Air Conditioners with Puron® Refrigerant – 24ABC6 / 24ABB3
As an ENERGY STAR® partner, Carrier Corporation has determined that the 25ABC6 and 25ABB3 air conditioners meet ENERGY STAR guidelines for energy efficiency.
Cool and Efficient Indoor Comfort in a Compact Design
Efficiency
Things to Consider Before You Buy
Seasonal Energy Efficiency Ratio, or SEER, is like gas Puron® Refrigerant mileage. A higher SEER Puron refrigerant is environmentally sound rating means a more energyand won’t deplete the ozone layer. Carrier efficient air conditioning introduced Puron refrigerant a full six system. As of mid-January years ahead of the UP TO of 2006, the U.S. competition, paving the Department of Energy way for the future. The required home cooling Clean Air Act of 1990 SEER systems to meet a RATING prohibits the production of minimum rating of 13.0 HCFC-based air conditioners and SEER. Carrier was one of the heat pumps by 2010, and bans Freon®-22* first leading air conditioner production by 2020. As Freon® production manufacturers to fully support reduces, its cost is predicted to increase. this environmentally-sound mandate.
16.0
● The Carrier 24ABC6 and 24ABB3 air conditioners are available with efficiency ratings starting at 13.0 and 14.5 SEER.
● As an ENERGY STAR® partner, Carrier Corporation has determined that the 24ABC6 and 24ABB3 air conditioners that achieve system combinations of 14.5 SEER and 12.0 EER or higher meet the ENERGY STAR guidelines for energy efficiency.
Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your dealer for details or visit www.energystar.gov.
Freon®-12 in the automotive industry increased by a whopping 800% in a short seven years following its phase-out! Ensure your cooling costs by investing in systems with Puron refrigerant – environmentally sound, efficient and dependable refrigerant designed for the future. Carrier® 24ABC6 and 24ABB3 air conditioners with Puron refrigerant deliver excellent reliability and proven performance.
Comfort Carrier specializes in creating a customized home comfort system tailored to your needs with our broad selection of heating and cooling products. Your Carrier dealer can help you choose the best system for your home including Carrier-exclusive features that further enhance your indoor environment. Carrier’s 24ABC6 and 24ABB3 air conditioners deliver proven reliability and comfort in a compact design.
Reliability At Carrier, your comfort is our business. That’s why we have one of the most extensive product research and development facilities in the world. From initial design to final assembly, we monitor product quality throughout all phases of the process. Our exclusive five-step, 100% run test ensures that every single unit we make exceeds industry expectations and meets the toughest standards of all – yours.
Durability Neither rain nor hail nor golf or soccer balls can keep a Carrier system from doing its job – it’s built tough inside and out. Outside
Inside
● WeatherArmor™ protection and galvanized steel cabinet protect against corrosion and keep your system looking its best for years.
● The Carrier compressor design has the most trouble-free performance record of any compressor on the market today.
● Heavy-duty wire grille prevents coil damage and promotes optimum airflow through the unit while making cleaning easy.
* Freon is a registered trademark of E.I. Dupont de Nemours & Co.
Technology Puron refrigerant – environmentally sound and won’t deplete the ozone layer.
1
1 Aerodynamic top – enhances airflow through the outdoor unit, and reduces noisy turbulence.
4b
4a
2 Compressor – the heart of the air conditioner, the compressor pumps refrigerant throughout the system.
3 Copper Microtube™/aluminum fin coil – transfers heat outside to maximize indoor cooling while resisting corrosion.
2 4 WeatherArmor™ protection package – combines design elements that protect your comfort. a. Galvanized steel cabinet
3
b. Heavy-duty wire coil guard protection
5 Filter drier – constantly filters the refrigerant to remove moisture or contaminants that can damage your system.
5
Specifications Air Conditioners Infinity® 21
Two-Stage Scroll Infinity® Infinity® System Controls Compressor Compressor
✓
Performance™ Series
✓ ✓*
Comfort™ Series Base Series
✓ ✓*
✓ ✓ ✓ ✓
SEER Rating Up to 21.0 Up to 17.0 Up to 17.0 Up to 16.0
Sound ENERGY Puron® Silencer Ratings STAR® Refrigerant System II™ Under 75 dB
✓ ✓* ✓* ✓*
✓ ✓ ✓ ✓
✓ ✓
✓ ✓ ✓*
*Not available on all models
Limited Warranty To the original owner, the Carrier® 24ABC6 and 24ABB3 air conditioners are covered by a 10-year parts limited warranty upon timely registration of your new equipment.* Ask your Carrier dealer about optional extended warranties which may include labor. * Warranty period is five years if not registered within 90 days. Jurisdictions where warranty benefits cannot be conditioned on registration will automatically receive a 10-year parts limited warranty. See warranty certificate at carrier.com for complete details.
10 YEAR LIMITED WARRANTY
Turn to the Experts Willis Carrier invented air conditioning in 1902. Over 100 years later, we’re proud to say Carrier® systems are trusted in more homes than any other brand. Carrier continues to be on the forefront of innovative engineering and unsurpassed standards of excellence. So when choosing a home comfort system, you’ll want to turn to the experts. Your Carrier dealer will evaluate your home, such as window placement and size, ductwork, other structural specifics and lifestyle to provide a customized indoor comfort plan designed specifically for you. And when you have an expert helping you make an educated decision, you’re going to feel more comfortable.
www.carrier.com
1-800-CARRIER
A member of the United Technologies Corporation family. Stock Symbol UTX. © Carrier Corporation 2010
01-824-028-25
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. Models 24ABB3, 24ABC6
13.0
-
16.0
Always look for these symbols, the air conditioning industry seals of certified performance, efficiency and capacity.
24ABB Air Conditioner with PuronŽ Refrigerant and WeatherShield™ Protection
Designed for Long-Lasting Performance in Harsh Coastal Climates
Efficiency
Things to Consider Before You Buy
Seasonal Energy Efficiency Ratio, or SEER, is like gas mileage. A higher SEER rating means a more energy-efficient air conditioning system. As of mid-January of 2006, the U.S. Department of Energy requires home cooling systems to meet a minimum rating of 13.0 SEER. Carrier was one of the first leading air conditioner manufacturers to fully support this environmentally-sound mandate.
Puron® Refrigerant Puron refrigerant is environmentally sound and won’t deplete the ozone layer. Carrier® introduced Puron refrigerant a full six years ahead of the competition, paving the way for the future. The Clean Air Act of 1990 prohibits the production of HCFC-based air conditioners and heat pumps by 2010, and bans Freon®–22* production by 2020. As Freon production reduces, its cost is predicted to increase.
Freon–12 in the automotive industry increased by a whopping 800% seven years following its phase-out! Ensure your future servicing costs by investing in systems with Puron refrigerant — the environmentally sound, efficient and dependable refrigerant designed for the future. Carrier air conditioners with Puron refrigerant deliver excellent reliability and proven performance.
Comfort ● Carrier Base air conditioners for coastal applications are available with efficiency ratings starting at 13.0 SEER.
AT
Carrier specializes in creating a customized home comfort system tailored to your needs with our broad selection of residential heating and cooling products. The 24ABB series air conditioners featuring WeatherShield™ protection deliver reliability and proven performance in harsh coastal climates.
13.0 SEER RATING
Reliability At Carrier, your comfort is our business. That’s why we have one of the most extensive product research and development facilities in the world. From initial design to final assembly, we monitor product quality throughout all phases of the process. Our exclusive five-step, 100% run test ensures that every single unit we make exceeds industry expectations and meets the toughest standards of all – yours.
Durability Neither rain nor hail nor golf or soccer balls can keep a Carrier system from doing its job – they’re built tough inside and out. Outside
Inside
● WeatherShield™ protection and galvanized steel cabinet protect against corrosion and keep your system looking its best for years.
● Carrier’s compressor design has the most trouble-free performance record of any compressor on the market today.
● Wire coil guard promotes optimum airflow through the outdoor unit and prevents coil damage from rocks, sticks, lawn and sports equipment and more.
* Freon is a registered trademark of E.I. Dupont de Nemours & Co.
● ArmorPlate™ coil coating protects the outdoor coil from harsh salt air. A specially formulated epoxy is permanently bonded to the coil surfaces. This advanced technology helps prevent the destructive galvanic corrosion that is common in coastal areas.
Technology Puron® refrigerant – environmentally sound and won’t deplete the ozone layer. 1 ArmorPlate™ coil fin coating –
2
protects the outdoor coil fin from harsh salt air. A specially formulated epoxy-phenolic coating is permanently bonded to the coil fin surfaces.
5b
2 Aerodynamic top – enhances airflow through the outdoor unit, and reduces noisy turbulence.
3 Compressor – the heart of the
1
air conditioner, the compressor pumps refrigerant throughout the system.
3
4 Copper Microtube™/aluminum fin coil – transfers heat outside to maximize indoor cooling while resisting corrosion.
4 5a
5 WeatherArmor™ protection package – combines design elements that protect your comfort. a. Galvanized steel cabinet
6 b. Heavy-duty wire coil guard protection
1 Standard Unit
6 Filter drier – constantly filters the refrigerant to remove moisture or contaminants that can damage your system. WeatherShield with ArmorPlate™
PRODUCT LIFE Rigorous testing by Carrier engineers has shown the WeatherShield™ coil to last three times longer than a standard coil in harsh coastal conditions. This improved performance is due to features such as the heavy-duty fin design that resists trapping salt water and the added protection of ArmorPlate™ coating.
Warranty
5 The Carrier 24ABB air conditioners for coastal applications includes a five-year limited warranty on the entire unit. Extended warranties are also available. Ask your Carrier dealer for details.
YEAR
LIMITED WARRANTY
Turn to the Experts Willis Carrier invented air conditioning in 1902. Over 100 years later, we’re proud to say Carrier systems are trusted in more homes than any other brand. Carrier continues to be on the forefront of innovative engineering and unsurpassed standards of excellence. So when choosing a home comfort system, you’ll want to turn to the experts. Your Carrier dealer will evaluate your home, such as window placement and size, ductwork, other structural specifics and lifestyle to provide a customized indoor comfort plan designed specifically for you. And when you have an expert helping you make an educated decision, you’re going to feel more comfortable.
www.carrier.com
1-800-CARRIER ISO 9001:2000
A member of the United Technologies Corporation family. Stock Symbol UTX. REGISTERED
© Carrier Corporation 2008
01-824-012-25
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. Model 24ABB3**C
13.0
Always look for these symbols, the air conditioning industry seals of certified performance, efficiency and capacity.
24ABB3 Base 13 Air Conditioner with Puron® Refrigerant Carrier Corporation•Syracuse, NY 13221 SUBJECT TO CHANGE WITHOUT NOTICE
Carrier Base 13 Air Conditioner with Puron Refrigerant, Model 24ABB3, is available in 1.5-5 ton nominal-sized units.
A08247
Shown with Dense Grille
STANDARD FEATURES Energy Efficiency – 13.0 - 13.2 SEER / 10.8 - 11.0 EER (based on tested combinations) Sound – Sound as low as 74 dBA with accessory sound blanket Reliability, Quality and Durability – Scroll Compressor – Field-installed Filter Drier – Front-seating Service Valves – Internal Pressure-Relief Valve – Internal thermal overload – Baked-on powder paint – Dense wire coil guard—Optional (Standard on 3 phase units) LIMITED WARRANTY* – 10 year limited to original purchaser on compressor and parts upon timely registration, otherwise 5 years *For owner occupied, residential applications
www.hvacsmartsystems.com
SUPERSEDES: 0924ABB3-01PP
Catalog No. 1024ABB3-01PP
Page 1 EFFECTIVE DATE: 12/31/2009
SAP ORDERING NO. 24ABB318(A,W)003 24ABB324(A,W)003 24ABB330(A,W)003 24ABB336(A,W)003 24ABB342(A,W)003 24ABB348(A,W)003 24ABB360A003 24ABB330A005 24ABB336A005 24ABB342A005 24ABB348A005 24ABB360A005 24ABB336A006 24ABB342A006 24ABB348A006 24ABB360A006 24ABB336A001 24ABB348A001 24ABB360A001
NOMINAL OPERATING COOLING VOLTS-PHASE VOLTAGE (60 HZ) SIZE RANGE (Btu x 1,000) 18 24 30 36 42 48 60 30 36 42 48 60 36 42 48 60 36 48 60
208/230/1
197-253
208/230-3
197-253
460-3
414-506
575-3
518-532
PACKAGED DIMENSIONS (IN.) D X W X H*†
APPROX SHIP WT (LB)†
24-1/4 x 27-3/8 x 33-1/2 24-1/4 x 27-3/8 x 33-1/2 24-1/4 x 27-3/8 x 33-1/2 26-7/8 x 30-1/16 x 35-15/16 32-3/8 x 35-1/2 x 35-15/16 32-3/8 x 35-1/2 x 39-3/8 32-3/8 x 35-1/2 x 32-9/16 24-1/4 x 27-3/8 x 33-1/2 26-7/8 x 30-1/16 x 35-15/16 32-3/8 x 35-1/2 x 35-15/16 32-3/8 x 35-1/2 x 39-3/8 32-3/8 x 35-1/2 x 32-9/16 26-7/8 x 30-1/16 x 35-15/16 32-3/8 x 35-1/2 x 35-15/16 32-3/8 x 35-1/2 x 39-3/8 32-3/8 x 35-1/2 x 32-9/16 26-7/8 x 30-1/16 x 35-15/16 32-3/8 x 35-1/2 x 39-3/8 32-3/8 x 35-1/2 x 32-9/16
130 134 136 170 218 224 226 136 170 218 224 230 170 218 224 230 170 224 230
PRICE $695 $715 $764 $940 $963 $1,051 $1,269 $1,204 $1,371 $1,463 $1,598 $1,870 $1,371 $1,463 $1,598 $1,870 N/A N/A N/A
* All units are individually skidded for shipment. † Weight and height may vary by series. See PD for actual weights and dimensions by series. Height shown is maximum. NOTE: (A,W) A = Dense Grille, W = Standard Grille
OPTIONAL EXTENDED WARRANTIES (Single Phase Puron Units Only)
NET PRICE
System Parts Only - 6th through 10th year*† System Labor Only - 2nd through 5th year* System Labor Only - 2nd through 10th year* System Labor Only - 1st through 5th year* System Labor only - 1st through 10th year* Parts Only - 6th through 10th year†‡ Labor Only - 2nd through 5th year‡ Labor Only - 2nd through 10th year‡ Labor Only - 1st through 5th year‡ Labor Only - 1st through 10th year‡ Compressor Parts Only - 6th through 10th year * Thermostat, Infinity Control, Infinity Air Purifier, Electronic Air Cleaner, Humidifier, UV Light, Strip Heater only can be added to the "system" at no additional charge when included with registration. Zoning should be added separately at an additional charge. UV Light includes only control, not lamp. † Excludes compressor. ‡Carrier branded thermostat or Infinity Control included. NOTE: To qualify for system purchase, all equipment must be manufactured by Carrier and branded Carrier; System includes (outdoor unit + indoor unit) + thermostat.
OPTIONAL EXTENDED WARRANTIES (Three Phase Puron Units Only) Parts Only 2nd through 5th year
SUPERSEDES: 0924ABB3-01PP
Catalog No. 1024ABB3-01PP
NET PRICE
Page 2 EFFECTIVE DATE: 12/31/2009
24ABC6 Base 16 16 SEER Air Conditioner with Puron® Refrigerant
SUBJECT TO CHANGE WITHOUT NOTICE
Carrier Base 16 Air Conditioner with Puron Refrigerant, Model 24ABC6, is available in 1.5-5 ton nominal-sized units.
A08247
STANDARD FEATURES Energy Efficiency – 14-16.5 SEER / 11-13.5 EER Sound – Sound as low as 76 dBA (74 dBA w/accessory sound blanket) Reliability, Quality and Durability – Scroll Compressor – Field-installed Filter Drier – Front-seating Service Valves – Internal Pressure-Relief Valve – Internal thermal overload – Baked-on powder paint – Dense wire Coil Guard LIMITED WARRANTY* – 10 year limited to original purchaser on comperssor and parts upon timely registration, otherwise 5 years *For owner occupied, residential applications
SAP ORDERING NO.
NOMINAL OPERATING COOLING VOLTS-PHASE VOLTAGE (60 HZ) SIZE RANGE (Btu x 1,000)
PACKAGED DIMENSIONS (IN.) D X W X H*†
APPROX SHIP WT (LB)†
208-230-1
26-7/8 x 30-1/16 x 32-9/16 32-3/8 x 35-1/2 x 32-9/16 32-3/8 x 35-1/2 x 35-15/16 36-1/8 x 39-5/16 x 32-9/16 36-1/8 x 39-5/16 x 42-3/4 36-1/8 x 39-5/16 x 35-15/16 36-1/8 x 39-5/16 x 49-9/16
154 183 188 204 254 274 310
24ABC618A003 24ABC624A003 24ABC630A003 24ABC636A003 24ABC642A003 24ABC648A003 24ABC660A003
18 24 30 36 42 48 60
197-253
PRICE $816 $863 $940 $1,039 $1,083 $1,188 $1,399
* All units are individually skidded for shipment. † Weight and height may vary by series. See PD for actual weights and dimensions by series. Height shown is maximum.
SUPERSEDES: NEW
Catalog No. 1024ABC6-01PP
Page 1 EFFECTIVE DATE: 12/31/2009
OPTIONAL EXTENDED WARRANTIES (Single Phase Puron Units Only)
NET PRICE
System Parts Only - 6th through 10th year*† System Labor Only - 2nd through 5th year* System Labor Only - 2nd through 10th year* System Labor Only - 1st through 5th year* System Labor only - 1st through 10th year* Parts Only - 6th through 10th year†‡ Labor Only - 2nd through 5th year‡ Labor Only - 2nd through 10th year‡ Labor Only - 1st through 5th year‡ Labor Only - 1st through 10th year‡ Compressor Parts Only - 6th through 10th year * Thermostat, Infinity Control, Infinity Air Purifier, Electronic Air Cleaner, Humidifier, UV Light, Strip Heater only can be added to the "system" at no additional charge when included with registration. Zoning should be added separately at an additional charge. UV Light includes only control, not lamp. † Excludes compressor. ‡Carrier branded thermostat or Infinity Control included.
ACCESSORIES DESCRIPTION
PART NO.
USED WITH
KAAFT0101AAA KAATD0101TDR KAAWS0101AAA
All All All
Low Ambient Pressure Switch - Puron
KSALA0301410
All
MotorMaster 230V Low-Ambient Controller*
KSALA0601AAA
All
HC32GE229 HC34GE240 HC32GE234 HC38GE228 HC40GE228 KSAHS1701AAA
36 24, 30 18 42 48, 60 All
Evaporator Freeze Thermostat Time-Delay Relay Winter Start Control
Ball-Bearing Fan Motor
Start Assist-Capacitor/Relay Type
Cycle Protector - 5 Minute Time Delay KSACY0101AAA Liquid-Line Solenoid Valve Support Feet Start Assist - PTC Low-Pressure Switch High-Pressure Switch Crankcase Heater
TXV - Hard Shutoff (Puron)
Compressor Sound Blanket
KAALS0201LLS KSASF0101AAA KAACS0201PTC KAALP0401PUR KAAHI0501PUR KAACH1701AAA KAACH1601AAA KSATX0201PUR KSATX0301PUR KSATX0401PUR KSATX0501PUR KSASH0601COP KSASH2101COP
PRICE
All All All All All All 18-36 42 18-30 36 42 48, 60 18-36 42-60
* The use of Motormaster Low Ambient Controller requires the following accessories: Ball-Bearing Fan Motor Crankcase Heater Evaporator Freeze Thermostat Winter Start Control Start Assist - Cap/Relay Type
SUPERSEDES: NEW
Catalog No. 1024ABC6-01PP
Page 2 EFFECTIVE DATE: 12/31/2009
SUPERSEDES: NEW
Catalog No. 1024ABC6-01PP
Page 3 EFFECTIVE DATE: 12/31/2009
24ABB3 Baset13 Air Conditioner with Puronr Refrigerant
Product Data INDUSTRY LEADING FEATURES / BENEFITS Efficiency S 13.0 -- 13.2 SEER/10.8-- 11.0 EER (based on tested combinations)
S S Sound S S
Microtube Technologyt refrigeration system Indoor air quality accessories available Sound level as low as 75 dBA Sound level as low as 74 dBA with accessory sound blanket
Comfort S System supports Edger Thermidistatt or standard thermostat controls
Reliability S Puronr refrigerant -- environmentally sound, won’t deplete the ozone layer and low lifetime servce cost.
the environmentally sound refrigerant
Carrier’s Air Conditioners with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 24ABB has been designed utilizing Carrier’s Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer. As an Energy Starr Partner, Carrier Corporation has determined that this product meets the Energy Starr guidelines for energy efficiency. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines. NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up--to--date ratings information.
S Scroll compressor S Internal pressure relief valve S Internal thermal overload S Filter drier S Balanced refrigeration system for maximum reliability Durability WeatherArmort protection package:
S S
Solid, durable sheet metal construction Dense wire coil guard available (3--phase units come standard with dense wire coil guard)
S Baked--on, complete outer coverage, powder paint Applications S Long--line -- up to 250 feet (76.20 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.)
S
Low ambient accessory kit
(down
to
--20_F/--28.9_C)) with
MODEL NUMBER NOMENCLATURE 1 N
2 N
3 A
4 A
5 A/N
6 N
7 N
8 N
9 A/N
10 A/N
11 A/N
12 N
13 N
2
4
A
B
B
3
3
6
A
0
0
3
0
Product Series
Product Family
Tier
Major Series
SEER
Cooling Capacity
Variations
Open
Open
Voltage
Series
24=AC
A=RES AC
B=Base
B=Puron
3=13 SEER
1.000 Btuh (nominal)
A=Dense Grille W=Wide Grille
0=Not Defined
0=Not Defined
3=208/230 ---1 5=208/230 ---3 6=460/3 1 = 575/3
0= Original Series
24ABB3
ISO 9001:2000
the environmentally sound refrigerant
REGISTERED
This product has been designed and manufactured to meet Energy Star速 criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturing refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.
STANDARD FEATURES Feature
18
24
30
36
42
48
60
Puron Refrigerant
X
X
X
X
X
X
X
Maximum SEER
14.50
14.25
15.0
14.0
14.0
14.0
13.5
Scroll Compressor
X
X
X
X
X
X
X
Field Installed Filter Drier
X
X
X
X
X
X
X
Front Seating Service Valves
X
X
X
X
X
X
X
Internal Pressure Relief Valve
X
X
X
X
X
X
X
Internal Thermal Overload
X
X
X
X
X
X
X
Long Line capability
X
X
X
X
X
X
X
Low Ambient capability with Kit
X
X
X
X
X
X
X
X
X
X
X
X
Dense Grille (standard on 3---Phase only) X = Standard
2
PHYSICAL DATA UNIT SIZE SERIES
18--- 31
24--- 31
30--- 31,51
36--- 31,51,61
42--- 30,50,60
48--- 31,51,61,11
60--- 32
60--- 52,62,12
Operating Weight lb (kg)
107 (48.5)
110 (50.0)
111 (50.3)
141 (64.0)
190 (86.2)
186 (84.4)
190 (86.2)
215 (97.5)
Shipping Weight lb (kg)
130 (60.0)
134 (60.8)
136 (61.7)
170 (77.1)
218 (98.9)
224 (101.6)
226 (102.5)
250 (113.4)
7.00 (3.2)
8.19 (3.7)
8.00 (3.6)
3365
Compressor Type
Scroll
REFRIGERANT
Puron (R---410A)
Control Charge lb (kg)
TXV (Puron Hard Shutoff) 3.50 (1.6)
3.80 (1.7)
4.10 (1.9)
5.34 (2.4)
COND FAN
5.84 (2.7)
Propeller Type, Direct Drive
Air Discharge
Vertical
Air Qty (CFM)
1792
2218
2218
2954
3167
3365
3365
Motor HP
1/12
1/10
1/10
1/4
1/5
1/4
1/4
1/4
Motor RPM
1100
1100
1100
1100
1100
1100
800
1100
Face Area (Sq ft)
8.40
8.40
9.80
13.13
17.25
19.40
12.93
15.09
Fins per In.
