48'-9" [14.86m]
20' [6.10m]
22'-1" [6.73m]
16'-10" [5.12m] LEFT SETBACK
42'-10" [13.06m]
E.EL. 72.45 P.EL. 72.79
E.EL. 72.54 P.EL. 72.84
5% DN
BUILDING - INTERIOR DESIGNERS
E
OP SL
] .62m K 7 [ ' 5 C 2 ETBA S R A RE GARAGE FRONT 73.30
E.EL. 73.59 P.EL. 73.47
22' [6.70m] FRONT SETBACK
E.EL. 73.32 P.EL. 73.32
77'-8" [23.66m] BUILDING DEPTH
6' [1.83m] RIGHT SETBACK
UDC DESIGN CENTER LTD
44'-3" [13.49m]
TO BE REMOVED
33'-10" [10.31m]
SITE PLAN SCALE:1/8"-1'
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
Pardeep Chahal PROJECT: CIVIC ADDRESS: 6108 136 STREET SURREY, BC LEGAL DESCRIPTION: LOT #8 SECTION 9
TOWNSHIP 2 NWD PLAN LMP32943 - PID: 023-750-235
SITE PLAN
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JULY. 2017
FILE NO.
SCALE:
1/8" = 1'-0"
V01
SHEET NO:
A1
41'-4" 26'-8" 4'-6"
14'-8"
21'-5"
5'-3"
6'-8"
7'-11"
3050RS
5080
7'-4"
5050RS
13'-10"
14'-10"
529439
8050TC
2680
22'-9"
7'
7'-6"
5080 3044RS
S CO
10'-4"
13'-4"
5'-3"
2'-4"
18080
10'-4"
2070TH
9'-2"
1'-9"
6'-10"
8'-4"
5080
2680
3080 2680
3080
LINE OF DROP CEILING
14'-2"
52'-3"
8050RS
4050RS
UP
2070TH
52'-3"
2680 2'-5"
2680
4'-1"
15'-8"
A1 A
3050RS
BUILDING - INTERIOR DESIGNERS
6080
8080
DN
A1 A
7'-10"
SMOKE ALARM & CARBON MONOXIDE (CO) ALARM
11'-10"
3080 9'-2"
4040RS 4'-9"
4040RS 4'-7"
4'-1"
9'-4"
21'
3080 10'-5"
3050RS
9'-8"
FIRE RATED, SOLID CORE, WEATHER STRIPPED, SELF CLOSING DOOR
6'-10"
1'-4"
3050RS
15'-4"
S
SMOKE ALARM & CARBON MONOXIDE (CO) ALARM
10'
S CO
EXTENT OF SUITE30 MIN. FIRE RATED FOR WALLS AND CLG.
4080
3050RS
3'-5"
S
5'-8"
4'-2"
2580 2880
EXTENT OF SUITE30 MIN. FIRE RATED FOR WALLS AND CLG.
FIRE RATED WALL
2'-8"
2'
21'-9"
21080
2680
3050RS
2380
5'-4"
3'-10"
2680
2'-8"
2680
6070RS
UDC DESIGN CENTER LTD
3'
5'
4040RS 5'-8"
2'-2"
5'-3"
5'-1"
20'-2"
14'-8" 27'-2"
77'-11"
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
Pardeep Chahal PROJECT: CIVIC ADDRESS: 6108 136 STREET SURREY, BC LEGAL DESCRIPTION: LOT #8 SECTION 9
TOWNSHIP 2 NWD PLAN LMP32943 - PID: 023-750-235
MAIN FLOOR
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JULY. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
SHEET NO:
A2
38'-4" 21'-5" 1'-6"
16'-11"
13'-10"
3'
3'
4'-7"
4040RS
4040RS
3'-11" 3'-11"
14'-9"
14'-3"
4568
6450RS
3'-6"
3'-5"
4068
S
11'-4"
5'-3"
2'-4"
4'-4"
21068
2668
5'-10"
3'
5'-8"
3'-10"
2668
6 : 12
8067FX
7'-6"
4'-10"
21068
5'-5"
A1 A 3'
5'-3"
15'-8"
BUILDING - INTERIOR DESIGNERS
4040FX
6 : 12
A1 A
24'-9"
S
5'-7"
52'-3"
21068
DN
52'-3"
6 : 12
2668
7'
9'-2" S
3'-8"
6040RS
2668
6'-11"
4060SH 27'-6"
3'-4" 1'-5"
2668
2668
S
3'-9"
4060SH
6'
LINE OF DROP CEILING
2030RS
2668
3'-8"
2068
11'-8"
11'-8"
7'-9"
6 : 12
7'-2"
3068
2668
21'-10"
8'-10"
S
6068
6 : 12
6 : 12
UDC DESIGN CENTER LTD
3'
2668
3'-6"
4040FX
10'-11"
4040FX
20'-11"
1'-4"
21'-6"
8'-6"
3' 11'-6"
5'-8"
4'-3"
4'
9'-11"
13'-11"
56'-9"
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
Pardeep Chahal PROJECT: CIVIC ADDRESS: 6108 136 STREET SURREY, BC LEGAL DESCRIPTION: LOT #8 SECTION 9
TOWNSHIP 2 NWD PLAN LMP32943 - PID: 023-750-235
TOP FLOOR
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JULY. 2017
FILE NO.
