Outdoor cables
FiberConnect® Universal cable with functional integrity 90 min
Fiber optic cables (SM / MM)
rodent protected , with central multi-fiber loose tube (2500 N)
Outer jacket Loose tube, gel-filled Rip cord inner fire protection tape Strain relief elements and rodent protection/outer fire protection tape
Functional integrity in the event of fire
U-D(ZN)BH n…FS Order no.
84 040 Q Q Q Q
Standardisation
IEC 60794-2
for at least 90 minutes
Description
Mechanical properties
Non-metallic, light and flexible cable with increased tensile
Min. bending radius static dynamic
strength that can be used both inside and outside buildings. Installation in cable ducts, on cable trays or in cable conduits.
15 × outer diameter 20 × outer diameter
Max. pull force on jacket
2500 N
Max. crush resistance
3000 N/dm
Composition Cable core
Loose tube, gel-filled
Fire performance
inner fire protection tape
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Multifunctional reinforced glass rovings,
Smoke density
IEC 61034
moisture blocking, as non-metallic strain
Absence of halogen IEC 60754-1
relief elements and rodent protection
Acidity of combus-
Cable jacket
Halogen-free, flame-retardant material
tion gases
Colour of jacket
O blue
Armour
IEC 60754-2
Functional integrity test Acc. to IEC 60 331-11, IEC 60 331-25 and EN 50200
Thermal properties
09
Transport/storage
– 25 °C to + 70 °C
Installation
– 5 °C to + 50 °C
Operating tempe-
– 20 °C to + 60 °C
90 min (VDE test report).
rature
Max. number of fibers
12 24
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
10.3 10.8
115 125
1.03 1.28
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
233
FiberConnect® Universal cable with functional integrity 120 min
Rip cord Outer jacket Corrugated steel conduit Inner jacket Loose tube, gel filled
Fiber optic cables (SM / MM)
rodent protected and transversely waterproof , with central multi-fiber loose tube (2500 N)
inner fire barrier Strain relief elements
Functional integrity in the event of fire
U-DQ(ZN)H(SR)H n… FS Order no.
84 047 Q Q Q Q
Standardisation
IEC 60794-2
for at least 120 minutes
Description
Mechanical properties
Mechanically rugged cable with increased tensile strength
Min. bending radius static dynamic
that can be used both inside and outside buildings. Installation in cable ducts, on cable trays or in cable conduits.
15 × outer diameter 20 × outer diameter
Max. pull force on jacket
2500 N
Max. crush resistance
2500 N/dm
Composition Cable core
Loose tube,
Fire performance
gel-filled inner fire barrier
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Non-metallic (glass rovings),
Smoke density
IEC 61034
moisture blocking
Absence of halogen IEC 60754-1
Inner jacket
Halogen-free and flame-retardant
Acidity of combus-
Corrugated
as fire barrier and
tion gases
steel conduit
rodent protection
Outer jacket
Halogen-free, flame-retardant material
Functional integrity test
Colour of jacket
O blue
Acc. to IEC 60 331-11, IEC 60 331-25 and EN 50200
Strain relief
IEC 60754-2
120 min (VDE test report). Thermal properties Transport/storage
– 25 °C to + 70 °C
Installation
– 5 °C to + 50 °C
Operating tempe-
– 20 °C to + 60 °C
rature
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24
12.5 12.5
215 215
2.8 2.8
www.leoni-fiber-optics.com
09
234
Outdoor cables
FiberConnect® Universal cable with stranded tight buffered fibers
Fiber optic cables (SM / MM)
rodent-protected
Outer jacket Rip cord Tight buffered or semi-tight buffered fiber Swelling tape GFR central strength member Strain relief elements and rodent protection
U-VQ(ZN)BH n… 84 Q Q Q Q Q Q Q Order no.
with UV-resistant FRNC material:
84 045 Q Q Q Q Standardisation
IEC 60794-2
Description
Thermal properties
Cable for use inside and outside buildings. Installation in cable
Transport/storage
– 25 °C to + 70 °C
ducts, on cable trays or in cable conduits. Non-metallic universal
Installation
– 5 °C to + 50 °C
cable for direct connector assembly.
Operating tempe-
– 20 °C to + 60 °C
Suitable for all types of installation in protective conduits.
rature Mechanical properties
Composition Cable core
Min. bending radius static GFR central strength member with
dynamic
15 × outer diameter 20 × outer diameter
stranding elements, designed as tight
Max. pull force on jacket
2500 N
buffered (TB) or semi-tight buffered
Max. crush resistance
1000 N/dm
(STB) fiber and, if applicable, dummy elements.