20
25
25
25
25
25
20
20
Rows
1
1
1
1
1
1
2
2
Circuits
3
3
3
3
4
5
5
6
Vapor
3/4
3/4
3/4
7/8
7/8
7/8
7/8
7/8
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
VALVE CONNECT. (In. ID)
REFRIGERANT TUBES* (In. OD) Rated Vapor*
3/4
7/8
Max Liquid Line{
1 ---1/8
3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation. { See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
3
24ABB3
COND COIL
REFRIGERANT PIPING LENGTH LIMITATIONS Liquid Line Sizing and Maximum Total Equivalent Lengths{ for Cooling Only Systems with Puronr Refrigerant: The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units. See Table below for liquid line sizing and maximum lengths :
24ABB3
Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit Size
Liquid Line Connection
018 AC with Puron
3/8
024 AC with Puron
3/8
030 AC with Puron
3/8
Liquid Line Diam. w/ TXV 1/4 5/16 3/8 1/4 5/16 3/8 1/4 5/16 3/8
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor Vertical Separation ft (m) 0--- 5 (0--- 1.5)
6--- 10 (1.8--- 3.0)
11--- 20 (3.4--- 6.1)
21--- 30 (6.4--- 9.1)
31--- 40 (9.4--- 12.2)
41--- 50 (12.5--- 15.2)
51--- 60 (15.5--- 18.3)
61--- 70 (18.6--- 21.3)
71--- 80 (21.6--- 24.4)
150 250* 250* 75 250* 250* 30 175 250*
150 250* 250* 75 250* 250* --- --225* 250*
125 250* 250* 75 250* 250* --- --200 250*
100 250* 250* 50 250* 250* --- --175 250*
100 250* 250* 50 250* 250* --- --125 250*
75 250* 250* --- --225* 250* --- --100 250*
--- --250* 250* --- --175 250* --- --75 250*
--- --225* 250* --- --125 250* --- ----- --250*
--- --150 250* --- --100 250* --- ----- --250*
036 5/16 175 150 150 100 AC with 3/8 3//8 250* 250* 250* 250* Puron 042 5/16 125 100 100 75 AC with 3/8 3/8 250* 250* 250* 250* Puron 048 AC with 3/8 3/8 250* 250* 250* 250* Puron 060 AC with 3/8 3/8 250* 250* 250* 225* Puron * Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line --- --- = outside acceptable range
100
100
75
--- ---
--- ---
250*
250*
250*
250*
250*
75
50
--- ---
--- ---
--- ---
250*
250*
250*
250*
150
250*
250*
230
160
--- ---
190
150
110
--- ---
--- ---
Guideline for details.
Maximum Total Equivalent Length Outdoor Unit ABOVE Indoor Unit Size
Liquid Line Connection
018 AC with Puron
3/8
024 AC with Puron
3/8
030 AC with Puron
3/8
Liquid Line Diam. w/ TXV 1/4 5/16 3/8 1/4 5/16 3/8 1/4 5/16 3/8
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor Vertical Separation ft (m) 25 (7.6)
26--- 50 (7.9--- 15.2)
51--- 75 (15.5--- 22.9)
76--- 100 (23.2--- 30.5)
101--- 125 (30.8--- 38.1)
126--- 150 (38.4--- 45.7)
151--- 175 (46.0--- 53.3)
176--- 200 (53.6--- 61.0)
175 250* 250* 100 250* 250* 30 250* 250*
250* 250* 250* 125 250* 250* --- --250* 250*
250* 250* 250* 175 250* 250* --- --250* 250*
250* 250* 250* 200 250* 250* --- --250* 250*
250* 250* 250* 225* 250* 250* --- --250* 250*
250* 250* 250* 250* 250* 250* --- --250* 250*
250* 250* 250* 250* 250* 250* --- --250* 250*
250* 250* 250* 250* 250* 250* --- --250* 250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
250*
036 5/16 225* 250* 250* 250* 250* AC with 3/8 3/8 250* 250* 250* 250* 250* Puron 042 5/16 175 200 250* 250* 250* AC with 3/8 3/8 250* 250* 250* 250* 250* Puron 048 AC with 3/8 3/8 250* 250* 250* 250* 250* Puron 060 3/8 3/8 250* 250* 250* 250* 250* AC with Puron * Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details. --- --- = outside acceptable range
4
REFRIGERANT CHARGE ADJUSTMENTS Liquid Line Size
Puron Charge oz/ft (g/m)
3/8
0.60 (17.74) (Factory charge for lineset = 9 oz / 266.16 g)
5/16
0.40 (11.83)
1/4
0.27 (7.98)
LONG LINE APPLICATIONS An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units. For Air Conditioner systems, the chart below shows when an application is considered Long Line. AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m) Beyond these lengths, long line accessories are required Liquid Line Size 1/4
Units On Same Level No accessories needed within allowed lengths
Outdoor Below Indoor No accessories needed within allowed lengths
Outdoor Above Indoor 175 (53.3)
5/16
120 (36.6)
50 (15.2) vertical or 120 (36.6) total
120 (36.6)
3/8
80 (24.4)
35 (10.7) vertical or 80 24.4) total
80 (24.4)
Note: See Long Line Guideline for details
VAPOR LINE SIZING AND COOLING CAPACITY LOSS Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant: Vapor Line Sizing and Cooling Capacity Losses — Puronr Refrigerant 1--Stage Air Conditioner Applications Unit Nominal Size (Btuh) 018 1 Stage AC with Puron 024 1 Stage AC with Puron 030 1 Stage AC with Puron 036 1 Stage AC with Puron 042 1 Stage AC with Puron 048 1 Stage AC with Puron 060 1 Stage AC with Puron
Maximum Liquid Line Diameters (In. OD) 3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line Diameters (In. OD)
26--- 50
51--- 80
81--- 100
(7.9--- 15.2)
(15.5--- 24.4)
(24.7--- 30.5)
1/2
1
2
5/8
0
1
3/4
0
5/8
Cooling Capacity Loss (%) Total Equivalent Line Length ft. (m) 101--- 125 126--- 150 151--- 175
176--- 200
201--- 225
226--- 250
(30.8--- 38.1)
(38.4--- 45.7)
(46.0--- 53.3)
(53.6--- 61.0)
(61.3--- 68.6)
(68.9--- 76.2)
3
5
6
7
8
9
11
1
1
2
2
2
3
3
0
0
0
1
1
1
1
1
0
1
2
2
3
3
4
5
5
3/4
0
0
1
1
1
1
1
2
2
7/8
0
0
0
0
0
1
1
1
1
5/8
1
2
3
3
4
5
6
7
8
3/4
0
0
1
1
1
2
2
2
3
7/8
0
0
0
0
1
1
1
1
1
5/8
1
2
4
5
6
8
9
10
12
3/4
0
1
1
2
2
3
3
4
4
7/8
0
0
0
1
1
1
1
2
2
3/4
0
1
2
2
3
4
4
5
6
7/8
0
0
1
1
1
2
2
2
3
1 1/8
0
0
0
0
0
0
0
0
0
3/4
0
1
2
3
4
5
5
6
7
7/8
0
0
1
1
2
2
2
3
3
1 1/8
0
0
0
0
0
0
0
1
1
3/4
1
2
4
5
6
7
9
10
11
7/8
0
1
2
2
3
4
4
5
5
1 1/8
0
0
0
1
1
1
1
1
1
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
5
24ABB3
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above. Charging Formula: [(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required? Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz. Net result is to remove 4.95 oz of refrigerant from the system Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment? Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz. Net result is to add 9 oz of refrigerant to the system
6
MOTOR FAN
MOTOR FAN
MOTOR FAN
MOTOR FAN
MOTOR FAN
MOTOR FAN
KIT CRKC HTR
KIT CRKC HTR
KIT CRKC HTR
KIT CRKC HTR
KIT CRKC HTR
KIT CRKC HTR
KIT PTC
KIT FRZ THERM
KIT PRESSURE SW
KIT PRESSURE SW
KIT SOL VALVE
KIT TIME DELAY
KIT WINTER ST
KIT CYCLE PROTR
KIT HARD START
KIT LOW AMBIENT
KIT MOTOR MASTER
KIT MOTOR MASTER
KIT SPRT FEET
KIT SOUND BLKT
KIT SOUND BLKT
KIT TXV
KIT TXV
KIT TXV
KIT TXV
HC34GE239
HC38GE219
HC38GE461
HC40GE225
HC40GE226
HC40GE466
KAACH1201AAA
KAACH1401AAA
KAACH1501AAA
KAACH1801AAA
KAACH1901AAA
KAACH2001AAA
KAACS0201PTC
KAAFT0101AAA
KAAHI0501PUR
KAALP0401PUR
KAALS0201LLS
KAATD0101TDR
KAAWS0101AAA
KSACY0101AAA
KSAHS1701AAA
KSALA0301410
KSALA0601AAA
KSALA0701AAA
KSASF0101AAA
KSASH0601COP
KSASH2101COP
KSATX0201PUR
KSATX0301PUR
KSATX0401PUR
KSATX0501PUR
X = Accessory
MOTOR FAN
DESCRIPTION
HC32GE234
KIT NUMBER
ACCESSORIES
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
18--- 31
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
24--- 31
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
30--- 31
X
X
X
X
X
X
X
X
X
X
X
X
X
X
30--- 51
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
36--- 31
X
X
X
X
X
X
X
X
X
X
X
X
X
X
36--- 51
X
X
X
X
X
X
X
X
X
X
X
X
X
X
36--- 61
X
X
X
X
X
X
X
X
X
X
X
X
36--- 11
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
42--- 50
X
X
X
X
X
X
X
X
X
X
X
X
X
X
42--- 60
Size --- Voltage, Series 42--- 30
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
48--- 31
X
X
X
X
X
X
X
X
X
X
X
X
X
X
48--- 51
24ABB3
X
X
X
X
X
X
X
X
X
X
X
X
X
X
48--- 61
X
X
X
X
X
X
X
X
X
X
X
X
48--- 11
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
60--- 32
X
X
X
X
X
X
X
X
X
X
X
X
X
X
60--- 52
X
X
X
X
X
X
X
X
X
X
X
X
X
X
60--- 62
X
X
X
X
X
X
X
X
X
X
X
X
60--- 12
ACCESSORY THERMOSTATS THERMOSTAT / SUBBASE PKG. TP---PRH01---A
Programmable Thermidistat
TP---NRH01---A
Non--- programmable Thermidistat
TP---PAC01
Performance Series Programmable AC Stat
TP---NAC01
Performance Series Non--- programmable AC Stat
TC ---PAC01
Comfort Series Programmable AC Stat
TC ---NAC01
Comfort Series Non--- programmable AC Stat
TB---PAC01
Base Series Programmable AC Stat
TB---NAC01
Base Series Non--- programmable AC Stat
TSTATCCSEN01---B
Outdoor Air Temperature Sensor
TSTATXXBBP01
Backplate for Builder’s Thermostat
TSTATXXNBP01
Backplate for Non--- Programmable Thermostat
TSTATXXPBP01
Backplate for Programmable Thermostat
TSTATXXCNV10
Thermostat Conversion Kit (4 to 5 wires) --- 10 Pack
ACCESSORY USAGE GUIDELINE ACCESSORY Ball Bearing Fan Motor Compressor Start Assist Capacitor and Relay Crankcase Heater Evaporator Freeze Thermostat Hard Shut---Off TXV Liquid Line Solenoid Valve Motor Master® Control or Low---ambient Pressure Switch Support Feet Winter Start Control
REQUIRED FOR LOW---AMBIENT COOLING APPLICATIONS (Below 55°F/12.8_C) Yes{ Yes Yes Yes Yes No
No Yes Yes No Yes No
REQUIRED FOR SEA COAST APPLICATIONS (Within 2 miles/3.22 km) No No No No Yes No
Yes
No
No
Recommended Yes #
No No
Recommended No
REQUIRED FOR LONG LINE APPLICATIONS*
* For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential (total equivalent length), refer to the Residential Split---System Longline Application Guideline. { Required for Low---Ambient Controller (full modulation feature) MotorMasterr Control. # Required if Low Pressure Switch is factory or field installed.
Accessory Description and Usage (Listed Alphabetically) 3. Compressor Start Assist — PTC Type Solid state electrical device which gives a ”soft” boost to the compressor at each start--up. Usage Guideline: Suggested in installations with marginal power supply. 4. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging. Usage Guideline: Required in low ambient cooling applications. Required in long line applications. Suggested in all commercial applications. 5. Cycle Protector The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5--minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling.
1. Ball--Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. Usage Guideline: Required on all units when MotorMasterr is used. 2. Compressor Start Assist -- Capacitor and Relay Start capacitor and relay gives a ”hard” boost to compressor motor at each start up. Usage Guideline: Required for reciprocating compressors in the following applications: Long line Low ambient cooling Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil Required for single--phase scroll compressors in the following applications: Long line Low ambient cooling Suggested for all compressors in areas with a history of low voltage problems.
7
24ABB3
DESCRIPTION
24ABB3
Accessory Description and Usage (Listed Alphabetically) (Continued) 6. Evaporator Freeze Thermostat An SPST temperature--actuated switch that stops unit operation when evaporator reaches freeze--up conditions. Usage Guideline: Required when low ambient kit has been added. 7. Low--Ambient Pressure Switch Kit A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low--ambient temperatures down to 0_F (--18_C) when properly installed. Usage Guideline: A Low--Ambient Pressure Switch or MotorMasterr Low--Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C). 8. MotorMasterr Low--Ambient Controller A fan--speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to --20_F (--28.9_C), it maintains condensing temperature at 100_F Âą10_F (37.8_C Âą 5.5_C). Usage Guideline: A MotorMasterr Low Ambient Controller or Low--Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C). Suggested for all commercial applications. 9. Outdoor Air Temperature Sensor Designed for use with Carrier Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also is required to enable special thermostat features such as auxiliary heat lock out. Usage Guideline: Suggested for all Carrier thermostats listed in this publication. 10. Sound Hood Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA. Usage Guideline: Suggested when unit is installed closer than 15 ft (4.57 m) to quiet areas, bedrooms, etc. Suggested when unit is installed between two houses less than 10 ft (3.05 m) apart.
11. Support Feet Four stick--on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion. Usage Guideline: Suggested in the following applications: Coastal installations. Windy areas or where debris is normally circulating. Rooftop installations. For improved sound ratings. 12. Thermostatic Expansion Valve (TXV) A modulating flow--control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available. NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required. Usage Guideline: Required to achieve ARI ratings in certain equipment combinations. Refer to combination ratings. Hard shut off TXV or LLS required in air conditioner long line applications. Required for use on all zoning systems. 13. Time--Delay Relay An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off. NOTE: Most indoor unit controls include this feature. For those that do not, use the guideline below. Usage Guideline: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. 14. Winter Start Control This control is designed to alleviate nuisance opening of the low--pressure switch by bypassing it for the first 3 minutes of operation.
8
UNIT SIZE --VOLTAGE, SERIES 18--- 31 24--- 31 30--- 31 36--- 31 42--- 30 48--- 31 60--- 32 30--- 51 36--- 51 42--- 50 48--- 51 60--- 52 36--- 61 42--- 60 48--- 61 60--- 62 36--- 11 48--- 11 60--- 12
V/PH
OPER VOLTS* MAX
MIN
208/230/1
253
197
208/230 ---3
253
197
460 ---3
506
414
575 ---3
532
518
COMPR
FAN
LRA
RLA
FLA
48.0 58.3 64.0 77.0 112.0 109.0 134.0 58.0 71.0 88.0 83.1 110.0 38.0 44.0 41.0 52.0 36.5 33.0 38.9
9.0 13.5 12.8 15.3 17.9 19.9 26.4 8.3 10.5 13.5 13.1 16.0 5.6 6.0 6.1 7.8 3.8 4.4 5.7
0.5 0.77 0.77 1.4 1.1 1.4 1.2 0.77 1.4 1.1 1.4 1.4 0.7 0.6 0.7 0.7 0.5 0.5 0.5
MCA 11.8 17.6 16.8 21.5 23.5 26.2 34.2 11.2 14.5 18.0 17.8 21.4 7.7 8.1 8.3 10.5 5.3 6.0 7.6
MIN WIRE SIZE{
MIN WIRE SIZE{
MAX LENGTH ft. (m)}
MAX LENGTH ft. (m)}
60째 C
75째 C
60째 C
75째 C
14 14 14 12 12 10 8 14 14 14 10 12 14 14 14 14 14 14 14
14 14 14 12 12 10 10 14 14 14 10 12 14 14 14 14 14 14 14
67 (20.4) 45 (13.7) 47 (14.3) 58 (17.7) 53 (16.2) 76 (23.2) 91 (27.7) 81 (24.7) 63 (19.2) 51 (15.5) 130 (39.6) 67 (20.4) 236 (71.9) 225 (68.5) 219 (66.8) 173 (52.7) 343 (104.5) 303 (92.4) 239 (72.8)
63 (19.2) 43 (13.1) 45 (13.7) 55 (16.8) 51 (15.5) 73 (22.3) 56 (17.1) 77 (23.5) 60 (18.3) 48 (14.6) 123 (37.5) 64 (16.5) 225 (68.5) 214 (65.2) 208 (63.4) 165 (50.3) 326 (99.4) 288 (87.8) 228 (69.5)
MAX FUSE** or CKT BRK AMPS 20 25 25 30 40 40 50 20 20 30 30 30 15 15 15 15 15 15 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily { If wire is applied at ambient greater than 30_C , consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75_C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70). } Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time ---Delay fuse. FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection. Complies with 2007 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER LEVEL UNIT SIZE 18--- 31 24--- 31 30--- 31, 51 36--- 31, 51, 62, 12 42--- 30, 50, 60 48--- 31, 51, 62, 12 60--- 32 60--- 52, 62, 12
STANDARD RATING dBA 72 76 74 75 78 80 78 79
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment) 125
250
500
1000
2000
4000
8000
53.5 55.0 55.0 59.5 57.5 58.5 59.0 59.5
59.5 61.5 63.5 63.0 65.0 67.5 67.5 69.5
63.5 67.0 68.5 68.5 71.0 73.5 71.5 72.5
67.0 71.5 68.5 70.0 73.0 75.0 73.5 73.5
63.5 69.0 65.5 65.5 70.5 70.5 69.0 71.0
59.0 61.0 61.0 61.5 67.5 67.5 66.0 68.0
52.5 55.0 54.0 53.5 62.5 64.5 63.5 63.5
NOTE: Tested in accordance with ARI Standard 270 ---2008 (not listed in AHRI).
A--WEIGHTED SOUND POWER LEVEL WITH SOUND SHIELD UNIT SIZE 18--- 31 24--- 31 30--- 31, 51 36--- 31, 51, 62, 12 42--- 30, 50, 60 48--- 31, 51, 62, 12 60--- 32 60--- 52, 62, 12
STANDARD RATING dBA 71 74 73 74 77 79 78 78
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment) 125
250
500
1000
2000
4000
8000
55.5 55.5 55.5 59.5 57.5 60.5 59.0 60.5
60.5 60.5 64.0 63.0 65.0 67.5 68.0 69.5
64.0 66.5 68.0 68.0 70.5 73.5 70.5 72.5
66.0 70.0 67.0 69.5 72.0 74.5 72.5 73.0
63.0 67.0 64.0 65.0 70.0 71.0 68.0 71.0
58.5 61.0 60.0 60.5 67.0 68.0 67.0 67.5
52.0 53.5 52.5 50.5 62.0 63.5 63.0 61.5
NOTE: Tested in accordance with ARI Standard 270 ---2008 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE) UNIT SIZE --- VOLTAGE & SERIES 18--- 31 24--- 31 30--- 31, 51 36--- 31, 51, 62, 12 42--- 30, 50, 60 48--- 31, 51, 62, 12 60--- 32 60--- 52, 62, 12
REQUIRED SUBCOOLING _F (_C) 10 (5.6) 10 (5.6) 10 (5.6) 14 (7.8) 10 (5.6) 15 (8.3) 13 (7.2) 10 (5.6)
9
24ABB3
ELECTRICAL DATA
10
O
X
O
X
X
X O
O
O
O
X
X X
X
X
X
X
O
X
X X
X
O
O
18,24,30 36 48,60 -
LINE CONN.
3 1/2”
23 1/2” X 23 1/2” 26” X 26”
UNIT SIZE
D VAPOR
C
FIELD POWER SUPPLY CONN. 7/8” HOLE WITH 1 1/8” KNOCKOUT
FIELD CONTROL SUPPLY CONN. 7/8” HOLE
2
24ABB360
B
1
1 0
24ABB336 24ABB342
1,2
1
24ABB330
24ABB360
1
24ABB348
1,2
24ABB324
208-230-1-60
575
24ABB318
X
O
X
X X
O
O
O
4 7/16” 21 1/4” 9 1/8” 2 15/16” 5/8” 6 9/16” 24 11/16” 9 1/8” 2 15/16” 5/8” 6 9/16” 24 11/16” 9 1/8” 2 15/16” 5/8”
31 3/16”
AIR DISCHARGE
SQ.
1 7/8”
P 3”
5/16”
K
16”
M G
14 1/8”
16 3/8”
14 1/4” 15 3/4”
16 1/2”
16 1/2”
16 1/2”
M
15”
15”
15”
N
15 1/2”
15 3/8”
15 3/8”
10 1/2” 16 1/4”
3/8” TIEDOWN KNOCKOUTS (2) PLACES
L
AIR IN
31 3/16” 28 15/16” 3 7/8” 7/8”
A
6 9/16” 24 11/16” 9 1/8” 2 15/16” 5/8”
3 7/8” 7/8”
X = YES O = NO
6 9/16” 24 11/16” 9 1/8” 2 15/16” 5/8”
3 7/8” 7/8”
35 3/4”
31 3/16” 25 1/2”
18 1/16” 7 13/16” 2 13/16” 1/2”
18 1/16” 7 13/16” 2 13/16” 1/2”
25 3/4” 32 5/16” 3 7/8” 7/8” 31 3/16” 32 5/16” 3 7/8” 7/8”
L
4 7/16”
K
23 1/8” 28 11/16” 3 3/4” 3/4”
G
18 1/16” 7 13/16” 2 13/16” 1/2”
F
4 7/16”
4 7/16”
E
25 5/16” 3 3/4” 3/4”
D
25 5/16” 3 3/4” 3/4”
C
23 1/8”
B
23 1/8”
ELECTRICAL SERIESCHARACTERISTICS A
208/230-3-60
UNIT
DIMENSIONS -- ENGLISH
460-3-60
198
190
186
141 190
111
110
107
230
226
224
170 218
136
134
130
OPERATING SHIPPING WEIGHT (lbs) WEIGHT (lbs)
AIR IN
AIR IN
AIR DISCHARGE
5. ALL DIMENSIONS ARE IN
4. CENTER OF GRAVITY
E
N
F AIR IN
INCHES" UNLESS NOTED.
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODEL NUMBER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F, MAX. 125°F.
NOTES: 1. ALLOW 24" CLEARANCE TO SERVICE END OF UNIT. 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 18” BETWEEN UNITS FOR PROPER AIRFLOW.
12 3/4”
11 3/8”
15 1/4”
16” 13 3/4”
14”
12”
12”
P
24ABB3
11
1
1
0
1
1,2
2
24ABB330
24ABB336
24ABB342
24ABB348
24ABB360
24ABB360
X
O
O
X
X
O
X
O
O
O
X
X
X
X
X
X
X
O
X
X
X
O
O
O
FIELD CONTROL SUPPLY CONN. 22.23 HOLE
X
O
X
X
X
X
O
O
18,24,30 36 48,60 -
UNIT SIZE
D VAPOR
C
LINE CONN.
88.9
FIELD POWER SUPPLY CONN. 22.23 HOLE WITH 28.58 KNOCKOUT
1
B
1,2
24ABB324
208-230-1-60
575
24ABB318 643.0 728.7 820.8 820.8 908.0 647.7 735.0
587.3 654.0 792.2 792.2 792.2 792.2 X = YES O = NO
643.0
587.3
B
587.3
ELECTRICAL SERIESCHARACTERISTICS A
208/230-3-60
UNIT
DIMENSIONS -- SI
460-3-60
22.2
22.2
22.2
22.2
22.2
19.0
19.0
19.0
D
AIR DISCHARGE
SQ.
A
98.4
98.4
98.4
98.4
98.4
95.2
95.2
95.2
C
166.7
166.7
166.7
166.7
112.7
112.7
112.7
112.7
E
627.1
627.1
627.1
627.1
539.8
458.8
458.8
458.8
F
47.6
P
231.8
231.8
231.8
231.8
231.8
198.4
198.4
198.4
G
76.2
L
K
406.4
358.8
415.9
400.0
362.0
419.1
419.1
G
M
393.7
390.5
390.5
412.8
266.7
381.0
381.0
381.0
N
9.53 TIEDOWN KNOCKOUTS (2) PLACES
L
M 419.1
8.0
15.9
15.9
15.9
15.9
15.9
12.7
12.7
12.7
AIR IN
74.6
74.6
74.6
74.6
74.6
71.4
71.4
71.4
K
89.8
86.2
84.4
86.2
64.0
50.3
49.9
48.5
104.3
102.5
101.6
98.9
77.1
61.7
60.8
59.0
OPERATING SHIPPING WEIGHT (Kgs) WEIGHT (Kgs)
24ABB3
AIR IN
AIR IN
E
N
F
MM" UNLESS NOTED. AIR DISCHARGE
5. ALL DIMENSIONS ARE IN
4. CENTER OF GRAVITY
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODEL NUMBER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 13째C, MAX. 52째C.
