Iaetsd load frequency control for a distributed grid

Page 1

ISBN:378-26-138420-0245

LOAD FREQUENCY CONTROL A DISTRIBUTED INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICALFOR ENGINEERING, ICCME-2014

GRID

SYSTEM INVOLVING WIND, HYDRO AND THERMAL POWER PLANTS P Suresh Kumar Dr.K.Rama Sudha PG scholar Professor Department Electrical & Electronics Engineering, Andhra University, Visakhapatnam, Andhra pradesh

Abstract- In an interconnected power system, as a

Rt

Temporary droop

power load demand varies randomly both area frequency and tie-line power interchange also vary. The objectives of load frequency control (LFC) are to minimize the deviations in these variables (area frequency and tie-line power interchange) and to ensure their steady state errors to be zero. In this area of energy crisis, renewable energy is the most promising solution to man’s ever increasing energy needs. But the power production by these resources cannot be controlled unlike in thermal plants. As a result, standalone operation of renewable energy is not reliable. Hence grid-connection of these along with conventional plants is preferred due to the improved performance in response to dynamic load. It is observed that fluctuations in frequency caused due to load variations are low with increase in penetration of renewable resources. Load frequency control (LFC) including PI controller is proposed in order to suppress frequency deviations for a power system involving wind, hydro and thermal plants owing to load and generating power fluctuations caused by penetration of renewable resources. A system involving four thermal plants, a wind farm and a hydro plant will be modeled using MATLAB.

Tg

Main servo time constant

Index Terms—Continuous power generation, load frequency, Control (LFC), wind power, hydro power, and thermal power plants LFC of multi area system, Frequency deviation in the multi area system.

operation of renewable resources is not reliable as they are

D

Change in load with respect to frequency

Tw

Water starting time

Tr

Reset time

Kt

Gain of turbine

Tt

Time constant of turbine

II. INTRODUCTION

The high Indian population coupled with increase in industrial growth has resulted in an urgent need to increase the installed power capacity. In India, majority of power production, around 65 percent is from thermal power stations. Due to problems related to uncertainty in pricing and supply of fossil fuels, renewable resources have been identified as a suitable alternative [7]. However, standalone

intermittent in nature. The intermittent nature of resource increases the frequency deviations which further add to the deviation caused by load variation. This necessitates the

I. NOMENCLATURE

grid connection of renewable resources [4] [2]. Frequency deviation is undesirable because most of the AC motors run

∆PC

Command signal

at speeds that are directly related to frequency. Also the

∆F

Frequency change

generator turbines are designed to operate at a very precise

∆YE

Changes in steam valve opening

speed. Microcontrollers are dependent on frequency for

R

Speed regulation of the governor

their timely operation. Thus it is imperative to maintain

Ksg

Gain of speed governor

system frequency constant. This is done by implementing

Tsg

Time constant of speed governor

Load Frequency Control (LFC). There are many LFC

Rp

Permanent droop

methods developed for controlling frequency. They include

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 39

www.iaetsd.in


ISBN:378-26-138420-0246

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

flat frequency control (FFC), tie-line bias control (TBC) and flat tie-line control (FTC) [1]. In FFC, Some areas act as load change absorbers and others as base load. The

∆ = ∆ − ∗ ∆ ∗

∗

(1)

advantage is the higher operating efficiencies of the base load as they run at their maximum rated value at all times. But the drawback here is the reduced number of areas absorbing load changes which makes the system more transient prone. In FTC load changes in each area are controlled within the area, thereby maintaining tie line frequency constant. The most commonly used method is the tie-line load bias control in which all power systems in

Fig 1.Block diagram representation of speed governing

the interconnection aid in regulating frequency regardless

system

of where the frequency change originates. In this paper, the power system considered has a Thermal system with four thermal areas, a Hydro plant and a wind farm.

B. Mathematical modeling Turbine model

III. MODELING OF THERMAL AREAS

The dynamic response of steam turbine is related to changes in steam valve opening ∆YE in terms of changes in power output. Typically the time constant Tt lies in the

The thermal areas have been modeled using transfer function. Speed governor, turbine and generator constitute the various parts namely the speed governing system,

range 0.2 to 2.5 sec. The dynamic response is largely influenced by two factors (i) entrained steam between the inlet steam valve and first

turbine model, generator load model .A complete block diagram representation of an isolated power system

Stage of the turbine, (ii) The storage action in the reheater which causes the

comprising Speed governor, turbine and generator and load is easily obtained by combining the block diagrams of individual components. [7].

