Contents Company profile
4
Product range overview
6
Features and benefits
8
Indoor units
12
Total heat exchanger
28
Outdoor units
30
Control systems
38
Optional parts
43
Hi-Toolkit
45
Set-Free Multimedia
46
3
Air Conditioning from HITACHI can justifiably be described as the art of exploiting the latest ideas and developments in technology to create a range of innovative products which provide a more comfortable and more productive environment in which people can happily live and work. It is also an art executed with a responsible concern for protecting the environment. Ecological thinking begins at the very first stages of new product design and continues throughout production, installation procedures, equipment and operation. Specifiers and users alike can always be assured that performance and costs are not the only parameters by which HITACHI products can be judged. To achieve success with such objectives on a global scale requires not only enormous resources but also a commitment to the future. As one of the largest companies in the world, with over 347,424 employees, HITACHI is well positioned to undertake this commitment with confidence that comes from successfully responding to the changing needs of people for over 90 years.
worldwide. In 1993 HITACHI invested in a new purpose built, state of the art factory (HAPE) in Barcelona, Spain. The site of the factory was carefully chosen to accommodate further building on its 40,000 square meter site. The creation of a European manufacturing facility and customer training centre helps reduce production costs, speed up delivery times and enables full support to be given to all customers. HITACHI’s advanced air conditioning products are specified all over the world, wherever there is a requirement for ultimate performance and cost effective, long term reliability. A wide range of units coupled with a choice of advanced control systems mean HITACHI can provide solutions to meet every possible air conditioning application or specification. Authorised Distributors all over the world contribute their own specialised technical support and practical assistance to provide individual system designs, commissioning and after sales service.
Hitachi Air Conditioning Products Europe HAPE works, Spain
Hitachi Appliances, Inc. (Shimizu works, Japan) has acquired International Standard Quality Management System ISO9001 and ISO14001 authorisation. Shimizu works perform thorough product quality control using various environmental tests, severe heating testing for compressors, and many others. Hitachi Set Free Series Outdoor units are manufactured according to this ISO certification system.
Hitachi Air Conditioning Products (M) Sdn.Bhd (HAPM works, Malaysia) has acquired International Standard Quality Management System ISO9001 and ISO14001 authorisation. HAPM perform thorough product quality control using various environmental tests. Hitachi Set Free Series RPK Indoor units are manufactured according to this ISO certification system.
HITACHI Authorised Distributors are committed to providing an unrivalled support from a combination of experienced engineers, local product and spare parts stock,
Company profile HITACHI – in Japanese the name means sunrise – is at the forefront of research and development turning new ideas and innovations into new products. Of its $80.9 billion sales worldwide in 2005, close to 4.3% was invested in research and development programs. This vast amount of money has given HITACHI the opportunity to conceive many ‘world firsts’ – examples of which include the technologically advanced and acclaimed scroll and semi-hermetic Screw compressors. These have been incorporated in HITACHI’s air conditioning systems and water chillers which have revolutionised air conditioning
Hitachi Air Conditioning Products Europe (HAPE works, Spain) has acquired International Standard Quality Management System ISO9001 & ISO 14001 authorisation. HAPE performs thorough product quality control using various environmental tests. Hitachi Set Free Series Indoor units and panels are manufactured according to this ISO certification system.
Hitachi Appliances, Inc. Shimizu works, Japan
Quality control
supported in turn by on-going technical support from HITACHI. From the initial product concept at HITACHI’s research and development facility in Japan, product development is dedicated to providing the products the customer requires. Product design and development is continuous with priority being given to the use of ecologically friendly refrigerants. To satisfy your cooling and heating requirements and to ensure the optimum indoor environment, consider HITACHI the first and last word in air conditioning.
Hitachi Air Conditioning Products (M) HAPM works, Malaysia
5
Indoor Units Capacity Range [HP]
0.8
1.0
1.3
1.5
1.8
2.3
2.0
2.5
2.8
3.0
5.0
4.0
6.0
8.0 10.0
In-the-Ceiling - +
-
-
-
-
- +
- +
-
- +
- +
- +
-
- +
-
-
+
- +
Mini In-the-Ceiling Mini 4-Way Cassette 4-Way Cassette 2-Way Cassette Wall
- +
Ceiling Floor-Standing Floor-Concealed
- +
-
- +
- +
- +
-
- +
- +
- +
-
- +
Capacity available with dip switch setting
Adjustable by dip switch setting - +
Outdoor Units Capacity Range [HP]
3
4
5
8
10
12
14
16
18
20
24
28
30
32
36
42
RAS-FSVN Series
Product range overview Hitachi’s range of Set Free Variable Refrigerant Flow systems has developed significantly in recent years following a great deal of investment in research and testing facilities at Hitachi’s factories and laboratories.
• Newly developed, highly efficient 2 blade Fan
Hitachi has continuously developed sophisticated energy-saving air conditioning systems that reduce CO2 emissions and protect the global environment.
• Large capacity DC Fan Motor
The latest offering from Hitachi is the Set Free FSN1 series featuring high energy-saving, easy installation and compact size for next generation buildings.
RAS-FSN Series RAS-FXN Series
• High efficiency DC Inverter fan module • High efficiency DC Inverter Compressor • Vector Control DC Inverter • High efficiency constant speed compressor
RAS-3FSVN(E)
RAS-4FSVN(E) RAS-5FSVN(E)
RAS-5FSN/FXN
RAS-8FSN1(E)/FXN(E) RAS-10FSN1(E)/FXN(E) RAS-12FSN1(E)/FXN(E)
RAS-14FSN1 RAS-16FSN1
RAS-16FXN RAS-18FSN1/FXN RAS-20FSN1/FXN
RAS-24FSN1/FXN RAS-28FSN1 RAS-30FXN RAS-32FSN1/FXN
RAS-36FSN/FXN RAS-42FSN/FXN
• Newly developed, energy saving heat exchanger • Supercooling circuit adopted
System Equipment Capacity Range [m3/h]
250
500
800
1,000
Total Heat Exchanger
7
High COP
• Reliability greatly improved by optimised bearing • Intake loss and leakage loss largely reduced by asymmetric scroll lap
Increased COP and EER Rotor shape optimized
Neodymium magnet used
Peculiar electromagnetic noise to DC compressor cut
Efficiency increased across entire range of rpm used
[˚C]
High-efficiency motor
Performance is greatly improved by the high-efficiency, high pressure, inverter driven scroll compressor.
Compressor rotor
• Heat loss largely reduced by oil return structure
95
DC motor AC motor
70
2,000
rpm
4,000
6,000
• Accurate oiling to the compressor by improved oiling system Supercooling circuit • Performance improved by high-efficiency plate type of heat exchanger
Effect of subcooler
DC Compressor By using DC, the performance is improved at around 30 - 40Hz where the operation time of the inverter compressor is longest. Also, to suppress electromagnetic noise interference and achieve low noise, the rotor has been divided into two and the electric pole displaced.
Refrigerating ability increased by supercooling circuit
Features and benefits
2-Blade Fan
Increased flexibility in project design
• Hitachi unique patented design • Noise is reduced by decreasing the number of blades to 2
SET-FREE FSN Outdoor unit capacity
Typical construction example of a conventional system
0.8 HP
8
8 HP
0.8 HP
13
10 HP
0.8 HP
16
12 HP
0.8 HP
16
14 HP
0.8 HP
20
16 HP
0.8 HP
20
18 HP
0.8 HP
20
20 HP
0.8 HP
20
24 HP
0.8 HP
27(20)*
28 HP
0.8 HP
31(24)*
32 HP
0.8 HP
32(27)*
36HP
0.8 HP
32*
42HP
0.8 HP
32*
SET-FREE FSN Series 2 outdoor units installed
Power source, grounding wire
Integral type unit for all product series • All units are assembled and tested at Hitachi factories therefore minimising problems at installation stage.
Transmission line
Max. number of indoor units connectable
5 HP
• The length of each blade is longer, increasing air quantity by 25% • Motor input decrease by 8%
Min. capacity of indoor units connectable
Power source, grounding wire, transmission line, connecting wire Power source, grounding wire
Outdoor connecting pipes (gas, liquid) Gas pipe Gas pipe Liquid pipe
Outdoor connecting kits (gas, liquid) : Areas where no installation is required in the new series
Liquid pipe
( ) Transmission line
*
Only for 0.8 HP indoor unit maximum connecting number.