NOTES: 1. ALLOW 609.6 CLEARANCE TO SERVICE END OF UNIT. 1219.2 ABOVE UNIT, 152.4 ON ONE SIDE, 304.8 ON REMAINING SIDE, AND 609.6 BETWEEN UNITS FOR PROPER AIRFLOW.
323.9
288.9
387.4
349.2
406.4
355.6
304.8
304.8
P
12
24” (609.6) Service
12” (304.8)
Note: Numbers in ( ) = mm
18” (457.2)
24” (609.6) Service
Wall 6” (152.4)
18” (457.2)
12” (304.8)
24” (609.6) Service
Wall
18” (457.2)
12” (304.8)
Clearances (various examples)
24” (609.6) Service
12” (304.8)
24” (609.6) Service
Wall
6” (152.4)
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
CLEARANCES
24ABB3
Wall
ARI Ref. No. 3249887 3249889 3249891 3249892 3249890 3249895 3249897 3249894 3249893 3249918 3249913 3249914 3249916 3249917 3249911 3249912 3249910 3249915 3249909 3249900 3249898 3249902 3249903 3249901 3249906 3249908 3249905 3249904 3249923 3249924 3249921 3249922 3249920 3249919 3249932 3249933 3249935 3404569 3249931 3249928
Model Number 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31 24ABB318(A,W)31
Indoor Model †CAP**1814A**+TDR CAP**1814A** CAP**2414A** CAP**2414A** CAP**2414A**+TDR CAP**2417A** CAP**2417A** CAP**2417A** CAP**2417A**+TDR CNPF*2418A**+TDR CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A**+TDR CNPV*1814A** CNPV*1814A**+TDR CNPV*2414A** CNPV*2414A** CNPV*2414A**+TDR CNPV*2417A** CNPV*2417A** CNPV*2417A** CNPV*2417A**+TDR CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A**+TDR FE4ANF002+UI FF1ENP018 FV4BNF002 FV4CNF002 FX4CNF024 FY4ANF018
3250356 3250357 3250358 3250361 3250362 3250364 3250360 3250359 3250366 3250367 3250365 3250371 3250372 3250373 3250368 3250467 3250424 3250399 3250401 3250406 3250398 3250393 3250404 3250392 3250415 3250418 3250421 3250422 3250423 3250410 3250412 3250409
24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31
†CAP**2414A**+TDR CAP**2414A** CAP**2414A** CAP**2417A** CAP**2417A** CAP**2417A** CAP**2417A** CAP**2417A**+TDR CAP**3014A** CAP**3014A** CAP**3014A**+TDR CAP**3017A** CAP**3017A** CAP**3017A** CAP**3017A**+TDR CAP**3617A** CNPF*2418A**+TDR CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A** CNPH*2417A**+TDR CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A**
Furnace Model 58PH*045---08 58CV(A,X)070---12 58PH*045---08 58CV(A,X)090---16 58MEB060---12 58MV(B,C)060---14
58CV(A,X)070---12 58CV(A,X)090---16 58MEB040---12 58MEB060---12 58MV(B,C)060---14 58MV(B,C)080---14 58MVB040---14 58PH*045---08 58PH*045---08 58CV(A,X)070---12 58PH*045---08 58CV(A,X)090---16 58MEB060---12 58MV(B,C)060---14 58CV(A,X)070---12 58CV(A,X)090---16 58MV(B,C)060---14 58MV(B,C)080---14 58MVB040---14
58CV(A,X)070---12 58PH*045---08 58CV(A,X)090---16 58MEB040---12 58MEB080---12 58MV(B,C)060---14 58CV(A,X)070---12 58PH*045---08 58MEB040---12 58MEB060---12 58MEB080---12 58PH*045---08 58CV(A,X)070---12 58CV(A,X)110---20 58MEB060---12 58MV(B,C)120---20 58MVB040---14 58PH*045---08 58CV(A,X)070---12 58CV(A,X)135---22 58MEB040---12 58MEB060---12 58MEB080---12 58MV(B,C)060---14 58MV(B,C)080---20 58MVB040---14
See notes on page 21
13
Capacity 17,600 17,800 17,800 18,000 17,900 17,800 18,000 17,800 17,900 17,900 17,800 17,800 18,000 18,000 17,800 17,700 17,800 17,800 17,900 17,800 17,600 17,800 18,000 17,900 17,800 18,000 17,800 17,900 17,900 17,900 17,900 17,900 17,800 17,900 17,300 17,500 17,300 17,300 18,000 17,700
EERA 10.9 12.0 12.2 12.2 11.0 12.2 12.5 12.2 11.0 11.0 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 11.0 12.0 10.9 12.2 12.2 11.0 12.2 12.2 12.2 11.0 12.2 12.2 12.2 12.2 12.2 11.0 12.2 10.9 12.2 12.2 12.2 10.9
SEER 13.0 14.5 14.5 14.5 13.2 14.5 15.0 14.5 13.2 13.2 14.5 14.5 15.0 15.0 14.5 14.5 14.5 14.5 13.2 14.5 13.0 14.5 14.5 13.2 14.5 15.0 14.5 13.2 14.5 14.5 14.5 14.5 14.5 13.2 14.5 13.0 14.5 14.5 14.5 13.0
23,000 22,800 23,000 23,000 23,400 23,200 23,200 23,000 23,000 23,400 23,200 23,600 23,800 23,600 23,200 23,400 23,000 22,800 22,800 23,200 23,000 22,800 23,000 23,000 23,000 23,200 23,600 23,800 23,600 23,400 23,000 23,200
11.0 12.0 11.7 12.2 12.2 12.2 12.2 11.0 12.0 12.0 11.0 12.2 12.2 12.2 11.0 12.2 11.0 11.7 11.7 12.0 12.0 11.7 11.7 11.0 12.0 12.2 12.2 12.2 12.2 12.2 12.2 12.2
13.0 14.0 14.0 14.5 14.5 14.5 14.5 13.0 14.5 14.0 13.0 14.5 14.5 14.5 13.0 14.5 13.0 14.0 14.0 14.5 14.0 14.0 14.0 13.0 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5
24ABB3
AHRI COMBINATION RATINGS*
24ABB3
AHRI COMBINATION RATINGS* CONTINUED ARI Ref. No. 3250408 3250376 3250374 3250380 3250381 3250377 3250385 3250383 3250389 3250386 3250432 3250433 3250435 3250436 3250440 3250427 3250428 3250429 3250426 3250425 3250448 3250451 3250454 3250455 3250456 3250443 3250444 3250445 3250446 3250447 3250442 3250453 3250441 3250462 3250464 3457533 3250466 3404579 3250459
Model Number 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31 24ABB324(A,W)31
Indoor Model CNPH*3017A**+TDR CNPV*2414A** CNPV*2414A**+TDR CNPV*2417A** CNPV*2417A** CNPV*2417A**+TDR CNPV*3014A** CNPV*3014A**+TDR CNPV*3017A** CNPV*3017A**+TDR CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A** CSPH*2412A**+TDR CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A**+TDR FE4AN(B,F)003+UI FF1ENP030 FF1ENP031 FV4BN(B,F)003 FV4CNF002 FX4CNF024
3250469 3250482 3250485 3250487 3250489 3250490 3250486 3250483 3250492 3250491 3250495 3250498 3250499 3250500 3250494 3250496 3250493 3250503 3250501 3414654 3414655 3250567 3250539 3250541 3250545 3250546 3250547 3250548 3250534 3250537 3250543 3250531 3250556
24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31
†CAP**3014A**+TDR CAP**3014A** CAP**3017A** CAP**3017A** CAP**3017A** CAP**3017A** CAP**3017A** CAP**3017A**+TDR CAP**3614A** CAP**3614A**+TDR CAP**3617A** CAP**3617A** CAP**3617A** CAP**3617A** CAP**3617A** CAP**3617A** CAP**3617A**+TDR CAP**3621A** CAP**3621A**+TDR CAP**4221A**+TDR CAP**4224A**+TDR CNPF*3618A**+TDR CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A** CNPH*3017A**+TDR CNPH*3617A**
Furnace Model 58PH*045---08 58MEB040---12 58MEB060---12 58PH*045---08 58MEB040---12 58CV(A,X)070---12 58CV(A,X)090---16 58CV(A,X)135---22 58CV(A,X)155---22 58MEB080---12 58MV(B,C)060---14 58MV(B,C)080---14 58MV(B,C)080---20 58MVB040---14 58CV(A,X)070---12 58CV(A,X)135---22 58MEB040---12 58MEB060---12 58MEB080---12 58MV(B,C)060---14 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)100---20 58MV(B,C)120---20 58MVB040---14 58PH*045---08
58CV(A,X)070---12 58CV(A,X)090---16 58MEB040---12 58MEB080---12 58MEB080---16 58PH*070---16 58CV(A,X)070---12 58CV(A,X)090---16 58MEB060---12 58MEB080---12 58MEB080---16 58MV(B,C)060---14 58PH*070---16 58MV(B,C)080---20
58CV(A,X)090---16 58CV(A,X)135---22 58MEB040---12 58MEB060---12 58MEB080---12 58MEB080---16 58MV(B,C)080---14 58MV(B,C)120---20 58PH*070---16 58CV(A,X)070---12
See notes on page 21
14
Capacity 23,200 23,000 23,000 23,200 23,200 23,000 23,200 23,200 23,600 23,200 23,000 23,200 23,200 23,200 23,400 23,400 23,000 23,000 23,200 23,000 23,000 23,200 23,600 23,800 23,600 23,600 23,200 23,000 23,200 23,400 23,200 23,400 23,200 23,400 23,000 23,200 23,400 22,600 23,200
EERA 11.0 11.7 11.0 12.0 12.0 11.0 12.0 11.0 12.2 11.0 12.0 12.0 12.0 12.0 12.2 12.0 12.0 12.0 12.0 11.0 12.0 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.2 12.0 11.0 12.2 10.9 11.7 12.2 12.0 11.7
SEER 13.0 14.0 13.0 14.5 14.5 13.0 14.0 13.0 14.5 13.0 14.0 14.0 14.0 14.0 14.5 14.0 14.0 14.0 14.0 13.0 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.5 14.0 13.0 14.5 13.0 14.0 14.5 14.0 14.0
27,400 27,200 27,400 27,600 27,600 27,800 27,400 27,400 27,400 27,400 27,400 27,600 27,600 28,000 27,600 27,600 27,600 27,400 27,600 27,600 27,600 27,400 27,400 27,400 27,600 27,800 27,600 27,800 27,200 27,400 27,400 27,400 27,400
10.8 11.7 12.0 12.0 12.0 11.7 11.7 10.8 11.7 10.8 12.0 12.0 12.0 11.7 12.0 11.7 10.8 12.0 10.8 11.0 11.0 10.8 11.7 12.0 12.0 11.7 12.0 11.7 11.7 12.0 11.5 10.8 11.7
13.0 14.0 14.0 14.5 14.0 14.0 14.0 13.0 14.0 13.0 14.5 14.5 14.5 14.0 14.0 14.0 13.0 14.0 13.0 13.0 13.0 13.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.0 14.0
ARI Ref. No. 3250558 3250559 3250564 3250566 3250551 3250552 3250555 3250549 3414658 3250508 3250507 3250513 3250515 3250516 3250510 3250509 3250519 3250521 3250522 3250523 3250524 3250518 3250520 3250517 3250529 3250527 3250528 3250530 3250525 3250481 3414656 3414657 3250480 3250575 3250576 3250577 3250578 3250579 3250583 3250584 3250585 3250571 3250572 3250574 3250569 3250581 3250568 3250594 3250595 3250596 3250600 3250601 3250603 3250588 3250589 3250590 3250591 3250587 3250586 3414659 3250474 3250476 3250478 3404583 3250472 3250471 3250470
Model Number 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31 24ABB330(A,W)31
Indoor Model CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A**+TDR CNPH*4221A**+TDR CNPV*3014A** CNPV*3014A**+TDR CNPV*3017A** CNPV*3017A** CNPV*3017A** CNPV*3017A** CNPV*3017A**+TDR CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A**+TDR CNPV*3621A** CNPV*3621A** CNPV*3621A** CNPV*3621A** CNPV*3621A**+TDR CNPV*4217A** CNPV*4217A**+TDR CNPV*4221A**+TDR CNPV*4821A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A** CSPH*3012A**+TDR CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A**+TDR CSPH*4212A**+TDR FE4AN(B,F)003+UI FF1ENP036 FV4BN(B,F)003 FV4CN(B,F)005 FX4CN(B,F)036 FX4CNF030 FY4ANF030
3490894 3490895 3490896 3490897 3490898
24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51
†CAP**3014A**+TDR CAP**3017A**+TDR CAP**3614A**+TDR CAP**3617A**+TDR CAP**3621A**+TDR
Furnace Model 58CV(A,X)110---20 58CV(A,X)135---22 58MEB060---12 58MEB080---16 58MV(B,C)060---14 58MV(B,C)080---14 58MV(B,C)120---20
58CV(A,X)070---12 58MEB040---12 58MEB080---12 58MEB080---16 58MV(B,C)060---14 58CV(A,X)090---16 58MEB040---12 58MEB060---12 58MEB080---12 58MEB080---16 58MV(B,C)060---14 58PH*070---16 58CV(A,X)110---20 58MV(B,C)080---20 58MV(B,C)100---20 58PH*090---16 58CV(A,X)090---16
58PH*090---16 58CV(A,X)070---12 58CV(A,X)090---16 58CV(A,X)110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB060---12 58MEB080---12 58MEB080---16 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)120---20 58MVB040---14 58PH*090---16 58CV(A,X)090---16 58CV(A,X)110---20 58CV(A,X)135---22 58MEB040---12 58MEB060---12 58MEB080---16 58MV(B,C)060---14 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)100---20 58MVB040---14
See notes on page 21
15
Capacity 27,400 27,400 27,200 27,800 27,600 27,200 27,400 27,400 27,600 27,200 27,400 27,600 27,600 27,800 27,600 27,400 27,400 27,200 27,200 27,000 27,800 27,600 27,400 27,400 27,400 27,400 27,200 27,600 27,400 27,800 27,600 27,600 28,400 27,200 27,400 27,600 27,600 27,600 27,800 27,600 27,800 27,400 27,400 27,600 27,400 27,600 27,400 27,800 27,800 27,800 27,400 27,400 27,800 28,000 27,800 27,800 27,600 27,800 27,400 27,600 27,600 27,400 27,600 28,400 27,800 27,600 27,000
EERA 11.7 12.0 12.0 11.7 11.7 11.7 12.0 10.8 11.0 11.7 10.8 12.0 12.0 11.7 11.7 10.8 11.7 12.0 12.0 12.0 11.7 11.7 11.5 10.8 11.7 11.7 11.7 11.7 10.8 12.2 11.0 11.0 12.2 11.7 11.7 11.7 11.7 12.0 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 10.8 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 10.8 11.0 12.2 10.9 12.2 12.2 11.5 11.7 10.9
SEER 14.0 14.0 14.5 14.0 14.0 14.0 14.0 13.0 13.0 14.0 13.0 14.0 14.0 14.0 14.0 13.0 14.0 14.5 14.5 14.5 14.0 14.0 14.0 13.0 14.0 14.0 14.0 14.0 13.0 14.5 13.0 13.0 14.5 13.5 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.5 14.0 13.0 14.5 14.0 14.0 14.5 14.5 14.0 14.0 14.0 14.0 14.0 14.0 13.0 13.0 14.5 13.0 14.5 14.5 13.5 14.0 13.0
27,400 27,400 27,400 27,600 27,600
10.8 10.8 10.8 10.8 10.8
13.0 13.0 13.0 13.0 13.0
24ABB3
AHRI COMBINATION RATINGS* CONTINUED
24ABB3
AHRI COMBINATION RATINGS* CONTINUED ARI Ref. No. 3490908 3490909 3490905 3490903 3490904 3490912 3490899 3490900 3490901 3490902 3490910 3490911 3490906 3490907 3490913
Model Number 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51 24ABB330A51
Indoor Model CAP**4221A**+TDR CAP**4224A**+TDR CNPF*3618A**+TDR CNPH*3017A**+TDR CNPH*3617A**+TDR CNPH*4221A**+TDR CNPV*3014A**+TDR CNPV*3017A**+TDR CNPV*3617A**+TDR CNPV*3621A**+TDR CNPV*4217A**+TDR CNPV*4221A**+TDR CSPH*3012A**+TDR CSPH*3612A**+TDR CSPH*4212A**+TDR
3250190 3250234 3250352 3250353 3250354 3250355 3250330 3250242 3250191 3250240 3250331 3250238 3250244 3250245 3250246 3250334 3250243 3250251 3250252 3250249 3250248 3250329 3250290 3250275 3250276 3250277 3250208 3250211 3250269 3250270 3250271 3250340 3250341 3250266 3250286 3250287 3250288 3250289 3250212 3250213 3250214 3250215 3250280 3250284 3250279 3250343 3250344 3250345 3250278 3250228 3250193 3250194 3250195 3250196 3250254 3250335 3250253
24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31
†CAP**3617A**+TDR CAP**3614A**+TDR CAP**3617A** CAP**3617A** CAP**3617A** CAP**3617A** CAP**3617A** CAP**3621A** CAP**3621A** CAP**3621A** CAP**3621A** CAP**3621A**+TDR CAP**4221A** CAP**4221A** CAP**4221A** CAP**4221A** CAP**4221A**+TDR CAP**4224A** CAP**4224A** CAP**4224A** CAP**4224A**+TDR CAP**4817A** CNPF*3618A**+TDR CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A** CNPH*3617A**+TDR CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A**+TDR CNPH*4821A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A** CNPV*3617A**+TDR
Furnace Model
58MEB040---12 58MEB060---12 58MEB080---12 58MEB080---16 58PH*070---16 58CV(A,X)110---20 58MEB100---20 58MV(B,C)080---20 58PH*090---16 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)100---20 58PH*110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MVB040---14 58PH*070---16 58CV(A,X)110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB060---12 58MEB100---20 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)100---20 58PH*070---16 58PH*090---16 58CV(A,X)090---16 58CV(A,X)110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB040---12 58MEB060---12 58MEB080---12 58MEB080---16 58MV(B,C)060---14 58MV(B,C)120---20 58MVB040---14 58PH*070---16 58PH*090---16 58PH*110---20 58MEB060---12 58MEB040---12 58MEB060---12 58MEB080---12 58MEB080---16 58MV(B,C)060---14 58PH*070---16
See notes on page 21
16
Capacity 27,600 27,600 27,400 27,400 27,400 27,600 27,400 27,400 27,400 27,400 27,600 27,600 27,400 27,400 27,600
EERA 11.0 11.0 10.8 10.8 10.8 11.0 10.8 10.8 10.8 10.8 11.0 11.0 10.8 10.8 11.0
SEER 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
33,800 32,800 33,600 33,600 33,600 33,600 33,400 33,400 33,600 33,400 33,800 33,800 33,600 33,600 33,800 34,200 34,000 33,600 33,800 33,400 33,800 34,400 33,800 33,400 33,400 33,400 33,400 33,200 33,200 33,200 33,400 33,200 33,400 33,800 33,600 33,800 33,600 33,800 33,800 33,800 33,800 33,800 33,800 33,600 33,400 33,600 34,000 34,000 34,000 34,600 33,400 33,400 33,400 33,400 33,400 33,200 33,800
10.9 11.0 11.7 11.7 11.7 11.7 11.2 11.7 12.0 11.7 12.0 11.0 11.5 11.7 11.7 12.0 11.0 12.0 12.0 11.7 11.0 11.7 11.0 11.5 11.7 11.7 11.7 11.7 11.5 11.5 11.5 11.0 11.7 11.0 11.7 11.7 12.0 12.0 11.7 11.7 11.7 11.7 11.7 11.7 11.5 11.2 12.0 12.0 11.0 12.0 11.7 11.7 11.7 11.7 11.5 11.2 11.0
13.0 13.0 14.0 14.0 14.0 14.0 13.5 14.0 14.0 14.0 14.0 13.0 13.5 14.0 14.0 14.0 13.0 14.0 14.0 13.5 13.0 14.0 13.0 13.5 14.0 14.0 14.0 14.0 13.5 13.5 13.5 13.5 14.0 13.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.5 13.5 14.0 14.0 13.0 14.5 14.0 14.0 14.0 14.0 13.5 13.5 13.0
ARI Ref. No. 3250197 3250257 3250258 3250336 3250337 3250256 3250200 3250202 3250199 3250201 3250198 3250265 3250206 3250262 3250263 3250264 3250338 3250339 3250261 3250230 3250233 3250298 3250299 3250300 3250301 3250302 3250217 3250218 3250221 3250293 3250296 3250292 3250347 3250348 3250291 3250310 3250311 3250313 3250222 3250224 3250225 3250226 3250305 3250306 3250307 3250308 3250349 3250351 3250303 3250320 3250321 3250322 3250319 3250324 3250326 3250327 3250328 3250325 3404577 3250317 3250318 3250316
Model Number 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31 24ABB336(A,W)31
Indoor Model CNPV*3621A** CNPV*3621A** CNPV*3621A** CNPV*3621A** CNPV*3621A** CNPV*3621A**+TDR CNPV*4217A** CNPV*4217A** CNPV*4217A** CNPV*4217A** CNPV*4217A**+TDR CNPV*4221A** CNPV*4221A** CNPV*4221A** CNPV*4221A** CNPV*4221A** CNPV*4221A** CNPV*4221A** CNPV*4221A**+TDR CNPV*4821A** CNPV*4821A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A** CSPH*3612A**+TDR CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A**+TDR FE4AN(B,F)003+UI FE4AN(B,F)005+UI FE4ANB006+UI FE4ANF002+UI FF1ENP036 FV4BN(B,F)003 FV4BN(B,F)005 FV4BNB006 FV4BNF002 FV4CN(B,F)005 FX4CN(B,F)036 FX4CN(B,F)042 FY4ANF042
3491901 3491903 3491904 3491905 3491906 3491912 3491910 3491911 3491907 3491908
24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11
†CAP**3617A**+TDR CAP**3614A**+TDR CAP**3621A**+TDR CAP**4221A**+TDR CAP**4224A**+TDR CNPF*3618A**+TDR CNPH*3617A**+TDR CNPH*4221A**+TDR CNPV*3617A**+TDR CNPV*3621A**+TDR