Fire performance
Multifunctional reinforced glass rovings
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
moisture-blocking as non-metallic strain
Smoke density
IEC 61034
relief elements and rodent protection
Absence of halogen IEC 60754-1
Cable jacket
Halogen-free, flame-retardant material
Acidity of combus-
Colour of jacket
O yellow
tion gases
Armour
09
Number of fibers
4 6 8 10 12 16 20 24
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
130 130 130 145 145 150 150 155
1.03 1.03 1.03 1.21 1.21 1.37 1.37 1.44
9.4 9.4 9.4 9.8 9.8 10.8 10.8 11.1
IEC 60754-2
Order no. TB
84950890 Q 84950251Q 84950891Q 84950892Q 84950893Q 84950906Q 84950895Q 84950896Q
TB900L TB900L TB900L TB900L TB900L TB900L TB900L TB900L
Order no. STB
84950495Q 84950910Q 84950712Q 84950911Q 84950522Q 84950912Q 84950913Q 84950914Q
STB900 STB900 STB900 STB900 STB900 STB900 STB900 STB900
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
235
Outer jacket Out Str Strain relief elements and rodent protection
Fiber optic cables (SM / MM)
FiberConnect® Universal cable with central multi-fiber loose tube (1750 N) rodent-protected
Loose tube, gel-filled Loo
U-DQ(ZN)BH n… 1750 N 84 025 Q Q Q Q with UV resistant FRNC material:
84 043 Q Q Q Q
Order no.
with material suited for direct burial:
84 068 Q Q Q Q Standardisation
IEC 60794-2
Description
Thermal properties
Non-metallic, light and flexible cable that can be used both
Transport/storage
– 25 °C to + 70 °C
inside and outside buildings. Installation in cable ducts, on cable
Installation
– 5 °C to + 50 °C
trays or in cable conduits.
Operating tempe-
– 20 °C to + 60 °C
rature Composition
Mechanical properties
Cable core
L oose tube, gel-filled
Armour
Multifunctional glass rovings, moisture
Min. bending radius static dynamic
15 × outer diameter 20 × outer diameter
blocking as non-metallic strain relief
Max. pull force on jacket
1750 N
elements and rodent protection
Max. crush resistance
1500 N/dm
Cable jacket
Halogen-free, flame-retardant material
Colour of jacket
O yellow
Fire performance Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. C
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Acidity of combustion gases
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24
7.0 7.5
55 60
0.71 0.79
www.leoni-fiber-optics.com
IEC 60754-2
09
236
Outdoor cables
Fiber optic cables (SM / MM)
FiberConnect® Universal cable with central multi-fiber loose tube (2500 N) rodent-protected
Outer jacket Rip cord Strain relief elements and rodent protection L oose tube, gel-filled
U-DQ(ZN)BH n… 2500 N 84 032 Q Q Q Q with UV resistant FRNC material:
Order no.
84 076 Q Q Q Q with material suited for direct burial:
84 052 Q Q Q Q Standardisation
IEC 60794-2
Description
Thermal properties
Non-metallic, light and flexible cable with increased tensile
Transport/storage
– 25 °C to + 70 °C
strength that can be used both inside and outside buildings.
Installation
– 5 °C to + 50 °C
Installation in cable ducts, on cable trays or in cable conduits.
Operating tempe-
– 20 °C to + 60 °C
rature Composition Cable core Armour
Loose tube, gel-filled
Mechanical properties
multifunctional, reinforced glass rovings,
Min. bending radius static
moisture blocking as non-metallic strain
dynamic
15 × outer diameter 20 × outer diameter
relief elements and rodent - protection
Max. pull force on jacket
2500 N
Cable jacket
Halogen-free, flame-retardant material
Max. crush resistance
3000 N/dm
Colour of jacket
O yellow
09
Fire performance Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24
9.2 9.7
100 110
1.25 1.34
Acidity of combus-
IEC 60754-2
tion gases
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
237
Outer jacket Rip cord GFR strength member
Fiber optic cables (SM / MM)
FiberConnect® Universal cable with stranded multi-fiber loose tubes
L oose tube, gel-filled Taping
U-DH n×m… 84 029 Q Q Q Q Order no.
with UV resistant FRNC material:
84 049 Q Q Q Q Standardisation
IEC 60794-2
Description
Thermal properties
Non-metallic cable, can be used both inside and outside build-
Transport/storage
– 40 °C to + 70 °C
ings. Installation in cable ducts, on cable trays or in cable con-
Installation
– 5 °C to + 50 °C
duits.
Operating tempe-
– 40 °C to + 60 °C
rature Composition Cable core
GFR strength members with stranding
Mechanical properties
elements, designed as loose tubes and,
Min. bending radius static
if applicable, dummy elements
dynamic
15 × outer diameter 20 × outer diameter
Cable jacket
Halogen-free, flame-retardant material
Max. pull force on jacket
1500 N
Colour of jacket
O yellow
Max. crush resistance
2000 N/dm
Fire performance Flame retardancy
IEC 60332-1-2
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Acidity of combustion gases Number of tubes
1×m 2×m 3×m 4×m 5×m 6×m 8×m
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24 36 48 60 72 96
10.5 10.5 10.5 10.5 10.5 11.0 12.4
105 105 105 105 105 125 145
2.2 2.2 2.2 2.2 2.2 2.6 3.0
www.leoni-fiber-optics.com
IEC 60754-2
09
238
Outdoor cables
Fiber optic cables (SM / MM)
FiberConnect® Universal cable with stranded multi-fiber loose tubes rodent-protected
Strain relief elements and rodent protection Outer jacket Rip cord GFR strength member Loose tube, gel-filled Swelling tape
U-DQ(ZN)BH n×m… 84 033 Q Q Q Q with UV resistant FRNC material:
84 044 Q Q Q Q
Order no.
with material suited for direct burial:
84 055 Q Q Q Q Standardisation
IEC 60794-2
Description
Thermal properties
Non-metallic cable, can be used both inside and outside build-
Transport/storage
– 40 °C to + 70 °C
ings. Installation in cable ducts, on cable trays or in cable con-
Installation
– 5 °C to + 50 °C
duits.