• Indoor unit selection is easier as the minimum capacity and the maximum number of indoor units to be connected are increased to match the indoor load.
9
More flexible refrigerant construction conditions
Expansion of Operation Range
Improved flexibility of design by increasing the pipe length to 150 m max. (equivalent length of 175 m) in FSN series.
Can be used with outdoor air temperatures down to -20 C
1 Max. pipe length: 150 m
4 Height difference between outdoor and indoor units: 50m*
0
• Fan motive energy is reduced by combining with a highefficiency fan • External static pressure of 60 Pa as standard
[˚C] 50
2 Between first branch and indoor unit: 40m or less 3 Height difference between highest and lowest indoor units: 15m or less
4
3
40
RAS-FSG
RAS-FSN1
43˚C
43˚C
30 20
1
15˚C
10 2
0
-5˚C
-5˚C -15˚C
-10
Refrigerant piping connections
15˚C
In an outdoor unit piping connections are easily conducted from any three directions: “front, rear or downwards”
-20˚C
-20
*
High Static Pressure, Long Duct Bell Mouth
In case the outdoor unit is installed at a higher level than indoor units. If the outdoor unit is installed lower than indoor units, the maximum height difference is 40m.
Table 1 : Outdoor Unit – 1st Multi-Kit If the equivalent piping length is less than 100m, use the following pipe size: Pipe size ( Unit
Gas
mm) Multi-kit Liquid
RAS-5FSN
5
/8
3
E-102SN
RAS-8FSN1E
3
/4
3
E-102SN
RAS-10FSN1E
7
/8
3
E-102SN
RAS-12FSN1E
7
/8
1
E-162SN
RAS-14FSN1
7
/8
1
E-162SN
RAS-16FSN1
11/8
1
E-162SN
RAS-18FSN1
11/8
5
E-242SN
RAS-20FSN1
11/8
5
E-242SN
RAS-24FSN1
11/8
5
E-242SN
RAS-28FSN1
11/4 (13/8)
3
E-302SN
RAS-32FSN1
11/4 (13/8)
3
E-302SN
RAS-36FSN
11/2
3
E-302SN
RAS-42FSN
11/2
3
E-302SN
/8 /8 /8 /2 /2 /2 /8 /8 /8 /4 /4 /4 /4
In case that the equivalent piping length is more than 100m use the following pipe size: Pipe size ( Unit
Features and benefits Improved Demand Control
Gas
mm) Multi-kit Liquid
RAS-5FSN
3
/4
1
E-102SN
RAS-8FSN1E
7
/8
1
E-102SN
RAS-10FSN1E
11/8
1
E-162SN
RAS-12FSN1E
11/8
5
E-242SN
RAS-14FSN1
11/8
5
E-242SN
RAS-16FSN1
11/4 (13/8)
5
E-302SN
RAS-18FSN1
11/4 (13/8)
3
E-302SN
RAS-20FSN1
11/4 (13/8)
3
E-302SN
RAS-24FSN1
11/4 (13/8)
3
E-302SN
RAS-28FSN1
11/2 (15/8)
7
E-302SN
RAS-32FSN1
11/2 (15/8)
7
E-302SN
RAS-36FSN
13/4
7
E-302SN(*)
RAS-42FSN
13/4
7
E-302SN(*)
/2 /2 /2 /8 /8 /8 /4 /4 /4 /8 /8 /8 /8
* please refer to applications department
The pipe size must be the same as the piping connection hole of the Outdoor Unit.
Control is optimised to suit each customers air conditioning environment.
Table 2 : 1st Multi-Kit – Last Multi-Kit
NEW Cut by internal signal
Cut by external signal
NEW
Wave function
Total Capacity of Indoor Units
Cut
Power consumption
Cut
Power consumption
Power consumption
External signal
Cut
Time specified Time Construction needed in advance
Time Power Cut according to site conditions
Time Cut by time control Minimising capacity down
Pipe size ( Gas
mm) Multi-kit Liquid
HP<16
5
/8
3
E-102SN
6<_HP<9
3
/4
3
E-102SN
9<_HP<13
7
/8
3
E-102SN
13<_HP<16
11/8
1
E-162SN
16<_HP<18
11/8
1
E-162SN
18<_HP<26
11/8
5
E-242SN
26<_HP<36
11/2
3
E-302SN
36<_HP<42
11/2
3
E-302SN
42<_HP
11/2
3
E-302SN
/8 /8 /8 /2 /2 /8 /4 /4 /4
11
General Data
Set Free – RPIM Technical Description Installation • New design • Requires minimum installation space • Greater noise reduction
The new RPIM units have been designed specifically for situations where only a reduced installation space is available. This is possible due to the positioning of the piping and electrical work which means no space is required from the sides of the units: Left Side
Suspension Bracket Sling Bolts
Model
Sling Bolts
RPIM-1.0 FSN2E
RPIM-1.5FSN2E
Nominal Cooling Capacity
kW
2.20
2.80
4.00
Nominal Heating Capacity
kW
2.50
3.20
4.80
m3/min
8/8/7
8/8/7
10/10/8.5
Hi (HSP)/Hi (LHP)
Pa
45/10
45/10
45/10
Fan Motor
W
33
33
33
dB (A)
31/27
31/27
33/29
dB (A)
50
50
51
Height
mm
275
275
275
Width
mm
702
702
702
Depth
mm
600
600
600
kg
25
25
26
Air Flow Rate (Hi/Me/Lo) at (SP-00)
Static Pressure
Sound Pressure Level (Hi/Lo)
Bolts
RPIM-0.8 FSN2E
Sound Power Level (Hi/Lo)
Outer Dimensions
Right Side Suspension Bracket Servicing
Net Weight
• In order to benefit from the minimum required installation space, access to the electrical box and refrigerant piping is enabled from the suction air side of the unit for easy maintenance.
Refrigerant
• Following the same concept as the refrigerant piping and electrical box, drain piping connection work is also easily accessible from the suction air side of the unit.
Liquid Line
Connections
R410A (Nitrogen-Charged in factory for Corrosion-Resistance) Connection with Flare Nuts
-
Refrigerant Piping
Gas Line
Condensate Drain
• The RPIM is fitted with a new type of air filter to allow for easy maintenance even with an installed air duct.
Mini – In the ceiling Noise Reduction Resulting from an accurate study of airflow distribution, turbulence reduction and an improved fan unit, the new RPIM unit focuses specifically on reduced noise which makes it an excellent option for installations that require a very low noise level or extremely quiet indoor unit.
mm(in.)
Ø6.35(1/4)
Ø6.35(1/4)
Ø12.7( /2)
Ø12.7( /2)
Ø12.7(1/2)
-
Ø25 OD
Ø25 OD
Ø25 OD
0.17
0.17
0.17
1
Ø6.35(1/4)
mm(in.)
3
1
Packing Measurements
m
Standard Accessories
-
Air Filter
Remote Control Switch
-
PC-ART/PC-P2HTE
NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the ISO 5151. Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB 19˚C WB Outdoor Air Inlet Temperature: 35˚C DB
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB 7.0 ˚C WB Outdoor Air Inlet Temperature: 6.0 ˚C DB
Pipe Length: 7.5 meters Piping Lift: 0 meter Pipe Height: 0 meters DB: Dry Bulb; WB: Wet Bulb
2. The sound pressure level is based on the following conditions: – 1.5 meters beneath the Unit (without ceiling under the unit), applying suction duct 1m. and discharge duct 2m. – Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anaechoic chamber so that reflected sound should be taken into condsideration when installing the unit.
Static Pressure RPIM units have been provided with 2 Static Pressure levels regulations: • Low static pressure (factory setting for standard installations without an air duct). • High static pressure (Optional setting where an air duct installation is necessary).
13
Set Free – RPI Technical Description
Slim design • Slim design
Less than 197mm in height, this unit can be fitted practically any existing false ceiling or formerly ducted space, without substantial modification.