Furnace Model 58MEB100---20 58MV(B,C)080---14 58MV(B,C)080---20 58PH*090---16 58PH*110---20 58CV(A,X)090---16 58MEB040---12 58MV(B,C)060---14 58PH*070---16 58CV(A,X)110---20 58MEB100---20 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)100---20 58PH*090---16 58PH*110---20 58MEB100---20 58PH*110---20 58CV(A,X)070---12 58CV(A,X)090---16 58CV(A,X)110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB040---12 58MEB060---12 58MEB100---20 58MV(B,C)060---14 58MV(B,C)100---20 58MVB040---14 58PH*090---16 58PH*110---20 58CV(A,X)070---12 58CV(A,X)090---16 58CV(A,X)135---22 58MEB040---12 58MEB080---12 58MEB080---16 58MEB100---20 58MV(B,C)060---14 58MV(B,C)080---14 58MV(B,C)080---20 58MV(B,C)100---20 58PH*070---16 58PH*110---20
See notes on page 21
17
Capacity 33,400 33,200 33,200 33,400 33,600 33,800 33,800 33,800 33,800 33,800 33,800 33,800 33,800 33,600 33,600 33,800 34,000 34,000 34,000 34,400 34,800 33,600 33,600 33,600 33,600 33,600 33,800 33,800 33,800 33,600 33,400 33,600 34,400 34,400 33,800 33,600 33,600 33,600 33,800 33,800 33,800 33,800 33,800 33,600 33,600 33,800 34,400 34,800 34,000 33,600 34,800 35,200 33,400 33,600 33,600 34,800 35,200 33,400 34,800 34,000 34,800 34,200
EERA 11.7 11.5 11.5 11.7 11.7 11.0 11.7 11.7 11.7 11.7 11.0 11.7 11.7 11.5 11.7 11.7 12.0 12.0 11.0 12.2 12.2 11.7 12.0 12.0 12.0 12.0 11.7 11.7 11.7 12.0 12.0 11.5 12.0 12.0 11.0 11.7 12.0 12.0 11.7 11.7 11.7 11.7 12.0 11.7 12.0 12.0 11.7 12.0 11.0 12.0 12.0 12.0 11.5 10.9 12.0 12.0 12.0 11.5 12.0 11.7 11.7 11.0
SEER 14.0 13.5 13.5 14.0 14.0 13.0 14.0 14.0 14.0 14.0 13.0 14.0 14.0 13.5 14.0 14.0 14.0 14.0 13.0 14.5 14.5 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.5 14.0 14.0 13.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.0 14.0 14.0 14.0 13.5 13.0 14.0 14.0 14.0 13.5 14.0 14.0 14.0 13.0
33,800 32,800 33,800 34,000 33,800 33,800 33,800 34,000 33,800 33,800
10.9 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
24ABB3
AHRI COMBINATION RATINGS* CONTINUED
24ABB3
AHRI COMBINATION RATINGS* CONTINUED ARI Ref. No. 3491902 3491909 3491913 3491914
Model Number 24ABB336A11 24ABB336A11 24ABB336A11 24ABB336A11
Indoor Model CNPV*4217A**+TDR CNPV*4221A**+TDR CSPH*3612A**+TDR CSPH*4212A**+TDR
3491040 3491042 3491043 3491044 3491045 3491051 3491049 3491050 3491046 3491047 3491041 3491048 3491052 3491053
24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51 24ABB336A51
3491470 3491472 3491473 3491474 3491475 3491481 3491479 3491480 3491476 3491477 3491471 3491478 3491482 3491483 3249936 3249965 3249937 3250011 3249966 3249939 3250009 3250014 3249967 3249969 3250013 3250012 3250017 3249942 3250015 3249943 3250018 3250036 3249983 3249985 3249987 3249988 3250031 3250030 3249990 3249991 3249993 3249994 3250034 3249954 3249956 3250033 3249978 3249975 3249972 3250023 3250022 3249944
Furnace Model
Capacity 33,800 34,000 33,800 34,000
EERA 11.0 11.0 11.0 11.0
SEER 13.0 13.0 13.0 13.0
†CAP**3617A**+TDR CAP**3614A**+TDR CAP**3621A**+TDR CAP**4221A**+TDR CAP**4224A**+TDR CNPF*3618A**+TDR CNPH*3617A**+TDR CNPH*4221A**+TDR CNPV*3617A**+TDR CNPV*3621A**+TDR CNPV*4217A**+TDR CNPV*4221A**+TDR CSPH*3612A**+TDR CSPH*4212A**+TDR
33,800 32,800 33,800 34,000 33,800 33,800 33,800 34,000 33,800 33,800 33,800 34,000 33,800 34,000
10.9 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61 24ABB336A61
†CAP**3617A**+TDR CAP**3614A**+TDR CAP**3621A**+TDR CAP**4221A**+TDR CAP**4224A**+TDR CNPF*3618A**+TDR CNPH*3617A**+TDR CNPH*4221A**+TDR CNPV*3617A**+TDR CNPV*3621A**+TDR CNPV*4217A**+TDR CNPV*4221A**+TDR CSPH*3612A**+TDR CSPH*4212A**+TDR
33,800 32,800 33,800 34,000 33,800 33,800 33,800 34,000 33,800 33,800 33,800 34,000 33,800 34,000
10.9 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30
†CAP**4221A**+TDR CAP**4221A** CAP**4221A** CAP**4224A** CAP**4224A** CAP**4224A** CAP**4224A**+TDR CAP**4817A** CAP**4817A** CAP**4817A** CAP**4817A** CAP**4817A**+TDR CAP**4821A** CAP**4821A** CAP**4821A**+TDR CAP**4824A** CAP**4824A**+TDR CNPF*4818A**+TDR CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A** CNPH*4221A**+TDR CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A**+TDR CNPV*4217A** CNPV*4217A** CNPV*4217A**+TDR CNPV*4221A** CNPV*4221A** CNPV*4221A**
41,000 40,500 40,500 40,500 40,500 40,500 41,000 40,000 41,000 41,000 40,000 40,500 41,000 41,000 41,500 41,000 41,500 41,500 40,500 40,500 40,500 40,500 40,000 41,000 41,000 41,000 41,000 41,000 40,500 41,000 41,000 41,500 41,000 40,500 41,000 40,500 40,000 40,500
11.0 11.7 11.7 11.5 12.0 12.0 11.0 11.5 11.7 11.7 11.5 11.0 11.5 12.0 11.0 12.0 11.0 11.0 11.7 11.7 11.7 11.7 11.2 11.0 11.7 11.7 12.0 12.0 11.2 12.0 12.0 11.0 11.7 11.2 11.0 11.5 11.2 11.7
13.0 14.0 14.0 14.0 14.0 14.0 13.0 14.0 14.0 14.0 14.0 13.2 14.0 14.0 13.2 14.0 13.2 13.2 14.0 14.0 14.0 14.0 13.5 13.0 14.0 14.0 14.0 14.0 13.5 14.0 14.0 13.2 14.0 13.5 13.0 14.0 13.5 14.0
58MEB100---20 58PH*090---16 58CV(A,X)135---22 58MEB120---20 58PH*135---20 58CV(A,X)090---16 58MEB040---12 58MEB080---12 58MV(B,C)060---14 58CV(A,X)110---20 58PH*110---20 58PH*135---20
58MEB040---12 58MEB080---12 58MEB100---20 58MEB120---20 58MV(B,C)040---14 58MEB060---12 58MEB080---12 58MEB100---20 58MEB120---20 58MV(B,C)040---14 58PH*090---16 58PH*135---20 58MEB080---12 58PH*070---16 58CV(A,X)110---20 58MV(B,C)080---14 58PH*090---16
See notes on page 21
18
ARI Ref. No. 3250021 3250025 3249946 3250024 3250029 3249982 3250028 3249948 3250027 3249995 3249996 3249998 3249999 3250000 3249957 3249958 3249959 3250037 3250001 3250002 3250003 3250004 3250005 3250006 3250041 3249963 3249964 3250040 3250047 3250048 3250049 3250045 3250043
Model Number 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30 24ABB342(A,W)30
Indoor Model CNPV*4221A**+TDR CNPV*4821A** CNPV*4821A** CNPV*4821A**+TDR CNPV*4824A** CNPV*4824A** CNPV*4824A** CNPV*4824A** CNPV*4824A**+TDR CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A** CSPH*4212A**+TDR CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A**+TDR FV4BN(B,F)003 FV4BN(B,F)005 FV4BNB006 FX4CN(B,F)042 FY4ANF042
3491211 3491213 3491214 3491215 3491216 3491222 3491220 3491221 3491212 3491217 3491218 3491219 3491223 3491224
24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50 24ABB342A50
3491641 3491643 3491644 3491645 3491646 3491652 3491650 3491651 3491642 3491647 3491648 3491649 3491653 3491654 3250050 3250143 3250051 3250055 3250053 3250054 3250056 3250057 3250060
Furnace Model
Capacity 41,000 40,500 41,000 41,500 41,000 41,000 41,000 41,000 41,500 41,000 41,000 41,000 41,000 41,000 40,500 40,500 40,500 41,000 41,000 41,000 41,000 41,000 41,000 41,000 41,000 41,000 41,000 41,500 40,500 41,500 42,500 41,500 41,000
EERA 11.0 11.2 12.0 11.0 11.7 12.0 11.2 12.0 11.0 11.7 11.7 11.7 12.0 12.0 11.5 11.7 12.0 11.0 11.7 11.7 11.7 11.7 12.0 12.0 11.2 12.0 12.0 11.0 11.5 11.7 12.0 11.2 11.0
SEER 13.0 13.5 14.0 13.2 14.0 14.0 13.5 14.0 13.2 14.0 14.0 14.0 14.0 14.0 13.5 14.0 14.0 13.2 14.0 14.0 14.0 14.0 14.0 14.0 13.5 14.0 14.0 13.2 14.0 14.0 14.0 13.5 13.0
†CAP**4221A**+TDR CAP**4224A**+TDR CAP**4817A**+TDR CAP**4821A**+TDR CAP**4824A**+TDR CNPF*4818A**+TDR CNPH*4221A**+TDR CNPH*4821A**+TDR CNPV*4217A**+TDR CNPV*4221A**+TDR CNPV*4821A**+TDR CNPV*4824A**+TDR CSPH*4212A**+TDR CSPH*4812A**+TDR
41,000 41,000 40,500 41,500 41,500 41,500 41,000 41,500 41,000 41,000 41,500 41,500 41,000 41,500
11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.2 13.2 13.2 13.2 13.0 13.2 13.0 13.0 13.2 13.2 13.2 13.2
24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60 24ABB342A60
†CAP**4221A**+TDR CAP**4224A**+TDR CAP**4817A**+TDR CAP**4821A**+TDR CAP**4824A**+TDR CNPF*4818A**+TDR CNPH*4221A**+TDR CNPH*4821A**+TDR CNPV*4217A**+TDR CNPV*4221A**+TDR CNPV*4821A**+TDR CNPV*4824A**+TDR CSPH*4212A**+TDR CSPH*4812A**+TDR
41,000 41,000 40,500 41,500 41,500 41,500 41,000 41,500 41,000 41,000 41,500 41,500 41,000 41,500
11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.2 13.2 13.2 13.2 13.0 13.2 13.0 13.0 13.2 13.2 13.2 13.2
24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31
†CAP**4821A**+TDR CAP**4817A** CAP**4817A**+TDR CAP**4821A** CAP**4821A** CAP**4821A** CAP**4821A** CAP**4821A** CAP**4824A**
46,000 45,000 45,000 45,000 44,500 45,000 45,000 45,000 45,000
11.0 11.0 11.0 11.7 11.5 11.2 11.7 11.7 11.7
13.2 13.5 13.2 13.5 13.5 13.5 13.5 14.0 14.0
58MV(B,C)080---14 58PH*090---16 58CV(A,X)135---22 58MEB120---20 58MV(B,C)040---14 58PH*135---20 58MEB040---12 58MEB060---12 58MEB080---16 58MEB100---20 58MEB120---20 58PH*070---16 58PH*090---16 58PH*110---20 58MEB040---12 58MEB060---12 58MEB080---12 58MEB080---16 58MEB100---20 58MEB120---20 58MV(B,C)040---14 58PH*110---20 58PH*135---20
58MEB080---16 58CV(A,X)110---20 58MV(B,C)080---20 58MV(B,C)100---20 58PH*090---16 58PH*110---20 58CV(A,X)135---22
See notes on page 21
19
24ABB3
AHRI COMBINATION RATINGS* CONTINUED
24ABB3
AHRI COMBINATION RATINGS* CONTINUED ARI Ref. No. 3250061 3250059 3250062 3250058 3250066 3250146 3250065 3250068 3250063 3250071 3250072 3250147 3250073 3250069 3250112 3250094 3250095 3250097 3250152 3250153 3250092 3250098 3250099 3250100 3250090 3250105 3250106 3250107 3250108 3250154 3250103 3250109 3250110 3250111 3250101 3250075 3250076 3250079 3250074 3250149 3250081 3250080 3250087 3250088 3250086 3250085 3250118 3250119 3250120 3250158 3250159 3250114 3250115 3250116 3250122 3250113 3250128 3250131 3250162 3250125 3250126 3250132 3250133 3250124 3250142 3250137 3250136 3250135
Model Number 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31 24ABB348(A,W)31
Indoor Model CAP**4824A** CAP**4824A** CAP**4824A** CAP**4824A**+TDR CAP**6021A** CAP**6021A** CAP**6021A** CAP**6021A** CAP**6021A**+TDR CAP**6024A** CAP**6024A** CAP**6024A** CAP**6024A** CAP**6024A**+TDR CNPF*4818A**+TDR CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A** CNPH*4821A**+TDR CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A**+TDR CNPV*4821A** CNPV*4821A** CNPV*4821A** CNPV*4821A**+TDR CNPV*4824A** CNPV*4824A** CNPV*4824A**+TDR CNPV*6024A** CNPV*6024A** CNPV*6024A** CNPV*6024A**+TDR CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A** CSPH*4812A**+TDR CSPH*6012A** CSPH*6012A** CSPH*6012A** CSPH*6012A** CSPH*6012A** CSPH*6012A** CSPH*6012A** CSPH*6012A**+TDR FV4BNB006 FX4CN(B,F)048 FY4ANB060 FY4ANF048
3492073 3492074 3492075 3492076 3492077 3492083 3492081 3492082
24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11
†CAP**4821A**+TDR CAP**4817A**+TDR CAP**4824A**+TDR CAP**6021A**+TDR CAP**6024A**+TDR CNPF*4818A**+TDR CNPH*4821A**+TDR CNPH*6024A**+TDR
Furnace Model 58CV(A,X)155---22 58MV(B,C)120---20 58PH*135---20 58CV(A,X)110---20 58MEB100---20 58MV(B,C)100---20 58PH*110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB120---20 58PH*135---20 58CV(A,X)090---16 58CV(A,X)110---20 58CV(A,X)155---22 58MEB100---20 58MEB120---20 58MV(B,C)100---20 58PH*090---16 58PH*110---20 58PH*135---20 58CV(A,X)090---16 58CV(A,X)110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB080---16 58MV(B,C)100---20 58PH*090---16 58PH*110---20 58PH*135---20 58MV(B,C)080---20 58MV(B,C)100---20 58PH*110---20 58MEB120---20 58MV(B,C)120---20 58CV(A,X)135---22 58CV(A,X)155---22 58MV(B,C)120---20 58CV(A,X)110---20 58CV(A,X)135---22 58CV(A,X)155---22 58MEB100---20 58MEB120---20 58MV(B,C)080---20 58MV(B,C)100---20 58MV(B,C)120---20 58PH*110---20 58CV(A,X)090---16 58CV(A,X)155---22 58MEB120---20 58MV(B,C)080---20 58MV(B,C)100---20 58PH*090---16 58PH*110---20
See notes on page 21
20
Capacity 45,000 45,000 45,500 45,500 46,000 45,000 46,000 46,000 46,000 46,000 46,000 45,000 46,000 46,500 45,000 45,000 45,000 45,500 45,000 45,000 45,000 45,000 45,000 45,500 45,500 46,000 46,000 46,000 46,000 45,000 46,000 46,000 46,000 46,000 46,500 44,500 45,000 45,000 45,500 45,000 45,000 45,500 46,000 46,000 46,000 46,500 45,000 45,000 45,000 45,000 45,000 44,500 45,000 45,000 45,000 46,000 46,000 46,000 45,000 45,500 46,000 46,000 46,000 46,500 46,500 46,000 46,500 45,500
EERA 12.0 11.5 11.7 11.0 12.0 12.0 11.7 12.0 11.2 12.0 12.2 12.0 12.0 11.2 11.0 11.7 11.7 12.0 11.7 11.7 11.2 11.7 11.7 11.7 11.0 11.7 12.0 12.0 12.2 11.5 11.7 11.7 12.0 12.0 11.2 11.5 11.2 11.7 11.0 11.7 11.5 11.0 12.0 12.2 11.7 11.2 11.7 11.7 12.0 11.7 11.7 11.5 11.2 11.5 11.7 11.0 12.0 12.2 12.0 11.7 11.7 12.0 12.0 11.2 12.2 12.0 11.2 11.2
SEER 14.0 13.5 13.5 13.2 14.0 14.0 13.5 14.0 13.2 14.0 14.5 14.0 14.0 13.2 13.2 13.5 13.5 14.0 14.0 14.0 13.5 13.5 14.0 13.5 13.2 14.0 14.0 14.0 14.5 13.5 13.5 14.0 14.0 14.0 13.2 13.5 13.5 14.0 13.2 14.0 13.5 13.2 14.0 14.5 14.0 13.2 13.5 14.0 14.0 14.0 14.0 13.5 13.5 13.5 14.0 13.2 14.0 14.5 14.0 13.5 13.5 14.0 14.0 13.2 14.5 14.0 13.2 13.2
46,000 45,000 45,500 46,000 46,500 45,000 45,500 46,500
11.0 11.0 11.0 11.2 11.2 11.0 11.0 11.2
13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2
ARI Ref. No. 3492078 3492079 3492080 3492084 3492085
Model Number 24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11 24ABB348A11
Indoor Model CNPV*4821A**+TDR CNPV*4824A**+TDR CNPV*6024A**+TDR CSPH*4812A**+TDR CSPH*6012A**+TDR
3491328 3491329 3491330 3491331 3491332 3491338 3491336 3491337 3491333 3491334 3491335 3491339 3491340
24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51 24ABB348A51
3491758 3491759 3491760 3491761 3491762 3491768 3491766 3491767 3491763 3491764 3491765 3491769 3491770
Capacity 45,500 45,500 46,500 46,000 46,500
EERA 11.0 11.0 11.2 11.0 11.2
SEER 13.2 13.2 13.2 13.2 13.2
†CAP**4821A**+TDR CAP**4817A**+TDR CAP**4824A**+TDR CAP**6021A**+TDR CAP**6024A**+TDR CNPF*4818A**+TDR CNPH*4821A**+TDR CNPH*6024A**+TDR CNPV*4821A**+TDR CNPV*4824A**+TDR CNPV*6024A**+TDR CSPH*4812A**+TDR CSPH*6012A**+TDR
46,000 45,000 45,500 46,000 46,500 45,000 45,500 46,500 45,500 45,500 46,500 46,000 46,500
11.0 11.0 11.0 11.2 11.2 11.0 11.0 11.2 11.0 11.0 11.2 11.0 11.2
13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2
24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61 24ABB348A61
†CAP**4821A**+TDR CAP**4817A**+TDR CAP**4824A**+TDR CAP**6021A**+TDR CAP**6024A**+TDR CNPF*4818A**+TDR CNPH*4821A**+TDR CNPH*6024A**+TDR CNPV*4821A**+TDR CNPV*4824A**+TDR CNPV*6024A**+TDR CSPH*4812A**+TDR CSPH*6012A**+TDR
46,000 45,000 45,500 46,000 46,500 45,000 45,500 46,500 45,500 45,500 46,500 46,000 46,500
11.0 11.0 11.0 11.2 11.2 11.0 11.0 11.2 11.0 11.0 11.2 11.0 11.2
13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2
3285396 3285405 3285404 3285407 3285398 3285400 3285401 3285414 3285411 3285409 3285410 3285408 3285417 3285403 3285418 3285415 3285422 3404614
24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32 24ABB360(A,W)32
†CAP**6024A**+TDR CAP**6021A** CAP**6021A**+TDR CAP**6024A** CAP**6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A** CNPH*6024A**+TDR CNPV*6024A** CNPV*6024A** CNPV*6024A**+TDR CSPH*6012A** CSPH*6012A** CSPH*6012A** CSPH*6012A**+TDR FV4BNB006 FV4CNB006
57,500 56,500 56,500 57,000 56,500 56,500 56,500 56,500 57,000 56,500 57,000 57,000 56,500 56,500 56,500 57,500 57,500 57,500
11.0 11.2 11.0 11.2 11.0 11.0 11.0 11.2 11.0 11.2 11.2 11.0 11.2 11.0 11.2 11.0 11.5 11.5
13.0 13.2 13.0 13.2 13.2 13.2 13.2 13.2 13.0 13.2 13.2 13.0 13.2 13.2 13.2 13.0 13.5 13.5
3492188 3492189 3492191 3492190 3492192
24ABB360A12 24ABB360A12 24ABB360A12 24ABB360A12 24ABB360A12
†CAP**6024A**+TDR CAP**6021A**+TDR CNPH*6024A**+TDR CNPV*6024A**+TDR CSPH*6012A**+TDR
57,500 56,500 57,000 57,000 57,500
11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.0 13.0 13.0
3491443 3491444 3491446 3491445 3491447
24ABB360A52 24ABB360A52 24ABB360A52 24ABB360A52 24ABB360A52
†CAP**6024A**+TDR CAP**6021A**+TDR CNPH*6024A**+TDR CNPV*6024A**+TDR CSPH*6012A**+TDR
57,500 56,500 57,000 57,000 57,500
11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.0 13.0 13.0
3491874 3491875 3491877 3491876 3491878
24ABB360A62 24ABB360A62 24ABB360A62 24ABB360A62 24ABB360A62
†CAP**6024A**+TDR CAP**6021A**+TDR CNPH*6024A**+TDR CNPV*6024A**+TDR CSPH*6012A**+TDR
57,500 56,500 57,000 57,000 57,500
11.0 11.0 11.0 11.0 11.0
13.0 13.0 13.0 13.0 13.0
* AHRI = Air Conditioning, Heating & Refrigeration Institute { Tested combination EERA — Energy Efficiency Ratio --- ’A’ conditions --- 80_F (26.6_C) indoor db/67_F (19.4_C) indoor wb & 95_F (35_C) outdoor wb. SEER — Seasonal Energy Efficiency Ratio TDR — Time---Delay Relay. In most cases, only one method should be used to achieve TDR function. Using more than one method in a system may cause degradation in performance. Use either the accessory Time---Delay Relay, KAATD0101TDR, or a furnace equipped with TDR. Most Carrier furnaces are equipped with TDR. UI — User Interface
Furnace Model
58PH*110---20 58CV(A,X)155---22 58MEB120---20 58MEB100---20 58MEB120---20 58PH*110---20 58CV(A,X)135---22 58CV(A,X)155---22 58CV(A,X)155---22 58MEB120---20 58PH*110---20
NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included. 2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computer simulation procedures. 3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature. 4. Do not apply with capillary tube coils as performance and reliability are significantly affected.