SCALE:
1/4"=1'-0"
V01
SHEET NO:
A3
4060SH
4'-912" [1.46m]
ATTIC ATTIC VENTILATION AS PER BUILDINGCODE A/300 OF INSULATED CEILING AREA MIN. 25% OF VENTING @TOP & 25% @ BOTTOM
4'-912" [1.46m]
U/S CEILING LVL. 80.35
6040RS
12 6
2
4040FX
3068
2668
5
12
6080 8080
2070TH
3044RS
2070TH 5080
3080
MAIN FL. LVL. 73.47 AVE. GRADE. LVL. 72.97
E.EL. 72.54 P.EL. 72.84
SCALE:1/8"-1'
SECTIONAL DETAILS AND SPECIFICATIONS: 1
MATERIAL SPECIFICATIONS
2.
OUTSIDE GUTTERS - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
3.
1 x 4 OVER 2" X 10" FASCIA BOARD
4.
4" OR 6" WINDOW AND DOOR TRIM
5.
HARDY PANEL
6.
ALUMINUM FRAMED WINDOW AND PATIO DOOR
7.
WOODEN EXTERIOR DOOR
8. 9.
STONE CEDAR
2680
2680
18080
5
ROOF: - ROOF FINISH: 210 # ASPHALT SHINGLES ROOF - STARTER STRIP - 716" OSB SHEATHING c/w. H. CLIPS - PREFAB. ENG. TRUSSES @ 24" O.C. - R-50 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
2
6
EXTERIOR WALLS (2 hr FRR):
B
0"
0"
7'-6" TO 8'-0"
18"
20"
8'-1" TO 9'-0"
14"
20"
9'-1" TO 10'-0"
12"
20"
5 8" ANCHOR BOLT @ 48" o.c. (MAX. OF 1 PLATE UNDER JOIST.)