• Adjustable fan speed • Adjustable static pressure
Minimum 5mm
• Drain Pump as standard • Air Filter as standard
197mm
120mm
False Ceiling (0.8 ~ 1.5HP)
Broader range of external static pressure up to 150 Pa. Flexibly supports a wide range of installation conditions at site, e.g. longer ducts. Increased flexibility and extended ducting now available, provides full temperature control even to remote areas. Adjustable air flow and fan speed control. Wide selection Full line-up from model 0.8HP to 6.0HP. Drain-up mechanism Drain-up mechanism is built in the units as standard.
In the ceiling
An electronic sensor monitors the water level and automatically activates the pump when draining becomes necessary. Return Air (2.0-6.0HP) Available as bottom or rear entry. Suction filter equipped as standard New RPI unit is equipped with a filter as standard.
Econofresh Kit As part of the Set Free range the Econofresh can provide up to 100% fresh air and has the ability to provide ‘free cooling’ via dampers when the outdoor ambient temperature is below the temperature required indoors. Available for 5.0HP unit.
General Data
RCIM Technical Description
Model
RCIM-1.0FSN
RCIM-1.5FSN
Power Supply Nominal Cooling Capacity Nominal Heating Capacity
• Quiet Operation • Compact Size
The RCIM – 4-way cassette type indoor unit benefits from quiet operation, DC fan, uniform panel sizing, weight, ceiling operation, adjustable, reduced mounting size, compact size, and improved flexible piping.
• Improved Flexible Piping
AC 1Ø, 230V, 50 Hz kW
2.8
4.5
5.6
kW
3.2
5.0
6.3
m3/min
13/12/11
15/13.5/12
16/14/12
W
52
52
52
dB(A)
36/34/32
38/35/33
42/39/37
Height
mm
295
295
295
Width
mm
570
570
570
Depth
mm
570
570
570
kg
17
17
17
Air Flow Rate (Hi/Med/Lo)
Features
RCIM-2.0FSN
Fan Motor Sound Pressure Level (Overall A Scale) (Hi/Med/Lo)
Outer Dimensions
Uniform square panel size for 600 x 600 ceiling Panel sizes are standardised to a 700mm square to facilitate the installation in grid ceiling. European standard module is 600mm. Compact, thin and weight can be installed in a small space
Net Weight
The height of the units is just 295mm, and weight is 17Kg and so they can be installed in a reduced space inside a false ceiling.
Refrigerant
R410A (Nitrogen Charged in Factory for Corrosion-Resistance)
Connections
Flare Nut Connection (With Flare Nuts)
Refrigerant Piping
Quiet operation
Liquid Line
By employing DC motor the electromagnetic noise is reduced. The following table lists air flow rates for RCIM. RCIM-1.5FSN Air Flow Rate
RCIM-2.0FSN
Ø6.35(1/4)
mm(in.)
Ø12.7( /2)
Ø12.7( /2)
Ø15.88(5/8)
Condensate Drain
mm
VPØ32 OD
VPØ32 OD
VPØ32 OD
Packing Measurements
m3
0.13
0.13
0.13
Gas Line
1
Adaptable Air Panel Model
Standard operation dB(A)
P-N23WAM
42
Colour (Munsell Code)
Medium
35
39
Outer Dimensions
Low
33
37
Height
mm
35
35
35
Width
mm
700
700
700
Depth
mm
700
700
700
Electrical box is located inside grill, which enables easier access to the electrical components, without opening the false ceiling. A pocket is provided for each of the four panel corners. so that the body height can be easily adjusted without removing the panel.
Plaste. White (4.1Y8.5 / 0.7)
Net Weight
kg
3.5
3.5
3.5
Packing Measurements
m3
0.07
0.07
0.07
Remote Control Switch
PC-P2HTE or PC-LH3A
High ceiling adaptability satisfies a wide variety of requirements This model has been adapted for high ceiling (3.5m high) installations by incorporating speed-up taps. This feature provides comfortable air conditioning in suburban stores and showrooms.
OD: Outer Diameter
NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616.
Ceiling Height 1.5HP
2.0HP
Standard
Below 2.5
Below 2.7
Speed-up (1)
2.5 to 2.9
2.7 to 3.1
Speed-up (2)
2.9 to 3.9
3.1 to 3.5
Fan motor input reduced by DC motor
Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 ˚C DB 19.0 ˚C WB Outdoor Air Inlet Temperature: 35.0 ˚C DB
Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 ˚C DB Outdoor Air Inlet Temperature:
Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb
7.0 ˚C DB 6.0 ˚C WB
2. The Sound Pressure Level is based on the following conditions: – 1.5 meters Beneath the Unit. – Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.
The DC fan motor greatly improves efficiency compared to conventional products that use AC motors. In addition, air blasts are reduced by controlling the rotation speed of the fan.
Body
Corner Packet
Ø6.35(1/4)
1
38
High Ceiling
Panel
Ø6.35(1/4)
Hi
Easy Installation and maintenance
Mini 4-way cassette
mm(in.)
The Body can be aligned with the celing surface by moving the body upward or downword with the packets
The motor input is reduced by employing a ferrite magnetic surfacemounted rotor, centralized winding system and split core system. The motor efficiency is improved in all aspects, and is 50% smaller and lighter than conventional machines. Equipped with drain up mechanism with high pump lift A drain pump lift of up to 600mm from the ceiling surface is achieved by employing a drain-up mechanism with high pump lift (500mm in the previous model).
17
Set Free – RCI Technical Description
New design air panel The air panel was revised to give a fresh and simple design. Prevention of smudging and short-circuiting is also taken into account. Extremely Quite Operation Uses a blade design resulting in an exceptionally quiet fan. HI-stream fan achieves the lowest level of noise, 28 dB (A) (RCI-1.0FSN1E). • Silent Operation • Slim Air Panel • Drain Pump as standard
Compact, low height units The height of the units is just 298mm so they can easily be installed in a small space. The units require limited ceiling space which enables improved work efficiency in installation behind the ceiling. Inside of ceiling
Indoor unit body 3HP
298mm
False ceiling
Air panel
High ceiling adaptability satisfies a wide variety of requirements This model is adaptable to a high ceiling with a height of 4.2m by using speed-up taps. These features allow comfortable air conditioning in high street stores.
4-way cassette
(m) High Ceiling
1.0/1.5/2.0/2.5 HP
3.0/3.5/4.0/5.0/6.0 HP
4-way
3-way
2-way
4-way
3-way
2-way
Standard
2.7
3.0
3.3
3.2
3.6
4.0
Speed-up (1)
3.0
3.3
3.5
3.6
4.0
4.2
Speed-up (2)
3.5
3.6
-
4.2
4.3
-
NOTES For setting 3 and 2 directions, the separately sold ‘3-way outlet parts set’ is necessary. Speed up (1) and Speed-up (2) can be selected through RCS by using C5 option.
Wireless controller (option) See page 43. Fresh air intake
Motor Efficiency (%)
Connection of fresh air intake can be taken in by connecting the duct beside indoor unit. The control duct fan will operate only when unit is operating giving good air recirculation and comfort. DC Motor Efficiency increased by 40%
Branch duct
(motor input halved)
Available across the range for added flexibility AC Motor
Revolutions per Min. (rpm)
DC Fan Motor with Outstanding Efficiency The DC fan motor greatly improves efficiency compared with conventional products having an AC motor. Also, air blasts are reduced by controlling the rotation speed of the fan. Drain-up mechanism is equipped as standard. Anti-mould filter is equipped as standard.
General Data
Set Free – RCD Technical Description
Model
RCD-1.0FSN
RCD-1.5FSN
RCD-2.5FSN
RCD-3.0FSN
RCD-4.0FSN
RCD-5.0FSN
Nominal Cooling Capacity kW
2.8
4.5
5.6
7.1
8.0
11.2
14.0
Nominal Heating Capacity kW
3.2
5.0
6.3
8.5
9.0
12.5
16.0
m3/min W
8/7/6
12/10/8.5
15/13/11
19/16/14
22/19/16
29/24/21
34/29/25
35
35
35
55
55
35 x 2
35 x 2
dB(A)
34/32/30
35/32/30
35/32/30
38/34/31
40/36/33
40/36/33
43/40/36
Height
mm
298
298
298
298
298
298
298
Width
mm
860
860
860
860
860
1,420
1,420
Depth
mm
620
620
620
620
620
620
620
kg
27
27
27
30
30
48
48
Power Supply
Quiet operation and low height design for any ceiling.