21
24ABB3
AHRI COMBINATION RATINGS* CONTINUED
22
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
COOLING INDOOR MODEL *CAP**1814A** CAP**2414A** CAP**2417A** CNPF*2418A** CNPH*2417A** CNPV*1814A** CNPV*2414A** CNPV*2417A** CSPH*2412A** FE4ANF002 FF1ENP018 FF1ENP024 FV4BNF002 FX4CNF018 FX4CNF024 FY4ANF018 FY4ANF024 CAP**1814A** CAP**2414A** CNPH*2417A** CNPV*1814A** CNPV*2414A** CSPH*2412A** CAP**2417A** CNPH*2417A** CNPV*2417A** CSPH*2412A** CAP**2417A** CNPH*2417A** CNPV*2417A** CSPH*2412A** CAP**2417A** CNPH*2417A** CNPV*2417A** CSPH*2412A** CAP**2417A** CNPH*2417A**
675
600
525
CFM
EWB ° F (° C)
EVAPORATOR AIR
POWER
1.00 1.01 1.01 1.01 1.01 1.00 1.01 1.01 1.01 0.88 0.99 0.99 0.88 0.93 0.91 1.01 1.02 0.90 0.90 0.90 0.90 0.90 0.91 0.90 0.90 0.90 0.91 0.89 0.91 0.91 0.91 0.89 0.91 0.91 0.91 0.90 0.90
1.00 1.02 1.02 1.02 1.02 1.00 1.02 1.02 1.02 0.98 0.99 0.99 0.98 1.02 1.02 1.01 1.02 0.99 1.01 1.01 0.99 1.01 1.02 1.01 1.01 1.01 1.02 1.02 1.02 1.02 1.02 1.02 1.02 1.02 1.02 1.01 1.01
10.51 12.93 12.55 15.32 17.00 11.01 13.74 13.32 16.44 17.70 11.48 14.52 14.06 18.11 18.26
Sens‡
CAPACITY
20.79 19.09 17.84 17.53 17.00 21.12 19.42 18.17 17.93 17.70 21.35 19.66 18.41 18.28 18.26
Total
Capacity MBtuh
75 (23.9)
19.89 18.24 17.02 16.74 16.36 20.19 18.54 17.32 17.12 17.02 20.39 18.76 17.55 17.55 17.55
Total
58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MV(B,C)060--- 14 58MV(B,C)060--- 14
COOLING INDOOR MODEL CNPV*2417A** CSPH*2412A** CNPH*2417A** CSPH*2412A** CNPH*2417A** CSPH*2412A** CAP**1814A** CAP**2414A** CNPH*2417A** CNPV*1814A** CNPV*2414A** CSPH*2412A** 1.01 1.02 1.01 1.02 1.01 1.01 1.01 1.02 1.01 1.01 1.02 1.02
CAPACITY 0.90 0.91 0.90 0.91 0.90 0.90 0.92 0.91 0.90 0.92 0.91 0.91
POWER 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MVB040--- 14 58MVB040--- 14 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08
FURNACE MODEL
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB318(A,W)31 Outdoor Section With CAP**1814A** Indoor Section 1.42 18.93 9.83 1.58 17.94 9.47 1.77 1.42 17.33 12.21 1.59 16.39 11.84 1.77 1.42 16.15 11.82 1.59 15.24 11.43 1.78 1.42 15.91 14.57 1.59 15.04 14.16 1.78 1.42 15.67 15.67 1.59 14.95 14.95 1.78 1.44 19.19 10.32 1.61 18.18 9.96 1.80 1.45 17.60 13.02 1.61 16.63 12.65 1.80 1.45 16.43 12.58 1.62 15.49 12.19 1.80 1.45 16.30 16.21 1.62 15.53 15.53 1.80 1.45 16.29 16.29 1.62 15.53 15.53 1.80 1.47 19.37 10.79 1.64 18.34 10.43 1.83 1.47 17.79 13.80 1.64 16.81 13.42 1.83 1.48 16.63 13.31 1.64 15.67 12.92 1.83 1.48 16.79 16.79 1.64 15.99 15.99 1.83 1.48 16.79 16.79 1.64 15.99 15.99 1.83
See notes on page 30
10.18 12.58 12.19 14.95 16.36 10.67 13.39 12.96 16.06 17.02 11.14 14.17 13.70 17.55 17.55
Sens‡
Capacity MBtuh
FURNACE MODEL
1.27 1.27 1.27 1.27 1.27 1.29 1.29 1.30 1.30 1.30 1.32 1.32 1.32 1.32 1.32
Total System KW**
85 (29.4)
DETAILED COOLING CAPACITIES#
24ABB3
115 (46.1)
16.87 15.37 14.26 14.17 14.18 17.07 15.59 14.48 14.71 14.71 17.20 15.74 14.64 15.13 15.13
Total 9.09 11.44 11.02 14.17 14.18 9.57 12.24 11.77 14.71 14.71 10.04 13.01 12.49 15.13 15.13
Sens‡
Capacity MBtuh
1.97 1.98 1.98 1.98 1.98 2.00 2.00 2.01 2.01 2.01 2.03 2.03 2.03 2.03 2.03
Total System KW**
125 (51.7)
15.67 14.26 13.22 13.33 13.33 15.84 14.44 13.40 13.81 13.81 15.94 14.58 13.54 14.18 14.18
Total
8.67 11.01 10.58 13.33 13.33 9.15 11.80 11.33 13.81 13.81 9.61 12.56 12.03 14.18 14.18
Sens‡
Capacity MBtuh
2.20 2.20 2.20 2.20 2.20 2.22 2.23 2.23 2.23 2.23 2.25 2.25 2.26 2.25 2.25
Total System KW**
23
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
COOLING INDOOR MODEL *CAP**2414A** CAP**2417A** CAP**3014A** CAP**3017A** CNPF*2418A** CNPH*2417A** CNPH*3017A** CNPV*2414A** CNPV*2417A** CNPV*3014A** CNPV*3017A** CSPH*2412A** CSPH*3012A** FE4AN(B,F)003 FE4ANF002 FF1ENP024 FF1ENP030 FV4BN(B,F)003 FV4BNF002 FX4CNF024 FX4CNF030 FY4ANF024 FY4ANF030 CAP**2414A** CAP**3014A** CNPH*2417A** CNPH*3017A** CNPV*2414A** CNPV*3014A** CSPH*2412A** CSPH*3012A** CAP**2417A** CAP**3017A** CNPH*2417A** CNPH*3017A** CNPV*2417A** CNPV*3017A** CSPH*2412A** CSPH*3012A**
900
800
700
CFM
EWB ° F (° C)
EVAPORATOR AIR
POWER
1.00 1.00 1.01 1.01 1.00 1.00 1.01 1.00 1.00 1.01 1.01 1.00 1.01 0.92 0.90 0.98 1.01 0.92 0.90 0.95 0.93 1.00 1.01 0.91 0.92 0.93 0.92 0.93 0.92 0.92 0.92 0.90 0.91 0.91 0.91 0.91 0.91 0.92 0.91
1.00 1.00 1.01 1.01 1.00 1.00 1.01 1.00 1.00 1.01 1.01 1.00 1.01 1.02 0.98 0.98 1.00 1.02 0.98 1.01 1.02 1.00 1.01 0.99 1.00 0.99 1.00 0.99 1.00 1.00 1.00 1.00 1.01 0.99 1.01 0.99 1.01 1.01 1.01
13.27 16.41 15.98 19.56 22.46 13.92 17.44 16.95 20.99 23.30 14.53 18.45 17.89 23.97 23.96
Sens‡
CAPACITY
27.09 24.89 23.39 23.01 22.46 27.52 25.25 23.76 23.47 23.30 27.79 25.51 24.03 23.97 23.96
Total
Capacity MBtuh
75 (23.9)
25.82 23.83 22.38 22.03 21.66 26.15 24.16 22.72 22.49 22.44 26.41 24.38 22.96 23.07 23.07
Total
58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16
12.82 15.99 15.55 19.14 21.66 13.46 17.03 16.53 20.52 22.44 14.07 18.03 17.47 23.07 23.07
Sens‡
Capacity MBtuh
FURNACE MODEL
1.65 1.65 1.64 1.64 1.64 1.69 1.68 1.68 1.68 1.68 1.73 1.72 1.72 1.72 1.72
Total System KW**
85 (29.4)
COOLING INDOOR MODEL CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CAP**2417A** CAP**3017A** CNPH*2417A** CNPH*3017A** CNPV*2417A** CNPV*3017A** CSPH*2412A** CSPH*3012A** CAP**2417A** CAP**3017A** CNPH*2417A** CNPH*3017A** CNPV*2417A** CNPV*3017A** CSPH*2412A** CSPH*3012A** CAP**2417A** CAP**3017A** CNPH*2417A** CNPH*3017A** CNPV*2417A** CNPV*3017A** CSPH*2412A** CSPH*3012A** CAP**2417A** CAP**3017A** CNPH*2417A** 0.99 1.01 1.01 1.01 0.99 1.01 1.01 1.01 0.99 1.01 1.01 1.01 1.02 1.03 1.01 1.03 1.01 1.03 1.02 1.03 1.02 1.03 1.01 1.03 1.01 1.03 1.02 1.03 1.01 1.03 1.01 1.03 1.01 1.03 1.02 1.03 1.01 1.02 1.01
CAPACITY 0.93 0.91 0.92 0.91 0.91 0.91 0.92 0.91 0.91 0.91 0.92 0.91 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.91 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.91 0.92 0.92
POWER 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14
FURNACE MODEL
115 (46.1)
11.54 14.66 14.17 18.91 18.91 12.16 15.69 15.14 19.54 19.54 12.76 16.66 16.05 20.03 20.04
24ABB3
2.56 2.56 2.56 2.56 2.56 2.59 2.59 2.59 2.59 2.59 2.63 2.63 2.63 2.63 2.63
Total System KW**
1.02 1.01 1.02 1.02 1.03 0.99 1.01 1.00 1.01 0.98 1.00 1.00 1.00 0.99 1.01 1.01 1.01 1.00 1.01 1.01 1.02 0.99 1.01 1.01 1.01 1.00 1.02 1.02 1.00 1.02 1.00 1.01 1.02 1.01 1.02
CAPACITY
Sens‡
See notes on page 30
22.08 20.30 18.98 18.91 18.91 22.29 20.53 19.22 19.54 19.54 22.42 20.68 19.39 20.03 20.04
Total
Capacity MBtuh
COOLING INDOOR MODEL CNPH*3017A** CNPV*2417A** CNPV*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CNPH*2417A** CNPH*3017A** CSPH*2412A** CSPH*3012A** CAP**2414A** CAP**3014A** CAP**3617A** CNPH*2417A** CNPH*3017A** CNPV*2414A** CNPV*3014A** CNPV*3617A** CSPH*2412A** CSPH*3012A**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB324(A,W)31 Outdoor Section With CAP**2414A** Indoor Section 1.85 24.63 12.41 2.06 23.42 12.00 2.30 1.84 22.71 15.56 2.05 21.55 15.13 2.29 1.84 21.29 15.11 2.05 20.18 14.66 2.29 1.84 20.99 18.67 2.05 19.94 18.19 2.29 1.83 20.79 20.79 2.05 19.89 19.89 2.29 1.88 24.91 13.04 2.10 23.67 12.62 2.33 1.88 23.00 16.60 2.09 21.82 16.16 2.33 1.87 21.60 16.08 2.09 20.46 15.63 2.33 1.87 21.52 21.52 2.09 20.58 20.58 2.33 1.87 21.53 21.53 2.09 20.58 20.58 2.33 1.92 25.10 13.63 2.13 23.83 13.21 2.37 1.91 23.21 17.59 2.13 22.00 17.15 2.37 1.91 21.82 17.01 2.12 20.66 16.55 2.36 1.91 22.11 22.11 2.12 21.12 21.12 2.36 1.91 22.11 22.11 2.12 21.12 21.12 2.36
DETAILED COOLING CAPACITIES# CONTINUED 125 (51.7)
0.92 0.92 0.92 0.93 0.93 0.91 0.91 0.92 0.91 0.90 0.90 0.92 0.90 0.91 0.91 0.92 0.91 0.92 0.91 0.92 0.92 0.93 0.91 0.92 0.91 0.94 0.93 0.92 0.94 0.93 0.94 0.92 0.92 0.92 0.93
POWER
20.57 18.89 17.65 17.82 17.82 20.73 19.09 17.86 18.38 18.38 20.83 19.22 18.01 18.82 18.82
Total
2.84 2.84 2.85 2.84 2.84 2.88 2.88 2.88 2.88 2.88 2.91 2.91 2.92 2.91 2.91
Total System KW**
58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MVB040--- 14 58MVB040--- 14 58MVB040--- 14 58MVB040--- 14 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08 58PH*045--- 08
FURNACE MODEL
11.04 14.14 13.64 17.82 17.82 11.65 15.16 14.60 18.38 18.38 12.24 16.12 15.49 18.82 18.82
Sens‡
Capacity MBtuh
24
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
COOLING INDOOR MODEL *CAP**3014A** CAP**3017A** CAP**3614A** CAP**3617A** CAP**3621A** CNPF*3618A** CNPH*3017A** CNPH*3617A** CNPV*3014A** CNPV*3017A** CNPV*3617A** CNPV*3621A** CSPH*3012A** CSPH*3612A** FE4AN(B,F)003 FE4AN(B,F)005 FE4ANF002 FF1ENP036 FV4BN(B,F)003 FV4BN(B,F)005 FV4BNF002 FX4CN(B,F)036 FX4CNF030 FY4ANF030 CAP**3014A** CAP**3614A** CNPH*3017A** CNPH*3617A** CNPV*3014A** CSPH*3012A** CSPH*3612A** CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CNPV*4217A** CSPH*3012A**
1125
1000
875
CFM
EWB ° F (° C)
EVAPORATOR AIR
POWER
1.00 1.00 1.00 1.01 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.89 0.92 0.93 0.99 0.89 0.92 0.90 0.95 0.93 0.98 0.92 0.92 0.92 0.92 0.92 0.92 0.91 0.90 0.90 0.92 0.92 0.92 0.92 0.90 0.92
1.00 1.00 1.00 1.01 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.01 1.04 1.01 1.00 1.01 1.04 0.98 1.01 1.01 0.99 0.99 1.00 0.99 1.00 0.99 0.99 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.01 1.00
16.57 20.70 20.13 24.80 27.10 17.38 22.03 21.38 27.82 28.04 18.14 23.30 22.57 28.79 28.79
Sens‡
CAPACITY
32.18 29.70 27.91 27.50 27.10 32.58 30.08 28.31 28.07 28.04 32.83 30.36 28.59 28.79 28.79
Total
Capacity MBtuh
75 (23.9)
30.84 28.44 26.69 26.34 26.12 31.18 28.79 27.06 27.00 27.01 31.40 29.03 27.32 27.71 27.71
Total
58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16
16.09 20.20 19.62 24.26 26.12 16.89 21.53 20.87 27.00 27.01 17.65 22.80 22.05 27.71 27.71
Sens‡
Capacity MBtuh
FURNACE MODEL
2.04 2.03 2.03 2.03 2.03 2.08 2.08 2.08 2.08 2.08 2.13 2.13 2.12 2.12 2.12
Total System KW**
85 (29.4)
COOLING INDOOR MODEL CSPH*3612A** CAP**3621A** CNPH*3017A** CNPH*3617A** CNPV*3621A** CSPH*3012A** CSPH*3612A** CNPH*3017A** CNPH*3617A** CSPH*3012A** CSPH*3612A** CNPH*3017A** CNPH*3617A** CSPH*3012A** CSPH*3612A** CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CSPH*3012A** CSPH*3612A** CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CSPH*3012A** CSPH*3612A** CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CSPH*3012A** CSPH*3612A** 1.01 1.01 1.00 1.00 1.00 1.01 1.01 1.00 1.00 1.01 1.01 1.00 1.00 1.01 1.01 1.01 1.01 1.01 0.99 1.01 0.99 1.01 1.00 1.01 1.01 1.01 0.99 1.01 0.99 1.01 1.00 1.01 1.01 1.01 0.99 1.01 0.99 1.01 1.00
CAPACITY 0.91 0.91 0.92 0.92 0.92 0.93 0.91 0.90 0.90 0.93 0.91 0.90 0.90 0.91 0.91 0.91 0.91 0.91 0.89 0.91 0.89 0.91 0.90 0.94 0.91 0.94 0.89 0.94 0.89 0.94 0.90 0.91 0.91 0.91 0.89 0.91 0.89 0.93 0.90
POWER 58CV(A,X)090--- 16 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12
FURNACE MODEL
115 (46.1)
26.28 24.11 22.52 22.71 22.71 26.50 24.36 22.78 23.42 23.42 26.63 24.54 22.98 23.98 23.98
Total 3.05 3.04 3.04 3.04 3.04 3.09 3.09 3.09 3.09 3.09 3.14 3.14 3.13 3.13 3.13
Total System KW**
1.01 1.02 1.01 1.01 1.01 1.01 1.01 1.01 1.00 1.01 1.01 1.01 1.01 1.01 1.01 1.02 1.00 0.99 0.99 0.99 1.00 1.01 1.00 1.00 1.00 1.00 1.00 1.01 0.99 0.99 0.99 0.99 0.99 1.01 1.00 1.00 1.01 1.02 1.00
CAPACITY
14.50 18.54 17.88 22.71 22.71 15.29 19.85 19.11 23.42 23.42 16.04 21.08 20.26 23.98 23.98
Sens‡
Capacity MBtuh
COOLING INDOOR MODEL CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CSPH*3012A** CSPH*3612A** CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CSPH*3012A** CSPH*3612A** CAP**3621A** CNPH*3017A** CNPH*3617A** CNPV*3621A** CSPH*3012A** CSPH*3612A** CAP**3621A** CNPH*3017A** CNPH*3617A** CNPV*3621A** CSPH*3012A** CSPH*3612A** CAP**3621A** CNPH*3017A** CNPH*3617A** CNPV*3621A** CSPH*3012A** CSPH*3612A** CNPH*3017A** CNPH*3617A** CSPH*3012A** CSPH*3612A** CNPH*3017A**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB330(A,W)31, 51 Outdoor Section With CAP**3014A** Indoor Section 2.25 29.42 15.59 2.49 27.93 15.07 2.76 2.25 27.08 19.68 2.49 25.67 19.13 2.75 2.25 25.39 19.07 2.49 24.02 18.50 2.75 2.25 25.11 23.67 2.49 23.94 23.94 2.75 2.25 25.05 25.05 2.49 23.94 23.94 2.75 2.30 29.72 16.38 2.54 28.19 15.86 2.81 2.30 27.40 21.00 2.54 25.96 20.45 2.80 2.30 25.72 20.31 2.53 24.32 19.74 2.80 2.29 25.89 25.89 2.53 24.72 24.72 2.80 2.29 25.89 25.89 2.53 24.72 24.72 2.80 2.35 29.91 17.14 2.59 28.35 16.62 2.85 2.34 27.62 22.26 2.58 26.15 21.70 2.85 2.34 25.95 21.49 2.58 24.53 20.90 2.85 2.34 26.54 26.54 2.58 25.33 25.33 2.85 2.34 26.55 26.55 2.58 25.33 25.33 2.85
DETAILED COOLING CAPACITIES# CONTINUED
24ABB3
POWER
24.43 22.39 20.88 21.35 21.35 24.59 22.60 21.11 21.98 21.98 24.68 22.76 21.29 22.47 22.47
Total
0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.91 0.92 0.91 0.93 0.93 0.93 0.93 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.91 0.90 0.92 0.92 0.92 0.92 0.91 0.92 0.92 0.92 0.92 0.92 0.91 0.90 0.90 0.93 0.92 0.92
125 (51.7)
3.36 3.35 3.35 3.35 3.35 3.40 3.40 3.40 3.40 3.40 3.45 3.45 3.44 3.44 3.44
Total System KW**
58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MVB040--- 14
FURNACE MODEL
13.86 17.88 17.21 21.35 21.35 14.65 19.17 18.42 21.98 21.98 15.40 20.38 19.53 22.47 22.47
Sens‡
Capacity MBtuh
25
See notes on page 30
COOLING INDOOR MODEL CNPH*3617A** CSPH*3012A** CSPH*3612A** CAP**3017A** CAP**3617A** CNPH*3017A** CNPH*3617A** CNPV*3017A** CNPV*3617A** CSPH*3012A** CSPH*3612A** CAP**3621A** CNPH*3017A** CNPH*3617A** CNPV*3621A** CNPV*4821A** CSPH*3012A** CSPH*3612A**
POWER
0.92 0.92 0.91 0.92 0.93 0.94 0.94 0.94 0.94 0.95 0.94 0.91 0.93 0.93 0.93 0.92 0.93 0.91
CAPACITY
1.00 1.00 1.01 1.00 1.01 1.00 1.00 1.00 1.00 1.01 1.01 1.01 1.01 1.01 1.01 1.04 1.01 1.01
58MVB040--- 14 58MVB040--- 14 58MVB040--- 14 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16
FURNACE MODEL
24ABB330(A,W)31, 51 Outdoor Section With CAP**3014A** Indoor Section
DETAILED COOLING CAPACITIES# CONTINUED
24ABB3
26
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
COOLING INDOOR MODEL *CAP**3617A** CAP**3614A** CAP**3621A** CAP**4221A** CAP**4224A** CNPF*3618A** CNPH*3617A** CNPH*4221A** CNPV*3617A** CNPV*3621A** CNPV*4217A** CNPV*4221A** CSPH*3612A** CSPH*4212A** FE4AN(B,F)003 FE4AN(B,F)005 FE4ANB006 FE4ANF002 FE5ANB004 FF1ENP036 FV4BN(B,F)003 FV4BN(B,F)005 FV4BNB006 FV4BNF002 FX4CN(B,F)036 FX4CN(B,F)042 FY4ANF036 FY4ANF042 CAP**3614A** CNPH*3617A** CNPH*4221A** CSPH*3612A** CSPH*4212A** CAP**3617A** CNPH*3617A** CNPH*4221A** CNPH*4821A** CNPV*3617A** CNPV*4217A**
1350
1200
1050
CFM
EWB ° F (° C)
EVAPORATOR AIR
POWER
1.00 0.97 1.00 1.01 1.00 1.00 1.00 1.01 1.00 1.00 0.99 1.01 0.99 1.00 0.90 0.94 0.95 0.94 0.94 0.99 0.90 0.94 0.95 0.94 0.94 0.96 0.98 1.00 0.91 0.93 0.94 0.93 0.93 0.92 0.93 0.93 0.90 0.93 0.93
1.00 0.97 1.00 1.01 1.00 1.00 1.00 1.01 1.00 1.00 1.00 1.01 1.00 1.01 0.99 1.03 1.04 0.99 1.04 0.99 0.99 1.03 1.04 0.99 1.01 1.03 0.98 1.01 0.96 0.98 0.99 0.99 0.99 0.99 0.98 0.99 1.01 0.98 1.00
21.00 25.73 24.88 30.44 32.55 21.97 27.30 26.36 32.60 33.87 22.89 28.79 27.77 34.90 34.96
Sens‡
CAPACITY
40.22 36.61 34.02 33.42 32.55 40.90 37.25 34.63 34.19 33.87 41.40 37.72 35.09 34.90 34.96
Total
Capacity MBtuh
75 (23.9)
38.50 35.00 32.50 31.97 31.38 39.11 35.57 33.04 32.73 32.61 39.55 36.00 33.47 33.63 33.64
Total
58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16
20.34 25.05 24.20 29.75 31.38 21.31 26.61 25.66 31.85 32.61 22.22 28.11 27.07 33.63 33.64
Sens‡
Capacity MBtuh
FURNACE MODEL
2.54 2.51 2.49 2.49 2.48 2.60 2.57 2.55 2.55 2.55 2.66 2.63 2.61 2.61 2.61
Total System KW**
85 (29.4)
COOLING INDOOR MODEL CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A** CNPH*4221A** CNPV*3621A** CNPV*4221A** CSPH*3612A** CSPH*4212A** CAP**4224A** CNPH*3617A** CNPH*4221A** CSPH*3612A** CSPH*4212A** CAP**4224A** CNPH*3617A** CNPH*4221A** CSPH*3612A** CSPH*4212A** CAP**3617A** CNPH*3617A** CNPH*4221A** CNPV*3617A** CNPV*4217A** CSPH*3612A** CSPH*4212A** CAP**3617A** CNPH*3617A** CNPH*4221A** CNPH*4821A** CNPV*3617A** CNPV*4217A** CSPH*3612A** CSPH*4212A** CAP**3617A** CNPH*3617A** CNPH*4221A** CNPH*4821A** 0.99 0.99 0.99 0.99 0.99 1.00 0.99 1.00 0.99 1.00 0.99 0.99 0.99 0.99 0.99 1.00 0.99 1.00 0.99 1.00 0.99 0.99 1.00 0.99 1.00 1.00 1.00 0.99 0.99 1.00 1.02 0.99 1.00 1.00 1.00 0.99 0.99 1.00 1.02
CAPACITY 0.90 0.90 0.92 0.90 0.94 0.93 0.94 0.93 0.90 0.91 0.90 0.92 0.90 0.90 0.90 0.91 0.92 0.91 0.90 0.91 0.93 0.92 0.93 0.92 0.93 0.93 0.93 0.93 0.92 0.93 0.93 0.92 0.93 0.93 0.93 0.93 0.92 0.93 0.91
POWER 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12
FURNACE MODEL
115 (46.1)
32.56 29.49 27.32 27.29 27.29 32.96 29.88 27.69 28.26 28.26 33.24 30.19 27.99 29.05 29.05
Total 3.76 3.74 3.73 3.73 3.73 3.82 3.80 3.79 3.79 3.79 3.88 3.86 3.85 3.85 3.85
Total System KW**
0.99 1.00 1.00 1.00 0.99 0.99 1.00 0.99 1.00 1.00 1.00 0.99 1.00 0.98 1.00 1.02 0.99 1.00 1.02 1.00 1.00 0.99 0.99 1.00 0.99 1.00 0.99 1.00 0.99 0.99 0.98 0.99 0.98 0.99 0.99 0.99 0.99 0.99 0.98
CAPACITY
18.15 22.81 21.94 27.29 27.29 19.09 24.35 23.37 28.26 28.26 19.97 25.81 24.73 29.05 29.05
Sens‡
Capacity MBtuh
COOLING INDOOR MODEL CNPV*3617A** CNPV*4217A** CSPH*3612A** CSPH*4212A** CAP**3617A** CNPH*3617A** CNPH*4221A** CNPV*3617A** CNPV*4217A** CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A** CNPH*4221A** CNPH*4821A** CNPV*3621A** CNPV*4221A** CNPV*4821A** CSPH*3612A** CSPH*4212A** CAP**3617A** CNPH*3617A** CNPH*4221A** CNPV*3617A** CNPV*4217A** CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A** CNPH*4221A** CNPV*3621A** CNPV*4221A** CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB330(A,W)31, 51, 61 Outdoor Section With CAP*3617A Indoor Section 2.79 36.66 19.65 3.07 34.69 18.93 3.39 2.76 33.29 24.35 3.04 31.46 23.60 3.36 2.74 30.89 23.49 3.02 29.17 22.73 3.35 2.74 30.45 29.01 3.02 28.86 28.20 3.35 2.73 30.12 30.12 3.02 28.77 28.77 3.35 2.85 37.20 20.61 3.13 35.17 19.88 3.45 2.82 33.80 25.90 3.10 31.91 25.15 3.42 2.80 31.38 24.94 3.08 29.60 24.18 3.41 2.80 31.24 31.24 3.08 29.83 29.83 3.41 2.80 31.27 31.27 3.08 29.83 29.83 3.41 2.91 37.60 21.52 3.19 35.50 20.77 3.51 2.88 34.19 27.39 3.16 32.26 26.63 3.48 2.86 31.76 26.34 3.14 29.94 25.57 3.47 2.86 32.22 32.22 3.15 30.70 30.70 3.47 2.86 32.23 32.23 3.15 30.70 30.70 3.47
DETAILED COOLING CAPACITIES# CONTINUED
24ABB3
POWER
30.22 27.34 25.29 25.64 25.65 30.54 27.67 25.61 26.52 26.52 30.75 27.93 25.88 27.22 27.22
Total
0.92 0.93 0.93 0.93 0.93 0.92 0.93 0.92 0.93 0.93 0.93 0.90 0.91 0.92 0.93 0.91 0.92 0.93 0.91 0.93 0.93 0.94 0.94 0.93 0.94 0.93 0.90 0.91 0.94 0.94 0.93 0.94 0.93 0.94 0.92 0.93 0.92 0.93 0.93
125 (51.7)
4.20 4.18 4.18 4.18 4.18 4.25 4.24 4.24 4.24 4.24 4.31 4.30 4.29 4.30 4.29
Total System KW**
58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20
FURNACE MODEL
17.30 21.95 21.07 25.64 25.65 18.23 23.48 22.48 26.52 26.52 19.10 24.92 23.82 27.22 27.22
Sens‡
Capacity MBtuh
27
See notes on page 30
COOLING INDOOR MODEL CNPH*4221A** CNPV*3621A** CNPV*4221A** CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A** CNPH*4221A** CNPV*3621A** CNPV*4221A** CSPH*3612A** CSPH*4212A** CAP**4224A** CNPH*3617A** CNPH*4221A** CSPH*3612A** CSPH*4212A** CAP**4224A** CNPH*3617A** CNPH*4221A** CSPH*3612A** CSPH*4212A** CAP**3617A** CAP**4817A** CNPH*3617A** CNPH*4221A** CNPV*3617A** CNPV*4217A** CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A** CNPH*4221A** CNPV*3621A** CNPV*4221A** CNPV*4821A** CSPH*3612A** CSPH*4212A** CAP**3621A** CAP**4221A** CNPH*3617A** CNPH*4221A** CNPV*3621A** CNPV*4221A** CNPV*4821A** CSPH*3612A** CSPH*4212A**
