CI/SfB | | Rf7 | |
DRYWALL MANUAL
INNOVATIVE DRYLINING SOLUTIONS
Welcome to the new look Siniat Drywall Manual – a comprehensive guide containing all the technical information you need to specify the best and most appropriate drywall, drylining product or system. From enabling you to design warm and safe residential environments, to guiding you to meeting and exceeding regulations for the most demanding of commercial and industrial installations, Siniat is confident you will find the best solution to match your particular requirement. This document is intended as guidance for the correct use of Siniat GTEC products and systems in typical, best practice applications. It incorporates detailed technical information to assist the user in selecting and specifying the correct systems for the intended applications. This document does not cover all possible configurations of products in all possible constructions. When project requirements are different from the typical construction solutions shown then consultation with Siniat Specification Managers, Technical Enquiryline or other suitably qualified professionals should be sought. There are references within this document to products to be supplied by other manufacturers; their advice should be sought when using their products. The fixing of GTEC products to various structures is beyond the scope of this document and advice should be sought from fixing suppliers and/or qualified professionals. This document is non-exhaustive and provides general advice in line with good practice; further information should be sought when required. This document supersedes all previous guidance. All reasonable efforts have been made to ensure accuracy and future changes
and improvements may be made to the document without prejudice or notice. The correct installation and specification of GTEC systems and components is the responsibility of the contractor and the specifier. All GTEC systems should be constructed in accordance with all relevant building regulations and the guidance in ‘BS 8212:1995 Code of Practice for Dry lining and Partitioning using Gypsum Plasterboard’, ‘BS 8000-8:1994 Workmanship on building sites -Code of practice for plasterboard partitions and dry linings’ and ‘BS EN 13964:2004+A1:2006 Suspended ceilings – requirements and test methods’. GTEC is registered trademark of Siniat Limited © 2012 Siniat Limited
Call the Technical Enquiryline for technical advice and details specific to your project
01275 377 789
INTRODUCTION CONSIDER...
SPECIFY...
REFER...
2
SYSTEMS FOR HEALTHCARE SYSTEMS FOR EDUCATION SYSTEMS FOR RESIDENTIAL INVENTED BY SINIAT SYSTEM PERFORMANCE
6 8 10 12 16
GTEC® PARTITIONS
20
GTEC® FLOORS AND CEILINGS
120
GTEC® LININGS
178
GTEC® FIRE PROTECTION
242
GTEC® FINISHING
276
Product Reference Profile Guide Screw Selection Guide Sustainability Health and Safety Standards Index
292 332 334 336 341 342 344
The latest version of this publication can be found at www.siniat.co.uk/drywallmanual
2
INTRODUCTION
SHAPING THE WAY PEOPLE BUILD BUILDING ON SOLID FOUNDATIONS Our company was established in the UK in 1987 with a manufacturing facility on the outskirts of Bristol – one of the most technically advanced drywall production units in the world. It has the capacity to produce and supply more than 50 million square metres of plasterboard a year. A second plant at Ferrybridge opened in 2007, enabling a 50% increase in UK manufacturing capacity. Excellence is achieved through continual investment in technology combined with high quality materials. Fully automated plant and high purity gypsum combine to produce plasterboard products of the highest quality. Siniat is a European leader in plasterboard manufacture and systems, active across Europe with major operations in France, Germany, Benelux, Italy, Romania and Ukraine. The worldwide head office located in Avignon, France, also houses the Technical Development Centre which has led the way in gypsum research and product innovation. Siniat joined Etex, a leading worldwide industrial and building materials group, in 2011.
OUR COMMITMENT TO SUSTAINABLE CONSTRUCTION The need for sustainable buildings, and the sustainable products to build them, is increasingly important for both the construction industry, the occupants of our buildings, and to us. We reacted early to this challenge, amassing a number of sustainability firsts in the process. Having led the way, we remain firmly committed to sustainability. We will continue to examine our product’s whole lifecycle, from source to disposal, always looking for new ways to reduce the amount of natural resources we use. Plasterboard is fully recyclable – with no loss in quality GTEC Products and Systems are BRE Green Guide A / A+ rated and help collect sustainability code credits Certified and managed sustainability: Responsible Sourcing BES 6001, ISO 9001 and ISO 14001 Full plasterboard site waste collection and recycling from GTEC Wasteline Direct The leading recycler of post-consumer plasterboard waste in each of the last three years For more information on our life cycle approach please refer to pages 336-340.
INTRODUCTION
GTEC速
GTEC速 LIFETIME SYSTEM WARRANTY
The GTEC brand represents quality, durability and assured performance across all our products and system solutions. Products include standard, performance and specialist boards, as well as finishing compounds, metal framing and fixings to satisfy the practical and performance needs of all new-build and refurbishment projects. GTEC Systems are built from four key component groups:
GTEC products and components are tested together to ensure compatibility and system performance. By completing this rigorous testing we are able to guarantee the technical performance of our systems; giving piece of mind to users, contractors, engineers and architects alike.
GTEC Board Standard, performance and specialist boards specifically designed for a wide range of construction applications, giving impact, moisture, vapour, sound and fire resistance. GTEC Frame A range of metal framing components for use in combination with GTEC Boards. From basic studwork to suspended ceilings and intricate curves. GTEC Fix A comprehensive range of screws, adhesives and other fixing components for attaching boards and connecting components. GTEC Finish Taping and jointing systems used for the seamless jointing of plasterboard for creating a high performance system with a perfect finish.
When systems are built entirely with GTEC components and materials, by qualified professionals, in accordance with our latest literature and relevant standards, we can offer our invaluable Lifetime System Warranty. In the unlikely event of failure, provided the system is unaltered, as originally designed and built, we will reinstate the system to its originally specified performance level. This warranty gives the confidence that Siniat GTEC systems will perform as intended throughout the life of the building. Warranties for products and systems in wet or severe humidity environments are available separately on request. For full details of the Lifetime System Warranty, please visit www.siniat.co.uk
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
3
4
GTEC速 SINIAT
RE-SHAPING THE SPECIFICATION PROCESS
GTEC® SINIAT
DEDICATED SUPPORT SERVICES TO THE SPECIFIER
FIND OUT EVEN MORE INFORMATION ON OUR WEBSITE
Whilst our suite of literature covers most typical uses and situations, we understand that every installation is different and there are bound to be situations that are not covered. For this reason, Siniat offers specification customers a range of dedicated support services.
With the increasing pressure on the industry to react and respond quickly to changes in legislation and find solutions to meet the ever-changing pressures towards sustainable solutions and cost efficiency, our information must be where you need it, when you need it.
Our field based specification managers are able to help with design, system selection, construction details and project specifications. Highly experienced they can develop solutions to improve speed of installation, fire, sound and thermal performance, as well as guiding you through sector-specific requirements.
Our website – www.siniat.co.uk – has been created to provide a one-stop resource for product, technical and legislative information. Built on the latest web technology, the new website guides you through the information you need including:
The dedicated Technical Enquiryline offer an immediate response to your technical queries including installation advice, product guidance, and acoustic and U-value calculations.
Online system selector to complement this manual Downloadable product and technical literature Case studies
We also provide a purpose-designed training centre, which has been accredited by the CITB and provides instruction in drywall installation and management for contractors, merchants and housebuilders.
Technical blogs News, videos, and features Sustainability
Other support services include a series of CPD seminars to keep our specifier customers updated on the latest developments and regulations. Siniat also subscribes to NBS Plus and continues to invest in new technology to improve the specification process.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
5
6
SOUTHMEAD HOSPITAL Bristol Project: Healthcare Architect: BDP Main Contractor: Carillion Construction Sub Contractor: BR Hodgson Project Value: ÂŁ430 million Completion: 2014 GTEC Systems used: GTEC C Stud Partitions, GTEC Acoustic Stud Partitions, GTEC Twin Frame Partitions, GTEC Dryliner Linings, GTEC Shaftwall Fire Protection GTEC Boards used: GTEC Aqua Board, GTEC Megadeco
GTECÂŽ SYSTEMS FOR HEALTHCARE
SYSTEMS FOR HEALTHCARE GTEC Plasterboard Systems have been used extensively in major healthcare projects across the UK and Ireland as fast and effective solutions to healthcare construction. The GTEC Boards and GTEC Systems have been developed to meet and exceed the full range of extraordinary demands placed on hospital and healthcare buildings.
EXTRAORDINARY DEMANDS ACOUSTICS:
The acoustic demands on partitions in Healthcare buildings are extreme; from ensuring consultation room privacy and operation suite concentration, to dealing with emergency vehicle sirens and the intensity of A&E departments. While layout can ease noise risk, GTEC Systems allow for flexible design with extremely high levels of sound insulation from space to space. The partition performance ensures that a superior healing environment is achieved. GTEC Pregybel ceilings also help to control noise levels through acoustic absorption.
FIRE:
Multi-storey constructions containing bed-bound patients, large public areas, multiple service entrances and numerous circulation routes, place a high fire resistance demand on any project. GTEC Partitions and GTEC Ceilings provide a simple design with high levels of fire resistance and robust detailing for design flexibility. GTEC Shaftwall and GTEC Encasement Fire Protection solutions offer specialist passive fire protection to lifts, shafts and structural steel.
IMPACT:
Hospitals are dynamic, highly trafficked, public environments where walls are subject to constant impact from staff, visitors and hospital equipment. GTEC LaDura, a unique and exceptionally strong plasterboard, achieves severe duty ratings with the minimum of boarding. Plus, it provides high levels of fixing resistance for crash rails, skirting, services and fixtures.
HYGIENE:
Easy to clean surfaces are vital for good healthcare environments which need frequent washing, and are dependent on excellent hygiene. GTEC Finishing solutions combined with GTEC Partition and Lining systems offer smooth, easy to joint and repairable surfaces which are easier to clean. GTEC Megadeco Board requires no pre-sealing for even faster finishing.
KEY GUIDANCE DOCUMENTS AND REGULATIONS: NHS Guidance: Acoustics: Technical Design Manual Firecode HTM 05
BREEAM New Construction: Healthcare Building Regulations: Approved Document Part B 2006 – Fire Safety
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
7
8
BARNSLEY COLLEGE Project: Education Architect: Jefferson Sheard Main Contractor: Miller Construction Sub Contractor: Ace Partitions Project Value: ÂŁ50 million Completion: 2012 GTEC Systems used: GTEC C Stud Partitions, GTEC Curved Twin Frame Partitions, GTEC Encasement Fire Protection, GTEC Mass Barrier Ceilings, GTEC Dryliner Thermal Linings GTEC Boards used: GTEC Megadeco, GTEC Fire Board, GTEC Thermal K Board
GTEC® SYSTEMS FOR EDUCATION
SYSTEMS FOR EDUCATION GTEC Plasterboard Systems have been adopted in hundreds of school, academy, college and university projects across the UK and Ireland to efficiently meet the needs of education construction. The range of GTEC Board and GTEC Systems suit the full scope of extraordinary demands placed on education buildings.
EXTRAORDINARY DEMANDS ACOUSTICS:
From music and sports noise to examination room silence, Education buildings place extreme acoustic demands on specification. The isolation and control of ambient noise from space to space is vital, as is good speech clarity in open spaces, along with controlled reverberation. While layout design can reduce noise risk, GTEC Systems’ high level of sound insulation allows design flexibility from space to space. GTEC Pregybel ceilings offer acoustic absorption and echo control, improving speech clarity and reducing noise distractions.
FIRE:
“Each year around 1 in 20 schools experiences a fire and nearly 60% of school fires are started deliberately.” BB100 Large circulation areas, multi-storey construction and broad types of use from science labs to sports halls place a high fire resistance need on any Education project. GTEC Partitions and GTEC Ceilings achieve high levels of fire resistance with uncomplicated, robust and proven detailing for design flexibility. GTEC Shaftwall and GTEC Encasement Fire Protection solutions offer specialist passive fire protection to lifts, shafts and structural steel.
IMPACT:
Education buildings face some of the most intense usage. With high levels of student movement, a wide variety of activities taking place and the chance of misuse, careful specification is needed to reduce maintenance and repairs. GTEC LaDura Board is exceptionally strong and achieves severe duty ratings with the minimum of boarding. It offers excellent impact performance for corridors and high levels of fixing resistance for fixtures and fittings.
DESIGN:
An innovative design can transform the learning experience of students, enhancing their performance, motivation, behaviour and engagement. Ideal for the most ambitious projects, GTEC Systems are flexible, high performance and easy to install, providing quick construction. GTEC LaDura, Aqua Board and Megadeco take plasterboard systems to new areas replacing slower, less flexible, wet construction methods.
KEY GUIDANCE DOCUMENTS AND REGULATIONS: Department for Education Guidance: BB93 – Acoustic Design in Schools BB100 – Design for Fire Safety in Schools BREEAM New Construction:
Building Regulations: Approved Document Part E 2003 – Resistance to the Passage of Sound Approved Document Part B 2006 – Fire Safety
Education
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
9
10
CASPIAN WHARF Bow, London Project: Residential Architect: Stefan Zins Associates Main Contractor: Berkeley Homes Sub Contractor: BDL Group Completion: 2012 GTEC Systems used: GTEC C Stud Partitions, GTEC Twin Frame Partitions, GTEC Shaftwall Fire Protection, GTEC Suspended MF Ceilings, GTEC Direct Bond Linings GTEC Boards used: GTEC LaDura, GTEC Aqua Board, GTEC dB Board
GTEC® SYSTEMS FOR RESIDENTIAL
SYSTEMS FOR RESIDENTIAL GTEC Plasterboard Systems have been used across the UK and Ireland to successfully build or renovate thousands of housing, apartment and hotel projects. The diverse range of GTEC Board and GTEC Systems features solutions ideal for the construction of homes and other residential buildings.
EXTRAORDINARY DEMANDS ACOUSTICS:
Busy lifestyles, close neighbours and urban noise can all combine to affect the quality of home life. Party walls, party floors, partitions and ceilings all require special attention to reduce noise issues. GTEC Systems are tested to achieve extremely high levels of sound insulation. They meet Part E Regulations and the enhanced CSH (Code for Sustainable Homes) requirements* with the minimum of components. *+3dB and +5dB over Part E for separating elements (Code for Sustainable Homes Technical Guide – November 2010)
FIRE:
With occupants of all ages, most often present at night while asleep, a fire resistant design is essential. Multi-storey buildings and their escape routes present even greater fire resistance needs, as stipulated by Building Regulations Part B – Fire Safety. GTEC Partitions and GTEC Ceilings achieve a full range of fire resistance using minimal components for multi-storey apartments, dense housing developments and detached houses. Robust and proven detailing enables design flexibility and economic construction.
SUSTAINABILITY:
Dwellings are responsible for up to 30% of national carbon emissions through their construction and use. Huge changes to the Building Regulations, as well as the Code for Sustainable Homes (CSH), have been implemented to reduce these carbon emissions representing a major shift in construction methods. The use of GTEC Systems can earn CSH credits in a variety of ways – for more details see the Sustainability section on pages 336-340. GTEC Systems are made up of fully recyclable components with gypsum plasterboard being 100% re-usable in a closed loop process. Recent product innovations use minimal components to achieve technical performances, limiting material usage and waste. All GTEC Lining systems can provide insulation to enhance the thermal performance of external walls. These include the GTEC Thermal Boards range; thermally laminated plasterboards which are recommended by Approved Document L1B to achieve thermal upgrades in renovation projects.
KEY GUIDANCE DOCUMENTS AND REGULATIONS: Code for Sustainable Homes Building Regulations:
Approved Document Part B 2006 – Fire Safety
Approved Document Part E 2003 – Resistance to the Passage of Sound
Approved Document Part L1 A&B 2010 – Conservation of Fuel and Power
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
11
12
INVENTED BY SINIAT
INVENTED BY SINIAT From over 25 years of experience on building sites we know there is unmet potential in drywall and have created the boards to unlock it. Excellent fire and acoustic performance is always expected and we have the range of boards with higher densities, highly developed additives and patented technology to achieve the top levels of fire and sound performance needed in the UK and Ireland. But we don’t consider that to be enough. Better finishing capabilities are available. As a result we are the first and only manufacturers of gypsum
plasterboards which offer exceptional water resistance, exceptional strength and exceptional finishing speed. We also know that one board can do more than one thing. Our boards combine the highest levels of performance making them suitable for a huge breadth of applications, reducing the amount of fixing, and potentially meaning only a single board type is needed on site.
OUR UNIQUE BOARDS GTEC LaDura Type D,E,F,H1, I and R to BS EN 520 Exceptionally strong for extreme impact applications and maximum fixture pull-out resistance. Severe Duty performance from a single 12.5mm boarded partition H1 moisture resistance for humid applications Highest board surface mass for maximum levels of sound insulation Fire, sound, impact and moisture performance allowing specification of just one board type per project
See System Tables on pages 22-25 Suitable for GTEC Partitions p20 and GTEC Linings p178
INVENTED BY SINIAT
GTEC Aqua Board Type GM-F, GM-H1 and GM-I to BS EN 15283 Highly water resistant gypsum board for wet areas and external use. High sound and fire resistance Ideal for wet and humid environments Fully mould and fungus resistant May be externally exposed for up to six months for innovative construction schedules Dimensionally stable and easier to cut, fix and handle than cementitious boards
See System Tables on pages 26-27 Suitable for GTEC Partitions p20, GTEC Linings p178, GTEC Floors and Ceilings p120 and external sheathing
GTEC Megadeco Type D,F, I and R to BS EN 520 Pre-sealed, white faced board for ease of decoration and finishing. Unique pre-sealed, white, paper facing Equivalent sound resistance to GTEC dB Board Equivalent fire resistance to GTEC Fire Board Substitute with GTEC Universal Board for skim plastering Fire, sound and impact performance allowing specification of just one board type per project
See System Tables on pages 28-31 Suitable for GTEC Partitions p20, GTEC Linings p178, GTEC Floors and Ceilings p120 and GTEC Fire Protection p242
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
13
14
INVENTED BY SINIAT
SYSTEM SOLUTIONS Each of our three unique boards elevates the final layer of the partition, ceiling or lining, to previously unknown levels of standard plasterboard construction. These capabilities drive a different ethos in specifying drywall systems – the basic demands of acoustics and fire are always achievable and the focus can now switch to these extra benefits. Good design means every space has its own needs and tuning boards to best suit these demands is made possible. FROM TWO BOARDS TO ONE
OPPOSING NEEDS
For many performance requirements the board configuration can be improved with Siniat products, from two layers of a lower spec board to just one layer of a board such as GTEC Megadeco or LaDura. This can drastically reduce the number of boards needed on site. One high performance technical board can often do the job of two standard boards. Installation time is reduced without having to fix multiple layers, there is less waste as material volumes are reduced and the whole project becomes simpler to specify and manage.
Great architectural design will not always place identical rooms on opposite sides of a partition. With Siniat systems this problem is solved with hybrid system make-ups giving different finishing performance on each side of the partition. For example, a partition between a shower room and a corridor in a school could use GTEC Aqua Board on one side and GTEC LaDura for the corridor side. The lower of the two corresponding performance values for sound or fire being would be used unless the system has been tested in a hybrid make-up.
RCP 006 2x12.5mm GTEC Standard Board
LDP 003 1x 15mm GTEC LaDura Board
25mm Mineral Wool Insulation
25mm Mineral Wool Insulation
Performance Fire: 60 Mins. Acoustic: 49 Rw dB Severe Duty 3.4m Max. Height Thickness: 100mm
Performance Fire: 60 Mins. Acoustic: 49 Rw dB Severe Duty 4.0m Max. Height Thickness: 100mm
Symmetrical System Same performance through the wall in both directions
Hybrid System Different finishing layer performances in different rooms
INVENTED BY SINIAT
MIXING LAYERS As Siniat’s unique boards offer their key improvements to the final layer of a system it can make sense to lower the capabilities of the inner board. Lower performing base layers can be used to open up new opportunities in system design, to value engineer, or to tune performance characteristics. These standardised layers, used as a base, are composed to build a system exactly right for the situation, e.g.:
FINISHING LAYER
BASE LAYER
GTEC Fire Board where fire resistance is key GTEC dB Board where high sound insulation is most important GTEC Standard Board or Plank where a lower density base layer will suffice
HIGHER PERFORMANCE
STANDARD PERFORMANCE
GTEC LaDura GTEC Aqua Board GTEC Megadeco GTEC Universal Board
GTEC Fire Board GTEC dB Board GTEC E Board GTEC Moisture Board GTEC Fire MR Board
HIGHER PERFORMANCE
STANDARD PERFORMANCE
GTEC Fire Board GTEC Fire MR Board GTEC dB Board GTEC Moisture Board
GTEC Standard Board GTEC Plank GTEC E Board
NOTE: System specific system boards, e.g. GTEC Acoustic Homespan Board and GTEC Contour Board are not included in the above matrix.
Homogenous System Single board type required More limited performance
Mixed Board System Superior final layer performance Improved attenuation range
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
15
16
SYSTEM PERFORMANCE
SYSTEM PERFORMANCE FIRE Gypsum is a naturally fire resistant material, locking in water which will be released during a fire. This water controls the temperature allowing plasterboard systems to survive a fire for substantial lengths of time. The requirement for fire protection in a project is driven by the Building Regulations, fire strategy and any high risk equipment or activity in a building. The ratings in this manual represent the minimum passive fire protection that can be expected in a fire and can be used to show compliance with the current Building Regulations in the UK and Northern Ireland. The fire ratings of the systems are determined by testing and assessment to British and European standards. In the UK the BS 476 series of test standards and BS EN 1361, 1362, 1363 standards are used to establish the fire resistance of building elements such as walls and ceilings. A different temperature monitoring method is adopted in the European test methods and the results obtained are not the same as the British Standard results; both results are declared in this manual where possible. The tests are carried out in 3m x 3m aperture furnaces which simulate the most intensive period in a fire. The results of these tests are expressed in terms of integrity, insulation and loadbearing capacity (where applicable).
System Ref.
Component
TYPICAL PARTITION AND FLOOR REQUIREMENTS* 30 mins
Between rooms within a dwelling or office unit
60 mins
Separating adjacent units in low rise buildings
90 mins
Between units in medium rise buildings
120 mins
Fire fighting or escape routes and between units in higher rise buildings
*consult relevant building regulations and fire strategy consultants for precise needs
The ratings in the system tables give the worst of the three criteria rounded down to the nearest 30, 60, 90 or 120 minutes, e.g. if insulation fails before integrity or loadbearing capacity then this will be the rating quoted. GTEC products are tested for reaction to fire and other fire sensitive properties to European and British Standards test methods and are classified as Materials of Limited Combustibility Euroclass A2-s1-d0, the second highest performance level for construction materials. In UK Building Regulations plasterboard products are generally considered Class 0.
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
27
3.7
95
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
30 30
Severe
48
LDP 008: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm 12.5mm GTEC 12 GTEC LaDura LaDura Board Board Studs: Stu ds: Sin Single gle GTEC GTEC CS70Rx CS70Rx C Studs Studs att 600mm 600mm centres centtre cen tres tres 25mm IInsulation: Ins nsula l ti tion: tio i n: 25m 2 5 m 16kg/m 116k 6kg//m 6kg 6k /m3 glass gllass mineral wool Accessories: –
LDP 001: C Stud Partition – see p50
SYSTEM PERFORMANCE
ACOUSTICS Control of sound in buildings is essential for comfort. Plasterboard systems can assist with acoustic requirements in two ways, through sound insulation and sound absorption. Sound insulation is principally driven by the surface mass of a building element. As a thin, dense material plasterboard can be used to provide adaptable solutions for minimising sound transmission. Plasterboards generally reflect sound, however, perforated boards enable effective sound absorbing systems to be built. For residential construction the Building Regulations contain minimum values for sound transmission between rooms and absorption within communal areas. For many other projects acoustics are beyond the remit of building regulations. It is essential to consider the noise tolerance and noise output of neighbouring spaces to select the right levels of sound insulation for the separating element, consultation with acousticians is recommended. The sound insulation values quoted in this manual use consistent laboratory testing to allow system comparison. Elements are placed in an aperture between spaces with the reduction in sound pressure between the two spaces being recorded; this testing is carried out to BS EN ISO 140 and BS EN ISO 717 standards. The result is the Weighted Sound Reduction Index (Rw) measured in decibels (dB) with higher values offering better insulation. Site testing uses a different measurement method of Standardised Level Difference (DnT,w) where values around 7dB lower than laboratory tests can be expected. It is critical to seal all air paths, avoid routes for sound to ‘flank’ the element and build to high standards to achieve
System Ref.
Component
Rw dB
RELATIVE ACOUSTIC PRIVACY
30
Normal conversation can be distinguished
35
Loud conversation can be distinguished
40
Loud conversation can be heard but not distinguished
45
Loud conversation cannot be heard
50
Shouting can be heard but not distinguished
55
All speech is totally blocked with a high level of privacy from other domestic noise
60
High level of privacy including noise from television or stereos
the best site results – just one air path can dramatically diminish the sound insulation of an element. Sound absorption is calculated through laboratory testing to European and ISO standards where a component is located in a space with known reverberation – the resulting reduction in reverberation time gives a coefficient of sound absorption. This co-efficient varies between 0 and 1 with higher values representing greater absorption per square metre.
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
LDP 008: C Stud Partition – see p50 Facing Outer Layer(s): 27 3.7 95 30 Severe 48 1x 12.5mm 1x 12.5 12. 12 2 5mm 5mm GTEC GTEC LaDura L Dura Board LaD Board Bo d 30 0 Studs: GTEC Studs Stu St ds: Single ds Single Si gl GT EC CS70Rx CS70R CS7 0Rx C Studs Stud Stu St ds ds att 600mm 600mm centres centtre cen tres tres 25mm IInsulation: nsula l ti tion: i 25mm 16kg/m 25 116k 6kg//m3 glass 6k l mineral wool Accessories: – ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
17
18
SYSTEM PERFORMANCE
STRUCTURE A major advantage of plasterboard systems is their low mass to height/span ratio, this enables tall partitions and wide spans to be created without imposing high loads on structures supporting the system. As a lightweight system overall robustness must be considered and by using the correct framework and board combinations extremely tough partitions, ceilings and linings can be built. The maximum height of a partition is determined from its ability to resist a uniformly distributed lateral pressure, taken as 0.2kN/m2 for most internal applications, and limiting the resulting deflection to height/240. Greater lateral pressures and other imposed loads are possible and depend on the layout adopted. The ‘Strength’ criterion in the System Performance Tables is determined according to the test methods and criteria given in BS 5234-2. There are four grades in the standard, increasing in robustness from Light, Medium, Heavy to Severe Duty. In most projects the use of the lowest duty grade will result in walls which are too flexible for the expectations of users and are not generally recommended.
Based on extensive testing and calculations the height values shown in this manual are the maximum that the system can safely satisfy when fully built. Care must be taken during construction to ensure that the construction sequence does not undermine structural strength and construction loads are not applied to the systems. The ceiling systems in this publication will not support imposed loads in addition to those given in the appropriate sections. Fixings to structural elements must be determined by suitably qualified professionals and are not the responsibility of Siniat.
GRADE
CATEGORY
EXAMPLES
Light Duty
Adjacent space only accessible to persons with high incentive to exercise care. Small chances of accident or of misuse.
Domestic accommodation
Medium Duty
Adjacent space moderately used primarily by persons with some incentive to exercise care. Chances of accident occurring and of misuse.
Office accommodation
Heavy Duty
Adjacent space frequently used by the public and others with little incentive to exercise care. Chances of accident occurring and of misuse.
Public circulation areas Industrial areas
Severe Duty
Adjacent space intensively used by the public and others with little incentive to exercise care. Prone to vandalism and abnormally rough use.
Major circulation areas Heavy industrial areas
Table extract from BS 5234-2: 1992
System Ref.
Component
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
27
3.7
95
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
30 30
Severe
48
LDP 008: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm 12.5mm GTEC 12 GTEC LaDura LaDura Board Board Studs: Stu ds: Sin Single gle GTEC GTEC C CS70Rx CS70Rx C Studs Studs at 600mm 600mm centres centre cen tress tre 25mm IInsulation: Ins nsula l ti tion: tio i n: 25 25m m 16kg/m 116k 6kg//m 6kg 6k /m3 glass gllass mineral wool Accessories: –
LDP 001: C Stud Partition – see p50
SYSTEM PERFORMANCE
THERMAL Plasterboard is not a low conductivity material but can be combined easily with different types of thermal insulation to create systems or products (such as GTEC Thermal Boards) which offer excellent thermal insulation properties. Plasterboard systems can contribute to construction with the most thermally efficient U-values satisfying new build or renovation building regulation requirements. Plasterboard is dimensionally stable and can be ideal as the air-tightness envelope in a building, with projects typically achieving 3m3/hr/m2 @ 50Pa, exceeding the building regulation requirement. The stability of plasterboard systems also allows construction independent of the substrate to prevent thermal bridging.
this manual so it is often possible to achieve improved U-values by changing the quality and quantity of insulation, contact Technical Enquiryline for further information.
The U-values quoted in the system performance tables can be used in SAP and SBEM calculations either as part of an external element or as the whole element where no other material is involved. For thermal upgrades to existing dwellings the default U-values for construction types and ages found in RdSAP 2009 have been used to indicate a resulting U-value with GTEC products and systems. Only a select range of systems configurations can be shown in
TYPICAL U-VALUES FOR PART L 2010
U-values are calculated, following the conventions of BR 443, using specialist calculation software, from conductivity values in international standards or manufacturers’ information. In product reference tables the quoted conductivity values (λ) W/mK for the materials in specific products have been used to calculate the thermal resistance (R) mK/W for that product. The GTEC range does not include independent insulation and therefore U-values should always be checked against manufacturer’s data for the actual insulation used in construction.
RENOVATION
NEW
App. Doc. L1B/L2B
App. Doc. L1B/L2B
App. Doc. L1B/L2B
App. Doc. L1A/L1B
Low Carbon* Construction
‘New’
‘Improved’
‘Threshold’
‘Limiting’
Wall (cavity insulation in place)
0.28
0.55
0.70
–
–
Wall
0.28
0.30
0.70
0.30
0.15
Pitched roof (insulation at ceiling level)
0.16
0.16
0.35
0.20
0.13
Pitched roof (insulation at rafter level)
0.18
0.18
0.35
0.20
0.13
Flat roof
0.18
0.18
0.35
0.20
0.13
Floors
0.22
0.25
0.70
0.25
0.12
Thermal Bridging (W/m2K)
–
–
–
–
0.04
Air permeability (m3/hr/m2 @ 50Pa)
–
–
–
–
5.2
*Worked examples to meet Fabric Energy Efficiency Standard (FEES) proposals for detached house – Zero Carbon Hub 2012
EXTERNAL WALLS
System Ref.
Component
Max Height
Min Thickness
U-Value
(m)
(mm)
(W/m2k)
Fire Perf. BS476-21 BS EN 1365-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
RFL 002 Facing Inner Layer(s): – 2.4 – 0.30 30 51 F Faci Fac acing ing g Ou O Out uter ter La L Layer ayer y ((s)): ): Facing Outer Layer(s): 30 1x 15mm 1x 15mm GTEC 15 GTEC T C Vapour Va Vapou Vapou p r Fire F Fiire ire Board Bo Board d Lining Lin ing g: Sh eathi eat thing board boar oard d – Recom R Re ecom commen mend men ded d Lining: Sheathing Recommended GTEC Aqua Board Insulation: 120mm glass fibre (BS5250) Internal Wall Leaf: Timber Frame Stud ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk work
19
20
GTEC速 PARTITIONS
21
PARTITIONS The GTEC range of metal stud profiles provides system solutions for most building projects. Combining the right GTEC plasterboard, fixings, frame and finishing products, gives partition solutions up to the most demanding levels of fire, acoustic and thermal performance.
System Performance Tables GTEC LaDura Partition Systems
22
GTEC Aqua Board Partition Systems
26
GTEC Megadeco Partition Systems
28
GTEC Universal Board Partition Systems
32
GTEC dB Board Partition Systems
33
GTEC Fire Board Partition Systems
38
GTEC Standard Board Partition Systems
41
GTEC Acoustic Homespan Partition Systems
43
GTEC E Board Partition Systems
44
GTEC Structural Frame Partition Systems
45
Masonry Robust Detail Systems
46
GTEC Timber Partition Systems
47
GTEC C Stud Partitions GTEC Acoustic Stud Partitions GTEC Acoustic Homespan Partitions GTEC Resilient Bar Partitions GTEC Twin Frame Partitions GTEC Timber Partitions
50 72 80 88 94 110
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
22
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® LADURA PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
95
30 30
Severe
48
4.0
100
60 60
Severe
41
33
4.0
100
60 60
Severe
49
33
3.8
100
60 60
Severe
51
33
4.0
100
60 60
Severe
50
45
4.6
120
60 60
Severe
56
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
27
3.7
33
LDP 008: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 001: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
LDP 003: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ADP 003: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 004: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
LDP 050: C Stud Partition – see p50 Facing Inner Layer(s): 1x 9.5mm GTEC Standard Board Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
120
120 90
Severe
56
5
120
120 120
Severe
56
64
5.6
130
120 120
Severe
57
33
5.0
120
60 60
Severe
50
33
5.0
120
60 60
Severe
51
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
52
5
52
LDP 011: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC LaDura Board Facing Outer Layer(s): 1x 12.5mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 011F: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 024: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC LaDura Board Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 128: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 138: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
23
24
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® LADURA PARTITION SYSTEMS continued
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
120
60 60
Severe
52
6.2
145
90 60
Severe
56
52
6.4
140
120 90
Severe
57
52
6.4
140
120 90
Severe
60
64
7.2
150
120 120
Severe
58
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
33
5.0
52
ADP 138: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC AS90Rx Acoustic C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 086: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 130: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC LaDura Board Facing Outer Layer(s): 1x 12.5mm GTEC LaDura Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ADP 130: Acoustic Stud Partition – see p72 Facing Inner Layer(s): 1x 12.5mm GTEC LaDura Board Facing Outer Layer(s): 1x 12.5mm GTEC LaDura Board Studs: Single GTEC AS90Rx Acoustic C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
LDP 140: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC LaDura Board Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
170
60 60
Severe
56
200
120 120
Severe
65, -8 Ctr
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
33
5.0
64
6.4
LDP 013: Twin Frame Partition – see p94 Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Twin GTEC CS50Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: GTEC V-Brace at 1500mm centres
LDP 038: Twin Frame Partition – see p94 Facing Inner Layer(s): 1x 15mm GTEC LaDura Board Facing Outer Layer(s): 1x 15mm GTEC LaDura Board Studs: Twin GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: GTEC V-Brace at 1500mm centres
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
25
26
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® AQUA BOARD PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
95
30 30
Medium
46
3.6
100
60 60
Severe
40
28
3.6
100
60 60
Severe
46
28
3.6
100
60 60
Severe
47
28
3.6
100
60 30
Severe
49
28
3.6
100
60 30
Severe
47
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
23
3.2
28
RAP 004: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC Aqua Board Studs: Single GTEC CS70/B C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RAP 001: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board Studs: Single GTEC CS70/B C Studs at 600mm centres Insulation: – Accessories: –
RAP 003: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board Studs: Single GTEC CS70/B C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RAP 044: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board Studs: Single GTEC CS70/B C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
RMAP 003: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board, 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMAP 004: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board, 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
98
60 60
Severe
46
3.6
98
60 60
Severe
47
28
3.6
100
60 60
Severe
52
44
4.4
120
60 60
Severe
56
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
26
3.5
26
RMAP 022: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board, 1x 12.5mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMAP 068: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board, 1x 12.5mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
AMAP 004: Acoustic C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Aqua Board, 1x 15mm GTEC Megadeco Board Studs: Single GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: GTEC AS70Rx Acoustic C Studs at 600mm centres Accessories: –
RMAP 050: C Stud Partition – see p50 Facing Inner Layer(s): 1x 9.5mm GTEC Standard Board Facing Outer Layer(s): 1x 15mm GTEC Aqua Board, 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
27
28
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® MEGADECO PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
100
60 60
Severe
40
3.8
100
60 60
Severe
49
29
3.8
100
60 60
Severe
51
27
3.8
100
60 60
Severe
50
30
3.8
100
60 60
Severe
52
27
3.8
100
60 60
Severe
53
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
27
3.8
27
RMP 001: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
RMP 003: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
AMP 003: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 004: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
AMP 004: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
AMP 140: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Facing Inner Layer(s): 1x 15mm GTEC Megadeco Board inside studs one side Studs: GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: – See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
120
60 60
Severe
56
4.6
120
120 120
Severe
52
44
4.6
120
120 120
Severe
56
27
4.6
120
60 60
Severe
42
27
4.6
120
60 60
Severe
50
27
4.6
120
60 60
Severe
51
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
40
4.6
43
RMP 050: C Stud Partition – see p50 Facing Inner Layer(s): 1x 9.5mm GTEC Standard Board Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 009: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
RMP 011: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Megadeco Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 127: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: – Accessories: –
RMP 128: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 138: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
29
30
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® MEGADECO PARTITION SYSTEMS continued
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
120
60 60
Severe
54
4.6
120
60 60
Severe
52
45
5.8
140
90 90
Severe
57
54
6.5
150
90 90
Severe
58
53
6.3
150
90 90
Severe
60
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
40
4.6
31
AMP 141: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Facing Inner Layer(s): 1x 15mm GTEC Megadeco Board inside studs one side Studs: Single GTEC AS90Rx Acoustic C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
AMP 138: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC AS90Rx Acoustic C Studs at 600mm centres Insulation: 75mm 16kg/m3 glass mineral wool Accessories: –
RMP 130: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC dB Board Facing Outer Layer(s): 1x 12.5mm GTEC Megadeco Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 140: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
AMP 142: Acoustic Stud Partition – see p72 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC AS90Rx Acoustic C Studs at 600mm centres Insulation: 75mm 16kg/m3 glass mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
176
60 60
Severe
42
7.3
176
60 60
Severe
52
57
8.9
206
90 90
Severe
57
55
5.3
200
120 90
Severe
63 -8 Ctr
54
6.7
206
120 120
Severe
61 -6 Ctr
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
29
8.8
28
RMP 062: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS146Y C Studs at 600mm centres Insulation: – Accessories:–
RMP 075: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 017: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RMP 038: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Twin GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: GTEC V-Brace at 1500mm centres
AMP 017: Acoustic Stud Partition – see p72 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Megadeco Board Studs: Single GTEC AS146Rx C Studs at 600mm centres Insulation: 100mm 10kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
31
32
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® UNIVERSAL BOARD PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
95
60 30
Heavy
45
3.8
100
60 60
Severe
40
46
5.5
120
120 120
Severe
55
46
8.6
196
120 120
Severe
50
47
8.6
196
120 120
Severe
57
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
24
4.3
27
RUP 055: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC Universal Board Studs: Single GTEC CS70B C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RUP 001: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Universal Board Studs: Single GTEC CS70B C Studs at 600mm centres Insulation: – Accessories: –
RUP 048: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Universal Board Facing Outer Layer(s): 1x 12.5mm GTEC Universal Board Studs: Single GTEC CS70B C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RUP 053: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Universal Board Facing Outer Layer(s): 1x 12.5mm GTEC Universal Board Studs: Single GTEC CS146B C Studs at 600mm centres Insulation: – Accessories: –
RUP 054: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Universal Board Facing Outer Layer(s): 1x 12.5mm GTEC Universal Board Studs: Single GTEC CS146B C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® dB BOARD PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
80
30 30
Heavy
40
3.5
75
30 30
Medium
44
23
4.5
95
30 30
Medium
40
23
4.5
95
30 30
Medium
45
27
4.4
100
30 30
Heavy
42
27
4.4
100
30 30
Heavy
46
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
27
3.4
23
RSP 001: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: – Accessories: –
RSP 002: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RSP 006: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
RSP 028: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RSP 007: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
RSP 008: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
33
34
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® dB BOARD PARTITION SYSTEMS continued
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
100
30 30
Heavy
49
3.6
100
60 60
Severe
53
45
4.6
120
60 60
Severe
58
53
5.1
130
90 90
Severe
56
53
5.1
130
90 60
Severe
57
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
28
4.5
45
ASP 003: Acoustic Stud Partition – see p72 Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: –
RSP 027: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC dB Board Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ASP 011: Acoustic Stud Partition – see p72 Facing Inner Layer(s): 1x 12.5mm GTEC dB Board Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Studs: GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RSP 013: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ASP 013: Acoustic Stud Partition – see p72 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: GTEC AS70Rx Acoustic C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
206
90 90
Severe
57
5.3
200
90 60
Severe
63 -7 Ctr
52
10.2
295
60 60
Severe
67 -9 Ctr
60
10.5
300
90 60
Severe
69 -9 Ctr
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
54
8.9
54
RSP 017: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RSP 038: Twin Frame Partition – see p94 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Twin GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: GTEC V-Brace at 1500mm centres
RSP 022: Twin Frame Partition – see p94 Facing Inner Layer(s): 1x 12.5mm GTEC dB Board Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Studs: Twin GTEC CS90W C Studs at 600mm centres Insulation: 100mm 10kg/m3 glass mineral wool Accessories: GTEC V-Brace at 3000mm centres plus extension
RSP 023: Twin Frame Partition – see p94 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Twin GTEC CS90W C Studs at 600mm centres Insulation: 100mm 10kg/m3 glass mineral wool Accessories: GTEC V-Brace at 3000mm centres plus extension
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
35
36
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® dB BOARD PARTITION SYSTEMS continued
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
400
120 90
Severe
74 -7 Ctr
5.3
130
60 60
Severe
59
54
3.7
147
90 90
Severe
62 -9 Ctr
54
7.2
223
90 90
Severe
63 -8 Ctr
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
86
12
56
RSP 037: Twin Frame Partition – see p94 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 2x 15mm GTEC dB Board Studs: Twin GTEC CS90W C Studs at 600mm centres Insulation: 2x 100mm 10kg/m3 glass mineral wool Accessories: GTEC V-Brace at 3000mm centres plus extension
RSP 085: I Stud Partition – contact Enquiryline Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Staggered GTEC IS60B I-Studs at 300mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: 72mm GTEC Track with IS10 clips
RSP 157: Resilient Bar Partition – see p88 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: Single GTEC Resilient Bar at 600mm vertical centres
RSP 159: Resilient Bar Partition – see p88 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: Single GTEC Resilient Bar at 600mm vertical centres
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
55
6.9
206
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
90 90
Severe
61 -6 Ctr
ASP 017: Acoustic Stud Partition – see p72 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Single GTEC AS146Rx C Studs at 600mm centres Insulation: 100mm 10kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
37
38
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® FIRE BOARD PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
100
120 120
Severe
52
4.0
100
60 60
Heavy
47
42
4.6
120
120 120
Severe
46
42
4.6
120
120 120
Severe
53
50
4.9
130
120 120
Severe
48
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
42
3.6
26
RFP 016: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 044: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 054: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
RFP 050: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 045: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: – Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
130
120 120
Severe
56
5.1
120
60 60
Heavy
40
42
5.3
140
120 120
Severe
48
42
5.3
140
120 120
Severe
56
26
6.6
176
60 60
Heavy
42
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
51
4.9
26
RFP 046: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 127: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: – Accessories: –
RFP 134: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: None Accessories: –
RFP 135: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Single GTEC CS90Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 062: C Stud Partition – see p50 Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: – Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
39
40
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® FIRE BOARD PARTITION SYSTEMS continued
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
196
120 120
Severe
57
6
205
240 240
Severe
65 -10 Ctr
50
3.3
147
120 120
Severe
61 -7 Ctr
52
4.5
200
120 120
Severe
62 -7 Ctr
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
43
8.0
88
RFP 076: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 112: Fire Wall Partition – contact Enquiryline Facing Inner Layer(s): 3x 15mm GTEC Fire Board down centre Facing Outer Layer(s): 2x 15mm GTEC Fire Board each side Studs: Twin Staggered GTEC CS50Rx C Studs at 600mm centres Insulation: 2x 25mm 16kg/m3 glass mineral wool Accessories: –
RFP 157: Resilient Bar Partition – see p88 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 50mm 16kg/m3 glass mineral wool Accessories: Single GTEC Resilient Bar at 600mm vertical centres
RFP 038: Twin Frame Partition – see p94 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Twin GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: GTEC V-Brace at 1500mm centres
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® STANDARD BOARD PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
75
30 –
Medium
34
3.2
75
30 30
Medium
41
18
4.2
95
30 30
Medium
42
34
4.6
120
60 30
Severe
45
35
4.6
120
60 30
Severe
49
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
17
3.2
18
RCP 001: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: – Accessories: –
RCP 002: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 33kg/m3 rock mineral wool Accessories: –
RCP 042: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 33kg/m3 rock mineral wool Accessories: –
RCP 045: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: None Accessories: –
RCP 046: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
41
42
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® STANDARD BOARD PARTITION SYSTEMS continued
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
196
60 30
Severe
48
7.6
196
60 30
Severe
52
8.2
206
90 60
Severe
56
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
35
7.6
35
43
RCP 064: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: None Accessories: –
RCP 067: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RCP 068: C Stud Partition – see p50 Facing Inner Layer(s): 1x 15mm GTEC Standard Board Facing Outer Layer(s): 1x 15mm GTEC Standard Board Studs: Single GTEC CS146Rx C Studs at 600mm centres Insulation: 25mm 33kg/m3 rock mineral wool Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® ACOUSTIC HOMESPAN PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
74
30 30
Heavy
40
2.7
74
30 30
Heavy
43
2.8
80
30 30
Heavy
41
2.8
80
30 30
Heavy
43
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
2.7
AHP 001: Acoustic Homespan Partition – see p80 Facing Outer Layer(s): 1x 15mm GTEC Acoustic Homespan Board Studs: GTEC AHS44Rx Acoustic Homespan Studs at 450mm centres Insulation: – Accessories: –
28
AHP 002: Acoustic Homespan Partition – see p80 Facing Outer Layer(s): 1x 15mm GTEC Acoustic Homespan Board Studs: GTEC AHS44Rx Acoustic Homespan Studs at 450mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
29
AHP 003: Acoustic Homespan Partition – see p80 Facing Outer Layer(s): 1x 15mm GTEC Acoustic Homespan Board Studs: GTEC AHS50Rx Acoustic Homespan Studs at 450mm centres Insulation: – Accessories: –
28
AHP 004: Acoustic Homespan Partition – see p80 Facing Outer Layer(s): 1x 15mm GTEC Acoustic Homespan Board Studs: GTEC AHS50Rx Acoustic Homespan Studs at 450mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
29
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
43
44
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® E BOARD PARTITION SYSTEMS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
75
30 30
Medium
41
3.4
100
60 60
Severe
43
21
4.3
95
30 30
Medium
42
41
4.6
120
60 60
Severe
46
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
21
3.3
41
REP 002: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC E Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
REP 005: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC E Board Facing Outer Layer(s): 1x 12.5mm GTEC E Board Studs: Single GTEC CS50Rx C Studs at 600mm centres Insulation: None Accessories: –
REP 042: C Stud Partition – see p50 Facing Outer Layer(s): 1x 12.5mm GTEC E Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
REP 045: C Stud Partition – see p50 Facing Inner Layer(s): 1x 12.5mm GTEC E Board Facing Outer Layer(s): 1x 12.5mm GTEC E Board Studs: Single GTEC CS70Rx C Studs at 600mm centres Insulation: None Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® STRUCTURAL FRAME PARTITION SYSTEMS
System Ref.
Fire Perf. BS476-21 BS EN 1365-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
310
60 60
Severe
Robust Detail Solution
4.5
315
60 60
Severe
Robust Detail Solution
–
4.0
310
90 60
Severe
66 -9 Ctr
–
4.5
245
60 60
Severe
61 -7 Ctr
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Twin Structural C-Studs at 600mm centres Insulation: 1x 50mm 33-60kg/m3 mineral wool Accessories: –
–
4.5
Facing Inner Layer(s): 1x 19mm GTEC Plank Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Twin Structural C-Studs at 600mm centres Insulation: 1x 50mm 33-60kg/m3 mineral wool Accessories: –
–
Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: Twin 100mm Structural C-Studs at 600mm centres Insulation: 2x 75mm 24kg/m3 glass mineral wool Accessories: –
Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1 x 15mm GTEC Fire Board Studs: Single 150mm Structural C-Studs at 600mm centres Insulation: 50mm 24kg/m3 glass mineral wool Accessories: Single GTEC Resilient Bar at 600mm vertical centres Both sides
Component
E-WS-1
E-WS-1 alt.
RLB 003
RLB 014
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
45
46
GTEC® PARTITIONS – PERFORMANCE TABLES
MASONRY ROBUST DETAIL SYSTEMS
System Ref.
Fire Perf. BS476-21 BS EN 1365-1 (mins)
Strength Duty Rating to BS 5234-2
Acoustic Perf. Rw dB (Ctr if applicable)
315
240 240
–
Robust Detail Solution
5.2
315
240 240
–
Robust Detail Solution
–
5.2
315
240 240
–
Robust Detail Solution
–
5.2
315
240 240
–
Robust Detail Solution
System Weight
Max. Height
Overall Thickness
(kg/m2)
(m)
(mm)
Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board both sides Lining: Sand Cement render Universal Bonding Compound to form 10mm cavity Cavity: 75mm; Insulation: – Internal Wall Leaf: 100mm Blocks Density 1850-2300kg/m3 External Wall Leaf: 100mm Blocks Density 1850-2300kg/m3
–
5.2
Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board both sides Lining: GTEC E Coat Render Universal Bonding Compound to form 10mm cavity Cavity: 75mm; Insulation: – Internal Wall Leaf: 100mm Blocks Density 1350-1600kg/m3 External Wall Leaf: 100mm Blocks Density 1350-1600kg/m3
–
Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board both sides Lining: Sand Cement render Universal Bonding Compound to form 10mm cavity Cavity: 75mm; Insulation: – Internal Wall Leaf: 100mm Star Performer Blocks External Wall Leaf: 100mm Star Performer Blocks
Facing Outer Layer(s): GTEC 12.5mm Standard Board both sides Lining: GTEC E Cont Render Universal Bonding Compound to form 10mm cavity Cavity: 100mm; Insulation: – Internal Wall Leaf: 100mm Blocks Density 1350-1600kg/m3 External Wall Leaf: 100mm Blocks Density 1350-1600kg/m3
Component
E-WM-3
E-WM-4
E-WM-5
E-WM-11
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® TIMBER PARTITION SYSTEMS
System Ref.