• Slim line design • New Air panel, perfect fit for any ceiling
Reduced weight and size simplify handling for easier renewal.
Fan Motor
The length of the 3HP type is reduced from 1,320mm to 860mm, the height is also reduced and the volume is decreased by about 50%. The reduced weight of 30kg also makes handling much easier.
Sound Pressure Level
398mm 298mm
odel Ne w M (50%)
AC 1Ø, 230V, 50 Hz
Indoor Fan Air Flow Rate (Hi/Med/Lo)
• Quiet Operation
RCD-2.0FSN
(Overall A Scale)
Outer Dimensions
Net Weight 860mm 1,320mm
del nt M o Curre %) (100
Refrigerant
R410A (Nitrogen-Charged for Corrosion-Resistance)
Connections
Flare Nut Connection
Refrigerant Piping
Low-profile design allows installation in a small space inside of ceiling. A compact turbo fan simplifies the structure and reduces the height to 298mm, for easy installation.
Liquid Line
mm (in.)
Ø6.35 (1/4)
Ø6.35 (1/4)
Ø6.35 (1/4)
Ø9.53 (3/8)
Ø9.53 (3/8)
Ø9.53 (3/8)
Ø9.53 (3/8)
Gas Line
mm (in.)
Ø12.7 (1/2)
Ø12.7 (1/2)
Ø15.88 (5/8)
Ø15.88 (5/8)
Ø15.88 (5/8)
Ø15.88 (5/8)
Ø15.88 (5/8)
m
Ø32 0D
Ø32 0D
Ø32 OD
Ø32 0D
Ø32 0D
Ø32 0D
Ø32 0D
Condensate Drain
3
Approximate Packing Measurements
Compact Turbo Fan Inside of Ceiling
0.23
0.23
0.23
0.23
0.23
0.37
0.37
P-G23DWA1
P-G23DWA1
P-G23DWA1
P-G23DWA1
P-G23DWA1
P-G46DWA1
P-G46DWA1
Colour 298mm
Ceiling
2-way cassette
Adaptable Air Panel Model
Height
mm
30+10
30+10
30+10
30+10
30+10
30+10
30+10
Width
mm
1,100
1,100
1,100
1,100
1,100
1,660
1,660
Depth
mm
710
710
710
710
710
710
710
kg
6
6
6
6
6
8
8
m3
0.10
0.10
0.10
0.10
0.10
0.15
0.15
Net Weight
Top-class noise control due to compact turbo fan. The three-dimensional twisted wings of the compact turbo fan greatly reduce noise and electromagnetic disturbance is minimised by PWM (Pulse Width Modulation) control.
Silky White (2.5Y 8.9/1)
Outer Dimensions
Approximate Packing Measurements Standard Accessories
Suspension Brackets
OD: Outer Diameter
Simple Maintenance
NOTES:
Auto-louvers are not flocked, therefore the unit does not accumulate dirt and is easy to clean.
1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616.
Speed-up tap ensures comfortable air conditioning even when installed in high ceiling areas. Even rooms with a high ceiling can be comfortably air-conditioned by setting the speed-up tap with the remote control switch.
Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 ˚C DB 19.0 ˚C WB Outdoor Air Inlet Temperature: 35.0 ˚C DB
Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 ˚C DB Outdoor Air Inlet Temperature:
Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb
7.0 ˚C DB 6.0 ˚C WB
2. The Sound Pressure Level is based on the following conditions: – 1.5 meters Beneath the Unit. – Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.
21
General Data
Set Free – RPK Technical Description
Model
RPK-1.0FSN2M
RPK-1.5FSN2M
RPK-2.5FSN2M
RPK-3.0FSN2M
RPK-4.0FSN2M
Nominal Cooling Capacity kW
2.8
4.5
5.6
7.1
8.0
11.2
Nominal Heating Capacity kW
3.2
5.0
6.3
8.5
9.0
12.5
dB(A)
38/36/34
40/38/36
41/39/37
43/40/37
43/40/37
49/46/43
Height Width
mm
280
280
295
333
333
333
mm
780
780
1030
1150
1150
1150
Depth
mm
210
210
208
245
245
245
kg
10
10
12
18
18
18
m3/min
10/8/7
11/10/9
W
20
20
Power Supply
RPK-2.0FSN2M AC 1Ø 230V / 50Hz
Sound Pressure Level (Overall Scale) (Hi-Me-Lo)
• Stylish Design
Outer Dimensions
• Easy Maintenance • Compact & Lightweight Design
Net Weight Refrigerant
Stylish Design and Easy Maintenance
Air Flow Rate (Hi/Me/Lo)
New flat panel design across all models. This flat panel allows for easy maintenance.
Fan Motor
Compact and Light Weight Design
Refrigerant Piping
Designed with ease of installation in mind this new space saving model also uses a high proportion of light weight parts reducing the unit weight. The new 1.0HP and 1.5HP models have a reduced weight of just 10kg.
Liquid Line
Connections
Gas Line Condensate Drain
Wireless or Wired Control The indoor unit is equipped with a wireless receiver kit inside as a standard accessory. The wired remote control switch, PC-P1HE is also applicable. Easy switching from wireless to wired remote controller is possible by using the dip switch built into the receiver part.
R410A (Nitrogen Charged in Factory for Corrosion-resistance) 14/12/10
17/16/14
17/16/14
22/20/17
30
30
30
30
Flare-Nut Connection (with Flare Nuts)
mm(in.)
Ø6.35(1/4) 1
Ø6.35(1/4) 1
Ø6.35(1/4) 5
Ø9.53(3/8) 5
Ø9.53(3/8) 5
Ø9.53(3/8)
mm(in.)
Ø12.7( /2)
Ø12.7( /2)
Ø15.88( /8)
Ø15.88( /8)
Ø15.88( /8)
Ø15.88(5/8)
–
VP16
VP16
VP16
VP16
VP16
VP16
m3
0.07
0.07
0.11
0.13
0.13
0.13
Packing Measurement (approx.) Remote Control Switch
PC-P2HTE or PC-LH3A
OD: Outer Diameter
NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616.
Wall mounted
Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB 19˚C WB Outdoor Air Inlet Temperature: 35˚C DB
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB Outdoor Air Inlet Temperature:
Pipe Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb
7.0 ˚C DB 6.0 ˚C WB
2. The Sound Pressure Level is based on the following conditions: – 1.0 meters beneath the unit, 1.0 meters from discharge grille – Voltage of the power source for the indoor fan motor is 230V The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.
23
Set Free – RPC Technical Description
Quiet operation, easy installation and space saving design Versatile mounting To expand installation and positioning options, HITACHI has added a second drain pipe connector, one more than conventional units. Refrigeration pipes have also been improved and can now be connected at the left, right or rear of the unit.
Rear Side Drain piping
Space saving design – Hitachi’s unique feature • Stylish design • Space saving design • Easy installation • Quiet Operation
An innovative fan and heat exchanger design led to the creation of today’s ultra-slim ceiling unit. Fully adjustable mounting brackets permit close fitting to the ceiling to make installation possible in even the smallest area. Less than 163mm of vertical space are required for installation. Quiet Operation The ceiling unit is equipped with a highly efficient, multi-blade centrifugal fan that generates a powerful yet gentle airflow throughout the room. A redesigned aerodynamically tested air panel minimises operational sound even at high fan speeds.
Ceiling suspended Easier installation By enabling refrigeration piping to be tucked-in close to each indoor unit, piping layout and installation have been made much easier. Anti-mildew filter Anti-mildew filter is equipped as a standard accessory.
Open Space 163mm Concealed 150mm (2,0, 2,5 and 3,0 HP)
Set Free – RPF/RPFI Technical Description
Space-saving slim unit, only 220mm in depth Floor mounted indoor units – RPF
Slim line design only 220mm in depth allowing the unit to be installed without spoiling the style or beauty of the room.
