Deutz-1

Page 1

Tide Power System TCM180 Diesel generator sets (50Hz-60Hz)

Generator Set Powered by DCEC CUMMINS They have the features as below: ¾ ¾

Composed of LEROY-SOMER alternator 10 Hours Base Fuel Tank (for below 50kVA) 8 Hours Base Fuel Tank (for below 500kVA)

¾

Equipped with MCCB

¾

Tide 3.0 Control Panel (standard)

¾

Wiring with IEC standard

¾

All the generator sets are equipped with industry silencer and residential silencer be optional

¾

Base are made with strong steel frame and with special touch.

¾

Soundproof or Canopy is optional.

Main Specification 50Hz-60Hz Genset Model

TCM 180

Voltage Available as below:

Rated Voltage

400V/230V

416V/240V

Prime Power

144kW180kVA

160kW/200kVA

380-208V 440-480/240V

Standby Power

158kW/198kVA

176kW/220kVA

Note: Any special voltage is also available for us and

Engine Model

6CTA8.3- G1/G2

Alternator Model Connection Rated Speed Ratted Current Governing

380-400-415V/220-230-240V 220V/440V

50Hz 60Hz

contact us for details.

LSA46.2M3 3 Phase 4 Wire

Ambient reference condition:

1500rpm

1800rpm

259

278 M/E

Altitude: 1000m Ambient Temperature: 40℃ Note: Contact us for details if there is different ambient.

(1) E: Electronic speed governor; M: Mechanical speed governor. (2) Power Factor: 4 Pole Partner alternators are designed to operate between 0.8 and 1 power factor. A derating is necessary below 0.8 power factor. (3)G1: Mechanical governing; G2: Electrical governing.

Dimensions

50Hz

60Hz

Dimension (mm)

Weight (kg)

Dimension (mm)

Weight (kg)

Open Type

2400×900×1650

1550

2400×900×1650

1550

Sound Proof

3000×1080×1650

2850

3000×1080×1650

2850


Tide Power System TCM180 Diesel generator sets (50Hz-60Hz) Engine DCEC CUMMINS 6CTA8.3- G1/G2 Displacement 8.3L Air intake way Air-air -cooled, turbo-charged Cylinder Bore 102mm Cylinder quantity 6 kW Stroke 120mm 163 Speed-droop 5% 179 Fuel system A pump_RSV Mechanical/WeiFu WuXi (G1) PB pump_GAC governor/NYC ASIMCO (G2)

@rpm 1500 1800

Exhaust System Max. back pressure

76mmHg

Diameter of exhaust pipe recommend

100mm

Engine Power Engine Speed

Air Intake system Diameter of intake pipe recommended

kW

180

198

Power

HP

241

265

Base

kW

163

179

Output

HP

219

241

Continuous

kW

133

146

Power

HP

178

196

Lubrication system 121℃

Oil pan capacity (Max_Min)

18.9_15.1

Lubrication system Min. Capacity

23.8L

Fuel system Total fuel overflow amount

1800rpm

Standby

125mm

Max. oil temp. permitted in oil pan

1500rpm

208L/h

Cooling system

Fuel Consumption curve

Coolant capacity-engine only

12.3L

Thermostat adjusting temperature (range)

83_95℃

Max. coolant temp. permitted_standby

104℃

Electric system Starter

12V/24V

Battery charging system

63A/40A 950CCA/

Min. battery capacity_-12℃

475CCA

Technical data Piston speed

6.8m/s

Engine coolant flow

3.3m/s

Air intake flow

192L/s

Exhaust flow

519L/s

Fuel Consumption (L/h) L/h

Standby Power

100% of prime power

75% of prime power

50% of prime power

25% of prime power

50Hz

45

40

30

20

11

60Hz

50

44

33

22

12

Excuse for none notice anymore in case of data changed.