TYPICAL FLOOR CONSTRUCTION
VERTICAL STEEL = 'A' (ALTERNATE HOOKS) MAX. COVER 2" HORIZONTAL STEEL = 'B' (LAP JOINTS 18" MINIMUM) APPLY DAMPROOFING AS REQ. BY N.B.C. SECT.9-13
INTERNAL INSULATED WALL
24"
W1(C): -38mm(121")X 89mm(312") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
W1(C): -38mm(112")X 89mm(312") STUDS SPACED 400mm OR 600mm -WITH 89mm THICK ABSORPTIVE MATERIAL -15.9mm(5 8") TYPE X GYPSUM BOARD
5
8" TYPE "X" GYPSUM BOARD ON BOTH SIDES CONTINUOUS TO UNDERSIDE OF FLOOR SHEATHING (HATCHED AREA)
F.R.R WALL DETAIL
SUBFLOOR
NOTCH OUT 12" TYPE "X" GYPSUM BOARD FOR FLOOR JOISTS
4" CONC. SLAB ON 6 MIL. POLY. V.B. ON 6" COMPACTED GRANULAR FILL
8" REINFORCED CONCRETE FOUNDATION WALL
- 2" AIR SPACE - 2 x 4 SPF # 2 STUDS @ 24" O.C. (U.N.O.) - R-14 BATT. INSULATION - 6 MIL. POLY. V.B. - C/W TUCK TAPE JOINTS - 1/2" DRYWALL
FLOOR JOIST
30 MIN. F.R.R. ASSEMBLY DETAIL
21 2" RIGID INSULATION (N.I.C.) TO BELOW FROSTLINE OR 2x4 FURRED WALL w/ R12 F.G. BATT INSUL. (N.I.C.) WHERE INDICATED
FOUNDATION WALLS:
A
EXTERIOR WALL CONSTRUCTION
GARAGE SLAB OR FINISHED GRADE
- 2 x 6 SILL PLATE - 8" CONC. FOUNDATION WALL - 2 COATS OF ASHPALT EMULSION TO EXTERIOR FACE - 2 - 15M T & B, 10M @16" O.C E/W.1.F UP TO GRADE
- STUCCO ON WIREMESH - METAL LATH - 19MM (3/4") AIR SPACE / @ 16" O.C. - 15# BREATHER TYPE BUILDING PAPER - 15 32" SHEATHING - 2 x 6 STUDS @ 16" O.C. - R-20 BATT INSULATION - 6 MIL. POLY. V.B. - 5/8" DRYWALL FIN.
A
LESS THAN 7'-6"
2" FROM GARAGE SLAB OR SIDEWALK 8" MIN. FROM FINISH GRADE
BASEMENT FLOOR:
INTERIOR PARTITIONS ( 1 hr FRR): 7
NET BACKFILL HT.
NOTE: 1. REBAR TO BE 230 MPa MINIMUM. 2. CONCRETE TO BE 20 MPa MINIMUM. 3. BACKFILL NOT TO EXCEED 20 KN/ cubic METER
- FINISH FLOOR: TO OWNERS SPEC'S - 0'-6" CONC. SLAB - 10 GA 6 x 6 WIRE MESH - 6 MIL. POLY. V.B. - R-10 RIGID INSULATION - MIN. 12" COMPACTED GRANULAR FILL
- 1/2" GYPSUM BOARD (BOTH SIDES) - 2 x 4 STUDS @ 16" O.C. - INSUALTED CAVITY
4
MAIN AND UPPER FLOOR (1 hr FRR):
- 5 8" TYPE "X" GYPSUM BOARD (FIN. AS PER OWNER)
- BUILT-IN GUTTER - 2 x 12 FASCIA BOARD - METAL SOFFIT WITH 2" CONTINUOUS SCREENED VENT
3
SUPPORTED WALL (10M BAR)
- FINISH FLOOR: TO OWNERS SPEC'S - P.T. 2x10 @16 o.c. JOISTS AS PER MANUFACTURERS SPECS - 11/2"th. CONCRETE TOPPING - R-40 SPRAT FOAM INSULATION
EAVES:
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(112")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(58") TYPE X GYPSUM BOARD
NET BACKFILL HEIGHT
REAR ELEVATION
ASPHALT SHINGLE 40 YRS - IKO CAMBRIDGE, DUAL BLACK
2680
7
E.EL. 73.32 P.EL. 73.32
SCALE:1/8"-1'
1.
2680
6 MAIN FL. LVL. 73.47 AVE. GRADE. LVL. 72.97 1'-73 4" [0.50m]
E.EL. 72.45 P.EL. 72.79
3050RS 15
5
8" TYPE "X" GYPSUM BOARD AGAINST SEPARATION WALL
F5(D): -SUBFLOOR OF 15.5mm PLYWOOD, OSB OR WAFERBOARD OR 17mm TONGUEAND GROOVE LUMBER -38mm(121")X 235mm(914") WOODFLOOR JOISTS -ABSORPTIVE MATERIAL IN CAVITY -METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm(58") TYPE X GYPSUM BOARD
-METAL FURRING CHANNELS SPACED 600mm O.C. -15.9mm (58") TYPE X GYPSUM BOARD
15M @ 15" o.c.
