Scroll Condensing Units
n Quiet and efficient Copeland scroll hermetic compressors n Generous wide finned, low noise level condensers supplied with protective coil coating n Wide range of factory fitted accessories available n Specifically designed for Australasian conditions
SR Medium / High
5.1 6.5 hp
MODEL
Nom. hp
SRS510
5.1
R134a
5015
6245
7655
R404A
6475
7750
9560
11205
R22
6180
7455
9190
11015
12990
14935
SR510
5.1
R134a
5015
6245
7655
9190
11060
12690
R404A
6475
7750
9560
11205
13055
14860
R22
6180
7455
9190
11015
12990
14935
SRS550
5.5
R134a
5455
6465
8045
9715
11910
14200
R404A
7105
9110
10960
12445
14190
16290
R22
6780
8760
10540
12225
14090
16375
SR550
5.5
R134a
5455
6465
8045
9715
11910
14200
R404A
7105
9110
10960
12445
14190
16290
R22
6780
8760
10540
12225
14090
16375
SR600
6.0
R134a
6015
7465
9055
10985
13040
15025
R404A
8370
9810
11825
13615
15720
17985
R22
7995
9435
11365
13380
15610
18095
SR650
6.5
R134a
6710
8290
9990
12075
14300
16675
R404A
9080
10775
13135
15285
17740
20670
R22
8685
10360
12650
15020
17620
20800
Refrigerant
www.pattonaustralia.com.au
-15
-10
Evaporating Temp 째C -5 0 5
10
15
9190
11060
12690
13055
14860
SR SCROLL MED/HIGH
CAPACITY (Watts) @ 38째C Ambient *
DIMENSIONS:
SR(S)510, SR(S)550, SR600
SR650
NTS (mm) Accessories not shown
TECHNICAL DATA:
COMPRESSOR MODEL
NOM. hp
MODEL
VOLTAGE
CONDENSER Fan Motor (1)
DISP. m3/hr
RLA Amps
LRA Amps
Airflow l/sec
Watts
RECEIVER
CONNECTIONS (3)
Amps
Capacity (kg) (2)
Receiver Outlet Valve
Comp Suct Valve
Noise Level (dbA) (4)
Weight (kg)
SRS510
5.1
ZR61KCE-PFZ 220-240/1/50
14.4
30.0
150.0
1470
290
1.5
8.8
5/8”FSw
7/8”FSw
59
109
SR510
5.1
ZR61KCE-TFD 380-420/3/50
14.4
11.0
65.5
1470
290
1.5
8.8
5/8”FSw
7/8”FSw
59
109
SRS550
5.5
ZR68KCE-PFJ 220-240/1/50
16.2
31.0
150.0
1470
290
1.5
8.8
5/8”FSw
7/8”FSw
58
111
SR550
5.5
ZR68KCE-TFD 380-420/3/50
16.2
10.0
74.0
1470
290
1.5
8.8
5/8”FSw
7/8”FSw
58
111
SR600
6.0
ZR72KCE-TFD 380-420/3/50
17.1
13.0
74.0
1550
520
3.0
8.8
5/8”FSw
7/8”FSw
61
114
SR650
6.5
ZR81KCE-TFD 380-420/3/50
19.2
15.0
101.0
1670
520
3.0
8.8
5/8”FSw
7/8”FSw
62
123
NOTES: 1. Fan motors are suitable for 220-240/1/50 2. R404A pump down capacity shown @ 80% full for 32°C liquid temperature 3. Max valve connection size shown. May reduce for different refrigerants & applications 4. All noise level ratings are “free field” based at a distance of 3 metres from source and are given as a guide only
5. *Capacity ratings are based on suction gas returning to compressor @ 20°C, without liquid sub-cooling. Ratings may be increased by approximately 1% for every 1.1°K of sub-cooling 6. Standard condensers fitted. Ratings must not be extrapolated 7. Check with Patton’s nearest outlet for applications outside the specified range 8. Pictured unit configuration subject to change and selected accessory options. The company reserves the right to make specification changes without notice. 11/03/10
www.pattonaustralia.com.au