POWER
0.93 0.93 0.93 0.93 0.90 0.93 0.93 0.94 0.93 0.94 0.93 0.90 0.91 0.90 0.94 0.93 0.90 0.90 0.92 0.93 0.94 0.94 0.93 0.96 0.95 0.97 0.97 0.96 0.93 0.95 0.95 0.91 0.91 0.92 0.91 0.92 0.91 0.91 0.92 0.93 0.91 0.92 0.93 0.91 0.93 0.91 0.92 0.92 0.94
CAPACITY
0.99 0.98 0.99 0.99 0.99 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 0.99 0.99 0.99 0.99 0.99 0.98 0.99 0.99 0.99 0.99 1.02 0.98 0.99 0.98 1.00 1.01 1.02 1.00 1.01 0.99 1.01 0.99 1.01 1.02 1.02 1.02 1.01 1.01 0.99 1.01 0.99 1.01 1.03 1.02 1.03
58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MVB040--- 14 58MVB040--- 14 58MVB040--- 14 58MVB040--- 14 58MVB040--- 14 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20
FURNACE MODEL
24ABB330(A,W)31, 51, 61 Outdoor Section With CAP*3617A Indoor Section
DETAILED COOLING CAPACITIES# CONTINUED
24ABB3
28
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
COOLING INDOOR MODEL *CAP**4221A** CAP**4224A** CAP**4817A** CAP**4821A** CAP**4824A** CNPF*4818A** CNPH*4221A** CNPH*4821A** CNPV*4217A** CNPV*4221A** CNPV*4821A** CNPV*4824A** CSPH*4212A** CSPH*4812A** FV4BN(B,F)003 FV4BN(B,F)005 FV4BNB006 FX4CN(B,F)042 FX4CN(B,F)048 FY4ANF042 FY4ANF048 CNPH*4221A** CNPH*4821A** CSPH*4212A** CSPH*4812A** CAP**4817A** CNPV*4217A** CAP**4221A** CAP**4821A** CNPV*4221A** CNPV*4821A** CAP**4224A** CAP**4824A** CNPV*4824A** CAP**4817A** CNPH*4221A** CNPH*4821A** CNPV*4217A** CSPH*4212A**
1575
1400
1225
CFM
EWB ° F (° C)
EVAPORATOR AIR
POWER
1.00 1.00 0.99 1.01 1.01 1.01 1.00 1.01 1.00 1.00 1.01 1.01 1.00 1.01 0.94 0.95 0.95 0.99 0.99 1.00 1.02 0.97 0.98 0.97 0.98 0.93 0.93 0.97 0.96 0.94 0.96 0.94 0.94 0.94 0.94 0.93 0.94 0.94 0.94
1.00 1.00 0.99 1.01 1.01 1.01 1.00 1.01 1.00 1.00 1.01 1.01 1.00 1.01 0.99 1.01 1.04 1.01 1.04 1.00 1.02 0.99 1.00 0.99 1.00 0.98 0.99 0.99 1.00 0.99 1.00 0.99 1.00 1.00 1.00 0.99 1.00 1.00 1.00
25.49 31.36 30.43 37.19 39.73 26.62 33.20 32.16 39.75 41.25 27.70 34.99 33.85 42.08 42.49
Sens‡
CAPACITY
48.49 44.47 41.53 40.83 39.73 49.21 45.16 42.22 41.69 41.25 49.75 45.69 42.75 42.52 42.49
Total
Capacity MBtuh
75 (23.9)
46.39 42.52 39.69 39.07 38.29 47.02 43.14 40.31 39.91 39.72 47.50 43.61 40.79 40.87 40.87
Total
58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)070--- 12 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12 58MEB040--- 12
24.69 30.54 29.59 36.35 38.29 25.80 32.37 31.31 38.85 39.72 26.88 34.15 33.00 40.87 40.87
Sens‡
Capacity MBtuh
FURNACE MODEL
3.39 3.33 3.29 3.28 3.27 3.47 3.42 3.38 3.37 3.37 3.56 3.50 3.46 3.46 3.46
Total System KW**
85 (29.4)
COOLING INDOOR MODEL CSPH*4812A** CAP**4817A** CNPH*4221A** CNPH*4821A** CNPV*4217A** CSPH*4212A** CSPH*4812A** CAP**4817A** CNPH*4221A** CNPH*4821A** CNPV*4217A** CSPH*4212A** CSPH*4812A** CAP**4817A** CNPH*4221A** CNPH*4821A** CNPV*4217A** CSPH*4212A** CSPH*4812A** CAP**4221A** CAP**4821A** CNPH*4221A** CNPH*4821A** CNPV*4221A** CNPV*4821A** CSPH*4212A** CSPH*4812A** CAP**4224A** CNPH*4221A** CNPH*4821A** CNPV*4824A** CSPH*4212A** CSPH*4812A** CAP**4224A** CAP**4824A** CNPH*4221A** CNPH*4821A** CNPV*4824A** CSPH*4212A** 1.00 1.00 0.99 1.00 1.00 1.00 1.00 1.00 0.99 1.00 1.00 1.00 1.00 1.00 0.98 1.00 0.99 1.00 1.00 0.99 1.00 0.99 1.00 0.99 1.00 1.00 1.00 0.99 0.99 1.00 1.00 1.00 1.00 0.98 1.00 0.98 0.99 1.00 0.98
CAPACITY 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.93 0.94 0.94 0.94 0.94 0.94 0.92 0.94 0.93 0.94 0.94 0.93 0.92 0.93 0.92 0.93 0.92 0.92 0.92 0.91 0.93 0.92 0.92 0.92 0.92 0.96 0.98 0.96 0.97 0.98 0.96
POWER 58MEB040--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB060--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 12 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MV(B,C)040--- 14 58MV(B,C)040--- 14 58MV(B,C)040--- 14 58MV(B,C)040--- 14 58MV(B,C)040--- 14 58MV(B,C)040--- 14
FURNACE MODEL
115 (46.1)
4.98 4.92 4.88 4.88 4.88 5.06 5.01 4.97 4.98 4.98 5.14 5.09 5.05 5.07 5.07
Total System KW**
1.00 0.98 0.99 0.98 0.99 0.98 0.99 0.96 0.98 1.00 0.99 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00 1.00 0.99 1.00
CAPACITY
22.03 27.82 26.84 33.32 33.34 23.11 29.63 28.53 34.45 34.45 24.16 31.38 30.18 35.32 35.32
Sens‡
See notes on page 30
39.28 35.93 33.47 33.32 33.34 39.67 36.34 33.89 34.45 34.45 39.94 36.65 34.23 35.32 35.32
Total
Capacity MBtuh
COOLING INDOOR MODEL CSPH*4812A** CAP**4817A** CNPV*4217A** CAP**4221A** CAP**4821A** CNPV*4221A** CNPV*4821A** CAP**4817A** CNPH*4221A** CNPH*4821A** CNPV*4217A** CSPH*4212A** CSPH*4812A** CAP**4221A** CAP**4821A** CNPH*4221A** CNPH*4821A** CNPV*4221A** CNPV*4821A** CSPH*4212A** CSPH*4812A** CAP**4221A** CAP**4821A** CNPH*4221A** CNPH*4821A** CNPV*4221A** CNPV*4821A** CSPH*4212A** CSPH*4812A** CAP**4224A** CAP**4824A** CNPH*4221A** CNPH*4821A** CNPV*4824A** CSPH*4212A** CSPH*4812A**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB342(A,W)30, 50, 60 Outdoor Section With 42 Indoor Section 3.73 44.18 23.85 4.11 41.83 22.97 4.52 3.67 40.46 29.67 4.05 38.28 28.77 4.47 3.63 37.74 28.72 4.01 35.68 27.80 4.43 3.63 37.22 35.45 4.00 35.29 34.48 4.42 3.62 36.76 36.76 4.00 35.12 35.12 4.42 3.81 44.73 24.95 4.19 42.30 24.06 4.61 3.76 41.00 31.49 4.13 38.75 30.59 4.55 3.72 38.28 30.42 4.09 36.17 29.51 4.51 3.71 38.02 38.02 4.09 36.34 36.34 4.51 3.71 38.08 38.08 4.09 36.34 36.34 4.51 3.90 45.14 26.02 4.27 42.64 25.12 4.69 3.84 41.42 33.28 4.22 39.12 32.36 4.63 3.80 38.72 32.11 4.17 36.55 31.18 4.59 3.80 39.14 39.14 4.18 37.31 37.31 4.61 3.80 39.15 39.15 4.18 37.32 37.32 4.61
DETAILED COOLING CAPACITIES# CONTINUED
24ABB3
POWER
36.45 33.34 31.05 31.36 31.36 36.75 33.67 31.40 32.33 32.33 36.95 33.93 31.68 33.09 33.09
Total
0.98 0.93 0.94 0.96 0.97 0.96 0.97 0.95 0.96 0.98 0.97 0.94 0.98 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.91 0.92 0.91 0.92 0.91 0.92 0.91 0.92 0.91 0.92 0.93 0.92 0.92 0.91 0.92
125 (51.7)
5.47 5.42 5.38 5.38 5.38 5.55 5.50 5.46 5.48 5.48 5.63 5.58 5.54 5.56 5.56
Total System KW**
58MV(B,C)040--- 14 58MV(B,C)060--- 14 58MV(B,C)060--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58MV(B,C)080--- 14 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*070--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20
FURNACE MODEL
21.00 26.78 25.79 31.36 31.36 22.07 28.57 27.47 32.33 32.33 23.10 30.29 29.07 33.09 33.09
Sens‡
Capacity MBtuh
29
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
COOLING INDOOR MODEL *CAP**4821A** CAP**4817A** CAP**4824A** CAP**6021A** CAP**6024A** CNPF*4818A** CNPH*4821A** CNPH*6024A** CNPV*4821A** CNPV*4824A** CNPV*6024A** CSPH*4812A** CSPH*6012A** FE4AN(B,F)005 FE4ANB006 FV4BN(B,F)005 FV4BNB006 FX4CN(B,F)048 FX4CN(B,F)060 FY4ANB060 FY4ANF048 CAP**4817A** CNPH*4821A** CNPH*6024A** CSPH*4812A** CSPH*6012A** CAP**4821A** CAP**6021A** CNPH*4821A** CNPH*6024A** CNPV*4821A** CSPH*4812A** CSPH*6012A** CAP**4824A** CAP**6024A** CNPH*4821A** CNPH*6024A** CNPV*4824A** CNPV*6024A**
1800
1600
1400
CFM
EWB ° F (° C)
EVAPORATOR AIR
POWER
1.00 0.98 0.99 0.98 0.99 0.98 0.99 0.99 0.99 0.99 0.99 1.00 0.99 0.92 0.91 0.92 0.91 0.92 0.95 0.99 0.97 0.94 0.92 0.94 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
1.00 0.98 0.99 1.00 1.01 0.98 0.99 1.01 0.99 0.99 1.01 1.00 1.01 1.00 1.01 1.00 1.01 1.00 1.03 1.01 0.99 0.98 0.98 1.00 0.99 1.00 0.98 1.00 0.98 1.00 0.98 0.98 1.00 0.98 1.00 0.98 1.00 0.98 1.00
26.42 32.57 31.55 38.68 44.55 27.67 34.60 33.46 41.42 46.27 28.85 36.53 35.26 47.66 47.67
Sens‡
CAPACITY
54.48 49.80 46.41 45.58 44.55 55.34 50.62 47.22 46.58 46.27 55.96 51.21 47.80 47.66 47.67
Total
Capacity MBtuh
75 (23.9)
58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)090--- 16 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)110--- 20 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)135--- 22
FURNACE MODEL
3.32 3.30 3.28 3.28 3.27 3.40 3.38 3.36 3.36 3.36 3.48 3.46 3.44 3.44 3.44
Total System KW**
85 (29.4)
COOLING INDOOR MODEL CSPH*4812A** CSPH*6012A** CAP**4824A** CAP**6024A** CNPH*4821A** CNPH*6024A** CNPV*4824A** CNPV*6024A** CSPH*4812A** CSPH*6012A** CAP**4817A** CNPH*4821A** CNPH*6024A** CSPH*4812A** CSPH*6012A** CAP**4821A** CAP**6021A** CNPH*4821A** CNPH*6024A** CNPV*4821A** CSPH*4812A** CSPH*6012A** CAP**4824A** CAP**6024A** CNPH*4821A** CNPH*6024A** CNPV*4824A** CNPV*6024A** CSPH*4812A** CSPH*6012A** CAP**4821A** CAP**6021A** CNPH*4821A** CNPH*6024A** CNPV*4821A** CSPH*4812A** CSPH*6012A** CAP**4821A** CAP**6021A** 0.98 1.00 0.98 1.00 0.99 1.00 0.98 1.00 0.98 1.00 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.97 0.98 0.97 0.99 0.97 0.97 0.99 0.98 1.00
CAPACITY 0.92 0.92 0.90 0.90 0.91 0.90 0.90 0.90 0.90 0.90 0.98 0.94 0.94 0.94 0.92 0.92 0.90 0.92 0.90 0.92 0.92 0.90 0.92 0.90 0.92 0.90 0.92 0.90 0.92 0.90 0.93 0.92 0.93 0.93 0.93 0.93 0.93 0.96 0.94
POWER 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB080--- 16 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)080--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20
FURNACE MODEL
115 (46.1)
24ABB3
4.94 4.92 4.91 4.91 4.91 5.02 5.00 4.99 4.99 4.99 5.10 5.08 5.06 5.07 5.07
Total System KW**
0.98 1.00 0.98 0.98 1.00 0.98 1.00 0.98 1.00 0.98 1.00 0.98 1.00 0.98 1.00 0.98 1.00 0.98 0.98 1.00 0.98 1.00 0.98 1.00 0.98 0.98 1.00 0.99 1.00 0.99 1.00 0.99 1.00 0.99 1.00
CAPACITY
22.96 29.02 27.94 37.47 37.47 24.17 31.01 29.80 38.75 38.75 25.32 32.89 31.55 39.77 39.77
Sens‡
See notes on page 30
44.34 40.34 37.46 37.47 37.47 44.84 40.84 37.96 38.75 38.75 45.18 41.20 38.33 39.77 39.77
Total
Capacity MBtuh
COOLING INDOOR MODEL CNPH*4821A** CNPH*6024A** CNPV*4821A** CSPH*4812A** CSPH*6012A** CAP**4824A** CAP**6024A** CNPH*4821A** CNPH*6024A** CNPV*4824A** CNPV*6024A** CSPH*4812A** CSPH*6012A** CAP**4821A** CAP**6021A** CNPH*4821A** CNPH*6024A** CNPV*4821A** CSPH*4812A** CSPH*6012A** CAP**4821A** CAP**6021A** CNPH*4821A** CNPH*6024A** CNPV*4821A** CSPH*4812A** CSPH*6012A** CAP**4824A** CAP**6024A** CNPH*4821A** CNPH*6024A** CNPV*4824A** CNPV*6024A** CSPH*4812A** CSPH*6012A**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB348(A,W)31, 51, 61, 11 Outdoor Section With CAP**4821A** Indoor Section 52.18 25.62 3.67 49.73 24.77 4.05 47.13 23.89 4.48 47.63 31.74 3.64 45.34 30.88 4.03 42.93 29.97 4.45 44.36 30.70 3.63 42.19 29.82 4.01 39.89 28.90 4.44 43.61 37.81 3.62 41.55 36.89 4.01 39.45 39.21 4.43 42.94 42.94 3.62 41.23 41.23 4.01 39.42 39.42 4.43 52.95 26.86 3.75 50.42 26.01 4.13 47.73 25.12 4.56 48.38 33.76 3.72 46.00 32.88 4.11 43.51 31.98 4.53 45.08 32.60 3.71 42.83 31.71 4.09 40.47 30.78 4.52 44.61 44.23 3.70 42.74 42.74 4.09 40.82 40.82 4.52 44.56 44.56 3.70 42.75 42.75 4.09 40.82 40.82 4.52 53.51 28.03 3.83 50.90 27.17 4.21 48.15 26.28 4.64 48.91 35.69 3.80 46.48 34.81 4.19 43.93 33.88 4.61 45.61 34.40 3.79 43.31 33.50 4.17 40.89 32.56 4.60 45.87 45.87 3.79 43.97 43.97 4.17 41.94 41.94 4.60 45.88 45.88 3.79 43.97 43.97 4.17 41.95 41.95 4.60
DETAILED COOLING CAPACITIES# CONTINUED
POWER
41.30 37.58 34.91 35.38 35.39 41.69 38.00 35.33 36.51 36.52 41.94 38.30 35.64 37.41 37.41
Total
0.96 0.94 0.96 0.96 0.94 0.94 0.94 0.92 0.94 0.94 0.94 0.94 0.94 0.92 0.92 0.92 0.94 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.93 0.92 0.93 0.92 0.93 0.92 0.93 0.92
125 (51.7)
5.45 5.43 5.42 5.42 5.42 5.52 5.51 5.49 5.50 5.50 5.60 5.58 5.57 5.58 5.58
Total System KW**
58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)100--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58MV(B,C)120--- 20 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*090--- 16 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20 58PH*135--- 20
FURNACE MODEL
21.95 28.02 26.94 35.38 35.39 23.15 29.98 28.77 36.51 36.52 24.28 31.83 30.47 37.41 37.41
Sens‡
Capacity MBtuh
30
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9)
POWER
1.00 0.98 1.00 1.00 1.00 0.96 0.96 0.98 0.98 0.97
1.00 0.98 0.99 0.99 1.00 1.00 1.00 1.00 0.98 0.98
34.82 43.00 41.80 51.13 56.63 36.45 45.67 44.30 54.75 58.75 37.99 48.20 46.68 60.44 60.47
Sens‡
CAPACITY
68.71 63.16 59.15 58.14 56.63 69.71 64.15 60.14 59.33 58.75 70.44 64.85 60.84 60.44 60.47
Total
Capacity MBtuh
75 (23.9)
58CV(A,X)135--- 22 58CV(A,X)135--- 22
FURNACE MODEL
4.37 4.29 4.24 4.23 4.21 4.48 4.40 4.35 4.34 4.33 4.59 4.51 4.45 4.45 4.45
Total System KW**
COOLING INDOOR MODEL CNPV*6024A** CSPH*6012A** CAP**6024A** CNPH*6024A** CNPV*6024A** CSPH*6012A** CAP**6021A** CNPH*6024A** CSPH*6012A** 0.98 0.98 0.99 0.99 0.99 0.98 0.98 0.98 0.98
CAPACITY 0.97 0.97 0.97 0.97 0.97 0.97 0.98 0.98 0.98
POWER 58CV(A,X)135--- 22 58CV(A,X)135--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58CV(A,X)155--- 22 58MEB100--- 20 58MEB100--- 20 58MEB100--- 20
FURNACE MODEL
115 (46.1)
6.42 6.36 6.31 6.31 6.31 6.53 6.46 6.42 6.42 6.42 6.63 6.56 6.52 6.54 6.54
Total System KW**
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
CAPACITY
30.09 38.20 36.96 47.55 47.55 31.67 40.80 39.39 49.05 49.05 33.16 43.27 41.69 50.23 50.23
Sens‡
See notes on page 30
55.54 51.03 47.79 47.55 47.55 56.07 51.58 48.36 49.05 49.05 56.41 51.96 48.77 50.23 50.23
Total
Capacity MBtuh
COOLING INDOOR MODEL CAP**6024A** CNPH*6024A** CNPV*6024A** CSPH*6012A** CAP**6021A** CNPH*6024A** CSPH*6012A** CSPH*6012A**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 95 (35) 105 (40.6) Total Total Total Capacity MBtuh Capacity MBtuh Capacity MBtuh System System System Total Sens‡ Total Sens‡ Total Sens‡ KW** KW** KW** 24ABB360(A,W)32, 51, 61, 11 Outdoor Section With CAP**6024A** Indoor Section 65.76 33.74 4.81 62.59 32.60 5.30 59.21 31.39 5.84 60.43 41.90 4.74 57.50 40.73 5.23 54.39 39.50 5.77 56.59 40.69 4.68 53.84 39.50 5.18 50.92 38.26 5.72 55.65 49.99 4.67 53.01 48.77 5.16 50.27 47.45 5.71 54.60 54.60 4.66 52.42 52.42 5.16 50.09 50.09 5.71 66.67 35.37 4.92 63.38 34.20 5.41 59.88 32.98 5.95 61.31 44.55 4.85 58.27 43.36 5.34 55.05 42.13 5.87 57.47 43.18 4.79 54.61 41.98 5.28 51.60 40.73 5.82 56.80 53.54 4.78 54.23 54.23 5.28 51.77 51.77 5.83 56.59 56.59 4.78 54.26 54.26 5.28 51.77 51.77 5.83 67.31 36.90 5.03 63.93 35.73 5.52 60.33 34.49 6.05 61.94 47.09 4.95 58.82 45.89 5.44 55.52 44.63 5.98 58.11 45.56 4.90 55.17 44.34 5.39 52.08 43.07 5.93 58.18 58.18 4.90 55.72 55.72 5.40 53.10 53.10 5.94 58.19 58.19 4.90 55.73 55.73 5.40 53.10 53.10 5.94 85 (29.4)
POWER
51.41 47.32 44.36 44.70 44.71 51.80 47.74 44.82 45.99 46.00 52.03 48.04 45.14 46.99 47.00
Total
0.98 0.98 0.98 0.98 0.97 0.97 0.97 0.97
125 (51.7)
7.05 6.99 6.95 6.96 6.96 7.15 7.10 7.06 7.07 7.07 7.25 7.20 7.16 7.18 7.18
Total System KW**
58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58MEB120--- 20 58PH*110--- 20 58PH*110--- 20 58PH*110--- 20 58PH*135--- 20
FURNACE MODEL
28.66 36.77 35.54 44.70 44.71 30.21 39.34 37.93 45.99 46.00 31.69 41.75 40.17 46.99 47.00
Sens‡
Capacity MBtuh
* Tested combination. { Total and sensible capacities are net capacities. Blower motor heat has been subtracted. } Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C). # Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240 ---2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ** System kw is total of indoor and outdoor unit kilowatts. {{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb. NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice. EWB — Entering Wet Bulb NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
COOLING INDOOR MODEL *CAP**6024A** CAP**6021A** CNPH*6024A** CNPV*6024A** CSPH*6012A** FE4ANB006 FV4BNB006 FX4CN(B,F)060 CAP**6024A** CNPH*6024A**
2250
2000
1750
CFM
EWB ° F (° C)
EVAPORATOR AIR
DETAILED COOLING CAPACITIES# CONTINUED
24ABB3
SST 째 F (째 C) 30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78)
30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78)
30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78)
30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78)
55 (12.78)
65 (18.33)
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
16.10 70.80 0.83 17.70 71.90 0.83 19.50 73.00 0.83 21.30 74.20 0.83 23.30 75.40 0.82 25.20 76.70 0.82
15.20 80.40 0.95 16.70 81.40 0.95 18.40 82.50 0.95 20.20 83.60 0.95 22.00 84.80 0.95 23.90 86.00 0.94
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
21.30 73.00 1.06 23.40 74.40 1.06 25.60 75.80 1.07 27.90 77.30 1.08 30.20 78.80 1.09 32.60 80.30 1.09
20.10 82.40 1.21 22.10 83.60 1.21 24.20 85.00 1.22 26.40 86.30 1.23 28.60 87.80 1.24 30.80 89.20 1.25
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
25.40 74.40 1.35 28.00 75.90 1.35 30.70 77.40 1.35 33.50 79.00 1.36 36.50 80.70 1.36 39.50 82.40 1.37
24.00 83.60 1.52 26.50 85.00 1.52 29.10 86.50 1.53 31.80 88.00 1.53 34.60 89.70 1.54 37.40 91.30 1.54
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
30.30 73.20 1.65 33.50 74.80 1.66 37.00 76.60 1.68 40.70 78.50 1.70 44.60 80.50 1.73 48.80 82.60 1.77
28.80 82.20 1.85 31.80 83.80 1.87 35.10 85.40 1.89 38.60 87.20 1.91 42.30 89.10 1.94 46.30 91.10 1.97
CONDENSER ENTERING AIR TEMPERATURES 째 F (째 C) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 24ABB318(A,W)31 14.20 13.30 12.30 11.30 89.90 99.50 109.10 118.80 1.09 1.24 1.40 1.57 15.70 14.70 13.70 12.60 90.90 100.40 109.90 119.60 1.09 1.24 1.40 1.58 17.40 16.20 15.10 14.00 91.90 101.30 110.80 120.40 1.09 1.23 1.40 1.58 19.00 17.90 16.70 15.40 93.00 102.30 111.70 121.20 1.08 1.23 1.40 1.58 20.80 19.50 18.20 16.90 94.10 103.40 112.60 122.00 1.08 1.23 1.40 1.58 22.50 21.20 19.80 18.50 95.20 104.40 113.60 122.90 1.08 1.23 1.39 1.58 24ABB324(A,W)31 18.90 17.70 16.50 15.20 91.80 101.20 110.60 120.20 1.37 1.56 1.77 1.99 20.90 19.60 18.20 16.90 93.00 102.30 111.70 121.10 1.38 1.57 1.77 2.00 22.90 21.50 20.00 18.60 94.20 103.50 112.70 122.10 1.39 1.58 1.78 2.01 24.90 23.40 21.90 20.40 95.50 104.70 113.80 123.10 1.40 1.58 1.79 2.02 27.00 25.40 23.70 22.10 96.80 105.90 114.90 124.10 1.40 1.59 1.80 2.03 29.10 27.30 25.60 23.90 98.20 107.10 116.10 125.20 1.41 1.60 1.81 2.03 24ABB330(A,W)31, 51 22.60 21.10 19.60 18.00 92.90 102.10 111.40 120.80 1.70 1.91 2.13 2.37 24.90 23.40 21.70 20.00 94.20 103.40 112.60 121.90 1.71 1.92 2.15 2.39 27.40 25.70 24.00 22.20 95.60 104.70 113.80 123.00 1.72 1.93 2.15 2.40 30.00 28.20 26.30 24.40 97.00 106.10 115.10 124.20 1.72 1.93 2.16 2.42 32.70 30.70 28.70 26.70 98.50 107.50 116.40 125.40 1.73 1.94 2.17 2.43 35.30 33.20 31.10 29.00 100.10 108.90 117.80 126.60 1.74 1.95 2.18 2.44 24ABB336(A,W)31, 51, 61 27.20 25.50 23.80 22.00 91.40 100.60 109.90 119.10 2.07 2.30 2.57 2.88 30.10 28.30 26.40 24.40 92.80 102.00 111.10 120.30 2.08 2.32 2.59 2.90 33.20 31.20 29.20 27.00 94.40 103.40 112.40 121.50 2.10 2.34 2.61 2.92 36.50 34.30 32.10 29.80 96.00 104.90 113.80 122.80 2.13 2.37 2.63 2.94 40.00 37.70 35.30 32.80 97.80 106.50 115.30 124.20 2.16 2.40 2.66 2.97 43.80 41.30 38.70 36.00 99.60 108.20 116.90 125.60 2.19 2.43 2.70 3.00
See notes on page 32
31
115 (46.11)
125 (51.67)
10.20 128.60 1.76 11.50 129.40 1.77 12.80 130.10 1.77 14.20 130.70 1.78 15.60 131.40 1.78 17.00 132.20 1.78
9.10 138.50 1.95 10.30 139.10 1.97 11.50 139.70 1.98 12.80 140.30 1.99 14.20 140.90 1.99 15.50 141.50 1.99
14.00 129.80 2.24 15.50 130.60 2.25 17.10 131.50 2.26 18.80 132.30 2.27 20.40 133.30 2.28 22.10 134.20 2.28