Operating tempe-
– 40 °C to + 60 °C
rature Composition
Mechanical properties
Cable core
GFR strength member with stranding
Min. bending radius static
elements, desiged as loose tubes and, if Armour
dynamic
15 × outer diameter 20 × outer diameter
appliccable, dummy elements.
Max. pull force on jacket
6000 N
multifunctional reinforced glass rovings
Max. crush resistance
3000 N/dm
moisture blocking as non-metallic strain
09
relief elements and rodent protection
Fire performance
Cable jacket
Halogen-free, flame-retardant material
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Colour of jacket
O yellow
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Acidity of combus-
IEC 60754-2
tion gases Number of tubes
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m
Max. number of fibers
12 24 36 48 60 72 96 120 144
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12.5 12.5 12.5 12.5 12.5 13.4 14.4 15.9 17.7
185 185 185 185 185 200 225 250 305
3.1 3.1 3.1 3.1 3.1 3.2 3.4 3.7 4.5
All rodent-protected universal cables with stranded multi-fiber loose tubes are also availble in designs with different pull forces. Pull force
Order no.
4000 N
84069 Q Q Q Q
6000 N
84033 Q Q Q Q
9000 N
84058 Q Q Q Q
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
239
FiberConnect® Universal cable with central multi-fiber loose tube
Aluminium tape Strain relief elements and rodent protection Outer jacket Rip cord
Fiber optic cables (SM / MM)
transversely waterproof
Loose tube, gel-filled
U-DQ(ZN)(L)H n… 84 034 Q Q Q Q
Order no.
Description
Thermal properties
Can be used both inside and outside buildings. Installation in
Transport/storage
– 25 °C to + 70 °C
cable ducts, on cable trays, in cable conduits or directly in the
Installation
– 5 °C to + 50 °C
ground.
Operating tempe-
– 20 °C to + 60 °C
rature Composition Cable core
Loose tube, gel-filled
Mechanical properties
Strain relief
non-metallic (glass rovings),
Min. bending radius static dynamic
moisture blocking
15 × outer diameter 20 × outer diameter
Aluminium taping
as absolute moisture barrier
Max. pull force on jacket
2500 N
Cable jacket
Halogen-free, flame-retardant material
Max. crush resistance
1000 N/dm
Colour of jacket
O yellow Fire performance Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Acidity of combustion gases
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24
10.8 11.3
160 165
1.50 1.57
www.leoni-fiber-optics.com
IEC 60754-2
09
240
Outdoor cables
FiberConnect® Universal cable with central multi-fiber loose tube
Fiber optic cables (SM / MM)
rodent-protected, transversely waterproof
Strain relief elements Outer jacket Corrugated steel conduit Loose tube, gel-filled Inner jacket Rip cord
U-DQ(ZN)H(SR)H n… 84 051 Q Q Q Q with UV resistant FRNC material:
Order no.
84 044 Q Q Q Q with material suited for direct burial:
84 062 Q Q Q Q
Description
Thermal properties
Can be used both inside and outside buildings. Installation in
Transport/storage
– 25 °C to + 70 °C
cable ducts, on cable trays, in cable conduits or directly in the
Installation
– 5 °C to + 50 °C
ground.
Operating tempe-
– 20 °C to + 60 °C
rature Composition Cable core
Loose tube, gel-filled
Mechanical properties
Strain relief
non-metallic (glass rovings),
Min. bending radius static dynamic
moisture blocking
15 × outer diameter 20 × outer diameter
halogen-free, flame-retardant corrugated
Max. pull force on jacket
2500 N
steel conduit
as highly effective rodent protection
Max. crush resistance
2500 N/dm
Outer jacket
Halogen-free, flame-retardant material
Colour of jacket
O yellow
Inner jacket
Fire performance
09
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Acidity of combusMax. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24
12.5 12.5
215 215
2.80 2.80
IEC 60754-2
tion gases
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
241
FiberConnect® Universal cable with stranded multi-fiber loose tubes
Strain relief elements Outer jacket Aluminium tape GFR central strength member
Fiber optic cables (SM / MM)
transversely waterproof
Loose tube, gel-filled Swelling tape
U-DQ(ZN)(L)H n×m… 84 035 Q Q Q Q Order no.
