10.REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR EXTENT EACH DISCIPLINE'S DEMOLITION. 9.PATCH, FILL, AND LEVEL ALL HOLES FLOOR SLAB DUE TO DEMOLITION OF PLUMBING RISERS, FLOOR DRAINS, ELECTRICAL RISERS, MILLWORK, CASEWORK, OR EQUIPMENT. 8.REPAIR HOLES EXISTING WALLS REMAIN WHERE WALL MOUNTED ITEMS ARE TO BE REMOVED. REFER TO ROOM FINISH LEGEND FOR FINAL FINISH. 7.REPAIR ALL CEILINGS TO MATCH EXISTING CEILINGS WHERE WALLS ARE TO DEMOLISHED AND EXISTING CEILING TO REMAIN. 6.ADDITIONAL DEMOLITION REQUIRED ACCOMMODATE NEW CONSTRUCTION SHOWN ON EACH INDIVIDUAL DISCIPLINES' SHEETS. CONTRACTORS TO REVIEW EXISTING CONDITIONS AND INCLUDE BASE BID ALL DEMOLITION REQUIRED FOR COMPLETE INSTALLATION. 5.COORDINATE WITH OWNER ITEMS TO BE SALVAGED AND STORED FOR OWNER'S USE. 4.MAINTAIN EGRESS ROUTES FROM EXISTING BUILDING THROUGHOUT COURSE OF CONSTRUCTION. 3.COORDINATE WITH OWNER WHICH ITEMS WILL REMOVED PRIOR TO START OF DEMOLITION. 2.REMOVE ALL EXISTING CONSTRUCTION INDICATED BY BOLD DASHED LINES. 1.LIGHT LINES INDICATE EXISTING CONSTRUCTION TO REMAIN. D1 EXISTING ROOF TO REMOVED D2 DOOR AND HARDWARE REMOVED D3 EXTERIOR WALL TO REMOVED D4 COLUMN CAP TO BE REMOVED D6 METAL STEP REMOVED D8 WALL SUPPORTS TO BE REMOVED D9 MEP TO REMOVED/RELOCATED D10 REMOVE TIE-OFF ANCHOR D11 REMOVE WALKWAY PAD D12 REMOVE ANGELED HSS STRUCTURE D13 PORTION STONE VENEER TO BE REMOVED D15 EXISTING ROOF REMAIN D16 REMOVE EXISTING LADDER AND ROOF HATCH D17 PORTION EXISTING STONE CLADDING AND WALL BASE REMOVED D18 PORTION EXISTING METAL PANEL WALL SYSTEM TO REMAIN D19 DELETE WALL, PORTION OF CONC CURB REMAIN. REF. STRUCT. DWGS FOR EXTENTS D20 REMOVE RAMP D21 REMOVE ELEVATOR OVERRUN ROOF VERTICAL MEMBRANE, STUD INSULATION. REMOVE INTERIOR SHAFTWALL TO COCNRETE SLAB. REF STRUCT. DWGS FOR STEEL DEMO NOTES D22 REMOVE PARAPET AND PORTION EXTERIOR WALL TO CONCRETE SLAB D23 REMOVE METAL GRAVEL STOP AND FASCIA 1/2" 1'-0" A5 DEMOLITION DETAIL AT EXISTING PARAPET 3/32" 1'-0" C5 DEMOLITION ELEVATION AT 4TH FLOOR EXTERIOR STAIR 1/2" 1'-0" B5 PARAPET SECTION DETAIL
123 12 EXTERIOR GLAZING THERMAL INSULATION EXTERIOR GLAZING -1/4" -1/2" CURTAIN WALL MULLION 1/4"SHADOW BOX 56 STAINLESS STEEL TILE VAPOR RESISTIVE AIR BARRIER GYPSUM SHEATHING COLD-FORMED METAL STUDS THERMAL INSULATION GYPSUM BOARD THERMAL INSULATION 13 567 FIBER REINFORCED CEMENTITIOUS PANEL THERMAL INSULATION VAPOR RESISTIVE AIR BARRIER EXTERIOR SHEATHING COLD-FORMED METAL STUD THERMAL INSULATION GYPSUM BOARD 13 567 FIBER REINFORCED CEMENTITIOUS PANEL MINERAL WOOL BLANKET INSULATION VAPOR RESISTIVE AIR BARRIER EXTERIOR GRADE