Component
System Weight
Max. Height
Overall Thickness
Fire Perf. BS476-22 Non-load bearing (NLB) BS EN 1364-1 (mins)
Fire Perf. BS476-21 Load bearing (LB) BS EN 1365-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr if applicable)
(kg/m2)
(m)
(mm)
55
3.6
166
60 60
60 60
Severe
57
21
3.0
88
30 30
– –
Medium
36
18
3.0
88
30 –
– –
Medium
35
21
3.9
114
30 30
30 –
Medium
35
38
2.8
113
60 30
– –
Severe
42
RTP 152: Timber Partition – see p110 Facing Inner Layer(s): 1x 15mm GTEC dB Board Facing Outer Layer(s): 1x 15mm GTEC dB Board Studs: 38x89mm Timber Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: GTEC Resilient Bar at 600mm centres
RTP 021: Timber Partition – see p110 Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: 38x63mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 001: Timber Partition – see p110 Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: 38x63mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 005: Timber Partition – see p110 Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: 38x89mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 031: Timber Partition – see p110 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: 38x63mm Timber Studs at 600mm centres Insulation: – Accessories: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
47
48
GTEC® PARTITIONS – PERFORMANCE TABLES
GTEC® TIMBER PARTITION SYSTEMS continued
System Ref.
Component
System Weight
Max. Height
Overall Thickness
Fire Perf. BS476-22 Non-load bearing (NLB) BS EN 1364-1 (mins)
Fire Perf. BS476-21 Load bearing (LB) BS EN 1365-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr if applicable)
(kg/m2)
(m)
(mm)
5.8
295
60 60
60 60
Severe
65
54
5.7
290
60 60
60 60
Severe
66
28
4.7
130
60 30
60 30
Heavy
38
36
2.9
125
60 30
60 30
Severe
43
23
3.9
113
30 30
30 30
Medium
36
RFL 011 RD: Timber Partition – see p110 Facing Inner Layer(s): 1x 19mm GTEC Plank Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: Twin 38x89mm Timber Studs at 600mm centres Insulation: 2x 50mm 16kg/m3 glass mineral wool Accessories: Brace at mid height
53
RFL 050 RD: Timber Partition – see p110 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: Twin 38x89mm Timber Studs at 600mm centres Insulation: 2x 50mm 16kg/m3 glass mineral wool Accessories: Brace at mid height
RTP 006: Timber Partition – see p110 Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: 50x100mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 012: Timber Partition – see p110 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: 50x75mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 035: Timber Partition – see p110 Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: 38x88mm Timber Studs at 600mm centres Insulation: – Accessories: –
See p49 for notes on alterations to partition configuration.
GTEC® PARTITIONS – PERFORMANCE TABLES
System Ref.
Component
System Weight
Max. Height
Overall Thickness
Fire Perf. BS476-22 Non-load bearing (NLB) BS EN 1364-1 (mins)
Fire Perf. BS476-21 Load bearing (LB) BS EN 1365-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr if applicable)
(kg/m2)
(m)
(mm)
39
3.4
138
60 60
60 60
Severe
45
27
3.5
118
60 30
30 –
High
37
27
3.5
118
60 30
30 –
High
41
35
3.4
138
30 30
30 –
Severe
42
RTP 043: Timber Partition – see p110 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Studs: 38x88mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 045: Timber Partition – see p110 Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: 38x88mm Timber Studs at 600mm centres Insulation: – Accessories: –
RTP 047: Timber Partition – see p110 Facing Outer Layer(s): 1x 15mm GTEC Fire Board Studs: 38x88mm Timber Studs at 600mm centres Insulation: 25mm 16kg/m3 glass mineral wool Accessories: –
RTP 059: Timber Partition – see p110 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Studs: 38x88mm Timber Studs at 600mm centres Insulation: – Accessories: –
PARTITION PERFORMANCE NOTES Performance values are for imperforate, jointed systems using Siniat GTEC components (metal studs and tracks, boards, metal accessories, screws and finishing systems) and specified insulation quilt material (type, thickness and density) and installed to Siniat specification and installation guides. Any alterations may impair the quoted performance. Contact Technical Enquiryline for further system configurations and their resulting performances. All maximum heights are based on a maximum partition deflection limit of height/240 at the stated duty ratings under a uniform lateral pressure of 0.2 kN/m2 and can be increased using thicker gauge studs. Maximum height can be increased by 0.3m for single layer boarding and by 0.6m for double layer boarding when studs centres are reduced to 400mm. The maximum partition height may vary from the quoted values if the fire resistance of the system is specified according to BS EN 1364-1. Insulation shown may be replaced with thicker and/or heavier quilt material without impairing the quoted performances.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
49
50
GTEC® C STUD PARTITION
®
GTEC C STUD PARTITION SYSTEMS GTEC Metal Stud Partitioning is an economical, friction-fit system for assembling internal partitions. The unique design of the components ensures high strength, easy installation and a higher performing alternative to traditional timber frame partitions. GTEC C Stud Partitions are constructed using a frame of GTEC U Track at the head and base with GTEC C Studs for vertical framing elements. A range of GTEC C Stud and U Track widths allow varying partition depth, enhancing fire resistance, sound insulation and maximum heights. For individual system performances, refer to the System Performance Tables on pages 22 to 44.
WHERE TO USE: GTEC C Stud Partitions create internal dividing walls within both domestic and commercial projects.
FEATURES
BENEFITS
Strong
Less material is required than a similar timber frame structure
Lightweight
Multiple lengths can be carried at one time
Natural resistance to bowing, bending and insect infestation
Metal maintains shape, removing the chance of ‘screw popping’
High fire resistance levels
Fire performance levels are easily achieved using metal
High acoustic performance levels
Acoustic performance levels are easily achieved using metal
Flat finish
Provides an easy surface for decoration
GTEC速 C STUD PARTITION
TIP: Partition heights can be increased with additional studs, e.g. with studs boxed, back-to-back, at closer centres or thicker stud gauges.
GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
timber stud for jamb reinforcement
GTEC Insulation Hold at 1200mm centres
GTEC Socket Pad
GTEC Intumescent Acoustic Sealant
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
51
52
GTEC速 C STUD PARTITION
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p22-44
GTEC C Stud Metal profile for vertical frame elements
CS50/RX, CS60/RX, CS70/RX, CS90/RX, CS146/RX, CS70/B, CS90/B, CS146/B, CS90/W, CS70/Y, CS90/Y, CS146/Y
GTEC U Track Metal profile for head and base frame elements
UT52/RX, UT62/RX, UT72/RX, UT92/RX, UT148/RX
GTEC U Track Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UDT62/B, UDT72/B, UDT92/B, UDT148/B, UT52/Y
GTEC U Track Extra Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UXT72/B, UXT92/W, UXT148/W
GTEC Fixing Channel Provide support for plasterboard joints and fixtures
MFIX/W
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
GTEC Flex Track Deep Flange Steel track for curved partitions
DFLEX/B
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See fixing selector, p334-335
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® C STUD PARTITION
SYSTEM GUIDANCE FRAME PT-CS-102S-Base
PT-CS-101S-Head – no deflection
GTEC U Track fixed at max. 600mm centres
GTEC Board to suit required performance 5mm shorter than floor to ceiling height
GTEC Intumescent Acoustic Sealant screw fix plasterboard to track
GTEC C Stud cut 5mm shorter than floor to ceiling height
GTEC Board to suit required performance 5mm shorter than floor to ceiling height
screw fix plasterboard to track GTEC Intumescent Acoustic Sealant
GTEC C Stud 5mm shorter than floor to ceiling height
GTEC U Track fixed at 600mm centres
SECTION PT-CS-103S-Base with timber sole plate and screed GTEC Board to suit required performance GTEC C Stud
screw fix plasterboard to track
GTEC U Track on timber sole plate GTEC Intumescent Acoustic Sealant
SECTION PT-CS-104P-End detail
GTEC Board to suit required performance
GTEC Corner 90º External / GTEC Flex Tape
GTEC C Stud boxed or increase stud gauge
FLOATING SCREED
Resilient layer
timber sole plate to same depth as screed
SECTION
PLAN
PT-CS-105M-Stud splice
600mm overlap for height ≤ 4m
1000mm overlap for height > 4m
screw fix at 150mm centres both sides
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
53
54
GTEC® C STUD PARTITION
FRAME continued Select compatible sizes (e.g. 50mm stud and 52mm track) of GTEC C Stud and GTEC U Track framing elements to meet system performance. GTEC U Track Deep or Extra Deep Flange to be used for heights greater than 4.2m and where deflection allowance is required. Studs abutting structure (starter studs) to be fixed with web flat to structure using appropriate fixings by others at maximum 600mm centres and fixed to head and track with appropriate GTEC Drywall Screws (see screw selector, p334-335). GTEC U Track to be fixed flat to structure using appropriate fixings by others at maximum 600mm centres. Timber sole plate may be required on uneven floors or where partition is constructed prior to screeding.
Protect base track from moisture with damp proof membrane when situated on newly laid concrete floors. All GTEC C Studs to be 5mm shorter than floor to ceiling height except in case of head deflection requirement (see p61). Intermediate GTEC C Studs, facing in same direction, to be friction fitted into tracks to allow for adjustment during boarding. GTEC C Studs to be at centres required to meet system performance with a maximum of 600mm centres. Where wall height exceeds available GTEC Stud length splice two lengths together ensuring overlap of 600mm for heights less than 4m and 1000mm for heights more than 4m.
INSULATION PT-CS-151M-Insulation Hold
Insulation, if required, to be of type and thickness to achieve performance and installed in a continuous layer between frames or studs.
GTEC Insulation Hold to support each insulation batt
Where insulation may be expected to slump suspend from GTEC Insulation Hold strips fixed across studs, 150mm from top of partition and at 1200mm vertical centres.
screw fixed to studs at max. 1200mm vertical centres
ISOMETRIC
GTEC® C STUD PARTITION
BOARDING PT-CS-201M-Board fixing – single layer
PT-CS-202M-Board fixing – double layer
screw fix plasterboard at maximum 300mm centres All joints in outer layer taped and jointed
joints on alternating studs
Joints on opposite faces offset and staggered between layers
ISOMETRIC PT-CS-203M-Horizontal joint reinforcement, single layer
ISOMETRIC PT-CS-204M-Horizontal joint reinforcement, double layer
fixing strap to reinforce horizontal edge of boards where partition > board height
fixing strap to reinforce horizontal edge of boards where partition > board height
screw fix to fixing strap at max. 300mm centres
screw fix to fixing strap at max. 300mm centres
GTEC Flat Strap FS50/RX screw fixed to studs through board
GTEC Flat Strap FS90/W screw fixed to stud
ISOMETRIC
GTEC Twin Frame partition system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables (p22-24) and Product Specification (p294-307) to achieve required performance. See High Performance Boards guide (p12-15) for further selection information. Boards to be 5mm less than floor to ceiling height except in case of deflection requirement, see p61.
ISOMETRIC
Boards to be mechanically fixed to studs at 300mm centres using appropriate GTEC Drywall Screws (see screw selector, p334-335). Base layers of boarding may be temporarily fixed at 600mm centres providing final layer is fixed through to stud at 300mm centres. Board edges to be centred over studs. Stagger all board joints between layers. Stagger all board joints on opposing sides of partition.
Strips of board 300mm wide or less to be avoided by stud location rearrangement.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
55
56
GTEC® C STUD PARTITION
BOARDING continued Over-height single layer boarding:
Over-height multiple layer boarding:
Where partition height exceeds board height GTEC Flat Strap FS90/W or GTEC MFIX to be fixed behind all horizontal joints to provide substrate for board fixing.
Where partition height exceeds board height for double or multiple layer boarding GTEC Flat Strap FS50/RX to be fixed behind all horizontal joints in outer layer of board.
MOVEMENT CONTROL JOINTS PT-CS-301P-Movement control joint – single boarded
screw fix plasterboard to stud
10mm between boards and tracks
GTEC Movement Control Joint
PT-CS-302P-Movement control joint – double boarded
10mm between boards and tracks
GTEC Movement Control Joint GTEC Fire Board 2x 15mm cut to exact width of stud
10mm
Rock mineral wool to fill void GTEC Board to suit required performance
GTEC Board to suit required performance
10mm
10mm
GTEC Fire Board 2 x 15 mm cut to exact width of stud
PLAN
Form movement control joints at maximum 10m intervals in the partition run. Form movement control joints where the partition crosses a structural movement joint.
20mm
screw fix plasterboard to stud
70mm
PLAN
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
GTEC® C STUD PARTITION
OPENINGS PT-CS-401P-Door frames – 25kg to 100kg door loads
GTEC Intumescent Acoustic Sealant Up to Door 25 kg
Timber stud minimum 32mm wide
GTEC C Stud 50-146mm wide 150mm
GTEC Intumescent Acoustic Sealant Timber stud minimum 32mm wide
Up to 50kg Door
GTEC C Stud boxed 50-146mm wide 150mm
GTEC Intumescent Acoustic Sealant Timber stud minimum 32mm wide
Up to 75kg Door
GTEC C Stud boxed 70-146mm wide 150mm
GTEC Intumescent Acoustic Sealant Timber stud minimum 32mm wide
Up to 100kg Door
GTEC C Stud boxed 70-146mm wide 150mm GTEC C Stud boxed 70- 146mm wide Note: Insulation not shown for clarity
PLAN PT-CS-403E-Single and double door frames
GTEC C Stud
400mm
GTEC UXT Track Section A-A
A
optional timber head stud for door fixing A
Min. 150mm
Max. 2m
Reinforcement as shown in door frame plan to full height of partition Single Door
Max. 150mm
Double Door
Max. 150mm
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
57
58
GTEC® C STUD PARTITION
OPENINGS continued Form openings following guidance in Construction Detail Drawings to suit door weights.
Reinforce jamb studs with timber and boxed studs as described in Construction Detail Drawings.
Reinforce head-to-jamb junction 150mm down each jamb stud by cutting and folding head track.
Jamb studs to be fixed to track with appropriate GTEC Drywall Screws (see screw selector, p334-335).
CORNERS AND JUNCTIONS PT-CS-502P-Corner detail, double layer
PT-CS-501P-Corner detail, single layer
GTEC C Stud GTEC C Stud GTEC Intumescent Acoustic Sealant
connect studs through plasterboard
screw fix plasterboard to stud
screw fix plasterboard to stud
connect studs through plasterboard
GTEC Board to suit required performance
GTEC Board to suit required performance
PLAN PLAN
PLAN PLAN PT-CS-503P-Non-acoustic T-junction, single layer
PT-CS-504P-Non-acoustic T-junction, double layer
connect studs through plasterboard
GTEC C Stud
GTEC C Stud
connect studs through plasterboard
screw fix plasterboard to stud GTEC Board to suit required performance
PLANPLAN
screw fix plasterboard to stud GTEC Board to suit required performance
PLAN
GTEC® C STUD PARTITION
PT-CS-505P-Acoustic rated T-junctions, single layer
PT-CS-506P-Acoustic rated T-junctions, double layer
GTEC Intumescent Acoustic Sealant
screw fix plasterboard to stud
GTEC C Stud
GTEC Intumescent Acoustic Sealant
GTEC C Stud
screw fix plasterboard to stud
GTEC Board to suit required performance
GTEC Board to suit required performance
PLAN PT-CS-507P-Splayed corners
PLAN PT-CS-508P-Four way junction
screw fix plasterboard to stud GTEC C Stud GTEC Intumescent Acoustic Sealant
screw fix plasterboard to stud
Timber fillet
GTEC External Corner Tape GTEC C Stud GTEC Board to suit required performance
Min. 10mm gap stud to stud connection on alternating sides
GTEC Board to suit required performance
PLAN PT-CS-509P-Junction with Masonry – Plastered
PLAN PT-CS-510P-Junction with Masonry – Dryliner & Direct Bond
GTEC Intumescent Acoustic Sealant GTEC Direct Bond lining system
screw fix plasterboard to stud
GTEC Intumescent Acoustic Sealant
existing skim plaster chased out to receive partition
GTEC Dryliner lining system
PLAN
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
59
60
GTEC® C STUD PARTITION
CORNERS AND JUNCTIONS continued PT-CS-509P-Junction with Masonry – Plastered
PT-CS-510P-Junction with Masonry – Dryliner & Direct Bond
GTEC Intumescent Acoustic Sealant GTEC Direct Bond lining system
screw fix plasterboard to stud
GTEC Intumescent Acoustic Sealant
existing skim plaster chased out to receive partition
GTEC Dryliner lining system
PLAN PT-CS-513P-T-Junction of Single into Twin Frame
PLAN PT-CS-514P-T-Junction of Twin into Single Frame
fix studs together through board GTEC Twin Frame System
GTEC Twin Frame System
fix studs together through board
fix stud to twin frame head and base track or ensure single frame partition coincides with twin frame studs GTEC Intumescent Acoustic Sealant GTEC C Stud or Acoustic Stud System
PLAN
Abutting partitions to coincide with studs, install additional intermediate ‘pick-up’ stud if required. Connect studs through plasterboards at corners and junctions at 600mm vertical centres using appropriate GTEC Drywall Screws.
PLAN
See Construction Details Drawings for further guidance on arrangement and fixing.
GTEC® C STUD PARTITION
HEAD DEFLECTION PT-CS-601S-Deflection head, general arrangement
GTEC INTUMESCENT ACOUSTIC SEALANT
MINERAL WOOL & CLOAKING ANGLE packers cut precisely to track width
use head deflection table to select packers GTEC Intumescent Acoustic Sealant
=
Cloaking angle
boards cut short of soffit by deflection amount
=
Rock Mineral Wool
studs cut short of track by deflection amount
5mm
Minimum overlap of boards and packers
allow deflection amount as minimum between track and fixing
Minimum 20mm overlap of stud and track
=
20mm
screw fix flat strap between outer board layer and substrate
Note: Refer to the deflection table
SECTION
Deflection required:
Packer for all fire ratings:
Track for all fire ratings:
30 & 60 mins
90 & 120 mins
0-5mm
12.5mm GTEC Fire Board
GTEC U Track (UT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
6-10mm
15mm GTEC Fire Board
GTEC U Track (UT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
11-20mm
2x 12.5mm GTEC Fire Board or 25mm GTEC Fire Core Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
21-25mm
2x 15mm GTEC Fire Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
26-32mm
3x 12.5mm GTEC Fire Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
33-40mm
3x 15mm GTEC Fire Board
GTEC Extra Deep Flange U Track (UXT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
41-45mm
2x 25mm GTEC Fire Core Board or 4x 12.5mm GTEC Fire Board
GTEC Extra Deep Flange U Track (UXT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
61
GTEC® C STUD PARTITION
HEAD DEFLECTION continued PT-CS-603S-Def. Head – parallel to profiled soffit
PT-CS-604S-Def. Head – perpendicular to simple profile
profiled insulation by others to fill profile cavity
GTEC Intumescent Acoustic Sealant
GTEC FS90W at 600mm centres
PROFILED SOFFIT
deflection amount
deflection amount
15mm GTEC Fire Board to close cavity between profile and partition use head deflection table to select packer NOTE: follow general deflection head arrangement guidance for full construction and component detail
overlap Min. 150mm
62
15mm GTEC Fire Board cut to shape of metal deck profile
GTEC Flat Strap
SECTION
SECTION
PT-CS-605S-Def. Head – perpendicular to complex profile profiled insulation by others to fill profile cavity
PROFILED SOFFIT
deflection amount 15mm GTEC Fire Board continuous head packers
GTEC Flat Strap
SECTION PT-CS-606S-Def. Head – parallel to purlins – purlins cloaked
GTEC Board to suit required performance composite box stud to pick up top fix (size to suit purlin)
GTEC Ceiling Channels at 400mm centres, with GTEC Edge Channel or angle to edge stud and board cut short by required deflection
Composite box U Track
GTEC Edge Channel deflection amount
GTEC Partition to suit C Stud
SECTION
GTEC® C STUD PARTITION
PURLIN ZONE
PT-CS-608S-Def. Head – perpendicular to purlins
PT-CS-609S-Def. Head – under beam
GTEC Intumescent Acoustic Sealant
GTEC U Track
Metal angle fixed to purlin to provide profile fixing GTEC C Stud or U Track fixed between purlins
GTEC C Stud
deflection amount
GTEC Metal Angle 90°
composite box ladder frame GTEC C Stud and GTEC U Track spanning across purlins
GTEC Metal Angle 90°
GTEC U Track fixed to composite box GTEC Flat Strap as top fixing of boards
GTEC Flat Strap
SECTION
SECTION
PT-CS-610M-Telescopic deflection head assembly GTEC U Track
Deflection amount
studs to be free moving in both directions
GTEC U Track 370mm + deflection amount
GTEC C Stud cut short by 80mm + deflection amount
GTEC C Stud / U Track 370mm + deflection amount
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
63
64
GTEC® C STUD PARTITION
HEAD DEFLECTION continued PT-CS-611S-Telescopic deflection head – parallel to purlins
GTEC Intumescent Acoustic Sealant
GTEC C Stud fixed at 600mm centres between and screw fixed to purlins
GTEC C Stud fixed at 600mm centres GTEC U Track
Telescopic head
GTEC Metal Angle
GTEC U Track
NOTE: Insulation removed for clarity
SECTION
See Construction Detail Drawings and Tables for full details. Contact Siniat Technical Enquiryline for further information.
GTEC Studs to be cut short of track by deflection amount.
Continuity of head packer to be maintained.
GTEC Studs and Tracks to overlap by minimum 20mm.
No mechanical connection to be made between stud and head track.
GTEC Boards to be short of partition height by deflection amount.
All air paths to be sealed with GTEC Intumescent Acoustic Sealant.
GTEC Boards to overlap packer by minimum of 5mm.
GTEC® C STUD PARTITION
PENETRATIONS PT-CS-701P-Small diameter pipe penetration
GTEC Intumescent Acoustic Sealant
PT-CS-702E-Cable tray penetration
insulation to seal around penetrating pipe or conduit
GTEC Fire Board
GTEC Intumescent Acoustic Sealant GTEC U Track cut and bent
pipe or conduit less than 50mm in diameter
PLAN PT-CS-703M-Cable tray penetration at soffit GTEC Intumescent Acoustic Sealant
ELEVATION PT-CS-704E-Socket pad fitting
Packers and head to suit deflection if required
GTEC Socket Pad pre-cut socket pad folded and pushed into socket box
GTEC U Track 150mm up turn
2x 15mm GTEC Fire Board
GTEC C Stud Infill section of GTEC U Track fixed to lower track
ELEVATION
ISOMETRIC ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
65
66
GTEC® C STUD PARTITION
PENETRATIONS continued PT-CS-705P-Multiple pipe penetrations – Single frame
150mm
100mm min. overlap voisd filled with dense rock mineral wool GTEC Fire Board pattress
GTEC Board to suit required performance
NOTE : Insulation may be reduced if partition is not fire-rated
PLAN
ELEVATION
PT-CS-706S Fire damper
damper suspension rods protected within cavity GTEC U Track cut and folded to reinforce jamb stud
Fire damper
GTEC Intumescent Acoustic Sealant Rock mineral wool packed around damper max. 600mm
SECTION
M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated partitions. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings.
ELEVATION
Protect all electrical cables in cavity with conduit.
GTEC® C STUD PARTITION
FIXTURES PT-CS-801M-Flat strap for light-weight fixings
PT-CS-802M-Plywood pattress for heavy-weight fixings
GTEC C Stud
GTEC Shallow Wall Channel
screw fix 15mm plywood to GTEC Shallow Wall Channel at max. 300mm centres GTEC Flat Strap or Fixing Channel to provide fixing reinforcement
screw fix GTEC Shallow Wall Channel to GTEC C Stud at max. 300mm centres
fix final layer of board to stud over pattress and through channel face
ISOMETRIC ISOMETRIC
ISOMETRIC
PT-CS-803M-Timber support for extreme-weight fixings
Horizontal nogging and central stud of timber sawn to suit size of GTEC Metal Studs notched and fixed through ends
300mm length of GTEC C Stud screw fixed back to back main stud where stud is not positioned to receive timber
Vertical timber framing as required fixed into track
GTEC U Track
ISOMETRIC
SECTION PT-CS-804M-LaDura adhesive pattress for heavy-weight fixings
PT-CS-805M-LaDura channel pattress for heavy-weight fixings
GTEC LaDura Pattress glued to back of board using Drywall Adhesive/ GTEC Intumescent Acoustic Sealant
GTEC C Stud
GTEC Shallow Wall Channel fixing should be surrounded by min. 150mm of board screw fix 15mm GTEC LaDura board to GTEC Shallow Wall Channel at max. 300mm centres GTEC Intumescent Acoustic Sealant to adhere GTEC LaDura Pattress to board
screw fix GTEC Shallow Wall Channel to GTEC C Stud at max. 300mm centres
GTEC C Stud fix final layer of board to stud over pattress and through channel face Note: Only possible on one side of partition unless pre-fixed to boards.
ISOMETRIC
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
67
68
GTEC® C STUD PARTITION
FIXTURES continued PT-CS-806S-LaDura pattress types for fixings both sides
GTEC Shallow Wall Channel
GTEC LaDura Board
fixture fixed through into pattress
fixture fixed through into pattress
GTEC Intumescent Acoustic Sealant to adhere GTEC LaDura Pattress to board GTEC Stud
SECTION
Select fixture details for recommended fixture provision in combination with fixing capability. Appropriate fixings for loadings and substrate to be supplied by others. Site testing of fixings with plasterboard is recommended. GTEC LaDura is recommended as pattress or facing to enhance mechanical resistance of the fixing.
For high loadings partitions must be checked for overall robustness. GTEC Boards have been tested for pull-out strength in combination with Spit fixings, see maximum loadings and required arrangements in summary table. For complete results please consult Technical Enquiryline. Other manufacturer’s fixings will require further testing before use.
GTEC® C STUD PARTITION
PT-CS-807M-Fixing options chart
Spit Spring Toggle
Spit Satelis
Spit Hollow Wall Anchor
Spit Driva® Plus
Spit Driva®
Spit Driva® LD
DESIGN PULL-OUT LOADS (kN) including safety factor With 15mm LaDura pattress
Without pattress
Spit Driva®
Spit Hollow Wall Anchor
Spit Satelis
Spit Driva®
Spit Hollow Wall Anchor
Spit Satelis
Single layer 15mm GTEC Standard Boards*
0.35
0.7
1.25
0.15
0.35
0.4
Single layer 15mm GTEC Technical Boards**
0.35
0.75
1.4
0.2
0.4
0.5
Single layer 15mm GTEC LaDura
0.4
0.85
1.8
0.25
0.5
0.85
Double layer 15mm GTEC Standard Boards*
0.4
0.85
1.55
0.25
0.55
0.7
Double layer 15mm GTEC Technical Boards**
0.45
1.0
2.05
0.3
0.65
1.1
Double layer 15mm GTEC LaDura
0.5
1.15
2.85
0.4
0.85
1.8
Board Arrangement
*Standard boards are those up to 10kg/m2 for 15mm boards **Technical boards are those up to 13kg/m2 for 15mm boards
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
69
70
GTEC® C STUD PARTITION
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances.
GTEC Finish materials appropriate to board type to be used.
SYSTEM CONTINUITY Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings.
GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission. Full, imperforate system continuity to be maintained to achieve rated performances.
CURVED PARTITIONS PT-CS-901M-Single frame curved partition
See table for stud spacing to achieve curve radius
GTEC Flat Strap to reinforce horizontal joints GTEC Board to suit required performance
GTEC C Stud
screw fix plasterboard to stud and flat strap at 150mm centres
screw fix plasterboard to stud at max. 300mm vertical centres and to each stud horizontally GTEC U Track minimum 300mm at each end of curve 15 0m m Two C studs separated by 150mm at start of straight section GTEC Flex Track Deep Flange
ISOMETRIC
GTEC® C STUD PARTITION
CURVED PARTITIONS continued PT-CS-902M-Flex track component
Boards to be installed horizontally. Fix boards to continuous band of GTEC Flat Strap FS90/Rx behind all horizontal joints. Consult Technical Enquiryline for further guidance on curved partition specification.
GTEC Flex Track Deep Flange pre-cut at 50mm centres to allow curves of minimum radius of 600mm
ISOMETRIC PT-CS-903P-Curved partition plan
GTEC C Stud GTEC Flex Track Deep Flange
GTEC Contour Board or other GTEC Board as required
PLAN
MAXIMUM STUD CENTRES (mm) Radius (m)
6mm GTEC Contour Board
9.5mm GTEC Board
12.5mm GTEC Board
15mm GTEC Board
0.6 – 0.9
150 Wet
–
–
–
0.9 – 1.0
200 Dry
150 Wet
–
–
1.0 – 1.5
200 Dry
200 Wet
150 Wet
–
1.5 – 2.0
200 Dry
250 Wet
200 Wet
–
2.0 – 3.0
200 Dry
300 Wet
200 Wet
150 Wet
3.0 – 4.0
300 Dry
450 Wet
400 Wet
200 Wet
4.0 – 8.0
300 Dry
450 Wet
500 Wet
400 Wet
8.0 – 12.0
300 Dry
600 Dry
600 Dry
600 Wet
12.0 –
300 Dry
600 Dry
600 Dry
600 Dry
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
71
72
GTEC® ACOUSTIC STUD PARTITION
®
GTEC ACOUSTIC STUD PARTITION SYSTEMS The GTEC Acoustic Stud is an alternative to 70mm, 90mm and 146mm GTEC C Studs, where higher levels of acoustic performance are needed from a partition. With a unique profile design, the engineered slots create a spring section, resulting in less acoustic energy being transmitted through the stud and sound is absorbed within the partition. Compatibility with the GTEC C Stud system and all GTEC Boards allows a range of partition performances within identical footprints. For individual system performances, refer to the System Performance Tables on pages 22 to 44.
WHERE TO USE: GTEC Acoustic Stud is an internal partition system for commercial and domestic applications requiring high acoustic performance levels.
Benefits from all key features as detailed for GTEC C Stud, plus:
FEATURES
BENEFITS
Compatible with GTEC U Tracks
Only requires one change in component in a specification and on site Partition types can be mixed on site
Unique spring section design
Can eliminate insulation or board layers to achieve acoustic performance
GTEC® ACOUSTIC STUD PARTITION
TIP: GTEC Acoustic Stud can improve the overall Rw dB performance of a partition by up to 3 dB.
Insulation to suit required performance
GTEC U Track Deep Flange
GTEC Acoustic Studs at 600mm centres
GTEC Board to suit required performance
screw fix plasterboard to stud at 300mm centres
GTEC Intumescent Acoustic Sealant
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
73
74
GTEC速 ACOUSTIC STUD PARTITION
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance table, p22-44
GTEC Acoustic Stud Metal profile for vertical frame elements with improved acoustic performance
AS70/RX, AS90/RX, AS146/RX
GTEC C Stud Metal profile for vertical frame elements at corners, door openings, abutments
CS50/RX, CS60/RX, CS70/RX, CS90/RX, CS146/RX, CS70/B, CS90/B, CS146/B, CS90/W, CS70/Y, CS90/Y, CS146/Y
GTEC U Track Metal profile for head and base frame elements
UT52/RX, UT62/RX, UT72/RX, UT92/RX, UT148/RX
GTEC U Track Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UDT62/B, UDT72/B, UDT92/B, UDT148/B, UT52/Y
GTEC U Track Extra Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UXT72/B, UXT92/W, UXT148/W
GTEC Fixing Channel Provide support for plasterboard joints and fixtures
MFIX/W
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Screws (as appropriate) For connecting plasterboard and metal components
See fixing selector, p334-335
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® ACOUSTIC STUD PARTITION
SYSTEM GUIDANCE See guidance in GTEC C Stud section and additional considerations given below: FRAME PT-AS-101M-Stud splice
600mm overlap for height ≤ 4m
1000mm overlap for height > 4m
screw fix at 150mm centres both sides
ISOMETRIC
Select compatible size (e.g. 50mm stud and 52mm track) GTEC Acoustic Stud, GTEC C Stud and GTEC U Track framing elements to suit system performance.
Intermediate studs to be GTEC Acoustic Studs, facing in same direction, to be friction fitted to allow for adjustment during boarding.
Studs abutting structure (starter studs) to be GTEC C Stud, fixed with web flat to structure using appropriate fixings at maximum 600mm centres and fixed to head and track with appropriate GTEC Drywall Screws (see screw selector, p334-335).
GTEC Studs to be at centres required to achieve performance and at a maximum of 600mm centres
All GTEC C and Acoustic Studs to be 5mm shorter than floor to ceiling height.
Where wall height exceeds available GTEC Stud length splice two lengths together ensuring overlap of 600mm for heights below 4m and 1000mm for heights above 4m.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
75
76
GTEC® ACOUSTIC STUD PARTITION
BOARDING PT-AS-201M- Horizontal joint reinforcement, single layer
PT-AS-202M-Horizontal joint reinforcement, double layer
fixing strap to reinforce horizontal edge of boards where partition > board height
fixing strap to reinforce horizontal edge of boards where partition > board height
screw fix to fixing strap at max. 300mm centres
screw fix to fixing strap at max. 300mm centres
GTEC Flat Strap FS50/RX screw fix strap to stud through board
GTEC Flat Strap FS90/W screw fix strap to stud
ISOMETRIC PT-AS-203M-Board fixing – single layer
ISOMETRIC PT-AS-204M-Board fixing – double layer
screw fix plasterboard at maximum 300mm centres
screw fix plasterboard at maximum 300mm centres
joints on alternating studs
joints on alternating studs
ISOMETRIC
GTEC Acoustic Stud partition system is suitable for single, double and multiple layer boarding.
ISOMETRIC
GTEC® ACOUSTIC STUD PARTITION
OPENINGS PT-AS-401P- Door frames – 25 to 100kg GTEC Intumescent Acoustic Sealant
Timber stud
Up to 25kg Door
GTEC C Stud 150mm
GTEC Intumescent Acoustic Sealant
Timber stud
Up to 50kg Door
GTEC C Stud boxed 150mm GTEC Intumescent Acoustic Sealant
Timber stud
Up to 75kg Door
GTEC C Stud boxed 150mm
GTEC Intumescent Acoustic Sealant
Timber stud
Up to 100kg Door
Note: Insulation not shown for clarity
GTEC C Stud boxed 150mm
PLAN
Form openings following guidance in Construction Detail Drawings to suit door weights.
GTEC C Studs to be used as jambs at openings to provide flat web for fixing.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
77
78
GTEC® ACOUSTIC STUD PARTITION
CORNERS AND JUNCTIONS PT-AS-501P- Acoustic T-junction, double layer
PT-AS-502P-Corner – double layer
GTEC Intumescent Acoustic Sealant
GTEC Intumescent Acoustic Sealant
GTEC C Stud screw fix plasterboard to stud
GTEC C Stud
screw fix plasterboard to stud
GTEC Board to suit required performance
GTEC Board to suit required performance
Insulation quilt to suit required performance
Insulation quilt to suit required performance
PLAN
GTEC C Studs to be used at corners and junctions to provide flat web for fixing.
CURVED PARTITIONS GTEC Acoustic Studs are not suitable for use in curved partitions.
PLAN
See Construction Details Drawings for further guidance on arrangement and fixing.
79
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
80
GTEC® ACOUSTIC HOMESPAN PARTITION
®
GTEC ACOUSTIC HOMESPAN PARTITION SYSTEMS The GTEC Acoustic Homespan system is a lightweight partition specifically designed to meet Building Regulation Part E where 40RwdB is required for internal partitions in dwellings. This performance is achieved using 44mm and 50mm GTEC Acoustic Homespan Studs and Tracks and GTEC Acoustic Homespan Board without the need to install insulation to achieve a 40RwdB rating. The narrow stud width and specially configured boards simplify specification and use the least material to achieve the demands of Part E.
WHERE TO USE: GTEC Acoustic Homespan is an internal partition for new-build domestic applications.
Benefits from all key features as detailed for GTEC C Stud, plus:
FEATURES
BENEFITS
Achieves acoustic performance using narrow width studs
Maintains a low system footprint to minimise the effect on the room size
Achieves acoustic performance without the need for insulation
Quicker to install than other systems which use insulation to achieve the same performance
GTEC® ACOUSTIC HOMESPAN PARTITION
TIP: With all acoustic partitions it is critical to seal any air paths to achieve the best sound ratings.
Insulation to suit required performance
GTEC U Track Deep Flange
GTEC Acoustic Studs at 600mm centres
GTEC Board to suit required performance
screw fix plasterboard to stud at 300mm centres
GTEC Intumescent Acoustic Sealant
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
81
82
GTEC速 ACOUSTIC HOMESPAN PARTITION
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
GTEC Acoustic Homespan Board 900mm board to provide wall surface suitable for finishing
See performance table, p43
GTEC Acoustic Homespan MR Board Moisture resistant 900mm board
See performance table
GTEC Acoustic Homespan Stud Metal profile for vertical frame elements with improved acoustic performance
AHS44/RX, AHS50/RX
GTEC Acoustic Homespan Starter Stud Metal profile for vertical frame elements at corners, door openings, abutments
CS44/RX, CS50/RX
GTEC U Track Metal profile for head and base frame elements
UT45/RX, UT52/RX
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334-335
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® ACOUSTIC HOMESPAN PARTITION
SYSTEM GUIDANCE See guidance in GTEC C Stud section and additional considerations given below: FRAME Select compatible size (e.g. 44mm stud and 45mm track) GTEC Acoustic Homespan Stud, GTEC Acoustic Homespan Starter Stud and GTEC U Track framing elements to suit system performance. GTEC Acoustic Homespan is not suitable for heights above 2.8m and so does not require deeper flange tracks.
Intermediate GTEC Acoustic Homespan Studs, facing in same direction, to be friction fitted to allow for adjustment during boarding. All GTEC Studs to be 5mm shorter than floor to ceiling height. GTEC Acoustic Homespan Studs to be at a maximum of 450mm centres.
Studs abutting structure to be GTEC Acoustic Homespan Starter Studs fixed with web flat to structure using appropriate fixings at maximum 600mm centres and fixed to head and track with appropriate GTEC Drywall Screws (see screw selector, p334-335).
INSULATION Insulation is not required to achieve 40 RwdB performance with the GTEC Acoustic Homespan system but may be fitted to increase performance, see performance tables p43.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
83
84
GTEC® ACOUSTIC HOMESPAN PARTITION
BOARDING PT-AH-201M-Horizontal joint reinforcement, single layer
PT-AH-202M-Horizontal joint reinforcement, double layer
fixing strap to reinforce horizontal edge of boards where partition > board height
fixing strap to reinforce horizontal edge of boards where partition > board height
screw fix to fixing strap at max. 300mm centres
screw fix to fixing strap at max. 300mm centres
GTEC Flat Strap FS90/W screw fixed to studs
GTEC Flat Strap FS50/RX screw fix strap to stud through board
ISOMETRIC PT-AH-203M-Board fixing – single layer
ISOMETRIC PT-AH-204M- Board fixing – double layer
screw fix plasterboard at maximum 300mm centres All joints in outer layer taped and jointed
joints on alternating studs
Joints on opposite faces offset and staggered between layers
ISOMETRIC
GTEC Acoustic Homespan partition system is suitable for single boarding using GTEC Acoustic Homespan Board only.
ISOMETRIC
GTEC® ACOUSTIC HOMESPAN PARTITION
OPENINGS PT-AH-401P-Door frames – 25kg to 50kg door loads
GTEC Intumescent Acoustic Sealant Timber stud minimum 32mm wide
Up to 25kg Door
GTEC C Stud 44-50mm wide 150mm
GTEC Intumescent Acoustic Sealant Timber stud minimum 32mm wide
Up to 50kg Door
150mm
GTEC C Stud boxed 44-50mm wide
Note: Insulation not shown for clarity
PLAN
Form openings following guidance in Construction Detail Drawings to suit door weights.
GTEC Acoustic Homespan Starter Studs to be used as jambs at openings to provide flat web for fixing.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
85
86
GTEC® ACOUSTIC HOMESPAN PARTITION
CORNERS AND JUNCTIONS PT-AH-501P-Acoustic T-junction, single layer
PT-AH-502P-Corner – single layer
GTEC Intumescent Acoustic Sealant
GTEC Acoustic Homespan Starter Stud
GTEC Acoustic Homespan Stud GTEC Intumescent Acoustic Sealant screw fix plasterboard to stud screw fix plasterboard to stud
GTEC Acoustic Homespan Starter Stud GTEC Acoustic Homespan Board GTEC Board to suit required performance GTEC Acoustic Homespan Studs
PLAN
GTEC Acoustic Homespan Starter Studs to be used at corners and junctions to provide flat web for fixing.
HEAD DEFLECTION GTEC Acoustic Homespan systems are not suitable for specification with deflection heads.
PLAN
See Construction Details Drawings for further guidance on arrangement and fixing.
CURVED PARTITIONS GTEC Acoustic Homespan Studs are not suitable for use in curved partitions.
87
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
88
GTEC® RESILIENT BAR PARTITION
®
GTEC RESILIENT BAR PARTITION SYSTEMS GTEC Resilient Bar is a versatile component that can be used with a variety of partitions to provide improved acoustic performance. GTEC Resilient Bar decouples the plasterboard from the metal frame to reduce sound transmission with little increase in thickness. It is fixed across the flanges of GTEC C Stud and GTEC Board to provide a substrate for the plasterboard away from the metal framing. Refer to the System Performance Tables on pages 22 to 44 for full details. See the GTEC Timber Partitions section for details on using the GTEC Resilient Bar with timber construction.
WHERE TO USE: GTEC Resilient Bar is used with the GTEC C Stud Partition system in both domestic and commercial applications.
FEATURES
BENEFITS
Easy to fit and install
Reduced installation time compared with more complex systems
Low profile component design
Increases acoustics with minimal effect on room size
Decouples board and frame
Gives increase in acoustic performance
GTEC® RESILIENT BAR PARTITION
TIP: When fixing GTEC Board to GTEC Resilient Bar it is vital to fix to the bar only or risk reducing acoustic performance.
GTEC Resilient Bar provides fixing at 50mm maximum from soffit
GTEC Resilient Bar spaced at 600mm vertical centres and screw fixed to GTEC C Studs
GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
screw fix board to resilient bar at 300mm centres
GTEC Socket Pad GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar at bottom to provide fixing at 50mm maximum from floor
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
89
90
GTEC速 RESILIENT BAR PARTITION
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p22-44
GTEC Resilient Bar Metal profile to provides acoustic separation of board and frame
RBD3000
GTEC C Stud Metal profile for vertical frame elements
CS50/RX, CS60/RX, CS70/RX, CS90/RX, CS146/RX, CS70/B, CS90/B, CS146/W, CS90/W, CS70/Y, CS146/Y
GTEC U Track Metal profile for head and base frame elements
UT52/RX, UT62/RX, UT72/RX, UT92/RX, UT148/RX
GTEC U Track Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UDT62/B, UDT72/B, UDT92/B, UDT148/B, UT52/Y
GTEC U Track Extra Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UXT72/B, UXT92/W, UXT148/W
GTEC Fixing Channel Provide support for plasterboard joints and fixtures
MFIX/W
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334-335
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® RESILIENT BAR PARTITION
SYSTEM GUIDANCE See guidance in GTEC C Stud section and additional considerations given below: FRAME PT-RB-101S-Head – no deflection
PT-RB-102S-Base junction v1
screw fix plasterboard to track
GTEC Intumescent Acoustic Sealant screw fix plasterboard to Resilient Bar
GTEC U Track Deep Flange fixed at 600mm centres
GTEC Resilient Bar inverted at top of stud
GTEC Insulation Hold
GTEC Board fixed to resilient bar only
GTEC C Stud
GTEC Board to suit required performance
GTEC C Stud
GTEC Resilient Bar max. 50mm from base
screw fix plasterboard to Resilient Bar only GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar screw fixed to stud at 600mm centres
screw fix plasterboard to track
GTEC U Track Deep Flange fixed at 600mm centres
SECTION
GTEC Resilient Bar to be installed on one side of partition, across studs at 600mm vertical centres and fixed to each stud with suitable GTEC Drywall Screws (see screw selector, p334-335).
SECTION
Uppermost GTEC Resilient Bar to be installed in inverted position at maximum of 50mm from top of partition. Lowest GTEC Resilient Bar to be installed at maximum of 50mm from base of partition.
BOARDING PT-RB-201M-Board fixing – double layer
GTEC Resilient Bar partition system is suitable for single and double layer boarding.
screw fix board to resilient bar only at max. 300mm centres
Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Tables (p22-44) and Product Specification (p294307) to achieve required performance. See High Performance Boards guide (p12-15) for further selection information.
stagger joints
Boards to be fixed to GTEC Resilient Bar only at 300mm centres using shortest appropriate GTEC Drywall Screws (see screw selector, p334-335). Screws must not penetrate through to substrate. Base and final layers of boarding to be fixed at 300mm centres. ISOMETRIC ISOMETRIC
Boards must not be fixed to studs or tracks to ensure acoustic performance.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
91
92
GTEC® RESILIENT BAR PARTITION
OPENINGS PT-RB-401P-Door frame – 25-100 kg GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar Up to 25kg Door
Timber stud minimum 32mm wide
GTEC C Stud 50-146mm wide 150mm GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar Timber stud minimum 32mm wide
Up to 50kg Door
GTEC C Stud boxed 50-146mm wide 150mm GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar Timber stud minimum 32mm wide
Up to 75kg Door
GTEC C Stud boxed 70-146mm wide 150mm GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar Timber stud minimum 32mm wide
Up to 100kg Door
GTEC C Stud boxed 70-146mm wide Note: Insulation not shown for clarity
150mm
PLAN PT-RB-402M-Horizontal joint reinforcement
Form openings following guidance in Construction Detail Drawings to suit door weights.
FS50/RX flat strap to support horizontal edge of boards
screw fix board to resilient bar only at max. 300mm centres
ISOMETRIC
GTEC® RESILIENT BAR PARTITION
CORNERS AND JUNCTIONS PT-RB-501P-Junction with masonry wall
PT-RB-502P-Corner detail (External Resbar)
GTEC Direct Bond lining system GTEC Resilent Bar to external side of corner GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar screw fix plasterboard to resilient bar
GTEC Resilient Tape or plasterboard packer
GTEC Board to suit required performance
GTEC Board to suit required performance
GTEC Dryliner lining system
PLAN PT-RB-503P-Corner detail (Internal Resbar)
PLAN PT-RB-504P-Acoustic T-junction, double layer
GTEC Resilent Bar to internal side of corner
GTEC Intumescent Acoustic Sealant
screw fix plasterboard to resilient bar GTEC Resilient Bar ensure 10mm min. gap GTEC Board to suit required performance
GTEC Board to suit required performance
PLAN
PLAN PLAN
See Construction Details Drawings for further guidance on arrangement and fixing.
CURVED PARTITIONS GTEC Resilient Bar is not suitable for curved partitions.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
93
94
GTEC® TWIN FRAME PARTITION
®
GTEC TWIN FRAME PARTITION SYSTEMS Separating walls and divisions between noisy or noise sensitive rooms requires very high levels of sound insulation. The GTEC Twin Frame metal system is a dual layer C Stud Partition used where the highest fire and acoustic performance is required. GTEC Twin Frame Partitions are constructed from two metal frames in parallel, braced together with GTEC Acoustic V Brace and boarded on the external sides only. Varying cavity size options help optimise acoustic insulation and provide a service cavity. The GTEC Twin Frame system is a lightweight, flexible option compared to traditional masonry separating walls. Refer to the System Performance Tables on pages 22 to 45 for full performance details.
WHERE TO USE: GTEC Twin Frame systems are suitable for creating internal dividing walls in both domestic and commercial applications with increased performance and / or height requirements. The highest performing GTEC Twin Frame partitions are commonly used in cinemas, theatres and schools.
Benefits from all key features as detailed for GTEC C Stud, plus:
FEATURES
BENEFITS
Cavity space between the two frames
Provides high levels of acoustic, thermal and fire performance
Varying cavity size
Optimisable for obstacles in the path of the partition Higher partition heights
Increased height capabilities
Enables use in large commercial spaces
GTEC速 TWIN FRAME PARTITION
TIP: GTEC Twin Frame Partitions have been built in cinemas across the UK as they are ideal for tall, highly sound insulated partitions. GTEC Intumescent Acoustic Sealant at all perimeters of run Twin GTEC C Studs
Twin GTEC U Tracks to suit height and deflection
mineral wool insulation to suit required performance
GTEC Insulation Hold
GTEC Acoustic V Brace to connect studs at 1500mm vertical centres
GTEC Board to suit required performance
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
95
96
GTEC® TWIN FRAME PARTITION
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance table, p22-45
GTEC C Stud Metal profile for vertical frame elements
CS50/RX, CS60/RX, CS70/RX, CS90/RX, CS146/RX, CS70/B, CS90/B, CS146/B, CS90/W, CS70/Y, CS90/Y, CS146/Y
GTEC I Stud Alternative metal profile for vertical frame elements
IS50/RX, IS60/B, IS60/B, IS70/B, IS90/B
GTEC U Track Metal profile for head and base frame elements
UT52/RX, UT62/RX, UT72/RX, UT92/RX, UT148/RX
GTEC U Track Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UDT62/B, UDT72/B, UDT92/B, UDT148/B, UT52/Y
GTEC U Track Extra Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UXT72/B, UXT92/W, UXT148/W
GTEC Acoustic V Brace Acoustic frame bracing
VBRACE
GTEC Acoustic V Brace 90 Acoustic frame bracing for connecting at 90°
VBRACE90
GTEC Resilient Tape Provides acoustic isolation between components
RAFT50
GTEC Fixing Channel Provide support for plasterboard joints and fixtures
MFIX/W
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
GTEC Flex Track Deep Flange Steel track for curved partitions
DFLEX/B
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
BOARDS
FRAME
INSULATION
GTEC® TWIN FRAME PARTITION
System Component
System primary use
Product Reference
GTEC Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334-335
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
FIX
FINISHING
SYSTEM GUIDANCE FRAME PT-CT-101S-Head – no deflection
PT-CT-102S-Base GTEC U Track Deep Flange fixed at 600mm centres GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
screw fix plasterboard to track GTEC C Stud
GTEC Board to suit required performance 5mm shorter than floor to ceiling height
GTEC C Stud 5mm shorter than floor to ceiling height
SECTION
GTEC U Track Deep Flange fixed at 600mm centres screw fix plasterboard to track GTEC Intumescent Acoustic Sealant
SECTION
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
97
98
GTEC® TWIN FRAME PARTITION
FRAME continued PT-CT-103S-Base with timber sole plate and screed
Insulation quilt to suit required performance
GTEC U Track on timber sole plate
floating screed
GTEC Board to suit required performance
GTEC C Stud
GTEC Intumescent Acoustic Sealant
timber sole plate same depth as screed Resilient layer
SECTION
Select compatible size (e.g. 50mm stud and 52mm track) GTEC C Stud and GTEC U Track framing elements to suit system performance.