with UV resistant FRNC material:
84 Q Q Q Q Q Q Q Description
Thermal properties
Can be used both inside and outside buildings. Installation in
Transport/storage
– 40 °C to + 70 °C
cable ducts, on cable trays, in cable conduits or directly in the
Installation
– 5 °C to + 50 °C
ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition Cable core
GFR central strength member with strand-
Mechanical properties
ing elements designed as gel-filled loose
Min. bending radius static
tubes and, if applicable, dummy elements Strain relief
dynamic
15 × outer diameter 20 × outer diameter
non-metallic (glass rovings),
Max. pull force on jacket
3000 N
moisture blocking
Max. crush resistance
1500 N/dm
Aluminium taping
as absolute moisture barrier
Cable jacket
Halogen-free, flame-retardant material
Fire performance
Colour of jacket
O yellow
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Smoke density
IEC 61034
Absence of halogen IEC 60754-1 Acidity of combustion gases
Number of tubes
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m
12 24 36 48 60 72 96 120 144
12.1 12.1 12.1 12.1 12.1 13.0 14.4 15.9 17.7
170 170 170 170 170 190 230 270 320
2.73 2.73 2.73 2.73 2.73 3.13 3.28 3.60 4.39
www.leoni-fiber-optics.com
IEC 60754-2
09
242
Outdoor cables
FiberConnect® Universal cable with stranded multi-fiber loose tubes
Fiber optic cables (SM / MM)
rodent-protected, transversely waterproof
Strain relief elements Outer jacket Corrugated steel conduit GFR strength member Loose tube, gel-filled Taping
U-DQ(ZN)(SR)H n×m… 84 037 Q Q Q Q Order no.
with UV resistant FRNC material:
84 046 Q Q Q Q Description
Thermal properties
Can be used both inside and outside buildings. Installation in
Transport/storage
– 40 °C to + 70 °C
cable ducts, on cable trays, in cable conduits or directly in the
Installation
– 5 °C to + 50 °C
ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition
Mechanical properties
Cable core
GFR strength members with stranding
Min. bending radius static
elements, designed as gel-filled loose Strain relief
dynamic
15 × outer diameter 20 × outer diameter
tubes and, if applicable, dummy elements
Max. pull force on jacket
3000 N
non-metallic (glass rovings),
Max. crush resistance
2000 N/dm
moisture blocking Corrugated steel
as highly effective rodent protection
conduit
Fire performance Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Cable jacket
Halogen-free, flame-retardant material
Smoke density
IEC 61034
Colour of jacket
O yellow
Absence of halogen IEC 60754-1
09
Acidity of combus- IEC 60754-2 tion gases
Number of tubes
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m
Max. number of fibers
12 24 36 48 60 72 96 120
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12.7 12.7 12.7 12.7 12.7 16.5 16.5 16.5
200 200 200 200 200 305 305 305
3.45 3.45 3.45 3.45 3.45 4.05 4.05 4.05
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
243
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Outer jacket Strain relief elements Inner jacket Corrugated steel conduit GFR strength member
Fiber optic cables (SM / MM)
rodent-protected, transversely waterproof
Loose tube, gel-filled Swelling tape Rip cord
U-DQ(ZN)H(SR)H nxm… UV Order no.
84 085 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Can be used both inside and outside buildings. Installation in
Transport/storage
– 40 °C to + 70 °C
cable ducts, on cable trays, in cable conduits or directly in the
Installation
– 5 °C to + 50 °C
ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition Cable core
Mechanical properties GFR strength member with stranding
Min. bending radius static
elements, designed as gel-filled loose
Strain relief
15 × outer diameter
dynamic
20 × outer diameter
tubes (Ø 2.4 mm) and, if applicable,
Max. pull force on jacket
4000 N
dummy elements. Swelling tape.
Max. crush resistance
3000 N/dm
non-metallic (glass rovings), moisture blocking
Fire performance
Inner jacket
Halogen-free, flame-retardant material
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Corrugated steel
as highly effective rodent protection
Smoke density
IEC 61034
conduit
Absence of halogen IEC 60754-1
Cable jacket
Halogen-free, flame-retardant material
Acidity of combus- IEC 60754-2
Colour of jacket
O yellow
tion gases
Number of tubes
09
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
mm
mm
12 24 36 48 60 72 96 144
16.7 16.7 16.7 16.7 16.7 18.8 18.8 21.0
360 360 360 360 360 430 430 510
4.15 4.15 4.15 4.15 4.15 4.63 4.63 5.33
340 340 340 340 340 380 380 420
250 250 250 250 250 285 285 315
1×m 2×m 3×m 4×m 5×m 6×m 8×m 12 × m
www.leoni-fiber-optics.com
Min. bending radius during installation
Min. bending radius installed
244
Outdoor cables
Fiber optic cables (SM / MM)
FiberConnect® Splittable outdoor cable
FRNC-Outer jacket Fleece FRNC subcable jacket GFR strength member Strain relief tight or semi-tight buffered fiber Rip cord
AT-VQ(ZN)HH n… 2.5 Order no.
84 202 Q Q Q Q
Standardisation
IEC 60794-2
Description
Thermal properties
Splittable outdoor cable for fixed installation in cable ducts and
Transport/storage
– 25 °C to + 70 °C
conduits. Suitable for direct connector assembly.