SHEATHING FIBERGLASS BATT INSULATION GYPSUM WALLBOARD FIBER REINFORCED CEMENTITIOUS PANEL MINERAL WOOL BLANKET INSULATION VAPOR RESISTIVE AIR BARRIER CAST- -PLACE CONCRETE 13 567 FIBER REINFORCED CEMENTITIOUS PANEL MINERAL WOOL BLANKET INSULATION VAPOR RESISTIVE AIR BARRIER EXTERIOR GRADE SHEATHING FIBERGLASS BATT INSULATION GYPSUM WALLBOARD 12 Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 2/14/2023 4:34:42 PMAutodesk Docs://10325067_Niswonger Children's Hospital_2022/10325067-A-CENTRAL_NISWONGER CHILDRENS HOSPITAL EXTERIOR WALL ASSEMBLY TYPES BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON Totals: 31.1131.440.030.03 INSIDE AIR FILM 0.680.68 4CURTAIN WALL BACK PAN 1/8" 0.61 1.64 3MINERAL WOOL WITH BLANKET...3" 0.04 inch SHADOW BOX 1/4" AIR CAVITY 1INSULATED COMPOSITE BACK-UP...1"3.453.70.290.29 OUTSIDE AIR FILM 0.170.25 Layer Material ThicknessWinterSummerWinterSummer Comments R-Value U-Value THERMAL PROPERTIES @ SHADOW BOX 1'-0" CURTAIN WALL SYSTEM-1 CWS1 Totals: 4.915.240.200.19 Inside Air Film 0.680.68 Curtain Wall Mullion 1/2" 0.61 1.64 1Insulated Glazing Unit (GLX) 1"3.453.70.290.2970 0.370.39 Outside Film 0.170.25 Layer Material ThicknessWinterSummerWinterSummer Comments R-Value U-Value Visible Transmittance Shading Coefficient Solar Heat Gain Coefficient THERMAL PROPERTIES MULLION (NOTE: ALL VALUES TO BE VERIFIED WITH SPECIFIED PRODUCTS DELETE THIS NOTE) 1'-0" STAINLESS STEEL TILE EWA-2 1'-0" FIBER REINFORCED CEMENTITIOUS PANELS EWA-1 FIBER REINFORCED CEMENTITIOUS PANELS 3"=1'- EWA-1A 3"=1'FIBER REINFORCED CEMENTITIOUS PANELS 3"=1'- EWA-1B EWA-1C CAST IN PLACE CONCRETE WALL Total Assembly: 44.9345.01 0.020.02=(R-Cavity R-Studs Percentage 90% 10% Totals: 45.0345.1144.0344.11 Inside Film 0.680.680.680.68 Gypsum Wallboard 5/8" 0.56 0.56 1.79 6Metal Studs Fiberglass Batt Insulation6 21 21 0.05 Exterior Sheathing 5/8" 0.67 0.67 1.49 Air/Vapor Barrier 1/16" 0.45 0.45 2.22 Mineral Wool Insulation 20 19 0.05 inch Space 3-3/4" 1.00 1Fiber Reinforced Concrete Panel3/8" 0.5 0.50 2.00 Outside Air Film 0.170.250.170.25 Layer Material ThicknessWinterSummerWinterSummerWinterSummer Comments R-Value CavityR-Value StudsU-Value THERMAL PROPERTIES Total Assembly: 34.9335.01 0.030.03=(R-Cavity R-Studs %) Percentage 90% 10% Totals: 35.0335.1134.0334.11 Inside Air Film 0.680.680.680.68 Gypsum Wallboard 5/8" 0.56 0.56 1.79 6Metal Studs w/ Fiberglass Batt Insulation6 0.05 Exterior Sheathing 5/8" 0.67 0.67 1.49 Air/Vapor Barrier 1/16" 0.45 0.45 2.22 Mineral Wool Insulation 0.10 inch Space 2-1/8" 1.00 1Fiber Reinforced Concrete Panel3/8" 0.50 2.00 