Retrofitting Melbourne's High-Rise Social Housing Buildings

Page 1

Retrofitting M elbourne’s high - rise social housing buildings: improv ing liveability and energy performance in a circular economy

Isabella Fyfe

The University of Melbourne, Melbourne, Australia i.fyfe@student.unimelb.edu.au

Supervisors:

Dr. Dominik Holzer

Dr. Behzad Rismanchi

Melbourne School of Design

Melbourne School of Engineering

The University of Melbourne 2023

Isabella Fyfe 1

Abstract:

Adopting circular economy principles such as retrofit is key for a low carbon transition in the built environment sector. Residential buildings are an important target for operational and embodied carbon reductions in Australia and transforming existing social housing buildings through retrofit presents a unique opportunity to address social and technical sustainability goals. However, social housing retrofits typically focus solely on technical improvements, including energy performance and embodied carbon reductions, meaning that social impacts like liveability are overlooked This thesis aims to propose a sociotechnical systems (STS) approach to the retrofit of Melbourne’s high-rise social housing buildings, to improve liveability and energy performance in the context of a circular economy. An STS decision support tool was developed, and its theoretical application demonstrated on the retrofit of a case study building through a ‘façade subtract and add’ design intervention. This approach was found to improve the liveability and energy performance of the building; however, further studies are required to assess the operational carbon savings against the embodied carbon required to deliver the intervention. This study shows that the retrofit of Melbourne’s high-rise social housing buildings is possible, and that it can be done in a way that improves liveability and energy performance with minimal disruption to residents.

1 Introduction

Mitigating climate change will require the decarbonisation of the built environment sector, which accounts for 39% of greenhouse gas (GHG) emissions globally (World Green Building Council, 2019). Adopting circular economy principles such as the retrofit is key for a low carbon transition (Intergovernmental Panel on Climate Change, 2022) Residential buildings account for almost one quarter of total energy use in Australia (Commonwealth of Australia, 2023) and are therefore an important target for both operational and embodied carbon reductions Within the residential building sector, transforming existing social housing buildings through retrofit presents a unique opportunity to address social and technical sustainability goals. Improving the liveability and energy performance of social housing, for example, could help to achieve the United Nations Sustainable Development Goals (UN SDGs) of making “cities and human settlements inclusive, safe, resilient and sustainable” and ensuring “access to affordable, reliable, sustainable and modern energy for all” (United Nations, 2016). However, social housing retrofits typically focus solely on technical improvements such as energy performance and embodied carbon reductions, meaning that social impacts such as liveability are overlooked (Baker et al., 2023) Hence, there is a need to balance technical and social retrofit aspirations to improve existing social housing buildings and the lives of those who live in them.

On 20 September 2023, the Victorian Government announced a significant urban renewal project called Victoria’s Housing Statement. Melbourne’s 44 high-rise social housing buildings will be demolished and replaced with a mixture of private and social housing between 2023 and 2051, resulting in the forcible relocation of approximately 10,000 residents (Victorian Government, 2023) Currently, there is no publicly available information that supports the government’s assertion that the buildings are derelict beyond the point of retrofit, and no potential retrofit alternatives have been proposed (Porter et al., 2023). This thesis aims to propose a socio-technical systems (STS) approach to the retrofit of Melbourne’s high-rise social housing buildings, to improve liveability and energy performance in the context of a

Isabella Fyfe 2

circular economy. The objectives of this study are to develop an STS decision support tool and demonstrate its theoretical application on the retrofit of a case study building through a design intervention. It is hoped that the findings in this paper will demonstrate to policymakers that the retrofit of Melbourne’s high-rise social housing buildings is possible, and that it can be done in a way that improves liveability and energy performance with minimal disruption to residents.

2 Literature review

This literature review includes an overview of the context surrounding high-rise social housing building retrofits, both in a global and Melbourne-specific context. Additionally, several example buildings are assessed against criteria in a background study conducted to identify different retrofit approaches. Finally, a gap analysis summarises key findings

2.1 High-rise social housing building retrofits

2.1.1

Context

Globally, social housing buildings are characterised by poor indoor environmental quality (IEQ) conditions and poor building thermal performance, putting low-income populations at higher health risk (Haddad et al., 2022) and negatively affecting liveability for residents. Retrofit is proposed as a cost-effective solution to concerns around energy performance, thermal performance, and quality issues (Baker et al., 2023) in the social housing sector. Furthermore, retrofit has the advantage of saving embodied carbon emissions associated with the demolition of existing buildings and the construction of new buildings (Giesekam et al., 2014). In a circular economy context, decisions to retrofit existing buildings are frequently based on technical aspects of building performance, including energy performance compared to new building standards, and assessment of environmental impacts, such as embodied carbon, of buildings over their lifetime (Crawford et al., 2014; Lalande et al., 2015). However, consideration of improving only technical aspects of building performance through retrofit such as energy or carbon can lead to undesirable effects (Vakalis et al., 2021); in a social housing context, adopting this approach means that social impacts are overlooked (Baker et al., 2023). However, it has been found that the refurbishment of social housing can simultaneously deliver significant energy improvements and improved living standards for residents (Crawford et al., 2014)

2.1.2

Opportunities

Onyszkiewicz and Sadowski (2022) conducted a review of several prefabricated Large Panel System (LPS) housing estate retrofits located predominately in Europe. They identified several best practice retrofit strategies that should be simultaneously considered during the retrofit process. These included social strategies, such as social participation, and detailed social and urban planning research, and technical strategies, including building evaluation, heat loss minimisation by transmission, façade and ventilation improvements, and energy performance simulations. The study highlights the technical and social benefits associated with an ‘add-on balcony system’ retrofit in eliminating existing thermal bridges, improving apartment functionality, enabling social participation by providing residents the opportunity to personalise space, and improving aesthetics of the building facades. Additionally, the study recommends the consideration of circular economy principles and prefabrication to reduce embodied carbon emissions associated with the use of new building materials. The re-use of dismantled façade elements in the retrofit of existing buildings is suggested as one way to achieve this.

Isabella Fyfe 3

Adopting a socio-technical systems (STS) approach to the retrofit of social housing buildings in the context of a circular economy can assist in balancing technical-dominated concepts of energy demand and embodied carbon reduction, alongside the people-focused experience of housing and liveability (Willand et al., 2019) STS are “material, conceptual or symbolic constructs that are characterised by the links between humans and materials, machines or technologies” that include several interacting elements that change over time and do not necessarily follow the rules of linearity or proportion (Shrubsole et al., 2018). Approaching social housing retrofits using an STS approach allows for greater comprehension and appreciation of how to manage the various complex social and material relationships at play (Ozarisoy & Altan, 2021). Several studies call for the adoption of this approach in projects that aim at improving building performance and social outcomes (Shrubsole et al., 2018; Willand et al., 2019)

2.2 Melbourne’s high-rise social housing buildings retrofit

2.2.1

Context

Melbourne’s high-rise (eight stories or more) social housing buildings were built between 1960 and 1975, comprising 45 buildings and 7,834 apartments, ranging from 27 m2 bedsitters to 96 m2 3-bedroom apartment units. The buildings were assembled in-situ using a structural system of precast concrete panel floors and walls, and have a projected life well into the 21st Century (Vella, 1990). Today, there are 44 high-rise social housing buildings across 21 estates in Melbourne (see Appendix 1). They account for 10% of the city’s social housing stock (McNeils & Reynolds, 2001) and house some of Australia’s most vulnerable people, including the low-income, elderly, and sick (Baeza et al., 2020). However, the buildings do not meet contemporary living standards due to decades of inadequate maintenance and repairs (Porter et al., 2023) and their poor IEQ conditions are negatively affecting the comfort, health, and wellbeing of residents (Jara-Baeza et al., 2023). Since the 1980s, retrofits of the buildings have been piecemeal, ranging from social initiatives aimed at improving resident wellbeing (McNeils & Reynolds, 2001), to technical glazing and insulation upgrades aimed at improving energy performance (Floyd, 2007). To date, no all-encompassing retrofit strategies to improve Melbourne’s high-rise social housing buildings have been proposed

2.2.2

Opportunities

There are some studies that identify potential retrofit opportunities for Melbourne’s high-rise social housing buildings. McNeils and Reynolds (2001) co-authored a review into the buildings that investigated ways to create better futures for residents. They found that upgrades to the apartments and common areas (including corridor spaces) could restore the buildings to contemporary housing standards, and address social issues of health, liveability, and poor amenity. Additionally, they found that technical upgrades to the windows and the external building (i.e. façade) could improve the poor energy performance of the buildings, which is attributed to poor shading of windows in summer and poor heat retention of windows in winter. However, to date, no in-depth energy performance analysis of the buildings has been published. Hence, these assumptions about potential technical retrofit opportunities are not well supported More recently, Jara-Baeza et al. (2023) conducted a holistic assessment of resident’s IEQ perceptions of the buildings. The study found that access to positive stimuli including fresh air, window control, natural light, and pleasant views (in order of importance) has several positive social outcomes, including improved wellbeing of residents. Additionally, the study found that pleasant views access can positively impact building-related health issues, suggesting a link between increased resident wellbeing and health, through the provision of access to positive stimuli.

Isabella Fyfe 4

2.3 Background study

A background study of existing high-rise social housing retrofits, both in Australia and globally, was conducted to determine the most effective socio-technical retrofit approaches.

2.3.1 Criteria

Six criteria (four social and two technical) were selected to evaluate five existing high-rise social housing retrofits. The evaluation criteria were selected based on key social and technical drivers relevant to the project. Example buildings were selected across the disciplines of architecture and engineering.

Social criteria

1. Fresh air access: resident’s ability to access fresh air from within apartment.

2. Window control access: resident’s ability to access window control from within apartment.

3. Natural light access: resident’s ability to access natural light from within apartment.

4. Pleasant views access: resident’s ability to access pleasant views from within apartment.

Technical criteria

5. Embodied carbon: embodied carbon emissions of an apartment retrofit.

6. Energy demand: amount of energy needed to heat and/or cool an apartment.

Objective ratings for each retrofit example were given based on available information in the literature. A normalized five-scale rating system was used (1 – Very Poor, 2 – Poor, 3 – Fair, 4 – Good, 5 – Very Good) to rate each retrofit example against the six criteria, with results of the comparison shown in Figure 1 (see Appendix 2 for justification of ratings). Weighted scores are shown in Table 1 with the criteria weighting and justification given in Table 2. A greater weighting is given to criteria deemed to be more significant, with consideration given to the findings and discussion in Sections 2.1 and 2.2.