Installation
– 5 °C to + 50 °C
Operating tempe-
– 25 °C to + 60 °C
rature
Composition Cable core
GFR strength member in the core, over
Mechanical properties
that single elements designed as tight
Min. bending radius static dynamic
buffered (TB) and semi-tight buffered (STB) fiber, gel-filled with non-metallic strain
Max. crush resistance
15 × outer diameter 20 × outer diameter 1500 N/dm
relief elements (aramid) and halogen-free, flame-retardant subcable jacket (Ø 2.5
Fire performance
mm) stranded in layers (2–24)
Flame retardancy
IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Cable jacket
Halogen-free, flame-retardant material
Smoke density
IEC 61034
Colour of jacket
O black
Absence of halogen IEC 60754-1 Acidity of combus-
IEC 60754-2
tion gases
09
Number of fibers
2 4 6 8 10 12 16 18 20 24
Outer Ø
Wall thickness
Weight
Fire load
Max. pull force
mm
mm
kg/km
MJ/m
N
8.5 8.5 10.0 11.9 13.6 15.2 15.2 16.0 16.3 18.5
1.0 1.0 1.1 1.2 1.2 1.2 1.4 1.4 1.5 1.5
65 65 80 110 150 180 190 175 220 280
1.20 1.20 1.38 1.55 1.72 1.88 1.94 1.90 2.25 2.61
800 800 1200 1200 1200 1200 1200 1200 1200 1200
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
245
PE outer jacket Strain relief/rodent protection Fleece FRNC subcable jacket Rip cord GFR strength member
Fiber optic cables (SM / MM)
FiberConnect® Splittable outdoor cable
Strain relief tight or semi-tight buffered fiber
AT-VQ(ZN)H(ZN)B2Y n… 2.5 Order no.
84 205 Q Q Q Q
Standardisation
IEC 60794-2
Description
Thermal properties
Splittable, transversely water resistant outdoor cable with
Transport/storage
– 25 °C to + 70 °C
non-metallic rodent protection for fixed installation indoors
Installation
– 5 °C to + 50 °C
and outdoors in cable ducts, conduits and cable trays. The
Operating tempe-
– 20 °C to + 60 °C
single cables are longitudinally waterproof. For direct connector
rature
assembly.
Mechanical properties Min. bending radius static
Composition
dynamic
Cable core
GFR strength member in the core, over
Max. crush resistance
15 × outer diameter 20 × outer diameter 1500 N/dm
that breakout single elements designed as tight buffered (TB) or semi-tight buff-
Fire performance
ered (STB)f, gel-filled with non-metallic
Absence of halogen IEC 60754-1
strain relief elements (aramid) and a halo-
Acidity of combus-
gen -free flame retardant subcable jacket
tion gases
IEC 60754-2
(Ø 2.5 mm) stranded in layers (2–24) Armour
Multifunctional reinforced glass rovings as non-metallic strain relief elements and rodent protection
Cable jacket
Polyethylene
Colour of jacket
O black
Number of fibers
Outer Ø
Wall thickness
Weight
Fire load
mm
mm
kg/km
MJ/m
N
2 4 6 8 10 12 16 20 24
10.0 10.0 11.0 13.0 14.5 16.0 16.0 18.0 19.0
1.0 1.0 1.2 1.2 1.2 1.2 1.5 1.5 1.5
85 90 115 145 175 210 215 315 360
1.20 1.20 1.38 1.55 1.72 1.88 1.94 2.25 2.61
2500 2500 3000 3000 3000 3000 3000 3000 3000
www.leoni-fiber-optics.com
max. Pull force
09
246
Outdoor cables
Fiber optic cables (SM / MM)
FiberConnect® Outdoor cable with central multi-fiber loose tube (1750 N) rodent-protected
Outer jacket Loose tube, gel-filled Strain relief elements and rodent protection
A-DQ(ZN)B2Y n… 1750 N Order no.
84 305 Q Q Q Q
Standardisation
IEC 60794-3
Description
Mechanical properties
Light, flexible and non-metallic outdoor cable for primary cab-
Min. bending radius static dynamic
ling and the backbone area. For pulling into conduits, installation on cable trays or directly in the ground.
15 × outer diameter 20 × outer diameter
Max. pull force
1750 N
Max. crush resistance
1500 N/dm
Composition Cable core Armour
Loose tube, gel-filled
Fire performance
multifunctional glass rovings,
Absence of halogen IEC 60754-1
moisture blocking as strain relief and
Acidity of combus-
rodent protection
tion gases
Cable jacket
Polyethylene
Colour of jacket
O black
IEC 60754-2
Note The Polyethylene jacket offers good protection against transversal water ingress.
Thermal properties
09
Transport/storage
– 25 °C to + 70 °C
Installation
– 5 °C to + 50 °C
Operating tempe-
– 20 °C to + 60 °C
rature
Max. number of fibers
12 24
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
7.0 7.5
42 47
1.10 1.20
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
247
Outer jacket Loose tube, gel-filled
Fiber optic cables (SM / MM)
FiberConnect® Direct buried cable
Strain relief elements
A-DQ(ZN)2Y n… 1750 N ZB Order no.