Outside Film 0.170.250.170.25 Layer Material ThicknessWinterSummerWinterSummerWinterSummer Comments R-Value @ CavityR-Value StudsU-Value THERMAL PROPERTIES Total Assembly: 48.8348.91 0.020.02=(R-Cavity R-Studs %) Percentage 90% 10% Totals: 49.0349.1147.0347.11 Inside Film 0.680.680.680.68 Gypsum Wallboard 5/8" 0.56 0.56 1.79 6Metal Studs Fiberglass Batt Insulation8 0.04 Exterior Sheathing 5/8" 0.67 0.67 1.49 Air/Vapor Barrier 1/16" 0.45 0.45 2.22 Mineral Wool Insulation 0.05 inch Air Space 3-3/4" 1.00 1Fiber Reinforced Concrete Panel3/8" 0.5 0.50 2.00 Outside Air Film 0.170.250.170.25 Layer Material ThicknessWinterSummerWinterSummerWinterSummer Comments R-Value CavityR-Value StudsU-Value THERMAL PROPERTIES Total Assembly: 26.926.98 0.040.04=(R-Cavity R-Studs Percentage 90% 10% Totals: 27.0027.0826.0026.08 Inside Film 0.680.680.680.68 5Cast Place Concrete Wall 10" 4.2 4.2 0.24 R.42 inch Air/Vapor Barrier 1/16" 0.45 0.45 2.22 Mineral Wool Insulation 20 19 0.05 inch Space 2-5/8" 1.00 1Fiber Reinforced Concrete Panel3/8" 0.5 0.50 2.00 Outside Air Film 0.170.250.170.25 Layer Material ThicknessWinterSummerWinterSummerWinterSummer Comments R-Value CavityR-Value StudsU-Value THERMAL PROPERTIES 3"=1'Total Assembly: 39.5339.61 0.030.03=(R-Cavity R-Studs Percentage 90% 10% Totals: 39.6339.7138.6338.71 Inside Air Film 0.680.680.680.68 Gypsum Wallboard 5/8" 0.56 0.56 1.79 5Metal Studs Fiberglass Batt Insulation6 21 0.05 Exterior Sheathing 5/8" 0.67 0.67 1.49 Air/Vapor Barrier 1/16" 0.45 0.45 2.22 Rigid Insulation 4" 15 0.06 R-4 inch Stainless Steel Tile 0.018" 0.1 0.1 10.00 R-0.1 inch Outside Film 0.170.250.170.25 Layer Material ThicknessWinterSummerWinterSummerWinterSummer Comments R-Value CavityR-Value StudsU-Value THERMAL PROPERTIES -202 -203 -204 A51.2 1.8 2.6 3.6 C.2 A-302 A-302 E.6 F.4 A-301 SERVICE ELEV H2 H2.8 H3 SOUTH STAIR C5S NORTH STAIR C5N CRASH C5318 CORR C5007 PASSAGE C5303 CORR C5002 CORR C5003 CORR C5304 CORR C5302 PASSAGE C5307 CLEAN SUPPLY C5323 SOIL HOLD C5020 MEDS C5319 MULTI-DISCIPLINE WORKRM C5320 PARENT GALLEY C5314 BED CLEAN C5316 PARENT LOUNGE C5313 RT STOR C5331 EQ STOR C5019 SOIL HOLD C5335 EVS C5336 EQ STOR C5315 PROV WORK C5310 PARENT GALLEY C5028 ON CALL C5035 OC TLT C5036 STAFF TLT C5017 STAFF LOUNGE C5016 ABG LAB C5031 RESPITE C5015 NICU PAT RM 508 C5108 NICU PAT RM 509 C5109 NICU ISOLATION RM 510 C5110 NICU PAT RM 506 C5106 NICU PAT RM 505 C5105 NICU PAT RM 504 C5104 NICU PAT RM 502 C5102 NICU PAT RM 501 C5101 DOUBLE NICU PAT RM 503 C5103 NICU PAT RM 511 C5111 NICU PAT RM 512 C5112 NICU PAT RM 513 C5113 NICU PAT RM 516 C5116 NICU