Isabella Fyfe 5
0 1 2 3 4 5 Fresh air access Window control access Natural light access Pleasant view access Embodied carbon Energy demand Cité du Grand Parc Park Hill Phase 1 Park Hill Phase 2 Cedar Court Ken Soble Tower
Figure 1 Background study comparison radar diagram.

Table 1 Background study weighted scores.

Table 2 Background study criteria weighting and justification.

Social 50% Since the primary focus of this study is to balance social and technical retrofit ambitions, a 50 per cent weighting was assigned to this category.

Fresh air access 20%

Window control access 10%

Access to fresh air from within the apartment was voted by Melbourne’s high-rise social housing residents as ‘Extremely important’ in Jara-Baeza et al.’s (2023) study which subjectively evaluated resident wellbeing. Hence, this criterion has the most significant weighting in the social category.

Access to window control from within the apartment was voted by Melbourne’s highrise social housing residents as ‘Very important’ in Jara-Baeza et al.’s (2023) study. Hence, this criterion was assigned a less significant weighting than ‘Fresh air access’ and equal weighting with the other social category criterion.

Natural light access 10% As above.

Pleasant views access

Technical 50% As above. Embodied carbon

As above.

Reducing both embodied and operational carbon emissions is necessary to decarbonise buildings. However, reducing embodied carbon emissions is becoming increasingly important. Hence, this criterion was given a greater weighting than energy demand.

Energy demand 20% Reducing energy demand (i.e. operational carbon emissions) is becoming less important as buildings become more energy efficient. Hence, this criterion was given a lesser weighting than embodied carbon.

Isabella Fyfe 6
Category Criteria Weighting Cité du Grand Parc Park Hill Phase 1 Park Hill Phase 2 Cedar Court Ken Soble Tower Social Fresh air access 20% 5 3 3 4 5 Window control access 10% 5 2 3 5 3 Natural light access 10% 5 4 3 3 3 Pleasant view access 10% 5 4 3 4 3 Technical Embodied carbon 30% 2 1 3 3 3 Energy demand 20% 4 3 4 4 5 Total 100% 3.9 2.5 3.2 3.7 3.8
Category Weighting Justification Criteria Weighting Justification
10%
30%

2.3.2 Findings

The following findings arose from the objective assessment and subjective weighting of the five existing high-rise social housing retrofits presented in Section 2.3.1:

• Retrofit aspirations tend to focus primarily on either social or technical improvements. Cité du Grand Parc, for example, exemplified a strong social retrofit focus. Resident’s access to fresh air, window control, natural light, and pleasant views were significantly improved post-retrofit. However, whilst there were improvements to the energy demand of apartments, there were significant embodied carbon emissions associated with the provision of the new winter garden spaces constructed from concrete, glass, steel, polycarbonate sheeting, and aluminium. Opposingly, Ken Soble Tower demonstrated a strong technical retrofit focus with each apartment achieving Passive House certification. Whilst there were significant improvements to fresh air access for residents, other social considerations were not a priority in the retrofit.

• The reduction of operational carbon (i.e. energy demand) is prioritised over embodied carbon reductions across all case studies. Furthermore, whilst each retrofit had some focus on reducing embodied carbon (i.e. retaining certain components of the existing building), there was no exemplar case study that used predominately low embodied carbon new building materials or re-used existing building elements in the retrofit.

• Disruption to residents was noted with some case studies enabling residents to remain in-situ throughout the retrofit process (i.e. Cité du Grand Parc and Cedar Court) and others requiring the full decant and temporary housing of residents (i.e. Park Hill Phase 1, Park Hill Phase 2, and Ken Soble Tower).

• Figure 2 illustrates the different retrofit approaches demonstrated by the examples. Cité du Grand Parc = approach A, Park Hill Phase 1 = approach B, Park Hill Phase 2 = approach C, and Cedar Court and Ken Soble Tower = approach D. Approach A, ‘façade subtract and add’, demonstrates the most potential to improve building performance and social outcomes, supporting the findings in the study by Onyszkiewicz and Sadowski (2022).

Isabella Fyfe 7
Figure 2 Background study comparison radar diagram.

2.4 Gap analysis

The literature review has revealed that social housing retrofits typically focus on technical improvements, such as energy performance, meaning that social impacts including liveability are overlooked Hence, there is a need to balance technical and social retrofit aspirations to improve existing social housing buildings and the lives of those who live in them. To date in Melbourne no all-encompassing retrofit strategies have been proposed to improve the city’s existing high-rise social housing buildings. Furthermore, no in-depth energy performance or embodied carbon analysis of the buildings has been performed or published. The results of these analyses are essential to inform retrofit interventions aimed at improving energy performance by reducing energy demand in the context of a circular economy. From the background study and literature review, a ‘façade subtract and add’ approach was found to have the most potential to improve both building performance and social outcomes. Additionally, the research calls for a socio-technical systems (STS) approach to projects that aim at improving building performance and social outcomes, such as energy performance and liveability. Circular economy principles such as prefabrication, material re-use, and the use of low embodied carbon materials for the retrofit should be considered, all whilst aiming to minimise disruption to residents.

3 Methodology and methods

This thesis aims to propose a socio-technical systems (STS) approach to the retrofit of Melbourne’s high-rise social housing buildings, to improve liveability and energy performance in the context of a circular economy. The outcome of this study is the development of an STS decision support tool and demonstration of its theoretical application on the retrofit of a case study building through a ‘façade subtract and add’ design intervention. The methodological sequence followed to achieve this outcome is shown in Figure 3 The first step is the research phase comprising a literature review and background study (see Section 2). The second step is the critical analysis phase which consists of identifying the research gap (see Section 2) and developing the STS tool (Section 3). The final phase is the technical analysis and design phase (see Section 4) This phase includes the proposed design intervention that responds to the thesis aim. This section (Section 3) illustrates the process followed to develop the STS tool, including defining key terms, formulation of social and technical criteria, introduction of the case study building, and explanation of the methods followed, including key limitations and assumptions.

3.1 Development of STS tool

Before developing the STS tool, it was necessary to define the concepts of ‘liveability’ and ‘energy performance’, and ‘circular economy’ which are central to the thesis aim. Defining these concepts helped to determine a set of social and technical criteria for use in the tool.

Isabella Fyfe 8 3 - Technical analysis and design 1 - Research 2 - Critical analysis
Figure 3 Methodological sequence.
Literature review inc. background study Research gap Development of STS tool STS tool application on case study building Design intervention

3.1.1 Defining liveability

There is no single definition of liveability and its meaning varies greatly according to its context (Tennakoon & Kulatunga, 2019). However, liveability is increasingly seen as a mechanism to enhance the wellbeing and health of people (Badland et al., 2014), hence, the terms wellbeing and health are linked under liveability. Additionally, the Victorian Competition and Performance Commission’s definition of liveability links place and wellbeing beneath the term: “Liveability reflects the wellbeing of a community and comprises the many characteristics that make a location a place where people want to live now and in the future” (Commission, 2008). Finally, there is a close association between liveability and the social determinants of health, which include the built and natural environments, or place, in which people live (Rydin et al., 2012). Therefore, place and health are also linked under liveability. Holistically linking the concepts of place, wellbeing, and health under the umbrella term of liveability (see Figure 4) allows for better appreciation and understanding of the system as a whole (Badland & Pearce, 2019). Hence, this holistic approach to defining liveability was adopted for this study.

From the literature review, it was found that the poor IEQ conditions of Melbourne’s highrise social housing buildings are negatively affecting the health, and wellbeing of residents. Thus, improving these conditions is critical to improving the liveability of the buildings. Rohde et al. (2019) defines the domains of wellbeing and health through an IEQ lens as:

• Wellbeing is associated with indoor environmental conditions which improve occupants’ happiness through the presence of positive stimuli, providing control and offering variations (associated with psychological dimension).

• Health is attributed to the indoor conditions which contribute to physical resilience, limiting conditions leading to infirmity, disease, and years of life lost (related to physical and psychological dimensions).

However, the health and wellbeing of residents is not limited to IEQ conditions. Places that foster social connection, for example, are found to be beneficial for resident health and wellbeing (Bethell et al., 2021). Therefore, creating spaces that enhance and support social connectedness also directly impacts the liveability of place and is an important consideration in improving liveability.

Isabella Fyfe 9
Figure 4 Graphic interpretation of liveability. Place Health Wellbeing Liveability

The wellbeing of Melbourne’s high-rise social housing building residents was subjectively evaluated by Jara-Baeza et al. (2023) through questions on how important it to have access to several positive stimuli. In the absence of detailed sociological and anthropological research into the liveability of the buildings, the results of this study were used to determine a set of social criteria for use in the STS tool. The study found access to fresh air, window control, natural light, and pleasant views (in order of importance) to be the most important positive stimuli that affected the wellbeing of residents. Additionally, the study found that access to view satisfaction can have an impact on building-related health issues, suggesting a link between increased resident wellbeing and health through the provision of access to positive stimuli. Hence, the four positive stimuli (access to fresh air, window control, natural light, and pleasant views) from the study were included as social criteria in the STS tool. A fifth criteria, access to social connection, was also included since it is also a factor that impacts liveability.

3.1.2 Defining circular economy

Circular economy can be defined as maintaining the value of biological and technological resources for as long as possible in closed-loop systems (F. Mendoza et al., 2019). Adopting circular economy principles, such as retrofit, is key to reducing building-related embodied carbon emissions. Consequently, it is becoming increasingly important to consider embodied carbon across the whole building life cycle (Densley Tingley et al., 2018; World Green Building Council, 2019) In the decision-making process for environmentally responsible design, the results from an embodied carbon analysis can inform decisions around material reuse, and the use of low embodied carbon materials when new materials are required. Hence, embodied carbon was included as a technical criterion in the STS tool to inform retrofit interventions in the context of a circular economy.

3.1.3 Defining energy performance

Improving the energy performance of existing buildings through retrofit can significantly reduce energy demand (i.e. energy loads) and consequently environmental, economic, and social impacts (Belussi et al., 2019). In Australia, current regulatory requirements for the energy demand of residential dwellings are specified in the National Construction Code of Australia (NCC). The Nationwide Housing Energy Rating Scheme (NatHERS) is a pathway commonly used to demonstrate compliance with the NCC, with around 90% of new home designs being assessed using the Scheme (Australian Building Codes Board, 2022). NatHERS gives a star rating for a dwelling out of ten with a higher number of stars representing lower thermal operational energy demand. Recent changes to NCC 2022 require new residential dwellings to meet new heating and cooling load limits using a NatHERS compliance pathway. These limits equate to a NatHERS rating of 7 stars and are specified in the NatHERS heating and cooling load limits Standard 2022 (Commonwealth of Australia and the States and Territories of Australia, 2022).