Timber sole plate may be required on uneven floors or where partition is constructed prior to screeding.
GTEC U Track Deep or Extra Deep Flange to be used for heights greater than 4.2m and where deflection allowance is required (see p105).
Protect base track from moisture with damp proof membrane when situated on newly laid concrete floors.
GTEC Twin Frame partition to be constructed using two parallel track and stud frames braced together with GTEC Acoustic V Brace at 1500mm vertical centres, mechanically fixed to both studs with four appropriate GTEC Drywall screws (see screw selector, p334-335). Separate parallel frames as required by system performance. Where frame separation is wider than GTEC Acoustic V Brace extend with additional length of GTEC Primary Channel or Dryliner Channel. Studs abutting structure (starter studs) to be fixed with web flat to structure using appropriate fixings at maximum 600mm centres and fixed to head and track with appropriate GTEC Drywall Screws (see screw selector, p334-335). GTEC U Track to be fixed flat to structure using appropriate fixings at maximum 600mm centres.
All GTEC C Studs to be 5mm shorter than floor to ceiling height except in case of deflection requirement (see p105). Intermediate GTEC C Studs, facing in same direction, to be friction fitted to allow for adjustment during boarding. GTEC C Studs to be at centres required to achieve performance and at a maximum of 600mm centres. Where wall height exceeds available GTEC Stud length splice two lengths together ensuring overlap of 600mm for heights below 4m and 1000mm for heights above 4m. Acoustic break in slab for party walls may be required.
GTEC® TWIN FRAME PARTITION
PT-CT-104M-Stud splice
PT-CT-105M-V-brace fixing and extensions
screw fix at 150mm centres both sides
1200mm min. between stagger joints
cut GTEC Dryliner Channel or Primary Channel to suit width of cavity
600mm overlap for height ≤ 4m
1000mm overlap for height > 4m
fix with GTEC Wafer / Pan Head Self Drilling Screws
ISOMETRIC
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
99
100
GTEC® TWIN FRAME PARTITION
INSULATION PT-CT-151M-Insulation Hold
Insulation, if required, to be of type and thickness to achieve performance and installed in a continuous layer between studs.
All joints in outer layer taped and jointed Joints on opposite faces offset and staggered between layers
Where insulation may be expected to slump suspend from GTEC Insulation Hold strips fixed across studs, 150mm from top of partition and at 1200mm vertical centres.
ISOMETRIC
BOARDING PT-CT-201M-Board fixing – double layer
PT-CT-202M-Horizontal joint reinforcement
fixing strap to reinforce horizontal edge of boards where partition > board height
screw fix to fixing strap at max. 300mm centres
GTEC Flat Strap FS50/RX screw fixed to stud through board
ISOMETRIC
GTEC Twin Frame partition system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Tables (p22-45) and Product Specification (p294307) to achieve required performance. See High Performance Boards guide (p12-15) for further selection information. Boards to be 5mm less than floor to ceiling height except in case of deflection requirement, see below. Strips of board 300mm wide or less to be avoided by stud location rearrangement.
ISOMETRIC
Boards to be mechanically fixed to studs at 300mm centres using appropriate GTEC Drywall Screws (see screw selector and guidance, p334-335). Base layers of boarding may be temporarily fixed at 600mm centres providing final layer is fixed through to stud at 300mm centres. Board edges to be centred over studs. Stagger all board joints between layers. Stagger all board joints on opposing sides of partition.
GTEC® TWIN FRAME PARTITION
Over-height single layer boarding: Where partition height exceeds board height fix boards to continuous band of GTEC Flat Strap FS90/W or GTEC MFIX behind all horizontal joints to maintain fire integrity. Over-height multiple layer boarding: Where partition height exceeds board height for double or multiple layer boarding fix outer layer of boards to continuous band of GTEC Flat Strap FS50/RX behind all horizontal joints.
MOVEMENT CONTROL JOINTS PT-CT-301P-Movement control joint – double boarded
10mm
GTEC Movement Control Joint
GTEC Fire Board 2x 15mm cut to exact width of cavity fixed to back of studs GTEC C Studs to suit required performance Rock mineral wool to fill void GTEC Intumescent Acoustic Sealant
10mm
GTEC Board to suit required performance
PLAN
Form movement control joints at maximum 10m intervals in the partition run. Form movement control joints where the partition crosses a structural movement joint.
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
101
GTEC® TWIN FRAME PARTITION
OPENINGS PT-CT-401P-Door frames – 25kg to 100kg door loads
GTEC C Stud boxed 50-146mm wide
Timber stud minimum 32mm wide 25- 50kg
GTEC LaDura Board or plywood 150mm
GTEC C Stud boxed 70-146mm wide
Timber stud minimum 32mm wide Up to 75kg
GTEC LaDura Board or plywood 150mm
GTEC C Stud boxed 70-146mm wide
Timber stud minimum 32mm wide Up to 100kg
GTEC LaDura Board or plywood 150mm
PLAN PT-CT-403E-Single and double door frames
GTEC C Stud GTEC UXT Track 400mm
102
Section A-A
A
optional head stud for door fixing A
Min. 150mm
Max. 2m
Reinforcement as shown in door frame plan to full height of partition Single Door
Max. 150mm
Double Door
Max. 150mm
ELEVATION
GTEC® TWIN FRAME PARTITION
Form openings following guidance in Construction Detail Drawings to suit door weights. Reinforce head-to-jamb junction 150mm down each jamb stud by cutting and folding head track. Reinforce jamb studs with timber and boxed studs as described in Construction Detail Drawings. Jamb studs to be fixed to track with appropriate GTEC Drywall Screws (see screw selector, p334-335).
CORNERS AND JUNCTIONS PT-CT-501P-Corner detail, double layer
PT-CT-502P-Acoustic T-junctions, double layer GTEC Board to suit required performance
GTEC Board to suit required performance
screw fix plasterboard to stud GTEC Acoustic V Brace
additional stud if required
Insulation to suit required performance
GTEC Intumescent Acoustic Sealant GTEC Acoustic V Brace
additional studs if required
screw fix plasterboard to stud
Insulation to suit required performance
Head packer configuration Head packer configuration
PLAN
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
103
104
GTEC® TWIN FRAME PARTITION
CORNERS AND JUNCTIONS continued PT-CT-503P-Splayed corners
PT-CT-504P-Four way junction GTEC External Corner Tape GTEC Board to suit required performance
Timber fillet
GTEC C Stud
GTEC Intumescent Acoustic Sealant
GTEC Intumescent Acoustic Sealant screw fix plasterboard to stud
screw fix plasterboard to stud
Insulation to suit required performance
GTEC Board to suit required performance
GTEC Acoustic V Brace
PLAN PT-CT-505P-Junction with Masonry – Plastered
PLAN PT-CT-506P-Junction with Masonry – Dryliner & Direct Bond
GTEC Intumescent Acoustic Sealant
GTEC Direct Bond lining system
screw fix plasterboard to stud
GTEC Resilient Tape or plasterboard packer
GTEC Resilient Tape or plasterboard packer
skim plastered
GTEC Dryliner lining system PLAN PLAN
PLAN PLAN
PT-CT-507P-Junction with external SFS wall, acoustic rated External Insulation and Finishing System (EIFS)
GTEC Board to suit required performance GTEC C Stud
SFS light steel framing system
GTEC Intumescent Acoustic Sealant GTEC Acoustic V Brace additional insulation
PLAN
Abutting partitions to coincide with studs, install additional intermediate ‘pick-up’ stud if required. Connect studs through plasterboards at corners and junctions at 600mm vertical centres using appropriate GTEC Drywall Screws. See Construction Details Drawings for further guidance on arrangement and fixing.
GTEC® TWIN FRAME PARTITION
HEAD DEFLECTION PT-CT-601S-Deflection head, general arrangement
GTEC INTUMESCENT ACOUSTIC SEALANT
MINERAL WOOL & CLOAKING ANGLE packers cut precisely to track width
GTEC Intumescent Acoustic Sealant
=
rock mineral wool
Cloaking angle
boards short of soffit by deflection amount
=
5mm Minimum 5mm overlap of boards and packers 15mm
=
Stud cut short of track by deflection amount
Minimum 15mm overlap of stud and track
allow deflection spacing as minimum between track and fixing
screw fix flat strap between outer board layer and substrate
Note : Refer to the deflection table below
SECTION
Deflection required:
Packer for all fire ratings:
Track for all fire ratings:
30 & 60 mins
90 & 120 mins
0-5mm
12.5mm GTEC Fire Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
6-10mm
15mm GTEC Fire Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
11-20mm
2x 12.5mm GTEC Fire Board or 25mm GTEC Fire Core Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
21-25mm
2x 15mm GTEC Fire Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
26-32mm
3x 12.5mm GTEC Fire Board
GTEC Deep Flange U Track (UDT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
33-40mm
3x 15mm GTEC Fire Board
GTEC Extra Deep Flange U Track (UXT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
41-45mm
2x 25mm GTEC Fire Core Board or 4x 12.5mm GTEC Fire Board
GTEC Extra Deep Flange U Track (UXT)
GTEC Intumescent Acoustic Sealant
Mineral wool & cloaking angle
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
105
106
GTEC® TWIN FRAME PARTITION
HEAD DEFLECTION continued See Construction Detail Drawings and Tables for full details. Contact Siniat Technical Enquiryline for further information.
GTEC Studs to be cut short of track by deflection amount.
Continuity of head packer to be maintained.
GTEC Studs and Tracks to overlap by minimum 30mm.
No mechanical connection to be made between stud and head track.
GTEC Boards to be cut short of partition height by deflection amount.
All air paths to be sealed with GTEC Intumescent Acoustic Sealant.
GTEC Boards to overlap packer by minimum of 5mm.
PENETRATIONS PT-CT-701P-Small diameter pipe penetration
PT-CT-702E-Cable tray penetration
GTEC Intumescent Acoustic Sealant GTEC Fire Board
GTEC Intumescent Acoustic Sealant
GTEC U Track cut and bent
pipe or conduit less than 50mm in diameter
PLAN
ELEVATION
ELEVATION
PT-CT-703M-Socket pad
M&E runs and other penetrating services to be pre-planned to minimise or eliminate penetrations through rated partitions.
GTEC Socket Pad pre-cut socket pad folded and pushed into socket box
Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings. Protect all electrical cables in cavity with conduit.
ISOMETRIC ISOMETRIC
GTEC® TWIN FRAME PARTITION
PT-CT-704P-Multiple pipe penetrations
GTEC Fire Board pattress
GTEC Board to suit required performance
GTEC Intumescent Acoustic Sealant
ELEVATION 150mm
void filled with dense mineral wool
100mm minimum overlap
PLAN
FIXTURES Consult fixture details in GTEC C Stud Section (p67-69) for recommended fixture provision.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances.
GTEC Finish materials appropriate to board type to be used.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
107
108
GTEC® TWIN FRAME PARTITION
SYSTEM CONTINUITY Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings.
Full, imperforate system continuity to be maintained to achieve rated performances.
GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
CURVED PARTITIONS PT-CT-901M-Curved partition
See table for stud spacing to achieve curve radius
GTEC Flat Strap to reinforce horizontal joints GTEC Contour Board or other to suit required performance
GTEC C Stud
screw fix plasterboard to stud and flat strap at 150mm centres
screw fix plasterboard to stud at max. 300mm vertical centres and to each stud horizontally GTEC U Track minimum 300mm at each end of curve
15 0m m Two C studs separated by 150mm at start of straight section
GTEC Flex Track Deep Flange to create curve
ISOMETRIC
GTEC® TWIN FRAME PARTITION
PT-CT-902M-Flex track component
Boards to be installed horizontally. Fix boards to continuous band of GTEC Flat Strap FS90/Rx behind all horizontal joints. Consult Technical Enquiryline for further guidance on curved partition specification.
GTEC Flex Track Deep Flange pre-cut at 50mm centres to allow curves of minimum radius of 600mm
ISOMETRIC PT-CT-903P-Twin frame curved partition plan
GTEC Flex Track Deep Flange
GTEC C Stud
GTEC Contour Board or other board to suit
GTEC Acoustic V Brace
PLAN
MAXIMUM STUD CENTRES (mm) Radius (m)
6mm GTEC Contour Board
9.5mm GTEC Board
12.5mm GTEC Board
15mm GTEC Board
0.6 – 0.9
150 Wet
–
–
–
0.9 – 1.0
200 Dry
150 Wet
–
–
1.0 – 1.5
200 Dry
200 Wet
150 Wet
–
1.5 – 2.0
200 Dry
250 Wet
200 Wet
–
2.0 – 3.0
200 Dry
300 Wet
200 Wet
150 Wet
3.0 – 4.0
300 Dry
450 Wet
400 Wet
200 Wet
4.0 – 8.0
300 Dry
450 Wet
500 Wet
400 Wet
8.0 – 12.0
300 Dry
600 Dry
600 Dry
600 Wet
12.0 –
300 Dry
600 Dry
600 Dry
600 Dry
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
109
110
GTEC® TIMBER PARTITION
®
GTEC TIMBER PARTITION SYSTEMS In timber frame construction or where traditional methods dominate, a timber partition may be the preferred construction method. GTEC Timber Partitions use timber studs and plates in place of metal framing with GTEC Board screw fixed to complete the partition. Refer to the System Performance Tables on pages 47 to 49 for full details. Separating walls can also be constructed with double layers of GTEC Board and twin timber frames built in parallel to create a separating cavity. Insulation is applied in between for further sound reduction.
WHERE TO USE: GTEC Timber Partitions are used to create internal and separating partitions within domestic applications.
FEATURES
BENEFITS
Strong
Less material required than masonry construction
GTEC Resilient Bar option
Provides improved acoustic performance
Compatible with full range of GTEC boards
Achieves excellent partition performance
Flat finish
Provides an easy surface for decoration
Cavity space between two frames
High levels of acoustic and fire performance
GTECÂŽ TIMBER PARTITION
TIP: GTEC LaDura has been tested for racking resistance making it an excellent choice for timber frame construction.
GTEC Board to suit required performance Timber studs at max. 600mm centres Mineral wool insulation ďŹ tted between timber studs
Single timber stud internal wall
Twin timber studs separating wall
GTEC Intumescent Acoustic Sealant
Timber sole plates
Timber head plates
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
111
112
GTEC速 TIMBER PARTITION
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p47-49
Timber Drywall partition framing
Supplied by others
GTEC Resilient Bar Metal profile to provides acoustic separation of board and frame
RBD3000
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
GTEC Flex Track Deep Flange Steel track for curved partitions
DFLEX/B
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC High Thread Screws (as appropriate) For attaching plasterboard to timber frame
See screw selector, p334-335
GTEC Corner and Edge beads Galvanised metal reinforcements for corner and edge protection
n/a
GTEC Joint Tape White perforated cross fibre tape for reinforcing joints in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® TIMBER PARTITION
SYSTEM GUIDANCE FRAME PT-TS-101S-Head Detail (Load Bearing)
PT-TS-102S-Head Detail (Non-Load Bearing)
Nogging GTEC Intumescent Acoustic Sealant
GTEC Intumescent Acoustic Sealant
screw fix plasterboard to timber
GTEC Board to suit required performance
Timber head track fixed through to full height timber in ceiling Mineral wool insulation as required fixed to board
Mineral wool insulation as required fixed to board GTEC Board to suit required performance
screw fix plasterboard to timber Timber head track fixed to full height timber in ceiling
GTEC Board to suit required performance
SECTION PT-TS-103S-Base Detail (Load Bearing)
PT-TS-104S-Base Detail (Non-Load Bearing)
GTEC Board to suit required performance Mineral wool insulation as required fixed to board
Timber base track fixed to full height timber in floor screw fix plasterboard to track
SECTION
GTEC Board to suit required performance Mineral wool insulation as required fixed to board
Timber base track fixed to full height timber in floor
GTEC Intumescent Acoustic Sealant
screw fix plasterboard to track GTEC Intumescent Acoustic Sealant
full height timber to coincide with partition to reduce sound and fire path
SECTION
SECTION
PT-TS-105P-End Detail
GTEC Board to suit required performance
screw fix strip of plasterboard to timber stud Timber Stud GTEC Corner 90º External / GTEC Flex Tape
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
113
114
GTEC® TIMBER PARTITION
FRAME continued PT-TT-101S-Head Detail
GTEC Resilien Bar Timber head plate
PT-TT-102S-Base Detail
screw fix plasterboard to timber
GTEC Board to suit required performance Mineral wool insulation to suit required performance
Timber packer
Mineral wool insulation to suit required performance
GTEC Board to suit required performance
Timber head plate screw fix plasterboard to timber
SECTION
Timber stud framing to be straight, plumb and true. Studs to be fixed to timber sole and head plates. All framing elements abutting structure to be fixed at maximum 600mm centres using appropriate fixings. Studs to have minimum board bearing width of 38mm. Studs to be arranged at maximum 400mm centres for 9.5mm board and maximum 600mm centres for 12.5 and 15mm board.
Timber packer GTEC Intumescent Acoustic Sealant
SECTION
GTEC Resilient Bar option only: GTEC Resilient Bar may be installed on one side of partition, across studs at 600mm vertical centres and fixed to each stud with suitable GTEC Drywall Screws (see screw selector, p334-335). Uppermost GTEC Resilient Bar to be installed in inverted position at maximum of 50mm from top of partition. Lowest GTEC Resilient Bar to be installed at maximum of 50mm from base of partition.
GTEC® TIMBER PARTITION
INSULATION PT-TS-151M-Insulation Hold
GTEC Insulation Hold to support each insulation batt GTEC Insulation Hold screw fixed to studs at maximum 1200mm vertical centres and within 600mm of top
ISOMETRIC
Insulation, if required, to be of type and thickness to achieve performance and installed in a continuous layer between frames or studs to suit required performance.
Where insulation may be expected to slump suspend from GTEC Insulation Hold strips fixed across studs, 150mm from top of partition and at 1200mm vertical centres.
BOARDING PT-TS-201M-Board fixing – single layer
PT-TS-202M-Overheight partition – single layer
opposing joints on alternating studs
screw fix plasterboard at maximum 300mm centres timber nogging or FS90/W flat strap to support horizontal edge of boards
screw fix to timber at max. 300mm centres
ISOMETRIC
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
115
116
GTEC® TIMBER PARTITION
BOARDING continued PT-TS-203M-Overheight partition – double layer
PT-TT-201M-Board fixing – double layer
screw fix to timber studs at max. 300mm centres Stagger joints between layers
FS50/RX flat strap to support horizontal edge of boards
Stagger on opposing sides
ISOMETRIC PT-TT-202M-Overheight partitions – double layer
ISOMETRIC PT-TT-203M-Overheight partitions – Single layer
screw fix to timber studs at max. 300mm centres
timber nogging or FS90/W flat strap to support horizontal edge of boards
screw fix board to timber studs at max. 300mm centres
FS50/RX flat strap to support horizontal edge of boards
ISOMETRIC
GTEC Timber Single Stud partition system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables (p47-49) and Product Specification (p294-307) to achieve required performance. See High Performance Boards guide (p12-15) for further selection information. Boards to be 5mm less than floor to ceiling height. Strips of board 300mm wide or less to be avoided by stud arrangement.
ISOMETRIC
Boards to be mechanically fixed to studs at 300mm centres using appropriate GTEC High-Thread Drywall Screws (see screw selector, p334-335). Base layers of boarding may be temporarily fixed at 600mm centres providing final layer is fixed through to stud at 300mm centres Board edges to be centred over studs. Stagger all board joints between layers. Stagger all board joints on opposing sides of partition.
GTEC® TIMBER PARTITION
Over-height single layer boarding:
GTEC Resilient Bar option only:
Where partition height exceeds board height fix boards to continuous band of GTEC Flat Strap FS90/W, GTEC MFIX, or timber nogging behind all horizontal joints to maintain fire integrity. Over-height multiple layer boarding: Where partition height exceeds board height for double or multiple layer boarding fix outer layer of boards to continuous band of GTEC Flat Strap FS50/RX behind all horizontal joints.
Boards to be mechanically fixed to GTEC Resilient Bar only at 300mm centres using shortest appropriate GTEC Drywall Screws (see screw selector, p334-335). Screws must not penetrate through to substrate. All layers of boarding to be fixed at 300mm centres. Boards must not be fixed to studs or tracks to ensure acoustic performance.
OPENINGS PT-TS-401P-Door jamb
PT-TT-401P-Door jamb
GTEC Intumescent Acoustic Sealant
GTEC Corner 90º External / GTEC Flex Tape
strips of board fixed to stud
Timber stud
GTEC Board to suit required performance
PLAN
GTEC Board to suit required performance
PLAN
Form door openings following guidance in Construction Detail Drawings to suit door weights.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
117
118
GTEC® TIMBER PARTITION
CORNERS AND JUNCTIONS PT-TS-501P-Corner Detail
PT-TS-502P-Acoustic T-junction
timber studs fixed together GTEC Intumescent Acoustic Sealant Timber Stud as required
screw fix plasterboard to stud GTEC Intumescent Acoustic Sealant
screw fix plasterboard to stud
GTEC Board to suit required performance
GTEC Board to suit required performance
PLAN PT-TS-503P-Junction of Twin and Single partition (LB)
PLAN PT-TS-504P-Non-rated T-junction
GTEC Intumescent Acoustic Sealant Timber Stud fixed through to twin frame studs continuos boarding
Timber Stud
Timber Studs to coincide
GTEC Intumescent Acoustic Sealant
screw fix plasterboard to stud
GTEC Board to suit required performance
PLAN
Abutting partitions to coincide with studs, install additional intermediate ‘pick-up’ stud if required. Additional studs to be installed where required to provide fixing substrate for boards. See Construction Details Drawings for further guidance on arrangement and fixing.
PLAN
GTEC® TIMBER PARTITION
HEAD DEFLECTION
SYSTEM CONTINUITY
Timber stud partitions are not generally compatible with deflection head requirements.
PENETRATIONS M&E runs and other penetrating services to be pre-planned to minimise or eliminate penetrations through rated partitions. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings.
Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission. Full, imperforate system continuity to be maintained to achieve rated performances.
Protect all electrical cables in cavity with conduit.
FIXTURES See guidance on p67-69 for further information.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
119
120
GTEC速 FLOORS AND CEILINGS
121 121
FLOORS AND CEILINGS GTEC Floor and Ceiling systems are used to achieve acoustic and fire rated solutions for both domestic and commercial building projects. A range of solutions are available; from direct soffit application to the creation of full supporting frames. They are suitable for varying building projects and can be built in large runs.
System Performance Tables GTEC Engineered Joist Systems
122
GTEC Ceiling Systems to Timber Floors
123
GTEC Dryliner Ceiling Systems to Concrete Soffit
127
GTEC Separating Floor Systems
128
GTEC Pregybel MF Ceiling Systems
131
GTEC Suspended MF Ceiling Systems to Timber Floors
133
GTEC Suspended MF Ceiling Systems to Protect Structure
135
GTEC Mass Barrier Ceilings
136
GTEC Acoustic Floor Systems
137
GTEC Suspended MF Ceiling GTEC Pregybel MF Ceiling GTEC Dryliner Ceiling GTEC Direct-to-Timber Ceiling GTEC Acoustic Floor
138 148 154 162 170
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
122
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® ENGINEERED JOIST SYSTEMS
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
292
30 30
47
74
27
277 (294)
30 –
40
83
31
275 (292)
30 30
40
80
31
277 (294)
30 –
43
74
30
277 (294)
30 30
41
80
System Weight
Minimum Thickness
(kg/m2)
(mm)
29
Impact Sound Insulation
REJ 023: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC dB Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: – Structure: min. 240mm engineered timber I-joists at 600mm centres Flooring Make-up: 22mm tongue and grooved chipboard
REJ 024: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Standard Board Accessories: (Single GTEC Resilient Bar at max. 450mm centres recommended) Insulation: – Structure: min. 240mm engineered timber I-joists at 600mm centres Flooring Make-up: 22mm tongue and grooved chipboard
REJ 026: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Accessories: (Single GTEC Resilient Bar at max. 450mm centres recommended) Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: min. 240mm engineered timber I-joists at 400mm centres Flooring Make-up: 22mm tongue and grooved chipboard
REJ 027: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Standard Board Accessories: (Single GTEC Resilient Bar at max. 450mm centres recommended) Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: min. 240mm engineered timber I-joists at 600mm centres Flooring Make-up: 22mm tongue and grooved chipboard
REJ 028: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board Accessories: (Single GTEC Resilient Bar at max. 450mm centres recommended) Insulation: – Structure: min. 240mm engineered timber I-joists at 450mm centres Flooring Make-up: 22mm tongue and grooved chipboard See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® CEILING SYSTEMS TO TIMBER FLOORS
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
233
30 30
38
77
35
235
30 –
38
78
38
235
30 –
40
79
43
254
30 30
40
76
38
252
30 30
52
69
System Weight
Minimum Thickness
(kg/m2)
(mm)
37
Impact Sound Insulation
RTC 052: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Standard Board Accessories: – Insulation: – Structure: 47mm x 200mm joists at 400mm centres without noggings Flooring Make-up: 18mm tongue and grooved chipboard
RTC 012: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: – Insulation: – Structure: 47mm x 200mm joists at 400mm centres without noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 065: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: – Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 400mm centres with noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 061: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Standard Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: – Structure: 47mm x 200mm joists at 450mm centres Flooring Make-up: 22mm tongue and grooved chipboard
RTC 017: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 600mm centres Flooring Make-up: 22mm tongue and grooved chipboard
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
123
124
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® CEILING SYSTEMS TO TIMBER FLOORS continued
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
247
30 30
40
78
48
247
30 30
42
75
38
235
30 30
44
75
34
235
30 30
41
77
37
237
60 60
41
76
System Weight
Minimum Thickness
(kg/m2)
(mm)
48
Impact Sound Insulation
RTC 003: Direct-to-Timber – see p162 Ceiling Inner Layer(s): 1x 12.5mm GTEC Standard Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: – Insulation: – Structure: 47mm x 200mm joists at 600mm centres Flooring Make-up: 22mm tongue and grooved chipboard
RTC 004: Direct-to-Timber – see p162 Ceiling Inner Layer(s): 1x 12.5mm GTEC Standard Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: – Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 600mm centres Flooring Make-up: 22mm tongue and grooved chipboard
RTC 028: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Accessories: – Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 600mm centres with noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 037: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Accessories: – Insulation: – Structure: 47mm x 200mm joists at 600mm centres with noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 018: Direct-to-Timber – see p162 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board (Fixed with 63mm GTEC High Thread screws) Accessories: – Insulation: – Structure: 47mm x 200mm joists at 600mm centres with noggings Flooring Make-up: 22mm tongue and grooved chipboard See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
252
60 30
43
72
52
247
30 30
44
75
54
–
30 30
47
71
55
–
60 60
48
70
System Weight
Minimum Thickness
(kg/m2)
(mm)
50
Impact Sound Insulation
RTC 016: Direct-to-Timber – see p162 Ceiling Inner Layer(s): 1x 15mm GTEC Standard Board Ceiling Outer Layer(s): 1x 15mm GTEC Standard Board Accessories: – Insulation: – Structure: 47mm x 200mm joists at 600mm centres with noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 014: Direct-to-Timber – see p162 Ceiling Inner Layer(s): 1x 12.5mm GTEC E Board Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Accessories: – Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 450mm centres without noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 029: Direct-to-Timber – see p162 Ceiling Inner Layer(s): Existing Lath & Plaster with Chicken Wire & Battens at 400mm centres Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: – Insulation: – Structure: 47mm x 200mm joists at 450mm centres without noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 020: Direct-to-Timber – see p162 Ceiling Inner Layer(s): Existing Lath & Plaster with Chicken Wire & Battens at 400mm centres Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board (Fixed with 63mm GTEC High Thread screws) Accessories: – Insulation: – Structure: 47mm x 200mm joists at 450mm centres without noggings Flooring Make-up: 22mm tongue and grooved chipboard
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
125
126
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® CEILING SYSTEMS TO TIMBER FLOORS continued
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
269
60 60
55
62
252
120 90
45
70
System Weight
Minimum Thickness
(kg/m2)
(mm)
55
50
Impact Sound Insulation
RTC 051: Direct-to-Timber – see p162 Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 1x 15mm GTEC dB Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 450mm centres without noggings Flooring Make-up: 22mm tongue and grooved chipboard
RTC 023: Direct-to-Timber – see p162 Ceiling Inner Layer(s): 1x 15mm GTEC Fire Board (Fixed with 50mm GTEC High Thread screws) Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board (Fixed with 75mm GTEC High Thread screws) Accessories: – Insulation: – Structure: 47mm x 200mm joists at 600mm centres with noggings Flooring Make-up: 22mm tongue and grooved chipboard
See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® DRYLINER CEILING SYSTEMS TO CONCRETE SOFFIT
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
–
– –
–
–
22
–
30 –
–
–
13
–
30 –
–
–
23
–
60 –
–
–
System Weight
Minimum Thickness
(kg/m2)
(mm)
11
Impact Sound Insulation
RDC 016: Dryliner – see p154 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: GTEC Dryliner Channel RD1 at 450mm max. centres Insulation: – Structure: Any Concrete Soffit Flooring Make-up: –
RDC 017: Dryliner – see p154 Ceiling Inner Layer(s): 1x 12.5mm GTEC Standard Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Accessories: GTEC Dryliner Channel RD1 at 450mm max. centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: Any Concrete Soffit Flooring Make-up: –
RDC 018: Dryliner – see p154 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Accessories: GTEC Dryliner Channel RD1 at 450mm max. centres Insulation: 50mm 24kg/m3 glass mineral wool Structure: Any Concrete Soffit Flooring Make-up: –
RDC 019: Dryliner – see p154 Ceiling Inner Layer(s): 1x 12.5mm GTEC Fire Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Accessories: GTEC Dryliner Channel RD1 at 450mm max. centres Insulation: 50mm 24kg/m3 glass mineral wool Structure: Any Concrete Soffit Flooring Make-up: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
127
128
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® SEPARATING FLOOR SYSTEMS
System Ref.
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
323
60 60
61, -11
54
71
–
60 60
60, -9
55
71
317
60 60
60, -9
55
System Weight
Minimum Thickness
(kg/m2)
(mm)
Ceiling Inner Layer(s): 1x 19mm GTEC Plank Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 600mm centres Flooring Make-up: 18mm tongue and grooved chipboard (from external layer) on 19mm GTEC Plank on 30mm 150kg/m3 rock mineral wool on 12mm plywood or OSB
70
Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 1x 15mm GTEC dB Board Frame: GTEC MF Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 400mm centres Flooring Make-up: 18mm tongue and grooved chipboard (from external layer) on 19mm GTEC Plank on 30mm 150kg/m3 rock mineral wool on 12mm plywood or OSB
Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 1x 15mm GTEC dB Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 400mm centres Flooring Make-up: 18mm tongue and grooved chipboard (from external layer) Spot bonded on GTEC 15mm dB Board on 30mm 150kg/m3 rock mineral wool on 12mm plywood or OSB
Component
Impact Sound Insulation
RTC 025
RTC 049
RTC 050
See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
System Ref.
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
-
60 60
Robust Detail Solution
Robust Detail Solution
44
271
60 60
65, -12
53
112
313
60 60
61, -7
57
–
60 60
–
–
System Weight
Minimum Thickness
(kg/m2)
(mm)
Ceiling Inner Layer(s): 1x 15mm GTEC Fire Board Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10-33kg/m3 glass mineral wool Structure: min. 240mm engineered timber I-joists Flooring Make-up: 18mm tongue and grooved chipboard (from external layer) Resilient Timber battens 13mm 33-36kg/m3 Rock mineral wool between battens on 15mm plywood or OSB
72
Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 1x 15mm GTEC dB Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 23kg/m3 glass mineral wool Structure: 150mm Structural Steel Joists at 400mm centres Flooring Make-up: 18mm tongue and grooved chipboard (from external layer) Spot bonded on GTEC 15mm dB Board on 30mm 120kg/m3 Rock Slab Insulation on 11mm OSB Sterling T&G Board
Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 1x 15mm GTEC dB Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10kg/m3 glass mineral wool Structure: 150mm Structural Steel Joists at 400mm centres Flooring Make-up: 40mm Gyvlon Screed on 6mm Ethafoam (from external layer) on 20mm OSB Sterling Board
Component
Impact Sound Insulation
E-FT-1: Robust Detail
RSF 002
RSF 003
RCC 015 Modified: Refurbishment as Approved Doc. E 4-3 Ceiling Inner Layer(s): 1x 12.5mm GTEC dB Board Ceiling Outer Layer(s): 1x 12.5mm GTEC dB Board Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Existing Ceiling: Existing Lath & Plaster Ceiling plus 15mm GTEC Fire Board Flooring Make-up: 18mm tongue and grooved chipboard
80
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
129
130
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® SEPARATING FLOOR SYSTEMS continued
System Ref.
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
–
– –
Robust Detail Solution
Robust Detail Solution
–
–
– –
Robust Detail Solution
Robust Detail Solution
–
–
– –
Robust Detail Solution
Robust Detail Solution
System Weight
Minimum Thickness
(kg/m2)
(mm)
Applicable Ceilings: (CT1) Metal ceiling system: GTEC MF Ceiling system providing 100mm (min) ceiling void with one layer 12.5mm GTEC Standard Board (CT2) Timber battens and counter battens: 50mm x 50mm softwood battens with 50mm x 50mm counter battens below and one layer 12.5mm GTEC Standard Board (CT3) Metal ceiling system: GTEC Dryliner SR or MF ceiling system providing 75mm (min) ceiling void with one layer 10+kg/m2 GTEC Board (CT4) Timber battens and resilient bar: 50mm x 50mm softwood with GTEC resilient bar RBD3000 mounted at 90° to softwood battens at 450mm c/c (max) and one layer 12.5mm GTEC E Board Floating floor: 18mm tongue and groove floorboards on resilient composite timber battens type FFT1 Screed: 40mm sand/cement or similar, minimum 80kg/m2 Structural floor: 150mm minimum precast concrete planks, minimum 300kg/m2
–
Applicable Ceilings: Metal ceiling system: GTEC Dryliner SR or MF ceiling system providing 75mm (min) ceiling void with one layer 10+kg/m2 GTEC Board Timber ceiling system: Any ceiling system providing 75mm void with one layer 12.5mm GTEC E Board Floating floor: 18mm tongue and groove floorboards on 25mm mineral wool batt insulation density 150kg/m3 type FFT4 Structural floor: 250mm minimum in-situ concrete slab, minimum 2400kg/m3 without screed
Applicable ceilings: Metal ceiling system: GTEC Dryliner or MF ceiling system providing 100mm or 15mm ceiling void with one layer 12.5mm GTEC Standard Board Timber ceiling system: Battens and counter battens providing 100mm ceiling void with one layer 12.5mm GTEC Standard Board Screed: 65mm (min) sand/cement or similar, minimum 80kg/m2 Upper resilient layer: 5mm foamed polyethylene 30-36kg/m3 Lower resilient layer: 25mm mineral wool batt 140kg/m3 (min) or 25mm expanded SD grade polystyrene or extruded polystyrene
Component
Impact Sound Insulation
E-FC-1
E-FC-2
E-FC-3
See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® PREGYBEL MF CEILING SYSTEMS
(kg/m2)
Acoustic Absorption Class, BS EN ISO 11654
Absorption co-efficient (_w), BS EN ISO 11654
12
B
0.80
12
C
0.75
12
C
0.70
12
C
0.60
12
C
0.7
12
C
0.65
System Weight
System Ref.
Component
PGC 001: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Frame: GTEC MF Ceiling Channels at Max 600mm centres Accessories: GTEC Connecting Clips Insulation: 75mm glass mineral wool and 600mm void Structure: Any suitable soffit
PGC 002: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Frame: GTEC MF Ceiling Channels at Max 600mm centres Accessories: GTEC Connecting Clips Insulation: 50mm glass mineral wool and 600mm void Structure: Any suitable soffit
PGC 003: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Frame: GTEC MF Ceiling Channels at Max 600mm centres Accessories: GTEC Connecting Clips Insulation: 50mm glass mineral wool and 300mm void Structure: Any suitable soffit
PGC 004: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Frame: GTEC MF Ceiling Channels at Max 600mm centres Accessories: GTEC Connecting Clips Insulation: 300mm void Structure: Any suitable soffit
PGC 101: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel R12no2 Frame: GTEC MF Ceiling Channels at Max 600mm centres Accessories: GTEC Connecting Clips Insulation: 50mm glass mineral wool and 300mm void Structure: Any suitable soffit
PGC 102: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel R12no2 Frame: GTEC MF Ceiling Channels at Max 600mm centres Accessories: GTEC Connecting Clips Insulation: 300mm void Structure: Any suitable soffit
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
131
132
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® PREGYBEL MF CEILING SYSTEMS continued
(kg/m2)
Acoustic Absorption Class, BS EN ISO 11654
Absorption co-efficient (_w), BS EN ISO 11654
12
C
0.70
12
C
0.7
12
C
0.60
12
D
0.50
12
D
0.55
12
D
0.55
System Weight
System Ref.
Component
PGC 201: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel R15no1 Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Connecting Clips Insulation: 50mm glass mineral wool and 300mm void Structure: Any suitable soffit
PGC 202: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel R15no1 Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Connecting Clips Insulation: 30mm glass mineral wool and 50mm void Structure: Any suitable soffit
PGC 301: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel R15no8 Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Connecting Clips Insulation: 50mm glass mineral wool and 300mm void Structure: Any suitable soffit
PGC 302: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel R15no8 Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Connecting Clips Insulation: 300mm void Structure: Any suitable soffit
PGC 401: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel L5x80no8 Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Connecting Clips Insulation: 80mm glass mineral wool and 300mm void Structure: Any suitable soffit
PGC 402: Pregybel MF – see p148 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x GTEC Pregybel L5x80no8 Frame: GTEC MF Ceiling Channels at Max 450mm centres Accessories: GTEC Connecting Clips Insulation: 80mm glass mineral wool and 100mm void Structure: Any suitable soffit
See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® SUSPENDED MF CEILING SYSTEMS TO TIMBER FLOORS
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr if applicable)
(Lnw dB)
n/a
30 30
43
72
40
n/a
60 30
44
72
42
n/a
60 30
46
69
System Weight
Minimum Thickness
(kg/m2)
(mm)
33
Impact Sound Insulation
RCC 011: Suspended MF – see p138 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Connecting Clips Insulation: – Structure: 47mm x 200mm Joists at 600mm centres Floor: Min. 18mm tongue and grooved boarding or similar
RCC 042: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 12.5mm GTEC Standard Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm Joists at 600mm centres Floor: Min. 18mm tongue and grooved boarding or similar
RCC 012: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 12.5mm GTEC E Board Ceiling Outer Layer(s): 1x 12.5mm GTEC E Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm Joists at 600mm centres Floor: Min. 18mm tongue and grooved boarding or similar
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
133
134
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® SUSPENDED MF CEILING SYSTEMS TO TIMBER FLOORS continued
System Ref.
Component
Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr if applicable)
(Lnw dB)
n/a
60 30
44
70
45
n/a
90 30
54
62
50
n/a
120 30
56
60
System Weight
Minimum Thickness
(kg/m2)
(mm)
34
Impact Sound Insulation
RCC 013: Suspended MF – see p138 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Connecting Clips Insulation: – Structure: 47mm x 200mm Joists at 600mm centres Floor: Min. 18mm tongue and grooved boarding or similar
RCC 014: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 12.5mm GTEC Fire Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm Joists at 600mm centres Floor: Min. 18mm tongue and grooved boarding or similar
RCC 015: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 15mm GTEC Fire Board Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm Joists at 600mm centres Floor: Min. 18mm tongue and grooved boarding or similar
See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® SUSPENDED MF CEILING SYSTEMS TO PROTECT STRUCTURE
System Ref.
Component
System Weight
Fire Perf. BS476-21 BS476-22
Fire Perf. BS476-23
Fire Perf. BS1364-2 BS1365-2
Acoustic Perf. Rw dB (Ctr if applicable)
Impact Sound Insulation
(kg/m2)
(mins)
(mins)
(mins)
11
– –
–
– –
–
–
22
– –
30
30 –
–
–
13
– –
30
30 –
–
–
26
– –
60
30 –
–
–
15
– 30
60
30 –
–
–
(Lnw dB)
RCC 016: Suspended MF – see p138 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Connecting Clips Insulation: – Structure: Any suitable soffit
RCC 017: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 12.5mm GTEC Standard Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Standard Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: Any suitable soffit
RCC 018: Suspended MF – see p138 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Connecting Clips Insulation: 50mm 24kg/m3 glass mineral wool Structure: Any suitable soffit
RCC 019: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 12.5mm GTEC Fire Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Frame should be screw fixed Insulation: 50mm 10.5kg/m3 glass mineral wool Structure: Any suitable soffit
RCC 028: Suspended MF – see p138 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board Frame: GTEC Ceiling Channels at max. 450mm centres Accessories: GTEC Connecting Clips Insulation: 50mm 24kg/m3 glass mineral wool Structure: Any suitable soffit
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
135
136
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® MASS BARRIER CEILINGS
System Ref.
Component
System Weight
Fire Perf. BS476-21 BS476-22
Fire Perf. BS476-23
Fire Perf. BS1364-2 BS1365-2
Acoustic Perf. Rw dB (Ctr if applicable)
Impact Sound Insulation
(kg/m2)
(mins)
(mins)
(mins)
30
– –
60
30 –
–
–
50
– –
90
90 –
–
–
(Lnw dB)
RCC 060: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 12.5mm GTEC dB Board Ceiling Outer Layer(s): 1x 12.5mm GTEC dB Board Frame: GTEC Ceiling Channels at max. 450mm centres Heavy Duty Primary channels UT52/Y at 900mm Centres Accessories: Phonissimo Acoustic Hangers as 1200mm Centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: Any suitable soffit
RCC 061: Suspended MF – see p138 Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 2x 15mm GTEC dB Board Frame: GTEC Ceiling Channels at max. 450mm centres Heavy Duty Primary channels UT52/Y at 900mm Centres Accessories: Phonissimo Acoustic Hangers as 1200mm Centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: Any suitable soffit
See p137 for notes on alterations to floors and ceilings configuration.
GTEC® FLOORS AND CEILINGS – PERFORMANCE TABLES
GTEC® ACOUSTIC FLOOR SYSTEMS Fire Perf. BS476-21 BS EN 1365-2 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
(Lnw dB)
60
60 60
63, -10
54
60
60 60
53
65
System Weight
System Ref.
(kg/m2)
Component
Impact Sound Insulation
RAF 050: Acoustic Floor – see p170 Ceiling Inner Layer(s): 1x 15mm GTEC dB Board Ceiling Outer Layer(s): 1x 15mm GTEC dB Board Accessories: Single GTEC Resilient Bar at max. 450mm centres Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 450mm centres Floor Inner Layer(s): 1x 15mm GTEC dB Board on GTEC Acoustic Floor Clips Floor Outer Layer(s): 22mm tongue and grooved chipboard
RAF 006: Acoustic Floor – see p170 Ceiling Inner Layer(s): 15mm GTEC Fire Board to joists and bridged over insulation Ceiling Outer Layer(s): Existing lath and plaster decorative ceiling Accessories: – Insulation: 100mm 10.5kg/m3 glass mineral wool Structure: 47mm x 200mm joists at 450mm centres Floor Inner Layer(s): 1x 19mm GTEC Plank on GTEC Acoustic Floor Clips Floor Outer Layer(s): 22mm tongue and grooved chipboard
FLOORS AND CEILINGS PERFORMANCE NOTES Performance values are for imperforate, jointed systems using Siniat GTEC components (metal studs and tracks, boards, metal accessories, screws and finishing systems) and specified insulation quilt material (type, thickness and density) and installed to Siniat specification and installation guides. Any alterations may impair the quoted performance. Contact Technical Enquiryline for further system configurations and their resulting performances. Insulation shown may be replaced with thicker and/or heavier quilt material without impairing the quoted performances. For maximum framing centres, joist connector and bracket centres and loading see tables within system guidance pages.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
137
138
GTEC® SUSPENDED MF CEILING
®
GTEC SUSPENDED MF CEILING SYSTEMS The GTEC Suspended MF Ceilings are used to create ‘false ceilings’ which house services between the ceiling and soffit. The large voids created also improve acoustic, fire and thermal performance. GTEC Suspended MF Ceilings are formed from a series of GTEC Primary Channels hung from the soffit. Attached to these channels are GTEC Ceiling Channels, slotted into GTEC Edge Channel to form the frame. GTEC Board is fixed to the MF frame to complete the system. Refer to the System Performance Tables on pages 133 to 136 for full details.
WHERE TO USE: GTEC Suspended MF Ceilings are used for commercial applications where services are required below the soffit. For ceilings with enhanced fire and acoustic performance in commercial and residential applications.
FEATURES
BENEFITS
Variable cavity depth
Optimisable cavity size for service and insulation requirements
High acoustic, fire and thermal capabilities
Required performance levels are easily achieved
Creates a ‘false ceiling’
Can be used to upgrade or protect existing structures
Demountable
Easy to renovate
Flat finish
Provides a smooth surface for decorating
GTEC® SUSPENDED MF CEILING
139
TIP: The most versatile option for a new ceiling, the optimisable depth gives a wide range of fire and sound ratings.
Insulation to suit required performance
GTEC Connecting Clip for single layer systems only
fix channels back to back if required minimum overlap of 150mm GTEC Metal Angle cut and bent to form appropriate fixing
GTEC Ceiling Channel GTEC Edge Channel
splice ceiling channel if necessary minimum overlap of 150mm GTEC Board to suit required performance
GTEC Primary Channel
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
140
GTEC速 SUSPENDED MF CEILING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p133-136
GTEC Ceiling Channel Steel channel to support boards
MFCC50
GTEC Primary Channel Steel channel to support GTEC Ceiling Channel
MFCP44
GTEC Heavy Gauge Primary Channel Heavy duty steel channel to support GTEC Ceiling Channel
UT52/Y
GTEC Edge Channel Steel channel used to form perimeter board support
MFCE26
GTEC Metal Angle Multi-purpose metal section as suspension hanger
MFC2330, MFC2525, MFC2550
GTEC Connecting Clip Steel clip for joining GTEC Ceiling Channel to GTEC Primary Channel
MFCCLEAT
GTEC Soffit Cleat Steel bracket to fix suspension hangers to substrate
MFSTRAP
GTEC Phonistar Acoustic Hanger A heavy duty (up to 120kg) acoustic suspended ceiling hanger bracket
PHONI
GTEC Phonissimo Acoustic Hanger A medium duty (up to 50kg) acoustic suspended ceiling hanger bracket
PHONIMO
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
Mineral wool insulation Increases fire and acoustic insulation performance
See performance tables supplied by others
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® SUSPENDED MF CEILING
SYSTEM GUIDANCE FRAME FC-MF-101S-Ceiling perimeter
Max. 1200mm
GTEC Metal Angle
GTEC Edge Channel screw fix to substrate at max. 600mm centres GTEC Primary Channel
Board fixed to GTEC Edge Channel at 150mm centres
GTEC Board to suit required performance
GTEC Intumescent Acoustic Sealant
SECTION FC-MF-102M & 103M-Ceiling channel splicing Ceiling Channel Splice
12 00 mm
15 0m ov m m erl in. ap
mm 00 12
mi n. be tw ee ns pli ce s
es lic sp en e tw be n. mi
Primary Channel Splice
n mi mmap 0 15 verl o
ISOMETRIC
GTEC Edge Channel to be fixed to structure at perimeter of ceiling run and around any obtrusions within the ceiling, e.g. columns. Fix at 600mm centres using appropriate fixings. Allow for board depth when positioning channel.
GTEC Primary Channels to be arranged at maximum centres (see table) according to expected loadings including system and board weight (as indicated in performance tables). Channels to be fixed to hangers using appropriate GTEC Drywall Screws.
GTEC Metal Angle suspension hangers to be fixed at maximum 1200mm centres to structural soffit using GTEC Soffit Cleats and appropriate structural fixings by others.
Max. primary channel centres
Maximum loading including system and board weight
600mm
74kg/m2
Hangers to be at maximum of 900mm from ceiling perimeter.
900mm
50kg/m2
1200mm
35kg/m2
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
141
142
GTEC® SUSPENDED MF CEILING
FRAME continued GTEC Ceiling Channels to be located into GTEC Edge Channel at maximum. 450mm centres and fixed at right angles to GTEC Primary Channel.