Tide Power System TCM180 Diesel generator sets (50Hz-60Hz)

Control System

TIDE 2.0 With HGM170 Control Module, the functions as below:

As an option we also have DSE 702 (DEEP SEA) control module to be chosen: FEATURES: ¾ Manual start ¾ Engine pre-heat ¾ Engine monitoring and protection features ¾ Protected solid state (PSS) outputs ¾ Front panel mounting ¾ Tamper proof engine hours counter ¾ Remote start ¾ LED indicators ¾ For less than 4 cylinder engine only BENEFITS ¾ Hours counter provides accurate information for monitoring maintenance and warranty periods. ¾ Multiple engine parameters are monitored simultaneously OVERSPEED PROTECTION The engine over speed trip setting can be calibrated at the rear of the module for 50Hz or 60Hz nominal operation (57Hz or 68Hz trip respectively). During engine cranking and for the first 10 seconds after the engine starts running , all alarm conditions are suspended (overspeed is enabled) to allow the engine to reach its optimum running speed.


Tide Power System TCM180 Diesel generator sets (50Hz-60Hz)

TIDE 3.0 With HGM6110 (Standard) control module Main Features

HGM6110

Display

LCD

Language

Chinese/English

Hours

Plug-pull terminal

Com port

Link

Fix Input

1

Config Input

2

Fix output

2

Config output

4

Analog Input

3

Generator Data

Engine Data

Fuel Level

Over speed

High engine temp.

Low oil pressure

Fail to start

Over voltage

Under voltage

Over current

Short circuit

Idle control

HGM6110

DSE7210

HGM6310

TIDE 3.0 has HGM6310 and DSE7210 for your option. HGM6310 has RS232/RS485 com port.

For your reference, we also have TIDE4.0, TIDE 5.0 and TIDE6.0 to fulfill your different requirements. TIDE 4.0 with DSE 7310 Control module has the function of supervising. TIDE 5.0 with DSE 7510 Control module mainly used in parallel operation, self synchronization, active and reactive power regulations. TIDE 6.0 with DSE 7520 Control module is applicable to parallel with mains, add GSM function if it is necessary.


Tide Power System TCM180 Diesel generator sets (50Hz-60Hz) Soundproof and Container Soundproof Canopy Soundproof Canopy which produced by Tide Power System not only meets with the sound control requirement, but also ensure cooling aeration request by normal operation. All the Gensets could be installed in the open air to save space. Features: ¾ Adopt assembly instruction which is facilitated to maintain. ¾ Special high-temperature flame-retardant sound insulation sponge. ¾ Slap-up hinge and door handle. ¾ Steel Plate of the soundproof canopy is 2mm. ¾ Soundproof cotton is 30mm each side. ¾ Noise Level: 75~78dB within 1m; 72~74dB within 7m. ¾ The muffler installed inside the soundproof canopy. ¾ The control can be installed at the front or side to meet your need

Container Containerized generator sets have standard type and soundproof type, manufactured and designed according to International Standard size of the container, there are 20’GP container and 40’GP container for your selection.

Trailer

Silent Type Gen Sets with Trailer: Besides all performances of Silent Type Gen Sets, the Silent Type Diesel Generator Set with Trailer has advantages as follows: Equipped armor plate spring of structure poised; The trailer adopt the adjustable- height bolted towed rack, which is suitable for different height trailer; Have mechanical under props at each corner of the trailer. Inertial traveling brake, station brake & disengage emergency brake between trailer and tractor With turning lamp, brake indicator light and standard BNC connector plugs for back lamp. We also have dual wheel and four-wheel for your option.


Tide Power System TCM180 Diesel generator sets (50Hz-60Hz) ATS

ATS (Auto Transfer Switch) Automatic Transfer Switch (ATS) between two-way electrical sources. There are different types of transfer switch to be chosen. ATS which with AMF control module can protect the two-way electrical source when the voltage is too high or too low and lack-phase. The System mainly used as Auto Emergency Service System together with the Genset. This kind of Gensets has a wide application such as hospital, bank, telecom, air port, broadcasting station and hotels.

Tide Power System Co., Ltd

Distributed By:

Simon Walker Sales Representative 826-2282