Currently, no in-depth energy performance analysis of Melbourne’s high-rise social housing buildings has been performed or is publicly available. However, Sustainability Victoria (2019) estimates that housing in Victoria built before 1990 averages about 1.5 out of 10 NatHERS stars. Therefore, it can be reasonably assumed that Melbourne’s high-rise social housing buildings have a similar NatHERS rating and therefore, do not meet the current regulatory requirements for energy demand (since the buildings were constructed before 1990) Hence, the results of an energy performance analysis are necessary to inform retrofit interventions for the buildings to improve their energy performance by reducing energy demand. Thus, energy demand was included as the second and final technical criterion in the STS tool.

Isabella Fyfe 10

3.2 STS tool

The STS tool consists of seven criteria (five social and two technical) that were determined in Section 3.1. The tool can be used by architects and engineers in an iterative way to better meet the sensitives of Melbourne’s high-rise social housing buildings and residents’ liveability preference, resulting in more tailored retrofit design interventions. The tool will primarily benefit residents by improving liveability, however, co-benefits include increased public health, reductions in energy poverty, decarbonization and reduced environmental impacts of buildings, and climate change mitigation. A visual overview of the tool, including its social and technical criteria, is given in Figure 5 and its intended application sequence in the retrofit process for Melbourne’s high-rise social housing buildings is illustrated in Figure 6. This sequence can be repeated until the desired retrofit intervention is achieved.

5 Socio-technical systems (STS) tool.

Technical analysis inc. energy demand and embodied carbon analyses

Qualitative assessment of social criteria

Informs retrofit design decisions

6 Socio-technical systems (STS) tool application sequence.

3.3 Case study building

A case study building was selected to demonstrate the theoretical application of the STS tool through a retrofit design intervention. The case study building is one of Melbourne’s existing high-rise social housing buildings, located within NatHERS Climate Zone 60 (Nationwide House Energy Rating Scheme, 2013) at 127 Gordon Street in Footscray, Melbourne. It is the only high-rise social housing building within the estate known as Gaskin Gardens (Vella, 1990) It is 13-storeys comprising 111 apartments of different configurations, including 89 x 1-bedroom apartments, 20 x bedsit apartments, and 2 x 2-bed apartments, across four different floor play typologies (see Appendix 3). The case study was selected based on the availability of documentation drawings and the shape of its plan The building’s T-shaped plan accounts

Isabella Fyfe 11
Figure Figure

for the second highest proportion (20%) of buildings surveyed in Jara Baeza et al.’s (2023) study into resident’s IEQ perceptions of Melbourne’s high-rise social housing buildings. This study was instrumental in determining the socio criteria in the STS tool. Images of the case study building are shown in Figure 7

3.4 Methods

This section outlines how each criterion within the STS tool was assessed. The social criteria were qualitatively assessed, and the technical criteria were quantitively assessed. Section 4 demonstrates the application and results of these assessments for the case study building before and after the ‘façade subtract and add’ retrofit design intervention.

3.4.1 Social criteria

Objective ratings for the STS tool’s five social criteria were given using a normalized fivescale rating system (1 – Very Poor, 2 – Poor, 3 – Fair, 4 – Good, 5 – Very Good). This process was repeated both before (see Section 4.1.1) and after (see Section 4.3.1) the design intervention for the case study building. This enabled the comparison of the building’s liveability before and after its retrofit. The ratings were assigned based on detailed justifications provided in the Appendices.

3.4.2 Technical criteria

3.4.2.1 Embodied carbon

A life cycle assessment (LCA) can be used to quantify the environmental impact of a building across its whole life cycle in accordance with EN 15978:2011. However, this process is significantly complicated and time consuming. Therefore, an LCA assessment for this study was not performed given data limitations and time constraints. Instead, a different approach using material production and assembly processes data in the form of material embodied environmental flow coefficients from the Environmental Performance in Construction (EPiC) database was adopted. To estimate the embodied carbon of the case study building, material quantities were multiplied with hybridised environmental flow coefficients from the EPiC database (see Equation 1).

Equation 1 Embodied carbon equation using hybridised environmental flow coefficients.

Isabella Fyfe 12
Figure 7 Case study building street view (left) and 3D view (right) (Google Maps, 2023).
�������������������������������� ������������������������ (�������������������� ����) = �������������������������������� ���������������������������� (����������������) × �������������������������������� ������������ ������������������������������������ ��������������������� ���� ���������������� �

The EPiC database was selected for this study because it comprises hybridised environmental flow coefficients for construction materials in an Australian-specific context. Due to the databases limitations, only the embodied carbon for the product stage (A1 – A3) was estimated for the case study building (see Figure 8). However, the majority of a building’s total embodied carbon is released upfront during the product stage (Carbon Leadership Forum, 2023), hence, diminishing the significance of this limitation.

Key limitations associated with this method include difficulties in accurately determining construction material types and quantities due to limited access to the case study building and absence of a detailed construction material inventory. Hence material quantities were assumed based on photographs, documentation drawings, and the information provided in the thermal performance analysis report by Floyd (2007). It should be noted that only residential floors (levels 1 – 12) were considered in the embodied carbon analysis since these floors are the focus of the design intervention (see Figure 9).

Isabella Fyfe 13
Figure 8 Life cycle inventory scope (EN 15978:2011). Figure 9 Scope of embodied carbon analysis (floors shown in bold were included).

3.4.2.2

Energy demand

NatHERS accredited simulation engine software Home Energy Rating and Optimisation (HERO) was used to quantify the annual energy demand of the apartments within the case study building. HERO calculates the transient heat gains and losses of residential spaces, factoring the thermal performance of the building envelope, thermal storage, orientation, latent and sensible internal gains, cooling effects from cross ventilation and ceiling fans, hourly weather data and typical occupant behaviours (Willand et al., 2019). Air permeability rates and provision, demand or location of HVAC systems are excluded from the software calculations. A typological approach was taken to the energy demand analysis of the case study building. Eleven apartments (see Figure 10) representative of all apartment typologies within the case study building (see Appendix 4) were modelled in HERO. For simplicity, it was assumed that the results from these analyses represented all apartments within the case study building. However, since the ceilings of apartments located on level 12 are located adjacent to the building’s roof space, they are assumed to have a lower energy performance rating compared to apartments on levels 1 – 11. This is because there is an increase conduction heat transfer areas compared to other floors, resulting in more heat loss (Yoon et al., 2019)

Isabella Fyfe 14
Figure 10 Typological approach adopted for energy demand analysis.

HERO has several assumptions built into the software including assumptions on occupant behaviour, openability of windows and doors etc. Where possible, these assumptions were manipulated to better reflect the case study building in accordance with the NatHERS Technical Note (29 September 2023) document. See Appendix 5 for a full list of the assumptions made for the HERO energy demand analysis. Furthermore, access to the case study building was restricted, therefore, several assumptions regarding apartment typologies, layouts, configurations, materiality etc. were made based on photographs and documentation drawings produced by BKK Architects, Peter Elliot Architecture and Urban Design, and Taylor Cullity Lethlean on 23 August 2011. It is known that several glazing and insulation improvements have been made to individual apartments within the case study building to improve their energy performance (Floyd, 2007). However, these improvements were not applied globally. Therefore, several assumptions about the building’s construction materials were made based on photographs, documentation drawings and the thermal performance analysis performed by Floyd (2007)

4 Results and analysis

This Section presents analysis performed on the case study building in accordance with the social and technical criteria STS tool, both before and after the proposed retrofit design intervention. See Section 5 for detailed discussion of the results.

4.1 Before retrofit

Results from the social and technical analysis of the case study building before the retrofit intervention are given below.

4.1.1 Social criteria

The five social criteria from the STS tool were objectively rated using a normalized five-scale rating system (1 – Very Poor, 2 – Poor, 3 – Fair, 4 – Good, 5 – Very Good) with results shown in Table 4 below. Refer to Appendix 6 for detailed justification of the ratings.

Table 3 Social criteria objective ratings before retrofit.

Social criteria Score

Fresh air access 2

Window control access 2

Brief justification

Windows = primary source of fresh air access for the apartments. In corridor spaces, there is always the provision of fresh air through vents located above the windows which are permanently open.

Residents can operate most windows in their apartments (awning and double hung). Some windows are fixed and cannot be operated. Vents and windows in corridor spaces are completely inoperable.

Natural light access 4 Jara-Baeza et al. (2023) found that residents had

Pleasant view access 3

All apartments have unobstructed pleasant views on the apartment-facing façade. Views are obstructed on the corridor side due to the provision of the half-height cold rolled steel wall and vents.

Social connection access 2 Limited access to social connection due to narrow corridor width.

4.1.2 Embodied carbon

The total embodied carbon for levels 1 – 12 of the case study building was found to be 1,658 tCO2e (see Table 4). The results show that concrete (floors, walls, and fire stairs) accounts for 51%, followed by cold rolled steel (corridor façade panels) and aluminium extruded powder coated (window frames and vents), which account for 20% and 12% of the embodied carbon for levels 1 – 12 respectively (see Figure 11). Appendix 7 provides justification of the material types selected for the embodied carbon calculations and shows detailed calculations for a typical floor.

Isabella Fyfe 15

Table 4 Embodied carbon results (levels 1 – 12) by material type before retrofit

3%

Plasterboard - 10mm 0%

Figure 11 Percentage breakdown of embodied carbon (levels 1 – 12) by material type before retrofit

4.1.3 Energy demand

The results from the typological approach energy demand analysis for the case study building (see Table 5) show that the average NatHERS rating for the apartments is 2.1 stars, with an annual average heating load, cooling load, and total load of 419.9 MJ/m2, 11.5 MJ/m2, and 410.0 MJ/m2, respectively (see Table 6). Additionally, the highest NatHERS rating achieved was 3.4 stars for model 8 and the lowest NatHERS rating achieved was 0.8 stars for model 11. The highest annual average heating load, cooling load, and total load were found to be 671.4 MJ/m2, 21.5 MJ/m2, and 690.0 MJ/m2, respectively. The lowest annual average heating load, cooling load, and total load were found to be 243.6 MJ/m2, 4.0 MJ/m2, and 251.3 MJ/m2, respectively. Appendix 8 presents the case study building material assumptions used in the energy modelling software and Appendix 9 provides a detailed overview the energy models for the apartments that achieved the highest (B.2.4) and lowest (C.8.10) NatHERS ratings respectively.

Isabella Fyfe 16
Material Total embodied carbon (kgCO₂e) Total embodied carbon (tCO₂e) Concrete 25MPa 845,225 845 Aluminium extruded powder coated 200,497 200 Cold rolled steel 329,717 330 Flat glass sheet - 12mm 69,525 70 Hardwood air-dried 9,040 9 Plasterboard - 10mm 5,621 6 Ceramic tile 45,138 45 Tufted carpet, nylon -quality 116,911 117 Linoleum sheet - 4mm 36,059 36 Total 1,657,731 1,658
51% Aluminium extruded powdercoated 12% Cold rolled steel 20% Flat glass sheet12mm 4%
Concrete 25MPa
Hardwood air-dried 1%
Ceramic tile Tufted carpet, nylon -quality 7% Linoleum sheet - 4mm 2%

Table 5 Energy demand analysis results.

Table 6 Highest, lowest, and average values from energy demand analysis.

4.2 Retrofit design intervention

The results presented in Section 4.1 were used to inform a retrofit design response for the case study building in accordance with the STS tool application sequence in Figure 6. A retrofit design intervention for the communal corridor spaces on the residential floors was proposed because these spaces offer the greatest potential for improved access to social connection. The intervention takes inspiration from the background study and literature review findings presented in Section 2 which found a ‘façade subtract and add’ approach to retrofit had the most potential to improve both building performance and social outcomes. Hence, this approach was adopted to create a liveable thermal corridor zone adjacent the existing façade of the case study building, drawing architectural inspiration from the Lacaton & Vassal retrofit example (Cité du Grand Parc in Bordeaux, France) examined in the background study. Circular economy principles such as prefabrication, material re-use, and the use of low embodied carbon materials were considered. Additionally, minimising disruption to residents was also a key focus of the intervention. Details of the retrofit intervention, including documentation drawings, are given in Appendix 10

Isabella Fyfe 17
HERO model number Floor level Apartment name NatHERS rating Annual heating demand (MJ/m2) Annual cooling demand (MJ/m2) Total annual demand (MJ/m2) 1 1 A.1.1 1.7 442.7 13.2 455.9 2 1 A.1.5 2.0 386.9 14.3 401.2 3 1 A.1.8 1.4 503.7 10.4 514.1 4 1 A.1.3 3.1 261.4 6.1 267.5 5 1 A.1.6 2.4 336.2 4.0 340.2 6 3 A.3.4 3.3 250.9 5.6 256.5 7 8 C.8.1 0.9 623.6 21.5 645.1 8 2 B.2.4 3.4 242 2 8.3 250.5 9 11 D.11.6 1.2 566.5 19.9 586.4 10 8 C.8.7 2.5 324 5.4 329.4 11 8 C.8.10 0.8 687.9 18.2 706.1
NatHERS rating Annual heating load (MJ/m2) Annual cooling load (MJ/m2) Total annual load (MJ/m2) Average value 2.1 420.5 11.5 432 1 Highest value 3.4 687.9 21.5 706.1 Lowest value 0.8 242.2 4.0 250 5
Figure 12 Render of design intervention.

4.3 After retrofit

Results from the social and technical analysis of the case study building after the retrofit intervention are given below.

4.3.1

Social criteria

Again, the five social criteria from the STS tool were objectively rated using a normalized five-scale rating system (1 – Very Poor, 2 – Poor, 3 – Fair, 4 – Good, 5 – Very Good) with results shown in Table 4 below. These results reflect the liveability of the case study building after the retrofit intervention. See Appendix 11 for detailed justification of the ratings. From the results it was found that after the retrofit intervention, the liveability of the case study building significantly increased (see Figure 13).

Table 7 Social criteria objective ratings after retrofit.

Social criteria Score

Fresh air access 4

Window control access 4

Natural light access 5

Pleasant view access 5

Social connection access 5

Brief justification

Increase in area on the corridor façade that can be opened to provide fresh air access, subsequently improving the fresh air access to the apartments through the kitchen and bathroom windows adjacent the corridor.

Post retrofit, residents can fully control windows in the corridor spaces. There is no change to the window control access in the apartments.

Although increased corridor width may reduce some provision of natural light to the kitchen, bathroom, and corridor spaces, this is assumed to be mitigated by provision of floor to ceiling semi-opaque polycarbonate sliding doors.

Again, the provision of semi-opaque floor to ceiling polycarbonate sliding doors in place of the half-height cold rolled steel wall and aluminium powder coated vents significantly increases access to pleasant views.

Additional balcony area transforms corridors from transitory spaces to liveable spaces where people connect with other residents.

Figure 13 Before and after retrofit intervention – social criterion comparison radar diagram.

4.3.2

Embodied carbon

The total embodied carbon for the retrofit intervention was found to be 552 tCO2e (see Table 8). The results show that the glulam structure accounts for 42%, followed by polycarbonate (sliding doors) and stainless-steel wire (façade mesh), which account for 27% and 18% of the

Isabella Fyfe 18
0 1 2 3 4 5 Fresh air access Window control access Natural light access Pleasant view access Social connection access Before retrofit After retrofit

embodied carbon for the retrofit intervention respectively (see Figure 14). The retrofit intervention accounts for 25% of the building’s total embodied carbon (see Table 9)

Importantly, the retrofit enabled the re-use of the existing cold rolled steel elements of the original corridor façade, saving 20% of the building’s existing embodied carbon. Appendix 12 provides justification of the material types selected for the embodied carbon calculations and shows detailed calculations.

Table 8 Embodied carbon results by material type after retrofit.

14

Table 9 Total embodied carbon for case study building including before and after retrofit

Isabella Fyfe 19
Material Total embodied carbon (kgCO₂e) Total embodied carbon (tCO₂e) Glued laminated timber (glulam) outdoor 228,985 229 Ceramic tile 12,237 12 Hardwood air-dried 63,404 63 Polycarbonate 148,736 149 Stainless steel wire 98,334 98 Total 551,696 552
Figure Percentage breakdown of embodied carbon by material type after retrofit.
Total embodied carbon (kgCO₂e) Total embodied carbon (tCO₂e) Percentage contribution (%) Before retrofit 1,657,731 1,658 75 After retrofit 551,696 552 25 Total 2,209,427 2,210 100
42% Ceramic tile 2% Hardwood air-dried 11% Polycarbonate 27%
steel wire 18%
Glued laminated timber (glulam) outdoor
Stainless

4.3.3 Energy demand

The retrofit design intervention was tested against the highest (apartment B.2.4) and lowest (apartment C.8.10) NatHERS rated apartments from the energy demand analysis. After the retrofit, the NatHERS energy rating for apartment B.2.4 (model 8) increased from 3.4 to 5.2 stars whilst apartment C.8.10 (model 11) increased from 0.8 stars to 1.4 stars (see Table 10). Interestingly in both cases the annual heating demand significantly decreased, and the annual cooling demand increased slightly. This resulted in a total annual energy demand reduction for apartment B.2.4 from 250.5 MJ/m2 to 160.3 MJ/m2, or 36%, and from 706.1 MJ/m2 to 514.5 MJ/m2, or 27%, for apartment C.8.10 (see Table 10). Appendix 13 provides a detailed overview the energy models.

Table 10 Energy demand analysis results before retrofit.

5 Discussion

5.1 Advantages

The results from this study shown that the development and use of the socio-technical systems (STS) tool to approach the retrofit of Melbourne’s high-rise social housing buildings has the following advantages:

• The use of the tool can help architects and engineers to balance technical-dominated concepts of energy demand and embodied carbon reduction, alongside the people-focused experience of liveability (Willand et al., 2019)

• The tool brings to light the complex relationship between embodied and operational carbon. It allows designers and decision-makers to weigh potential operational carbon savings from improved energy performance against the embodied carbon required to deliver these savings.

• The tool has the potential to be applied to Melbourne’s other high-rise social housing buildings and the social criteria adjusted to better reflect liveability requirements of residents on a case-by-case basis. Additionally, the tool has the potential to assign weightings to the social and technical criteria. These weightings could be adjusted to suit different retrofit aspirations (i.e. equally balanced social and technical aspirations or retrofit aspirations more weighted either towards social or technical aspirations).

Additionally, this study has demonstrated that the proposed ‘façade subtract and add’ retrofit intervention design approach has the following advantages:

• The approach shows significant potential in improving social outcomes for residents, particularly by improving access to social connection through the provision of liveable spaces that also double as a thermal barrier, insulating the existing building. This

Isabella Fyfe 20
HERO model number Floor level Apartment name NatHERS rating Annual heating demand (MJ/m2) Annual cooling demand (MJ/m2) Total annual demand (MJ/m2) Percentage reduction in total annual demand Before 8 2 B.2.4 3.4 242 2 8.3 250.5 36% After (corridor closed) 5.2 137.3 23.0 160.3 Before 11 8 C.8.10 0.8 687.9 18.2 706.1 27% After (corridor closed) 1.4 489.8 24.7 514.5

insulating thermal barrier is shown to have an additional benefit of improving the thermal performance of the building, evidenced by reduced energy demand for the apartments.

• The design intervention has the potential to improve access to social participation by providing residents with the possibility of arranging spaces according to their living preferences (Onyszkiewicz & Sadowski, 2022).

• The intervention can be installed with minimal disruption to residents, with the structure being erected alongside the existing building. There are additional social and economic benefits of not having to decant or relocate residents during this process (Crawford et al., 2014)

• The proposed retrofit intervention has the potential to be applied to the non-loadbearing kitchen/living room facades of the case study building which may result in further operational carbon savings from improved energy performance. Additionally, there may be improved liveability benefits associated with increased access to positive stimuli and social connection.

• The intervention can be scaled, adapted, and applied to Melbourne’s other high-rise social housing buildings due to their similar design, construction, building elements, and material characteristics, resulting in far-reaching potential positive social and environmental impacts.

5.2 Limitations

There are several limitations associated with this study, including the following:

• Economic factors were not considered as part of this study.

• A detailed structural analysis of the proposed retrofit design intervention was not performed.

• A retrofit intervention was only proposed for the communal corridor spaces, therefore, for example, excluding additional potential social and technical benefits that could be achieved through the provision of the intervention to the apartment facades.

• A structural analysis of the overall condition of Melbourne’s high-rise social housing buildings is necessary to determine the scope and timeframe of any potential retrofit interventions. Once this information is known, potential operational carbon savings from improved energy performance over the building’s remaining life can be weighed against embodied carbon emissions required to deliver these savings.

• Energy performance calculations after the retrofit intervention were only performed for the highest and lowest NatHERS rated apartments. Additionally, only the enclosed situation (i.e. when all sliding doors are closed) for the proposed retrofit intervention was modeled. It is anticipated that results will differ for the case where the corridor spaces are open (i.e. when all sliding doors are open)

• The use of hybridised environmental flow coefficients resulted in a conservative estimate of the case study building’s embodied carbon. This is because the coefficients can vary greatly, particularly in terms of geographic (i.e. transport distances) and temporal factors (i.e. different manufacturing processes and efficiencies over time) (Reap et al., 2008) Hence, the results are not accurate given that manufacturing processes, transport, and construction processes have become more efficient over time (Crawford & Stephan, 2021). However, the results show the amount of upfront embodied carbon required to replace a building of a similar typology today.

• In the absence of detailed sociological and anthropological research into the liveability of the case study building, the results of the Jara-Baeza et al. (2023) study were used to determine a set of social criteria for use in the STS tool.

Isabella Fyfe 21

• The low value of the annual cooling demand results presented in Table 5 and Table 10 was noted Relative compactness, which is defined as the ratio of volume to surface area, is a building typology factor that directly influences the cooling energy demand in high-rise buildings, with higher ratios associated with lower cooling energy demand and therefore total energy demand (Anaya et al., 2021). For the apartments in the case study building, the amount of wall area exposed to ambient conditions is minimal (predominately the living room/kitchen façade since the corridor façade is shaded and partially enclosed). Hence, the apartments have a high relative compactness ratio which may explain the low annual cooling demand results

5.3 Recommendations

• There is considerable diversity between Melbourne’s high-rise social housing buildings. The buildings vary in size, shape, context, location, orientation, construction date, condition, maintenance history, renovations and alterations, social history etc. Therefore, it is important that sociological and anthropological research for each building. The results can then be used to determine a set of social criteria for use in the STS tool that is unique to each building.

• The provision of the retrofit intervention to the kitchen/living room apartment facades should be modelled and analysed to determine other potential liveability and energy performance improvements in the context of a circular economy

• A detailed design for the structure and connection joints of the retrofit intervention should be performed to assess its feasibility. Additionally, prototypes could be designed and constructed to test joints and monitor the performance of materials, especially with regards to their durability.

• It is important to assess the amount of embodied carbon required to implement the retrofit intervention to see how it weighs against potential operational carbon savings from energy performance improvements. A structural analysis of the buildings is necessary to determine the potential scope of the project and inform this analysis.

• It is evident that the building’s concrete elements contribute most significantly towards the building’s embodied carbon. Therefore, all proposed retrofit interventions for the buildings should retain these elements as much as possible.

• There is potential for the STS tool to assign weighted scores to both the social and technical criteria with greater weighting given to criteria deemed to be more significant. This would result in unique design solutions and retrofit outcomes tailored to each building and their residents

• The façades of the buildings should be insulated where the ‘façade subtract and add’ retrofit intervention cannot be applied to minimise heat loss by transmission (Yoon et al., 2019).

• A life cycle analysis that considers the other stages from EN 15978:2011 could be performed to analyse the impact of the project over its entire lifecycle For example, the sourcing of the materials could greatly influence the sustainability of the project and its impacts on the environment regarding embodied carbon.

• An energy performance assessment for the remaining nine energy models after the retrofit intervention could be performed to determine if the improved energy performance trend is consistent across all apartment typologies. Additionally, modelling for the case where the corridor spaces are open (i.e. when all sliding doors are open) should be performed to provide a more holistic overview of how the retrofit intervention performs in different situations.

• Economic studies should be performed to determine the feasibility of the retrofit design intervention in a real-world scenario.

Isabella Fyfe 22

6 Conclusion

As part of this study, an STS decision support tool was developed, and its theoretical application demonstrated on the retrofit of one of Melbourne’s high-rise social housing buildings through a ‘façade subtract and add’ design intervention (see Figure 15). It was found that the intervention, which comprised a low embodied carbon prefabricated glulam structure erected alongside the existing corridors that re-used the existing cold rolled steel facade elements, could improve the liveability and energy performance of the building, all whilst reducing embodied carbon impacts and minimising disruption to residents. Analysis of the building’s liveability, embodied carbon, and energy demand, performed both before and after the intervention, was used to support this finding. It is anticipated that the intervention could be applied to the apartment facades, further contributing to improved liveability and energy performance outcomes for the building. Additionally, it is thought that intervention can be scaled, adapted, and applied to Melbourne’s other high-rise social housing buildings due to their similar design, construction, building elements, and material characteristics, resulting in far-reaching potential positive social and environmental impacts.

Isabella Fyfe 23
Figure 15 Corridor view.

7 References

Anaya, B., Hou, D., Hassan, I., Wang, L., & Rahman, A. (2021). INFLUENCING FACTORS ON COOLING DEMAND OF HIGH-RISE BUILDINGS IN HOT/HUMID CLIMATES: A REVIEW https://doi.org/10.2495/SC210351

Australian Building Codes Board. (2022). Building for 7 Stars: top tips and guidance. Retrieved 2 October from https://ncc.abcb.gov.au/news/2022/building-7-stars-top-tipsand-guidance

Badland, H., & Pearce, J. (2019). Liveable for whom? Prospects of urban liveability to address health inequities. Social Science & Medicine, 232, 94-105. https://doi.org/https://doi.org/10.1016/j.socscimed.2019.05.001

Badland, H., Whitzman, C., Lowe, M., Davern, M., Aye, L., Butterworth, I., Hes, D., & Giles-Corti, B. (2014). Urban liveability: Emerging lessons from Australia for exploring the potential for indicators to measure the social determinants of health. Social Science & Medicine, 111, 64-73. https://doi.org/https://doi.org/10.1016/j.socscimed.2014.04.003

Baeza, F. J., Rajagopalan, P., & Andamon, M. M. (2020). Reviewing indoor environmental quality of high-rise social housing. Proceedings of the International Conference of Architectural Science Association,

Baker, E., Moore, T., Daniel, L., Cairnes, R., Padilla, H., & Lester, L. (2023). Sustainable social housing retrofit? Circular economy and tenant trade-offs.

Belussi, L., Barozzi, B., Bellazzi, A., Danza, L., Devitofrancesco, A., Fanciulli, C., Ghellere, M., Guazzi, G., Meroni, I., Salamone, F., Scamoni, F., & Scrosati, C. (2019). A review of performance of zero energy buildings and energy efficiency solutions. Journal of Building Engineering, 25, 100772. https://doi.org/https://doi.org/10.1016/j.jobe.2019.100772

Bethell, J., Aelick, K., Babineau, J., Bretzlaff, M., Edwards, C., Gibson, J.-L., Hewitt Colborne, D., Iaboni, A., Lender, D., Schon, D., & McGilton, K. S. (2021). Social Connection in Long-Term Care Homes: A Scoping Review of Published Research on the Mental Health Impacts and Potential Strategies During COVID-19. Journal of the American Medical Directors Association, 22(2), 228-237.e225. https://doi.org/https://doi.org/10.1016/j.jamda.2020.11.025

Blundell-Jones, P. (2011). Reframing Park Hill [Sheffield, England] [journal article]. Architectural review(1376), 83-93.

https://search.ebscohost.com/login.aspx?direct=true&AuthType=sso&db=bvh&AN=6 69491&site=ehost-live&custid=s2775460

Carbon Leadership Forum. (2023). Understanding Embodied Carbon. Retrieved 15 October from https://carbonleadershipforum.org/embodied-carbon101/#:~:text=The%20majority%20of%20a%20building's,after%20the%20building%2 0is%20constructed.

Commission, V. C. a. E. (2008). A State of Liveability: An Inquiry into Enhancing Victoria's Liveability. Commonwealth of Australia. (2023). Residential buildings. Retrieved 11 October from https://www.energy.gov.au/government-priorities/buildings/residential-buildings

Isabella Fyfe 24

Commonwealth of Australia and the States and Territories of Australia. (2022). NatHERS Heating and Cooling Load Limits Standard. In. Canberra: Australian Building Codes Board.

Crawford, K., Johnson, C., Davies, F., Joo, S., & Bell, S. (2014). Demolition or Refurbishment of Social Housing?: A review of the evidence.

Crawford, R., & Stephan, A. (2021). The effect of data age on the assessment of a building's embodied energy.

Densley Tingley, D., Giesekam, J., & Cooper-Searle, S. (2018). Applying Circular Economic Principles to Reduce Embodied Carbon. In F. Pomponi, C. De Wolf, & A. Moncaster (Eds.), Embodied Carbon in Buildings: Measurement, Management, and Mitigation (pp. 265-285). Springer International Publishing. https://doi.org/10.1007/978-3-31972796-7_12

Dunlop, A. (2019, 7 November 2019). Getting warmer: Collective Architecture upgrades Glasgow tower blocks. Retrieved 8 August from https://www.architectsjournal.co.uk/buildings/getting-warmer-collective-architectureupgrades-glasgow-tower-blocks

ERA Architects. (Unknown). Ken Soble Tower. Retrieved 8 August from https://www.eraarch.ca/projects/ken-soble-towertransformation/#:~:text=One%20of%20the%20first%20of,retrofit%20project%20in% 20the%20world

F. Mendoza, J. M., Gallego Schmid, A., & Azapagic, A. (2019). Building a business case for implementation of circular economy in higher education institutions. Journal of Cleaner Production, 220, 553-567. https://doi.org/10.1016/j.jclepro.2019.02.045

Floyd, W. (2007). Building thermal performance report: Office of Housing Tower, Gordon Street, Footscray

Gandh, V., & North, M. L. (2019). Sirius: Retrofitting Brutalism in Sydney. IOP Conference Series: Earth and Environmental Science, 290(1), 012153. https://doi.org/10.1088/1755-1315/290/1/012153

Giesekam, J., Barrett, J., Taylor, P., & Owen, A. (2014). The greenhouse gas emissions and mitigation options for materials used in UK construction. Energy and Buildings, 78, 202-214. https://doi.org/https://doi.org/10.1016/j.enbuild.2014.04.035

Haddad, S., Paolini, R., Synnefa, A., De Torres, L., Prasad, D., & Santamouris, M. (2022). Integrated assessment of the extreme climatic conditions, thermal performance, vulnerability, and well-being in low-income housing in the subtropical climate of Australia [Article]. Energy and Buildings, 272, Article 112349. https://doi.org/10.1016/j.enbuild.2022.112349

Intergovernmental Panel on Climate Change. (2022). Mitigation Pathways Compatible with 1.5°C in the Context of Sustainable Development. In Global Warming of 1.5°C: IPCC Special Report on Impacts of Global Warming of 1.5°C above Pre-industrial Levels in Context of Strengthening Response to Climate Change, Sustainable Development, and Efforts to Eradicate Poverty (pp. 93-174). Cambridge University Press.

https://doi.org/DOI: 10.1017/9781009157940.004

Jara-Baeza, F., Rajagopalan, P., & Andamon, M. M. (2023). A holistic assessment of indoor environmental quality perception in Australian high-rise social housing [Article].

Isabella Fyfe 25

Energy and Buildings, 284, Article 112859. https://doi.org/10.1016/j.enbuild.2023.112859

Lacaton & Vassal. (2021). Rothwell Chair Symposium. Living in the city: exemplary social and affordable housing design, Sydney.

Lalande, C., Emma-Liisa, H., Herda, G., Garrigan, C., Halcomb, J., & Bonetti, M. (2015). Green Building Interventions for Social Housing. UN-Habitat. https://unhabitat.org/green-building-interventions-for-social-housing

Mark, L. (2023). Park Hill, phase 2 : Mikhail Riches' second phase in the restoration of Sheffield's Park Hill grapples with the constructional complexities of Europe's largest listed building [journal article]. Architectural review(1499), 68-76. https://search.ebscohost.com/login.aspx?direct=true&AuthType=sso&db=bvh&AN=8 55868&site=ehost-live&custid=s2775460

McNeils, S., & Reynolds, A. (2001). Creating better futures for residents of high-rise public housing in Melbourne.

Nationwide House Energy Rating Scheme. (2013, March 2013). Climate Zone Map Retrieved 14 October from https://www.nathers.gov.au/themes/custom/govcms8_uikit_starter/climatemap/index.html

Onyszkiewicz, J., & Sadowski, K. (2022). Proposals for the revitalization of prefabricated building facades in terms of the principles of sustainable development and social participation. Journal of Building Engineering, 46, 103713. https://doi.org/https://doi.org/10.1016/j.jobe.2021.103713

Ozarisoy, B., & Altan, H. (2021). A novel methodological framework for the optimisation of post-war social housing developments in the South-eastern Mediterranean climate: Policy design and life-cycle cost impact analysis of retrofitting strategies [Article]. Solar Energy, 225, 517-560. https://doi.org/10.1016/j.solener.2021.07.008

Porter, L., Kelly, D., Kunjan, P., Levin, I., Shaw, K., & Davies, L. (2023). Victoria’s Housing Statement: A critical explainer. https://cur.org.au/cms/wpcontent/uploads/2023/09/vic-housing-statement-explainer.pdf

Reap, J., Roman, F., Duncan, S., & Bras, B. (2008). A survey of unresolved problems in life cycle assessment. The International Journal of Life Cycle Assessment, 13(5), 374-388. https://doi.org/10.1007/s11367-008-0009-9

Rohde, L., Larsen, T., Jensen, R., & Larsen, O. (2019). Framing holistic indoor environment: Definitions of comfort, health and well-being. Indoor and Built Environment, 1420326X1987579. https://doi.org/10.1177/1420326X19875795

Rydin, Y., Bleahu, A., Davies, M., Dávila, J. D., Friel, S., De Grandis, G., Groce, N., Hallal, P. C., Hamilton, I., Howden-Chapman, P., Lai, K. M., Lim, C. J., Martins, J., Osrin, D., Ridley, I., Scott, I., Taylor, M., Wilkinson, P., & Wilson, J. (2012). Shaping cities for health: complexity and the planning of urban environments in the 21st century. Lancet, 379(9831), 2079-2108. https://doi.org/10.1016/s0140-6736(12)60435-8

Shrubsole, C., Hamilton, I. G., Zimmermann, N., Papachristos, G., Broyd, T., Burman, E., Mumovic, D., Zhu, Y., Lin, B., & Davies, M. (2018). Bridging the gap: The need for a systems thinking approach in understanding and addressing energy and environmental performance in buildings. Indoor and Built Environment, 28(1), 100-117. https://doi.org/10.1177/1420326X17753513

Isabella Fyfe 26

Sustainability Victoria. (2019). Comprehensive Energy Efficiency Retrofits to Existing Victorian Houses https://assets.sustainability.vic.gov.au/susvic/Report-EnergyComprehensive-Energy-Efficiency-Retrofits-to-Existing-Victorian-Houses-PDF.pdf

Tennakoon, M., & Kulatunga, U. (2019). Understanding liveability: related concepts and definitions. https://doi.org/10.31705/WCS.2019.57

United Nations. (2016). Sustainable Development Goals. Retrieved 11 October from https://www.un.org/sustainabledevelopment/

Vakalis, D., Diaz Lozano Patino, E., Opher, T., Touchie, M. F., Burrows, K., MacLean, H. L., & Siegel, J. A. (2021). Quantifying thermal comfort and carbon savings from energyretrofits in social housing. Energy and Buildings, 241, 110950. https://doi.org/https://doi.org/10.1016/j.enbuild.2021.110950

Vella, K. (1990). The high rise at a glance : a summary paper profiling Ministry of Housing and Construction high rise accommodation. In V. M. o. H. a. Construction (Ed.).

Victorian Government. (2023). Victoria's Housing Statement. https://www.vic.gov.au/sites/default/files/202309/DTP0424_Housing_Statement_v6_FA_WEB.pdf

Willand, N., Maller, C., & Ridley, I. (2019). Addressing health and equity in residential low carbon transitions – Insights from a pragmatic retrofit evaluation in Australia [Article]. Energy Research and Social Science, 53, 68-84. https://doi.org/10.1016/j.erss.2019.02.017

World Green Building Council. (2019). Advancing Net Zero. Retrieved 29 August from https://worldgbc.org/advancing-net-zero/embodied-carbon/

Yoon, Y. B., Seo, B., Koh, B. B., & Cho, S. (2019). Performance analysis of a double-skin façade system installed at different floor levels of high-rise apartment building. Journal of Building Engineering, 26, 100900. https://doi.org/https://doi.org/10.1016/j.jobe.2019.100900

Isabella Fyfe 27
Isabella Fyfe 28 8 Appendices
1
Melbourne’s
high-rise
1990). Table
Inventory of Melbourne’s 44 high-rise social housing buildings (Vella, 1990). Estate number Estate name Estate location Address Building shape 1 Floyd Lodge Williamstown 63 Hamner Street 2 Nelson Heights Williamstown 235 Nelson Place 3 Gaskin Gardens Footscray 127 Gordon Street 4 Kensington Estate Kensington 56 Derby Street 72 Derby Street (demolished in 1999) 94 Ormond Street 100 Altona Street 5 Crown Street Estate Flemington 29 Crown Street
8.1 Appendix
Figure 16 Location of
21
social housing estates (Vella,
11
Isabella Fyfe 29 Estate number Estate name Estate location Address Building shape 6 Debney Park Flemington 12 Holland Court 120 Racecourse Road 125 Racecourse Road 130 Racecourse Road 7 North Melbourne/Hotham Hill Estate North Melbourne 33 Alfred Street 76 Canning Street 159 Melrose Street 12 Sutton Street 8 Reeves Street/Lygon Street Estate Carlton 480 Lygon Street 510 Lygon Street 530 Lygon Street 140 Neill Street 9 Elgin & Nicholson Street Estate Carlton 20 Elgin Street 141 Nicholson Street 10 Atherton Gardens Fitzroy 90 Brunswick Street 125 Napier Street 140 Brunswick Street 95 Napier Street 11 Collingwood Estate Collingwood 229 Hoddle Street 253 Hoddle Street 240 Wellington Street 12 Emerald Hill South Melbourne 200 Dorcas Street 13 Park Towers South Melbourne 332 Park Street 14 Layfield Court South Melbourne 150 Victoria Street 15 Horace Petty South Yarra 259 Malvern Street
Isabella Fyfe 30 Estate number Estate name Estate location Address Building shape 16 King Street Estate Prahran 1 Simmons Street 1 Surrey Road 25 King Street 27 King Street 17 Loxton Lodge Windsor 49 Union Street 18 Inkerman Heights East St. Kilda 150 Inkerman Street 19 Barkly Street Estate Brunswick 351 Barkly Street 20 Frank Wilkes Court Northcote 1 Holmes Street 21 Langdon Park Richmond 106 Elizabeth Street 108 Elizabeth Street 110 Elizabeth Street 112 Elizabeth Street 139 Highett Street

Table 12 Inventory of Melbourne’s 44 high-rise social housing buildings (Vella, 1990).

Image Name Location Architect(s) Social criteria Score Justification

Cité du Grand Parc Bordeaux, France Christophe Hutin architecture, Frédéric Druot, and Lacaton & Vassal

Fresh air access

5 Open-air balconies and provision of operable sliding doors increases resident's access to fresh air.

Window control access

Natural light access

Park Hill, Phase 1 Sheffield, UK Hawkins\ Brown and Studio Egret West

Pleasant views access

Fresh air access

5 Residents have total window (sliding door) control.

5 Replacing existing bay windows, sills and external walls with floor-to-ceiling glazing maximises access to natural light.

5 As above.

3 Windows are ventilated via side panels to keep their design simple, increasing fresh air access without the need to open a window.

Window control access

Natural light access

2 Windows are inoperable. There is some window (sliding door) access which can be controlled by residents.

4 The proportion of glazing was enlarged from one-third to twothirds.

criteria

Embodied carbon

Energy demand

2 Materials used in apartment retrofit include concrete, steel, transparent polycarbonate sheeting and aluminium doubleglazed glass sliding doors. All these materials have high embodied carbon emissions. However, most of the existing apartment structure was retained during the retrofit.

4 Significant improvements to energy performance recorded through addition of winter gardens, new glazing and thermal curtains. Heating consumption cut by 60%. Winter gardens have a double benefit as liveable space and thermal insulator.

Embodied carbon 1 The building was stripped back to its structural frame, resulting in significant embodied carbon emissions to replace the existing infill (precast concrete, brick and glass). New materials used include glass, concrete, steel, and anodised aluminium panelsmaterials which have high embodied carbon emissions.

(Lacaton & Vassal, 2021)

Energy demand 3 New external skins comply with required energy performance standards.

(BlundellJones, 2011; Gandh & North, 2019)

Isabella Fyfe 31 8.2 Appendix
2
Technical
Score Justification
Source

Pleasant views access

Park Hill, Phase

2 Sheffield, UK Mikhail Riches Fresh air access

Window control access

4 Floor to ceiling glazing provides access to pleasant views for residents. Views are somewhat obstructed by the anodised aluminium panels.

3 Fresh air only accessible through operable sliding doors. Not available through unoperable windows.

3 Window control through provision of sliding doors in living spaces and spaces with access to balconies. All other windows are fixed and nonoperable.

Natural light access

Pleasant views access

Cedar Court Glasgow, Scotland Collective Architecture Fresh air access

Window control access

Natural light access

3 No significant improvement to natural light access (openings remained same size).

3 No significant improvement to pleasant views access (openings remained same size).

4 Sufficient fresh air access through provision of operable windows.

5 All windows are operable giving residents full access.

3 Sufficient natural light access. Openings remain the same size after retrofit.

Embodied carbon

3 Majority of existing structure retained. Embodied carbon emissions associated with demolition and rebuild of apartment entrance areas, some internal walls, and insulation. New steel framing system, concrete railings, insulation, glazing and entry ways.

(Mark, 2023)

Energy demand

4 Thermal improvements made by adding insulation to inside of apartments - including cavity wall brick panels, balcony flank walls and soffits. Windows moved back into thermal line. Predicted operational energy improvement of 87% supporting transition from gas to electric heating.

Embodied carbon 3 Retention of existing building deemed positive. New windows, external insulation, HVAC systems, and winter gardens (enclosed existing balconies).

Energy demand

4 80% reduction in heating demand.

(Dunlop, 2019)

Isabella Fyfe 32

Pleasant views access 4 Access to pleasant views through addition of winter garden which provide more liveable space and transparency with the outside.

Ken Soble Tower Hamilton, Canada ERA Architects Fresh air access

5 Individual suite ventilations ensures fresh air delivery under Passive House certification.

3 Limited window control due to Passive House requirements. Natural light access 3 Some improved natural light access through the provision of floor to ceiling windows.

Embodied carbon 3 Majority of existing structure retained. Retrofit included addition of insulating building envelope, installation of Passive House certified windows, systems upgrade and internal renovation.

(ERA Architects, Unknown) Window control access

Energy demand 5 Operational carbon emissions reduced by 94%. Apartments meet Passive House energy performance standards.

Pleasant views access 3 Some improved pleasant view access through the provision of floor to ceiling windows.

Isabella Fyfe 33

8.3 Appendix 3

Table 13 Case study building existing apartment configurations and floor plan typologies.

Figure 17 Case study building floor plan typology A (not to scale).

Isabella Fyfe 34
Apartment floor level Bedsit 1-bed 2-bed Total Floor plan type 1 0 7 1 8 A 2 5 6 0 11 B 3 0 7 1 8 A 4 3 7 0 10 C 5 1 8 0 9 D 6 3 7 0 10 C 7 1 8 0 9 D 8 3 7 0 10 C 9 1 8 0 9 D 10 1 8 0 9 D 11 1 8 0 9 D 12 1 8 0 9 D Total 20 89 2 111

18 Case study building floor plan typology B (not to scale).

19 Case study building floor plan typology C (not to scale).

Isabella Fyfe 35
Figure Figure

Figure 20 Case study building floor plan typology D (not to scale).

Table 14 Floor play typology frequency. Floor Type Frequency

Isabella Fyfe 36
A 2 B 1 C 3 D 6 Total 12
Isabella Fyfe 37 8.4 Appendix 4
Figure 21 Apartment naming convention.

Figure 22 Apartment typologies selected for energy demand modelling including names and percentage of total apartments represented by each typology.

Isabella Fyfe 38

8.5 Appendix 5

Table 15 Case study building HERO energy software assumptions

Item

NCC building class

Climate Zone

Site exposure

Regulatory profile

Thermal bridging settings

Assumption

Class 2 Apartment(s)

60 – Tullamarine

Description

Exposed No buildings within immediate vicinity

NatHERS (2022)

NatHERS

Ceiling fan / ceiling penetrations No ceiling fans or ceiling penetrations

Exhaust fans to bathroom and kitchen

Zone type

Assume impact negligible on overall thermal performance of apartment

Kitchen/Living = Kitchen/Living

Bathroom = unconditioned

Bedroom = bedroom

2023 not available in software

NatHERS thermal bridging modelling settings applied

From photos, LED lights with external wiring are shown. Additionally, because floors are part of the buildings structural frame and constructed from precast concrete it is unlikely, they would be penetrated to install downlights.

Due to limitation in HERO software, exhaust fans are unable to be modelled within walls

In accordance with Technical Note

Insulation No insulation assumed (Floyd, 2007)

Eave connections

Screen connections

The shading devices with the most impact for each wall were modelled.

The shading devices with the most impact for each wall were modelled.

Due to software limitations, only two eave connections per wall can be made.

Due to software limitations, only three screen connections per wall can be made.

Isabella Fyfe 39

Table 16 NatHERS Technical Note modelling adjacencies matrix for Class 2 buildings.

Note: Number 11 was modelled for the case study building before the retrofit intervention and number 9 was modelled after the retrofit.

Isabella Fyfe 40

Fresh air access 2

Table 17 Social criterion scores before retrofit intervention.

Residents rely on passive systems within their apartments to provide fresh air access, since no HVAC systems are present. Hence, windows are the primary source of fresh air access for the apartments. The only mechanical systems present are wall-mounted extractor fans contained within the hallway windows adjacent the bathroom and kitchen spaces. Hence, air from the bathrooms and kitchens are expelled directly into the corridor spaces. Jara-Baeza et al. (2023) found that residents were ‘slightly satisfied with ventilation in the apartments. Within the corridor spaces themselves, there is always the provision of fresh air through vents located above the windows which are permanently open.

Extractor fans located in bathroom and kitchen spaces adjacent corridors

Window types in the apartments comprise different combinations of double hung, awning and fixed windows. These windows can be operated by residents when desired. However, the close proximity of neighbours passing by in the corridor spaces may limit and or restrict resident’s use of windows on apartment walls adjacent the corridor. Windows in the hallways are completely inoperable. Therefore, residents currently have no window control access in the corridor spaces.

Documentation drawings produced by BKK

Architects, Peter Elliot Architecture and Urban Design, and Taylor Cullity Lethlean on 23 August 2011; (Jara-Baeza et al., 2023); and photographs by Chris Barnett (date unknown).

Inoperable windows in corridor spaces

Documentation drawings produced by BKK Architects, Peter Elliot Architecture and Urban Design, and Taylor Cullity Lethlean on 23 August 2011; and photographs by Chris Barnett (date unknown).

Natural light access

Pleasant view access

Jara-Baeza et al. (2023) found that residents had a high (72%) level of daylight satisfaction. (Jara-Baeza et al., 2023)

All apartments have unobstructed pleasant views on the apartment-facing façade. However, views are obstructed on the corridor side due to the provision of the half-height cold rolled steel wall and vents.

Photographs by Chris Barnett (date unknown).

Isabella Fyfe 41 8.6 Appendix 6
Social criterion Score Justification Source
2
Window control access
4
3
Corridor vents

Social criterion Score

Social connection access 2

Currently, there is limited space for residents to stop and interact in the corridor spaces because they are too narrow. This limits residents access to social connection. Currently, resident's front doors open outwards into corridor space. Currently there is limited space for residents to stop and interact in the corridor spaces because they are too narrow.

Limited space for social connection

Isabella Fyfe 42
Justification Source
Photographs by Chris Barnett (date unknown).

8.7 Appendix 7

Table 18 Material information from EPiC database for use in embodied carbon calculations.

Material

Concrete 25MPa 2409 m³

Aluminium extruded powder coated 2712 kg

Justification

Commonly used for floor slabs, suspended slabs & precast wall panels

Common uses window frames and profiles,

Source Uses

EPiC database

Floor slabs, internal walls, fire stair walls,

EPiC database and Thermal Performance Report by (Floyd, 2007) Window frames Cold rolled steel 7850 kg 3.7

Commonly used for wall systems EPiC database Corridor wall panels Flat glass sheet - 12mm

Single glazed windows

Thermal Performance Report by (Floyd, 2007) All glazing Hardwood airdried

Solid timber door

Thermal Performance Report by (Floyd, 2007)

Doors and cupboards Plasterboard

Common use internal ceiling lining EPiC database Internal bulkhead

Images Communal flooring

Thermal Performance Report by (Floyd, 2007) Carpet to sitting/bed room

No vinyl available in EPiC, substitute with linoleum

Thermal Performance Report by (Floyd, 2007)

Bathroom and kitchen

Table 17 shows the embodied carbon calculations for floor plan typology D. Calculations for the other three floor plan typologies (A, B and C) were also conducted, however, the results of these calculations are not shown for simplicity.

Isabella Fyfe 43
Density (kg/m^3) Functional unit Embodied carbon (kgCO₂e/unit)
361
33.6
2600 m2 62.9
720 m³ 944
10mm 570 m2 5.8
-
Ceramic tile 2900 kg 1.3
images of building
Tufted carpet, nylon -quality 350 m2 33.3
See internal
See images
1200 m2 21.2
Linoleum sheet - 4mm

Table 19 Embodied carbon calculations for typical floor plan (floor plan typology D).

Isabella Fyfe 44
Isabella Fyfe 45 8.8 Appendix 8
Zone Element Base specification HERO software specification Notes Kitchen/ Living Floor 127mm pre cast concrete 150mm suspended concrete slab Closest floor thickness to actual thickness selected Floor covering Vinyl tiles (kitchen) and carpet (living) Vinyl (kitchen) and carpet (living) Ceiling 127mm pre cast concrete, light coloured paint 150mm concrete slab with exposed concrete ceiling, white coloured
ceiling thickness to actual thickness selected. For apartments modelled on Level 12, ceiling was modelled as a metal roof
adjacency to 'roofspace' with natural ventilation. External walls (loadbearing) 152mm pre cast concrete, internal light coloured paint, external rendered finish 150mm cast concrete, cream coloured Closest wall thickness and colour selected External walls (nonloadbearing) 102mm pre cast concrete, light coloured paint 100mm cast concrete, white coloured Closest wall thickness and colour selected Internal walls (loadbearing) 152mm pre cast concrete, light coloured paint 150mm cast concrete, white coloured Closest wall thickness and colour selected Windows Standard aluminium frames with single glazing Double and fixed windows Awning windows In accordance with NatHERS Guide to Windows Door Solid timber door Timber door hollow/solid R0.22 Bedroom Floor 127mm pre cast concrete 150mm suspended concrete slab Closest floor thickness to actual thickness selected Floor covering Carpet Carpet Ceiling 127mm pre cast concrete, light coloured paint 150mm concrete slab with exposed concrete ceiling, white coloured
ceiling thickness to actual thickness selected. For apartments modelled on Level 12, ceiling was modelled as a metal roof with adjacency to 'roofspace' with natural ventilation. External walls (loadbearing) 152mm pre cast concrete, light coloured paint 150mm cast concrete, cream coloured Closest wall thickness and colour selected
Table 20 Case study building material assumptions.
Closest
with
Closest

Internal walls (loadbearing)

Internal walls (nonloadbearing)

pre cast concrete, light coloured paint

pre cast concrete, light coloured paint

Standard aluminium frames with single glazing

cast concrete, white coloured

cast concrete, white coloured

wall thickness and colour selected

wall thickness and colour selected

Internal walls (loadbearing)

Internal

loadbearing)

External walls (nonloadbearing)

pre cast concrete, light coloured paint

pre cast concrete, light coloured paint

pre cast concrete, light coloured paint

pre cast concrete, light coloured paint

Closest ceiling thickness to actual thickness selected. For apartments modelled on Level 12, ceiling was modelled as a metal roof with adjacency to 'roofspace' with natural ventilation.

wall thickness and colour selected

windows In accordance with NatHERS Guide to Windows

Isabella Fyfe 46
152mm
150mm
Closest
102mm
100mm
Windows
Double
fixed
Awning
NatHERS
Door Solid timber door Timber door hollow/solid R0.22 Bathroom
127mm pre cast concrete 150mm suspended concrete slab Floor covering Vinyl Vinyl
127mm
150mm
Closest
and
windows
windows In accordance with
Guide to Windows
Floor
Ceiling
concrete slab with exposed concrete ceiling, white coloured
152mm
150mm
Closest
cast concrete, white coloured
wall thickness and colour selected
102mm
100mm cast
Closest
walls (non-
concrete, white coloured
wall thickness and colour selected
102mm
100mm
Closest
Windows
Double
Awning
Door Solid timber door Timber door hollow/solid R0.22 Corridor (retrofit
Structural frame 220 mm
220 mm Glulam outdoor CLT 200 mm non reflective cavity, timber clad, exposed Most
cast concrete, white coloured
Standard aluminium frames with single glazing
and fixed windows
intervention)
x
similar material of closest thickness was selected.

Floor

Sliding doors

Cold rolled steel panels with pebble-crete façade (150mm total thickness)

Doubled walled 5mm thick polycarbonate panels

cast concrete, stone covering

Timber framed double-glazed windows modelled at 0% openability

Metal floor unable to be selected. Alternative materials available = concrete or timber. Concrete selected over timber. Stone covering selected to reflect pebble-crete finish.

Window type with most similar U and SHGC values selected. 0% openability was modelled to reflect the case where all sliding-doors are closed

Isabella Fyfe 47
150mm

8.9 Appendix 9

This appendix details the parameters used to create energy model 8 (i.e. apartment B.2.4) and model 11 (i.e. apartment C.8.10).

Eave continued off page

Wing wall continued off page

Can only have max. 5 screen connections and 2 eave

Apartment B.2.4

Wing wall continued off page

Figure 23 Model 8 showing wall adjacencies (see legend) and screen (shown as green dashed lines) and eave attachments (shown as red dashed lines).

Table 21 Model 8 – wall types and adjacencies.

Isabella Fyfe 48

Table 22 Model 8 – floor types and adjacencies.

Table 23 Model 8 – ceiling types and adjacencies.

Table 24 Model 8 – door and window specifications.

Table 25 Model 8 – screen connections.

Table 26 Model 8 – wing wall parameters.

Isabella Fyfe 49

Table 27 Model 8 – eave connections.

Eave continued off page

Wing wall continued off page

Eave continued off page

Figure 24 Model 11 showing wall adjacencies (see legend) and screen (shown as green dashed lines) and eave attachments (shown as red dashed lines).

Isabella Fyfe 50
Apartment C.8.10

Table 28 Model 11 – wall types and adjacencies.

Table 29 Model 11 – floor types and adjacencies.

Table 30 Model 11 – ceiling types and adjacencies.

Table 31 Model 11 – door and window specifications.

Table 32 Model 11 – wing wall parameters.

Isabella Fyfe 51

Table 33 Model 11 – screen connections.

Table 34 Model 11 – eave connections.

Isabella Fyfe 52

8.10 Appendix 10

This appendix presents drawings of the retrofit intervention It should be noted that all social and technical analyses conducted as part of the STS decision support tool application on the case study building was performed for the ‘base case’ retrofit design intervention (see Figure 25). This includes embodied carbon calculations and energy performance analysis for the case study building post-retrofit. The proposed design intervention incorporates a push/pull façade system of elements that can be used to create different spatial configurations and therefore liveability conditions (see Figure 26 and Figure 27). Hence, the liveability, embodied carbon, and energy performance results of this potential case will differ from the base case results.

Isabella Fyfe 53
Figure 25 Base case plan.

26 Push/pull façade system of elements.

Figure 27 Potential retrofit case demonstrating push/pull façade system.

Isabella Fyfe 54
Figure

8.11 Appendix 11

Table 35 Social criterion scores after retrofit intervention.

Social criterion Score

Fresh air access 4

Window control access 4

Natural light access 5

Pleasant view access 5

Social connection access 5

Justification

Fresh air access has significantly improved for the corridor spaces. The amount of space on the corridor façade able to be opened to provide fresh air access has significantly improved. This will also improve the fresh air access to the apartments through the kitchen and bathroom windows adjacent the corridor.

Post retrofit, residents can fully control windows in the corridor spaces. There is no change to the window control access in the apartments.

Access to natural light significantly improved in the corridor spaces due to the provision of semi-opaque floor to ceiling polycarbonate sliding doors. Increased natural light in the corridor spaces also increases the natural light in the bathroom and kitchen spaces, since these are adjacent the corridor. Although the increase corridor width as part of the retrofit intervention may reduce some provision of natural light, this is assumed to be mitigated by provision of the floor to ceiling sliding doors.

Again, the provision of semi-opaque floor to ceiling polycarbonate sliding doors in place of the half-height cold rolled steel wall and aluminium powder coated vents significantly increases access to pleasant views.

The additional balcony space is 1720 mm deep. This increase in area allows for better access to social connection for residents. The corridor spaces are transitioned from transitory spaces to spaces where people can stop and have conversations, arrange furniture, create community and/or private gardens, etc.

Isabella Fyfe 55

8.12 Appendix 12

Table 36 Material information from EPiC database for use in embodied carbon calculations post retrofit.

Material

Glued laminated timber (glulam) outdoor 430.00 m³ 1605

Concrete 25MPa 2409 m³ 361

Justification

Commonly used for structural members, columns and beams

Source Uses

Gluelam columns, beams, and cross bracing

Commonly used for floor slabs, suspended slabs & precast wall panels Pebblecrete facade panel

Glued laminated timber (glulam) outdoor

Concrete 25MPa Cold rolled steel 7,850.00 kg 3.7

Commonly used for wall systems Corridor wall panels Cold rolled steel

Ceramic tile 2,900.00 kg 1.3 See internal images of building Communal flooring Ceramic tile Hardwood airdried 720.00 m³ 944 Solid timber door Balustrade Hardwood air-dried

Polycarbonate 1,200.00 kg 14 2-walled polycarbonate Sliding doors Polycarbonate Stainless steel wire 7,740.00 kg 13.9 Wire mesh facade Stainless steel wire

Isabella Fyfe 56
Functional unit
carbon
Density (kg/m^3)
Embodied
(kgCO₂e/unit)
Isabella Fyfe 57
Figure 28 Embodied carbon calculations for retrofit intervention.

8.13 Appendix 13

This appendix details the parameters used to create energy model 8 (i.e. apartment B.2.4) and model 11 (i.e. apartment C.8.10) after the retrofit intervention. Note: a significant limitation of this model is the inability to model doors and windows on the apartment wall adjacent to the corridor zone. This is due to limitations in HERO software that prevent doors and windows being modelled inside walls that are not modelled with internal or external adjacency. Instead, the adjacency of the was default set to ‘corridor’ by the software.

Artificial internal walls of zone modelled as ‘neighbour’ adjacency

Glulam structure modelled as CLT since material not present in material library

Unable to model doors and windows on apartment wall adjacent corridor zone

Timber-framed polycarbonate sliding doors modelled as timberframed single glazed sliding doors since material not present in library

Zone modelled as ‘glazed corridor’ and is excluded from apartment energy performance calculations

Isabella Fyfe 58
Figure 29 Model 8 after retrofit showing wall adjacencies.

Table 37 Model 8 after retrofit – wall types and adjacencies.

Table 38 Model 8 after retrofit – floor types and adjacencies.

Table 39 Model 8 after retrofit – ceiling types and adjacencies.

Isabella Fyfe 59

Table 40 Model 8 after retrofit – door and window specifications.

Table 41 Model 8 after retrofit – wing wall parameters.

Artificial internal walls of zone modelled as ‘neighbour’ adjacency

Unable to model doors and windows on apartment wall adjacent corridor zone

Figure 30 Model 11 after retrofit showing wall adjacencies (see legend) and screen and eave attachments (shown as red dashed lines).

Isabella Fyfe 60

Table 42 Model 11 after retrofit – wall types and adjacencies.

Table 43 Model 11 after retrofit – floor types and adjacencies.

Table 44 Model 11 after retrofit – ceiling types and adjacencies.

Isabella Fyfe 61

Table 45 Model 11 after retrofit – door and window specifications.

Table 46 Model 11 after retrofit – wing wall parameters.

Isabella Fyfe 62

Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.