DETAIL AT 'A'
8"
WITH DRAIN ROCKS
ON PLAN
E.EL. 73.59 P.EL. 73.47
3050RS 15
1'-115 8" [0.60m] FOOTING LVL.: 72.37
5080
3050RS
TYP.FLR. ASSEMBLY GYPSUM BOARD FLR. JOINTS @ 16" o.c. AS ER STRUC. ENG. 5 " T&G PLYWOOD SUBFLOOR 8 RADIANT HEATING PIPES ON WIRE MESH 1- 12" LIGHT WEIGHT CONC. TOPPING FLOOR FINISH 1" 2
1'-73 4" [0.50m]
5080
26'-7" [8.11m]
26'-7" [8.11m] 6070RS
11'-13 8" [3.39m]
11'-13 8" [3.39m]
4050RS
FRONT ELEVATION
F.R.R. CEILING DETAIL
2-15M CONT. AS NOTED ON PLAN
12 6
4040RS
4040RS 16
9'-03 4" [2.76m]
U/S CEILING LVL. 80.35
9'-03 4" [2.76m]
U/S CEILING LVL. 80.35
4040FX 16
SUPPORTED WALL SECTION
12 6
4'-912" [1.46m]
MEAN ROOF LVL. 81.92
4'-912" [1.46m]
MEAN ROOF LVL. 81.92
4'-912" [1.46m]
ROOF RIDGE LVL. 83.49
4'-912" [1.46m]
ROOF RIDGE LVL. 83.49
16
2030RS 4040FX
6
16
26'-7" [8.11m] 3050RS
5050RS 15
25
3080
E.EL. 72.54 P.EL. 72.84
E.EL. 72.45 P.EL. 72.79
1'-73 4" [0.50m]
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
MAIN FL. LVL. 73.47 AVE. GRADE. LVL. 72.97 1'-73 4" [0.50m]
MAIN FL. LVL. 73.47 AVE. GRADE. LVL. 72.97
18080
11'-13 8" [3.39m]
SECOND FLOOR LVL. 77.59
11'-13 8" [3.39m]
SECOND FLOOR LVL. 77.59 26'-7" [8.11m]
BUILDING - INTERIOR DESIGNERS
1'-73 4" [0.50m]
MAIN FL. LVL. 73.47 AVE. GRADE. LVL. 72.97
8050TC
SECOND FLOOR LVL. 77.59
6
11'-13 8" [3.39m]
SECOND FLOOR LVL. 77.59 26'-7" [8.11m]
SECOND FLOOR LVL. 77.59
AS NOTED
6068
DUROID ROOF BUILDING PAPER ON 12" PLYWOOD ENG.TRUSSES @24" O/C R-40 BATT INSULATION 6 MIL POLY V.B. (LAPPED JOINTS,SEAL ELECT. OUTLETS) (WARM SIDE) 5 8" GYPSUM BOARD BUFFLES 2" CLEAR FROM TOP
9'-03 4" [2.76m]
6450RS 4060SH
MEAN ROOF LVL. 81.92
9'-03 4" [2.76m]
U/S CEILING LVL. 80.35
8067FX
12 6
4'-912" [1.46m]
MEAN ROOF LVL. 81.92
9'-03 4" [2.76m]
U/S CEILING LVL. 80.35
ROOF RIDGE LVL. 83.49
4'-912" [1.46m]
12 6
4'-912" [1.46m]
MEAN ROOF LVL. 81.92
UDC DESIGN CENTER LTD
ROOF RIDGE LVL. 83.49
4'-912" [1.46m]
ROOF RIDGE LVL. 83.49
4040FX 3050RS
16
4040FX
4040FX 3050RS
16
15
16 15
3080
3080
E.EL. 73.59 P.EL. 73.47 E.EL. 73.32 P.EL. 73.32
LEFT ELEVATION
RIGHT ELEVATION
SCALE:1/8"-1'
SCALE:1/8"-1'
LEFT ELEVATION
RIGHT ELEVATION
TOTAL AREA: 1018 SQ. FT. [94 SQ.M] DISTANCE TO PROPERTY LINE: 11'3" (3.44 M) ≈ 4.0M MAX. ALLOWABLE UNPROTECTED AREA @ 18.0% = 183.24 SQ. FT. PROPOSED UNPROTECTED AREA: 88 SQ. FT
TOTAL AREA: 1336 SQ. FT. [130 SQ.M] DISTANCE TO PROPERTY LINE: 6'0" (1.83 M) ≈ 2.0M MAX. ALLOWABLE UNPROTECTED AREA @ 8.0% = 106.8 SQ. FT. PROPOSED UNPROTECTED AREA: = 100 SQ. FT
CLIENT:
SHEET TITLE:
Pardeep Chahal PROJECT: CIVIC ADDRESS: 6108 136 STREET SURREY, BC LEGAL DESCRIPTION: LOT #8 SECTION 9
TOWNSHIP 2 NWD PLAN LMP32943 - PID: 023-750-235
ELEVATIONS AND SECTION
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JULY. 2017
FILE NO.