84 375 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Light, flexible and non-metallic outdoor cable for primary
Transport/storage
– 40 °C to + 70 °C
cabling and the backbone area. For pulling into contduits, instal-
Installation
– 5 °C to + 50 °C
lation on cable trays or directly in the ground.
Operating tempe-
– 40 °C to + 60 °C
rature Mechanical properties
Composition Cable core
Min. bending radius static
Two-layer loose tube, gel-filled,
dynamic
diameter 3.5 mm ( up o 12 fibers),
15 × outer diameter 20 × outer diameter
4.0 mm (to 24 fibers)
Max. pull force
1750 N
Colour: yellow (E9/125), green (G50/125)
Max. crush resistance
2000 N/dm
and blue (G62.5/125). Strain relief
Non-metallic (aramid)
Fire performance
Cable jacket
Polyethylene
Absence of halogen IEC 60754-1
Colour of jacket
O black
Acidity of combus-
IEC 60754-2
tion gases
09
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
7.0 7.5
37 42
1.5 1.7
12 24
www.leoni-fiber-optics.com
248
Outdoor cables
Fiber optic cables (SM / MM)
FiberConnect® Outdoor cable with central multi-fiber loose tube (2500 N) rodent-protected
Outer jacket n ds a Withsta of e rc pull fo
25 u p to
Rip cord Loose tube, gel-filled
00 N
Strain relief elements and rodent protection
A-DQ(ZN)B2Y n… 2500 N Order no.
84 321 Q Q Q Q
Standardisation
IEC 60794-3
Description
Mechanical properties
Non-metallic construction for primary cabling and the back-
Min. bending radius static dynamic
bone area. For pulling into conduits, installation on cable trays or directly in the ground.
15 × outer diameter 20 × outer diameter
Max. pull force
2500 N
Max. crush resistance
3000 N/dm
Composition Cable core Armour
Loose tube, gel-filled
Fire performance
multifunctional reinforced glass rovings,
Absence of halogen IEC 60754-1
moisture blocking as strain relief and
Acidity of combus-
rodent protection
tion gases
Cable jacket
Polyethylene with imprint
Colour of jacket
O black
IEC 60754-2
Note The Polyethylene jacket offers good protection against transversal water ingress.
Thermal properties
09
Transport/storage
– 25 °C to + 70 °C
Installation
– 5 °C to + 50 °C
Operating tempe-
– 20 °C to + 60 °C
rature
Max. number of fibers
12 24
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
9.2 9.7
76 81
1.90 2.00
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
249
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Outer jacket Swelling tape Rip cord Loose tube, gel-filled
Fiber optic cables (SM / MM)
rodent-protected, dry core
Strain relief elements and rodent protection GFR strength member
A-DQ(ZN)B2Y n×m… Order no.
84 316 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Non-metallic, rugged outdoor cable. Installation-friendly
Transport/storage
– 40 °C to + 70 °C
because of the grease-free cable core. Installation in conduits,
Installation
– 5 °C to + 50 °C
on cable trays and directly in the ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition
Mechanical properties GFR strength member with stranding ele-
Cable core
Min. bending radius static
ments designed as gel-filled loose tubes and, Armour
dynamic
15 × outer diameter 20 × outer diameter
if applicable, dummy elements
Max. pull force
4000 N
multifunctional reinforced glass rovings
Max. crush resistance
3000 N/dm
as non-metallic strain relief elements and rodent protection
Fire performance
Cable jacket
Polyethylene with hot stamped marking
Absence of halogen IEC 60754-1
Colour of jacket
O black
Acidity of combus-
IEC 60754-2
tion gases
09 Note Q
The Polyethylene jacket offers good protection against transversal water ingress
Number of tubes
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m 16 × m 24 × m
12 24 36 48 60 72 96 120 144 192 288
11.4 11.4 11.4 11.4 11.4 12.3 13.7 15.2 17.0 17.3 20.2
115 115 115 115 115 135 160 190 230 240 320
4.1 4.1 4.1 4.1 4.1 4.5 5.0 5.5 6.2 6.2 6.2
www.leoni-fiber-optics.com
Q
Higher fiber counts and pull forces on request
Q
Also available with aluminium layer or corrugated steel jacket.
All rodent-protected universal cables with stranded multi-fiber loose tubes are also available with different pull forces. Pull force
Order no.
4000 N
84316 Q Q Q Q
6000 N
84346 Q Q Q Q
9000 N
84330 Q Q Q Q
250
Outdoor cables
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Fiber optic cables (SM / MM)
grease-filled
Outer jacket Swelling tape Loose tube, gel-filled Core filling Strain relief elements GFR strength member
A-DF(ZN)2Y n×m… Order no.
84 300 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Non-metallic cable for primary cabling and the backbone area.