PAT RM 518 C5118 DOUBLE NICU PAT RM 519 C5119 NICU PAT RM 520 C5120 NICU PAT RM 521 C5121 NICU PAT RM 522 C5122 NICU PAT RM 517 C5117 PAT TLT C5105T PAT TLT C5104T PAT TLT C5107T PAT TLT C5106T NICU PAT RM 507 C5107 PAT TLT C5108T PAT TLT C5109T PAT TLT C5111T PAT TLT C5112T PAT TLT C5113T PAT TLT C5116T PAT TLT C5117T PAT TLT C5118T PAT TLT C5120T PAT TLT C5121T PAT TLT C5122T PAT TLT C5102T PAT TLT C5101T SMALL COMM CTR C5013 COMM CENTER C5317 ELEC C5324 IDF C5326 PROC RM 514 C5114 PARENT GALLEY C5012 NICU ANTE C5110A EVS C5334 RECEPTION C5327 WAITING C5306 IMG ALC C5034 STAFF TLT C5311 CORR C5004 ADA TLT C5119T ADA TLT C5110T ALC C5003B CORR C5001 NICU PAT RM 515 C5115 PAT TLT C5115T TRANSP STOR C5032 PASSAGE C5033 ADA TLT C5103T VENT DECONT C5332 CHARGE NRS C5014 ALC C5003A ALC C5002A ALC C5003C ALC C5003D ALC C5004A ALC C5302C ALC C5302B ALC C5302A ALC C5301B ALC C5301A LAUNDRY C5312 PUBLIC TLT C5322 PUBLIC TLT C5321 EQ STOR C5333 MEDS C5025 MULTI-DISCIPLINE WORKRM C5027 CLEAN SUPPLY C5023 COMM CENTER C5029 ASST. NURSE MGR OFFICE C5022 STAFF TLT C5024 PASSAGE C5308 CORR C5008 PASSAGE C5005 ELEC C5008A CORR C5011 SCRUB C5021 SCRUB C5328 STAFF LOCKER C5018 CONNECTOR C5701 SERVICE VEST. C5702 STOR C5703 37 35 G1 -205 -205 PUBLIC ELEV 1/2" 1/2" 1/2" 25' 53' 1/2" 26' 28' 32' 20' -205 CORR C5010 1/2" 1' 8 1/2" 16' 1/2" 1/2" C3 -205 22' 10" A01 F13 F12 152' F01 F10 F11 152' MATCHLINESEE: A105BMATCHLINE SEE A5/ -105A MATCHLINE SEE A5/ -105C MATCHLINE SEE A5/ -105A MATCHLINE SEE A5/ -105E MATCHLINE SEE A5/ -105A MATCHLINE SEE A5/ -105E 1/2" -420 F10 1/2" 1/2" 1/2" 1/2" CORR C5301 FLOOR PLAN LEGEND SHEET KEYNOTES FLOOR PLAN GENERAL NOTES Project Number Original Issue Sheet Number Sheet Name Project Status Project Designer Project Manager Project Architect Technology Engineer Civil Engineer Structural Engineer Mechanical Engineer Electrical Engineer Interior Designer Equipment Planner Wayfinding Sheet Reviewer Plumbing Engineer 4'8' 16' SCHEMATIC DESIGN ISSUE 01/28/2022 DESIGN DEVELOPMENT ISSUE 07/22/2022 CONSTRUCTION DOCUMENT ISSUE 02/14/2023 2/14/2023 4:33:30 PMAutodesk Docs://10325067_Niswonger Children's Hospital_2022/10325067-A-CENTRAL_NISWONGER CHILDRENS HOSPITAL _R22.rvt OVERALL - FIFTH FLOOR PLAN BALLAD HEALTH NISWONGER CHILDREN'S VERTICAL EXPANSION CONSTRUCTION DOCUMENT ISSUE 400 NORTH STATE OF FRANKLIN ROAD JOHNSON CITY, TENNESSEE 37604-6094 HDR Architecture 10325067 02/14/2023 4880 Sadler Road Suite 100 Glen Allen, VA 23060 Author CHRIS YAGO HAMED AALI KATHRYN BARRY LINDA SADLER JEFF COOKE MAX CONNOR JIM KOEHL MELISSA MOSELEY GEOFFREY BAGWELL BRIAN SWANSON 3/32" 1'-0" A4 OVERALL PLAN -FIFTH FLOOR PLAN 24.ALL ITEMS SHOWN WITH GRAY DASHED LINES ARE OWNER FURNISHED. ITEMS SHOWN WITH BLACK DASHED LINES ARE MEDICAL EQUIPMENT. 