• Floor Type • Slim design, only 200mm deep
Effective use of space by window
• Low height, only 630mm
With a height of 630mm, may be installed by a window leaving plenty of window space. Best installed in a perimeter zone.
• Light unit • Low sound level
Low height Only 630mm.
Floor concealed indoor units – RPFI
Concealed Floor Mounted
• Compact design • 620mm in height • 220mm in depth
Compact design for limited space inside of perimeter wall. So compact that it fits into even the smallest space. Special emphasis placed on interior design compatibility as well as space saving design, allowing it to fit perfectly into the space below a bay window. Optional location for remote control switch Install the PC-P1HE under the plastic cover
Floor mounted
Set Free – KPI Technical Description
Various Control Examples of Total Heat Exchanger Standard Connection
Central Station (PSC-5S) 1
2
3
Example of System
H-LINK
Provides a comfortable environment by control interlocking with air conditioning units.
Structure
SET-FREE
Controllable using the remote control switch for the air conditioning unit. Outdoors
Air discharge Air filter (for discharge)
Outdoor air
Can be controlled in various ways using the remote control switch for the air conditioning unit (PC-P2HT). Functions
Indoor air
PC-P1H
PC-P1HE
PC-P1H
T.H.E+PC-P1H PC-P1H
Outlook of System
Able to control with PC-P1H directry
Able to control up to 16 Indoor Units and Total Heat Exchanger Units
Component of System
( T.H.E )
1 ~ 5 :NEW AVAILABLE SYSTEM
Hitachi Computer Control Network System CS-NET (version 7) 4
Example of
Indoors
:TOTAL HEAT EXCHANGER
• Individual operation of heat exchanging unit • Fan speed control (high/medium/low)
Electrical components box
PSC-5S
Able to control up to 128 Indoor Units consist of 16 refrigeration series • Central Station (PSC-5S) • Remote Control Switch (PC-P1H)
Remote Control Switch (PC-P1H)
• Simultaneous RUN/STOP switch both for air conditioning units and heat exchanging unit Air supply fan
:INDOOR UNIT
UTOPIA
System
5
H-LINK
• Ventilation mode selection (automatic/heat exchange/bypass)*1
H-LINK
Air supply
Fixed Type Heat Exchanging Element • The newly developed fixed type heat exchanging element with high temperature exchange efficiency equivalent to the rotor type element, has been adopted for the new total heat exchangers (Temp Exchange Efficiency: 77% <in case of 500m3/h type unit>). In addition, reliability is increased due to reduction of moving parts. • Low weight with simple unit structure: 33kg (in case of 500m3/h type unit).
• Pre-cool/pre-heat control (interlocking start with delay in 30 or 60 minutes)*1 PC-P1H
CS-NET
PC-P1H
• ON/OFF timer (every half hour, maximum 24 hours) • Increased air supply operation • Specific alarm display
Outlook of System
CS-NET
CS-NET
PC-P1H
Able to control up to 128 Indoor Units consist of 16 refrigeration series • CS-NET • Remote Control Switch (PC-P1H)
Component of System
*1 Required option to be selected at remote control switch.
Automatic selection of most suitable ventilation mode Depending on temperature conditions both outdoors and indoors, the most suitable ventilation mode is automatically selected, designed for energy efficiency.
General Data Model
Total heat exchanger
Power Supply Air Flow Rate (m3/min)
External Pressure (mmAq)
Other Characteristics • Quiet operation with low noise level of 32.5-33.5 dB (A) (at Hi Tap of KPI 5021 Type) has been realised by improving the flow path configuration. • Operation not only with SET-FREE Series Indoor Unit, but also with UTOPIA Series Indoor Unit. • Connectable to H-LINK System with Central Station or with CS-NET in Operation with Indoor Unit. • Flexible Duct Installation: The connecting direction of duct at outdoor side (OA,EA) can be changed according to the condition of the installation site (2 directions).
KPI-2521
KPI-5021
KPI-8021
KPI-10021
AC 1Ø, 230V, 50 Hz Hi
4.1
8.3
13.3
16.6
Me
4.1
8.3
13.3
16.6
Lo
2.75
5.8
11.1
14.5
Hi
6.5
15
14
16
Me
4
6
10
10
Lo
2
3
7
8
Hi
78
77
78
79
Me
78
77
78
79
Lo
83
82
80.5
81
Enthalpy Exchange Efficiency
Hi
69/62.5
67/61.5
71/64.5
70/64.5
for Heating/Cooling (%)
Me
69/62.5
67/61.5
71/64.5
70/64.5
Lo
74/68
73/68
73/68
Sound Pressure Level
Hi
26.5-27.5
32.5-33.5
33.5-34.5
(Overall A Scale) at 1.5m
Me
25-26
30-31
32-33
from the unit (under)*3
Lo
21-22
23.5-24.5
30-31
Temperature Exchange Efficiency (%)
73/67 36-37 34-35 31.5-32.5
Outer Dimensions
• Reduced packing material for environment protection. The wood for the packing use has been reduced for environment protection.
Height
275
317
398
398
Width
735
1016
1004
1231
780
888
1164
• Can also be installed upside down.
Net Weight
Kg
21
33
61
72
Approx Packing Measurement
m3
0.26
0.46
0.70
0.84
Depth
NOTES: *1 KPI-10021 has different units according to the applied power supply, 220-240v, 50Hz and 200V/60Hz *2 Use it under the following conditions. KPI-8021: 29Pa or more, KPI-10021: 49Pa or more *3 The sound pressure level is based on the following conditions; 1.5 meter beneath the unit and this data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. *4 The sound pressure is based on the total heat exchange mode. In case of the bypass ventilation mode, the sound pressure level increased by approximately 1dB(A).
1164
29
Set Free – FSVNE (Mini Heat Pump) Technical Description – Outdoor units
Set Free – FSN1(E) (Heat Pump) Technical Description – Outdoor units
General Data
General Data
Model
RAS-3FSVNE
Power Supply Nominal Cooling Capacity Nominal Heating Capacity
RAS-5FSVNE
8.0
kW
11.2
9.0
12.5
46(42)/47
RAS-3FSVNE
47(43)/48
800
AC 3Ø, 380-415V, 3~ 50Hz 28.0
33.5
40.0
45.0
16.0
kW
16.0
25.0
31.5
37.5
45.0
50.0
Energy Efficiency Rate (EER)
–
3.45
3.72
3.54
3.39
3.22
3.10
COP
–
3.87
4.36
4.07
3.71
3.97
3.99
61/(56)
62/(57)
950
950
Depth
mm
315
315
315
90
Refrigerant
97
Hermetic (Rotary)
Hermetic (Scroll)
2YC63BXD
EK405AHD
1
1
56/(51)
58/(53)
60/(55)
Height
mm
1,645
1,745
1,745
1,745
1,745
1,745
Width
mm
630
950
950
950
1,210
1,210
Depth
mm
750
750
750
750
750
750
kg
160
215
225
225
335
335
1
1
1+1
1+1
6.00
7.20
4.80+4.40
6.00+4.40
Net Weight
Micro-Computer Control Expansion Valve
Compressor
52/(47)
Outer Dimensions
R410A
Flow control
Natural Grey (1.0Y8.5/0.5)
Sound Pressure Levels (Night Mode) dB(A)
1,240
850
68
Hermetic (Scroll)
Refrigerant
R410A Microprocessor-controlled Expansion Valve
Flow Control Model Quantity
EK405AHD
Compressor
1 Quantity
Motor Output (Pole)
kW
1.7(4)
Heat Exchanger
Heat Exchanger
2
m3/min
52
88
W
0.05(8)x1
2
1
1
kW
3
4.80
–
Multi-Pass Cross-Finned Tube
0.05(8)x1+0.07(8)x1
0.05(8)x1+0.07(8)x1
Flare Nut Connection
–
1
1
1
1
1
1
m3/min
138
172
185
210
210
210
Motor (output)
W
160
380
380
380
380
380
Refrigerant Piping
mm(in.)
Ø9.53
Ø9.53
Ø9.53
Gas Line
mm(in.)