Transport/storage
– 40 °C to + 70 °C
For pulling into conduits, installation on cable trays or directly in
Installation
– 5 °C to + 50 °C
the ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition Cable core
GFR strength member with stranding
Mechanical properties
elements, designed as gel-filled loose
Min. bending radius static dynamic
tubes and, if applicable, dummy elements. Cable core filled with petroleum jelly
Max. pull force
15 × outer diameter 20 × outer diameter
≤ 7 stranding element 3000 N > 7 stranding element 4000 N
Strain relief
Glass rovings
Cable jacket
Polyethylene with hot stamped marking
Colour of jacket
O black
Max. crush resistance
3000 N/dm
Fire performance Absence of halogen IEC 60754-1 Acidity of combus-
09
IEC 60754-2
tion gases Note Q
Number of tubes
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m 16 × m
Max. number of fibers
12 24 36 48 60 72 96 120 144 192
Outer Ø
Weight
transversal water ingress
Fire load
mm
kg/km
MJ/m
11.4 11.4 11.4 11.4 11.4 12.3 13.7 15.2 17.0 16.8
120 120 120 120 120 135 170 200 240 255
4.3 4.3 4.3 4.3 4.3 4.6 5.1 5.7 6.5 7.4
The Polyethylene jacket offers good protection against
Q
Also available with aluminium layers, corrugated steel jacket and copper elements
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
251
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Core filling Outer jacket Corrugated steel conduit Inner jacket Rip cord
Fiber optic cables (SM / MM)
rodent-protected, grease-filled
Swelling tape Loose tube, gel-filled Strain relief elements GFR strength member
A-DF(ZN)2Y(SR)2Y n×m… Order no.
84 310 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Rugged outdoor cable for primary cabling and the backbone
Transport/storage
– 40 °C to + 70 °C
area. For pulling into contduits, installation on cable trays or
Installation
– 5 °C to + 50 °C
directly in the ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition Cable core
GFR strength member with stranding
Mechanical properties
elements designed as gel-filled loose tubes
Min. bending radius static dynamic
and, if applicable, dummy elements. Cable core filled with petroleum jelly.
Max. pull force
Glass rovings
Inner jacket
Polyethylene, O black
Corrugated steel
as highly effective rodent protection
≤ 7 stranding elements 3000 N
Max. crush resistance
3000 N/dm
Fire performance
conduit Cable jacket
Polyethylene with hot stamped marking
Absence of halogen IEC 60754-1
Colour of jacket
O black
Acidity of combustion gases
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m 16 × m
20 × outer diameter
> 7 stranding elements 4000 N
Strain relief
Number of tubes
15 × outer diameter
Max. number of fibers
12 24 36 48 60 72 96 120 144 192
www.leoni-fiber-optics.com
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
16.7 16.7 16.7 16.7 16.7 17.5 18.8 21.8 21.8 21.8
275 275 275 275 275 335 335 335 370 380
10.4 10.4 10.4 10.4 10.4 12.0 12.0 12.5 13.1 13.8
IEC 60754-2
09
252
Outdoor cables
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Fiber optic cables (SM / MM)
rodent-protected, transversely waterproof
PE outer jacket Corrugated steel conduit PE inner jacket Rip cord Strain relief Swelling tape Loose tube GFR strength member
A-DQ(ZN)2Y(SR)2Y n×m… Order no.
84 329 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Dry-core, longitudinally and transversely waterproof fiber optic
Transport/storage
– 40 °C to + 70 °C
outdoor cable with highly effective rodent protection. For direct
Installation
– 5 °C to + 50 °C
burial, installation in conduits, ducts or on trays, also suited for
Operating tempe-
– 40 °C to + 60 °C
vertical ladders.
rature
Suitable for all installation techniques (e. g. pulling and blowing in). Mechanical properties Composition
Min. bending radius static
Cable core
dynamic
GFR strength member with stranding elements, designed as gel-filled loose
Max. pull force
tubes (Ø 2.4 mm) and, if applicable, dummy elements
> 7 stranding elements 4000 N Max. crush resistance
1000 N/dm
Glass rovings
Inner jacket
Polyethylene
Fire performance
Corrugated steel
as highly effective rodent protection
Absence of halogen IEC 60754-1 Acidity of combus-
Cable jacket
Polyethylene with hot stamped marking
Colour of jacket
O black
Composition
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/km
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m
12 24 36 48 60 72 96 120 144
16.7 16.7 16.7 16.7 16.7 16.7 18.8 21.0 21.0
275 275 275 275 275 275 340 335 370
10.4 10.4 10.4 10.4 10.4 12.0 12.0 12.5 13.1
20 × outer diameter
≤ 7 stranding elements 3000 N
Strain relief
conduit
09
15 × outer diameter
IEC 60754-2
tion gases
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
253
FiberConnect® Outdoor cable with central multi-fiber loose tube
Outer jacket Aluminium tape Rip cord Loose tube, gel-filled
Fiber optic cables (SM / MM)
transversely waterproof
Strain relief elements
A-DQ(ZN)(L)2Y n… Order no.
84 333 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Light outdoor cable with diffusion barrier. Installation in cable
Transport/storage
– 25 °C to + 70 °C
ducts, on cable trays, in cable conduits or directly in the ground.