Output of the low pressure stage to lag behind that of the High pressure stage

A. Mathematical modeling of speed Governing System

The command signal ∆PC initiates a sequence of events-the pilot valve moves upwards, high pressure oil flows on to the top of the main piston moving it downwards; the steam

Fig 2.Turbine transfer function model

valve opening consequently increases, the turbine generator speed increases, i.e. the frequency goes up which is modeled mathematically.

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 40

www.iaetsd.in


ISBN:378-26-138420-0247

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

C. Mathematical modeling Generator Load Model

The increment in power input to the generator-load system is related to frequency change as ∆ = ∆ − ∆ ∗

(2)

Fig 3. Block diagram representation of generator-load

IV. MODELING OF HYDRO AND WIND

Model

AREA

D. Entire thermal area

A. Modeling of hydro area The representation of the hydraulic turbine and water column in stability studies is usually based on certain

Typical values of time constants of load frequency control

assumptions. The hydraulic resistance is considered

system are related as Tsg< Tt << Tps. Fig. 4 shows the

negligible. The penstock pipe is assumed inelastic and

required block diagram and Table 1 shows the different

water incompressible. Also the velocity of the water is

parameters of the four thermal areas.

considered to vary directly with the gate opening and with the square root of the net head and the turbine output power is nearly proportional to the product of head and volume flow [3]. Hydro plants are modeled the same way as thermal plants. The input to the hydro turbine is water instead of steam. Initial droop characteristics owing to reduced pressure on turbine on opening the gate valve has to be compensated. Hydro turbines have peculiar response

Fig 4. Block diagram of entire thermal area

due to water inertia; a change in gate position produces an initial turbine power change which is opposite to that

Table 1 Parameters of all four thermal areas

sought. For stable control performance, a large transient (temporary) droop with a long resettling time is therefore required in the forms of transient droop compensation as shown in Fig. 5. The compensation limits gate movement until water flow power output has time to catch up. The

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 41

www.iaetsd.in


ISBN:378-26-138420-0248

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

result is governor exhibits a high droop for fast speed

uses a torque controller in order to maintain the speed at 1.2

deviations and low droop in steady state.

pu [6] [9] [10].

Fig 6. Block diagram of simple wind turbine Fig 5.Block diagram of hydro area.

V. LFC FOR A MULTI-AREA SYSTEM B. Modeling of wind farm An extended power system can be divided into a number of Wind passes over the blades, generating lift and exerting a

load frequency control areas interconnected by means of tie

turning force. The rotating blades turn a shaft inside the

lines. The control objective now is to regulate the frequency

nacelle, which goes into a gearbox. The gearbox increases

of each area and to simultaneously regulate the tie line

the rotational speed to that which is appropriate for the

power as per inter-area contacts. As in case of frequency,

generator, which uses magnetic fields to convert the

proportional plus integral controller will be installed so as

rotational energy into electrical energy. The power in the

to give zero steady state error in the tie line power flow as

wind that can be extracted by a wind turbine is proportional

compared to the contracted power. It is conveniently

to the cube of the wind speed and is given in watts by

assumed that each control area can be represented by an

P= ( Aν3 Cp)/2 where ρ is the air density, A is the rotor

equivalent turbine,

swept area, ν is the wind speed and Cp is the power

Symbols used with suffix 1 refer to area 1 & those with

coefficient. A maximum value of Cp is defined by the Betz

suffix 2 refer to area 2 and so on. Incremental tie line power

limit, which states that a turbine can never extract more

out of area 1 given by [5].

than 59.3% of the power from an air stream. In reality, wind turbine rotors have maximum Cp values in the range

generator

and

governor

∆ !"#, = 2&' ( ) ∆* +, − ) ∆*( +,

system.

(3)

25–45%. A wind farm consisting of Doubly-fed induction generator

Similarly, the incremental tie line power output of area 2

(DFIG) wind turbine is considered. DFIG consists of a

is given by

wound rotor induction generator and an AC/DC/AC IGBTbased PWM converter. The stator winding is connected

∆ !"#,( = 2&' ( ) ∆*( +, − ) ∆* +,

(4)

directly to the 50 Hz grid while the rotor is fed at variable frequency through the AC/DC/AC converter. The wind

Where T12 = synchronizing coefficient

speed is maintained constant at 11 m/s. The control system

f1 and f2 represent frequency of the respective area.

