Tæknilegar Upplýsingar fyrir DBZ Metal Anchor

Page 1

DBZ Light duty metal anchors Economical wedge anchor Anchor version

Benefits - Well proven - Simple installation - Small drill bit diameter

DBZ

- Suitable for cracked and noncracked concrete C20/25 to C50/60

(M6)

- Redundant fastening only, e.g. suspended ceilings

Base material

Concrete (non-cracked)

Load conditions

Concrete (cracked)

Static / quasi-static

Redundant fastening

Fire resistance

Other information

European Technical Assessment

CE conformity

Approvals / certificates Description European Technical Assessment a) Fire test report Assessment fire report a)

Authority / Laboratory DIBt, Berlin DIBt, Berlin warringtonfire

No. / date of issue ETA-06/0179 / 2016-09-15 ETA-06/0179 / 2016-09-15 WF364181 / 2016-05-03

All data given in this section according ETA-06/0179, issue 2016-09-15. The anchor is to be used only for redundant fastening for non-structural applications.

Basic loading data All data in this section applies to: Correct setting (See setting instruction) No edge distance and spacing influence Concrete C20/25 to C50/60 Anchors in redundant fastening Characteristic resistance Anchor size Resistance, all load directions

1

DBZ 6 / 4,5 FRk

[kN]

DBZ 6 / 35 5,0

Updated: Dec-17


Design resistance Anchor size Resistance, all load directions

DBZ 6 / 4,5 FRd

[kN]

DBZ 6 / 35 3,3

Recommended loads a) Anchor size Resistance, all load directions a)

DBZ 6 / 4,5 FRec

[kN]

DBZ 6 / 35 2,4

With overall partial safety factor for action  = 1,4. The partial safety factors for action depend on the type of loading and shall be taken from national regulations.

The definition of redundant fastening according to Member States is given in the ETAG 001 Part six, Annex 1. In Absence of a definition by a Member States the following default values may be taken. Minimum number of fixing points 3 4 a)

Minimum number of anchors per fixing point 1 1

Maximum design load of action NSd per fixing pointa) 2 3

The value for maximum design load of actions per fastening point NSd is valid in general that means all fastening points are considered in the design of the redundant structural system. The value NSd may be increased if the failure of one (=most unfavourable) fixing point is taken into account in the design (serviceability and ultimate limit state) of the structural system e.g. suspended ceiling.

Materials Mechanical properties Anchor size Nominal tensile strength Yield strength Stressed cross-section Char. bending resistance

fuk fyk As M0Rk,s

[N/mm2] [N/mm2] [mm2] [Nm]

Material quality Part Anchor shank (1) Expansion pin (2) Anchor dimension Anchor size Height anchor head Max. distance Length of anchor shaft

Updated: Dec-17

DBZ 6 / 4,5 390 310 26 5,0

DBZ 6 / 35 390 310 26 5,0

Material Cold-formed steel, galvanized  5m Cold-formed steel, galvanized  5m

l1 d1 l2

[mm] [mm] [mm]

DBZ 6 / 4,5 2,5 6,4 37,5

DBZ 6 / 35 2,5 6,4 68

2


Setting information

Setting details Anchor size Thickness of fixture Depth of drill hole Cutting diameter of drill bit Nominal diameter of drill bit Clearance hole diameter

tfix h1 ≥ dcut ≤ d0 df ≤

[mm] [mm] [mm] [mm] [mm]

Installation equipment Anchor size Rotary hammer Other tools Setting parameters Anchor size Thickness of fixture Minimum member thickness Effective anchorage length Spacing Edge distance a)

3

DBZ 6 / 4,5 ≤ 4,5 40

DBZ 6 / 35 20 ≤ tfix ≤ 35 5 ≤ tfix ≤ 20 55 70 6,4 6 7

DBZ 6 / 4,5

DBZ 6 / 35 TE 2 -TE 7 Hammer, blow out pump

tfix hmin ≥ hef ≥ smin= scr cmin= ccr

[mm] [mm] [mm] [mm] [mm]

DBZ 6 / 4,5 ≤ 4,5 80

DBZ 6 / 35 20 ≤ tfix ≤ 35 5 ≤ tfix ≤ 20 100 32 200 150

The critical spacing (critical edge distance) shall be kept. Smaller spacing (edge distance) than critical spacing (critical edge distance) are not covered by the design method.

Updated: Dec-17


Setting instruction *For detailed information on installation see instruction for use given with the package of the product. Setting instructions Drill hole with drill bit Blow out dust completely Insert anchor with fixture

Hammer down the expansion pin

Check if the pin is completely flattened

Max. exceedance of 2mm can be accepted

In case the pin exceedance is larger than 2mm replace the used drill bit with a new drill bit

Updated: Dec-17

4