Ø15.88
Ø15.88
Ø15.88
kg
1.75
2.8
3.0
Wiring Holes Power Supply
mm
Ø26.5
Ø26.5
Control Circuit
mm
Ø26.5
Ø26.5
Ø26.5 Ø26.5
2
2
2
Propeller Fan
Air Flow Rate
Quantity
99
Liquid Line
Refrigerant Charge
Hermetic (Scroll) –
Outdoor Fan
1
Refrigerant Piping
RAS-4FSVNE / RAS-5FSVNE
Power
Propeller Fan
Quantity
Motor Output (Pole)
3.0(4)
Multi-Pass Cross-Finned Tube
Condenser Fan
Air Flow Rate
2.2(4)
RAS-16FSN1
Nominal Heating Capacity
mm
kg
RAS-14FSN1
22.4
50(46)/51
1,240
RAS-12FSN1(E)
14.0
Cabinet Colour (Munsell Code) mm
RAS-10FSN1(E)
kW
Width
Net Weight
RAS-8FSN1(E)
Nominal Cooling Capacity
Outer Dimensions Height
RAS-5FSN
14.0
Natural Grey (1.0Y8.5/0.5) dB(A)
Model Power Supply
AC 1Ø, 230V, 50 Hz kW
Cabinet Colour Sound Pressure Levels (Night Shift)
RAS-4FSVNE
–
Flare-Nut and/or Flange Connection (Factory supplied)
Liquid Line
mm(in.)
Ø9.53(3/8)
Ø9.53(3/8)
Ø9.53(3/8)
Ø12.70(1/2)
Ø12.70(1/2)
Ø12.70(1/2)
Gas Line
mm(in.)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.20(7/8)
Ø25.40(1)
Ø25.40(1)
Ø28.60(11/8)
Refrigerant Charge
kg
5.4
7.0
8.5
9.0
13.0
13.0
Maximum Current
A
9.6
14
20
22
29
34
m3
0.87
1.44
1.44
1.44
1.81
1.81
Approximate Packing Measurement
Connecting Wire between Indoor and Outdoor unit
NOTES:
Approximate Packing Measurement
m3
0.34
0.5
0.5
Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) 19.0˚C WB (66.2˚F WB) Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB)
NOTES: 1. The cooling and heating capacities show the capacities when the outdoor unit is operated with the 100% rating of indoor units, and are based on the standard JIS B8616-1984. Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) 19.0˚C WB (66.2˚F WB) Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB)
1. The nominal cooling and heating capacity is the combined capacity of the SET FREE system, and is based on JIS 158616.
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB (68˚F DB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB) 6˚C WB (43˚F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
OD: Outer Diameter Pipe Length: 7.5 Meters Pipe Height: 0 Meters
Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB) 6˚C WB (43˚F WB)
DB: Dry Bulb; WB: Wet Bulb
2. The sound pressure level is based on following conditions: – 1 meter from the frontal surface of the unit. 1.5 meters from floor level – Voltage of the power source is 400V The above data was measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit. 3. In case of Night Shift conditions, the noise level decreases 5 dB (A). 4. The COP and EER have been calculated with RCI-FSN1E units. (Indoor unit input power excluded).
2. The sound pressure level is based on following conditions. In case of cooling operation mode. In case of heating operation mode, the sound pressure level increases by approximately 1~2dB. 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. Voltage of the power source is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
31
Set Free – FSN1(E) (Heat Pump) Technical Description – Outdoor units
Set Free – FSN1(E) (Heat Pump) Technical Description – Outdoor units
General Data
General Data
Model
RAS-18FSN1
RAS-20FSN1
RAS-24FSN1
Power Supply
RAS-28FSN1
RAS-32FSN1
AC 3Ø, 380-415V, 3~ 50Hz
Model
RAS-36FSN
Power Supply
RAS-42FSN AC 3Ø, 400V, 3~ 50Hz
Nominal Cooling Capacity
kW
50.4
56.0
69.0
80.0
90.0
Nominal Cooling Capacity
W
101.0
118.0
Nominal Heating Capacity
kW
56.0
63.0
77.5
90.0
100.0
Nominal Heating Capacity
W
113.0
132.0
Energy Efficiency Rate (EER)
–
3.50
3.14
3.25
3.03
3.01
Energy Efficiency Rate (EER)
–
3.01
3.02
COP
–
3.91
3.70
3.92
3.87
3.85
COP
–
3.47
Cabinet Colour (Munsell Code)
Natural Grey (1.0Y8.5/0.5)
Sound Pressure Levels (Night Mode) dB(A)
62/(57)
62/(57)
63/(58)
3.43
Cabinet Colour (Munsell Code) 64/(59)
64/(59)
Outer Dimensions
Natural Grey (1.0Y8.5/0.5)
Sound Pressure Levels (Night Mode) dB(A)
64(59)
65(60)
Outer Dimensions
Height
mm
1,745
1,745
1,745
1,745
1,745
Height
mm
1,745
1,745
Width
mm
1,910
1,910
2,430
2,430
2,430
Width
mm
3,390
3,390
Depth
mm
750
750
750
750
750
Depth
mm
750
750
kg
460
460
675
720
720
Net Weight
kg
920
Net Weight Refrigerant
R410A
Compressor Quantity Power
Heat Exchanger
1+1
1+1
kW
6.00+5.60
7.20+5.60
–
Outdoor Fan
R410A Microprocessor-controlled Expansion Valve
Flow Control
Hermetic (Scroll) –
970
Refrigerant
Microprocessor-controlled Expansion Valve
Flow Control
Compressor
1+4
1+5
1+5
1.40+4x4.40
1.40+5x4.40
1.40+5x4.40
Quantity Power
Multi-Pass Cross-Finned Tube
Heat Exchanger
Propeller Fan
Condenser Fan
Hermetic (Scroll) –
1+4
kW
4.9+5.6x4
1+5 4.9+5.6x4 Multi-Pass Cross-Finned Tube Propeller Fan
–
2
2
2
2
2
3
3
Air Flow Rate
m3/min
210
344
382
382
382
Air Flow Rate
m3/min
554
554
Motor (output)
W
380+275
380+275
380+275
380+275
380+275
Motor Output
W
380+275x2
380+275x2
Liquid Line
mm(in.)
Ø15.88(5/8)
Ø15.88(5/8)
Ø15.88(5/8)
Ø19.05(3/4)
Ø19.05(3/4)
Liquid Line
mm(in.)
Ø19.05(3/4)
Ø19.05(3/4)
Gas Line
mm(in.)
Ø28.60(11/8)
Ø28.60(11/8)
Ø28.60(11/8)
Ø31.75(11/4)
Ø31.75(11/4)
Gas Line
mm(in.)
Ø38.1(1-1/2)
Ø38.1(1-1/2)
Refrigerant Charge
kg
19
19
23
25
26
Refrigerant Charge
kg
31
32
Maximum Current
A
34
38
50
63
77
Maximum Current
A
70.4
81.7
m3
1.81
2.82
3.57
3.57
3.57
m3
4.99
4.99
Quantity
Refrigerant Piping
Flare-Nut and/or Flange Connection (Factory supplied)
Measurement
Quantity
Refrigerant Piping
Approximate Packing
RAS-24/28/32FSN
Flare-Nut and/or Flange Connection (Factory supplied)
RAS-36/42FSN
Approximate Packing
NOTES:
NOTES:
1. The nominal cooling and heating capacity is the combined capacity of the SET FREE system, and is based on JIS 158616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) 19.0˚C WB (66.2˚F WB) Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB)
Measurement
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
OD: Outer Diameter Pipe Length: 7.5 Meters Pipe Height: 0 Meters
Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB) 6˚C WB (43˚F WB)
DB: Dry Bulb; WB: Wet Bulb
1. The cooling and heating capacities show the capacities is the combine capacity of the SET FREE system, and is based on JIS 158616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) 19.0˚C WB (66.2˚F WB) Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB)
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
OD: Outer Diameter Pipe Length: 7.5 Meters Pipe Height: 0 Meters
Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB) 6˚C WB (43˚F WB)
2. The sound pressure level is based on following conditions: – 1 meter from the frontal surface of the unit. 1.5 meters from floor level – Voltage of the power source is 400V The above data was measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit.