Installation
– 5 °C to + 50 °C
Operating tempe-
– 20 °C to + 60 °C
rature
Composition Cable core
Loose tube, gel-filled
Strain relief
non-metallic (glass rovings),
Mechanical properties
moisture blocking
Min. bending radius static dynamic
15 × outer diameter 20 × outer diameter
Alumimium taping
as absolute moisture barrier
Cable jacket
Polyethylene with imprint
Max. pull force
2500 N
O black
Max. crush resistance
1000 N/dm
Colour of jacket
Fire performance Absence of halogen IEC 60754-1 Acidity of combustion gases
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12 24
10.8 11.3
128 135
1.42 1.62
www.leoni-fiber-optics.com
IEC 60754-2
09
254
Outdoor cables
FiberConnect® Outdoor cable with central multi-fiber loose tube
Fiber optic cables (SM / MM)
rodent-protected, transversely waterproof
Outer jacket Corrugated steel conduit Inner jacket Rip cord Loose tube, gel-filled Strain relief elements
A-DQ(ZN)2Y(SR)2Y n… Order no.
84 331 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Rugged outdoor cable for installation in cable ducts, conduits,
Transport/storage
– 40 °C to + 70 °C
on cable trays or directly in the ground.
Installation
– 5 °C to + 50 °C
Operating tempe-
– 40 °C to + 70 °C
rature
Composition Cable core
loose tube, gel-filled
Strain relief
non-metallic (glass rovings),
Mechanical properties
moisture blocking
Min. bending radius static dynamic
Inner jacket
Polyethylene, O black
Corrugated steel
as highly effective rodent protection
conduit Outer jacket
Polyethylene with imprint
Colour of jacket
O black
15 × outer diameter 20 × outer diameter
Max. pull force
2500 N
Max. crush resistance
2500 N/dm
Fire performance Absence of halogen IEC 60754-1 Acidity of combus-
IEC 60754-2
tion gases
09
Number of fibers
12 24
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
12.5 12.5
160 160
1.8 1.8
www.leoni-fiber-optics.com
FiberConnect®
FiberTech ®
FiberSwitch ®
FiberSplit®
Outdoor cables
255
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Outer jacket Aluminium tape Rip cord Swelling tape
Fiber optic cables (SM / MM)
transversely waterproof
Loose tube, gel-filled Strain relief elements GFR strength member
A-DQ(ZN)(L)2Y n×m… Order no.
84 326 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Rugged outdoor cable with diffusion barrier. For installation
Transport/storage
– 40 °C to + 70 °C
in cable ducts and conduits, on cable trays or directly in the
Installation
– 5 °C to + 50 °C
ground.
Operating tempe-
– 40 °C to + 60 °C
rature Composition Cable core
GFR strength member with stranding
Mechanical properties
elements, designed as gel-filled loos tubes
Min. bending radius static dynamic
and , if applicable, dummy elements Strain relief
15 × outer diameter 20 × outer diameter
Non-metallic (glass rovings),
Max. pull force
3000 N
moisture blocking
Max. crush resistance
1500 N/dm
Aluminium taping
as absolute moisture barrier
Cable jacket
Polyethylene with hot stamped marking
Fire performance
Colour of jacket
O black
Absence of halogen IEC 60754-1 Acidity of combustion gases
Number of tubes
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
1×m 2×m 3×m 4×m 5×m 6×m 8×m 10 × m 12 × m
12 24 36 48 60 72 96 120 144
12.1 12.1 12.1 12.1 12.1 13.0 14.4 15.9 17.7
140 140 140 140 140 160 200 240 280
4.9 4.9 4.9 4.9 4.9 5.6 5.9 6.4 7.2
www.leoni-fiber-optics.com
IEC 60754-2
09
256
Outdoor cables
FiberConnect® Outdoor cable with stranded multi-fiber loose tubes
Fiber optic cables (SM / MM)
rodent-protected, transversely waterproof
Outer jacket Corrugated steel conduit Rip cord Loose tube,gel-filled Strain relief elements GFR strength member Fleece
A-DQ(ZN)(SR)2Y n×m… Order no.
84 334 Q Q Q Q
Standardisation
IEC 60794-3
Description
Thermal properties
Rugged outdoor cable for installation in cable ducts or conduits,
Transport/storage
– 40 °C to + 70 °C
on cable trays or directly in the ground.
Installation
– 5 °C to + 50 °C
Operating tempe-
– 40 °C to + 60 °C
rature
Composition Cable core
GFR strength member with stranding
Strain relief
elements, designed as gel-filled loose
Mechanical properties
tubes and , if applicable, dummy elements
Min. bending radius static dynamic
Non-metallic (glass rovings),
15 × outer diameter 20 × outer diameter
moisture blocking
Max. pull force
3000 N
as highly effective rodent protection
Max. crush resistance
2000 N/dm
Cable jacket
Polyethylene with hot stamped marking
Fire performance
Colour of jacket
O black
Absence of halogen IEC 60754-1
Corrugated steel conduit
Acidity of combus-
IEC 60754-2
tion gases
09
Number of tubes
Max. number of fibers
Outer Ø
Weight
Fire load
mm
kg/km
MJ/m
1×m 2×m 3×m 4×m 5×m
12 24 26 48 60
12.7 12.7 12.7 12.7 12.7
165 165 165 165 165
4.6 4.6 4.6 4.6 4.6
www.leoni-fiber-optics.com