23.REFER TO EQ SERIES SHEETS FOR MEDICAL EQUIPMENT INFORMATION. 22.REFER TO SHEET A7.30 FOR CASEWORK DETAILS AND INFORMATION. 21.REFER TO SHEET A6.01 A6.02 FOR DOOR INFORMATION, SCHEDULES AND DETAILS. 20.REFER TO SHEET A4.42 FOR TYPICAL TOILET LAYOUTS AND A7.35 FOR TOILET ACCESSORY MOUNTING DIAGRAMS. 19.REFER TO SHEET A7.20 FOR PARTITION TYPES, GRAPHIC AND SYMBOLLIC DESIGNATIONS, NOTES, AND DETAILS. 18.VERIFY INTEGRITY OF ALL EXISTING WALLS SHOWN BE FIRE RATED. 17.ALL OUTSIDE CORNERS OF COUNTERS TO HAVE RADIUS. 16.COORDINATE ALL COUNTER TOP SUPPORT LOCATIONS WITH KNEESPACES. 15.CONTRACTOR PROVIDE MOUNTING SUPPORT TYPE FOR ALL OWNER FURNISHED CONTRACTOR INSTALLED EQUIPMENT U.N.O. 14.PROVIDE FIRE RATED GLASS DOOR VISION LIGHTS WHERE REQUIRED ACHIEVE SCHEDULED RATED DOOR LABEL. 13.PROVIDE END CAP AT PARTITIONS LOCATED DIRECTLY AGAINST EXTERIOR CURTAIN WALL. 12.PROVIDE ACOUSTIC PARTITION CLOSURE BETWEEN WALL END AND FACE OF GLASS. 11.CENTER WALLS ON EXTERIOR MULLIONS U.N.O. 10.PROVIDE SIDED PROTECTION ALL OUTLET BOXES RATED... 9.SOAP AND PAPER TOWEL DISPENSER WILL BE PROVIDED EACH SINK. TYPICAL MOUNTING SUPPORT "A". 8.HIGHER RATED FIRE WALLS TAKE PRECEDENCE OVER LOWER RATED WALLS ARE TO CONTINUE THROUGH ALL SUCH INTERSECTIONS. 7.REFER TO LIFE SAFETY SHEETS FOR ADDITIONAL FIRE SMOKE RATING REQUIREMENTS. 6.ALL DOOR FRAMES ARE TO BE INSTALLED AWAY OF ADJACENT PERPENDICULAR WALLS UNLESS NOTED OTHERWISE. 5.USE PARTITION TYPE "H3" UNLESS NOTED OTHERWISE. 4.REFER TO DEMOLITION DRAWINGS FOR WORK REQUIRED ADVANCE CONSTRUCTION AND COORDINATE ACCORDINGLY. 3.ALL DIMENSIONS ARE TO COLUMN CENTERLINES OR FACE OF FINISHED GWB WALLS OR SURFACES UNLESS NOTED OTHERWISE. 2.DO NOT SCALE DRAWINGS, DIMENSIONAL INFORMATION REQUIRED NOT FOUND, NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION. 1.DRAWINGS SPECIFICATIONS ARE COMPLIMENTARY COMPONENTS OF THE CONTRACT DOCUMENTS, REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR THE COMPLETE SCOPE OF WORK. NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION INCONSISTENCIES, CONTRADICTIONS OR OMISSIONS ARE DISCOVERED. F01 METAL COLUMN COVER F02 LINE OF CEILING SOFFIT ABOVE F06 EXISTING STRUCTURE TO REMAIN F10 EXISTING ELEVATOR CAB F11 EXPANSION JOINT F12 EXIST. EXTERIOR PLASTER INSULATION SYSTEM ON 1/2" GWB SHEATHING F13 EXIST. PRECAST CONCRETE PANEL F14 CENTER PARTITION ON WINDOW MULLION F15 ALIGN F16 COILING FIRE AND SMOKE RATED DOOR