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 42

www.iaetsd.in


ISBN:378-26-138420-0249

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

For purpose, a single from ∆f is fed through an integrator to ∆ !"#,( . = −

(/012 12

∗ ∆ − ∆ (

(5)

This has been represented by fig.7

the speed changer resulting in block diagram configuration shown .the system now modifies to a proportional plus integral controller, which is well known from control theory, gives zero steady state error.

Therefore In the case of an isolated control area, ACE (area control error) is the change in area frequency which when used in integral control loop forced the steady state frequency error to zero. In order that the steady state tie line power error in a two area control be made zero another Fig 7. Block diagram of Tie-line power flow

integral control loop (one for each area) must be introduced to integrate the incremental tie line power signal and feed it back to the speed changer as shown in Fig 8

With the primary LFC loop a change in the system load will result in a steady state frequency deviation, depending on the governor speed regulation. In order to reduce the frequency deviation to zero we must provide a reset action by introducing an integral controller to act on the load reference setting to change the speed set point. The integral controller increases the system type by 1 which forces the final frequency deviation to zero. The integral controller gain must be adjusted for a satisfactory transient response. It is seen from the above discussion that with the speed

Fig.8 Diagram for Proportional plus Integral Load

governing system installed on each machine, the steady

frequency Control

load frequency characteristic for a given speed changer setting has considerable droop, from no load to full load .system frequency system specifications are rather stringent and, therefore so much change in frequency cannot be tolerated. In fact, it is expected that the steady change in

For free governor operation the steady change in system frequency for a sudden change in load demand (Pd) is given as

frequency will be zero. While steady state frequency can be brought back to the scheduled value by adjusting speed changer setting, the system could undergo intolerable dynamic frequency changes with changes in load. It leads

∆ =

3 ∆45/7 8 9

: :;: < 81=> 9∗ 1=>;

(6)

to the natural suggestion that the speed changer setting be adjusted automatically by monitoring the frequency

This is accomplished by a single integrating block by

changes.

redefining ACE as a linear combination of incremental frequency and tie line power. Thus for control area 1

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 43

www.iaetsd.in


ISBN:378-26-138420-0250

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

ACE1 = ∆Ptie,1 +b1∆f1 Taking Laplace transform ACE1(s) = ∆Ptie,1(s) +b1∆f1(s) Similarly, for control area n, ACEn(s) = ∆Ptie,n(s) +bn∆fn(s) Combining the basic block diagrams of multiple control areas with ∆Pc1(s) to ∆Pcn(s) generated by integrals of respective ACEs (obtained through signals representing changes in tie line power and local frequency bias) and employing the block diagram of Fig. 7, we easily obtain the composite block diagrams.

VI. SIMULATION AND RESULTS

A. LFC for thermal system four area system

The four thermal systems have been combined and the composite block diagram is simulated in Simulink/Matlab R2010a as shown in Fig. 9.

Fig.9 Thermal system Let the loads ∆PD1 to ∆PD4 be simultaneously applied in control areas 1 to 4 respectively. The system parameters of 4 area system are given in Table I. The frequency deviation versus time scale of 4 thermal areas for step load change is shown in Fig. 10

Frequency deviation Vs time for thermal system only

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 44

www.iaetsd.in


ISBN:378-26-138420-0251

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

Frequency Deviation Vs Time(s) 0.025 0.02 0.015 0.01

f (Hz)

0.005 0 -0.005 -0.01 -0.015 -0.02 -0.025

0

50

100

150

200

250 300 Time (sec)

350

400

450

500

Fig. 10. Response for Fixed load (Thermal system only)

B. LFC for Thermal and Hydro System (multi area)

Fig.11 Hydro and thermal systems (multi area)

The four thermal systems along with hydro unit are combined and composite block diagram is simulated as

Frequency deviation versus time for integrated thermal and

shown in figure.11

hydro system for step load change is shown in Fig. 12 from the curves it can be concluded that penetration of hydro energy (renewable) does not affect the system frequency adversely as the frequency deviation is well within limits.