GTEC Primary Channels may be spliced if necessary by fixing back-to-back with minimum four appropriate GTEC Drywall Screws.
Fixing between Ceiling and Primary channels to be made using appropriate GTEC Drywall Screws.
GTEC Ceiling Channels may be jointed by overlapping profiles by minimum 150mm and fixing with minimum four appropriate GTEC Drywall Screws.
GTEC Connecting Clips may only be used to connect GTEC Ceiling Channel to Primary Channel in single board layer systems with no additional loadings. GTEC Connecting Clips to be alternated in direction to counteract any movement.
INSULATION Any insulation to be of type and thickness to achieve performance and installed in a continuous layer between primary channels and over ceiling channels and boards.
GTEC® SUSPENDED MF CEILING
BOARDING FC-MF-201M & 202M Board Layout
SINGLE LAYER
GTEC Ceiling Channel
screw fix plasterboard to GTEC Ceiling Channel at 230mm centres
screw fix cut end of plasterboard to GTEC Ceiling Channel at 150mm centres
screw fix cut end of plasterboard to GTEC Edge Channel at 150mm centres
GTEC Intumescent Acoustic Sealant GTEC Edge Channel
DOUBLE LAYER
stagger joints and fixings between layers
GTEC Intumescent Acoustic Sealant GTEC Edge Channel
PLAN
GTEC Suspended MF Ceiling system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables (p133-136) and Product Specification (p294-307) to achieve required performance. See High Performance Boards guide p12 for further selection information. Boards to span across GTEC Ceiling Channels. Joints between boards must occur at centre of channels. Board ends and joints to be centred over channels.
Boards to be mechanically fixed to GTEC Edge Channel at 150mm centres using appropriate GTEC Drywall Screws. See screw selector p334. Boards to be mechanically fixed to GTEC Ceiling Channels at 230mm centres in centre of board or at bound edges and at 150mm centres at cut edges, using appropriate GTEC Drywall Screws. See screw selector p334. Board joints to be staggered between layers. Any GTEC Fire Board, or other GTEC Type F (BS EN 520) board, required by the system performance, to be installed as the outermost/finishing layer.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
143
144
GTEC® SUSPENDED MF CEILING
MOVEMENT CONTROL JOINTS FC-MF-301S-Movement joint – parallel to c. channels
FC-MF-302S-Movement joint – perpendicular to c. channels
GTEC Metal Angle 60x60mm 40kg/m3 Rock Mineral Wool to maintain fire integrity
GTEC Primary Channel
GTEC Board to suit required performance
60mm Mineral Wool to maintain fire integrity
60mm
60mm GTEC Edge Channel
GTEC Ceiling Channel extended to end of board
10mm Max. 50mm
Max. 50mm
GTEC Ceiling Channel GTEC Movement Control Joint
GTEC Board to suit required performance
GTEC Primary Channel
GTEC Ceiling Channel
10mm
GTEC Movement Control Joint
screw fix board at 150mm centres
SECTION
Form movement control joints at maximum 10m intervals in any direction in ceiling run. Form movement control joints where ceiling crosses a structural movement joint.
SECTION
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples. Follow measures to ensure fire resistance and stability as shown in Construction Details.
OPENINGS FC-MF-401M-Opening in ceiling GTEC Ceiling Channel
Frame formed from GTEC Edge Channel
GTEC Primary Channel
Note: hangers not shown for clarity
Frames around openings and large penetrations in ceiling to be formed from GTEC Edge Channel with additional GTEC Primary Channel to support opening frame and GTEC Ceiling Channels.
ISOMETRIC
GTEC® SUSPENDED MF CEILING
HEIGHT CHANGE & JUNCTIONS FC-MF-501S-Junction of partition to ceiling
FC-MF-502S-Junction of ceiling to partition
GTEC Metal Angle fixed at 1200mm centres GTEC Ceiling Channel to coincide with partition
GTEC Primary Channel
Ceiling boards separated at partition heads to reduce sound transmission
Track fixed through to channel
GTEC Edge Channel fixed through to stud
GTEC Partition System to suit required performance
GTEC Intumescent Acoustic Sealant
GTEC Partition System to suit required performance
SECTION FC-MF-503S-Change in ceiling height Max. 150mm
Max. 150mm
SECTION FC-MF-504S-Bulkhead GTEC Soffit Cleat
GTEC Metal Angle
GTEC Intumescent Acoustic Sealant
GTEC Primary Channel
GTEC Metal Angle
GTEC Edge Channel
GTEC Edge Channel
Max. 600mm
GTEC Ceiling Channel screw fixed at 400mm centres
Max. 600mm
GTEC Primary Channel
GTEC Edge Channel
fix channels together fix channels together GTEC Corner 90º External / GTEC Flex Tape
SECTION
Abutting partitions to coincide with and fix to GTEC Ceiling Channel, install additional intermediate ‘pick-up’ channels if required. Separate boards at partition head to reduce sound transmission.
GTEC Ceiling Channel
GTEC Corner 90º External / GTEC Flex Tape
SECTION
Where ceiling abuts partition fix GTEC Edge Channel through to stud. Form 90° junction in ceiling by fixing GTEC Edge Channels at right angle with GTEC Ceiling Channel spanning vertically as required. Hangers to be positioned at maximum 150mm from change in height.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
145
146
GTEC® SUSPENDED MF CEILING
FIXTURES Where possible fixtures and loadings to be suspended from structural soffit and not GTEC Suspended MF Ceiling system. Loads suspended from ceiling to be fixed to frame not boards. Framing centres to suit total load, see guidance on centres in ‘Frame’ guidance section, and appropriate fixings selected to suit full loadings. Services running through ceiling void to be supported by structural soffit and not GTEC Suspended MF Ceiling System.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. Where a ceiling is not intended to be decorated GTEC Intumescent Sealant to be used to seal board joints. GTEC Finish materials appropriate to board type to be used.
SYSTEM CONTINUITY Full, imperforate system continuity to be maintained to achieve rated performances.
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated ceilings.
Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings.
Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire and sound resisting material.
GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
GTEC® SUSPENDED MF CEILING
ACOUSTIC MASS BARRIER CEILINGS FC-MF-002S-Phonissimo Acoustic Hanger – general arrangement FC-MF-003M-Phonissimo Acoustic Hanger – assembly M6 threaded rod by others at 1200mm centres
Mineral wool insulation to suit required performance
GTEC Phonissimo Acoustic Hanger
M6 threaded rod by fitted into GTEC Phonissimo
GTEC Heavy Gauge Primary Channel
GTEC Heavy Gauge Primary Channel at 1200mm centres Nut to secure end of rod
GTEC Board to suit required performance GTEC Ceiling Channel at 400mm centres
GTEC Phonissimo Acoustic Hanger
ISOMETRIC
SECTION FC-MF-004S-Phonistar Resilient Hanger – general arrangement M6 threaded rod by others at 1200mm centres
GTEC Phonistar Resilient Hanger at 1200mm centres
FC-MF-005M-Phonistar Resilient Hanger – assembly
M6 threaded rod by fitted into GTEC Phonistar GTEC Phonistar Acoustic Hanger GTEC Heavy Gauge Primary Channel
GTEC Heavy Gauge Primary Channel at 1200mm centres
Hole drilled in channel to receive phoniostar rod
Square washer
GTEC dB Board to suit required performance
Nut to secure end of rod
GTEC Ceiling Channel at 400mm centres
SECTION
For Acoustic Mass Barrier system configurations suspend frame from GTEC Phonistar or GTEC Phonissimo hangers at maximum 1200mm centres using M6 threaded rod.
ISOMETRIC
GTEC Heavy Gauge Primary Channel UT52/Y to be used instead of GTEC Primary Channel.
GTEC Phonissimo and GTEC Phonistar hangers are acoustically dampened, high strength hangers to support higher mass ceilings which offer the highest acoustic insulation.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
147
148
GTEC® PREGYBEL MF CEILING
®
GTEC PREGYBEL MF CEILING SYSTEMS The GTEC Pregybel MF Ceiling system is used for creating sound absorbing ceilings to control sound reflection in larger spaces, creating a more comfortable level of sound and improved audibility. GTEC Pregybel MF Ceilings combine the easy to install advantages of the GTEC Suspended MF Ceiling with the sound absorption capability of GTEC Pregybel Board. Using frame components from the GTEC Suspended MF system enables flexible design and specification. GTEC Pregybel board is perforated in a range of patterns for attractive designs and reduction in the reflective surface of the board to limit echo or reverberation. Refer to the System Performance Tables on pages 131 to 132 for full performance details.
WHERE TO USE: GTEC Pregybel MF ceilings are used in commercial applications where large, hard-surfaced and uninterrupted spaces would otherwise suffer from echoing. GTEC Pregybel MF ceilings are also required for corridors and stairwells in residential blocks to reduce sound travel through the building.
FEATURES
BENEFITS
Variable cavity depth
Cavity size can be optimised for service and insulation requirements Up to Class B acoustic absorption
Utilises GTEC Suspended MF framing
One set of components on site Easy to install
Creates a ‘false ceiling’
Can be used to upgrade existing structures
Perforated boards in a range of patterns
Provides a range of aesthetic options to add variation in large spaces
GTEC® PREGYBEL MF CEILING
TIP: When painting GTEC Pregybel it is crucial not to use spray applied paint which can block the board’s tissue backer.
Glass Mineral wool insulation to suit required performance
GTEC Pregybel Board to suit required performance
GTEC MF Suspended Ceiling System
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
149
150
GTEC速 PREGYBEL MF CEILING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p131-132
GTEC Ceiling Channel Steel channel to support boards.
MFCC50
GTEC Primary Channel Steel channel to support GTEC Ceiling Channel
MFCP44
GTEC Edge Channel Steel channel used to form perimeter board support
MFCE26
GTEC Metal Angle Multi-purpose metal section as suspension hanger
MFC2330, MFC2525, MFC2550
GTEC Connecting Clip Steel clip for joining GTEC Ceiling Channel to GTEC Primary Channel
MFCCLEAT
GTEC Soffit Cleat Galvanised steel bracket to fix suspension hangers to substrate
MFSTRAP
GTEC Strap Hanger Suspension hanger for depths up to 1m
MFSTRAP
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
Mineral wool insulation Increases acoustic absorption
See performance tables supplied by others
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to prevent dust accumulation
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® PREGYBEL MF CEILING
SYSTEM GUIDANCE See guidance in GTEC Suspended MF section and additional considerations given below: FRAME FC-PG-101S-Pregybel Secondary Ceiling GTEC Metal Angle fixed at max. 1200mm centres GTEC Primary Channel screw fixed at centres to support loading GTEC Ceiling Channel screw fixed at 400mm centres GTEC Board to suit required performance Fix Pregybel ceiling through to Ceiling Channel GTEC Metal Angle fixed to every other ceiling channel Mineral wool insulation to suit required performance GTEC Primary Channel screw fixed at centres to support loading GTEC Ceiling Channel screw fixed at 600mm centres GTEC Pregybel Board
GTEC Connecting Clips may be used to connect GTEC Ceiling Channel to Edge Channel in all single layer GTEC Pregybel MF systems providing no additional loads are being carried.
SECTION
GTEC Ceiling Channel to be at maximum 600mm centres to coincide with unperforated areas of board.
INSULATION Any insulation to be of type and thickness to achieve performance and installed in a continuous layer between primary channels and over ceiling channels and boards.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
151
GTEC速 PREGYBEL MF CEILING
BOARDING FC-PG-201E-Pregybel board designs GTEC Pregybel R12 no. 2
12
25
GTEC Pregybel C10 no. 8
10
10
20
GTEC Pregybel R15 no. 1
15
30
GTEC Pregybel R15 no. 8
15
30
GTEC Pregybel L5x80 no. 8
5
80
All units in millimetres
80
10
152
ELEVATION
GTEC® PREGYBEL MF CEILING
FC-PG-002S-Pregybel Standalone Bulkhead
FC-PG-501S-Pregybel Ceiling Height Change Max. 150mm
Max. 150mm
GTEC Metal Angle
GTEC Primary Channel GTEC C Stud Brace diagonally with GTEC U Track
GTEC Edge Channel Max. 600mm
GTEC Ceiling Channel screw fixed at 400mm centres GTEC Edge Channel
GTEC U Track
fix channels together
screw fix tracks together
GTEC Corner 90º External / GTEC Flex Tape
GTEC Pregybel Board
SECTION
SECTION
PENETRATIONS
FINISHING
M&E runs and other penetrating services to be pre-planned to minimise or eliminate penetrations through rated ceilings.
All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances.
Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire and sound resisting material.
GTEC Pregybel Board, once sealed, to be painted with rollers to prevent paint blocking tissue backing and reducing absorption capacity. GTEC Finish materials appropriate to board type to be used.
SYSTEM CONTINUITY Only areas with full system continuity will achieve rated performances. Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings to prevent dust accumulation.
GTEC Pregybel MF Ceiling system is suitable for single layer boarding. Select GTEC Pregybel Board according to acoustic performance required and desired perforation pattern. GTEC Pregybel boards to be arranged to achieve desired board pattern. GTEC Pregybel Boards and GTEC Boards may be mixed for decorative effect however acoustic absorption only occurs where board, void and insulation match the system performance. Boards to span across GTEC Ceiling Channels.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
153
154
GTEC® DRYLINER CEILING
®
GTEC DRYLINER CEILING SYSTEMS The GTEC Dryliner Ceiling system is a simple, quick and cost-effective method for constructing a true, flat ceiling, even when connecting to uneven joists or concrete soffits. It also creates a small cavity to accommodate services. GTEC Dryliner ceilings are made from GTEC Dryliner Brackets fixed to the soffit or joists, with GTEC Dryliner Channels secured to them. The channels provide a strong, level substrate for fixing the plasterboard. GTEC Dryliner Brackets are available for a range of cavity depths up to 130mm. Fire rating and acoustic performance can be enhanced by the selection of appropriate GTEC Boards. Refer to the System Performance Tables on page 127 for full details.
WHERE TO USE: GTEC Dryliner Ceilings are used for both domestic and commercial applications for either new build or renovation projects.
FEATURES
BENEFITS
Improved fire protection for timber joists
Cost effective solution for achieving required performance
Creates a cavity
Accommodates services without the need to drill joists
Adjustable brackets
Creates a flat surface even with uneven joists or soffit
Separation from soffit
Provides improved acoustic performance
No direct connection between board and joists
Reduces risk of plasterboard cracking from movement of wooden joists
GTEC速 DRYLINER CEILING
155
TIP: GTEC Boards are strongest in their long axis so must span across channels.
GTEC Dryliner Channel
GTEC Dryliner Bracket
GTEC Dryliner Track
GTEC Intumescent Acoustic Sealant GTEC Board to suit required performance
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
156
GTEC速 DRYLINER CEILING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p127
GTEC Dryliner Channel A galvanised steel furring channel for plasterboard fixing
RD1
GTEC Dryliner Channel Connector A galvanised clip used to join sections of GTEC Dryliner Channel
RD3
GTEC SR bracket Adjustable bracket to connect GTEC Dryliner Channel to substrate
RD2
GTEC XR bracket Adjustable, extended reach bracket to connect GTEC Dryliner Channel to substrate
RD11
GTEC Dryliner Track J shaped metal section used as a track and perimeter channel
RD9
GTEC Metal Angle Multi-purpose metal section as suspension hanger
MFC2330, MFC2525, MFC2550
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
Mineral wool insulation Increases fire and acoustic insulation performance
See performance tables supplied by others
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
BOARDS
FRAME
INSULATION
FIX
FINISHING
GTEC® DRYLINER CEILING
SYSTEM GUIDANCE FRAME FC-DC-101E-Dryliner cavity sizes
FC-DC-102S-Ceiling perimeter Mineral wool insulation to suit required performance
Max. 60mm
Max. 150mm
fix bracket to soffit with appropriate fixing by others GTEC Standard Reach Dryliner Bracket
GTEC Dryliner Channel
Min. 25mm
GTEC Standard Reach Dryliner Bracket
GTEC Dryliner Track fixed to substrate at 600mm centres with appropriate fixings by others
Max. 130mm
GTEC Intumescent Acoustic Sealant
GTEC Extended Reach Dryliner Bracket
GTEC Board to suit required performance
SECTION
GTEC Dryliner Track to be fixed to structure at perimeter of ceiling run and around any obtrusions within the ceiling, e.g. columns. Fix at 600mm centres using appropriate fixings by others. Allow for board depth when positioning channel. Select GTEC Dryliner Brackets (SR and XR) to suit cavity depth required:
Min. 25mm
GTEC Extended Reach Dryliner Bracket
GTEC Dryliner Bracket
Cavity Depth Range
GTEC SR Bracket
25mm-60mm
GTEC XR Bracket
25mm-130mm
remove excess bracket as required
SECTION
GTEC Dryliner Channel to be positioned at maximum 450mm centres. GTEC Dryliner Brackets to be positioned at maximum 600mm centres for double layer boarding and at maximum 900mm centres for single layer boarding. GTEC Dryliner Brackets to be fixed to soffit/joists in line to receive GTEC Dryliner Channel: GTEC SR and XR Brackets to be fixed using appropriate structural fixings by others.
GTEC Dryliner Channel to be 5mm shorter than ceiling length/width, located into GTEC Dryliner Track, attached to both GTEC Dryliner Bracket legs with appropriate GTEC Drywall Screws (see screw selector p334) and levelled by adjusting brackets. Excess bracket leg length to be removed or bent back. GTEC Dryliner Channel may be spliced if necessary using GTEC Dryliner Channel Connector. Any jointed sections to be fixed to soffit/joist with additional brackets where required.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
157
158
GTEC® DRYLINER CEILING
INSULATION Any insulation to be of type and thickness to achieve performance and tightly installed in a
continuous layer between brackets and over channels.
BOARDING FC-DC-201P & 202P-Single boarding and double layer boarding
SINGLE LAYER
Boards edges must coincide with channels
Insulation quilt to suit required performance
Screw fix at 150mm at cut edges
Screw fix at 230mm centres elsewhere
Stagger all joints
Screw fix at 150mm centres around perimeter
DOUBLE LAYER
Boards edges must coincide with channels
Insulation quilt to suit required performance
Screw fix at 230mm centres in centre of board and at bound edges Screw fix at 150mm at cut edges
Stagger all joints
Screw fix at 150mm centres around perimeter
PLAN
GTEC® DRYLINER CEILING
GTEC Dryliner Ceiling system is suitable for single and double layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables (p133-136) and Product Specification (p294-307) to achieve required performance. See High Performance Boards guide p12 for further selection information. Boards to span across GTEC Dryliner Channels with bound edges at right angles to channels. Board ends and joints to be centred over channels.
Boards to be mechanically fixed to GTEC Dryliner Track at 150mm centres using appropriate GTEC Drywall Screws. See screw selector p334. Boards to be mechanically fixed to GTEC Dryliner Channels at 230mm centres in field of board or at bound edges and at 150mm centres at cut edges, using appropriate GTEC Drywall Screws. See screw selector p334. Board joints to be staggered between layers. Any GTEC Fire Board, or other GTEC Type F (BS EN 520) board, required by the system performance, to be installed as the outermost/finishing layer.
MOVEMENT CONTROL JOINTS FC-DC-301S-Movement joint
Max. 50mm
Max. 50mm
GTEC Movement Control Joint 10mm
50mm Rock Mineral wool insulation 40kg/m3 (if fire rated system)
SECTION
Form movement control joints at maximum 10m intervals in any direction in ceiling run. Form movement control joints where ceiling crosses a structural movement joint.
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples. Follow measures to ensure fire resistance and stability as shown in Construction Details.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
159
160
GTEC® DRYLINER CEILING
HEIGHT CHANGE & JUNCTIONS FC-DC-501S-Junction of partition to ceiling
FC-DC-502S-Junction of ceiling to partition Max. 150mm
Max. 150mm
GTEC Intumescent Acoustic Sealant screw fix track through to channel
GTEC Intumescent Acoustic Sealant GTEC Partition System to suit required performance
GTEC Partition System to suit required performance
SECTION FC-DC-503S-Bulkhead
SECTION FC-DC-504S-Change in ceiling height GTEC Dryliner Bracket to suit required depth
GTEC Intumescent Acoustic Sealant GTEC Dryliner Channel
GTEC Dryliner Track fix plasterboard to channel at 150mm centres
GTEC Board to suit required performance
fix to track at 150mm centres GTEC Corner 90º External / GTEC Flex Tape
SECTION
Abutting partitions to coincide with and fix to GTEC Dryliner Channel, install additional intermediate ‘pick-up’ channels with brackets where required. Where ceiling abuts partition fix GTEC Dryliner Track through to stud and install GTEC Dryliner Channels with brackets within 150mm of partition.
SECTION
Form 90° junction in ceiling with GTEC Dryliner Track as corner reinforcement or position GTEC Dryliner brackets to receive edge board along legs.
GTEC® DRYLINER CEILING
SYSTEM CONTINUITY
FIXTURES Fixtures and loadings to be suspended from structural soffit/joist and not GTEC Dryliner Ceiling system. Any services or installations in ceiling void to be supported by structural soffit/joist and not GTEC Dryliner Ceiling System.
Full, imperforate system continuity to be maintained to achieve rated performances. Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated ceilings. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire and sound resisting material.
GTEC Dryliner Ceiling system may be used to upgrade existing, retained ceilings provided all fixing is into structural soffit/joists and any combustible material is removed from retained ceiling or evaluated as inert.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. Where ceiling is not intended to be decorated GTEC Intumescent Sealant to be used to seal board joints. GTEC Finish materials appropriate to board type to be used.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
161
162
GTEC® DIRECT-TO-TIMBER CEILING
®
GTEC DIRECT-TO-TIMBER CEILING SYSTEMS The GTEC Direct-to-Timber Ceiling system is the simplest method of creating a flat ceiling surface for decoration and achieving excellent fire performance. GTEC Plasterboard is attached directly to the underside of floor joists or to the bottom chords of roof trusses with insulation between rafter to boost acoustic and fire performance. Refer to the System Performance Tables on pages 122 to 126 for full details.
WHERE TO USE: The GTEC Direct to Timber system is used in both renovation and new-build domestic applications.
FEATURES
BENEFITS
Only requires board and screws
Reduces installation time and costs
Compatible with GTEC Board options
Achieves required fire performance
Flat finish
Provides easy to decorate surface
Can be used with GTEC Resilient Bar
Improves acoustic performance and reliability with some engineered joists
GTEC® DIRECT-TO-TIMBER CEILING
163
TIP: In double layer systems it is important to stagger all joists to prevent fire or sound bypassing boards.
Screw fix board to joist at 230mm centres in centre of board Joist
GTEC Intumescent Acoustic Sealant
Screw fix board to joist at 150mm centres at perimeter and cut ends
Stagger all joints Span boards across joists
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
Nogging
164
GTEC速 DIRECT-TO-TIMBER CEILING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p122-126
Timber frame Structural frame forming part of an external or internal wall
Supplied by others
GTEC Resilient Bar Metal profile to provide acoustic separation of board and joists
RBD3000
GTEC High Thread Screws (as appropriate) For attaching plasterboard to timber
See screw selector, p334
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
BOARDS
FRAME
FIX
FINISHING
GTEC® DIRECT-TO-TIMBER CEILING
SYSTEM GUIDANCE FRAME FC-DT-101S-Perimeter detail
FC-DT-102M-Timber ceiling with resilient bar
Timber perimeter nogging
Mineral wool insulation to suit required performance
Timber joist
GTEC Board to suit required performance
screw fix board to perimeter noggings at 150mm centres
GTEC Resilient Bar
GTEC Board to suit required performance
GTEC Intumescent Acoustic Sealant
Engineered or square joists
ISOMETRIC
SECTION
Joist spacings without noggings to be maximum 450mm for boards up to 15mm and maximum 600mm for 19mm GTEC Plank. Joist spacings with noggings to be maximum 600mm for all boards. Noggings to be fitted around perimeter of ceiling, around any obtrusions such as columns and between joists to provide board fixing at bound board edges. Joists and noggings to have minimum bearing face of 44mm. Trusses to BS 5268-3 may have bearing face of minimum 38mm.
GTEC Resilient Bar option only: GTEC Resilient Bar to be installed across joists at maximum 450mm centres and fixed to each joist with suitable GTEC Drywall Screws (see screw selector p334). GTEC Resilient Bar to be spliced if necessary by overlapping at joists and fixing both sections to joist. Noggings may be required to provide fixing for full perimeter of GTEC Resilient Bar.
Inclusion of GTEC Resilient Bar is recommended when fixing boards to engineered joists to mitigate potential for differential movement between substrate and board.
INSULATION Any insulation to be of type and thickness to achieve performance and tightly installed in a continuous layer between joists.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
165
166
GTEC® DIRECT-TO-TIMBER CEILING
BOARDING FC-DT-201, 202 & 203P-Board Layout – single layer
GTEC Board to suit required performance SINGLE LAYER
Joists at 400/450 or 600mm centres
Noggings at 1200mm centres to support boards
all board ends to coincide with joists
Perimeter noggings
GTEC Board to suit required performance
boards cut to form staggered joints between layers
DOUBLE LAYER
Joists at 400/450 or 600mm centres
Noggings at 1200mm centres to support edges of second layer of boards
all board ends to coincide with joists
GTEC Base Board only
Perimeter noggings
Stagger all joints
GTEC BASE BOARD ONLY
Joists 50mm wide at max. 406mm centres
all board ends to coincide with joists
No intermediate noggings
Perimeter noggings
PLAN
GTEC® DIRECT-TO-TIMBER CEILING
GTEC Direct-to-Timber Ceiling system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables (p133-p136) and Product Specification (p294-307) to achieve required performance. See High Performance Boards guide p12 for further selection information. Boards to span across joists with bound edges at right angles to joists. Board ends and joints to be centred over joists or intermediate noggings. Boards to be mechanically fixed to perimeter noggings at 150mm centres using appropriate GTEC Drywall Screws. See screw selector p334.
Board joints to be staggered between layers. Any GTEC Fire Board, or other GTEC Type F (BS EN 520) board, required by the system performance, to be installed as the outermost/finishing layer. GTEC Resilient Bar option only: GTEC Resilient Bar is suitable for single and double layer boarding. Boards to be mechanically fixed to GTEC Resilient Bar only at 150mm centres for cut edges and perimeter and at 230mm centres in centre of board and bound edges, using shortest appropriate GTEC Drywall Screws. See screw selector p334. Boards to be fixed to GTEC Resilient Bar only to ensure acoustic performance. Screws must not penetrate through to substrate.
Boards to be mechanically fixed to joists or intermediate noggings at 230mm centres in centre of board or bound edges and at 150mm centres at cut edges, using appropriate GTEC Drywall Screws. See screw selector p334.
JUNCTIONS FC-DT-501S-Junction of partition to ceiling
Abutting partitions to coincide with and fix to joist install additional intermediate ‘pick-up’ joists/noggings as required. coincide partition with joist
GTEC Intumescent Acoustic Sealant
Separate boards at partition head to reduce sound transmission.
screw fix track through to joist
GTEC Partiton System to suit required performance
SECTION
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
167
168
GTEC® DIRECT-TO-TIMBER CEILING
FIXTURES
SYSTEM CONTINUITY
Fixtures and loadings to be suspended from structural soffit/joist and not GTEC Board.
Full, imperforate system continuity to be maintained to achieve rated performances.
Services running through ceiling void to be supported by structural soffit/joist and not GTEC Board.
Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings.
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated ceilings. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire and sound resisting material.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. Where ceiling is not intended to be decorated GTEC Intumescent Sealant to be used to seal board joints. GTEC Finish materials appropriate to board type to be used.
GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
169
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
170
GTEC® ACOUSTIC FLOOR
®
GTEC ACOUSTIC FLOOR SYSTEMS Load bearing timber floors separating dwellings or other spaces have limited sound reduction properties. The GTEC Acoustic Floor, ‘floating floor’ system improves the acoustic performance of these floors with minimal additional depth. The system is installed in a two stage process. GTEC Acoustic Clips temporarily support GTEC Board mounted on GTEC Metal Angle between the joists, until the final floorboard layers are fixed to the plasterboard. The only contact between the board and structure is through GTEC Resilient Tape. The GTEC Acoustic Floor system also enables fire protection for existing, hard to renovate, decorative ceilings by applying GTEC Fire Board from above. Refer to the System Performance Tables on page 137 for full details.
WHERE TO USE: GTEC Acoustic Floors are used for domestic renovation and conversion projects or new build.
FEATURES
BENEFITS
Improved acoustic performance
Meets new build and conversion regulations
Provision of GTEC Fire Board
Cost effective method of achieving required fire rating to existing timber joist flooring
Low profile system design
Minimal addition to floor depth
GTEC® ACOUSTIC FLOOR
TIP: GTEC Acoustic Floor can be built from one side allowing the room and finishes below to be left undisturbed.
Tongue and groove floor boards
GTEC Resilient Tape
GTEC Metal Angle
GTEC Board to suit required performance GTEC Resilient Bar GTEC Acoustic Floor Clip GTEC Board to suit required performance fixed to metal angle only Insulation laid in continuous layer
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
171
172
GTEC速 ACOUSTIC FLOOR
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p137
GTEC Acoustic Floor Clip Metal clips for connecting to wooden joists
RACFC25
GTEC Resilient Tape Self adhesive acoustic isolation tape
RAFT50
GTEC Metal Angle Metal section to brace joists and acoustic floor
MFC
GTEC Resilient Bar Metal profile to provide acoustic separation of board and joists
RBD3000
GTEC Acoustic Floor Self Tapping Screws For attaching plasterboard to metal angle
See screw selector, p334
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating
See compounds guidance, p280
BOARDS
FRAME
FIX
FINISHING
GTEC® ACOUSTIC FLOOR
SYSTEM GUIDANCE FRAME FC-AF-101S-Perimeter detail
GTEC Resilient Tape only point of contact of floorboards
floorboards fixed to GTEC Board and angle only
GTEC Metal Angle GTEC Acoustic Floor Clip at 400mm centres
GTEC Board to suit required performance
GTEC Intumescent Acoustic Sealant
GTEC Resilient Bar spaced at 400mm vertical centres and screw fixed to GTEC C Studs
SECTION
GTEC Acoustic Floor Clips to be fixed to joists at 400mm centres each side of joist. Perimeter joists to be fitted with clips on open side. Joists to be minimum 38mm thick and structurally sound.
GTEC Metal Angle MFC2330 to be fitted into GTEC Acoustic Floor Clips Joists with short leg into clip. Lengths of metal angle to have minimum number of joints with any joints located at clips.
GTEC Acoustic Floor Clips on opposing sides to be fixed at same point where joist width allows and staggered where joist is too narrow.
Where required by system configuration GTEC Resilient Bar to be installed across underside of joists at maximum 450mm centres and fixed to each joist with suitable GTEC Drywall Screws (see screw selector p334).
GTEC Resilient Tape to be fitted along top of joist and any full depth noggings, over clips, to isolate floorboards. GTEC Acoustic Floor Screws to be used to fix floorboard through plasterboard to GTEC Metal Angle.
GTEC Resilient Bar may be spliced by overlapping at joists and fixing both sections to joist. Noggings may be required to provide fixing for full perimeter of GTEC Resilient Bar.
INSULATION Insulation to be of type and thickness to achieve performance and tightly installed in a continuous layer between joists.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
173
174
GTEC® ACOUSTIC FLOOR
BOARDING FC-AF-201S-Assembly stages – 1 and 2
GTEC Acoustic Floor Clip at 400mm centres
GTEC Resilient Tape only point of contact of floorboards
fixing of floorboards into angle through GTEC Board pulls angle clear of clip
GTEC Metal Angle
SECTION FC-AF-202S-Retained ceiling
GTEC Fire Board to suit required performance
GTEC Intumescent Acoustic Sealant 100mm insulation quilt laid over existing ceiling Existing ceiling 100mm strips of GTEC Fire Board fixed to joists
SECTION
GTEC® ACOUSTIC FLOOR
FC-AF-203P-Flooring layout
GTEC Metal Angle 90° GTEC Acoustic Floor Clip
400mm GTEC Board to suit required performance
floorboards laid across joists
GTEC Metal Angle 90° GTEC Acoustic Floor Clip
400mm GTEC Board to suit required performance
floorboards laid across joists
PLAN FC-DC-502S-Junction of ceiling to partition
U track fixed through to joists GTEC Acoustic Floor System
Rock Mineral wool
Partition boards short of floor boards
GTEC Intumescent Acoustic Sealant U track fixed to joists GTEC Twin Frame Partition System to suit required performance
SECTION
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
175
176
GTEC® ACOUSTIC FLOOR
BOARDING continued Boarding to underside of ceiling to follow guidance in GTEC Direct-to-Timber section p162-169. Where required by retained ceiling system configuration 100mm strips of 15mm GTEC Fire Board to be fitted along each side of joists. Further 15mm GTEC Fire Board to be installed to bridge from strip to strip providing a continuous barrier between joists. Select GTEC Board as required by system performance cut 4mm shorter than space between joists, to be temporarily secured to GTEC Metal Angle only at approx. 600mm centres.
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated ceilings. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire and sound resisting material.
Floorboards to be installed across joists and fixed through GTEC Board to GTEC Metal Angle both sides of every joist using appropriate GTEC Acoustic Floor Screws in pattern shown in Construction Detail drawing. Free-floating floor is created when angle is pulled out of clips during fixing of floorboards and GTEC Board to GTEC Metal Angle. Floorboards to be in contact with GTEC Resilient Tape only. Floorboards to be 3mm clear of perimeter wall and sealed with GTEC Acoustic Intumescent Sealant. Softwood floorboards may require gluing to a plywood base to prevent warping.
SYSTEM CONTINUITY Full, imperforate system continuity to be maintained to achieve rated performances. Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
177
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
178
GTEC速 LININGS
179 179
LININGS GTEC Lining systems offer a wide range of plasterboard lining fixing systems to walls and roofs for most typical substrates. Different depths of cavity spaces can be created between the GTEC Board or GTEC Thermal Board lining and underlying wall. These cavities hide services or help to achieve high levels of fire resistance, U-Values and sound insulation.
System Performance Tables GTEC Lining Systems to New External Walls
180
GTEC Lining Systems to Upgrade Internal Walls
182
GTEC Lining Systems to Thermally Upgrade External Walls
184
GTEC Lining Systems to Framed External Walls
187
GTEC Pregybel Independent Lining Systems
190
GTEC GTEC Direct Bond Linings GTEC Contour Linings GTEC Shallow Channel Linings GTEC Dryliner Linings GTEC Independent Wall Linings GTEC Pregybel Independent Linings
192 202 208 216 226 236
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
180
GTEC® LININGS – PERFORMANCE TABLES
GTEC® LINING SYSTEMS TO NEW EXTERNAL WALLS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
0.30
– –
–
Max Height
Min Thickness
U-Value
(m)
(mm)
(W/m2k)
325
RDL 101: Direct Bond or Shallow Channel – see p192 or p208 Facing layer (s): 1x 30mm GTEC Thermal K Board Lining: GTEC Universal Bonding Compound to form 10mm cavity or GTEC Shallow Channel Insulation: 25mm expanded polystyrene (BS 5250) within cavity Internal Wall Leaf: 100mm Celcon Solar Blocks External Wall Leaf: 102mm brick with 75mm cavity
–
RDL 102: Direct Bond or Shallow Channel – see p192 or p208 Facing layer (s): 1x 60mm GTEC Thermal K Board Lining: GTEC Universal Bonding Compound to form 10mm cavity or GTEC Shallow Channel Insulation: – Internal Wall Leaf: 100mm Celcon Solar Blocks External Wall Leaf: 100mm brick with 75mm cavity
–
342
0.26
– –
–
–
–
0.28
– –
–
–
–
0.30
– –
–
RDS 103: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC Standard Board Lining: GTEC Dryliner Channel System Insulation: 120mm glass fibre (BS 5250) Wall Leaf: 100mm concrete blockwork (2300kg/m3) Finish: 100mm brick with 75mm cavity
RDS 104: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC Standard Board Lining: GTEC Dryliner Channel System Insulation: 120mm glass fibre (BS 5250) Wall Leaf: 215mm concrete blockwork (2300kg/m3) Finish: Sand Cement Render
See p191 for notes on alterations to linings configuration.
GTEC® LININGS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
0.28
– –
–
–
0.27
– –
–
-
0.29
– –
–
Max Height
Min Thickness
U-Value
(m)
(mm)
(W/m2k)
–
–
–
–
RDS 108: Dryliner – see p216 Facing Layer(s): 1x 70mm GTEC Thermal K Board Lining: GTEC Dryliner Channel System Insulation: – Wall Leaf: 215mm concrete blockwork (2300kg/m3) Finish: 12mm sand/cement render
RDS 109: Dryliner – see p216 Facing Layer(s): 1x 70mm GTEC Thermal K Board Lining: GTEC Dryliner Channel System Insulation: – Wall Leaf: 215mm brickwork Finish: 12mm sand/cement render
RDS 110: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC Vapour Board Lining: GTEC Dryliner Channel System Insulation: 120mm glass fibre (BS 5250) Wall Leaf: 215mm brickwork Finish: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
181
182
GTEC® LININGS – PERFORMANCE TABLES
GTEC® LINING SYSTEMS TO UPGRADE INTERNAL WALLS
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
–
60 30
65 -7
177
–
30 0
60 -9
–
140
–
– –
49
–
177
–
30 –
59
–
290
–
30 –
62 -17
Max Height
Min Thickness
U-Value
(m)
(mm)
(W/m2k)
–
202
–
RDS 023: Dryliner – see p216 Facing Layer(s): 2x 12.5mm GTEC dB Board Lining: GTEC Dryliner Channel System Insulation: 25mm glass mineral wool 16kg/m³ Wall Leaf: 102mm brickwork Finish: Sand Cement Render
RDS 024: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC dB Board Lining: GTEC Dryliner Channel System Insulation: 25mm glass mineral wool 16kg/m³ Wall Leaf: 102mm brickwork Finish: Sand Cement Render
RDS 031: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC dB Board Lining: GTEC Dryliner Channel System Insulation: – Wall Leaf: 102mm brickwork Finish: None
RDS 032: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC dB Board both sides Lining: GTEC Dryliner Channel System both sides Insulation: 25mm glass mineral wool 16kg/m³ both sides Wall Leaf: 102mm brickwork Finish: –
RDS 021: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC dB Board both sides Lining: GTEC Dryliner Channel System both sides Insulation: 25mm glass mineral wool 16kg/m³ both sides Wall Leaf: 215mm Solid Dense Block 2300kg/m³ Finish: – See p191 for notes on alterations to linings configuration.
GTEC® LININGS – PERFORMANCE TABLES
System Ref.
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
–
30 –
63 -15
0.29
60 60
–
60 60
–
60 60
–
30 30
–
Max Height
Min Thickness
U-Value
(m)
(mm)
(W/m2k)
–
325
IS50Rx
–
RDS 022: Dryliner – see p216 Facing Layer(s): 1x 12.5mm GTEC dB Board Both sides Lining: GTEC Dryliner Channel System Both sides Insulation: 25mm glass mineral wool 16kg/m³ both sides Wall Leaf: 2 x 100mm Solid Dense Block 2300kg/m³ with cavity Finish: –
RCL 004: Independent Wall – see p226 Facing Inner Layer(s): 1x 12.5mm GTEC Fire V Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Lining: GTEC IS50Rx/IS60B/IS70B/IS90B GTEC I Studs at 600mm centres Insulation: 150mm glass fibre (BS 5250) External Wall Leaf: Profiled metal cladding
2.7
Based on IS70B stud
IS60B
3.9 IS70B
4.5 IS90B
5.4
RCL 005: Independent Wall – see p226 Facing Inner Layer(s): 1x 12.5mm GTEC Fire V Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Lining: GTEC IS50Rx/IS60B/IS70B/IS90B GTEC I Studs at 600mm centres Insulation: 140mm glass fibre (BS 5250) External Wall Leaf: 102mm brick or block work
IS50Rx
2.7
–
0.30 Based on IS70B stud
IS60B
3.9 IS70B
4.5 IS90B
5.4
RCL 021: Independent Wall – see p226 Facing Inner Layer(s): 1x 60mm GTEC Thermal K Board Facing Outer Layer(s): 1x 12.5mm GTEC dB Board Lining: GTEC IS50Rx/IS60B/IS70B/IS90B GTEC I Studs at 600mm centres Insulation: 50mm glass fibre (BS5250) External Wall Leaf: 300mm concrete
IS50Rx
2.7
–
0.26 Based on IS50Rx stud
IS60B
3.9 IS70B
4.5 IS90B
5.4
RCL 017: Independent Wall – see p226 Facing Inner Layer(s): 1x 12.5mm GTEC Standard Board Facing Outer Layer(s): 1x 12.5mm GTEC Standard Board Lining: GTEC IS50Rx/IS60B/IS70B/IS90B GTEC I Studs at 600mm centres Insulation: 130mm glass fibre (BS 5250) External Wall Leaf: 102mm brickwork with a of 0.752W/mK
IS50Rx
2.7 IS60B
3.9
–
0.30 Based on IS50Rx stud
IS70B
4.5 IS90B
5.4
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
183
184
GTEC® LININGS – PERFORMANCE TABLES
GTEC® LINING SYSTEMS TO THERMALLY UPGRADE EXTERNAL WALLS
System Ref.
Component
(W/m2k)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
Max Height
Min Thickness
U-Value
(m)
(mm)
RdSAP 01: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Solid brick walls to 1966 and cavity walls pre 1900 Facing Inner Layer(s): 1x 50mm GTEC Thermal K Board
–
–
0.40
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.33
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.28
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
RdSAP 02: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Cavity walls 1900-1975 Facing Inner Layer(s): 1x 50mm GTEC Thermal K Board
–
–
0.38
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.31
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.27
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
RdSAP 03: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Solid brick walls and cavity walls 1976-1982 Facing Inner Layer(s): 1x 40mm GTEC Thermal K Board
–
–
0.40
––
–
Or: 1x 50mm GTEC Thermal K Board
–
–
0.33
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.28
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.24
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
RdSAP 04: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Solid brick walls and cavity walls 1983-1995 Facing Inner Layer(s): 1x 35mm GTEC Thermal XP Board
–
–
0.40
––
–
Or: 1x 55mm GTEC Thermal XP Board
–
–
0.33
––
–
Or: 1x 30mm GTEC Thermal K Board
–
–
0.38
––
–
Or: 1x 40mm GTEC Thermal K Board
–
–
0.31
––
–
Or: 1x 50mm GTEC Thermal K Board
–
–
0.27
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.23
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.21
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
See p191 for notes on alterations to linings configuration.
GTEC® LININGS – PERFORMANCE TABLES
System Ref.
Component
(W/m2k)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
Max Height
Min Thickness
U-Value
(m)
(mm)
RdSAP 05: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Solid brick walls and cavity walls 1996-2002 Facing Inner Layer(s): 1x 22mm GTEC Thermal Board
–
–
0.38
––
–
Or: 1x 30mm GTEC Thermal Board
–
–
0.35
––
–
Or: 1x 40mm GTEC Thermal Board
–
–
0.32
––
–
Or: 1x 50mm GTEC Thermal Board
–
–
0.29
––
–
Or: 1x 27mm GTEC Thermal XP Board
–
–
0.36
––
–
Or: 1x 35mm GTEC Thermal XP Board
–
–
0.33
––
–
Or: 1x 55mm GTEC Thermal XP Board
–
–
0.28
––
–
Or: 1x 30mm GTEC Thermal K Board
–
–
0.31
––
–
Or: 1x 40mm GTEC Thermal K Board
–
–
0.27
––
–
Or: 1x 50mm GTEC Thermal K Board
–
–
0.24
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.21
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.19
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
RdSAP 06: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Solid brick walls and cavity walls 2003-2006 Facing Inner Layer(s): 1x 22mm GTEC Thermal Board
–
–
0.31
––
–
Or: 1x 30mm GTEC Thermal Board
–
–
0.28
––
–
Or: 1x 40mm GTEC Thermal Board
–
–
0.26
––
–
Or: 1x 50mm GTEC Thermal Board
–
–
0.25
––
–
Or: 1x 27mm GTEC Thermal XP Board
–
–
0.29
––
–
Or: 1x 35mm GTEC Thermal XP Board
–
–
0.27
––
–
Or: 1x 55mm GTEC Thermal XP Board
–
–
0.24
––
–
Or: 1x 30mm GTEC Thermal K Board
–
–
0.26
––
–
Or: 1x 40mm GTEC Thermal K Board
–
–
0.23
––
–
Or: 1x 50mm GTEC Thermal K Board
–
–
0.21
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.18
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.17
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
185
186
GTEC® LININGS – PERFORMANCE TABLES
GTEC® LINING SYSTEMS TO THERMALLY UPGRADE EXTERNAL WALLS continued
System Ref.
Component
(W/m2k)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
Max Height
Min Thickness
U-Value
(m)
(mm)
RdSAP 07: Direct Bond or Shallow Channel – see p192 or p208 RdSAP Wall: Solid brick walls and cavity walls 2007-2010 Facing Inner Layer(s): 1x 22mm GTEC Thermal Board
–
–
0.27
––
–
Or: 1x 30mm GTEC Thermal Board
–
–
0.25
––
–
Or: 1x 40mm GTEC Thermal Board
–
–
0.23
––
–
Or: 1x 50mm GTEC Thermal Board
–
–
0.22
––
–
Or: 1x 27mm GTEC Thermal XP Board
–
–
0.25
––
–
Or: 1x 35mm GTEC Thermal XP Board
–
–
0.24
––
–
Or: 1x 55mm GTEC Thermal XP Board
–
–
0.21
––
–
Or: 1x 30mm GTEC Thermal K Board
–
–
0.23
––
–
Or: 1x 40mm GTEC Thermal K Board
–
–
0.21
––
–
Or: 1x 50mm GTEC Thermal K Board
–
–
0.19
––
–
Or: 1x 60mm GTEC Thermal K Board
–
–
0.17
––
–
Or: 1x 70mm GTEC Thermal K Board
–
–
0.16
––
–
Lining: GTEC Universal Bonding Compound to form 10mm cavity
See p191 for notes on alterations to linings configuration.
GTEC® LININGS – PERFORMANCE TABLES
GTEC® LINING SYSTEMS TO FRAMED EXTERNAL WALLS
System Ref.
Fire Perf. BS476-21 BS EN 1365-1 (mins)
Acoustic Perf. Rw dB (Ctr where applicable)
0.30
30 30
51
–
0.29
60 60
53
2.4
–
0.29
30 30
60 -5
Facing Inner Layer(s): 1x 12.5mm GTEC Vapour Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Lining: Sheathing Board. Recommended GTEC Aqua Board Insulation: 120mm glass fibre (BS5250) Internal Wall Leaf: Timber Frame Stud work with GTEC Resilient Bars at 600mm Centres External Wall Leaf: Brickwork
2.4
–
0.29
60 60
61 -4
Facing Inner Layer(s): 1x 12.5mm GTEC Vapour Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Lining: 1 x 15mm GTEC Aqua Board Insulation: 150mm glass fibre (BS 5250) within SFS Internal Wall Leaf: 150mm SFS External Wall Leaf: 100mm brick with 50mm cavity
4.2
–
0.34
60 60
59
Max Height
Min Thickness
U-Value
(m)
(mm)
(W/m2k)
Facing Inner Layer(s): – Facing Outer Layer(s): 1x 15mm GTEC Vapour Fire Board Lining: Sheathing board – Recommended GTEC Aqua Board Insulation: 120mm glass fibre (BS5250) Internal Wall Leaf: Timber Frame Stud work External Wall Leaf: Brickwork
2.4
–
Facing Inner Layer(s): 1x 12.5mm GTEC Vapour Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire Board Lining: Sheathing Board – Recommended GTEC Aqua Board Insulation: 120mm glass fibre (BS5250) Internal Wall Leaf: Timber Frame Stud work External Wall Leaf: Brickwork
2.4
Facing Inner Layer(s): – Facing Outer Layer(s): 1x 15mm GTEC Vapour Fire Board Lining: Sheathing Board. Recommended GTEC Aqua Board Insulation: 120mm glass fibre (BS 5250) Internal Wall Leaf: Timber Frame Stud work with GTEC Resilient Bars at 400mm Centres External Wall Leaf: Brickwork
Component
RFL 002
RFL 003
RFL 015
RFL 016
RFL 051
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
187
188
GTEC® LININGS – PERFORMANCE TABLES
GTEC® ROOF LINING SYSTEMS Fire Perf. BS476-22 BS EN 1364-1 (mins)
U-Value (W/m2k)
9.2
– –
0.17
9.2
– –
0.17
7.2
– –
0.16
Ceiling: 1x 70mm GTEC Thermal K Board Lining: – Insulation: 75mm 10.5kg/m3 glass mineral wool Structure: 47mm x 150mm Joists at 600mm centres with noggings, roofing material above
7.3
– –
0.25
Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire Board Accessories: – Insulation: 100mm glass mineral wool between Trusses, 150mm over Trusses, 10.5kg/m3 Structure: 47mm x 100mm Trusses at 600mm centres with noggings
11
30 30
0.15
Ceiling Inner Layer(s): 1x 12.5mm GTEC Fire V Board Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire V Board Accessories: – Insulation: 100mm glass mineral wool between Trusses, 150mm over Trusses, 10.5kg/m3 Structure: 47mm x 100mm Trusses at 600mm centres with noggings
12
60 30
0.15
Board Weight
System Ref.
Component
(kg/m2)
RIR 001: Pitched roof Ceiling: 1x 70mm GTEC Thermal K Board Lining: – Insulation: 100mm Glass fibre (BS5250) Structure: 47mm x 150mm rafters at 600mm centres with noggings
RIR 002: Pitched roof Ceiling: 1x 70mm GTEC Thermal K Board Lining: – Insulation: 50mm Kooltherm K7 Structure: 47mm x 100mm rafters at 600mm centres with noggings
RIR 003: Horizontal ceiling at roof apex Ceiling: 1x 30mm GTEC Thermal K Board Lining: – Insulation: 100mm Glass fibre over joists, 100mm between joists (BS 5250) Structure: 38mm x 100mm Truss Joists at 600mm centres with noggings
RIR 004: Ceiling under flat roof
RTC 031
RTC 032
See p191 for notes on alterations to linings configuration.