2. The sound pressure level is based on following conditions: – 1 meter from the frontal surface of the unit. 1.5 meters from floor level – Voltage of the power source is 400V The above data was measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit.
3. In case of Night Shift conditions, the noise level decreases 5 dB (A).
3. In case of Night Shift conditions, the noise level decreases 5 dB (A).
4. The COP and EER have been calculated with RCI-FSN1E units. (Indoor unit input power excluded).
4. The COP and EER have been calculated with RCI-FSN1E units. (Indoor unit input power excluded).
DB: Dry Bulb; WB: Wet Bulb
33
Set Free – FXN (Heat Recovery) Technical Description – Outdoor units
Set Free – FXN (Heat Recovery) Technical Description – Outdoor units
General Data
General Data
Model
RAS-8 FXNE
RAS-10 FXNE
Power Supply Nominal Cooling Capacity Nominal Heating Capacity
RAS-12 FXNE
RAS-16 FXN
RAS-18 FXN
W
22.4 25.0
28.0
33.5
31.5
45.0
37.5
Cabinet Colour
50.0
50.0 56.0
RAS-8/10/12FXNE
dB(A)
56(51)
58(53)
60(55)
62(57)
56.0
mm
1,745
1,745
1,745
1,745
1,745
Width
mm
950
950
950
1,910
1,910
mm kg
750 295
750
750
305
750
305
Refrigerant
527
750 570
AC 3Ø, 400V, 50Hz
Nominal Cooling Capacity
kW
56.0
69.0
85.0
90.0
Nominal Heating Capacity
W
63.0
77.5
95.0
100.0
63(58)
Natural Grey
(Night Shift)
dB(A)
62(57)
62(57)
63(58)
Height
mm
1,745
1,745
1,745
1,745
Width
mm
1,910
2,430
2,430
2,430
Depth
mm
750
750
750
750
Net Weight
kg
570
712
755
755
Refrigerant
R410A
Flow control
Model
Micro-Computer Control Expansion Valve
Compressor
Hermetic (Scroll) E405AHD
E405AHD
E405AHD
E405AHD
E405AHD
E505DH
E605DH
E655DH
E605DHx2
E605DHx3
Hermetic (Scroll)
Model
E405AHD
E405AHD
E405AHD
E405AHD
E605DHx3
E605DHx4
E655DHx
E655DHx
65D2Yx5
-49D2Y Quantity Motor Output (Pole) kW
RAS-16/18/20FXN
1+1
1+1
1+1
1+1x2
1+1x3
1.8(4)+
2.3(4)+
3.7(4)+
3.0+4.4
1.4(4)x1+
3.7(2)
4.4(2)
4.4(2)
(2)x2
4.4(2)x3
Heat Exchanger
Multi-Pass Cross-Finned Tube
Condenser Fan
Propeller Fan
Quantity
Motor Output (Pole)
1
1
Gas Line Low Gas Line High Refrigerant Charge
1
2
0
138
172
185
210
172+172
W
380(8)
380(8)
380(8)
380(8)
380(8)
Control Circuit
mm(in.) kg
Ø19.05(3/4) Ø15.88(5/8) 8.5
Ø22.2(7/8) Ø19.05(3/4) 9.5
Ø25.4(1) Ø19.05(3/4)
Ø28.6(11/8) Ø22.2(7/8)
10.0
19.0
Ø28.6(11/8) Ø22.2(7/8) 19.0
mm mm
Ø56 Ø26.5
Ø56 Ø26.5
Ø56 Ø26.5
Ø56 Ø26.5
Ø56 Ø26.5
Connecting Wire between Indoor and Outdoor unit
2
2
2
2
2
1+1x5
1+1x5
1.8(4)+
1.4(4)+
1.4(4)+
1.4(4)+
4.4(2)x3
4.4(2)x4
4.4(2)x5
4.4(2)x5
Air Flow Rate Motor Output (Pole)
m3/min W
Refrigerant Piping
2
2
2
172+172
210+172
210+172
2 210+172
380(8)
380(8)
380(8)
380(8)
+275(6)
+275(6)
+275(6)
+275(6)
Flare-Nut and/or Flange Connection (Factory supplied)
Liquid Line
mm(in.)
Ø15.88(5/8)
Ø15.88(5/8)
Ø19.05(3/4) Ø19.05(3/4)
Gas Line Low
mm(in.)
Ø28.6(11/8)
Ø28.6(11/8)
Ø31.75(11/4) Ø31.75(11/4)
Gas Line High
mm(in.)
Ø22.2(7/8)
Ø25.4(1)
Ø28.6(11/8)
Ø28.6(11/8)
kg
19.0
26.0
26.0
26.0
Power Supply
mm
Ø56
Ø70
Ø70
Control Circuit
mm
Ø26.5
Ø26.5
Ø26.5
Ø26.5
2
2
2
2
2.82
3.57
3.57
3.57
Refrigerant Charge Wiring Holes
Ø70
Connecting Wire between
Approximate Packing Measurement
Quantity
Flare-Nut and/or Flange Connection (Factory supplied) mm(in.)
1+1x4
Condenser Fan
Wiring Holes Power Supply
kW
65D2Yx5
1+1x3
Heat Exchanger
m3/min
Refrigerant Piping
Quantity Motor Output (Pole)
RAS-24/30/32FXN
R410A
Flow control
Micro-Computer Control Expansion Valve
Compressor
Air Flow Rate
RAS-32 FXN
Outer Dimensions
Height
Net Weight
RAS-30 FXN
Sound Pressure Levels
Outer Dimensions
Depth
RAS-24 FXN
Cabinet Colour
Natural Grey
Sound Pressure Levels (Night Shift)
RAS-20 FXN
Power Supply
AC 3Ø, 400V, 50Hz kW
Model
m3
1.44
1.44
1.44
2.82
2.82
Indoor and Outdoor unit Approximate Packing Measurement
m3
NOTES:
NOTES:
1. The cooling and heating capacities show the capacities when the outdoor unit is operated with the 100% rating of indoor units, and are based on the standard JIS B8616-1984.
2. The sound pressure level is based on following conditions. In case of cooling operation mode. In case of heating operation mode, the sound pressure level increases by approximately 1~2dB. 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. Voltage of the power source is 400V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
Cooling Operation Conditions Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) 19.0˚C WB (66.2˚F WB) Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB)
Heating Operation Conditions Indoor Air Inlet Temperature: 20˚C DB (68˚F DB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB) 6˚C WB (43˚F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
35
The new Changeover boxes from Hitachi are compatible with FXN Set Free Heat Recovery systems. Piping connections are reduced from 5 (3 from outdoor unit and 2 into indoor unit) to 3 (2 from outdoor unit and 1 into indoor unit). The height of the Changeover boxes is as low as 197mm and the installation time is reduced due to the strainer being installed at manufacturing stage. The flexible location of the electrical box is another advantage of this new model as it enables easier access for servicing and it can be positioned at either side of the Changeover box.
Technical Description General Data Model
CH-4.0NE
Power Supply Nominal Capacity
CH-8.0NE
CH-12.0NE
AC 1Ø, 230V, 50 Hz HP
HP<4
4≤HP<8X
8<HP≤12
4
8
5
mm
197x345x299
197x345x299
197x345x299
kg
10
10
11
No of Max.I/D Unit Dimensions HxWxD
Weight Connections Refrigerant Piping
Flare-Nut and/or Flange Connection (Factory supplied)
Refrigerant Piping From Outdoor Unit
Changeover Box
High Pressure Gas Pipe
mm(in)
Ø12.70(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Low Pressure Gas Pipe
mm(in)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
mm(in)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
To Indoor Unit Indoor Gas Pipe
37
CS Net Web
CS-NET web
Computer System Network for the remote control and monitoring of air conditioning installation. CS-NET web is a standalone central controller that can control up to 128 indoor units and up to 16 outdoor units connected to the Hitachi H-Link communication system. Using its Ethernet port, CS-NET Web connects to the Local Area Network or Internet (using a DSL router), allowing remote parameter setting and monitoring. CS-NET web client software is accessed directly through Internet Explorer and uses a Java application for remote control and monitoring. A useful feature is that two levels of access are available depending on the user type:
Control systems
• ‘User’ access, allowing monitoring and setting of the unit • ‘Installer’ access, allowing also Timer setting and change of system configuration
Touch Screen
H-Link Transmission System This system connects the control wires for the outdoor and indoor units across two or more refrigerant systems. Regardless of the order or number of units to be connected, all the units can be controlled once they have been connected. By this method, design flexibility is very high, installation is easy and total costs are reduced. Furthermore, central control is possible by connecting CS-NET web to H-LINK wiring located in the room next to the room where CS-NET web is installed.