Frequency deviation Vs time for (thermal hydro) system

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 45

www.iaetsd.in


ISBN:378-26-138420-0252

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

governor, turbo generator and load system consisting of four thermal areas, a hydro area and wind farm is controlled by a controller. By a batch control, the load is divided amongst various power plants in the ratio of their capacities by control system. This entire power system is modeled as shown in fig.13

Fig. 12. Response for Fixed load (thermal +hydro system)

C. LFC for Thermal, Hydro and Wind system

To compensate the intermittent nature of renewable, grid connection of the same is imperative for reliable power

Fig.13 LFC for Thermal, Hydro and Wind system

generation. The four thermal areas and the hydro unit are combined together in the ‘Thermal & Hydro’ subsystem which is same as the model shown in Fig. 8. The output ∆F of this subsystem gets reflected in the grid voltage. DFIG wind farm draws supply for stator from grid and the changing wind speeds has an impact on its output. Power from the DFIG is fed to the grid via stator and rotor depending on the wind speed. Higher the wind speed, higher is the power output, rotor feeds power; lower the wind speed, power It is possible to divide an extended power system into sub areas in which the generators are tightly coupled together so

output is low, hence rotor draws power from grid to have constant power flow through stator.

as to form a coherent group, i.e. all the generators respond in unison to changes in load or speed changer settings. Such a coherent area is called control area in which frequency is

Frequency Deviation (Hz) vs. Time(s) for the Integrated System

assumed to be same throughout in static and dynamic conditions. For the purpose of developing a suitable control strategy, a control area can be reduced to a single speed

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 46

www.iaetsd.in


ISBN:378-26-138420-0253

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

different units using Tie Line Bias Control method of LFC as it gives minimal frequency deviation.

VIII. REFERENCES

[1] R. Oba, G. Shirai, R. Yokoyama, T. Niimura, and G. Fujita, “Suppression of Short Term Disturbances from Fig. 14. Response for Fixed Load (Thermal + Hydro +

Renewable Resources by Load Frequency Control

Wind Systems)

Considering Different Characteristics of Power Plants”, IEEE Power & Energy Society General Meeting, pp.1 –

The output of wind farm is sent to the central control system to calculate the load distribution over thermal

7, Jul.2009. [2] N. R. Ullah, T. Thiringer, and Daniel

station. Random load of 1.7pu with maximum variation of

Karlsson,“Temporary Primary Frequency Control

0.8pu is considered here. Frequency deviation versus Time

Support by Variable Speed Wind Turbines— Potential

for Integrated Thermal, Hydro and Wind system for step

And Applications”, IEEE Transactions on Power

load change is shown in Fig. 14 Real time systems are best

Systems, vol.23, No.2, May 2008.

described by introducing random load variation. From the

[3]

curves, it can be concluded that in an integrated system with high penetration of renewable, frequency deviation has

ed., New York: McGraw-Hill, 1993. [4] L. Freris and D. Infield, Renewable Energy in Power

increased. Nevertheless, it is within limits thereby making renewable energy sources desirable.

P. Kundur, Power System Stability and Control, 1st

Systems, 1st ed., J.Wiley Sons Ltd., 2008. [5]

H. Saadat, Power System Analysis, 1st ed., Tata McGraw- Hill, 2002.

[6] O. Anaya-Lara, N. Jenkins, J. Ekanayake, P. Cartwright, M. Hughes, Wind Energy generation Modeling and Control, 1st ed., J. Wiley Sons Ltd.,

VII. CONCLUSION Load frequency control becomes more important, when a

2009. [7]

large amount of renewable power supplies like wind power generation are introduced. In this paper Load Frequency

Introduction, 2nd ed., Tata McGraw-Hill, 1983 [8] L.R. Chang-Chien, W.T. Lin and Y.C. Yin,

Control with considerable penetration of renewable has

“Enhancing frequency response control by DFIGs in

been analyzed in the presence of Thermal, Hydro and Wind

The high wind penetrated power systems,” IEEE

Systems with pi controller. It is observed that frequency deviation is low when wind system is introduced into the actual thermal systems, and it is within the tolerable limits for fixed load variations. The loads are distributed among

O. Elgerd, Electric Energy Systems Theory An

Transactions on power systems, 2010 [9]

G. Lalor, A. Mullane, and M. O’Malley, “Frequency Control and wind turbine technologies,” IEEE Trans. Power Syst., vol. 20, no. 4, pp. 1905–1913, Nov.

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 47

www.iaetsd.in


ISBN:378-26-138420-0254

INTERNATIONAL CONFERENCE ON CIVIL AND MECHANICAL ENGINEERING, ICCME-2014

2005. [10]

J. de Almeida and R. G. Lopes, “Participation of Doubly fed induction wind generators in system Frequency regulation,” IEEE Trans. Power Syst., vol. 22, no. 3, pp. 944–950, Aug. 2007.

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT 48

www.iaetsd.in


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.