12.60 139.40 2.51 14.10 140.20 2.52 15.60 140.90 2.53 17.10 141.60 2.54 18.60 142.40 2.55 20.20 143.10 2.55
16.40 130.20 2.63 18.30 131.20 2.65 20.30 132.20 2.67 22.40 133.30 2.69 24.60 134.30 2.70 26.70 135.40 2.71
14.60 139.60 2.89 16.40 140.50 2.92 18.40 141.40 2.95 20.30 142.30 2.97 22.30 143.20 2.99 24.30 144.20 3.00
20.00 128.40 3.25 22.30 129.50 3.26 24.80 130.60 3.28 27.40 131.80 3.30 30.20 133.00 3.32 33.20 134.30 3.35
18.00 137.80 3.68 20.10 138.70 3.69 22.40 139.70 3.70 24.80 140.80 3.72 27.40 141.90 3.73 30.20 143.00 3.76
24ABB3
CONDENSER ONLY RATINGS*
CONDENSER ONLY RATINGS* CONTINUED SST ° F (° C) 30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0)
24ABB3
55 (12.78)
30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78)
30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78)
55 (12.78)
65 (18.33)
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
38.00 73.20 1.95 41.90 74.80 1.97 46.00 76.40 1.98 50.30 78.10 2.01 54.90 80.00 2.03 59.70 81.90 2.06
36.00 82.30 2.20 39.70 83.70 2.22 43.60 85.20 2.23 47.70 86.90 2.26 52.10 88.60 2.28 56.60 90.30 2.30
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
41.10 73.80 2.19 45.20 75.30 2.22 49.60 76.90 2.24 54.30 78.50 2.27 59.30 80.20 2.30 64.60 82.10 2.34
38.90 83.00 2.46 42.80 84.40 2.49 47.10 86.00 2.51 51.60 87.50 2.54 56.40 89.20 2.58 61.40 91.00 2.61
TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW
54.90 77.60 2.73 60.30 79.50 2.79 66.00 81.60 2.86 72.10 83.80 2.93 78.50 86.10 3.01 85.10 88.60 3.09
51.90 86.40 3.07 57.10 88.20 3.13 62.60 90.20 3.20 68.30 92.20 3.27 74.40 94.40 3.35 80.60 96.60 3.44
CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 24ABB342(A,W)30, 50, 60 33.90 31.90 29.70 27.60 91.40 100.60 109.80 119.10 2.48 2.80 3.14 3.53 37.40 35.10 32.80 30.50 92.80 101.90 111.00 120.20 2.50 2.81 3.16 3.54 41.10 38.70 36.20 33.60 94.20 103.20 112.20 121.30 2.52 2.83 3.18 3.56 45.10 42.40 39.60 36.80 95.70 104.60 113.50 122.50 2.54 2.85 3.19 3.58 49.20 46.20 43.20 40.20 97.20 106.00 114.80 123.70 2.56 2.87 3.21 3.60 53.40 50.20 46.90 43.50 98.90 107.50 116.20 124.90 2.58 2.89 3.23 3.62 24ABB348(A,W)31, 51, 61, 11 36.70 34.40 32.10 29.70 92.30 101.60 111.00 120.40 2.76 3.10 3.47 3.87 40.50 38.00 35.50 32.90 93.70 102.90 112.20 121.50 2.79 3.13 3.50 3.90 44.50 41.90 39.20 36.40 95.10 104.30 113.40 122.60 2.82 3.15 3.53 3.93 48.80 46.00 43.10 40.10 96.60 105.70 114.70 123.80 2.85 3.19 3.56 3.97 53.40 50.30 47.10 43.90 98.10 107.10 116.10 125.10 2.88 3.22 3.59 4.00 58.10 54.80 51.40 47.90 99.80 108.70 117.50 126.40 2.92 3.25 3.63 4.04 24ABB360(A,W)32, 51, 61, 11 49.00 46.00 42.90 39.80 95.30 104.20 113.20 122.20 3.45 3.88 4.34 4.85 53.90 50.70 47.30 43.90 97.00 105.80 114.70 123.60 3.51 3.94 4.40 4.92 59.10 55.50 51.90 48.20 98.80 107.50 116.30 125.00 3.58 4.00 4.47 4.98 64.50 60.70 56.70 52.60 100.70 109.30 117.90 126.50 3.65 4.08 4.54 5.06 70.20 66.00 61.60 57.20 102.70 111.20 119.60 128.10 3.73 4.15 4.62 5.13 76.10 71.40 66.70 61.80 104.80 113.10 121.40 129.70 3.81 4.24 4.70 5.21
* ARI listing applies only to systems shown in Combination Ratings table. KW --- Outdoor Unit Kilowatts Only. SDT --- Saturated Temperature Leaving Compressor (° F/° C) SST --- Saturated Temperature Entering Compressor (° F/° C) TCG --- Gross Cooling Capacity (1000 Btuh)
32
115 (46.11)
125 (51.67)
25.30 128.40 3.95 28.00 129.40 3.97 30.90 130.40 3.98 33.90 131.40 4.00 37.00 132.50 4.01 40.10 133.60 4.03
22.90 137.70 4.41 25.50 138.60 4.43 28.10 139.50 4.44 30.90 140.40 4.45 33.60 141.30 4.47 36.40 142.20 4.48
27.20 129.70 4.30 30.20 130.80 4.34 33.50 131.80 4.38 36.90 132.90 4.41 40.50 134.10 4.45 44.20 135.20 4.48
24.50 139.10 4.76 27.40 140.00 4.81 30.40 141.00 4.85 33.60 142.00 4.89 36.90 143.00 4.92 40.30 144.00 4.96
36.50 131.20 5.41 40.30 132.50 5.48 44.30 133.80 5.54 48.40 135.10 5.61 52.50 136.50 5.68 56.70 137.90 5.75
33.10 140.20 6.01 36.50 141.30 6.08 40.10 142.50 6.15 43.80 143.60 6.21 47.50 144.80 6.27 51.20 146.00 6.34
System Description Outdoor--mounted, air--cooled, split--system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air--cooled coil, propeller--type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit. Quality Assurance — Unit will be rated in accordance with the latest edition of AHRI Standard 210. — Unit will be certified for capacity and efficiency, and listed in the latest AHRI directory. — Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC. — Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c--UL--us approval. — Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500--hr salt spray test. — Air--cooled condenser coils will be leak tested at 150 psig and pressure tested at 450 psig. — Unit constructed in ISO9001 approved facility. Delivery, Storage, and Handling — Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations. Warranty (for inclusion by specifying engineer) — U.S. and Canada only.
PRODUCTS Equipment Factory assembled, single piece, air--cooled air conditioner unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge Puronr (R--410A), and special features required prior to field start--up. Unit Cabinet — Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint. — 3 phase equipment available with dense grille only. — Single phase equipment available with wide (W) or dense (A) grille option.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER 24ABB3 1--1/2 TO 5 NOMINAL TONS Fans — Condenser fan will be direct--drive propeller type, discharging air upward. — Condenser fan motors will be totally enclosed, 1--phase type with class B insulation and permanently lubricated bearings. Shafts will be corrosion resistant. — Fan blades will be statically and dynamically balanced. — Condenser fan openings will be equipped with coated steel wire safety guards. Compressor — Compressor will be hermetically sealed. — Compressor will be mounted on rubber vibration isolators. Condenser Coil — Condenser coil will be air cooled. — Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed. Refrigeration Components — Refrigeration circuit components will include liquid--line shutoff valve with sweat connections, vapor--line shutoff valve with sweat connections, system charge of Puronr (R--410A) refrigerant, and compressor oil. — Unit will be equipped with high--pressure switch, low pressure switch and filter drier for Puron refrigerant. Operating Characteristics — The capacity of the unit will meet or exceed _____ Btuh at a suction temperature of _____ _F/_C. The power consumption at full load will not exceed _____ kW. — Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at conditions of _____ CFM entering air temperature at the evaporator at _____ _F/_C wet bulb and _____ _F/_C dry bulb, and air entering the unit at _____ _F/_C. — The system will have a SEER of _____ Btuh/watt or greater at DOE conditions. Electrical Requirements — Nominal unit electrical characteristics will be _____ v, single phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of _____ v to _____ v. — Nominal unit electrical characteristics will be _____ v, three phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of _____ v to _____ v. — Unit electrical power will be single point connection. — Control circuit will be 24v. Special Features — Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.
33
24ABB3
GUIDE SPECIFICATIONS GENERAL
SYSTEM DESIGN SUMMARY 1. 2. 3. 4. 5. 6.
7.
24ABB3
8. 9.
Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C). Maximum outdoor operating air temperature is 125_F (51.7_C). For reliable operation, unit should be level in all horizontal planes. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4 mm). Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. Do not apply capillary tube indoor coils to these units. Factory--supplied filter drier must be installed.
Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
Edition Date: 07/09
Catalog No: 24ABB3---6PD Replaces: 24ABB3--- 5PD
24ABB, 24ABC Baset Series Air Conditioners with Puronr Refrigerant 1---1/2 To 5 Nominal Tons
Installation Instructions SAFETY CONSIDERATIONS
GENERAL
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment. 1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer. 2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity. 3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends. 4. Leave some slack between structure and unit to absorb vibration. 5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon--based caulk. (See Fig. 1.) 6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls. 7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.(See Fig. 1.) 8. Ensure that tubing insulation is pliable and completely surrounds vapor tube. 9. When necessary, use hanger straps which are 1 in. (25.4 mm) wide and conform to shape of tubing insulation. (See Fig. 1.) 10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
Recognize safety information. This is the safety--alert symbol !! When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
!
NOTE: Avoid contact between tubing and structure OUTDOOR WALL
INDOOR WALL
CAULK
LIQUID TUBE
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
INSULATION
VAPOR TUBE
THROUGH THE WALL JOIST HANGER STRAP (AROUND VAPOR TUBE ONLY)
INSULATION VAPOR TUBE
CAUTION
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
1� (25.4 mm) MIN. SUSPENSION
LIQUID TUBE
A94026
Fig. 1 -- Piping Installation
The outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field--supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section of this instruction. IMPORTANT: Maximum liquid--line size is 3/8--in. OD for all residential applications including long line. Refer to Residential Piping and Longline Guideline for further information. IMPORTANT: Always install the factory--supplied liquid--line filter drier. If replacing the filter drier, refer to Product Data Digest for appropriate part number. Obtain replacement filter driers from your distributor or branch.
Make Piping Connections
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow--control devices, including solenoid valves. Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.
INSTALLATION 24ABB / 24ABC
Check Equipment and Job Site
!
UNPACK UNIT Move to final location. Remove carton taking care not to damage unit.
Failure to follow this caution may result in equipment damage or improper operation.
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
If ANY refrigerant tubing is buried, provide a 6--in (152.4 mm). vertical rise at service valve. Refrigerant tubing lengths up to 36--in (914.4 mm). may be buried without further special consideration. Do not bury lines more than 36--in. (914.4 mm).
Install on a Solid, Level Mounting Pad
Clearance Requirements When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6--in. (152.4 mm) clearance on 1 side of unit and 12--in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m) Position so water, snow, or ice from roof or eaves cannot fall directly on unit. NOTE: 18” (457.2 mm) clearance option described above is approved for outdoor units with wire grille coil guard only. Units with louver panels require 24” (609.6 mm) between units. On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.
Operating Ambient The minimum outdoor operating ambient in cooling mode without accessory is 55 _F (12.78 _C), and the maximum outdoor operating ambient in cooling mode is 125_F (51.67 _C).
CAUTION
UNIT DAMAGE HAZARD
Inspect Equipment
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location. For hurricane tie downs, contact local distributor for details and PE (Professional Engineer) certification, if required by local authorities. On rooftop applications, mount on level platform or frame. Place unit above a load--bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications. Roof mounted units exposed to winds may require wind baffles. Consult the Application Guideline and Service Manual -Residential Split System Air Conditioners and Heat Pumps for wind baffle construction. NOTE: Unit must be level to within ±2_ (±3/8 in./ft ,.±9.5 mm/m) per compressor manufacturer specifications.
WARNING
!
3/8--- in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places
View From Top TIEDOWN KNOCKOUT LOCATIONS in. (mm) A B C
UNIT BASE PAN Dimension in. (mm) 23 ---1/2 X 23 ---1/2 7 ---13/16 (198.4) (596.9 X 596.9) 26 X 26 9–1/8 (231.8) (660.4 X 660.4) 31–1/2 X 31–1/2 9–1/8 (231.8) (800.1 X 800.1) 35 X 35 9–1/8 (231.8) (889 X 889)
4–7/16 (112.7)
18–1/16 (458.8)
4–7/16 (112.7)
21–1/4 (539.8)
6–9/16 (166.7)
24–11/16 (627.1)
6–9/16 (166.7)
28–7/16 (722.3) A05177
Fig. 2 -- Tiedown Knockout Locations Outdoor units may be connected to indoor section using accessory tubing package or field--supplied refrigerant grade tubing of correct size and condition. Rated tubing diameters shown in Table 1 are recommended up to 80 ft. (24.38 m). See Product Data for acceptable alternate vapor diameters and associated capacity losses. For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the recommendations in the Longline Guideline will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 5 for accessory requirements. There are no buried--line applications greater than 36--in. (914.4 mm) allowed. If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
2
Outdoor Unit Connected to Factory Approved Indoor Unit Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field--supplied or factory--accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.
Refer to Fig. 3 and install filter drier as follows: 1. Braze 5--in. liquid tube to the indoor coil. 2. Wrap filter drier with damp cloth. 3. Braze filter drier to above 5--in. (127 mm) liquid tube. Flow arrow must point towards indoor coil. 4. Connect and braze liquid refrigerant tube to the filter drier.
Refrigerant Tubing Connection Outdoor Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1.) Use refrigerant grade tubing
Sweat Connection
CAUTION
UNIT DAMAGE HAZARD
A05178
Failure to follow this caution may result in equipment damage or improper operation.
Fig. 3 -- Liquid Line Filter Drier
Evacuate Refrigerant Tubing and Indoor Coil
Service valves must be wrapped in a heat--sinking material such as a wet cloth while brazing.
Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE 18, 24 30 36 42, 48 60
UNIT SIZE 18, 24 30 36 42, 48, 49 60, 61
24ABB3 LIQUID Connection & Max. Tube Diameter 3/8 3/8 3/8 3/8 3/8
RATED VAPOR* Connection Diameter
Tube Diameter
3/4 3/4 7/8 7/8 7/8
3/4 3/4 7/8 7/8 1 ---1/8
24ABC6 LIQUID RATED VAPOR* Connection Connection Tube & Max. Tube Diameter Diameter Diameter 3/8 3/4 3/4 3/8 3/4 3/4 3/8 7/8 7/8 3/8 7/8 7/8 3/8 7/8 1 ---1/8
* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets. Notes: 1. Do not apply capillary tube or fixed orifice indoor coils to these units. 2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide line --- Air Conditioners and Heat Pumps using Puron refrigerant. 3. For alternate liquid line options on 18 ---42 size units, see Product Data or Residential Piping and Application Guideline
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump. Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.
Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4. 5000 4500 4000 3500 3000 2500 2000 1500 1000
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. 1. Installation of filter drier in liquid line is required.
VACUUM TIGHT TOO WET TIGHT DRY SYSTEM
500 0
Install Liquid-- Line Filter Drier Indoor
!
LEAK IN SYSTEM
MICRONS
Use refrigeration grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
CAUTION
!
1
2
3 4 5 MINUTES
6
7
A95424
A95424
Fig. 4 -- Deep Vacuum Graph
Final Tubing Check IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
2. Filter drier must be wrapped in a heat--sinking material such as a wet cloth while brazing. 3
24ABB / 24ABC
!
Installing with Indoor Piston Outdoor Unit Connected to Factory Approved Indoor Unit Check piston size shipped with indoor unit to see if it matches required indoor piston size. If it does not match, replace indoor piston with correct piston size. NOTE: Correct pistons are shipped with outdoor units in the accessory bag and are only qualified for piston fan coils. Example fan coils with piston: FB4C and FY5B (1.5 through 4 ton) When changing indoor piston, use a back−up wrench. Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ft−lbs. The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body, and must be installed properly to ensure proper seating. See Fig. 13/16” BRASS HEX NUT TEFLON® SEAL
24ABB / 24ABC
TEFLON® RINGS
3/4” BRASS HEX BODY “H” DISTRIBUTOR
PISTON PISTON RETAINER A10342
Fig. 5 -- Indoor (Cooling) Piston
!
CAUTION
PRODUCT OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation. If using a TXV in conjunction with a single--phase reciprocating compressor, a compressor start capacitor and relay are required. Units with Cooling Mode TXV Units installed with cooling mode TXV require charging by the subcooling method. 1. Operate unit a minimum of 15 minutes before checking charge. 2. Measure liquid service valve pressure by attaching an accurate gage to service port. 3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil. 4. Refer to unit rating plate for required subcooling temperature. 5. Refer to Table 2 -- Rating Plate (required) Subcooling Temperature. Find the point where required subcooling temperature intersects measured liquid service valve pressure. 6. To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of 3_F (1.7_C).
Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method. The following procedure is valid when indoor airflow is within 21 percent of its rated CFM. 1. Operate unit a minimum of 15 minutes before checking charge. 2. Measure suction pressure by attaching an accurate gage to suction valve service port. 3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service valve. 4. Measure outdoor air dry bulb temperature with thermometer. 5. Measure indoor air (entering indoor coil) wet--bulb temperature with a sling psychrometer. 6. Refer to Table 3 -- Superheat Charging -- AC Only. Find outdoor temperature and evaporator entering air wet--bulb temperature. At this intersection, note superheat. Where a dash (----) appears on the table, do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighted in, adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 feet (4.6m) respectively. 7. Refer to Table 4 -- Required Suction--Line Temperature. Find superheat temperature (from #6 above) and suction pressure. At this intersection, note suction line temperature. 8. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached. 9. If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached. 10. When adding refrigerant, charge in liquid form into suction service port using a flow--restricting device. 11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on chart. 12. Optimum performance will be achieved when the operating charge produces 10_F suction superheat at suction service valve with 95_F (35_C) outdoor ambient and 80_F (27_C) dry bulb (67_F / 19_C) wet bulb) indoor temperature (DOE “A” test conditions) at rated airflow.