The touch screen allows the continuous monitoring and control of the CS NET WEB data. 2 mounting positions are possible: • TS001 + TS001-TS (Table Support) • TS001 + TS001-WS (Wall Support)
Touch Screen
39
Unit Setting
Specifications of HARC-BX
Different setting of the unit can be programmed remotely using CS-NET Web. Type
Standard
Connectable Q’ty
Timer 4 year timer can be stored in the CS-NET Web remotely, allowing it to run standalone without a PC or manual operation.
Option A
64
Option B
64
32
Control
Monitor
Control
Monitor
Control
Monitor
Run/Stop & Alarm*
•
•
•
•
•
•
Operation Mode
•
•
•
•
•
Set Temp
•
•
•
•
•
Fan Speed
–
–
•
–
•
•
Louver Position
–
–
–
–
•
•
RC. Sw.Permission/Prohibition
–
–
•
–
•
–
Alarm Code
–
–
–
–
–
•
IU Inlet Air Temp
–
–
–
•
–
•
IU Outlet Air Temp
–
–
–
–
–
•
Outdoor Air Temp
–
–
–
–
–
•
Thermo-ON/OFF
–
•
–
–
–
–
Remark
Use PC-P2HTE or PC-2H2
Maximum Wiring Length
1000m (Bus Total length)
*Alarm for monitor only
Lon Works interface ®
Gateway Interface to LON WORKS® BMS Systems System Status and Historical Data
Using HARC-BX allows control of up to 5 setting points and remote monitoring of up to 9 valves. By connecting HARC-BX to H-LINK, a group of up to 16 remote controls can be used and up to 64 indoor units can be controlled.
Different readings from the unit can be accessed remotely in order to give fast assistance for maintenance and monitoring of the system. These parameters are stored locally for several days to ease maintenance.
HARC-BX
41
PC-P2HTE/PC-ART Remote Control Switch with Seven Day Timer This remote controller can control up to 16 indoor units, has a large LCD display and an internal thermostat. It has a weekly timer function allowing four different schedules to be set over seven days. There is also a self diagnostic function and
all indoor unit functions including alarm codes can be accessed and displayed by this controller. • • • • •
Can control up to 16 indoor units Weekly timer function Full fault diagnostic facility Frost protection facility Energy Saving Option
PC-LH3A Wireless Remote Control Switch A wireless remote control switch that provides simple one-touch operation and can control two or more units simultaneously. No wiring work is required and the receiver kit is integral in wall mounted units. A receiver kit PC-RLH11 is required for all other models.
• Wireless Remote Control • For use in place of hard wired PC-P2HTE • Receiver PC RLH4 required with CS Net and central station.
PC-P5H1/PC-ARH Simplified Remote Control Switch Smaller than the conventional remote controller the main function is temperature adjustment. It is ideal for a variety of applications such as hotels, restaurants and offices because it is easy to use. It can control a maximum of 16 indoor units similar to the standard
hard wired controller and displays alarm codes on a simple LED panel. • Simple and easy to use • On/off temperature and fan speed control • Limited range of diagnostic functions
Optional parts
Remote controllers PSC-5S/PSC-A645 Centralised Remote Control Switch The Central Station enables centralised control of up to 16 groups of indoor units (256 units in total). It features a wide range of functions, including a large liquid crystal display screen remote start/stop and alarm code display.
• Simple control for large installations • Max of 256 units • Remote control grouping
PSC-5T/PSC-A1T 7-Day Timer The 7-Day Timer allows long-term unattended control. By connecting this timer to the optional remote control switch or central station daily ON/OFF operation control throughout the week is available. The ON/OFF setting is available three times a day in two different patterns.
• Two types of weekly schedule (A and B) can be set, and can easily be changed for summer and winter operation • Settings are all digitally displayed, allowing operations and settings to be easily checked
43
Indoor Units
Set Free Selection Software – Hi-toolKit
4-Way and Mini 4-Way Cassette Type
Item
RCI-1.0-6.0FSN1E
Receiver Kit for Wireless Control
PC-RLH8/PC-ALH (on the panel) PC-RLH11 (wall mounted)
• Quick and reliable • Simple and user friendly 2-Way Cassette Type
• Free of charge
Hitachi has developed a new programme to design Set Free systems which meet building consultants and technical advisors requirements. The software allows the user to proceed quickly and easily through the phases of selection of a system through to the complete project. Your project in just 6 clicks... Product Selection
Item
RCD-1.0-5.0FSN
Receiver Kit for Wireless Control
PC-RLH9/PC-ALHD (on the panel)
This software allows the user the flexibility to choose the required number of indoor and outdoor units and control systems either by model or capacity.
PC-RLH11 (wall mounted)
Refrigeration Schematic Automatic calculation of pipe sizes and multikits. Option for automatic or manual drawings which can be exported into CAD software.
Mini Wall Mounted Type
Item
Electrical Drawing
RPK-0.8-4.0FSNM
Wireless Remote Controller
PC-LH3A
Wired Remote Controller
PC-P1HE
Electrical drawing showing the power supply, communication cables, accessories and control systems. Specification Using the selected information the software allows the user to produce a full product specification in word format.
In-the-Ceiling, Wall, Floor and Ceiling Type
Item
Schedule of Equipment
RPI (0.8-5.0HP), RPK (0.8-4.0HP), RPC (2.0-5.0HP), RPF (1.0-2.5HP), RPFI (1.0-2.5HP)
This shows a list of the number of Hitachi systems chosen, pipework and wiring digrams and the refrigerant charge required.
Receiver Kit for Wireless Control (with 5m cable)
PC-RLH11/PC-ALHC (wall mounted)
Hi-toolKit
Control System Compatibility
Item
RPI-FSN
RCI-FSN
RCD-FSN
RPK-FSN
RPC-FSN
RPF(I)-FSN
KPI
(without cable)
•
•
•
•
•
•
•
PC-LH3A (new)
•
•
•
•
•
•
•
Control Switch
PCP-5H1/PC-ARH
•
•
•
•
•
•
•
7-Day Timer
PSC-5T/PSC-A1T
•
•
•
•
•
•
•
Control Switch*3
PSC-5S/PSC-A645
•
•
•
•
•
•
•
Remote Control Cable
PRC-10E1, 15E1, 20E1, 30E1
Remote Control Switch*1
Commissioning Automatically produces dip switch settings, equipment list and commissioning checklist.
PC-P1H
Wireless Remote Control Switch*2 Half-size Remote
Centralised Remote
for PC-P1H
•
•
•
•
•
•
•
3P Connector Cable
PCC-1A
•
•
•
•
•
•
•
Remote Sensor
THM-R2A
•
•
•
–
•
•
–
CS-NET
•
•
•
•
•
•
•
Computer Controlled Network System
*1 As the PC-P1H does not include a remote control cable, prepare one in the field, or use PRC-10E1, 15E1, 20E1, 30E1. *2 PC-LH3 can be used instead of PC-LH3A. *3 Supply 220V or 240V
45
Set Free Multimedia
The Set Free Multimedia software has been specifically designed in order to help promote Hitachi Set Free VRF to consultants and end users. • Features & Benefits Guide • Technical explanations of key components • Selection Programme • Examples of installations across Europe. The multimedia is user friendly and is based around sophisticated 3D computer animation and audio commentary A useful presentation mode is also available which is ideal for presenting to customers.
47
Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to their customers. Omitting typing errors. Hitachi Europe Ltd Whitebrook Park Lower Cookham Road Maidenhead Berkshire SL6 8YA United Kingdom
email: aircon.enquiries@hitachi-eu.com www.hitachiaircon.com
HELGB-SF-004
Distributed by: