Tæknilegar Upplýsingar fyrir HFB Nail Anchor

Page 1

HFB NAIL ANCHOR Technical Datasheet Update: Apr-21


HFB Nail anchor Premium Fastener for Fire Protection Panels, Light Duty applications and Light Ventilated Facades Anchor version

Benefits

HFB (M6)

- Verified for ISO 834 (celluloid) curve, HCM curve, ZTV-ING part 5 curve and RWS fire curve. - System tests with several market leading Boards

HFB-R (M6)

HFB-A-R (M6)

- Keeps its place under static, dynamic and seismic (C1) conditions thereby minimizing economical impact. - Comes with a cordless electric power tool for drilling, setting and removal allowing the fastest (re-) installation time, ensuring that the service interruption is minimized. - The anchor can easily be removed, even the “nail head” geometry”

HFB-HCR (M6)

- Pre-assembled washer - Mesh clip for a quick and easy installation support when used with sprayed fire protection mortar

HFB-A-HCR (M6)

- Pre-assembled rubber washer, ideal for installation of light ventilated façade brakckets

HFB-R RW (M6)

Base material

Concrete (cracked)

Load conditions

Static/ quasi-static

Seismic C1

Installation conditions

Other information

Hammer drilled holes

European Technical Assessment

1

Fire resistance

Fatigue/Dynamic

CE conformity

Updated: Apr-21


Approvals / certificates Description European technical assessment Fire test report a) Fire test report (RWS/HCinc) France Seismic EFECTIS report EFR-18-J-002325 Fatigue a)

a)

Authority / Laboratory ZAG. Ljubljana ZAG. Ljubljana EFECTIS France Fastening-technology Hilti technical data

No. / date of issue ETA-17/0168, 2021-01-18 ETA-17/0168, 2021-01-18 EFR-18-J-002325 TA-1703, 2018-05-25 TA

All data given in this section according to ETA-17/0168, issue 2021-01-18.

Static and quasi-static loading (for a single anchor) All data in this section applies to: - Correct setting (See setting instruction) - No edge distance and spacing influence - Steel failure - Minimum base material thickness - Concrete C 20/25, fck,cube = 25 N/mm² Effective anchorage depth for static Anchor size Eff. Anchorage depth

hef

[mm]

25

M6 30

35a)

Characteristic resistance Anchor size Cracked concrete Load in all directions F0Rk

HFB-R, HFB-R RW, HFB-HCR, HFB-A-HCR

M6

[kN]

HFB, HFB-A-R;

3,0

5,0

6,0

3,0

4,5

6,0a)

Design resistance Anchor size Cracked concrete Load in all directions F0Rd

HFB-R, HFB-R RW , HFB-HCR, HFB-A-HCR

M6

[kN]

HFB, HFB-A-R

2,0

3,3

4,0

2,0

3,0

4,0a)

Recommended resistance Anchor size Cracked concrete HFB-R, HFB-R RW, HFB-HCR, Load in all HFB-A-HCR directions F0Rec HFB, HFB-A-R a) b)

M6

[kN]

1,4

2,4

2,8

1,4

2,1

2,8a)

Not applicable to HFB (CS), since it is not tested for hef=35. With overall partial safety factor for action  = 1,4, The partial safety factors for action depend on the type of loading and shall be taken from national regulations.

Updated: Apr-21

2


Seismic loading (for a single anchor) All data in this section applies to: - Correct setting (See setting instruction) - No edge distance and spacing influence - Steel failure - Minimum base material thickness - Concrete C 20/25, fck,cube = 25 N/mm² - All data given in this section is according to TA-1703, issue 2018-05-25

Effective anchorage depth for seismic C1 Anchor size Effective Anchorage depth hef [mm]

25

Characteristic resistance in case of seismic performance C1 Anchor size Cracked concrete HFB-R, HFB-R RW [kN] Tension NRk HFB-A-R Shear VRk

HFB-R, HFB-R RW HFB-A-R

[kN]

Design resistance in case of seismic performance C1 Anchor size Cracked concrete HFB-R, HFB-R RW [kN] Tension NRd HFB-A-R Shear VRd

HFB-R, HFB-R RW HFB-A-R

[kN]

Recomended resistance in case of seismic performance C1 Anchor size Cracked concrete HFB-R, HFB-R RW [kN] Tension NRec HFB-A-R Shear VRec a)

3

HFB-R, HFB-R RW HFB-A-R

[kN]

M6 30

35

M6 3,0

4,0

4,0

3,0

4,0

4,0

-

3,5

3,5

-

-

-

M6 2,0

2,6

2,6

2,0

2,6

2,6

-

2,3

2,3

-

-

-

M6 1,4

1,9

1,9

1,4

1,9

1,9

-

1,6

1,6

-

-

-

With overall partial safety factor for action  = 1,4, The partial safety factors for action depend on the type of loading and shall be taken from national regulations,

Updated: Apr-21


Fire resistance All data in this section applies to: - Correct setting (See setting instruction) - No edge distance and spacing influence - Steel failure - Minimum base material thickness - Concrete C 20/25 to C50/60 - Partial safety factor for resistance under fire exposure  M,fi = 1,0 (in absence of other national regulations) Effective anchorage depth Anchor size Eff, Anchorage depth a)

hef

[mm]

25

M6 30

35a)

Not applicable to HFB (CS), since it is not tested for hef=35.

Characteristic resistance Anchor size Fire exposure R30 HFB Load in all HFB-R, HFB-HCR, HFB-R RW directions F0Rk HFB-A-R, HFB-A-HCR

M6

[kN]

0,5

0,9

- a)

0,5

0,9

1,2

0,5

0,9

1,0

0,5

0,6

- a)

0,5

0,9

1,2

0,5

0,6

0,6

0,4

0,4

- a)

0,5

0,9

1,2

0,3

0,3

0,3

0,3

0,3

- a)

0,2

0,7

1,0

0,1

0,1

0,1

Fire exposure R60 HFB Load in all directions F0Rk

HFB-R, HFB-HCR, HFB-R RW

[kN]

HFB-A-R, HFB-A-HCR Fire exposure R90 HFB Load in all directions F0Rk

HFB-R, HFB-HCR, HFB-R RW

[kN]

HFB-A-R, HFB-A-HCR Fire exposure R120 HFB Load in all directions F0Rk

HFB-R, HFB-HCR, HFB-R RW

[kN]

HFB-A-R, HFB-A-HCR Design resistance Anchor size Fire exposure R30 HFB Load in all HFB-R, HFB-HCR, HFB-R RW directions F0Rd HFB-A-R, HFB-A-HCR

M6

[kN]

0,5

0,9

- a)

0,5

0,9

1,2

0,5

0,9

1,0

0,5

0,6

- a)

0,5

0,9

1,2

0,5

0,6

0,6

0,4

0,4

- a)

0,5

0,9

1,2

0,3

0,3

0,3

0,3

0,3

- a)

0,2

0,7

1,0

Fire exposure R60 HFB Load in all directions F0Rd

HFB-R, HFB-HCR, HFB-R RW

[kN]

HFB-A-R, HFB-A-HCR Fire exposure R90 HFB Load in all directions F0Rd

HFB-R, HFB-HCR, HFB-R RW

[kN]

HFB-A-R, HFB-A-HCR Fire exposure R120 Load in all directions F0Rd Updated: Apr-21

HFB HFB-R, HFB-HCR, HFB-R RW

[kN]

4


HFB-A-R, HFB-A-HCR

0,1

0,1

0,1

Materials Material quality Part Metal parts made of carbon steel Anchor Bolt

Material

HFB

Expansion Sleeve HFB Metal parts made of stainless steel HFB-R, HFB-A-R, HFB-R Anchor Bolt RW Expansion Sleeve

HFB-R, HFB-A-R, HFB-R RW

Washer

HFB-R, HFB-A-R, HFB-R RW

Carbon steel, galvanized, coated, rupture elongation (lo = 5d) > 8% 8% Stainless steel A4 Stainless steel A4, coated, rupture elongation (lo = 5d) > 8% 8% Stainless steel A4 Stainless steel A4

HFB-R, HFB-A-R, HFB-R Stainless steel A4 RW Metal parts made of high corrosion resistant steel High corrosion resistance steel, coated, Anchor Bolt HFB-HCR HFB-A-HCR rupture elongation (lo = 5d) > 8% Expansion Sleeve HFB-HCR HFB-A-HCR High corrosion resistance steel Washer HFB-HCR HFB-A-HCR High corrosion resistance steel Hexagon/Special nut HFB-HCR HFB-A-HCR High corrosion resistance steel Rubber parts Washer HFB-R RW Elastomer, black Hexagon/Special nut

Anchor dimensions Anchor Maximum length of anchor Anchor diameter Shaft diameter at the cone Diameter of head Length of expansion sleeve Diameter of washer Thickness of washer

5

HFB-R, HFB-R RW, HFB-HCR 150

HFB lmax ≤ d1 dR dH ≤ ls dw ≤ hw ≤

[mm] [mm] [mm] [mm] [mm] [mm] [mm]

HFB-A-R and HFB-A-HCR

5,9

5,2 4,2

12,2

10,1

-

30 1,5

Updated: Apr-21


Setting information Setting details Anchor Nominal diameter of drill bit Cutting diameter of drill bit Maximum diameter of clearance hole in the fixture Nominal embedment depth Effective embedment depth Drill hole depth a)

do dcut ≤

[mm] [mm]

df

[mm]

hnom hef h1 ≥

[mm] [mm] [mm]

HFB, HFB-R, HFB-R RW HFB-A-R, HFB-HCR and HFBA-HCR 6 6,40 7 30 25 34

35 30 39

40a) 35a) 44a)

Not applicable to HFB (CS), since it is not tested for hef=35.

Setting parameters Anchor Size Effective anchorage depth Minimum base material thickness Minimum spacing Minimum edge distance a)

hef

[mm]

hmin

[mm]

smin

[mm]

for c ≥

[mm]

cmin

[mm]

for s ≥

[mm]

HFB, HFB-R, HFB-R RW, HFB-A-R, HFB-HCR and HFB-A-HCR 25 30 35a) 80 80 80a) 50 50 50a) 50 50 50a) 40 40 40a) 75 80 80a)

Not applicable to HFB (CS), since it is not tested for hef=35.

Updated: Apr-21

6


Installation equipment Anchor size

HFB

Rotary hammer Setting tool Setting tool pneumatic Setting tube Socket wrench

-

Mesh clip

-

HFB-R, HFBHFB-A-R HFB-HCR R RW TE-4 (-A) – TE-6 (-A) TE-C-HFB-ST P-HFB-ST D-HFB-ST

-

HFB-A-HCR

SI-HFB-RS

-

SI-HFB-RS

HFB-CM 20 HFB-CM 20

-

-

Applications

Fastening of pre-fabricated fire protection boards

7

Updated: Apr-21


Fastening of light wire mesh reinforcement for fire protection mortar

Updated: Apr-21

8


Setting instructions *For detailed information on installation see instruction for use given with the package of the product Setting instruction for HFB-R, HFB-R RW* , HFB-A-R, HFB-HCR and HFB-A-HCR Hammer drilling 1. Drill the hole

2.

3a. Insert the anchor with hammer

3b. Insert the anchor with setting tool TE-C-HFB-ST

3c. Insert the anchor with setting tool D-HFB-ST

Clean the hole

3d. Insert the anchor with setting tool P-HFB-ST

4. Check the anchor

9

Updated: Apr-21


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.