4
Table 2 – Rating Plate (required) Subcooling Temperatures R --- 410A Required Liquid Line Temperature _F (_C)
Measure Liquid Pressure (psig)
_F
(_C)
_F
(_C)
_F
(_C)
_F
(_C)
_F
(_C)
_F
6
3
8
4
10
6
12
7
14
8
16
9
251
78
26
76
24
74
23
72
22
70
21
68
20
259
80
27
78
26
76
24
74
23
72
22
70
21
266
82
28
80
27
78
26
76
24
74
23
72
22
274
84
29
82
28
80
27
78
26
76
24
74
23
283
86
30
84
29
82
28
80
27
78
26
76
24
291
88
31
86
30
84
29
82
28
80
27
78
26
299
90
32
88
31
86
30
84
29
82
28
80
27
308
92
33
90
32
88
31
86
30
84
29
82
28
317
94
34
92
33
90
32
88
31
86
30
84
29
326
96
36
94
34
92
33
90
32
88
31
86
30
335
98
37
96
36
94
34
92
33
90
32
88
31
345
100
38
98
37
96
36
94
34
92
33
90
32
364
104
40
102
39
100
38
98
37
96
36
94
34
374
106
41
104
40
102
39
100
38
98
37
96
36
384
108
42
106
41
104
40
102
39
100
38
98
37
395
110
43
108
42
106
41
104
40
102
39
100
38
406
112
44
110
43
108
42
106
41
104
40
102
39
416
114
46
112
44
110
43
108
42
106
41
104
40
427
116
47
114
46
112
44
110
43
108
42
106
41
439
118
48
116
47
114
46
112
44
110
43
108
42
450
120
49
118
48
116
47
114
46
112
44
110
43
462
122
50
120
49
118
48
116
47
114
46
112
44
474
124
51
122
50
120
49
118
48
116
47
114
46
Table 3 – Superheat Charging -- AC Only OUTDOOR TEMP (_F)
EVAPORATOR ENTERING AIR TEMPERATURE (_F WB) 50
52
54
56
58
60
62
64
67
68
70
72
74
76
55
9
12
14
17
20
23
26
29
32
35
37
40
42
45
60
7
10
12
15
18
21
24
27
30
33
35
38
40
43
65
—
6
10
13
16
19
21
24
27
30
33
36
38
41
70
—
—
7
10
13
16
19
21
24
27
30
33
36
39
75
—
—
—
6
9
12
15
18
21
24
28
31
34
37
80
—
—
—
—
5
8
12
15
18
21
25
28
31
35
85
—
—
—
—
—
—
8
11
15
19
22
26
30
33
90
—
—
—
—
—
—
5
9
13
16
20
24
27
31
95
—
—
—
—
—
—
—
6
10
14
18
22
25
29
100
—
—
—
—
—
—
—
—
8
12
15
20
23
27
105
—
—
—
—
—
—
—
—
5
9
13
17
22
26
110
—
—
—
—
—
—
—
—
—
6
11
15
20
25
115
—
—
—
—
—
—
—
—
—
—
8
14
18
23
*Optimum performance point, 95_F (35_C) outdoor ambient and (80_F / 27_C dry bulb), (67_F / 19_C wet bulb) indoor conditions. (DOE A Test Conditions) Where a dash (--- --- ) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in. Note: Superheat _F is at low--- side service port, Allow a tolerance of ±3_F (±1.7_C) Note: Indoor dry bulb between 70_F and 80_F (21_C and 27_C)
5
24ABB / 24ABC
(_C)
Table 4 – Required Suction--Line Temperature
24ABB / 24ABC
SUPERHEAT TEMP (_F)
SUCTION PRESSURE AT SERVICE PORT (PSIG) 107.8
112.2
116.8
121.2
126
130.8
138.8
140.8
145.8
0
35
37
39
41
43
45
47
49
51
2
37
39
41
43
45
47
49
51
53
4
39
41
43
45
47
49
51
53
55
6
41
43
45
47
49
51
53
55
57
8
43
45
47
49
51
53
55
57
59
10
45
47
49
51
53
55
57
59
61
12
47
49
51
53
55
57
59
61
63
14
49
51
53
55
57
59
61
63
65
16
51
53
55
57
59
61
63
65
67
18
53
55
57
59
61
63
65
67
69
20
55
57
59
61
63
65
67
69
71
22
57
59
61
63
65
67
69
71
73
24
59
61
63
65
67
69
71
73
75
26
61
63
65
67
69
71
73
75
77
28
63
65
67
69
71
73
75
77
79
30
65
67
69
71
73
75
77
79
81
32
67
69
71
73
75
77
79
81
83
34
69
71
73
75
77
79
81
83
85
36
71
73
75
77
79
81
83
85
87
38
73
75
77
79
81
83
85
87
89
40
75
77
79
81
83
85
87
89
91
6
Make Electrical Connections
Final Wiring Check
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device. NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits. NOTE: Use copper wire only between disconnect switch and unit. NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440--14 of NEC.
IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Route Ground and Power Wires
Refer to the individual instructions packaged with kits or accessories when installing.
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit. A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Residential Piping and Longline Guideline and Service Manual Longline Section--Residential Split--System Air Conditioners and Heat Pumps.
Install Electrical Accessories Start--Up
!
WARNING
!
CAUTION
ELECTRICAL SHOCK HAZARD
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or death.
Failure to follow this caution may result in personal injury, equipment damage or improper operation. S Do not overcharge system with refrigerant. S Do not operate unit in a vacuum or at negative pressure. S Compressor dome temperatures may be hot.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
!
Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.
CAUTION
PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury.
DISCONNECT PER N.E.C. AND/OR LOCAL CODES
Wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following: S Front seating service valves are equipped with Schrader valves.
CONTACTOR
FIELD POWER WIRING 3 PHASE ONLY
Follow these steps to properly start up system:
BLUE
1. After system is evacuated, fully open liquid and vapor service valves. 2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger--tight and tighten with wrench an additional 1/12 turn. 3. Close electrical disconnects to energize system. 4. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature. 5. Set room thermostat to COOL and fan control to ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system refrigerant charge.
FIELD GROUND WIRING
GROUND LUG
A94025
Fig. 6 -- Line Connections
Connect Control Wiring Route 24--v control wires through control wiring grommet and connect leads to control wiring (See Fig. 7). Refer to Installation Instructions packaged with thermostat. Use No. 18 AWG color--coded, insulated (35_C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG color--coded wire to avoid excessive voltage drop. All wiring must be NEC Class 1 and must be separated from incoming power leads. Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum. NOTE: Use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required.
7
24ABB / 24ABC
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
Compressor Crankcase Heater
24ABB / 24ABC
3-- Phase Monitor
Check Charge
In 3--phase units a small circuit board is factory installed to monitor line voltage. A small led will flash if a phase problem exists. See code descriptions on monitor. If LED is flashing, disconnect power to unit and interchange 2 field--wiring leads on unit contactor.
Factory charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on information plate inside unit. To properly check or adjust charge, conditions must be favorable for subcooling charging. Favorable conditions exist when the outdoor temperature is between 70_F and 100_F (21.11_C and 37.78_C), and the indoor temperature is between 70_F and 80_F (21.11_C and 26.67_C). Follow the procedure below: Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15ft (4.57 m) respectively. For standard refrigerant line lengths (80 ft/24.38 m or less), allow system to operate in cooling mode at least 15 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system. If the indoor temperature is above 80_F (26.67_C), and the outdoor temperature is in the favorable range, adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F (26.67_C) before attempting to check system charge by subcooling method as described above. If the indoor temperature is below 70_F (21.11_C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15ft (4.57 m) only. Charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range. NOTE: If line length is beyond 80 ft (24.38 m) or greater than 20 ft (6.10 m) vertical separation, See Long Line Guideline for special charging requirements.
A00010
Fig. 7 -- 3--Phase Monitor Control (Applies to 3--Phase Units Only) Table 5 – Three--Phase Monitor LED Indicators LED OFF FLASHING ON
!
STATUS No call for compressor operation Reversed phase Normal
CAUTION
UNIT DAMAGE HAZARD
Final Checks
Failure to follow this caution may result in equipment damage or improper operation.
IMPORTANT: Before leaving job, be sure to do the following: 1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub--through or wire pinching. 2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers. 3. Tighten service valve stem caps to 1/12--turn past finger tight. 4. Leave Owner’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual. 5. Fill out Dealer Installation Checklist and place in customer file.
Ensure compressor rotation is correct. S 3--phase scroll compressors are rotation sensitive. S A flash LED on phase monitor indicates reverse rotation. (See Table 3) This will not allow contractor to be energized. S Disconnect power to unit and interchange 2 field--wiring leads on unit contactor.
Sequence of Operation Turn on power to indoor and outdoor units. Transformer is energized. On a call for cooling, thermostat makes circuits R--Y and R--G. Circuit R--Y energizes contactor, starting outdoor fan motor and compressor circuit. R--G energizes indoor unit blower relay, starting indoor blower motor on high speed. When thermostat is satisfied, its contacts open, de--energizing contactor and blower relay. Compressor and motors stop. If indoor unit is equipped with a time--delay relay circuit, the indoor blower will run an additional 90 seconds to increase system efficiency.
CARE AND MAINTENANCE For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment. Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Owner’s Manual for information.
8
Table 6 – Accessory Usage ACCESSORY
REQUIRED FOR LOW --- AMBIENT COOLING APPLICATIONS (Below 55°F/12.8_C)
REQUIRED FOR LONG LINE APPLICATIONS*
REQUIRED FOR SEA COAST APPLICATIONS (Within 2 miles/3.22 km)
Ball Bearing Fan Motor
Yes{
No
No
Compressor Start Assist Capacitor and Relay
Yes
Yes
No
Crankcase Heater
Yes
Yes
No
Evaporator Freeze Thermostat
Yes
No
No
Hard Shut--- Off TXV
Yes
Yes
Yes No
Liquid Line Solenoid Valve
No
No
Motor Master® or Low--- ambient Pressure Switch
Yes
No
No
Support Feet
Recommended
No
Recommended
Winter Start Control Yes No No * For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Piping and Longline Guideline. { Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.
24ABB / 24ABC
Always Ask For
A/C THERMOSTAT
Typical FURNACE
24 VAC HOT
R
R
24 VAC COM
C
C
HEAT STAGE 1
W/W1
W
COOL STAGE 1
Y/Y2 G
INDOOR FAN
A/C THERMOSTAT
AIR CONDITIONER
Typical FAN COIL
24 VAC HOT
R
24 VAC COM
C
AIR CONDITIONER
R
C C
HEAT STAGE 1
W/W1
Y
COOL STAGE 1
Y/Y2
G
INDOOR FAN
G
W2
C
G A02326
LEGEND 24-V FACTORY WIRING 24-V FIELD WIRING FIELD SPLICE CONNECTION C
CONTACTOR A97368
Fig. 8 -- Generic Wiring Diagrams (See Thermostat Installation Instruction for specific unit combinations)
9
PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDE S Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron refrigerant S Puron refrigerant cylinders are rose colored. S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. S Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low--side retard. S Use hoses with 700 psig service pressure rating. S Leak detectors should be designed to detect HFC refrigerant. S Puron refrigerant, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil. S Do not use liquid--line filter driers with rated working pressures less than 600 psig.
24ABB / 24ABC
S Do not leave Puron suction line filter driers in line longer than 72 hours. S Do not install a suction--line filter drier in liquid line. S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A factory approved liquid--line filter drier is required on every unit. S Do NOT use an R--22 TXV. S If indoor unit is equipped with an R--22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV. S Never open system to atmosphere while it is under a vacuum. S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging. S Do not vent Puron refrigerant into the atmosphere. S Do not use capillary tube coils. S Observe all warnings, cautions, and bold text. S All indoor coils must be installed with a hard shutoff Puron TXV metering device.
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 07/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
Catalog No: 24ABB---C ---6SI Replaces: 24ABB--- C--- 5SI
24ABB3 Baset Series Air Conditioner with Puronr 1---1/2 to 5 Nominal Tons Single and Three Phase
Wiring Diagrams CONNECTION DIAGRAM
*CHS *CH
BLK or RED
BLK
BLK COMP BLU CONT BLK C S H 21 11 R C 23 YEL 23
RED or BLK L1 L2
BLK
208/230 1Ø POWER SUPPLY
EQUIP GND
YEL OFM
SCHEMATIC DIAGRAM (LADDER FORM) L1
BLK
(NOTE #9)
BLU BLU
CAP
+t
YEL
*ST BRN
YEL *SC
F
(NOTE #8)
BRN
C
2
EQUIP GND *CHS
S
2
5 1
H
*SR
5 *SR
C F (NOTE #14)
VIO
CONT
*CTD YEL/PNK
YEL/PNK
BLK
*HPS BLK
BLU/PNK
*LLS BLK
*LPS
T2
*DTS
BLK
LOGIC
BLU/PNK T1
C R
Y R G INDOOR THERMOSTAT (NOTE #6)
EXTERNAL POWER SUPPLY 24 V (NOTE #3)
Y
IFR
G R
R INDOOR THERMOSTAT
251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474
78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124
76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122
10 12 14 16 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120
72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118
70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114
1. Only use sub cooling charging method when OD ambient is greater than 70ºF and less than 100ºF, indoor temp is greater than 70ºF and less than 80ºF, and line set is less than 80 ft. 2. Operate unit a minimum of 15 minutes before checking the charge. 3. Measure liquid service valve pressure by attaching an accurate gauge to the service port. 4. Measure the liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the liquid line near the outdoor coil. 5. Refer to unit rating plate for required subcooling temperature. 6. Find the point where the required subcooling temperature intersects the measured liquid service valve pressure. 7. To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated. When adding refrigerant, charge in liquid form using a flow restricting device into suction service port. Recover refrigerant if temperature is lower. Allow a tolerance of +/- 3ºF.
NOTES: 1. 2. 3. 4. 5. 6. 7.
C
EXTERNAL POWER SUPPLY 24 V
INDOOR BLOWER MOTOR
Temperature (ºF) 8
T3 * CTD
*LLS
LEGEND
For use with units using R-410A refrigerant COOLING ONLY REQUIRED LIQUID LINE TEMPERATURE CHARGING PROCEDURE Liquid Pressure Required Subcooling 6
T2 T1
T3
CONDENSING UNIT CHARGING INSTRUCTIONS
at Service Valve (psig)
*HPS LOGIC
BRN/YEL
YEL/ BLU
CAP
BRN/YEL
BLK
*DTS
CONT 23 23
OFM
YEL
*LPS
*ST +t
*SC
1
*CH (NOTE #14) YEL/ BLU
L2
COMP R
CONT 11 21
Symbols are electrical representation only. Compressor and fan motor furnished with inherent thermal protection. To be wired in accordance with National Electric N.E.C. and local codes. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF). Connection for typical cooling only thermostat. For other arrangements see installation instructions. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead. 8. When start relay and start capacitor are installed, start thermistor is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS or CTD are used.
CONT CAP *CH *CHS COMP *CTD *DTS *HPS IFR *LLS *LPS OFM *SC *SR *ST
FACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION CONTACTOR CAPACITOR (DUAL RUN) CRANKCASE HEATER CRANKCASE HEATER SWITCH COMPRESSOR COMPRESSOR TIME DELAY DISCHARGE TEMP SWITCH HIGH PRESSURE SWITCH INDOOR FAN RELAY LIQ LINE SOLENOID VALVE LOW PRESSURE SWITCH OUTDOOR FAN MOTOR START CAPICATOR START RELAY START THERMISTOR
* MAY BE FACTORY INSTALLED
CAUTION 1. Compressor damage may occur if system is over charged. 2. This unit is factory charged with R-410A in accordance with the amount shown on the rating plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. Check refrigerant charge for maximum efficiency. See Product Data Literature for required Indoor air Flow Rates and for use of line lengths over 15 feet. 3. Relieve pressure and recover all refrigerant before system repair or final disposal. Use all service ports and open all flow-control devices, including solenoid valves. 4. Never vent refrigerant to atmosphere. Use approved recovery equipment. 330440-101 REV. F
Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1
CONNECTION DIAGRAM
* CH
L1
BLK
RED or BLK
L2
CONT L1 L3
11
21
13
23
T2 T3
YEL
CAP
CONT 11 21
EQUIP GND
YEL
T2
T1 T3
EQUIP GND BLK YEL
OFM
*CHS
PRM
PRM CONT 24V COM
BLU
L2 COM
BRN/YEL
BRN/YEL
BLK *HPS
*LPS
VIO
YEL/BLU
T2
CONT
LOGIC T1
*LPS
* CTD
*HPS YEL/PNK
YEL/PNK
CONT 13 23
OFM
*CH
YEL
COMP CAP
BRN
BLK BLU
L3 L1 CONT 24
BLU
COMP
T1
BLK
L3
PRM L2 L3 L1
RED or BLK
L2
208/23 0 3Ø OR 460 3Ø POWER SUPPLY
SCHEMATIC DIAGRAM (LADDER FORM)
*CHS
BLU/PNK
LOGIC T1
* CTD
*LLS
T2
BLU/PNK
T3
Y
T3
IFR G
BRN/YEL
R
*LLS BLK
BLK IFR
Y
G
R
INDOOR THERMOSTAT (NOTE #6)
C R
EXTERNAL POWER SUPPLY 24 V (NOTE #3)
R INDOOR THERMOSTAT
NOTE
Required Subcooling Temperature (ºF) 6
8
78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124
76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122
NOTES:
1. Symbols are electrical representation only. 2. Compressor and fan motor OFF: NO 24VAC furnished with inherent ON: OK INDOOR BLOWER MOTOR thermal protection. FLASH: PHASE PROBLEM 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. CONT CONTACTOR 5. Use copper conductors CAP CAPACITOR (DUAL RUN) only. Use conductors 1. Only use sub cooling charging method suitable for at least *CH CRANKCASE HEATER when OD ambient is greater than 70ºF 75ºC (167ºF). and less than 100ºF, indoor temp is *CHS CRANKCASE HEATER SWITCH 6. Connection for typical cooling only thermostat. greater than 70ºF and less than 80ºF, 72 70 68 COMPRESSOR COMP For other arrangements 74 72 70 and line set is less than 80 ft. see installation instructions. *CTD COMPRESSOR TIME DELAY 76 74 72 2. Operate unit a minimum of 15 minutes 7. If indoor section has a transformer with a *HPS HIGH PRESSURE SWITCH 78 76 74 before checking the charge. grounded secondary, 80 78 76 IFR INDOOR FAN RELAY connect the grounded 82 80 78 3. Measure liquid service valve pressure by side to the BRN/YEL lead. LIQ LINE SOLENOID VALVE *LLS attaching an accurate gauge to the 84 82 80 8. If any of the original wire, 86 84 82 as supplied must be *LPS LOW PRESSURE SWITCH service port. replaced, use the same or 88 86 84 4. Measure the liquid line temperature by OFM OUTDOOR FAN MOTOR equivalent wire. 90 88 86 attaching an accurate thermistor type or PRM PHASE ROTATION MONITOR 9. Check all electrical 92 90 88 connections inside control electronic thermometer to the liquid line * MAY BE FACTORY INSTALLED box for tightness. 94 92 90 10. Do not attempt to operate near the outdoor coil. 96 94 92 unit service valves have 98 96 94 5. Refer to unit rating plate for required been opened. 1. Compressor damage may occur if system is 11. Do not rapid cycle 100 98 96 subcooling temperature. over charged. compressor. 102 100 98 6. Find the point where the required subCompressor must be off 2. This unit is factory charged with R-410A in 104 102 100 3 minutes to allow cooling temperature intersects the accordance with the amount shown on the 106 104 102 pressures to equalize measured liquid service valve pressure. rating plate. The charge is adequate for most 108 106 104 between high and low systems using matched coils and tubing not side before starting. 110 108 106 7. To obtain the required subcooling over 15 feet long. Check refrigerant charge 12. It is imperative to connect temperature at specific liquid line 112 110 108 3Ø field power to unit with for maximum efficiency. See Product Data 114 112 110 pressure, add refrigerant if liquid line correct phasing. The Literature for required Indoor air Flow Rates 116 114 112 Phase Rotation Monitor temperature is higher than indicated. and for use of line lengths over 15 feet. 118 116 114 will not allow the contactor 3. Relieve pressure and recover all refrigerant When adding refrigerant, charge in liquid to be energized if the before system repair or final disposal. Use all phasing is not correct. If form using a flow restricting device into phasing is reversed, service ports and open all flow-control suction service port. Recover refrigerant simply inter change any devices, including solenoid valves. two of the three power if temperature is lower. Allow a tolerance 4. Never vent refrigerant to atmosphere. Use connections on field side.
REQUIRED LIQUID LINE TEMPERATURE
251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474
EXTERNAL POWER SUPPLY 24 V
LEGEND
PRM LED INDICATOR
CONDENSING UNIT CHARGING INSTRUCTIONS For use with units using R-410A refrigerant Liquid Pressure at Service Valve (psig)
C
COOLING ONLY CHARGING PROCEDURE
FACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION
10 12 14 16 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120
335874-101 REV.A
CAUTION
of +/- 3ºF.
approved recovery equipment.
Fig. 2 – Wiring Diagram — Model size 2--1/2 -- 5 tons, 208/230--3 and Model size 3 -- 5 tons, 460/3
2
SCHEMATIC DIAGRAM (LADDER FORM)
CONNECTION DIAGRAM BLU
575 3Ø POWER SUPPLY
L1
CONT
L2 L1 L3
12
22
11
21
13
23
BLK
COMP CONT 11 21
T3 CAP
YEL YEL
T2
T1
EQUIP GND
BRN
RED or BLK
CAP
OFM
CONT 13 23
BLK
*CH
*CH
YEL
RED or BLK BRN/YEL
CONT
BLK
*HPS
*LPS
T2
VIO
LOGIC T1
*LPS
*HPS YEL/PNK
YEL/PNK
* CTD
T2
Y
LOGIC
BLU/PNK
BLU/PNK
T1
IFR
T3
G R
BRN/YEL
BLK C R
IFR
Y
G
R INDOOR THERMOSTAT
EXTERNAL POWER SUPPLY 24 V (NOTE #3)
CONDENSING UNIT CHARGING INSTRUCTIONS For use with units using R-410A refrigerant Liquid Pressure at Service Valve (psig) 251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474
Required Subcooling Temperature (ºF) 6
8
78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124
76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122
10 12 14 16 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120
335875-101 REV. A
72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118
70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114
EXTERNAL POWER SUPPLY 24 V
COOLING ONLY CHARGING PROCEDURE 1. Only use sub cooling charging method when OD ambient is greater than 70ºF and less than 100ºF, indoor temp is greater than 70ºF and less than 80ºF, and line set is less than 80 ft. 2. Operate unit a minimum of 15 minutes before checking the charge. 3. Measure liquid service valve pressure by attaching an accurate gauge to the service port. 4. Measure the liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the liquid line near the outdoor coil. 5. Refer to unit rating plate for required subcooling temperature. 6. Find the point where the required subcooling temperature intersects the measured liquid service valve pressure. 7. To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated. When adding refrigerant, charge in liquid form using a flow restricting device into suction service port. Recover refrigerant if temperature is lower. Allow a tolerance of +/- 3ºF.
CAUTION
approved recovery equipment.
Fig. 3 – Wiring Diagram — Model size 3 -- 5 tons, 575/3
3
NOTES:
1. Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. CONT CONTACTOR 5. Use copper conductors only. Use conductors CAP CAPACITOR suitable for at least *CH CRANKCASE HEATER 75ºC (167ºF). *CHS CRANKCASE HEATER SWITCH 6. Connection for typical cooling only thermostat. COMP COMPRESSOR For other arrangements see installation instructions. *CTD COMPRESSOR TIME DELAY 7. If indoor section has a *HPS HIGH PRESSURE SWITCH transformer with a grounded secondary, IFR INDOOR FAN RELAY connect the grounded *LLS LIQ LINE SOLENOID VALVE side to the BRN/YEL lead. LOW PRESSURE SWITCH 8. If any of the original wire, *LPS as supplied must be OUTDOOR FAN MOTOR OFM replaced, use the same or equivalent wire. 9. Check all electrical connections inside control box for tightness. * MAY BE FACTORY INSTALLED 10. Do not attempt to operate unit service valves have been opened. 1. Compressor damage may occur if system is 11. Do not rapid cycle compressor. over charged. Compressor must be off 2. This unit is factory charged with R-410A in 3 minutes to allow accordance with the amount shown on the pressures to equalize rating plate. The charge is adequate for most between high and low systems using matched coils and tubing not side before starting. over 15 feet long. Check refrigerant charge 12. It is imperative to connect 3Ø field power to unit with for maximum efficiency. See Product Data correct phasing. The Literature for required Indoor air Flow Rates Phase Rotation Monitor and for use of line lengths over 15 feet. will not allow the contactor 3. Relieve pressure and recover all refrigerant to be energized if the before system repair or final disposal. Use all phasing is not correct. If phasing is reversed, service ports and open all flow-control simply inter change any devices, including solenoid valves. two of the three power 4. Never vent refrigerant to atmosphere. Use connections on field side.
FACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION
INDOOR BLOWER MOTOR
REQUIRED LIQUID LINE TEMPERATURE
C
LEGEND
R
INDOOR THERMOSTAT (NOTE #6)
T3 * CTD
*LLS
*LLS BLK
L3
CONT 12 22
T3
OFM
EQUIP GND
L2
T2 COMP
T1
Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 09/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
Catalog No: 24ABB3---1W Replaces: New