GTEC® LININGS – PERFORMANCE TABLES
Board Weight
System Ref.
(kg/m2)
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
U-Value (W/m2k)
RTC 033 Ceiling Inner Layer(s): – Ceiling Outer Layer(s): 1x 12.5mm GTEC Fire V Board Accessories: – Insulation: 100mm glass mineral wool between Trusses, 150mm over Trusses, 10.5kg/m3 Structure: 38mm x 100mm Trusses at 600mm centres with noggings
11
30 30
0.15
Ceiling Inner Layer(s): 1x 15mm GTEC Fire V Board Ceiling Outer Layer(s): 1x 15mm GTEC Fire Board Accessories: – Insulation: 100mm glass mineral wool between Trusses, 150mm over Trusses, 10.5kg/m3 Structure: 38mm x 100mm Trusses at 600mm centres with noggings
26
60 60
0.15
RTC 034
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
189
190
GTEC® LININGS – PERFORMANCE TABLES
GTEC® PREGYBEL INDEPENDENT LINING SYSTEMS
System Ref.
Acoustic Absorption Class, BS EN ISO 11654
Absorption co-efficient (_w), BS EN ISO 11654
12
B
0.8
12
C
0.75
12
C
0.70
12
B
0.60
12
C
0.7
12
C
0.65
Max Height
Weight
(m)
(kg/m2)
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
Component
PGL 001: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 75mm glass mineral wool and 600mm void
PGL 002: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 50mm glass mineral wool and 600mm void
PGL 003: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 50mm glass mineral wool and 300mm void
PGL 004: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel C10no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 300mm void
PGL 101: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel R12no2 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 50mm glass mineral wool and 300mm void
PGL 102: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel R12no2 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 300mm void
See p191 for notes on alterations to linings configuration.
GTEC® LININGS – PERFORMANCE TABLES
System Ref.
Acoustic Absorption Class, BS EN ISO 11654
Absorption co-efficient (_w), BS EN ISO 11654
12
C
0.70
12
C
0.7
12
C
0.60
12
D
0.50
12
D
0.55
12
D
0.55
Max Height
Weight
(m)
(kg/m2)
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
IS50Rx
2.7
IS60B
3.9
IS70B
4.5
IS90B
5.4
Component
PGL 201: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel R15no1 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 50mm glass mineral wool and 300mm void
PGL 202: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel R15no1 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 30mm glass mineral wool and 50mm void
PGL 301: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel R15no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 50mm glass mineral wool and 300mm void
PGL 302: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel R15no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 300mm void
PGL 401: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel L5x80no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 80mm glass mineral wool and 300mm void
PGL 402: Pregybel Lining – see p236 Ceiling Outer Layer(s): 1x GTEC Pregybel L5x80no8 Lining: GTEC IS50Rx/IS60B/IS70B/ IS90B GTEC I Studs at 600mm centres Insulation: 80mm glass mineral wool and 100mm void
LININGS PERFORMANCE NOTES Performance values are for imperforate, jointed systems using Siniat GTEC components (metal studs and tracks, boards, metal accessories, screws and finishing systems) and specified insulation quilt material (type, thickness and density) and installed to Siniat specification and installation guides. All calculations are in accordance with Building Regulations: Conservation of fuel and power, Approved Document L: 2010.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
191
192
GTEC® DIRECT BOND LINING
®
GTEC DIRECT BOND LINING SYSTEMS The GTEC Direct Bond Lining system is the simplest option for single layer drylining of masonry substrates. It provides a clean, flat and easy to finish surface by bonding GTEC Board to the masonry substrate. This construction method reduces drying out time speeding up internal fit-out. The system uses GTEC Universal Bonding Compound to directly attach GTEC Plasterboards to the wall and corrects minor surface irregularities. GTEC Thermal Boards can also be bonded to increase thermal performance through the wall.
WHERE TO USE: GTEC Direct Bond Lining systems are used in new build residential and general renovation projects.
FEATURES
BENEFITS
Few products required
Low installation cost
Limited increase in wall thickness
Minimal effect on room size and achieves the required finish
Service cavity of 10-25mm can be created
Allows installation of conduits and small services
Suitable for GTEC Thermal Boards
One-fix method of achieving required thermal performance
Workable bonding compound
Easily achieves air tightness by bonding around the wall perimeter Allows adjustment during boarding
Bonds to the majority of masonry substrates
Suits most construction projects and corrects surface irregularities
GTEC速 DIRECT BOND LINING
193
non-laminated GTEC Board to suit required performance
continuous bonding compound ribbon 50mm from top of board
250 x 75mm dab of GTEC Universal Bonding Compound
cut board to receive socket box
continuous dab around socket boxes
max. spacing of 600mm continuous bonding compound ribbon 50mm from base of board
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
194
GTEC速 DIRECT BOND LINING
TIP: With GTEC Thermal Boards the wall surface and insulation is installed in one operation.
continuous bonding compound ribbon 50mm from top of board GTEC Thermal Board to suit required performance
GTEC Universal Bonding Compound
GTEC Nailable Plug
continuous dab around socket boxes cut board to receive socket box
max. spacing of 400mm continuous bonding compound ribbon 50mm from base of board
GTEC速 DIRECT BOND LINING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards, except GTEC Aqua Board and GTEC Vapour Board Provides wall surface suitable for finishing.
See performance tables, p180-191
All GTEC Thermal Boards Provides wall surface suitable for finishing and thermal insulation
See performance tables, p180-191
BOARDS
FRAME None required
FIX GTEC Universal Bonding Compound Directly bonds plasterboard to walls
n/a
GTEC Nailable Plug Mechanical secondary fixing of GTEC Thermal Boards
n/a
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
FINISHING
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
195
196
GTEC® DIRECT BOND LINING
SYSTEM GUIDANCE SUBSTRATE GTEC Direct Bond Lining system is suitable for most level, masonry substrates. All substrates to be clean and dust free with all loose material removed. All grease, oil and contaminants to be removed; chemical cleaning may be required. Substrate treatment for bonding: Substrate
Treatment
Very low suction
May require mechanical fixing
Low and medium suction
None
High suction
PVAC bonding agent
All loose plasterwork to be removed. Existing plasterwork in good condition may be suitable for GTEC Direct Bonding provided all paint has been removed and adequate key is established by treating with a PVAC bonding agent according to manufacturer’s instructions. Substrates subject to moisture ingress to use mechanical fixing system. External solid walls with render finishes exposed to severe frosts are not suitable for bonding.
BONDING LG-DB-181S-Base detail
LG-DB-180M-Dab sizing -75 50 25
GTEC Board to suit required performance
50
continuous ribbon of GTEC Universal Bonding Compound to support skirting
0 25 GTEC Universal Bonding Compound
GTEC Intumescent Acoustic Sealant
ISOMETRIC LG-DB-182S-Base detail – GTEC Thermal Boards
SECTION LG-DB-183S-Head detail
GTEC Thermal Board to suit required performance
continuous ribbon of GTEC Universal Bonding Compound to support skirting
Continuous ribbon of GTEC Universal Bonding Compound
GTEC Board to suit required performance
GTEC Intumescent Acoustic Sealant
SECTION
SECTION
GTEC® DIRECT BOND LINING
LG-DB-184S-Head detail – GTEC Thermal Boards
Continuous ribbon of GTEC Universal Bonding Compound
GTEC Thermal Board to suit required performance
SECTION SECTION
Boards to be fixed to substrate using GTEC Universal Bonding Compound. Minimum 20% contact area between boards and dabs. Bonding dabs to be:
Continuous ribbons of bonding compound to be provided 50mm from head and base of each board and around perimeter of walls to ensure air-tightness and provide robust fixing for trims. Socket boxes to be surrounded by continuous ribbon of bonding compound.
250mm x 50-75mm. Minimum 10mm thick and up to 25mm to provide board levelling. At 600mm maximum horizontal centres and 300mm maximum vertical centres. At 400mm maximum horizontal centres and 300mm vertical centres for GTEC Thermal Boards. Minimum of three ‘columns’ of dabs per board. Minimum 25mm from board edges.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
197
198
GTEC® DIRECT BOND LINING
BOARDING LG-DB-201E-Nailable plug arrangement
The GTEC Direct Bond lining system is suitable for single layer boarding only.
1200mm
25mm
300mm
Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables, p180-191, and Product Specification, p294-307 to achieve required performance. See High Performance Boards guide p12 for further selection information. GTEC Vapour Board and GTEC Aqua Board cannot be bonded using the GTEC Direct Bond lining system. Boards to be 5mm less than floor to ceiling height. Thermal Boards only: Select GTEC Thermal Board type and thickness according to desired thermal value and requirement for vapour barrier.
2100mm
GTEC Thermal Board thickness may be reduced by utilising higher insulation grade boards, e.g. GTEC Thermal K Board. Retain each GTEC Thermal Board with two GTEC Nailable Plugs to suit board depth, fitted through holes drilled in board, through cavity and penetrating 25mm into masonry substrate. Render or plaster should not be regarded as a stable substrate for GTEC Nailable Plug penetration.
ELEVATION
MOVEMENT CONTROL JOINTS Form movement control joints at maximum 10m intervals in the lining run. Form movement control joints where the lining crosses a structural movement joint.
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples. Continuous ribbon of GTEC Universal Bonding Compound to be provided either side of movement control joint.
GTEC® DIRECT BOND LINING
OPENINGS LG-DB-402P-Door jamb
LG-DB-401P-Window reveal
GTEC Board to suit required performance
Continuous ribbon of GTEC Universal Bonding Compound GTEC Corner 90º External / GTEC Flex Tape
Continuous ribbon of GTEC Universal Bonding Compound
GTEC Board to suit required performance
PLAN
PLAN
LG-DB-403P-Window reveal – GTEC Thermal Boards
Thinner, higher grade of GTEC Thermal Board to reduce reveal depth
Continuous ribbon of GTEC Universal Bonding Compound
GTEC Corner 90º External / GTEC Flex Tape GTEC Thermal Board to suit required performance
PLAN
See Construction Details Drawings for further guidance on arrangement and fixing.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
199
200
GTEC® DIRECT BOND LINING
CORNERS AND JUNCTIONS LG-DB-502P-Internal corner – GTEC Thermal Boards
LG-DB-501P-Internal corner
Continuous ribbon of GTEC Universal Bonding Compound
Continuous ribbon of GTEC Universal Bonding Compound
GTEC Thermal Board to suit required performance
GTEC Board to suit required performance
PLAN LG-DB-503P-External corner
PLAN PLAN
LG-DB-504P-External corner – GTEC Thermal Boards GTEC Corner 90º External / GTEC Flex Tape
GTEC Corner 90º External / GTEC Flex Tape
Continuous ribbon of GTEC Universal Bonding Compound Continuous ribbon of GTEC Universal Bonding Compound GTEC Board to suit required performance
GTEC Thermal Board to suit required performance
10-25mm GTEC Universal Bonding Compound dabs GTEC Universal Bonding Compound dabs
PLAN LG-DB-505P-Partition junction
PLAN LG-DB-506P-Partition junction – GTEC Thermal Boards Continuous ribbon of GTEC Universal Bonding Compound
Continuous ribbon of GTEC Universal Bonding Compound
Mineral wool insulation to improve continuity of thermal layer
GTEC Partition System to suit required performance
GTEC Partition System to suit required performance
GTEC Board to suit required performance GTEC Thermal Board to suit required performance
PLAN
PLAN
GTEC® DIRECT BOND LINING
See Construction Details Drawings for further guidance on arrangement and fixing.
FINISHING
FIXTURES
All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used.
PENETRATIONS
All fixtures to be fixed through to substrate using appropriate fixings.
SYSTEM CONTINUITY Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings.
M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated linings.
GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings.
Full, imperforate system continuity to be maintained to achieve rated performances.
Protect all electrical cables in cavity with conduit.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
201
202
GTEC® CONTOUR LINING
®
GTEC CONTOUR LINING SYSTEMS The GTEC Contour Lining system is a simple and fast means of renovating flat walls which simply need a new, consistently smooth finish e.g. tiled or plastered walls which have become scuffed or chipped. The system uses GTEC Wall Lining Adhesive to directly attach light and strong GTEC Contour Board to the substrate. It provides a smooth surface by boarding over existing finishes but will not correct substrates which are out of plumb. Once complete, the system provides a smooth and easy to finish plasterboard surface in the minimum thickness.
WHERE TO USE: GTEC Contour Board Lining system is suitable for use over existing wall finishes such as distressed tiled walls.
FEATURES
BENEFITS
8mm total lining thickness
Minimum increase in wall thickness
Quick curing adhesive
Can be jointed and finished quickly after initial installation
High strength adhesive
No need to remove firmly attached plasterwork or tiling from the substrate
Lightweight board
Easy to install
GTEC速 CONTOUR LINING
TIP: Thin, but strong, GTEC Contour Board is ideal for resurfacing but also excellent for curved partitions, see p70.
GTEC Contour Board
GTEC Wall Lining Adhesive 25 x 25mm dabs at 300mm horizontal and vertical centres
flat, smooth substrate requiring refurbishment of surface only
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
203
204
GTEC速 CONTOUR LINING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
BOARDS All GTEC Boards, except GTEC Aqua Board and GTEC Vapour Board Provides wall surface suitable for finishing
GTEC Contour Board Provides wall surface suitable for finishing in minimum thickness
FRAME None required
FIX GTEC Wall Lining Adhesive Ready mixed adhesive for direct bonding to substrate
n/a
GTEC Nailable Plug Mechanical secondary fixing of GTEC Contour Boards
n/a
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
FINISHING
GTEC® CONTOUR LINING
SYSTEM GUIDANCE SUBSTRATE GTEC Contour Lining system is suitable for most flat, level, secure substrates not subject to moisture ingress which require only surface renovation. All substrates to be clean with all loose material, wallpaper and protrusions removed. All contaminants to be removed from ceramic tiles.
Substrate treatment for bonding:
Substrate
Treatment
Low suction / dusty
May require PVAC bonding agent
Medium suction
Coarse sanding
High suction
n/a
BONDING Boards to be fixed to substrate using GTEC Wall Lining Adhesive. Bonding dabs to be: 25mm x 25mm. 2mm thick after board application. At 300mm maximum horizontal and vertical centres. Minimum 25mm from board edges.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
205
GTEC® CONTOUR LINING
BOARDING LG-CN-201E-Nailable plug arrangement
25mm
600mm
1600mm
800mm
1200mm
206
ELEVATION
The GTEC Contour Board lining system is suitable for single layer boarding only. The GTEC Contour Lining system is designed for use with 6mm GTEC Contour Board only.
Thermal Boards only: GTEC Contour Lining system is not suitable for use with GTEC Thermal Boards.
Boards to be 5mm less than floor to ceiling height. Retain each GTEC Contour Board with five GTEC Nailable Plugs to suit board depth, fitted through holes drilled in board, penetrating 25mm into substrate. Render or plaster should not be regarded as a stable substrate for GTEC Nailable Plug Penetration.
MOVEMENT CONTROL JOINTS Form movement control joints at maximum 10m intervals in the lining run. Form movement control joints where the lining crosses a structural movement joint. Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used.
FIXTURES All fixtures to be fixed through to substrate using appropriate fixings.
SYSTEM CONTINUITY The substrate behind the GTEC Contour Lining system must provide the fire, acoustic and thermal performance required by the wall element, GTEC Contour Board is a surface renovation board only.
207
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
208
GTEC® SHALLOW WALL LINING
®
GTEC SHALLOW WALL LINING SYSTEMS The GTEC Shallow Wall Lining system is an alternative to the GTEC Direct Bond Lining system. It provides a mechanical fix for boards which are unsuitable for use with GTEC Universal Bonding Compound. It can also create a fully mechanically fixed option where the substrate cannot be bonded, such as some concrete walls. The system uses GTEC Universal Bonding Compound to attach GTEC Shallow Wall Channels to the substrate providing a fixing surface for GTEC Boards. When bonded, it can correct minor surface irregularities through minimal levelling adjustment of the shallow channel before the dabs have cured. Alternatively, the GTEC Shallow Wall Channels can be fixed directly into the substrate.
WHERE TO USE: The GTEC Shallow Wall Lining system is suitable for most project types and masonry substrates.
FEATURES
BENEFITS
Plasterboard finish
Easy to decorate flat surface
Intermittent cavity up to 25mm deep
Space for small conduits and services
Mechanical board fixing
Substrate for all GTEC Boards
Mechanical or adhesive channel fixing
Fixes to most substrates
Compatible with GTEC Thermal Boards
Improves U-values
Perforated channel for bonding key
Strong and easy to fix
GTEC® SHALLOW WALL LINING
TIP: GTEC Aqua Board is an extremely water resistant plasterboard, ideal for wet rooms.
GTEC Aqua Board or Vapour Board or other to suit required performance
channel continuously fixed around openings and perimeter
250mm dabs at max. 450mm centres
GTEC Shallow Wall Channel bonded or mechanically fixed to wall
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
209
210
GTEC速 SHALLOW WALL LINING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing in minimum thickness
See performance tables, p180-191
All GTEC Thermal Boards Provides wall surface suitable for finishing and thermal insulation
See performance tables, p180-191
GTEC Shallow Wall Channel Dabbed or fixed to wall to provide fixing substrate for boards
MFCS/RX
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
GTEC Universal Bonding Compound Gypsum based compound for bonding GTEC Shallow Wall Channel to walls. Suitable for GTEC thermal boards
n/a
GTEC Drywall Screws (as appropriate) For mechanical fixing of boards to GTEC Shallow Wall Channel
See screw selector, p334
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
BOARDS
FRAME
FIX
FINISHING
GTEC® SHALLOW WALL LINING
SYSTEM GUIDANCE SUBSTRATE GTEC Shallow Wall Lining system is suitable for most level, masonry substrates and may be bonded or mechanically fixed. All substrates to be clean and dust free with all loose material removed. All grease, oil and contaminants to be removed; chemical cleaning may be required. Substrate treatment for bonding: Substrate
Treatment
Very low suction
May require mechanical fixing
Low and medium suction
None
High suction
PVAC bonding agent
All loose plasterwork to be removed. Existing plasterwork in good condition may be suitable for GTEC Universal Bonding Compound provided all paint has been removed and key is established by treating with a PVAC bonding agent according to manufacturer’s instructions. Substrates subject to moisture ingress require mechanical fixing of GTEC Shallow Wall Channels. External solid walls with render finishes exposed to severe frosts are not suitable for bonding.
FRAME LG-ML-102S-Base Detail
LG-ML-101S-Head Detail GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
GTEC Universal Bonding Compound
GTEC Universal Bonding Compound
screw fix plasterboard to channel at 300mm centres
screw fix plasterboard to channel at 300mm centres GTEC Shallow Wall Channel Max. 80mm
GTEC Shallow Wall Channel GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
SECTION LG-DB-180M-Dab sizing
SECTION LG-ML-181M-Mechanical fixing
-75 50 25 GTEC Shallow Wall Channel mechanically fixed to substrate
50
0 25 GTEC Universal Bonding Compound
ISOMETRIC
board fixed to channel at max. 300mm centres
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
211
212
GTEC® SHALLOW WALL LINING
FRAME continued GTEC Shallow Wall Channel to be fixed to substrate in continuous vertical lengths at 600mm horizontal centres using dabs of GTEC Universal Bonding Compound or mechanically fixed using appropriate fixings by others. GTEC Shallow Wall Channels may be shot fired to dense substrates following fixing manufacturer’s instructions. Horizontal lengths of GTEC Shallow Wall Channel to be fixed maximum 50mm from head and base of lining.
Bonding dabs to be: 250mm x 50-75mm. Minimum 10mm thick and up to 25mm to provide board levelling. At 450mm maximum vertical centres. Minimum of two dabs per channel not exceeding vertical centres above. Minimum 25mm from board edges. Continuous ribbons of bonding compound to be provided 50mm from head and base of board and around perimeter of walls and openings to provide fixing for horizontal channel. Socket boxes to be surrounded by continuous ribbon of bonding compound.
BOARDING The GTEC Shallow Wall lining system is suitable for single layer boarding only. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables, p180-191, and Product Specification, p294-307, to achieve required performance. See High Performance Boards guide p12 for further selection information. Boards to be 5mm less than floor to ceiling height. Board edges to be centred over channels. Boards to be mechanically fixed to channels at 300mm centres using appropriate GTEC Drywall Screws. See screw selector p334.
Height of GTEC Shallow Wall linings should not exceed two boards in height in one operation. Safety precautions should be taken when bonding boards above single board height. Thermal Boards only: Select GTEC Thermal Board type and thickness according to desired thermal value and requirement for vapour barrier. GTEC Thermal Board thickness may be reduced by utilising higher insulation grade boards, e.g. GTEC Thermal K Board.
GTEC® SHALLOW WALL LINING
MOVEMENT CONTROL JOINTS LG-ML-301P-Movement joint
GTEC Universal Bonding Compound
Max. 80mm
Max. 80mm
GTEC Shallow Wall Channel
GTEC Board to suit required performance
GTEC Movement Control Joint 10mm
PLAN
Form movement control joints at maximum 10m intervals in the lining run. Form movement control joints where the lining crosses a structural movement joint.
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
OPENINGS AND CORNERS LG-ML-401P-Window reveal
LG-ML-402P-Door jamb
GTEC Board to suit required performance
GTEC Universal Bonding Compound
GTEC Board to suit required performance GTEC Universal Bonding Compound GTEC Corner 90º External / GTEC Flex Tape
GTEC Shallow Wall Channel
GTEC Shallow Wall Channel
PLAN
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
213
GTEC® SHALLOW WALL LINING
OPENINGS AND CORNERS continued LG-ML-501P-Internal corner
LG-ML-502P-External corner fix board to channel at 300mm centres
fix board to channel at 300mm centres
GTEC Corner 90º External / GTEC Flex Tape
GTEC Universal Bonding Compound
GTEC Universal Bonding Compound
GTEC Shallow Wall Channel GTEC Shallow Wall Channel
GTEC Board to suit required performance
PLAN
GTEC Board to suit required performance
PLAN
LG-ML-503P-Junction with partition
Max. 80mm
GTEC Shallow Wall Channel
GTEC Intumescent Acoustic Sealant
Max. 80mm
214
GTEC Partition System
GTEC Board to suit required performance
PLAN
GTEC Shallow Wall Channel to be fixed vertically and horizontally around openings to provide maximum 50mm of unsupported board.
At corners GTEC Shallow Wall Channel to be fixed vertically to provide maximum 50mm of unsupported board.
GTEC® SHALLOW WALL LINING
FINISHING
FIXTURES
All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used
PENETRATIONS
All fixtures to be fixed through to substrate using appropriate fixings.
SYSTEM CONTINUITY Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings.
M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated linings.
GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings.
Full, imperforate system continuity to be maintained to achieve rated performances.
Protect all electrical cables in cavity with conduit.
Where channels are mechanically fixed there are no inherent restrictions on height providing board loads are fully transferred to substrate.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
215
216
GTEC® DRYLINER LINING
®
GTEC DRYLINER LINING SYSTEMS The GTEC Dryliner Lining system is a fully dry, light frame, drylining system. The cavity created behind the boards allows for heavier services and sound or thermal insulation. For stable, high performance drylining, the system uses GTEC Dryliner Brackets fixed to the substrate to support a frame of GTEC Dryliner Channel and Tracks. Once complete, the GTEC Dryliner Lining system provides a clean, flat and easy to finish plasterboard surface with superior technical performance than shallow lining systems.
WHERE TO USE: The GTEC Dryliner Lining system is ideal for most stable substrates where continuous cavities behind boards of up to 130mm are required and/or where high levels of substrate correction are needed.
FEATURES
BENEFITS
Plasterboard finish
Easy to decorate flat surface
Cavity up to 130mm deep
Space for heavy duty services and insulation
Mechanical fixing board
Fixes all GTEC Boards
Cavity frame design
Achieves higher technical performances
Mechanical fixing bracket
Fixes to most stable substrates
Compatible with GTEC Thermal Boards
Improves U-values
Adjustable bracket design
Can adjust depth for high level of substrate correction
GTEC速 DRYLINER LINING
TIP: The GTEC Drywall Screw range has been improved, see the Screw Selector Guide on p334. GTEC Dryliner Track m 0m 0 6 x. Ma GTEC Dryliner Channel
Max. 800mm
GTEC Dryliner Brackets to suit cavity depth
GTEC Board to suit required performance
GTEC Intumescent Acoustic Sealant
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
217
218
GTEC速 DRYLINER LINING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides ceiling surface suitable for finishing
See performance tables, p180-191
All GTEC Thermal Boards Provides wall surface suitable for finishing and thermal insulation
See performance tables, p180-191
GTEC Dryliner Channel A galvanised steel furring channel for plasterboard fixing
RD1
GTEC Dryliner Channel Connector A galvanised clip used to join sections of GTEC Dryliner Channel
RD3
GTEC SR bracket Adjustable bracket to brace GTEC Dryliner Channel to substrate
RD2
GTEC XR bracket Adjustable, extended reach bracket to brace GTEC Dryliner Channel to substrate
RD11
GTEC Dryliner Track J shaped metal section used as a track and perimeter channel
RD9
GTEC Metal Angle Multi-purpose metal section
MFC2330, MFC2525, MFC2550
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
Mineral wool insulation Increases fire and acoustic insulation performance
See performance tables supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
BOARDS
FRAME
INSULATION
FIX
GTEC® DRYLINER LINING
System Component
System primary use
Product Reference
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
FINISHING
SYSTEM GUIDANCE SUBSTRATE GTEC Dryliner Lining system is suitable for most stable substrates where fixing of bracket will be structurally secure.
GTEC Independent Wall Lining system to be used for substrates subject to uncontrolled moisture ingress.
Finished substrates may be fixed to provided bracket fixing penetrates into structure.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
219
GTEC® DRYLINER LINING
FRAME LG-DY-102S-Head detail – GTEC Thermal Boards
LG-DY-002P-Cavity size range
GTEC Intumescent Acoustic Sealant
GTEC Standard Reach Dryliner Bracket
Max. 800mm
Max. 60mm
GTEC Dryliner Track
screw fix plasterboard to channel at 300mm centres
GTEC Thermal Board to suit required performance
GTEC Dryliner Channel
GTEC Dryliner Brackets to suit required cavity depth
Min. 25mm
GTEC Standard Reach Dryliner Bracket
SECTION LG-DY-104S-Base detail – GTEC Thermal Boards GTEC Dryliner Brackets to suit required cavity depth
GTEC Extended Reach Dryliner Bracket
Max. 800mm
Max. 130mm
GTEC Dryliner Channel
GTEC Thermal Board to suit required performance
screw fix plasterboard to channel at 300mm centres
GTEC Dryliner Track GTEC Intumescent Acoustic Sealant
SECTION
SECTION LG-DY-101S-Head detail
LG-DY-103S-Base detail
GTEC Intumescent Acoustic Sealant
GTEC Dryliner Brackets to suit required cavity depth
GTEC Dryliner Track
screw fix plasterboard to channel at 300mm centres
GTEC Board to suit required performance
Max. 800mm
GTEC Dryliner Channel
Max. 800mm
220
GTEC Board to suit required performance
screw fix plasterboard to channel at 300mm centres
GTEC Dryliner Channel GTEC Dryliner Track GTEC Dryliner Brackets to suit required cavity depth
SECTION
GTEC Intumescent Acoustic Sealant
SECTION
GTEC® DRYLINER LINING
GTEC Dryliner Track to be fixed to structure at perimeter of lining run. Fix at 600mm centres using appropriate fixings. Allow for board depth when positioning channel and to achieve required cavity depth. Select GTEC Dryliner Brackets (SR and XR) to suit cavity depth required: GTEC Dryliner Bracket
Cavity Depth Range
GTEC SR Bracket
25mm-60mm
GTEC XR Bracket
25mm-130mm
GTEC Dryliner Channel to be positioned at maximum 600mm centres for GTEC Board and at maximum 400mm horizontal centres for GTEC Thermal Boards.
GTEC Dryliner Brackets to fixed to structure in a line at maximum 800mm vertical centres to receive GTEC Dryliner Channel: GTEC SR and XR Brackets to be fixed using appropriate structural fixing supplied by others. GTEC Dryliner Channel to be 5mm shorter than floor to ceiling height, located into GTEC Dryliner Track. GTEC Dryliner Channel to be attached to both GTEC Dryliner Bracket legs with appropriate GTEC Drywall Screws (see screw selector p334) and levelled by adjusting brackets. Excess bracket leg length to be removed or bent back. GTEC Dryliner Channel may be spliced if necessary using GTEC Dryliner Channel Connector.
INSULATION Any insulation to be of type and thickness to achieve performance and tightly installed in a continuous layer between brackets and behind channels.
Where insulation may be expected to slump suspend from GTEC Insulation Hold strips 150mm from top of partition and at 1200mm vertical centres. 10mm clear gap to be maintained between substrate and insulation.
BOARDING The GTEC Dryliner lining system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables, p180-191, and Product Specification, p294-307, to achieve required performance. See High Performance Boards guide p12 for further selection information. Boards to be 5mm less than floor to ceiling height. Board edges to be centred over channels. Boards to be mechanically fixed to channels and track at 300mm centres using appropriate GTEC Drywall Screws. See screw selector p334. Board joints to be staggered between layers.
Over-height single layer boarding: Where partition height exceeds board height fix boards to continuous band of GTEC Flat Strap FS90/W or GTEC MFIX behind all horizontal joints to maintain fire integrity. Over-height multiple layer boarding only: Where partition height exceeds board height for double or multiple layer boarding fix outer layer of boards to continuous band of GTEC Flat Strap FS50/RX behind all horizontal joints. Thermal Boards only: Select GTEC Thermal Board type and thickness according to desired thermal value and requirement for vapour barrier. GTEC Thermal Board thickness may be reduced by utilising higher insulation grade boards, e.g. GTEC Thermal K Board.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
221
222
GTEC® DRYLINER LINING
MOVEMENT CONTROL JOINTS LG-DY-301P-Movement joint Max. 50mm
LG-DY-302P-Movement joint – GTEC Thermal Boards Max. 50mm
Max. 50mm
Max. 50mm
50mm Rock Mineral wool insulation 40kg/m3 (if fire rated system)
Mineral Wool insulation
GTEC Board to suit required performance
GTEC Movement Control Joint 10mm
GTEC Thermal Board to suit required performance
GTEC Movement Control Joint 10mm
PLAN
Form movement control joints at maximum 10m intervals in the lining run. Form movement control joints where the lining crosses a structural movement joint.
PLAN
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
OPENINGS AND CORNERS LG-DY-401P-Window reveal
LG-DY-402P-Window reveal – GTEC Thermal Boards
GTEC Dryliner Track
GTEC Dryliner Track Thinner, higher grade of GTEC Thermal Board to reduce reveal depth
GTEC Board to suit required performance GTEC Metal Angle
GTEC Dryliner Brackets to suit required cavity depth
GTEC Corner 90º External / GTEC Flex Tape GTEC Dryliner Channel GTEC Dryliner Brackets to suit required cavity depth
GTEC Metal Angle
GTEC Corner 90º External / GTEC Flex Tape GTEC Dryliner Channel
PLAN
PLAN
GTEC® DRYLINER LINING
LG-DY-501P-Internal Corner
LG-DY-502P-Internal corner – GTEC Thermal Boards
GTEC Intumescent Acoustic Sealant GTEC Intumescent Acoustic Sealant fold bracket over channel and fix to suit corners
fold bracket over channel and fix to suit corners
GTEC Dryliner Channel GTEC Dryliner Channel GTEC Dryliner Brackets to suit required cavity depth
GTEC Dryliner Brackets to suit required cavity depth GTEC Thermal Board to suit required performance
GTEC Board to suit required performance
PLAN LG-DY-503P-External corner
PLAN LG-DY-504P-External corner – GTEC Thermal Boards
25mm
25mm
GTEC Corner 90º External / GTEC Flex Tape
GTEC Corner 90º External / GTEC Flex Tape
GTEC Metal Angle fixed to the track GTEC Metal Angle fixed to the track GTEC Dryliner Channel
GTEC Dryliner Brackets to suit required cavity depth
GTEC Dryliner Channel
GTEC Dryliner Brackets to suit required cavity depth
GTEC Board to suit required performance
GTEC Board to suit required performance
PLAN LG-DY-505P-Partition junction
PLAN LG-DY-506P-Partition junction – GTEC Thermal Boards
GTEC Dryliner Brackets to suit required cavity depth
GTEC Dryliner Brackets to suit required cavity depth GTEC Dryliner Channel
GTEC Dryliner Channel
GTEC Partition System to suit required performance
GTEC Partition System to suit required performance
Rock wool insulation to improve continuity of thermal layer at first stud
GTEC Intumescent Acoustic Sealant
GTEC Intumescent Acoustic Sealant GTEC Board to suit required performance
GTEC Thermal Board to suit required performance
PLAN
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
223
224
GTEC® DRYLINER LINING
OPENINGS AND CORNERS continued LG-DY-507P-Change in lining depth
GTEC Dryliner Bracket to suit required depth
GTEC Dryliner Channel fix plasterboard to channel at 150mm centres
GTEC Board to suit required performance
GTEC Corner 90º External / GTEC Flex Tape
SECTION
At external corners GTEC Dryliner Channel and brackets to be positioned maximum of 25mm from edge of substrate. GTEC Metal Angle to be fixed to head and base track to provide internal reinforcement and fixing substrate.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used.
FIXTURES Fixtures may be fixed through to substrate using appropriate fixings or fixed through board to channels. Fixtures may be attached directly to board provided adequate provision has been made. See guidance in GTEC C Stud Partitions section, p67.
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated linings. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings. Protect all electrical cables in cavity with conduit.
SYSTEM CONTINUITY Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission. Full, imperforate system continuity to be maintained to achieve rated performances. There are no inherent restrictions on height provided loads are fully transferred to substrate. Contact Technical Enquiryline for further guidance.
225
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
226
GTEC® INDEPENDENT WALL LINING
®
GTEC INDEPENDENT WALL LINING SYSTEMS Based on the GTEC C Stud Partition system, the GTEC Independent Wall Lining system is a fully dry, light frame, drylining system. It is completely separated from the underlying substrate. The GTEC Independent Wall Lining system combines GTEC Boards with GTEC I or C Studs fixed into GTEC U Tracks. The cavity created behind the boards can be of any depth. This allows for heavy services, ducting, and insulation. Once complete, the GTEC Independent Wall Lining system provides a clean, flat and easy to finish plasterboard surface, offering the highest technical performances.
WHERE TO USE: Ideal for commercial projects where deep continuous cavities behind boards are needed to correct or isolate substrates and accommodate services. Particularly suited to substrates which may not be suitable for direct fixing, e.g. metal cladding and other modern methods of construction.
FEATURES
BENEFITS
Plasterboard finish
Easy to decorate flat surface
Completely variable cavity depth
Provides space for heavy duty services and the highest levels of insulation
Mechanical board fixing
Fix all GTEC Boards
Cavity frame design
Achieves higher technical performances
Based on GTEC Metal C Stud system
Reliable and commonly used
Completely independent from substrate
No thermal bridging created
Drylines any substrate
Can adjust depth for high level of substrate correction
Creates false wall
Upgrade existing structures
GTEC® INDEPENDENT WALL LINING
TIP: ‘False walls’ created with GTEC Independent Wall Linings can hide unattractive services or structure.
GTEC C Studs fixed at right angles GTEC U Track Deep Flange snipped and folded down to reinforce corners
GTEC C Stud fixed back to back to create opening
GTEC I Stud
GTEC Board to suit required performance GTEC U Track
GTEC Intumescent Acoustic Sealant
Insulation quilt to suit required performance Timber sole plate if required
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
227
228
GTEC® INDEPENDENT WALL LINING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
All GTEC Boards Provides wall surface suitable for finishing
See performance tables, p180-191
All GTEC Thermal Boards Provides wall surface suitable for finishing and thermal insulation
See performance tables, p180-191
GTEC I Studs Metal profile for vertical frame elements
IS50/RX, IS60/B, IS70/B, IS90/B
GTEC C Stud Metal profile for vertical frame elements
CS50/RX, CS60/RX, CS70/RX, CS90/RX, CS146/RX, CS70/B, CS90/B, CS146/B, CS90/W, CS70/Y, CS90/Y, CS146/Y
GTEC U Track Metal profile for head and base frame elements
UT52/RX, UT62/RX, UT72/RX, UT92/RX, UT148/RX
GTEC U Track Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UDT62/B, UDT72/B, UDT92/B, UDT148/B, UT52/Y
GTEC U Track Extra Deep Flange Used for partitions with heights exceeding 4.2m and with deflection heads
UXT72/B, UXT92/W, UXT148/W
GTEC Acoustic V Brace 90° For bracing lining to substrate
VBRACE90
GTEC Fixing Channel Provide support for plasterboard joints and fixtures
MFIX/W
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
BOARDS
FRAME
INSULATION
FIX
GTEC速 INDEPENDENT WALL LINING
System Component
System primary use
Product Reference
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
FINISHING
SYSTEM GUIDANCE SUBSTRATE GTEC Independent Wall Lining system is fully independent of the substrate.
Protrusions greater than design cavity depth to be removed.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
229
230
GTEC® INDEPENDENT WALL LINING
FRAME LG-IW-101S-Head detail
LG-IW-102S-Base detail GTEC U Track Deep Flange fixed at 600mm centres
Min. 10mm
screw fix plasterboard to stud at 300mm centres
GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
GTEC Board to suit required performance
GTEC I Stud cut 5mm shorter than floor to ceiling height
GTEC I Stud 5mm shorter than floor to ceiling height
Min. 10mm
screw fix plasterboard to stud at 300mm centres
SECTION
Select compatible sized (e.g. 50mm stud and 52mm track) GTEC I Stud, GTEC C Stud and GTEC U Track framing elements to suit system performance. GTEC U Track Deep or Extra Deep Flange to be used for heights greater than 4.2m.
GTEC Intumescent Acoustic Sealant GTEC U Track Deep Flange fixed at 600mm centres
SECTION
Protect base track from moisture with damp proof membrane when situated on newly laid concrete floors. All GTEC Studs to be 5mm shorter than floor to ceiling height except in case of deflection requirement.
GTEC C Studs as starter studs to be fixed with web flat to structure using appropriate fixings at maximum 600mm centres and fixed to head and track with appropriate GTEC Drywall Screws (see screw selector p334).
Intermediate GTEC Studs to be friction fitted to allow for adjustment during boarding.
GTEC U Track to be fixed flat to structure using appropriate fixings at maximum 600mm centres and positioned a minimum of 10mm from substrate.
For heights over values in performance tables GTEC Acoustic V Brace 90 may be used to brace linings while maintaining acoustic isolation. Contact Technical Enquiryline for more information.
Timber sole plate may be required on uneven floors or where lining is constructed prior to screeding.
GTEC Studs to be at centres required to achieve performance and at a maximum of 600mm centres.
GTEC® INDEPENDENT WALL LINING
INSULATION Any insulation to be of type and thickness to achieve performance and installed in a continuous layer between and behind studs to suit required performance.
Where insulation may be expected to slump suspend from GTEC Insulation Hold strips fixed across studs, 150mm from top of partition and at 1200mm vertical centres.
BOARDING GTEC Independent Lining system is suitable for single, double and multiple layer boarding. Select base layer(s) and finishing layer(s) GTEC Boards by consulting System Performance Tables, p180-191, and Product Specification, p294-307, to achieve required performance. See High Performance Boards guide p12 for further selection information. Boards to be 5mm less than floor to ceiling height. Strips of board 300mm wide or less to be avoided by stud location rearrangement. Boards to be mechanically fixed to studs at 300mm centres using appropriate GTEC Drywall Screws. See screw selector p334. Base layers of boarding may be temporarily fixed at 600mm centres providing final layer is fixed through to stud at 300mm centres
Over-height single layer boarding only: Where partition height exceeds board height fix boards to continuous band of GTEC Flat Strap FS90/W or GTEC MFIX behind all horizontal joints to maintain fire integrity. Over-height multiple layer boarding only: Where partition height exceeds board height for double or multiple layer boarding fix outer layer of boards to continuous band of GTEC Flat Strap FS50/RX behind all horizontal joints. Thermal Boards only: Select GTEC Thermal Board type and thickness according to desired thermal value and requirement for vapour barrier. GTEC Thermal Board thickness may be reduced by utilising higher insulation grade boards, e.g. GTEC Thermal K Board.
Board edges to be centred over studs. Stagger all board joints between layers. Stagger all board joints on opposing sides of partition.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
231
232
GTEC® INDEPENDENT WALL LINING
MOVEMENT CONTROL JOINTS LG-IW-301P-Movement joint
Max. 50mm
Max. 50mm
rock mineral wool insulation
GTEC I Stud
GTEC Board to suit required performance 10mm
GTEC Movement Control Joint
PLAN
Form movement control joints at maximum 10m intervals in the partition run. Form movement control joints where the partition crosses a structural movement joint.
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
OPENINGS LG-IW-401P-Window reveal
Sections of GTEC C Studs to be fitted to back of jamb C Stud above and below opening.
GTEC Intumescent Acoustic Sealant fix board to back of GTEC C Stud to create rewell
GTEC Corner 90º External / GTEC Flex Tape GTEC Board to suit required performance
PLAN
Reinforce head-to-jamb junction 150mm down each jamb stud by cutting and folding head track. Jamb studs to be fixed to track with appropriate GTEC Drywall Screws (see screw selector p334). Reveals may be formed by fixing plasterboard to web of GTEC C Stud. Additional studs and tracks may be required for deeper reveals.
GTEC® INDEPENDENT WALL LINING
CORNERS AND JUNCTIONS LG-IW-501P-Internal Corner
LG-IW-502P-External Corner GTEC Intumescent Acoustic Sealant
screw fix GTEC C Stud together board at 600mm centres
GTEC Board to suit required performance
screw fix GTEC C Stud together through board at 600mm centres GTEC Intumescent Acoustic Sealant GTEC I Stud at max. 600mm centres
GTEC I Stud at max. 600mm centres
GTEC Board to suit required performance
PLAN LG-IW-503P-Junction with partition
PLAN LG-IW-504P-Acoustic rated junction
GTEC Board to suit required performance
Ensure GTEC I Stud coincides with partition
GTEC Board to suit required performance
GTEC Resilient Tape where required by substrate
Screw fix GTEC C Stud to GTEC I Stud at 600mm centres
GTEC Partition System to suit required performance
GTEC Partition System to suit required performance GTEC C Stud fixed to substrate
GTEC Intumescent Acoustic Sealant
GTEC Intumescent Acoustic Sealant
PLAN PLAN
PLAN
LG-IW-505P-Braced acoustic lining
Abutting partitions to coincide with studs, install additional intermediate ‘pick-up’ stud if required. GTEC Board to suit required performance
GTEC Acoustic V Brace 90º at 3m vertical centres
Connect studs through plasterboards at corners and junctions at 600mm vertical centres using appropriate GTEC Drywall Screws. See Construction Details Drawings for further guidance on arrangement and fixing.
GTEC C Stud fixed to brace
PLAN
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
233
234
GTEC® INDEPENDENT WALL LINING
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated partitions. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings. Protect all electrical cables in cavity with conduit.
FIXTURES Fixtures may be attached directly to board provided adequate provision has been made. See guidance in GTEC C Stud Partitions section, p50.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used.
SYSTEM CONTINUITY Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission. Full, imperforate system continuity must be maintained to achieve rated performances.
235
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
236
GTEC® PREGYBEL INDEPENDENT LINING
®
GTEC PREGYBEL INDEPENDENT LINING SYSTEMS Sound absorbing wall linings can be created using the GTEC Pregybel Independent Lining system to improve acoustic comfort by reducing sound reflection in larger spaces. Used above pedestrian height perforated GTEC Pregybel Board is applied to the GTEC Independent Wall Lining system with insulation for an easy to install sound absorbing lining. Flexible design and simple specification can be achieved by using these standard components. Attractive designs are possible created with the variety of patterns in the GTEC Pregybel range. Standalone acoustic panels can also be created to mount to walls to improve sound absorption.
WHERE TO USE: GTEC Pregybel Independent Linings are used in commercial applications to improve the acoustic conditions in large spaces.
FEATURES
BENEFITS
Variable cavity depth
Cavity size can be optimised for service and insulation requirements Up to Class B acoustic absorption
Utilises GTEC Independent Wall Lining framing
One set of components on site. Easy to install.
Creates a false wall
Can be used to upgrade existing structures
Perforated boards in a range of patterns
Provides a range of aesthetic options for variation in large spaces
GTEC® PREGYBEL INDEPENDENT LINING
TIP: GTEC Pregybel is only recommended above accessible levels where it is less prone to damage.
GTEC U Track GTEC C Studs fixed at right angles GTEC I Studs
GTEC Flat Strap
Insulation quilt and void to suit required performance
GTEC Pregybel Board to suit required performance
GTEC Board to suit required performance GTEC Corner 90º External or GTEC Flex Tape to reinforce joints
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
237
238
GTEC® PREGYBEL INDEPENDENT LINING
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
GTEC Pregybel Boards Perforated board for acoustic absorption
See performance tables, p180-191
GTEC I Studs Metal profile for vertical frame elements
IS50/RX, IS60/B, IS70/B, IS90/B
GTEC C Stud Metal profile for vertical frame elements
CS50/RX, CS60/RX, CS70/RX, CS90/RX, CS146/RX, CS70/B, CS90/B, CS146/B, CS90/W, CS70/Y, CS90/Y, CS146/Y
GTEC U Track Metal profile for head and base frame elements
UT52/RX/Y, UT62/RX, UT72/RX, UT92/ RX, UT148/RX
GTEC U Track Deep Used for linings with heights exceeding 4.2m
UDT52/B, UDT62/B, UDT72/B, UDT92/B, UDT148/B
GTEC U Track Extra Deep Used for linings with heights exceeding 4.2m
UXT72/B, UXT92/W, UXT148/W
GTEC Acoustic V Brace 90° For bracing lining to substrate
VBRACE90
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Movement Control Joint Flexible metal profile to create movement joint
MCJ304D
Mineral wool insulation Increases fire and acoustic insulation performance
See performance table supplied by others
GTEC Insulation Hold Secures insulation to prevent slump
INSR
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
BOARDS
FRAME
INSULATION
FIX
GTEC® PREGYBEL INDEPENDENT LINING
System Component
System primary use
Product Reference
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration. Ensures system performance
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
GTEC Socket Pad To maintain acoustic and fire integrity at sockets
PAD1&2
FINISHING
SYSTEM GUIDANCE See guidance in GTEC Independent Wall Lining section and additional considerations given below:
BOARDING LG-PG-101S-Head detail
LG-PG-102S-Base detail
Min. 10mm GTEC Intumescent Acoustic Sealant
screw fix plasterboard to stud at 300mm centres
GTEC U Track Deep Flange fixed at 600mm centres
GTEC Pregybel Board to suit required performance GTEC I Stud 5mm shorter than floor to ceiling height
GTEC Pregybel Board to suit required performance
GTEC I Stud cut 5mm shorter than floor to ceiling height GTEC U Track Deep Flange fixed at 600mm centres
Min. 10mm screw fix plasterboard to stud at 300mm centres
SECTION
GTEC Intumescent Acoustic Sealant
SECTION
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
239
240
GTEC® PREGYBEL INDEPENDENT LINING
BOARDING continued LG-PG-501P-Internal Corner
LG-PG-502P-External Corner
GTEC Intumescent Acoustic Sealant
screw fix GTEC C Stud together board at 600mm centres
screw fix GTEC C Stud together through board at 600mm centres
GTEC Pregybel Board to suit required performance
GTEC Intumescent Acoustic Sealant
GTEC Pregybel Board to suit required performance
PLAN
GTEC Pregybel Independent Lining system is suitable for single layer boarding. Select GTEC Pregybel Board according to acoustic performance required and desired perforation pattern. Studs to coincide with areas of unperforated board.
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated linings.
FINISHING All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Pregybel Board to be sealed and painted with rollers to prevent blocking tissue backing and reducing absorption capability. GTEC Finish materials appropriate to board type to be used.
PLAN
GTEC Pregybel boards to be arranged to achieve desired board pattern. GTEC Pregybel Boards and GTEC Boards may be mixed for decorative effect however acoustic absorption only occurs where board, void and insulation match the system performance. GTEC Pregybel boards are recommended for use above pedestrian height unless otherwise protected.
SYSTEM CONTINUITY Only areas with full system continuity will achieve rated performances. Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings to prevent dust accumulation.
GTEC® PREGYBEL INDEPENDENT LINING
ACOUSTIC PANEL LG-PG-002M-Pregybel Acoustic Panel
LG-PG-103E-Acoustic Panel frame options
GTEC Pregybel Board to suit required performance
GTEC UDT70/B Tracks
GTEC Board Fix to wall with appropriate fixing by others
GTEC Metal Angle (MFC2550)
Max. 3 metres
GTEC CS70/B Stud
GTEC FS50/Rx Flat Strap
GTEC Flat Strap to brace frame
GTEC MFC2550 Angle Max. 500mm
Stud and Track Frame
GTEC CS70/B Studs
Insulation quilt and void to suit required performance
Max. 3 metres
GTEC UDT70/B Tracks
Fix to wall with appropriate fixing by others
GTEC Metal Angle (MFC2550)
GTEC MFC2550 Angle Max. 500mm
ISOMETRIC
GTEC Acoustic Panels are suitable for fixing to most, level, stable and secure substrates and should be fixed with appropriate fixings capable of supporting the load of the panel.
SECTION
Board and insulation configuration to be selected according to acoustic absorption and pattern required, see performance tables p180-191.
Box to be positioned above height of pedestrian movement to prevent crowd loading, GTEC Acoustic Panels are selfsupporting only.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
241
242
GTEC速 FIRE PROTECTION
243
FIRE PROTECTION GTEC Shaftwall range uses a specially designed system to protect voids and shafts in buildings. It resists pressure changes and enables installation from one side of the shaft only. GTEC Encasement Fire Protection offers rapid installation of ďŹ re protection around columns and beams.
Performance Tables GTEC Shaftwall systems
244
GTEC Shaftwall Stairwell systems
248
GTEC Horizontal Shaftwall systems
249
GTEC Encasement systems
250
GTEC Shaftwall systems GTEC Encasement systems
254 268
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
244
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
GTEC® SHAFTWALL SYSTEMS See p254 for guidance
System Ref.
Component
Max Height Nominal System Max Thickness Weight Height Back-toBack GTEC E Studs (m) (mm) (kg/m2) (m)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr where applicable)
RCS 102 Facing: 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
35
4.2
2x ES60B 4.5
78
60 30
Severe
39
Facing: 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
36
4.2
2x ES60B 4.5
78
60 60
Severe
45
Facing: 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
36
6.0
2x ES90B 6.4
107
60 30
Severe
43
Facing: 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
37
6.0
2x ES90B 6.4
107
60 60
Severe
51
Facing: 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
38
6.8
2x ES146B 8.0
161
60 60
Severe
43
Facing: 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
38
6.8
2x ES146B 8.0
161
60 60
Severe
51
RCS 106
RCS 203
RCS 208
RCS 310
RCS 311
See p251 for notes on alterations to fire protection configuration.
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
System Ref.
Max Height Nominal System Max Thickness Weight Height Back-toBack GTEC E Studs (m) (mm) (kg/m2) (m)
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr where applicable)
RCS 103 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
42
4.4
2x ES60B 4.7
88
90 90
Severe
40
Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
43
4.4
2x ES60B 4.7
88
90 90
Severe
46
Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
43
6.4
2x ES90B 6.8
118
90 90
Severe
45
Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
44
6.4
2x ES90B 6.8
118
90 90
Severe
52
Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
47
7.5
2x ES146B 8.2
175
90 90
Severe
50
RCS 104
RCS 205
RCS 207
RCS 301
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
245
246
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
GTEC® SHAFTWALL SYSTEMS continued
System Ref.
Component
Max Height Nominal System Max Thickness Weight Height Back-toBack GTEC E Studs (m) (mm) (kg/m2) (m)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr where applicable)
RCS 302 Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
47
7.5
2x ES146B 8.2
175
90 90
Severe
52
Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
45
4.8
2x ES60B 5.1
95
120 90
Severe
41
Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
46
4.8
2x ES60B 5.1
95
120 90
Severe
47
Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
47
6.7
2x ES90B 7.1
120
120 90
Severe
47
Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
48
6.7
2x ES90B 7.1
120
120 90
Severe
54
RCS 109
RCS 110
RCS 206
RCS 210
See p251 for notes on alterations to fire protection configuration.
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
System Ref.
Max Height Nominal System Max Thickness Weight Height Back-toBack GTEC E Studs (m) (mm) (kg/m2) (m)
Component
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr where applicable)
RCS 303 Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
51
8.0
2x ES146B 9.2
180
120 90
Severe
51
Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: 25mm 16kg/m3 glass mineral wool
52
8.0
2x ES146B 9.2
180
120 90
Severe
54
RCS 304
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
247
248
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
GTEC® SHAFTWALL STAIRWELL SYSTEMS See p265 for guidance
System Ref.
Component
Max Height Nominal System Max Thickness Weight Height Back-toBack GTEC E Studs (m) (mm) (kg/m2) (m)
Fire Perf. BS476-22 BS EN 1364-1 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr where applicable)
RCS 503 Facing: 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: 1x 12.5mm GTEC Fire or Megadeco Board Insulation: –
42
4.5
– –
88
120 90
Severe
40
Facing: 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: 1x 12.5mm GTEC Fire or Megadeco Board Insulation: 25mm 16kg/m3 glass mineral wool
43
4.5
– –
88
120 90
Severe
44
Facing Inner Layer(s): 1x 12.5mm GTEC Fire Board Facing Outer Layer(s): 1x 12.5mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: 1x 12.5mm GTEC Fire or Megadeco Board Insulation: –
54
5.4
– –
101
120 120
Severe
43
RCS 504
RCS 505
See p251 for notes on alterations to fire protection configuration.
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
GTEC® HORIZONTAL SHAFTWALL SYSTEMS See p267 for guidance System Max Weight Span
System Ref.
(kg/m2) (m)
Component
Max Span Nominal Back-toThickness Back GTEC E Studs (m) (mm)
Fire Perf. BS476-22 BS EN 1364-2 (mins)
Strength Duty Rating to BS 5234
Acoustic Perf. Rw dB (Ctr where applicable)
RCS 901: HORIZONTAL Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS60B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
42
2.5
– –
95
90 90
–
41
47
3.6
– –
123
90 90
–
47
51
4.2
– –
180
90 90
–
51
RCS 904: HORIZONTAL Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS90B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
RCS 905: HORIZONTAL Facing Inner Layer(s): 1x 15mm GTEC Fire Board Facing Outer Layer(s): 1x 15mm GTEC Fire or Megadeco Board Studs: GTEC CHS146B CH-Studs at 600mm centres Core: 1x 25mm GTEC Fire Core Board Core Facing: – Insulation: –
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
249
250
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
GTEC® ENCASEMENT SYSTEMS See p268 for guidance
System Ref.
Component type
Component
Facing: Framing: Fire resistance columns:
1x 12.5mm GTEC Fire or Megadeco Board GTEC Edge Channel & CB Clips at 600mm Centres 30 Mins up to 280 Hp/A factor 60 Mins up to 280 Hp/A Factor 30 Minutes up to 280 Hp/A factor 60 Minutes up to 115 Hp/A Factor
RCE 001
Fire resistance beams:
RCE 002 Facing: Framing: Fire resistance columns: Fire resistance beams:
1x 15mm GTEC Fire or Megadeco Board GTEC Edge Channel & CB Clips at 600mm Centres 90 Mins up to 115 Hp/A factor 60 Minutes up to 280 Hp/A factor 90 Minutes up to 50 Hp/A Factor
Facing: Inner Facing: Outer Framing: Fire resistance Columns Fire resistance Beams
1x 12.5mm GTEC Fire 1x 12.5mm GTEC Fire or Megadeco Board GTEC Edge Channel & CB Clips at 600mm Centres 90 Minutes up to 280 Hp/A factor 120 Minutes up to 140 Hp/A Factor 90 Minutes up to 280 Hp/A Factor
Facing: Framing: Fire resistance columns: Fire resistance beams:
1x 25mm GTEC Fire Core Board GTEC Edge Channel & CB Clips at 600mm Centres 120 Minutes up to 185 Hp/A factor 120 Minutes up to 85 Hp/A factor
Facing: Inner Facing: Outer Framing: Fire resistance columns: Fire resistance beams:
1x 15mm GTEC Fire 1x 15mm GTEC Fire or Megadeco Board GTEC Edge Channel & CB Clips at 600mm Centres 120 Minutes up to 235 Hp/A factor 120 Minutes up to 180 Hp/A Factor
RCE 003
RCE 004
RCE 005
See p251 for notes on alterations to fire protection configuration.
GTEC® FIRE PROTECTION – PERFORMANCE TABLES
System Ref.
Component type
Component
Facing: Inner Facing: Outer Framing: Fire resistance columns:
1x 25mm GTEC Fire Core Board 1x 15mm GTEC Fire or Megadeco Board GTEC Edge Channel & CB Clips at 600mm Centres 120 Minutes up to 280 Hp/A factor 180 Minutes up to 130 Hp/A Factor 120 Minutes up to 280 Hp/A Factor 180 Minutes up to 80 Hp/A Factor
RCE 006
Fire resistance beams:
RCE 007 Facing: Inner Facing: Outer Framing: Fire resistance columns: Fire resistance beams:
1x 25mm GTEC Fire Core Board 1x 25mm GTEC Fire Core Board GTEC Edge Channel & CB Clips at 600mm Centres 180 Minutes up to 280 Hp/A Factor 180 Minutes up to 280 Hp/A Factor
NOTE: All Encasement systems tested to BS476-21.
FIRE PROTECTION PERFORMANCE NOTES Performance values are for imperforate, jointed systems using Siniat GTEC components (metal studs and tracks, boards, metal accessories, screws and finishing systems) and specified insulation quilt material (type, thickness and density) and installed to Siniat specification and installation guides. Maximum heights depend on deflection criteria and applied air pressure.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
251
GTEC® FIRE PROTECTION – ENCASEMENT TABLES
UNIVERSAL BEAMS WITH BOX ENCASEMENT Section factor Hp/A m-1
Size of steelwork (mm)
Mass per metre (kg)
3 sides
4 sides
914 x 419
388 343 289 253 224 201 226 194 176 197 173 147 170 152 140 125 238 179 149 140 125 113 101 122 109 101 92 82 98 89 82 74 67 82 74 67 60 52 74 67 60 54 46 39 67 57 51 45 39 33 54 46 40
45 50 60 65 75 80 70 80 90 70 80 95 75 85 90 100 50 70 80 80 90 100 110 85 95 100 110 120 90 100 105 115 130 105 115 125 140 160 105 115 130 145 160 190 105 125 135 155 170 195 115 130 150
55 60 65 75 85 95 80 90 100 85 95 110 90 95 105 115 60 80 95 95 105 115 130 95 110 115 125 140 105 115 125 135 150 120 130 145 160 180 125 140 155 170 185 220 125 145 165 185 195 225 140 160 180
48 42 37 33 28 25 37 31 28 25 22 30 25 23 19 16 13
125 140 155 175 200 225 140 160 170 190 215 145 165 175 190 190 195
145 160 180 200 225 260 170 200 200 220 250 180 210 210 230 235 240
914 x 305
838 x 292
762 x 267
686 x 254
610 x 305
610 x 229
533 x 210
457 x 191
457 x 152
406 x 178
406 x 140 356 x 171
356 x 127 305 x 165
305 x 127
305 x 102
254 x 146 254 x 102
203 x 133 203 x 102 172 x 102 152 x 89 127 x 76
280
RCE 006 RCE 002
200
RCE 003
Hp/A factor
252
180
RCE 001
RCE 007
RCE 005
118
100 85 75
RCE 001
50
RCE 002
RCE 004
RCE 006
0 30
60
90
120
Fire Resistance (mins)
180
GTEC® FIRE PROTECTION – ENCASEMENT TABLES
UNIVERSAL COLUMNS WITH BOX ENCASEMENT Section factor Hp/A m-1
Size of steelwork (mm)
Mass per metre (kg)
3 sides
356 x 406
634
15
20
551
20
25
467
20
30
393
25
35
340
30
35
287
30
45
235
40
50
202
45
60
305 x 305
254 x 254
203 x 203
152 x 152
177
50
65
153
55
75
129
65
90
283
30
40
240
35
45
198
40
50
158
50
65
137
55
70
118
60
85
97
75
100
167
40
50
132
50
65
107
60
75
89
70
90
73
80
110
86
60
80
71
70
95
60
80
110
52
95
125
46
105
140
37
100
135
30
120
160
23
155
205
280 RCE 006 230
200 RCE 003
Hp/A factor
356 x 368
4 sides
RCE 001
RCE 005
RCE 007
185
RCE 004
RCE 001
140 130
100 105
RCE 002
RCE 003
RCE 006
120
180
0 30
60
90
Fire Resistance (mins)
STEEL JOISTS WITH BOX ENCASEMENT Size of steelwork (mm)
Mass per metre (kg)
Section factor Hp/A m-1 3 sides 4 sides
254 x 203
81.85
70
90
254 x 114
37.20
130
155
203 x 152
52.09
85
105
152 x 127
37.20
90
120
127 x 114
29.76
100
130
127 x 114
26.79
110
140
114 x 114
26.79
100
135
102 x 102
23.07
105
140
89 x 89
19.35
105
145
76 x 76
12.65
140
185
EXAMPLE OF USE Beam = 610mm x 305mm x 179kg/m Exposed on four sides Hp/A = 80m-1
Choice of systems Up to 60mins = RCE001 Up to 90mins = RCE003 Up to 120mins = RCE004 Up to 180mins = RCE007
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
253
254
GTEC® SHAFTWALL
®
GTEC SHAFTWALL SYSTEMS The GTEC Shaftwall Fire Protection system protects shafts and voids in multi-storey buildings with a rapid installation system preventing continuous routes for the spread of fire. The system uses a non-symmetrical board assembly for full installation from one side of the shaft, allowing construction in tight spaces. The frame features friction fit channels to receive GTEC Fire Core Board and a fixing flange for the installation of GTEC Fire, Megadeco or Universal Boards ready to finish on the room side. The shaft side can also be decoratively finished using GTEC Shaftwall Stairwell systems, this is commonly used in stairwells. GTEC Shaftwall Fire Protection can also be used horizontally to protect the underside of ductwork or provide a ‘lid’ to a shaft. In horizontal applications, further boards may be needed to achieve fire performances. Refer to the System Performance Tables on pages 244 to 249 for full details.
WHERE TO USE: GTEC Shaftwall Systems are used to protect voids in commercial or public multi-storey buildings and is suitable for most construction types.
FEATURES
BENEFITS
System designed to be erected from one side only
No scaffolding required
Offers fire protection from both directions
Provides up to 120 minutes fire performance
Lightweight friction fit framing system
Fast to install with less material costs
Specialised components designed as a system
Reliable and easy to specify
Framing includes cavity
Allows space for services to run
High strength frame
Resists pressure changes likely in deep shafts and voids
Fully sealed
Prevents whistling, dirt accumulation and ensures fire performance
GTEC® SHAFTWALL
255
TIP: GTEC Intumescent Acoustic Sealant is vital to fire rated systems, it secures boards and improves fire resistance.
GTEC J Track / U Track Deep Flange at base fixed to structure at 300mm centres
GTEC Board to suit required performance GTEC Intumescent Acoustic Sealant
GTEC E Stud fixed to structure at 300mm centres GTEC Fire Core Board
Mineral wool
staggered joints between layers
Alternative finishing layer may be used see tables
GTEC J Track / U Track Deep Flange at base fixed to structure at 300mm centres
GTEC CH Studs at 600mm centres GTEC E Studs fixed at right angles at 300mm centres
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
256
GTEC速 SHAFTWALL
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
GTEC Fire Core Board High strength fire and moisture resistant board for use in steel fire encasement
See performance tables, p250-253
GTEC Fire Board A fire resistant plasterboard
See performance tables, p250-253
GTEC High Performance Type F Boards Fire resistant boards, with improved acoustic and impact performance for room-side of system
See performance tables, p250-253
GTEC CH Stud Metal profile for vertical frame elements
CH60/B, CHS90/B, CHS146/B
GTEC E Stud Metal profile used for vertical frame element at junctions and end studs
ES60/B, ES90/B, ES146/B
GTEC J Track Metal profile for head and base channel
JT62/B, JT92/B, JT148/B
GTEC U Track Deep Flange Deep flange metal profile for deflection heads
UDT62/B, UDT92/B, UDT148/B
GTEC U Track Extra Deep Flange Extra deep flange metal profile for deflection heads
UXT92/W, UXT148/W
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
Mineral wool insulation Provide fire resistance
See performance table supplied by others
BOARDS
FRAME
INSULATION
GTEC速 SHAFTWALL
System Component
System primary use
Product Reference
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration to achieve quoted performances
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
FIX
FINISHING
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
257
258
GTEC® SHAFTWALL
SYSTEM GUIDANCE FRAME AND SHAFT-SIDE BOARDING FP-SH-101S-Head
FP-SH-102S-Base
GTEC Fire Board to suit system
fix track at 300mm centres
25mm
GTEC Fire Core Board 100mm
GTEC Intumescent Acoustic Sealant
GTEC J Track
GTEC CH Stud cut 10mm less than ceiling height
GTEC J Track GTEC Fire Board to suit system screw fix plasterboard to track
GTEC Fire Core Board
GTEC Intumescent Acoustic Sealant
GTEC CH Stud cut 10mm less than ceiling height
fix track at 300mm centres
SECTION FP-SH-103M-Stud reinforcement (back-to-back E-studs)
SECTION FP-SH-201P-Partition assembly – start GTEC Intumescent Acoustic Sealant
GTEC Fire Core Board installed after each stud is fitted GTEC CH Stud
Screw fix at 150mm staggered centres
GTEC J Track GTEC Fire Board installed after all core board and studs are in place GTEC E Stud fixed at 300mm centres
PLAN Stagger joints by minimum 1m
FP-SH-202P-Partition assembly – end
GTEC CH Stud NOTES:
Snip and bend GTEC J Track temporarily to allow fitting of final stud and core board
Avoid splicing unless necessary All board joints minimum 450mm from splice Minimum 4 board fixings between board joint and stud splice
ISOMETRIC
mechanically fix GTEC E Stud to structure at 300mm centres
PLAN
GTEC® SHAFTWALL
FP-SH-203S-Overheight shaftwalls reinforcement – option 1
FP-SH-204S-Overheight shaftwalls reinforcement – option 2
GTEC Fire Core Board
Joints within 1/3 height of head or base of shaftwall
MIn. 50mm
MIn. 50mm
GTEC Fire Core Board
GTEC Intumescent Acoustic Sealant
GTEC Board to suit required performance
SECTION
Joints within 1/3 height of head or base of shaftwall
GTEC CH Stud to reinforce joint fitted between vertical studs
GTEC Board to suit required performance
SECTION
Select compatible size (e.g. 90mm stud and 92mm track) GTEC CH Stud, GTEC E Stud and GTEC J Track framing elements to suit system performance.
GTEC Fire Core Board to be installed before intermediate stud with construction proceeding progressively, alternating in sequence between board and GTEC CH Stud.
Bead of GTEC Intumescent Sealant to be applied at junction of all metal framing with structure, at junction of all metal framing with GTEC Fire Core Board, and at all other locations specified in drawings.
All GTEC CH Studs to be 10mm shorter than floor to ceiling height except in case of deflection requirement. Each GTEC CH Stud to be firmly fitted to board and friction fitted into track.
GTEC J Track at head and base to be fixed flat to structure, long leg of track to shaft side, using appropriate fixings at maximum 300mm centres.
100mm deep strip of GTEC Fire Core Board spanning between studs to be fixed through main GTEC Fire Core Board to GTEC J Track to form fire stop at head.
First GTEC E Stud, 10mm less than floor to ceiling height, to be fixed abutting structure using appropriate fixings at maximum 300mm centres. Stud to be fixed to head and base track with appropriate GTEC Drywall Screws (see screw selector, p334-335). Final GTEC E Stud to be installed with final GTEC Fire Core Board.
Where wall height exceeds available GTEC CH Stud length, lengths of GTEC E Stud to be spliced together, back-to-back, ensuring overlaps of 600mm for heights below 4m and 1000mm for heights above 4m.
Protect base track from moisture with damp proof membrane when situated on newly laid concrete floors.
Where partition exceeds 3m height, horizontal joints to be at alternating maximum 1/3 or 2/3 height with reinforcement from GTEC CH Stud noggings or 100mm deep strips of GTEC Fire Core Board.
GTEC Fire Core Board to be 25mm short of floor to ceiling height with 25mm gap at top of Shaftwall frame.
Studs and tracks to be clean of fire protective coatings which may have been applied to main structure.
INSULATION Insulation to be of type and thickness to achieve performance and installed in a continuous layer between frames or studs to suit required performance.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
259
260
GTEC® SHAFTWALL
GENERAL BOARDING GTEC Fire Core Board to be used as shaft-side boarding (see p299). GTEC Fire Board, Megadeco or Universal Board, 5mm short of floor to ceiling height, to be used as room-side boarding. Select GTEC Boards by consulting System Performance Tables (p244-251) to achieve required performance. All layers of boarding to be mechanically fixed to studs at 300mm centres using appropriate GTEC Drywall Screws (see screw selector, p334-335). Board edges to be centred over studs.
Stagger all board joints between layers and stagger screws by 100mm compared to adjacent boards and layers. Over-height single layer boarding: Where partition height exceeds board height fix boards to continuous band of GTEC Flat Strap FS90/W or GTEC MFIX behind all horizontal joints to maintain fire integrity. Over-height multiple layer boarding: Where partition height exceeds board height for double or multiple layer boarding fix outer layer of boards to continuous band of GTEC Flat Strap FS50/RX behind all horizontal joints.
MOVEMENT CONTROL JOINTS FP-SH-301P-Movement control joint
GTEC Fire Core Board
rock mineral wool 40kg/m3
10mm
GTEC Intumescent Acoustic Sealant
GTEC E Stud
GTEC Board to suit required performance
GTEC Movement Control Joint 10mm
10mm
PLAN
Form movement control joints at maximum 10m intervals in the partition run. Form movement control joints where the partition crosses a structural movement joint.
Fix GTEC Movement Control Joint, butted end-to-end, to board with sheradised or galvanised staples.
GTEC® SHAFTWALL
OPENINGS FP-SH-401P-Door jamb
GTEC J Track GTEC Intumescent Acoustic Sealant
GTEC Fire Core Board Timber stud
GTEC E Stud inside track GTEC Board to suit required performance
PLAN
Form openings following guidance in Construction Detail Drawings to suit duct penetration or door configuration. For doors, reinforce head-to-jamb junction down each jamb stud by cutting and folding head track, continue track down full length of jamb and reinforce with timber as described in Construction Detail Drawings. Jamb studs to be configured to ensure continuity of GTEC Fire Core Board to inside of opening. Jamb studs to be fixed to track with appropriate GTEC Drywall Screws (see screw selector, p334-335).
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
261
262
GTEC® SHAFTWALL
CORNERS AND JUNCTIONS FP-SH-501P-Internal corner
FP-SH-502P-External corner
GTEC Fire Core Board strip fixed to back of GTEC Stud at 300mm Centres
GTEC Fire Core Board
GTEC Fire Board GTEC E Stud GTEC Intumescent Acoustic Sealant
Tracks separated by depth of plasterboard
Fix GTEC E Studs together at 300mm centres GTEC Intumescent Acoustic Sealant GTEC E Stud
PLAN FP-SH-503P-T-junction – room side
PLAN FP-SH-504P-T-junction – shaftside
GTEC CH Stud arranged to coincide with shaftwall abutment
GTEC Fire Core Board
screw fix GTEC E Stud to GTEC CH Stud at 300mm centres GTEC E Stud arranged as it coincides with the shaftwall abutment
GTEC Intumescent Acoustic Sealant
screw fix GTEC E Stud to GTEC CH Stud at 300mm centres
GTEC E Stud
GTEC Fire Board
GTEC Fire Core Board
GTEC Board to suit required performance
GTEC CH Stud
PLAN
PLAN
FP-SH-505 P-Junction of partition to shaftwall option 1,2&3
GTEC CH Stud arranged to coincide with shaftwall abutment
GTEC Flat Strap fixed across studs at 600mm vertical centers
GTEC C Stud fixed to track to support partition
GTEC CH Stud
screw fix partition stud through GTEC CH Stud at 600mm centres
screw fix partition stud to GTEC Flat Strap through board at 600mm centres
screw fix partition stud to GTEC C Stud through board at 600mm centres
GTEC Board to suit required performance
PLAN
GTEC® SHAFTWALL
FP-SH-506P-Column junction – at corner
See encasement details for component information
Column encased prior to shaftwall construction
GTEC E Stud
PLAN
Abutting partitions to coincide with Shaftwall stud; additional intermediate ‘pick-up’ GTEC C Stud; or GTEC Flat Strap at 600mm vertical centres.
Ensure continuity of GTEC Fire Core Board at corners. See Construction Details Drawings for further guidance on arrangement and fixing.
Connect studs through plasterboards at corners and junctions.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
263
264
GTEC® SHAFTWALL
PENETRATIONS FP-SH-701M-Duct penetration isometric
GTEC J Track
Back to back GTEC E Studs to create opening
GTEC E Stud
Insert GTEC E Stud (shown in red) cut short of GTEC CH Stud and fixed into GTEC J Track to reinforce
Screw fix GTEC E Stud (shown in red) to GTEC J Track at 200mm centres
GTEC CH Studs between jambs m 0m 60 . x Ma
Note: Boards not shown for clarity
ISOMETRIC FP-SH-702P-Duct penetration plan
FP-SH-703S-Duct penetration section
Cable Tray or duct (may require fire damper)
GTEC Intumescent Acoustic Sealant
GTEC E Stud
GTEC Board to suit required performance GTEC E Stud inserted and fixed at 200mm centres into GTEC J Track to reinforce
Cable Tray or duct (may Require fire damper)
GTEC Board to suit required performance
GTEC Fire Core Board screw fixed to GTEC E Stud
GTEC Fire Core Board screw fixed to GTEC J Track GTEC Fire Core Board
SECTION
SECTION
GTEC® SHAFTWALL
PENETRATIONS M&E runs and other services to be pre-planned to minimise or eliminate penetrations through rated Shaftwall systems.
Ductwork to be independently supported and not supported by the Shaftwall system. Protect all electrical cables in cavity with conduit.
Continuity of GTEC Fire Core Board to be maintained around penetration openings. Any penetrations must be fully sealed with GTEC Intumescent Acoustic Sealant or other fire resisting material as specified in Construction Detail Drawings.
FIXTURES
SYSTEM CONTINUITY
See fixture guidance in GTEC C Stud Partition section, p50, for further guidance. GTEC LaDura is recommended as pattress to enhance mechanical resistance of the fixing.
Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission.
FINISHING All room-side board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances.
Full, imperforate system continuity must be maintained to achieve rated performances.
GTEC Finish materials appropriate to board type to be used.
STAIRWELL SYSTEMS FP-SH-010P-Stairwelll system
FP-SH-011P-Stairwell perimeter detail GTEC Board to finish over GTEC Fire Core Board GTEC Intumescent Acoustic Sealant
GTEC Intumescent Acoustic Sealant
GTEC Fire Core Board
GTEC Fire Core Board
GTEC Board to suit required performance
GTEC E Stud GTEC E Stud
PLAN
Where finishing of both sides of Shaftwall system is required one decorative board may be transferred to shaft side in accordance with system requirements, see performance tables p244.
GTEC Board to suit required performance
PLAN
Transferred board to be screw fixed at maximum 300mm centres to exposed flanges of GTEC CH Stud, GTEC E Stud and track.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
265
GTEC® SHAFTWALL
DUCT PROTECTION SYSTEMS FP-SH-021S-Duct protection shaftwall – 90 minutes
fix track to substrate at 300mm centres using appropriate fixings by others
GTEC Intumescent Acoustic Sealant
GTEC Fire Board screw fixed to track and stud at 150mm centres DUCT Max. 1200mm
266
GTEC CH Stud screw fixed to track
GTEC Fire Core Board
GTEC U Track
GTEC Edge Channel
screw fix tracks together at 150mm centres GTEC Ceiling Channel screw fixed to track and stud at 400mm centres
Max. 1200mm
SECTION
Horizontal runs of GTEC Shaftwall systems to protect underside of duct work require additional material and configurations of frame, see performance tables p244-251 for requirements.
GTEC Shaftwall duct protection is not designed to support ductwork or any other loads.
GTEC® SHAFTWALL
HORIZONTAL SYSTEMS FP-SH-031S-Horizontal shaftwall
GTEC Intumescent Acoustic Sealant
GTEC CH Stud GTEC Fire Core Board GTEC U Track Deep Flange
GTEC E Stud GTEC Fire Board to suit performance SECTION ACROSS STUDS
GTEC Fire Core Board GTEC E Stud
GTEC U Track Deep Flange GTEC Fire Board to suit performance SECTION ALONG STUDS
SECTION
GTEC Horizontal Shaftwall to be fixed to structure using appropriate fixings as recommended by fixing manufacturer to support self-weight of Shaftwall.
Horizontal systems are not designed to support any additional loads.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
267
268
GTEC® ENCASEMENT
®
GTEC ENCASEMENT SYSTEMS The GTEC Encasement Fire Protection system provides high levels of fire resistance to structural I-section columns and beams, delaying the loss of strength in steel which occurs at temperatures over 550°C. The system uses push-fit GTEC CB Clips to secure GTEC Edge Channel to the steel. GTEC Fire Core Boards, Fire Boards, and other high performance boards as detailed in the performance tables, are fixed to the edge channel to protect columns and beams. Excellent fire performance is achieved by holding the boards off the columns on a strong metal frame.
WHERE TO USE: The system is used in commercial multi-storey construction to ensure structural safety during fire. The range of impact resistant boards compatible with the system enables use in high traffic areas.
FEATURES
BENEFITS
Uses GTEC Fire Board
Economical and effective
Uses GTEC Fire Core Board
Fewer board layers required
Fully tested
Allows use of Hp/A factors, giving performance to a range of column and beam dimensions
Fully dry installation
Efficient to install
Friction fit frame installation
Efficient to install Allows differential movement during fire
Simple frame design
Requires no specialist equipment
Plasterboard finish
Flat, easy to decorate, surface. Suitable for use with GTEC Partitions, Ceilings and Linings
GTEC® ENCASEMENT
269
TIP: Using plasterboard encasement means that beams or columns can be finished as easily and consistently as plasterboard walls or ceilings.
GTEC Edge Channel push fit into GTEC CB Clip
GTEC CB Clip at 600mm centres
M joi 300 in. nt sta mm gg er
GTEC Board to suit required performance GTEC Flat Strap to reinforce joint screw fix plasterboard at max. 300mm centres (Min.2 per board edge)
GTEC Corner 90º External / GTEC Flex Tape to reinforce corner joints
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
270
GTEC速 ENCASEMENT
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
GTEC Fire Core Board High strength fire and moisture resistant board for use in steel fire encasement
See performance tables, p250-253
GTEC Fire Board A fire resistant plasterboard
See performance tables, p250-253
GTEC High Performance Type F Boards Fire resistant boards, with improved acoustic and impact performance for room-side of system
See performance tables, p250-253
GTEC CB Clip Steel clip for connecting channels to structural steelwork
CB17, CB27, CB40
GTEC Edge Channel Steel channel to provide metal frame and bearing surface for plasterboard
MFCE26
GTEC Metal Angle Multi-purpose galvanised metal section
MFC2525, MFC2550, MFC2330
GTEC Fixing Channel Provide support for plasterboard joints and fixtures
MFIX/W
GTEC Flat Strap Provide support for plasterboard joints and fixtures
FS50/RX, FS90/W
GTEC Drywall Screws (as appropriate) For connecting plasterboard and metal components
See screw selector, p334
GTEC Corner and Edge beads Corner and edge reinforcement
n/a
GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
n/a
GTEC Intumescent Acoustic Sealant Perimeter sealing to restrict smoke, sound and fire penetration to achieve quoted performances
n/a
GTEC Compounds To finish joints between boards and bed corner beads prior to decorating. Ensures system performance
See compounds guidance, p280
GTEC Sealers To seal plasterboard prior to decoration
n/a
BOARDS
FRAME
FIX
FINISHING
GTEC® ENCASEMENT
SYSTEM GUIDANCE FRAME FP-EN-101P-Column encasement – single layer GTEC Corner 90º External / GTEC Flex Tape screw fix plasterboard at 300mm centres
GTEC Board to suit required performance
GTEC CB Clip at max. 600mm centres
GTEC Edge Channel pushed into GTEC CB Clip
SECTION FP-EN-102P-Column encasement – double layer GTEC Corner 90º External / GTEC Flex Tape screw fix plasterboard at 300mm centres
Joints of layers staggered by min. 300mm
GTEC CB Clip at max. 600mm centres
GTEC Edge Channel pushed into GTEC CB Clip GTEC Board to suit required performance
SECTION FP-EN-103S-Single boarded beam encasement
GTEC Intumescent Acoustic Sealant Option A – GTEC Metal Angle fixed to the beam
GTEC Flat Strap / GTEC Fixing Channel if beam greater than 300mm deep
GTEC CB Clip at max. 600mm centres
GTEC Edge Channel pushed into GTEC CB Clip
Option B – GTEC Metal Angle fixed to the soffit
GTEC Board to suit required performance
screw fix plasterboard at 300mm centres
GTEC Corner 90º External / GTEC Flex Tape
SECTION
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
271
272
GTEC® ENCASEMENT
FRAME FP-EN-104S-Double boarded beam encasement
GTEC Intumescent Acoustic Sealant Option B – GTEC Metal Angle fixed to the soffit
Option A – GTEC Metal Angle fixed to the beam
GTEC Board to suit required performance
GTEC Flat Strap / GTEC Fixing Channel if beam greater than 300mm deep
GTEC Flat Strap FS90/W to reinforce board joints GTEC CB Clip at max. 600mm centres screw fix plasterboard at 300mm centres GTEC Edge Channel pushed into GTEC CB Clip GTEC Corner 90º External / GTEC Flex Tape
Select GTEC CB Clips to suit flange thickness of steel to be protected: GTEC CB Clip
To fit flange size:
CB 17
7-17mm
CB 27
17-27mm
CB 40
27-40mm
SECTION
GTEC CB Clips to be friction fitted to flanges of steel at maximum 600mm centres beginning at 150mm from both ends of steel. GTEC Edge Channel to be friction fitted into GTEC CB Clips along length of steel. Where steel abuts structure GTEC Metal Angle to be fixed to structure or shot fired to inside of steel flange with appropriate fixings, and following guidance of steel designer, to provide substrate for plasterboard.
BOARDING FP-EN-201M-300-600mm beam board reinforcement
FP-EN-202M-Over 600mm beam board reinforcement
GTEC Edge Channel push fit into GTEC CB Clip where not abutting soffit
GTEC Edge Channel push fit into GTEC CB Clip
GTEC Flat Strap FS90/W / GTEC Fixing Channel fixed to GTEC Edge Channel to support board
GTEC Flat Strap / GTEC Fixing Channel to support board
Over 600mm depth
300 to 600mm depth to or th mmleng 0 0 d 24 boar it su
GTEC CB Clip GTEC CB Clip m 0m 60
ISOMETRIC
ISOMETRIC
GTEC® ENCASEMENT
Select GTEC Boards by consulting System Performance Tables (p250-251) and Hp/A tables (p252-253) to achieve required performance.
Where flange/web dimension exceeds 300mm all plasterboard joints along beam/column to be reinforced with GTEC Flat Strap or GTEC MFIX Channel.
GTEC Board to be fixed to GTEC Edge Channel, GTEC Metal Angle and any reinforcement at maximum 300mm centres using appropriate GTEC Drywall Screws (see screw selector p334-335). Fixing positions to be staggered on next boarding layer. Minimum 2 screws per board edge.
Where flange/web dimension exceeds 600mm provide reinforcement to board with GTEC Flat Strap or GTEC MFIX fixed to GTEC Edge Channel at maximum 600mm centres and at board joints.
CORNERS AND JUNCTIONS FP-EN-501P-Junct. partition to column – Opt.1 (non-acoustic)
GTEC Flat Strap at 600mm vertical centres to provide fixing for partition stud
column encased prior to partition construction
GTEC Partition System to suit reqired performance
GTEC Intumescent Acoustic Sealant fix stud through to strap
SECTION FP-EN-502P-Junct. partition to column – Opt.2 (acoustic)
GTEC Metal Angle 90° fixed through to GTEC C Stud
GTEC CB Clip at max. 600mm centres
GTEC Partition System minimum fire resistances to match column encasement
GTEC Resilient Tape
GTEC Intumescent Acoustic Sealant GTEC Edge Channel pushed into GTEC CB Clip GTEC Corner 90º External / GTEC Flex Tape
SECTION
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
273
274
GTEC® ENCASEMENT
CORNERS AND JUNCTIONS continued FP-EN-503S-Column in masonry wall
GTEC Metal Angle
GTEC Intumescent Acoustic Sealant
GTEC CB Clip at max. 600mm centres
GTEC Edge Channel pushed into GTEC CB Clip
GTEC Corner 90º External / GTEC Flex Tape
GTEC Board to suit required performance
SECTION FP-EN-504S-Junction of partition along beam (non-acoustic)
GTEC Board to suit required performance
beam encased prior to partition construction
GTEC Flat Strap to provide partition fixing at maximum 600mm centres
fix U track through to GTEC Flat Strap or fixing channel at 600mm centres
GTEC Intumescent Acoustic Sealant GTEC Partition System to suit required performance
SECTION
Provide GTEC Flat Strap as reinforcement for abutting partitions at 600mm centres behind final layer of encasement board. Studs or tracks to be fixed through to reinforcement.
GTEC® ENCASEMENT
HEAD DEFLECTION
SYSTEM CONTINUITY
GTEC Encasement systems are designed to move with beam deflection. Partitions meeting beams liable to deflection to be detailed according to guidance in GTEC C Stud system guidance (see p61).
PENETRATIONS Penetrations must not be made through GTEC Encasement systems.
Bead of GTEC Intumescent Acoustic Sealant to be applied to perimeter of all runs and in all other locations specified in Construction Detail Drawings. GTEC Intumescent Acoustic Sealant to seal all other acoustic or air paths to prevent fire/ smoke spread and acoustic transmission. Full, imperforate system continuity must be maintained to achieve rated performances.
FIXTURES Fixtures to be supported by structure and not supported by GTEC Encasement systems.
FINISHING All corners to be reinforced with GTEC Corner 90. All board joints to be taped, jointed or finished according to guidance in Finishing section (p276-291) to achieve system performances. GTEC Finish materials appropriate to board type to be used.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
275
276
GTEC速 FINISHING
277
FINISHING GTEC Taping and Jointing provides a finish to joints between GTEC boards creating a continuous, fire resistant and easy to decorate surface. Skimming can achieve similar results but is a more labour and time intensive method. Tiling GTEC moisture and wet area GTEC boards can achieve exceptionally high levels of water resistance. GTEC Cove is a decorative gypsum element used to finish the junction between partition and ceiling.
GTEC Taping and Jointing Alternative finishing methods GTEC Cove
278 284 288
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
278
GTEC® TAPING AND JOINTING
®
GTEC TAPING AND JOINTING GTEC drywall systems require taping and jointing to complete the wall surface, reinforce joints to prevent cracking, and ensure fire and sound performances are achieved. GTEC Taping and Jointing products use limited combustibility, gypsum and limestone based compounds which secure the fire rating of the system. These are reinforced with paper tape or corner beads to create a smooth, durable surface, ready for decoration. Two and three stage processes are available using the correct GTEC Finish products to provide options on site and different setting times. Water resistant compounds and finishing accessories are available for GTEC Aqua Board. The GTEC Deco compound range complements the use of GTEC Megadeco for direct decoration.
WHERE TO USE: Taping and jointing are suitable for large surface areas where speed and ease of application can greatly reduce installation cost and drying time.
FEATURES
BENEFITS
Applied to low surface areas
Quicker than a full plaster skim with less drying out time
Can be used with automatic taping tools
Flexible, high speed application
Can be hand applied
Versatile enough to suit any job
Wide product range
Suitable for different applications and needs
Gypsum/limestone finish
Excellent finish quality with limited combustibility
Two and three stage processes
Provides a range of speed and product options
GTEC速 TAPING AND JOINTING
SYSTEM COMPONENT TABLE System Component
System primary use
BOARDS All GTEC Boards (see specialist compounds for Aqua & Megadeco) Provides wall surface suitable for finishing.
FINISHING GTEC Joint Filler Xtra Gypsum based joint compound for filling joints in plasterboards, 90 minute set time GTEC Joint Cement Xtra Air-drying joint cement for finishing joints
GTEC Easy Finish Extra All purpose compound suitable for all stages of the jointing process with 90 minute set time GTEC Smartmix Ready mixed all purpose jointing compound suitable for all stages of the jointing process GTEC Aquamix Ready mixed all purpose jointing compound for use with GTEC Aqua system in severe wet applications GTEC Deco Filler An all purpose gypsum based joint filler for use with GTEC Megadeco. 90 minute set time GTEC Deco Joint Cement An air drying ready mixed compound for finishing joints with GTEC Megadeco GTEC Deco Machine An air drying ready mixed compound for use with automatic taping tools to finish joints with GTEC Megadeco GTEC Joint Tape Joint reinforcement in conjunction with GTEC Jointing Compounds
GTEC Aquastrip Mesh tape for use with GTEC Aqua system to protect exposed drylining perimeters for wet applications
GTEC Sealers To seal plasterboard prior to decoration
GTEC Corner and Edge beads Corner and edge reinforcement
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
279
280
GTEC® TAPING AND JOINTING
SYSTEM GUIDANCE COMPOUND SELECTION Joint compound selection is largely a matter of site preference, depending on weather conditions, time and equipment. GTEC Compounds can be combined in numerous permutations each offering a high quality surface finish. However, GTEC Aqua Board and
GTEC Megadeco require specific compounds to suit their unique facers. Taping and jointing is conducted in three main stages: Bedding; Second Coat; and Finishing Coat.
TWO STAGE PROCESS
1
THREE STAGE PROCESS BEDDING Tape or bead is bedded into the compound and taper filled out
SECOND COAT The taper is re-filled with compound where required
1 2
FINISHING COAT
2
Final compound layer is applied and sanded for a smooth finish
3
COMPOUND TYPES All compounds are suitable for Bedding and Second Coat, however, setting and hybrid compounds reduce overall time required. Setting and hybrid compounds must not be used over air-drying compounds. Only air-drying or hybrid compounds are suitable for the final finishing coat.
Air-drying and hybrid compounds are low shrinkage. Where low shrinkage compounds have been used in Bedding layer the Second Coat may not be required. The drying time of air-drying compounds is dependent on climatic conditions and layer thickness. Drying takes approximately 24 hours but may be extended by adverse conditions.
GTEC® TAPING AND JOINTING
GTEC Compound
Format
Type
Joint Filler Xtra
Powder
Setting
Compatible Boards
Machine Use
Shrinkage
Setting Time
No
Standard
90 mins
Yes
Low
n/a
All Joint Cement Xtra
Powder
Air-drying
Smartmix Xtra
Readymix
Air-drying
optional
Yes
Low
n/a
Easy Finish Xtra
Powder
Hybrid
optional
No
Low
90 mins
Aquamix
Readymix
Air-drying
GTEC Aqua Board
Yes
Standard
n/a
Deco Filler
Powder
No
Standard
90 mins
No
Low
n/a
Yes
Standard
n/a
Setting
Deco Joint Cement
Readymix
Air-drying
Deco Machine
Readymix
Air-drying
GTEC Megadeco only
SUBSTRATE Plasterboard to be tapered edged to allow GTEC Joint Tape to sit below finished surface for best finish. Square edged plasterboard may also be jointed following guidance in drawings.
Gaps over 3mm to be filled with GTEC Joint Filler Xtra or GTEC Easy Finish. Taping & jointing should not be carried out at extreme temperatures (greater than 40ºC or less than 5ºC). Do not tape and joint on frozen backgrounds.
Board surfaces to be dry, clean, protected from weather, secure and evenly fixed. Correct screw fixings to be used with screw heads just below surface of board.
TAPING & JOINTING FN-TJ-101&102M – Tapered edge
Bed tape into layer of appropriate jointing compound
GTEC Joint tape and bedding layer Stage 1 bedding layer struck off with plasterboard face
Ma 60 x. mm Ma 60 x. mm
30 0m m GTEC Joint Tape
Second coat feathered out on to plasterboard
Stage 2
Finishing layer feathered out on to plasterboard and sanded once dry
Stage 3
ap pro x.
ISOMETRIC
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
281
282
GTEC® TAPING AND JOINTING
FN-TJ-103&104M – Square or cut edge
GTEC Joint Tape and Bedding layer
Bed tape into layer of jointing compound
Stage 1
bedding layer down both edges of tape
20 0m m
Second coat feathered out beyond filling layer
Stage 2
Finishing layer feathered out on to plasterboard and sanded once dry
Stage 3
20 0m m
40 0m m
GTEC Joint Tape
ISOMETRIC FN-TJ-105 & 106M – Internal corner Tape bedded into layer of jointing compound
GTEC Joint Tape and bedding layer
Stage 1
Second coat feathered out beyond bedded layer
Stage 2
Finishing layer feathered out on to plasterboard and sanded once dry
Stage 3
GTEC Joint Tape
ISOMETRIC FN-TJ-107&108M – External corner Tape bedded into layer of jointing compound
Tape and bedding layer
filling layer feathered out
Second coat feathered out Finishing layer feathered out on to plasterboard and sanded once dry
GTEC Flex Tape / GTEC Corner 90º External
ISOMETRIC
GTEC® TAPING AND JOINTING
Screws to be spotted with appropriate jointing compound. Compound to be applied in nominal 1mm layers. Thicker layers will extend drying out time. GTEC Joint Tape cut to length to be pressed into bedding compound without trapping air bubbles, bedding layer of compound to be flush with plasterboard face. Pound to be flush with plasterboard face. Second coat of jointing compound if required to be applied over dry joint, feathered out 5060mm beyond the edge of first coat. Second coat to be set hard or dry prior to third stage. Finishing coat of compound feathered out 50-60mm beyond second coat. Finished, dry joint to be sanded to smooth finish for sealing and decoration.
Square edge joints only: Joint width to be wider to reduce visible crowning. External corners only: GTEC Flex Tape to be applied in place of GTEC Joint Tape as reinforcement. Machine application: Air-drying compounds only to be used in automatic taping machines. Setting compounds such as GTEC Joint Filler or GTEC Allset Xtra are not suitable for automatic taping machines. High and Severe Moisture Exposure: GTEC Aquamix compound to be used in high and severe moisture/humidity exposure areas. In areas of severe moisture exposure GTEC Aqua Board to be coated with two layers of GTEC Drywall Sealer.
DECORATION Surfaces and joints to be dry prior to finishing.
Two coats of GTEC Drywall Sealer can provide 15 MNs/g vapour barrier.
Joint to be sanded smooth for decoration. Surfaces to be dust free prior to sealing.
Paint to be applied in accordance with manufacturer’s instructions to dry and dust free surface.
Seal with GTEC Universal Sealer prior to paint application to improve whiteness and paint coverage. GTEC Megadeco Boards and GTEC Deco joints together do not require sealing.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
283
284
SKIMMING
SKIMMING A traditional skimming plaster finish provides a surface ready to be decorated and is an alternative to GTEC Taping and Jointing in certain applications. It is particularly suitable where the quality of board installation is poor, as it will cover surface imperfections, and where drying out time is not important. Most GTEC Boards are designed to accept skim plasters.
SYSTEM GUIDANCE APPLICATION Skim plaster can be applied by hand or machine. Refer to skim plaster manufacturer’s instructions for application details. Moisture resistant GTEC Boards (GTEC MR range and GTEC LaDura) to be pre-treated with bonding agent by others. Board to be clean of dust, dirt and grease, and sufficiently true to allow the specified thickness of plaster.
FINISHING Skim plaster to be allowed to dry out thoroughly before decoration or tiling is started. Paint manufacturer’s instructions should be followed for decorating to new plaster.
GTEC Board
Suitable for Skim
Pre-treatment
Standard Board
Yes
None
Plank
Yes
None
Contour
Yes
None
Base Board
Yes
None
Vapour Board
Yes
None
Vapour Base Board
Yes
None
Moisture Board
Yes
Bonding agent
Fire Board
Yes
None
Fire MR Board
Yes
Bonding agent
Fire V Board
Yes
None
Fire Core Board
Yes
Bonding agent
E Board
Yes
None
dB Board
Yes
None
Acoustic Homespan
Yes
None
Acoustic Homespan MR
Yes
Bonding agent
Megadeco
No
n/a
Universal Board
Yes
None
Thermal
Yes
None
Thermal XP
Yes
None
Thermal K
Yes
None
LaDura
Yes
Bonding agent
Aqua Board
No
n/a
Render Board
No
n/a
TILING
TILING Internal dry-lined surfaces are suitable for tiling in a wide variety of applications in both domestic and commercial applications including showers, toilets and bathrooms as well as permanently wet areas such as swimming pools. Ceramic tiling can be applied to GTEC Aqua, LaDura and Moisture Boards for use in wet, moist or humid areas. Tiling can be applied to any board if the area is generally dry, such as decorative tiles in a corridor. Vertical frame centres for linings and partitions to be determined by system height and tile weight. Advice in the subsequent section is for low, medium, high and severe humidity applications.
Normal conditions
Low to Medium Humidity
High to Severe Humidity
GTEC Board
General internal applications
Washrooms, toilets, kitchens, bathrooms
Swimming pool, spa, wet rooms, public showers
Aqua Board
Moisture Board
LaDura
All other boards
x
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
285
286
TILING
FN-TL-001M ‘Low to High Humidity’
FN-TL-002M ‘Severe Humidity’
GTEC Aqua Board / GTEC Moisture Board / GTEC LaDura Board
GTEC Joint Tape and tile adhesive
Tile adhesive by others
GTEC Aqua Board
GTEC Aquamix bedding layer only
2 coats of GTEC Drywall Sealer applied prior to tile adhesive
Tile adhesive by others Tiles by others
Tiles by others
GTEC Aquastrip bedded in Drywall Sealer
ISOMETRIC
ISOMETRIC
TILING
SYSTEM GUIDANCE SUBSTRATE All surfaces to be clean and dust free with all loose material removed.
Where primer is recommended follow manufacturer’s instructions.
BONDING Tiles to be fixed in accordance with BS 5385. Ceramic, glazed and stone tiles to be fixed directly to board using waterproof adhesive which is suitable for plasterboard substrates. Tiles not to exceed maximum weight per metre depending on board type.
Maximum weight of tiles by type of board at 400mm stud centres: Maximum weight of tiles* GTEC Moisture Board
32kg/m²
GTEC LaDura Board
32kg/m²
GTEC Aqua Board
36kg/m²
*for greater tile weight please contact Technical Enquiryline for recommendations
BOARDING Untiled areas to be taped and jointed, see GTEC Taping and Jointing section, p278. Taper edge boards to be used to enable formation of flush joints in untiled areas and to ensure flat substrate for tiling.
Drylining systems using GTEC Universal Bonding Compound in their construction to be allowed 10 days to achieve full strength before tiling.
FINISHING For concealed joints only GTEC Joint Tape may be bedded with waterproof, ceramic tile adhesive. Untiled areas to be taped and jointed using GTEC Aquamix. In severe humidity areas tiles to be finished with suitable waterproof tile grout and sealed if required.
Seal around pipes, baths, shower fittings, openings and outlets with waterproof silicone sealant. In areas of severe humidity GTEC Drywall Sealer with GTEC Aquastrip to be used to protect base of partition/lining.
Details at junctions, corners and perimeters to be designed to prevent moisture penetration.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
287
288
GTEC® COVE
®
GTEC COVE GTEC Cove provides a decorative feature to the ceiling and wall junction, masking unsightly cracks and improving the acoustic mass and sealing along the junction. GTEC Cove is made from gypsum encased in a profiled and strong paper liner, available in two sizes, 90 and 120mm. It is bonded to the wall and ceiling using GTEC Cove Adhesive and it is easy to work with, rigid and provides an excellent surface for decoration.
WHERE TO USE: Used in domestic new build or renovation projects to complement the wall and ceiling junction.
FEATURES
BENEFITS
Flat rear profile
Easy to fix
Decorative shape
Distinctive feature
Gypsum product with paper finish
Easy to decorate and lightweight
Mitre cut to create continuos profile
fix with continuous bead of GTEC Cove Adhesive
GTEC速 COVE
SYSTEM COMPONENT TABLE System Component
System primary use
Product Reference
GTEC Cove Gypsum plaster moulding used to finish the junction of walls and ceilings
n/a
GTEC Cove Adhesive Gypsum based adhesive, 40 minute setting time for fast fixing of cove
n/a
GTEC Universal Sealer Use prior to painting to improve brightness and coverage
n/a
COVE
FIX
FINISH
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
289
290
GTEC® COVE
SYSTEM GUIDANCE COVING FN-CV-101S – Cove 90 and 120
Substrate to be dry, rigid and dust free, with any wallpaper, whitewash or loose decoration removed. Surfaces which have been previously painted to be abraded and coated bonding agent. Nails to be installed below cove location and at 1500mm centres to act as temporary support while cove adhesive sets. 84mm
m 0m 12
GTEC Cove Adhesive to be applied in 3mm thick and 10mm wide beads along full length of each edge of GTEC Cove. GTEC Cove Adhesive to fill any gaps between cove and wall or ceiling.
GTEC Cove 120
With uneven ceilings it may be necessary to permanently nail cove 25mm from one edge. Nail heads should be countersunk and covered with GTEC Cove Adhesive. Ensure temperature does not fall below 5ºC.
64mm
m m 90
GTEC Cove 90
PLAN
FINISHING Coat of GTEC Universal Sealer to be applied to enhance paint coverage and finish.
Plasterboard strips may be added between coving and ceiling to add extra stepped features. Visible edges of plasterboard strips to be bound edges for decoration.
291
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
292
REFERENCE
293
REFERENCE Product Reference GTEC Board
294
GTEC Frame
308
GTEC Fix
321
GTEC Finish
324
ProďŹ le Guide Screw Selection Guide Sustainability Health and Safety Standards Index
332 334 336 341 342 344
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
294
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD GTEC Standard Board A simple, lightweight and cost-effective board. Standards: BS EN 520 Type A (formerly BS 1230 Type 1) Composition: Aerated calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers bonded with starch and PVA edge glue. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Standard Board can be jointed and finished with the GTEC Joining Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE)
Breaking Loads (acc. BS EN 520) Long.
Trans.
9.5
1.8 to 2.7
900, 1200
5.95
0.052m2K/W
0.25
≥ 400N
≥ 160N
12.5
1.8 to 3.0
900, 1200
8.2
0.064m2K/W
0.25
≥ 550N
≥ 210N
2
1.8 to 3.0
900, 1200
10.0
0.079m K/W
0.25
≥ 650N
≥ 250N
9.5
1.8 to 2.4
900, 1200
5.95
0.052m2K/W
0.25
≥ 400N
≥ 160N
12.5
1.8 to 3.0
900, 1200
8.2
0.064m2K/W
0.25
≥ 550N
≥ 210N
0.25
≥ 650N
≥ 250N
15.0 Square Edge (SE)
15
2.4
900, 1200
10.0
2
0.079m K/W
GTEC Plank A 19mm version of GTEC Standard Board for use in flooring applications. Standards: BS EN 520 Type A (formerly BS 1230 Type 1) Composition: Aerated Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Plank Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Long.
Tapered Edge (TE) 19
Breaking Loads (acc. BS EN 520) Trans.
2.4
600
13.8
R = 0.099m²K/W
λ = 0.25
≥ 1000N ≥ 500N
2.4
600
13.8
R = 0.099m²K/W
λR = 0.25
≥ 1000N ≥ 500N
R
Square Edge (SE) 19
PRODUCT REFERENCE – GTEC® BOARD
GTEC Contour Board A strong, light-weight and flexible 6mm board for creating curved walls and ceilings. Standards: BS EN 520 type D (formerly BS 1230 Type 1) Composition: Aerated calcium sulphate di-hydrate with liners made from re-cycled waste paper. The core is high density gypsum re-enforced with chopped strands of glass fibre. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Contour Board can be jointed and finished with GTEC Jointing Systems. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 6
2.4
1200
5.5
R = 0.026m²K/W
λR = 0.25
Breaking Loads (acc. BS EN 520) Long.
Trans.
> 258
> 100,8
GTEC Base Board A 4 foot long ceiling board ideal for skim plastering. Sold in complete pallets only. Standards: BS EN 520 Type P (formerly BS 1230 Type 2 and 6) Composition: Aerated Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Base Board is designed for skim finishing Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Square Edge (TE) 9.5
1.22
900
5.95
R = 0.050m²K/W
λR = 0.25
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 180
≥ 125
*Some combinations of length and widths may not be commonly available.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
295
296
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD continued GTEC Vapour Board GTEC Standard Board with an additional laminated vapour control layer. Standards: BS EN 520 Type A (formerly BS1230 Type1) and BS EN 14190 Composition: GTEC Vapour Board has the same physical properties as GTEC Standard Board but has a silver metallised polyester film back liner to enhance vapour resistance. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Vapour Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE)
Breaking Loads (acc. BS EN 520) Long.
Trans.
9.5
1.8 to 2.7
900, 1200
5.95
0.052m2K/W
0.25 W/mK
≥ 400N
≥ 160N
12.5
1.8 to 3.0
900, 1200
8.2
0.064m2K/W
0.25 W/mK
≥ 550N
≥ 210N
15.0
1.8 to 3.0
900, 1200
10.0
0.079m2K/W
0.25 W/mK
≥ 650N
≥ 250N
9.5
1.8 to 2.4
900, 1200
5.95
0.052m2K/W
0.25 W/mK
≥ 400N
≥ 160N
12.5
1.8 to 3.0
900, 1200
8.2
0.064m2K/W
0.25 W/mK
≥ 550N
≥ 210N
15
2.4
900, 1200
10.0
0.079m2K/W
0.25 W/mK
≥ 650N
≥ 250N
Square Edge (SE)
GTEC Vapour Base Board GTEC Base Board with an additional laminated vapour control layer. Standards: BS EN 520 Type P (formerly BS 1230 Type 2 and 6) and BS EN 14190 Composition: GTEC Vapour Base Board has the same physical properties as GTEC Base Board but has a silver metallised polyester film back liner to enhance vapour resistance.. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Vapour Base Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
R = 0.050m²K/W
λ = 0.25
Square Edge (TE) 9.5
1.22
900
5.95
*Some combinations of length and widths may not be commonly available.
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 180
≥ 125
PRODUCT REFERENCE – GTEC® BOARD
GTEC Moisture Board A board with water resistant additives designed for use in humid areas. Standards: BS EN 520 Type H1 (formerly BS 1230 Type 3 and 4) Composition: Aerated Calcium sulphate di-hydrate with fillers enclosed inside a green paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Moisture Board can be jointed and finished with GTEC jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating and treating with PVA bonding agent before plastering. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5
Breaking Loads (acc. BS EN 520) Long.
Trans.
2.4 to 3.0
1200
9
R= 0.062m²K/W
λR = 0.24
≥ 550N
≥ 210N
2.4
1200
11.85
R= 0.076m²K/W
λR = 0.24
≥ 650N
≥ 250N
GTEC Fire Board Provides superior fire resistance. Standards: BS EN 520 Types D and F (formerly BS1230 Type 5) Composition: Aerated Calcium sulphate di-hydrate with fire-resisting fillers and fibres enclosed inside a tough pink paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Fire Board can be jointed and finished with GTEC Jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
R= 0.052m²K/W
Long.
Trans.
λ = 0.24
≥ 725N
≥ 300N
Tapered Edge (TE) 12.5 15
1.8 to 3.0
900, 1200
10.2
Breaking Loads (acc. BS EN 520)
R
1.8 to 3.0
900, 1200
12.3
R= 0.062m²K/W
λ = 0.24
≥ 870N
≥ 360N
1.8 to 2.4
900, 1200
10.2
R= 0.052m²K/W
λR = 0.24
≥ 725N
≥ 300N
R
Square Edge (SE) 12.5
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
297
298
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD continued GTEC Fire MR Board Provides both fire and moisture resistance. Standards: BS EN 520 Types D, F and H1 (formerly BS 1230 Types 3, 4 and 5) Composition: Aerated Calcium sulphate di-hydrate with fire-resisting fillers and fibres enclosed inside a tough pink paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Fire MR Board can be jointed and finished with GTEC Jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating. Requires PVA treatment prior to skimming. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5
2.4
1200
10.3
R= 0.05m²K/W
15
2.4 to 3.0
1200
12.5
R= 0.06m²K/W
λR = .25
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 550N
≥ 210N
≥ 650N
≥ 250N
GTEC Fire V Board GTEC Fire Board with an additional laminated vapour control. Standards: BS EN 520 Types D and F (formerly BS1230 Type 5) and BS EN 14190 Composition: GTEC Fire Vapour Board has same physical properties as GTEC Fire Board but has a silver metallised polyester film back liner to enhance vapour resistance Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Fire V Board can be jointed and finished with GTEC Jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5 15
1.8 to 3.0 1.8 to 3.0
900, 1200 900, 1200
10.2 12.3
Breaking Loads (acc. BS EN 520) Long.
Trans.
R= 0.052m²K/W
λR = 0.24
≥ 725N
≥ 300N
R= 0.062m²K/W
λ = 0.24
≥ 870N
≥ 360N
*Some combinations of length and widths may not be commonly available.
R
PRODUCT REFERENCE – GTEC® BOARD
GTEC Fire Core Board High strength fire resistant board for use in GTEC Shaftwall systems, steelwork fire encasement. Standards: BS EN 520 Types D, H1I and R (formerly BS 1230 Types 3, 4 and 5) Composition: Aerated Calcium sulphate di-hydrate with fire-resisting fillers and fibres enclosed inside a moisture resistant paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Fire Core Board can be jointed and finished with GTEC Jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
R= 0.089m²K/W
λ = 0.28
Tapered Edge (TE) 25
3
600
21.6
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 1500N
≥ 700N
GTEC E Board Engineered for use within dwellings to comply with the latest Building Regulations Approved Document E Regulations. Standards: BS 520 Type D (formerly BS 1230 Type 1) Composition: Aerated Calcium sulphate di-hydrate inside tough liner papers with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC E Board can be jointed and finished with any of the GTEC Jointing systems. It can be plastered on either side using single coat proprietary gypsum finishing plasters not less then 2mm thick. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5
2.4
1200
10.2
R = 0.052m²K/W
λR = 0.24
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 550N
≥ 250N
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
299
300
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD continued GTEC dB Board For superior acoustic performance. Standards: BS EN 520 Types D and I (formerly BS 1230 Type 1) Composition: Aerated Calcium sulphate di-hydrate with fillers and fibres enclosed inside tough liner papers with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC dB Board can be jointed and finished with any of the GTEC Jointing systems. It can be plastered on either side using single coat proprietary gypsum finishing plasters not less then 2mm thick. The blue liner paper requires more paint obscuration than normal ivory liner. Allow 10 litres / 100m2. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5
2.4
1200
11
R= 0.046m²K/W
15
2.4 to 3.0
1200
13
R= 0.056m²K/W
λR = 0.27
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 550N
≥ 210N
≥ 700N
≥ 300N
GTEC Acoustic Homespan Board For use with the GTEC Acoustic Homespan Partition System. Standards: BS EN 520 Type D (formerly BS 1230 Type 1) Composition: Aerated Calcium sulphate di-hydrate with fillers and fibres enclosed inside tough liner papers with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Acoustic Homespan Board can be jointed and finished with GTEC Jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 15
2.4 to 2.7
900
12.7
R= 0.060m²K/W
*Some combinations of length and widths may not be commonly available.
λR = 0.27
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 250N
≥ 350N
PRODUCT REFERENCE – GTEC® BOARD
GTEC Acoustic Homespan MR Board For use with the GTEC Acoustic Homespan Partition System when superior moisture resistance is required. Standards: BS EN 520 Type D and H1 (formerly BS 1230 Type 3) Composition: Aerated Calcium sulphate di-hydrate with fillers and fibres enclosed inside a moisture resistant paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Acoustic Homespan MR Board can be jointed and finished with GTEC Jointing systems. The boards require priming with GTEC Universal Sealer prior to decorating. Requires PVA treatment prior to skimming. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
R= 0.060m²K/W
λ = 0.27
Tapered Edge (TE) 15
2.4
900
12.7
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 250N
≥ 350N
GTEC Megadeco Pre-sealed performance board, combining fire and impact resistance with acoustic insulation. Unique to Siniat. Standards: BS EN 520 Type D, F, I and R (formerly BS1230 Type 4 and 5) Composition: Aerated Calcium sulphate di-hydrate with fillers and fibres enclosed inside a white pre-sealed paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Megadeco Board can be jointed and finished with only GTEC Deco jointing systems. The boards require no primer prior to decorating. The board is not suitable for skim plaster finish. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
R= 0.046m²K/W R= 0.055m²K/W
Long.
Trans.
λ = 0.27
≥ 725N
≥ 300N
λ = 0.27
≥725N
≥ 360N
Tapered Edge (TE) 12.5 15
2.4 to 3.0 2.4 to 3.0
1200 1200
11 13
Breaking Loads (acc. BS EN 520)
R
R
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
301
302
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD continued GTEC Universal Board Highly versatile multi-performance board providing outstanding fire, impact and acoustic resistance. Standards: BS EN 520 Type D, F, I and R (formerly BS1230 Type 4 and 5) Composition: Aerated calcium sulphate di-hydrate with fillers and fibres enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Universal Board can be jointed and finished with any of the GTEC Jointing systems. The surface is suitable for finishing with skimming plaster. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5
2.4 to 3.0
1200
11
R = 0.046m²K/W
15
2.4 to 3.0
1200
13
R = 0.055m²K/W
λR = 0.27
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 725N
≥ 300N
≥ 870N
≥ 360N
GTEC LaDura Stronger and harder than standard plaster board, giving greater impact and pull out resistance. Moisture resistant. Offers a far superior finish than gypsum fibreboards. The ultimate in performance plasterboard. Standards: BS EN 520 Type D, E, F, H1, I & R Composition: Aerated calcium sulphate di-hydrate with fillers, glass fibre, wood fibres and moisture resistant agent enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC LaDura Board can be jointed and finished with any of the GTEC Jointing systems Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
λ = 0.25
Tapered Edge (TE) 12.5
2.4 to 3.0
1200
12.8
R= 0.05m²K/W
15
2.4 to 3.0
1200
15.6
R= 0.06m²K/W
*Some combinations of length and widths may not be commonly available.
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 725N
≥ 300N
≥ 870N
≥ 360N
PRODUCT REFERENCE – GTEC® BOARD
GTEC Aqua Board The UK’s first gypsum based board for use in high humidity or wet applications. Ideal as a tile backing board for bathrooms. Can also be used as an external sheathing board. Standards: BS EN 15283 Type GM-F, GM-H1 and GM-I Composition: Aerated Calcium sulphate di-hydrate with liners made from non woven tissue with fillers and fibres enclosed inside gypsum core. Core and papers bonded with starch. Edge glue is PVA. Water resistant additive is silicone oil. Core contains biocide to prevent mould growth. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Aqua Board can be jointed and finished with GTEC Aqua Mix jointing system. In wet areas the boards require priming with GTEC Drywall Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
λ = 0.25
Tapered Edge (TE) 12.5
0.85 to 2.7
1200
10.8
R = 0.05m²K/W
15
2.4 to 3.0
1200
13
R = 0.06m²K/W
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
≥ 500N
≥ 250N
≥ 650N
≥ 300N
GTEC Render Board GTEC Render Board is the pioneering external board for direct render applications. Standards: BS EN 15283 Type GM-F, GM-H1 and GM-I Composition: The board is composed of hydrophobic liner, a water resistant high density gypsum core treated with silicone, antifungi and polymeric additive. Core and liner are bonded with starch. Edge glue is PVA. The core contains a biocide to prevent mould growth. Reaction to fire: Euroclass A2-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 12.5
2.4
1200
10.8
R= 0.05m²K/W
λR = 0.25
Breaking Loads (acc. BS EN 520) Longs.
Trans.
≥ 500N
≥ 250N
ENQUIRYLINE ENQUIRY LINE T: 01275 T: 01234 377789 567 890 E: enquiryline@siniat.co.uk E: enquiry@siniat.com www.siniat.co.uk www.siniat.co.uk
303
304
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD continued GTEC Thermal Board GTEC Standard Board laminated to expanded polystyrene insulation. Standards: BS EN 13950 Composition: Aerated Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Expanded polystyrene (EPS) is factory bonded to 9.5mm board using PVA adhesive. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Thermal Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 22
2.4
1200
6.3
R = 0.36m²K/W
λ = 0.037
30
2.4
1200
6.4
R = 0.57m²K/W
(insulation)
40
2.4
1200
6.5
R = 0.84m²K/W
50
2.4
1200
6.6
R = 1.10m²K/W
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
GTEC Thermal XP Board GTEC Standard Board laminated to extruded polystyrene insulation. Standards: BS EN 13950 Composition: Aerated Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Extruded polystyrene (XPS) is factory bonded to 9.5mm board using PVA adhesive. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Thermal XP Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 27
2.4
1200
6.7
R = 0.61m²K/W
λ = 0.033
35
2.4
1200
6.9
R = 0.88m²K/W
(insulation)
55
2.4
1200
7.4
R = 1.55m²K/W
*Some combinations of length and widths may not be commonly available.
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
PRODUCT REFERENCE – GTEC® BOARD
GTEC Thermal PIR Board GTEC Standard Board laminated to rigid PIR insulation. Standards: BS EN 13950 Composition: Aerated Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Polyisocyanurate Foam is factory bonded to 9.5mm board with various thicknesses using PVA adhesive. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Thermal K Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with TEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 35
2.4
1200
6.8
R = 1.19m²K/W
λ = 0.022
50
2.4
1200
7.3
R = 1.87m²K/W
(insulation)
60
2.4
1200
7.6
R = 2.33m²K/W
R
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
GTEC Thermal K Board GTEC Standard Board laminated to phenolic foam. Standards: BS EN 13950 Composition: Aerated Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges. Core and papers are bonded with starch. Edge glue is PVA. Phenol formaldehyde foam (PF) is factory bonded to 9.5mm board with various thicknesses of using PVA adhesive. Reaction to fire: Euroclass A2-s1, d0 Finishing: GTEC Thermal K Board can be jointed and finished with GTEC Jointing Systems. The boards require priming with GTEC Universal Sealer prior to decorating. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Thermal Resistance: (R)
Thermal Conductivity (W/mk)
Tapered Edge (TE) 30
2.4
1200
7.2
R = 0.94m²K/W
λR = 0.023
40
2.4
1200
7.7
R = 1.50m²K/W
λR = 0.021
50
2.4
1200
8.2
R = 1.98m²K/W
λR = 0.021
60
2.4
1200
8.7
R = 2.58m²K/W
λR = 0.020
70
2.4
1200
9.2
R = 3.08m²K/W
λR = 0.020
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
(insulation)
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
305
306
PRODUCT REFERENCE – GTEC® BOARD
GTEC BOARD continued GTEC Pregybel C10 no. 8 Standards: BS EN 14190 Composition: Standard plasterboard with 10mm square perforations in eight blocks. Perforated area = 16% Reaction to fire: B-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Tapered Edge 12.5
2.4
1200
6.89
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
GTEC Pregybel R12 no. 2 Standards: BS EN 14190 Composition: Standard plasterboard with 12mm round perforations in two blocks. Perforated area = 14% Reaction to fire: B-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Tapered Edge 12.5
2.4
1200
*Some combinations of length and widths may not be commonly available.
7.05
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
PRODUCT REFERENCE – GTEC® BOARD
GTEC Pregybel R15 no. 1 Standards: BS EN 14190 Composition: Standard plasterboard with 15mm round perforations in one block. Perforated area = 16% Reaction to fire: B-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Tapered Edge 12.5
2.4
1200
6.89
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
GTEC Pregybel R15 no. 8 Standards: BS EN 14190 Composition: Standard plasterboard with 15mm round perforations in eight blocks. Perforated area = 11% Reaction to fire: B-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Tapered Edge 12.5
2.4
1200
7.23
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
GTEC Pregybel L5x80 no. 8 Standards: BS EN 14190 Composition: Standard plasterboard with 5 x 80mm line perforations in eight blocks. Perforated area = 11% Reaction to fire: B-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Thickness (mm)
Lengths* (m)
Widths* (mm)
Nominal Weight: (kg/m2)
Tapered Edge 12.5
2.4
1200
7.23
Breaking Loads (acc. BS EN 520) Long.
Trans.
–
–
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
307
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME Thickness (mm)
Width (mm)
Lengths* (m)
Code Ref.
0.52
44
2.4
CS44/RX
0.52
50
2.4, 2.5, 2.7, 3.0, 3.6
CS50/RX
0.52
60
3.0
CS60/RX
0.52
70
2.4, 2.7, 3.0, 3.6, 4.2, 4.8
CS70/RX
GTEC C Studs Galvanised C shaped metal section used with GTEC U Track to provide vertical framework for wall linings and partitions and at abutments in other systems
34
36
Standards: BS EN 14195
W
0.52
90
3.0, 3.6, 4.2
CS90/RX
Composition: Galvanised Steel, hot dipped to BS EN 10346
0.52
146
3, 3.6, 4.2, 6.0
CS146/RX
Reaction to fire: A1
0.7
70
4.2
CS70/B
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
0.7
90
4.2
CS90/B
0.7
146
4.8, 4.6
CS146/B
0.9
90
4.8, 6.0
CS90/W
1.2
70
4.8
CS70/Y
1.2
90
4.8
CS90/Y
1.2
146
6.0
CS146/Y
0.52
44
2.4, 2.7
AHS44/RX
0.52
50
2.4
AHS50/RX
0.52
44
2.4
CS44/RX
0.52
50
2.4
CS50/RX
GTEC Acoustic Homespan C Studs Galvanised C shaped metal section used with GTEC U Track to provide vertical framework for GTEC Acoustic Homespan Partitions Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 36
38
Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
W
GTEC Acoustic Homespan Starter Studs GTEC Acoustic Homespan Starter Studs are used at wall abutments and at door openings as part of the GTEC Acoustic Homespan System Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 38
Reaction to fire: A1 36
308
W
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
*Bespoke lengths to order.
PRODUCT REFERENCE – GTEC® FRAME
Thickness (mm)
Width (mm)
Lengths* (m)
Depth (mm)
Code Ref.
0.52
70
3.6
AS70/RX
0.52
90
4.2
AS90/RX
0.52
146
3
AS146/RX
Galvanised I Shaped metal section used with GTEC U Track to provide a metal frame for the main run of wall linings
0.52
50
3
IS50/RX
0.7
60
3.0, 3.6
IS60/B
0.7
70
3.6, 4.2
IS70/B
Standards: BS EN 14195
0.7
90
6
IS90/B
Galvanised U shaped metal section used to receive GTEC C Studs to provide framework for wall linings and partitions
0.52
45
2.4
30
UT45/RX
0.52
52
3
30
UT52/RX
0.52
62
3
30
UT62/RX
Standards: BS EN 14195
0.52
72
3
30
UT72/RX
Composition: Galvanised Steel, hot dipped to BS EN 10346
0.52
92
3
30
UT92/RX
0.52
148
3
30
UT148/RX
GTEC Acoustic Stud A unique galvanised shaped stud which, when used in a partition system, gives up to 3 Rw dB increased acoustic insulation over standard 70mm metal studs with the same board linings
34
36
Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1
W
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC I Stud
Composition: Galvanised Steel, hot dipped to BS EN 10346 W
Reaction to fire: A1 39
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC U Track
50
Reaction to fire: A1
W
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
*Bespoke lengths to order.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
309
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME continued Thickness (mm)
Width (mm)
Lengths* (m)
Depth (mm)
Code Ref.
0.7
52
3
50
UDT52/B
0.7
62
3
50
UDT62/B
0.7
72
3
50
UDT72/B
Composition: Galvanised Steel, hot dipped to BS EN 10346
0.7
92
3
50
UDT92/B
0.7
148
3
50
UDT148/B
Reaction to fire: A1
1.2
52
3
50
UT52/Y
0.7
72
3
70
UXT72/B
0.9
92
3
70
UXT92/W
0.9
148
3
70
UXT148/W
0.7
0.7
3
GTEC U Track Deep Flange Used for partitions with heights exceeding 4.2m, or at the soffit where a deflection head is required Standards: BS EN 14195
50
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting W
GTEC U Track Extra Deep Flange Used for partitions with heights exceeding 4.2m or at the soffit where a deflection head is required Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
70
310
W
GTEC Flex Track Deep Flange GTEC Flex track is designed to allow easy construction of curved partitions. It is a galvanised 0.7mm metal angle used in place of standard metal GTEC U Tack. It is supplied pre-cut to allow a minimum radius of 600mm to be achieved. Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
*Bespoke lengths to order.
DFLEX/B
PRODUCT REFERENCE – GTEC® FRAME
Thickness (mm)
Width (mm)
Lengths* (m)
Depth (mm)
Code Ref.
0.55
79
3.6
25
MFCC50
0.80
15
3.6
44
MFCP44
0.55
28
3.6
26
MFCE26
1.2
52
3
30
UDT52/Y
GTEC Ceiling Channel Galvanised steel channel used to support boards in the GTEC Suspended MF Ceiling System Standards: BS EN 13964
25
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 50
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC Primary Channel Galvanised steel channel used to support the GTEC Ceiling Channel MFCC50 in the GTEC Suspended MF Ceiling System Standards: BS EN 13964
15
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1
44
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC Edge Channel Galvanised steel channel used to form the perimeter support of the GTEC Suspended MF Ceiling System Standards: BS EN 13964 Composition: Galvanised Steel, hot dipped to BS EN 10346 19
30
Reaction to fire: A1
26
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC Heavy Gauge Primary Channel Used in mass barrier GTEC Suspended MF Ceilings to support increased load Standards: BS EN 13964 Composition: Galvanised Steel, hot dipped to BS EN 10346 30
Reaction to fire: A1
52
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
*Bespoke lengths to order.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
311
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME continued Thickness (mm)
Width (mm)
Lengths* (m)
Depth (mm)
Code Ref.
GTEC Connecting Clip MFCCLIP
A galvanised steel clip for joining GTEC Ceiling Channel to GTEC Primary Channel in single layer systems only Standards: BS EN 13964 Composition: Galvanised Spring Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Soffit Cleat MFCCLEAT
Galvanised steel bracket used to fix angle brackets or strap hanger to the substrate for the GTEC Suspended MF Ceiling System Standards: BS EN 13964 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Dryliner Channel A galvanised steel furring channel for plasterboard fixing in the GTEC Dryliner system Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 17
312
Reaction to fire: A1 47
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
*Bespoke lengths to order.
0.55
47
2.4, 2.7, 3.0, 3.6
17
RD1
PRODUCT REFERENCE – GTEC® FRAME
Thickness (mm)
Width (mm)
Lengths* (m)
Depth (mm)
Code Ref.
0.55
30
3
19
RD9
GTEC Dryliner Track Galvanised metal J shaped section used as a track or perimeter channel in the GTEC Dryliner System Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346
20
30
Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
19
Cavity Depth (mm)
Length (mm)
Overall Width (mm)
Code Ref.
25-60
47
35
RD2
Cavity Width (mm)
Length (mm)
Overall Width (mm)
Code Ref.
25-130
47
35
RD11
GTEC SR Bracket Steel bracket used to brace GTEC Dryliner Channels to substrate in the GTEC Dryliner Ceiling and Lining systems Standards: BS EN 14195
63
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
48
GTEC XR Bracket Extended reach steel bracket used to brace GTEC Dryliner Channels to substrate in the GTEC Dryliner Ceiling and Lining systems Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346
133
Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
48
*Bespoke lengths to order.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
313
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME continued Width (mm)
Length (mm)
Depth (mm)
Code Ref.
47
100
16
RD3
Thickness Depth (mm)
Length (mm)
Depth (mm)
Width (mm)
Code Ref.
0.52
2400
15
79
MFCS/RX
Thickness (mm)
Width (mm)
Length* (m)
Code Ref.
0.7
60
3000
CHS60/B
0.7
60
4800
CHS60/B
0.7
90
6600
CHS90/B
0.7
146
6000
CHS146/B
GTEC Dryliner Channel Connector A galvanised clip used to join GTEC Dryliner Channels (RD1) Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Shallow Wall Channel Galvanised channel for dabbing to walls or for shot-firing to masonry walls. Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 43 15
Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
18
GTEC CH Stud Light-weight non-loadbearing steel sections which are installed between GTEC Fire Core Board and provide the bearing surface to which plasterboard is applied in GTEC Shaftwall system
35
Standards: BS EN 14195 25
314
W
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
PRODUCT REFERENCE – GTEC® FRAME
Thickness (mm)
Width (mm)
Length (m)
Code Ref.
0.7
60
3.0, 4.8
ES60/B
0.7
90
6.6
ES90/B
0.7
146
6
ES146/B
0.7
62
3
JT62/B
0.7
92
3
JT92/B
0.7
148
3
JT148/B
3
RBD3000/RX
GTEC E Stud Light-weight steel sections used for starter studs, intersections, door openings and end studs in GTEC Shaftwall System Standards: BS EN 14195
25
35
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
W
GTEC J Track Light-weight steel sections positioned at floor and soffit to guide GTEC CH Studs in GTEC Shaftwall system Standards: BS EN 14195
50
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1
25
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
W
GTEC Resilient Bar Acoustic isolation bar for improving the sound performance of a partition or ceiling, and minimising the risk of joints cracking due to timber movement during drying out
0.52
Standards: BS EN 14195 17
45
18
Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
315
316
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME continued Thickness
Max. Steel Flange (mm)
Code Ref.
0.55
17
CB17
0.55
27
CB27
0.55
40
CB40
Total Length (mm)
Min. frame separation (mm)
Code Ref.
106
35
VBRACE
65
35
VBRACE90
GTEC CB Clip Light-weight steel clips friction fitted to flanges of structural steelwork in the GTEC Column and Beam Clip System. Used in conjunction with GTEC Edge Channel. Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 D
Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Acoustic V Brace Acoustic brace for bracing twin wall partitions Standards: BS EN 14195 Composition: Spring steel with black phosphate coating 106
Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Acoustic V Brace 90º Acoustic brace for bracing linings and twin frame partitions Standards: BS EN 14195 Composition: Spring steel with black phosphate coating Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
PRODUCT REFERENCE – GTEC® FRAME
Overall Size (mm)
Coating (mm)
Max Weight (kg)
Code Ref.
50
PHONIMO
120
PHONI
GTEC Phonissimo Acoustic Hanger Heavy duty acoustic suspended ceiling hanger bracket for use with the GTEC Suspended MF Ceiling System. This bracket is capable of supporting services and a secondary ceiling.
70 x 30 x 30
Standards: BS EN 14195 Composition: Spring steel with black phosphate coating Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Phonistar Acoustic Hanger Very heavy duty acoustic suspended ceiling hanger bracket for use with the GTEC Suspended MF Ceiling System. This bracket is capable of supporting services and a secondary ceiling.
55 x 75
Zinc
Standards: BS EN 14195 Composition: Zinc galvanised mild steel / Moulded neoprene elastomeric rubber Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
GTEC Acoustic Floor Clip Metal clip used in the GTEC Acoustic Floor System
50 x 30
RAFC25
Standards: BS EN 14195 Composition: Spring steel with black phosphate coating Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
317
318
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME continued Overall size (mm)
Code Ref.
12 x 27.5 x 38
ISC10
GTEC Staggered Stud Clip A spacing clip for use in GTEC partitions with staggered GTEC I Studs Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
Width (mm)
Length (m)
Code Ref.
50
12
RAFT50
Gauge (mm)
Length (m)
Code Ref.
0.55
25
MFSTRAP
GTEC Resilient Tape Self-adhesive acoustic isolation tape Composition: Natural Rubber with a solvent based acrylic adhesive
GTEC Strap Hanger May be used in lieu of GTEC Metal Angle for ceiling depths up to 1 metre Standards: BS EN 14195 Composition: Galvanised Mild Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling and fitting
PRODUCT REFERENCE – GTEC® FRAME
Flange Width (width) (depth)
Length (m)
Code Ref.
23
30
3.6
MFC
25
25
3.6
MFC
25
50
3.6
MFC
Gauge
Width (mm)
Length (mm)
Code Ref.
0.52
50
2.4
FS50/RX
0.85
90
2.4
FS90
Thickness (mm)
Width (mm)
Length (mm)
Code Ref.
0.9
99
2.4
MFIX/W
GTEC Metal Angle 90° Galvanised versatile metal section used in a number of systems Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 D
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting W
GTEC Flat Strap Galvanised metal GTEC Flat Strap used in linings and partitions to provide support for GTEC Flat Strap Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC Fixing Channel Galvanised metal channel used in linings and partitions to provide support to plasterboard joints and heavy fixtures. Also provides a fire stop Standards: BS EN 14195 Composition: Galvanised Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
319
320
PRODUCT REFERENCE – GTEC® FRAME
GTEC FRAME continued Length (mm)
Code Ref.
3.048
MCJ3048
Width (mm)
Code Ref.
25
INSR
GTEC Movement Control Joint Metal sections fixed between boards to control movement up to 10mm. Composition: Galvanised Steel, hot dipped to BS EN 10346 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC Insulation Hold Metal strip used with timber and metal framing for supporting mineral wool insulation Composition: Galvanised Mild Steel, hot dipped to BS EN 10346 Reaction to fire: A1 Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
PRODUCT REFERENCE – GTEC® FIX
GTEC FIX Size
Coverage Guide
Application
25kg bag
8m² Internal walls
Hand only
5ltr bucket
50m²
Hand application only
25kg bag
5m²
Hand application only
GTEC Universal Bonding Compound Gypsum based compound for direct bonding plasterboard to walls or bonding GTEC Metal Furring Wall Channels to walls. Suitable for bonding GTEC Thermal Boards. Standards: BS EN 14496 Composition: Calcium sulphate hemihydrate with polymer binders Reaction to fire: A2, s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Wall Lining Adhesive For bonding plasterboard to tiles or bonding flooring to plasterboard in some flooring systems Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC E-coat A gypsum based acoustic render for use on party walls prior to direct bonding. Robust Detail approved. Composition: Calcium sulphate hemihydrate and limestone with polymer binders Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
321
322
PRODUCT REFERENCE – GTEC® DRYWALL SCREWS
GTEC DRYWALL SCREWS Length (mm)
Diameter (mm)
Head Type
Drive Type
Thread
Point
25
3.5
Bugle
Phillips 2
Fine
Self-tapping
32
3.5
38
3.5
42
3.5
50
3.5
65
4.2
75
4.2
90
4.8
32
3.5
Bugle
Phillips 2
Coarse
Self-tapping
38
3.5
42
3.5
50
3.5
65
4.2
75
4.2
90
4.8
100
4.8
25
3.5
Bugle
Phillips 2
Fine
Self-drilling
32
3.5
42
3.5
50
3.5
65
4.2
90
4.8
Bugle
Phillips 2
Fine
Self-tapping
Bugle
Phillips 2
Fine
Self-tapping
GTEC Drywall Screw – Self Tapping Screw for attaching plasterboard to light gauge metal. Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Drywall Screw – High Thread Screw for attaching plasterboard to timber framework. Standards: BS EN 14566 Composition: Carbon steel with black phosphate coating
GTEC Drywall Screw – Self Drilling Screw for attaching plasterboard to heavy gauge metal. Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Performance Drywall Screw – Self Tapping For attaching GTEC Performance board to light gauge metal and ceiling systems.
32
3.9
38
3.9
45
3.9
Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Performance Drywall Screw – Wet Area For attaching GTEC Wet Area boards to various substrates. Standards: BS EN 14566 Composition: Carbon steel with ceramic coating
25
3.9
38
3.9
Fine
Self-tapping
42
3.9
Coarse
Self-tapping
32
3.9
Fine
Self-drilling
PRODUCT REFERENCE – GTEC® DRYWALL SCREWS
Length (mm)
Diameter (mm)
Head Type
Drive Type
Thread
Point
13
4.2
Wafer Head
Phillips 2
Fine
Self-tapping
12
4.2
Fine
Self-drilling
13
3.9
Fine
Self-tapping
12
3.9
Fine
Self-drilling
GTEC Drywall Screw – Wafer Head Screw for connecting metal components beneath plasterboard. Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Drywall Screw – Pan Head Screw for connecting metal components.
Pan Head
Phillips 2
Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Drywall Screw – Acoustic Floor – Self Tapping For use with the GTEC Acoustic Floor System.
63
4.2
Countersunk
Phillips 2
Fine
Self-tapping
Bugle
Phillips 2
Fine
Self-tapping
Bugle
Phillips 2
Coarse
Self-tapping
Length (mm)
Plug Material
Pilot Hole Size
60
Red Plastic
8mm
Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Collated Drywall Screws – Self Tapping Strips of 50 collated drywall screws for use with auto-feed drywall tools.
25
3.5
35
3.5
38
3.5
Standards: BS EN 14566
44
3.5
Composition: Carbon steel with zinc coating
GTEC Collated Drywall Screws – High Thread Strips of 50 collated drywall screws for use with auto-feed drywall tools.
38
3.5
51
3.5
Standards: BS EN 14566 Composition: Carbon steel with zinc coating
GTEC Nailable Plugs For the secondary mechanical fixing of GTEC Thermal and GTEC Contour Boards when bonded. Standards: n/a Composition: n/a
80 100 120
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
323
324
PRODUCT REFERENCE – GTEC® FINISH
GTEC FINISH Bag Size (kg)
Coverage Guide
Application
12.5
25m² Bedding & Filling
Hand only
GTEC Joint Filler Xtra GTEC Joint Filler Xtra is a gypsum based joint compound with 90 minute setting time for bedding tapes by hand application.
37m² Bedding only
Standards: Type 1B to BS EN 13963 Composition: Calcium sulphate hemihydrate and limestone with polymer binders Reaction to fire: A1 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Joint Cement Xtra Air-Drying Compound – GTEC Joint Cement Xtra is a light-weight, air-drying joint cement offering superior Coverage Guide and easy sanding. Can be used for bedding tapes and finishing joints in a 2-stage application. Also suitable for machine application.
22.5
64m² Full Taping Operation
Hand or machine application
174m² Finishing Coat only
Standards: Type 3A to BS EN 13963 Composition: Limestone and mica based, containing amounts of vinyl polymers and workability aids Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Easy Finish Xtra Setting/Air-Drying Combined – GTEC Easy Finish – revolutionary and lightweight, GTEC Easy Finish is the ideal jointing compound for same day completion of the jointing application due to a 90 minute setting time. Standards: Type 3B to BS EN 13963 Composition: Calcium sulphate hemihydrate and limestone with polymer binders Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
10
64m² Full Taping Operation 174m² Finishing Coat only
Hand application only
PRODUCT REFERENCE – GTEC® FINISH
Size (kg)
Coverage Guide
Application
20
50m2 Full Taping Operation
Hand or machine application
GTEC Smartmix Xtra Air-Drying Compound Ready Mixed – GTEC Smartmix Xtra is a light-weight compound offering superior coverage and easy sanding. Can be used for bedding tapes and finishing joints in a 2-stage application. Ideal for machine application.
135m2 Finishing Coat Only
Standards: Type 3A to BS EN 13963 Composition: Limestone and mica based, containing amounts of vinyl polymers and workability aids. Water based. Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Aquamix GTEC Aquamix is a water resistant readymixed joint cement. For use in humid and wet applications
5 20
50m² Full Taping Operation
Hand application only
135m² Finishing Coat Only
Standards: Type 3A to BS EN 13963 Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
(20kg)
GTEC Deco Filler Deco Setting Compound – GTEC Deco Filler is a gypsum based compound designed for bedding and filling joints by hand when using the GTEC Deco System.
12.5
25m² Bedding & Filling only
Hand application only
Standards: Type 1B to BS EN 13963 Composition: Calcium sulphate hemihydrate and limestone with polymer binders Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
325
326
PRODUCT REFERENCE – GTEC® FINISH
GTEC FINISH continued Size (kg)
Coverage Guide
Application
20
50m² Full Taping
Hand or machine application
GTEC Deco Joint Cement Deco Air-Drying Compounds Ready Mixed – GTEC Deco Joint Cement is a light-weight, readymixed compound which must be used for the final coat of the jointing process and can be used for bedding and filling when using the GTEC Deco System.
135m² Finishing Coat only
Standards: Type 3A to BS EN 13963 Composition: Limestone and mica based, containing amounts of vinyl polymers and workability aids. Water based. Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Deco Machine Deco Air-Drying Compounds Ready Mixed – GTEC Deco Machine is a light-weight, readymixed compound formulated for use with Premier International Taping Tools. As with GTEC Deco Joint Cement, GTEC Deco Machine must be used for the final coat of the jointing process when using the GTEC Deco System. Standards: Type 3A to BS EN 13963 Composition: Limestone and mica based, containing amounts of vinyl polymers and workability aids. Water based. Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
20
50m² Full Taping 135m² Finishing Coat only
Machine only
PRODUCT REFERENCE – GTEC® FINISH
Roll Size (m)
Nominal Width (mm)
150
53
90
52
33
51
50
100
GTEC Joint Tape White perforated cross fibre tape for reinforcing joints. Suitable for hand or mechanical application with GTEC Jointing Compounds. Standards: BS EN 13963 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Patching Tape Self adhesive fibreglass tape for patching plasterboard. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Flex Tape Cross fibre paper tape with heat bonded zinc coated steel strips for the protection of external corner angles. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Aquastrip This mesh strip is used in the GTEC Aqua System to protect exposed drylining perimeters for wet applications. Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
327
328
PRODUCT REFERENCE – GTEC® FINISH
GTEC FINISH continued Length (mm)
GTEC Corner 90º External Tape-On Beads are a paper tape reinforced with galvanised metal for protection of external corners and board edges. Used for taping and jointing.
2400 3000
Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Duo Bead Galvanised steel angle bead with 3mm nose for drywall corner reinforcement.
2400 3000
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
GTEC Edging Bead Galvanised steel bead gives a neat edge to plasterboard. Perforated to provide a key for jointing compound.
3000
Health and Safety: Always wear protective gloves and eyewear when handling, cutting and fitting
Bucket Size (kg)
Coverage Guide
Application
10
100m² One coat
Hand application only
10
100m² One coat
Hand application only
GTEC Universal Sealer For use on plasterboard prior to painting for improved whiteness and covering power. Does not provide a vapour control layer. Composition: A blend of limestone and silica fillers dispersed with polymers Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Drywall Sealer Ivory, pre-decoration coat for plasterboard. Can provide 15 MNs/g vapour check, with two coats. Composition: Aqueous, modified adhesive based on polyvinyl acetate Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
70m² Two coats
PRODUCT REFERENCE – GTEC® FINISH
Length (mm)
GTEC Cove 90 Gypsum plaster moulding in a traditional cove profile, provides an attractive feature at the junction of walls and ceilings.
3000
Standards: BS EN 14209 Composition: Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges Reaction to fire: Euroclass A2-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
GTEC Cove 120 Gypsum plaster moulding in a larger traditional cove profile, provides an attractive feature at the junction of walls and ceilings.
3000 3600 4200
Standards: BS EN 14209 Composition: Calcium sulphate di-hydrate enclosed inside a tough paper with bound edges Reaction to fire: Euroclass A2-s1, d0 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
Bag Size (kg)
Coverage Guide
Application
5
11 linear metres (approx)
Hand application only
33 linear metres (approx)
40 minute setting time
GTEC Cove Adhesive A gypsum based adhesive with a 40 minute setting time for fast fixing of cove. Composition: Calcium sulphate hemihydrate with Polymer binders
12.5
Reaction to fire: A2 Health and Safety: Please read the relevant Health and Safety Datasheet available on our website or through Technical Enquiryline
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
329
330
PRODUCT REFERENCE – GTEC® FINISH
GTEC FINISH continued Pad Size (mm)
Thickness (mm)
Size
Code Ref.
170 x 170
4
Single socket
PAD1
230 x 170
4
GTEC Socket Pads GTEC Socket Pads are used to protect the fire and acoustic integrity of partitions where electrical sockets are used.
PAD2 Double socket
Size (ltr)
Coverage (6mm Bead)
Colour
Maximum joint width (mm)
0.9
29 linear metres
White
25
White
2
0.38
12 linear metres
0.6
17 linear metres
GTEC Intumescent Acoustic Sealant Gun applied water based sealant for use as an acoustic sealant, resilient adhesive, decorators caulk or as intumescent mastic to seal air gaps at system perimeter. Composition: Acrylic emulsion containing inert fillers and fungicide
331
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
PROFILE GUIDE
PROFILE GUIDE width
GTEC C Stud – W gauge (CS)
GTEC C Stud – Y gauge (CS)
UT
30
50
70
GTEC C Stud – RX and B gauge (CS)
C Stud (CS)
width
width
Width (mm)
Gauge
44 50 60 70 90 146
RX
33
36
34
36
34
36
GTEC STUD AND TRACK PROFILES
–
–
–
70 90 146
–
–
–
–
90
–
–
–
–
90 146
–
B W Y
Width (mm)
Gauge
45 52 62 72 92 148
RX
–
52 62 72 92 148
B
–
52
–
–
Y
–
–
–
–
–
–
–
72
UDT width
width
width
GTEC U Track (UT)
GTEC U Track Deep Flange (UDT)
GTEC U Track Extra Deep Flange (UXT)
–
–
92 148
W
UXT –
–
B
39
Width (mm)
34
36
38
W
36
AHS 44 50
width
width
GTEC I Stud (IS)
GTEC Acoustic Homespan Stud (AHS)
AS
–
–
–
–
–
50
–
–
–
–
Gauge –
–
70 90 146 –
–
RX RX
–
RX
–
B
IS 60 70 90
GTEC Acoustic Stud (AS) Gauge Thickness
RX B W Y
0.52mm 0.70mm 0.90mm 1.2mm
GTEC ACCESSORIES GTEC Flat Strap 50
45
106
90
41 11
17
(FS50/RX)
18 GTEC Resilient Bar (RBD3000/RX)
(FS90/W)
GTEC Acoustic V Brace (VBRACE)
GTEC Movement Control Joint (MCJ304D)
GTEC Metal Angle
25 (MFC2550)
25 (MFC2525)
6
23
25
50
332
30 (MFC2330)
98 GTEC Fixing Channel (MFIX/W)
All dimensions are in mm
PROFILE GUIDE
30
25
15
19
30
GTEC SUSPENDED MF CEILING PROFILES
26
44
50
GTEC Edge Channel (MFCE26)
52
GTEC Ceiling Channel (MFC50)
GTEC Primary Channel (MFCP44)
GTEC Heavy Guage Primary Channel (UDT52/Y)
17
20
30
GTEC DRYLINER PROFILES
19
47
63
133
GTEC Dryliner Channel (RD1)
GTEC Dryliner Track (RD9)
15
10
43
48
30
18
GTEC CR Bracket (RD7)
GTEC Shallow Wall Channel (MFCS/RX)
48 GTEC SR Bracket (RD2)
GTEC XR Bracket (RD11)
Gauge Thickness
RX B W Y
0.52mm 0.70mm 0.90mm 1.2mm
25
25
Width (mm)
Gauge
JT
62 92 148
B
ES
60 90 146
B
CHS 60 90 146
B
35
50
GTEC FIRE PROTECTION PROFILES
width
width GTEC E Stud (ES)
depth
35
GTEC J Track (JT)
Depth (mm) CB CLIP
25
17
27
40
width GTEC CH Stud (CHS)
GTEC CB Clip (CB)
All dimensions are in mm
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
333
334
SCREW SELECTION GUIDE
SCREW SELECTION GUIDE GTEC Drywall Screws are a comprehensive range of mechanical ďŹ xings essential for use in GTEC systems. All screws have been rigorously tested for mechanical characteristics such as shear and pull-out, allowing the design of systems with superior levels of structural performance. Only the use of GTEC screws will enable maximum heights and loadings to be achieved safely. GTEC Drywall Screws are fully CE marked and compliant with BS EN 14566. Purpose Fixing boards to timber framing Fixing boards to metal framing Fixing boards to metal framing Fixing boards to timber framing Fixing boards to metal framing Fixing boards to metal framing
Board Density
Min. Length
Thread & Point
Product
Timber
Board(s) Thickness + 25mm
Coarse, self-tapping
GTEC High Thread Drywall Screw
Thin gauge metal Rx (0.52mm) & B (0.7mm)
Board(s) Thickness + 10mm
Fine, self-tapping
GTEC Self-Tapping Drywall Screw
Thick gauge metal W (0.9mm) & Y (1.2mm)
Board(s) Thickness + 10mm
Fine, self-drilling
GTEC Self-Drilling Drywall Screw
Timber
Board(s) Thickness + 25mm
Coarse, self-tapping
GTEC HD High Thread Drywall Screw
Thin gauge metal Rx (0.52mm) & B (0.7mm)
Board(s) Thickness + 10mm
Fine, self-tapping
GTEC HD Self-Tapping Drywall Screw
Thick gauge metal W (0.9mm) & Y (1.2mm)
Board(s) Thickness + 10mm
Fine, self-drilling
GTEC HD Self-Drilling Drywall Screw
Timber
Board(s) Thickness + 25mm
Coarse, self-tapping
GTEC Wet Area High Thread Drywall Screw
Thin gauge metal Rx (0.52mm) & B (0.7mm)
Board(s) Thickness + 10mm
Fine, self-tapping
GTEC Wet Area Self-Tapping Drywall Screw
Thick gauge metal W (0.9) & Y (1.2)
Board(s) Thickness + 10mm
Fine, self-drilling
GTEC Wet Area Self-Drilling Drywall Screw
Lower 12.5mm < 11kg/m2 15mm < 13kg/m2
Higher 12.5mm > 11kg/m2 15mm > 13kg/m2
Fixing boards to timber framing in wet areas Fixing boards to metal framing in wet areas
Substrate
All
Fixing boards to metal framing in wet areas Fixing metal to metal below board layer
n/a
All metal gauges
n/a
Fine, self-drilling
GTEC Wafer Head Drywall Screw
Fixing metal to metal, generally
n/a
All metal gauges
n/a
Fine, self-drilling
GTEC Pan Head Drywall Screw
Fixing floorboards to boards and metal angles in GTEC Acoustic Floor System
All
n/a
n/a
Fine, self-tapping
GTEC Acoustic Floor Screw
Secondary board retention
All
Masonry
Thickness of board + 25mm
Nail
GTEC Nailable Plug
SCREW SELECTION GUIDE
RF-SC-001-Fixing to metal framing
SCREW SELECTION Select screws based on application, substrate and board density outlined in table above. Higher density boards are those with a weight of 11kg/m2 and above for 12.5mm boards and 13kg/m2 and above for 15mm boards.
Min.13mm
Min.10mm
CUT EDGES
BOUND EDGES
For timber substrates minimum length of screws to be total board thickness plus 25mm penetration into the substrate. For metal substrates minimum length of screws to be total board thickness plus 10mm penetration into the substrate.
Min.10mm
Min. 3mm
When fixing to GTEC Resilient Bar screws must be fixed to bar only and not penetrate into metal or timber substrate below. RF-SC-002 -Fixing to timber framing
SCREW POSITIONING Screws to be located minimum of 10mm from bound edges. Screws to be located minimum of 13mm from cut edges. Screw location for timber studs to be minimum of 6mm from edge of stud.
Min.13mm
CUT EDGES
Screw location for metal frame to be minimum of 3mm from edge of profile.
MAXIMUM SPACINGS
Min.10mm
BOUND EDGES
Min.25mm
Min. 3mm
GTEC Partitions – 300mm. See section for more detailed guidance. GTEC Linings – 300mm. See section for more detailed guidance. GTEC Fire Protection systems – 300mm. See section for more detailed guidance. GTEC Ceilings – 150mm at perimeters and/ or cut edges, and 230mm in field of board and/or bound edges. See section for more detailed guidance.
RF-SC-003-Point and thread types
Fine thread, self-tapping
Coarse thread,
FINISHING
self-tapping
Screw heads to be driven into board until slightly recessed into board surface. Screws heads to be sealed with GTEC Drywall or Universal Sealer and spotted with GTEC Jointing Compound to create flush finish.
Fine thread, self-drilling
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
335
336
SUSTAINABILITY
SUSTAINABILITY SINIAT AND SUSTAINABILITY Plasterboard is fully recyclable – with no loss in quality GTEC Products and Systems are BRE Green Guide A and A+ rated and help collect sustainability code credits Unique product innovations minimise the number of boards needed in a design Certified and managed sustainability: Responsible Sourcing BES 6001, ISO 9001 and ISO 14001 Full plasterboard site waste collection and recycling from GTEC Wasteline Direct The leading recycler of post-consumer plasterboard waste per unit sales (2009-2011)
INTRODUCTION
SINIAT FIRSTS:
Sustainability has long been a core value at Siniat and is now top of the agenda for everyone in the construction supply chain. We remain committed to sustainable development and construction in both our business approach and in meeting the needs of the built environment. As a leading supplier of construction products, Siniat has a huge responsibility. Building materials meet basic human needs for the buildings that are part of everyday life. With economic growth and social development increasing demand we have to balance the human benefits of our products with the availability of finite and non-renewable resources.
2004: The first plasterboard manufacturer in the UK to achieve ISO 9001 and ISO 14001 certification for all activities – these international standards provide the framework for our conservation of natural resources. They ensure continuous improvement in quality and service, as well as emission reductions and innovative solutions for ever more sustainable buildings.
Therefore, at Siniat, we focus on environmental sustainability and leaving the lightest possible trace on the earth while enabling the social and economic sustainability of our operations.
2011: The first plasterboard manufacturer in the UK to achieve BES6001 certification, the industry sustainability standard for the responsible sourcing of construction products. This independent assessment certifies environmental stewardship and social and economic sustainability within our operations and supply chain.
SUSTAINABILITY
OUR SUSTAINABILITY POLICY: A LIFE CYCLE APPROACH
GYPSUM WASTE RECYCLING
To meet your client’s sustainability targets, Siniat takes a life cycle approach to minimising the environmental impacts of manufacturing and supply operations. All of our plant and supply chain activities translate into embodied impacts (such as carbon, water and recycled content) within your construction project. Therefore, we intervene at every life cycle stage to reduce these through material and energy resource minimisation, efficiency and recycling.
AND IT’S NOT JUST ABOUT THE ENVIRONMENT… As part of our product stewardship, we provide for the communities of people supplying our materials; manufacturing our products; living near to our plants; or installing our products and systems on site. We have adopted the United Nations Global Compact within our Responsible Sourcing Policy and expect suppliers to do the same.
MINIMISING WASTE Whilst all drywall projects generate waste from off-cuts, steps can be taken to minimise this. Our project teams can help you reduce waste through selecting appropriate products and systems, and efficient design detailing. Where necessary, we can supply boards and metal studs in non-standard lengths to reduce wastage on site. Reducing damage to boards and pallets with good site storage and transport practices can also make a big contribution.
An outstanding sustainability credential of plasterboard is that it can be recycled into new board products with no loss in quality. Siniat has been recycling plasterboard process waste for many years, becoming the first to eliminate plasterboard manufacturing waste to landfill in 2005. We’ve expanded our site waste recycling and recovery activities since 2000 and are now the leading recycler of plasterboard waste in the UK. Our post-consumer waste recycling rate exceeded the sector average in each of the years 2009-2011. European and UK regulations now require all gypsum waste to be segregated at source. While it remains legal to landfill gypsum waste in dedicated facilities our GTEC Wasteline Direct service makes this easy to avoid, recycling many thousands of tonnes of waste every year. Offered to merchants, distributors and contractors our GTEC Wasteline Direct service can take care of all your plasterboard waste management needs. Siniat partners with specialist providers, to offer cost-competitive collections on a national basis. Monthly reports of quantities removed are provided by GTEC Wasteline Direct. Siniat will endeavour to recycle the waste back into new plasterboard wherever viable. Where this is not possible, we direct the recovered gypsum to other favourable uses approved by the Environment Agency. GTEC Wasteline Direct will not landfill any clean plasterboard waste recovered by the scheme. An up-to-date list of the GTEC products accepted by the scheme is available on our website where you can also request a service cost quotation. Or, telephone 01275 377579 or email gtecwasteline@siniat.co.uk
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
337
338
SUSTAINABILITY
MANAGING THE PRODUCT LIFECYCLE
1. Gypsum Quarry
Used Packaging
2. Power Station 3. Paper Mill
Natural Gypsum by ship
By-product Gypsum by Conveyor
4. Plasterboard plant
Paper by road
Recycled Paper
5. & 6. Products
Site waste via
Recycled Gypsum
Wasteline Direct
Construction site
1. All our supply quarries have a biodiversity rehabilitation plan with state-of-the-art replanting. Delivery by bulk shipping is 20 times more carbon efficient than road transport. 2. Flue Gas Desulphurisation (FGD) systems used in power stations eliminate sulphur dioxide emissions and produce high purity gypsum as a by-product. We operate the only integrated FGD gypsum plasterboard manufacturing site in the UK, eliminating delivery transport. 3. The plasterboard liners we use comprise 100% recycled paper, principally from post-consumer packaging. 4. Our manufacturing process has very few emissions as all process water and waste is recycled internally. Zero waste goes to landfill. Our £1.6 million investments in energy efficiency saved over 40,000 tonnes of carbon dioxide by 2010.
7. Board Recycling Plant
5. Packaging is the second largest source of waste in construction. Against a national target of 20% Siniat reduced packaging by over 50% following investments of over £1 million. The bearers used for board packaging are from certified and sustainable sources. 6. We pioneered the use of fuel-saving ‘teardrop’ trailers to limit the impacts of product delivery. Coupled with LPG conversion the carbon footprint of our distribution activities has been reduced by 10%. 7. Almost all GTEC Plasterboards are fully recyclable into new products. The gypsum and paper are separated, with both suitable for closed-loop recycling. Our GTEC Wasteline Direct service offers a plasterboard recovery and recycling service. In each of the years 2009-2011, Siniat reported the highest post-consumer board recycling rate in the industry.
SUSTAINABILITY
SUSTAINABLE CONSTRUCTION RESPONSIBLE SOURCING AND BES6001
GTEC PRODUCTS AND SYSTEMS FOR SUSTAINABLE BUILDINGS As well as meeting regulation standards, our high performance products and systems enhance the sustainability of your building projects in many ways: Thermal boards contribute to the conservation of energy and CO2 emissions Fire boards contribute to safety as well as building durability Acoustic boards provide sound insulation and enhance the conditions required in our buildings and homes Impact boards meet the severe duty ratings required in public areas, reducing maintenance and promoting durability Through constant innovation, the GTEC range includes unique, specialist boards with enhanced features and performance to minimise the volume used on site. GTEC Megadeco This patented product is unique. Its pre-sealed surface speeds up installation by eliminating sealing on site.
Siniat was the first manufacturer in the UK to offer plasterboard products certified to the BRE Environmental and Sustainability Framework Standard for the Responsible Sourcing of Construction Products, BES6001. Our review in 2012 extended our rating to the ‘Very Good’ grading. This certificate may be downloaded from BRE’s Green Book Live website: www.greenbooklive.com. When using GTEC products on your projects, you can collect credits within the Materials section of the Code for Sustainable Homes or BREEAM.
BRE GREEN GUIDE Due to the low environmental impact of plasterboard products, the BRE Green Guide rating for most of the GTEC systems listed in the manual is A or A+. Embodied carbon figures for building elements are also listed. Our projects team will seek to provide the highest possible rating in line with your project’s specific performance requirements.
GTEC LaDura GTEC LaDura offers similar resource efficiency plus metal stud savings, due to its high strength. Excellent durability will reduce the need for maintenance. GTEC Aqua Board The unique range of boards for wet areas and external applications offers major carbon reductions compared to the cementitious boards traditionally used. Excellent stability provides superior air-tightness of the building envelope.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
339
340
SUSTAINABILITY
THE CODE FOR SUSTAINABLE HOMES The Code for Sustainable Homes applies in England and Wales to drive a step-change in sustainable home building practice. GTEC Products, Systems and Services help gain credits, pushing projects up the rating scale. The Code measures the sustainability of the home in nine design categories, and awards a rating of one to six stars, depending on achievement against the Code benchmarks. For all Code levels, there are minimum requirements for Energy and CO2 emissions and Water consumption.
building sustainability. As with the Code for Sustainable Homes, the GTEC range can make a significant contribution to higher ratings. BREEAM involves nine key areas of project design. Credits are awarded in each of the design areas and the overall score is calculated from a weighted scorecard of the section credits. The final score is then rated as Pass, Good, Very Good, Excellent or Outstanding. Education and Healthcare buildings must meet certain minimum ratings, and other ratings criteria may apply to building projects as a condition of planning approval.
REFURBISHMENT PROJECTS
Credits are awarded in each of the design areas, and the overall score is calculated from a weighted scorecard of the section credits. The assignment of credits within the Code’s Energy section has been recently updated to reflect the importance of installing a thermally efficient building fabric as the most cost-effective approach. This hierarchy, known as the ‘fabric first’ approach, is now reflected in the Code with credits for Fabric Energy Efficiency performance.
Following much regulation in the new build sector, the UK Low Carbon Construction Action Plan is now focusing on improving the thermal performance of existing buildings. The Government is due to launch its Green Deal package in Autumn 2012 where building improvements will be funded by energy savings in consumer energy bills. Siniat offers several products and systems suitable for Green Deal measures: please contact Technical Enquiryline for further details.
BUILDING RESEARCH ESTABLISHMENT ENVIRONMENTAL ASSESSMENT METHOD (BREEAM)
Alongside the Green Deal, BRE have launched a new BREEAM scheme in 2012 for the sustainability assessment of domestic refurbishment projects. Building on our experience gained piloting the scheme, Siniat will be pleased to support you with any project requirements.
BREEAM is the most widely used environmental assessment method for buildings in the UK. It provides a consistent and robust means of rating
GTEC SYSTEMS IN THE CODE FOR SUSTAINABLE HOMES AND BREEAM: The range of high performance GTEC Thermal Boards provide for space-efficient insulation. The Global Warming Potential (GWP) of all these insulated boards is below 5, accessing additional credits. GTEC systems achieve the high sound insulation values necessary to gain the credits for exceeding Building Regulation requirements. In the Materials Section, the excellent BRE Green Guide ratings of GTEC Systems and our BES6001 certification for Responsible Sourcing both access credits. Our plasterboard waste recovery service, GTEC Wasteline Direct, can support your site waste management needs and is also eligible for credits. Durability credits are available where Severe Duty partitions are used in corridors and public areas. (BREEAM only). The zero release of VOC’s (volatile organic compounds) from GTEC boards contributes to Indoor Air Quality. Specification of GTEC Megadeco can also minimise the release of VOC’s during the build. (BREEAM only). Siniat supports contractors during construction in areas relevant to Project Management credits, e.g. by minimising construction site impacts. Drawing on their vast experience with all building types, our projects team will support achievement of the best possible BREEAM or Code rating.
HEALTH AND SAFETY
HEALTH AND SAFETY Siniat has a deep commitment to zero harm in our industrial activity. We follow an active policy for continuous improvement in reducing incidents and protecting our employeesâ&#x20AC;&#x2122; health. In our supply chain we require similar exacting standards from our suppliers. To protect the health of construction workers and building occupants, we minimise the use of any hazardous materials and will avoid using substances of high concern. Our development programme brings innovative products to market which reduce health and safety risks on site and throughout the life of the building. CE MARKING All Siniat GTEC products are CE marked in accordance with the EU Construction Products Directive and the relevant harmonised European standard. This ensures that the essential requirements relevant to safety in use (e.g. reaction to fire or tensile strength) are type tested in accredited laboratories. Our ISO9001 quality management processes ensure continuing compliance. From July 2013, products will be CE Marked with reference to the EU Construction Products Regulation 2011/305/EC.
MANUAL HANDLING
CHEMICAL SUBSTANCES AND PRODUCT SAFETY Siniat ensures that all materials in its supply chain are registered under REACH* where necessary. We have also registered directly as a producer of calcium sulphate, the main raw material used in our products; evidence and our REACH registration number is available on request. Siniat board products do not contain or emit volatile organic compounds (VOCs) and our pre-finished GTEC Megadeco Board removes the need for on-site sealing, further enhancing the indoor air quality of your projects.
In collaboration with the Health & Safety Executive, Siniat has introduced weight labelling on all UK-produced board products. This information helps users to reduce injuries through risk assessment.
The sealing products in the Siniat GTEC range have an aqueous base and contain VOCs at the lowest classification level under the current regulations (<30g/litre).
Example of product marking:
All GTEC products are classified as non-hazardous according to the CHIP4 (UK) and CLP (EU) Regulations and are stable and non-reactive with other building materials. The sawing of plasterboard and the sanding of finishing compounds may generate dust. Whilst there are no known toxicological effects for gypsum products, Occupational Exposure Limits (OEL) exist for mineral dusts and the use of personal protective equipment is recommended.
HANDLE SAFELY
25kg
A range of mechanical handling aids for plasterboard lifting and positioning is commercially available to reduce the risk of injury. Please contact Technical Enquiryline for further information.
Safety Data Sheets are available for all GTEC products covering handling, storage, use and disposal. Latest versions may be downloaded from our website or obtained on request from our Technical Enquiryline. *European Regulation 2006/1907/EC on the Regulation, Evaluation, Authorisation and Restriction of Chemicals.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
341
342
STANDARDS
STANDARDS GTEC PRODUCT STANDARDS AND TESTS BS EN 520
BS EN 14353
Gypsum plasterboards. Definitions, Requirements and Test Methods.
Metal beads and feature profiles for use with gypsum plasterboards. Definitions, Requirements and Test Methods.
BS EN 14190 Gypsum plasterboard products from reprocessing. Definitions, Requirements and Test Methods.
BS EN 13950 Gypsum plasterboard thermal/acoustic insulation composite panels. Definitions, Requirements and Test Methods.
BS EN 15283 Gypsum boards with fibrous reinforcement – Definitions, Requirements and Test Methods. þ Part 1: Gypsum board with mat reinforcement
BS EN 14195 Metal framing components for gypsum plasterboard systems. Definitions, Requirements and Test Methods.
BS EN 14209 Preformed plasterboard cornices. Definitions, Requirements and Test Methods.
BS EN 13963 Jointing materials for gypsum plasterboards. Definitions, Requirements and Test Methods.
BS EN 14496 Gypsum based adhesives for thermal/acoustic insulation composite panels and plasterboards. Definitions, Requirements and Test Methods.
BS EN 13964 Suspended Ceilings – Requirements and Test Methods.
BS EN 14566 Mechanical fasteners for gypsum plasterboard systems. Definitions, Requirements and Test Methods.
SYSTEMS / DESIGN / CODES OF PRACTICE BS 8212
BS 5250
Code of practice for dry lining and – Partitioning using gypsum plasterboard
Code of Practice for the control of condensation in buildings
BS 8000
BS 5385
Workmanship on building sites þ Part 8: Code of practice for plasterboard – Partitions and dry linings
Wall and floor tiling – Code of practice þ Part 1: Design and installation of ceramic, natural stone and mosaic wall tiling in normal conditions
BS EN 13914
þ Part 4: Design and installation of ceramic and mosaic tiling in special conditions
Design, preparation and application of external rendering and internal plastering
BS EN ISO 6946
BS 5234 Specification for performance requirements for strength and robustness þ Part 1: – Partitions (including matching linings) – Code of practice for design and installation
Building components and building elements. Thermal resistance and thermal transmittance. Calculation method.
BS 9999: 2008 Code of Practice for fire safety in the design, management and use of buildings
STANDARDS
TEST METHODS BS EN 13238
BS EN ISO 10140
Reaction to fire tests for building products. Conditioning procedures and general rules for selection of substrates.
Acoustics. Laboratory measurement of sound insulation of building elements.
BS 476
BS EN ISO 140
Fire tests on building materials and structures. Guide to the principles, selection, role and application of fire testing and their outputs. þ Part 4: Non-combustibility test for materials
Acoustics. Measurement of sound insulation in buildings and of building elements.
þ Part 6: Method of test for fire propagation for products
Specification for performance requirements for strength and robustness. þ Part 2: Partitions (including matching linings) – Specification for performance requirements for strength and robustness including methods of test
þ Part 7: Method for classification of the surface spread of flame of products þ Part 20: Methods for determination of the fire resistance of elements of construction (general principles) þ Part 21: Method for determination of the fire resistance of loadbearing elements of construction þ Part 22: Methods for determination of the fire resistance of non-loadbearing elements of construction þ Part 23: Methods for the determination of the contribution of components to the fire resistance of a structure
BS 5234
BS EN ISO 717 Acoustics. Rating of sound insulation in buildings and of building elements. þ Part 1: Airborne sound insulation þ Part 2: Impact sound insulation
BS EN ISO 11654
BS EN 1363
Acoustics. Sound absorbers for use in buildings. Rating of sound absorption.
Fire resistance tests. General requirements. þ Part 1: General requirements
BS EN 13823
BS EN 1364 Fire Resistance tests for non-loadbearing elements. þ Part 1: Walls
Reaction to fire tests for building products. Building products excluding floorings exposed to the thermal attack by a single burning item.
þ Part 2: Ceilings
BS EN ISO 1182
BS EN 1365
Reaction to fire tests for building products. Non-combustibility test
Fire Resistance tests for loadbearing elements. þ Part 1: Walls
BS EN ISO 1716 Reaction to fire tests for products. Determination of the gross heat of combustion (calorific value).
þ Part 2: Floors and Roofs þ Part 3: Beams þ Part 4: Columns
BS EN ISO 11925
ENV 13381
Reaction to fire tests. Ignitability of products subjected to direct impingement of flame. þ Part 2: Single-flame source test
Test methods for determining the contribution to the fire resistance of structural members. þ Part 4: Test methods for determining the contribution to the fire resistance of structural members
MISCELLANEOUS BS EN 13279
BS EN 13164
Gypsum binders, and gypsum plasters. þ Part 1: Definitions and requirements þ Part 2: Test methods
Thermal insulation products for buildings. Factory made products of extruded polystyrene foam (XPS). Specification.
BS EN 10346
BS EN 13165
Continuously hot-dip coated steel flat products. Technical delivery conditions.
Thermal insulation products for buildings. Factory made rigid polyurethane foam (PUR) products. Specification.
BS 12524
BS EN ISO 12572
Building materials and products. Hygrothermal properties. Tabulated design values.
BS EN 1313 Round and sawn timber. Permitted deviations and preferred sizes. þ Part 1: Softwood sawn timber
Hygrothermal performance of building materials and products. Determination of water vapour transmission properties. NOTE: Standards are listed without publishing year to allow for updates, where applicable the latest dated versions should be used.
BS EN 13163 Thermal insulation products for buildings. Factory made products of expanded polystyrene (EPS). Specification.
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
343
344
INDEX
INDEX A
acoustic sealant, Intumescent Acoustic Sealant 330
acoustic board see Acoustic Homespan Board; dB Board; LaDura; Universal; Megadeco
Acoustic Stud 309, 332
Acoustic Homespan Board 300
Acoustic Stud Partition Systems 72–8
Acoustic Homespan MR Board 301
acoustic T-junctions
Aqua Board 303
Acoustic Floor Clip 317 Acoustic Floor Systems 137, 170–6 Acoustic Homespan Board 300 Acoustic Homespan C Studs 308 Acoustic Homespan MR Board 301 Acoustic Homespan Partition Systems 43, 80–6 Acoustic Homespan Starter Studs 308 Acoustic Homespan Stud 332 acoustic mass barrier ceilings 147 acoustic performance 17 Acoustic Floor Systems 137 Acoustic Homespan Partition Systems 43 Aqua Board Partition Systems 26–7 Ceiling Systems to Timber Floors 126 dB Board Partition Systems 33–7 Dryliner Ceiling Systems to Concrete Soffit 127
boards 12–13, 294–307 alternative configurations 14–15
Acoustic Homespan Partition Systems 86
Base Board 295
Acoustic Stud Partition Systems 78
dB Board 300
C Stud Partition Systems 59
E Board 299
Resilient Bar Partition Systems 93
Fire Board 297
Timber Partition Systems 118
Fire Core Board 299
Twin Frame Partition Systems 103
Fire MR Board 298
Contour Board 295
Acoustic V Brace 316, 332
Fire V Board 298
Acoustic V Brace 90° 230, 316
LaDura 302
adhesive
Megadeco 301
Cove Adhesive 329
Moisture Board 297
Wall Lining Adhesive 321
Plank 294
Aqua Board 13, 303
Pregybel Boards 306–7
Aqua Board Partition Systems 26–7
Render Board 303
Aquamix 325
Standard Board 294
Aquastrip 327
Thermal Board 304 Thermal K Board 305
B
Thermal PIR Board 305
E Board Partition Systems 44 Engineered Joist Systems 122
Base Board 295
Universal Board 302
Fire Board Partition Systems 38–40
beading products 328
Vapour Base Board 296
Horizontal Shaftwall Systems 249
beams
LaDura Partition Systems 22–5 Lining Systems To Framed External Walls 187 Lining Systems To Upgrade Internal Walls 182–3 Mass Barrier Ceilings 136 Megadeco Partition Systems 28–31
fire resistant encasement 252, 271–2, 274 head deflection 63 boarding details Acoustic Floor Systems 174–6 Acoustic Homespan Partition Systems 84
Pregybel Independent Lining Systems 190–1
Acoustic Stud Partition Systems 76
Pregybel MF Ceiling Systems 131–2
Contour Lining System 206
Separating Floor Systems 128–30
Direct Bond Lining Systems 198
Shaftwall Stairwell Systems 248 Shaftwall Systems 244–7
Direct-to-Timber Ceiling Systems 166–7
Standard Board Partition Systems 41–2
Dryliner Ceiling Systems 158–9
Structural Frame Partition Systems 45
Dryliner Lining Systems 221
Suspended MF Ceiling Systems to Protect Structure 135
Independent Wall Lining Systems 231
Suspended MF Ceiling Systems to Timber Floors 133–4
C Stud Partition Systems 55–6
Pregybel Independent Lining Systems 239–40 Pregybel MF Ceiling Systems 152
Timber Partition Systems 47–9
Resilient Bar Partition Systems 91
Universal Board Partition Systems 32
Shaftwall Systems 258–60
Masonry Robust Detail Systems 46
Shallow Wall Lining Systems 212 Suspended MF Ceiling Systems 143 Timber Partition Systems 115–16 Twin Frame Partition Systems 100–1
Thermal XP Board 304
Vapour Board 296 bonding Contour Lining System 205 Direct Bond Lining Systems 196–7 Shallow Wall Lining Systems 211–12 Tiling 287 Universal Bonding Compound 321 BRE Green Guide 339 breaking loads, Board 294–307 BREEAM (Building Research Establishment environmental Assessment Method) 336 British Standards 342–3 BS 476-21 122–37 BS 476-22 22–49, 135–6, 244–9 BS 5234-2 18, 22–49, 244–9 BS EN 1364-1 22–49, 244–8 BS EN 1364-2 135–6, 249 BS EN 1365-2 122–37 BS EN ISO 140 17 BS EN ISO 717 17 BS EN ISO 11654 131–2
INDEX
Building Regulations
Ceiling Systems to Timber Floors 126
acoustic performance 17
ceramic tiling 285–7
compliance with Approved Document E 299
CH Stud 314, 333
fire performance 16
codes of practice 342
thermal performance 11
Collated Drywall Screws 323
Building Research Establishment environmental Assessment Method (BREEAM) 336 Building Research Establishment Green Guide 339 bulkhead Dryliner Ceiling Systems 160 Pregybel MF Ceiling Systems 153 Suspended MF Ceiling Systems 145
Code for Sustainable Homes 340
columns, fire resistant encasement 253, 263, 271, 273 composition
C Stud Partition Systems 50–71 C Studs 308, 332 cable tray penetrations C Stud Partition Systems 65 Twin Frame Partition Systems 106
dimensions (see also maximum height; thickness)
Frame 308–20 conductivity, Board 19, 294–307 Contour Board 295 Contour Lining Systems 202–6 Corner 90º External 328 Corner and Edge beads 328 corner details Acoustic Homespan Partition Systems 86
ceiling channel splicing 141
Dryliner Lining Systems 223
ceiling height change
Encasement Systems 273
Dryliner Ceiling Systems 160
Independent Wall Lining Systems 233
Pregybel MF Ceiling Systems 153
Pregybel Independent Lining Systems 240 Resilient Bar Partition Systems 93
Ceiling Systems to Timber Floors 126
Shaftwall Systems 262
Direct-to-Timber Ceiling Systems 162–8
Shallow Wall Lining Systems 214
Dryliner Ceiling Systems 154–61
Twin Frame Partition Systems 103
Suspended MF Ceiling Systems 138–47 Suspended MF Ceiling Systems to Protect Structure 135
deflection heads see head deflection
Fix 321
Direct Bond Lining Systems 200
Separating Floor Systems 128–30
decoration 283
dimensionally stability 19
Ceiling Channel 311, 333
Pregybel MF Ceiling Systems 131–2, 148–53
Deco Machine 326
Finish 324–30
C Stud Partition Systems 58, 59
Mass Barrier Ceilings 136
Deco Joint Cement 326
design pull-out loads see pull-out loads
Acoustic Stud Partition Systems 78
Dryliner Ceiling Systems to Concrete Soffit 127
Deco Filler 325
Drywall Screws 322–3
CE marking 341
ceiling systems
dB Board Partition Systems 33–7
design codes 342
CB Clip 316, 333
Suspended MF Ceiling Systems 145
dB Board 300
Board 294–307
Connecting Clip 312
C
D
Timber Partition Systems 118 corners, taping and jointing 282, 328 Cove 288–90, 329 Cove Adhesive 329 curved partitions C Stud Partition Systems 70–1
Board 294–307 Frame 308–20 Direct Bond Lining Systems 192–201 Direct-to-Timber Ceiling Systems 162–8 domestic buildings see residential projects door frames/jambs Acoustic Homespan Partition Systems 85 Acoustic Stud Partition Systems 77 C Stud Partition Systems 57–8 Direct Bond Lining Systems 199 Resilient Bar Partition Systems 92 Shallow Wall Lining Systems 213 Timber Partition Systems 117 Twin Frame Partition Systems 102 Dryliner Ceiling Systems 154–61 Dryliner Ceiling Systems to Concrete Soffit 127 Dryliner Channel 312, 333 Dryliner Channel Connector 314 Dryliner Lining Systems 216–24 Dryliner Profiles 333 Dryliner Track 313, 333 Drywall Screws 322–3, 334–5 Drywall Sealer 328
Contour Board 295
duct penetrations, Shaftwall Systems 264–5
Contour Lining Systems 202–6
duct protection systems 266
Twin Frame Partition Systems 108–9
Duo Bead 328 duty rating see strength duty
Suspended MF Ceiling Systems to Timber Floors 133–4
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
345
346
INDEX
INDEX E E Board 299 E Board Partition Systems 44 E Stud 315, 333 Easy Finish Xtra 324 E-coat 321
Fire Board 297
fire protection systems 244–75
Fire Core Board 299
Encasement Fire Protection Systems 250–3
Fire MR Board 298
Encasement Systems 268–75
fire performance 16
Horizontal Shaftwall Systems 249
Fire Board Partition Systems 38–40
Acoustic Floor Systems 137
Shaftwall Stairwell Systems 248 Shaftwall Systems 244–7, 254–67
Edge Channel 311, 333
Acoustic Homespan Partition Systems 43
Fire V Board 298
Edging Bead 328
Aqua Board Partition Systems 26–7
Fixing Channel 319, 332
educational projects 9
Board 294–307
fixing details see boarding details
electrical services see cable tray penetrations
Ceiling Systems to Timber Floors 126
fixing options 69
dB Board Partition Systems 33–7
fixing products
Encasement Fire Protection Systems 250–3, 268–75 Engineered Joist Systems 122 environmental issues 336–9 external insulation 184–7
F finishing 278–90 Board 294–307 Taping and Jointing Systems 278–83 Tiling 287 skim plastering 284 finishing products 324–30 Aquamix 325
Dryliner Ceiling Systems to Concrete Soffit 127 E Board Partition Systems 44 Engineered Joist Systems 122 Finish 324–30
bonding and adhesives 321 Drywall Screws 322–3 fixtures C Stud Partition Systems 67–8 Suspended MF Ceiling Systems 146
Fire Board Partition Systems 38–40
Flat Strap 319, 332
Fix 321
Flex Tape 327
Frame 308–20
Flex Track Deep Flange 310
Horizontal Shaftwall Systems 249
floor systems 121
LaDura Partition Systems 22–5
Acoustic Floor Systems 137, 170–6
Lining Systems To Framed External Walls 187
Engineered Joist Systems 122
Lining Systems To New External Walls 180–1
Plank 294 Separating Floor Systems 128–30 four way junctions
Aquastrip 327
Lining Systems To Upgrade Internal Walls 182–3
Corner 90º External 328
Mass Barrier Ceilings 136
Cove 90 329
Megadeco Partition Systems 28–31
Cove 120 329
Roof Lining Systems 188–9
Cove Adhesive 329
Separating Floor Systems 128–30
Deco Filler 325
Shaftwall Stairwell Systems 248
Deco Joint Cement 326
Shaftwall Systems 244–7
Deco Machine 326
Standard Board Partition Systems 41–2
Acoustic V Brace 316
Structural Frame Partition Systems 45
C Studs 308
Drywall Screw heads 335 Drywall Sealer 328 Duo Bead 328 Easy Finish Xtra 324 Edging Bead 328 Flex Tape 327 Intumescent Acoustic Sealant 330 Joint Cement Xtra 324 Joint Filler Xtra 324 Joint Tape 327 Patching Tape 327 Smartmix Xtra 325 Socket Pads 330 Universal Sealer 328
Suspended MF Ceiling Systems to Protect Structure 135
C Stud Partition Systems 59 Twin Frame Partition Systems 103 frame components 308–20 Acoustic Floor Clip 317 Acoustic Homespan C Studs 308 Acoustic Homespan Starter Studs 308 Acoustic Stud 309 Acoustic V Brace 90º 316 CB Clip 316 Ceiling Channel 311
Suspended MF Ceiling Systems to Timber Floors 133–4
CH Stud 314
Timber Partition Systems 47–9
Dryliner Channel 312
Universal Board Partition Systems 32
Dryliner Channel Connector 314
Masonry Robust Detail Systems 46
Dryliner Track 313
Fire Protection profiles 333
Connecting Clip 312
E Stud 315 Edge Channel 311 Fixing Channel 319 Flat Strap 319 Flex Track Deep Flange 310
INDEX
Heavy Gauge Primary Channel 311 I Stud 309 Insulation Hold 320
H
J
head deflection
J Track 315, 333
J Track 315 Metal Angle 90° 319 Movement Control Joint 320 Phonissimo Acoustic Hanger 317 Phonistar Acoustic Hanger 317 Primary Channel 311 Resilient Bar 315 Resilient Tape 318 Shallow Wall Channel 314
Joint Filler Xtra 324 joint reinforcement see horizontal joint reinforcement
Heavy Gauge Primary Channel 311, 333 height see ceiling height change; maximum height
jointing systems see taping and jointing systems
horizontal joint reinforcement
junction details
Acoustic Homespan Partition Systems 84
Strap Hanger 318 U Track 309
frame details
Acoustic Stud Partition Systems 75 C Stud Partition Systems 53–4 Direct-to-Timber Ceiling Systems 165 Dryliner Ceiling Systems 157 Dryliner Lining Systems 220–1 Encasement Systems 271–2 Independent Wall Lining Systems 230 Pregybel MF Ceiling Systems 151 Resilient Bar Partition Systems 91 Shaftwall Systems 258–9 Shallow Wall Lining Systems 211–12 Suspended MF Ceiling Systems 141–2 Timber Partition Systems 113–14 Twin Frame Partition Systems 97–9
G
Acoustic Floor Systems 175
Acoustic Stud Partition Systems 76
Acoustic Homespan Partition Systems 86
C Stud Partition Systems 55
Acoustic Stud Partition Systems 78
Resilient Bar Partition Systems 92
C Stud Partition Systems 58–60
Twin Frame Partition Systems 100
Direct Bond Lining Systems 200
Horizontal Shaftwall Systems 249
Direct-to-Timber Ceiling Systems 167
horizontal shaftwall systems 267
Dryliner Ceiling Systems 160
hospitals see healthcare projects
Dryliner Lining Systems 223
hybrid systems 14
Encasement Systems 273
Acoustic Floor Systems 173 Acoustic Homespan Partition Systems 83
Joint Tape 327
homogenous systems 15
Staggered Stud Clip 318
XR Bracket 313
joint compounds 324–6
healthcare projects 7
SR Bracket 313
U Track Extra Deep Flange 310
Joint Cement Xtra 324
Twin Frame Partition Systems 105–6 health and safety 341
Soffit Cleat 312
U Track Deep Flange 310
C Stud Partition Systems 61–2
Independent Wall Lining Systems 233 Resilient Bar Partition Systems 93
I
Shaftwall Systems 262–3
I Stud 309, 332
Shallow Wall Lining Systems 213
impact sound insulation
Suspended MF Ceiling Systems 145
Acoustic Floor Systems 137
Timber Partition Systems 118
Ceiling Systems to Timber Floors 126
Twin Frame Partition Systems 103–4
Dryliner Ceiling Systems to Concrete Soffit 127 Engineered Joist Systems 122 Mass Barrier Ceilings 136 Separating Floor Systems 128–30 Suspended MF Ceiling Systems to Protect Structure 135 Suspended MF Ceiling Systems to Timber Floors 133–4 Independent Wall Lining Systems 226–34 insulation acoustic/sound 17
GTEC 3
fire 16
GTEC Lifetime System Warranty 3
thermal 19
gypsum waste recycling 337–8
Acoustic Homespan Partition Systems 83 C Stud Partition Systems 54 Dryliner Lining Systems 221 Timber Partition Systems 115 Twin Frame Partition Systems 100 insulation board see Thermal Insulation Hold 320 Intumescent Acoustic Sealant 330
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
347
348
INDEX
INDEX L
Walls 187
N
LaDura Partition Systems 22–5
Lining Systems To Upgrade Internal Walls 183
LaDura Board 12, 302
Megadeco Partition Systems 28–31
LaDura pattress 67–8, 69 Lafarge Plasterboard see Siniat
Pregybel Independent Lining Systems 190–1
O
lengths
Shaftwall Stairwell Systems 248
openings
Nailable Plug 323
Board 294–307
Shaftwall Systems 244–7
Frame 308–20 life cycle approach 337
Standard Board Partition Systems 41–2
light steel framing systems (SFS) see SFS junctions
Structural Frame Partition Systems 45
C Stud Partition Systems 57–8
lining depth change 224
Timber Partition Systems 47–9
Dryliner Lining Systems 222
lining systems 179–241
Universal Board Partition Systems 32
Independent Wall Lining Systems 232
Masonry Robust Detail Systems 46
Resilient Bar Partition Systems 92
Contour Lining Systems 202–6 Direct Bond Lining Systems 192–201
Acoustic Homespan Partition Systems 85 Acoustic Stud Partition Systems 77 Direct Bond Lining Systems 199
Megadeco 13, 301
Shaftwall Systems 261
Dryliner Lining Systems 216–24
Megadeco Partition Systems 28–31
Shallow Wall Lining Systems 213
Independent Wall Lining Systems 226–34
Metal Angle 90° 319, 332
Suspended MF Ceiling Systems 144
metal bead 328
Timber Partition Systems 117
Lining Systems To Framed External Walls 187 Lining Systems To New External Walls 180 Lining Systems To Thermally Upgrade External Walls 184–6 Lining Systems To Upgrade Internal Walls 182–3 Pregybel Independent Lining Systems 190–1, 236–41 Roof Lining Systems 188–9 Shallow Wall Lining Systems 208–15
M
minimum thickness Acoustic Floor Systems 137 Ceiling Systems to Timber Floors 126
C Stud Partition Systems 56
Dryliner Ceiling Systems to Concrete Soffit 127
Dryliner Lining Systems 221
Engineered Joist Systems 122
Timber Partition Systems 115–16, 117
Lining Systems To Framed External Walls 187
Twin Frame Partition Systems 101
Lining Systems To New External Walls 180–1 Lining Systems To Thermally Upgrade External Walls 184–6 Lining Systems To Upgrade Internal Walls 182–3 Pregybel MF Ceiling Systems 131–2
manual handling 341
Separating Floor Systems 128–30
Masonry Robust Detail Systems 46
Suspended MF Ceiling Systems to Timber Floors 133–4
masonry substrates 196, 211 masonry wall junctions
mixed board systems 15
C Stud Partition Systems 59–60
Moisture Board 297
Encasement Systems 274 Resilient Bar Partition Systems 93
moisture resistant board see Aqua; LaDura; Moisture
Twin Frame Partition Systems 104
Movement Control Joint 320, 332
Mass Barrier Ceilings 136
movement control joints
mass to height/span ratio 18
C Stud Partition Systems 56
maximum height 18
Contour Lining System 206
Acoustic Homespan Partition Systems 43
Direct Bond Lining Systems 198
Aqua Board Partition Systems 26–7
Dryliner Lining Systems 222
dB Board Partition Systems 33–7
Independent Wall Lining Systems 232
E Board Partition Systems 44
Shaftwall Systems 260
Fire Board Partition Systems 38–40
Shallow Wall Lining Systems 213
Horizontal Shaftwall Systems 249
Suspended MF Ceiling Systems 144
LaDura Partition Systems 22–5
Twin Frame Partition Systems 101
Lining Systems To Framed External
Twin Frame Partition Systems 102 over-height boarding
Dryliner Ceiling Systems 159
Independent Wall Lining Systems 231
P partition systems 21–119 Acoustic Homespan Partition Systems 43, 80–6 Acoustic Stud Partition Systems 72–8 Aqua Board Partition Systems 26–7 C Stud Partition Systems 50–71 dB Board Partition Systems 33–7 E Board Partition Systems 44 Fire Board Partition Systems 38–40 LaDura Partition Systems 22–5 Megadeco Partition Systems 28–31 Resilient Bar Partition Systems 88–93 Standard Board Partition Systems 41–2 Structural Frame Partition Systems 45 Timber Partition Systems 47–9, 110–19 Twin Frame Partition Systems 94–108 Universal Board Partition Systems 32 Masonry Robust Detail Systems 46
INDEX
parge coat see E Coat Patching Tape 327 penetrations C Stud Partition Systems 65–6 Shaftwall Systems 264–5 Twin Frame Partition Systems 106 perforated board see Pregybel performance tables see system performance Phonissimo Acoustic Hanger 317 Phonistar Acoustic Hanger 317 pipe penetrations C Stud Partition Systems 65, 66
S
fire resistant encasement 250–3, 271–5
safe handing 341
Fire Core Board 299
school buildings see educational projects
SFS junctions 104
screws Drywall Screws 322–3 selection guide 334–5 sealant Intumescent Acoustic Sealant 330 sealer
shaftwall junction 263 Strap Hanger 318 strength duty 18 Acoustic Homespan Partition Systems 43 Aqua Board Partition Systems 26–7 dB Board Partition Systems 33–7
Drywall Sealer 328
E Board Partition Systems 44
Universal Sealer 328
Fire Board Partition Systems 38–40
Separating Floor Systems 128–30
Horizontal Shaftwall Systems 249
service openings see penetrations
LaDura Partition Systems 22–5
SFS junctions 104
Megadeco Partition Systems 28–31
Shaftwall Stairwell Systems 248
Shaftwall Stairwell Systems 248
Shaftwall Systems 244–7, 254–67
Shaftwall Systems 244–7
Shallow Wall Channel 314, 333
Standard Board Partition Systems 41–2
Pregybel MF Ceiling Systems 131–2, 148–53
Shallow Wall Lining Systems 208–15
Structural Frame Partition Systems 45
Siniat 2
Timber Partition Systems 47–9
Primary Channel 311, 333
skim plastering 284
Universal Board Partition Systems 32
product life cycles 337
Smartmix Xtra 325
Masonry Robust Detail Systems 46
product safety 341
socket pad fittings
Structural Frame Partition Systems 45
Twin Frame Partition Systems 106, 107 Plank 294 Pregybel Acoustic Panel 241 Pregybel Boards 306–7 Pregybel Independent Lining Systems 190–1, 236–41
profile guide 332–3
C Stud Partition Systems 65
structural performance 18
pull-out loads 69
Twin Frame Partition Systems 106
Stud and Track profiles 332
purlins, head deflection, C Stud Partition Systems 62–3, 64
R recycling of waste 337–8 refurbishment projects (sustainability) 340 render, E-coat 321
Socket Pads 330
Acoustic Stud Partition Systems 75
sound absorption see acoustic performance
C Stud Partition Systems 53
sound insulation see acoustic performance splayed corners C Stud Partition Systems 59 Twin Frame Partition Systems 103
Render Board 303
SR Bracket 313, 333
renovating walls, Contour Lining Systems 202–6
Staggered Stud Clip 318
residential projects 11
stairwell systems, Shaftwall Systems 265
Resilient Bar 315, 332
Standard Board 294
Resilient Bar Partition Systems 88–93
Standard Board Partition Systems 41–2
Resilient Tape 318
standards 342–3 (see also British Standards)
Responsible Sourcing of Construction Products (BES6001) 339
stud splices
Soffit Cleat 312
Board 294–307
Robust Details 46, 129-30
Drywall Screws 322–3
Roof Lining Systems 188–9
Finish 324–30 Fix 321 Frame 308–20 steelwork
Twin Frame Partition Systems 99 Shaftwall Systems 258 substrates (see also masonry substrates) Contour Lining System 205 Direct Bond Lining Systems 196 Dryliner Lining Systems 219 Shallow Wall Lining Systems 211 Taping and Jointing Systems 281 Suspended Ceiling profiles 333 Suspended MF Ceiling Systems 138–47 Suspended MF Ceiling Systems to Protect Structure 135 Suspended MF Ceiling Systems to Timber Floors 133–4 sustainability issues 2, 11, 336–40 symmetrical systems 14 system performance 16–19 Floor and Ceiling Systems 122–37 Lining Systems 180–91 Partition Systems 22–49 Shaftwall Systems 244–53
ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
349
350
INDEX T
V
tape on bead 328
Vapour Base Board 296
taping and jointing systems 278–83, 324–7
Vapour Board 296 V-brace fixing 99
telescopic deflection head assembly 63–4 test methods 343 Thermal Board 304
W Wall Lining Adhesive 321
Thermal K Board 305
wall linings see linings
thermal performance 19, 294–307
waste recycling 337–8
Thermal PIR Board 305
Wasteline Direct 337–8
Thermal XP Board 304
website, Siniat 5
thickness (see also minimum thickness)
weight
Board 294–307
Board 294–307
Frame 308–20
Floor and Ceiling Systems 122–37
Partition Systems 22–49
Partition Systems 22–49
Shaftwall Systems 244–9 tiling Contour Lining Systems 202–6 Tiling 285–7 Timber Partition Systems 47–9, 110–19 T-junctions C Stud Partition Systems 58–60 Shaftwall Systems 262
Shaftwall Systems 244–9 weighted sound reduction index (Rw) 17 wet areas (see also Aqua) tiling 285–7 widths Board 294–307 Frame 308–20 window reveals
Timber Partition Systems 118
Direct Bond Lining Systems 199
Twin Frame Partition Systems 103–4
Dryliner Lining Systems 222
Twin Frame Partition Systems 94–108
Independent Wall Lining Systems 232 Shallow Wall Lining Systems 213
U U Track 309, 332 U Track Deep Flange 310, 332 U Track Extra Deep Flange 310, 332 universal beams see beams Universal Board 302 Universal Board Partition Systems 32 Universal Bonding Compound 321 universal columns see columns Universal Sealer 328 U-values 19 Lining Systems To Framed External Walls 187 Lining Systems To New External Walls 180–1 Lining Systems To Thermally Upgrade External Walls 184–6 Lining Systems To Upgrade Internal Walls 183 Roof Lining Systems 188–9
X XR Bracket 313, 333
351
NOTTINGHAM UNIVERSITY, SCHOOL OF HUMANITIES Project: Education Architect: CPMG Main Contractor: Clegg Construction Sub Contractor: L Reynolds Project Value: ÂŁ5.4 million Completion: January 2010 GTEC Systems used: GTEC Acoustic Stud Partitions, GTEC C Stud Partitions, GTEC Shaftwall GTEC Boards used: GTEC Universal Board, GTEC LaDura Board, GTEC Fire Core Board ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
352
353
SOUTH BRISTOL SKILLS ACADEMY Project: Education Architect: Atkins Walters & Webster Main Contractor: Cowlin Construction Sub Contractor: GHT Plastering Project Value: ÂŁ23 million Completion: June 2010 GTEC Systems used: GTEC C Stud Partitions, GTEC Independent Wall Lining, GTEC Pregybel MF Ceilings GTEC Boards used: GTEC Megadeco, GTEC Fire MR, GTEC Pregybel Board ENQUIRYLINE T: 01275 377789 E: enquiryline@siniat.co.uk www.siniat.co.uk
GB ORDERLINE For placing orders, delivery enquiries and local stockists etc.
T 0800 373636 F 01275 377700 E orderline@siniat.co.uk LITERATURELINE For Siniat literature.
T 01275 377582 E literatureline@siniat.co.uk THE TRAINING CENTRE For all drywall training needs from basic introduction to advanced skills and development.
T 01275 377581 F 01275 377402 E training@siniat.co.uk IRELAND ORDERLINE For placing orders, delivery enquiries and local stockists etc.
T +353 (0)1 6203114 F +353 (0)1 6203117 E irelandorders@siniat.com TECHNICAL ENQUIRYLINE Technical advice and project enquiries.
T 01275 377789 F 01275 377456 E enquiryline@siniat.co.uk GTEC® WASTELINE DIRECT Plasterboard waste management enquiries.
T 01275 377579 F 01275 774950 E gtecwasteline@siniat.co.uk
SINIAT LIMITED Marsh Lane, Easton-in-Gordano Bristol BS20 0NF T +44 (0)1275 377773 www.siniat.co.uk © 2012 Siniat Limited GB_CC_01_0912
e: Barnsley
Cover imag
e page 8.
College: se