SCALE:
1/8" = 1'-0"
V01
SHEET NO:
A4
BUILDING - INTERIOR DESIGNERS
UDC DESIGN CENTER LTD
∙
UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
Pardeep Chahal PROJECT: CIVIC ADDRESS: 6108 136 STREET SURREY, BC LEGAL DESCRIPTION: LOT #8 SECTION 9
TOWNSHIP 2 NWD PLAN LMP32943 - PID: 023-750-235
ENERGY DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JULY. 2017
FILE NO.
SCALE:
N.T.S.
V01
SHEET NO:
A5
GRID
GRID GRID
HEADER
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.) 1/2"CONTROL JOINT FLOOR FINISH ON C/W CAULK AND ROD CONCRETE TOPPING
MIN. 3/8" GAP BETWEEN WINDOW & 1X2 STRAPPING
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
4" ADHERED FLASHING MEMBRANE
INTERIOR
100 mm (4")
FLOOR FINISH ON CONCRETE TOPPING
SHEATHING PAPER BEHIND FLASHING AND INTO WINDOW OPENING INSECT SCREEN
MIN. 2% SLOPE TO DRAIN SEALANT JOINT AT VENT DUCT TO HOUSEWRAP (A.B.)
2"CONTINUOUS FLANGE AT PERIMETER OF HOOD
STUD @ 16" O.C
2"
2
SEALANT OR GASKET (A.B.) BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED
1 MIN 2"
BLDG. PAPER
4.06
23.03
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
3.99
22.61
0.68
4.11
23.29
ADHERED MEMBRANE FLASHING TO LAP 100mm (4") OVER SHEATHING PAPER BELOW
ROOF ASSEMBLY COMPONENTS (W/ ASPHALT SHINGLES) 1 ROOFING SHINGLES 2 POLYTHENE V.B 5 ″ (15.88 MM) OSB SHEATHING 3 8 4 2 x 10 JOISTS W/ R50 BATT @ 24″ O.C. 5 POLYETHYLENE 6 1/2″ (12.7 MM) GYPSUM BOARD 7 INTERIOR AIR FILM
RSI 0.077 0.00 0.136 8.8 0.00 0.08 0.12
R 0.44 0.00 0.77 50.0 0.00 0.45 0.68
SEALANT OR GASKET JOINT AT POLYETHYLENE (A.B. & V.B.) TO PLATE (A.B.)
2X10 FLOOR JOISTS
SEAL POLYETHYLENE (V.B.) TO SHEATHING PAPER (A.B.)
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
9.21
50.34
FLOOR ASSEMBLY OVER UNHEATED SPACE 1 EXTERIOR AIR FILM 2 FLOOR FINISHES (3 4" HARDWOOD) 3 POLYETHYLENE 4 512" CONC. SLAB 5 R-28 INSULATION 9 NATURAL GRADE
RSI 0.03 0.12 0.00 0.15 4.99 0.00
R 0.17 0.68 0.00 0.83 28.00 0.00
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
5.29
29.68
TRIPLE GLAZED WINDOWS & DOORS LOW E, DOUBLE GLAZED (6mm GAP), TEMPERED GLASS εn = 0.1, AIR FILLED WITH VINYL OR FIBRE GLASS FRAME
USI
U
1.4
0.246
SEPERATION AIR SPACE
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
1 MIN.
RSI R 0.03 0.17 0.035 0.20 1.06 6.00 0.00 0.00 0.11 0.62 2.55 14.49 0.00 0.00 0.08 0.45 0.00 0.00 0.12 0.68 .12
1" 2
2a
2 SEALANT OR GASKET (A.B.)
EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
EFFECTIVE RSI / R VALUE OF ENTIRE ASSEMBLY
12mm (1/2")
SEAL POLYETHYLENE (A.B. & V.B.) TO HOUSEWRAP (A.B.)
1X2 STRAPPING
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
PREFINISHED METAL FLASHING C/W END DAMS TO EXTEND 1" PAST END OF WINDOW FRAME
VENTED ALUMINUM SOFFIT PANELS EFFECTIVE RSI - 4.06 SEAL SHEATHING PAPER (A.B.) TO WINDOW FRAME REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
1.5" SILL PLATE
BUILDING - INTERIOR DESIGNERS
EXTERIOR STUCCO CLADDING
- HEAVY- DUTY POLYVINYL CHLORIDE (PVC )
INTERIOR
AIR SPACE W/ 1x2 TREATED WOOD STRAPPING SCREWED THROUGH INSULATION
THERMOPLASTIC WATER PROOFING MEMBRANES ARE OVERLAPPED AND HEAT FUSED ( APPLICATION CODE :CGSB -37-GP-55M)
SEALANT OR GASKET POLYETHYLENE TO PLATE (A.B.)
FLASHING & COUNTER FLASHING
SEALANT OR GASKET (A.B.)
ASPHALT IMPREGNATED PAPER
INSECT SCREEN - NO DAMPERS
EFFECTIVE RSI VALUE = 6.06 ROOFING SHINGLES (M.B.) WATERPROOF ROOF MEMBRANE (M.B.) FOR EAVE PROTECTION 5/8" OSB ROOF SHEATHING W/ H CLIPS WOOD ROOF FRAMING R-50 BATT INSULATION POLYETHYLENE (A.B. & V.B.) GYPSUM BOARD
GRID
1/2″ (12.7 MM) PLYWOOD SHEATHING
2 X 2 BLOCKING AT BOTH ENDS OF VENT 11/2" CONT. VENT
POLYETHYLENE VAPOR BARRIER
ADHERE SUBFLOOR TO HEADER (A.B.) FLOOR FINISH ON CONCRETE TOPPING
EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING
EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 (RSI-1.06)
1/2″ (12.7 MM) GYPSUM BOARD
MIN. 2% SLOPE TO DRAIN
2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. SLOPED SUB-SILL FRAMING
SEALANT OR GASKET (A.B.) REFER TO W-1 FOR EXTERNAL WALL ASSEMBLY DETAIL
INSULATION GUARD
POLYETHYLENE (V.B. AND A.B.) SEALANT OR GASKET (A.B.)
EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
GASKET (A.B.)
BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED
LAP POLYETHYLENE AND SEAL TO ADHERED MEMBRANE (A.B. AND V.B.)
W-1
SEALANT AND BACKER ROD JOINT AT WINDOW FRAME TO MEMBRANE (A.B. AND M.B.) SEALANT FILLET JOINT PREFINISHED METAL DRIP FLASHING
SEALANT BETWEEN POLYETHYLENE AND HOUSEWRAP (A.B.) FLOOR FINISH ON CONCRETE TOPPING
INTERMITTENT 1/8" P.T. SHIM BEHIND WINDOW FLANGE TO CREATE DRAINAGE PATH (ALTERNATELY DRILL HOLES OR SLOTS THROUGH WINDOW FLANGES TO TO ALLOW FOR DRAINAGE)
HOUSEWRAP AT HEADER (A.B.)
BATT INSULATION POLYETHYLEN (V.B.) STAPLED IN PLACED GYPSUM BOARD
BATT INSULATION POLYETHYLENE (V.B.) STAPLED IN PLACE
25mm (1")
ADHERED MEMBRANE FLASHING (M.B.) SILL GASKET (A.B.)
2" MIN.
FILTER CLOTH
CEMENT OR ACRYLIC STUCCO PARGING
SEE 'FLASHING-BEST PRACTICE GUIDE' FOR ADDITIONAL ROOF FLASHING DETAILS
DAMP PROOFING / VAP. BARRIER EFFECTIVE RSI - 4.06 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
8" CONC. FOUNDATION WALL
FINISHED GRADE
4" EXTRUDED POLYSTYRENE R-5/in. 1" 2
REFER TO W-2/A-501 FOR FND WALL ASSEMBLY DETAIL
DRYWALL FINISH
912"
INSECT SCREEN
VENTED ALUMINUM SOFFIT PANELS
FLOOR OVER UNHEATED SPACE EFFECTIVE RSI 2.06
512"
CEMENT OR ACRYLIC STUCCO PARGING
8" MINIMUM
SHEATHING PAPER TO LAP OVER ADHERED MEMBRANE FLASHING
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
SEAL HOUSEWRAP (A.B.) TO FRAMING
CONTINUE EAVE PROTECTION 12" BEYOND INSIDE FACE OF WALL
ADHERED MEMBRANE FLASHING TO EXTEND 4" AND LAP OVER SHEATHING PAPER
INTERIOR
1/2"
UDC DESIGN CENTER LTD
ROD AND SEALANT
4" FLANGE
25.4mm (1")
R 0.17 0.62 6.00 0.00 0.62 14.49 0.00 0.45 0.00 0.68
WALL ASSEMBLY COMPONENTS (W/ STUCCO CLADDING) 1 EXTERIOR AIR FILM 3 " STUCCO FIN. 2 4 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER2 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM
SHEATHING PAPER TO LAP METAL FLASHING
ROD AND SEALANT 1
RSI 0.03 0.11 1.06 0.00 0.11 2.55 0.00 0.08 0.00 0.12
VALUES ADOPTED FROM CANADIAN WOOD COUNCIL
4" FLANGE 6
WALL ASSEMBLY COMPONENTS (W/ NINYL CLADDING) 1 EXTERIOR AIR FILM 2 VINYL SIDING (NO AIR SPACE) 3 EXTERNAL 1.5" RIGID MINERAL FIBRE INSUL. R-6 4 ASPHALT IMPREGNATED PAPER 5 1/2″ (12.7 MM) PLYWOOD SHEATHING 6 2×6 FRAMING FILLED WITH R22 BATT @ 16″ O.C. 7 POLYETHYLENE 8 1/2″ (12.7 MM) GYPSUM BOARD 9 FINISH: 1 COAT LATEX PRIMER AND LATEX PAINT 10 INTERIOR AIR FILM
EXTERIOR
4"
EFFECTIVE RSI - 3.99 REFER TO W-1/ A-501 FOR EXTERNAL WALL ASSEMBLY DETAIL EXTERNAL WALL W/1.5" RIGID MINERAL FIBRE INSUL. R-6
RSI / R VALUE CALCULATIONS FOR ASSEMBLIES
EFFECTIVE USI VALUE - 1.4 OPERABLE VINYL OR FIBERGLASS FRAME LOW ENERGY, DBL. GLAZED TEMP. GLASS W/ SLOPED SILL WEATHER STRIPPING
COMPLETE W/ 4" EXTRUDED POLYSTYRENE FOAM BOARD INSUL. R-5/in.
WOOD FRAMING (STUDS OR STRAPPING)
W-2 UNIT # 202, 7750 128 STREET SURREY BC, V3W0R6 TEL: 778-858-8794 FAX:604-593-5864 EMAIL: UDCDESIGN @HOTMAIL.COM WEB: WWW.UDCDESIGNS.COM
CLIENT:
SHEET TITLE:
Pardeep Chahal PROJECT: CIVIC ADDRESS: 6108 136 STREET SURREY, BC LEGAL DESCRIPTION: LOT #8 SECTION 9
TOWNSHIP 2 NWD PLAN LMP32943 - PID: 023-750-235
GENERAL DETAIL
DRAWN BY:
G.S.B.
PROJECT NO.
CHECKED BY:
B.M.
1278
DATE:
JULY. 2017
FILE NO.
SCALE:
N.T.S.
V01
SHEET NO:
A6